Gendiesel 50 TD en

Download as pdf or txt
Download as pdf or txt
You are on page 1of 168

50 Hz

GEN Series with Diesel Engine Pumps


FIRE-FIGHTING BOOSTER SETS EN 12845, HIGH EFFICIENCY ELECTRIC PUMPS
FHF and SHF SERIES WITH HIGH EFFICIENCY MOTORS AND DIESEL ENGINE PUMPS

Cod. 191000461 R
ev
.A Ed.11/2011
Rev
ev.A

CONTENTS

General introduction .............................................................................................................................

10

Characteristics of electric pumps diesel engine pumps .................................................................

13

Accessories and main components ..................................................................................................

26

Choice and selection ........................................................................................................................

35

GEN..D/FHF series ..........................................................................................................................

37

Range ...............................................................................................................................................

41

Hydraulic performance tables ...........................................................................................................

53

Electrical performace tables ..............................................................................................................

55

DFHF series .......................................................................................................................................

59

GEN..00D/FHF series .........................................................................................................................

63

GEN..01D/FHF series .........................................................................................................................

69

GEN..10D/FHF series .........................................................................................................................

73

GEN..11D/FHF series .........................................................................................................................

79

Hc pressure drop curve in suction kit ...............................................................................................

CONTENTS

91

GEN..D/SHF series ........................................................................................................................

93

Range ...............................................................................................................................................

96

Hydraulic performance tables ...........................................................................................................

106

Electrical performance tables .......................................................................................................

107

DSHF series ..................................................................................................................................

111

GEN..00D/SHF series ....................................................................................................................

115

GEN..01D/SHF series ....................................................................................................................

119

GEN..10D/SHF series ....................................................................................................................

123

GEN..11D/SHF series ....................................................................................................................

127

Hc pressure drop curve in suction kit ..........................................................................................

137

Accessories .................................................................................................................................

152

Product description by technical specifications ...........................................................................

The GEN booster sets are built in conformity with EN12845 for automatic sprinkler systems and with UNI10779 for
hydrant systems.
In accordance with the above standards, all the main components of the booster set are factory connected and
assembled.
The configuration of the booster set depends on the number of pumps installed and on the type of electric motor or
diesel engine, consistently with the type of supply chosen for the fire-fighting system from among those described in
the standard. The water supply can be single, superior, duplicated or combined. Two main service pumps, one backing
up the other, are normally installed for fire-fighting systems. The choice of electric motors or diesel engines depends on
the level of reliability required from the system. In practice, fire-fighting booster sets have one electric service pump and
one diesel service pump.
Point 10.2 of EN 12845 states that for superior or duplicate water supplies, and if more than one pump is installed, no
more than one service pump can be driven by the electric motor.
This concept means that mixed assemblies, comprising electric or diesel pumps, have to be installed.
This does not mean that it is not possible to have two electric pumps, one backing up the other, if the ascertained fire
risk is low (single supplies) or if a diesel generator is already incorporated in the system.
The Lowara GEN series of booster sets are therefore configured according to system requirements and initial
considerations. They are also factory tested and comprise the following:
One or two horizontal or vertical service pumps with the same hydraulic performance level, driven by
an electric motor.
Two horizontal service pumps with the same hydraulic performance level, driven by an electric motor
and a diesel engine.
A horizontal service pump driven by a diesel engine.
The booster set is built and completed with the following main components:
A Lowara SV series jockey electric pump (if required), controlled by an electric panel in the automatic
mode. The jockey pump is automatically started and stopped by its pressure switch in order to restore
supply pressure. This prevents the service pumps from starting and activating the main alarms.
A control panel for each service pump.
Two pressure switches for each service pump (if the first fails, the second repeats permission for the
pump to start).
On the discharge side of each service pump there is a on-off valve, a check valve and a tap for connection
to the priming circuit for suction lift installations. Moreover, if the service pump works with a closed
discharge line, a water recirculation tap has been applied to the pump body in order to prevent the
pump from overheating.
Discharge manifold connected to each service pump, fitted with a weld-on flange for connection to
the system.
Single base containing all the booster set components within a compact structure and ready for
installation.
To complete the pump station as requested by the standard, the GEN series of booster sets are fitted with the
following accessories:
Suction side kit.
Flow meter.
Alarm panel.
Set of spare parts for diesel engines.
Priming tank with accessories (for suction lift installations).
24L diaphragm tanks.

INTRODUCTION

GEN SERIES OF BOOSTER SETS


GENERAL INTRODUCTION PRODUCT DESCRIPTION

SET IDENTIFICA
TION CODE
IDENTIFICATION
DIESEL ENGINE PUMP
D

FHF

X /

32-200/D204

/ B / IP55

INTRODUCTION

Options:
IP55 = Panels with IP55 protection.
_ = Language group IT, EN, FI, PT.
B = Language group EN, FR, DE, NL.
Pump model.

GRU

X = Automatic shut-off.
A = Version with periodic self-test.
EN 12845 Fire-fighting series.
FHF = Pump code.
SHF = Pump code.
Diesel engine pump.

DIESEL ENGINE PUMP SET


GEN

00D

/ FHF 32-200/D204

/ B / IP55
Options:
IP55 = Panels with IP55 protection.
_ = Language group IT, EN, FI, PT.
B = Language group EN, FR, DE, NL.
FHF = Pump code.
SHF = Pump code.
Diesel engine pump only.
X = Automatic shut-off.
A = Version with periodic self-test.
GEN Fire-fighting series.

SET WITH DIESEL ENGINE PUMP AND ELECTRIC PUMP


GEN

D / FHF 32-200/40/D204 + 1SV15 /

B / IP55
Options:
CP = Clean contacts in electric pump panel.
IP55 = Panels with IP55 protection.
KV = Voltmeter kit.
_ = Language group IT, EN, FI, PT.
B = Language group EN, FR, DE, NL.
Jockey pump code.
FHF = Service pump code.
SHF = Service pump code.
D = With diesel engine pump.
0 = Without electric jockey pump.
1 = With electric jockey pump.
0 = Without electric service pump.
1 = With 1 electric service pump.
X = Automatic shut-off.
B = Basic version (only mark if electric service
pump is present).
A = Version with periodic self-test.
Electric service pump electric start-up
D = Direct start (Up to and including 22 kW).
Y = Star/delta start.
I = Impedance start.
GEN Fire-fighting series.

REFERENCE ST
ANDARDS
STANDARDS

- Machine Directive 2006/42/EC.


- Low Voltage Directive 2006/95/EC.
- Electromagnetic Compatibility Directive 2004/108/EC.
The electric pump performance is declared to be in accordance with the following standard:
ISO 9906-A Rotodynamic pumps hydraulic performance tests and acceptation criteria.
The fire-fighting booster sets conform to the European fire-fighting Standard EN 12845.
The automatic shut-off versions also conform to the UNI 10779 Italian Standard for hydrant systems.

INTRODUCTION

The Lowara fire-fighting booster sets are EC certified in conformity with the following directives:

GEN SERIES OF BOOSTER SETS


FUNCTIONAL DIAGRAM FOR POSITIVE SUCTION HEAD INST
ALLA
TIONS
INSTALLA
ALLATIONS
P

INTRODUCTION

PRESSURE GAUGE

MEMBRANE VESSEL

DRIVE UNIT

LEVEL SWITCH

ON-OFF VALVE

MQ

PUMP

FIRE FIGHTING
SYSTEM

FIRE FIGHTING
SYSTEM

PRESSURE SWITCH
STARTING

NON RETURN VALVE

OPEN DRAINAGE

RUBBER JOINT

FLOW METER

MQ

QF, CONTROL PANEL FOR DUTY ELECTRIC PUMP


QF, CONTROL PANEL FOR DUTY DIESEL PUMP
QPD, CONTROL PANEL FOR JOCKEY PUMP
QAL, ALARMS CONTROL PANEL

STRAINER

FLOATING
TAP

PM

ECCENTRIC REDUCER

PUMP RUNNING
PRESSURE SWITCH

PM

PM

CONNECTIONS

WATER SUPPLY

WATER SUPPLY

HYDRAULIC PIPING LINE

POWER SUPPLY

ELEMENTS ON REQUEST

INSTALLATION BY CUSTOMER

NOTE: ONLY APPROXIMATE DRAWING

QF

QPD

POWER SUPPLY

QMTP

POWER SUPPLY

QAL

POWER SUPPLY
POWER SUPPLY

12845-GEN11D_SPB-EN_B_SC

GEN SERIES OF BOOSTER SETS


FUNCTIONAL DIAGRAM FOR SUCTION LIF
T INST
ALLA
TIONS
LIFT
INSTALLA
ALLATIONS

PRESSURE GAUGE

MEMBRANE VESSEL

DRIVE UNIT

LEVEL SWITCH

ON-OFF VALVE

PUMP

MQ

FIRE FIGHTING
SYSTEM

FIRE FIGHTING
SYSTEM

MQ

PRESSURE SWITCH
STARTING

NON RETURN VALVE

OPEN DRAINAGE

RUBBER JOINT

FLOW METER

QF, CONTROL PANEL FOR DUTY ELECTRIC PUMP


QF, CONTROL PANEL FOR DUTY DIESEL PUMP
QPD, CONTROL PANEL FOR JOCKEY PUMP
QAL, ALARMS CONTROL PANEL

STRAINER

FLOATING
TAP

PM

ECCENTRIC REDUCER

PUMP RUNNING
PRESSURE SWITCH

WATER TANK
SUPPLY

CONNECTIONS

PM
PM

M
M

HYDRAULIC PIPING LINE

POWER SUPPLY

ELEMENTS ON REQUEST

INSTALLATION BY CUSTOMER

NOTE: ONLY APPROXIMATE DRAWING

QF

POWER SUPPLY

QPD

QMTP

POWER SUPPLY

QAL

POWER SUPPLY
POWER SUPPLY

12845-GEN11D_STB-EN_B_SC

INTRODUCTION

GEN SERIES OF BOOSTER SETS


MECHANICAL CONFIGURA
TION
CONFIGURATION

DENOMINAZIONE COMPONENTI
GRUPPI DIESEL EN12845
REF.

1
2
3
4
5
6*
7
8
9

DESCRIPTION

REF.

electric service pump


diesel engine service pump
jockey pump discharge line
control panels
pump suction line
on-off valve on suction line
eccentric divergent
vacuum pressure gauge
anti-vibration joint

10
11
12
13
14
15
16
17
18

* Optional in case of positive suction head installation.

DESCRIPTION

divergent on discharge line


inspectable check valve
on-off valve on discharge line
pressure gauge
discharge manifold
service pump starter (2x)
diaphragm tanks
priming circuit tap
recirculation circuit tap
gen11d-comp-en_b_tp

CHARACTERISTIC
S OF THE PUMPS USED IN THE GEN SERIES
CHARACTERISTICS
OF BOOSTER SETS

INTRODUCTION

1SV ELECTRIC PUMPS (JOCKEY PUMP)


Multistage centrifugal vertical electric pumps. All
metal parts in contact with pumped liquid are made
of stainless steel.
Version F: round flanges, in-line discharge and
suction ports, AISI 304 (Standard version).
Version N: round flanges, in-line discharge and
suction ports, AISI 316 (Available on request).
Reduced axial thrusts enable the use of standard
motors that are easily found in the market.
Standard supplied IE2 three-phase surface
motors 0,75 kW are compliant with
Regulation (EC) no. 640/2009
640/2009.

Mechanical seal according to EN 12756 (ex DIN


24960) and ISO 3069.
Easy maintenance. No special tools required for
assembly or disassembly.
For other characteristics, consult the relative
dedicated technical catalogue.

FHF32, 40, 50, 65, 80, 100, 125 PUMP SERIES


Single impeller cast iron horizontal centrifugal pump and shaft made of AISI 316L stainless steel. End suction
and radial discharge ports.
Impeller: made of AISI 316L stainless steel laser technology welded, for sizes 32, 40, 50, 65-125, or cast iron for
sizes 65-160, 65-200, 65-250, 80, 100, 125.
Hydraulic sizes and nominal diameter DN of suction and discharge ports according to EN 733 (ex DIN 24255).
Flanges according to EN 1092-2 (ex UNI 2236) and DIN 2532.
Motor: motor/pump coupling with bracket, support, flexible coupling with spacer coupling and aligning and
anchoring base. Standard supplied IE2 three-phase surface motors 0,75 kW are compliant
with Regulation (EC) no. 640/2009 and IEC 60034-30.
Performance levels according to EN 60034-1.
Back pull out design, impeller, adaptor and motor can be extracted without disconnecting the pump body
from the pipes.
For other characteristics, consult the relative dedicated technical catalogue.

SHF32, 40, 50, 65, 80 PUMP SERIES


Single impeller horizontal centrifugal pump with pump body and shaft made of AISI 316L stainless steel. End
suction and radial discharge ports.
Closed impeller made of AISI 316L stainless steel laser technology welded (for sizes 25, 32, 40, 50, 65-160/75
and 65-160/110A) or AISI CF8M cast stainless steel.
Hydraulic sizes and nominal diameter DN of suction and discharge ports according to EN 733 (ex DIN 24255).
Flanges according to EN 1092-1 (ex UNI 2236) and DIN 2532.
Motor: motor/pump coupling with bracket, support, flexible coupling with spacer coupling and aligning and
anchoring base. Standard supplied IE2 three-phase surface motors 0,75 kW are compliant
with Regulation (EC) no. 640/2009 and IEC 60034-30.
Performance levels according to EN 60034-1.
Back pull out design, impeller, adaptor and motor can be extracted without disconnecting the pump body
from the pipes.
For other characteristics, consult the relative dedicated technical catalogue.

10

MAIN COMPONENTS

Diesel engine with coupling to service pump.


Electric panel for control of diesel engine pump and battery charger.
Diesel engine start circuit with two independent batteries.
Double engine starting relay.
Engine shut-off device from electric control (Electric stop).
Fuel tank for diesel engine equipped with float.
Base made of structural steel with epoxy powder painting RAL 5010.

The diesel engine pump is mounted on its own base complete with vibration-damping feet, and comes with a
wall-mounted electric panel fitted with 3-metre cables (5 metre length available on request), fuel tank with wall or
floor mounting depending on capacity, floor-mounted or on-board batteries. Special versions of additional diesel
fuel tank available on request.
A panel mounting bracket kit for floor mounting and a jockey pump kit can be supplied on request.
The installation of the diesel engine must provide for adequate ventilation and exhaust of combustion fumes.

FIRE-FIGHTING SETS WITH DIESEL ENGINE PUMP (GEN..00D)


FIRE-FIGHTING SETS WITH ELECTRIC PUMP AND DIESEL ENGINE
(GEN..D)
On/off valves on the delivery side of each pump, ball valves with lever handle for diameters up to and including
1" 1/2 butterfly valve with lever handle from DN50 to DN100 diameter, butterfly valve with handwheel and
reduction manual gear for DN125 diameter and above. Device for monitoring ON/OFF status included. Electrical
connections by customer.
(Lockable kit available on request).
Recirculation device for each service pump.
The re-circulation device allows a minimum capacity in order to prevent the pump overheating when working
with closed delivery. It includes the activation pressure switch for the alarms of the pumps running, the test valve
for checking the seal of the check valves, the couplings for any connecting pipes to the priming tank in the case
of suction lift installation. The connection of each re-circulation to the suction tank or the priming tank is to be
seen to by the person installing the equipment.
Pressure gauge on the delivery side of each service pump between check valve and on/off valve.
Inspectable check valve on the discharge side of each pump. Threaded coupling for diameters up to 1"1/2
included, flanged coupling for larger sizes.
Painted iron delivery manifold (PN 16) and threaded stubs with relative caps for connecting any 24 litre
membrane tanks. Blind and welding zinc-plated flanges.
Two start-up pressure switches for every service pump.
For the electric service pumps, start-up takes place through the pressure switch, but it must be manually stopped
using the key-operated selector switch on the panel (excluding the version with automatic shut-off). For the
electric jockey pump, if present, both start-up and stopping are determined by the pressure switch.
Start-up pressure switch circuit for the service pump, including connecting pipes for the delivery manifold,
recirculation circuit.
This circuit includes on/off valve, a non-return valve, a discharge valve and various pipe fittings. The
configuration of the circuit allows the pressure switch to intervene also when the relative on/off valve is closed.
Various pipe fittings (copper, zinc-plated steel).
Base made of bent sheet or structural iron with epoxy powder painting RAL 5010.
Control panel frame made of structural iron with epoxy powder painting RAL 5010.
Diesel engine with coupling to service pump.
Vibration-damping joints on discharge side.
Electric panel for control of diesel engine pump and battery charger.
Diesel engine start circuit with two independent batteries. Length of cable connecting the batteries to the
connection box 3 m.
Double engine starting relay.
Engine shut-off device from electric control (Electric stop).

11

INTRODUCTION

FIRE-FIGHTING DIESEL ENGINE PUMP (D..)

INTRODUCTION

Fuel tank for diesel engine. Special versions of additional diesel fuel tank available on request.
Electric panel for each electric service pump.
Starting: Direct (DOL) up to and including 22 kW, star/triangle from 30 kW up.
The diesel engine pump is mounted on its own base complete with vibration-damping feet, and comes with a
wall-mounted electric panel fitted with 3-metre cables (5 metre length available on request), fuel tank with wall or
floor mounting depending on capacity, floor-mounted or on-board batteries depending on size.
A panel mounting bracket kit for floor mounting and a jockey pump kit can be supplied on request.
The installation of the diesel engine must provide for adequate ventilation and exhaust of combustion fumes.
The control panels for the electric pumps up to 55 kW power supply are fixed on bracket. For higher powers, the
control panels for electric pump service are floor mounted, instead the jockey electric pump panel is wall mounted
fixed.
Sets featuring a single diesel engine pump plus jockey pump are equipped with electric jockey pump with 1 x 230V
single-phase power supply.

SUCTION KIT

The set is supplied with its suction side free from components.
On request, for the SUCTION side of the individual service pump, TWO versions are available according to the
systems installation type:

T KIT
POSITIVE SUCTION HEAD and SUCTION LIF
LIFT
Kit suitable for positive suction head or suction lift installation.
The suction side of the individual pump includes:
- Anti-vibration joint to attach to the pump inlet.
- Eccentric cone or flanged stub pipe.
- Vacuum pressure gauge.
- On/off butterfly valve (optional in case of positive suction head installation) with lever handle for diameters
up to DN100, butterfly valve with handwheel and reduction manual gear for DN125 and higher. Device for
monitoring ON/OFF status included. Electrical connections by customer.
(Valve lock kit available on request).
- Weld-on flange.
Conforming to the requirements of the EN 12845 Standard (chapter 10.5 and chapter 10.6).
These requirements are connected with the type of installation and the measurement of the piping sections.
(see tables on pages 140-143).
OTHER VERSIONS
As well as the basic GENDB versions (direct start-up), GENYB (star triangle start-up), GENIB (impedance start-up),
the following versions are also available:
GEN..A
With periodic self-test function.
There is a self-test circuit including a weekly clock on the electric panel of each electric service pump. For the time
and date pre-set, the pump is started up and kept functioning for 1 minute. During this interval the check circuit
checks that the pressure in the re-circulation circuit closes the pressure switch contact of the pump which is
running. In the case of irregularities, the relative auxiliary self-test alarm relay available for remote signalling is
activated and memorised.
The EN12845 Standard does not provide for the presence of a self-test circuit but asks for periodic checks to be
carried out by the user, hence the periodic self-test function cannot substitute the above checks.
GEN..X (For fire hydrant systems, UNI 10779)
With automatic shut-off.
There is an automatic shut-off circuit on the electric panel of each electric service pump.
In certain situations, it allows automatic shut-off once the system pressure has been kept at higher values than the
start-up values for at least twenty minutes.
The self-test and automatic shut-off versions are available for each type of GEND.., GENY.., GENI.. start-up and in
combination between them (See identification codes page).
12

Protection against dry running for the electric jockey pump in


one of the following versions:
- Float switch, in case of suction lift.
- Probes kit in case of suction lift (needs optional probe module
in the electric jockey pump).
- Minimum pressure switch, in case of positive suction head.
Electric panel for remote status and alarm monitoring of one or
two Lowara pumps installed in GEN fire-fighting booster sets,
according to EN12845.
In the electric service pump mode, the following conditions are
visualised: Motor powered, pump start-up request, pump
running, failure to start.
In the diesel engine service pump mode, the following
conditions are visualised: switch in non-automatic position,
QAL12845 Panel
diesel engine fails to start after 6 attempts, pump running,
controller failure.
Additionally: minimum suction tank or fuel level, minimum
priming tank level, on-off valve on suction and discharge side
not fully open.
All the above conditions, required by EN12845, are visualised
with signal LEDs and buzzers.
A buzzer alarm reset button and LED tester button are
included.
The control unit is also fitted out to signal the following
general alarms, if present:
- General alarm for incorrect electrical connection in the
exchange contacts of: flow meter circuit valve, discharge
pump, jockey pump status.
- Fault in electrical connection in the exchange contact relative
to panel 1 (electric pump/diesel engine pump).
Flow meter
- Fault in electrical connection in the exchange contact relative
to panel 2 (electric pump/diesel engine pump).
- Jockey pump overload; - Jockey pump running; - Discharge pump overload;
- Battery low; - No communication with ModBus system.
All the above conditions are visualised with signal LEDs and on the display. The customer may decide to enable
the buzzer. Further information available on page 144.
Circuit for test flow of the service pumps. Includes the direct reading flow meter (sized according to the capacity
of the service pump) according to the type of flow meter, connecting piping and straight piping upline from the
instrument, on/off ball valve for diameters up to and including 2 butterfly valve with lever handle from DN65 to
DN100 diameter, butterfly valve with handwheel and reduction manual gear for DN125 diameter and above.
ON/OFF status monitoring included.
New model of flow meter (P6) for diameters up to and including DN80.
Diaphragm tank with relative ball valve, in the same number as that of the pumps present, for dampening any
pressure oscillations in the system. 24 litre model with maximum pressure 8, 10 and 16 bar or 20 litre model
with maximum pressure 25 bar according to the maximum head of the pumps.
Priming tank for each service pump, in the case of suction lift installation.
Accessories for the priming tank suck as float switch tap, level indicator, valves, automatic air discharger on each
service pump, in the case of suction lift installation.

All the main characteristics of the priming tanks, the flow meters and the available membrane tanks are shown in
the accessories section.

13

INTRODUCTION

ACCES
SORIES A
VAILABLE ON REQUEST
ACCESSORIES
AV

SPECIAL EQUIPMENT ON REQUEST


(Contact the Sales and technical Assistance Service)

INTRODUCTION

Sets for pumping sea water with electric pumps, valves, manifold and AISI 316 piping or compatible alloys.
Non-standard supply power sets.
Sets with two diesel engine service pumps. (See page 15).
Sets with separate electric jockey pump supplied as a kit.
Sets installed inside prefabricated boxes for outdoor use.
Sets with oversized fuel tank.
Sets with diesel engine pump with compressed air start system.
Diesel engine pump with ambient air cooling device.
Notes
The set is supplied without a suction manifold in accordance with the EN12845 Standard (points 10.6.2.2 and
10.6.2.3) which provides for independent suction for each pump.
Please see the EN12845 Standard on fixed systems and fire extinguishing Automatic sprinkler systems Design,
installation and maintenance?- for sizing the suction piping, define whether the installation is to be considered
suction lift or positive suction head for the use limits.
The Standard ask that, whenever possible, the pumps are installed with positive suction head, otherwise priming
tanks must be provided with suitable automatic devices for signalling and reintegration.
The EN12845 Standard states that the water pressure should not exceed 12 bar (point 8.2.1). In some applications
it is possible to have pressures of over 12 bar (point 8.2.2).
In this case, pump sets with higher pressures than those within the regulatory limit are used.
The catalogue also shows booster sets with pump closing head up to 150 metres suitable for such installations.

14

INTRODUCTION

SPECIAL EQUIPMENT ON REQUEST

15

COMMAND P
ANEL FOR THE ELECTRIC SERVICE PUMP
PANEL

INTRODUCTION

Painted metal casing (IP 54) complete with:


General door-locking switch.
Analogical ammeter.
MAN AUT 0 selector with extractable key only in
automatic position.
Keyboard for indicating electric voltage presence,
correct phase sequence (three phase power supply),
start-up request, pump functioning and no start-up,
through LED lamps, lamp test button and starting and
stopping buttons, according to the provisions of
EN12845 paragraph 10.8.6.
Inside:
12/24V transformer for auxiliary circuits and electronic
board.
Fuse holder and fuses for power and auxiliary circuits.
Line contact maker (direct start-up up to 22 kW
included), line and star/triangle contact makers (startriangle start-up), line contact makers and reactance
switching (impedance start-up).
Star/triangle exchanger timer or reactance switching.
Relay for signalling no phase.
Auxiliary relays.
Current transformer.
Terminal boards.
Clean contacts (max. 24V, 1A) for activating acoustic/
visual alarms for no phase, pump on demand, pump
running and start failure.
Cable glands (excluding the versions to be fixed to the
floor).
Wiring diagram.

16

Electric service pump panel

COMMAND P
ANEL FOR THE ELECTRIC JOCKEY PUMP
PANEL
Painted metal casing (IP 55) complete with:

INTRODUCTION

General door-locking switch.


Visual indicators for line, running, thermal shutdown.
Manual automatic selector excluded.
Inside:
Transformer for 24V auxiliary circuits.
Fuse holder and fuses for power and auxiliary circuits.
Line contact maker.
Overload cut-out switch.
Pump shut-off timer (0 90 s).
Terminal boards.
Cable glands.
Wiring diagram.
Suitable for connecting to a float switch or a minimum
pressure switch for preventing dry running. An optional
level control module (supplied on request) allows the
connection of probes with the possibility of regulating the
sensitivity according to the hardness of the water.

Electric jockey pump panel

OPTIONS A
VAILABLE ON REQUEST
AV
CP alternative
Series of clean contacts for checking the status of the electric service pump panel, as well as the contacts already
provided for signalling alarms:
No phase
Motor running
Selector position MAN-AUT-0
No start-up
Start-up request
Series of clean contacts for checking the status of the electric jockey pump:
Pump running
Thermal shutdown (overload)
No water
KV alternative
Control panel for the electric service pump with analogical voltmeter and with phase switch.
IP55 alternative
Electric service pump panel with extra IP55 protection.

17

COMMAND P
ANEL FOR DIESEL ENGINE PUMP
PANEL

INTRODUCTION

Painted metal casing (IP 54) complete with:


Electronic control and management unit for the diesel
engine. Display of alarms and status, battery voltage,
speedometer, hour counter, alarm programming, date
display, main signals and manual start button.
Man-Auto-0 selector switch with key removable only in
the auto position.
Pair of emergency battery start buttons.
General door-locking switch.
Inside:
Fuse holder and fuses for power and auxiliary circuits.
Pair of battery chargers 12Vdc/24Vdc.
Control unit for management of diesel engine and
alarms.
Auxiliary relays.
Power circuits for engine heaters.
Terminal boards.
RS232 connector for communication port.
Cable glands.
Wiring diagram.

Diesel engine pump panel

The panel is supplied standard with clean alarm signal


contacts (max. 1A,30Vdc/125Vac/277Vac):
Non-automatic operating mode.
Controller fault.
Motor running.
Failure to start.
General alarm.
Single-phase 1x230V standard power supply.

OPTIONS A
VAILABLE ON REQUEST
AV
IP55 alternative
Diesel engine service pump panel with additional IP55 protection.

The set is supplied already assembled, calibrated and factory tested. The set is supplied
complete with an instruction manual, pump manuals and wiring diagrams for the panels.
For the sets including floor panels, the electric panels are sent together with the set in a separate pack and
supplied with 5-metre long connecting cables (longer lengths available on request). The fitter is responsible for
preparing the routes and installing the cables.

18

COMMAND P
ANEL DIMENSIONS
PANEL

POWER (kW)

PROTECTION

CLASS
from 0,7 to 7,5

IP54

350

160

500

from 9,2 to 22

IP54

400

200

600

from 30 to 37

IP54

500

200

700

from 45 to 55

IP54

600

250

800

from 75 to 90

IP54

600

300

1500

from 110 to 160

IP54

800

400

1700

IP55: same dimensions as standard panels IP54

qe-serv-en_d_td

Power over 55 kW: floor cupboard

JOCKEY PUMP P
ANEL
PANEL

PROTECTION
CLASS

IP54

250

160

IP55: same dimensions as standard panels IP54

H
300
qe-pil-en_b_td

ENGINE PUMP P
ANEL
PANEL

PROTECTION
CLASS

IP54

350

200

IP55: same dimensions as standard panels IP54

* The control panels are included in the supply.

19

H
500
qe-mtp12845_en_b_td

INTRODUCTION

SERVICE PUMP P
ANEL
PANEL

INTRODUCTION

EN 12845 DIESEL ENGINE PUMP T


ANKS
TANKS
DIMENSIONS AND CAP
ACITY
CAPACITY

VOLUME (litres)

TYPE

30

260

280

550

65

380

330

550

90

420

420

1200

130

420

420

1450

190

540

550

1340

240

570

570

1400

2
serb-mtp-en_b_td

Note: Special versions of additional diesel fuel tank available on request.

20

PUMP
FHF32-125/D119
FHF32-125/D136
FHF32-160/D150
FHF32-160/D164
FHF32-200/D188
FHF32-200/D204
FHF40-125/D112
FHF40-125/D122
FHF40-125/D143
FHF40-160/D159
FHF40-160/D171
FHF40-200/D190
FHF40-200/D209
FHF40-250/D218
FHF40-250/D233
FHF40-250/D251
FHF50-125/D119
FHF50-125/D130
FHF50-125/D139
FHF50-160/D158
FHF50-160/D174
FHF50-200/D197
FHF50-200/D209
FHF50-250/D224
FHF50-250/D237
FHF50-250/D250
FHF65-125/D121
FHF65-125/D129
FHF65-125/D140
FHF65-160/D161
FHF65-160/D168
FHF65-160/D178
FHF65-200/D187
FHF65-200/D198
FHF65-200/D210
FHF65-250/D220
FHF65-250/D241
FHF65-250/D258
FHF80-160/D163
FHF80-160/D173
FHF80-200/D189
FHF80-200/D207
FHF80-250/D225
FHF80-250/D238
FHF80-250/D256

CAPACITY' (l)
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
65
65
30
30
30
30
30
30
30
65
65
65
65
90
30
65
65
65
90
90
130

D..

GEN..00D

GEN..01D

GEN..10D

GEN..11D

WALL MOUNTED

WALL MOUNTED

ON BOARD

ON BOARD

ON BOARD

WALL MOUNTED

WALL MOUNTED

ON BOARD

ON BOARD

ON BOARD

WALL MOUNTED

WALL MOUNTED

ON BOARD

ON BOARD

ON BOARD

WALL MOUNTED

WALL MOUNTED

ON BOARD

ON BOARD

ON BOARD

FLOOR-MOUNTED

FLOOR-MOUNTED

FLOOR-MOUNTED

FLOOR-MOUNTED

FLOOR-MOUNTED

WALL MOUNTED

WALL MOUNTED

ON BOARD

ON BOARD

ON BOARD

FLOOR-MOUNTED

FLOOR-MOUNTED

FLOOR-MOUNTED

FLOOR-MOUNTED

FLOOR-MOUNTED

pos-serb-fhf12845-en_c_td

21

INTRODUCTION

EN 12845 DIESEL ENGINE PUMP T


ANKS
TANKS
COMBINA
TIONS AND POSITIONING
COMBINATIONS

EN 12845 DIESEL ENGINE PUMP T


ANKS
TANKS
COMBINA
TIONS AND POSITIONING
COMBINATIONS

INTRODUCTION

PUMP

CAPACITY' (l)

FHF100-160/D150

30

FHF100-160/D165

65

FHF100-160/D185

65

FHF100-200/D168

65

FHF100-200/D192

65

FHF100-200/D203

90

FHF100-200/D213

90

FHF100-250/D200

65

FHF100-250/D221

90

FHF100-250/D235

130

FHF100-250/D254

190

FHF100-250/D267

190

FHF125-200/D180

65

FHF125-200/D206

90

FHF125-200/D216

130

FHF125-270/D224

190

FHF125-270/D237

190

FHF125-270/D253

240

FHF125-270/D266

240

D..

GEN..00D

GEN..01D

GEN..11D

WALL MOUNTED

WALL MOUNTED

ON BOARD

ON BOARD

FLOOR-MOUNTED

FLOOR-MOUNTED

FLOOR-MOUNTED

FLOOR-MOUNTED

WALL MOUNTED

WALL MOUNTED

ON BOARD

ON BOARD

FLOOR-MOUNTED

FLOOR-MOUNTED

FLOOR-MOUNTED

FLOOR-MOUNTED

WALL MOUNTED

WALL MOUNTED

ON BOARD

ON BOARD

FLOOR-MOUNTED

FLOOR-MOUNTED

FLOOR-MOUNTED

FLOOR-MOUNTED

pos-serb-fhf100-12845-en_c_td

22

PUMP
SHF32-125/D121
SHF32-125/D136
SHF32-160/D150
SHF32-160/D168
SHF32-200/D188
SHF32-200/D204
SHF32-250/D222
SHF32-250/D242
SHF32-250/D256
SHF40-125/D112
SHF40-125/D126
SHF40-125/D143
SHF40-160/D159
SHF40-160/D171
SHF40-200/D190
SHF40-200/D209
SHF40-250/D218
SHF40-250/D233
SHF40-250/D251
SHF50-125/D119
SHF50-125/D130
SHF50-125/D139
SHF50-160/D158
SHF50-160/D174
SHF50-200/D197
SHF50-200/D209
SHF50-250/D224
SHF50-250/D237
SHF50-250/D250
SHF65-160/D119
SHF65-160/D129
SHF65-160/D137
SHF65-160/D168
SHF65-160/D177
SHF65-200/D192
SHF65-200/D203
SHF65-200/D215
SHF65-250/D240
SHF65-250/D255
SHF80-160/D169
SHF80-160/D177
SHF80-160/D186
SHF80-200/D198
SHF80-200/D215
SHF80-200/D226
SHF80-250/D237
SHF80-250/D252
SHF80-250/D270

CAPACITY' (l)
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
65
65
30
30
30
30
30
30
65
65
65
90
30
30
65
65
65
90
90
130
190

D..

GEN..00D

GEN..01D

GEN..10D

GEN..11D

WALL MOUNTED

WALL MOUNTED

ON BOARD

ON BOARD

ON BOARD

WALL MOUNTED

WALL MOUNTED

ON BOARD

ON BOARD

ON BOARD

WALL MOUNTED

WALL MOUNTED

ON BOARD

ON BOARD

ON BOARD

WALL MOUNTED

WALL MOUNTED

ON BOARD

ON BOARD

ON BOARD

FLOOR-MOUNTED

FLOOR-MOUNTED

FLOOR-MOUNTED

FLOOR-MOUNTED

FLOOR-MOUNTED

WALL MOUNTED

WALL MOUNTED

ON BOARD

ON BOARD

ON BOARD

FLOOR-MOUNTED

FLOOR-MOUNTED

FLOOR-MOUNTED

FLOOR-MOUNTED

FLOOR-MOUNTED

pos-serb-shf12845-en_c_td

23

INTRODUCTION

EN 12845 DIESEL ENGINE PUMP T


ANKS
TANKS
COMBINA
TIONS AND POSITIONING
COMBINATIONS

INTRODUCTION

ST
ARTING BA
T TERIES FOR DIESEL ENGINE PUMP EN 12845
STARTING
BAT
COMBINA
TIONS AND SIZES
COMBINATIONS

TABELLA ABBINAMENTI POMPA SERVIZIO FH32-125 - BATTERIA AVVIAM. MTP GR

TABLE OF DIESEL ENGINE PUMP FHF 32-125 COMBINA


TIONS
COMBINATIONS
DIESEL

BATTERY

DIESEL

BATTERY

ENGINE PUMP

TYPE

ENGINE PUMP

TYPE

TYPE
DFHFE..

TYPE
DFHFE..

PUMP

PUMP

32-125/D119

65-200/D187

32-125/D136

65-200/D198

32-160/D150

65-200/D210

32-160/D164

65-250/D220

32-200/D188

65-250/D241

32-200/D204

65-250/D258

40-125/D112

80-160/D163

40-125/D122

80-160/D173

40-125/D143

80-200/D189

40-160/D159

80-200/D207

40-160/D171

80-250/D225

80-250/D238

40-200/D190

40-200/D209

40-250/D218

80-250/D256

100-160/D150

40-250/D233

100-160/D165

40-250/D251

100-160/D185

50-125/D119

100-200/D168

50-125/D130

100-200/D192

50-125/D139

100-200/D203

100-200/D213

50-160/D158

50-160/D174

50-200/D197

100-250/D200

100-250/D221

50-200/D209

100-250/D235

50-250/D224

100-250/D254

50-250/D237

100-250/D267

50-250/D250

125-200/D180

125-200/D206

65-125/D121
65-125/D129

125-200/D216

65-125/D140

125-270/D224

65-160/D161

125-270/D237

65-160/D168

125-270/D253

65-160/D178

125-270/D266

12845-FHF32-125_ab-en_a_tc

24

ST
ARTING BA
T TERIES FOR DIESEL ENGINE PUMP EN 12845
STARTING
BAT
TABELLA ABBINAMENTI POMPA SERVIZIO SH32-80 - BATTERIA AVVIAM. MTP GRU
TABLE OF DIESEL ENGINE PUMP SHF 32-80 COMBINA
TIONS
COMBINATIONS
DIESEL

BATTERY

ENGINE PUMP

TYPE

TYPE
A

INTRODUCTION

DSHFE..
PUMP
32-125/D121

32-125/D136

32-160/D150

32-160/D168

32-200/D188

32-200/D204

32-250/D222

32-250/D242

32-250/D256

40-125/D112

40-125/D126

40-125/D143

40-160/D159

40-160/D171

40-200/D190

40-200/D209

40-250/D218

40-250/D233

40-250/D251

50-125/D119

50-125/D130

50-125/D139

50-160/D158

50-160/D174

50-200/D197

50-200/D209

50-250/D224

50-250/D237

50-250/D250
65-160/D119
65-160/D129

65-160/D137

65-160/D168

65-160/D177

65-200/D192

65-200/D203

65-200/D215

65-250/D240

65-250/D255

80-160/D169

80-160/D177

80-160/D186

80-200/D198

80-200/D215

80-200/D226

80-250/D237

80-250/D252

80-250/D270

12845-SHF32-80_ab-en_a_tc

25

GEN SERIES OF BOOSTER SETS


CHOICE AND SELECTION

INTRODUCTION

Criteria for choosing fire-fighting sets


The correct choice of a fire-fighting set must consider various factors, including the correct sizing of the performance
levels required for the system, local regulations and legislation, and especially the installation conditions relative to
the installation site and whether a suction lift or a positive suction head is involved.
Choosing the type of water supply
The type of water supply and, therefore, the type of booster set to select depends on the type of system involved and
is chosen according to the risk analysis performed by the designer.
There is no written rule for identifying the correct number of pumps to install.
GEN booster sets are normally designed so that every service pump can satisfy the following requirements:
100% of rated capacity with one or two pumps installed (one in service and the other in reserve).
If three pumps are installed, the capacity of the pump will be 50% of the total rated capacity and the third service
pump will be considered as a reserve. In these cases, when superior or duplicated water supplies are involved, only
one pump must be driven by an electric motor. This type of configuration is available on request.
Suction conditions of the booster set
The type of installation, suction lift or positive suction head, tends to affect (negatively or positively) the hydraulic
performance of the pump. Remembering that EN12845 recommends against using suction lift installations, the
following condition given by EN12845 must be satisfied in order to use the pump curve correctly:
NPSHd NPSHr +1 [m]
Where: NPSHd is defined available.
NPSHr is defined requested from the pump.
As the suction check condition must be made at the max. requested flow, there can be different performance levels
always respecting the NPSHd condition.
To select the booster set, consult the dedicated sections. Choice and selection. Hydraulic performance levels. Suction
lift or positive suction head installation.
Performance levels of booster sets: using the tables
The tables showing the hydraulic performance levels of booster sets indicate the flow values according to the risk
class for precalculated systems followed by the respective pressure value. This value does not refer to pump performance
but is net of the pressure drop on the pump discharge line, to the discharge manifold flange.
This field is shown in grey and the selection must be made here, where performance levels comply with the reference
standard which considers the following conditions:
Maximum water speed in the service pump discharge piping 6 m/sec.
NPSHd NPSHr + 1 at the maximum flow required.
Max. difference in level of water considered 3,2 m (for positive suction head).
Suction pressure drops due to valves, piping, suction kit 1,5 m (limit value).
The reference suction conditions are the severest and most extreme that can occur.
The values taken in the fields that are not in grey indicate booster set performance levels in areas outside the limits of
the standard and must not be used to choose the set.

26

GEN SERIES OF BOOSTER SETS


CHOICE AND SELECTION

Referring to EN 12845, after identifying the risk classes of the activity to protect and performing the precalculation
method, the flow and head values required for the fire-fighting system can be obtained.
This data is used as follows:
1. Configuration of the booster set, choice of the number of service pumps and relative type of motor/engine
(two pumps, one electric and the other driven by a diesel engine).
2. Installation conditions (e.g.. positive suction head), see performance levels for positive suction head installation.
3. Determination of service flow e.g.: 1100 l/min risk class OH3.
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE FHF50 2 poli 50 Hz 1 POMPA DI SERVIZIO, INST SOPRAB

RATED

FHF..

POWER

ELECTRIC

PUMP

PUMP

OH3n

TYPE

OH2n

RISK CLASS

Q = DELIVERY
l/min 0

600

700

m3/h 0

36

42

725

850

1000

1100

1200

1300

1350

1400

1500

1600

44

51

60

66

72

78

81

84

90

96

H = TOTAL HEAD METRES COLUMN OF WATER

kW

11,8

3,7

15,8

8,0

4. Determining
the
head e.g.:
35GRUPPI
m. EN12845 SERIE20,2
TABELLA
DI PRESTAZIONI
IDRAULICHE
NETTE
FHF50 2 poli 50 Hz 1 13,1
POMPA DI SERVIZIO, INST SOPRAB
27,3

18,2

34,8

FHF..

POWER

ELECTRIC

PUMP

PUMP

42,8

31,2

49,9

38,6

OH3n

RATED

OH2n

TYPE

RISK 26,5
CLASS

60,4
69,5

48,8

Q = DELIVERY

58,8

l/min 0

600

700

725

850

1000

1100

1200

1300

1350

1400

1500

1600

m3/h 0

36

42

44

51

60

66

72

78

81

84

90

96

79,0

68,1

H = TOTAL HEAD METRES COLUMN OF WATER

kW

50-125/22

50-125/D119

1 x 2,2

16,8

13,7

12,3

11,8

9,5

6,2

3,7

0,9

50-125/30

50-125/D130

1x3

19,9

17,5

16,1

15,8

13,6

10,5

8,0

5,3

2,3

50-125/40

50-125/D139

1x4

24,3

21,8

20,6

20,2

18,3

15,3

13,1

10,5

7,7

6,2

4,6

50-160/55

50-160/D158

1 x 5,5

31,8

29,3

27,7

27,3

24,8

21,1

18,2

15,0

11,4

9,5

7,6

50-160/75

50-160/D174

1 x 7,5

39,8

36,6

35,2

34,8

32,5

29,1

26,5

23,5

20,2

18,5

16,7

50-200/110A 50-200/D197

1 x 11

50,6

45,6

43,4

42,8

39,5

34,8

31,2

27,3

23,1

20,9

18,6

50-200/110

1 x 11

58,0

52,6

50,5

49,9

46,7

42,1

38,6

34,7

30,4

28,1

25,7

50-200/D209

60,4

48,8

69,5

58,8

12,7
20,7

As can be seen, the required flow value enters the operating


area in accordance
with the standard, and the value of
79,0
68,1
the corresponding head enters the field in grey.
From the example shown above, we can identify the booster set that satisfies the request. The model is pump
50-200/110 providing a head of 38,6 m.

27

INTRODUCTION

Method of selecting a fire-fighting booster set

GEN SERIES OF BOOSTER SETS


CHOICE AND SELECTION - POSITIVE SUCTION HEAD INST
ALLA
TION
INSTALLA
ALLATION

INTRODUCTION

EN12845 recommends always installing pumps in suction lift conditions, where possible If this is not possible, the
pumps can be installed in positive suction head conditions according to the following rules:
The height of the minimum water level at the pump axis must not be greater than 3,2 m.
A foot valve must be installed in the lowest point of the suction piping.
If more than one pump is installed, the suction piping must not be interconnected.
optional

Liv. normale
Normal
level

Max 3,2 m

Liv.level
Min XX
Min.

