Ee 1404 Power System Lab Manual
Ee 1404 Power System Lab Manual
Ee 1404 Power System Lab Manual
LIST OF EXPERIMENTS
1. COMPUTATION OF PARAMETERS AND MODELLINGOF TRANSMISSION LINES.
2.
FORMATION OF ADMITTANCE MATRICES.
3.
FORMATION OF IMPEDANCE MATRICES.
4.
SOLUTION OF POWER FLOW USING GAUSS-SEIDEL METHOD.
5.
SHORT CIRCUIT ANALYSIS.
6.
SOLUTION OF POWER FLOW USING NEWTON-RAPHSON METHOD.
7.
LOAD FREQUENCY DYNAMICS OF SINGLE AREA POWER SYSTEMS.
8.
LOAD FREQUENCY DYNAMICS OF TWO AREA POWER SYSTEMS.
9.
TRANSIENT AND SMALL SIGNAL STABILITY ANALYSIS SINGLE MACHINE INFINITE BUS SYSTEM
.
10.
ECONOMIC DISPATCH IN POWER SYSTEMS
PREPARED BY V.BALAJI, M.Tech, (Ph.D) Asst.Professor /EEE
Page 2
I CYCLE
1.
COMPUTATION OF PARAMETERS AND MODELLINGOF TRANSMISSION LINES.
2.
FORMATION OF ADMITTANCE MATRICES.
3.
FORMATION OF IMPEDANCE MATRICES.
4.
SOLUTION OF POWER FLOW USING GAUSS-SEIDEL METHOD.
5.
SHORT CIRCUIT ANALYSIS.
II CYCLE
6.
SOLUTION OF POWER FLOW USING NEWTON-RAPHSON METHOD.
7.
LOAD FREQUENCY DYNAMICS OF SINGLE AREA POWER SYSTEMS.
8.
LOAD FREQUENCY DYNAMICS OF TWO AREA POWER SYSTEMS.
9.
TRANSIENT AND SMALL SIGNAL STABILITY ANALYSIS SINGLE MACHINE INFINITE BUS SYSTEM
.
10.
ECONOMIC DISPATCH IN POWER SYSTEMS
PREPARED BY V.BALAJI, M.Tech, (Ph.D) Asst.Professor /EEE
Page 3
CONTENTS
S.NO
Date
Name of the Experiment
Page NO
Marks
Remarks
out of 10 /Signature
PREPARED BY V.BALAJI, M.Tech, (Ph.D) Asst.Professor /EEE
Page 4
S.NO
Date
Name of the Experiment
Page NO
Marks
Remarks
out of 10 /Signature
PREPARED BY V.BALAJI, M.Tech, (Ph.D) Asst.Professor /EEE
Page 5
GMD is the equivalent GMD per phase & is given by GMD = [DAB * DBC * DCA]1/3 wher
e, DAB, DBC&DCA are GMD between each phase group A-B, B-C, C-A which are given b
y DAB = [Da1b1 * Da1b2 * Da2b1 * Da2b2]1/4 DBC = [Db1c1 * Db1c2 * Db2c1 * Db2c2]
1/4 DCA = [Dc1a1 * Dc2a1 * Dc2a1 * Dc2a2]1/4 Capacitance A general formula for e
valuating capacitance per phase in micro farad per km of a transmission line is
given by C = 0.0556/ ln (GMD/GMR) F/km Where, GMD is the Geometric mean distance wh
ich is same as that defined for inductance under various cases.
PROCEDURE: 1. Enter the command window of the MATLAB. 2. Create a new M file by
selecting File - New M File 3. Type and save the program in the editor window. 4
. Execute the program by either pressing Tools Run. 5. View the results.
EXERCISES: 1 A three-phase transposed line composed of one ACSR, 1,43,000 cmil,
47/7 Bobolink conductor per phase with flat horizontal spacing of 11m between ph
ases a and b and between phases b and c. The conductors have a diameter of 3.625
cm and a GMR of 1.439 cm. The line is to be replaced by a three-conductor bundl
e of ACSR 477,000-cmil, 26/7 Hawk conductors having the same cross sectional are
a of aluminum as the single-conductor line. The conductors have a diameter of 2.
