ACCUREX Hoods & Accessories PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 48

All the products you need for

Engineered Kitchen Ventilation Systems.


Hoods, Fire Systems, Controls, Accessories
October 2013
[ 2 ]
Accurex specializes in ventilation comfortfor restaurants and other food service establishments. Our top performing
kitchen ventilation products reect the industrys latest technological advances and will provide you with a fully
integrated ventilation system that results in a positive, balanced building where customers and employees prefer to
dine and work.
Our state-of-the-art, computer-aided product selection program (CAPS) helps you select and congure products for
your system, view real-time drawings and create AutoCAD les quickly. Youll also like the friendly, responsive
customer service we provide. Your Accurex representative is just a phone call or e-mail away, and is always
well prepared to help you design a ventilation system that reduces future energy and operating costs.
We listen to you, our customer, when
designing our diverse product line.
Accurex believes in continuous improvement. Our engineers are constantly developing
and redesigning products, responding to the needs of our customers. Extensive
prototype modeling and testing results in products that have higher efciencies with
lower installation and operating costs. Accurex engineers are focused on delivering
reliable and convenient products that result in a positive ventilation experience.
Reliability and top performance are
assured through extensive testing.
Accurex products are comprehensively tested for structural integrity, aerodynamic
performance, sound levels, mechanical operation, vibration, temperatures, environmental
impact and more. Fans are tested in two on-site air chambers and a sound testing facility. Accurex
products carry several certications including AMCA, UL, NSF, and ETL.
A single source for all your kitchen ventilation needs.
Whether its a large project or a small one, Accurex will build and deliver your entire kitchen system quickly
and efciently. Our products range from kitchen hoods, exhaust fans, dedicated make-up air, packaged rooftop
units, controls, variable volume systems, re suppression, utility distribution and more.
Comfortable energy efcient
kitchen ventilation starts here.
[ 3 ]
Table of Contents
Model Application Pages
Grease Hoods Type I
Type I kitchen hoods are used over cooking equipment producing
grease-laden efuent.
6-13
Heat/Condensate Hoods Type II
Type II kitchen hoods are designed to capture heat and/or condensate
from non-grease producing appliances such as ovens and dishwashers.
14-18
Filtration Options
Accurex offers industry-leading grease extraction lters to match your
restaurant needs.
19-27
External Supply Plenums
Accurex has a variety of solutions available to properly introduce air into
the space when exhaust only hoods are being used.
28-30
Fire Suppression Systems
The rst line of defense against re in a commercial kitchen is the
hood re protection system. Accurex has a variety of factory prepiped
re protection systems available from the two leading manufacturers,
Amerex

and Ansul

.
31-34
Controls/Energy Management
Accurex understands the importance of managing the various
relationships between your kitchen system components, so we provide
several options to control your environment.
35-40
Utility Distribution Systems
Accurexs utility distribution systems (UDS) provides exible, convenient
and safe utility connections for commercial cooking operations while
saving installation time in the eld.
41-44
Pollution Control
Accurexs pollution control units provide exceptional secondary ltration -
removing smoke, grease and odor from your kitchen exhaust system.
45-47
[ 4 ]
1. Will you be exhausting grease-laden air or non-grease-laden air?
Type I Hoods: Used if you are exhausting grease-laden air.
Type II Hoods: Used if you are exhausting non-grease-laden air (heat/condensate).
Decision Guide... 2 Easy Steps...
[ 5 ]
2. Type I Hoods: What style of hood do I need?
Is your cooking equipment against a wall?
Wall canopy hoods:
Most common when the cooking battery is against a wall.
Proximity (Backshelf) hoods:
Used when you have a low ceiling and/or it is to be placed over
griddles and fryers, typically used in quick service restaurants.

Is your cooking equipment placed in the open, like an
island?
Single-island hoods:
Used when the cooking battery is in one row, not against a wall.
Double-island hoods:
Used when the cooking battery is in two back-to-back rows, not
against a wall.
Type II Hoods: What style of hood do I need?
Heat and fume:
Heat only hoods are typically used for oven applications.
Condensate:
Condensate hoods are typically used above dishwashers.
What style hood do I need?
Single-Island Hood
Double-Island Hood
Heat and Fume
Wall Canopy Hood
Proximity (Backshelf) Hood
Condensate densate
Proximity (Backshelf) Hood
[ 6 ]
Accurex Type I hoods are UL 710 Listed.
NSF
Grease Hoods Type I
[ 7 ]
XB - E - W
Hood Type
XB - Baffle Filter
XX - Grease-X-Tractor
XG - Grease Grabber
XK - High Velocity Cartridge Filter
XW - Water Wash
Model Number Code
Make-Up Air Style
E - Exhaust Only
D - Exhaust Only - Double-Wall Front
F - Face Supply
C - Face and Air Curtain Supply
Configuration
W - Wall Style Canopy
V - Single-Island Style (V-Bank) Canopy
P - Proximity (Backshelf)
R - Pizza Hood
The Model Number Code is designed to completely identify the unit. The correct code letters must be specified
to designate the configurations and size.
Type I hoods are designed for use above grease-producing equipment and are available in several styles and
congurations.
Accurex grease hoods offer the following benets:
Standard construction is a minimum of 18 gauge 430 stainless steel
Hoods can be built in single section lengths from 3-16 feet
Flexible lengths, widths and heights
Hood lengths: Available in 1-inch increments
Hood widths: Available in 3-inch increments
Longer hoods are available in multiple sections and can be made to appear as one hood by utilizing our
continuous capture option to improve performance and aesthetics
Standing seam construction for superior strength
Excellent dimensional tolerances due to highly tooled manufacturing
UL 710 Listed and bears the National Sanitation Foundation (NSF) Seal of Approval (Standard 2)
Rated for 400F, 600F, 700F
Includes Performance Enhancing Lip (PEL) to improve capture efficiency by turning air back into the hood
Grease Hoods
Model Overview
[ 8 ]
Grease Hoods Type I
Model Comparison
Wall Canopy Hoods.
Accurexs wall canopy hoods are used over cooking equipment that produce heat and grease-laden efuent. Wall
canopy hoods are intended to be used when the cooking equipment is placed against a wall. A wide variety of sizing
and hood options, along with several accessories, makes Accurex the right choice to meet your varying design
requirements.
Exhaust Only
Supply air is introduced through ceiling diffusers or external
supply plenums (shown on page 28)
More dimensional flexibility than other manufacturers
Single-Wall Front
Double-Wall Front (see inset detail)
- One-inch of insulation between the two front panels
provides for additional strength and rigidity
Wall Canopy Hoods
Face and Air Curtain Supply
Supply air is introduced horizontally through the face and vertically
through the front perimeter via perforated panels in a manner that
does not interfere with the cooking operation beneath the hood(s)
Perforated panels ensure precise volume control and will limit the
throw to within several feet of the hood(s)
Face Supply
Supply air is introduced horizontally through the face via perforated
panels in a manner that does not interfere with the cooking
operation beneath the hood(s)
Perforated panels are located on the face to ensure precise volume
control and will limit the throw to within several feet of the hood(s)
Higher level of dimensional flexibility than other manufacturers
[ 9 ]
Typical grease hoods, though low-cost up front, carry many overlooked and expensive maintenance issues that can
lead to high costs over their lifespan. Capturing the grease generated by cooking processes is a challenge and the
clean-up of grease is both costly and time consuming.
Grease Grabber H
2
O System Benets
Water Wash Hood
Designed to reduce the labor involved in removing and cleaning lters manually, the Accurex water wash hood
system self-cleans the lters in place. Nozzles spray hot water and detergent on the lter(s) cleaning the grease that
has deposited on the surfaces. Additionally, nozzles are located in the plenum to clean the area behind the lters.
Water wash hoods can be programmed to automatically start the cleaning process when desired or may be manually
operated.
Proven Grease Grabber dual-stage filtration technology
No manual filtration removal resulting in labor savings
Filter maintenance is automatically carried out
Programmable timer allows for cleaning to be completed on a
set schedule or by the push of a button
The Grease Grabber H
2
Os recirculation method reduces hot
water consumption by 50% helping to reduce operating costs
How it Works - Extracting the Grease
Grease Grabber H
2
O utilizes the Grease Grabber dual stage ltration system which consists of an Grease-X-Tractor
lter in conjunction with an Grease Grabber lter. Together, this ltration system provides the best mechanical grease
extraction in the industry.
The Grease-X-Tractor is the primary lter and takes the brunt of the grease and heat. The proprietary design of the
lter provides greater strength, thereby making it the best re barrier in the industry. The Grease-X-Tractor extracts
69% of grease particles at 8 microns from the efuent airstream.
The Grease Grabber, acting as a secondary lter, uses a 1/2 inch packed bead bed to remove smaller particles
that pass through the Grease-X-Tractor. Together this system removes 100% of the grease at 5 microns and larger
(smoke to spatter).
Cleaning the Hoods and Filters
The Grease Grabber H
2
Os innovative auto-cleaning system is a highly efcient, closed
system that combines time-saving convenience with cost reductions related to labor,
water and energy use.
Upon activation of the cleaning cycle, the system lls a tank in the hood with a hot
water/detergent mixture. The system washes the lter banks and plenum using
specically aimed spray nozzles located throughout the plenum area. The mix is
recycled through the system by a high-efciency pump, purged, and then the hood is
rinsed with fresh hot water.
No need for a gravity drain
Detergent is biodegradable so waste water can be drained to a standard grease trap
All plumbing and controls are factory-installed in an end-mounted utility cabinet for
ease of installation
CLEAN
HOOD
472616
SYSTEM
FAULT
FILL
DETERGENT
After pressing CLEAN HOOD, Fans will automatically stop.
In case of emergency, the wash cycle can be stopped by pressing CLEAN HOOD.
HOOD
LIGHTS
FAN
ON/OFF
Grease Grabber H2O
Keypad
Grease Hoods - Type I
Model Comparison
Wall Canopy Hoods.
[ 10 ]
Grease Hoods Type I
Model Comparison
Single-Island and Proximity Hoods.
Single-Island (V-Bank) Canopy Hoods
Accurexs single-island style canopy hoods are used over cooking equipment that produce heat and grease-laden
efuent (Type I Hood). Single-island style canopy hoods are used over one row of cooking equipment placed where
no walls exist. Single-island hoods can be seen from all directions and have four nished (all stainless steel) sides
available in both V-bank and single-bank lter congurations. Accurex offers a variation of the single-island hood for
use over pizza ovens. Contact your Accurex representative for more information.
Exhaust Only - Single-Wall
Supply air is introduced through ceiling diffusers or external supply
plenums
Face Supply
Make-up air is supplied horizontally through the face via perforated
panels in a manner that does not interfere with the cooking operation
beneath the hood(s)
Perforated panels are located on the face to ensure precise volume
control and will limit the throw to within several feet of the hood
Specialty Hoods
Accurex offers many specialty hoods such as radius corners, heavier
gauges and hoods with cladding. Contact your Accurex representative for
more information.
Proximity (Backshelf) Hoods
Accurex proximity hoods have an industry-leading ve dimensions of
adjustment which make them the perfect solution for low ceilings and light
and medium duty cooking applications. The Accurex proximity hood sits
close to the cooking equipment allowing for lower exhaust rates and smaller
hoods.
Proximity hoods are designed for grease- and heat-laden efuent (Type I
Hood) and are shorter in height and width than a canopy hood. The name
Proximity or Backshelf refers to the close proximity of the hood with
respect to the cooking equipment. In addition, Accurex proximity hoods
have an optional plate shelf and/or pass-over enclosure to meet your varying
design requirements.
[ 11 ]
Filtration Options A variety of filtration options are
available with increasing grease extraction efficiencies
to suit specific needs. See Filtration Option section for
more detail.
External Supply Plenums* Several supply
plenum options are available to supply air back to
the spaceevenly. See External Supply section for
moredetail.
Continuous Capture*
Provides a UL Listed
bolted connection
allowing end to end
hoods to be connected
and appear as
onehood.
Material Options* Standard construction is stainless
steel where exposed and galvanized steel in the
unexposed plenum. 100% stainless steel construction is
available. Either option is available in 300 series or 430
stainlesssteel.
Lighting Options* Multiple lighting
options are available. Incandescent
fixtures are standard. Recessed
incandescent and 2-, 3-, or 4-foot
recessed fluorescent and LED
fixtures are also available. All fixtures
are vaporproof and UL Approved.
LED lighting provides a bright, warm
light for cooking and a significantly
longer operating life. LED lights
save up to 95% in electrical costs
when compared to using standard
incandescent lights in a kitchen
hood.
Tapered Hood* For low
ceiling applications, tapered
fronts are available in 18-,
15- or 12-inch heights.
15- and 12-inch tapers
require a 12-inch overhang
on all exposed sides.
Exhaust Collars
Ship Loose Shipping exhaust collars loose provides
an exhaust collar to be used, but no exhaust cutout
in the hood. This enables the contractor to locate
and cut the exhaust opening where desired when not
known ahead of time.
Shape To accommodate various ductwork, several
sizes of rectangular and round collars are available.
Location* Top or back placement for mounted
exhaust collars can go anywhere within the
plenumarea.
Supply Collars
Additional Collars* To keep supply airflow
velocities around the hood low, additional supply
collars can be added for higher supply cfm amounts.
Shape (Round or Rectangle) To accommodate
various ductwork, different sized collars are
available on most supply plenums in both round and
rectangular forms.
Ceiling Enclosure When the top of the hood is
mounted lower than the
finished ceiling height,
enclosure panels can be
provided in 300 series
or 430 stainless steel to
match your hood. These
enclosures create an
aesthetically pleasing finish.
Backsplash Panels/Side Splash
Panels Provides an aesthetically
desirable and easily cleanable
stainless steel surface behind
or on adjacent walls near the
hood. Constructed of 300 series
or 430 stainless steel to match
the hood. Also available with
1-inchinsulation.
*See options chart on page 13 for specic options for Type I Grease Hoods
Grease Hoods Type I
Options and Accessories