Fig. 1 positive suction head installation diagram


In accordance with EN 12845 (10.6.2.1), the suction piping, including all the valves and unions, must be designed to
ensure that the NPSH available at the pump inlet exceeds the required NPSH by at least 1 m at the maximum required
flow rate.
NPSHd NPSHr + 1
When selecting the type of pump to use for the boosters sets, the installation conditions must be considered as these
determine different pump performance levels.
An example of how to choose and check of the installation conditions is shown below:
considering the precalculation method, a suitable risk class for the system is identified, e.g.: OH3. For this risk class,
the rated flow is 1100 l/min (Qn), while the maximum requested flow is 1350 l/min (Qm). Being in a positive suction
head condition, the most difficult situation is considered, i.e.: the maximum difference in water level of 3,2 m, as
indicated in the standard.
Being aware of the rated flow 1100 l/min and the pressure required for the system (e.g.: 35 m), the pump is
selected according to the tables on page 44-45, making sure the performance rating lies inside the area shown in
grey. The pump that satisfies the required work point is FHF50-200/110.

28

GEN SERIES OF BOOSTER SETS


CHOICE AND SELECTION - POSITIVE SUCTION HEAD INST
ALLA
TION
INSTALLA
ALLATION

The following values are replaced in the known relation, NPSHd NPSHr + 1:
NPSHr can be deduced from the table on page 45 which in this case is 4,6 m at the maximum requested flow.
After replacing the value, the following will be true (water temperature around 15C):
NPSHd = 10,33 + (-3,2) - Hct
Where
10,33 atmospheric pressure
3,2 geodetic difference in level
Hct suction pressure drop ((valves, pipes, elbows..)
The value of Hct considers the pressure drops of the suction kit, inclusive of vibration-proof joint, reduction cone
and on-off valve (Hc), as well as the pressure drops relative to all the suction piping, foot valve, elbows, elbows,
etc...
The value of Hc at the maximum required flow of the selected pump can be found in the diagram on page 81.
This value is 0,16 m.
After entering it in the formula, we will have:
Hct = 0,16 + X
Where X is the pressure drop relative to all the suction piping
Hence
NPSHd NPSHr + 1. After replacing this, we will have:
10,33 + (-3,2) - Hct = 4,6 +1
10,33 + (-3,2) 0,16 - X = 4,6 +1 which gives
X = 1,37 m
Maximum value of total drops to consider on the inlet piping in order to respect the conditions of the standard.
Of course, this case was deliberately put in the worst suction conditions. The designer must check and set the
values in an attempt to optimise suction conditions.

29

INTRODUCTION

At this point, the installation conditions (positive suction head) must be checked at the maximum required
flow.
flow

GEN SERIES OF BOOSTER SETS


CHOICE AND SELECTION - POSITIVE SUCTION HEAD INST
ALLA
TION
INSTALLA
ALLATION

INTRODUCTION

Checking performance of the set at rated flow


flow..
The performance of the booster set must now be checked in the installation conditions of the example used up
until now.
Work point: Qn: 1100 l/min H = 35 m
The selected pump is FHF50-200/110
Starting from the usual relation given by the standard, we will have:
NPSHd NPSHr + 1
NPSHd = 10,33 + (-3,2) - Hct
NPSHr can be deduced from the table on page 45 which in this case is 2,9 m at the rated flow.
The value of Hct considers the pressure drops of the suction kit, inclusive of vibration-proof joint, reduction cone
and on-off valve (Hc), as well as the pressure drops relative to all the suction piping, foot valve, elbows, elbows,
etc...
The value of Hc at the rated required flow of the selected pump can be found in the diagram on page 81. This
value is 0,12 m.
After entering it in the formula, we will have:
Hct = 0,12 + X
Where X is the pressure drop relative to all the suction piping
Hence
NPSHd NPSHr + 1. After replacing this, we will have:
10,33 + (-3,2) - Hct = 2,9 +1
10,33 + (-3,2) 0,12 - X = 2,9 +1 which gives
X = 3,11 m
Value of the total drops to consider on the suction piping
Taking the pressure value of the selected set, the value corresponds to 38,6 m at the rated flow.
Therefore, the verification of the pressure values in the above suction conditions becomes:
H = 38,6 -0,12 -3,11 = 35,4 m > 35 m which is the pressure required for the system
The result satisfies the performance required for the system in the installation conditions of the example.

30

GEN SERIES OF BOOSTER SETS


CHOICE AND SELECTION - SUCTION LIF
T INST
ALLA
TION
LIFT
INSTALLA
ALLATION

EN12845 recommends always installing pumps in suction lift conditions, where possible, according to the following
rules:
At least two thirds of the effective capacity of the suction tank must be above the level of the pump axis.
The pump axis must not be more than 2 m above the minimum water level in the suction tank.

Normal
level
Liv.
normale

2/3
2/3 della
of
capacit
effective
effettiva
capacity

Max 2 m
Min. Min
levelXX
Liv.

Fig. 2 suction lift installation diagram


In accordance with EN 12845 (10.6.2.1), the suction piping, including all the valves and unions, must be designed to
ensure that the NPSH available at the pump inlet exceeds the required NPSH by at least 1 m at the maximum required
flow rate.
NPSHd NPSHr + 1
When selecting the type of pump to use for the boosters sets, the installation conditions must be considered as these
determine different pump performance levels.
An example of how to choose and check of the installation conditions is shown below:
considering the precalculation method, a suitable risk class for the system is identified, e.g.: OH3. For this risk class,
the rated flow is 1100 l/min (Qn), while the maximum requested flow is 1350 l/min (Qm). Being in the suction lift
condition, a neutral situation is used in order to consider the water level on the same horizontal plane as the pump,
without benefiting from any positive suction head.

31

INTRODUCTION

Suction lift installation

GEN SERIES OF BOOSTER SETS


CHOICE AND SELECTION - SUCTION LIF
T INST
ALLA
TION
LIFT
INSTALLA
ALLATION

INTRODUCTION

Being aware of the rated flow 1100 l/min and the pressure required for the system (e.g.: 35 m), the pump is selected
according to the tables on page 44-45, making sure the performance rating lies inside the area shown in grey.
The pump that satisfies the required work point is FHF50-200/110.
At this point, the installation conditions (suction lift) must be checked at the maximum required flow.
The following values are replaced in the known relation, NPSHd NPSHr + 1:
NPSHr can be deduced from the table on page 45 which in this case is 4,6 m at the maximum requested flow.
After replacing the value, the following will be true (water temperature around 15C):
NPSHd = 10,33 + (0) - Hct
Where
10,33 atmospheric pressure
0 geodetic difference in level
Hct suction pressure drop (valves, pipes, elbows...)
The value of Hct considers the pressure drops of the suction kit, inclusive of vibration-proof joint, reduction cone
and on-off valve (Hc), as well as the pressure drops relative to all the suction piping, foot valve, elbows, elbows, etc
The value of Hc at the maximum required flow of the selected pump can be found in the diagram on page 87.
This value is 0,32 m.
After entering it in the formula, we will have:
Hct = 0,32 + X
Where X is the pressure drop relative to all the suction piping
Hence
NPSHd NPSHr + 1. After replacing this, we will have:
10,33 + (0) - Hct = 4,6 +1
10,33 + (0) 0,32 - X = 4,6 +1 which gives
X = 4,41 m
Maximum value of total drops to consider on the inlet piping in order to respect the conditions of the standard.
Of course, the case in point was deliberately tested in neutral suction conditions that neither benefit nor optimise
suction.
The designer must check and set the values in an attempt to make suction conditions as efficient as possible.

32

GEN SERIES OF BOOSTER SETS


CHOICE AND SELECTION - SUCTION LIF
T INST
ALLA
TION
LIFT
INSTALLA
ALLATION

The performance of the booster set must now be checked in the installation conditions of the example used up until
now.
Work point: Qn 1100 l/min H = 35 m
The selected pump is FHF50-200/110
Starting from the usual relation given by the standard, we will have:
NPSHd NPSHr + 1
NPSHd = 10,33 + (0) - Hct
NPSHr can be deduced from the table on page 45 which in this case is 2,9 m at the rated flow
flow.
The value of Hct considers the pressure drops of the suction kit, inclusive of vibration-proof joint, reduction cone
and on-off valve (Hc), as well as the pressure drops relative to all the suction piping, foot valve, elbows, elbows, etc...
The value of Hc at the rated required flow of the selected pump can be found in the diagram on page 87. This value
is 0,22 m.
After entering it in the formula, we will have:
Hct = 0,22 + X
Where X is the pressure drop relative to all the suction piping
Hence
NPSHd NPSHr + 1. After replacing this, we will have:
10,33 + (0) - Hct = 2,9 +1
10,33 + (0) 0,22 - X = 2,9 +1 which gives
X = 6,21 m
Value of the total drops to consider on the suction piping
Taking the pressure value of the selected set, the value corresponds to 38,6 m at the rated flow.
Therefore, the verification of the pressure values in the above suction conditions becomes:
H = 38,6 -0,22 -6,21 = 32,17 m < 35 m which is the pressure required for the system.
The value obtained, doesnt satisfy the performance necessary for the system, but as is evident, we have used deliberately
a neutral installation condition that it doesnt give benefits to the suction. It results that installed the pump with
positive suction of 3 m, we will have a pressure value of 35,17 m that it satisfied the relation.

33

INTRODUCTION

Checking performance of the selected set at rated flow


flow..

34

INTRODUCTION

GEN..D/FHF Series

GEN..D/FHF

Fire-fighting booster sets EN 12845,


electric pumps FHF series with high efficiency
motors and diesel engine pumps
50 Hz

35

36

GEN..D/FHF

RANGE
GEN..D/FHF RANGE
The range of EN 12845 fire-fighting booster sets with diesel and
electric service pumps and optional jockey pump to adapt to the
specific needs of every application.

D.. ENGINE PUMP

Head up to 100 m.
Flow up to 650 m3/h.

GEN..00D SERIES

Fire-fighting sets with diesel engine


centrifugal service pump, in
horizontal design with cast iron
casing, FHF series.

Head up to 100 m.
Flow up to 650 m3/h.

GEN..01D SERIES

Fire-fighting sets with diesel engine


service pump and electric jockey
pump. The centrifugal service pump
has horizontal design and cast iron
casing. FHF series.

Head up to 100 m.
Flow up to 650 m3/h.

GEN..10D SERIES

Fire-fighting sets with diesel engine


service pump and electric jockey
pump. The centrifugal service pump
has horizontal design and cast iron
casing. FHF series.

Head up to 100 m.
Flow up to 1300 m3/h.

GEN..11D SERIES

Fire-fighting sets with diesel engine


service pump, electric service pump
and electric jockey pump. The
centrifugal service pump has
horizontal design and cast iron
casing. FHF series.

37

Head up to 100 m.
Flow up to 1300 m3/h.

GEN..D/FHF

Single fire-fighting centrifugal


pump in horizontal design with
cast iron casing, FHF series.

GEN..D/FHF BOOSTER SETS SERIES


TABELLA DI PRESTAZIONI IDRAULICHE SERIE 1SV 3SV 5SV 2p 50 Hz
HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 Hz (JOCKEY PUMP)
HYDRAULIC
TABLE
AT
PUMP

NOMINAL

TYPE

POWER

Q = DELIVERY
l/min 0

12

20

25

30

35

40

m /h 0

0,7

1,2

1,5

1,8

2,1

2,4

12,2
18,0
23,7
29,3
34,8
40,2
48,1
53,7
59,4
65,1
73,3
79,2
90,9
105,2
117,0
134,6
152,6

12,2
18,0
23,5
28,9
34,2
39,2
47,9
53,4
59,0
64,5
73,1
78,9
90,5
104,9
116,7
134,1
152,4

7,9
11,4
14,6
17,4
20,0
22,2
30,4
33,5
36,6
39,5
47,6
51,2
58,1
68,6
75,8
86,1
99,1

6,0
8,4
10,6
12,5
14,0
15,2
22,4
24,6
26,6
28,5
35,7
38,2
43,1
51,2
56,3
63,5
72,7

GEN..D/FHF

1SV 02
1SV 03
1SV 04
1SV 05
1SV 06
1SV 07
1SV 08
1SV 09
1SV 10
1SV 11
1SV 12
1SV 13
1SV 15
1SV 17
1SV 19
1SV 22
1SV 25

kW

HP

0,37
0,37
0,37
0,37
0,37
0,37
0,55
0,55
0,55
0,55
0,75
0,75
0,75
1,1
1,1
1,1
1,5

0,5
0,5
0,5
0,5
0,5
0,5
0,75
0,75
0,75
0,75
1
1
1
1,5
1,5
1,5
2

H = TOTAL HEAD METRES COLUMN OF WATER

11,5
17,0
22,1
27,0
31,7
36,1
45,2
50,4
55,5
60,4
69,3
74,8
85,6
100,0
111,0
127,4
145,5

Prestazioni conformi alle norme ISO 9906 - Annex A.

10,7
15,7
20,4
24,8
28,9
32,7
41,8
46,4
51,0
55,5
64,3
69,4
79,3
93,1
103,2
118,1
135,4

9,5
13,8
17,9
21,6
25,0
28,1
36,8
40,8
44,7
48,5
57,1
61,6
70,1
82,6
91,5
104,4
120,0

EN12845_pp_1sv-2p50-en_a_th

38

GEN..D/FHF 32-80 BOOSTER SETS SERIES


TABELLA ABBINAMENTI POMPA SERVIZIO FH32-80 - POMPA PILOTA GRUPPI GEN 1
SERVICE PUMP JOCKEY PUMP COMBINA
TIONS
COMBINATIONS
SERVICE PUMP

JOCKEY PUMP

1SV 19

1SV 17

1SV 15

1SV 13

1SV 12

1SV 11

1SV 10

PUMP

32-125/D119
32-125/D136
32-160/D150
32-160/D164
32-200/D188
32-200/D204
40-125/D112
40-125/D122
40-125/D143
40-160/D159
40-160/D171
40-200/D190
40-200/D209
40-250/D218
40-250/D233
40-250/D251
50-125/D119
50-125/D130
50-125/D139
50-160/D158
50-160/D174
50-200/D197
50-200/D209
50-250/D224
50-250/D237
50-250/D250
65-125/D121
65-125/D129
65-125/D140
65-160/D161
65-160/D168
65-160/D178
65-200/D187
65-200/D198
65-200/D210
65-250/D220
65-250/D241
65-250/D258
80-160/D163
80-160/D173
80-200/D189
80-200/D207
80-250/D225
80-250/D238
80-250/D256

12845-FHF32-80_ap-en_b_tc

39

GEN..D/FHF

PUMP

32-125/07
32-125/11
32-160/15
32-160/22
32-200/30
32-200/40
40-125/11
40-125/15
40-125/22
40-160/30
40-160/40
40-200/55
40-200/75
40-250/110A
40-250/110
40-250/150
50-125/22
50-125/30
50-125/40
50-160/55
50-160/75
50-200/110A
50-200/110
50-250/150
50-250/185
50-250/220
65-125/40
65-125/55
65-125/75
65-160/110A
65-160/110
65-160/150
65-200/150
65-200/185
65-200/220
65-250/220
65-250/300
65-250/370
80-160/150
80-160/185
80-200/220
80-200/300
80-250/370
80-250/450
80-250/550

1SV 09

FHF..
ELECTRIC

1SV 08

1SV 07

TYPE

GEN..D/FHF 100-125 BOOSTER SETS SERIES


TABELLA ABBINAMENTI POMPA SERVIZIO FH100-125 - POMPA PILOTA GRUPPI GE
SERVICE PUMP JOCKEY PUMP COMBINA
TIONS
COMBINATIONS
SERVICE PUMP

JOCKEY PUMP

GEN..D/FHF

PUMP

100-160/185
100-160/220
100-160/300
100-200/185
100-200/300
100-200/370
100-200/450
100-250/300
100-250/450
100-250/550
100-250/750
100-250/900
125-200/300
125-200/450
125-200/550
125-270/750
125-270/900
125-270/1100
125-270/1320

1SV 19

1SV 17

1SV 15

1SV 13

1SV 12

1SV 11

1SV 10

1SV 09

FHF..
ELECTRIC

1SV 08

1SV 07

TYPE

PUMP

100-160/D150
100-160/D165
100-160/D185
100-200/D168
100-200/D192
100-200/D203
100-200/D213
100-250/D200
100-250/D221
100-250/D235
100-250/D254
100-250/D267
125-200/D180
125-200/D206
125-200/D216
125-270/D224
125-270/D237
125-270/D253
125-270/D266

12845-FHF100-125_ap-en_b_tc

40

HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (POSITIVE SUCTION HEAD)
HYDRAULIC
TABLE
AT
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPO EN12845 SERIE FHF32 2 poli 50 Hz, 1 POMPA DI SERVIZIO, ASP ESCLUSA INS SOPRA
GEN..D/FHF 32 BOOSTER SETS SERIES
RATED

FHF..

POWER

ELECTRIC

PUMP

PUMP

Q = DELIVERY
l/min 0

100

150

200

225

250

275

300

375

400

425

450

500

m3/h 0

12

14

15

17

18

23

24

26

27

30

H = TOTAL HEAD METRES COLUMN OF WATER

kW

32-125/07

32-125/D119

1 x 0,75

16,9

15,6

14,1

12,1

10,9

9,6

8,1

6,6

32-125/11

32-125/D136

1 x 1,1

21,9

20,5

19,1

17,2

16,1

14,9

13,5

12,1

7,1

5,2

32-160/15

32-160/D150

1 x 1,5

27,3

25,6

24,0

21,8

20,5

19,0

17,4

15,6

9,5

7,2

32-160/22

32-160/D164

1 x 2,2

34,7

33,1

31,5

29,3

27,9

26,5

24,9

23,2

17,3

15,0

12,7

10,2

32-200/30

32-200/D188

1x3

44,2

41,3

39,3

36,8

35,3

33,7

32,0

30,1

23,4

20,8

18,0

15,0

32-200/40

32-200/D204

1x4

54,4

51,7

49,5

46,8

45,2

43,5

41,7

39,7

33,2

30,8

28,2

25,6

20,0

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
12845_1pg-sp-fhf32-2p50-en_a_th
LHn = class of risk value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure that these drops, added to the difference in level (max. 3.2m), are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (SUCTION LIF
T)
HYDRAULIC
TABLE
AT
LIFT)
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPO EN12845 SERIE FHF32 2 poli 50 Hz, 1 POMPA DI SERVIZIO, ASP ESCLUSA INS SOTTO
GEN..D/FHF 32 BOOSTER SETS SERIES
TYPE

RATED

FHF..

POWER

ELECTRIC

PUMP

PUMP

LHn

RISK CLASS

Q = DELIVERY
l/min 0

100

150

200

225

250

275

300

375

400

425

450

500

m3/h 0

12

14

15

17

18

23

24

26

27

30

H = TOTAL HEAD METRES COLUMN OF WATER

kW

32-125/07

32-125/D119

1 x 0,75

16,9

15,6

14,1

12,1

10,9

9,6

8,1

6,6

32-125/11

32-125/D136

1 x 1,1

21,9

20,5

19,1

17,2

16,1

14,9

13,5

12,1

7,1

5,2

32-160/15

32-160/D150

1 x 1,5

27,3

25,6

24,0

21,8

20,5

19,0

17,4

15,6

9,5

7,2

32-160/22

32-160/D164

1 x 2,2

34,7

33,1

31,5

29,3

27,9

26,5

24,9

23,2

17,3

15,0

12,7

10,2

32-200/30

32-200/D188

1x3

44,2

41,3

39,3

36,8

35,3

33,7

32,0

30,1

23,4

20,8

18,0

15,0

32-200/40

32-200/D204

1x4

54,4

51,7

49,5

46,8

45,2

43,5

41,7

39,7

33,2

30,8

28,2

25,6

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
LHn = class of risk value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure these drops are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

20,0

12845_1pg-st-fhf32-2p50-en_a_th

TABELLA DI PRESTAZIONI IDRAULICHE NPSHr GRUPPI EN12845 SERIE FHF32 2 poli 50 Hz

NPSH REQUIRED FOR PUMP SERIES FHF 32


TYPE

RATED

FHF..

POWER

ELECTRIC

PUMP

PUMP

LHn
LH

RISK CLASS

Q = DELIVERY
l/min 0

100

150

200

225

250

275

300

350

375

400

450

500

3
m /h 0

12

14

15

17

18

21

23

24

27

30

NPSHr [METRES COLUMN OF WATER]

kW

32-125/07

32-125/D119

1 x 0,75

1,6

1,6

1,7

1,8

2,0

2,2

32-125/11

32-125/D136

1 x 1,1

1,6

1,6

1,7

1,8

2,0

2,2

2,9

3,4

4,0

32-160/15

32-160/D150

1 x 1,5

2,2

2,4

2,5

2,7

2,8

3,0

3,6

3,9

4,4

32-160/22

32-160/D164

1 x 2,2

2,2

2,4

2,5

2,7

2,8

3,0

3,6

3,9

4,4

5,9

32-200/30

32-200/D188

1x3

2,7

2,9

3,1

3,3

3,5

3,8

4,3

4,6

4,9

5,5

32-200/40

32-200/D204

1x4

2,7

2,9

3,1

3,3

3,5

3,8

4,3

4,6

4,9

5,5

The declared NPSH values were obtained in the laboratory and refer to a single service pump
LHn = class of risk value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Check that NPSHd NPSHr+1m is satisfied

41

6,2

12845_1p-fhf32-2p50_NPSHr-en_a_th

GEN..D/FHF

TYPE

LHn

RISK CLASS

HYDRA
ULIC PERFORMANCE
T
ABLE
T 50
SUCTION
HEAD)
HYDRAULIC
TABLE
AT
TABELLA DI PRESTAZIONI
IDRAULICHE NETTE GRUPPI EN12845
SERIEA
FHF40
2 poliHZ
50 Hz(POSITIVE
1 POMPA DI SERVIZIO,
ASP ESCLUSA INST
SOPRAB
GEN..D/FHF 40 BOOSTER SETS SERIES
TYPE

RATED

FHF..

POWER

ELECTRIC

PUMP

Q = DELIVERY
l/min 0

300

350

375

540

600

700

725

750

800

900

1000

1100

m3/h 0

18

21

23

32

36

42

44

45

48

54

60

66

H = TOTAL HEAD METRES COLUMN OF WATER

kW

40-125/11

40-125/D112

1 x 1,1

13,9

11,3

10,0

9,3

3,4

40-125/15

40-125/D122

1 x 1,5

18,0

15,3

14,0

13,3

7,4

0,7
4,7

40-125/22

40-125/D143

1 x 2,2

25,3

21,8

20,5

19,8

14,0

11,4

6,4

5,0

3,6

40-160/30

40-160/D159

1x3

31,6

28,1

26,8

26,0

19,5

16,5

10,8

9,2

7,6

40-160/40

40-160/D171

1x4

38,3

35,1

33,7

32,9

26,5

23,6

18,1

16,5

15,0

0,6
11,7

40-200/55

40-200/D190

1 x 5,5

46,4

42,7

41,2

40,4

33,1

29,7

23,3

21,5

19,6

40-200/75

40-200/D209

1 x 7,5

57,5

53,1

51,6

50,7

43,8

40,7

34,8

33,2

31,5

28,0

40-250/110A 40-250/D218

1 x 11

63,6

57,8

56,2

55,2

47,8

44,5

38,2

36,5

34,8

31,1

40-250/110

40-250/D233

1 x 11

71,7

66,0

64,3

63,4

55,7

52,3

45,8

44,0

42,1

38,3

40-250/150

40-250/D251

1 x 15

85,0

78,6

76,9

76,0

68,4

65,0

58,6

56,8

55,0

51,1

42,6

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
12845_1pg-sp-fhf40-2p50-en_a_th
OHn = class of risk value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure that these drops, added to the difference in level (max. 3.2m), are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

HYDRA
ULIC PERFORMANCE T
ABLE
A2 T
50 HZ (SUCTION LIF
T)
HYDRAULIC
TABLE
LIFT)
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845
SERIE FHF40AT
poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA
INST SOTTO
GEN..D/FHF 40 BOOSTER SETS SERIES
RISK CLASS
TYPE

RATED

FHF..

POWER

ELECTRIC

PUMP

PUMP

OH1n

GEN..D/FHF

PUMP

OH1n

RISK CLASS

Q = DELIVERY
l/min 0

300

350

375

540

600

700

725

750

800

900

1000

1100

m3/h 0

18

21

23

32

36

42

44

45

48

54

60

66

H = TOTAL HEAD METRES COLUMN OF WATER

kW

40-125/11

40-125/D112

1 x 1,1

13,9

11,3

10,0

9,3

3,4

40-125/15

40-125/D122

1 x 1,5

18,0

15,3

14,0

13,3

7,4

0,7
4,7

40-125/22

40-125/D143

1 x 2,2

25,3

21,8

20,5

19,8

14,0

11,4

6,4

5,0

3,6

40-160/30

40-160/D159

1x3

31,6

28,1

26,8

26,0

19,5

16,5

10,8

9,2

7,6

0,6

40-160/40

40-160/D171

1x4

38,3

35,1

33,7

32,9

26,5

23,6

18,1

16,5

15,0

40-200/55

40-200/D190

1 x 5,5

46,4

42,7

41,2

40,4

33,1

29,7

23,3

21,5

19,6

40-200/75

40-200/D209

1 x 7,5

57,5

53,1

51,6

50,7

43,8

40,7

34,8

33,2

31,5

28,0

40-250/110A 40-250/D218

1 x 11

63,6

57,8

56,2

55,2

47,8

44,5

38,2

36,5

34,8

31,1

11,7

40-250/110

40-250/D233

1 x 11

71,7

66,0

64,3

63,4

55,7

52,3

45,8

44,0

42,1

38,3

40-250/150

40-250/D251

1 x 15

85,0

78,6

76,9

76,0

68,4

65,0

58,6

56,8

55,0

51,1

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
OHn = class of risk value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure these drops are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

42

42,6

12845_1pg-st-fhf40-2p50-en_a_th

NPSH
REQUIRED
PUMP
FHF
TABELLA DI PRESTAZIONI
IDRAULICHEFOR
NPSHr GRUPPI
EN12845 SERIES
SERIE FHF40 2 poli
50 Hz 140
POMPA DI SERVIZIO

FHF..

POWER

ELECTRIC

PUMP

PUMP

l/min 0

300

350

375

540

600

700

725

750

800

900

1000

1100

m3/h 0

18

21

23

32

36

42

44

45

48

54

60

66

Q = DELIVERY

NPSHr [METRES COLUMN OF WATER]

kW

40-125/11

40-125/D112

1 x 1,1

1,8

1,9

1,9

2,4

2,7

40-125/15

40-125/D122

1 x 1,5

1,8

1,9

1,9

2,4

2,7

3,7

40-125/22

40-125/D143

1 x 2,2

1,8

1,9

1,9

2,4

2,7

3,7

4,1

4,6

40-160/30

40-160/D159

1x3

1,9

1,9

1,9

2,4

2,9

4,1

4,5

5,0

6,3

40-160/40

40-160/D171

1x4

1,9

1,9

1,9

2,4

2,9

4,1

4,5

5,0

40-200/55

40-200/D190

1 x 5,5

2,0

2,1

2,2

2,9

3,4

4,5

4,9

5,3

6,2

40-200/75

40-200/D209

1 x 7,5

2,0

2,1

2,2

2,9

3,4

4,5

4,9

5,3

6,3

40-250/110A 40-250/D218

1 x 11

1,0

1,1

1,2

1,6

1,7

2,1

2,2

2,3

2,6

40-250/110

40-250/D233

1 x 11

1,0

1,1

1,2

1,6

1,7

2,1

2,2

2,3

2,6

40-250/150

40-250/D251

1 x 15

1,0

1,1

1,2

1,6

1,7

2,1

2,2

2,3

2,6

The declared NPSH values were obtained in the laboratory and refer to a single service pump
OHn, OHm = class of risk value referred to the required rated and maximum capacity (Tab.6 para 7.3.1 EN12845)
Check that NPSHd NPSHr+1m is satisfied at the maximum requested capacity

43

3,5

12845_1p-fhf40-2p50_NPSHr-en_a_th

GEN..D/FHF

RATED

OH1m

TYPE

OH1n

RISK CLASS

HYDRA
ULIC PERFORMANCE
T
ABLE
T 50
SUCTION
HYDRAULIC
TABLE
AT
TABELLA DI PRESTAZIONI
IDRAULICHE NETTE GRUPPI EN12845
SERIEA
FHF50
2 poliHZ
50 Hz(POSITIVE
1 POMPA DI SERVIZIO,
INST SOPRAB HEAD)
GEN..D/FHF 50 BOOSTER SETS SERIES
RATED

FHF..

POWER

ELECTRIC

PUMP

Q = DELIVERY
l/min 0

600

700

725

850

1000

1100

1200

1300

1350

1400

1500

1600

m3/h 0

36

42

44

51

60

66

72

78

81

84

90

96

H = TOTAL HEAD METRES COLUMN OF WATER

kW

50-125/22

50-125/D119

1 x 2,2

16,8

13,7

12,3

11,8

9,5

6,2

3,7

0,9

50-125/30

50-125/D130

1x3

19,9

17,5

16,1

15,8

13,6

10,5

8,0

5,3

2,3

50-125/40

50-125/D139

1x4

24,3

21,8

20,6

20,2

18,3

15,3

13,1

10,5

7,7

6,2

4,6

50-160/55

50-160/D158

1 x 5,5

31,8

29,3

27,7

27,3

24,8

21,1

18,2

15,0

11,4

9,5

7,6

50-160/75

50-160/D174

1 x 7,5

39,8

36,6

35,2

34,8

32,5

29,1

26,5

23,5

20,2

18,5

16,7

50-200/110A 50-200/D197

1 x 11

50,6

45,6

43,4

42,8

39,5

34,8

31,2

27,3

23,1

20,9

18,6

12,7

50-200/110

50-200/D209

1 x 11

58,0

52,6

50,5

49,9

46,7

42,1

38,6

34,7

30,4

28,1

25,7

50-250/150

50-250/D224

1 x 15

68,1

62,8

60,9

60,4

57,3

52,6

48,8

44,4

39,4

36,7

33,8

50-250/185

50-250/D237

1 x 18,5

76,5

71,7

70,0

69,5

66,6

62,3

58,8

54,7

50,0

47,4

44,7

38,6

50-250/220

50-250/D250

1 x 22

86,0

81,2

79,5

79,0

76,1

71,7

68,1

64,0

59,4

56,8

54,1

48,1

20,7

41,4

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
12845_1pg-sp-fhf50-2p50-en_a_th
OHn = class of risk value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure that these drops, added to the difference in level (max. 3.2m), are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

HYDRA
ULIC PERFORMANCE T
ABLE
A2 T
50 HZ (SUCTION LIF
T)
HYDRAULIC
TABLE
LIFT)
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845
SERIE FHF50AT
poli 50 Hz 1 POMPA DI SERVIZIO, INST SOTT
GEN..D/FHF 50 BOOSTER SETS SERIES
TYPE

RATED

FHF..

POWER

ELECTRIC

PUMP

PUMP

OH3n

RISK CLASS

OH2n

GEN..D/FHF

PUMP

OH3n

TYPE

OH2n

RISK CLASS

Q = DELIVERY
l/min 0

600

700

725

850

1000

1100

1200

1300

1350

1400

1500

1600

m3/h 0

36

42

44

51

60

66

72

78

81

84

90

96

H = TOTAL HEAD METRES COLUMN OF WATER

kW

50-125/22

50-125/D119

1 x 2,2

16,8

13,7

12,3

11,8

9,5

6,2

3,7

0,9

50-125/30

50-125/D130

1x3

19,9

17,5

16,1

15,8

13,6

10,5

8,0

5,3

2,3

50-125/40

50-125/D139

1x4

24,3

21,8

20,6

20,2

18,3

15,3

13,1

10,5

7,7

6,2

4,6

50-160/55

50-160/D158

1 x 5,5

31,8

29,3

27,7

27,3

24,8

21,1

18,2

15,0

11,4

9,5

7,6

50-160/75

50-160/D174

1 x 7,5

39,8

36,6

35,2

34,8

32,5

29,1

26,5

23,5

20,2

18,5

16,7

50-200/110A 50-200/D197

1 x 11

50,6

45,6

43,4

42,8

39,5

34,8

31,2

27,3

23,1

20,9

18,6

12,7

50-200/110

50-200/D209

1 x 11

58,0

52,6

50,5

49,9

46,7

42,1

38,6

34,7

30,4

28,1

25,7

50-250/150

50-250/D224

1 x 15

68,1

62,8

60,9

60,4

57,3

52,6

48,8

44,4

39,4

36,7

33,8

50-250/185

50-250/D237

1 x 18,5

76,5

71,7

70,0

69,5

66,6

62,3

58,8

54,7

50,0

47,4

44,7

38,6

50-250/220

50-250/D250

1 x 22

86,0

81,3

79,5

79,0

76,1

71,7

68,2

64,1

59,5

56,9

54,2

48,2

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
OHn = class of risk value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure these drops are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

44

20,7

41,6

12845_1pg-st-fhf50-2p50-en_a_th

NPSH
REQUIRED
FOR
PUMP
SERIES
TABELLA DI PRESTAZIONI
IDRAULICHE
NPSHr GRUPPI
EN12845
SERIE FHF50 FHF
2 poli 50 50
Hz 1 POMPA DI SERVIZIO

Q = DELIVERY
l/min 0

ELECTRIC

PUMP

PUMP

m /h 0

600

700

725

850

1000

1100

1200

1300

1350

1400

1500

1600

36

42

44

51

60

66

72

78

81

84

90

96

NPSHr [METRES COLUMN OF WATER]

kW

50-125/22

50-125/D119

1 x 2,2

2,1

2,3

2,3

2,6

3,1

3,5

3,9

50-125/30

50-125/D130

1x3

2,1

2,3

2,3

2,6

3,1

3,5

3,9

4,4

50-125/40

50-125/D139

1x4

2,1

2,3

2,3

2,6

3,1

3,5

3,9

4,4

4,7

5,0

50-160/55

50-160/D158

1 x 5,5

1,9

2,1

2,2

2,5

2,9

3,2

3,6

4,2

4,6

5,1

50-160/75

50-160/D174

1 x 7,5

1,9

2,1

2,2

2,5

2,9

3,2

3,6

4,2

4,6

5,1

50-200/110A 50-200/D197

1 x 11

1,8

1,9

2,0

2,2

2,6

2,9

3,4

4,1

4,6

5,1

50-200/110

50-200/D209

1 x 11

1,8

1,9

2,0

2,2

2,6

2,9

3,4

4,1

4,6

5,1

50-250/150

50-250/D224

1 x 15

1,5

1,7

1,7

2,0

2,4

2,7

3,1

3,6

3,9

4,2

50-250/185

50-250/D237

1 x 18,5

1,5

1,7

1,7

2,0

2,4

2,7

3,1

3,6

3,9

4,2

5,1

50-250/220

50-250/D250

1 x 22

1,5

1,7

1,7

2,0

2,4

2,7

3,1

3,6

3,9

4,2

5,1

The declared NPSH values were obtained in the laboratory and refer to a single service pump
OHn, OHm = class of risk value referred to the required rated and maximum capacity (Tab.6 para 7.3.1 EN12845)
Check that NPSHd NPSHr+1m is satisfied at the maximum requested capacity

45

6,5
6,7

6,4

12845_1p-fhf50-2p50_NPSHr-en_a_th

GEN..D/FHF

POWER

OH3m

FHF..

OH3n

RATED

OH2n

TYPE

OH2m

RISK CLASS

HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (POSITIVE SUCTION HEAD)
HYDRAULIC
TABLE
AT
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE FHF65 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA INST SOPRAB
GEN..D/FHF 65 BOOSTER SETS SERIES
RATED

FHF..

POWER

ELECTRIC

PUMP

Q = DELIVERY
l/min 0

800

900

1000

1100

1200

1350

1400

1500

1800

2000

2100

2300

m3/h 0

48

54

60

66

72

81

84

90

108

120

126

138

H = TOTAL HEAD METRES COLUMN OF WATER

kW

65-125/40

65-125/D121

1x4

19,1

15,6

14,6

13,5

12,3

10,9

8,7

7,9

6,2

65-125/55

65-125/D129

1 x 5,5

22,7

19,6

18,8

17,8

16,7

15,5

13,5

12,7

11,2

5,7

65-125/75

65-125/D140

1 x 7,5

27,1

24,3

23,5

22,7

21,7

20,7

18,9

18,2

16,8

12,0

8,1

65-160/110A 65-160/D161

1 x 11

32,7

29,2

28,3

27,2

26,0

23,9

23,2

21,6

15,9

11,5

9,0

65-160/110

65-160/D168

1 x 11

35,9

32,5

31,5

30,5

29,4

27,4

26,7

25,2

19,8

15,6

13,3

65-160/150

65-160/D178

1 x 15

41,9

38,9

38,1

37,1

36,1

34,2

33,6

32,2

27,2

23,2

21,1

65-200/150

65-200/D187

1 x 15

45,2

43,4

42,3

41,1

39,7

37,3

36,4

34,6

28,4

23,8

21,3

65-200/185

65-200/D198

1 x 18,5

51,6

50,2

49,2

48,2

47,0

44,9

44,1

42,4

36,5

31,8

29,2

65-200/220

65-200/D210

1 x 22

59,1

57,2

56,3

55,3

54,2

52,1

51,4

49,8

44,1

39,6

37,1

65-250/220

65-250/D220

1 x 22

62,8

60,6

59,4

58,0

56,4

53,5

52,5

50,2

42,1

35,7

32,1

16,3

31,6

65-250/300

65-250/D241

1 x 30

76,4

75,0

73,9

72,6

71,1

68,5

67,5

65,4

57,8

51,6

48,2

40,6

65-250/370

65-250/D258

1 x 37

90,8

89,9

89,0

88,0

86,7

84,5

83,7

81,8

74,8

68,8

65,4

57,7

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
12845_1pg-sp-fhf65-2p50-en_a_th
OHn = class of risk value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure that these drops, added to the difference in level (max. 3.2m), are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (SUCTION LIF
T)
HYDRAULIC
TABLE
AT
LIFT)
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE FHF65 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA INST SOTTOB
GEN..D/FHF 65 BOOSTER SETS SERIES
TYPE

RATED

FHF..

POWER

ELECTRIC

PUMP

PUMP

OH4n

RISK CLASS

OH3n

GEN..D/FHF

PUMP

OH4n

TYPE

OH3n

RISK CLASS

Q = DELIVERY
l/min 0

800

900

1000

1100

1200

1350

1400

1500

1800

2000

2100

2300

m3/h 0

48

54

60

66

72

81

84

90

108

120

126

138

H = TOTAL HEAD METRES COLUMN OF WATER

kW

65-125/40

65-125/D121

1x4

19,1

15,6

14,6

13,5

12,3

10,9

8,7

7,9

6,2

65-125/55

65-125/D129

1 x 5,5

22,7

19,6

18,8

17,8

16,7

15,5

13,5

12,7

11,2

5,7

65-125/75

65-125/D140

1 x 7,5

27,1

24,3

23,5

22,7

21,7

20,7

18,9

18,2

16,8

12,0

8,1

65-160/110A 65-160/D161

1 x 11

32,7

29,2

28,3

27,2

26,0

23,9

23,2

21,6

15,9

11,5

9,0

65-160/110

1 x 11

35,9

32,5

31,5

30,5

29,4

27,4

26,7

25,2

19,8

15,6

13,3

65-160/D168

65-160/150

65-160/D178

1 x 15

41,9

38,9

38,1

37,1

36,1

34,2

33,6

32,2

27,2

23,2

21,1

65-200/150

65-200/D187

1 x 15

45,2

43,4

42,3

41,1

39,7

37,3

36,4

34,6

28,4

23,8

21,3

65-200/185

65-200/D198

1 x 18,5

51,6

50,2

49,2

48,2

47,0

44,9

44,1

42,4

36,5

31,8

29,2

65-200/220

65-200/D210

1 x 22

59,1

57,2

56,3

55,3

54,2

52,1

51,4

49,8

44,1

39,6

37,1

65-250/220

65-250/D220

1 x 22

62,8

60,6

59,4

58,0

56,4

53,5

52,5

50,2

42,1

35,7

32,1

16,3

31,6

65-250/300

65-250/D241

1 x 30

76,4

75,0

73,9

72,6

71,1

68,5

67,5

65,4

57,8

51,6

48,2

40,6

65-250/370

65-250/D258

1 x 37

90,8

89,9

89,0

88,0

86,7

84,5

83,7

81,8

74,8

68,8

65,4

57,7

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
OHn = class of risk value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure these drops are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

46

12845_1pg-st-fhf65-2p50-en_a_th

NPSH
REQUIRED FOR PUMP SERIES FHF 65
TABELLA DI PRESTAZIONI IDRAULICHE NPSHr GRUPPI EN12845 SERIE FHF65 2 poli 50 Hz 1 POMPA DI SERVIZIO

Q = DELIVERY
l/min 0

ELECTRIC

PUMP

PUMP

m /h 0

800

900

1000

1100

1200

1350

1400

1500

1800

2000

2100

2300

48

54

60

66

72

81

84

90

108

120

126

138

NPSHr [METRES COLUMN OF WATER]

kW

65-125/40

65-125/D121

1x4

1,0

1,2

1,3

1,6

1,9

2,4

2,6

3,1

65-125/55

65-125/D129

1 x 5,5

1,0

1,2

1,3

1,6

1,9

2,4

2,6

3,1

5,1

65-125/75

65-125/D140

1 x 7,5

1,0

1,2

1,3

1,6

1,9

2,4

2,6

3,1

5,1

7,0

65-160/110A 65-160/D161

1 x 11

2,4

2,4

2,5

2,6

2,9

2,9

3,2

4,2

5,3

6,0

65-160/110

65-160/D168

1 x 11

2,3

2,4

2,5

2,7

2,8

2,9

3,1

3,7

4,4

4,9

65-160/150

65-160/D178

1 x 15

2,3

2,4

2,5

2,7

2,8

2,9

3,1

3,7

4,4

4,9

65-200/150

65-200/D187

1 x 15

1,8

1,9

2,0

2,1

2,3

2,4

2,6

3,4

4,5

5,3

65-200/185

65-200/D198

1 x 18,5

1,8

1,9

2,0

2,1

2,3

2,4

2,6

3,4

4,3

4,9

65-200/220

65-200/D210

1 x 22

1,8

1,9

2,0

2,1

2,3

2,4

2,6

3,4

4,3

4,9

65-250/220

65-250/D220

1 x 22

1,7

2,0

2,2

2,5

2,9

3,1

3,4

4,3

5,0

5,4

65-250/300

65-250/D241

1 x 30

1,7

2,0

2,2

2,5

2,9

3,1

3,4

4,3

5,0

5,4

6,2

65-250/370

65-250/D258

1 x 37

1,7

2,0

2,2

2,5

2,9

3,1

3,4

4,3

5,0

5,4

6,2

The declared NPSH values were obtained in the laboratory and refer to a single service pump
OHn, OHm = class of risk value referred to the required rated and maximum capacity (Tab.6 para 7.3.1 EN12845)
Check that NPSHd NPSHr+1m is satisfied at the maximum requested capacity

47

6,6

6,6

12845_1p-fhf65-2p50_NPSHr-en_a_th

GEN..D/FHF

POWER

OH4m

FHF..

OH4n

RATED

OH3n

TYPE

OH3m

RISK CLASS

HYDRA
ULIC PERFORMANCE
T
ABLE
T 50
SUCTION
HEAD)
HYDRAULIC
TABLE
AT
TABELLA DI PRESTAZIONI
IDRAULICHE NETTE GRUPPI EN12845
SERIEA
FHF80
2 poliHZ
50 Hz(POSITIVE
1 POMPA DI SERVIZIO,
ASP ESCLUSA INST
SOPRA
GEN..D/FHF 80 BOOSTER SETS SERIES
RATED

FHF..