1793 cm and a GMR of 0.8839 cm. The new line will also have a flat horizontal co
nfiguration, but it is to be operated at a higher voltage and therefore the phas
e spacing is increased to 14m as measured from the center of the bundles. The sp
acing between the conductors in the bundle is 45 cm. (a) Determine the inductanc
e and capacitance per phase per kilometer of the above two lines. (b) Verify the
results using the MATLAB program.
PREPARED BY V.BALAJI, M.Tech, (Ph.D) Asst.Professor /EEE
Page 8
PROGRAM :
[GMD, GMRL, GMRC] = gmd; L = 0.2*log(GMD/GMRL) C = 0.0556/log(GMD/GMRC)
MANUAL CALCULATIONS :
PREPARED BY V.BALAJI, M.Tech, (Ph.D) Asst.Professor /EEE
Page 9
2. A three phase overhead line 200km long R = 0.16 ohm/km and Conductor diameter
of 2cm with spacing 4,5,6m transposed.Find A,B,C,D constants ,sending end volta
ge,current ,power factor and power when the line is delivering full load of 50MW
at 132kV ,0.8 pf lagging , transmission efficiency , receiving end voltage and
regulation. PROGRAM :
ab=input( value of ab ); bc=input( value of bc ); ca=input( value of ca ); pr=in
put( receving end power in mw ); vr=input( receving end voltage in kv ); pfr=inp
ut( receving end powerfactor ); l=input( length of the line in km ); r=input( re
sistance/ph/km ); f=input( frequency ); D=input( diameter in m ); rad=D/2; newra
d=(0.7788*rad); deq=(ab*bc*ca)^(1/3); L=2*10^(-7)*log(deq/newrad); C=(2*pi*8.854
*10^-12)/log(deq/rad); XL=2*pi*f*L*l*1000; rnew=r*l; Z=rnew+i*(XL); Y=i*(2*pi*f*
C*l*1000); A=1+((Y*Z)/2); D=A; B=Z; C=Y*(1+(Y*Z)/4); vrph=(vr*10^3)/1.732; irold
=(pr*10^6)/(1.732*vr*10^3*.8); k=sin(acos(pfr)); ir=irold*(pfr-(j*k)); vs=((A*vr
ph)+(B*ir)); is=((C*vrph)+(D*ir)); angle(vs); angle(is); f=angle(vs); u=angle(is
); PFS=cos(f-u); eff=((pr*10^6)/(3*abs(vs)*abs(is)*PFS))*100; reg=(((abs(vs)/abs
(A))-abs(vrph))/abs(vrph))*100; L C rnew A B C abs(vs) abs(is) angle(vs)*180/pi
angle(is)*180/pi PFS eff reg
Page 11
MANUAL CALCULATIONS:
PREPARED BY V.BALAJI, M.Tech, (Ph.D) Asst.Professor /EEE
Page 12
RESULT :
PREPARED BY V.BALAJI, M.Tech, (Ph.D) Asst.Professor /EEE
Page 13
RESULT:
PREPARED BY V.BALAJI, M.Tech, (Ph.D) Asst.Professor /EEE
Page 17
RESULT:
PREPARED BY V.BALAJI, M.Tech, (Ph.D) Asst.Professor /EEE
Page 21
EXERCISE : The figure shows the single line diagram of a simple 3 buses power sy
stem with generator at bus 1.The magnitude at bus 1 is adjusted to 1.05pu. The s
cheduled loads at buses 2 and 3 are marked on the diagram. Line impedance are ma
rked in pu. The base value is 100kVA. The line charging susceptances are neglect
ed. Determine the phasor values of the voltage at the load buses 2 and 3. Find t
he slack bus real and reactive power. Verify the result using MATLAB.