[ 12 ]
*See options chart on page 13 for specic options for Type I Grease Hoods
Grease Hoods Type I
Options and Accessories
End Skirts* End skirts
are available in both full
and mini configurations
and are constructed with
either 300 series or 430
stainless steel to match
the hood. End skirts can
lower required exhaust
rates as they improve
capture.
Airspace/Filler Panels
To assist with
clearances to
combustible
surfaces, stainless
steel airspaces can
be supplied. These
panels can also be
used to fill in open
spaces and/or improve aesthetics.
Zero Clearance* Our
clearance reduction
system utilizes a
one-inch wide (thick)
insulating material
on the front, back,
sides and top of the
hood as needed.
This provides great value, especially in retrofit building
applications allowing new hoods to be mounted closer
to combustible surfaces such as cabinetry and wood
roof trusses while satisfying both safety standards and
codes.
Exhaust Air Balancing Bafes* To help balance
exhaust airflows between multiple ducts or hood
sections being
exhausted through
one duct line. Air
balancing baffles
can be mounted at
the exhaust collar
openings which allow
the exhaust opening to
be closed up to 50%.
Switches* Switches can be shipped loose for remote
mounting, mounted on the hood face, or in the utility
cabinet.
Finished Back* With most wall canopy hoods,
hanging is done against a wall making the need for an
aesthetically pleasing finished back unnecessary. For
instances in which the back is visible, the same finish as
the other three sides of the hood can be provided.
Insulated Supply Plenum* With some plenums,
condensation can occur from bringing in cold air near
to where hot air is being exhausted. By insulating these
plenums, problems with condensation are alleviated.
This also helps prevent cooler incoming air from being
heated by warmer exhaust air.
Automatic Fire Damper* In areas where exhaust fire
dampers are required, a UL Listed motorized butterfly
damper can be installed in the exhaust collar that closes
at 285F.
Utility Cabinets Hood
Mount/Wall Mount* Utility
cabinets for fire system and/
or control mounting can be
attached to the left or right
side of the hood. Remote
(wall mount) cabinets are
also available.
Filter Removal Tool* Used to enable
operators to safely reach and remove filters
from the hood while standing on the floor in
front of appliances.
Trim Strips * Stainless steel strips that can be used
anywhere hood sections meet to improve aesthetics.
[ 13 ]
Grease Hoods Type I
Options and Accessories
Options
Guide
Make-Up
Air Style
Wall Canopy
Single-Island
(V-Bank)
Proximity
(Backshelf)
Pizza
Oven
Exhaust Only
Face
Supply
Face and
Air Curtain
Supply
Exhaust
Only
Face
Supply
Exhaust
Only
Exhaust
Only
Single-
Wall
Double-
Wall
Options and Accessories Model --EW --DW --FW --CW --EV --FV --EP --ER
Grease Grabber Multistage
Filtration System
XG-- Optional Optional Optional Optional Optional Optional Optional Optional
Grease-X-Tractor
Centrifugal Filtration
XX-- Optional Optional Optional Optional Optional Optional Optional Optional
Baffle Filter XB-- Optional Optional Optional Optional Optional Optional Optional Optional
High Velocity Cartridge Filter XK-- Optional Optional Optional Optional Optional Optional Optional Optional
Water Wash Hood XW-- Optional Optional Optional Optional
Horizontal Supply Plenum (HSP) - Optional Optional Optional Optional Optional
Air Curtain Supply Plenum (ASP) - Optional Optional Optional Optional
Variable Supply Plenum (VSP) - Optional Optional Optional Optional
Back Supply Plenum (BSP) - Optional Optional Optional Optional Optional Optional
Continuous Capture - Optional Optional Optional Optional Optional
Material Options - Optional Optional Optional Optional Optional Optional Optional Optional
Lighting Options - Optional Optional Optional Optional Optional Optional Optional
Additional Supply Duct Collars - Optional Optional Optional
Tapered Hood - Optional Optional Optional
*Supply Collar Shape Round/Rectangle - Optional Optional Optional
Exhaust Collar Ship Loose - Optional Optional Optional Optional Optional Optional Optional Optional
Exhaust Collar Location (Back) - Optional Optional Optional Optional Optional
Exhaust Collar Shape - Optional Optional Optional Optional Optional Optional Optional Optional
Switches - Optional Optional Optional Optional Optional Optional Optional
Ceiling Enclosures - Optional Optional Optional Optional Optional Optional Optional Optional
Utility Cabinets Hood Mount/Wall Mount - Optional Optional Optional Optional Optional Optional
Wall Mount
Only
Optional
Backsplash Panels/Sidesplash Panels - Optional Optional Optional Optional Optional
End Skirt - Optional Optional Optional Optional Optional Optional Optional
Airspace/Filler Panels - Optional Optional Optional Optional Optional Optional Optional Optional
Zero Clearance - Optional Optional Optional Optional Optional Optional Optional Optional
Exhaust Air Balancing Baffles - Optional Optional Optional Optional Optional Optional Optional
Finished Back - Optional Optional Optional Optional Optional
Insulated Supply Plenum - Optional Optional Optional
Automatic Fire Damper - Optional Optional Optional Optional Optional Optional Optional Optional
Filter Removal Tool - Optional Optional Optional Optional Optional Optional Optional Optional
Trim Strips - Optional Optional Optional Optional Optional Optional Optional
*Round supply collars are not available on back supply plenums
[ 14 ]
Heat and Condensate Hoods Type II
NSF
[ 15 ]
Type II hoods are designed to capture heat and/or condensate from non-grease producing appliances such as ovens
and dishwashers.
Accurex heat and condensate hoods offer the following benefits:
The National Sanitation Foundation (NSF) Seal of Approval (Standard 2)
Standard construction is a minimum of 18 gauge 430 stainless steel
Flexible lengths, widths and heights
Hood lengths: Available in 1-inch increments
Hood widths: Available in 3-inch increments
Standing seam construction for superior strength
Excellent dimensional tolerances due to highly tooled manufacturing
Heat and Condensate Hoods Type II
Model Overview
Model Number Code
XO
Accurex Hood Type II
XO - Oven, General Ventilation
XD1 - Condensate - No Baffle
XD2 - Condensate - Single-Baffle
XD3 - Condensate - Double-Baffle
The Model Number Code is designed to completely identify the unit. The correct code letters must
be specified to designate the configurations and size.
[ 16 ]
Models XD1. XD2. XD3.
Primarily used for dishwasher or condensate applications to
capture heat and vapor, creating a more comfortable environment
for the cooking staff
These hoods are constructed with a gutter and drain
The condensate hoods are available in three styles:
No Baffles (XD1) - Most economical and flexible in
condensate applications
Single-Baffle (XD2) - Designed for moderate
condensation applications. Great for vertical door
dishwasher applications
Double-Baffle (XD3) - Designed for heavy condensate applications
Heat and Condensate Hoods Type II
Model Comparison
Model XO
This hood is primarily used for ovens or general ventilation applications to
capture heat and vapor, creating a more comfortable environment for the
cooking staff.
Condensate Hoods
Non-Filtered Heat and Fume Hoods
[ 17 ]
Heat and Condensate Hoods Type II
Options and Accessories
Material Options Standard construction is stainless
steel where exposed and galvanized steel in the
unexposed plenum. 100% stainless steel construction is
available. Either option is available in 300 series or 430
stainlesssteel.
Incandescent Lighting* UL Listed
vapor proof incandescent light fixtures
are available.
External Supply Plenums* Several supply plenum
options are available to supply air back to the space
