1MRK505186-UEN D en Application Manual Line Differential Protection IED RED 670 1.1
1MRK505186-UEN D en Application Manual Line Differential Protection IED RED 670 1.1
1MRK505186-UEN D en Application Manual Line Differential Protection IED RED 670 1.1
670 series
Line differential protection RED670
Application manual
Document ID: 1MRK505186-UEN
Issued: June 2010
Revision: D
Product version: 1.1
Copyright 2010 ABB. All rights reserved
Copyright
This document and parts thereof must not be reproduced or copied without written
permission from ABB, and the contents thereof must not be imparted to a third
party, nor used for any unauthorized purpose.
The software or hardware described in this document is furnished under a license
and may be used or disclosed only in accordance with the terms of such license.
Trademarks
ABB and Relion are registered trademarks of ABB Group. All other brand or
product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
ABB AB
Substation Automation Products
SE-721 59 Vsters
Sweden
Telephone: +46 (0) 21 32 50 00
Facsimile: +46 (0) 21 14 69 18
http://www.abb.com/substationautomation
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept
or product description and are not to be deemed as a statement of guaranteed
properties. All persons responsible for applying the equipment addressed in this
manual must satisfy themselves that each intended application is suitable and
acceptable, including that any applicable safety or other operational requirements
are complied with. In particular, any risks in applications where a system failure and/
or product failure would create a risk for harm to property or persons (including but
not limited to personal injuries or death) shall be the sole responsibility of the
person or entity applying the equipment, and those so responsible are hereby
requested to ensure that all measures are taken to exclude or mitigate such risks.
This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested
to notify the manufacturer. Other than under explicit contractual commitments, in
no event shall ABB be responsible or liable for any loss or damage resulting from
the use of this manual or the application of the equipment.
Conformity
This product complies with the directive of the Council of the European
Communities on the approximation of the laws of the Member States relating to
electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning
electrical equipment for use within specified voltage limits (Low-voltage directive
2006/95/EC).
This conformity is proved by tests conducted by ABB AB in accordance with the
generic standard EN 50263 for the EMC directive, and with the standards EN
60255-5 and/or EN 50178 for the low voltage directive.
This product is designed and produced for industrial use.
Table of contents
Section 1 Introduction.....................................................................13
Introduction to the application manual..............................................13
About the complete set of manuals for an IED............................13
About the application manual......................................................14
Intended audience.......................................................................14
Related documents......................................................................15
Revision notes.............................................................................15
Section 2 Requirements.................................................................17
Current transformer requirements....................................................17
Current transformer classification................................................17
Conditions....................................................................................18
Fault current................................................................................19
Secondary wire resistance and additional load...........................19
General current transformer requirements..................................20
Rated equivalent secondary e.m.f. requirements........................20
Line differential protection......................................................20
Distance protection.................................................................22
Current transformer requirements for CTs according to
other standards............................................................................22
Current transformers according to IEC 60044-1,
class P, PR.............................................................................23
Current transformers according to IEC 60044-1, class
PX, IEC 60044-6, class TPS
(and old British Standard, class X).........................................23
Current transformers according to ANSI/IEEE.......................23
Voltage transformer requirements....................................................24
SNTP server requirements...............................................................25
Section 3 IED application...............................................................27
General IED application....................................................................27
Analog inputs....................................................................................28
Introduction..................................................................................28
Setting guidelines........................................................................29
Setting of the phase reference channel..................................29
Setting parameters......................................................................53
Local human-machine interface.......................................................58
Human machine interface ...........................................................58
Local HMI related functions.........................................................60
Introduction.............................................................................60
Table of contents
1
Application manual
General setting parameters....................................................60
Indication LEDs...........................................................................60
Introduction.............................................................................60
Setting parameters.................................................................61
Basic IED functions..........................................................................63
Self supervision with internal event list........................................63
Application..............................................................................63
Setting parameters.................................................................63
Time synchronization...................................................................64
Application..............................................................................64
Setting guidelines...................................................................64
Setting parameters.................................................................66
Parameter setting groups............................................................68
Application..............................................................................68
Setting guidelines...................................................................69
Setting parameters.................................................................69
Test mode functionality TEST.....................................................69
Application..............................................................................69
Setting guidelines...................................................................69
Setting parameters.................................................................70
Change lock CHNGLCK..............................................................70
Application..............................................................................70
Setting parameters.................................................................71
IED identifiers..............................................................................71
Application..............................................................................71
Setting parameters.................................................................71
Product information.....................................................................72
Application..............................................................................72
Setting parameters.................................................................72
Rated system frequency PRIMVAL.............................................73
Application..............................................................................73
Setting guidelines...................................................................73
Setting parameters.................................................................73
Signal matrix for binary inputs SMBI...........................................73
Application..............................................................................73
Setting guidelines...................................................................73
Setting parameters.................................................................73
Signal matrix for binary outputs SMBO ......................................74
Application..............................................................................74
Setting guidelines...................................................................74
Setting parameters.................................................................74
Signal matrix for mA inputs SMMI...............................................74
Application..............................................................................74
Table of contents
2
Application manual
Setting guidelines...................................................................74
Setting parameters.................................................................74
Signal matrix for analog inputs SMAI..........................................74
Application..............................................................................75
Frequency values...................................................................75
Setting guidelines...................................................................76
Setting parameters.................................................................81
Summation block 3 phase 3PHSUM...........................................82
Application..............................................................................82
Setting guidelines...................................................................82
Setting parameters.................................................................83
Authority status ATHSTAT..........................................................83
Application..............................................................................83
Setting parameters.................................................................83
Differential protection........................................................................84
1Ph High impedance differential protection HZPDIF ..................84
Application..............................................................................84
Connection examples.............................................................91
Setting guidelines...................................................................94
Setting parameters...............................................................101
Line differential protection.........................................................101
Application............................................................................102
Setting guidelines.................................................................110
Setting parameters...............................................................127
Impedance protection ....................................................................136
Distance measuring zones, quadrilateral characteristic
ZMQPDIS, ZMQAPDIS, ZDRDIR..............................................136
Application............................................................................137
Setting guidelines.................................................................152
Setting parameters...............................................................161
Distance measuring zone, quadrilateral characteristic for
series compensated lines ZMCPDIS, ZMCAPDIS,
ZDSRDIR...................................................................................163
Application............................................................................163
Setting guidelines.................................................................205
Setting parameters...............................................................217
Phase selection, quadrilateral characteristic with fixed
angle FDPSPDIS.......................................................................221
Application............................................................................221
Setting guidelines.................................................................221
Setting parameters...............................................................228
Full-scheme distance measuring, Mho characteristic
ZMHPDIS .................................................................................229
Application............................................................................229
Table of contents
3
Application manual
Setting guidelines.................................................................242
Setting parameters...............................................................249
Full-scheme distance protection, quadrilateral for earth
faults ZMMPDIS, ZMMAPDIS...................................................250
Application............................................................................250
Setting guidelines.................................................................264
Setting parameters...............................................................271
Additional distance protection directional function for earth
faults ZDARDIR.........................................................................272
Application............................................................................272
Setting guidelines.................................................................272
Setting parameters...............................................................274
Mho impedance supervision logic ZSMGAPC...........................275
Application............................................................................275
Setting guidelines.................................................................275
Setting parameters...............................................................276
Faulty phase identification with load encroachment
FMPSPDIS................................................................................277
Application............................................................................277
Setting guidelines.................................................................278
Setting parameters...............................................................280
Power swing detection ZMRPSB ..............................................281
Application............................................................................281
Setting guidelines.................................................................282
Setting parameters...............................................................290
Power swing logic ZMRPSL .....................................................291
Application............................................................................291
Setting guidelines.................................................................292
Setting parameters...............................................................298
Pole slip protection PSPPPAM .................................................298
Application............................................................................298
Setting guidelines.................................................................301
Setting parameters...............................................................311
Automatic switch onto fault logic, voltage and current based
ZCVPSOF .................................................................................312
Application............................................................................312
Setting guidelines.................................................................312
Setting parameters...............................................................314
Phase preference logic PPLPHIZ..............................................314
Application............................................................................314
Setting guidelines.................................................................318
Setting parameters...............................................................319
Current protection...........................................................................319
Instantaneous phase overcurrent protection PHPIOC .............319
Table of contents
4
Application manual
Application............................................................................320
Setting guidelines.................................................................320
Setting parameters...............................................................325
Four step phase overcurrent protection OC4PTOC .................325
Application............................................................................325
Setting guidelines.................................................................326
Setting parameters...............................................................336
Instantaneous residual overcurrent protection EFPIOC ...........341
Application............................................................................341
Setting guidelines.................................................................341
Setting parameters...............................................................344
Four step residual overcurrent protection EF4PTOC ...............344
Application............................................................................344
Setting guidelines.................................................................346
Setting parameters...............................................................356
Sensitive directional residual overcurrent and power
protection SDEPSDE ................................................................362
Application............................................................................362
Setting guidelines.................................................................363
Setting parameters...............................................................371
Thermal overload protection, one time constant LPTTR ..........373
Application............................................................................373
Setting guideline...................................................................374
Setting parameters...............................................................375
Breaker failure protection CCRBRF .........................................375
Application............................................................................376
Setting guidelines.................................................................376
Setting parameters...............................................................380
Stub protection STBPTOC .......................................................380
Application............................................................................381
Setting guidelines.................................................................381
Setting parameters...............................................................382
Pole discordance protection CCRPLD .....................................382
Application............................................................................383
Setting guidelines.................................................................383
Setting parameters...............................................................384
Directional underpower protection GUPPDUP..........................384
Application............................................................................385
Setting guidelines.................................................................387
Setting parameters...............................................................390
Directional overpower protection GOPPDOP ...........................391
Application............................................................................391
Setting guidelines.................................................................393
Table of contents
5
Application manual
Setting parameters...............................................................397
Broken conductor check BRCPTOC ........................................398
Application............................................................................398
Setting guidelines.................................................................398
Setting parameters...............................................................399
Voltage protection...........................................................................399
Two step undervoltage protection UV2PTUV ...........................399
Application............................................................................400
Setting guidelines.................................................................400
Setting parameters...............................................................404
Two step overvoltage protection OV2PTOV .............................406
Application............................................................................406
Setting guidelines.................................................................407
Setting parameters...............................................................410
Two step residual overvoltage protection ROV2PTOV ............412
Application............................................................................412
Setting guidelines.................................................................412
Setting parameters...............................................................417
Overexcitation protection OEXPVPH .......................................418
Application............................................................................419
Setting guidelines.................................................................421
Setting parameters...............................................................424
Voltage differential protection VDCPTOV .................................425
Application............................................................................425
Setting guidelines.................................................................427
Setting parameters...............................................................429
Loss of voltage check LOVPTUV .............................................429
Application............................................................................429
Setting guidelines.................................................................430
Setting parameters...............................................................430
Frequency protection......................................................................430
Underfrequency protection SAPTUF ........................................430
Application............................................................................431
Setting guidelines.................................................................431
Setting parameters...............................................................433
Overfrequency protection SAPTOF ..........................................433
Application............................................................................433
Setting guidelines.................................................................434
Setting parameters...............................................................435
Rate-of-change frequency protection SAPFRC ........................435
Application............................................................................435
Setting guidelines.................................................................436
Setting parameters...............................................................437
Table of contents
6
Application manual
Multipurpose protection..................................................................437
General current and voltage protection CVGAPC.....................437
Application............................................................................437
Setting parameters...............................................................443
Secondary system supervision.......................................................450
Current circuit supervision CCSRDIF .......................................450
Application............................................................................450
Setting guidelines.................................................................451
Setting parameters...............................................................451
Fuse failure supervision SDDRFUF..........................................451
Application............................................................................451
Setting guidelines.................................................................452
Setting parameters...............................................................455
Control............................................................................................456
Synchrocheck, energizing check, and synchronizing
SESRSYN.................................................................................456
Application............................................................................457
Application examples...........................................................461
Setting guidelines.................................................................468
Setting parameters...............................................................473
Autorecloser SMBRREC ..........................................................475
Application............................................................................475
Setting guidelines.................................................................486
Setting parameters...............................................................497
Apparatus control APC..............................................................498
Application............................................................................498
Interaction between modules...............................................505
Setting guidelines.................................................................507
Setting parameters...............................................................508
Interlocking ...............................................................................510
Configuration guidelines.......................................................512
Interlocking for line bay ABC_LINE .....................................512
Interlocking for bus-coupler bay ABC_BC ...........................517
Interlocking for transformer bay AB_TRAFO .......................523
Interlocking for bus-section breaker A1A2_BS.....................524
Interlocking for bus-section disconnector A1A2_DC ...........528
Interlocking for busbar earthing switch BB_ES ...................536
Interlocking for double CB bay DB ......................................542
Interlocking for 1 1/2 CB BH ................................................544
Horizontal communication via GOOSE for interlocking
GOOSEINTLKRCV..............................................................545
Logic rotating switch for function selection and LHMI
presentation SLGGIO................................................................545
Application............................................................................545
Table of contents
7
Application manual
Setting guidelines.................................................................546
Setting parameters...............................................................547