Program %Gauss Sedial clc; data=[1 1 2 10-j*20 2 1 3 10-j*30 3 2 3 16-j*32] elem
ents=max(data(:,1)); bus=max(max(data(:,2)),max(data(:,3))); y=zeros(bus,bus); f
or p=1:bus, for q=1:elements, if(data(q,2)==p|data(q,3)==p) y(p,p)=y(p,p)+data(q
,4); end end end
PREPARED BY V.BALAJI, M.Tech, (Ph.D) Asst.Professor /EEE
Page 23
Page 24
RESULT
PREPARED BY V.BALAJI, M.Tech, (Ph.D) Asst.Professor /EEE
Page 26
SOLUTION OF POWER FLOW USING NEWTON-RAPHSON METHOD Expt.No : Date : AIM : To det
ermine the power flow analysis using Newton Raphson method SOFTWARE REQUIRED : M
ATLAB THEORY : The Newton Raphson method of load flow analysis is an iterative m
ethod which approximates the set of non-linear simultaneous equations to a set o
f linear simultaneous equations using Taylors series expansion and the terms are
limited to first order approximation. The load flow equations for Newton Raphson
method are non-linear equations in terms of real and imaginary part of bus volt
ages. PP =
n q=1 n
ep(eq Gpq + fq Bpq) + fp (fq Gpq - eq Bpq)
QP =
q=1
f (eq Gpq + fq Bpq) - ep (fq Gpq - eq Bpq)
1. Consider the 3 bus system each of the 3 line bus a series impedance of 0.02 +
j0.08 p.u and a total shunt admittance of j0.02 pu. The specified quantities at
the buses are given below : Bus Real load Reactive demand, QD 1 0 0.6 Load Real
power Reactive Power Voltage Specified V1=1.04 Unspecified V3 = 1.04
demand, PD 1 2 3 2 0 1.5
generation,PG Generation, QG 0.5 0 1 QG3 = ?
2. Verify the result using MATLAB
PROGRAM :
%NEWTON RAPHSON METHOD clc; gbus = [1 2.0 1.0 0.0 0.0 2 0.0 0.0 0.5 1.0 3 1.5 0.
6 0.0 0.0]; ybus = [5.882-j*23.528 -2.941+j*11.764 -2.941+j*11.764 -2.941+j*11.7
64 5.882-j*23.528 -2.941+j*11.764 -2.941+j*11.764 -2.941+j*11.764 5.882-j*23.528
]; t= 0.001 v1=1.04+j*0; v2=1+j*0; v3=1.04+j*0; del3=angle(v3); del1=angle(v1);
del2=angle(v2); %abs(ybus(2,1)) %abs(v2) for i=1:10 p2=(abs(v2)*abs(v1)*abs(ybus
(2,1))*cos((angle(ybus(2,1)))+del1del2))+abs(v2)* abs(v2)*abs(ybus(2,2))*cos((an
gle(ybus(2,2))))+(abs(v2)*abs(v3)* abs(ybus(2,3))*cos((angle(ybus(2,3))+del3-del
2)); q2=-(abs(v2)*abs(v1)*abs(ybus(2,1))*sin((angle(ybus(2,1)))+del1-del2))abs(v
2)*abs(v2)*abs(ybus(2,2))*sin((angle(ybus(2,2))))-(abs(v2)*abs(v3)* abs(ybus(2,3
))*sin((angle(ybus(2,3)))+del3-del2)); p3=(abs(v3)*abs(v1)*abs(ybus(3,1))*cos((a
ngle(ybus(3,1)))+del1del3))+abs(v3)*abs(v3)*abs(ybus(3,3))*cos((angle(ybus(3,3))
))+(abs(v2)*abs(v3)* abs(ybus(3,2))*cos((angle(ybus(3,2)))+del2-del3)); delp20=g
bus(2,4)-gbus(2,2)-p2; delp30=gbus(3,4)-gbus(3,2)-p3; delq20=gbus(2,5)-gbus(2,3)
-q2; J(1,1)=(abs(v2)*abs(v1)*abs(ybus(2,1))*sin((angle(ybus(2,1)))+del1del2))+(a
bs(v2)*abs(v3)*abs(ybus(2,3))*sin((angle(ybus(2,3)))+del3del2)); J(1,2)=-(abs(v2
)*abs(v3)*abs(ybus(2,3))*sin((angle(ybus(2,3)))+del3del2)); J(1,3)=(abs(v1)*abs(
ybus(2,1))*cos((angle(ybus(2,1)))+del1PREPARED BY V.BALAJI, M.Tech, (Ph.D) Asst.Professor /EEE
Page 28
del2))+2*(abs(v2)*abs(ybus(2,2))*cos((angle(ybus(2,2))))+(abs(v3)*abs(ybus(2,3)
)* cos((angle(ybus(2,3)))+del3-del2)); J(2,1)=-(abs(v3)*abs(v2)*abs(ybus(3,2))*s
