Moulded-case circuit-breakers overview

SACE Tmax
Brochure | April 2012
2 SACE Tmax Moulded-case circuit-breakers | ABB ABB | SACE Tmax Moulded-case circuit-breakers 3
A single family of moulded-case circuit-breakers up to 3200 A
Tmax moulded-case circuit-breakers guarantee an extremely
high performance level while being progressively smaller in
size, simple to install and able to provide increasingly better
safety guarantees for the operator.
In addition to being ideal for the secondary distribution
of alternmate and direct current, they feature dedicated
solutions for all application requirements.
Moulded-case circuit-breakers can be used in low voltage
civil and industrial installations with 1 to 3200 A operating
current. The Tmax family includes 9 circuit-breaker sizes in
three- or four-pole versions:
- XT1, XT2, XT3 and XT4 up to 250A;
- T4, T5 and T6 up to 1000A;
- T7 and T8 up to 3200A.
Up to 250 A Up to 1000 A Up to 3200 A
The ultimate short-circuit breaking capacity (Icu) at 415V
ranges from 18kA to 200kA, or up to 100kA for 690V.
The following ranges are available:
- Circuit-breakers for AC and DC power distribution;
- Circuit-breakers for zone selectivity;
- Circuit-breakers for motor protection;
- Circuit-breakers for up to 1150V AC and 1000V DC
applications;
- Switch-disconnectors.
All Tmax circuit breakers can be enhanced with a vast range
of standardized accessories. This convenience not only cuts
down on inventory, but creates an extremely flexible and easily
managed solution.
Tmax circuit-breakers can be equipped with thermomagnetic,
solely magnetic or electronic trip units;, all of which are
interchangeable.
Since assembly instructions are simple, trip units can quickly
and easily be replaced; even in the field.
All this makes the circuit-breakers very easy to operate with
considerable savings due to rationalized stock management.
4 SACE Tmax Moulded-case circuit-breakers | ABB ABB | SACE Tmax Moulded-case circuit-breakers 5
Up to 250 A
Up to 1000 A
Up to 3200 A
A single family of moulded-case circuit-breakers up to 3200 A
Construction characteristics
SACE Tmax XT1 XT2 XT3 XT4
Size [A] 160 160 250 160/250
Rated service voltage, Ue (AC) 50-60Hz [V] 690 690 690 690
DC [V] 500 500 500 500
(4)
Versions Fixed, Plug-in
(1)
Fixed, Plug-in, Withdrawable Fixed, Plug-in Fixed, Plug-in, Withdrawable
Breaking capacity according to IEC 60947-2 B C N S H N S H L V N S N S L H V
Rated ultimate short-circuit breaking capacity, Icu
Icu @ 220-230-240V 50-60Hz (AC) [kA] 25 40 65 85 100 65 85 100 150 200 50 85 65 85 100 150 200
Icu @ 415V 50-60Hz (AC) [kA] 18 25 36 50 70 36 50 70 120 150 36 50 36 50 70 120 150
Icu @ 690V 50-60Hz (AC) [kA] 3 4 6 8 10 10 12 15 18 20 5 6 10 12 15 20 25/100
(2)
(DC) 500V - 2 poles in series [kA] - - - - - - - - - - - - 36 50 70 85 100
(DC) 500V - 3 poles in series [kA] 18
(3)
25
(3)
36
(3)
50
(3)
70
(3)
36 50 70 85 100 36 50 36 50 70 85 100
(DC) 750V - 3 poles in series [kA] - - - - - - - - - - - -
(4) (4) (4) (4) (4)
Rated service short-circuit breaking capacity, Ics
Ics @ 220-230-240V 50-60Hz (AC) [kA] 100% 100% 75%(50) 75% 75% 100% 100% 100% 100% 100% 75% 50% 100% 100% 100% 100% 100%