POWER

ELECTRIC

PUMP

Q = DELIVERY
l/min 0

1500

1650

1800

2050

2100

2200

2300

2600

3216

3500

3600

3650

m3/h 0

90

99

108

123

126

132

138

156

193

210

216

219

H = TOTAL HEAD METRES COLUMN OF WATER

kW

80-160/150

80-160/D163

1 x 15

32,9

30,2

29,1

27,8

25,4

24,9

23,8

22,7

18,8

9,4

4,4

80-160/185

80-160/D173

1 x 18,5

39,0

35,6

34,5

33,4

31,2

30,7

29,7

28,6

25,1

16,2

11,3

80-200/220

80-200/D189

1 x 22

48,0

44,7

43,4

41,8

39,0

38,3

37,0

35,6

30,9

19,2

12,8

80-200/300

80-200/D207

1 x 30

59,9

56,9

55,8

54,4

51,9

51,3

50,1

48,9

44,7

34,2

28,5

80-250/370

80-250/D225

1 x 37

70,8

67,3

65,8

63,9

60,4

59,6

57,9

56,1

50,1

34,7

26,1

9,5

8,5

26,4

25,3

80-250/450

80-250/D238

1 x 45

80,0

78,0

76,5

74,8

71,5

70,8

69,2

67,6

62,0

47,5

39,6

36,5

80-250/550

80-250/D256

1 x 55

88,9

89,9

88,8

87,5

84,8

84,2

82,9

81,5

76,7

64,0

56,7

54,0

52,6

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
12845_1pg-sp-fhf80-2p50-en_a_th
OHn, HHn = class of risk value referred to the required rated capacity (Tab.6 para 7.3.1, Tab.7 para 7.3.2 EN12845)
Inlet pressure drops must be deducted. Make sure that these drops, added to the difference in level (max. 3.2m), are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

HYDRA
ULIC PERFORMANCE
T
ABLE
(SUCTION
LIF
T)
HYDRAULIC
TABLE
AT
LIFT)
TABELLA DI PRESTAZIONI
IDRAULICHE NETTE GRUPPI EN12845
SERIE FHF80A
2T
poli50
50 Hz HZ
1 POMPA
DI SERVIZIO, ASP ESCLUSA
INST SOTTO
GEN..D/FHF 80 BOOSTER SETS SERIES
RISK CLASS
RATED

FHF..

POWER

ELECTRIC

PUMP

PUMP

HH1n

TYPE

OH4n

GEN..D/FHF

PUMP

HH1n

TYPE

OH4n

RISK CLASS

Q = DELIVERY
l/min 0

1500

1650

1800

2050

2100

2200

2300

2600

3216

3500

3600

3650

m3/h 0

90

99

108

123

126

132

138

156

193

210

216

219

H = TOTAL HEAD METRES COLUMN OF WATER

kW

80-160/150

80-160/D163

1 x 15

32,9

30,2

29,1

27,8

25,4

24,9

23,8

22,7

18,8

9,4

4,4

80-160/185

80-160/D173

1 x 18,5

39,0

35,6

34,5

33,4

31,2

30,7

29,7

28,6

25,1

16,2

11,3

80-200/220

80-200/D189

1 x 22

48,0

44,7

43,4

41,8

39,0

38,3

37,0

35,6

30,9

19,2

12,8

80-200/300

80-200/D207

1 x 30

59,9

56,9

55,8

54,4

51,9

51,3

50,1

48,9

44,7

34,2

28,5

80-250/370

80-250/D225

1 x 37

70,8

67,3

65,8

63,9

60,4

59,6

57,9

56,1

50,1

34,7

26,1

9,5

8,5

26,4

25,3

80-250/450

80-250/D238

1 x 45

80,0

78,0

76,5

74,8

71,5

70,8

69,2

67,6

62,0

47,5

39,6

36,5

80-250/550

80-250/D256

1 x 55

88,9

89,9

88,8

87,5

84,8

84,2

82,9

81,5

76,7

64,0

56,7

54,0

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
OHn, HHn = class of risk value referred to the required rated capacity (Tab.6 para 7.3.1, Tab.7 para 7.3.2 EN12845)
Inlet pressure drops must be deducted. Make sure these drops are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

48

52,6

12845_1pg-st-fhf80-2p50-en_a_th

NPSH
REQUIRED FOR PUMP SERIES FHF 80
TABELLA DI PRESTAZIONI IDRAULICHE NPSHr GRUPPI EN12845 SERIE FHF80 2 poli 50 Hz 1 POMPA DI SERVIZIO

ELECTRIC

PUMP

PUMP

Q = DELIVERY
l/min 0

1500

1650

1800

2050

2100

2200

2300

2600

3216

3500

3600

3650

3
m /h 0

90

99

108

123

126

132

138

156

193

210

216

219

6,5

6,8

6,9

7,3

NPSHr [METRES COLUMN OF WATER]

kW

80-160/150

80-160/D163

1 x 15

3,7

3,8

3,9

4,0

4,1

4,2

4,2

4,5

5,4

6,2

80-160/185

80-160/D173

1 x 18,5

3,7

3,8

3,9

4,0

4,1

4,2

4,2

4,5

5,4

6,2

80-200/220

80-200/D189

1 x 22

2,8

3,0

3,1

3,3

3,4

3,5

3,6

3,9

5,1

6,3

80-200/300

80-200/D207

1 x 30

2,8

3,0

3,1

3,3

3,4

3,5

3,6

3,9

5,1

6,3

80-250/370

80-250/D225

1 x 37

3,0

3,1

3,3

3,6

3,6

3,8

3,9

4,4

6,0

7,4

80-250/450

80-250/D238

1 x 45

2,4

2,6

2,7

3,0

3,1

3,2

3,3

3,8

4,9

5,5

5,7

80-250/550

80-250/D256

1 x 55

2,4

2,6

2,7

3,0

3,1

3,2

3,3

3,8

4,9

5,5

5,7

The declared NPSH values were obtained in the laboratory and refer to a single service pump

OHn, OHm, HHn, HHm = class of risk value referred to the required rated and maximum capacity (Tab.6 para 7.3.1, Tab.7 para 7.3.2 EN12845)
Check that NPSHd NPSHr+1m is satisfied at the maximum requested capacity

49

5,8

12845_1p-fhf80-2p50_NPSHr-en_a_th

GEN..D/FHF

POWER

HH1m

FHF..

HH1n

RATED

OH4n

TYPE

OH4m

RISK CLASS

HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (POSITIVE SUCTION HEAD)
HYDRAULIC
TABLE
AT
GEN..D/FHF 100 BOOSTER SETS SERIES

POWER

ELECTRIC

PUMP

PUMP

HH4n

FHF..

HH3n

RATED

HH2n

TYPE

HH1n

RISK CLASS

l/min 0

1333

1500

1667

2300

2900

3050

3216

3800

4066

4266

4333

5000

5166

5316

5500

6000

m3/h 0

80

90

100

138

174

183

193

228

244

256

260

300

310

319

330

360

Q = DELIVERY

H = TOTAL HEAD METRES COLUMN OF WATER

kW

100-160/185

100-160/D150

1 x 18,5

26,7

26,0

25,6 25,2 22,9

19,9

19,0 18,0

13,9 11,8 10,2

9,6

3,5

1,8

100-160/220

100-160/D165

1 x 22

33,0

32,2

31,7 31,2 28,7

25,3

24,4 23,3

18,8 16,6 14,8 14,2

7,6

5,9

100-160/300

100-160/D185

1 x 30

42,3

41,2

40,8 40,3 37,8

34,6

33,6 32,5

28,2 26,0 24,2 23,6 16,9 15,1 13,5 11,4

100-200/185

100-200/D168

1 x 18,5

36,3

33,5 32,7 28,6

23,5

22,0 20,3

13,5 10,1

100-200/300

100-200/D192

1 x 30

49,0

47,5 46,9 43,7

39,5

38,3 36,8

31,0 28,0 25,5 24,7 15,5 12,9

100-200/370

100-200/D203

1 x 37

56,0

54,6 54,0 51,0

46,9

45,8 44,4

38,7 35,8 33,4 32,6 23,7 21,2 18,9 16,0

100-200/450

100-200/D213

1 x 45

61,0

60,0 59,5 57,1

53,6

52,6 51,4

46,3 43,7 41,5 40,7 32,3 29,9 27,7 24,8

100-250/300

100-250/D200

1 x 30

54,6

52,1 47,7

41,8

40,0 37,9

29,3 24,8 21,2 19,9

100-250/450

100-250/D221

1 x 45

68,8

66,9 63,5

58,7

57,2 55,4

48,1 44,2 41,0 39,9 27,2 23,6 20,3 15,9

100-250/550

100-250/D235

1 x 55

78,5

76,9 74,0

69,8

68,5 66,9

60,2 56,6 53,6 52,6 40,6 37,2 34,0 29,8

7,4

4,2

2,2
5,3

6,4

5,9

POWER

ELECTRIC

PUMP

PUMP

Q = DELIVERY
l/min 0

1667

2500

3800

4150

4550

4700

4800

5000

5316

5500

6000

6366

6416

6500

6716

6750

m3/h 0

100

150

228

249

273

282

288

300

319

330

360

382

385

390

403

405

H = TOTAL HEAD METRES COLUMN OF WATER

kW

100-250/750

100-250/D254

1 x 75

100-250/900

100-250/D267

1 x 90

HH6n

FHF..

HH5n

RATED

HH4n

TYPE

90,5

86,9 75,9 71,7

66,1

63,7 62,1

58,7 52,9 49,3 38,3 29,3 28,0

102,9 101,6

91,7

98,2 87,5 83,4

77,9

75,6 74,0

70,7 64,9 61,3 50,5 41,5 40,2 38,0 32,0

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
HHn = class of risk value referred to the required rated capacity (Tab.7 par. 7.3.2 EN12845)
Inlet pressure drops must be deducted. Make sure these drops, added to the difference in level (max 3,2mt), are less than 4,5mt
The values shown identify performance levels according to the reference standard EN12845.

31,1

12845_1pg-sp-fhf100-2p50-en_b_th

HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (SUCTION LIF
T)
HYDRAULIC
TABLE
AT
LIFT)
GEN..D/FHF 100 BOOSTER SETS SERIES

POWER

ELECTRIC

PUMP

PUMP

HH4n

FHF..

HH3n

RATED

HH2n

TYPE

HH1n

RISK CLASS

l/min 0

1333

1500

1667

2300

2900

3050

3216

3800

4066

4266

4333

5000

5166

5316

5500

6000

m3/h 0

80

90

100

138

174

183

193

228

244

256

260

300

310

319

330

360

Q = DELIVERY

H = TOTAL HEAD METRES COLUMN OF WATER

kW

100-160/185

100-160/D150

1 x 18,5

26,7

26,0

25,6

25,2 22,9

19,9

19,0 18,0

13,9

11,8 10,2

9,6

3,5

1,8

100-160/220

100-160/D165

1 x 22

33,0

32,2

31,7

31,2 28,7

25,3

24,4 23,3

18,8

16,6 14,8 14,2

7,6

5,9

100-160/300

100-160/D185

1 x 30

42,3

41,2

40,8

40,3 37,8

34,6

33,6 32,5

28,2

26,0 24,2 23,6 16,9 15,1 13,5 11,4

100-200/185

100-200/D168

1 x 18,5

36,3

33,5

32,7 28,6

23,5

22,0 20,3

13,5

10,1

100-200/300

100-200/D192

1 x 30

49,0

47,5

46,9 43,7

39,5

38,3 36,8

31,0

28,0 25,5 24,7 15,5 12,9

100-200/370

100-200/D203

1 x 37

56,0

54,6

54,0 51,0

46,9

45,8 44,4

38,7

35,8 33,4 32,6 23,7 21,2 18,9 16,0

100-200/450

100-200/D213

1 x 45

61,0

60,0

59,5 57,1

53,6

52,6 51,4

46,3

43,7 41,5 40,7 32,3 29,9 27,7 24,8

100-250/300

100-250/D200

1 x 30

54,6

52,1 47,7

41,8

40,0 37,9

29,3

24,8 21,2 19,9

100-250/450

100-250/D221

1 x 45

68,8

66,9 63,5

58,7

57,2 55,4

48,1

44,2 41,0 39,9 27,2 23,6 20,3 15,9

100-250/550

100-250/D235

1 x 55

78,5

76,9 74,0

69,8

68,5 66,9

60,2

56,6 53,6 52,6 40,6 37,2 34,0 29,8

7,4

4,2

2,2
5,3

6,4

5,9

RATED

FHF..

POWER

ELECTRIC

PUMP

PUMP

Q = DELIVERY
l/min 0

1667

2500

3800

4150

4550

4700

4800

5000

5316

5500

6000

6366

6416

6500

6716

6750

m3/h 0

100

150

228

249

273

282

288

300

319

330

360

382

385

390

403

405

H = TOTAL HEAD METRES COLUMN OF WATER

kW

100-250/750

100-250/D254

1 x 75

100-250/900

100-250/D267

1 x 90

HH6n

TYPE

HH5n

RISK CLASS
HH4n

GEN..D/FHF

RISK CLASS

90,5

86,9

75,9

71,7

66,1

63,7 62,1

58,7 52,9 49,3 38,3 29,3 28,0

102,9 101,6

91,7

98,2

87,5

83,4

77,9

75,6 74,0

70,7 64,9 61,3 50,5 41,5 40,2 38,0 32,0

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
HHn = class of risk value referred to the required rated capacity (Tab.7 par. 7.3.2 EN12845)
Inlet pressure drops must be deducted. Make sure these drops are less than 4,5mt
The values shown identify performance levels according to the reference standard EN12845.

50

31,1

12845_1pg-st-fhf100-2p50-en_b_th

NPSH REQUIRED FOR PUMP SERIES FHF 100

HH4m

HH3m

HH2m

HH4n

POWER

HH1m

FHF..

HH3n

RATED

HH2n

TYPE

HH1n

RISK CLASS

Q = DELIVERY
l/min 0 1333 1500 1667 2300 2900 3050 3216 3800 4066 4266 4333 5000 5166 5316 5500 6000

100-160/185
100-160/220
100-160/300
100-200/185
100-200/300
100-200/370
100-200/450
100-250/300
100-250/450
100-250/550

m3/h 0

PUMP

PUMP

80

90

100

138

100-160/D150
100-160/D165
100-160/D185
100-200/D168
100-200/D192
100-200/D203
100-200/D213
100-250/D200
100-250/D221
100-250/D235

1 x 18,5
1 x 22
1 x 30
1 x 18,5
1 x 30
1 x 37
1 x 45
1 x 30
1 x 45
1 x 55

174

183

193

228

244

256

260

300

310

319

330

360

NPSHr [METRES COLUMN OF WATER]

kW

6,3
5,0
5,0

6,4
5,2
5,2
4,2
3,1
3,1
3,1

6,6
5,4
5,4
4,2
3,1
3,1
3,1
4,7
4,6
4,6

7,3
6,2
6,2
4,6
3,3
3,3
3,3
5,0
4,7
4,7

8,0
6,9
6,9
5,6
3,5
3,5
3,5
5,3
4,7
4,7

8,2
7,0
7,0
6,0
3,6
3,6
3,6
5,4
4,8
4,8

8,4
7,2
7,2
6,5
3,7
3,7
3,7
5,4
4,8
4,8

9,2
7,9
7,9
9,2
4,2
4,2
4,2
5,7
4,8
4,8

9,5 9,8 9,9 11,0 11,4


8,3 8,5 8,6 9,6 9,9 10,3 10,7
8,3 8,5 8,6 9,6 9,9 10,3 10,7 12,8
11,1 12,8 13,5
4,6 4,9 5,1 7,0 7,7
4,6 4,9 5,1 7,0 7,7 8,4 9,5
4,6 4,9 5,1 7,0 7,7 8,4 9,5
5,8 5,9 6,0 6,3
4,9 4,9 4,9 5,1 5,2 5,2 5,3
4,9 4,9 4,9 5,1 5,2 5,2 5,3
HH6m

HH5m

POWER

HH4m

FHF..

HH6n

RATED

HH5n

TYPE

HH4n

RISK CLASS

Q = DELIVERY
l/min 0 1667 2500 3800 4150 4550 4700 4800 5000 5316 5500 6000 6366 6416 6500 6716 6750

ELECTRIC

100-250/750
100-250/900

m3/h 0 100

PUMP

PUMP

150

228

249

100-250/D254
100-250/D267

1 x 75
1 x 90

273

282

288

300

319

330

360

382

385

390

403

405

6,6
6,6

6,7
6,7

6,9

7,8

7,9

NPSHr [METRES COLUMN OF WATER]

kW

4,6
4,6

4,7
4,7

4,8
4,8

4,9
4,9

5,0
5,0

5,0
5,0

5,0
5,0

5,1
5,1

5,2
5,2

The declared NPSH values were obtained in the laboratory and refer to a single service pump
HHn, HHm = class of risk value referred to the required rated and maximum capacity (Tab.7 para 7.3.2 EN12845)
Check that NPSHd NPSHr+1m is satisfied at the maximum requested capacity

51

5,3
5,3

5,8
5,8

12845_1p-fhf100-2p50_NPSHr-en_a_th

GEN..D/FHF

ELECTRIC

HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (POSITIVE SUCTION HEAD)
HYDRAULIC
TABLE
AT
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE FHF125 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA INST SOPRA
GEN..D/FHF 125 BOOSTER SETS SERIES
0

384

403

Q = DELIVERY

150

288

407

450

479

504

520

538

560

575

600

620

650

H = TOTAL HEAD METRES COLUMN OF WATER

125-200/300

125-200/D180

1 x 30

32,8 29,8 28,4

19,8

19,6

15,8

14,4

12,6 11,2 10,9

125-200/450

125-200/D206

1 x 45

47,2 44,8 43,5

34,8

34,6

30,3

28,6

26,4 24,5 24,1 19,7 16,6 13,9 12,1

7,6

125-200/550

125-200/D216

1 x 55

57,4 55,1 54,0

45,6

45,4

41,0

39,3

36,8 34,8 34,3 29,3 25,6 22,3 20,0 17,4 14,1

125-270/750

125-270/D224

1 x 75

65,1

63,7

56,0

55,8

51,5

49,8

47,3 45,3 44,8 39,8 36,1 32,7 30,5 27,9 24,6 22,3

125-270/900

125-270/D237

1 x 90

75,3

73,6

67,0

66,8

62,8

61,1

58,8 56,8 56,3 51,2 47,4 43,8 41,4 38,5 34,8 32,2

27,5

125-270/1100 125-270/D253

1 x 110

88,2

85,4

79,2

79,0

75,1

73,5

71,2 69,2 68,8 63,5 59,5 55,7 53,0 49,9 45,8 42,8

37,6

33,1

125-270/1320 125-270/D266

1 x 132

97,5

94,8

88,6

88,4

84,7

83,2

81,1 79,2 78,8 74,0 70,3 66,8 64,5 61,7 58,0 55,4

50,7

46,8

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
HHn = class of risk value referred to the required rated capacity (Tab.7 par. 7.3.2 EN12845)
Inlet pressure drops must be deducted. Make sure these drops, added to the difference in level (max 3,2mt), are less than 4,5mt
The values shown identify performance levels according to the reference standard EN12845.

40,5

12845_1pg-sp-fhf125-2p50-en_b_th

HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (SUCTION LIF
T)
HYDRAULIC
TABLE
AT
LIFT)
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE FHF125 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA INST SOTTOB
GEN..D/FHF 125 BOOSTER SETS SERIES
0

342

291

PUMP

403

m3/h 0 120

kW

ELECTRIC

384

360

PUMP

Q = DELIVERY

POWER

6716 6783 7500 7983 8400 8667 8966 9333 9583 10000 10333 10833

4850

FHF..

6400

l/min 0 2000 2500 4800

RATED

HH10n

6000

TYPE

HH9n

5700

HH7n

HH8n

RISK CLASS

HH6n

150

288

407

450

479

504

520

538

560

575

600

620

650

H = TOTAL HEAD METRES COLUMN OF WATER

125-200/300

125-200/D180

1 x 30

32,8 29,8 28,4

19,8

19,6

15,8

14,4

12,6 11,2 10,9

125-200/450

125-200/D206

1 x 45

47,2 44,8 43,5

34,8

34,6

30,3

28,6

26,4 24,5 24,1 19,7 16,6 13,9 12,1

7,6

125-200/550

125-200/D216

1 x 55

57,4 55,1 54,0

45,6

45,4

41,0

39,3

36,8 34,8 34,3 29,3 25,6 22,3 20,0 17,4 14,1

125-270/750

125-270/D224

1 x 75

65,1

63,7

56,0

55,8

51,5

49,8

47,3 45,3 44,8 39,8 36,1 32,7 30,5 27,9 24,6 22,3

125-270/900

125-270/D237

1 x 90

75,3

73,6

67,0

66,8

62,8

61,1

58,8 56,8 56,3 51,2 47,4 43,8 41,4 38,5 34,8 32,2

27,5

125-270/1100 125-270/D253

1 x 110

88,2

85,4

79,2

79,0

75,1

73,5

71,2 69,2 68,8 63,5 59,5 55,7 53,0 49,9 45,8 42,8

37,6 33,1

125-270/1320 125-270/D266

1 x 132

97,5

94,8

88,6

88,4

84,7

83,2

81,1 79,2 78,8 74,0 70,3 66,8 64,5 61,7 58,0 55,4

50,7 46,8

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
HHn = class of risk value referred to the required rated capacity (Tab.7 par. 7.3.2 EN12845)
Inlet pressure drops must be deducted. Make sure these drops are less than 4,5mt
The values shown identify performance levels according to the reference standard EN12845.

40,5

12845_1pg-st-fhf125-2p50-en_b_th

TABELLA DI PRESTAZIONI IDRAULICHE NPSHr EN12845 SERIE FHF125 2 poli 50 Hz 1 POMPA DI SERVIZIO

NPSH REQUIRED FOR PUMP SERIES FHF 125

PUMP

HH9m

l/min 0

2000

2500

4800

4850

5700

6000

6400

6716

6783

7500

7983

8400

8667

8966

9333

9583

m3/h 0

120

150

288

291

342

360

384

403

407

450

479

504

520

538

560

575

HH7m

HH8m

PUMP

HH6m

ELECTRIC

HH10n

POWER

HH9n

FHF..

HH8n

RATED

HH7n

TYPE

HH10m

RISK CLASS

HH6n

GEN..D/FHF

360

342

291

m3/h 0 120

kW

PUMP

PUM

ELECTRIC

6716 6783 7500 7983 8400 8667 8966 9333 9583 10000 10333 10833

6400

6000

5700

POWER

HH10n

4850

FHF..

HH9n

l/min 0 2000 2500 4800

RATED

HH6n

TYPE

HH8n

RISK CLASS
HH7n

Q = DELIVERY
10000 10333 10833
600

620

650

NPSHr [METRES COLUMN OF WATER]

kW

125-200/300

125-200/D180

1 x 30

6,5

6,8

8,5

8,5

9,1

9,3

9,6

9,9

9,9

10,4

125-200/450

125-200/D206

1 x 45

6,1

6,2

7,1

7,1

7,6

7,7

8,0

8,3

8,3

8,9

9,5

10,0

10,4

125-200/550

125-200/D216

1 x 55

6,1

6,2

7,1

7,1

7,6

7,7

8,0

8,3

8,3

8,9

9,5

10,0

10,4

10,8

11,5

125-270/750

125-270/D224

1 x 75

7,8

8,3

8,3

8,5

8,6

8,7

8,8

8,9

9,3

9,7

10,1

10,5

11,1

11,9

12,7

125-270/900

125-270/D237

1 x 90

6,0

6,9

6,9

7,2

7,3

7,5

7,7

7,7

8,1

8,4

8,8

9,0

9,4

9,9

10,4

11,4

125-270/1100 125-270/D253

1 x 110

6,0

6,9

6,9

7,2

7,3

7,5

7,7

7,7

8,1

8,4

8,8

9,0

9,4

9,9

10,4

11,4

12,5

125-270/1320 125-270/D266

1 x 132

6,0

6,9

6,9

7,2

7,3

7,5

7,7

7,7

8,1

8,4

8,8

9,0

9,4

9,9

10,4

11,4

12,5

The declared NPSH values were obtained in the laboratory and refer to a single service pump
HHn, HHm = class of risk value referred to the required rated and maximum capacity (Tab.7 para 7.3.2 EN12845)
Check that NPSHd NPSHr+1m is satisfied at the maximum requested capacity

52

14,8

12845_1p-fhf125-2p50_NPSHr-en_a_th

GEN..D/FHF 100-125 BOOSTER SETS


TABELLA DATI ELETTRICI GRUPPI GEN..D/FHF 2 poli 50 Hz
ELECTRICAL DA
TA T
ABLE A
T 50 Hz
DAT
TABLE
AT
SERVICE
PUMP

ELECTRIC JOCKEY
PUMP

CURRENT (*)
ABSORBED SET

3 X 400 V
TYPE

32-125/07
32-125/11
32-160/15
32-160/22
32-200/30
32-200/40
40-125/11
40-125/15
40-125/22
40-160/30
40-160/40
40-200/55
40-200/75
40-250/110A
40-250/110
40-250/150
50-125/22
50-125/30
50-125/40
50-160/55
50-160/75
50-200/110A
50-200/110
50-250/150
50-250/185
50-250/220
65-125/40
65-125/55
65-125/75
65-160/110A
65-160/110
65-160/150
65-200/150
65-200/185
65-200/220
65-250/220
65-250/300
65-250/370
80-160/150
80-160/185
80-200/220
80-200/300
80-250/370
80-250/450
80-250/550

1x230V

3x400V

Pn
kW

In
A

In
A

0,37
0,55
0,55
0,55
0,55
0,75
0,37
0,55
0,55
0,55
0,55
0,55
0,75
0,75
0,75
1,1
0,37
0,55
0,55
0,55
0,55
0,75
0,75
0,75
0,75
1,1
0,37
0,55
0,55
0,55
0,55
0,55
0,55
0,75
0,75
0,75
0,75
1,1
0,55
0,55
0,55
0,75
0,75
0,75
1,1

2,82
3,88
3,88
3,88
3,88
4,88
2,82
3,88
3,88
3,88
3,88
3,88
4,88
4,88
4,88
6,77
2,82
3,88
3,88
3,88
3,88
4,88
4,88
4,88
4,88
6,77
2,82
3,88
3,88
3,88
3,88
3,88
3,88
4,88
4,88
4,88
4,88
6,77
3,88
3,88
3,88
4,88
4,88
4,88
6,77

1,35
1,48
1,48
1,48
1,48
1,76
1,35
1,48
1,48
1,48
1,48
1,48
1,76
1,76
1,76
2,36
1,35
1,48
1,48
1,48
1,48
1,76
1,76
1,76
1,76
2,36
1,35
1,48
1,48
1,48
1,48
1,48
1,48
1,76
1,76
1,76
1,76
2,36
1,48
1,48
1,48
1,76
1,76
1,76
2,36

3x400

POWER
PUMP

32-125/D119
32-125/D136
32-160/D150
32-160/D164
32-200/D188
32-200/D204
40-125/D112
40-125/D122
40-125/D143
40-160/D159
40-160/D171
40-200/D190
40-200/D209
40-250/D218
40-250/D233
40-250/D251
50-125/D119
50-125/D130
50-125/D139
50-160/D158
50-160/D174
50-200/D197
50-200/D209
50-250/D224
50-250/D237
50-250/D250
65-125/D121
65-125/D129
65-125/D140
65-160/D161
65-160/D168
65-160/D178
65-200/D187
65-200/D198
65-200/D210
65-250/D220
65-250/D241
65-250/D258
80-160/D163
80-160/D173
80-200/D189
80-200/D207
80-250/D225
80-250/D238
80-250/D256

Pn
kW

In
A

0,75
1,1
1,5
2,2
3
4
1,1
1,5
2,2
3
4
5,5
7,5
11
11
15
2,2
3
4
5,5
7,5
11
11
15
18,5
22
4
5,5
7,5
11
11
15
15
18,5
22
22
30
37
15
18,5
22
30
37
45
55

1,76
2,36
3,02
4,64
5,91
7,50
2,36
3,02
4,64
5,91
7,50
11,00
14,30
19,80
19,80
26,20
4,64
5,91
7,50
11,00
14,30
19,80
19,80
26,20
32,90
39,10
7,50
11,00
14,30
19,80
19,80
26,20
26,20
32,90
39,10
39,10
53,60
65,80
26,20
32,90
39,10
53,60
65,80
78,00
95,00

TYPE

1SV 07
1SV 08
1SV 08
1SV 09
1SV 11
1SV 12
1SV 07
1SV 08
1SV 08
1SV 09
1SV 10
1SV 11
1SV 12
1SV 13
1SV 15
1SV 17
1SV 07
1SV 08
1SV 08
1SV 09
1SV 10
1SV 12
1SV 12
1SV 15
1SV 15
1SV 17
1SV 07
1SV 08
1SV 08
1SV 09
1SV 10
1SV 10
1SV 11
1SV 12
1SV 12
1SV 13
1SV 15
1SV 17
1SV 09
1SV 10
1SV 11
1SV 12
1SV 15
1SV 15
1SV 17

GEN..00D GEN..01D GEN..10D GEN..11D


A
A
A
A

3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3

5,8
6,9
6,9
6,9
6,9
7,9
5,8
6,9
6,9
6,9
6,9
6,9
7,9
7,9
7,9
9,8
5,8
6,9
6,9
6,9
6,9
7,9
7,9
7,9
7,9
9,8
5,8
6,9
6,9
6,9
6,9
6,9
6,9
7,9
7,9
7,9
7,9
9,8
6,9
6,9
6,9
7,9
7,9
7,9
9,8

4,8
5,4
6,0
7,6
8,9
10,5
5,4
6,0
7,6
8,9
10,5
14,0
17,3
22,8
22,8
29,2
7,6
8,9
10,5
14,0
17,3
22,8
22,8
29,2
35,9
42,1
10,5
14,0
17,3
22,8
22,8
29,2
29,2
35,9
42,1
42,1
56,6
68,8
29,2
35,9
42,1
56,6
68,8
81,0
98,0

6,1
6,8
7,5
9,1
10,4
12,3
6,7
7,5
9,1
10,4
12,0
15,5
19,1
24,6
24,6
31,6
9,0
10,4
12,0
15,5
18,8
24,6
24,6
31,0
37,7
44,5
11,9
15,5
18,8
24,3
24,3
30,7
30,7
37,7
43,9
43,9
58,4
71,2
30,7
37,4
43,6
58,4
70,6
82,8
100,4

ENMTP-FHF_2p50-en_d_te

(*) The current indicated is the maximum current absorbed.


At the set 3x400V three-phase power supply GEN..10D and GEN..11D to add the control panel current of the engine pump (GEN..0D) 1x230V
The sets GEN..01D have the electric jockey pump 1x230V single-phase power supply.

53

GEN..D/FHF

FHF..
ELECTRIC
PUMP

1 x 230V
NOMINAL

GEN..D/FHF 100-125 BOOSTER SETS


TABELLA DATI ELETTRICI GRUPPI GEN..D/FHF 2 poli 50 Hz
ELECTRICAL DA
TA T
ABLE A
T 50 Hz
DAT
TABLE
AT
SERVICE
PUMP

ELECTRIC JOCKEY
PUMP

CURRENT (*)
ABSORBED SET

3 X 400 V
TYPE
FHF..
ELECTRIC

GEN..D/FHF

PUMP

100-160/185
100-160/220
100-160/300
100-200/185
100-200/300
100-200/370
100-200/450
100-250/300
100-250/450
100-250/550
100-250/750
100-250/900
125-200/300
125-200/450
125-200/550
125-270/750
125-270/900
125-270/1100
125-270/1320

1 x 230V
NOMINAL
POWER

PUMP

100-160/D150
100-160/D165
100-160/D185
100-200/D168
100-200/D192
100-200/D203
100-200/D213
100-250/D200
100-250/D221
100-250/D235
100-250/D254
100-250/D267
125-200/D180
125-200/D206
125-200/D216
125-270/D224
125-270/D237
125-270/D253
125-270/D266

Pn

In

kW

18,5
22
30
18,5
30
37
45
30
45
55
75
90
30
45
55
75
90
110
132

32,9
39,1
53,6
32,9
53,6
65,8
78,0
53,6
78,0
95,0
129,0
154,0
53,6
78,0
95,0
129,0
154,0
188,0
223,0

TYPE

1SV 08
1SV 09
1SV 11
1SV 10
1SV 11
1SV 12
1SV 13
1SV 12
1SV 15
1SV 15
1SV 17
1SV 19
1SV 09
1SV 11
1SV 12
1SV 13
1SV 15
1SV 17
1SV 19

1x230V

3x400V

3x400

Pn

In

In

kW

GEN..00D GEN..01D GEN..10D GEN..11D


A

0,55
0,55
0,55
0,55
0,55
0,75
0,75
0,75
0,75
0,75
1,1
1,1
0,55
0,55
0,75
0,75
0,75
1,1
1,1

3,88
3,88
3,88
3,88
3,88
4,88
4,88
4,88
4,88
4,88
6,77
6,77
3,88
3,88
4,88
4,88
4,88
6,77
6,77

1,48
1,48
1,48
1,48
1,48
1,76
1,76
1,76
1,76
1,76
2,36
2,36
1,48
1,48
1,76
1,76
1,76
2,36
2,36

3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
4,5
4,5

6,9
6,9
6,9
6,9
6,9
7,9
7,9
7,9
7,9
7,9
9,8
9,8
6,9
6,9
7,9
7,9
7,9
11,3
11,3

35,9
42,1
56,6
35,9
56,6
68,8
81,0
56,6
81,0
98,0
132,0
157,0
56,6
81,0
98,0
132,0
157,0
192,5
227,5

37,4
43,6
58,1
37,4
58,1
70,6
82,8
58,4
82,8
99,8
134,4
159,4
58,1
82,5
99,8
133,8
158,8
194,9
229,9

ENMTP-FHF100-en_2p50_d_te

(*) The current indicated is the maximum current absorbed.


At the set 3x400V three-phase power supply GEN..10D and GEN..11D to add the control panel current of the engine pump (GEN..0D) 1x230V
The sets GEN..01D have the electric jockey pump 1x230V single-phase power supply.

54

Fire-fighting
booster sets
EN 12845

MARKET SECTORS
CIVIL, INDUSTRIAL
APPLICA
TIONS
APPLICATIONS
Fixed fire-fighting systems.

Automatic Sprinkler systems.

GEN..D/FHF

DFHF
Series

SPECIFICA
TIONS
SPECIFICATIONS
Flow up to 650 m3/h.

Diesel engine with battery start.

Head up to 100 m.

Diesel engine service pump

Panel supply power voltage:


1 x 230V 10%.

in horizontal design
design:
- FHF series.

Maximum running pressure: 12 bar.

Frequency: 50 Hz.
Voltage for controls outside panel:
12 - 24 Vac.

Protection grade:

- electric panel: IP54.

Electric pumps maximum power


132 kW.

55

GEN..D/FHF

DFHF 32-80 DIESEL ENGINE PUMP SERIES


FIRE-FIGHTING EN 12845

For the overall dimensions of the fuel tank and the starting batteries, see tables on pages 20-25.

56

D..

DNA

DNM

H1

H2

FHFE32-125/D119

R 2"

32

400

350

80

710

900

262

402

630

FHFE32-125/D136

R 2"

32

400

350

80

710

900

262

402

630

FHFE32-160/D150

R 2"

32

400

350

80

690

900

282

442

650

FHFE32-160/D164

R 2"

32

400

350

80

690

900

282

442

650

FHFE32-200/D188

R 2"

32

400

350

80

690

900

260

440

630

FHFE32-200/D204

R 2"

32

500

450

80

790

950

310

490

710

FHFE40-125/D112

65

40

400

350

80

690

900

262

402

630

FHFE40-125/D122

65

40

400

350

80

690

900

262

402

630

FHFE40-125/D143

65

40

400

350

80

690

900

262

402

630

FHFE40-160/D159

65

40

400

350

80

690

900

282

442

650

FHFE40-160/D171

65

40

400

350

80

690

900

282

442

650

FHFE40-200/D190

65

40

500

450

100

770

950

310

490

710

FHFE40-200/D209

65

40

500

450

100

770

950

310

490

720

FHFE40-250/D218

65

40

530

480

100

820

1000

280

505

690

FHFE40-250/D233

65

40

530

480

100

920

1200

330

555

800

FHFE40-250/D251

65

40

530

480

100

920

1200

330

555

800

FHFE50-125/D119

65

50

400

350

100

690

950

282

442

650

FHFE50-125/D130

65

50

400

350

100

690

950

282

442

650

FHFE50-125/D139

65

50

500

450

100

740

950

282

442

650

FHFE50-160/D158

65

50

500

450

100

770

950

310

490

710

FHFE50-160/D174

65

50

500

450

100

770

950

310

490

720

FHFE50-200/D197

65

50

530

480

100

820

1000

310

510

720

FHFE50-200/D209

65

50

530

480

100

870

1200

360

560

830

FHFE50-250/D224

65

50

530

480

100

920

1200

330

555

800

FHFE50-250/D237

65

50

530

480

100

970

1300

380

605

800

FHFE50-250/D250

65

50

530

480

100

970

1300

380

605

900

FHFE65-125/D121

80

65

500

450

100

725

950

310

490

710

FHFE65-125/D129

80

65

500

450

100

755

950

310

490

710

FHFE65-125/D140

80

65

500

450

100

755

1000

310

490

720

FHFE65-160/D161

80

65

530

480

100

820

1000

310

510

720

FHFE65-160/D168

80

65

530

480

100

920

1200

360

560

830

FHFE65-160/D178

80

65

530

480

100

920

1200

360

560

830

FHFE65-200/D187

80

65

530

480

100

920

1200

330

555

800

FHFE65-200/D198

80

65

530

480

100

970

1350

380

605

800

FHFE65-200/D210

80

65

530

480

100

970

1350

380

605

800

FHFE65-250/D220

80

65

530

480

100

955

1450

360

610

880

FHFE65-250/D241

80

65

640

590

100

1130

1550

360

610

1000

FHFE65-250/D258

80

65

640

590

100

1130

1550

360

610

1010

FHFE80-160/D163

100

80

530

480

125

920

1250

330

555

800

FHFE80-160/D173

100

80

530

480

125

970

1350

380

605

800

FHFE80-200/D189

100

80

530

480

125

970

1450

380

630

900

FHFE80-200/D207

100

80

640

590

125

1095

1550

360

610

1000

FHFE80-250/D225

100

80

640

590

125

1130

1550

360

640

1010

FHFE80-250/D238

100

80

640

590

125

1180

1550

365

645

1030

80

660

610

125

1240

1750

390

670

FHFE80-250/D256
100
Dimensions in mm. Tolerance 10 mm.

1080
d_fhfe-en_h_td

57

GEN..D/FHF

DFHF 32-80 DIESEL ENGINE PUMP SERIES


FIRE-FIGHTING EN 12845

GEN..D/FHF

DFHF 100-125 DIESEL ENGINE PUMP SERIES


FIRE-FIGHTING EN 12845

For the overall dimensions of the fuel tank and the starting batteries, see tables on pages 20-25.

D..

DNA

DNM

H1

H2

FHFE100-160/D150

125

100

530

480

125

1000

1350

348

628

870

FHFE100-160/D165

125

100

530

480

125

960

1450

398

678

870

FHFE100-160/D185

125

100

640

590

125

1150

1550

348

628

990

FHFE100-200/D168

125

100

530

480

125

1000

1450

373

653

800

FHFE100-200/D192

125

100

640

590

125

1150

1550

373

653

1010

FHFE100-200/D203

125

100

640

590

125

1200

1550

373

653

1000

FHFE100-200/D213

125

100

640

590

125

1140

1550

368

648

1010

FHFE100-250/D200

125

100

640

590

140

1200

1600

348

628

990

FHFE100-250/D221

125

100

640

590

140

1200

1600

348

628

1000

FHFE100-250/D235

125

100

640

590

140

1190

1750

393

673

1080

FHFE100-250/D254

125

100

700

650

140

1300

2050

373

653

1040

FHFE100-250/D267

125

100

700

650

140

1300

2050

373

653

1040

FHFE125-200/D180

150

125

640

590

140

1200

1650

373

688

1010

FHFE125-200/D206

150

125

640

590

140

1190

1650

343

658

1000

FHFE125-200/D216

150

125

640

590

140

1190

1800

393

708

1080

FHFE125-270/D224

150

125

700

650

140

1300

2100

423

778

1090

FHFE125-270/D237

150

125

700

650

140

1300

2100

423

778

1100

FHFE125-270/D253

150

125

800

750

140

1300

2050

478

833

1350

125

800

750

140

1300

2050

478

833

FHFE125-270/D266
150
Dimensions in mm. Tolerance 10 mm.

1350
d_fhfe100-en_e_td

58

Fire-fighting
booster sets
EN 12845

MARKET SECTORS
CIVIL, INDUSTRIAL
APPLICA
TIONS
APPLICATIONS
Fixed fire-fighting systems.

Automatic Sprinkler systems.

GEN..D/FHF

GEN..00D/FHF
Series

SPECIFICA
TIONS
SPECIFICATIONS
Flow up to 650 m3/h.
Head up to 100 m.

Diesel engine with battery start.


Diesel engine service pump

Panel supply power voltage:


1 x 230V 10%.

Frequency: 50 Hz.

in horizontal design
design:
- FHF series.

Maximum running pressure: 12 bar.

Voltage for controls outside panel:


12 - 24 Vac.

Protection grade:

- electric panel: IP54.

Electric pumps maximum power


132 kW.

59

GEN..D/FHF

GEN..00D/FHF 32-80 SERIES


FIRE-FIGHTING BOOSTER SETS EN 12845

For the overall dimensions of the fuel tank and the starting batteries, see tables on pages 20-25.

60

GEN..00D

DRW N

DNA

DNM

FHF32-125/D119

R 2"

R 1"1/2

400

350

80

710

262

900

913

1487

FHF32-125/D136

R 2"

R 1"1/2

400

350

80

710

262

900

913

1487

FHF32-160/D150

R 2"

R 1"1/2

400

350

80

690

282

900

953

1527

FHF32-160/D164

R 2"

R 1"1/2

400

350

80

690

282

900

953

1527

FHF32-200/D188

R 2"

R 1"1/2

400

350

80

690

260

900

951

1525

FHF32-200/D204

R 2"

R 1"1/2

500

450

80

790

310

950

1001

1575

FHF40-125/D112

65

65

400

350

80

690

262

900

1109

1697

FHF40-125/D122

65

65

400

350

80

690

262

900

1109

1697

FHF40-125/D143

65

65

400

350

80

690

262

900

1109

1697

FHF40-160/D159

65

65

400

350

80

690

282

900

1149

1737

FHF40-160/D171

65

65

400

350

80

690

282

900

1149

1737

FHF40-200/D190

65

65

500

450

100

770

310

950

1197

1785

FHF40-200/D209

65

65

500

450

100

770

310

950

1197

1785

FHF40-250/D218

65

65

530

480

100

820

280

1000

1212

1800

FHF40-250/D233

65

65

530

480

100

920

330

1200

1262

1850

FHF40-250/D251

65

65

530

480

100

920

330

1200

1262

1850

FHF50-125/D119

65

65

400

350

100

690

282

950

1241

1829

FHF50-125/D130

65

65

400

350

100

690

282

950

1241

1829

FHF50-125/D139

65

65

500

450

100

740

282

950

1241

1829

FHF50-160/D158

65

65

500

450

100

770

310

950

1289

1877

FHF50-160/D174

65

65

500

450

100

770

310

950

1289

1877

FHF50-200/D197

65

65

530

480

100

820

310

1000

1309

1897

FHF50-200/D209

65

65

530

480

100

870

360

1200

1359

1947

FHF50-250/D224

65

65

530

480

100

920

330

1200

1354

1942

FHF50-250/D237

65

65

530

480

100

970

380

1300

1404

1992

FHF50-250/D250

65

65

530

480

100

970

380

1300

1404

1992

FHF65-125/D121

80

80

500

450

100

725

310

950

1356

1950

FHF65-125/D129

80

80

500

450

100

755

310

950

1356

1950

FHF65-125/D140

80

80

500

450

100

755

310

1000

1356

1950

FHF65-160/D161

80

80

530

480

100

820

310

1000

1376

1970

FHF65-160/D168

80

80

530

480

100

920

360

1200

1426

2020

FHF65-160/D178

80

80

530

480

100

920

360

1200

1426

2020

FHF65-200/D187

80

80

530

480

100

920

330

1200

1421

2015

FHF65-200/D198

80

80

530

480

100

970

380

1350

1471

2065

FHF65-200/D210

80

80

530

480

100

970

380

1350

1471

2065

FHF65-250/D220

80

80

530

480

100

955

360

1450

1476

2070

FHF65-250/D241

80

80

640

590

100

1130

360

1550

1476

2070

FHF65-250/D258

80

80

640

590

100

1130

360

1550

1476

2070

FHF80-160/D163

100

100

530

480

125

920

330

1250

1504

2111

FHF80-160/D173

100

100

530

480

125

970

380

1350

1554

2161

FHF80-200/D189

100

100

530

480

125

970

380

1450

1579

2186

FHF80-200/D207

100

100

640

590

125

1095

360

1550

1559

2166

FHF80-250/D225

100

100

640

590

125

1130

360

1550

1589

2196

FHF80-250/D238

100

100

640

590

125

1180

365

1550

1594

2201

FHF80-250/D256
2
100
Dimensions in mm. Tolerance 10 mm.

