Lumen Method

Illuminance: The quantity of light reaching a certain surface. Its


measured in lux, and as this level varies across the working plane, an
average figure is used.

CIBSE Lighting Guides (Chartered Institute of Building
Services Engineers) give values of illuminance that are
suitable for various areas.
The section - Lighting Levels in these notes also
gives illuminance values.

The lumen method is used to determine the number of lamps that should
be installed for a given area or room.

Calculating for the Lumen Method
The method is a commonly used technique of lighting design, which is
valid, if the light fittings (luminaires) are to be mounted overhead in a
regular pattern.
The luminous flux output (lumens) of each lamp needs to be known as
well as details of the luminaires and the room surfaces.
Usually the illuminance is already specified e.g. office 500 lux, kitchen
300 lux, the designer chooses suitable luminaires and then wishes to know
how many are required.



1- Number of Lamps
The number of lamps is given by the formula:


where,
N : number of lamps required.
E : illuminance level required (lux or lm/ m
2
)
A : area at working plane height (m
2
)
F : average luminous flux from each lamp (lm)
CU : Coefficient of utilization utilisation factor, an allowance for the
light distribution of the luminaire and the room surfaces.
LLF: light loss factor, an allowance for reduced light output
because of deterioration and dirt.
LLF= LLD x LDD

Example 1

A production area in a factory measures 60 metres x 24 metres.
Find the number of lamps required if each lamp has a Lighting Design
Lumen (LDL) output of 18,000 lumens.
The illumination required for the factory area is 200 lux.
Utilisation factor = 0.4
Lamp Maintenance Factor = 0.75

CU LLF




N = ( 200 lux x 60m x 24m ) / ( 18,000 lumens x 0.4 x 0.75 )
N = 53.33
N = 54 lamps.


Spacing

The aim of a good lighting design is to approach uniformity in
illumination over the working plane.
Complete uniformity is impossible in practice, but an acceptable standard
is for the minimum to be at least 70% of the maximum illumination
level.

This means, for example, that for a room with an illumination level of
500 lux, if this is taken as the minimum level, then the maximum level in
another part of the room will be no higher than 714 lux as shown below.

500 / 0.7 = 714 lux

Data in manufacturer's catalogues gives the maximum ratio between
the spacing (centre to centre) of the fittings and their height ( tolamp
centre) above the working plane (0.85 metres above f.f.l.)


Example 2



Using data in the previous example show the lighting design layout below.
The spacing to mounting height ratio is 3 : 2.
The mounting height (H
m
) = 4 metres.
The spacing between lamps is calculated from from Spacing/H
m
ratio of 3
: 2.
If the mounting height is 4 m then the maximum spacing is:

3 / 2 = Spacing / 4

Spacing = 1.5 x 4 = 6 metres


The number of rows of lamps is calculated by dividing the width of the
building (24 m) by the spacing:

24 / 6 = 4 rows of lamps

This can be shown below. Half the spacing is used for the ends of rows.


The number of lamps in each row can be calculated by dividing the total
number of lamps found in example 1 by the number of rows.

Total lamps 54 / 4 = 13.5 goes up to nearest whole number = 14
lamps in each row.

The longitudinal spacing between lamps can be calculated by dividing the
length of the building by the number of lamps per row.
Length of building 60 m / 14 = 4.28 metres.

There will be half the spacing at both ends = 4.28 / 2
= 2.14 metres


This can be shown below.



The total array of fittings can be seen below.


For more even spacing the layout should be re-considered.
The spacing previously was 6 m between rows and 4.28 m between lamps.

If 5 rows of 11 lamps were used then the spacing would be:

Spacing between rows = 24 / 5 = 4.8 metres
Spacing between lamps = 60 / 11 = 5.45 metres

Installed Flux

Sometimes it is useful to know the total amount of light or flux, which has
to be put into a space.
Installed flux (lm) = Number of fittings (N) x Number of lamps per
fitting x L.D.L. output of each lamp (F)

Example 3

A factory measuring 50m x 10m has a lighting scheme consisting of 4 rows
of 25 lighting fittings each housing 2No. 65-Watt fluorescent lamps.

(a) Find the installed flux in total.
(b) What is the installed flux per m
2
of floor area.



The output of the lamps in the above example may be found from
catalogues. For a 65-Watt fluorescent lamp the Lighting Design Lumens
(LDL) is 4400 lm.

(a)
Installed flux (lm) = N x no. lamps/fitting x F
= 4 x 25 x 2 x 4400
= 880,000 lumens

(b)
The floor area = 50 x 10 = 500 m
2
.
Installed flux per m
2
= 880,000 / 500
= 1760 lm/m
2
.


Example 4

A room measures 15m x 7m x 3.6m high and the design illumination is
200 lux on the working plane (0.85 metres above the floor).
The Utilisation factor is 0.5 and the Maintenance factor is 0.8.
If the LDL output of each fitting is 2720 lumens, calculate;
(a) the number of fittings required.
(b) the fittings layout.
(c) If the spacing/mounting height ratio is 1 : 1 determine whether the
current design is acceptable.

(a) Number of fittings.
N = ( 200 x 15 x 7 ) / ( 2720 x 0.5 x 0.8 )
N = 19.3
N = 20 lamps

(b) Fittings layout

For shallow fittings, the mounting height (H
m
) may be taken as the distance
form the ceiling to the working plane.

Therefore H
m
= 3.6 - 0.85
H
m
= 2.75 metres

If 3 rows of 7 fittings are considered then the spacing is;


(c) Spacing/ mounting height.

Spacing / H
m
ratio:
2.33 / 2.75 = 0.847 Therefore ratio is 0.85 : 1.0
2.14 / 2.75 = 0.778 Therefore ratio is 0.78 : 1.0




Example 5

A room, as shown below, has a design illumination is 500 lux on the
working plane (0.85 metres above the floor).
The Utilisation factor is 0.5 and the Maintenance factor is 0.8.
If the LDL output of each fitting is 2720 lumens, calculate;
(a) the number of fittings required.
(b) the fittings layout.
(c) If the spacing/mounting height ratio is 1 : 1 determine whether the
current design is acceptable.



(a)
N = ( 500 x 10 x 12 ) / ( 2720 x 0.5 x 0.8 )
N = 55.15
N = 56 lamps.

(b)
Spacing, say 8 lamps x 7 rows.
Spacing along 12 m wall = 12 / 8 = 1.50 m
Spacing along 10 m wall = 10 / 7 = 1.43 m

(c)
Mounting height = 3.0 - 0.85 = 2.15 m
Desired Ratio = 1:1
Actual ratio = 1.5 / 2.15 = 0.69 Therefore ratio is 0.69 :
1.0
Actual ratio = 1.43 / 2.15 = 0.67 Therefore ratio is 0.67 :
1.0