evenly. See External Supply Plenum section for more
detail.
Mesh Filter* With most Type II hoods,
the exhaust opening is exposed. Adding
a mesh filter in the exhaust collar helps
prevent anything other than heat and
moisture from passing through the duct
opening.
Exhaust Collars
Ship Loose Shipping exhaust collars loose will
provide an exhaust collar to be used, but no exhaust
cutout in the hood. This enables the contractor to
locate and cut the exhaust opening where desired,
when not known ahead of time.
Shape To accommodate various ductwork, several
sizes of rectangular and round collars are available.
Switches* Accurex Type II hoods allow for switch
mounting in a cabinet attached to the hood or as a
remote option.
Ceiling Enclosure When
the top of the hood is
mounted lower than the
finished ceiling height,
enclosure panels can be
provided in 300 series or
430 stainless steel to match
your hood. These enclosures
create an aesthetically pleasing finish.
Trim Strips Stainless steel strips to be used anywhere
hood sections meet to improve aesthetics.
Utility Cabinets Hood Mount/
Wall Mount Utility cabinets for
fire system and/or control mounting
can be attached to the left or right
side of the hood. All hoods can
be supplied with a cabinet to be
remote mounted in the space.
Backsplash Panels/Side
Splash Panels Backsplash
and side splash stainless steel
sheets cover back/side walls.
They provide an aesthetically
desirable and easy-to-
clean surface behind or on
adjacent walls near the hood.
Constructed of 300 series or
430 stainless steel to match
the hood. Also available with
1-inchinsulation.
End Skirts End skirts are
available in both full and
mini configurations and are
constructed with either 300
series or 430 stainless steel to
match the hood. End skirts can
lower required exhaust rates as
they improve capture.
Airspace/Filler Panels To assist with clearances to
combustible surfaces,
stainless steel
airspaces can be
supplied. These
panels can also be
used to fill in open
spaces and/or
improve aesthetics.
Exhaust Air
Balancing Bafes To help balance exhaust airflows
between multiple ducts
or hood sections being
exhausted through one duct
line. Air balancing baffles can
be mounted at the exhaust
collar openings which allow the
exhaust opening to be closed
up to 50%.
* See options chart on page 18 for specic options for Type II Heat
and Condensate Hoods
upply plenum
[ 18 ]
Heat and Condensate Hoods Type II
Options and Accessories
Options
Guide
Heat/Oven
Condensate
No Bafe Single Bafe Double Bafe
Options and Accessories Model XO Model XD1 Model XD2 Model XD3
Incandescent Lighting Optional Optional Optional
Horizontal Supply Plenum (HSP) Optional Optional Optional Optional
Air Curtain Supply Plenum (ASP) Optional Optional Optional Optional
Variable Supply Plenum (VSP) Optional Optional Optional Optional
Back Supply Plenum (BSP) Optional Optional Optional Optional
Mesh Filter Optional Optional
Exhaust Collar Ship Loose Optional Optional Optional Optional
Exhaust Collar Shape Optional Optional Optional Optional
Switches Optional Optional Optional
Ceiling Enclosures Optional Optional Optional Optional
Utility Cabinets Hood Mount/Wall Mount Optional Optional Optional Optional
Backsplash Panels/Sidesplash Panels Optional Optional Optional Optional
End Skirt Optional Optional Optional Optional
Airspace/Filler Panels Optional Optional Optional Optional
Exhaust Air Balancing Bafes Optional Optional Optional Optional
Trim Strips Optional Optional Optional Optional
[ 19 ] [ 19 ]
Accurex filters are UL 1046 Listed.
Filtration Options
NSF
[ 20 ]
Filter Application
Example
Appliances
Static
Pressure
(9 x 4 foot hood
at 2050 cfm)
Grease
Removal
Efciency*
at 8 microns
Grease
Removal
Efciency*
3-10 microns
Grease Grabber
Multistage
Filtration System
Heavy to Extra
Heavy Duty
Grease
Solid Fuel Cooking
Appliances
Upright Broiler
Gas, Electric & Lava
Rock Char-Broiler
Mesquite
Infrared Broiler
Wok Chain Broiler
1.1 to 1.3
in. wg
100% 99%
Grease-X-Tractor
Centrifugal
Filtration
Medium to
Heavy Duty
Grease
Combination Ovens
Gas & Electric Fryers
Griddles
Grill
Up-right Broiler
Electric Char-Broiler
0.7 to 0.8
in. wg
69% 51%
High-Velocity
Cartridge
Light Duty
Grease
Gas & Electric Ovens/
Steamers/Ranges
Food Warmers
Pizza Ovens
0.7 to 0.8
in. wg
42% 21%
Bafe
Light Duty
Grease
Gas & Electric Ovens/
Steamers/Ranges
Food Warmers
Pizza Ovens
0.5 to 0.6
in. wg
28% 16%
Accurex is the industry leader in grease ltration as veried by testing to ASTM F2519-2005 standards. This is
crucial to the restaurant owner/operator because the grease generated by restaurant kitchens pose many problems;
frequent duct cleaning, rooftop grease problems and compliance with tougher air emissions standards. Accurexs
offering of innovative lter designs attack the problem at the source at a fraction of the cost of other grease removal
devices or electrostatic precipitators.
Filtration Options
Quick Select Guide
*See Efciency Chart in the efciency section of ltration options
[ 21 ]
Filtration Options
Grease Dened
Total kitchen exhaust includes all grease particulate sizes as well as grease vapors. Grease is the by-product of
commercial cooking processes that must be extracted from the efuent airstream via the kitchen ventilation system.
Grease can be broken down into three different categories:
Submicron particles: Produced when a drop of grease or water comes in contact with a hot surface and
immediately burns off. Particle sizes range from .03 to .55 microns (smoke).
Steam: Grease covered moisture and air mixture is produced by the long burning of cold or frozen food on a hot
cooking surface. Particle sizes range from .55 to 6.2 microns.
Spatter: Larger more visible effluent that is produced during the cooking process. Particle sizes range from 6.2 to
150 microns.
Research and testing has determined that a signicant concentration of grease particles can be found in the
submicron and steam phases. Most currently applied grease extraction devices remove very large grease particulate
that is 10 to 150 microns in size (spatter phase), but are not capable of removing ne particulates that are found in
the submicron and steam phases.
What is in my Kitchens Exhaust?
Spatter
6.2 to 150 microns
Submicron
less than .1 microns
Steam
.5 to 6.2 microns
Testing of Grease Extraction Devices
Older tests designed to test the efciency of a grease lter did not effectively portray the full range of particles
produced during the cooking operation. This led to development of a new test standard ASTM F2519-2005. This test
shows the entire spectrum of the lter's efciency from 0.3 to 100 microns. The efciency is expressed as a graph
similar to a fan curve rather than using one percentage to cover all size particles.
ASTM F2519-2005 Standard Test Method for Grease Particle Capture Efciency of Commercial Kitchen Filters and
Extractors is the rst universally accepted test method in the commercial kitchen ventilation industry that covers
efciency testing of both removable lters and xed extractors such as water wash hoods.
ASTM F2519-2005 tests generate a controlled quantity of particles in size ranges from .3 to 10 microns that
are released into a kitchen hood to represent the cooking efuent. The particles are then sampled and counted
downstream in the ductwork with an optical particle counter with and without the extractor in place. These are used
to calculate the fractional efciency graphed versus the particle size.
The efciency graphs that Accurex uses reect the test methods used in ASTM F2519-2005.
[ 22 ]
Filtration Options
Efciency
Accurex Efciency Chart
0
10
20
30
40
50
60
70
80
90
100
0.1 1 10 100
Grease Grabber Grease-X-Tractor Bafe Filter Water Wash Hood Cartridge Filter
Particle Size
E
f