100

660

610

125

1240

390

1750

1619

2226

gen00d_fhf-en_h_td

61

GEN..D/FHF

GEN..00D/FHF 32-80 SERIES


FIRE-FIGHTING BOOSTER SETS EN 12845

GEN..D/FHF

GEN..00D/FHF 100-125 SERIES


FIRE-FIGHTING BOOSTER SETS EN 12845

For the overall dimensions of the fuel tank and the starting batteries, see tables on pages 20-25.

GEN..00D

DRW N

DNA

DNM

FHF100-160/D150

125

125

530

480

125

1000

348

1350

1676

2296

FHF100-160/D165

125

125

530

480

125

960

398

1450

1726

2346

FHF100-160/D185

125

125

640

590

125

1150

348

1550

1676

2296

FHF100-200/D168

125

125

530

480

125

1000

373

1450

1701

2321

FHF100-200/D192

125

125

640

590

125

1150

373

1550

1701

2321

FHF100-200/D203

125

125

640

590

125

1200

373

1550

1701

2321

FHF100-200/D213

125

125

640

590

125

1140

368

1550

1696

2316

FHF100-250/D200

125

125

640

590

140

1200

348

1600

1676

2296

FHF100-250/D221

125

125

640

590

140

1200

348

1600

1676

2296

FHF100-250/D235

125

125

640

590

140

1190

393

1750

1721

2341

FHF100-250/D254

125

125

700

650

140

1300

373

2050

1701

2321

FHF100-250/D267

125

125

700

650

140

1300

373

2050

1701

2321

FHF125-200/D180

150

150

640

590

140

1200

373

1650

1868

2502

FHF125-200/D206

150

150

640

590

140

1190

343

1650

1838

2472

FHF125-200/D216

150

150

640

590

140

1190

393

1800

1888

2522

FHF125-270/D224

150

150

700

650

140

1300

423

2100

1958

2592

FHF125-270/D237

150

150

700

650

140

1300

423

2100

1958

2592

FHF125-270/D253

150

150

800

750

140

1300

478

2050

2013

2647

FHF125-270/D266
2
150
Dimensions in mm. Tolerance 10 mm.

150

800

750

140

1300

478

2050

2013

2647

gen00d_fhf100-en_f_td

62

Fire-fighting
booster sets
EN 12845

MARKET SECTORS
CIVIL, INDUSTRIAL
APPLICA
TIONS
APPLICATIONS
Fixed fire-fighting systems.
Automatic Sprinkler systems.

GEN..D/FHF

GEN..01D/FHF
Series

SPECIFICA
TIONS
SPECIFICATIONS
Flow up to 650 m3/h.
Head up to 100 m.
Panel supply power voltage:

- Electric pump: 1 x 230V 10%.


- Diesel engine pump: 1 x 230V
10%.

Frequency: 50 Hz.
Voltage for controls outside panel:
12 - 24 Vac.

Protection grade:

Electric motor start :

- Direct start for powers up to 22 kW


included for electric pump.
Diesel engine with battery start.

Service pump in

horizontal design
design:
- FHF series.

ey pump
jockey
Electric jock

with vertical axis


axis:
- SV Series (motor protection
grade IP55).

- electric panel: IP54.

Electric pumps maximum power


132 kW.

63

Maximum running pressure: 12 bar.

GEN..D/FHF

GEN..01D/FHF 32-80 SERIES


FIRE-FIGHTING BOOSTER SETS EN 12845

For the overall dimensions of the fuel tank and the starting batteries, see tables on pages 20-25.

64

GEN..01D/FHF 32-80 SERIES


FIRE-FIGHTING BOOSTER SETS EN 12845
DRW N DNA

DNP

DNM

A1

FHF32-125/D119

R 2"

Rp 1"

R 1"1/2

330

220

280

905

80

225

362 1400 400

950 1265 1013 1587

FHF32-125/D136

R 2"

Rp 1"

R 1"1/2

330

220

280

905

80

225

362 1400 400

950 1265 1013 1587

FHF32-160/D150

R 2"

Rp 1"

R 1"1/2

330

220

280

885

80

225

382 1400 400

950 1245 1053 1627

FHF32-160/D164

R 2"

Rp 1"

R 1"1/2

330

220

280

885

80

225

382 1400 400

950 1245 1053 1627

FHF32-200/D188

R 2"

Rp 1"

R 1"1/2

330

220

280

885

80

225

360 1400 400

950 1245 1051 1625

FHF32-200/D204

R 2"

Rp 1"

R 1"1/2

400

225

280 1005

80

225

410 1400 475 1100 1365 1101 1675

FHF40-125/D112

65

Rp 1"

65

330

220

280

885

80

225

362 1400 400

950 1245 1206 1794

FHF40-125/D122

65

Rp 1"

65

330

220

280

885

80

225

362 1400 400

950 1245 1206 1794

FHF40-125/D143

65

Rp 1"

65

330

220

280

885

80

225

362 1400 400

950 1245 1206 1794

FHF40-160/D159

65

Rp 1"

65

330

220

280

885

80

225

382 1400 400

950 1245 1246 1834

FHF40-160/D171

65

Rp 1"

65

330

220

280

885

80

225

382 1400 400

950 1245 1246 1834

FHF40-200/D190

65

Rp 1"

65

400

225

280

985

100

225

410 1400 475 1100 1365 1294 1882

FHF40-200/D209

65

Rp 1"

65

400

225

280

985

100

225

410 1400 475 1100 1365 1294 1882

FHF40-250/D218

65

Rp 1"

65

390

235

280

975

100

225

380 1400 475 1100 1355 1309 1897

FHF40-250/D233

65

Rp 1"

65

390

235

280 1170 100

225

430 1400 475 1100 1550 1359 1947

FHF40-250/D251

65

Rp 1"

65

390

235

280 1170 100

225

430 1400 475 1100 1550 1359 1947

FHF50-125/D119

65

Rp 1"

65

330

220

280

885

100

225

382 1400 400

950 1265 1338 1926

FHF50-125/D130

65

Rp 1"

65

330

220

280

885

100

225

382 1400 400

950 1265 1338 1926

FHF50-125/D139

65

Rp 1"

65

400

225

280

955

100

225

382 1400 475 1100 1335 1338 1926

FHF50-160/D158

65

Rp 1"

65

400

225

280

985

100

225

410 1400 475 1100 1365 1386 1974

FHF50-160/D174

65

Rp 1"

65

400

225

280

985

100

225

410 1400 475 1100 1365 1386 1974

FHF50-200/D197

65

Rp 1"

65

390

235

280

975

100

225

410 1400 475 1100 1355 1406 1994

FHF50-200/D209

65

Rp 1"

65

390

235

280 1120 100

225

460 1400 475 1100 1500 1456 2044

FHF50-250/D224

65

Rp 1"

65

390

235

280 1170 100

225

430 1400 475 1100 1550 1451 2039

FHF50-250/D237

65

Rp 1"

65

390

235

280 1220 100

225

480 1550 475 1100 1600 1501 2089

FHF50-250/D250

65

Rp 1"

65

390

235

280 1220 100

225

480 1550 475 1100 1600 1501 2089

FHF65-125/D121

80

Rp 1"

80

400

225

280

940

100

225

410 1400 475 1100 1320 1453 2047

FHF65-125/D129

80

Rp 1"

80

400

225

280

970

100

225

410 1400 475 1100 1350 1453 2047

FHF65-125/D140

80

Rp 1"

80

400

225

280

970

100

225

410 1400 475 1100 1350 1453 2047

FHF65-160/D161

80

Rp 1"

80

390

235

280

975

100

225

410 1400 475 1100 1355 1473 2067

FHF65-160/D168

80

Rp 1"

80

390

235

280 1170 100

225

460 1400 475 1100 1550 1523 2117

FHF65-160/D178

80

Rp 1"

80

390

235

280 1170 100

225

460 1400 475 1100 1550 1523 2117

FHF65-200/D187

80

Rp 1"

80

390

235

280 1170 100

225

430 1400 475 1100 1550 1518 2112

FHF65-200/D198

80

Rp 1"

80

390

235

280 1220 100

225

480 1550 475 1100 1600 1568 2162

FHF65-200/D210

80

Rp 1"

80

390

235

280 1220 100

225

480 1550 475 1100 1600 1568 2162

FHF65-250/D220

80

Rp 1"

80

390

235

280 1305 100

225

460 1550 475 1100 1685 1573 2167

FHF65-250/D241

80

Rp 1"

80

460

380

180 1270 100

245

480 1750 530 1370 1550 1593 2187

FHF65-250/D258

80

Rp 1"

80

460

380

180 1270 100

245

480 1750 530 1370 1550 1593 2187

FHF80-160/D163

100

Rp 1"

100

390

235

280 1170 125

225

430 1400 475 1100 1575 1601 2208

FHF80-160/D173

100

Rp 1"

100

390

235

280 1220 125

225

480 1550 475 1100 1625 1651 2258

FHF80-200/D189

100

Rp 1"

100

390

235

280 1370 125

225

480 1550 475 1100 1775 1676 2283

FHF80-200/D207

100

Rp 1"

100

500

270

280 1440 125

245

480 1750 530 1300 1845 1676 2283

FHF80-250/D225

100

Rp 1"

100

460

380

155 1270 125

245

480 1750 530 1370 1550 1706 2313

FHF80-250/D238

100

Rp 1"

100

505

265

280 1550 125

245

485 1940 530 1300 1955 1711 2318

FHF80-250/D256
2
100
Rp 1"
Dimensions in mm. Tolerance 10 mm.

100

505

265

245 1380 125

265

530 1960 530 1300 1750 1756 2363


gen01d_fhf-en_g_td

65

GEN..D/FHF

GEN..01D

GEN..D/FHF

GEN..01D/FHF 100-125 SERIES


FIRE-FIGHTING BOOSTER SETS EN 12845

For the overall dimensions of the fuel tank and the starting batteries, see tables on pages 20-25.

66

GEN..01D/FHF 100-125 SERIES


FIRE-FIGHTING BOOSTER SETS EN 12845
DRW N DNA DNP

DNM

A1

FHF100-160/D150

125

Rp 1"

125

390

235

280 1300 125

225

448 1550 475 1100 1705 1773 2393

FHF100-160/D165

125

Rp 1"

125

390

235

280 1360 125

225

498 1550 475 1100 1765 1823 2443

FHF100-160/D185

125

Rp 1"

125

460

380

135 1290 125

245

468 1750 530 1370 1550 1793 2413

FHF100-200/D168

125

Rp 1"

125

390

235

280 1300 125

225

473 1550 475 1100 1705 1798 2418

FHF100-200/D192

125

Rp 1"

125

460

380

135 1290 125

245

493 1750 530 1370 1550 1818 2438

FHF100-200/D203

125

Rp 1"

125

500

270

280 1545 125

245

493 1750 530 1300 1950 1818 2438

FHF100-200/D213

125

Rp 1"

125

500

270

280 1485 125

245

488 1750 530 1300 1890 1813 2433

FHF100-250/D200

125

Rp 1"

125

500

270

280 1545 140

245

468 1750 530 1300 1965 1793 2413

FHF100-250/D221

125

Rp 1"

125

500

270

280 1545 140

245

468 1750 530 1300 1965 1793 2413

FHF100-250/D235

125

Rp 1"

125

505

265

280 1660 140

245

513 1750 530 1300 2080 1838 2458

FHF100-250/D254

125

Rp 1"

125

550

265

570 1340 140

215

513

570 1385 2050 1838 2458

FHF100-250/D267

125

Rp 1"

125

550

265

570 1340 140

215

513

570 1385 2050 1838 2458

FHF125-200/D180

150

Rp 1"

150

500

270

280 1545 140

245

493 1750 530 1300 1965 1985 2619

FHF125-200/D206

150

Rp 1"

150

505

265

280 1560 140

245

463 1750 530 1300 1980 1955 2589

FHF125-200/D216

150

Rp 1"

150

505

265

280 1710 140

245

513 1940 530 1300 2130 2005 2639

FHF125-270/D224

150

Rp 1"

150

550

265

620 1340 140

220

563

570 1385 2100 2095 2729

FHF125-270/D237

150

Rp 1"

150

550

265

620 1340 140

220

563

570 1385 2100 2095 2729

FHF125-270/D253

150

Rp 1"

150

600

265

570 1340 140

220

618

620 1485 2050 2150 2784

FHF125-270/D266
3
150 Rp 1"
Dimensions in mm. Tolerance 10 mm.

150

600

265

570 1340 140

220

618

620 1485 2050 2150 2784


gen01d_fhf100-en_f_td

67

GEN..D/FHF

GEN..01D

68

GEN..D/FHF

Fire-fighting
booster sets
EN 12845

MARKET SECTORS
CIVIL, INDUSTRIAL
APPLICA
TIONS
APPLICATIONS
Fixed fire-fighting systems.
Automatic Sprinkler systems.

GEN..D/FHF

GEN..10D/FHF
Series

SPECIFICA
TIONS
SPECIFICATIONS
Flow up to 1300 m3/h.
Head up to 100 m.
Panel supply power voltage:

- Electric pump: 3 x 400V 10%.


- Diesel engine pump: 1 x 230V
10%.

Frequency: 50 Hz.
Voltage for controls outside panel:
12 - 24 Vac.

Electric motor start :

- Direct start for powers up to 22 kW


included for pump (GEND...).
- Star/delta start for higher powers
(GENY... set).
Diesel engine with battery start.

Service pump in

horizontal design
design:
- FHF series (IP55 electric
motor protection).

Maximum running pressure: 12 bar.

Protection grade:

- electric panel: IP54.

Electric pumps maximum power


132 kW.

69

GEN..D/FHF

GEN..10D/FHF 32-80 SERIES


FIRE-FIGHTING BOOSTER SETS EN 12845

For the overall dimensions of the fuel tank and the starting batteries, see tables on pages 20-25.

70

GEN..10D

DRW N DNA

DNM

A1

FHF32-125/07/D119

R 2"

R 2"

320

310

240

870

80

362

1400

470

1100

1190

1019

1599

FHF32-125/11/D136

R 2"

R 2"

320

310

240

870

80

362

1400

470

1100

1190

1019

1599

FHF32-160/15/D150

R 2"

R 2"

320

310

240

850

80

382

1400

470

1100

1170

1059

1639

FHF32-160/22/D164

R 2"

R 2"

320

310

240

850

80

382

1400

470

1100

1170

1059

1639

FHF32-200/30/D188

R 2"

R 2"

320

310

240

850

80

360

1400

470

1100

1170

1057

1637

FHF32-200/40/D204

R 2"

R 2"

380

350

240

960

80

410

1400

570

1300

1280

1107

1687

FHF40-125/11/D112

65

65

320

310

240

850

80

362

1400

470

1100

1170

1206

1794

FHF40-125/15/D122

65

65

320

310

240

850

80

362

1400

470

1100

1170

1206

1794

FHF40-125/22/D143

65

65

320

310

240

850

80

362

1400

470

1100

1170

1206

1794

FHF40-160/30/D159

65

65

320

310

240

850

80

382

1400

470

1100

1170

1246

1834

FHF40-160/40/D171

65

65

320

310

240

850

80

382

1400

470

1100

1170

1246

1834

FHF40-200/55/D190

65

65

380

350

240

940

100

410

1400

570

1300

1280

1294

1882

FHF40-200/75/D209

65

65

380

350

240

940

100

410

1400

570

1300

1280

1294

1882

FHF40-250/110A/D218

65

65

420

370

180

1145

100

380

1400

610

1400

1425

1309

1897

FHF40-250/110/D233

65

65

420

370

280

1225

100

430

1400

610

1400

1605

1359

1947

FHF40-250/150/D251

65

65

420

370

280

1225

100

430

1400

610

1400

1605

1359

1947

FHF50-125/22/D119

65

80

320

310

240

850

100

382

1400

470

1100

1190

1345

1939

FHF50-125/30/D130

65

80

320

310

240

850

100

382

1400

470

1100

1190

1345

1939

FHF50-125/40/D139

65

80

380

350

240

910

100

382

1400

570

1300

1250

1345

1939

FHF50-160/55/D158

65

80

380

350

240

940

100

410

1400

570

1300

1280

1393

1987

FHF50-160/75/D174

65

80

380

350

240

940

100

410

1400

570

1300

1280

1393

1987

FHF50-200/110A/D197

65

80

420

370

110

1080

100

410

1400

610

1400

1290

1413

2007

FHF50-200/110/D209

65

80

420

370

110

1080

100

460

1400

610

1400

1290

1463

2057

FHF50-250/150/D224

65

80

420

370

280

1225

100

430

1400

610

1400

1605

1458

2052

FHF50-250/185/D237

65

80

420

370

280

1275

100

480

1550

610

1400

1655

1508

2102

FHF50-250/220/D250

65

80

420

370

280

1275

100

480

1550

610

1400

1655

1508

2102

FHF65-125/40/D121

80

100

380

350

240

895

100

410

1400

570

1300

1235

1465

2072

FHF65-125/55/D129

80

100

380

350

240

925

100

410

1400

570

1300

1265

1465

2072

FHF65-125/75/D140

80

100

380

350

240

925

100

410

1400

570

1300

1265

1465

2072

FHF65-160/110A/D161

80

100

420

370

180

1145

100

410

1400

610

1400

1425

1485

2092

FHF65-160/110/D168

80

100

420

370

280

1225

100

460

1400

610

1400

1605

1535

2142

FHF65-160/150/D178

80

100

420

370

280

1225

100

460

1400

610

1400

1605

1535

2142

FHF65-200/150/D187

80

100

420

370

280

1225

100

430

1400

610

1400

1605

1530

2137

FHF65-200/185/D198

80

100

420

370

280

1275

100

480

1550

610

1400

1655

1580

2187

FHF65-200/220/D210

80

100

420

370

280

1275

100

480

1550

610

1400

1655

1580

2187

FHF65-250/220/D220

80

100

420

370

280

1260

100

460

1550

610

1400

1640

1585

2192

FHF65-250/300/D241

80

100

480

450

280

1450

100

480

1750

730

1660

1830

1605

2212

FHF65-250/370/D258

80

100

480

450

280

1450

100

480

1750

730

1660

1830

1605

2212

FHF80-160/150/D163

100

125

420

370

280

1225

125

430

1400

610

1400

1630

1614

2234

FHF80-160/185/D173

100

125

420

370

280

1275

125

480

1550

610

1400

1680

1664

2284

FHF80-200/220/D189

100

125

420

370

280

1275

125

480

1550

610

1400

1680

1689

2309

FHF80-200/300/D207

100

125

480

450

280

1415

125

480

1750

730

1660

1820

1689

2309

FHF80-250/370/D225

100

125

480

450

280

1450

125

480

1750

730

1660

1855

1719

2339

FHF80-250/450/D238

100

125

480

450

320

1450

125

485

1940

730

1660

1895

1724

2344

FHF80-250/550/D256
2
100
Dimensions in mm. Tolerance 10 mm.

125

480

450

320

1505

125

530

1960

730

1660

1950

1769

2389

gen10d_fhf-en_g_td

71

GEN..D/FHF

GEN..10D/FHF 32-80 SERIES


FIRE-FIGHTING BOOSTER SETS EN 12845

72

GEN..D/FHF

Fire-fighting
booster sets
EN 12845

MARKET SECTORS
CIVIL, INDUSTRIAL
APPLICA
TIONS
APPLICATIONS
Fixed fire-fighting systems.
Automatic Sprinkler systems.

GEN..D/FHF

GEN..11D/FHF
Series

SPECIFICA
TIONS
SPECIFICATIONS
Flow up to 1300 m3/h.
Head up to 100 m.
Panel supply power voltage:

- Electric pump: 3 x 400V 10%.


- Diesel engine pump: 1 x 230V
10%.

Frequency: 50 Hz.
Voltage for controls outside panel:
12 - 24 Vac.

Electric motor start :

- Direct start for powers up to 22 kW


included for pump (GEND...).
- Star/delta start for higher powers
(GENY... set).
Diesel engine with battery start.

Service pump in

horizontal design
design:
- FHF series (IP55 electric motor
protection).

ey pump
jockey
Electric jock

Protection grade:

- electric panel: IP54.

Electric pumps maximum power


132 kW.

73

with vertical axis


axis:
- SV Series (motor protection
grade IP55).

Maximum running pressure: 12 bar.

GEN..D/FHF

GEN..11D/FHF 32-80 SERIES


FIRE-FIGHTING BOOSTER SETS EN 12845

For the overall dimensions of the fuel tank and the starting batteries, see tables on pages 20-25.

74

GEN..11D/FHF 32-80 SERIES


FIRE-FIGHTING BOOSTER SETS EN 12845
GEN..11D

DRW DNA DNP DNM

A1

I1

FHF32-125/07/D119

R 2"

Rp 1"

R 2" 305 295 240

905

80

225

362 1400 400

400 1400 1225 1019 1599

FHF32-125/11/D136

R 2"

Rp 1"

R 2" 305 295 240

905

80

225

362 1400 400

400 1400 1225 1019 1599

FHF32-160/15/D150

R 2"

Rp 1"

R 2" 305 295 240

850

80

225

382 1400 400

400 1400 1170 1059 1639

FHF32-160/22/D164

R 2"

Rp 1"

R 2" 305 295 240

850

80

225

382 1400 400

400 1400 1170 1059 1639

FHF32-200/30/D188

R 2"

Rp 1"

R 2" 305 295 240

850

80

225

360 1400 400

400 1400 1170 1057 1637

FHF32-200/40/D204

R 2"

Rp 1"

R 2" 400 375 240 1005

80

225

410 1400 475

430 1680 1325 1107 1687

FHF40-125/11/D112

65

Rp 1"

65

305 295 240

850

80

225

362 1400 400

400 1400 1170 1206 1794

FHF40-125/15/D122

65

Rp 1"

65

305 295 240

850

80

225

362 1400 400

400 1400 1170 1206 1794

FHF40-125/22/D143

65

Rp 1"

65

305 295 240

850

80

225

362 1400 400

400 1400 1170 1206 1794

FHF40-160/30/D159

65

Rp 1"

65

305 295 240

850

80

225

382 1400 400

400 1400 1170 1246 1834

FHF40-160/40/D171

65

Rp 1"

65

305 295 240

850

80

225

382 1400 400

400 1400 1170 1246 1834

FHF40-200/55/D190

65

Rp 1"

65

400 375 240

940

100

225

410 1400 475

430 1680 1280 1294 1882

FHF40-200/75/D209

65

Rp 1"

65

400 375 240

940

100

225

410 1400 475

430 1680 1280 1294 1882

FHF40-250/110A/D218

65

Rp 1"

65

365 355 180

995

100

225

380 1400 475

475 1670 1275 1309 1897

FHF40-250/110/D233

65

Rp 1"

65

375 385 280

995

100

225

430 1400 475

475 1710 1375 1359 1947

FHF40-250/150/D251

65

Rp 1"

65

375 385 280

995

100

225

430 1400 475

475 1710 1375 1359 1947

FHF50-125/22/D119

65

Rp 1"

80

305 295 240

850

100

225

382 1400 400

400 1400 1190 1345 1939

FHF50-125/30/D130

65

Rp 1"

80

305 295 240

850

100

225

382 1400 400

400 1400 1190 1345 1939

FHF50-125/40/D139

65

Rp 1"

80

400 375 240 1005 100

225

382 1400 475

430 1680 1345 1345 1939

FHF50-160/55/D158

65

Rp 1"

80

400 375 240

940

100

225

410 1400 475

430 1680 1280 1393 1987

FHF50-160/75/D174

65

Rp 1"

80

400 375 240

940

100

225

410 1400 475

430 1680 1280 1393 1987

FHF50-200/110A/D197

65

Rp 1"

80

385 345 110

895

100

225

410 1400 475

475 1680 1105 1413 2007

FHF50-200/110/D209

65

Rp 1"

80

385 345 205

895

100

225

460 1400 475

475 1680 1200 1463 2057

FHF50-250/150/D224

65

Rp 1"

80

375 385 280

995

100

225

430 1400 475

475 1710 1375 1458 2052

FHF50-250/185/D237

65

Rp 1"

80

400 395 280

995

100

225

480 1550 475

475 1745 1375 1508 2102

FHF50-250/220/D250

65

Rp 1"

80

400 395 280

995

100

225

480 1550 475

475 1745 1375 1508 2102

FHF65-125/40/D121

80

Rp 1"

100 400 375 240

895

100

225

410 1400 475

430 1680 1235 1465 2072

FHF65-125/55/D129

80

Rp 1"

100 400 375 240

925

100

225

410 1400 475

430 1680 1265 1465 2072

FHF65-125/75/D140

80

Rp 1"

100 400 375 240

925

100

225

410 1400 475

430 1680 1265 1465 2072

FHF65-160/110A/D161

80

Rp 1"

100 365 355 180

995

100

225

410 1400 475

475 1670 1275 1485 2092

FHF65-160/110/D168

80

Rp 1"

100 375 385 280

995

100

225

460 1400 475

475 1710 1375 1535 2142

FHF65-160/150/D178

80

Rp 1"

100 375 385 280

995

100

225

460 1400 475

475 1710 1375 1535 2142

FHF65-200/150/D187

80

Rp 1"

100 375 385 280

995

100

225

430 1400 475

475 1710 1375 1530 2137

FHF65-200/185/D198

80

Rp 1"

100 400 395 280

995

100

225

480 1550 475

475 1745 1375 1580 2187

FHF65-200/220/D210

80

Rp 1"

100 400 395 280

995

100

225

480 1550 475

475 1745 1375 1580 2187

FHF65-250/220/D220

80

Rp 1"

100 400 395 370

980

100

225

460 1550 475

475 1745 1450 1585 2192

FHF65-250/300/D241

80

Rp 1"

100 470 435 290 1160 100

195

480 1750 530

490 1925 1550 1605 2212

FHF65-250/370/D258

80

Rp 1"

100 470 435 290 1160 100

195

480 1750 530

490 1925 1550 1605 2212

FHF80-160/150/D163

100

Rp 1"

125 375 385 280

995

125

225

430 1400 475

475 1710 1400 1614 2234

FHF80-160/185/D173

100

Rp 1"

125 400 395 280

995

125

225

480 1550 475

475 1745 1400 1664 2284

FHF80-200/220/D189

100

Rp 1"

125 400 395 330

995

125

225

480 1550 475

475 1745 1450 1689 2309

FHF80-200/300/D207

100

Rp 1"

125 470 435 300 1125 125

195

480 1750 530

490 1925 1550 1689 2309

FHF80-250/370/D225

100

Rp 1"

125 470 435 280 1160 125

195

480 1750 530

490 1925 1565 1719 2339

FHF80-250/450/D238

100

Rp 1"

125 470 395 320 1205 125

195

485 1940 530

490 1885 1650 1724 2344

FHF80-250/550/D256
2 100 Rp 1"
Dimensions in mm. Tolerance 10 mm.

125 485 455 355 1270 125

215

530 1960 530

530 2000 1750 1769 2389


gen11d_fhf-en_g_td

75

GEN..D/FHF

GEN..D/FHF

GEN..11D/FHF 100-125 SERIES


FIRE-FIGHTING BOOSTER SETS EN 12845

For the overall dimensions of the fuel tank and the starting batteries, see tables on pages 20-25.

76

GEN..11D/FHF 100-125 SERIES


FIRE-FIGHTING BOOSTER SETS EN 12845
GEN..11D

DRW DNA DNP DNM

A1

I1

N
2

125

Rp 1"

150

400 395 265 1020 125 225 448 1550 475

FHF100-160/220/D165

125

Rp 1"

150

400 395 340

125 225 498 1550 475

475 1745 1450 1837 2471

FHF100-160/300/D185

125

Rp 1"

200

470 395 280 1175 125 195 468 1750 530

490 1885 1580 1833 2492

FHF100-200/185/D168

125

Rp 1"

150

400 395 300 1025 125 225 473 1550 475

475 1745 1450 1812 2446

FHF100-200/300/D192

125

Rp 1"

150

470 395 265 1175 125 195 493 1750 530

490 1885 1565 1832 2466

FHF100-200/370/D203

125

Rp 1"

150

470 395 280 1225 125 195 493 1750 530

490 1885 1630 1832 2466

FHF100-200/450/D213

125

Rp 1"

200

450 460 320 1405 125 195 488 1750 530

530 1970 1850 1853 2512

FHF100-250/300/D200

125

Rp 1"

150

470 395 320 1225 140 195 468 1750 530

490 1885 1685 1807 2441

FHF100-250/450/D221

125

Rp 1"

200

470 395 320 1225 140 195 468 1750 530

490 1885 1685 1833 2492

FHF100-250/550/D235

125

Rp 1"

200

450 460 320 1405 140 195 513 1750 530

530 1970 1865 1878 2537

FHF100-250/750/D254

125

Rp 1"

200

550 545 570 1340 140 215 513

570

570 2235 2050 1878 2537

FHF100-250/900/D267

125

Rp 1"

200

550 545 570 1340 140 215 513

570

570 2235 2050 1878 2537

FHF125-200/300/D180

150

Rp 1"

200

470 395 360 1150 140 200 493 1750 530

490 1885 1650 2011 2670

FHF125-200/450/D206

150

Rp 1"

200

450 460 320 1405 140 200 463 1750 530

530 1970 1865 1981 2640

FHF125-200/550/D216

150

Rp 1"

200

450 460 320 1405 140 200 513 1940 530

530 1970 1865 2031 2690

FHF125-270/750/D223

150

Rp 1"

250

550 555 545 1415 140 220 563

570

570 2245 2100 2148 2834

FHF125-270/900/D237

150

Rp 1"

250

550 555 620 1340 140 220 563

570

570 2245 2100 2148 2834

FHF125-270/1100/D253

150

Rp 1"

250

600 615 642 1340 140 220 618

620

640 2475 2122 2203 2889

FHF125-270/1320/D266 3 150 Rp 1"


Dimensions in mm. Tolerance 10 mm.

250

600 615 642 1340 140 220 618

620

640 2475 2122 2203 2889

985

475 1745 1410 1787 2421

gen11d_fhf100-en_f_td

77

GEN..D/FHF

FHF100-160/185/D150

78

GEN..D/FHF

GEN..D/FHF SERIES OF BOOSTER SETS (POSITIVE SUCTION HEAD)


Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

0
0

20

40

20

ISO 9906 - Annex A

60

40

80

60

80

Q [US gpm]
120

100

0,25

20

40

20

ISO 9906 - Annex A

60

40

Q
[Imp gpm]
100

80

60

80

Q [US gpm]
120

100

0,25

0,8

H [ft]

Hc [m]

0,8

Hc [m]

2900 [rpm]

FH 32 - 160

Q [Imp gpm]
100

0,20

H [ft]

FH 32 - 125

0,20
0,6

0,6

0,15

0,15
0,4

0,4

0,10

0,10

0,2

0,2

0,05

0,05

0,00
6

0,0

0,00
10

0,0

8
15

25

4
NPSHr [m]

NPSHr [ft]

NPSHr [m]

15
4

NPSHr [ft]

20

6
10

10
5
2

0
0

10
100

15
200

20
20

25

300

40
40

60
60

0
0
0

ISO 9906 - Annex A


80

80

Q [m3/h]
30
Q [l/min]
500

400

2900 [rpm]

FH 32 - 200
0

20

100

10
100

15
200

100

Q120
[Imp gpm]

Q [US gpm]
140

400

100

Q [l/min]
500

ISO 9906 - Annex A


150

100

Q [m3/h]
30

150

200

Q [Imp gpm]

Q [US
250 gpm]

200

0,4

1,5

H [ft]

H [ft]

1,5

Hc [m]

0,5

Hc [m]

0,5

50
50

25

300

2900 [rpm]

FH 40 - 125

120

20

76475_A_CH

76474_A_CH

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5

0,1

0,1

0,0
10

0,0

0,0
15

0,0

30
40

8
25
10

20

NPSHr [ft]

NPSHr [m]

15
4

NPSHr [ft]

NPSHr [m]

30

20

10

10

0
0
0

10
100

15
200

20
300

25
400

30

Q [m3/h]
35

500

Q [l/min]

0
0
0

10
200

20

30
400

40
600

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

79

50
800

Q [m3/h]
60
Q 1000
[l/min]

76477_A_CH

76476_A_CH

GEN..D/FHF

30

GEN..D/FHF SERIES OF BOOSTER SETS (POSITIVE SUCTION HEAD)


Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

FH 40 - 160
0
0

50

100

50

ISO 9906 - Annex A


150

100

150

200

Q [US
250 gpm]

200

2900 [rpm]

FH 40 - 200

Q [Imp gpm]

50

0,5

ISO 9906 - Annex A

100

50

150

100

150

200

Q [Imp gpm]

Q [US
250 gpm]

200

0,4

H [ft]

Hc [m]

1,5

H [ft]

Hc [m]

0,6

0,5
1,5
0,4

1,0

0,3

1,0

0,3
0,2
0,2

0,5

0,5
0,1

0,1

0,0

0,0
15

0,0

40

40

10

10

20
5

0
0
0

10

20

200

30
400

50

100

50

50

600

Q 1000
[l/min]

0
0

150

200

20

200

30

Q [Imp gpm]

50

600

100

Q 1000
[l/min]

ISO 9906 - Annex A

200

100

Q [m3/h]
60

800

2900 [rpm]

0
0

40

400

FH 50 - 125

Q [US
250 gpm]

200

10

ISO 9906 - Annex A


150

100

Q [m3/h]
60

800

2900 [rpm]

FH 40 - 250
0

40

76456_A_CH

10

76478_A_CH

10

Q [Imp gpm]

300

200

300

400

Q [US gpm]

Hc [m]

H [ft]
0,5

1,5

H [ft]

0,5

0,6
Hc [m]

NPSHr [ft]

NPSHr [m]

20

30
NPSHr [ft]

NPSHr [m]

30

0,4
1,5

0,4
1,0

0,3
1,0

0,3

0,2
0,2

0,5
0,5
0,1

0,1

0,0
15

0,0

0,0
15

0,0

40

40

10

10

20

NPSHr [ft]

NPSHr [ft]

20

30
NPSHr [m]

30
NPSHr [m]

0
0
0

10
200

20

30
400

40
600

50
800

Q [m3/h]
60
Q 1000
[l/min]

10

0
0
0

20
200

40
400

600

60
800

1000

80
1200

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

80

1400

Q [m3100
/h]
1600
Q [l/min]

76481_A_CH

10

76457_A_CH

GEN..D/FHF

0,0
15

GEN..D/FHF SERIES OF BOOSTER SETS (POSITIVE SUCTION HEAD)


Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

FH 50 - 160
0

100

ISO 9906 - Annex A

200

100

300

200

300

400

2900 [rpm]

FH 50 - 200

Q [Imp gpm]

Q [US gpm]

100

100

300

200

400

300

Q [Imp gpm]

Q
[US gpm]
500

400

0,4

1,5
0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5
0,1

0,0
15

0,0

0,0
15

0,0

40

40

10

10

20

NPSHr [ft]

NPSHr [m]

20

30
NPSHr [ft]

NPSHr [m]

30

0
0
0

20
200

40
400

600

800

80

1000

1200

2900 [rpm]

FH 50 - 250
0

60

100

200

100

1400

Q
1600
[l/min]

0
0

300

400

40

60

500

Q [Imp gpm]

0
0

100
1500

2900 [rpm]

100

200

100

300

Q [l/min]
2000

ISO 9906 - Annex A

300

200

3
Q [m120
/h]

Q
[Imp gpm]
500

400
400

Q [US
600 gpm]

500

H [ft]
0,5

H [ft]

0,6
Hc [m]

0,6

80

1000

FH 65 - 125

Q
[US gpm]
500

400

20

ISO 9906 - Annex A


300

200

3
Q [m100
/h]

76483_A_CH

10

76482_A_CH

10

0,5

1,5

1,5

0,4

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5

0,1

0,1

0,0
15

0,0

0,0
15

0,0

40

40

10

10

20

NPSHr [ft]

NPSHr [m]

20

30
NPSHr [ft]

NPSHr [m]

30

0
0
0

20

40
500

60
1000

80

100
1500

3
Q [m120
/h]

0
0

Q [l/min]
2000

20

40
500

60
1000

80

100
1500

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

81

120

0
3
Q [m140
/h]

2000

Q [l/min]

76485_A_CH

10

76484_A_CH

10

GEN..D/FHF

0,1

Hc [m]

H [ft]

H [ft]

1,5

Hc [m]

0,5

Hc [m]

0,5

200

ISO 9906 - Annex A

GEN..D/FHF SERIES OF BOOSTER SETS (POSITIVE SUCTION HEAD)


Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

FH 65 - 160
0
0

100
100

200
200

ISO 9906 - Annex A

300
300

400
400

500

500

Q [US
gpm]
700

600

100

200

100

ISO 9906 - Annex A

300

200

300

400
400

Q [Imp gpm]

500

500

Q [US
gpm]
700

600

H [ft]
0,5

H [ft]

0,6
Hc [m]

0,6

0,5

1,5

1,5

0,4

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5

0,1

0,1

0,0

0,0
15

0,0

40

40

10

10

20

187

65-160/150
178

20

5
65-200/220
65-200/185

178

0
0

20

40

500

60
1000

100
100

100

120

1500

200
200

400
400

3
Q [m160
/h]

0
0

2500
Q [l/min]

500

500

600

198

10

ISO 9906 - Annex A

300
300

140

2000

2900 [rpm]

FH 65 - 250
0

80

210

10

20

40
500

60
1000

Q [Imp gpm]

0
0

1500

120

200
200

400
400

140

2000

2500
Q [l/min]

ISO 9906 - Annex A


600

600

0
3
Q [m160
/h]

Q [Imp gpm]

800
800

1000

Q [US gpm]

0,5
H [ft]

Hc [m]

0,6

100

2900 [rpm]

FH 80 - 160

Q [US
gpm]
700

80

76487_A_CH

168

76486_A_CH

65-160/150
65-160/110

Hc [m]

65-200/150

NPSHr [ft]

65-160/150
178

30
NPSHr [ft]

NPSHr [m]

161

NPSHr [m]

30
65-160/110A

0,5

1,5
0,4

1,5
0,4
1,0

0,3
1,0

0,3

0,2
0,2

0,5
0,5
0,1

0,1

0,0
15

0,0

0,0
15

0,0

40

40

10

10

65-160/150
178

20

NPSHr [ft]

20

NPSHr [ft]

65-160/150
178

30
NPSHr [m]

30
NPSHr [m]

0
0
0

20

40
500

60
1000

80

100
1500

120
2000

140

3
Q [m160
/h]

2500
Q [l/min]

10

0
0
0

50
1000

100

150
2000

200
3000

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

82

3
Q [m250
/h]

Q 4000
[l/min]

76489_A_CH

10

76488_A_CH

GEN..D/FHF

0,0
15

H [ft]

Hc [m]

2900 [rpm]

FH 65 - 200

Q [Imp gpm]

GEN..D/FHF SERIES OF BOOSTER SETS (POSITIVE SUCTION HEAD)


Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

FH 80 - 200
0

200

ISO 9906 - Annex A

400

200

600

400

600

800
800

1000

2900 [rpm]

FH 80 - 250

Q [Imp gpm]

Q [US gpm]

200

400

200

600

400

600

Q [Imp gpm]

800

1000 Q [US gpm]

800

0,4

1,5

H [ft]

H [ft]

1,5

Hc [m]

0,5

Hc [m]

0,5

ISO 9906 - Annex A

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5
0,1

0,0
15

0,0

0,0
15

0,0

40

40

10

10

80-250/370

225

65-160/150
178

20

NPSHr [ft]

20

NPSHr [m]

65-160/150
178

30
NPSHr [ft]

NPSHr [m]

30

5
80-250/550
80-250/450

256
238

0
50

100

1000

3000

2900 [rpm]

200
200

400
400

600
600

Q 4000
[l/min]

0
0

1000

1000

1400

1600 Q [US gpm]

0,25

150

1000

2000

3000

2900 [rpm]

200
200

400
400

600
600

0
3
Q [m250
/h]

200

ISO 9906 - Annex A

800
800

Q 4000
[l/min]

1000

1000

Q
[Imp gpm]
1400

1200

1200

1400

1600 Q [US gpm]

0,25

0,8

H [ft]

Hc [m]

0,8

Hc [m]

100

FH 100 - 200

Q
[Imp gpm]
1400

1200

1200

50

ISO 9906 - Annex A

800
800

3
Q [m250
/h]

200

2000

FH 100 - 160
0

150

0,20

H [ft]

76491_A_CH

10

76490_A_CH

10

0,20
0,6

0,6

0,15

0,15
0,4

0,4

0,10

0,10

0,2

0,2

0,05

0,05

0,00
15

0,0

100-160/185

0,00
15

0,0

40

135/165

100-200/185

10

40

141/195

10

65-160/150
178

20

65-160/150
178
100-200/450
100-200/370
100-200/300

213
203
189/195

0
0

50
1000

100

150
2000

200
3000

250
4000

300
5000

350
6000

0
3
Q [m400
/h]
Q [l/min]

10

76492_A_CH

10

20

NPSHr [ft]

159/171

30

0
0
0

50
1000

100

150
2000

200
3000

250
4000

300
5000

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

83

350
6000

0
3
Q [m400
/h]
Q [l/min]

76493_A_CH

185

NPSHr [m]

100-160/300
100-160/220

NPSHr [ft]

NPSHr [m]

30

GEN..D/FHF

0,1

GEN..D/FHF SERIES OF BOOSTER SETS (POSITIVE SUCTION HEAD)


Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

500

ISO 9906 - Annex A

1000

500

1000

Q [US gpm]

1500

0,25

2900 [rpm]

FH 125 - 200

1500 Q [Imp gpm]

500
500

1000
1000

ISO 9906 - Annex A

1500
1500

Q2500
[Imp gpm]

2000
2000

Q3000
[US gpm]

2500

0,25

0,8

Hc [m]

H [ft]

Hc [m]

0,8

0,20

H [ft]

FH 100 - 250

0,20
0,6

0,6

0,15

0,15
0,4

0,4

0,10

0,10

0,2

0,2

0,05

0,05

0,00
15

0,0

0,00
15

0,0

162/194

40

10
200

30

20

125-200/550
125-200/450

NPSHr [m]

65-160/150
178

NPSHr [ft]

NPSHr [m]

100-250/300

30

216
205

65-160/150
178

20

NPSHr [ft]

10

5
267
254

10

221

0
0

100

200
2000

6000

2900 [rpm]

500
500

1000
1000

Q [l/min]

0
0
0

100
2000

200

300
4000

400
6000

500
8000

ISO 9906 - Annex A

1500
1500

0
3
Q [m500
/h]

400

4000

FH 125 - 270

300

10

2000
2000

2500

2500

Q [Imp gpm]

3000

Q [US
3500gpm]

0,25

H [ft]

Hc [m]

0,8

0,20
0,6
0,15
0,4
0,10

0,2
0,05

0,00
20

0,0

60

50

15

125-270/750

216/230

125-270/1320 266
65-160/150
125-270/1100 253
178
125-270/900 237

30

NPSHr [ft]

40
10

20
5

0
0
0

100
2000

200

300
4000

400
6000

500
8000

600
10000

700

0
3
Q [m800
/h]

12000

Q [l/min]

76496_A_CH

10

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

84

600
10000

0
3
Q [m700
/h]
Q [l/min]

76495_A_CH

235

76494_A_CH

100-250/900
100-250/750
100-250/550
100-250/450

NPSHr [m]

GEN..D/FHF

125-200/300

40

GEN..D/FHF SERIES OF BOOSTER SETS (SUCTION LIF


T)
LIFT)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

FH 32 - 125
0
0

20

40

20

ISO 9906 - Annex A

60

40

80

60

80

Q [US gpm]
120

100

2900 [rpm]

FH 32 - 160

Q [Imp gpm]
100

0,5

20

40

20

ISO 9906 - Annex A

60

40

Q
[Imp gpm]
100

80

60

80

Q [US gpm]
120

100

0,4

H [ft]

Hc [m]

1,5

H [ft]

Hc [m]

0,6

0,5
1,5
0,4

1,0

0,3

1,0

0,3
0,2
0,2

0,5

0,5
0,1

0,1

0,0
6

0,0

0,0
10

0,0

8
15

25

4
NPSHr [m]

NPSHr [ft]

NPSHr [m]

15
4

NPSHr [ft]

20

6
10

10
5
2

0
0

10
100

15
200

20
20

25

300

40
40

60
60

100

10
100

15
200

100

Q120
[Imp gpm]

120

Q [US gpm]
140

20

50

100

50

25

300

400

2900 [rpm]