Ics @ 415V 50-60Hz (AC) [kA] 100% 100% 100% 75% 50% (37,5) 100% 100% 100% 100% 100% 75% 50% (27) 100% 100% 100% 100% 100%
Ics @ 690V 50-60Hz (AC) [kA] 100% 100% 100% 75% 50% 100% 100% 100% 75% (15) 75% (15) 75% 50% 100% 100% 100% 100% 75% (20)
Mechanical life [N Operations] 25000 25000 25000 25000
[N Hourly opertions] 240 240 240 240
Electrical life @ 415V (AC) [N Operations] 8000 8000 8000 8000
[N Hourly opertions] 120 120 120 120
Dimensions
(Width/Depth/Height)
3 poles [mm] 76,2x70x130 90x82,5x130 105x70x150 105x82,5x160
4 poles [mm] 101,6x70x130 120x82,5x130 140x70x150 140x82,5x160
(1)
XT1 plug-in In max=125A
(2)
25kA@690V available for XT4 250; 100kA@690V available
for XT4 160
(3)
XT1 500V DC 4 poles in series
(4)
XT4 750V DC ask ABB SACE whether available

(5)
Withdrawable not available for T6 1000A
(6)
V version only available for frame 630A/800A
(7)
75% for T5 630
(8)
50% for T5 630

(9)
Only for T7 800/1000/1250
(10)
Only for T7 800
SACE Tmax T4 T5 T6
Size [A] 320 400/630 630/800/1000
Rated service voltage, Ue (AC) 50-60Hz [V] 690 690 690
(DC) [V] 750 750 750
Versions Fixed, Plug-in, Withdrawable Fixed, Plug-in, Withdrawable Fixed, Withdrawable
(5)
Breaking capacity according to IEC 60947-2 N S H L V N S H L V N S H L V
(6)
Rated ultimate short-circuit breaking capacity, Icu
Icu @ 220-230-240V 50-60Hz (AC) [kA] 70 85 100 200 200 70 85 100 200 200 70 85 100 200 200
Icu @ 415V 50-60Hz (AC) [kA] 36 50 70 120 200 36 50 70 120 200 36 50 70 100 150
Icu @ 690V 50-60Hz (AC) [kA] 20 25 40 70 80 20 25 40 70 80 20 22 25 30 40
(DC) 500V - 2 poles in series [kA] 25 36 50 70 100 25 36 50 70 100 20 35 50 65 70
(DC) 500V - 3 poles in series [kA] -
(DC) 750V - 3 poles in series 16 25 36 50 70 16 25 36 50 70 16 20 36 50 50
Rated service short-circuit breaking capacity, Ics
Ics @ 220-230-240V 50-60Hz (AC) [kA] 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 75% 100%
Ics @ 415V 50-60Hz (AC) [kA] 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 75% 75%
Ics @ 690V 50-60Hz (AC) [kA] 100% 100% 100% 100% 100% 100% 100% 100%
(7)
100%
(8)
100%
(8)
75% 75% 75% 75% 75%
Mechanical life [N Operations] 20000 20000 20000
[N Hourly opertions] 240 120 120
Electrical life @ 415V (AC) [N Operations] 6000 7000 (400 A) - 5000 (630 A) 7000 (630A) - 5000 (800A) - 4000 (1000A)
[N Hourly opertions] 120 60 60
Dimensions
(Width/Depth/Height)
3 poles [mm] 105 x 103.5 x 205 140 x 103.5 x 205 210 x 103.5 x 268
4 poles [mm] 140 x 103.5 x 205 186 x 103.5 x 205 280 x 103.5 x 268
SACE Tmax T7 T8
Size [A] 800/1000/1250/1600 2000/2500/3200
Rated service voltage, Ue (AC) 50-60Hz [V] 690 690
(DC) [V] -
Versions Fixed, Withdrawable Fixed
Breaking capacity according to IEC 60947-2 S H L V
(9)
X
(10)
L V
Rated ultimate short-circuit breaking capacity, Icu
Icu @ 220-230-240V 50-60Hz (AC) [kA] 85 100 200 200 170 85 130
Icu @ 415V 50-60Hz (AC) [kA] 50 70 120 150 170 85 130
Icu @ 690V 50-60Hz (AC) [kA] 30 42 50 60 75 50 80
(DC) 500V - 2 poles in series [kA]
(DC) 500V - 3 poles in series [kA]
(DC) 750V - 3 poles in series
Rated service short-circuit breaking capacity, Ics
Ics @ 220-230-240V 50-60Hz (AC) [kA] 100% 100% 100% 100% 100% 100% 75%
Ics @ 415V 50-60Hz (AC) [kA] 100% 100% 100% 100% 100% 100% 75%
Ics @ 690V 50-60Hz (AC) [kA] 100% 75% 75% 75% 100% 100% 75%