c
i
e
n
c
y
Efciency vs. Particle Size
600 CFM

m
[ 23 ]
Filtration Options
Model Comparison
The Grease Grabber dual-stage ltration system uses the Grease-X-Tractor
along with the Grease Grabber lter to remove 100% of the grease particles, at
5microns and larger, out of the airstream. The Grease Grabber filter is designed
for heavy-duty grease applications.
How it works:
The Grease-X-Tractor is the primary lter that removes large grease particles
using centrifugal force.
The Grease Grabber is the secondary lter that uses a -inch packed bead
bed to remove the small particles of grease that are not removed by the
Grease-X-Tractor lter.
Grease Grabber Multistage Filtration System
600 cfm Efciency Grease Grabber Griddle after Grease Grabber Gas Griddle Hamburger Emissions
Particle Size m
P
a
r
t
i
c
u
l
a
t
e

E
f

c
i
e
n
c
y
0
10
20
30
40
50
60
70
80
90
100
0
20
40
60
80
100
120
140
0.1 1 10
160
180
200
M
a
s
s

(
m
g
/
m
3

)
Mass & Grease Extraction Efciency vs. Particle Size
Grease Grabber Over Griddle with Hamburger
System Efciency = 99%
1% of particulate is exhausted into duct
Tested to ASTM F2519-2005
UL 1046 Listed
NSF Certified
See Third-Party Grease Extraction Efciency Verication on page 27
Grease-X-Tractor with Grease Grabber removes 100% of the
grease particles at 5 microns
[ 24 ]
The Grease-X-Tractor filter is the ideal lter for medium grease loading applications. The
design of the lter gives the lter great strength and makes it the best re barrier in the
industry as well as removing 69% of the grease particles at 8 microns.
How it works:
The Grease-X-Tractor filter consists of individual vortex chambers having air inlets at
the top and bottom front of the filter.
Air travels in a helical or corkscrew like path through the filter
chambers, subjecting the grease particulate to centrifugal
force.
Grease collects on the interior walls of the filter, where it
drains into the hood grease trough and grease cup.
Grease-X-Tractor Centrifugal Filtration
Mass & Grease Extraction Efciency vs. Particle Size
Grease-X-Tractor Over Griddle with Hamburger
P
a
r
t
i
c
u
l
a
t
e

E
f

c
i
e
n
c
y
Particle Size m
600 CFM Efciency Grease-X-Tractor Griddle after GX Gas Griddle Hamburger Emissions
0
10
20
30
40
50
60
70
80
90
100
0
20
40
60
80
100
120
140
0.1 1 10
160
180
200
M
a
s
s

(
m
g
/
m
3

)
System Efciency = 73%
27% of particulate is exhausted into duct
The Grease-X-Tractor removes 69% of
the grease particles at 8 microns
Tested to ASTM F2519-2005
standard method of test
UL 1046 Listed
NSF Certified
See Third-Party Grease Extraction Efciency Verication on page 27
Filtration Options
Model Comparison
[ 25 ]
Filtration Options
Model Comparison
0
10
20
30
40
50
60
70
80
90
100
0
20
40
60
80
100
120
140
0.1 1 10
160
180
200
Mass & Grease Extraction Efciency vs. Particle Size
Cartridge Over Griddle with Hamburger
P
a
r
t
i
c
u
l
a
t
e

E
f

c
i
e
n
c
y
Particle Size m
Efciency Cartridge Filter 600 CFM Griddle after Cartridge Gas Griddle Hamburger Emissions
M
a
s
s

(
m
g
/
m
3

)
System Efciency = 55%
45% of particulate is exhausted into duct
The high velocity cartridge lter removes 42%
of particles at 8 microns
See Third-Party Grease Extraction Efciency Verication on page 27
The high velocity cartridge is designed for light-duty grease applications.
How it works:
Exhaust or contaminated air passes through the high velocity stainless steel
cartridge.
As the air turns, the particles momentum throws the particle out of the airstream
as it changes direction, causing the particulates impact upon the cartridge.
The grease then runs down the cartridge into the grease trough which drains into
a removable grease container.
High Velocity Cartridge
Tested to ASTM F2519-2005
standard method of test
UL 1046 Listed
NSF Certified
[ 26 ]
Standard Bafe
The industry standard bafe lter is designed for light-duty grease applications.
How it works:
Exhaust air passes through the aluminum/stainless steel baffles.
As the air turns, the particles momentum throws the particle out of the airstream as
it changes direction the particulates impact upon the baffles.
The grease then runs down the baffle into the grease trough which drains into a
removable grease container.
0
10
20
30
40
50
60
70
80
90
100
0
20
40
60
80
100
120
140
0.1 1 10
160
180
200
Mass & Efciency vs. Particle Size
Bafe Over Griddle with Hamburger
P
a
r
t
i
c
u
l
a
t
e

E
f

c
i
e
n
c
y
Particle Size m
Efciency Bafe Filter 600 CFM Griddle after Bafe Gas Griddle Hamburger Emissions
M
a
s
s

(
m
g
/
m
3

)
System Efciency = 31%
69% of particulate is exhausted into duct

Tested to ASTM F2519-2005


standard method of test
UL 1046 Listed
NSF Certified
The bafe lter removes 28% of particles at 8 microns
See Third-Party Grease Extraction Efciency Verication on page 27
Filtration Options
Model Comparison
[ 27 ]
Grease Extraction by Cooking Equipment Type
Different appliances and types of food will produce different amounts of grease. There is a need for different levels of
grease extraction efciency.
Accurex recommends lters for each type of cooking equipment. If there is a diverse cooking lineup, use a worse
case scenario for the type of lter used.
Filtration Options
Applications
Cooking Equipment Grease Emissions
0
10
20
30
40
50
60
Gas
Griddle
Electric
Griddle
Gas
Fryer
Electric
Fryer
Gas
Broiler
Electric
Broiler
Gas
Broiler
Electric
Broiler
Gas
Oven
Electric
Oven
Gas
Range
Electric
Range
Hamburger Hamburger Hamburger Hamburger Chicken Chicken Pizza Pizza Spaghetti Spaghetti French Fries French Fries
G
r
e
a
s
e

P
a
r
t
i
c
u
l
a
t
e

(
l
b
/
1
,
0
0
0

l
b
.