FH 40 - 125

Q [l/min]
500

ISO 9906 - Annex A


150

100

Q [m3/h]
30

150

200

Q [Imp gpm]

Q [US
250 gpm]

200

H [ft]
0,5

H [ft]

0,6
Hc [m]

0,6
Hc [m]

0
0

ISO 9906 - Annex A


80

80

Q [m3/h]
30
Q [l/min]
500

400

2900 [rpm]

FH 32 - 200
0

20

76452_A_CH

76451_A_CH

0,5

1,5

1,5

0,4

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5

0,1

0,1

0,0
10

0,0

0,0
15

0,0

30
40

8
25
10

20

NPSHr [ft]

NPSHr [m]

15
4

NPSHr [ft]

NPSHr [m]

30

20

10

10

0
0
0

10
100

15
200

20
300

25
400

30

Q [m3/h]
35

500

Q [l/min]

0
0
0

10
200

20

30
400

40
600

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

85

50
800

Q [m3/h]
60
Q 1000
[l/min]

76454_A_CH

76453_A_CH

GEN..D/FHF

30

GEN..D/FHF SERIES OF BOOSTER SETS (SUCTION LIF


T)
LIFT)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

FH 40 - 160
0
0

50

100

50

ISO 9906 - Annex A


150

100

150

200

Q [US
250 gpm]

200

50

ISO 9906 - Annex A

100

50

150

100

150

200

Q [Imp gpm]

Q [US
250 gpm]

200

H [ft]
0,5

H [ft]

0,6
Hc [m]

0,6

0,5

1,5

1,5

0,4

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5

0,1

0,1

0,0

0,0
15

0,0

40

40

10

10

20
5

0
0
0

10

20

200

30
400

50

100

50

50

600

Q 1000
[l/min]

0
0

150

200

20

200

30

Q [Imp gpm]

600

100

800

Q 1000
[l/min]

ISO 9906 - Annex A

200

100

Q [m3/h]
60

Q [Imp gpm]

300

200

300

400

Q [US gpm]

H [ft]
0,5

H [ft]

0,6
Hc [m]

0,6

50

2900 [rpm]

0
0

40

400

FH 50 - 125

Q [US
250 gpm]

200

10

ISO 9906 - Annex A


150

100

Q [m3/h]
60

800

2900 [rpm]

FH 40 - 250
0

40

76456_A_CH

10

76455_A_CH

10

0,5

1,5

1,5

0,4

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5

0,1

0,1

0,0
15

0,0

0,0
15

0,0

40

40

10

10
NPSHr [ft]

20

30
NPSHr [m]

30

20

NPSHr [ft]

Hc [m]

NPSHr [ft]

NPSHr [m]

20

30
NPSHr [ft]

NPSHr [m]

30

NPSHr [m]

5
10

0
0
0

10
200

20

30
400

40
600

50
800

Q [m3/h]
60
Q 1000
[l/min]

10

76457_A_CH

GEN..D/FHF

0,0
15

0
0
0

20
200

40
400

600

60
800

1000

80
1200

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

86

1400

0
3
Q [m100
/h]
1600
Q [l/min]

76458_A_CH

Hc [m]

2900 [rpm]

FH 40 - 200

Q [Imp gpm]

GEN..D/FHF SERIES OF BOOSTER SETS (SUCTION LIF


T)
LIFT)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

FH 50 - 160
0

100

ISO 9906 - Annex A

200

100

300

200

300

400

Q [US gpm]

100

200

100

ISO 9906 - Annex A


300

200

400

300

Q [Imp gpm]

Q
[US gpm]
500

400

H [ft]
0,5

H [ft]

0,6
Hc [m]

0,6

0,5

1,5

1,5

0,4

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5
0,1

0,0
15

0,0

0,0
15

0,0

40

40

10

10

20
5

0
0

20
200

40
400

600

800

100

1000

200

100

1200

1400

Q
1600
[l/min]

0
0

300

400

40

60

500

Q [Imp gpm]

0
0

100
1500

2900 [rpm]

100

200

100

300

Q [l/min]
2000

ISO 9906 - Annex A

300

200

3
Q [m120
/h]

Q
[Imp gpm]
500

400
400

Q [US
600 gpm]

500

H [ft]
0,5

H [ft]

0,6
Hc [m]

0,6

80

1000

FH 65 - 125

Q
[US gpm]
500

400

20

ISO 9906 - Annex A


300

200

0
3
Q [m100
/h]

80

2900 [rpm]

FH 50 - 250
0

60

76473_A_CH

10

76459_A_CH

10

0,5

1,5

1,5

0,4

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5

0,1

0,1

0,0
15

0,0

0,0
15

0,0

40

40

10

10
NPSHr [m]

20

30
NPSHr [ft]

NPSHr [m]

30

20

NPSHr [ft]

Hc [m]

NPSHr [ft]

NPSHr [m]

20

30
NPSHr [ft]

NPSHr [m]

30

0
0
0

20

40
500

60
1000

80

100
1500

3
Q [m120
/h]

Q [l/min]
2000

10

76460_A_CH

10

0
0
0

20

40
500

60
1000

80

100
1500

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

87

120

0
3
Q [m140
/h]

2000

Q [l/min]

GEN..D/FHF

0,1

76461_A_CH

Hc [m]

2900 [rpm]

FH 50 - 200

Q [Imp gpm]

GEN..D/FHF SERIES OF BOOSTER SETS (SUCTION LIF


T)
LIFT)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

FH 65 - 160
0
0

100
100

200
200

ISO 9906 - Annex A

300
300

400
400

500

500

Q [US
gpm]
700

600

100

200

100

ISO 9906 - Annex A

300

200

300

400
400

Q [Imp gpm]

500

500

Q [US
gpm]
700

600

H [ft]
0,5

H [ft]

0,6
Hc [m]

0,6

0,5

1,5

1,5

0,4

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5

0,1

0,1

0,0

0,0
15

0,0

40

40

10

10

20

187

65-160/150
178

20

5
65-200/220
65-200/185

178

0
20

40

500

60
1000

100
100

100

120

1500

200
200

3
Q [m160
/h]

2500
Q [l/min]

0
0
0

ISO 9906 - Annex A

300
300

140

2000

2900 [rpm]

FH 65 - 250
0

80

400
400

500

500

600

198

10

0
0

210

10

20

40
500

60
1000

Q [Imp gpm]

0
0

1500

120

200
200

400
400

140

2000

2500
Q [l/min]

ISO 9906 - Annex A


600

600

0
3
Q [m160
/h]

Q [Imp gpm]

800
800

1000

Q [US gpm]

H [ft]
0,5

H [ft]

0,6
Hc [m]

0,6

100

2900 [rpm]

FH 80 - 160

Q [US
gpm]
700

80

76463_A_CH

168

76462_A_CH

65-160/150
65-160/110

0,5

1,5

1,5

0,4

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5

0,1

0,1

0,0
15

0,0

0,0
15

0,0

40

40

10

10

20

NPSHr [ft]

65-160/150
178

30
NPSHr [m]

30

65-160/150
178

20

NPSHr [ft]

Hc [m]

65-200/150

NPSHr [ft]

65-160/150
178

30
NPSHr [ft]

NPSHr [m]

161

NPSHr [m]

30
65-160/110A

NPSHr [m]

5
10

0
0
0

20

40
500

60
1000

80

100
1500

120
2000

140

3
Q [m160
/h]

2500
Q [l/min]

10

76464_A_CH

GEN..D/FHF

0,0
15

0
0
0

50
1000

100

150
2000

200
3000

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

88

3
Q [m250
/h]

Q 4000
[l/min]

76465_A_CH

Hc [m]

2900 [rpm]

FH 65 - 200

Q [Imp gpm]

GEN..D/FHF SERIES OF BOOSTER SETS (SUCTION LIF


T)
LIFT)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

FH 80 - 200
0

200

ISO 9906 - Annex A

400

200

600

400

600

800
800

1000

Q [US gpm]

200

ISO 9906 - Annex A

400

200

600

400

600

Q [Imp gpm]

800

1000 Q [US gpm]

800

H [ft]
0,5

H [ft]

0,6
Hc [m]

0,6

0,5

1,5

1,5

0,4

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5
0,1

0,0
15

0,0

0,0
15

0,0

40

40

10

10

80-250/370

225

65-160/150
178

20

NPSHr [ft]

20

NPSHr [m]

65-160/150
178

30
NPSHr [ft]

NPSHr [m]

30

5
80-250/550
80-250/450

256
238

0
50

100

1000

3000

2900 [rpm]

200
200

400
400

600
600

Q 4000
[l/min]

0
0

1000

1000

1400

1600 Q [US gpm]

0,25

150

1000

2000

3000

2900 [rpm]

200
200

400
400

600
600

0
3
Q [m250
/h]

200

ISO 9906 - Annex A

800
800

Q 4000
[l/min]

1000

1000

Q
[Imp gpm]
1400

1200

1200

1400

1600 Q [US gpm]

0,25

0,8

H [ft]

Hc [m]

0,8

Hc [m]

100

FH 100 - 200

Q
[Imp gpm]
1400

1200

1200

50

ISO 9906 - Annex A

800
800

3
Q [m250
/h]

200

2000

FH 100 - 160
0

150

0,20

H [ft]

76467_A_CH

10

76466_A_CH

10

0,20
0,6

0,6

0,15

0,15
0,4

0,4

0,10

0,10

0,2

0,2

0,05

0,05

0,00
15

0,0

100-160/185

0,00
15

0,0

40

135/165

100-200/185

10

40

141/195

10

159/171

65-160/150
178

20

30

65-160/150
178
100-200/450
100-200/370
100-200/300

213
203
189/195

0
0

50
1000

100

150
2000

200
3000

250
4000

300
5000

350
6000

0
3
Q [m400
/h]
Q [l/min]

10

76468_A_CH

10

20

NPSHr [ft]

185

NPSHr [m]

100-160/300
100-160/220

NPSHr [ft]

NPSHr [m]

30

0
0
0

50
1000

100

150
2000

200
3000

250
4000

300
5000

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

89

350
6000

0
3
Q [m400
/h]
Q [l/min]

GEN..D/FHF

0,1

76469_A_CH

Hc [m]

2900 [rpm]

FH 80 - 250

Q [Imp gpm]

GEN..D/FHF SERIES OF BOOSTER SETS (SUCTION LIF


T)
LIFT)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

500

ISO 9906 - Annex A

1000

500

1000

Q [US gpm]

1500

0,25

2900 [rpm]

FH 125 - 200

1500 Q [Imp gpm]

500
500

1000
1000

ISO 9906 - Annex A

1500
1500

Q2500
[Imp gpm]

2000
2000

Q3000
[US gpm]

2500

0,25

0,8

Hc [m]

H [ft]

Hc [m]

0,8

0,20

H [ft]

FH 100 - 250

0,20
0,6

0,6

0,15

0,15
0,4

0,4

0,10

0,10

0,2

0,2

0,05

0,05

0,00
15

0,0

0,00
15

0,0

162/194

40

10
200

30

20

125-200/550
125-200/450

NPSHr [m]

65-160/150
178

NPSHr [ft]

NPSHr [m]

100-250/300

30

216
205

65-160/150
178

20

NPSHr [ft]

10

5
267
254

10

221

0
0

100

200
2000

6000

2900 [rpm]

500
500

1000
1000

Q [l/min]

0
0
0

100
2000

200

300
4000

400
6000

500
8000

ISO 9906 - Annex A

1500
1500

0
3
Q [m500
/h]

400

4000

FH 125 - 270

300

10

2000
2000

2500

2500

Q [Imp gpm]

3000

Q [US
3500gpm]

0,25

H [ft]

Hc [m]

0,8

0,20
0,6
0,15
0,4
0,10

0,2
0,05

0,00
20

0,0

60

50

15

125-270/750

216/230

125-270/1320 266
65-160/150
125-270/1100 253
178
125-270/900 237

30

NPSHr [ft]

40
10

20
5

0
0
0

100
2000

200

300
4000

400
6000

500
8000

600
10000

700

0
3
Q [m800
/h]

12000

Q [l/min]

76472_A_CH

10

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

90

600
10000

0
3
Q [m700
/h]
Q [l/min]

76471_A_CH

235

76470_A_CH

100-250/900
100-250/750
100-250/550
100-250/450

NPSHr [m]

GEN..D/FHF

125-200/300

40

GEN..D/SHF Series
Fire-fighting booster sets EN 12845,
electric pumps SHF series with high efficiency
motors and diesel engine pumps

GEN..D/SHF

50 Hz

91

92

GEN..D/SHF

RANGE
GEN..D/SHF RANGE
The range of EN 12845 fire-fighting booster sets with diesel and
electric service pumps and optional jockey pump to adapt to the
specific needs of every application.

D.. DIESEL ENGINE PUMP

Single fire-fighting centrifugal


pump in horizontal design with
stainless steel casing, SHF series.

Head up to 100 m.
Flow up to 220 m3/h.

GEN..00D SERIES

Fire-fighting sets with diesel engine


centrifugal service pump, in
horizontal design with stainless
steel casing, SHF series.

Head up to 100 m.
Flow up to 220 m3/h.

Fire-fighting sets with diesel engine


service pump and electric jockey
pump. The centrifugal service pump
has horizontal design and stainless
steel casing. SHF series.

Head up to 100 m.
Flow up to 220 m3/h.

GEN..10D SERIES

Fire-fighting sets with diesel engine


centrifugal service pump. The
centrifugal service pump has
horizontal design and stainless steel
casing. SHF series.

Head up to 100 m.
Flow up to 440 m3/h.

GEN..11D SERIES

Fire-fighting sets with diesel engine


service pump, electric service pump
and electric jockey pump. The
centrifugal service pump has
horizontal design and stainless steel
casing. SHF series.

93

Head up to 100 m.
Flow up to 440 m3/h.

GEN..D/SHF

GEN..01D SERIES

GEN..D/SHF BOOSTER SETS SERIES


TABELLA DI PRESTAZIONI IDRAULICHE SERIE 1SV 3SV 5SV 2p 50 Hz
HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (JOCKEY PUMP)
HYDRAULIC
TABLE
AT
PUMP

NOMINAL

TYPE

POWER

Q = DELIVERY
l/min 0

12

20

25

30

35

40

m /h 0

0,7

1,2

1,5

1,8

2,1

2,4

12,2
18,0
23,7
29,3
34,8
40,2
48,1
53,7
59,4
65,1
73,3
79,2
90,9
105,2
117,0
134,6
152,6

12,2
18,0
23,5
28,9
34,2
39,2
47,9
53,4
59,0
64,5
73,1
78,9
90,5
104,9
116,7
134,1
152,4

7,9
11,4
14,6
17,4
20,0
22,2
30,4
33,5
36,6
39,5
47,6
51,2
58,1
68,6
75,8
86,1
99,1

6,0
8,4
10,6
12,5
14,0
15,2
22,4
24,6
26,6
28,5
35,7
38,2
43,1
51,2
56,3
63,5
72,7

1SV 02
1SV 03
1SV 04
1SV 05
1SV 06
1SV 07
1SV 08
1SV 09
1SV 10
1SV 11
1SV 12
1SV 13
1SV 15
1SV 17
1SV 19
1SV 22
1SV 25

kW

HP

0,37
0,37
0,37
0,37
0,37
0,37
0,55
0,55
0,55
0,55
0,75
0,75
0,75
1,1
1,1
1,1
1,5

0,5
0,5
0,5
0,5
0,5
0,5
0,75
0,75
0,75
0,75
1
1
1
1,5
1,5
1,5
2

H = TOTAL HEAD METRES COLUMN OF WATER

11,5
17,0
22,1
27,0
31,7
36,1
45,2
50,4
55,5
60,4
69,3
74,8
85,6
100,0
111,0
127,4
145,5

Prestazioni conformi alle norme ISO 9906 - Annex A.

10,7
15,7
20,4
24,8
28,9
32,7
41,8
46,4
51,0
55,5
64,3
69,4
79,3
93,1
103,2
118,1
135,4

9,5
13,8
17,9
21,6
25,0
28,1
36,8
40,8
44,7
48,5
57,1
61,6
70,1
82,6
91,5
104,4
120,0

GEN..D/SHF

EN12845_pp_1sv-2p50-en_a_th

94

GEN..D/SHF BOOSTER SETS SERIES


TABELLA ABBINAMENTI POMPA SERVIZIO SH32-80 - POMPA PILOTA GRUPPI GEN 1
SERVICE PUMP JOCKEY PUMP COMBINA
TIONS
COMBINATIONS

1SV 19

1SV 17

1SV 15

1SV 13

1SV 12

1SV 10

1SV 09

PUMP

32-125/D121
32-125/D136
32-160/D150
32-160/D168
32-200/D188
32-200/D204
32-250/D222
32-250/D242
32-250/D256
40-125/D112
40-125/D126
40-125/D143
40-160/D159
40-160/D171
40-200/D190
40-200/D209
40-250/D218
40-250/D233
40-250/D251
50-125/D119
50-125/D130
50-125/D139
50-160/D158
50-160/D174
50-200/D197
50-200/D209
50-250/D224
50-250/D237
50-250/D250
65-160/D119
65-160/D129
65-160/D137
65-160/D168
65-160/D177
65-200/D192
65-200/D203
65-200/D215
65-250/D240
65-250/D255
80-160/D169
80-160/D177
80-160/D186
80-200/D198
80-200/D215
80-200/D226
80-250/D237
80-250/D252
80-250/D270

GEN..D/SHF

32-125/07
32-125/11
32-160/15
32-160/22
32-200/30
32-200/40
32-250/55
32-250/75
32-250/110
40-125/11
40-125/15
40-125/22
40-160/30
40-160/40
40-200/55
40-200/75
40-250/110A
40-250/110
40-250/150
50-125/22
50-125/30
50-125/40
50-160/55
50-160/75
50-200/110A
50-200/110
50-250/150
50-250/185
50-250/220
65-160/40
65-160/55
65-160/75
65-160/110A
65-160/110
65-200/150
65-200/185
65-200/220
65-250/300
65-250/370
80-160/110
80-160/150
80-160/185
80-200/220
80-200/300
80-200/370
80-250/450
80-250/550
80-250/750

1SV 08

ELECTRIC
PUMP

1SV 07

TYPE
SHF

1SV 11

JOCKEY PUMP

SERVICE PUMP

12845-SHF_ap-en_b_tc

95

HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (POSITIVE SUCTION HEAD)
HYDRAULIC
TABLE
AT
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE SHF32 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA SOPRABATT
GEN..D/SHF 32 BOOSTER SETS SERIES
TYPE

RATED

SHF..

POWER

LHn

RISK CLASS

Q = DELIVERY
l/min 0

ELECTRIC

PUMP

PUMP

m /h 0

150

180

200

225

300

350

375

400

416

425

450

540

11

12

14

18

21

23

24

25

26

27

32

15,2

13,1
24,1

H = TOTAL HEAD METRES COLUMN OF WATER

kW

32-125/07

32-125/D121

1 x 0,75

16,7

14,0

12,9

12,1

11,0

7,6

5,1

3,7

1,9

32-125/11

32-125/D136

1 x 1,1

21,6

19,0

17,9

17,0

15,9

12,3

9,6

8,1

6,2

32-160/15

32-160/D150

1 x 1,5

27,6

24,2

22,9

21,8

20,5

16,3

13,0

11,3

9,1

32-160/22

32-160/D168

1 x 2,2

35,0

32,0

30,9

29,9

28,7

24,7

21,5

19,7

17,5

16,1

32-200/30

32-200/D188

1x3

43,8

38,1

36,4

35,1

33,4

28,0

23,9

21,6

18,8

17,1

32-200/40

32-200/D204

1x4

53,6

48,6

47,1

45,9

44,4

39,3

35,1

32,8

29,9

28,1

27,0

32-250/55

32-250/D222

1 x 5,5

61,7

56,3

54,6

53,2

51,6

46,0

41,7

39,3

36,4

32-250/75

32-250/D242

1 x 7,5

74,1

68,4

66,7

65,3

63,6

58,1

53,8

51,4

48,6

46,9

45,8

32-250/110

32-250/D256

1 x 11

86,3

79,8

77,9

76,5

74,7

69,0

64,7

62,3

59,5

57,8

56,7

54,0

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
12845_1pg-sp-shf32-2p50-en_a_th
LHn = risk class value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure that these drops, added to the difference in level (max. 3.2m), are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (SUCTION LIF
T)
HYDRAULIC
TABLE
AT
LIFT)
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE SHF32 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA SOTTOBATT
GEN..D/SHF 32 BOOSTER SETS SERIES
TYPE

RATED

SHF..

POWER

ELECTRIC

PUMP

PUMP

LHn

GEN..D/SHF

RISK CLASS

Q = DELIVERY
l/min 0

150

180

200

225

300

350

375

400

416

425

450

540

3
m /h 0

11

12

14

18

21

23

24

25

26

27

32

15,2

13,1
24,1

H = TOTAL HEAD METRES COLUMN OF WATER

kW

32-125/07

32-125/D121

1 x 0,75

16,7

14,0

12,9

12,1

11,0

7,6

5,1

3,7

1,9

32-125/11

32-125/D136

1 x 1,1

21,6

19,0

17,9

17,0

15,9

12,3

9,6

8,1

6,2

32-160/15

32-160/D150

1 x 1,5

27,6

24,2

22,9

21,8

20,5

16,3

13,0

11,3

9,1

32-160/22

32-160/D168

1 x 2,2

35,0

32,0

30,9

29,9

28,7

24,7

21,5

19,7

17,5

16,1

32-200/30

32-200/D188

1x3

43,8

38,1

36,4

35,1

33,4

28,0

23,9

21,6

18,8

17,1

32-200/40

32-200/D204

1x4

53,6

48,6

47,1

45,9

44,4

39,3

35,1

32,8

29,9

28,1

27,0

32-250/55

32-250/D222

1 x 5,5

61,7

56,3

54,6

53,2

51,6

46,0

41,7

39,3

36,4

32-250/75

32-250/D242

1 x 7,5

74,1

68,4

66,7

65,3

63,6

58,1

53,8

51,4

48,6

46,9

45,8

32-250/110

32-250/D256

1 x 11

86,3

79,8

77,9

76,5

74,7

69,0

64,7

62,3

59,5

57,8

56,7

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
LHn = risk class value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845).
Inlet pressure drops must be deducted. Make sure these drops are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

96

54,0

12845_1pg-st-shf32-2p50-en_a_th

NPSH REQUIRED FOR PUMP SERIES SHF 32


TABELLA DI PRESTAZIONI IDRAULICHE NPSHr GRUPPI EN12845 SERIE SHF32 2 poli 50 Hz

TYPE

RATED

SHF..

POWER

LHn

RISK CLASS

Q = DELIVERY
l/min 0

ELECTRIC

PUMP

PUMP

m /h 0

150

180

200

225

300

350

375

400

416

425

450

540

11

12

14

18

21

23

24

25

26

27

32

4,4

5,2
6,9

NPSHr [METRES COLUMN OF WATER]

kW

32-125/07

32-125/D121

1 x 0,75

1,0

1,0

1,1

1,2

1,6

2,1

2,3

2,7

32-125/11

32-125/D136

1 x 1,1

1,0

1,0

1,1

1,2

1,6

2,1

2,3

2,7

32-160/15

32-160/D150

1 x 1,5

1,5

1,6

1,7

1,9

2,5

3,0

3,2

3,5

32-160/22

32-160/D168

1 x 2,2

1,2

1,4

1,5

1,6

2,2

2,8

3,3

3,8

4,2

32-200/30

32-200/D188

1x3

1,7

1,8

1,9

2,1

2,8

3,7

4,3

5,2

5,8

32-200/40

32-200/D204

1x4

1,6

1,8

2,0

2,2

2,8

3,4

3,9

4,6

5,1

5,5

32-250/55

32-250/D222

1 x 5,5

2,8

3,2

3,5

3,8

5,1

6,2

6,9

7,7

32-250/75

32-250/D242

1 x 7,5

2,7

3,0

3,2

3,5

4,5

5,3

5,8

6,3

6,6

6,9

32-250/110

32-250/D256

1 x 11

2,7

3,0

3,2

3,5

4,5

5,3

5,8

6,3

6,6

6,9

The declared NPSH values were obtained in the laboratory and refer to a single service pump

7,5

12845_1p-shf32-2p50_NPSHr-en_a_th

LHn = risk class value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)

GEN..D/SHF

Check that NPSHd NPSHr+1m is satisfied

97

HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (POSITIVE SUCTION HEAD)
HYDRAULIC
TABLE
AT
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE SHF40 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA, INST SOPRA
GEN..D/SHF 40 BOOSTER SETS SERIES
TYPE

RATED

SHF..

POWER

ELECTRIC

PUMP

PUMP

OH1n

RISK CLASS

Q = DELIVERY
l/min 0

300

375

540

640

677

700

725

750

800

833

850

1000

m3/h 0

18

23

32

38

41

42

44

45

48

50

51

60

H = TOTAL HEAD METRES COLUMN OF WATER

kW

40-125/11

40-125/D112

1 x 1,1

13,9

11,3

10,0

9,3

3,4

0,7

40-125/15

40-125/D126

1 x 1,5

18,0

15,3

14,0

13,3

7,4

4,7

40-125/22

40-125/D143

1 x 2,2

25,3

21,8

20,5

19,8

14,0

11,4

6,4

5,0

3,6

40-160/30

40-160/D159

1x3

31,6

28,1

26,8

26,0

19,5

16,5

10,8

9,2

7,6

40-160/40

40-160/D171

1x4

38,3

35,1

33,7

32,9

26,5

23,6

18,1

16,5

15,0

40-200/55

40-200/D190

1 x 5,5

46,4

42,7

41,2

40,4

33,1

29,7

23,3

21,5

19,6

40-200/75

0,6
11,7

40-200/D209

1 x 7,5

57,5

53,1

51,6

50,7

43,8

40,7

34,8

33,2

31,5

28,0

40-250/110A 40-250/D218

1 x 11

63,6

57,8

56,2

55,2

47,8

44,5

38,2

36,5

34,8

31,1

40-250/110

40-250/D233

1 x 11

71,7

66,0

64,3

63,4

55,7

52,3

45,8

44,0

42,1

38,3

40-250/150

40-250/D251

1 x 15

85,0

78,6

76,9

76,0

68,4

65,0

58,6

56,8

55,0

51,1

42,6

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
12845_1pg-sp-shf40-2p50-en_a_th
OHn = risk class value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure that these drops, added to the difference in level (max. 3.2m), are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (SUCTION LIF
T)
HYDRAULIC
TABLE
AT
LIFT)
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE SHF40 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA, INST SOTT
GEN..D/SHF 40 BOOSTER SETS SERIES
TYPE

RATED

SHF..

POWER

ELECTRIC

PUMP

PUMP

OH1n

GEN..D/SHF

RISK CLASS

Q = DELIVERY
l/min 0

300

375

540

640

677

700

725

750

800

833

850

1000

m3/h 0

18

23

32

38

41

42

44

45

48

50

51

60

H = TOTAL HEAD METRES COLUMN OF WATER

kW

40-125/11

40-125/D112

1 x 1,1

13,9

11,3

10,0

9,3

3,4

40-125/15

40-125/D126

1 x 1,5

18,0

15,3

14,0

13,3

7,4

0,7
4,7

40-125/22

40-125/D143

1 x 2,2

25,3

21,8

20,5

19,8

14,0

11,4

6,4

5,0

3,6

40-160/30

40-160/D159

1x3

31,6

28,1

26,8

26,0

19,5

16,5

10,8

9,2

7,6

40-160/40

40-160/D171

1x4

38,3

35,1

33,7

32,9

26,5

23,6

18,1

16,5

15,0

40-200/55

40-200/D190

1 x 5,5

46,4

42,7

41,2

40,4

33,1

29,7

23,3

21,5

19,6

40-200/75

0,6
11,7

40-200/D209

1 x 7,5

57,5

53,1

51,6

50,7

43,8

40,7

34,8

33,2

31,5

28,0

40-250/110A 40-250/D218

1 x 11

63,6

57,8

56,2

55,2

47,8

44,5

38,2

36,5

34,8

31,1

40-250/110

40-250/D233

1 x 11

71,7

66,0

64,3

63,4

55,7

52,3

45,8

44,0

42,1

38,3

40-250/150

40-250/D251

1 x 15

85,0

78,6

76,9

76,0

68,4

65,0

58,6

56,8

55,0

51,1

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
OHn = risk class value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure these drops are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

98

42,6

12845_1pg-st-shf40-2p50-en_a_th

NPSH
REQUIRED FOR PUMP SERIES SHF 40
TABELLA DI PRESTAZIONI IDRAULICHE GRUPPI EN12845 SERIE SHF40 2 poli 50 Hz 1 POMPA DI SERVIZIO

RATED

SHF..

POWER

ELECTRIC

PUMP

PUMP

OH1m

TYPE

OH1n

RISK CLASS

l/min 0

300

375

540

640

677

700

725

750

800

833

850

1000

m3/h 0

18

23

32

38

41

42

44

45

48

50

51

60

Q = DELIVERY

NPSHr [METRES COLUMN OF WATER]

kW

40-125/11

40-125/D112

1 x 1,1

0,7

1,0

1,5

2,0

40-125/15

40-125/D126

1 x 1,5

0,7

1,0

1,5

2,0

2,3

2,5

40-125/22

40-125/D143

1 x 2,2

0,7

1,0

1,5

2,0

2,3

2,5

2,8

3,1

40-160/30

40-160/D159

1x3

1,1

1,4

2,1

2,6

2,9

3,2

3,5

3,8

40-160/40

40-160/D171

1x4

1,1

1,4

2,1

2,6

2,9

3,2

3,5

3,8

4,9

40-200/55

40-200/D190

1 x 5,5

1,4

1,8

2,7

3,4

3,7

3,9

4,2

4,5

5,4

40-200/75

40-200/D209

1 x 7,5

1,4

1,8

2,7

3,4

3,7

3,9

4,2

4,5

5,4

6,4

40-250/110A 40-250/D218

1 x 11

1,4

1,4

1,7

3,0

4,1

5,0

40-250/110

40-250/D233

1 x 11

1,3

1,4

1,6

1,8

1,9

40-250/150

40-250/D251

1 x 15

1,3

1,4

1,6

1,8

1,9

2,2

2,5

3,3

4,3

2,1

5,0

12845_1p-shf40-2p50_NPSHr-en_a_th

GEN..D/SHF

The declared NPSH values were obtained in the laboratory and refer to a single service pump
OHn, OHm = risk class value referred to the required rated and maximum capacity (Tab.6 para 7.3.1 EN12845)
Check that NPSHd NPSHr+1m is satisfied at the maximum requested capacity

99

HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (POSITIVE SUCTION HEAD)
HYDRAULIC
TABLE
AT
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE SHF50 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASPESCLUSA INST SOPRA
GEN..D/SHF 50 BOOSTER SETS SERIES
RATED

SHF..

POWER

ELECTRIC

PUMP

PUMP

OH3n

TYPE

OH2n

RISK CLASS

Q = DELIVERY
l/min 0

600

680

725

1000

1100

1200

1300

1350

1380

1400

1450

1500

m3/h 0

36

41

44

60

66

72

78

81

83

84

87

90

12,5

10,4

H = TOTAL HEAD METRES COLUMN OF WATER

kW

50-125/22

50-125/D119

1 x 2,2

17,2 13,2

12,0

11,3

5,9

3,6

1,2

50-125/30

50-125/D130

1x3

21,7 17,4

16,1

15,3

9,8

7,6

5,2

50-125/40

50-125/D139

1x4

25,6 21,8

20,6

19,8

14,4

12,1

9,8

7,3

6,0

5,3

4,7

50-160/55

50-160/D158

1 x 5,5

34,0 29,3

27,8

26,9

20,4

17,5

14,4

11,1

9,4

8,3

7,6

50-160/75

2,8

50-160/D174

1 x 7,5

40,7 36,1

34,7

33,9

27,6

24,7

21,6

18,1

16,3

15,2

14,4

50-200/110A 50-200/D197

1 x 11

34,0 29,3

27,8

26,9

20,4

17,5

14,4

11,1

9,4

8,3

7,6

50-200/110

50-200/D209

1 x 11

40,7 36,1

34,7

33,9

27,6

24,7

21,6

18,1

16,3

15,2

14,4

12,5

50-250/150

50-250/D224

1 x 15

70,3 65,5

64,0

63,0

54,6

50,4

45,4

39,6

50-250/185

50-250/D237

1 x 18,5

80,1 73,8

72,1

71,1

62,8

58,7

54,1

48,9

46,0

44,2

50-250/220

50-250/D250

1 x 22

88,9 83,2

81,6

80,6

72,3

68,4

64,0

59,1

56,4

54,7

53,6

50,6

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
12845_1pg-sp-shf50-2p50-en_a_th
OHn = risk class value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure that these drops, added to the difference in level (max. 3.2m), are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

TYPE

RATED

SHF..

POWER

ELECTRIC

PUMP

PUMP

OH3n

RISK CLASS

OH2n

GEN..D/SHF

HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (SUCTION LIF
T)
HYDRAULIC
TABLE
AT
LIFT)
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE SHF50 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASPESCLUSA INST SOTTO
GEN..D/SHF 50 BOOSTER SETS SERIES

Q = DELIVERY
l/min 0

600

680

725

1000

1100

1200

1300

1350

1380

1400

1450

1500

m3/h 0

36

41

44

60

66

72

78

81

83

84

87

90

12,5

10,4

H = TOTAL HEAD METRES COLUMN OF WATER

kW

50-125/22

50-125/D119

1 x 2,2

17,2 13,2

12,0

11,3

5,9

3,6

1,2

50-125/30

50-125/D130

1x3

21,7 17,4

16,1

15,3

9,8

7,6

5,2

2,8

50-125/40

50-125/D139

1x4

25,6 21,8

20,6

19,8

14,4

12,1

9,8

7,3

50-160/55

50-160/D158

1 x 5,5

34,0 29,3

27,8

26,9

20,4

17,5

14,4

11,1

9,4

8,3

7,6

50-160/75

50-160/D174

1 x 7,5

40,7 36,1

34,7

33,9

27,6

24,7

21,6

18,1

16,3

15,2

14,4

50-200/110A 50-200/D197

1 x 11

34,0 29,3

27,8

26,9

20,4

17,5

14,4

11,1

9,4

8,3

7,6

50-200/110

50-200/D209

1 x 11

40,7 36,1

34,7

33,9

27,6

24,7

21,6

18,1

16,3

15,2

14,4

12,5

50-250/150

50-250/D224

1 x 15

70,3 65,5

64,0

63,0

54,6

50,4

45,4

39,6

50-250/185
50-250/220

50-250/D237
50-250/D250

1 x 18,5
1 x 22

80,1 73,8
88,9 83,2

72,1
81,6

71,1
80,6

62,8
72,3

58,7
68,4

54,1
64,0

48,9
59,1

46,0
56,4

44,2
54,7

53,6

50,6

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
OHn = risk class value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure these drops are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

100

6,0

5,3

4,7

12845_1pg-st-shf50-2p50-en_a_th

NPSH REQUIRED FOR PUMP SERIES SHF 50


TABELLA DI PRESTAZIONI IDRAULICHE NPSHr GRUPPI EN12845 SERIE SHF50 2 poli 50 Hz 1 POMPA DI SERVIZIO

POWER
3

PUMP

PUMP

600

680

725

1000

1100

1200

1300

1350

1380

1400

1450

1500

36

41

44

60

66

72

78

81

83

84

87

90

6,5

7,6

Q = DELIVERY
l/min 0

ELECTRIC

OH3m

SHF..

OH3n

RATED

OH2m

TYPE

OH2n

RISK CLASS

m /h 0

NPSHr [METRES COLUMN OF WATER]

kW

50-125/22

50-125/D119

1 x 2,2

1,6

1,8

1,9

2,8

3,4

4,3

50-125/30

50-125/D130

1x3

1,6

1,8

1,9

2,7

3,1

3,7

4,6

50-125/40

50-125/D139

1x4

1,6

1,8

1,9

2,7

3,1

3,7

4,6

5,2

5,7

6,0

50-160/55

50-160/D158

1 x 5,5

2,0

2,1

2,1

2,8

3,2

3,7

4,7

5,4

5,9

6,3

50-160/75

50-160/D174

1 x 7,5

1,9

2,1

2,2

2,8

3,1

3,6

4,3

4,9

5,3

5,6

50-200/110A 50-200/D197

1 x 11

2,0

2,1

2,1

2,8

3,2

4,0

5,2

6,1

6,7

7,2

50-200/110

50-200/D209

1 x 11

1,9

2,1

2,2

2,8

3,2

3,7

4,7

5,4

5,9

6,3

7,5

50-250/150

50-250/D224

1 x 15

1,6

1,7

1,8

2,3

2,7

3,3

4,8

50-250/185

50-250/D237

1 x 18,5

1,5

1,7

1,8

2,4

2,7

3,1

3,7

4,1

4,4

50-250/220

50-250/D250

1 x 22

1,5

1,7

1,8

2,4

2,7

3,1

3,7

4,1

4,7

5,4

The declared NPSH values were obtained in the laboratory and refer to a single service pump

4,4

12845_1p-shf50-2p50_NPSHr-en_a_th

GEN..D/SHF

OHn, OHm = risk class value referred to the required rated and maximum capacity (Tab.6 para 7.3.1 EN12845)
Check that NPSHd NPSHr+1m is satisfied at the maximum requested capacity

101

HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (POSITIVE SUCTION HEAD)
HYDRAULIC
TABLE
AT
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE SHF65 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA INST SOPRA
GEN..D/SHF 65 BOOSTER SETS SERIES
RATED

SHF..

POWER

ELECTRIC

PUMP

PUMP

OH4n

TYPE

OH3n

RISK CLASS

Q = DELIVERY
l/min 0

800

900

1000

1100

1350

1500

1800

1900

2000

2050

2100

2200

m3/h 0

48

54

60

66

81

90

108

114

120

123

126

132

H = TOTAL HEAD METRES COLUMN OF WATER

kW

65-160/40

65-160/D119

1x4

19,6

15,9

14,9

13,8

12,6

9,4

7,3

2,9

65-160/55

65-160/D129

1 x 5,5

24,2

20,5

19,5

18,4

17,2

13,9

11,7

7,0

5,4

65-160/75

65-160/D137

1 x 7,5

28,2

25,1

24,2

23,1

22,0

18,8

16,7

12,0

10,4

65-160/110A 65-160/D168

1 x 11

38,2

34,3

33,0

31,5

29,8

25,2

22,0

15,2

12,9

39,7

38,4

36,9

35,3

30,6

27,4

20,5

18,1

47,5

45,9

44,1

38,9

35,3

27,1

24,1

65-160/110

65-160/D177

1 x 11

42,9

65-200/150

65-200/D192

1 x 15

53,0

8,7
15,6

65-200/185

65-200/D203

1 x 18,5

60,2

55,2

53,6

51,9

46,9

43,4

35,5

32,6

29,5

65-200/220

65-200/D215

1 x 22

68,0

63,0

61,6

60,0

55,2

51,9

44,3

41,5

38,5

37,0

35,5

65-250/300

65-250/D240

1 x 30

83,7

80,2

78,9

74,9

71,9

64,4

61,4

58,3

56,6

54,9

65-250/370

65-250/D255

1 x 37

96,7

93,6

92,2

88,0

84,9

77,4

74,6

71,7

70,1

68,5

65,2

HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (SUCTION LIF
T)
HYDRAULIC
TABLE
AT
LIFT)
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE SHF65 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA INST SOTTO
GEN..D/SHF 65 BOOSTER SETS SERIES
TYPE

RATED

SHF..

POWER

ELECTRIC

PUMP

PUMP

OH4n

RISK CLASS

OH3n

GEN..D/SHF

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
12845_1pg-sp-shf65-2p50-en_a_th
OHn = risk class value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure that these drops, added to the difference in level (max. 3.2m), are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

Q = DELIVERY
l/min 0

800

900

1000

1100

1350

1500

1800

1900

2000

2050

2100

2200

m3/h 0

48

54

60

66

81

90

108

114

120

123

126

132

H = TOTAL HEAD METRES COLUMN OF WATER

kW

65-160/40

65-160/D119

1x4

19,6

15,9

14,9

13,8

12,6

9,4

7,3

2,9

65-160/55

65-160/D129

1 x 5,5

24,2

20,5

19,5

18,4

17,2

13,9

11,7

7,0

5,4

65-160/75

65-160/D137

1 x 7,5

28,2

25,1

24,2

23,1

22,0

18,8

16,7

12,0

10,4

65-160/110A 65-160/D168

1 x 11

38,2

34,3

33,0

31,5

29,8

25,2

22,0

15,2

12,9

39,7

38,4

36,9

35,3

30,6

27,4

20,5

18,1

47,5

45,9

44,1

38,9

35,3

27,1

24,1

65-160/110

65-160/D177

1 x 11

42,9

65-200/150

65-200/D192

1 x 15

53,0

8,7
15,6

65-200/185

65-200/D203

1 x 18,5

60,2

55,2

53,6

51,9

46,9

43,4

35,5

32,6

29,5

65-200/220

65-200/D215

1 x 22

68,0

63,0

61,6

60,0

55,2

51,9

44,3

41,5

38,5

37,0

35,5

65-250/300

65-250/D240

1 x 30

83,7

80,2

78,9

74,9

71,9

64,4

61,4

58,3

56,6

54,9

65-250/370

65-250/D255

1 x 37

96,7

93,6

92,2

88,0

84,9

77,4

74,6

71,7

70,1

68,5

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
OHn = risk class value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure these drops are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

102

65,2

12845_1pg-st-shf65-2p50-en_a_th

NPSH
REQUIRED FOR PUMP SERIES SHF 65
TABELLA DI PRESTAZIONI IDRAULICHE NPSHr GRUPPI EN12845 SERIE SHF65 2 poli 50 Hz 1 POMPA DI SERVIZIO

POWER

ELECTRIC

PUMP

PUMP

OH4m

SHF..

l/min 0

800

900

1000

1100

1350

1400

1500

1800

1900

2000

2100

2200

m3/h 0

48

54

60

66

81

84

90

108

114

120

126

132

OH4n

RATED

OH3m

TYPE

OH3n

RISK CLASS

Q = DELIVERY

NPSHr [METRES COLUMN OF WATER]

kW

65-160/40

65-160/D119

1x4

1,9

1,8

1,9

1,9

2,5

2,7

3,3

7,4

65-160/55

65-160/D129

1 x 5,5

1,9

1,9

1,9

1,9

2,4

2,6

3,1

5,4

6,6

65-160/75

65-160/D137

1 x 7,5

1,9

1,9

1,9

1,9

2,4

2,6

3,1

5,4

6,6

65-160/110A 65-160/D168

1 x 11

1,3

1,4

1,6

1,7

2,1

2,1

2,4

3,5

4,2

1,3

1,4

1,6

1,7

2,1

2,1

2,4

3,5

4,2

1,7

1,7

1,6

1,7

1,7

1,9

4,1

6,4

65-160/110

65-160/D177

1 x 11

65-200/150

65-200/D192

1 x 15

8,0
5,2

65-200/185

65-200/D203

1 x 18,5

1,7

1,7

1,6

1,7

1,7

1,9

3,0

3,9

5,3

65-200/220

65-200/D215

1 x 22

1,7

1,7

1,6

1,7

1,7

1,9

3,0

3,9

5,3

7,5

65-250/300

65-250/D240

1 x 30

1,3

1,3

1,4

1,5

1,7

3,2

4,1

5,4

7,0

65-250/370

65-250/D255

1 x 37

1,3

1,3

1,3

1,4

1,6

2,9

3,7

4,8

6,2

8,1

12845_1p-shf65-2p50_NPSHr-en_a_th

GEN..D/SHF

The declared NPSH values were obtained in the laboratory and refer to a single service pump
OHn, OHm = risk class value referred to the required rated and maximum capacity (Tab.6 para 7.3.1 EN12845)
Check that NPSHd NPSHr+1m is satisfied at the maximum requested capacity

103

HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (POSITIVE SUCTION HEAD)
HYDRAULIC
TABLE
AT
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE SHF80 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA INST SOPRA
GEN..D/SHF 80 BOOSTER SETS SERIES
RATED

SHF..