Mechanical life [N Operations] 10000 15000
[N Hourly opertions] 60 60
Electrical life @ 415V (AC) [N Operations] 2000 (versioni S, H, L) / 3000 (versione V) 4500(2000A);4000 (2500A);3000 (3200A)
[N Hourly opertions] 60 20
Dimensions
(Width/Depth/Height)
3 poles [mm] 210 x 154 (leva) /178 (motorizzabile) x 268 427 x 282 x 382
4 poles [mm] 280 x 154 (leva) /178 (motorizzabile) x 268 553 x 282 x 382
Icc = 50 kA
Icc = 50 kA
T5S
XT4S
XT1C
T5S
T
o
t
a
l

s
e
l
e
c
t
i
v
i
t
y
Back-up 50 kA
6 SACE Tmax Moulded-case circuit-breakers | ABB ABB | SACE Tmax Moulded-case circuit-breakers 7
1
1
1
1
3
3
T5S 630 PR221DS LS/I 3p
Electronic trip unit PR221DS LS/I for AC applications.
Features a protection L function against overload with
adjustable current, (I
1
= 0.41xIn), and timing. Protection
against short-circuit can be delayed (S), with an adjustable,
or instantaneous delay (I). The tripping threshold is adjust-
able in both cases (I
2
, I
3
= 110xIn).
XT1 160 TMD 3p with RC Sel
Thermomagnetic trip unit TMD for AC/DC applications. Ther-
mal protection is adjustable I
1
= 0.71xIn,
magnetic protection is fixed I
3
=10xIn.
Selectivity
As can be seen from the selectivity tables, there is total selectivity (T), equal to 50 A, between a Tmax
XT4S TM and T5S EL.
Advantages:
- Continuity of service
- Rapid identication of the fault zone
Tmax moulded-case circuit-breakers are the ideal solution for all distribution levels, from the main low
voltage switchboard to the subswitchboards in the installation. They feature high peak current and
specic let-through energy-limiting characteristics that allow the circuits and equipment on the load
side to be sized in an optimum way.
The SACE Tmax family of moulded-case circuit-breakers is available with:
n thermomagnetic trip units for protecting direct and alternate current networks. These trip units
use the physical properties of a bimetal and an electromagnet to detect the overloads and short-
circuits;
n electronic trip units for protecting alternate current networks. These trip units use microprocessor
technology to obtain protection functions that make the operations extremely reliable and accu-
rate.
Due to dedicated devices, the SACE Tmax family of moulded-case circuit-breakers allows the insula-
tion state of the installation to be monitored and ensures that people are protected against direct and
indirect contacts, in accordance with the reference standards.
Selectivity and back-up
Selective coordination can be used among various protection devices in an installation when it
is necessary to minimize the problems associated with faults and abnormal service conditions.
If selective coordination is not a requirement, back-up protection can be used. This method
implies that the supply side device provides protection during a short-circuit, allowing the use
of a lower breaking capacity device on the load side.
XT4 250 TMA 3p
Thermomagnetic trip unit TMA for AC/DC
applications. Thermal protection is adjustable I
1
= 0.71xIn,
magnetic protection is adjustable I
3
= 510xIn.
RC SEL is a selective residual current release for assembly
in conjunction with the circuit-breaker. It has adjustable cur-
rent thresholds and 2xIn adjustable non-actuating times.