o
f

f
o
o
d
)
Type of Appliance
Reference - ASHRAE 745-RP
= Grease Grabber
= Grease-X-Tractor
*Third-Party Grease Extraction Efciency Verication
The previous charts show the amount of grease that is extracted by a typical bafe lter, cartridge lter, Accurexs
Grease-X-Tractor, and Accurexs Grease Grabber ltration system. The charts also show the amount of grease that
passes through the lter and into your exhaust duct, exhaust fan and onto your roof.
This data was gathered by a third-party testing agency while cooking beef patties on a griddle. The cooking of beef
patties on a griddle yields the largest mass of grease particles at ~18 microns in size and the smallest at ~.2 microns
in size (human hair ~100 microns).
The blue area represents the amount of grease that passes through the lter. The green area represents the amount
of grease extracted by the lter. The more green area there is, the more grease that is extracted at the lter. The
orange efciency line shows the efciency of the lter for a specic particle size.
[ 28 ]
External Supply Plenums
Model Overview
Make-up air can be introduced several ways, including through-the-hood with an integrated supply plenum
or an external supply plenum. External plenums positioned around the perimeter of exhaust only hoods are a
great alternative to integral supply plenums. Unlike integral supply plenums, they do not sacrice valuable hood
containment area. They can also be retrotted to almost any hood and are generally less expensive than integral
plenums. Accurex offers four external supply choices - Air Curtain Supply Plenum (ASP), Horizontal Supply Plenum
(HSP), Variable Supply Plenum (VSP), and the Back Supply Plenum (BSP).
Standard construction features:
18 gauge 430 stainless steel
Perforated discharge panels (23% open)
Supply plenums are available in lengths from 3 to 16 feet where additional lengths require multipleplenums
Plenum Type
Discharge
Opening
(Inches)
Recommended
Supply Rate
(cfm/ft)
Recommended
Application
Air Curtain Supply (ASP)
14-inch or 24-inch
14-inch: 12
24-inch: 22
14-inch: Up to 110
24-inch: Up to 145
Non-Tempered/Heat Only*
To minimize mixing with air in
the space by distributing airow
at the hood, downward.
Horizontal Supply (HSP) 15.5 Up to 150
Tempered Air
(Heated and Cooling)*
Provides supply air to mix with
roomair.
Back Supply (BSP) 6 Up to 145
Non-Tempered or
Marginally Tempered Air
Air is kept near hood to
minimize mixing with air
in the space.
Variable Supply (VSP)
Face 8
Curtain 8
Face Up to 160
Curtain Up to 80
Non-Tempered or
Marginally Tempered Air
Air is kept near hood to
minimize mixing with air
in the space.
* Climate determines tempering conditions.
[ 29 ]
External Supply Plenums
Model Comparison
Air Curtain Supply Plenum (ASP)
Air curtain supply plenums are typically used in non-tempered
or heat-only applications, depending upon climate (can be
used as an efcient method for spot-cooling).
Air curtain supply plenums introduce the air near the hood
to minimize mixing with air in the space
A series of perforated panels evenly distribute air at lower
discharge velocities which benefit hood capture and
containment
Easy and flexible installation
Mounted 14-20 inches above the bottom edge of the
hood or flush with a drop ceiling
External plenums can be placed on multiple sides of the hood to create a curtain of air on all exposed sides and
increasing the volume of air brought in at the hood
The ASP is 14 or 24 inches wide by 10 inches high
Horizontal Supply Plenum (HSP)
Horizontal supply plenums are typically used in fully tempered air applications since the air will mix with the air in the
surrounding space.
Make-up air is introduced horizontally through the face of the
external supply plenum via perforated panels in a manner
that does not interfere with the cooking operations
beneath the hood(s)
Perforated panels are located on the face of the external
supply plenum to limit the throw to within several feet of
the hood(s) and maintain laminar flow
Easy and flexible installation
The HSP is typically mounted flush with the top of the hood
The HSP is 12 inches wide by 18 inches high
e
[ 30 ]
External Supply Plenums
Model Comparison
Variable Supply Plenum (VSP)
The variable supply plenum is a versatile plenum combining the features of the face
and air curtain supply plenums.
Make-up air is supplied horizontally through the face and
vertically through the front perimeter via perforated panels
in a manner that does not interfere with the cooking
operations beneath the hood(s)
Easy and flexible installation
Manual damper is included in the plenum to modulate
airflow between the face and air curtain allowing 0 to 50
percent through the air curtain and 50 to 100 percent through
the face
Best suited for cooler climates where outside air can be used to cool
the kitchen (although either tempered or non-tempered air can be used
depending on climate and comfort goals)
The VSP is 12 inches wide by 18 inches high
Back Supply Plenum (BSP)
Back supply plenums are typically used in non-tempered or marginally
tempered applications, and these plenums are also ideal for heating
air during the colder months since hot air will rise from its low
discharge position.
An effective way to introduce make-up air into the kitchen
is from the rear of the hood through a back supply plenum
(double layer of perforated panels allow for well-distributed
low-velocity airflow at discharge behind and below the cooking
battery)
Back supply plenums also function as a backsplash panel and
provide the proper clearance to limited combustibles needed in
many installations to meet NFPA 96 standards
Easy and flexible installation
This plenum directs airflow through perforated panels behind and
below the cooking equipment without affecting capture and containment,
cooking surface temperature, or pilot lights
When using non-tempered air, utilizing low air velocities will keep the air
near the hood
These plenums are 6 inches deep and stretch the entire length of the hood
and discharge at 31.25 inches above the finished floor
y
gh
d t l
[ 31 ]
Code Information
The Restaurant Fire Suppression System is constructed in compliance with the following:
National Fire Protection Association (NFPA) Bulletin #96 and #17A
UL Standard 300 Listed
UL Standard 2092 Listed (Piranha)
International Association of Plumbing and Mechanical Officials (IAPMO) Interim Guide IGC 113-07
ISO 9001-2000
Fire Suppression Systems
NSF
[ 32 ]
Model Fire Suppression Category
Amerex

KP Appliance Specific
Amerex

Zone Defense Overlapping Coverage


Ansul

R-102

Appliance Specific
Ansul

R-102

Overlapping Overlapping Coverage


Ansul

Piranha

Dual Agent
Fire Suppression Model Code
The Model Code below is designed as a brief overview of the options that Accurex provides for Fire
Suppression Systems.
The rst line of defense against re in a commercial kitchen is the re protection system installed in the exhaust
hood. Accurex has a variety of factory prepiped re protection systems available from the two leading manufacturers,
Amerex