POWER

ELECTRIC

PUMP

PUMP

80-160/110
80-160/150
80-160/185
80-200/220
80-200/300
80-200/370
80-250/450
80-250/550
80-250/750

HH1n

TYPE

OH4n

RISK CLASS

Q = DELIVERY
l/min 0

1200

1500

1800

2100

2300

3216

3300

3500

3600

3700

3800

4000

m3/h 0

72

90

108

126

138

193

198

210

216

222

228

240

14,1
20,2
31,1
40,4
44,6
59,6
77,0

12,4
29,3
38,5

27,4
36,6

32,7

57,3
74,8

72,5

H = TOTAL HEAD METRES COLUMN OF WATER

kW

80-160/D169
80-160/D177
80-160/D186
80-200/D198
80-200/D215
80-200/D226
80-250/D237
80-250/D252
80-250/D270

1 x 11
1 x 15
1 x 18,5
1 x 22
1 x 30
1 x 37
1 x 45
1 x 55
1 x 75

33,0
39,5
46,4
51,9
62,2
69,8
82,2
93,9
109,7

30,9
37,8
44,7

69,9

28,6
35,6
42,6
48,5
59,7
68,1
79,1
91,9
108,6

25,7
32,7
39,8
45,8
57,1
65,7
76,2
89,2
106,0

22,2
29,4
36,6
42,5
53,9
62,8
72,6
85,9
102,7

19,7
26,9
34,2
40,1
51,5
60,5
69,8
83,2
100,2

6,2
13,2
20,7
26,7
37,8
47,2
53,3
67,7
85,0

4,8
11,8
19,3
25,3
36,4
45,7
51,5
66,0
83,3

8,4
15,9
21,9
32,9
42,2
47,0
61,8
79,2

HYDRA
ULIC PERFORMANCE T
ABLE A
T 50 HZ (SUCTION LIF
T)
HYDRAULIC
TABLE
AT
LIFT)
TABELLA DI PRESTAZIONI IDRAULICHE NETTE GRUPPI EN12845 SERIE SHF80 2 poli 50 Hz 1 POMPA DI SERVIZIO, ASP ESCLUSA INST SOTTO
GEN..D/SHF 80 BOOSTER SETS SERIES
RISK CLASS
RATED

SHF..

POWER

ELECTRIC

PUMP

PUMP

80-160/110
80-160/150
80-160/185
80-200/220
80-200/300
80-200/370
80-250/450
80-250/550
80-250/750

Q = DELIVERY
l/min 0

1200

1500

1800

2100

2300

3216

3300

3500

3600

3700

3800

4000

m3/h 0

72

90

108

126

138

193

198

210

216

222

228

240

14,1
20,2
31,1
40,4
44,6
59,6
77,0

12,4
29,3
38,5

27,4
36,6

32,7

57,3
74,8

72,5

H = TOTAL HEAD METRES COLUMN OF WATER

kW

80-160/D169
80-160/D177
80-160/D186
80-200/D198
80-200/D215
80-200/D226
80-250/D237
80-250/D252
80-250/D270

1 x 11
1 x 15
1 x 18,5
1 x 22
1 x 30
1 x 37
1 x 45
1 x 55
1 x 75

HH1n

TYPE

OH4n

GEN..D/SHF

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
12845_1pg-sp-shf80-2p50-en_a_th
OHn = risk class value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure that these drops, added to the difference in level (max. 3.2m), are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

33,0
39,5
46,4
51,9
62,2
69,8
82,2
93,9
109,7

30,9
37,8
44,7

69,9

28,6
35,6
42,6
48,5
59,7
68,1
79,1
91,9
108,6

25,7
32,7
39,8
45,8
57,1
65,7
76,2
89,2
106,0

22,2
29,4
36,6
42,5
53,9
62,8
72,6
85,9
102,7

19,7
26,9
34,2
40,1
51,5
60,5
69,8
83,2
100,2

6,2
13,2
20,7
26,7
37,8
47,2
53,3
67,7
85,0

Performance levels relative to set with 1 service pump running and compliant with ISO 9906 - Annex A.
OHn = risk class value referred to the required rated capacity (Tab.6 para 7.3.1 EN12845)
Inlet pressure drops must be deducted. Make sure these drops are less than 4.5m
The values shown identify performance levels according to the reference standard EN12845.

104

4,8
11,8
19,3
25,3
36,4
45,7
51,5
66,0
83,3

8,4
15,9
21,9
32,9
42,2
47,0
61,8
79,2

12845_1pg-st-shf80-2p50-en_a_th

NPSH REQUIRED FOR PUMP SERIES SHF 80

TABELLA DI PRESTAZIONI IDRAULICHE GRUPPI EN12845 SERIE SHF80 2 poli 50 Hz 1 POMPA DI SERVIZIO

POWER

ELECTRIC

PUMP

PUMP

80-160/110
80-160/150
80-160/185
80-200/220
80-200/300
80-200/370
80-250/450
80-250/550
80-250/750

l/min 0

1200

1500

1800

2100

2300

3216

3300

3500

3600

3700

3800

4000

m3/h 0

72

90

108

126

138

193

198

210

216

222

228

240

6,1
4,9
4,4
4,4
4,6
4,6
4,6

6,8
4,7
4,7

5,0
5,0

6,0

5,1
5,1

6,0

Q = DELIVERY

NPSHr [METRES COLUMN OF WATER]

kW

80-160/D169
80-160/D177
80-160/D186
80-200/D198
80-200/D215
80-200/D226
80-250/D237
80-250/D252
80-250/D270

1 x 11
1 x 15
1 x 18,5
1 x 22
1 x 30
1 x 37
1 x 45
1 x 55
1 x 75

HH1m

SHF..

HH1n

RATED

OH4m

TYPE

OH4n

RISK CLASS

2,3
2,3
2,3

2,0

2,5
2,5
2,5
2,2
2,2
2,2
1,9
1,9
1,9

2,7
2,7
2,7
2,4
2,4
2,4
2,2
2,2
2,2

3,0
2,9
2,9
2,7
2,6
2,6
2,4
2,4
2,4

3,2
3,0
3,0
2,8
2,8
2,8
2,6
2,6
2,6

5,9
4,3
4,3
3,9
3,7
3,7
3,6
3,6
3,6

6,5
4,6
4,6
4,1
3,8
3,8
3,7
3,7
3,7

5,5
5,5
4,6
4,2
4,2
4,2
4,2
4,2

GEN..D/SHF

The declared NPSH values were obtained in the laboratory and refer to a single service pump
12845_1p-shf80-2p50_NPSHr-en_a_th
OHn, OHm, HHn, HHm = risk class value referred to the required rated and maximum capacity (Tab.6 para 7.3.1, Tab.7 para 7.3.2 EN12845)
Check that NPSHd NPSHr+1m is satisfied at the maximum requested capacity

105

GEN..D/SHF 32-80 BOOSTER SETS


TABELLA DATI ELETTRICI GRUPPI GEN..D/SHF 2 poli 50 Hz
ELECTRICAL DA
TA T
ABLE A
T 50 Hz
DAT
TABLE
AT
SERVICE
PUMP

ELECTRIC JOCKEY
PUMP

CURRENT (*)
ABSORBED SET

3 X 400 V
TYPE
SHF..
ELECTRIC

GEN..D/SHF

PUMP

32-125/07
32-125/11
32-160/15
32-160/22
32-200/30
32-200/40
32-250/55
32-250/75
32-250/110
40-125/11
40-125/15
40-125/22
40-160/30
40-160/40
40-200/55
40-200/75
40-250/110A
40-250/110
40-250/150
50-125/22
50-125/30
50-125/40
50-160/55
50-160/75
50-200/110A
50-200/110
50-250/150
50-250/185
50-250/220
65-160/40
65-160/55
65-160/75
65-160/110A
65-160/110
65-200/150
65-200/185
65-200/220
65-250/300
65-250/370
80-160/110
80-160/150
80-160/185
80-200/220
80-200/300
80-200/370
80-250/450
80-250/550
80-250/750

PUMP

32-125/D121
32-125/D136
32-160/D150
32-160/D168
32-200/D188
32-200/D204
32-250/D222
32-250/D242
32-250/D256
40-125/D112
40-125/D126
40-125/D143
40-160/D159
40-160/D171
40-200/D190
40-200/D209
40-250/D218
40-250/D233
40-250/D251
50-125/D119
50-125/D130
50-125/D139
50-160/D158
50-160/D174
50-200/D197
50-200/D209
50-250/D224
50-250/D237
50-250/D250
65-160/D119
65-160/D129
65-160/D137
65-160/D168
65-160/D177
65-200/D192
65-200/D203
65-200/D215
65-250/D240
65-250/D255
80-160/D169
80-160/D177
80-160/D186
80-200/D198
80-200/D215
80-200/D226
80-250/D237
80-250/D252
80-250/D270

3x400

1 x 230V
NOMINAL
POWER
Pn

In

kW

0,75
1,1
1,5
2,2
3
4
5,5
7,5
11
1,1
1,5
2,2
3
4
5,5
7,5
11
11
15
2,2
3
4
5,5
7,5
11
11
15
18,5
22
4
5,5
7,5
11
11
15
18,5
22
30
37
11
15
18,5
22
30
37
45
55
75

1,76
2,36
3,02
4,64
5,91
7,5
11
14,3
19,8
2,36
3,02
4,64
5,91
7,5
11
14,3
19,8
19,8
26,2
4,64
5,91
7,5
11
14,3
19,8
19,8
26,2
32,9
39,1
7,5
11
14,3
19,8
19,8
26,2
32,9
39,1
53,6
65,8
19,8
26,7
32,9
39,1
53,6
65,8
78
95
129

TYPE

1SV 07
1SV 08
1SV 08
1SV 09
1SV 11
1SV 12
1SV 12
1SV 15
1SV 17
1SV 07
1SV 07
1SV 08
1SV 09
1SV 10
1SV 11
1SV 12
1SV 13
1SV 15
1SV 17
1SV 07
1SV 08
1SV 08
1SV 09
1SV 10
1SV 12
1SV 12
1SV 15
1SV 15
1SV 17
1SV 08
1SV 08
1SV 08
1SV 10
1SV 10
1SV 12
1SV 12
1SV 15
1SV 17
1SV 17
1SV 09
1SV 10
1SV 11
1SV 12
1SV 13
1SV 15
1SV 15
1SV 17
1SV 19

1x230V

3x400V

Pn

In

In

kW

GEN..00D GEN..01D GEN..10D GEN..11D


A

0,37
0,55
0,55
0,55
0,55
0,75
0,75
0,75
1,1
0,37
0,37
0,55
0,55
0,55
0,55
0,75
0,75
0,75
1,1
0,37
0,55
0,55
0,55
0,55
0,75
0,75
0,75
0,75
1,1
0,55
0,55
0,55
0,55
0,55
0,75
0,75
0,75
1,1
1,1
0,55
0,55
0,55
0,75
0,75
0,75
0,75
1,1
1,1

2,82
3,88
3,88
3,88
3,88
4,88
4,88
4,88
6,77
2,82
2,82
3,88
3,88
3,88
3,88
4,88
4,88
4,88
6,77
2,82
3,88
3,88
3,88
3,88
4,88
4,88
4,88
4,88
6,77
3,88
3,88
3,88
3,88
3,88
4,88
4,88
4,88
6,77
6,77
3,88
3,88
3,88
4,88
4,88
4,88
4,88
6,77
6,77

1,35
1,48
1,48
1,48
1,48
1,76
1,76
1,76
2,36
1,35
1,35
1,48
1,48
1,48
1,48
1,76
1,76
1,76
2,36
1,35
1,48
1,48
1,48
1,48
1,76
1,76
1,76
1,76
2,36
1,48
1,48
1,48
1,48
1,48
1,76
1,76
1,76
2,36
2,36
1,48
1,48
1,48
1,76
1,76
1,76
1,76
2,36
2,36

3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3

5,82
6,88
6,88
6,88
6,88
7,88
7,88
7,88
9,77
5,82
5,82
6,88
6,88
6,88
6,88
7,88
7,88
7,88
9,77
5,82
6,88
6,88
6,88
6,88
7,88
7,88
7,88
7,88
9,77
6,88
6,88
6,88
6,88
6,88
7,88
7,88
7,88
9,77
9,77
6,88
6,88
6,88
7,88
7,88
7,88
7,88
9,77
9,77

4,76
5,36
6,02
7,64
8,91
10,5
14
17,3
22,8
5,36
6,02
7,64
8,91
10,5
14
17,3
22,8
22,8
29,2
7,64
8,91
10,5
14
17,3
22,8
22,8
29,2
35,9
42,1
10,5
14
17,3
22,8
22,8
29,2
35,9
42,1
56,6
68,8
22,8
29,7
35,9
42,1
56,6
68,8
81
98
132

6,11
6,84
7,5
9,1
10,4
12,3
15,8
19,1
25,2
6,71
7,37
9,1
10,4
12,0
15,5
19,1
24,6
24,6
31,6
9,0
10,4
12,0
15,5
18,8
24,6
24,6
31,0
37,7
44,5
12,0
15,5
18,8
24,3
24,3
31,0
37,7
43,9
59,0
71,2
24,3
31,2
37,4
43,9
58,4
70,6
82,8
100,4
134,4

ENMTP-SHF_2p50-en_d_te

(*) The current indicated is the maximum current absorbed.


At the set 3x400V three-phase power supply GEN..10D and GEN..11D to add the control panel current of the engine pump (GEN..0D) 1x230V
The sets GEN..01D have the electric jockey pump 1x230V single-phase power supply.

106

Fire-fighting
booster sets
EN 12845

MARKET SECTORS
CIVIL, INDUSTRIAL
APPLICA
TIONS
APPLICATIONS
Fixed fire-fighting systems.

Automatic Sprinkler systems.

GEN..D/SHF

DSHF
Series

SPECIFICA
TIONS
SPECIFICATIONS
Flow up to 220 m3/h.
Head up to 100 m.

Diesel engine with battery start.


Diesel engine service pump

Panel supply power voltage:


1 x 230V 10%.

Frequency: 50 Hz.

in horizontal design
design:
- SHF series.

Maximum running pressure: 12 bar.

Voltage for controls outside panel:


12 - 24 Vac.

Protection grade:

- electric panel: IP54.

Electric pumps maximum power


75 kW.

107

DSHF 32-80 DIESEL ENGINE PUMP SERIES


FIRE-FIGHTING EN 12845

GEN..D/SHF

For the overall dimensions of the fuel tank and the starting batteries, see tables on pages 20-25.

108

D..

DNA

DNM

H1

H2

SHFE32-125/D121

R 2"

32

400

350

80

710

900

262

402

630

SHFE32-125/D136

R 2"

32

400

350

80

710

900

262

402

630

SHFE32-160/D150

R 2"

32

400

350

80

690

900

282

442

650

SHFE32-160/D168

R 2"

32

400

350

80

690

900

282

442

650

SHFE32-200/D188

R 2"

32

400

350

80

690

900

260

440

630

SHFE32-200/D204

R 2"

32

500

450

80

790

950

260

440

630

SHFE32-250/D222

R 2"

32

500

450

100

805

950

280

505

680

SHFE32-250/D242

R 2"

32

500

450

100

805

950

280

505

690

SHFE32-250/D256

R 2"

32

500

450

100

720

1000

280

505

690

SHFE40-125/D112

65

40

400

350

80

690

900

262

402

630

SHFE40-125/D126

65

40

400

350

80

690

900

262

402

630

SHFE40-125/D143

65

40

400

350

80

690

900

262

402

630

SHFE40-160/D159

65

40

400

350

80

690

900

282

442

650

SHFE40-160/D171

65

40

400

350

80

690

900

282

442

650

SHFE40-200/D190

65

40

500

450

100

770

950

310

490

710

SHFE40-200/D209

65

40

500

450

100

770

950

310

490

720

SHFE40-250/D218

65

40

530

480

100

820

1000

280

505

690

SHFE40-250/D233

65

40

530

480

100

920

1200

330

555

800

SHFE40-250/D251

65

40

530

480

100

920

1200

330

555

800

SHFE50-125/D119

65

50

400

350

100

690

950

282

442

650

SHFE50-125/D130

65

50

400

350

100

690

950

282

442

650

SHFE50-125/D139

65

50

500

450

100

740

950

282

442

650

SHFE50-160/D158

65

50

500

450

100

770

950

310

490

710

SHFE50-160/D174

65

50

500

450

100

770

950

310

490

720

SHFE50-200/D197

65

50

530

480

100

820

1000

310

510

720

SHFE50-200/D209

65

50

530

480

100

820

1200

310

510

720

SHFE50-250/D224

65

50

530

480

100

920

1200

330

555

800

SHFE50-250/D237

65

50

530

480

100

970

1350

380

555

800

SHFE50-250/D250

65

50

530

480

100

970

1350

380

605

800

SHFE65-160/D119

80

65

500

450

100

755

950

260

460

630

SHFE65-160/D129

80

65

500

450

100

805

950

310

510

710

SHFE65-160/D137

80

65

530

480

100

855

1000

310

510

720

SHFE65-160/D168

80

65

530

480

100

820

1000

310

510

720

SHFE65-160/D177

80

65

530

480

100

920

1200

360

560

830

SHFE65-200/D192

80

65

530

480

100

920

1200

330

555

800

SHFE65-200/D203

80

65

530

480

100

970

1350

380

555

800

SHFE65-200/D215

80

65

530

480

100

970

1350

380

605

900

SHFE65-250/D240

80

65

640

590

100

1130

1550

360

610

1000

SHFE65-250/D255

80

65

640

590

100

1130

1550

360

610

1010

SHFE80-160/D169

100

80

530

480

125

920

1250

330

555

800

SHFE80-160/D177

100

80

530

480

125

920

1250

330

555

800

SHFE80-160/D186

100

80

530

480

125

970

1350

380

605

800

SHFE80-200/D198

100

80

530

480

125

970

1450

380

630

900

SHFE80-200/D215

100

80

640

590

125

1095

1550

360

610

1000

SHFE80-200/D226

100

80

640

590

125

1095

1550

360

610

1010

SHFE80-250/D237

100

80

640

590

125

1180

1550

365

645

1030

SHFE80-250/D252

100

80

660

610

125

1240

1750

390

670

1080

SHFE80-250/D270
100
80
Dimensions in mm. Tolerance 10 mm.

700

650

125

1310

2050

420

700

1090
d_shfe-en_f_td

109

GEN..D/SHF

DSHF 32-80 DIESEL ENGINE PUMP SERIES


FIRE-FIGHTING EN 12845

110

GEN..D/SHF

Fire-fighting
booster sets
EN 12845

MARKET SECTORS
CIVIL, INDUSTRIAL
APPLICA
TIONS
APPLICATIONS
Fixed fire-fighting systems.

Automatic Sprinkler systems.

GEN..D/SHF

GEN..00D/SHF
Series

SPECIFICA
TIONS
SPECIFICATIONS
Flow up to 220 m3/h.
Head up to 100 m.

Diesel engine with battery start.


Diesel engine service pump

Panel supply power voltage:


1 x 230V 10%.

Frequency: 50 Hz.

in horizontal design
design:
- SHF series.

Maximum running pressure: 12 bar.

Voltage for controls outside panel:


12 - 24 Vac.

Protection grade:

- electric panel: IP54.

Electric pumps maximum power


75 kW.

111

GEN..D/SHF

GEN..00D/SHF 32-80 SERIES


FIRE-FIGHTING BOOSTER SETS EN 12845

For the overall dimensions of the fuel tank and the starting batteries, see tables on pages 20-25.

112

GEN..00D

DRW N

DNA

DNM

SHF32-125/D121

R 2"

R 1"1/2

400

350

80

710

262

900

913

1487

SHF32-125/D136

R 2"

R 1"1/2

400

350

80

710

262

900

913

1487

SHF32-160/D150

R 2"

R 1"1/2

400

350

80

690

282

900

953

1527

SHF32-160/D168

R 2"

R 1"1/2

400

350

80

690

282

900

953

1527

SHF32-200/D188

R 2"

R 1"1/2

400

350

80

690

260

900

951

1525

SHF32-200/D204

R 2"

R 1"1/2

500

450

80

790

260

950

951

1525

SHF32-250/D222

R 2"

R 1"1/2

500

450

100

805

280

950

1016

1590

SHF32-250/D242

R 2"

R 1"1/2

500

450

100

805

280

950

1016

1590

SHF32-250/D256

R 2"

R 1"1/2

500

450

100

720

280

1000

1016

1590

SHF40-125/D112

65

65

400

350

80

690

262

900

1106

1694

SHF40-125/D126

65

65

400

350

80

690

262

900

1106

1694

SHF40-125/D143

65

65

400

350

80

690

262

900

1106

1694

SHF40-160/D159

65

65

400

350

80

690

282

900

1146

1734

SHF40-160/D171

65

65

400

350

80

690

282

900

1146

1734

SHF40-200/D190

65

65

500

450

100

770

310

950

1194

1782

SHF40-200/D209

65

65

500

450

100

770

310

950

1194

1782

SHF40-250/D218

65

65

530

480

100

820

280

1000

1209

1797

SHF40-250/D233

65

65

530

480

100

920

330

1200

1259

1847

SHF40-250/D251

65

65

530

480

100

920

330

1200

1259

1847

SHF50-125/D119

65

65

400

350

100

690

282

950

1238

1826

SHF50-125/D130

65

65

400

350

100

690

282

950

1238

1826

SHF50-125/D139

65

65

500

450

100

740

282

950

1238

1826

SHF50-160/D158

65

65

500

450

100

770

310

950

1286

1874

SHF50-160/D174

65

65

500

450

100

770

310

950

1286

1874

SHF50-200/D197

65

65

530

480

100

820

310

1000

1306

1894

SHF50-200/D209

65

65

530

480

100

820

310

1200

1306

1894

SHF50-250/D224

65

65

530

480

100

920

330

1200

1351

1939

SHF50-250/D237

65

65

530

480

100

970

380

1350

1401

1989

SHF50-250/D250

65

65

530

480

100

970

380

1350

1401

1989

SHF65-160/D119

80

80

500

450

100

755

260

950

1323

1917

SHF65-160/D129

80

80

500

450

100

805

310

950

1373

1967

SHF65-160/D137

80

80

530

480

100

855

310

1000

1373

1967

SHF65-160/D168

80

80

530

480

100

820

310

1000

1373

1967

SHF65-160/D177

80

80

530

480

100

920

360

1200

1423

2017

SHF65-200/D192

80

80

530

480

100

920

330

1200

1418

2012

SHF65-200/D203

80

80

530

480

100

970

380

1350

1468

2062

SHF65-200/D215

80

80

530

480

100

970

380

1350

1493

2087

SHF65-250/D240

80

80

640

590

100

1130

360

1550

1473

2067

SHF65-250/D255

80

80

640

590

100

1130

360

1550

1473

2067

SHF80-160/D169

100

100

530

480

125

920

330

1250

1501

2108

SHF80-160/D177

100

100

530

480

125

920

330

1250

1501

2108

SHF80-160/D186

100

100

530

480

125

970

380

1350

1551

2158

SHF80-200/D198

100

100

530

480

125

970

380

1450

1576

2183

SHF80-200/D215

100

100

640

590

125

1095

360

1550

1556

2163

SHF80-200/D226

100

100

640

590

125

1095

360

1550

1556

2163

SHF80-250/D237

100

100

640

590

125

1180

365

1550

1591

2198

SHF80-250/D252

100

100

660

610

125

1240

390

1750

1616

2223

SHF80-250/D270
2
100
Dimensions in mm. Tolerance 10 mm.

100

700

650

125

1310

420

2050

1646

2253

gen00d_shf-en_h_td

113

GEN..D/SHF

GEN..00D/SHF 32-80 SERIES


FIRE-FIGHTING BOOSTER SETS EN 12845

114

GEN..D/SHF

Fire-fighting
booster sets
EN 12845

MARKET SECTORS
CIVIL, INDUSTRIAL
APPLICA
TIONS
APPLICATIONS
Fixed fire-fighting systems.

Automatic Sprinkler systems.

GEN..D/SHF

GEN..01D/SHF
Series

SPECIFICA
TIONS
SPECIFICATIONS
Flow up to 220 m3/h.
Head up to 100 m.
Panel supply power voltage:

- Electric pump: 1 x 230V 10%.


- Diesel engine pump: 1 x 230V
10%.

Frequency: 50 Hz.
Voltage for controls outside panel:
12 - 24 Vac.

Protection grade:

Electric motor start :

- Direct start for powers up to 22 kW


included for electric pump.
Diesel engine with battery start.

Service pump in

horizontal design
design:
- SHF series.

ey pump
jockey
Electric jock

with vertical axis


axis:
- SV Series (motor protection
grade IP55).

- electric panel: IP54.

Electric pumps maximum power


75 kW.

115

Maximum running pressure: 12 bar.

GEN..D/SHF

GEN..01D/SHF 32-80 SERIES


FIRE-FIGHTING BOOSTER SETS EN 12845

For the overall dimensions of the fuel tank and the starting batteries, see tables on pages 20-25.

116

GEN..01D/SHF 32-80 SERIES


FIRE-FIGHTING BOOSTER SETS EN 12845
DRW N DNA

DNP

DNM

A1

SHF32-125/D121

R 2"

Rp 1"

R 1"1/2

330

220

280

905

80

225

362 1400 400

950 1265 1013 1587

SHF32-125/D136

R 2"

Rp 1"

R 1"1/2

330

220

280

905

80

225

362 1400 400

950 1265 1013 1587

SHF32-160/D150

R 2"

Rp 1"

R 1"1/2

330

220

280

885

80

225

382 1400 400

950 1245 1053 1627

SHF32-160/D168

R 2"

Rp 1"

R 1"1/2

330

220

280

885

80

225

382 1400 400

950 1245 1053 1627

SHF32-200/D188

R 2"

Rp 1"

R 1"1/2

330

220

280

885

80

225

360 1400 400

950 1245 1051 1625

SHF32-200/D204

R 2"

Rp 1"

R 1"1/2

400

225

280 1005

80

225

360 1400 475 1100 1365 1051 1625

SHF32-250/D222

R 2"

Rp 1"

R 1"1/2

400

225

280 1020 100

225

380 1400 475 1100 1400 1116 1690

SHF32-250/D242

R 2"

Rp 1"

R 1"1/2

400

225

280 1020 100

225

380 1400 475 1100 1400 1116 1690

SHF32-250/D256

R 2"

Rp 1"

R 1"1/2

400

225

280

915

100

225

380 1400 475 1100 1295 1116 1690

SHF40-125/D112

65

Rp 1"

65

330

220

280

885

80

225

362 1400 400

950 1245 1206 1794

SHF40-125/D126

65

Rp 1"

65

330

220

280

885

80

225

362 1400 400

950 1245 1206 1794

SHF40-125/D143

65

Rp 1"

65

330

220

280

885

80

225

362 1400 400

950 1245 1206 1794

SHF40-160/D159

65

Rp 1"

65

330

220

280

885

80

225

382 1400 400

950 1245 1246 1834

SHF40-160/D171

65

Rp 1"

65

330

220

280

885

80

225

382 1400 400

950 1245 1246 1834

SHF40-200/D190

65

Rp 1"

65

400

225

280

985

100

225

410 1400 475 1100 1365 1294 1882

SHF40-200/D209

65

Rp 1"

65

400

225

280

985

100

225

410 1400 475 1100 1365 1294 1882

SHF40-250/D218

65

Rp 1"

65

390

235

280

975

100

225

380 1400 475 1100 1355 1309 1897

SHF40-250/D233

65

Rp 1"

65

390

235

280 1170 100

225

430 1400 475 1100 1550 1359 1947

SHF40-250/D251

65

Rp 1"

65

390

235

280 1170 100

225

430 1400 475 1100 1550 1359 1947

SHF50-125/D119

65

Rp 1"

65

330

220

280

885

100

225

382 1400 400

950 1265 1338 1926

SHF50-125/D130

65

Rp 1"

65

330

220

280

885

100

225

382 1400 400

950 1265 1338 1926

SHF50-125/D139

65

Rp 1"

65

400

225

280

955

100

225

382 1400 475 1100 1335 1338 1926

SHF50-160/D158

65

Rp 1"

65

400

225

280

985

100

225

410 1400 475 1100 1365 1386 1974

SHF50-160/D174

65

Rp 1"

65

400

225

280

985

100

225

410 1400 475 1100 1365 1386 1974

SHF50-200/D197

65

Rp 1"

65

390

235

280

975

100

225

410 1400 475 1100 1355 1406 1994

SHF50-200/D209

65

Rp 1"

65

390

235

280

975

100

225

410 1400 475 1100 1355 1406 1994

SHF50-250/D224

65

Rp 1"

65

390

235

280 1170 100

225

430 1400 475 1100 1550 1451 2039

SHF50-250/D237

65

Rp 1"

65

390

235

280 1220 100

225

480 1550 475 1100 1600 1501 2089

SHF50-250/D250

65

Rp 1"

65

390

235

280 1220 100

225

480 1550 475 1100 1600 1501 2089

SHF65-160/D119

80

Rp 1"

80

400

225

280

100

225

360 1400 475 1100 1350 1423 2017

SHF65-160/D129

80

Rp 1"

80

400

225

280 1020 100

225

410 1400 475 1100 1400 1473 2067

SHF65-160/D137

80

Rp 1"

80

390

235

280 1105 100

225

410 1400 475 1100 1485 1473 2067

SHF65-160/D168

80

Rp 1"

80

390

235

280

100

225

410 1400 475 1100 1355 1473 2067

SHF65-160/D177

80

Rp 1"

80

390

235

280 1170 100

225

460 1400 475 1100 1550 1523 2117

SHF65-200/D192

80

Rp 1"

80

390

235

280 1170 100

225

430 1400 475 1100 1550 1518 2112

SHF65-200/D203

80

Rp 1"

80

390

235

280 1220 100

225

480 1550 475 1100 1600 1568 2162

SHF65-200/D215

80

Rp 1"

80

390

235

280 1220 100

225

480 1550 475 1100 1600 1593 2187

SHF65-250/D240

80

Rp 1"

80

460

380

180 1270 100

245

480 1750 530 1370 1550 1593 2187

SHF65-250/D255

80

Rp 1"

80

460

380

180 1270 100

245

480 1750 530 1370 1550 1593 2187

SHF80-160/D169

100

Rp 1"

100

390

235

280 1170 125

225

430 1400 475 1100 1575 1601 2208

SHF80-160/D177

100

Rp 1"

100

390

235

280 1170 125

225

430 1400 475 1100 1575 1601 2208

SHF80-160/D186

100

Rp 1"

100

390

235

280 1220 125

225

480 1550 475 1100 1625 1651 2258

SHF80-200/D198

100

Rp 1"

100

390

235

280 1370 125

225

480 1550 475 1100 1775 1676 2283

SHF80-200/D215

100

Rp 1"

100

500

270

280 1440 125

245

480 1750 530 1300 1845 1676 2283

SHF80-200/D226

100

Rp 1"

100

500

270

280 1440 125

245

480 1750 530 1300 1845 1676 2283

SHF80-250/D237

100

Rp 1"

100

505

265

280 1550 125

245

485 1750 530 1300 1955 1711 2318

SHF80-250/D252

100

Rp 1"

100

505

265

245 1380 125

265

530 1770 530 1300 1750 1756 2363

SHF80-250/D270
2
100
Rp 1"
* Wall mounted control panel.
Dimensions in mm. Tolerance 10 mm.

100

550

265

575 1350 125

215

560

970

975

570 1385 2050 1786 2393


gen01d_shf-en_g_td

117

GEN..D/SHF

GEN..01D

118

GEN..D/SHF

Fire-fighting
booster sets
EN 12845

MARKET SECTORS
CIVIL, INDUSTRIAL
APPLICA
TIONS
APPLICATIONS
Fixed fire-fighting systems.

Automatic Sprinkler systems.

GEN..D/SHF

Serie
GEN..10D/SHF

SPECIFICA
TIONS
SPECIFICATIONS
Flow up to 440 m3/h.
Head up to100 m.
Panel supply power voltage:

- Electric pump: 3 x 400V 10%.


- Diesel engine pump: 1 x 230V
10%.

Frequency: 50 Hz.
Voltage for controls outside panel:

Electric motor start :

- Direct start for powers up to 22 kW


included for pump (GEND...).
- Star/delta start for higher powers
(GENY... set).
Diesel engine with battery start.

Service pump in

horizontal design
design:
- SHF series (IP55 electric motor
protection).

12 - 24 Vac.

Protection grade:

Maximum running pressure: 12 bar.

- electric panel: IP54.

Electric pumps maximum power


75 kW.

119

GEN..D/SHF

GEN..10D/SHF 32-80 SERIES


FIRE-FIGHTING BOOSTER SETS EN 12845

For the overall dimensions of the fuel tank and the starting batteries, see tables on pages 20-25.

120

GEN..10D

DRW N DNA

DNM

A1

SHF32-125/07/D121

R 2"

R 2"

320

310

240

870

80

362

1400

470

1100

1230

1019

1599

SHF32-125/11/D136

R 2"

R 2"

320

310

240

870

80

362

1400

470

1100

1230

1019

1599

SHF32-160/15/D150

R 2"

R 2"

320

310

240

850

80

382

1400

470

1100

1210

1059

1639

SHF32-160/22/D168

R 2"

R 2"

320

310

240

850

80

382

1400

470

1100

1210

1059

1639

SHF32-200/30/D188
SHF32-200/40/D204
SHF32-250/55/D222

1
1
1

R 2"
R 2"
R 2"

R 2"
R 2"
R 2"

320
380
380

310
350
350

240
240
240

850
960
1025

80
80
100

360
360
380

1400
1400
1400

470
570
570

1100
1300
1300

1210
1320
1405

1057
1057
1122

1637
1637
1702

SHF32-250/75/D242

R 2"

R 2"

380

350

240

1025

100

380

1400

570

1300

1405

1122

1702

SHF32-250/110/D256

R 2"

R 2"

420

370

280

995

100

380

1400

610

1400

1375

1122

1702

SHF40-125/11/D112

65

65

320

310

240

850

80

362

1400

470

1100

1210

1206

1794

SHF40-125/15/D126

65

65

320

310

240

850

80

362

1400

470

1100

1210

1206

1794

SHF40-125/22/D143

65

65

320

310

240

850

80

362

1400

470

1100

1210

1206

1794

SHF40-160/30/D159

65

65

320

310

240

850

80

382

1400

470

1100

1210

1246

1834

SHF40-160/40/D171

65

65

320

310

240

850

80

382

1400

470

1100

1210

1246

1834

SHF40-200/55/D190

65

65

380

350

240

940

100

410

1400

570

1300

1320

1294

1882

SHF40-200/75/D209

65

65

380

350

240

940

100

410

1400

570

1300

1320

1294

1882

SHF40-250/110A/D218

65

65

420

370

180

1145

100

380

1400

610

1400

1425

1309

1897

SHF40-250/110/D233

65

65

420

370

280

1225

100

430

1400

610

1400

1605

1359

1947

SHF40-250/150/D251

65

65

420

370

280

1225

100

430

1400

610

1400

1605

1359

1947

SHF50-125/22/D119

65

80

320

310

240

850

100

382

1400

470

1100

1230

1345

1939

SHF50-125/30/D130

65

80

320

310

240

850

100

382

1400

470

1100

1230

1345

1939

SHF50-125/40/D139

65

80

380

350

240

910

100

382

1400

570

1300

1290

1345

1939

SHF50-160/55/D158

65

80

380

350

240

940

100

410

1400

570

1300

1320

1393

1987

SHF50-160/75/D174

65

80

380

350

240

940

100

410

1400

570

1300

1320

1393

1987

SHF50-200/110A/D197

65

80

420

370

130

1080

100

410

1400

610

1400

1460

1413

2007

SHF50-200/110/D209

65

80

420

370

205

1080

100

410

1400

610

1400

1460

1413

2007

SHF50-250/150/D224

65

80

415

375

280

1225

100

430

1400

610

1400

1605

1458

2052

SHF50-250/185/D237

65

80

420

370

280

1275

100

480

1550

610

1400

1655

1508

2102

SHF50-250/220/D250

65

80

420

370

280

1275

100

480

1550

610

1400

1655

1508

2102

SHF65-160/40/D119

80

100

380

350

240

925

100

360

1400

570

1300

1305

1435

2042

SHF65-160/55/D129

80

100

380

350

240

975

100

410

1400

570

1300

1355

1485

2092

SHF65-160/75/D137

80

100

420

370

240

1065

100

410

1400

570

1360

1445

1485

2092

SHF65-160/110A/D168

80

100

420

370

180

1145

100

410

1400

610

1400

1425

1485

2092

SHF65-160/110/D177

80

100

415

375

280

1225

100

460

1400

610

1400

1605

1535

2142

SHF65-200/150/D192

80

100

415

375

280

1225

100

430

1400

610

1400

1605

1530

2137

SHF65-200/185/D203

80

100

420

370

280

1275

100

480

1550

610

1400

1655

1580

2187

SHF65-200/220/D215

80

100

420

370

280

1275

100

480

1550

610

1400

1655

1605

2212

SHF65-250/300/D240

80

100

480

450

290

1450

100

480

1750

730

1660

1840

1605

2212

SHF65-250/370/D255

80

100

480

450

290

1450

100

480

1750

730

1660

1840

1605

2212

SHF80-160/110/D169

100

125

415

375

280

1225

125

430

1400

610

1400

1630

1614

2234

SHF80-160/150/D177

100

125

415

375

280

1225

125

430

1400

610

1400

1630

1614

2234

SHF80-160/185/D186

100

125

420

370

280

1275

125

480

1550

610

1400

1680

1664

2284

SHF80-200/220/D198

100

125

420

370

330

1275

125

480

1550

610

1400

1730

1689

2309

SHF80-200/300/D215

100

125

480

450

300

1415

125

480

1750

730

1660

1840

1689

2309

SHF80-200/370/D226

100

125

480

450

300

1415

125

480

1750

730

1660

1840

1689

2309

SHF80-250/450/D237

100

125

480

450

320

1450

125

485

1750

730

1660

1895

1724

2344

SHF80-250/550/D252

100

125

480

450

355

1505

125

530

1770

730

1660

1985

1769

2389

SHF80-250/750/D270
2
100
* Wall mounted control panel.
Dimensions in mm. Tolerance 10 mm.

125

550

555

555

1450

125

560

800

1905

2150

1799

2419

gen10d_shf-en_f_td

121

GEN..D/SHF

GEN..10D/SHF 32-80 SERIES


FIRE-FIGHTING BOOSTER SETS EN 12845

122

GEN..D/SHF

Fire-fighting
booster sets
EN 12845

MARKET SECTORS
CIVIL, INDUSTRIAL
APPLICA
TIONS
APPLICATIONS
Fixed fire-fighting systems.

Automatic Sprinkler systems.

GEN..D/SHF

GEN..11D/SHF
Series

SPECIFICA
TIONS
SPECIFICATIONS
Flow up to 440 m3/h.
Head up to 100 m.
Panel supply power voltage:

- Electric pump: 3 x 400V 10%.


- Diesel engine pump: 1 x 230V
10%.

Frequency: 50 Hz.
Voltage for controls outside panel:

Electric motor start :

- Direct start for powers up to 22 kW


included for pump (GEND...).
- Star/delta start for higher powers
(GENY... set).
Diesel engine with battery start.

Service pump in

horizontal design
design:
- SHF series (IP55 electric motor
protection).

12 - 24 Vac.

Protection grade:

ey pump
Electric jock
jockey

- electric panel: IP54.

Electric pumps maximum power


75 kW.

with vertical axis


axis:
- SV Series (motor protection
grade IP55).

Maximum running pressure: 12 bar.

123

GEN..D/SHF

GEN..11D/SHF 32-80 SERIES


FIRE-FIGHTING BOOSTER SETS EN 12845

For the overall dimensions of the fuel tank and the starting batteries, see tables on pages 20-25.

124

GEN..11D/SHF 32-80 SERIES


FIRE-FIGHTING BOOSTER SETS EN 12845
GEN..11D

DRW DNA

DNP

DNM

A1

I1

SHF32-125/07/D121

R 2"

Rp 1"

R 2" 305 295

240

905

80

225

362 1400 400

400 1400 1225 1019 1599

SHF32-125/11/D136

R 2"

Rp 1"

R 2" 305 295

240

905

80

225

362 1400 400

400 1400 1225 1019 1599

SHF32-160/15/D150

R 2"

Rp 1"

R 2" 305 295

240

850

80

225

382 1400 400

400 1400 1170 1059 1639

SHF32-160/22/D168

R 2"

Rp 1"

R 2" 305 295

240

850

80

225

382 1400 400

400 1400 1170 1059 1639

SHF32-200/30/D188

R 2"

Rp 1"

R 2" 305 295

240

850

80

225

360 1400 400

400 1400 1170 1057 1637

SHF32-200/40/D204

R 2"

Rp 1"

R 2" 400 375

240 1005

80

225

360 1400 475

430 1680 1325 1057 1637

SHF32-250/55/D222

R 2"

Rp 1"

R 2" 355 375

240 1005 100

225

380 1400 475

475 1680 1345 1122 1702

SHF32-250/75/D242

R 2"

Rp 1"

R 2" 355 375

240 1005 100

225

380 1400 475

475 1680 1345 1122 1702

SHF32-250/110/D256

R 2"

Rp 1"

R 2" 355 375

280 1120 100

225

380 1400 475

475 1680 1500 1122 1702

SHF40-125/11/D112

65

Rp 1"

65

305 295

240

850

80

225

362 1400 400

400 1400 1170 1206 1794

SHF40-125/15/D126

65

Rp 1"

65

305 295

240

850

80

225

362 1400 400

400 1400 1170 1206 1794

SHF40-125/22/D143

65

Rp 1"

65

305 295

240

850

80

225

362 1400 400

400 1400 1170 1206 1794

SHF40-160/30/D159

65

Rp 1"

65

305 295

240

850

80

225

382 1400 400

400 1400 1170 1246 1834

SHF40-160/40/D171

65

Rp 1"

65

305 295

240

850

80

225

382 1400 400

400 1400 1170 1246 1834

SHF40-200/55/D190

65

Rp 1"

65

400 375

240

940

100

225

410 1400 475

430 1680 1280 1294 1882

SHF40-200/75/D209

65

Rp 1"

65

400 375

240

940

100

225

410 1400 475

430 1680 1280 1294 1882

SHF40-250/110A/D218 2

65

Rp 1"

65

365 355

180

995

100

225

380 1400 475

475 1670 1275 1309 1897

SHF40-250/110/D233

65

Rp 1"

65

375 385

280

995

100

225

430 1400 475

475 1710 1375 1359 1947

SHF40-250/150/D251

65

Rp 1"

65

375 385

280

995

100

225

430 1400 475

475 1710 1375 1359 1947

SHF50-125/22/D119

65

Rp 1"

80

305 295

240

850

100

225

382 1400 400

400 1400 1190 1345 1939

SHF50-125/30/D130

65

Rp 1"

80

305 295

240

850

100

225

382 1400 400

400 1400 1190 1345 1939

SHF50-125/40/D139

65

Rp 1"

80

400 375

240 1005 100

225

382 1400 475

430 1680 1345 1345 1939

SHF50-160/55/D158

65

Rp 1"

80

400 375

240

940

100

225

410 1400 475

430 1680 1280 1393 1987

SHF50-160/75/D174

65

Rp 1"

80

400 375

240

940

100

225

410 1400 475

430 1680 1280 1393 1987

SHF50-200/110A/D197 2

65

Rp 1"

80

385 345

130

895

100

225

410 1400 475

475 1680 1125 1413 2007

SHF50-200/110/D209

65

Rp 1"

80

385 345

205

895

100

225

410 1400 475

475 1680 1200 1413 2007

SHF50-250/150/D224

65

Rp 1"

80

375 385

280

995

100

225

430 1400 475

475 1710 1375 1458 2052

SHF50-250/185/D237

65

Rp 1"

80

400 395

280

995

100

225

480 1550 475

475 1745 1375 1508 2102

SHF50-250/220/D250

65

Rp 1"

80

400 395

280

995

100

225

480 1550 475

475 1745 1375 1508 2102

SHF65-160/40/D119

80

Rp 1"

100 400 375

240

925

100

225

360 1400 475

430 1680 1265 1435 2042

SHF65-160/55/D129

80

Rp 1"

100 390 365

240

975

100

225

410 1400 475

430 1660 1315 1485 2092

SHF65-160/75/D137

80

Rp 1"

100 385 330

240 1065 100

225

410 1400 475

430 1620 1405 1485 2092

SHF65-160/110A/D168 2

80

Rp 1"

100 365 355

180

995

100

225

410 1400 475

475 1670 1275 1485 2092

SHF65-160/110/D177

80

Rp 1"

100 375 385

280

995

100

225

460 1400 475

475 1710 1375 1535 2142

SHF65-200/150/D192

80

Rp 1"

100 375 385

280

995

100

225

430 1400 475

475 1710 1375 1530 2137

SHF65-200/185/D203

80

Rp 1"

100 400 395

280

995

100

225

480 1550 475

475 1745 1375 1580 2187

SHF65-200/220/D215

80

Rp 1"

100 400 395

280

995

100

225

480 1550 475

475 1745 1375 1605 2212

SHF65-250/300/D240

80

Rp 1"

100 470 435

290 1160 100

195

480 1750 530

490 1925 1550 1605 2212

SHF65-250/370/D255

80

Rp 1"

100 470 435

290 1160 100

195

480 1750 530

490 1925 1550 1605 2212

SHF80-160/110/D169

100

Rp 1"

125 375 385

280

995

125

225

430 1400 475

475 1710 1400 1614 2234

SHF80-160/150/D177

100

Rp 1"

125 375 385

280

995

125

225

430 1400 475

475 1710 1400 1614 2234

SHF80-160/185/D186

100

Rp 1"

125 400 395

280

995

125

225

480 1550 475

475 1745 1400 1664 2284

SHF80-200/220/D198

100

Rp 1"

125 400 395

330

995

125

225

480 1550 475

475 1745 1450 1689 2309

SHF80-200/300/D215

100

Rp 1"

125 470 435

300 1125 125

195

480 1750 530

490 1925 1550 1689 2309

SHF80-200/370/D226

100

Rp 1"

125 470 435

300 1125 125

195

480 1750 530

490 1925 1550 1689 2309

SHF80-250/450/D237

100

Rp 1"

125 470 395

320 1205 125

195

485 1750 530

490 1885 1650 1724 2344

SHF80-250/550/D252

100

Rp 1"

125 485 455

355 1270 125

215

530 1770 530

530 2000 1750 1769 2389

SHF80-250/750/D270
2 100
Rp 1"
* Wall mounted control panel.
Dimensions in mm. Tolerance 10 mm.