A single family of moulded-case circuit-breakers up to 3200 A
Distribution solutions
Sup. side T5
Version S
Relay EL
Model 400 400 630
Load side In [A] 320 400 630
XT4 S TM 250
200 T T T
225 T T T
250 T T T
Back-up
As can be seen from the back-up tables, the back-up value between a Tmax XT1C and a T5S is 50 kA.
Advantages:
- Financial savings
Supply side XT1 XT2 XT3 XT4 T5 T6 T7
Version S
Load side Version Icu [kA] 50
XT1 C 25 50 50 50 40
2
2
2
2
2
Circuit-breakers for distribution
Trip unit
Frame [A]
160 250 400 500 630 800 1000 1600 2500 3200
TMD (Adjustable Thermal, Fixed Magnetic) Tmax XT1-XT3
TMA (Adjustable Thermal, Adjustable Magnetic) Tmax XT2-XT4-T5-T6
LS/I (Electronic trip unit) Tmax XT2-XT4-T4-T5-T6-T7-T8
Residual Current Devices
Frame [A]
160 250 400 500 630 800 1000 1600 2500 3200
RC Instantaneous Tmax XT1-XT3
RC Selective Tmax XT2-XT4-T4-T5
Integrated RC Protection in release Tmax T7-T8
RC on outside of switchboard (RCQ) Tmax XT1-XT2-XT3-XT4-T4-T5-T6-T7
Converter
RS-232/RS-485
M
o
d
b
u
s

R
T
U
8 SACE Tmax Moulded-case circuit-breakers | ABB ABB | SACE Tmax Moulded-case circuit-breakers 9
Circuit-breakers for energy measurement and communication
3
3
5
5
5
5
5
A low voltage electrical installation is similar to an industrial process for electricity distribution
and needs a supervisory and monitoring system that is able to increase reliability and optimize
management.
To achieve integration between conventional plant engineering techniques and control sys-
tems for the purpose of running, controlling and monitoring civil and industrial installations in a
centralized and automatic way, one can consider the electrical installation as being affected by
two flows:
n a main flow (energy flow) formed by the power and energy supplied to the users and loads
of an installation through the line conductors and control and protection devices;
n an information flow (digital flow) formed by all the information, data and commands required
to control and manage the installation.
The supervisory system handles the flow of information that transits through the communica-
tion network.
A single family of moulded-case circuit-breakers up to 3200 A
Solutions for energy measurement and communication
1
4
1
1 4
2
2
In this type of installation, the circuit-breaker acts as both sensor and actuator. As a sensor,
it collects sensitive information and data and sends them to the supervision system. As an
actuator, it executes the command received from the control device (e.g. PC or PLC).
These characteristics are of particular importance since they meet the growing demands for
circuit-breaker integration into latest generation networks (Smart Grid).
XT4 250 Ekip E-LSIG 3p - Ekip Com, MOE-E
Due to its integrated current and voltage sensors, the Ekip E elec-
tronic trip unit can measure both the main electrical quantities and
the most advanced Power quality indicators; such as Power Factor,
Harmonic distortion and THD.
By means of the trip unit and Ekip Com Communication module,
the MOE-E motor operator allows the digital signals from the su-
pervision and control system to be used and converted into power
signals for operating the circuit-breaker in the remote mode.
T5 400 PR223DS 3p - MOE-E, VM210
Due the conventional L, S, I and G protection functions, the
PR223DS trip unit also allows the main electrical quantities to
be measured.
Using the VM210 accessory and without the need for voltage
transformers, the user can obtain both the current values and
the voltage, power and energy values in the local and remote
modes via a supervising and control system.
T7M 1600 PR332/P 3p - PR330/V, PR330/D-M
The SACE PR332 trip unit for Tmax T7 provides a sophisticated
and exible protection system. Fitted with the PR330/D-M internal
dialogue module, PR332/P becomes a smart protection, measur-
ing and communication device based on the Modbus

RTU
protocol. Module PR330/V measures and processes the neutral
and phase voltages, then transfers these data to the protection
release so that a set of protection and measuring functions can be
implemented.