and Ansul

.
Added value in choosing an Accurex factory-installed fire suppression system:
Convenience - Accurex coordinates all of the fieldwork saving you valuable time
Factory prepiped systems require less jobsite installation time, freeing up factory space for other work to be
completed
Includes application for permits and performing puff tests
Factory-installed systems are much more aesthetically pleasing
- Allows for a streamlined setup that will not interfere with the kitchen workflow
- Factory systems look finished and professionally done
- No unsightly holes or pipes that create an eyesore
Fire Suppression Systems
Model Overview
[ 33 ]
Amerex
Fire Suppression Systems
Restaurant res can be devastating. A re can begin on an appliance, in the hood
or ductwork, and quickly spread to the building. A pre-engineered re suppression
system is the rst line of defense against a restaurant kitchen re. Amerex has
been in the re protection industry since 1971 and has a reputation for excellence,
customer service and innovation unsurpassed in the industry.
Amerex Zone Defense Fire Suppression Systems
The full ood/overlapping restaurant re suppression
systems were developed to solve the real world problem of
how to protect a kitchen where the appliances are moved
around, rolled in and out for cleaning, or replaced with
different appliances to accommodate changing menus.
These systems are also cost effective with medium and
heavy duty cooking lines requiring greater protection.
Amerex KP Fire Suppression Systems
Appliance specic re suppression is a wet chemical
system to be used when the equipment placement
is known and expect few, if any, changes. Nozzles
are selected and aimed at specic hazards on each
appliance. The chemical agent itself a low pH thats
non-corrosive to stainless steel which can be safely
cleaned up with water and a sponge.
The Restaurant Fire Suppression System is constructed in compliance with the following:
UL/ULC Listed per UL 300 fire test specifications
New York City Department of Buildings (MEA)
Meets requirements of NFPA 96 (Standard for the Installation of Equipment for the Removal of Smoke and
Grease-Laden Vapors from Commercial Cooking Equipment)
Meets requirements of NFPA 17A (Standard on Wet Chemical Extinguishing Systems)
ISO 9001:2000 and ISO 14001:2004 certified
Features and Benefits
Stainless agent tank enclosures provide a professional look
Fusible link or pneumatic tubing detection - flexibility to suit design requirements
Additional switches (two SPDT is standard) for additional equipment shutdown as required
Additional pull stations (one is standard) for large rooms with multiple exits
Metal blow off caps - for high heat applications
Horn strobes - for visual and audible emergency notification
Low pressure alarm helps prevent a false discharge due to pressure loss
K-Class handheld extinguishers to meet NFPA 96 code requirements
[ 34 ]
Ansul
Ansul has been protecting restaurants since 1962 and is one of the
industry leaders in re suppression systems,
Ansul led the industry at a time when kitchen res were a leading cause
of restaurant loss, and their continued advancements in technology
and design have made Ansul the number one foodservice re
protection solution in the world.
Fire Suppression Systems
Ansul R-102 Fire Suppression System
In an appliance specic re
system, the nozzles and
placement are chosen for the
type of cooking equipment it
needs to protect. This is the
most cost-effective system, as
only the appliances that need
protection are covered.
Ansul Piranha Fire Suppression System
Dual agent re suppression
systems combine water and
chemical agent to suppress the
re. The agent is discharged
rst, suppressing the re, and
water follows to cool the hazard
and prevent reash. Dual agent
systems can be either appliance
specic or full ood.
Options and Accessories
Stainless tank enclosures provide a professional look
Flexible agent distribution hose so appliances can be rolled out for cleaning
Additional switches (two SPDT is standard) for additional equipment shutdown as required
Additional pull stations (one is standard) for large rooms with multiple exits
Metal blow off caps - for high heat applications
Horn strobes - for visual and audible emergency notification
K-Class handheld extinguishers to meet NFPA 96 code requirements
The Restaurant Fire Suppression System is constructed in compliance with the following:
UL/ULC Listed per UL 300 fire test specifications
New York City Department of Buildings (MEA)
Meets requirements of NFPA 96 (Standard for the Installation of Equipment for the Removal of Smoke and
Grease-Laden Vapors from Commercial Cooking Equipment)
Meets requirements of NFPA 17A (Standard on Wet Chemical Extinguishing Systems)
ABS - American Bureau of Shipping
[ 35 ]
Accurex Variable Volume Systems are UL Listed to Standard 891
Accurex XFCC is UL Listed to Standard 891.
Controls/Energy Management
NSF
[ 36 ]
Accurex understands the importance of managing the various relationships between your kitchen systems. It is
because we understand your needs, we provide many options to match your systems needs.
Fan Control Center
Accurexs fan control center manages all of the various power connections and relationships between the hoods,
fans, make-up air and lighting from a single source. This makes controlling your kitchen systems much easier through
one-stop control.
Vari-Flow Demand Controlled Ventilation
We realize that cooking loads vary throughout the day. Rather than having a fan and make-up air run constantly, all
day long at 100%, we offer a variable volume ventilation system that tracks the cooking load and varies the exhaust
and supply rate based on need. Thus, reducing operating costs primarily through decreasing temperature loads and
energy required to move air.
Temperature Interlock
Accurexs temperature interlock is designed and installed to automatically activate the exhaust fan(s), if not manually
started, whenever cooking operations occur. The temperature interlock activates the fan(s) when cooking exhaust
reaches the preset temperature. This control satisfies IMC code 507.2.1.1. It is also an option on our fan control
center and standard on variable volume controls.
Controls/Energy Management
Model Overview
[ 37 ]
Controls/Energy Management
Model Comparison
Temperature Interlock.
Digital Temperature Interlock
The temperature interlock is designed to automatically start the kitchen hood exhaust fans and keep them running
while heat is being generated from the cooking appliances. The interlock will override the switch and start the
fans once heat is detected in the event an operator fails to turn on the fans manuallyensuring safety and code
compliance. These systems are available as a stand-alone control or as an integrated option in our other pre-
engineered controls.
Easily Adjustable - Digital Temperature Interlock adjusts
the temperature set point through an accessible digital
display or thermostat control utilizes a sensor with set
dial screw on the back to adjust the temperature. This
can be advantageous when trying to control several
sensors, as they can be connected in parallel back to
one small control
Versatile - Use with both Type 1 and Type II hoods
Automatic Activation - Exhaust fans start when cooking
equipment generates heat
Quick Installation - Pre-installed or shipped ready for
installation
Cycling Prevention - Prevents fan from cycling on and off during variable cooking periods by use of temperature
delay control, which keeps exhaust fans running until temperature drops below and remains below a given set
point.
Automatic Shut Down - Turns off exhaust fans automatically once the temperature has dropped below the safety
set point and remains there.
Efficient - Maximize efficiency by using one temperature interlock package per hood system (each temperature
interlock activates all fans linked to system simultaneously)
Optional Switches
Meets IMC code 507.2.1.1
Temperature Interlock
Accurexs temperature interlock is designed and installed to automatically activate the exhaust fan, if not manually
started, whenever cooking operations occur. The activation of the exhaust fan occurs through a temperature probe
that detects an increased temperature and activates the fans. Accurex offers a stand-alone package as well as an
option on our fan control center XFCC.
Stand-Alone Package Features:
Temperature probe with adjustable temperature
setting is factory-mounted in the exhaust collar
Shipped loose for field installations for ship loose
collars and J-box with open back and cover
8 in. x 8 in. relay box
Single-Pole Double-Throw (SPDT) relay
1-100minute time delay
Terminal strip
Typical mounting locations:
Hood top
Utility cabinet (Hood or Remote)
Utility distribution system (UDS)
Remote
[ 38 ]
Fan Control Center
Fan control centers manage the various power connections and relationships to other equipment. This can be a
challenge. The Accurex fan control center (XFCC) allows you to manage them from one location, with well-labeled
connections and a variety of options to reduce installation and coordination time at the
jobsite. (The XFCC is prewired. Minimal field wiring is required for the main power and
connection to fans and lighting.) This eliminates the often complex field wiring that
can lead to mistakes and job delays resulting in failed inspections. The XFCC offers
clean, safe, and dependable control for the kitchen fans and hood lights. A variety
of options are available.
Standard Construction Features:
Prewired
UL Listed to Standard 891
Magnetic motor starters
Light & fan switch mounted on door (wall mounted only)
Numbered terminal strip
Color coded wiring with diagram mounted inside door
Exhaust on in fire mode
Thermal overloads in cabinet
Controls/Energy Management
Model Comparison
XFCC. Options.
Fan Control Center Options
Trim Ring Cosmetic feature designed to trim out the
XFCC when recessed into the wall.
Removal of Starter When Supplied in Unit Option
used when the starter for the fan is already supplied.
Up To 2 Status Lights Lights that indicate a specic
function is on. These lights can be either 24 Volt or
120Volt.
Up To 2 Extra Fire Relays Two optional re relays to
hook-up to other features as needed.
Lights Out in Fire Connecting lights with this option
will shut lights off in the event of a re.
Supply Fan Failure Indicator Light Lights up when
the supply fan fails.
Exhaust Fan Failure Indicator Light Lights up when
the exhaust fan fails.
Single Light/Fan Switch One switch that turns on all
lights and fans.
Power For Shunt Trip Prewired at the factory to
provide power to shunt trip. This option eliminates the
need for eld hook-up.
Automatic Damper Switch Reset switch that opens
the damper up again after re triggered the damper
toclose.
Temperature Interlock Designed and installed to
automatically activate the exhaust fan, if not manually
started whenever cooking operations occur. (See
temperature interlock section for details).
[ 39 ]
Controls/Energy Management
Model Comparison
Variable Volume.
Variable Volume
Saving energy is as simple as recognizing that cooking loads vary throughout the day. Accurexs Vari-Flow Controls
detect these changes in cooking activity and modulate the exhaust and supply air based on demand, thereby saving
energy and reducing operating costs.
The Accurex Vari-Flow Air Management System utilizes strategically placed heat sensors to effectively monitor the
cooking operation and quickly adjust airow to meet the demand. Reducing energy during slower periods of the day
reduces electrical energy consumption and decreases heating and cooling loadsall signicantly reducing operating
costs. See Figures 1-3 on the next page.
Features Exceptional Turndown
Industry-leading turndown capabilities on both exhaust and tempered make-up air of up to
50%, resulting in up to 90% electrical savings and additional heating and cooling savings.
User Interface Keypad
Membrane keypad to control fans, lights, manual override conditions and identify
system events.
User Interface Touchscreen with Digital Displays
An intuitive, high-resolution touchscreen user interface with a simple tablet-based
navigation.
Independent fan and light control to consolidate systems and maximize both first
cost and operating cost savings.
Live system operation dashboard to monitor energy savings throughout the day
as well as historical trending.
Capture Tank Mounted Temperature Sensor
Responds up to 5 times faster than duct mounted temperature sensors when sensing temperature change for
excellent control and more efcient operation.
Space Pressure Control
Vari-Flow has an option to control the supply air unit by sensing static pressure in the space, independent of the
exhaust fan speed, to ensure proper room pressurization at all times.
Melink