Selector mini switch VSGGIO....................................................547
Application............................................................................547
Setting guidelines.................................................................548
Setting parameters...............................................................548
Generic double point function block DPGGIO...........................548
Application............................................................................549
Setting guidelines.................................................................549
Single point generic control 8 signals SPC8GGIO....................549
Application............................................................................549
Setting guidelines.................................................................549
Setting parameters...............................................................550
AutomationBits, command function for DNP3.0 AUTOBITS.....550
Application............................................................................550
Setting guidelines.................................................................551
Setting parameters...............................................................551
Single command, 16 signals SINGLECMD...............................564
Application............................................................................565
Setting guidelines.................................................................566
Setting parameters...............................................................567
Scheme communication.................................................................567
Scheme communication logic for distance or overcurrent
protection ZCPSCH ..................................................................567
Application............................................................................567
Setting guidelines.................................................................572
Setting parameters...............................................................574
Phase segregated scheme communication logic for
distance protection ZC1PPSCH ...............................................574
Application............................................................................574
Setting guidelines.................................................................579
Setting parameters...............................................................580
Current reversal and weak-end infeed logic for distance
protection ZCRWPSCH ............................................................580
Application............................................................................580
Setting guidelines.................................................................582
Setting parameters...............................................................583
Local acceleration logic ZCLCPLAL..........................................583
Application............................................................................584
Setting guidelines.................................................................584
Setting parameters...............................................................585
Scheme communication logic for residual overcurrent
protection ECPSCH ..................................................................585
Application............................................................................585
Table of contents
8
Application manual
Setting guidelines.................................................................586
Setting parameters...............................................................587
Current reversal and weak-end infeed logic for residual
overcurrent protection ECRWPSCH .........................................587
Application............................................................................587
Setting guidelines.................................................................589
Setting parameters...............................................................590
Current reversal and weak-end infeed logic for phase
segregated communication ZC1WPSCH .................................591
Application............................................................................591
Setting guideline...................................................................595
Setting parameters...............................................................596
Logic...............................................................................................597
Tripping logic SMPPTRC ..........................................................597
Application............................................................................597
Setting guidelines.................................................................601
Setting parameters...............................................................601
Trip matrix logic TMAGGIO.......................................................602
Application............................................................................602
Setting guidelines.................................................................602
Setting parameters...............................................................602
Configurable logic blocks...........................................................603
Application............................................................................603
Setting parameters...............................................................604
Fixed signal function block FXDSIGN.......................................605
Application............................................................................605
Setting parameters...............................................................606
Boolean 16 to Integer conversion B16I.....................................606
Application............................................................................606
Setting parameters...............................................................606
Boolean 16 to Integer conversion with logic node
representation B16IGGIO..........................................................607
Application............................................................................607
Setting parameters...............................................................607
Integer to Boolean 16 conversion IB16.....................................607
Application............................................................................607
Setting parameters...............................................................607
Integer to Boolean 16 conversion with logic node
representation IB16GGIO..........................................................607
Application............................................................................608
Setting parameters...............................................................608
Monitoring.......................................................................................608
Measurement.............................................................................608
Application............................................................................609
Table of contents
9
Application manual
Zero clamping.......................................................................610
Setting guidelines.................................................................611
Setting parameters...............................................................621
Event counter CNTGGIO...........................................................634
Application............................................................................635
Setting parameters...............................................................635
Event function EVENT...............................................................635
Introduction...........................................................................635
Setting guidelines.................................................................635
Setting parameters...............................................................636
Logical signal status report BINSTATREP................................638
Application............................................................................638
Setting guidelines.................................................................639
Setting parameters...............................................................639
Fault locator LMBRFLO.............................................................639
Application............................................................................639
Setting guidelines.................................................................640
Setting parameters...............................................................641
Measured value expander block RANGE_XP...........................642
Application............................................................................642
Setting guidelines.................................................................643
Disturbance report DRPRDRE..................................................643
Application............................................................................643
Setting guidelines.................................................................644
Setting parameters...............................................................649
Event list....................................................................................658
Application............................................................................658
Setting guidelines.................................................................659
Indications.................................................................................659
Application............................................................................659
Setting guidelines.................................................................659
Event recorder ..........................................................................660
Application............................................................................660
Setting guidelines.................................................................660
Trip value recorder....................................................................661
Application............................................................................661
Setting guidelines.................................................................661
Disturbance recorder.................................................................661
Application............................................................................661
Setting guidelines.................................................................662
Metering..........................................................................................662
Pulse-counter logic PCGGIO.....................................................662
Application............................................................................663
Table of contents
10
Application manual
Setting guidelines.................................................................663
Setting parameters...............................................................664
Function for energy calculation and demand handling
ETPMMTR.................................................................................664
Application............................................................................664
Setting guidelines.................................................................665
Setting parameters...............................................................666
Section 4 Station communication.................................................669
Overview.........................................................................................669
IEC 61850-8-1 communication protocol.........................................669
Application IEC 61850-8-1.........................................................669
Setting guidelines......................................................................671
Setting parameters....................................................................671
IEC 61850 generic communication I/O functions SPGGIO,
SP16GGIO................................................................................671
Application............................................................................671
Setting guidelines.................................................................671
Setting parameters...............................................................672
IEC 61850 generic communication I/O functions MVGGIO.......672
Application............................................................................672
Setting guidelines.................................................................672
Setting parameters...............................................................672
LON communication protocol.........................................................673
Application.................................................................................673
Setting parameters....................................................................675
SPA communication protocol.........................................................675
Application.................................................................................675
Setting guidelines......................................................................677
Setting parameters....................................................................678
IEC 60870-5-103 communication protocol.....................................678
Application.................................................................................678
Setting parameters....................................................................683
Multiple command and transmit MULTICMDRCV,
MULTICMDSND.............................................................................686
Application.................................................................................686
Setting guidelines......................................................................687
Settings................................................................................687
Setting parameters....................................................................687
Section 5 Remote communication................................................689
Binary signal transfer......................................................................689
Application.................................................................................689
Communication hardware solutions.....................................689
Table of contents
11
Application manual
Setting guidelines......................................................................690
Setting parameters....................................................................692
Section 6 Configuration................................................................695
Introduction.....................................................................................695
Description of configuration RED670.............................................696
Introduction................................................................................696
Description of configuration A31..........................................696
Description of configuration A32..........................................699
Description of configuration B31..........................................702
Description of configuration B32..........................................705
Section 7 Glossary.......................................................................709
Table of contents
12
Application manual
Section 1 Introduction
About this chapter
This chapter introduces the user to the manual as such.
1.1 Introduction to the application manual
1.1.1 About the complete set of manuals for an IED
The users manual (UM) is a complete set of five different manuals:
IEC09000744-1-en.vsd
P
l
a
n
n
i
n
g
&
p
u
r
c
h
a
s
e
d
i
s
p
o
s
a
l
E
n
g
i
n
e
e
r
i
n
g
I
n
s
t
a
l
l
i
n
g
C
o
m
m
i
s
s
i
o
n
i
n
g
O
p
e
r
a
t
i
o
n
M
a
i
n
t
e
n
a
n
c
e
D
e
c
o
m
m
i
s
s
i
o
n
i
n
g
d
e
i
n
s
t
a
l
l
i
n
g
&
Application manual
Operators manual
Installation and
Engineeringmanual
Commissioning manual
manual
Technical reference
IEC09000744 V1 EN
The Application Manual (AM) contains application descriptions, setting
guidelines and setting parameters sorted per function. The application manual
should be used to find out when and for what purpose a typical protection function
could be used. The manual should also be used when calculating settings.
The Technical Reference Manual (TRM) contains application and functionality
descriptions and it lists function blocks, logic diagrams, input and output signals,
setting parameters and technical data sorted per function. The technical reference
1MRK505186-UEN D Section 1
Introduction
13
Application manual
manual should be used as a technical reference during the engineering phase,
installation and commissioning phase, and during normal service.
The Installation and Commissioning Manual (ICM) contains instructions on
how to install and commission the protection IED. The manual can also be used as
a reference during periodic testing. The manual covers procedures for mechanical
and electrical installation, energizing and checking of external circuitry, setting and
configuration as well as verifying settings and performing directional tests. The
chapters are organized in the chronological order (indicated by chapter/section
numbers) in which the protection IED should be installed and commissioned.
The Operators Manual (OM) contains instructions on how to operate the
protection IED during normal service once it has been commissioned. The
operators manual can be used to find out how to handle disturbances or how to
view calculated and measured network data in order to determine the cause of a fault.
The Engineering Manual (EM) contains instructions on how to engineer the IEDs
using the different tools in PCM600. The manual provides instructions on how to
set up a PCM600 project and insert IEDs to the project structure. The manual also
recommends a sequence for engineering of protection and control functions, LHMI
functions as well as communication engineering for IEC 61850 and DNP3.
1.1.2 About the application manual
The application manual contains the following chapters:
The chapter Requirements describes current and voltage transformer
requirements.
The chapter IED application describes the use of the included software
functions in the IED. The chapter discusses application possibilities and gives
guidelines for calculating settings for a particular application.
The chapter Station communication describes the communication
possibilities in a SA-system.
The chapter Remote communication describes the remote end data
communication possibilities through binary signal transferring.
The chapter Configuration describes the preconfiguration of the IED and
its complements.
The chapter Glossary is a list of terms, acronyms and abbreviations used in
ABB technical documentation.
1.1.3 Intended audience
General
The application manual is addressing the system engineer/technical responsible
that is responsible for specifying the application of the IED.
Section 1 1MRK505186-UEN D
Introduction
14
Application manual
Requirements
The system engineer/technical responsible must have a good knowledge about
protection systems, protection equipment, protection functions and the configured
functional logics in the protection.
1.1.4 Related documents
Documents related to RED670 Identity number
Operators manual 1MRK 505 184-UEN
Installation and commissioning manual 1MRK 505 185-UEN
Technical reference manual 1MRK 505 183-UEN
Application manual 1MRK 505 186-UEN
Buyers guide 1MRK 505 188-BEN
Sample specification SA2005-001281
Connection diagram, Single breaker arr. Three phase tripping arr. 1MRK 002 801-BA
Connection diagram, Single breaker arr. Single phase tripping arr. 1MRK 002 801-CA
Connection diagram, Multi breaker arr. Three phase tripping arr. 1MRK 002 801-DA
Connection diagram, Multi breaker arr. Single phase tripping arr. 1MRK 002 801-EA
Configuration diagram A, Single breaker with single or double busbars 1MRK 004 500-82
Configuration diagram B, Single breakers with single or double busbars 1MRK 004 500-83
Configuration diagram C, Multi breakers such as 1 1/2 or ring busbar arr. 1MRK 004 500-84
Configuration diagram D, Multi breakers such as 1 1/2 or ring busbar arr. 1MRK 004 500-85
Setting example 1, 230 kV Short cable line with 1 1/2CB arr. 1MRK 505 175-WEN
Connection and Installation components 1MRK 513 003-BEN
Test system, COMBITEST 1MRK 512 001-BEN
Accessories for IED 670 1MRK 514 012-BEN
Getting started guide IED 670 1MRK 500 080-UEN
SPA and LON signal list for IED 670, ver. 1.1 1MRK 500 083-WEN
IEC 61850 Data objects list for IED 670, ver. 1.1 1MRK 500 084-WEN
Generic IEC 61850 IED Connectivity package 1KHA001027-UEN
Protection and Control IED Manager PCM 600 Installation sheet 1MRS755552
Engineering guide IED 670 products 1MRK 511 179-UEN
More information can be found on www.abb.com/substationautomation.
1.1.5 Revision notes
Revision Description
C No functionality added. Changes made in content due to problem reports.
1MRK505186-UEN D Section 1
Introduction
15
Application manual
16
Section 2 Requirements
About this chapter
This chapter describes current and voltage transformer requirements.
2.1 Current transformer requirements
The performance of a protection function will depend on the quality of the
measured current signal. Saturation of the current transformer (CT) will cause
distortion of the current signal and can result in a failure to operate or cause
unwanted operations of some functions. Consequently CT saturation can have an
influence on both the dependability and the security of the protection. This
protection IED has been designed to permit heavy CT saturation with maintained
correct operation.
2.1.1 Current transformer classification
To guarantee correct operation, the current transformers (CTs) must be able to
correctly reproduce the current for a minimum time before the CT will begin to
saturate. To fulfill the requirement on a specified time to saturation the CTs must
fulfill the requirements of a minimum secondary e.m.f. that is specified below.
There are several different ways to specify CTs. Conventional magnetic core CTs
are usually specified and manufactured according to some international or national
standards, which specify different protection classes as well. There are many
different standards and a lot of classes but fundamentally there are three different
types of CTs:
High remanence type CT
Low remanence type CT
Non remanence type CT
The high remanence type has no limit for the remanent flux. This CT has a
magnetic core without any airgap and a remanent flux might remain almost infinite
time. In this type of transformers the remanence can be up to around 80% of the
saturation flux. Typical examples of high remanence type CT are class P, PX, TPS,
TPX according to IEC, class P, X according to BS (old British Standard) and non
gapped class C, K according to ANSI/IEEE.
The low remanence type has a specified limit for the remanent flux. This CT is
made with a small air gap to reduce the remanence to a level that does not exceed
10% of the saturation flux. The small air gap has only very limited influences on
1MRK505186-UEN D Section 2
Requirements
17
Application manual
the other properties of the CT. Class PR, TPY according to IEC are low remanence
type CTs.
The non remanence type CT has practically negligible level of remanent flux.
This type of CT has relatively big air gaps in order to reduce the remanence to
practically zero level. In the same time, these air gaps reduce the influence of the DC-
component from the primary fault current. The air gaps will also decrease the
measuring accuracy in the non-saturated region of operation. Class TPZ according
to IEC is a non remanence type CT.
Different standards and classes specify the saturation e.m.f. in different ways but it
is possible to approximately compare values from different classes. The rated
equivalent limiting secondary e.m.f. E
al
according to the IEC 60044 6 standard is
used to specify the CT requirements for the IED. The requirements are also
specified according to other standards.
2.1.2 Conditions
The requirements are a result of investigations performed in our network simulator.
The current transformer models are representative for current transformers of high
remanence and low remanence type. The results may not always be valid for non
remanence type CTs (TPZ).
The performances of the protection functions have been checked in the range from
symmetrical to fully asymmetrical fault currents. Primary time constants of at least
120 ms have been considered at the tests. The current requirements below are thus
applicable both for symmetrical and asymmetrical fault currents.
Depending on the protection function phase-to-earth, phase-to-phase and three-
phase faults have been tested for different relevant fault positions for example,
close in forward and reverse faults, zone 1 reach faults, internal and external faults.
The dependability and security of the protection was verified by checking for
example, time delays, unwanted operations, directionality, overreach and stability.
The remanence in the current transformer core can cause unwanted operations or
minor additional time delays for some protection functions. As unwanted
operations are not acceptable at all maximum remanence has been considered for
fault cases critical for the security, for example, faults in reverse direction and
external faults. Because of the almost negligible risk of additional time delays and
the non-existent risk of failure to operate the remanence have not been considered
for the dependability cases. The requirements below are therefore fully valid for all
normal applications.
It is difficult to give general recommendations for additional margins for
remanence to avoid the minor risk of an additional time delay. They depend on the
performance and economy requirements. When current transformers of low
remanence type (for example, TPY, PR) are used, normally no additional margin is
needed. For current transformers of high remanence type (for example, P, PX, TPS,
TPX) the small probability of fully asymmetrical faults, together with high
Section 2 1MRK505186-UEN D
Requirements
18
Application manual
remanence in the same direction as the flux generated by the fault, has to be kept in
mind at the decision of an additional margin. Fully asymmetrical fault current will
be achieved when the fault occurs at approximately zero voltage (0).
Investigations have shown that 95% of the faults in the network will occur when
the voltage is between 40 and 90. In addition fully asymmetrical fault current
will not exist in all phases at the same time.
2.1.3 Fault current
The current transformer requirements are based on the maximum fault current for
faults in different positions. Maximum fault current will occur for three-phase
faults or single phase-to-earth faults. The current for a single phase-to-earth fault
will exceed the current for a three-phase fault when the zero sequence impedance
in the total fault loop is less than the positive sequence impedance.
When calculating the current transformer requirements, maximum fault current for
the relevant fault position should be used and therefore both fault types have to be
considered.
2.1.4 Secondary wire resistance and additional load
The voltage at the current transformer secondary terminals directly affects the
current transformer saturation. This voltage is developed in a loop containing the
secondary wires and the burden of all relays in the circuit. For earth faults the loop
includes the phase and neutral wire, normally twice the resistance of the single
secondary wire. For three-phase faults the neutral current is zero and it is just
necessary to consider the resistance up to the point where the phase wires are
connected to the common neutral wire. The most common practice is to use four
wires secondary cables so it normally is sufficient to consider just a single
secondary wire for the three-phase case.