in((angle(ybus(3,2)))+del2del3)); J(2,2)=(abs(v3)*abs(v1)*abs(ybus(3,1))*sin((an
gle(ybus(3,1)))+del1del3))+(abs(v3)*abs(v2)*abs(ybus(3,2))*sin((angle(ybus(3,2))
)+del2del3)); J(2,3)=(abs(v3)*abs(ybus(3,2))*cos((angle(ybus(3,2)))+del2-del3));
J(3,1)=(abs(v2)*abs(v1)*abs(ybus(2,1))*cos((angle(ybus(2,1)))+del1del2))-(abs(v
2)*abs(v3)*abs(ybus(2,3))*cos((angle(ybus(2,3)))+del2del3)); J(3,2)=(abs(v2)*abs
(v3)*abs(ybus(2,3))*cos((angle(ybus(2,3)))+del2del3)); J(3,3)=-(abs(v2)*abs(ybus
(2,1))*sin((angle(ybus(2,1)))+del1del2))-2*(abs(v2)*abs(ybus(2,2))*sin((angle(yb
us(2,2))))(abs(v3)*abs(ybus(2,3))* sin((angle(ybus(2,3)))+del3-del2)); end J inv
(J); A=[del2;del3;abs(v2)]; delA0=[delp20;delp30;delq20]; delA1=inv(J)*delA0; de
lA1; b0=abs(v2); A1=[del2;del3;b0]+delA1; A1-delA0; if((A1-delA0)<=t) break; del
2=A1(1,1); del3=A1(2,1); abs(v2)=A1(3,1); end A1
MANUAL CALCULATIONS :
PREPARED BY V.BALAJI, M.Tech, (Ph.D) Asst.Professor /EEE
Page 29
RESULT:
PREPARED BY V.BALAJI, M.Tech, (Ph.D) Asst.Professor /EEE
Page 32
SHORT CIRCUIT ANALYSIS Expt.No : Date : AIM : To become familiar with modelling
and analysis of power systems under faulted condition and to compute the fault l
evel, post-fault voltages and currents for different types of faults, both symme
tric and unsymmetric. PROGRAM REQUIRED: MATLAB 5.3 THEORY : Symmetrical Fault :
II. Three phase fault : From the thevenins equivalent circuit Vth Fault current If
= Z th Where Vth = Thevenins Voltage Z th = Thevenins Impedance Unsymmetrical Fau
lt : Single line to ground fault : Fault current If = Ia = 3Ia1 Ia1 = Ea Z1+Z2+Z
0
Line to line fault: Fault current If = Ia1(a2 a ) Ea Ia1 = Z1+Z2 Double Line to
ground fault : Fault current If = 2 Ia0 +( Ia1+ Ia2) (a2 + a ) Ea Ia1 = Z1 + Z0Z
2 Page 33
PREPARED BY V.BALAJI, M.Tech, (Ph.D) Asst.Professor /EEE
The one line diagram of a simple power system is shown in figure. The neutral of
each generator is grounded through a current limiting reactor of 0.25/3 per uni
t on a 100MVA base. The system data expressed in per unit on a common 100 MVA ba
se is tabulated below. The generators are running on no load at their rated volt
age and rated frequency with their emfs in phase. Determine the fault current fo
r the following faults. (a) A balanced three phase fault at bus 3 through a faul
t impedance Zf = j0.1 per unit. (b) A single line to ground fault at bus3 throug
h a fault impedance Zf = j0.1 per unit. (c) A line to line fault at bus3 through
a fault impedance Zf = j0.1 per unit. (d) A double line to ground fault at bus3
through a fault impedance Zf = j0.1 per unit. Item G1 G2 T1 T2 L12 L13 L23 Base
MVA 100 100 100 100 100 100 100 Voltage Rating kV 20 20 20/220 20/220 220 220 2
20 X1 0.15 0.15 0.10 0.10 0.125 0.15 0.25 X2 0.15 0.15 0.10 0.10 0.125 0.15 0.25
X0 0.05 0.05 0.10 0.10 0.30 0.35 0.7125
Verify the result using MATLAB program. PROGRAM : zdata1 = [0 0 1 1 2 1 0 0.25 2
0 0.25 2 0 0.125 3 0 0.15 3 0 0.25];
zdata0 = [0 1 0 0.40 0 2 0 0.10 1 2 0 0.30 1 3 0 0.35 2 3 0 0.7125]; zdata2 = zd
ata1; Zbus1 = zbuild(zdata1) Zbus0 = zbuild(zdata0) Zbus2 = Zbus1; symfault(zdat