Intelli-Hood

The Melink

Intelli-Hood

uses both heat sensors and optic sensors to monitor the cooking
operation and modulate the airow. The optic sensors provide additional control, especially
in large cooking batteries containing steamers, kettles and other similar appliances that
produce a lot of smoke or steam.
Product Features & Advantages:
Optic Sensors - In addition to a primary temperature sensor in the duct collar, the
Intelli-Hood system includes optic sensors to sense steam and/or smoke being
generated from the cooking process. When as little as seven percent of the optics
infrared beam is blocked, the exhaust fans are sent to full speed to capture the effluent.
Professional Service - Melink includes a factory start-up with the purchase of their system. This start-up
includes a site visit from a Melink field technician to ensure that the system is installed correctly and programmed
based on the application. The technician will also provide basic training to operators present during the start-up.
Control Large Systems - The system is designed to easily handle larger systems and can be easily programmed
and monitored from its keypad control.
Increased Savings - Reduces airflow by 50% or more during idle cooking periods generating more electrical,
heating and cooling savings.
SETUP
%
100%
Listed 33 x 7
LUCES
VENTILADORES
FANS
LIGHTS
CLEAN
FAULT
RESET
HOOD
Melink Customer Service USA: 877-477-4190
FAN
FAN 100%
LIGHTS
TEMPERATURE
INTERLOCK
SYSTEM
FAULT
FAN
FAN 100%
LIGHTS
TEMPERATURE
INTERLOCK
FAN
FAN 100%
LIGHTS
TEMPERATURE
INTERLOCK
INDIVIDUAL
LIGHT ON/OFF
ALL LIGHTS
INDIVIDUAL
FAN ON/OFF
ALL FANS
ON/OFF
AUTO
TEMPERING
100%
OVERRIDE
CLEAN
HOOD
TEMP INTERLOCK
INDICATOR
100
75
50
25
0
1
EXHAUST FAN
2 3 4
100
75
50
25
0
SUPPLY FAN
1 2
10:11:57
INDIVIDUAL
LIGHT ON/OFF
ALL LIGHTS ALL LIGHTS
INDIVIDUAL
FAN ON/OFF
ALL FANS ALL FANS
ON/OFF
AUTO
TEMPERING
100% 100%
OVERRIDE
CLEAN CLEAN
HOOD
TEMP INTERLOCK TEMP INTERLOCK
INDICATOR
100
75
50
25
0
1
EXHAUST FAN
2 3 4
100
75
50
25
0
SUPPLY FAN
1 2
10:11:57
[ 40 ]
Controls/Energy Management
Model Comparison
Variable Volume.
The charts below are an example of how the cooking load in a typical restaurant varies throughout the day
and how the temperature only variable volume system can work with the load and save money.
For responsibilities and start-up processes go to www.accurex.com.
Variable Volume
Figure 2 The cooking load through out the
day varies significantly. The maximum ventilation
requirements of the kitchen operation only account
for a small percentage of the day. The shaded
area in Fig. 2 represents the savings potential
for variablevolume. The red line is showing fan
operation at 100% regardless of cooking load.
Figure 3 A variable volume system will track
the cooking load (red line) and vary the exhaust
and supply ventilation. The area above the red line
represents energy savings. The chart is an example
of a daily cooking load.
0%
20%
40%
60%
80%
100%
11 10 9 8 7 6 5 4 3 2 1 12 11 10 9 8 7 6
Constant Volume Design Airow
Operating Hours
C
F
M
B
r
e
a
k
f
a
s
t
L
u
n
c
h
D
i
n
n
e
r
= Constant Volume
$
$ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $
$ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $
$ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $
$ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $
$ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $
$
$ $ $ $ $
0%
20%
40%
60%
80%
100%
11 10 9 8 7 6 5 4 3 2 1 12 11 10 9 8 7 6
Variable Volume Matches Airow to Cooking Load
Operating Hours
C
F
M
B
r
e
a
k
f
a
s
t
L
u
n
c
h
D
i
n
n
e
r
0%
20%
40%
60%
80%
100%
11 10 9 8 7 6 5 4 3 2 1 12 11 10 9 8 7 6
= Variable Volume
Figure 1 In a typical kitchen, the ventilation
equipment runs at the maximum cfm through
the entire day based on a peak load calculation.
Expensive tempered air is exhausted and supplied
regardless of the cooking load. The red line is
showing fan operation at 100% regardless of
cooking load.
0%
20%
40%
60%
80%
100%
11 10 9 8 7 6 5 4 3 2 1 12 11 10 9 8 7 6
Constant CFM - Exhaust and Supply Fan on all Day
Operating Hours
C
F
M
Design CFM
= Constant Volume
[ 41 ]
Utility Distribution Systems
Accurex Utility Distribution Systems are UL 891 Listed.
NSF
[ 42 ]
Accurexs Utility Distribution Systems (UDS) provide exible, convenient and safe utility connections for commercial
cooking operations while saving installation time in the eld. Factory-built systems offer a cost-effective way to
replace contractor built utilities in walls which require a lot of time and energy spent coordinating with various trades.
They also allow for future expansion or relocation of appliances without expensive modications. The Accurex UDS
provides a single point of connection for gas, electricity, water and optional utilities. The stainless steel exterior is easy
to clean and safely conceals all wiring. Utility distribution systems are available in wall and island styles and can be
manufactured in incremental lengths, expandable to accommodate virtually any cooking line-up.
Designation Description
I XM Standard
XU Custom
II I Island
W Wall
C Chase Only
O Overhead
E Electric Pole
U Utility Column
III B Buss Bar
H Horizontal Cable
V Vertical Cable
R Receptacles Only
N None
Designation Description
IV G Gas
H Hot Water
C Cold Water
O Filtered Water
L Chilled Water
S Steam/Condensate Return
A Air, Compressed
D Drain and Vent
F Fire System
K Fan/Hood Controls
P Prison Package
N None
V Unit Length Feet-Inches
Model Number Code
The Model Number Code is designed to completely identify the unit. The correct code letters must be
specified to designate the configurations and size.
I II III IV V
XM I V - GHC - 15-6
Utility Distribution Systems
Model Overview
Benets of an Accurex UDS
Flexibility
Fast installation
Cost-effective
Convenient
Mobility
Safety
Expandable
Custom units are available
[ 43 ]
Utility Distribution Systems
Standard Construction Features
Options and Accessories
Standard Construction Features
Configuration:
16 gauge 300 series stainless steel where exposed
Wall or island style units are available for positioning against a wall or between hoods
Flexible length units are manufactured in 1-inch increments starting at 8 feet to unlimited
Unit width standard 12 inches or an optional slim line unit of 6 inches
Riser length standard 24 inches and available in one-inch incremental lengths from 12 to 48 inches
Field joints bolt together with stainless steel pedestal on the chase
Filler panels provided to finish area between hoods and utility distribution system yielding a professional and
finished appearance
Gas:
Main gas line standard 2-inch diameter. 1
1
4- or 1
1
2-inch lines are available as options
Gas configuration: Gas lines are provided entering the system through one riser. (For longer units, looped gas will
be provided).
Water:
Hot and cold water. Insulated 3/4 or 1-inch diameter line provided
Electrical:
Fan and light switches are standard, based on need
Convenience receptacle 120/1 - 20A GFCI is provided on the end of each riser
Conguration
Chase Style Standard at top. Peaked optional.
Riser Termination An adjustable height collar (78-
to 84-inch) is provided. If required, an optional riser
extension is available at specied heights.
Special Congurations are available, please contact
your Accurex representative for details.
Gas
Drop Size Alternating
3
4 and 1
1
4 are standard and
placed every 12 inches. Capped for future if not being
used.
Quick Disconnect Hoses Provides an easy method of
connecting or disconnecting gas lines (available in 48-,
60-, and 72-inch lengths).
Restraint Cables Prevents cooking equipment from
being moved without disconnecting the gas line.
Main Ball Valve On incoming service to turn gas off at
the unit.
Fire System Gas Valve Mechanical or electric with
manual reset gas valves can be mounted in the unit to
turn off gas in re mode.
Battery Backup For Gas Solenoid Is available for
your gas utilities.
Ball Valves Available in
1
2-, -, 1- or 1
1
4-inch for
shut off at each connection
along the chase.
[ 44 ]
Utility Distribution Systems
Options and Accessories
Electrical
Primary Electrical Service Choose from panel board
or point-of-use breakers. Main breaker and branch
breakers are provided with primary electrical service.
See table for available sizes.
Electrical Receptacles 120 Volt or 208 Volt based on
need and the receptacles. NEMA conguration is straight
blade with an available twist lock option in 120/1-20A
GFCI (GFCI not available with twist lock). Optional
cordset is available.
Controls For the primary electrical service option that
includes optional status lights, re system connection,
optional light or fan (switches), gas solenoid control
panel (with a solenoid gas valve), optional emergency
shutdown and prewired tempering switch (if required).
Secondary Electrical Service Choose from panel
board or point-of-use breakers. Main breaker and branch
breakers are provided with secondary electrical service.
See table for available sizes.
Breaker Voltage Phase
Min Size
(Amp)
Max Size
(Amp)
Main 120 or 208 1 40 400
Branch 120 1 20 50
Branch 208 1 20 70
Branch 208 3 20 125
Breaker Voltage Phase
Min Size
(Amp)
Max Size
(Amp)
Main 480 or 208 3 40 400
Branch 120 1 20 50
Branch 208 1 20 70
Branch 208 3 20 125
Branch 480 3 20 100
Water
Main Ball Valves On incoming service to provide a
main shutoff at the unit
Gauges Available for either
pressure/temperature or
pressure only.
Fill Faucet With 60-inch hose.
Water Hoses Available in lengths of 48-, 60- or
72-inches.
Water Filters Available in single appliance and multiple
appliance styles.
Hot and Cold Water Drops
3
4-inch diameter and
placed every 24 inches.
Shock Arrestors To prevent water hammering that
typically occurs when the water is shut off.
Pressure Reducing Valve Is used when the water
pressure entering the UDS is too high. The reducer valve
reduces the pressure to an appropriate level (typically
40-60 psi).
Hand Sink Mounted on the riser is available. Sink is
12inches wide.
Hose Reel Assembly Mounted on one of the risers
and is available for auxiliary hoses.
Ball Valves Available from
1
4-,
3
8-, - and
3
4-inch for
shut off at each connection along the chase.
Additional Utilities and Options
Steam / condensate system
Chilled water line with insulation
Compressed air line
Gasketed construction
Weatherproof receptacle / switch covers
While-in-use receptacle covers
12 x 12-inch viewing window in riser
Hinged access doors on risers
Water filter bracket on chase
10 foot conduit for wiring to hood lights
Ground fault equipment protection
XFCC mounted in riser
Variable volume system mounted in riser
Temperature interlock mounted in riser
[ 45 ]
Grease Grabber
Pollution Control Units
With the increasing size of the urban landscape, the focus on clean air, and multi-use buildings, restaurant odor control
and grease control play an increasingly important role in commercial kitchen exhaust systems.
No one wants their apartment or hotel room smelling like the restaurant below or their windows smeared from greasy
kitchen exhaust air. In addition, restaurants on the ground oor of a high rise building need a cost-effective way to
discharge closer to ground level to prevent having to run duct work for many stories.
Accurexs Grease Grabber Triple Play and Power Play products are specically designed to eliminate both smoke
and grease particles from your kitchen exhaust system, and odor control modules eliminate or reduce odors to
acceptable levels.
Triple Play
The Grease Grabber Triple Play uses a 3-stage
mechanical lter arrangement to clean grease and
smoke particles from the exhaust air at a low up front
cost. Independent pressure switches signal when any of
the three lter stages need replacing, taking the guess
work out of maintaining the equipment. The Grease
Grabber Triple Play incorporates activated carbon
panels to remove odor molecules prior to discharging
the air, reducing the impact of kitchen exhaust to the
surroundings.
Power Play
The Grease Grabber Power Play electrostatic precipitator
is the best available technology when it comes to kitchen
pollution control. It provides optimum performance
with low operating costs. The permanent electrostatic
collector section removes grease and smoke particles
from the airstream. Additionally, the integrated self-
cleaning sequence, initiated by the system controls,
readies the Power Play to go to work again without the
time and expense of replacing lters. The Power Play
incorporates activated carbon panels to remove odor
molecules prior to discharging the air, reducing the
impact of kitchen exhaust to the surroundings.
[ 46 ]
Grease Grabber Triple Play
Standard Construction Features
Options and Accessories
Model
XPBRC
Maximum
Air Volume
1