The conclusion is that the loop resistance, twice the resistance of the single
secondary wire, must be used in the calculation for phase-to-earth faults and the
phase resistance, the resistance of a single secondary wire, may normally be used
in the calculation for three-phase faults.
As the burden can be considerable different for three-phase faults and phase-to-
earth faults it is important to consider both cases. Even in a case where the phase-to-
earth fault current is smaller than the three-phase fault current the phase-to-earth
fault can be dimensioning for the CT depending on the higher burden.
In isolated or high impedance earthed systems the phase-to-earth fault is not the
dimensioning case and therefore the resistance of the single secondary wire always
can be used in the calculation, for this case.
1MRK505186-UEN D Section 2
Requirements
19
Application manual
2.1.5 General current transformer requirements
The current transformer ratio is mainly selected based on power system data for
example, maximum load. However, it should be verified that the current to the
protection is higher than the minimum operating value for all faults that are to be
detected with the selected CT ratio. The minimum operating current is different for
different functions and normally settable so each function should be checked.
The current error of the current transformer can limit the possibility to use a very
sensitive setting of a sensitive residual overcurrent protection. If a very sensitive
setting of this function will be used it is recommended that the current transformer
should have an accuracy class which have an current error at rated primary current
that is less than 1% (for example, 5P). If current transformers with less accuracy
are used it is advisable to check the actual unwanted residual current during the
commissioning.
2.1.6 Rated equivalent secondary e.m.f. requirements
With regard to saturation of the current transformer all current transformers of high
remanence and low remanence type that fulfill the requirements on the rated
equivalent secondary e.m.f. E
al
below can be used. The characteristic of the non
remanence type CT (TPZ) is not well defined as far as the phase angle error is
concerned. If no explicit recommendation is given for a specific function we
therefore recommend contacting ABB to confirm that the non remanence type can
be used.
The CT requirements for the different functions below are specified as a rated
equivalent limiting secondary e.m.f. E
al
according to the IEC 60044-6 standard.
Requirements for CTs specified in different ways are given at the end of this section.
2.1.6.1 Line differential protection
The current transformers must have a rated equivalent secondary e.m.f. E
al
that is
larger than the maximum of the required secondary e.m.f. E
alreq
below:
sn R
al alreq k max CT L
2
pn r
I S
E E I R R
I I
= + +
EQUATION1409 V1 EN (Equation 1)
sn R
al alreq t max CT L
2
pn r
I S
E E 2 I R R
I I
= + +
EQUATION1410 V1 EN (Equation 2)
Section 2 1MRK505186-UEN D
Requirements
20
Application manual
where:
I
kmax
Maximum primary fundamental frequency fault current for internal close-in faults
(A)
I
tmax
Maximum primary fundamental frequency fault current for through fault current
for external faults (A)
I
pn
The rated primary CT current (A)
I
sn
The rated secondary CT current (A)
I
r
The rated current of the protection IED (A)
R
CT
The secondary resistance of the CT (W)
R
L
The resistance of the secondary wire and additional load (W). The loop
resistance containing the phase and neutral wires must be used for faults in
solidly earthed systems. The resistance of a single secondary wire should be
used for faults in high impedance earthed systems.
S
R
The burden of an IED current input channel (VA). S
R
=0.020 VA/channel for I
r
=1
A and S
r
=0.150 VA/channel for I
r
=5 A
In substations with breaker-and-a-half or double-busbar double-breaker
arrangement, the through fault current may pass two main CTs for the line
differential protection without passing the protected line. In such cases and if both
main CTs have equal ratios and magnetization characteristics the CTs must satisfy
equation 1 and equation 3.
sn R
al alreq tfdb CT L
2
pn r
I S
E E I R R
I I
= + +
EQUATION1411 V1 EN (Equation 3)
where:
I
tfdb
Maximum primary fundamental frequency through fault current that passes two main CTs (one-
and-a-half or double-breaker) without passing the protected line (A)
If a power transformer is included in the protected zone of the line differential
protection the CTs must also fulfill equation 4.
sn R
al alreq nt CT L
2
pn r
I S
E E 30 I R R
I I
= + +
EQUATION1412 V1 EN (Equation 4)
where:
I
nt
The rated primary current of the power transformer (A)
1MRK505186-UEN D Section 2
Requirements
21
Application manual
2.1.6.2 Distance protection
The current transformers must have a rated equivalent secondary e.m.f. E
al
that is
larger than the maximum of the required secondary e.m.f. E
alreq
below:
k max sn R
al alreq CT L
2
pn r
I I S
E E a R R
I I
= + +
EQUATION1080 V1 EN (Equation 5)
kzone1 sn R
al alreq CT L
2
pn r
I I S
E E k R R
I I
= + +
EQUATION1081 V1 EN (Equation 6)
where:
I
kmax
Maximum primary fundamental frequency current for close-in forward and
reverse faults (A)
I
kzone1
Maximum primary fundamental frequency current for faults at the end of zone 1
reach (A)
I
pn
The rated primary CT current (A)
I
sn
The rated secondary CT current (A)
I
r
The rated current of the protection IED (A)
R
CT
The secondary resistance of the CT (W)
R
L
The resistance of the secondary wire and additional load (W). In solidly earthed
systems the loop resistance containing the phase and neutral wires should be
used for phase-to-earth faults and the resistance of the phase wire should be
used for three-phase faults.
In isolated or high impedance earthed systems the resistance of the single
secondary wire always can be used.
S
R
The burden of an IED current input channel (VA). S
R
=0.020 VA/channel for I
r
=1
A and S
r
=0.150 VA/channel for I
r
=5 A
a This factor is a function of the primary time constant for the dc component in the
fault current.
a= 2 for the primary time constant T
p
50 ms
a = 3 for the primary time constant T
p
> 50 ms
k A factor of the primary time constant for the dc component in the fault current for
a three-phase fault at the set reach of zone 1.
k = 4 for the primary time constant T
p
30 ms
k = 6 for the primary time constant T
p
> 30 ms
2.1.7 Current transformer requirements for CTs according to
other standards
All kinds of conventional magnetic core CTs are possible to use with the IEDs if
they fulfill the requirements corresponding to the above specified expressed as the
rated equivalent secondary e.m.f. E
al
according to the IEC 60044-6 standard. From
Section 2 1MRK505186-UEN D
Requirements
22
Application manual
different standards and available data for relaying applications it is possible to
approximately calculate a secondary e.m.f. of the CT comparable with E
al
. By
comparing this with the required secondary e.m.f. E
alreq
it is possible to judge if the
CT fulfills the requirements. The requirements according to some other standards
are specified below.
2.1.7.1 Current transformers according to IEC 60044-1, class P, PR
A CT according to IEC 60044-1 is specified by the secondary limiting e.m.f. E
2max
.
The value of the E
2max
is approximately equal to the corresponding E
al
according
to IEC 60044-6. Therefore, the CTs according to class P and PR must have a
secondary limiting e.m.f. E
2max
that fulfills the following:
2 max alreq
E max imum of E >
EQUATION1383 V1 EN (Equation 7)
2.1.7.2 Current transformers according to IEC 60044-1, class PX, IEC
60044-6, class TPS (and old British Standard, class X)
CTs according to these classes are specified approximately in the same way by a
rated knee-point e.m.f. E
knee
(E
k
for class PX, E
kneeBS
for class X and the limiting
secondary voltage U
al
for TPS). The value of the E
knee
is lower than the
corresponding E
al
according to IEC 60044-6. It is not possible to give a general
relation between the E
knee
and the E
al
but normally the E
knee
is approximately 80 %
of the E
al
. Therefore, the CTs according to class PX, X and TPS must have a rated
knee-point e.m.f. E
knee
that fulfills the following:
E
knee
E
k
E
kneeBS
U
al
> 0.8 (maximum of E
alreq
)
EQUATION2100 V1 EN (Equation 8)
2.1.7.3 Current transformers according to ANSI/IEEE
Current transformers according to ANSI/IEEE are partly specified in different
ways. A rated secondary terminal voltage U
ANSI
is specified for a CT of class C.
U
ANSI
is the secondary terminal voltage the CT will deliver to a standard burden at
20 times rated secondary current without exceeding 10 % ratio correction. There
are a number of standardized U
ANSI
values for example, U
ANSI
is 400 V for a C400
CT. A corresponding rated equivalent limiting secondary e.m.f. E
alANSI
can be
estimated as follows:
1MRK505186-UEN D Section 2
Requirements
23
Application manual
E
alANSI
20 I
sn
R
CT
U
ANSI
+ 20 I
sn
R
CT
20 I
sn
Z
bANSI
+ = =
EQUATION971 V1 EN (Equation 9)
where:
Z
bANSI
The impedance (that is, complex quantity) of the standard ANSI burden for the specific C
class (W)
U
ANSI
The secondary terminal voltage for the specific C class (V)
The CTs according to class C must have a calculated rated equivalent limiting
secondary e.m.f. E
alANSI
that fulfills the following:
alANSI alreq
E max imum of E >
EQUATION1384 V1 EN (Equation 10)
A CT according to ANSI/IEEE is also specified by the knee-point voltage
U
kneeANSI
that is graphically defined from an excitation curve. The knee-point
voltage U
kneeANSI
normally has a lower value than the knee-point e.m.f. according
to IEC and BS. U
kneeANSI
can approximately be estimated to 75 % of the
corresponding E
al
according to IEC 60044 6. Therefore, the CTs according to ANSI/
IEEE must have a knee-point voltage U
kneeANSI
that fulfills the following:
E
kneeANSI
> 0.75 (maximum of E
alreq
)
EQUATION2101 V1 EN (Equation 11)
2.2 Voltage transformer requirements
The performance of a protection function will depend on the quality of the
measured input signal. Transients caused by capacitive voltage transformers
(CVTs) can affect some protection functions.
Magnetic or capacitive voltage transformers can be used.
The capacitive voltage transformers (CVTs) should fulfill the requirements
according to the IEC 600445 standard regarding ferro-resonance and transients.
The ferro-resonance requirements of the CVTs are specified in chapter 7.4 of the
standard.
The transient responses for three different standard transient response classes, T1,
T2 and T3 are specified in chapter 15.5 of the standard. CVTs according to all
classes can be used.
The protection IED has effective filters for these transients, which gives secure and
correct operation with CVTs.
Section 2 1MRK505186-UEN D
Requirements
24
Application manual
2.3 SNTP server requirements
The SNTP server to be used is connected to the local network, that is not more than
4-5 switches or routers away from the IED. The SNTP server is dedicated for its
task, or at least equipped with a real-time operating system, that is not a PC with
SNTP server software. The SNTP server should be stable, that is, either
synchronized from a stable source like GPS, or local without synchronization.
Using a local SNTP server without synchronization as primary or secondary server
in a redundant configuration is not recommended.
1MRK505186-UEN D Section 2
Requirements
25
Application manual
26
Section 3 IED application
About this chapter
This chapter describes the use of the included software functions in the IED. The
chapter discusses application possibilities and gives guidelines for calculating
settings for a particular application.
3.1 General IED application
RED670 is used for the protection, control and monitoring of overhead lines and
cables in all types of networks. The IED can be used from distribution up to the
highest voltage levels. It is suitable for the protection of heavily loaded lines and
multi-terminal lines where the requirement for tripping is one-, two-, and/or three-
phase. The IED is also suitable for protection of cable feeders to generator block
transformers.
The phase segregated current differential protection provides an excellent
sensitivity for high resistive faults and gives a secure phase selection. The
availability of six stabilized current inputs per phase allows use on multi-breaker
arrangements in three terminal applications or up to five terminal applications with
single breaker arrangements. The communication between the IEDs involved in the
differential scheme is based on the IEEE C37.94 standard and can be duplicated for
important installations when required for redundancy reasons. Charging current
compensation allows high sensitivity also on long overhead lines and cables. A full
scheme distance protection is included to provide independent protection in parallel
with the differential scheme in case of a communication channel failure for the
differential scheme. The distance protection then provide protection for the entire
line including the remote end back up capability either in case of a communications
failure or via use of an independent communication channel to provide a fully
redundant scheme of protection (that is a second main protection scheme). Eight
channels for intertrip and other binary signals are available in the communication
between the IEDs.
The auto-reclose for single-, two- and/or three phase reclosing includes priority
circuits for multi-breaker arrangements. It co-operates with the synchronism check
function with high-speed or delayed reclosing.
High set instantaneous phase and earth overcurrent, four step directional or un-
directional delayed phase and earth overcurrent, thermal overload and two step
under- and overvoltage functions are examples of the available functions allowing
the user to fulfill any application requirement.
1MRK505186-UEN D Section 3
IED application
27
Application manual
Disturbance recording and fault locator are available to allow independent post-
fault analysis after primary disturbances. The Disturbance recorder will also show
remote station currents, as received to this IED, time compensated with measure
communication time.
Out of Step function is available to separate power system sections close to
electrical centre at occurring out of step.
The advanced logic capability, where the user logic is prepared with a graphical
tool, allows special applications such as automatic opening of disconnectors in multi-
breaker arrangements, closing of breaker rings, load transfer logics etc. The
graphical configuration tool ensures simple and fast testing and commissioning.
A loop testing function allows complete testing including remote end IED when
local IED is set in test mode.
Serial data communication is via optical connections to ensure immunity against
disturbances.
The wide application flexibility makes this product an excellent choice for both
new installations and the refurbishment of existing installations.
3.2 Analog inputs
3.2.1 Introduction
Analog input channels must be configured and set properly to get correct
measurement results and correct protection operations. For power measuring and
all directional and differential functions the directions of the input currents must be
defined properly. Measuring and protection algorithms in the IED use primary
system quantities. Set values are done in primary quantities as well and it is
important to set the data about the connected current and voltage transformers
properly.
A reference PhaseAngleRef can be defined to facilitate service values reading. This
analog channels phase angle will always be fixed to zero degree and all other angle
information will be shown in relation to this analog input. During testing and
commissioning of the IED the reference channel can be changed to facilitate testing
and service values reading.
The availability of VT inputs depends on the ordered transformer
input module (TRM) type.
Section 3 1MRK505186-UEN D
IED application
28
Application manual
3.2.2 Setting guidelines
The available setting parameters related to analog inputs are
depending on the actual hardware (TM) and the logic configuration
made in PCM600.
3.2.2.1 Setting of the phase reference channel
All phase angles are calculated in relation to a defined reference. An appropriate
analog input channel is selected and used as phase reference. The parameter
PhaseAngleRef defines the analog channel that is used as phase angle reference.
Example
The setting PhaseAngleRef=7 shall be used if a phase-to-earth voltage (usually the
L1 phase-to-earth voltage connected to VT channel number 7 of the analog card) is
selected to be the phase reference.
Setting of current channels
The direction of a current to the IED is depending on the connection of the CT.