125 585 540

555 1370 125

215

560

570 2265 2050 1799 2419

570

gen11d_shf-en_h_td

125

GEN..D/SHF

126

GEN..D/SHF

GEN..D/SHF SERIES OF BOOSTER SETS (POSITIVE SUCTION HEAD)


Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

0
0

20
20

40

ISO 9906 - Annex A

60

40

80

60

80

Q [US gpm]
120

100

0,25

20
20

40

ISO 9906 - Annex A

60

40

100 Q [Imp gpm]

80

60

80

Q [US gpm]
120

100

0,25

0,8

H [ft]

Hc [m]

0,8

Hc [m]

2900 [rpm]

SH 32 - 160

Q [Imp gpm]
100

0,20

H [ft]

SH 32 - 125

0,20
0,6

0,6

0,15

0,15
0,4

0,4

0,10

0,10

0,2

0,2

0,05

0,05

0,00
6

0,0

0,00
8

0,0
25

15

20

15
32-160/15

150

65-160/150
32-160/15 178
164

10

NPSHr [ft]

NPSHr [m]

10

NPSHr [ft]

NPSHr [m]

2
5

10

15

100

200

20
20

25

300

400

2900 [rpm]

SH 32 - 200
0

20

40
60

Q [l/min]
500

0
0

80
80

100

100 Q [Imp gpm]

0
0

15

100

200

300

40

400

60

Q [l/min]
500

ISO 9906 - Annex A

60

40

Q [m330
/h]

25

2900 [rpm]

20
20

20

100 Q [Imp gpm]

80
80

Q [US gpm]
120

100

0,25

0,8

H [ft]

Hc [m]

0,8

Hc [m]

10

SH 32 - 250

Q [US gpm]
120

0,25

ISO 9906 - Annex A

60

40

Q [m3/h]
30

0,20

H [ft]

0,20
0,6

0,6

0,15

0,15
0,4

0,4

0,10

0,10

0,2

0,2

0,05

0,05

0,00
8

0,0

0,00
8

0,0

25

25

32-250/55

20

20

15
4
32-200/40 204
65-160/150
178

10

NPSHr [m]

188

15
4
65-160/150
178

10

NPSHr [ft]

32-250/110 256
32-250/75 242

NPSHr [ft]

0
0
0

10
100

15
200

20
300

25
400

Q [m330
/h]
Q [l/min]
500

76519_A_CH

0
0
0

10
100

15
200

20
300

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

127

25
400

Q [m330
/h]
Q [l/min]
500

76520_A_CH

NPSHr [m]

32-200/30

222

GEN..D/SHF

0
0

76518_A_CH

76517_A_CH

GEN..D/SHF SERIES OF BOOSTER SETS (POSITIVE SUCTION HEAD)


Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

50

ISO 9906 - Annex A

100

50

150

100

200 Q [US gpm]

150

0,25

50

ISO 9906 - Annex A

100

50

Q [Imp gpm]

150

100

200 Q [US gpm]

150

0,25

0,8

H [ft]

Hc [m]

0,8

Hc [m]

2900 [rpm]

SH 40 - 160

Q [Imp gpm]

0,20

H [ft]

SH 40 - 125

0,20
0,6

0,6

0,15

0,15
0,4

0,4

0,10

0,10

0,2

0,2

0,05

0,05

0,0

0,00
8

0,0

25

20

10

NPSHr [m]

15
4

20

NPSHr [ft]

15
4
10
2

100

20
200

300

30
400

50

500

600

700

150

100

Q800
[l/min]

0
0
0

ISO 9906 - Annex A

100

50

Q [m3/h]
50

40

2900 [rpm]

SH 40 - 200

Q [Imp gpm]

100

20
200

0
0

30

300

40

400

500

600

2900 [rpm]
50

100

50

Q [m3/h]
60

50
700

Q800
[l/min]

ISO 9906 - Annex A


200 Q [Imp gpm]

150

100

150

Q [US
250gpm]

200

0,25

0,8

H [ft]

Hc [m]

0,8

Hc [m]

10

SH 40 - 250

Q [US gpm]
200

150

0,25

0,20

0,20
0,6

0,6

0,15

0,15
0,4

0,4

0,10

0,10

0,2

0,2

0,05

0,05

0,0

0,00
8

0,0

25

25

20

10

NPSHr [m]

15
4

20

NPSHr [ft]

40-250/110A

15

216

4
65-160/150
178
40-250/150
40-250/110

251
233

0
0
0

10
100

20
200

300

30
400

40
500

50
600

700

Q [m3/h]
60
Q800
[l/min]

76523_A_CH

10

NPSHr [ft]

0,00
8

NPSHr [m]

GEN..D/SHF

10

H [ft]

76522_A_CH

76521_A_CH

0
0
0

10
200

20

30
400

40
600

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

128

50
800

Q [m360
/h]
Q [l/min]
1000

76524_A_CH

NPSHr [m]

25

NPSHr [ft]

0,00
8

GEN..D/SHF SERIES OF BOOSTER SETS (POSITIVE SUCTION HEAD)


Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

100

ISO 9906 - Annex A

200

100

300

200

Q [US gpm]
400

300

100

0,25

ISO 9906 - Annex A

200

100

Q [Imp gpm]

300

200

Q [US gpm]
400

300

0,25

0,8

H [ft]

Hc [m]

0,8

Hc [m]

2900 [rpm]

SH 50 - 160

Q [Imp gpm]

0,20

H [ft]

SH 50 - 125

0,20
0,6

0,6

0,15

0,15
0,4

0,4

0,10

0,10

0,2

0,2

0,05

0,05

0,00
8

0,0

0,00
10

0,0

25
30
8
20

15
50-125/40 139
50-125/30
130
65-160/150
178

10

50-160/55

20

119

15
65-160/150
178
50-160/75
174

NPSHr [ft]

119

NPSHr [m]

NPSHr [m]

50-125/22

25

NPSHr [ft]

10
2
2

20
200

40
400

600

60
800

1200

2900 [rpm]

SH 50 - 200
0

100

1000

1400

Q
1600
[l/min]

300

200

Q [Imp gpm]

200

40
400

600

60
800

100

1000

1200

1400

Q
1600
[l/min]

ISO 9906 - Annex A

200

100

3
Q [m100
/h]

80

2900 [rpm]

Q [US gpm]
400

300

20

SH 50 - 250

Q [Imp gpm]

300

200

Q [US gpm]
400

300

H [ft]
0,25

0,8

0,20

H [ft]

0,30
Hc [m]

0,30

0,25

0,8

0,20
0,6

0,6

0,15

0,15
0,4

0,4

0,10

0,10
0,2

0,05

0,00
10

0,2

0,05

0,0

0,00
10

0,0

30

30

8
25

50-200/110 209
65-160/150
178

15

20

6
50-250/150

224

15
65-160/150
178

10

50-250/220
50-250/185

250

NPSHr [ft]

20
NPSHr [m]

NPSHr [m]

197

NPSHr [ft]

50-200/110A

25

10

237

0
0
0

20
200

40
400

600

60
800

1000

80
1200

1400

3
Q [m100
/h]

Q
1600
[l/min]

5
76527_A_CH

0
0
0

20
200

40
400

600

60
800

1000

80
1200

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

129

1400

3
Q [m100
/h]

Q
1600
[l/min]

76528_A_CH

Hc [m]

0
0

ISO 9906 - Annex A

200

100

3
Q [m100
/h]

80

GEN..D/SHF

0
0

76526_A_CH

76525_A_CH

GEN..D/SHF SERIES OF BOOSTER SETS (POSITIVE SUCTION HEAD)


Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

SH 65 - 160
0

100

200

100

ISO 9906 - Annex A

300

200

300

400
400

Q [US600
gpm]

500

100

200

100

ISO 9906 - Annex A

300

200

300

Q
[Imp gpm]
500

400
400

Q [US600
gpm]

500

Hc [m]

H [ft]
0,25

1,2

H [ft]

0,4

0,30
Hc [m]

2900 [rpm]

SH 65 - 160

Q
[Imp gpm]
500

0,8
1,0

0,3
0,20
0,6

0,8
0,2

0,15

0,6
0,4
0,10

0,4
0,1
0,2

0,05

0,2

0,00
10

0,0

0,0
10

0,0

30

30

8
25

15

NPSHr [m]

NPSHr [m]

65-160/40 139
65-160/30 130
65-160/150
178

20

15
65-160/150
178

10

10

65-160/110 177
65-160/110A 168

0
0
200

40

400

600

60
800

1000

100

80
1200

100

1400

1600

2900 [rpm]

SH 65 - 200
200

100

300

1800

2000

3
Q [m140
/h]

Q
2200
[l/min]

0
0
0

ISO 9906 - Annex A

300

200

120

Q
[Imp gpm]
500

400
400

200

40

400

Q [US600
gpm]

500

20

600

60
800

1000

100
100

80
1200

100

1400

1600

200
200

2000

3
Q [m140
/h]

Q
2200
[l/min]

ISO 9906 - Annex A

300
300

120
1800

2900 [rpm]

SH 65 - 250

0,4

400
400

Q [Imp gpm]

500

500

600 Q [US gpm]


700
H [ft]

Hc [m]

H [ft]

Hc [m]

0,6
1,2

0,5
1,5

1,0

0,3

0,4
0,8
0,2

1,0

0,3
0,6
0,2

0,4

0,5

0,1

0,0
10

0,2

0,1

0,0

0,0
10

0,0

30

30

8
25

25

15
65-160/150
178

65-250/300

240

65-250/370

255

10
65-200/220
65-200/185

10

215
203

20
200

400

40
600

60
800

1000

80
1200

1400

100
1600

120
1800

2000

3
Q [m140
/h]

Q
2200
[l/min]

5
76531_A_CH

15

65-160/150
178

0
0
0

20

40
500

60
1000

80

100
1500

120
2000

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

130

140

3
Q [m160
/h]

2500
Q [l/min]

76532_A_CH

20

6
NPSHr [m]

192

NPSHr [ft]

65-200/150

NPSHr [ft]

20

6
NPSHr [m]

GEN..D/SHF

20

5
76529_A_CH

NPSHr [ft]

20

76530_A_CH

119

NPSHr [ft]

65-160/22

25

GEN..D/SHF SERIES OF BOOSTER SETS (POSITIVE SUCTION HEAD)


Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

SH 80 - 160
0
0

200
200

400
400

ISO 9906 - Annex A


600

800

600

Q [US gpm]
1000

800

2900 [rpm]

SH 80 - 200

Q [Imp gpm]

200

400
400

600
600

1000 Q [Imp gpm]

800
800

Q [US gpm]
1200

1000

1,0

0,3

H [ft]

H [ft]

1,2

Hc [m]

0,4

Hc [m]

0,4

200

ISO 9906 - Annex A

0,3

1,5

0,2

1,0

0,1

0,5

0,0
10

0,0

0,8
0,2
0,6

0,4
0,1
0,2

0,0
10

0,0

30

30

8
25

80-160/185
80-160/150

186
177

20

198

80-200/370 225
65-160/150
80-200/300
215
178

10

10

50

100

1000

3000

2900 [rpm]
200

200

400
400

3
Q [m250
/h]

200

2000

SH 80 - 250
0

150

Q4000
[l/min]

0
0
0

50
1000

100

150
2000

200
3000

ISO 9906 - Annex A


600

600

800

Q [Imp gpm]

Q [US gpm]
1000

800

H [ft]

Hc [m]

0,4
1,2

1,0

0,3

0,8
0,2
0,6

0,4
0,1
0,2

0,0
10

0,0

30
8
25

15
65-160/150
178

NPSHr [ft]

20

10
2

0
0
0

50
1000

100

150
2000

200
3000

3
Q [m250
/h]

4000
Q [l/min]

76535_A_CH

250
4000

3
Q [m300
/h]

Q [l/min]
5000

GEN..D/SHF

0
0

76534_A_CH

5
76533_A_CH

NPSHr [m]

15

NPSHr [ft]

15
65-160/150
178

80-200/220

6
NPSHr [m]

NPSHr [m]

20

169x15

NPSHr [ft]

80-160/150

25

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

131

GEN..D/SHF SERIES OF BOOSTER SETS (SUCTION LIF


T)
LIFT)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

SH 32 - 125
0
0

20
20

40

ISO 9906 - Annex A

60

40

80

60

80

Q [US gpm]
120

100

2900 [rpm]

SH 32 - 160

Q [Imp gpm]
100

0,4

20
20

40

ISO 9906 - Annex A

60

40

100 Q [Imp gpm]

80

60

80

Q [US gpm]
120

100

H [ft]

Hc [m]

H [ft]

Hc [m]

0,6

0,5

1,0

0,3

1,5
0,4

0,2

1,0

0,3
0,5
0,2

0,5

0,1
0,1

0,0
6

0,0

0,0
8

0,0
25

15

20

15
32-160/15

150

65-160/150
32-160/15 178
164

10

NPSHr [ft]

NPSHr [m]

10

NPSHr [ft]

NPSHr [m]

2
5

0
0

15

100

0
0

25

300

400

2900 [rpm]

20
20

20

200

SH 32 - 200
40

60

Q [l/min]
500

80
80

100

10

15

100

100 Q [Imp gpm]

Q [US gpm]
120

300

40

400

60

Q [l/min]
500

ISO 9906 - Annex A

60

40

Q [m330
/h]

25

2900 [rpm]

20
20

20

200

SH 32 - 250

100 Q [Imp gpm]

80
80

Q [US gpm]
120

100

0,5

H [ft]

Hc [m]

0,6
H [ft]

0,5

1,5

1,5

0,4

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5

0,1

0,1

0,0
8

0,0

0,0
8

0,0

25

25

32-250/55

20

20

15
4
32-200/40 204
65-160/150
178

10

NPSHr [m]

188

15
4
65-160/150
178

10

NPSHr [ft]

32-250/110 256
32-250/75 242

NPSHr [ft]

32-200/30

222

0
0
0

10
100

15
200

20
300

25
400

Q [m330
/h]
Q [l/min]
500

76499_A_CH

0
0
0

10
100

15
200

20
300

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

132

25
400

Q [m330
/h]
Q [l/min]
500

76500_A_CH

Hc [m]

0
0

ISO 9906 - Annex A

60

40

Q [m3/h]
30

0,6

NPSHr [m]

GEN..D/SHF

10

76498_A_CH

76497_A_CH

GEN..D/SHF SERIES OF BOOSTER SETS (SUCTION LIF


T)
LIFT)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

SH 40 - 125
0

50

ISO 9906 - Annex A

100

50

150

100

200 Q [US gpm]

150

50

ISO 9906 - Annex A

100

50

Q [Imp gpm]

150

100

200 Q [US gpm]

150

H [ft]
0,5

H [ft]

0,6
Hc [m]

0,6

0,5

1,5

1,5

0,4

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5

0,1

0,1

0,0

0,0
8

0,0

25

20

10

NPSHr [m]

15
4

20

NPSHr [ft]

15
4
10
2

10
100

20
200

300

30
400

50

500

600

2900 [rpm]

SH 40 - 200

700

150

100

Q800
[l/min]

Q [Imp gpm]

100

20
200

Q [US gpm]
200

150

10

30

300

40

400

500

50

100

50

Q [m3/h]
60

50
600

2900 [rpm]

SH 40 - 250

0,6

700

Q800
[l/min]

ISO 9906 - Annex A


200 Q [Imp gpm]

150

100

150

Q [US
250gpm]

200

0,5

H [ft]

Hc [m]

0,6
H [ft]

Hc [m]

0
0

ISO 9906 - Annex A

100

50

Q [m3/h]
50

40

0,5

1,5

1,5

0,4

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5

0,1

0,1

0,0
8

0,0

0,0
8

0,0

25

20

10

NPSHr [m]

15
4

20

NPSHr [ft]

NPSHr [m]

25

40-250/110A

15

216

4
65-160/150
178
40-250/150
40-250/110

233

0
0
0

10
100

20
200

300

30
400

40
500

50
600

700

Q [m3/h]
60
Q800
[l/min]

76503_A_CH

10

251

0
0
0

10
200

20

30
400

40
600

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

133

50
800

Q [m360
/h]
Q [l/min]
1000

GEN..D/SHF

0
0

76502_A_CH

76501_A_CH

NPSHr [ft]

NPSHr [m]

25

NPSHr [ft]

0,0
8

76504_A_CH

Hc [m]

2900 [rpm]

SH 40 - 160

Q [Imp gpm]

GEN..D/SHF SERIES OF BOOSTER SETS (SUCTION LIF


T)
LIFT)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

SH 50 - 125
0

100

ISO 9906 - Annex A

200

100

300

200

Q [US gpm]
400

300

100

ISO 9906 - Annex A

200

100

Q [Imp gpm]

300

200

Q [US gpm]
400

300

H [ft]
0,5

H [ft]

0,6
Hc [m]

0,6
Hc [m]

2900 [rpm]

SH 50 - 160

Q [Imp gpm]

0,5

1,5

1,5

0,4

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5

0,1

0,1

0,0
8

0,0

0,0
10

0,0

25
30
8
20

15
50-125/40 139
50-125/30
130
65-160/150
178

10

50-160/55

20

119

15
65-160/150
178
50-160/75
174

NPSHr [ft]

119

NPSHr [m]

NPSHr [m]

50-125/22

25

NPSHr [ft]

10
2
2

0
0
200

40
400

600

60
800

100

1000

1200

1400

Q
1600
[l/min]

300

200

Q [Imp gpm]

200

40
400

600

60
800

100

1000

1200

1400

Q
1600
[l/min]

ISO 9906 - Annex A

200

100

3
Q [m100
/h]

80

2900 [rpm]

Q [US gpm]
400

300

20

SH 50 - 250

Q [Imp gpm]

300

200

Q [US gpm]
400

300

H [ft]
0,5

H [ft]

0,6
Hc [m]

0,6

0,5

1,5

1,5

0,4

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5

0,1

0,1

0,0
10

0,0

0,0
10

0,0

30

30

8
25

20

15

NPSHr [m]

50-200/110 209
65-160/150
178

20

6
50-250/150

224

15
65-160/150
178

10

50-250/220
50-250/185

250

NPSHr [ft]

197

NPSHr [ft]

50-200/110A

25

10

237

0
0
0

20
200

40
400

600

60
800

1000

80
1200

1400

3
Q [m100
/h]

Q
1600
[l/min]

5
76507_A_CH

0
0
0

20
200

40
400

600

60
800

1000

80
1200

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

134

1400

3
Q [m100
/h]

Q
1600
[l/min]

76508_A_CH

Hc [m]

0
0

ISO 9906 - Annex A

200

100

3
Q [m100
/h]

80

2900 [rpm]

SH 50 - 200

NPSHr [m]

GEN..D/SHF

20

76506_A_CH

76505_A_CH

GEN..D/SHF SERIES OF BOOSTER SETS (SUCTION LIF


T)
LIFT)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

SH 65 - 160
0

100

200

100

ISO 9906 - Annex A

300

200

300

400
400

Q [US600
gpm]

500

100

200

100

ISO 9906 - Annex A

300

200

300

Q
[Imp gpm]
500

400
400

Q [US600
gpm]

500

H [ft]
0,5

H [ft]

0,6
Hc [m]

0,6

0,5

1,5

1,5

0,4

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5

0,1

0,1

0,0
10

0,0

0,0
10

0,0

30

30

8
25

15
65-160/150
178

10

10

65-160/110 177
65-160/110A 168

0
0
0

20
200

40

400

600

60
800

1000

100

1200

100

1400

1600

2900 [rpm]

SH 65 - 200
0

80

200

100

300

1800

2000

3
Q [m140
/h]

Q
2200
[l/min]

Q
[Imp gpm]
500

400
400

200

40

400

Q [US600
gpm]

500

20

600

60
800

1000

100
100

80
1200

100

1400

1600

200
200

2000

3
Q [m140
/h]

Q
2200
[l/min]

ISO 9906 - Annex A

300
300

120
1800

2900 [rpm]

SH 65 - 250

400
400

Q [Imp gpm]

500

500

600 Q [US gpm]


700

H [ft]
0,5

H [ft]

0,6
Hc [m]

0,6

0,5

1,5

1,5

0,4

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5

0,1

0,1

0,0
10

0,0

0,0
10

0,0

30

30

8
25

20
192

15
65-160/150
178

20

6
NPSHr [m]

65-200/150

NPSHr [ft]

6
NPSHr [m]

25

65-250/300

240

65-250/370

255

10
65-200/220
65-200/185

10

215
203

20
200

400

40
600

60
800

1000

80
1200

1400

100
1600

120
1800

2000

3
Q [m140
/h]

Q
2200
[l/min]

5
76512_A_CH

15

65-160/150
178

NPSHr [ft]

Hc [m]

0
0

ISO 9906 - Annex A

300

200

120

5
76510_A_CH

0
0
0

20

40
500

60
1000

80

100
1500

120
2000

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

135

140

3
Q [m160
/h]

2500
Q [l/min]

GEN..D/SHF

15

NPSHr [m]

NPSHr [m]

65-160/40 139
65-160/30 130
65-160/150
178

20

NPSHr [ft]

20

76511_A_CH

119

NPSHr [ft]

65-160/22

25

76513_A_CH

Hc [m]

2900 [rpm]

SH 65 - 160

Q
[Imp gpm]
500

GEN..D/SHF SERIES OF BOOSTER SETS (SUCTION LIF


T)
LIFT)
Hc PRES
SURE DROP CURVE IN SUCTION KIT
PRESSURE
2900 [rpm]

SH 80 - 160
0
0

200
200

400
400

ISO 9906 - Annex A


600

800

600

Q [US gpm]
1000

800

200
200

400
400

ISO 9906 - Annex A

600
600

1000 Q [Imp gpm]

800
800

Q [US gpm]
1200

1000

H [ft]
0,5

H [ft]

0,6
Hc [m]

0,6

0,5

1,5

1,5

0,4

0,4

1,0

0,3

1,0

0,3

0,2

0,2
0,5

0,5

0,1

0,1

0,0
10

0,0

0,0
10

0,0

30

30

8
25

80-160/185
80-160/150

186
177

20

198

80-200/370 225
65-160/150
80-200/300
215
178

10

10

0
0

50

100

1000

3000

2900 [rpm]
200

200

400
400

3
Q [m250
/h]

200

2000

SH 80 - 250
0

150

Q4000
[l/min]

0
0
0

50
1000

100

150
2000

200
3000

ISO 9906 - Annex A


600

600

5
76514_A_CH

800

Q [Imp gpm]

Q [US gpm]
1000

800

H [ft]

Hc [m]

0,6

0,5
1,5
0,4

1,0

0,3

0,2
0,5
0,1

0,0
10

0,0

30
8
25

15
65-160/150
178

NPSHr [ft]

20

6
NPSHr [m]

10
2
5

0
0
0

50
1000

100

150
2000

200
3000

3
Q [m250
/h]

4000
Q [l/min]

76516_A_CH

GEN..D/SHF

15

NPSHr [ft]

15
65-160/150
178

80-200/220

6
NPSHr [m]

NPSHr [m]

20

169x15

NPSHr [ft]

80-160/150

25

The declared performance value are valid for liquids with density = 1.0 Kg/dm3 and kinematic viscosity = 1 mm2/sec.
The NPSHr values required for the service pump were obtained in the laboratory. When using them for EN 12845 for fire-fighting systems, increase the value by 1 m.
Hc: Pressure drop curve in suction kit.

136

250
4000

3
Q [m300
/h]

Q [l/min]
5000

76515_A_CH

Hc [m]

2900 [rpm]

SH 80 - 200

Q [Imp gpm]

ACCES
SORIES
ACCESSORIES

ACCESSORIES

137

DIAPHRAGM T
ANKS
TANKS
The booster sets are ready for installation, directly on the manifold, of 24-litre diaphragm tanks, one for each
pump. The sets are also equipped with caps to close off the unused couplings. Larger tanks can also be connected
to the unused end of the discharge manifold. For proper sizing of the tank please refer to the technical appendix.
Kit featuring the following accessories are available on request
request:
diaphragm tank;
on-off ball valve;
operating instructions;
packaging.

DIMENSIONI T
KIT
VASIKIT
A MEMBRANA
DIAPHRAGM
ANK
TANK
DIMENSIONS (mm)

Materials

Volume

PN

Litres

bar

Valve

Diaphragm

Vessel

Valve

205

390

1" FF

EPDM

Painted steel

Nickel-plated brass

24

270

555

1" FF

EPDM

Painted steel

Nickel-plated brass

24

10

270

555

1" FF

EPDM

Painted steel

Nickel-plated brass

24

16

270

555

1" FF

EPDM

Painted steel

Nickel-plated brass

24

10

270

575

1" FF

Butyl

Stainless steel

AISI 316 stainless steel

20

25

270

555

1" FF

EPDM

Painted steel

Nickel-plated brass
Gcom-vmb-en_c_td

COUNTERFLANGE KIT
Counterflange coupling kits made of zinc-plated or stainless steel are available on request.
The counterflange kits are equipped with:
- N. 2 flanges.
- gasket and bolts/screws.

THREADED COUNTERFLANGES
DIMENSIONI KIT CONTROFLANGE TONDE FI
DIMENSIONS (mm)

ACCES
SORIES
ACCESSORIES

KIT

HOLES

TYPE

DN

PN

2"

50

Rp 2

125

16

165

24

18

25

2"

65

Rp 2

145

16

185

23

18

16

3"

80

Rp 3

160

17

200

27

18

16

Gcom-ctf-tonde-f-en_a_td

DIMENSIONI KIT CONTROFLANGE TONDE A SALDARE


-ON COUNTERFLANGES
WELD-ON
WELD
DIMENSIONS (mm)

KIT

HOLES

TYPE

DN

PN

2"

50

61

125

19

165

18

16

2"1/2

65

77

145

20

185

18

16

3"

80

90

160

20

200

18

16

4"

100

116

180

22

220

18

16

5"

125

141,5

210

22

250

18

16

6"

150

170,5

240

24

285

22

16

8"

200

221,5

295

26

340

22

12

16

10"

250

276,5

355

29

405

26

12

16

12"

300

327,5

410

32

460

26

12

16

Gcom-ctf-tonde-s-en_c_td

138

ACCES
SORIES FOR BOOSTER SETS
ACCESSORIES
SUCTION SIDE KIT
The EN 12845 fire-fighting booster sets are supplied without valves and stubs on the suction side of the service pump
and can be completed with suitable kits that depend on legal standards.
These requirements are expressed by EN 12845 (chapter 10.5 and chapter 10.6) and are connected with the maximum
speed value of the water in the pipes, their minimum section and type of installation - suction lift or positive suction
head.
To provide for one suction kit for each duty pump.
The suction side kit are equipped with:
- Anti-vibration joint to attach to the pump inlet.
- Eccentric cone or flanged stub pipe.
- Vacuum pressure gauge.
- On/off butterfly valve (optional in case of positive suction head installation) with lever handle for diameters
up to DN100, butterfly valve with handwheel and reduction manual gear for DN125 and higher. Device for
monitoring ON/OFF status included. Electrical connections by customer.
(Valve lock kit available on request).
- Weld-on flange.

ACCES
SORIES
ACCESSORIES

The following table summarises the pump type installed on the fire-fighting sets and the kit that corresponds to the
installation type.

139

GEN../ SERIES OF FIRE-FIGHTING BOOSTER SETS


SUCTION SIDE KIT DIMENSIONS T
ABLE
TABLE

DIMENSIONS

SUCTION

L (mm)

ACCES
SORIES
ACCESSORIES

KIT
TYPE

DNS

PN

DNA

PN

H (mm)

Type 1

Type 2

50 X 32

50

16

32

16

243

283

50 X 40

50

16

40

16

243

283

65 X 32

65

16

32

16

17

269

312

65 X 40

65

16

40

16

14

255

298

65 X 50

65

16

50

16

266

309

80 X 32

80

16

32

16

23

304

347

80 X 40

80

16

40

16

20

288

331

80 X 50

80

16

50

16

14

266

309

80 X 65

80

16

65

16

277

320

100 X 40

100

16

40

16

33

362

411

100 X 50

100

16

50

16

27

340

389

100 X 65

100

16

65

16

19

307

356

100 X 80

100

16

80

16

13

296

345

125 X 50

125

16

50

16

40

410

463

125 X 65

125

16

65

16

32

377

430

125 X 80

125

16

80

16

25

357

410

125 X 100

125

16

100

16

13

303

356

150 X 65

150

16

65

16

46

460

513

150 X 80

150

16

80

16

40

440

493

150 X 100

150

16

100

16

27

377

430

150 X 125

150

16

125

16

14

355

408

200 X 80

200

10

80

16

65

579

636

200 X 100

200

10

100

16

52

516

573

200 X 125

200

10

125

16

40

482

539

200 X 150

200

10

150

16

25

415

472

250 X 100

250

10

100

16

79

672

737

250 X 125

250

10

125

16

67

637

702

250 X 150

250

10

150

16

52

570

635

300 X 125

300

10

125

16

92

774

849

300 X 150

300

10

150

16

78

707

782

350 X 150

350

10

150

16

94

798

873

400 X 150

400

10

150

16

119

946

Dimensions in mm. Tolerance 10 mm.

1045
kit-asp20-en_a_td

140

GEN../FHF 32-80 SERIES FIRE-FIGHTING BOOSTER SETS


SUCTION SIDE KIT DIMENSIONS T
ABLE
TABLE

PUMP

POSITIVE SUCTION HEAD

SUCTION

RISK

SUCTION

RISK

SUCTION

RISK

CLASS *

KIT

CLASS *

KIT

CLASS *

KIT

CLASS *

TYPE

TYPE

TYPE

SUCTION
KIT
TYPE

FHF 32-125/07

LH

65 X 50

LH

80 X 50

FHF 32-125/11

LH

65 X 50

LH

80 X 50

FHF 32-160/15

LH

65 X 50

LH

80 X 50

FHF 32-160/22

LH

65 X 50

LH

80 X 50

FHF 32-200/30

LH

65 X 50

LH

80 X 50

FHF 32-200/40

LH

65 X 50

LH

80 X 50

FHF 40-125/11

OH1

80 X 65

OH1

100 X 65

FHF 40-125/15

OH1

80 X 65

OH1

100 X 65

FHF 40-125/22

OH1

80 X 65

OH1

100 X 65

FHF 40-160/30

OH1

80 X 65

OH1

100 X 65

FHF 40-160/40

OH1

80 X 65

OH1

100 X 65

FHF 40-200/55

OH1

80 X 65

OH1

100 X 65

FHF 40-200/75

OH1

80 X 65

OH1

100 X 65

FHF 40-250/110A

OH1

80 X 65

OH1

100 X 65

FHF 40-250/110

OH1

80 X 65

OH1

100 X 65

FHF 40-250/150

OH1

80 X 65

OH1

100 X 65

FHF 50-125/22

OH2

100 X 65

OH2

125 X 65

FHF 50-125/30

OH2

100 X 65

OH2

125 X 65

FHF 50-125/40

OH3

125 X 65

OH2

100 X 65

OH3

150 X 65

OH2

125 X 65

FHF 50-160/55

OH3

125 X 65

OH2

100 X 65

OH3

150 X 65

OH2

125 X 65

FHF 50-160/75

OH3

125 X 65

OH2

100 X 65

OH3

150 X 65

OH2

125 X 65

FHF 50-200/110A

OH3

125 X 65

OH2

100 X 65

OH3

150 X 65

OH2

125 X 65

FHF 50-200/110

OH3

125 X 65

OH2

100 X 65

OH3

150 X 65

OH2

125 X 65

FHF 50-250/150

OH3

125 X 65

OH2

100 X 65

OH3

150 X 65

OH2

125 X 65

FHF 50-250/185

OH3

125 X 65

OH2

100 X 65

OH3

150 X 65

OH2

125 X 65

FHF 50-250/220

OH3

125 X 65

OH2

100 X 65

OH3

150 X 65

OH2

125 X 65

FHF 65-125/40

OH3

125 X 80

OH3

150 X 80

FHF 65-125/55

OH3

125 X 80

OH3

150 X 80

FHF 65-125/75

OH3

125 X 80

OH3

150 X 80

FHF 65-160/110A

OH4

150 X 80

OH3

125 X 80

OH4

200 X 80

OH3

150 X 80

FHF 65-160/110

OH4

150 X 80

OH3

125 X 80

OH4

200 X 80

OH3

150 X 80

FHF 65-160/150

OH4

150 X 80

OH3

125 X 80

OH4

200 X 80

OH3

150 X 80

FHF 65-200/150

OH4

150 X 80

OH3

125 X 80

OH4

200 X 80

OH3

150 X 80

FHF 65-200/185

OH4

150 X 80

OH3

125 X 80

OH4

200 X 80

OH3

150 X 80

FHF 65-200/220

OH4

150 X 80

OH3

125 X 80

OH4

200 X 80

OH3

150 X 80

FHF 65-250/220

OH4

150 X 80

OH3

125 X 80

OH4

200 X 80

OH3

150 X 80

FHF 65-250/300

OH4

150 X 80

OH3

125 X 80

OH4

200 X 80

OH3

150 X 80

FHF 65-250/370

OH4

150 X 80

OH3

125 X 80

OH4

200 X 80

OH3

150 X 80

FHF 80-160/150

HH1

200 X 100

OH4

150 X 100

HH1

200 X 100

OH4

200 X 100

FHF 80-160/185

HH1

200 X 100

OH4

150 X 100

HH1

200 X 100

OH4

200 X 100

FHF 80-200/220

HH1

200 X 100

OH4

150 X 100

HH1

200 X 100

OH4

200 X 100

FHF 80-200/300

HH1

200 X 100

OH4

150 X 100

HH1

200 X 100

OH4

200 X 100

FHF 80-250/370

HH1

200 X 100

OH4

150 X 100

HH1

200 X 100

OH4

200 X 100

FHF 80-250/450

HH1

200 X 100

OH4

150 X 100

HH1

200 X 100

OH4

200 X 100

FHF 80-250/550

HH1

200 X 100

OH4

150 X 100

HH1

200 X 100

OH4

* For the risk classes refer to para 6, UNI EN12845.

200 X 100
kit-asp-fhf-en_b_td

- the pumps must be chosen according to the performance levels indicated in Tab. 6 para 7.3.1, Tab.7 para 7.3.2 and the classes of risk.
- some pump models can satisfy the conditions of one or more classes of risk.
- always check the correct selection of the pump depending on the performance level of the set.
** Insert the 50 mm minimal thickness under the GEN10 fire-fighting booster sets only.

141

ACCES
SORIES
ACCESSORIES

SUCTION LIFT
RISK

GEN../FHF 100-125 SERIES FIRE-FIGHTING BOOSTER SETS


SUCTION SIDE KIT DIMENSIONS T
ABLE
TABLE
SUCTION LIFT
PUMP

POSITIVE SUCTION HEAD

RISK

SUCTION

RISK

SUCTION

RISK

SUCTION

RISK

CLASS *

KIT

CLASS *

KIT

CLASS *

KIT

CLASS *

TYPE

TYPE

TYPE

SUCTION
KIT
TYPE

FHF 100-160/185

HH3

250 X 125

HH2

250 X 125

HH3

250 X 125

HH2

250 X 125

FHF 100-160/220

HH4

250 X 125

HH3

250 X 125

HH4

300 X 125**

HH3

250 X 125

FHF 100-160/300

HH4

250 X 125

HH3

250 X 125

HH4

300 X 125**

HH3

250 X 125

FHF 100-200/185

HH3

250 X 125**

HH2

250 X 125**

HH3

250 X 125**

HH2

250 X 125**

FHF 100-200/300

HH3

250 X 125**

HH2

250 X 125**

HH3

250 X 125**

HH2

250 X 125**

FHF 100-200/370

HH4

250 X 125**

HH3

250 X 125**

HH4

300 X 125**

HH3

250 X 125**

FHF 100-200/450

HH4

250 X 125

HH3

250 X 125

HH4

300 X 125**

HH3

250 X 125

FHF 100-250/300

HH3

250 X 125

HH2

250 X 125

HH3

250 X 125

HH2

250 X 125

FHF 100-250/450

HH4

250 X 125

HH3

250 X 125

HH4

300 X 125**

HH3

250 X 125

FHF 100-250/550

HH4

250 X 125

HH3

250 X 125

HH4

300 X 125

HH3

250 X 125

FHF 100-250/750

HH5

300 X 125

HH4

250 X 125

HH5

300 X 125

HH4

300 X 125

FHF 100-250/900

HH6

300 X 125

HH5

300 X 125

HH6

300 X 125

HH5

300 X 125

FHF 125-200/300

HH7

300 X 150

HH6

300 X 150

HH7

300 X 150

HH6

300 X 150

FHF 125-200/450

HH9

300 X 150

HH8

300 X 150

HH9

400 X 150**

HH8

350 X 150**

FHF 125-200/550

HH10

350 X 150**

HH9

300 X 150

HH10

400 X 150**

HH9

400 X 150**

FHF 125-270/750

HH10

350 X 150

HH9

300 X 150

HH10

400 X 150

HH9

400 X 150

FHF 125-270/900

HH10

350 X 150

HH9

300 X 150

HH10

400 X 150

HH9

400 X 150

FHF 125-270/1100

HH10

350 X 150

HH9

300 X 150

HH10

400 X 150

HH9

400 X 150

FHF 125-270/1320

HH10

350 X 150

HH9

300 X 150

HH10

400 X 150

HH9

400 X 150

* For the risk classes refer to para 6, UNI EN12845.

kit-asp-fhf100-en_a_td

- the pumps must be chosen according to the performance levels indicated in Tab. 6 para 7.3.1, Tab. 7 para 7.3.2 and the classes of risk.
- some pump models can satisfy the conditions of one or more classes of risk.
- always check the correct selection of the pump depending on the performance level of the set.

ACCES
SORIES
ACCESSORIES

** Insert the 50mm minimal thickness under the GEN10 fire-fighting booster sets only.

142

GEN../SHF 32-80 SERIES FIRE-FIGHTING BOOSTER SETS


SUCTION SIDE KIT DIMENSIONS T
ABLE
TABLE
PUMP

POSITIVE SUCTION HEAD

SUCTION

RISK

SUCTION

RISK

SUCTION

RISK

CLASS *

KIT

CLASS *

KIT

CLASS *

KIT

CLASS *

TYPE

TYPE

TYPE

SUCTION
KIT
TYPE

SHF 32-125/07

LH

65 X 50

LH

80 X 50

SHF 32-125/11

LH

65 X 50

LH

80 X 50

SHF 32-160/15

LH

65 X 50

LH

80 X 50

SHF 32-160/22

LH

65 X 50

LH

80 X 50

SHF 32-200/30

LH

65 X 50

LH

80 X 50

SHF 32-200/40

LH

65 X 50

LH

80 X 50

SHF 32-250/55

LH

65 X 50

LH

80 X 50

SHF 32-250/75

LH

65 X 50

LH

80 X 50

SHF 32-250/110

LH

65 X 50

LH

80 X 50

SHF 40-125/11

OH1

80 X 65

OH1

100 X 65

SHF 40-125/15

OH1

80 X 65

OH1

100 X 65

SHF 40-125/22

OH1

80 X 65

OH1

100 X 65

SHF 40-160/30

OH1

80 X 65

OH1

100 X 65

SHF 40-160/40

OH1

80 X 65

OH1

100 X 65

SHF 40-200/55

OH1

80 X 65

OH1

100 X 65

SHF 40-200/75

OH1

80 X 65

OH1

100 X 65

SHF 40-250/110A

OH1

80 X 65

OH1

100 X 65

SHF 40-250/110

OH1

80 X 65

OH1

100 X 65

SHF 40-250/150

OH1

80 X 65

OH1

100 X 65

SHF 50-125/22

OH2

100 X 65

OH2

125 X 65

SHF 50-125/30

OH2

100 X 65

OH2

125 X 65

SHF 50-125/40

OH3

125 X 65

OH2

100 X 65

OH3

150 X 65

OH2

125 X 65

SHF 50-160/55

OH3

125 X 65

OH2

100 X 65

OH3

150 X 65

OH2

125 X 65

SHF 50-160/75

OH3

125 X 65

OH2

100 X 65

OH3

150 X 65

OH2

125 X 65

SHF 50-200/110A

OH3

125 X 65

OH2

100 X 65

OH3

150 X 65

OH2

125 X 65

SHF 50-200/110

OH3

125 X 65

OH2

100 X 65

OH3

150 X 65

OH2

125 X 65

SHF 50-250/150

OH2

100 X 65

OH2

125 X 65

SHF 50-250/185

OH3

125 X 65

OH2

100 X 65

OH3

150 X 65

OH2

125 X 65

SHF 50-250/220

OH3

125 X 65

OH2

100 X 65

OH3

150 X 65

OH2

125 X 65

SHF 65-160/40

OH3

125 X 80

OH3

150 X 80

SHF 65-160/55

OH3

125 X 80

OH3

150 X 80

SHF 65-160/75

OH3

125 X 80

OH3

150 X 80

SHF 65-160/110A

OH3

125 X 80

OH3

150 X 80

SHF 65-160/110

OH3

125 X 80

OH3

150 X 80

SHF 65-200/150

OH3

125 X 80

OH3

150 X 80

SHF 65-200/185

OH3

125 X 80

OH3

150 X 80

SHF 65-200/220

OH4

150 X 80

OH3

125 X 80

OH4

200 X 80

OH3

150 X 80

SHF 65-250/300

OH4

150 X 80

OH3

125 X 80

OH4

200 X 80

OH3

150 X 80

SHF 65-250/370

OH4

150 X 80

OH3

125 X 80

OH4

200 X 80

OH3

150 X 80

SHF 80-160/110

HH1

200 X 100

OH4

150 X 100

HH1

200 X 100

OH4

200 X 100

SHF 80-160/150

HH1

200 X 100

OH4

150 X 100

HH1

200 X 100

OH4

200 X 100

SHF 80-160/185

HH1

200 X 100

OH4

150 X 100

HH1

200 X 100

OH4

200 X 100

SHF 80-200/220

HH1

200 X 100

OH4

150 X 100

HH1

200 X 100

OH4

200 X 100

SHF 80-200/300

HH1

200 X 100

OH4

150 X 100

HH1

200 X 100

OH4

200 X 100

SHF 80-200/370

HH1

200 X 100

OH4

150 X 100

HH1

200 X 100

OH4

200 X 100

SHF 80-250/450

HH1

200 X 100

OH4

150 X 100

HH1

200 X 100

OH4

200 X 100

SHF 80-250/550

HH1

200 X 100

OH4

150 X 100

HH1

200 X 100

OH4

200 X 100

SHF 80-250/750

HH1

200 X 100

OH4

150 X 100

HH1

200 X 100

OH4

* For the risk classes refer to para 6, UNI EN12845.

200 X 100
kit-asp-shf-en_a_td

- the pumps must be chosen according to the performance levels indicated in Tab. 6 para 7.3.1, Tab. 7 para 7.3.2 and the classes of risk.
- some pump models can satisfy the conditions of one or more classes of risk.
- always check the correct selection of the pump depending on the performance level of the set.
** Insert the 50mm minimal thickness under the GEN10 fire-fighting booster sets only.