(cfm)
A B C D E
Unit Weight
(pounds)
Height
(inches)
Width
2

(inches)
Inlet Transition
3

(inches)
Unit Length
(inches)
Outlet Trans/Fan
(inches)
-10-10 2,000 34 26.3 18-26 98 52.3 1100
-10-20 4,000 34 50.0 18-26 98 57.8 1600
-10-30 6,000 34 73.7 18-26 98 71.5 2150
-20-20 8,000 58 50.0 18-26 98 72.0 2600
-20-30 12,000 58 73.7 18-26 98 77.8 3500
-20-40 16,000 58 97.4 18-26 98 99.1 4200
-30-30 18,000 82 73.7 18-26 98 78.0 4700
-30-40 24,000 82 97.4 18-26 98 84.1 5700
-40-40 32,000 109 97.4 18-26 98 98.4 7300
-40-50 40,000 109 121.5 18-26 98 104.4 8000
1 Maximum air volume is based on 500 ft./min. air velocity across the precipitator
2 Lifting lugs for the unit add a nominal 4 inches to each side of the unit width
3 Actual dimension based on incoming duct dimension to ensure expansion angles do not exceed 45
NOTE: Dimensions are subject to change pending final fan selection
NOTE: Type and volume of cooking and cooking fuel must be factored in when selecting unit. Consult factory for final selection.
Metal framed filters in
extruded aluminum
and gasketed tracks
prevents air from
bypassing the filters.
Internal pressure switches
monitor each individual filter
stage. A remote filter status
indicator panel advises
maintenance staff when each
filter stage requires replacement.
A
B C D E
1
2
3
4
5
6
Factory inlet transition fabricated to match ductwork
for ease of installation
MERV 8 pre-filter removes large particles from the
incoming airstream to protect high efficiency filters
and minimize maintenance
MERV 14 high capacity bag filter removes a large
percentage of smaller particles not captured by the
pre-filter
MERV 16 rigid final filter ensures a minimum overall
particulate removal efficiency of 95%
1
2
3
4
6
5 Bonded activated carbon filters reduce cooking
odors with a generous application of 95 lbs. of
carbon per 1,000 cfm of exhaust to maximize
performance and minimize maintenance
Accurex utility set fan with motor and drive mounted
outside of the airstream per NFPA 96. Factory-
provided high temperature flex fabric transition.
Optional Items
MERV 17 HEPA filters available for efficiencies greater
than 95%.
Potassium permanganate and other impregnates available
for code compliance and/or to deal with specific odors.
Accurex inline fan options available to fit specific job needs.
Unit can be constructed in multiple sections for field
assembly if required.
ANSI/UL 867 Listed
Built in accordance
with NFPA 96
[ 47 ]
Grease Grabber Power Play
Standard Construction Features
Options and Accessories
A
B C D E
1
2
3
4
5
6
7
1
2
3
4
6
7
5
Optional Items
MERV 17 HEPA filters available for efficiencies greater
than 95%.
Potassium permanganate and other impregnates available
for code compliance and/or to deal with specific odors.
Accurex inline fan options available to fit specific job needs.
Unit can be constructed in multiple sections for field
assembly if required.
Factory inlet transition fabricated to match
ductwork for ease of installation
Aluminum mesh pre-filter removes large particles
from the incoming airstream prior to reaching the
ionizer cell.
The electrostatic collectors ionizer imparts a
positive electrical charge on the grease and
smoke particles as they pass. These particles are
then repelled by positively charged plates and
collected on negatively charged plates.
Aluminum mesh mist eliminator that prevents
wash water from entering safety filter and carbon
sections.
MERV 14 high capacity bag filter acts as a safety
filter preventing high amounts of grease from
saturating the carbon panels should the units
ionizer lose power.
Bonded activated carbon filters reduce cooking
odors with a generous application of 156 lbs. of
carbon per 1,000 cfm of exhaust to maximize
performance and minimize maintenance.
Accurex utility set fan with motor and drive mounted
outside of the airstream per NFPA 96. Factory-
provided high temperature flex fabric transition.
Model
XSA
Maximum
Air Volume
1

(cfm)
A B C D E
Unit Weight
(pounds)
Height
(inches)
Width
2

(inches)
Inlet Transition
3

(inches)
Unit Length
(inches)
Outlet Trans/Fan
(inches)
-02-03 2,000 41 42.625 18-26 106.125 58.313 3100
-02-04 2,500 41 54.625 18-26 106.125 65.313 3620
-02-05 3,500 41 65.375 18-26 106.125 65.313 4025
-02-06 4,000 41 77.375 18-26 106.125 67.313 4280
-04-04 5,500 65 54.625 18-26 106.125 76.188 4580
-04-05 6,500 65 65.375 18-26 106.125 78.313 5200
-04-06 8,000 65 77.375 18-26 106.125 83.313 5700
-04-07 9,000 65 89.063 18-26 106.125 83.313 6420
-04-08 10,500 65 101.063 18-26 106.125 96.876 7080
-04-09 12,000 65 112.750 18-26 106.125 101.375 7560
-06-08 16,000 88.875 101.063 18-26 106.125 103.313 8800
-06-09 18,000 88.875 112.750 18-26 106.125 103.313 9510
1 Maximum air volume is based on 350 ft./min. air velocity across the precipitator
2 Lifting lugs for the unit add a nominal 4 inches to each side of the unit width
3 Actual dimension based on incoming duct dimension to ensure expansion angles do not exceed 45
NOTE: Dimensions are subject to change pending final fan selection
NOTE: Type and volume of cooking and cooking fuel must be factored in when selecting unit. Consult factory for final selection.
Remote mounted detergent dispenser for
the electrostatic collector self-cleaning
system. Holds up to 55 gallons for less
frequent maintenance.
Remote mounted control panel is pre-
programmed to sequence the wash cycle
of the electrostatic collector section at a set
schedule, minimizing manual maintenance.
OPERATOR INTERFACE
SYSTEM START SYSTEM STAND BY NORMAL OPERATION
MANUAL WASH WASH IN PROGRESS DETERGENT LOW LEVEL
RESET RESET INDICATOR
POWER SUPPLY HIGH VOLTAGE
POWER SUPPLY PRIMARY POWER POWER SUPPLY HIGH VOLTAGE
ANSI/UL 867 Listed
Built in accordance
with NFPA 96
Copyright 2013 Accurex, LLC
Kitchen Ventilation Systems
Hoods, Fire Systems, Controls, Accessories
00.ACX.1002 R2 10-2013 IP
P.O. Box 410 Schoeld, WI 54476
Phone: 800.333.1400 Fax: 715.241.6191
www.accurex.com
A Greenheck Company