Unless indicated otherwise, the main CTs are supposed to be star connected and
can be connected with the earthing point to the object or from the object. This
information must be set to the IED. The convention of the directionality is defined
as follows: A positive value of current, power, and so on means that the quantity
has the direction into the object and a negative value means direction out from the
object. For directional functions the direction into the object is defined as Forward
and the direction out from the object is defined as Reverse. See figure 1
Protected Object
Line, transformer, etc
Forward Reverse
Definition of direction
for directional functions
Measured quantity is
positive when flowing
towards the object
e.g. P, Q, I
Reverse Forward
Definition of direction
for directional functions
e.g. P, Q, I
Measured quantity is
positive when flowing
towards the object
Set parameter
CTStarPoint
Correct Setting is
"ToObject"
Set parameter
CTStarPoint
Correct Setting is
"FromObject"
en05000456.vsd
IEC05000456 V1 EN
Figure 1: Internal convention of the directionality in the IED
With correct setting of the primary CT direction, CTStarPoint set to FromObject or
ToObject, a positive quantities always flowing towards the object and a direction
1MRK505186-UEN D Section 3
IED application
29
Application manual
defined as Forward always is looking towards the object. The following examples
show the principle.
Example 1
Two IEDs used for protection of two objects.
Transformer
protection
Transformer
Line
Line
Setting of current input:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
Forward Reverse
Definition of direction
for directional functions
Line protection
Setting of current input:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
Setting of current input:
Set parameter
CTStarPoint with
Line as
reference object.
Correct setting is
"FromObject"
en05000753.vsd
I
s
I
s
I
p
I
p
I
p
IEC05000753 V1 EN
Figure 2: Example how to set CTStarPoint parameters in the IED
The figure 2 shows the most normal case where the objects have their own CTs.
The settings for CT direction shall be done according to the figure. To protect the
line the direction of the directional functions of the line protection shall be set to
Forward. This means that the protection is looking towards the line.
Example 2
Two IEDs used for protection of two objects and sharing a CT.
Section 3 1MRK505186-UEN D
IED application
30
Application manual
Transformer
protection
Transformer
Line
Setting of current input:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
Forward Reverse
Definition of direction
for directional functions
Line protection
Setting of current input:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
Setting of current input:
Set parameter
CTStarPoint with
Line as
reference object.
Correct setting is
"FromObject"
en05000460.vsd
IEC05000460 V1 EN
Figure 3: Example how to set CTStarPoint parameters in the IED
This example is similar to example 1 but the transformer is feeding just one line
and the line protection uses the same CT as the transformer protection does. The
CT direction is set with different reference objects for the two IEDs though it is the
same current from the same CT that is feeding two IEDs. With these settings the
directional functions of the line protection shall be set to Forward to look towards
the line.
Example 3
One IED used to protect two objects.
1MRK505186-UEN D Section 3
IED application
31
Application manual
Transformer and
Line protection
Transformer
Line
Setting of current input:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
Reverse Forward
Definition of direction
for directional
line functions
Setting of current input:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
en05000461.vsd
IEC05000461 V1 EN
Figure 4: Example how to set CTStarPoint parameters in the IED
In this example one IED includes both transformer and line protection and the line
protection uses the same CT as the transformer protection does. For both current
input channels the CT direction is set with the transformer as reference object. This
means that the direction Forward for the line protection is towards the transformer.
To look towards the line the direction of the directional functions of the line
protection must be set to Reverse. The direction Forward/Reverse is related to the
reference object that is the transformer in this case.
When a function is set to Reverse and shall protect an object in reverse direction it
shall be noted that some directional functions are not symmetrical regarding the
reach in forward and reverse direction. It is in first hand the reach of the directional
criteria that can differ. Normally it is not any limitation but it is advisable to have it
in mind and check if it is acceptable for the application in question.
If the IED has a sufficient number of analog current inputs an alternative solution is
shown in figure 5. The same currents are fed to two separate groups of inputs and
the line and transformer protection functions are configured to the different inputs.
The CT direction for the current channels to the line protection is set with the line
as reference object and the directional functions of the line protection shall be set to
Forward to protect the line.
Section 3 1MRK505186-UEN D
IED application
32
Application manual
Transformer and
Line protection
Transformer
Line
Setting of current input
for transformer functions:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
Forward Reverse
Definition of direction
for directional
line functions
Setting of current input
for transformer functions:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
Setting of current input
for line functions:
Set parameter
CTStarPoint with
Line as
reference object.
Correct setting is
"FromObject"
en05000462.vsd
IEC05000462 V1 EN
Figure 5: Example how to set CTStarPoint parameters in the IED
1MRK505186-UEN D Section 3
IED application
33
Application manual
Busbar
Protection
Busbar
1
2
2
1
en06000196.vsd
IEC06000196 V1 EN
Figure 6: Example how to set CTStarPoint parameters in the IED
For busbar protection it is possible to set the CTStarPoint parameters in two ways.
The first solution will be to use busbar as a reference object. In that case for all CT
inputs marked with 1 in figure 6, set CTStarPoint = ToObject, and for all CT inputs
marked with 2 in figure 6, set CTStarPoint = FromObject.
The second solution will be to use all connected bays as reference objects. In that
case for all CT inputs marked with 1 in figure 6, set CTStarPoint = FromObject,
and for all CT inputs marked with 2 in figure 6, set CTStarPoint = ToObject.
Regardless which one of the above two options is selected busbar differential
protection will behave correctly.
Section 3 1MRK505186-UEN D
IED application
34
Application manual
The main CT ratios must also be set. This is done by setting the two parameters
CTsec and CTprim for each current channel. For a 1000/1 A CT the following
setting shall be used:
CTprim = 1000 (value in A)
CTsec =1 (value in A).
Examples how to connect, configure and set CT inputs for most
commonly used CT connections
Figure 7 defines the marking of current transformers terminals commonly used
around the world:
I
Sec
I
P
r
i
S1 (X1)
P1
(H1)
P2
(H2)
S2 (X2)
P2
(H2)
P1
(H1)
x x
a) b) c)
en06000641.vsd
S2 (X2) S1 (X1)
IEC06000641 V1 EN
Figure 7: Commonly used markings of CT terminals
Where:
a) is symbol and terminal marking used in this document. Terminals marked with a dot indicates
the primary and secondary winding terminals with the same (that is, positive) polarity
b) and c) are equivalent symbols and terminal marking used by IEC (ANSI) standard for CTs. Note that
for this two cases the CT polarity marking is correct!
It shall be noted that depending on national standard and utility practices rated
secondary current of a CT has typically one of the following values:
1A
5A
However in some cases the following rated secondary currents are as well used:
2A
10A
The IED fully supports all of these rated secondary values.
1MRK505186-UEN D Section 3
IED application
35
Application manual
It is recommended to:
use 1A rated CT input into the IED in order to connect CTs
with 1A and 2A secondary rating
use 5A rated CT input into the IED in order to connect CTs
with 5A and 10A secondary rating
Example how to connect star connected three-phase CT set to the IED
Figure 8 gives an example how to connect the star connected three-phase CT set to
the IED. It as well gives overview of required actions by the user in order to make
this measurement available to the built-in protection and control functions within
the IED.
7
8
9
10
11
12
1
2
3
4
5
6
L1
I
L
1
I
L
2
I
L
3
L2 L3
Protected Object
CT 600/5
Star Connected
IL1
IL2
IL3
AI 01 (I)
AI 02 (I)
AI 03 (I)
AI 04 (I)
AI 05 (I)
AI 06 (I)
IR
IED
1
2
3
4
5
IEC06000642-2-en.vsd
6
SMAI2
BLOCK
^GRP2L1
TYPE
AI3P
AI1
AI2
AI3
AI4
AIN
^GRP2L2
^GRP2L3
^GRP2N
IEC06000642 V2 EN
Figure 8: Star connected three-phase CT set with star point towards the protected object
Where:
1) shows how to connect three individual phase currents from star connected three-phase CT
set to three CT inputs in the IED.
2) shows how to connect residual/neutral current from the three-phase CT set to the fourth
inputs in the IED. It shall be noted that if this connection is not made, the IED will still
calculate this current internally by vectorial summation of the three individual phase currents.
Table continues on next page
Section 3 1MRK505186-UEN D
IED application
36
Application manual
3) is TRM module where these current inputs are located. It shall be noted that for all these
current inputs the following setting values shall be entered.
CTprim=600A
CTsec=5A
CTStarPoint=ToObject
Inside the IED only the ratio of the first two parameters is used. The third parameter as set
in this example will have no influence on the measured currents (that is, currents are
already measured towards the protected object).
4) are three connections made in the Signal Matrix tool (SMT), which connects these three
current inputs to the first three input channels of the preprocessing function block 6).
Depending on the type of functions, which need this current information, more than one
preprocessing block might be connected in parallel to these three CT inputs.
5) is a connection made in the Signal Matrix tool (SMT), which connects the residual/neutral
current input to the fourth input channel of the preprocessing function block 6). Note that
this connection in SMT shall not be done if the residual/neutral current is not connected to
the IED. In that case the pre-processing block will calculate it by vectorial summation of
the three individual phase currents.
6) Preprocessing block has a task to digitally filter the connected analog inputs and calculate:
fundamental frequency phasors for all four input channels
harmonic content for all four input channels
positive, negative and zero sequence quantities by using the fundamental frequency
phasors for the first three input channels (channel one taken as reference for
sequence quantities)
These calculated values are then available for all built-in protection and control functions
within the IED, which are connected to this preprocessing function block in the
configuration tool. For this application most of the preprocessing settings can be left to the
default values.
If frequency tracking and compensation is required (this feature is typically required only
for IEDs installed in the generating stations) then the setting parameters DFTReference
shall be set accordingly.
Another alternative is to have the star point of the three-phase CT set as shown in
figure 9:
1MRK505186-UEN D Section 3
IED application
37
Application manual
7
8
9
10
11
12
1
2
3
4
5
6
L1
I
L
1
I
L
2
I
L
3
L2 L3
Protected Object
CT 800/1
Star Connected
IL1
IL2
IL3
AI 01 (I)
AI 02 (I)
AI 03 (I)
AI 04 (I)
AI 05 (I)
AI 06 (I)
IR
IED
1
3
4
2
5
IEC06000644-2-en.vsd
6
SMAI2
BLOCK AI3P
AI1
AI2
AI3
AI4
AIN
^GRP2L2
^GRP2L1
^GRP2L3
^GRP2N
TYPE
IEC06000644 V2 EN
Figure 9: Star connected three-phase CT set with star point from the
protected object
Please note that in this case everything is done in a similar way as in the above
described example, except that for all used current inputs on the TRM the
following setting parameters shall be entered:
CTprim=800A
CTsec=1A
CTStarPoint=FromObject
Inside the IED only the ratio of the first two parameters is used. The third
parameter as set in this example will invert the measured currents (that is, turn the
currents by 180) in order to ensure that the currents within the IED are measured
towards the protected object.
Example how to connect delta connected three-phase CT set to the
IED
Figure 10 gives an example how to connect the delta connected three-phase CT set
to the IED. It as well gives overview of required actions by the user in order to
make this measurement available to the built-in protection and control functions
within the IED.
Section 3 1MRK505186-UEN D
IED application
38
Application manual
7
8
9
10
11
12
1
2
3
4
5
6
L1
I
L
1
I
L
2
I
L
3
L2 L3
Protected Object
AI 01 (I)
AI 02 (I)
AI 03 (I)
AI 04 (I)
AI 05 (I)
AI 06 (I)
IED
IL1-IL2
IL2-IL3
IL3-IL1
1
2
3
.
# Not used
5
IEC06000645-2-en.vsd
SMAI2
BLOCK
^GRP2L1
TYPE
AI3P
AI1
AI2
AI3
AI4
AIN
^GRP2L2
^GRP2L3
^GRP2N
4
C
T
6
0
0
/
5
i
n
D
e
l
t
a
D
A
B
C
o
n
n
e
c
t
e
d
IEC06000645 V2 EN
Figure 10: Delta DAB connected three-phase CT set
Where:
1) shows how to connect three individual phase currents from delta connected three-phase
CT set to three CT inputs in the IED.
2) is TRM module where these current inputs are located. It shall be noted that for all these
current inputs the following setting values shall be entered.
CTprim=600/1.732=346A
CTsec=5A
CTStarPoint=ToObject
Inside the IED only the ratio of the first two parameters is used. The third parameter as set
in this example will have no influence on the measured currents (that is, currents are
already measured towards the protected object).
Table continues on next page
1MRK505186-UEN D Section 3
IED application
39
Application manual
3) are three connections made in Signal Matrix Tool (SMT) which connect these three current
inputs to first three input channels of the preprocessing function block 6). Depending on
type of functions which need this current information, more then one preprocessing block
might be connected in parallel to these three CT inputs.
4) shows that the fourth input channel of the preprocessing function block shall not be
connected in SMT.
5) Preprocessing block has a task to digitally filter the connected analog inputs and calculate:
fundamental frequency phasors for all four input channels
harmonic content for all four input channels
positive, negative and zero sequence quantities by using the fundamental frequency
phasors for the first three input channels (channel one taken as reference for
sequence quantities)
These calculated values are then available for all built-in protection and control functions
within the IED, which are connected to this preprocessing function block in the
configuration tool. For this application most of the preprocessing settings can be left to the
default values.
If frequency tracking and compensation is required (this feature is typically required only
for IEDs installed in the generating stations) then the setting parameters DFTReference
shall be set accordingly.
Another alternative is to have the delta connected CT set as shown in figure 11:
7
8
9
10
11
12
1
2
3
4
5
6
L1
I
L
1
I
L
2
I
L
3
L2 L3
Protected Object
AI 01 (I)
AI 02 (I)
AI 03 (I)
AI 04 (I)
AI 05 (I)
AI 06 (I)
IED
IL3-IL2
IL2-IL1
IL1-IL3
2
3
#Not used
5
IEC06000646-2-en.vsd
4
SMAI2
BLOCK
^GRP2L1
TYPE
AI3P
AI1
AI2
AI3
AI4
AIN
^GRP2L2
^GRP2L3
^GRP2N C
T
8
0
0
/
1
i
n
d
e
l
t
a
D
C
A
C
o
n
n
e
c
t
e
d
IEC06000646 V2 EN
Figure 11: Delta DAC connected three-phase CT set
Section 3 1MRK505186-UEN D
IED application
40
Application manual
Please note that in this case everything is done in a similar way as in the above
described example, except that for all used current inputs on the TRM the
following setting parameters shall be entered:
CTprim=800/1.732=462A
CTsec=1A
CTStarPoint=ToObject
Inside the IED only the ratio of the first two parameters is used. The third
parameter as set in this example will have no influence on the measured currents
(that is, currents are already measured towards the protected object).
Example how to connect single-phase CT to the IED
Figure 12 gives an example how to connect the single-phase CT to the IED. It as
well gives overview of required actions by the user in order to make this
measurement available to the built-in protection and control functions within the IED.