a1,Zbus1) lgfault(zdata0, Zbus0, zdata1, Zbus1, zdata2, Zbus2) llfault(zdata1, Z
bus1, zdata2, Zbus2) dlgfault(zdata0, Zbus0, zdata1, Zbus1, zdata2, Zbus2)
PREPARED BY V.BALAJI, M.Tech, (Ph.D) Asst.Professor /EEE
Page 35
MANUAL CALCULATIONS:
PREPARED BY V.BALAJI, M.Tech, (Ph.D) Asst.Professor /EEE
Page 36
RESULT
PREPARED BY V.BALAJI, M.Tech, (Ph.D) Asst.Professor /EEE
Page 39
LOAD FREQUENCY DYNAMICS OF SINGLE AREA POWER SYSTEMS Expt . No : Date AIM : To b
ecome familiar with modelling and analysis of the frequency and tie-line flow dy
namics of a power system without and with load frequency controllers (LFC) and t
o design better controllers for getting better responses. THEORY : Active power
control is one of the important control actions to be perform to be normal opera
tion of the system to match the system generation with the continuously changing
system load in order to maintain the constancy of system frequency to a fine to
lerance level. This is one of the foremost requirements in proving quality power
supply. A change in system load cases a change in the speed of all rotating mas
ses ( Turbine generator rotor systems) of the system leading to change in system
frequency. The speed change form synchronous speed initiates the governor contr
ol (primary control) action result in all the participating generator turbine un
its taking up the change in load, stabilizing system frequency. Restoration of f
requency to nominal value requires secondary control action which adjust the loa
d - reference set points of selected ( regulating) generator turbine units. The
primary objectives of automatic generation control (AGC) are to regulate system
frequency to the set nominal value and also to regulate the net interchange of e
ach areas to the scheduled value by adjusting the outputs of the regulating unit
s. This function is referred to as load frequency control(LFC). :
PROCEDURE : 1. Enter the command window of the MATLAB. 2. Create a new Model by
selecting File - New Model 3. Pick up the blocks from the simulink library brows
er and form a block diagram. 4. After forming the block diagram , save the block
diagram. 5. Double click the scope and view the result.
PREPARED BY V.BALAJI, M.Tech, (Ph.D) Asst.Professor /EEE
Page 40
EXERCISE: 1.An isolated power station has the following parameters Turbine time
constant T = 0.5sec Governor time constant g = 0.2sec Generator inertia constant H
= 5sec Governor speed regulation = R per unit The load varies by 0.8 percent fo
r a 1 percent change in frequency , i.e,D = 0.8 (a) Use the Routh Hurwitz array
to find the range of R for control system stability. (b) Use MATLAB to obtain th
e root locus plot. (c) The governor speed regulation is set to R = 0.05 per unit
.The turbine rated output is 250MW at nominal frequency of 60Hz. A sudden load c
hange of 50MW( PL = 0.2 per unit) occurs. (i) (ii) Find the steady state frequen
cy deviation in Hz. Use MATLAB to obtain the time domain performance specificati
ons and the frequency deviation step response.