HMI030
This device, which can be installed on the front of the switchboard,
comprises a graphic display showing all the measurements and
alarms/events of the trip unit. Thanks to its high-level accuracy, the
device is a valid substitute for conventional multimeters without the
need for current/voltage transformers.
XT2 160 Ekip LSIG 3p - Ekip Com, Ekip Display
Ekip Display is a unit that can be applied to the front of the ad-
vanced electronic trip unit and shows the current values, voltage
values, alarms and programmed protection and communication
parameter settings.
Trip units
Frame [A]
160 250 400 500 630 800 1000 1600 2500 3200
LSI (Advanced electronic trip unit) Tmax XT2-XT4-T4-T5-T6-T7-T8
LSIG (Advanced electronic trip unite) Tmax XT2-XT4-T4-T5-T6-T7-T8
Functions
Frame [A]
160 250 400 500 630 800 1000 1600 2500 3200
Energy measurement Tmax XT4-T4-T5-T6-T7-T8
Supervision and Monitoring Tmax XT4-T4-T5-T6-T7-T8
G
CB1
CB2
CB3
PL1
PL2
PL3
PL4
NPL
TR1
normal
line
CB1 CB2
GS1
stand by
line
ATS
G
non-priority
load (NPL)
priority
load (PL)
CB3
G
CB2 CB1
CB3
NPL
CB2 CB1
CB3
NPL
10 SACE Tmax Moulded-case circuit-breakers | ABB ABB | SACE Tmax Moulded-case circuit-breakers 11
2
2
2
2
A single family of moulded-case circuit-breakers up to 3200 A
Automatic network-generator transfer solutions
1
1
ATS022
The ATS022 device monitors both the supply lines and ana-
lyzes phase, frequency imbalance and phase loss. In addiction
to the standard control functions, ATS022 allows you to: select
the priority line, control a third circuit-breaker, integrate the
device into a supervision system with Modbus communication,
read and enter the parameters, display measurements and
alarms using a graphic display.
T7 M (CB1) and T7 M (CB2) Interlocked
XT4 (CB3) for disconnection
Non-priority loads (NPL)
To achieve a correct configuration, each circuit-breaker con-
nected to the ATS must be
accessorized with:
mechanical interlock;
motor operator for opening and closing;
key lock against sole manual operation for MOE motor
operators;
state (open/closed) and tripped contact signalling contact;
connected contact (for the withdrawable circuit-breaker
version).
The ATS (Automatic Transfer Switch) is the network-generator transfer unit used in installations
where switching the main power line to an emergency one is required in order to ensure power
supply to the loads in the case of anomalies in the main line.
The new generation of ATS (ATS021 and ATS022) offers the most advanced and complete so-
lutions to guarantee service continuity. The ATS021 and ATS022 can be used both with all the
circuitbreakers in the SACE Tmax XT family and with the switch-disconnectors. Reliable, safe
and smart, the new ATS family conforms to international standards, is easy to configure and is
suitable for all applications.
Fully coordinated systems are ensured, since ATS integrates perfectly with the entire range of
ABB circuit-breakers and switch-disconnectors.
Multi-function logic meets all requirements:
n standard switching logic that allows normal and emergency lines to be monitored, com-
mands to be transmitted to the generator and verification that the circuit-breakers have
been switched (ATS021, ATS022);
n control of the two lines, both of which are non-priority (ATS021, ATS022);
n control of a third, bus-tie breaker (ATS022);
n non-priority load disconnection management (ATS022).
LINE-GENERATOR
If the main network is
lost, the AST021 and
ATS022 devices switch
to the emergency line
equipped with a GenSet.
NON-PRIORITY LOAD
CONTROL USING A
BUS-TIE
If the main network is
lost, the ATS022 device
switches to a second line used
as a standby by disconnecting
non-priority loads (NPL) via a
bus-tie.