Protected Object
7
8
9
10
11
12
1
2
3
4
5
6
L1 L2 L3
AI 01 (I)
AI 02 (I)
AI 03 (I)
AI 04 (I)
AI 05 (I)
AI 06 (I)
IED
I
N
P
INP
INP
2
1
3
# Not used
# Not used
# Not used
IEC06000647-2-en.vsd
5
SMAI2
BLOCK
^GRP2L1
TYPE
AI3P
AI1
AI2
AI3
AI4
AIN
^GRP2L2
^GRP2L3
^GRP2N
4
C
T
1
0
0
0
/
1
a)
b)
IEC06000647 V2 EN
Figure 12: Connections for single-phase CT input
1MRK505186-UEN D Section 3
IED application
41
Application manual
Where:
1) shows how to connect single-phase CT input in the IED.
2) is TRM module where these current inputs are located. It shall be noted that for all these
current inputs the following setting values shall be entered.
For connection a) shown in figure 12:
CTprim=1000A
CTsec=1A
CTStarPoint=ToObject
Inside the IED only the ratio of the first two parameters is used. The third parameter as set
in this example will have no influence on the measured currents (that is, currents are
already measured towards the protected object).
For connection b) shown in figure 12:
CTprim=1000A
CTsec=1A
CTStarPoint=FromObject
Inside the IED only the ratio of the first two parameters is used. The third parameter as set
in this example will invert the measured currents (that is, turn the currents by 180) in
order to ensure that the currents within the IED are measured towards the protected object.
3) shows that in this example the first three input channel of the preprocessing block is not
connected in Signal Matrix Tool (SMT).
4) shows the connection made in SMT tool which connect this CT input to the fourth input
channel of the preprocessing function block 5).
5) Preprocessing block has a task to digitally filter the connected analog inputs and calculate:
fundamental frequency phasors for all four input channels
harmonic content for all four input channels
positive, negative and zero sequence quantities by using the fundamental frequency
phasors for the first three input channels (channel one taken as reference for
sequence quantities)
These calculated values are then available for all built-in protection and control functions
within the IED, which are connected to this preprocessing function block in the
configuration tool. For this application most of the preprocessing settings can be left to the
default values.
If frequency tracking and compensation is required (this feature is typically required only
for IEDs installed in the generating stations) then the setting parameters DFTReference
shall be set accordingly.
Setting of voltage channels
As the IED uses primary system quantities the main VT ratios must be known. This
is done by setting the two parameters VTsec and VTprim for each voltage channel.
The phase-to-phase value can be used even if each channel is connected to a phase-
to-earth voltage from the VT.
Example
Consider a VT with the following data:
Section 3 1MRK505186-UEN D
IED application
42
Application manual
132 110
3 3
kV V
EQUATION2016 V1 EN (Equation 12)
The following setting should be used: VTprim=132 (value in kV) VTsec=110
(value in V)
Examples how to connect, configure and set VT inputs for most
commonly used VT connections
Figure 13 defines the marking of voltage transformers terminals commonly used
around the world.
A
(H1)
B
(H2)
b
(X2)
a
(X1)
A
(H1)
N
(H2)
n
(X2)
a
(X1)
b) c)
A
(H1)
N
(H2)
dn
(X2)
da
(X1)
d)
U
Pri
+ +
U
Sec
a)
en06000591.vsd
IEC06000591 V1 EN
Figure 13: Commonly used markings of VT terminals
Where:
a) is symbol and terminal marking used in this document. Terminals marked with a dot
indicates the primary and secondary winding terminals with the same (that is, positive)
polarity
b) is equivalent symbol and terminal marking used by IEC (ANSI) standard for phase-to-earth
connected VT
c) is equivalent symbol and terminal marking used by IEC (ANSI) standard for open delta
connected VT
d) is equivalent symbol and terminal marking used by IEC (ANSI) standard for phase-to-
phase connected VT
It shall be noted that depending on national standard and utility practices rated
secondary voltage of a VT has typically one of the following values:
100 V
110 V
115 V
120 V
The IED fully supports all of these values and most of them will be shown in the
following examples.
1MRK505186-UEN D Section 3
IED application
43
Application manual
Examples how to connect three phase-to-earth connected VTs to the
IED
Figure 14 gives an example how to connect the three phase-to-earth connected VTs
to the IED. It as well gives overview of required actions by the user in order to
make this measurement available to the built-in protection and control functions
within the IED.
19
20
21
22
23
24
13
14
15
16
17
18
L1
AI 07 (I)
AI 08 (U)
AI 09 (U)
AI 10 (U)
AI 11 (U)
AI 12 (U)
IED
L2
L3
66
3
110
3
kV
V
1
3
2
66
3
110
3
kV
V
66
3
110
3
kV
V
.
#Not used
5
IEC06000599-2-en.vsd
SMAI2
BLOCK
^GRP2L1
TYPE
AI3P
AI1
AI2
AI3
AI4
AIN
^GRP2L2
^GRP2L3
^GRP2N
4
IEC06000599 V2 EN
Figure 14: Three phase-to-earth connected VTs
Where:
1) shows how to connect three secondary phase-to-earth voltages to three VT inputs in the IED
2) is TRM module where these three voltage inputs are located. It shall be noted that for
these three voltage inputs the following setting values shall be entered:
VTprim=66 kV
VTsec= 110 V
Inside the IED, only the ratio of these two parameters is used. It shall be noted that the
ratio of the entered values exactly corresponds to ratio of one individual VT.
66
66
3
110
110
3
=
EQUATION1903 V1 EN (Equation 13)
Table continues on next page
Section 3 1MRK505186-UEN D
IED application
44
Application manual
3) are three connections made in Signal Matrix Tool (SMT) which connect these three voltage
inputs to first three input channels of the preprocessing function block 5). Depending on
type of functions which need this voltage information, more then one preprocessing block
might be connected in parallel to these three VT inputs
4) shows that in this example the fourth (that is, residual) input channel of the preprocessing
block is not connected in SMT tool. Thus the preprocessing block will automatically
calculate 3Uo inside by vectorial sum from the three phase to earth voltages connected to
the first three input channels of the same preprocessing block. Alternatively, the fourth
input channel can be connected to open delta VT input, as shown in figure 16.
5) Preprocessing block has a task to digitally filter the connected analog inputs and calculate:
fundamental frequency phasors for all four input channels
harmonic content for all four input channels
positive, negative and zero sequence quantities by using the fundamental frequency
phasors for the first three input channels (channel one taken as reference for
sequence quantities)
These calculated values are then available for all built-in protection and control functions
within the IED, which are connected to this preprocessing function block in the
configuration tool. For this application most of the preprocessing settings can be left to the
default values. However the following settings shall be set as shown here:
UBase=66 kV (that is, rated Ph-Ph voltage)
If frequency tracking and compensation is required (this feature is typically required only for
IEDs installed in the generating stations) then the setting parameters DFTReference shall
be set accordingly.
Example how to connect two phase-to-phase connected VTs to the IED
Figure 15 gives an example how to connect the two phase-to-phase connected VTs
to the IED. It as well gives overview of required actions by the user in order to
make this measurement available to the built-in protection and control functions
within the IED. It shall be noted that this VT connection is only used on lower
voltage levels (that is, rated primary voltage below 40 kV).
1MRK505186-UEN D Section 3
IED application
45
Application manual
19
20
21
22
23
24
13
14
15
16
17
18
L1
AI 07 (I)
AI 08 (U)
AI 09 (U)
AI 10 (U)
AI 11 (U)
AI 12 (U)
IED
L2
L3
13.8
120
kV
V
1
2
3
#Not Used
13.8
120
kV
V
.
5
IEC06000600-2-en.vsd
4
SMAI2
BLOCK
^GRP2L1
TYPE
AI3P
AI1
AI2
AI3
AI4
AIN
^GRP2L2
^GRP2L3
^GRP2N
IEC06000600 V2 EN
Figure 15: Two phase-to-phase connected VTs
Where:
1) shows how to connect secondary side of two phase-to-phase VTs to three VT inputs in the
IED
2) is the TRM module where these three voltage inputs are located. It shall be noted that for
these three voltage inputs the following setting values shall be entered:
VTprim=13.8 kV
VTsec=120 V
Please note that inside the IED only ratio of these two parameters is used.
Table continues on next page
Section 3 1MRK505186-UEN D
IED application
46
Application manual
3) are three connections made in the Signal Matrix tool (SMT), which connects these three
voltage inputs to first three input channels of the preprocessing function block 5).
Depending on the type of functions, which need this voltage information, more than one
preprocessing block might be connected in parallel to these three VT inputs
4) shows that in this example the fourth (that is, residual) input channel of the preprocessing
block is not connected in SMT.
5) Preprocessing block has a task to digitally filter the connected analog inputs and calculate:
fundamental frequency phasors for all four input channels
harmonic content for all four input channels
positive, negative and zero sequence quantities by using the fundamental frequency
phasors for the first three input channels (channel one taken as reference for
sequence quantities)
These calculated values are then available for all built-in protection and control functions
within the IED, which are connected to this preprocessing function block in the
configuration tool. For this application most of the preprocessing settings can be left to the
default values. However the following settings shall be set as shown here:
ConnectionType=Ph-Ph
UBase=13.8 kV
If frequency tracking and compensation is required (this feature is typically required only
for IEDs installed in the generating stations) then the setting parameters DFTReference
shall be set accordingly.
Example how to connect the open delta VT to the IED for high
impedance earthed or unearthed
Figure 16 gives an example how to connect the open delta VT to the IED for high
impedance earthed or unearthed power systems. It shall be noted that this type of
VT connection presents secondary voltage proportional to 3Uo to the IED.
In case of a solid earth fault close to the VT location the primary value of 3Uo will
be equal to:
3 3 3
Ph Ph Ph E
Uo U U
- -
= =
EQUATION1921 V1 EN (Equation 14)
The primary rated voltage of such VT is always equal to U
Ph-E
. Therefore, three
series connected VT secondary windings will give the secondary voltage equal to
three times the individual VT secondary winding rating. Thus the secondary
windings of such open delta VTs quite often has a secondary rated voltage equal to
one third of the rated phase-to-phase VT secondary voltage (that is, 110/3V in this
particular example). Figure 16 as well gives overview of required actions by the
user in order to make this measurement available to the built-in protection and
control functions within the IED.
1MRK505186-UEN D Section 3
IED application
47
Application manual
19
20
21
22
23
24
13
14
15
16
17
18
L1
AI 07 (I)
AI 08 (U)
AI 09 (U)
AI 10 (U)
AI 11 (U)
AI 12 (U)
IED
L2
L3
6.6
3
110
3
kV
V
+3Uo
6.6
3
110
3
kV
V
6.6
3
110
3
kV
V
1
2
4
3
# Not Used
5
IEC06000601-2-en.vsd
# Not Used
# Not Used
SMAI2
BLOCK
^GRP2L1
^GRP2L2
^GRP2L3
^GRP2N
TYPE
AI3P
AI1
AI2
AI3
AI4
AIN
IEC06000601 V2 EN
Figure 16: Open delta connected VT in high impedance earthed power system
Section 3 1MRK505186-UEN D
IED application
48
Application manual
Where:
1) shows how to connect the secondary side of open delta VT to one VT input in the IED.
+3Uo shall be connected to the IED
2) is TRM module where this voltage input is located. It shall be noted that for this voltage
input the following setting values shall be entered:
3 6.6 11.43 VTprim kV = =
EQUATION1923 V1 EN (Equation 15)
110
sec 3 110
3
VT V = =
EQUATION1924 V1 EN (Equation 16)
Inside the IED, only the ratio of these two parameters is used. It shall be noted that the
ratio of the entered values exactly corresponds to ratio of one individual open delta VT.
6.6
3 6.6
3
110
110
3
=
EQUATION1925 V1 EN (Equation 17)
3) shows that in this example the first three input channel of the preprocessing block is not
connected in SMT tool.
4) shows the connection made in Signal Matrix Tool (that is, SMT) which connect this
voltage input to the fourth input channel of the preprocessing function block 5).
5) Preprocessing block has a task to digitally filter the connected analog inputs and calculate:
fundamental frequency phasors for all four input channels
harmonic content for all four input channels
positive, negative and zero sequence quantities by using the fundamental frequency
phasors for the first three input channels (channel one taken as reference for
sequence quantities)
These calculated values are then available for all built-in protection and control functions
within the IED, which are connected to this preprocessing function block in the
configuration tool. For this application most of the preprocessing settings can be left to the
default values.
If frequency tracking and compensation is required (this feature is typically required only
for IEDs installed in the generating stations) then the setting parameters DFTReference
shall be set accordingly.
Example how to connect the open delta VT to the IED for low
impedance earthed or solidly earthed power systems
Figure 17 gives an example how to connect the open delta VT to the IED for low
impedance earthed or solidly earthed power systems. It shall be noted that this type
of VT connection presents secondary voltage proportional to 3Uo to the IED.
1MRK505186-UEN D Section 3
IED application
49
Application manual
In case of a solid earth fault close to the VT location the primary value of 3Uo will
be equal to:
3
3
Ph Ph
Ph E
U
Uo U
-
-
= =
EQUATION1926 V1 EN (Equation 18)
The primary rated voltage of such VT is always equal to UPh-E Therefore, three
series connected VT secondary windings will give the secondary voltage equal
only to one individual VT secondary winding rating. Thus the secondary windings
of such open delta VTs quite often has a secondary rated voltage close to rated phase-
to-phase VT secondary voltage, that is, 115V or 115/3V as in this particular
example. Figure 17 as well gives overview of required actions by the user in order
to make this measurement available to the built-in protection and control functions
within the IED.
19
20
21
22
23
24
13
14
15
16
17
18
L1
AI07 (I)
AI08 (U)
AI09 (U)
AI10 (U)
AI11 (U)
AI12 (U)
IED
L2
L3
138
3
115
3
kV
V
+3Uo
138
3
115
3
kV
V
138
3
115
3
kV
V
1
2
4
3
IEC06000602-2-en.vsd
SMAI2
BLOCK
^GRP2L1
^GRP2L2
^GRP2L3
^GRP2N
TYPE
AI3P
AI1
AI2
AI3
AI4
AIN
5
# Not Used
# Not Used
# Not Used
IEC06000602 V2 EN
Figure 17: Open delta connected VT in low impedance earthed power system
Section 3 1MRK505186-UEN D
IED application
50
Application manual
Where:
1) shows how to connect the secondary side of open delta VT to one VT input in the IED.
+3Uo shall be connected to the IED.
2) is TRM module where this voltage input is located. It shall be noted that for this
voltage input the following setting values shall be entered:
138
3 138
3
VTprim kV = =
EQUATION1928 V1 EN (Equation 19)
115
sec 3 115
3
VT V = =
EQUATION1929 V1 EN (Equation 20)
Inside the IED, only the ratio of these two parameters is used. It shall be noted that
the ratio of the entered values exactly corresponds to ratio of one individual open
delta VT.
138
138
3
115
115
3
=
EQUATION1930 V1 EN (Equation 21)
3) shows that in this example the first three input channel of the preprocessing block is
not connected in SMT tool.
4) shows the connection made in Signal Matrix Tool (SMT) which connect this voltage
input to the fourth input channel of the preprocessing function block 5).