PREPARED BY V.BALAJI, M.Tech, (Ph.D) Asst.Professor /EEE
Page 41
MANUAL CALCULATIONS:
PREPARED BY V.BALAJI, M.Tech, (Ph.D) Asst.Professor /EEE
Page 42
RESULT:
PREPARED BY V.BALAJI, M.Tech, (Ph.D) Asst.Professor /EEE
Page 44
LOAD FREQUENCY DYNAMICS OF TWO AREA POWER SYSTEMS Expt . No : Date AIM : To beco
me familiar with modelling and analysis of the frequency and tie-line flow dynam
ics of a two area power system without and with load frequency controllers (LFC)
and to design better controllers for getting better responses. THEORY: Active p
ower control is one of the important control actions to be perform to be normal
operation of the system to match the system generation with the continuously cha
nging system load in order to maintain the constancy of system frequency to a fi
ne tolerance level. This is one of the foremost requirements in proving quality
power supply. A change in system load cases a change in the speed of all rotatin
g masses ( Turbine generator rotor systems) of the system leading to change in s
ystem frequency. The speed change form synchronous speed initiates the governor
control (primary control) action result in all the participating generator turbi
ne units taking up the change in load, stabilizing system frequency. Restoration
of frequency to nominal value requires secondary control action which adjust th
e load - reference set points of selected ( regulating) generator turbine units.
The primary objectives of automatic generation control (AGC) are to regulate sy
stem frequency to the set nominal value and also to regulate the net interchange
of each areas to the scheduled value by adjusting the outputs of the regulating
units. This function is referred to as load frequency control(LFC). :
PROCEDURE: 1. Enter the command window of the MATLAB. 2. Create a new Model by s
electing File - New Model 3. Pick up the blocks from the simulink library browse
r and form a block diagram. 4. After forming the block diagram , save the block
diagram. 5. Double click the scope and view the result.
PREPARED BY V.BALAJI, M.Tech, (Ph.D) Asst.Professor /EEE
Page 45
EXERCISE : 1. A two area system connected by a tie line has the following parame
ters on a 1000MVA common base Area Speed Regulation Frequency sens.load coeff. In
ertia Constant Base Power Governor Time Constant Turbine Time Constant 1 R1=0.05
D1=0.6 H1=5 1000MVA g1 = 0.2sec T1 =0.5sec 2 R2=0.0625 D2=0.9 H2=4 1000MVA g1 = 0.
3sec T1 =0.6sec
The units are operating in parallel at the nominal frequency of 60Hz. The synchr
onizing power coefficient is computed from the initial operating condition and i
s given to be Ps = 2 p.u. A load change of 187.5 MW occurs in area1. (a) Derterm
ine the new steady state frequency and the change in the tie-line flow. (b) Cons
truct the SIMULINK block diagram and obtain the frequency deviation response for
the condition in part(a). SIMULINK BLOCK DIAGRAM :
PREPARED BY V.BALAJI, M.Tech, (Ph.D) Asst.Professor /EEE
Page 46
MANUAL CALCULATION:
PREPARED BY V.BALAJI, M.Tech, (Ph.D) Asst.Professor /EEE
Page 47
RESULT:
PREPARED BY V.BALAJI, M.Tech, (Ph.D) Asst.Professor /EEE
Page 50
TRANSIENT AND SMALL SIGNAL STABILITY ANALYSIS SINGLE MACHINE INFINITE BUS SYSTEM
Expt.No : Date :
AIM : To become familiar with various aspects of the transient and small signal
stability analysis of Single-Machine-Infinite Bus (SMIB) system
PROGRAM REQUIRED : MATLAB 5.3 THEORY : Stability : Stability problem is concerne
d with the behaviour of power system when it is subjected to disturbance and is
classified into small signal stability problem if the disturbances are small and
transient stability problem when the disturbances are large. Transient stabilit
y: When a power system is under steady state, the load plus transmission loss eq
uals to the generation in the system. The generating units run a synchronous spe
ed and system frequency, voltage, current and power flows are steady. When a lar
ge disturbance such as three phase fault, loss of load, loss of generation etc.,