NON-PRIORITY LOAD
CONTROL ON THE
OUTGOING LINE
If the main network is
lost, the ATS022 device
switches to a second line
used as a standby by
disconnecting non-priority
loads (NPL) branched from
the main busbar.
LINE-LINE
If the main network is
lost, the AST021 and ATS022
devices switch
to a second line used as a
standby. Selection of the
priority line from the two
available lines is allowed by
ATS022.
2
20A motor start-up unit
Protection and operation are guaranteed by circuit-
breaker XT2 MA In20A 3p in conjunction with the
thermal relay and contactor.
200A motor start-up unit
Protection and operation are guaranteed by circuit-
breaker XT4 Ekip M-LRIU In200A 3p in conjunction
with the contactor.
12 SACE Tmax Moulded-case circuit-breakers | ABB ABB | SACE Tmax Moulded-case circuit-breakers 13
1
2
3
4
4
4
3
3
3
1
3
3
A single family of moulded-case circuit-breakers up to 3200 A
Motor protection solutions
T8 2000A 3 poles with PR332 LSIG
General circuit-breaker used for protecting the load side
circuit-breakers dedicated to motor protection.
T8 800A 3 poles with PR221-1
Circuit-breaker used for motor protection in conjunction with
a thermal relay and a contactor. Instantaneous short-circuit
protection (I) can be adjusted from 1 to 10xIn.
XT4 250A 3 poles with Ekip M-LRIU
Circuit-breaker used for integrated motor protection.
Ekip M-LRIU is fitted with the following protections:
against overload (L): threshold adjustable from 0.4...1xIn.
The tripping time is established by choosing the tripping
class defined by standard IEC 60947-4-1.
rotor locking (R): with threshold adjustable in OFF or from
3...9x I1, with adjustable tripping time;
against instantaneous short-circuit (I): with threshold
adjustable from 6...13xIn and instantaneous tripping time;
against phase imbalance (U): with threshold adjustable
in ON or OFF.
XT2 160A 3 poles with MA
Circuit-breaker used for motor protection in conjunction with
a thermal relay and a contactor. Instantaneous short-circuit
protection (I) can be adjusted from 6...14xIn.
Start-up is a particularly critical phase for the motor itself and for the installation powering it.
Even rated service needs to be adequately monitored and protected in order to respond to
any faults that might occur.
When it comes to direct starting, ABB SACE proposes two different solutions:
n a conventional system with three poles circuit-breaker equipped with a magnetic only trip
unit for protection against short-circuits, a.thermal relay for protection against overloads
and phase failure or imbalance, and a contactor to operate the motor;
nan advanced protection system which integrates all the protection and monitoring functions,
and a contactor for operating the motor, in the circuit-breaker itself.
Releases
Frame [A]
160 200 400 630 800 1000 1600
MF-MA (Magnetic only trip unit) Tmax XT2-XT3-XT4
I (Basic Magnetic only trip unit) Tmax XT2-XT4-T5-T6-T7-T8
LIU (Advanced Magnetic only trip unit) Tmax XT2-XT4
LRIU (Advanced Magnetic only trip unit) Tmax XT2 XT4 T5 T6
Circuit-breakers for motor protection
Coordination tables
Suitable devices for protection and motor operation can be identified, given the type of starting, the electrical characteris-
tics of the installation and the characteristics of the motor.
Motor MCCB Contactor Thermal relay
Rated
power
Rated
current
Type Magnetic protection
setting
Type Type Setting
range
I max
Pe Ie [A] min [A] max [A] [A]
5.50 11.50 XT2S 160 MF 12.5 175 AF38 EF19-18.9 5.70 18.90 12.50
7.50 15.50 XT2S 160 MA 20 240 AF38 EF19-18.9 5.70 18.90 18.90
9.00 18.60 XT2S 160 MA 20 280 A50 EF45-30 9 30 20
11.00 22.00 XT2S 160 MA 32 320 A50 EF45-30 9 30 30
14 SACE Tmax Moulded-case circuit-breakers | ABB ABB | SACE Tmax Moulded-case circuit-breakers 15
A single family of moulded-case circuit-breakers up to 3200 A
Certifications and Shipping Registers
The moulded-case circuit-breakers and their accessories comply
with IEC60947-2 international standards and conform to EC directive
Low Voltage Directives (LVD) N 73/23 EEC and Electromagnetic
Compatibilities Directives (EMC) N 89/ 336 EEC.