5) preprocessing block has a task to digitally filter the connected analog inputs and
calculate:
fundamental frequency phasors for all four input channels
harmonic content for all four input channels
positive, negative and zero sequence quantities by using the fundamental
frequency phasors for the first three input channels (channel one taken as
reference for sequence quantities)
These calculated values are then available for all built-in protection and control
functions within the IED, which are connected to this preprocessing function block in
the configuration tool. For this application most of the preprocessing settings can be
left to the default values.
If frequency tracking and compensation is required (this feature is typically required
only for IEDs installed in the generating stations) then the setting parameters
DFTReference shall be set accordingly.
1MRK505186-UEN D Section 3
IED application
51
Application manual
Example how to connect the neutral point VT to the IED
Figure 18 gives an example how to connect the neutral point VT to the IED. It shall
be noted that this type of VT connection presents secondary voltage proportional to
Uo to the IED.
In case of a solid earth fault in high impedance earthed or unearthed systems the
primary value of Uo voltage will be equal to:
3
Ph Ph
Ph E
U
Uo U
-
-
= =
EQUATION1931 V1 EN (Equation 22)
Figure 18 as well gives overview of required actions by the user in order to make
this measurement available to the built-in protection and control functions within
the IED.
19
20
21
22
23
24
13
14
15
16
17
18
L1 L2 L3
AI07 (I)
AI08 (I)
AI09 (I)
AI10 (U)
AI11 (U)
AI12 (U)
IED
6.6
3
100
kV
V
R
Uo
1
2
3
IEC06000603-2-en.vsd
5
SMAI2
BLOCK
^GRP2L1
^GRP2L2
^GRP2L3
^GRP2N
TYPE
AI3P
AI1
AI2
AI3
AI4
AIN
# Not Used
# Not Used
# Not Used
4
Protected Object
IEC06000603 V2 EN
Figure 18: Neutral point connected VT
Section 3 1MRK505186-UEN D
IED application
52
Application manual
Where
:
1) shows how to connect the secondary side of neutral point VT to one VT input in the IED.
+Uo shall be connected to the IED.
2) is TRM module where this voltage input is located. It shall be noted that for this voltage
input the following setting values shall be entered:
6.6
3.81
3
VTprim kV = =
EQUATION1933 V1 EN (Equation 23)
sec 100 VT V =
EQUATION1934 V1 EN (Equation 24)
Inside the IED, only the ratio of these two parameters is used. It shall be noted that the ratio
of the entered values exactly corresponds to ratio of the neutral point VT.
3) shows that in this example the first three input channel of the preprocessing block is not
connected in SMT tool.
4) shows the connection made in Signal Matrix Tool (SMT) which connect this voltage input to
the fourth input channel of the preprocessing function block 5).
5) preprocessing block has a task to digitally filter the connected analog inputs and calculate:
fundamental frequency phasors for all four input channels
harmonic content for all four input channels
positive, negative and zero sequence quantities by using the fundamental frequency
phasors for the first three input channels (channel one taken as reference for
sequence quantities)
These calculated values are then available for all built-in protection and control functions
within the IED, which are connected to this preprocessing function block in the
configuration tool. For this application most of the preprocessing settings can be left to the
default values.
If frequency tracking and compensation is required (this feature is typically required only for
IEDs installed in the generating stations) then the setting parameters DFTReference shall
be set accordingly.
3.2.3 Setting parameters
The available setting parameters related to analog inputs are
depending on the actual hardware (TRM) and the logic
configuration made in PCM600.
1MRK505186-UEN D Section 3
IED application
53
Application manual
Table 1: AISVBAS Non group settings (basic)
Name Values (Range) Unit Step Default Description
PhaseAngleRef TRM40-Ch1
TRM40-Ch2
TRM40-Ch3
TRM40-Ch4
TRM40-Ch5
TRM40-Ch6
TRM40-Ch7
TRM40-Ch8
TRM40-Ch9
TRM40-Ch10
TRM40-Ch11
TRM40-Ch12
TRM41-Ch1
TRM41-Ch2
TRM41-Ch3
TRM41-Ch4
TRM41-Ch5
TRM41-Ch6
TRM41-Ch7
TRM41-Ch8
TRM41-Ch9
TRM41-Ch10
TRM41-Ch11
TRM41-Ch12
- - TRM40-Ch1 Reference channel for phase angle
presentation
Table 2: TRM_12I Non group settings (basic)
Name Values (Range) Unit Step Default Description
CTStarPoint1 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec1 1 - 10 A 1 1 Rated CT secondary current
CTprim1 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint2 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec2 1 - 10 A 1 1 Rated CT secondary current
CTprim2 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint3 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec3 1 - 10 A 1 1 Rated CT secondary current
CTprim3 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint4 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec4 1 - 10 A 1 1 Rated CT secondary current
CTprim4 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint5 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec5 1 - 10 A 1 1 Rated CT secondary current
CTprim5 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint6 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
Table continues on next page
Section 3 1MRK505186-UEN D
IED application
54
Application manual
Name Values (Range) Unit Step Default Description
CTsec6 1 - 10 A 1 1 Rated CT secondary current
CTprim6 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint7 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec7 1 - 10 A 1 1 Rated CT secondary current
CTprim7 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint8 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec8 1 - 10 A 1 1 Rated CT secondary current
CTprim8 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint9 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec9 1 - 10 A 1 1 Rated CT secondary current
CTprim9 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint10 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec10 1 - 10 A 1 1 Rated CT secondary current
CTprim10 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint11 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec11 1 - 10 A 1 1 Rated CT secondary current
CTprim11 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint12 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec12 1 - 10 A 1 1 Rated CT secondary current
CTprim12 1 - 99999 A 1 3000 Rated CT primary current
Table 3: TRM_9I_3U Non group settings (basic)
Name Values (Range) Unit Step Default Description
CTStarPoint1 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec1 1 - 10 A 1 1 Rated CT secondary current
CTprim1 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint2 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec2 1 - 10 A 1 1 Rated CT secondary current
CTprim2 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint3 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec3 1 - 10 A 1 1 Rated CT secondary current
CTprim3 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint4 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
Table continues on next page
1MRK505186-UEN D Section 3
IED application
55
Application manual
Name Values (Range) Unit Step Default Description
CTsec4 1 - 10 A 1 1 Rated CT secondary current
CTprim4 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint5 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec5 1 - 10 A 1 1 Rated CT secondary current
CTprim5 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint6 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec6 1 - 10 A 1 1 Rated CT secondary current
CTprim6 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint7 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec7 1 - 10 A 1 1 Rated CT secondary current
CTprim7 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint8 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec8 1 - 10 A 1 1 Rated CT secondary current
CTprim8 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint9 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec9 1 - 10 A 1 1 Rated CT secondary current
CTprim9 1 - 99999 A 1 3000 Rated CT primary current
VTsec10 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim10 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec11 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim11 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec12 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim12 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
Table 4: TRM_6I_6U Non group settings (basic)
Name Values (Range) Unit Step Default Description
CTStarPoint1 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec1 1 - 10 A 1 1 Rated CT secondary current
CTprim1 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint2 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec2 1 - 10 A 1 1 Rated CT secondary current
CTprim2 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint3 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec3 1 - 10 A 1 1 Rated CT secondary current
Table continues on next page
Section 3 1MRK505186-UEN D
IED application
56
Application manual
Name Values (Range) Unit Step Default Description
CTprim3 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint4 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec4 1 - 10 A 1 1 Rated CT secondary current
CTprim4 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint5 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec5 1 - 10 A 1 1 Rated CT secondary current
CTprim5 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint6 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec6 1 - 10 A 1 1 Rated CT secondary current
CTprim6 1 - 99999 A 1 3000 Rated CT primary current
VTsec7 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim7 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec8 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim8 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec9 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim9 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec10 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim10 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec11 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim11 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec12 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim12 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
Table 5: TRM_6I Non group settings (basic)
Name Values (Range) Unit Step Default Description
CTStarPoint1 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec1 1 - 10 A 1 1 Rated CT secondary current
CTprim1 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint2 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec2 1 - 10 A 1 1 Rated CT secondary current
CTprim2 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint3 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec3 1 - 10 A 1 1 Rated CT secondary current
CTprim3 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint4 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
Table continues on next page
1MRK505186-UEN D Section 3
IED application
57
Application manual
Name Values (Range) Unit Step Default Description
CTsec4 1 - 10 A 1 1 Rated CT secondary current
CTprim4 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint5 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec5 1 - 10 A 1 1 Rated CT secondary current
CTprim5 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint6 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec6 1 - 10 A 1 1 Rated CT secondary current
CTprim6 1 - 99999 A 1 3000 Rated CT primary current
3.3 Local human-machine interface
3.3.1 Human machine interface
The local human machine interface is available in a small and a medium sized
model. The difference between the two models is the size of the LCD. The small
size LCD can display seven lines of text and the medium size LCD can display the
single line diagram with up to 15 objects on each page. Up to 12 single line
diagram pages can be defined, depending on the product capability.
The local HMI is divided into zones with different functionality.
Status indication LEDs.
Alarm indication LEDs, which consist of 15 LEDs (6 red and 9 yellow) with
user printable label. All LEDs are configurable from PCM600.
Liquid crystal display (LCD).
Keypad with push buttons for control and navigation purposes, switch for
selection between local and remote control and reset.
Isolated RJ45 communication port.
Section 3 1MRK505186-UEN D
IED application
58
Application manual
IEC05000055-LITEN V1 EN
Figure 19: Small, alpha numeric HMI
IEC05000056-LITEN V1 EN
Figure 20: Medium graphic HMI, 15 controllable objects
1MRK505186-UEN D Section 3
IED application
59
Application manual
3.3.2 Local HMI related functions
3.3.2.1 Introduction
The local HMI can be adapted to the application configuration and to user preferences.
Function block LocalHMI
Function block LEDGEN
Setting parameters
3.3.2.2 General setting parameters
Table 6: SCREEN Non group settings (basic)
Name Values (Range) Unit Step Default Description
Language English
OptionalLanguage
- - English Local HMI language
DisplayTimeout 10 - 120 Min 10 60 Local HMI display timeout
AutoRepeat Off
On
- - On Activation of auto-repeat (On) or not (Off)
ContrastLevel -10 - 20 % 1 0 Contrast level for display
DefaultScreen 0 - 0 - 1 0 Default screen
EvListSrtOrder Latest on top
Oldest on top
- - Latest on top Sort order of event list
SymbolFont IEC
ANSI
- - IEC Symbol font for Single Line Diagram
3.3.3 Indication LEDs
3.3.3.1 Introduction
The function block LEDGEN controls and supplies information about the status of
the indication LEDs. The input and output signals of LEDGEN are configured with
PCM600. The input signal for each LED is selected individually with the Signal
Matrix Tool in PCM600.
LEDs (number 16) for trip indications are red.
LEDs (number 715) for start indications are yellow.
Each indication LED on the local HMI can be set individually to operate in six
different sequences
Two sequences operate as follow type.
Four sequences operate as latch type.
Section 3 1MRK505186-UEN D
IED application
60
Application manual
Two of the latching sequence types are intended to be used as a
protection indication system, either in collecting or restarting mode, with
reset functionality.
Two of the latching sequence types are intended to be used as signaling
system in collecting (coll) mode with an acknowledgment functionality.
The light from the LEDs can be steady (-S) or flashing (-F). See the technical
reference manual for more information.
3.3.3.2 Setting parameters
Table 7: LEDGEN Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation mode for the LED function
tRestart 0.0 - 100.0 s 0.1 0.0 Defines the disturbance length
tMax 0.0 - 100.0 s 0.1 0.0 Maximum time for the definition of a
disturbance
SeqTypeLED1 Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
- - Follow-S Sequence type for LED 1
SeqTypeLED2 Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
- - Follow-S Sequence type for LED 2
SeqTypeLED3 Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
- - Follow-S Sequence type for LED 3
SeqTypeLED4 Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
- - Follow-S Sequence type for LED 4
SeqTypeLED5 Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
- - Follow-S Sequence type for LED 5
SeqTypeLED6 Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
- - Follow-S Sequence type for LED 6
Table continues on next page
1MRK505186-UEN D Section 3
IED application
61
Application manual
Name Values (Range) Unit Step Default Description
SeqTypeLED7 Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
- - Follow-S Sequence type for LED 7
SeqTypeLED8 Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
- - Follow-S sequence type for LED 8
SeqTypeLED9 Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
- - Follow-S Sequence type for LED 9
SeqTypeLED10 Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
- - Follow-S Sequence type for LED 10
SeqTypeLED11 Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
- - Follow-S Sequence type for LED 11
SeqTypeLED12 Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
- - Follow-S Sequence type for LED 12
SeqTypeLED13 Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
- - Follow-S Sequence type for LED 13
SeqTypeLED14 Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
- - Follow-S Sequence type for LED 14
SeqTypeLED15 Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
- - Follow-S Sequence type for LED 15
Section 3 1MRK505186-UEN D
IED application
62
Application manual
3.4 Basic IED functions
3.4.1 Self supervision with internal event list
3.4.1.1 Application
The protection and control IEDs have many included functions. The included self-
supervision with internal event list function block provides good supervision of the
IED. The fault signals make it easier to analyze and locate a fault.
Both hardware and software supervision is included and it is also possible to
indicate possible faults through a hardware contact on the power supply module and/
or through the software communication.
Internal events are generated by the built-in supervisory functions. The supervisory
functions supervise the status of the various modules in the IED and, in case of
failure, a corresponding event is generated. Similarly, when the failure is corrected,
a corresponding event is generated.
Apart from the built-in supervision of the various modules, events are also
generated when the status changes for the:
built-in real time clock (in operation/out of order).
external time synchronization (in operation/out of order).
Events are also generated:
whenever any setting in the IED is changed.
The internal events are time tagged with a resolution of 1 ms and stored in a list.
The list can store up to 40 events. The list is based on the FIFO principle, that is,
when it is full, the oldest event is overwritten. The list cannot be cleared and its
content cannot be modified.
The list of internal events provides valuable information, which can be used during
commissioning and fault tracing.
The information can only be retrieved with the aid of a Station Monitoring System
(SMS). The PC can either be connected to the front port, or to the port at the back
of the IED.
3.4.1.2 Setting parameters
The function does not have any parameters available in the local HMI or PCM600.
1MRK505186-UEN D Section 3
IED application
63
Application manual
3.4.2 Time synchronization
3.4.2.1 Application
Use time synchronization to achieve a common time base for the IEDs in a
protection and control system. This makes comparison of events and disturbance
data between all IEDs in the system possible.
Time-tagging of internal events and disturbances are an excellent help when
evaluating faults. Without time synchronization, only the events within the IED can
be compared to one another. With time synchronization, events and disturbances
within the entire station, and even between line ends, can be compared at evaluation.
In the IED, the internal time can be synchronized from a number of sources:
BIN (Binary Minute Pulse)
GPS
SNTP
IRIG-B
SPA
LON
PPS
For time synchronization of line differential protection RED670 with diff
communication in GPS-mode, a GPS-based time synchronization is needed. This
can be optical IRIG-B with 1344 from an external GPS-clock or an internal GPS-
receiver.
