60870-5-103, Clause 8 IEC:1997 1 ipConv, IEC103Master

8 Int eroperabi l i t y
8.1 Physi cal l ayer
8.1.1 El ect ri cal i nt erf ace

X EIA RS-485

X Number of loads 32 for one protection equipment

NOTE EIA RS-485 standard defines unit loads so that 32 of them can be operated on one line. For detailed information refer
to clause 3 of EIA RS-485 standard.

8.1.2 Opt i cal i nt erf ace
Glass fibre
Plastic fibre
F-SMA type connector
BFOC/2,5 type connector
8.1.3 Transmi ssi on speed
X 9 600 bit/s
X 19 200 bit/s
8.2 Li nk l ayer
There are no choices for the link layer.
8.3 Appl i cat i on l ayer
8.3.1 Transmi ssi on mode f or appl i cat i on dat a
Mode 1 (least significant octet first), as defined in 4.10 of IEC 60870-5-4, is used exclusively in this
companion standard.
8.3.2 COMMON ADDRESS OF ASDU
X One COMMON ADDRESS OF ASDU (identical with station address)
X More than one COMMON ADDRESS OF ASDU

60870-5-103, Clause 8 IEC:1997 2 ipConv, IEC103Master
8.3.3 Sel ect i on of st andard i nf ormat i on numbers i n moni t or di rect i on
8.3.3.1 Syst em f unct i ons i n moni t or di rect i on
INF Semantics
X <0> End of general interrogation
X <0> Time synchronization
<2> Reset FCB
X <3> Reset CU
X <4> Start/restart
X <5> Power on
8.3.3.2 St at us i ndi cat i ons i n moni t or di rect i on
INF Semantics
X <16> Auto-recloser active
X <17> Teleprotection active
X <18> Protection active
X <19> LED reset
X <20> Monitor direction blocked
X <21> Test mode
X <22> Local parameter setting
X <23> Characteristic 1
X <24> Characteristic 2
X <25> Characteristic 3
X <26> Characteristic 4
X <27> Auxiliary input 1
X <28> Auxiliary input 2
X <29> Auxiliary input 3
X <30> Auxiliary input 4

60870-5-103, Clause 8 IEC:1997 3 ipConv, IEC103Master
8.3.3.3 Supervi si on i ndi cat i ons i n moni t or di rect i on
INF Semantics
X <32> Measurand supervision I
X <33> Measurand supervision V
X <35> Phase sequence supervision
X <36> Trip circuit supervision
X <37> I>>back-up operation
X <38> VT fuse failure
X <39> Teleprotection disturbed
X <46> Group warning
X <47> Group alarm
8.3.3.4 Eart h f aul t i ndi cat i ons i n moni t or di rect i on
INF Semantics
X <48> Earth fault L
1

X <49> Earth fault L
2

X <50> Earth fault L
3

X <51> Earth fault forward, i.e. line
X <52> Earth fault reverse, i.e. busbar

60870-5-103, Clause 8 IEC:1997 4 ipConv, IEC103Master
8.3.3.5 Faul t i ndi cat i ons i n moni t or di rect i on
INF Semantics
X <64> Start /pick-up L
1

X <65> Start /pick-up L
2

X <66> Start /pick-up L
3

X <67> Start /pick-up N
X <68> General trip
X <69> Trip L
1

X <70> Trip L
2

X <71> Trip L
3

X <72> Trip I>>(back-up operation)
X <73> Fault location X in ohms
X <74> Fault forward/line
X <75> Fault reverse/busbar
X <76> Teleprotection signal transmitted
X <77> Teleprotection signal received
X <78> Zone 1
X <79> Zone 2
X <80> Zone 3
X <81> Zone 4
X <82> Zone 5
X <83> Zone 6
X <84> General start/pick-up
X <85> Breaker failure
X <86> Trip measuring system L
1

X <87> Trip measuring system L
2

X <88> Trip measuring system L
3

X <89> Trip measuring system E
X <90> Trip I>
X <91> Trip I>>
X <92> Trip IN>
X <93> Trip IN>>

60870-5-103, Clause 8 IEC:1997 5 ipConv, IEC103Master
8.3.3.6 Aut o-recl osure i ndi cat i ons i n moni t or di rect i on
INF Semantics
X <128> CB on by AR
X <129> CB on by long-time AR
X <130> AR blocked
8.3.3.7 Measurands i n moni t or di rect i on
INF Semantics
X <144> Measurand I
X <145> Measurands I, V
X <146> Measurands I, V, P, Q
X <147> Measurands I
N
, V
EN

X <148> Measurands I
L1,2,3
, V
L1,2,3
, P, Q, f
8.3.3.8 Generi c f unct i ons i n moni t or di rect i on
INF Semantics
<240> Read headings of all defined groups
<241> Read values or attributes of all entries of one group
<243> Read directory of a single entry
<244> Read value or attribute of a single entry
<245> End of general interrogation of generic data
<249> Write entry with confirmation
<250> Write entry with execution
<251> Write entry aborted
8.3.4 Sel ect i on of st andard i nf ormat i on numbers i n cont rol di rect i on
8.3.4.1 Syst em f unct i ons i n cont rol di rect i on
INF Semantics
X <0> Initiation of general interrogation
X <0> Time synchronization

60870-5-103, Clause 8 IEC:1997 6 ipConv, IEC103Master
8.3.4.2 General commands i n cont rol di rect i on
INF Semantics
X <16> Auto-recloser on/off
X <17> Teleprotection on/off
X <18> Protection on/off
X <19> LED reset
X <23> Activate characteristic 1
X <24> Activate characteristic 2
X <25> Activate characteristic 3
X <26> Activate characteristic 4
8.3.4.3 Generi c f unct i ons i n cont rol di rect i on
INF Semantics
<240> Read headings of all defined groups
<241> Read values or attributes of all entries of one group
<243> Read directory of a single entry
<244> Read value or attribute of a single entry
<245> General interrogation of generic data
<248> Write entry
<249> Write entry with confirmation
<250> Write entry with execution
<251> Write entry abort
8.3.5 Basi c appl i cat i on f unct i ons
Test mode
Blocking of monitor direction
Disturbance data
Generic services
Private data

60870-5-103, Clause 8 IEC:1997 7 ipConv, IEC103Master
8.3.6 Miscellaneous
Measurands are transmitted with ASDU 3 as well as with ASDU 9. As defined in 7.2.6.8, the maximum
MVAL can either be 1,2 or 2,4 times the rated value. No different rating shall be used in ASDU 3 and
ASDU 9, i.e. for each measurand there is only one choice.
Measurand Max. MVAL = rated value times
1,2 or 2,4
Current L
1
X X
Current L
2
X X
Current L
3
X X
Voltage L
1-E
X X
Voltage L
2-E
X X
Voltage L
3-E
X X
Active power P X X
Reactive power Q X X
Frequency f X X
Voltage L
1
- L
2
X X