Certification of conformity with the product Standards is carried out
in the ABB SACE tests laboratory (accredited by SINAL) in respect
of the EN 45011 European Standard, by the Italian certification body
ACAE (Association for Certification of Electrical Apparatus), member
of the European LOVAG organisation (Low Voltage Agreement Group)
and by the Swedish certification body SEMKO belonging to the inter-
national IECEE organisation.
The SACE Tmax XT series has a hologram on the front, obtained
using special anti-forgery techniques,a guarantee of the quality and
genuineness of the circuit-breaker as an ABB SACE product.
There is also an entire range of moulded-case circuit-breakers
conforming to UL/CSA standards, with rated current values ranging
from 1 to 3000A and breaking capacities, at 600V AC, that can reach
100kA.
All the equipment also conforms to the specifications for installations
on board and to those of RINA, DNV, BV, ABS, GL, LRs, PRS, RMRS,
NKK type-approvals.
Corporate Quality System
The ABB SACE Quality System conforms with the following Stand-
ards:
ISO 9001 international Standard;
EN ISO 9001 (equivalent) European Standards;
UNI EN ISO 9001 (equivalent) Italian Standards;
IRIS International Railway Industry Standard
The ABB SACE Quality System attained its rst certication with
the RINA certication body in 1990.
The ABB laboratory
The ABB S.p.A - ABB SACE Division Laboratory develops,
certifies and performs follow-up activities for the production
of switchgear and controlgear designed and manufactured in
various different ABB plants. The Laboratory provides a vast
range of installations and experience with regard to the elec-
trical, mechanical, climatic and functional tests required for
low and medium voltage operating, control, safety and meas-
uring mechanisms.
ABB's respect for the environment
Attention to protection of the environment is a priory commitment for
ABB SACE. Conrmation ofthis is the realisation of an Environmental
Management System certied by RINA (ABB SACE was
the rst industry in the electromechanical sector in Italy to obtain this
recognition) in conformity with the International ISO14001 Standard.
In 1999 the Environmental Management System was integrated with
the Occupational Health and Safety Management System according
to the OHSAS 18001 Standard and later, in 2005, with the SA 8000
(Social Accountability 8000) Standard, committing itself to respect
of business ethics and working conditions.
The commitment to environmental protection becomes concrete
through:
selection of materials, processes and packaging which optimise
the true environmental impact of the product
use of recyclable materials
voluntary respect of the RoHS directive
ISO 14001, 18001 and SA8000 recognitions togheter with ISO
9001 made it possible to obtain RINA BEST FOUR CERTIFICATION.
The Laboratory has been certified in Italy by ACCREDIA
and, due to acknowledgements from important international
certification bodies such as ACAE/LOVAG, ANCE, ASTA, ETL
SEMKO, UL, CSA and Shipping Registers, offers ABB and
external customers a qualified certification test service for low
and medium voltage electrical devices and equipment, in ac-
cordance with the respective product standards.
Contacts
1
S
D
C
2
1
0
0
5
3
B
0
2
0
1

-

0
5
.
2
0
1
2

-

3
.
0
0
0
ABB SACE
A division of ABB S.p.A.
L.V. Circuit-breakers
Via Baioni, 35
24123 Bergamo
Tel.: 035 395 111
Fax: 035 395306-433
bol.it.abb.com
www.abb.com

The data and illustrations are not binding.
We reserve the right to modify the contents of this
document without prior notice following technical
and product developments.
Copyright 2012 ABB. All rights reserved.