Out of these, LON and SPA contains two types of synchronization messages:
Coarse time messages are sent every minute and contain complete date and
time, that is year, month, day, hour, minute, second and millisecond.
Fine time messages are sent every second and comprise only seconds and
milliseconds.
The setting tells the IED which of these that shall be used to synchronize the IED.
It is possible to set several time-sources, that is for instance both SNTP and GPS,
and in that case the IED will automatically choose the time-source that will provide
the best accuracy. At a given point in time, only one time-source will be used.
3.4.2.2 Setting guidelines
System time
The time is set with years, month, day, hour, minute, second and millisecond.
Section 3 1MRK505186-UEN D
IED application
64
Application manual
Synchronization
The setting parameters for the real-time clock with external time synchronization
(TIME) are set via local HMI or PCM600.
TimeSynch
When the source of the time synchronization is selected on the local HMI, the
parameter is called TimeSynch. The time synchronization source can also be set
from PCM600. The setting alternatives are:
FineSyncSource which can have the following values:
Off
SPA
LON
BIN (Binary Minute Pulse)
GPS
GPS+SPA
GPS+LON
GPS+BIN
SNTP
GPS+SNTP
GPS+IRIG-B
IRIG-B
PPS
CoarseSyncSrc which can have the following values:
Off
SPA
LON
SNTP
DNP
The function input to be used for minute-pulse synchronization is called TIME-
MINSYNC.
The system time can be set manually, either via the local HMI or via any of the
communication ports. The time synchronization fine tunes the clock (seconds and
milliseconds).
Set the course time synchronizing source (CoarseSyncSrc) to Off
when GPS time synchronization of line differential function is used.
Set the fine time synchronization source (FineSyncSource) to GPS.
The GPS will thus provide the complete time synchronization. GPS
alone shall synchronize the analogue values in such systems. No
other external time synchronizing source is allowed including
minute pulse, not even as back-up in version 1.1 rev 9 and earlier.
This limitation is eliminated in version 1.1 rev 10 and later.
1MRK505186-UEN D Section 3
IED application
65
Application manual
3.4.2.3 Setting parameters
Path in the local HMI is located under Main menu/Setting/Time
Path in PCM600 is located under Main menu/Settings/Time/Synchronization
Table 8: TIMESYNCHGEN Non group settings (basic)
Name Values (Range) Unit Step Default Description
CoarseSyncSrc Off
SPA
LON
SNTP
DNP
- - Off Coarse time synchronization source
FineSyncSource Off
SPA
LON
BIN
GPS
GPS+SPA
GPS+LON
GPS+BIN
SNTP
GPS+SNTP
IRIG-B
GPS+IRIG-B
PPS
- - Off Fine time synchronization source
SyncMaster Off
SNTP-Server
- - Off Activate IEDas synchronization master
TimeAdjustRate Slow
Fast
- - Slow Adjust rate for time synchronization
Table 9: SYNCHBIN Non group settings (basic)
Name Values (Range) Unit Step Default Description
ModulePosition 3 - 16 - 1 3 Hardware position of IO module for time
synchronization
BinaryInput 1 - 16 - 1 1 Binary input number for time
synchronization
BinDetection PositiveEdge
NegativeEdge
- - PositiveEdge Positive or negative edge detection
Table 10: SYNCHSNTP Non group settings (basic)
Name Values (Range) Unit Step Default Description
ServerIP-Add 0 - 18 IP
Address
1 0.0.0.0 Server IP-address
RedServIP-Add 0 - 18 IP
Address
1 0.0.0.0 Redundant server IP-address
Section 3 1MRK505186-UEN D
IED application
66
Application manual
Table 11: DSTBEGIN Non group settings (basic)
Name Values (Range) Unit Step Default Description
MonthInYear January
February
March
April
May
June
July
August
September
October
November
December
- - March Month in year when daylight time starts
DayInWeek Sunday
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
- - Sunday Day in week when daylight time starts
WeekInMonth Last
First
Second
Third
Fourth
- - Last Week in month when daylight time starts
UTCTimeOfDay 0 - 86400 s 1 3600 UTC Time of day in seconds when
daylight time starts
Table 12: DSTEND Non group settings (basic)
Name Values (Range) Unit Step Default Description
MonthInYear January
February
March
April
May
June
July
August
September
October
November
December
- - October Month in year when daylight time ends
DayInWeek Sunday
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
- - Sunday Day in week when daylight time ends
WeekInMonth Last
First
Second
Third
Fourth
- - Last Week in month when daylight time ends
UTCTimeOfDay 0 - 86400 s 1 3600 UTC Time of day in seconds when
daylight time ends
1MRK505186-UEN D Section 3
IED application
67
Application manual
Table 13: TIMEZONE Non group settings (basic)
Name Values (Range) Unit Step Default Description
NoHalfHourUTC -24 - 24 - 1 0 Number of half-hours from UTC
Table 14: SYNCHIRIG-B Non group settings (basic)
Name Values (Range) Unit Step Default Description
SynchType BNC
Opto
- - Opto Type of synchronization
TimeDomain LocalTime
UTC
- - LocalTime Time domain
Encoding IRIG-B
1344
1344TZ
- - IRIG-B Type of encoding
TimeZoneAs1344 MinusTZ
PlusTZ
- - PlusTZ Time zone as in 1344 standard
3.4.3 Parameter setting groups
3.4.3.1 Application
Six sets of settings are available to optimize IED operation for different system
conditions. By creating and switching between fine tuned setting sets, either from
the local HMI or configurable binary inputs, results in a highly adaptable IED that
can cope with a variety of system scenarios.
Different conditions in networks with different voltage levels require highly
adaptable protection and control units to best provide for dependability, security
and selectivity requirements. Protection units operate with a higher degree of
availability, especially, if the setting values of their parameters are continuously
optimized according to the conditions in the power system.
Operational departments can plan for different operating conditions in the primary
equipment. The protection engineer can prepare the necessary optimized and pre-
tested settings in advance for different protection functions. Six different groups of
setting parameters are available in the IED. Any of them can be activated through
the different programmable binary inputs by means of external or internal control
signals.
A function block, SETGRPS, defines how many setting groups are used. Setting is
done with parameter MAXSETGR and shall be set to the required value for each
application. Only the number of setting groups set will be available in the
Parameter Setting tool for activation with the ActiveGroup function block.
Section 3 1MRK505186-UEN D
IED application
68
Application manual
3.4.3.2 Setting guidelines
The setting ActiveSetGrp, is used to select which parameter group to be active. The
active group can also be selected with configured input to the function block
SETGRPS.
The length of the pulse, sent out by the output signal SETCHGD when an active
group has changed, is set with the parameter t.
The parameter MAXSETGR defines the maximum number of setting groups in use
to switch between. Only the selected number of setting groups will be available in
the Parameter Setting tool (PST) for activation with the ActiveGroup function block.
3.4.3.3 Setting parameters
Table 15: ActiveGroup Non group settings (basic)
Name Values (Range) Unit Step Default Description
t 0.0 - 10.0 s 0.1 1.0 Pulse length of pulse when setting
changed
Table 16: SETGRPS Non group settings (basic)
Name Values (Range) Unit Step Default Description
ActiveSetGrp SettingGroup1
SettingGroup2
SettingGroup3
SettingGroup4
SettingGroup5
SettingGroup6
- - SettingGroup1 ActiveSettingGroup
MAXSETGR 1 - 6 No 1 1 Max number of setting groups 1-6
3.4.4 Test mode functionality TEST
3.4.4.1 Application
The protection and control IEDs have a complex configuration with many included
functions. To make the testing procedure easier, the IEDs include the feature,
which allows to individually blocking a single, several or all functions.
This means that it is possible to see when a function is activated or trips. It also
enables the user to follow the operation of several related functions to check
correct functionality and to check parts of the configuration, and so on.
3.4.4.2 Setting guidelines
Remember always that there are two possible ways to place the IED in the Test
mode: On state. If, the IED is set to normal operation (TestMode = Off), but the
1MRK505186-UEN D Section 3
IED application
69
Application manual
functions are still shown being in the test mode, the input signal INPUT on the
TESTMODE function block might be activated in the configuration.
3.4.4.3 Setting parameters
Table 17: TESTMODE Non group settings (basic)
Name Values (Range) Unit Step Default Description
TestMode Off
On
- - Off Test mode in operation (On) or not (Off)
EventDisable Off
On
- - Off Event disable during testmode
CmdTestBit Off
On
- - Off Command bit for test required or not
during testmode
3.4.5 Change lock CHNGLCK
3.4.5.1 Application
Change lock function CHNGLCK is used to block further changes to the IED
configuration once the commissioning is complete. The purpose is to make it
impossible to perform inadvertent IED configuration changes beyond a certain
point in time.
However, when activated, CHNGLCK will still allow the following changes of the
IED state that does not involve reconfiguring of the IED:
Monitoring
Reading events
Resetting events
Reading disturbance data
Clear disturbances
Reset LEDs
Reset counters and other runtime component states
Control operations
Set system time
Enter and exit from test mode
Change of active setting group
The binary input controlling the function is defined in ACT or SMT. The
CHNGLCK function is configured using ACT.
LOCK Binary input signal that will activate/deactivate the function, defined in ACT or
SMT.
Section 3 1MRK505186-UEN D
IED application
70
Application manual
When CHNGLCK has a logical one on its input, then all attempts to modify the
IED configuration will be denied and the message "Error: Changes blocked" will
be displayed on the local HMI; in PCM600 the message will be "Operation denied
by active ChangeLock". The CHNGLCK function should be configured so that it is
controlled by a signal from a binary input card. This guarantees that by setting that
signal to a logical zero, CHNGLCK is deactivated. If any logic is included in the
signal path to the CHNGLCK input, that logic must be designed so that it cannot
permanently issue a logical one on the CHNGLCK input. If such a situation would
occur in spite of these precautions, then please contact the local ABB
representative for remedial action.
3.4.5.2 Setting parameters
Table 18: CHNGLCK Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation LockHMI and Com
LockHMI,
EnableCom
EnableHMI,
LockCom
- - LockHMI and Com Operation mode of change lock
3.4.6 IED identifiers
3.4.6.1 Application
IED identifiers (TERMINALID) function allows the user to identify the individual
IED in the system, not only in the substation, but in a whole region or a country.
Use only characters A-Z, a-z and 0-9 in station, object and unit names.
3.4.6.2 Setting parameters
Table 19: TERMINALID Non group settings (basic)
Name Values (Range) Unit Step Default Description
StationName 0 - 18 - 1 Station name Station name
StationNumber 0 - 99999 - 1 0 Station number
ObjectName 0 - 18 - 1 Object name Object name
ObjectNumber 0 - 99999 - 1 0 Object number
UnitName 0 - 18 - 1 Unit name Unit name
UnitNumber 0 - 99999 - 1 0 Unit number
1MRK505186-UEN D Section 3
IED application
71
Application manual
3.4.7 Product information
3.4.7.1 Application
The Product identifiers function identifies the IED. The function has seven pre-set,
settings that are unchangeable but nevertheless very important:
IEDProdType
ProductDef
FirmwareVer
SerialNo
OrderingNo
ProductionDate
The settings are visible on the local HMI , under Main menu/Diagnostics/IED
status/Product identifiers
They are very helpful in case of support process (such as repair or maintenance).
3.4.7.2 Setting parameters
The function does not have any parameters available in the local HMI or PCM600.
Factory defined settings
The factory defined settings are very useful for identifying a specific version and
very helpful in the case of maintenance, repair, interchanging IEDs between
different Substation Automation Systems and upgrading. The factory made settings
can not be changed by the customer. They can only be viewed. The settings are
found in the local HMI under Main menu/Diagnostics/IED status/Product
identifiers
The following identifiers are available:
IEDProdType
Describes the type of the IED (like REL, REC or RET). Example: REL670
ProductDef
Describes the release number, from the production. Example: 1.1.r01
FirmwareVer
Describes the firmware version. Example: 1.4.51
Firmware versions numbers are running independently from the
release production numbers. For every release numbers (like 1.4.51)
there can be one or more firmware versions, depending on the small
issues corrected in between releases.
IEDMainFunType
Main function type code according to IEC 60870-5-103. Example: 128
(meaning line protection).
Section 3 1MRK505186-UEN D
IED application
72
Application manual
SerialNo
OrderingNo
ProductionDate
3.4.8 Rated system frequency PRIMVAL
3.4.8.1 Application
The rated system frequency is set under Main menu/General settings/ Power
system/ Primary Values in the local HMI and PCM600 parameter setting tree.
3.4.8.2 Setting guidelines
Set the system rated frequency. Refer to section "Signal matrix for analog inputs
SMAI" for description on frequency tracking.
3.4.8.3 Setting parameters
Table 20: PRIMVAL Non group settings (basic)
Name Values (Range) Unit Step Default Description
Frequency 50.0 - 60.0 Hz 10.0 50.0 Rated system frequency
3.4.9 Signal matrix for binary inputs SMBI
3.4.9.1 Application
The Signal matrix for binary inputs function SMBI is used within the Application
Configuration tool in direct relation with the Signal Matrix tool. SMBI represents
the way binary inputs are brought in for one IED configuration.
3.4.9.2 Setting guidelines
There are no setting parameters for the Signal matrix for binary inputs SMBI
available to the user in Parameter Setting tool. However, the user must give a name
to SMBI instance and the SMBI inputs, directly in the Application Configuration
tool. These names will define SMBI function in the Signal Matrix tool. The user
defined name for the input or output signal will also appear on the respective
output or input signal.
3.4.9.3 Setting parameters
The function does not have any parameters available in local HMI or PCM600.
1MRK505186-UEN D Section 3
IED application
73
Application manual
3.4.10 Signal matrix for binary outputs SMBO
3.4.10.1 Application
The Signal matrix for binary outputs function SMBO is used within the
Application Configuration tool in direct relation with the Signal Matrix tool.
SMBO represents the way binary outputs are sent from one IED configuration.
3.4.10.2 Setting guidelines
There are no setting parameters for the Signal matrix for binary outputs SMBO
available to the user in Parameter Setting tool. However, the user must give a name
to SMBO instance and SMBO outputs, directly in the Application Configuration
tool. These names will define SMBO function in the Signal Matrix tool.
3.4.10.3 Setting parameters
The function does not have any parameters available in local HMI or PCM600.
3.4.11 Signal matrix for mA inputs SMMI
3.4.11.1 Application
The Signal matrix for mA inputs function SMMI is used within the Application
Configuration tool in direct relation with the Signal Matrix tool. SMMI represents
the way milliamp (mA) inputs are brought in for one IED configuration.
3.4.11.2 Setting guidelines
There are no setting parameters for the Signal matrix for mA inputs SMMI
available to the user in the Parameter Setting tool. However, the user must give a
name to SMMI instance and SMMI inputs, directly in the Application
Configuration tool.
3.4.11.3 Setting parameters
The function does not have any parameters available in the local HMI or PCM600.