143

ACCES
SORIES
ACCESSORIES

SUCTION LIFT
RISK

ALARMS CONTROL ELECTRICAL P


ANEL
PANEL
Electric panel for remote status and alarm monitoring of one or two Lowara pumps installed in GEN fire-fighting
booster sets, according to EN12845.
In the electric service pump mode, the following conditions are visualised:
- Motor powered.
- Pump start-up request.
- Pump running
- Failure to start.
Additionally: minimum suction tank level, minimum priming tank level, on-off valve on suction and discharge side
not fully open. The valves are complete with status monitor.

The control unit is also fitted out to signal the following general alarms, if present:
- General alarm for incorrect electrical connection in the exchange contacts of: flow meter circuit valve, discharge
pump, jockey pump status.
- Fault in electrical connection in the exchange contact relative to panel 1 (electric pump/diesel engine pump)
- Fault in electrical connection in the exchange contact relative to panel 2 (electric pump/diesel engine pump)
- Jockey pump overload (*).
- Jockey pump running(*)
- Discharge pump overload (*).
- Battery voltage low.
- Communications failure with ModBus system.
All the above conditions are visualised with signal LEDs and on the display. The customer may decide to enable
the buzzer.
The panel comprises a plastic casing (IP55), battery, battery charger, alarms and pump status display, if connected
with 485 serial communication.
Fitted to transmit alarms for GSM or PC module.
The electric connection between the contacts on the electric alarms control panel and other electric panels is to be
seen to by the person installing the equipment.
(*) Check that the electric control panel combined with the electric pump is complete with clean contacts for
pump running and overload signals.

QUADRO TAMPONE ALLARMI


TIONS
SPECIFICATIONS
TECHNICAL SPECIFICA

275

DESCRIPTION

Input voltage (single-phase)

VALUE

(1F+N) 230V +/-10%, 50-60 Hz

V
L1/

V
+

L2/

L2/

V
L3

A
L3

N.P.

INCREASE

Absorbed
Dimensions

0,1A

Rated battery voltage

ENTER

A
L1/

DECREASE / MENU'

370 x 275 x 160 mm

Protection grade
Battery

SHIFT

IP55

370

ACCES
SORIES
ACCESSORIES

In the diesel engine service pump mode, the following conditions are visualised, as required by EN12845:
- Switch on diesel engine pump control panel in non-automatic position.
- Diesel engine ails to start after 6 attempts.
- Pump running
- Controller fault.
Additionally: minimum fuel or suction tank level, minimum priming tank level, on-off valve on suction and
discharge side not fully open. The valves are complete with status monitor.
All the above conditions, required by EN12845, are visualised with signal LEDs and buzzers. A buzzer alarm reset
button and LED tester button are included.

Hermetic lead
12 Vcc

LAMPS TEST
PROVA
LAMPADE

BUZZER
SWITCH OFF
TACITAZIONE
SIRENA

ELECTRIC PUMP / POMPA ELETTRICA

L2
L1

JOCKEY PUMP

L3

Type

DSRC

Plant Type:
Tipo impianto:

GA11E+1D

POWER ON
PRESENZA TENSIONE
-

2,3 Ah ( uncharged in 20 h)

Dimensions of battery

178 x 34 x 66 mm

Sound emission levels

75dB

Control panel weight

1,5kg

+ UNDER THRESHOLD
SOTTO SOGLIA
PUMP ON
POMPA IN MARCIA

INTERRUPTED LINES
LINEE INTERROTTE

Voltage 230 V - 50-60 Hz


Battery 12 V 2,3 Ah

Code N. 32.000.10.0
Buzzer 12Vcc 90mA 75dB(A)

L2

OVERLOAD
SOVRACCARICO
SPRINKLER PUMPS ROOM
SPRINKLER SALA POMPE
PUMP SET ON DEMAND
RICHIESTA DI AVVIAMENTO
SELECTOR NOT IN
AUT. FUNCTION
SELETTORE NON IN AUT.

!
OFF

!
OFF
1

DIESEL PUMP / MOTOPOMPA

POMPA COMPENSAZIONE

Rated battery capacity

L3

L1

Circ. N. 17.029.001.0
0,2 A

IP 55

PHASE SEQUENCE FAILURE


ERRATA SEQUENZA FASE

MINIMUM FUEL LEVEL


MIN. LIVELLO COMBUSTIBILE

START FAILURE
MANCATO AVVIAMENTO

SWITCHBOARD FAILURE
GUASTO QUADRO

!
OFF
1

!
OFF
2

MINIMUM LEVEL SUCTION TANK


MINIMO LIVELLO VASCA ASPIRAZIONE
MINIMUM LEVEL PRIMING TANK
MINIMO LIVELLO VASCA ADESCAMENTO
PARTIALLY OPENED SUCTION VALVE
VALVOLA IN ASPIRAZIONE NON
COMPLETAMENTE APERTA
PARTIALLY OPENED DISCHARGE VALVE
VALVOLA IN MANDATA NON
COMPLETAMENTE APERTA

12845_002_D_DD

12845-qal-en_b_td

144

SPRINKLER DRAINAGE
PUMPS ROOM FAULT PUMP

ACCORDING TO EN12845

FL
OW METER KIT
FLOW
The flow meter is supplied as part of the assembly kit. The EN 12845 standard requires the presence of the flow meter
for checking the hydraulic performance during the test stage and duration periodic inspections. The suction side kit
are equipped with:
- Direct reading flow meter.
- On/off ball valve for diameters up to 2" inclusive, butterfly valve with lever handle from DN65 to DN100
diameter, butterfly valve with handwheel and reduction manual gear for DN125 diameter and above. Device
for monitoring ON/OFF status included. Electrical connections by customer. (Valve lock kit available on request).
- Connection piping.
The meter is available in various sizes according to the flow of a service pump and suitable for being connected to the
offtake of the head manifold. For a correct match, identify the type as shown in the set size tables. The flow meter
must be installed, where possible, in a stretch of piping with a steady flow and sufficient back pressure at the
discharge outlet. The assembly and the discharge piping towards the tank and discharge outlet are to be seen to by
the person installing the equipment.

A
SHAPE B
C
TABELLASHAPE
DIMENSIONALE
KIT_FLUSSIMETRO
GRUPPISHAPE
EN12845

SHAPE D

DIMENSIONS (mm)

DIMENSIONS (mm)
TYPE

DN

DNAS

SHAPE

DN

DNAS

SHAPE

32X25P

32

25

90

605

100X40P

100

40

300

760

32X32P

32

32

90

625

100X50P

100

50

300

750

32X40P

32

40

90

645

100X65P

100

65

340

410

40X25P

40

25

100

605

100X80P

100

80

340

410

40X32P

40

32

100

630

100X125

100

125

340

945

40X40P

40

40

100

645

125X50P

125

50

300

760

40X50P

40

50

100

640

125X65P

125

65

340

425

50X25P

50

25

105

610

125X80P

125

80

340

425

50X32P

50

32

105

635

125X125

125

125

340

755

50X40P

50

40

105

655

125X150

125

150

340

1085

50X50P

50

50

105

645

150X65P

150

65

380

435

65X25P

65

25

300

700

150X80P

150

80

380

440

65X32P

65

32

300

725

150X125

150

125

380

770

65X40P

65

40

300

740

150X150

150

150

380

900

65X50P

65

50

300

730

150X200

150

200

380

1380

65X65P

65

65

340

390

200X80P

200

80

380

465

65X80P

65

80

340

595

200X125

200

125

380

795

80X40P

80

40

300

745

200X150

200

150

380

925

80X50P

80

50

300

735

200X200

200

200

380

1170

80X65P

80

65

340

400

250X125

250

125

440

825

80X80P

80

80

340

400

250X150

250

150

440

950

80X125

80

125

340

910

250X200

250

200

440

1195

12845_kit_flux-acc-en_a_td

145

ACCES
SORIES
ACCESSORIES

TYPE

TABLE OF COMBINA
TIONS FOR FL
OW METER KIT
COMBINATIONS
FLOW
AND FHF SERVICE PUMP SERIES

ELECTRIC

TYPE

COMBINATION

TYPE

COMBINATION

FHF..

FLOW METER KIT

FHF..

FLOW METER KIT

GEN..

PUMP

PUMP

00D

01D

ELECTRIC
10D

11D

GEN..

PUMP

PUMP

00D

01D

10D

11D

32-125/07

32-125/D119

40X25P 40X25P 50X25P 50X25P 65-200/150

65-200/D187

80X80P 80X80P 100X80P 100X80P

32-125/11

32-125/D136

40X32P 40X32P 50X32P 50X32P 65-200/185

65-200/D198

80X80P 80X80P 100X80P 100X80P

32-160/15

32-160/D150

40X32P 40X32P 50X32P 50X32P 65-200/220

65-200/D210

80X80P 80X80P 100X80P 100X80P

32-160/22

32-160/D164

40X32P 40X32P 50X32P 50X32P 65-250/220

65-250/D220

80X80P 80X80P 100X80P 100X80P

32-200/30

32-200/D188

40X32P 40X32P 50X32P 50X32P 65-250/300

65-250/D241

80X80P 80X80P 100X80P 100X80P

32-200/40

32-200/D204

40X32P 40X32P 50X32P 50X32P 65-250/370

65-250/D258

80X80P 80X80P 100X80P 100X80P

40-125/11

40-125/D112

65X40P 65X40P 65X40P 65X40P 80-160/150

80-160/D163

100X80P 100X80P 125X80P 125X80P

40-125/15

40-125/D122

65X40P 65X40P 65X40P 65X40P 80-160/185

80-160/D173

100X125 100X125 125X125 125X125

40-125/22

40-125/D143

65X50P 65X50P 65X50P 65X50P 80-200/220

80-200/D189

100X80P 100X80P 125X80P 125X80P

40-160/30

40-160/D159

65X40P 65X40P 65X40P 65X40P 80-200/300

80-200/D207

100X125 100X125 125X125 125X125

40-160/40

40-160/D171

65X50P 65X50P 65X50P 65X50P 80-250/370

80-250/D225

100X80P 100X80P 125X80P 125X80P

40-200/55

40-200/D190

65X40P 65X40P 65X40P 65X40P 80-250/450

80-250/D238

100X125 100X125 125X125 125X125

40-200/75

40-200/D209

100X125 100X125 125X125 125X125

80-250/D256

65X50P 65X50P 65X50P 65X50P 100-160/185

100-160/D150 125X125 125X125 150X125 150X125

40-250/110

40-250/D233

65X50P 65X50P 65X50P 65X50P 100-160/220

100-160/D165 125X125 125X125 150X125 150X125

40-250/150

40-250/D251

65X50P 65X50P 65X50P 65X50P 100-160/300

100-160/D185 125X150 125X150 200X150 200X150

50-125/22

50-125/D119

65X50P 65X50P 80X50P 80X50P 100-200/185

100-200/D168 125X125 125X125 150X125 150X125

50-125/30

50-125/D130

65X65P 65X65P 80X65P 80X65P 100-200/300

100-200/D192 125X125 125X125 150X125 150X125

50-125/40

50-125/D139

65X65P 65X65P 80X65P 80X65P 100-200/370

100-200/D203 125X125 125X125 150X125 150X125

50-160/55

50-160/D158

65X65P 65X65P 80X65P 80X65P 100-200/450

100-200/D213 125X125 125X125 200X125 200X125

50-160/75

50-160/D174

65X65P 65X65P 80X65P 80X65P 100-250/300

100-250/D200 125X125 125X125 150X125 150X125

50-200/110A 50-200/D197

65X65P 65X65P 80X65P 80X65P 100-250/450

100-250/D221 125X125 125X125 200X125 200X125

50-200/110

50-200/D209

65X65P 65X65P 80X65P 80X65P 100-250/550

100-250/D235 125X125 125X125 200X125 200X125

50-250/150

50-250/D224

65X65P 65X65P 80X65P 80X65P 100-250/750

100-250/D254 125X150 125X150 200X150 200X150

50-250/185

50-250/D237

65X65P 65X65P 80X65P 80X65P 100-250/900

100-250/D267 125X150 125X150 200X150 200X150

50-250/220

50-250/D250

65X65P 65X65P 80X65P 80X65P 125-200/300

125-200/D180 150X150 150X150 200X150 200X150

65-125/40

65-125/D121

80X65P 80X65P 100X65P 100X65P 125-200/450

125-200/D206 150X200 150X200 200X200 200X200

65-125/55

65-125/D129

80X65P 80X65P 100X65P 100X65P 125-200/550

125-200/D216 150X200 150X200 200X200 200X200

65-125/75

65-125/D140

80X65P 80X65P 100X65P 100X65P 125-270/750

125-270/D224 150X200 150X200 250X200 250X200

65-160/110A 65-160/D161

80X80P 80X80P 100X80P 100X80P 125-270/900

125-270/D237 150X200 150X200 250X200 250X200

65-160/110

65-160/D168

80X80P 80X80P 100X80P 100X80P 125-270/1100 125-270/D253 150X200 150X200 250X200 250X200

65-160/150

65-160/D178

80X80P 80X80P 100X80P 100X80P 125-270/1320 125-270/D266 150X200 150X200 250X200 250X200

ACCES
SORIES
ACCESSORIES

65X50P 65X50P 65X50P 65X50P 80-250/550

40-250/110A 40-250/D218

12845_kit_flux-fhf_00D-11D-en_b_th

146

TABLE OF COMBINA
TIONS FOR FL
OW METER KIT
COMBINATIONS
FLOW
AND SHF SERVICE PUMP SERIES

ELECTRIC

TYPE

COMBINATION

TYPE

COMBINATION

SHF..

FLOW METER KIT

SHF..

FLOW METER KIT

GEN..

PUMP

PUMP

00D

01D

ELECTRIC
10D

11D

GEN..

PUMP

PUMP

00D

01D

10D

11D

32-125/07

32-125/D121

40X32P 40X32P 50X32P 50X32P 50-200/110A 50-200/D197

65X65P 65X65P 80X65P 80X65P

32-125/11

32-125/D136

40X32P 40X32P 50X32P 50X32P 50-200/110

50-200/D209

65X65P 65X65P 80X65P 80X65P

32-160/15

32-160/D150

40X32P 40X32P 50X32P 50X32P 50-250/150

50-250/D224

65X65P 65X65P 80X65P 80X65P

32-160/22

32-160/D168

40X32P 40X32P 50X32P 50X32P 50-250/185

50-250/D237

65X65P 65X65P 80X65P 80X65P

32-200/30

32-200/D188

40X32P 40X32P 50X32P 50X32P 50-250/220

50-250/D250

65X65P 65X65P 80X65P 80X65P

32-200/40

32-200/D204

40X32P 40X32P 50X32P 50X32P 65-160/40

65-160/D119

80X65P 80X65P 100X65P 100X65P

32-250/55

32-250/D222

40X32P 40X32P 50X32P 50X32P 65-160/55

65-160/D129

80X65P 80X65P 100X65P 100X65P

32-250/75

32-250/D242

40X32P 40X32P 50X32P 50X32P 65-160/75

65-160/D137

80X65P 80X65P 100X65P 100X65P

32-250/110

32-250/D256

40X32P 40X32P 50X32P 50X32P 65-160/110A 65-160/D168

80X65P 80X65P 100X65P 100X65P

40-125/11

40-125/D112

65X40P 65X40P 65X40P 65X40P 65-160/110

65-160/D177

80X65P 80X65P 100X65P 100X65P

40-125/15

40-125/D126

65X40P 65X40P 65X40P 65X40P 65-200/150

65-200/D192

80X65P 80X65P 100X65P 100X65P

40-125/22

40-125/D143

65X40P 65X40P 65X40P 65X40P 65-200/185

65-200/D203

80X65P 80X65P 100X65P 100X65P

40-160/30

40-160/D159

65X40P 65X40P 65X40P 65X40P 65-200/220

65-200/D215

80X80P 80X80P 100X80P 100X80P

40-160/40

40-160/D171

65X50P 65X50P 65X50P 65X50P 65-250/300

65-250/D240

80X80P 80X80P 100X80P 100X80P

40-200/55

40-200/D190

65X50P 65X50P 65X50P 65X50P 65-250/370

65-250/D255

80X80P 80X80P 100X80P 100X80P

40-200/75

40-200/D209

65X50P 65X50P 65X50P 65X50P 80-160/110

80-160/D169

100X80P 100X80P 125X80P 125X80P

40-250/110A 40-250/D218

65X40P 65X40P 65X40P 65X40P 80-160/150

80-160/D177

100X80P 100X80P 125X80P 125X80P

40-250/110

65X40P 65X40P 65X40P 65X40P 80-160/185

80-160/D186

100X125 100X125 125X125 125X125

40-250/D233

40-250/150

40-250/D251

65X50P 65X50P 65X50P 65X50P 80-200/220

80-200/D198

100X125 100X125 125X125 125X125

50-125/22

50-125/D119

65X50P 65X50P 80X50P 80X50P 80-200/300

80-200/D215

100X125 100X125 125X125 125X125

50-125/30

50-125/D130

65X65P 65X65P 80X65P 80X65P 80-200/370

80-200/D226

100X125 100X125 125X125 125X125

50-125/40

50-125/D139

65X65P 65X65P 80X65P 80X65P 80-250/450

80-250/D237

100X125 100X125 125X125 125X125

50-160/55

50-160/D158

65X65P 65X65P 80X65P 80X65P 80-250/550

80-250/D252

100X125 100X125 125X125 125X125

50-160/75

50-160/D174

65X65P 65X65P 80X65P 80X65P 80-250/750

80-250/D270

100X125 100X125 125X125 125X125

ACCES
SORIES
ACCESSORIES

12845_kit_flux-shf_00D-11D-en_c_th

147

PRIMING T
ANK
TANK
The priming tank is used in suction lift installations and carries out the function of maintaining the pump body
and suction pipe full of water even if there are leaks through the bottom valve.
Each pump must have its own independent priming tank, placed at a higher level than the pump. The tank must
be connected to a water source for adding water and keeping it full. The diameter of the connecting pipe to the
pump depends on the use class. The return piping for re-circulation can be connected to the tank, which must
also provide for discharge if it is too full.
A level indicator automatically actions the service pump if the level of the tank drops and is not reintegrated.
The hydraulic connections must be seen to by the person installing the equipment.
The horizontal 500 l tank is made of zinc-plated steel.

ACCES
SORIES PRIMING T
ANK KIT
ACCESSORIES
TANK
The available accessories kit includes:
- Filling and discharge valves, reductions, non-return valve, closing plugs and automatic air discharger.
- Float switch tap complete with ring nut for fixing to the hole through the tank.
- Level indicator to connect to the electric panel and assembly instruction sheet.
Available on request tank support, height 75, 100, 150, 200 cm.

ACCES
SORIES
ACCESSORIES

Example of connection to the tank and accessories:

1
2
3
4
5
6
7

DESCRIPTION

Pump priming tank


Pipe return from pump delivery side
Floating valve
In flow on-off valve
In flow
Low level switch
Drain

8
9
10
11
12
13
14

DESCRIPTION

Priming supply non return valve


Priming supply on-off valve
Over flow
Pressure switch
Pump
To trunk main
Pipe connection to delivery side of the pump
En-acc-adesc-en_b_tc

148

ELECTRIC JOCKEY PUMP KIT

ACCES
SORIES
ACCESSORIES

The jockey pump or compensation pump has the job of keeping the system under pressure and compensating for
any small loses without the intervention of the service pumps. In fact, the jockey pump is commanded by an
automatic shut-off panel. Should an electric jockey pump of a different size from the standard be required or
should it be installed later on sets which are not predisposed, or should non-standard different size requirements
be required, it is possible to configure the booster set with just the service pumps and add the electric jockey
pump, also later on.
The kit includes:
- the hydraulic components for installing the electric pump (base, valves, pressure switch).
- the pre-chosen electric pump and the relative electric panel.
The hydraulic connection to the set can be easily carried out using one of the couplings on the delivery manifold
for the membrane tanks using an adaptor.
Kits are available for the vertical electric jockey pumps 1SV series and submersed series 2GS, 4GS, 6GS.
The diagram illustrates some connection examples:

1
2
3
4
5

DESCRIPTION

Electric pump
Control Box
Connection to trunk main
Pipe connection to delivery side of the jockey pump
To trunk main
acc-kit-fil-en_a_tc

149

PANEL BRACKET KIT


The electric command panels supplied separately, for example in
the sets with submersed pumps, are suitable for being mounted
on the wall. Universal bracket kit are available, upon request, for
supporting the panels; it must be fixed to the floor using blocks.

GU_ACC_M0001_A_SC

ACCES
SORIES
ACCESSORIES

HYDRA
ULIC CONNECTION FOR FIRE-FIGHTING EN 12845 SETS
HYDRAULIC

1
2
3
4

DESCRIPTION

Suction piping kit *


Delivery manifold
Drain
From priming tank *

5
6
7
8

* See the instruction sheets.

DESCRIPTION

Flow meter kit *


Drain
Open discharge
To trunk main
En-acc-gener-en_a_tc

150

ACCES
SORIES
ACCESSORIES

NEW RATE OF FLOW


INDICATOR < DN100

FLOATS

VALVES

HYDRO TUBE

ACCES
SORIES
ACCESSORIES

MONITORED VALVES

FLOW METER

RATE OF FLOW INDICATOR

ELASTIC JOINTS

151

PRESSURE SWITCHS

PRODUCT DESCRIPTION B
Y TECHNICAL SPECIFICA
TIONS
BY
SPECIFICATIONS
Description EN 12845 fire-fighting booster set
Series : GEN
Model: electric service pump
diesel service pump
jock
ey or compensation pump
jockey
The pump station will comprise the following components:
- N1 electric jockey pump;
- N1 electric service pump;- N1 backup diesel pump;
- One electrical power and control panel for the electric service pump;
- One electrical power and control panel for the diesel pump;
- One electrical power and control panel for the electric jockey pump;
- Components and materials required for perfect operation and assembly;
Lowara booster sets are CE-certified and comply with the following directives:

Machinery Directive 2006/42/EC.


Low V
oltage Directive 2006/95/EC.
Voltage
Electromagnetic Compatibility Directive 2004/108/EC.
The hydraulic pump complies with the following standard:

ISO 9906-A Rotodynamic pumps hydraulic performance acceptance tests.


The fire-fighting booster set complies with European standard EN 12845:
Fixed fire-fighting installations
Automatic sprinkler systems, design, installation and maintenance.

ACCES
SORIES
ACCESSORIES

V
ersion with automatic switch-off according to UNI 10779 Hydrant systems
Version
design, installation and operating.

152

PRODUCT DESCRIPTION B
Y TECHNICAL SPECIFICA
TIONS
BY
SPECIFICATIONS
Basic version with periodic auto-test, Series GEN..A.
Electronic auto-test circuit with weekly programmer in the electrical panel of the service pump. The pump is turned
on an kept working for a minute at the previously established time and date.
During this interval the check circuit checks that the pressure in the re-circulation circuit closes the pressure switch
contact of the pump which is running. In the case of irregularities, the relative auxiliary self-test alarm relay available
for remote signalling is activated and memorised.
The EN 12845 Standard does not provide for the presence of a self-test circuit but asks for periodic checks to be
carried out by the user, hence the periodic self-test function cannot substitute the above checks.
For the precalculated HHP and HHS risk class systems and in the integrally calculated systems, the pump must be able
to provide, at 140% of rated capacity, a pressure of not less than 70% of the rated pressure of the pump.
Each pump generally backs up the other even if much depends on the chosen type of water supply. If the service
pump fails, or a blackout occurs, system pressure will decrease and the backup diesel pump will start. The pumps are
started automatically by the pressure switches while they are manually stopped from the electrical panel (key switch).

Fire-fighting set components: electric pump

Electric service pump comprising:


End-suction horizontal centrifugal pump, model FHF
FHF....................., single impeller, with cast iron body and
AISI316L stainless steel shaft. End suction and radial discharge ports. Impeller in AISI316L stainless steel or cast
iron. Hydraulic sizes and nominal diameter DN of suction and discharge ports according to EN 733 (ex DIN
24255).
Flanging to EN 1092-2 (formerly UNI2236) and DIN2532. Maximum running pressure: 12 bar. Mechanical seal
according to EN12756 (formerly DIN 24960) in Ceramic/Carbon/NBR lubricated with recirculation duct between
discharge and seal housing.

B3 three-phase electric motor with short circuit squirrel cage, totally enclosed, fan-cooled. The performance levels of
the electric motors lie within what is usually referred to as efficiency class 1. Protected to IP55, insulation class F.

153

ACCES
SORIES
ACCESSORIES

The pump is directly coupled to the respective motor with an elastic spacer joint (back pull out version) and
alignment and anchor base.

PRODUCT DESCRIPTION B
Y TECHNICAL SPECIFICA
TIONS
BY
SPECIFICATIONS
Main characteristics of the electric service pump:
TABELLA MATERIALI POMPA SERVIZIO FHF PER CAPITOLATI TECNICI
Brand
Model:
Flow rate
Head:
Pump body:
Seal housing:
Impeller:
Shaft:
Elastomers:
Mechanical seal:
Motor power:
Input voltage:
Frequency:
Rated current input:
Speed of rotation:
Max. ambient temp:
Protection class:
Insulation class:

LOWARA
FHF
m3/h
m.c.a.
Cast iron, EN 1561-GJL-200 (JL1030)
Cast iron, EN 1561-GJL-200 (JL1030)
Cast iron, EN 1561-GJL-200 (JL1030)
Stainless steel EN10088-1-X2 CrNiMo17-12-2
NBR
Ceramic/Carbon/NBR
Kw
V
Hz
A
r.p.m.
C

400 / 3
50
2900
40
IP 55
F

tec_FHF-en_b_tm

Back
up diesel engine pump comprising:
Backup
Normalised horizontal centrifugal pump, FHF
FHF........................ according to EN 733 (ex DIN 24255) max. operating
pressure PN12. End suction and radial discharge ports. Impeller in AISI316L stainless steel or cast iron, mechanical
seal in Ceramic/Carbon/NBR lubricated with recirculation duct between the discharge and the seal housing according
to EN12756 (formerly DIN 24960).

ACCES
SORIES
ACCESSORIES

Main components of the diesel engine pump:


-

Electrical panel with battery charger.

Diesel engine start circuit with two independent batteries.

Double engine starting relay.

Engine shut-off device from electric control (Electric stop).

Fuel tank for diesel engine equipped with float

Diesel engine coupled to service pump.

Base made of structural steel with epoxy powder painting RAL 5010.

The diesel pump is supplied on its own base complete with vibration-proof feet, wall-mounted electrical panel fixed
to the bracket of the set complete with 3-metre long cable (5 metres available on request) wall- or floor-mounted fuel
tank depending on capacity, pair of batteries lying on base with three metres of electrical cable for positioning by the
final user near the diesel engine.

154

PRODUCT DESCRIPTION B
Y TECHNICAL SPECIFICA
TIONS
BY
SPECIFICATIONS
Main characteristics of the diesel engine service pump:
TABELLA MATERIALI MOTOPOMPA SERVIZIO FHF PER CAPITOLATI TECNICI
Brand:
Model:
Flow rate:
Head:
Pump body:
Seal housing:
Impeller:
Shaft:
Elastomers:
Mechanical seal:
Diesel engine motor power:
Motor speed:

LOWARA
DFHF
m3/h
m.c.a.
Cast iron, EN 1561-GJL-200 (JL1030)
Cast iron, EN 1561-GJL-200 (JL1030)
Cast iron, EN 1561-GJL-200 (JL1030)
Stainless stee EN10088-1-X2 CrNiMo17-12-2
NBR
Ceramic/Carbon/NBR

Max. ambient temp.:


Diesel fuel tank capacity:

3000
40

Kw
r.p.m.
C
l
tec_DFHFE-en_b_tm

Electric jock
ey pump comprising:
jockey
Multi-cell vertical centrifugal Jockey pump, 1SV
1SV.... with metal parts in contact with liquid in stainless steel, pump
body and shaft in AISI 304 stainless steel, impeller in AISI 304 stainless steel, mechanical seal in Carburundum/
carbon/EPDM.

ACCES
SORIES
ACCESSORIES

Three-phase electric motor, shape B14, performance values within what is referred to as efficiency class 2, short
circuit squirrel cage motor, closed aluminium casing and external ventilation, performance according to EN 60034-1,
directly coupled to the vertical pump. Protected to IP55, insulation class F.

155

PRODUCT DESCRIPTION B
Y TECHNICAL SPECIFICA
TIONS
BY
SPECIFICATIONS
Main technical characteristics of the jock
ey pump:
jockey
TABELLA MATERIALI POMPA SERVIZIO SV PER CAPITOLATI TECNICI
Brand:
Model:
Flow rate:
Head:
Pump body:
Impeller:
Diffuser:
Shaft:
Outer sleeve:
Mechanical seal:
Motor power:
Input voltage:
Frequency:
Rated current:
Speed:
Max. ambient temp.:
Protection class:
Insulation class:

LOWARA
1SV
m3/h
m.c.a.
Stainless steel (1.4301)
Stainless steel (1.4301)
Stainless steel (1.4301)
Stainless steel (1.4301)
Stainless steel (1.4301)
Silicon carbide/Carbon/EPDM
Kw
V
Hz
A
r.p.m.
C

400 / 3
50
2900
40
IP - 55
F

tec_SV-en_b_tm

Electric panels

Electric service pump panel


Painted metal casing (IP54) complete with:

ACCES
SORIES
ACCESSORIES

General door-locking switch.


Analogical ammeter.
MAN AUT 0 selector with extractable key only in automatic position.
Keyboard for indicating electric voltage presence, correct phase sequence (three phase power supply), start-up
request, pump functioning and no start-up, through LED lamps, lamp test button and starting and stopping
buttons, according to the provisions of EN12845 paragraph 10.8.6.

Inside:
-

12/24V transformer for auxiliary circuits and electronic board.


Fuse holder and fuses for power and auxiliary circuits.

156

PRODUCT DESCRIPTION B
Y TECHNICAL SPECIFICA
TIONS
BY
SPECIFICATIONS
-

Line contact maker (direct start-up), line and star/delta contact makers (star/delta start-up), line contact makers
and reactance switching (impedance start-up).
Star/delta exchanger timer or reactance switching.
Relay for signalling no phase.
Auxiliary relays.
Current transformer.
Terminal boards.
Clean contacts (max 24V, 1A) for activating acoustic/ visual alarms for no phase, pump on demand, pump
running and start failure.
Cable glands (excluding the versions to be fixed to the floor).
Wiring diagram.

Jock
ey pump electrical panel
Jockey
Painted metal casing (IP55) complete with:

General door-locking switch.


Visual indicators for line, running, thermal shutdown.
Manual automatic selector excluded.

Inside:
Transformer for auxiliary circuits at 24 V.
Fuse holder and fuses for power and auxiliary circuits.
Line contact maker.
Overload cut-out switch.
Pump shut-off timer (0 90 s).
Terminal boards.
Cable glands.
Wiring diagram.

Suitable for connecting to a float switch or a minimum pressure switch for preventing dry running. An optional level
control module (supplied upon request) allows the connection of probes with the possibility of regulating the sensitivity
according to the hardness of the water.
Control panel for diesel engine pump
Painted metal casing (IP54) complete with:

General door-locking switch.


Electronic unit for control and management of the diesel engine. Display of alarms and status, battery voltage,
speedometer, hour counter, alarm programming, date display, main signals and manual start button.

157

ACCES
SORIES
ACCESSORIES

PRODUCT DESCRIPTION B
Y TECHNICAL SPECIFICA
TIONS
BY
SPECIFICATIONS
-

MAN AUT 0 selector with extractable key only in automatic position.


Pair of emergency battery start buttons.

Inside:

Fuse holder and fuses for power and auxiliary circuits.


Pair of battery chargers 12Vdc/24Vdc.
Control unit for management of diesel engine and alarms.
Auxiliary relays.
Power circuits for engine heaters.
Terminal boards.
RS232 connector for communication port.
Cable glands.
Wiring diagram.

The panel is supplied standard with dry alarm signal contacts (max 1, 30Vdc/125vac/277V
ac):
30Vdc/125vac/277Vac):

Non-automatic operating mode.


Controller fault.
Motor running.
Failure to start.
General alarm.

Standard single-phase input voltage 1 x 230V.

ACCES
SORIES
ACCESSORIES

Series of clean contacts for checking the status of the electric service pump panel, as well as
the contacts already provided for signalling alarms (on request):

No phase.
Motor running..
Selector position Man-Aut-0.
Failure to start.
Start-up request.

Series of clean contacts for checking the status of the electric jock
ey pump (on request)
jockey
- Pump running.
- Thermal shutdown (overload).
- No water.
Electrical alarms panel
Plastic casing protected to IP55 with an electronic board at the front for the visual and acoustic signalling of the
status of one or two service pumps. The following alarms are signalled :

158

PRODUCT DESCRIPTION B
Y TECHNICAL SPECIFICA
TIONS
BY
SPECIFICATIONS
Electric pump
Power off.
Start-up request.
Pump running.
No start-up.
Diesel pump
Non-automatic.
Controller fault.
Pump running.
No start-up.
The electric panel is fitted with a buzzer with reset button, signal LED test button, battery charger and battery and is
fitted out to signal the following general alarms, if present:
- General alarm for incorrect electrical connection in the exchange contacts of:
status of flow measurement circuit valve, drain pump, jockey pump.
- Fault in electrical connection in the exchange contact relative to panel 1 (electric pump/diesel engine pump).
- Fault in electrical connection in the exchange contact relative to panel 2 (electric pump/diesel engine pump).
- Jockey pump overload.
- Jockey pump running.
- Discharge pump overload.
- Battery voltage low.
- Communications failure with ModBus system.
GSM modem system status transmission module and RS232/485 converter module available on request.

QUADRO TAMPONE ALLARMI


TIONS
SPECIFICATIONS
TECHNICAL SPECIFICA

275

DESCRIPTION

Input voltage (single-phase)

VALUE

(1F+N) 230V +/-10%, 50-60 Hz

V
L1/

V
+

L2/

L2/

V
L3

A
L3

N.P.

INCREASE

Absorbed

A
L1/

370 x 275 x 160 mm


IP55

Rated battery voltage

Hermetic lead
12 Vcc

Rated battery capacity

2,3 Ah ( uncharged in 20 h)

Dimensions of battery

178 x 34 x 66 mm

Sound emission levels

75dB

Control panel weight

1,5kg

SPRINKLER DRAINAGE
PUMPS ROOM FAULT PUMP

ACCORDING TO EN12845
LAMPS TEST
PROVA
LAMPADE

BUZZER
SWITCH OFF
TACITAZIONE
SIRENA

ELECTRIC PUMP / POMPA ELETTRICA

L2
L1

JOCKEY PUMP

L3

Type

DSRC

Plant Type:
Tipo impianto:

GA11E+1D

POWER ON
PRESENZA TENSIONE
-

+ UNDER THRESHOLD
SOTTO SOGLIA
PUMP ON
POMPA IN MARCIA

INTERRUPTED LINES
LINEE INTERROTTE

Voltage 230 V - 50-60 Hz


Battery 12 V 2,3 Ah

Code N. 32.000.10.0
Buzzer 12Vcc 90mA 75dB(A)

L2

OVERLOAD
SOVRACCARICO
SPRINKLER PUMPS ROOM
SPRINKLER SALA POMPE
PUMP SET ON DEMAND
RICHIESTA DI AVVIAMENTO
SELECTOR NOT IN
AUT. FUNCTION
SELETTORE NON IN AUT.

!
OFF

!
OFF
1

DIESEL PUMP / MOTOPOMPA

POMPA COMPENSAZIONE

L3

L1

Circ. N. 17.029.001.0
0,2 A

IP 55

PHASE SEQUENCE FAILURE


ERRATA SEQUENZA FASE

MINIMUM FUEL LEVEL


MIN. LIVELLO COMBUSTIBILE

START FAILURE
MANCATO AVVIAMENTO

SWITCHBOARD FAILURE
GUASTO QUADRO

!
OFF
1

!
OFF
2

MINIMUM LEVEL SUCTION TANK


MINIMO LIVELLO VASCA ASPIRAZIONE
MINIMUM LEVEL PRIMING TANK
MINIMO LIVELLO VASCA ADESCAMENTO
PARTIALLY OPENED SUCTION VALVE
VALVOLA IN ASPIRAZIONE NON
COMPLETAMENTE APERTA
PARTIALLY OPENED DISCHARGE VALVE
VALVOLA IN MANDATA NON
COMPLETAMENTE APERTA

12845_002_D_DD

12845-qal-en_b_td

Control instruments and hydraulic accessories

The main components of the sets are:

On/off valves on the delivery side of each pump, ball valves with lever handle for diameters up to 11/4" inclusive,
butterfly valve with lever handle from DN65 to DN100 diameter, butterfly valve with handwheel and reduction
manual gear for DN125 diameter and above.
- Re-circulation device for each service pump.
The re-circulation device allows a minimum capacity in order to prevent the pump overheating when working with
closed delivery. It includes the activation pressure switch for the alarms of the pumps running, the test valve for
checking the seal of the check valves, the couplings for any connecting pipes to the priming tank in the case of
suction lift installation. The connection of each re-circulation to the suction tank or the priming tank is to be seen
to by the person installing the equipment.

159

ACCES
SORIES
ACCESSORIES

Protection grade
Battery

ENTER

DECREASE / MENU'

370

Dimensions

SHIFT

0,1A

PRODUCT DESCRIPTION B
Y TECHNICAL SPECIFICA
TIONS
BY
SPECIFICATIONS
-

Pressure gauge on the delivery side of each service pump between check valve and on/off valve.

Check valve be inspected type, on the delivery side of each pump. Threaded connector up to and including a
diameter of 11/4". Flanged connector for larger diameters.

Painted iron delivery manifold (PN 16) and threaded stubs with relative caps for connecting any 24 litre
membrane tanks. Blind and welding zinc-plated flanges.

Two start-up pressure switches for every service pump.


For the electric service pumps, start-up takes place through the pressure switch, but it must be manually
stopped using the key-operated selector switch on the panel (excluding the version with automatic shut-off).
For the electric jockey pump, if present, both start-up and stopping are determined by the pressure switch.

Start-up pressure switch circuit for the service pump, including connecting pipes for the delivery manifold,
recirculation circuit. This circuit includes on/off valve, a non-return valve, a discharge or test valve and various
pipe fittings. The configuration of the circuit allows the pressure switch to intervene also when the relative on/off
valve is closed.

Various pipe fittings (copper, zinc-plated steel).

Base made of bent sheet or structural iron with epoxy powder painting RAL 5010.

Control panel frame made of structural iron with epoxy powder painting RAL 5010.

ACCES
SORIES
ACCESSORIES

The control panels for the electric pumps up to 55 kW power supply are fixed on bracket. For higher powers, the
control panels for electric pump service are floor mounted, instead the jockey electric pump panel is wall mounted
fixed.

Diesel engine with coupling to service pump.

Vibration-damping joints on discharge side.

Electric panel for control of diesel engine pump and battery charger.

Diesel engine start circuit with two independent batteries.

Double engine starting relay.

Engine shut-off device from electric control (electric stop).

Fuel tank for diesel engine.

160

PRODUCT DESCRIPTION B
Y TECHNICAL SPECIFICA
TIONS
BY
SPECIFICATIONS
-

Electric panel for each electric service pump.

The diesel engine pump is mounted on its own base complete with vibration-damping feet, and comes with a
wall-mounted electric panel fitted with 3-metre cables (5 metre length available on request), fuel tank with wall or
floor mounting depending on capacity, floor-mounted batteries with iron frame to position to the side of the
diesel engine. The installation of the diesel engine must provide for adequate ventilation and exhaust of
combustion fumes.
Flow meter
The flow meter is supplied as part of the assembly kit. The EN 12845 standard requires the presence of the flow
meter for checking the hydraulic performance during the test stage and duration periodic inspections. The kit
comprises:
- Direct reading flow meter.
- On/off ball valve for diameters up to 2 inclusive, butterfly valve with lever handle from DN65 to DN100 diameter,
butterfly valve with handwheel and reduction manual gear for DN125 diameter and above.
- Straight plastic connection piping.
IThe flow meter is available in various sizes according to the flow of a service pump and suitable for being connected
to the offtake of the head manifold. For a correct match, identify the type as shown in the set size tables.
The assembly and the discharge piping towards the tank and discharge outlet are to be seen to by the person
installing the equipment.
The following illustration shows the type and size of flow meter:

Dimensions (mm):

ACCES
SORIES
ACCESSORIES

DN =
DNAS =
L=
H=
Qmax (m3/h) =

161

PRODUCT DESCRIPTION B
Y TECHNICAL SPECIFICA
TIONS
BY
SPECIFICATIONS
Diaphragm tanks
The booster sets are ready for installation, directly on the manifold, of 24-litre diaphragm tanks, one for each pump.
The sets are also equipped with caps to close off the unused couplings. Larger tanks can also be connected to the
unused end of the discharge manifold.
The kit is made up of the following accessories:

Diaphragm tank;
On-off ball valve;
Instructions manual;
Packaging.

Suction kit
The EN 12845 fire-fighting booster sets are supplied without valves and stubs on the suction side of the service pump
and can be completed with suitable kits that depend on legal standards.
These requirements are expressed by EN 12845 (chapter 10.5 and chapter 10.6) and are connected with the
maximum speed value of the water in the pipes, their minimum section and type of installation - suction lift or
positive suction head. To provide for one suction kit for each duty pump.
The kit comprises:

Anti-vibration joint to attach to the pump inlet.


On/off butterfly valve (optional in case of positive suction head installation) with lever handle for diameters up to
DN100, butterfly valve with handwheel and reduction manual gear for DN125 and higher.
Eccentric cone.
Vacuum pressure gauge.
Weld-on flange.

ACCES
SORIES
ACCESSORIES

The following illustration shows the suction kit:

Dimensions (mm):

DNA =
DNS =

L=
H=

162

PRODUCT DESCRIPTION B
Y TECHNICAL SPECIFICA
TIONS
BY
SPECIFICATIONS
The set is supplied already assembled, calibrated and factory tested. The set is supplied
complete with an instruction manual, pump manuals and wiring diagrams for the panels.
F
or the sets including floor panels, the electric panels are sent together with the set in a
For
separate pack and supplied with 5-metre long connecting cables (longer lengths
available on request). The fitter is responsible for preparing the routes and installing the
cables.

ACCES
SORIES
ACCESSORIES

163

FURTHER PRODUCT SELECTION AND DOCUMENT


ATION
DOCUMENTA
Xylect

Xylect is pump solution selection software with an extensive online database of product information across the entire
Lowara, and Vogel range of pumps and related products, with multiple search options and helpful project management
facilities. The system holds up-to-date product information on thousands of products and accessories.
The possibility to search by applications and the detailed information output given makes it easy to make the optimal
selection without having detailed knowledge about the Lowara and Vogel products.

ACCES
SORIES
ACCESSORIES

The search can be made by:

Application

Product type

Duty point

Xylect gives a detailed output:

List with search results

Performance curves (flow, head, power,


efficiency, NPSH)

Motor data

Dimensional drawings

Options

Data sheet printouts

Document downloads incl dxf files

The search by application guides users not familiar with


the product range to the right choice.

164

FURTHER PRODUCT SELECTION AND DOCUMENT


ATION
DOCUMENTA
Xylect

The detailed output makes it easy to select the optimal pump from the given alternatives.

Set own standard units

Create and save projects

Share projects with other Xylect users

ACCES
SORIES
ACCESSORIES

The best way to work with Xylect is to create a


personal account. This makes it possible to:

Every user have a My Xylect space, where all projects


are saved.
For more information about Xylect please contact
our sales network or visit www.xylect.com.

Dimensional drawings appear on the screen and can be


downloaded in dxf format.

165

166

ACCES
SORIES
ACCESSORIES

Xylem
1) The tissue in plants that brings water upward from the roots;
2) a leading global water technology company.
Were 12,000 people unied in a common purpose: creating innovative solutions
to meet our worlds water needs. Developing new technologies that will improve
the way water is used, conserved, and re-used in the future is central to our work.
We move, treat, analyze, and return water to the environment, and we help people
use water efciently, in their homes, buildings, factories and farms. In more than 150
countries, we have strong, long-standing relationships with customers who know us
for our powerful combination of leading product brands and applications expertise,
backed by a legacy of innovation.
For more information on how Xylem can help you, go to xyleminc.com.

Headquarters
LOWARA S.r.l. Unipersonale
Via Lombardi 14
36075 Montecchio Maggiore - Vicenza - Italy
Tel.(+39) 0444 707111 - Fax(+39) 0444 492166
e-mail: [email protected]
web: www.lowara.com - www.completewatersystems.com
LOWARA reserves the right to make modication without prior notice.
LOWARA is a trademark of Xylem Inc. or one of its subsidiaries.

You might also like