occurs the power balance is upset and the generating units rotors experience ei
ther acceleration or deceleration. The system may come back to a steady state co
ndition maintaining synchronism or it may break into subsystems or one or more m
achines may pull out of synchronism. In the former case the system is said to be
stable and in the later case it is said to be unstable. Small signal stability:
When a power system is under steady state, normal operating condition, the syst
em may be subjected to small disturbances such as variation in load and generati
on, change in field voltage, change in mechanical toque etc., The nature of syst
em response to small disturbance depends on the operating conditions, the transm
ission system strength, types of controllers etc. Instability that may result fr
om small disturbance may be of two forms, (i) Steady increase in rotor angle due
to lack of synchronising torque. (ii) Rotor oscillations of increasing magnitud
e due to lack of sufficient damping torque. FORMULA : Reactive power Qe = sin(co
s-1(p.f)) S* Stator Current It = = Et* Voltage behind transient condition E1 = E
t + j Xd1It Et* Pe - jQe
PREPARED BY V.BALAJI, M.Tech, (Ph.D) Asst.Professor /EEE
Page 51
During Fault Condition: Pe = PEii = 0 Find out X from the equivalent circuit dur
ing fault condition Post fault Condition: Find out X from the equivalent circuit
during post fault condition E1 x EB Power Pe = X max = - o Pm Pe = sinmax Critical
Clearing Angle: Pm(max - o ) + P3maxcosmax - P2maxcoso Coscr = P3max - P2max sin
PREPARED BY V.BALAJI, M.Tech, (Ph.D) Asst.Professor /EEE
Page 52
MANUAL CALCULATION:
PREPARED BY V.BALAJI, M.Tech, (Ph.D) Asst.Professor /EEE
Page 54
RESULT:
PREPARED BY V.BALAJI, M.Tech, (Ph.D) Asst.Professor /EEE
Page 55
PGi,min PGi PGi, ,max The units production cost function is usually approximated
by quadratic function Fi (PGi) = ai PG2i + bi PGi + ci ; i = 1,2,.N where ai , bi
and ci are constants Necessary conditions for the existence of solution to ED p
roblem
(4)
(5)
The ED problem given by the equations (1) to (4). By omitting the inequality con
straints (4) tentatively, the reduce ED problem (1),(2) and (3) may be restated
as an unconstrained optimization problem by augmenting the objective function (1
) with the constraint multiplied by LaGrange multiplier, to obtained the LaGrang
e function, L as Min : L (PG1 ..PGN , ) = Fi(PGi) - [ PGi PD]
i=1 i=1 N N
(6)
The necessary conditions for the existence of solution to (6) are given by L / PGi
= 0 = dFi (PGi) / dPGi - ; i = 1, 2,..N L / = 0 = PGi PD
i=1 N
(7) (8)
The solution to ED problem can be obtained by solving simultaneously the necessa
ry conditions (7) and (8) which state that the economic generation schedules not
only satisfy the system power balance equation (8) but also demand that the inc
remental cost rates of all the units be equal be equal to which can be interpret
ed as incremental cost of received power.
When the inequality constraints(4) are included in the ED problem the necessary
condition (7) gets modified as dFi (PGi) / dPGi = PGi,min PGi PGi, ,max ____(9)
(10)
for
for PGi = PGi, ,max ` PGi = PGi, ,mi for Economic Schedule PGi = ( -bi)/ 2ai ; i=1
,2.N
PREPARED BY V.BALAJI, M.Tech, (Ph.D) Asst.Professor /EEE
Page 57
Page 58
2. The fuel cost functions for three thermal plants in $/h are given by C1 = 500
+ 5.3 P1 + 0.004 P12 ; C2 = 400 + 5.5 P2 + 0.006 P22 ; C3 = 200 +5.8 P3 + 0.009
P32 ; The total load , PD is 975MW. Generation limits: 200 P1 450 MW 150 P2 350
MW 100 P3 225 MW Find the optimal dispatch and the total cost in $/h by analyti
cal method. Verify the result using MATLAB program. PROGRAM : cost = [500 5.3 0.
004 400 5.5 0.006 200 5.8 0.009]; mwlimits = [200 450 150 350 100 225]; Pdt = 97
5; dispatch gencost P1 in MW P2 in MW P3 in MW
MANUAL CALCULATION:
PREPARED BY V.BALAJI, M.Tech, (Ph.D) Asst.Professor /EEE
Page 60
RESULT :
PREPARED BY V.BALAJI, M.Tech, (Ph.D) Asst.Professor /EEE
Page 63