3.4.12 Signal matrix for analog inputs SMAI
Section 3 1MRK505186-UEN D
IED application
74
Application manual
3.4.12.1 Application
Signal matrix for analog inputs function SMAI (or the pre-processing function) is
used within PCM600 in direct relation with the Signal Matrix tool or the
Application Configuration tool. Signal Matrix tool represents the way analog
inputs are brought in for one IED configuration.
3.4.12.2 Frequency values
The frequency functions includes a functionality based on level of positive
sequence voltage, IntBlockLevel, to validate if the frequency measurement is valid
or not. If positive sequence voltage is lower than IntBlockLevel the function is
blocked. IntBlockLevel, is set in % of UBase/3
If SMAI setting ConnectionType is Ph-Ph at least two of the inputs GRPxL1,
GRPxL2 and GRPxL3 must be connected in order to calculate positive sequence
voltage. If SMAI setting ConnectionType is Ph-N, all three inputs GRPxL1,
GRPxL2 and GRPxL3 must be connected in order to calculate positive sequence
voltage.
If only one phase-phase voltage is available and SMAI setting ConnectionType is
Ph-Ph the user is advised to connect two (not three) of the inputs GRPxL1,
GRPxL2 and GRPxL3 to the same voltage input as shown in figure 21 to make
SMAI calculating a positive sequence voltage (that is input voltage/3).
IEC10000060-1-en.vsd
IEC10000060 V1 EN
Figure 21: Connection example
The above described scenario does not work if SMAI setting
ConnectionType is Ph-N. If only one phase-earth voltage is
available, the same type of connection can be used but the SMAI
ConnectionType setting must still be Ph-Ph and this has to be
accounted for when setting IntBlockLevel. If SMAI setting
ConnectionType is Ph-N and the same voltage is connected to all
three SMAI inputs, the positive sequence voltage will be zero and
the frequency functions will not work properly.
The outputs from the above configured SMAI block shall only be
used for Overfrequency protection (SAPTOF), Underfrequency
1MRK505186-UEN D Section 3
IED application
75
Application manual
protection (SAPTUF) and Rate-of-change frequency protection
(SAPFRC) due to that all other information except frequency and
positive sequence voltage might be wrongly calculated.
3.4.12.3 Setting guidelines
The parameters for the signal matrix for analog inputs (SMAI) functions are set via
the local HMI or PCM600.
Every SMAI function block can receive four analog signals (three phases and one
neutral value), either voltage or current. SMAI outputs give information about
every aspect of the 3ph analog signals acquired (phase angle, RMS value,
frequency and frequency derivates, and so on 244 values in total). Besides the
block group name, the analog inputs type (voltage or current) and the analog
input names that can be set directly in ACT.
Instantaneous protection function with a 3 ms cycle time, needs to be connected to
the processing SMAI function block, which is also running at 3 ms task cycle. In
addition, logic function blocks used with these fast cycle protection functions need
to have 3 ms task cycle. Same procedure needs to be followed for each cycle time.
DFTRefExtOut: Parameter valid for function block SMAI1 only. Reference block
for external output (SPFCOUT function output).
DFTReference: Reference DFT for the block.
These DFT reference block settings decide DFT reference for DFT calculations
(Internal DFTRef will use fixed DFT reference based on set system frequency.
AdDFTRefChn will use DFT reference from the selected group block, when own
group selected adaptive DFT reference will be used based on calculated signal
frequency from own group.ExternalDFTRef will use reference based on input
DFTSPFC.
ConnectionType: Connection type for that specific instance (n) of the SMAI (if it is
Ph-N or Ph-Ph). Depending on connection type setting the not connected Ph-N or
Ph-Ph outputs will be calculated.
Negation: If the user wants to negate the 3ph signal, it is possible to choose to
negate only the phase signals Negate3Ph, only the neutral signal NegateN or both
Negate3Ph+N; negation means rotation with 180 of the vectors.
UBase: Base voltage setting (for each instance x).
MinValFreqMeas: The minimum value of the voltage for which the frequency is
calculated, expressed as percent of UBase (for each instance n).
Settings DFTRefExtOut and DFTReference shall be set to default
value InternalDFTRef if no VT inputs are available.
Section 3 1MRK505186-UEN D
IED application
76
Application manual
Examples of adaptive frequency tracking
1MRK505186-UEN D Section 3
IED application
77
Application manual
IEC07000197.vsd
SMAI i nstance 3 phase group
SMAI1:1 1
SMAI2:2 2
SMAI3:3 3
SMAI4:4 4
SMAI5:5 5
SMAI6:6 6
SMAI7:7 7
SMAI8:8 8
SMAI9:9 9
SMAI10:10 10
SMAI11:11 11
SMAI12:12 12
Task ti me group 1
SMAI i nstance 3 phase group
SMAI1:13 1
SMAI2:14 2
SMAI3:15 3
SMAI4:16 4
SMAI5:17 5
SMAI6:18 6
SMAI7:19 7
SMAI8:20 8
SMAI9:21 9
SMAI10:22 10
SMAI11:23 11
SMAI12:24 12
Task ti me group 2
SMAI i nstance 3 phase group
SMAI1:25 1
SMAI2:26 2
SMAI3:27 3
SMAI4:28 4
SMAI5:29 5
SMAI6:30 6
SMAI7:31 7
SMAI8:32 8
SMAI9:33 9
SMAI10:34 10
SMAI11:35 11
SMAI12:36 12
Task ti me group 3
AdDFTRefCh7
AdDFTRefCh4
IEC07000197 V2 EN
Figure 22: SMAI instances as organized in different task time groups and the
corresponding parameter numbers
Section 3 1MRK505186-UEN D
IED application
78
Application manual
The examples shows a situation with adaptive frequency tracking with one
reference selected for all instances. In practice each instance can be adapted to the
needs of the actual application.
Example 1
IEC07000198.vsd
SMAI1:1
BLOCK
DFTSPFC
^GRP1L1
^GRP1L2
^GRP1L3
^GRP1N
TYPE
SPFCOUT
AI3P
AI1
AI2
AI3
AI4
AIN
SMAI1:13
BLOCK
DFTSPFC
^GRP1L1
^GRP1L2
^GRP1L3
^GRP1N
TYPE
SPFCOUT
AI3P
AI1
AI2
AI3
AI4
AIN
SMAI1:25
BLOCK
DFTSPFC
^GRP1L1
^GRP1L2
^GRP1L3
^GRP1N
TYPE
SPFCOUT
AI3P
AI1
AI2
AI3
AI4
AIN
IEC07000198 V2 EN
Figure 23: Configuration for using an instance in task time group 1 as DFT
reference
Assume instance SMAI7:7 in task time group 1 has been selected in the
configuration to control the frequency tracking . Observe that the selected reference
instance must be a voltage type.
For task time group 1 this gives the following settings (see Figure 22 for numbering):
SMAI1:1: DFTRefExtOut = AdDFTRefCh7 to route SMAI7:7 reference to the
SPFCOUT output, DFTReference = AdDFTRefCh7 for SMAI1:1 to use SMAI7:7
as reference (see Figure 23) SMAI2:2 SMAI12:12: DFTReference =
AdDFTRefCh7 for SMAI2:2 SMAI12:12 to use SMAI7:7 as reference.
For task time group 2 this gives the following settings:
SMAI1:13 SMAI12:24: DFTReference = ExternalDFTRef to use DFTSPFC
input as reference (SMAI7:7)
For task time group 3 this gives the following settings:
SMAI1:25 SMAI12:36: DFTReference = ExternalDFTRef to use DFTSPFC
input as reference (SMAI7:7)
Example 2
1MRK505186-UEN D Section 3
IED application
79
Application manual
IEC07000199.vsd
SMAI1:13
BLOCK
DFTSPFC
^GRP1L1
^GRP1L2
^GRP1L3
^GRP1N
TYPE
SPFCOUT
AI3P
AI1
AI2
AI3
AI4
AIN
SMAI1:1
BLOCK
DFTSPFC
^GRP1L1
^GRP1L2
^GRP1L3
^GRP1N
TYPE
SPFCOUT
AI3P
AI1
AI2
AI3
AI4
AIN
SMAI1:25
BLOCK
DFTSPFC
^GRP1L1
^GRP1L2
^GRP1L3
^GRP1N
TYPE
SPFCOUT
AI3P
AI1
AI2
AI3
AI4
AIN
IEC07000199 V2 EN
Figure 24: Configuration for using an instance in task time group 2 as DFT
reference.
Assume instance SMAI4:16 in task time group 2 has been selected in the
configuration to control the frequency tracking for all instances. Observe that the
selected reference instance must be a voltage type
For task time group 1 this gives the following settings (see Figure 22 for numbering):
SMAI1:1 SMAI12:12: DFTReference = ExternalDFTRef to use DFTSPFC input
as reference (SMAI4:16)
For task time group 2 this gives the following settings:
SMAI1:13: DFTRefExtOut = AdDFTRefCh4 to route SMAI4:16 reference to the
SPFCOUT output, DFTReference = AdDFTRefCh4 for SMAI1:13 to use
SMAI4:16 as reference (see Figure 24) SMAI2:14 SMAI12:24: DFTReference =
AdDFTRefCh4 to use SMAI4:16 as reference.
For task time group 3 this gives the following settings:
SMAI1:25 SMAI12:36: DFTReference = ExternalDFTRef to use DFTSPFC
input as reference (SMAI4:16)
Section 3 1MRK505186-UEN D
IED application
80
Application manual
3.4.12.4 Setting parameters
Table 21: SMAI1 Non group settings (basic)
Name Values (Range) Unit Step Default Description
DFTRefExtOut InternalDFTRef
AdDFTRefCh1
AdDFTRefCh2
AdDFTRefCh3
AdDFTRefCh4
AdDFTRefCh5
AdDFTRefCh6
AdDFTRefCh7
AdDFTRefCh8
AdDFTRefCh9
AdDFTRefCh10
AdDFTRefCh11
AdDFTRefCh12
External DFT ref
- - InternalDFTRef DFT reference for external output
DFTReference InternalDFTRef
AdDFTRefCh1
AdDFTRefCh2
AdDFTRefCh3
AdDFTRefCh4
AdDFTRefCh5
AdDFTRefCh6
AdDFTRefCh7
AdDFTRefCh8
AdDFTRefCh9
AdDFTRefCh10
AdDFTRefCh11
AdDFTRefCh12
External DFT ref
- - InternalDFTRef DFT reference
ConnectionType Ph-N
Ph-Ph
- - Ph-N Input connection type
TYPE 1 - 2 Ch 1 1 1=Voltage, 2=Current
Table 22: SMAI1 Non group settings (advanced)
Name Values (Range) Unit Step Default Description
Negation Off
NegateN
Negate3Ph
Negate3Ph+N
- - Off Negation
MinValFreqMeas 5 - 200 % 1 10 Limit for frequency calculation in % of
UBase
UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage
1MRK505186-UEN D Section 3
IED application
81
Application manual
Table 23: SMAI2 Non group settings (basic)
Name Values (Range) Unit Step Default Description
DFTReference InternalDFTRef
AdDFTRefCh1
AdDFTRefCh2
AdDFTRefCh3
AdDFTRefCh4
AdDFTRefCh5
AdDFTRefCh6
AdDFTRefCh7
AdDFTRefCh8
AdDFTRefCh9
AdDFTRefCh10
AdDFTRefCh11
AdDFTRefCh12
External DFT ref
- - InternalDFTRef DFT reference
ConnectionType Ph-N
Ph-Ph
- - Ph-N Input connection type
TYPE 1 - 2 Ch 1 1 1=Voltage, 2=Current
Table 24: SMAI2 Non group settings (advanced)
Name Values (Range) Unit Step Default Description
Negation Off
NegateN
Negate3Ph
Negate3Ph+N
- - Off Negation
MinValFreqMeas 5 - 200 % 1 10 Limit for frequency calculation in % of
UBase
UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage
3.4.13 Summation block 3 phase 3PHSUM
3.4.13.1 Application
The analog summation block 3PHSUM function block is used in order to get the
sum of two sets of 3 phase analog signals (of the same type) for those IED
functions that might need it.
3.4.13.2 Setting guidelines
The summation block receives the three-phase signals from SMAI blocks. The
summation block has several settings.
SummationType: Summation type (Group 1 + Group 2, Group 1 - Group 2, Group
2 - Group 1 or (Group 1 + Group 2)).
DFTReference: The reference DFT block (InternalDFT Ref,AdDFTRefCh1 or
External DFT ref) .
Section 3 1MRK505186-UEN D
IED application
82
Application manual
FreqMeasMinVal: The minimum value of the voltage for which the frequency is
calculated, expressed as percent of UBasebase voltage setting (for each instance x).
UBase: Base voltage setting.
3.4.13.3 Setting parameters
Table 25: 3PHSUM Non group settings (basic)
Name Values (Range) Unit Step Default Description
SummationType Group1+Group2
Group1-Group2
Group2-Group1
-(Group1+Group2)
- - Group1+Group2 Summation type
DFTReference InternalDFTRef
AdDFTRefCh1
External DFT ref
- - InternalDFTRef DFT reference
Table 26: 3PHSUM Non group settings (advanced)
Name Values (Range) Unit Step Default Description
FreqMeasMinVal 5 - 200 % 1 10 Amplitude limit for frequency calculation
in % of Ubase
UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage
3.4.14 Authority status ATHSTAT
3.4.14.1 Application
Authority status (ATHSTAT) function is an indication function block, which
informs about two events related to the IED and the user authorization:
the fact that at least one user has tried to log on wrongly into the IED and it
was blocked (the output USRBLKED)
the fact that at least one user is logged on (the output LOGGEDON)
The two outputs of ATHSTAT function can be used in the configuration for
different indication and alarming reasons, or can be sent to the station control for
the same purpose.
3.4.14.2 Setting parameters
The function does not have any parameters available in the local HMI or PCM600.
1MRK505186-UEN D Section 3
IED application
83
Application manual
3.5 Differential protection
3.5.1 1Ph High impedance differential protection HZPDIF
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
1Ph High impedance differential
protection
HZPDIF
Id
SYMBOL-CC V2 EN
87
3.5.1.1 Application
The 1Ph High impedance differential protection function HZPDIFcan be used as:
Autotransformer differential protection
Restricted earth fault protection
T-feeder protection
Tertiary (or secondary busbar) protection
Tertiary connected reactor protection
Generator differential protection at block connected generators.
The application will be dependent on the primary system arrangements and
location of breakers, available independent cores on CTs and so on.
Section 3 1MRK505186-UEN D
IED application
84
Application manual
IEC05000163-1-en.vsd
3Id
3Id
3Id
Id
3Id
3Id
3Id
G
3Id
IEC05000163 V2 EN
Figure 25: Different applications of a 1Ph High impedance differential
protection HZPDIF function
The basics of the high impedance principle
The high impedance differential protection principle has been used for many years
and is well documented. The operating characteristic provides very good sensitivity
and high speed operation. One main benefit offered by the principle is an absolute
stability (that is, non-operation) for external faults even in the presence of heavy
CT saturation. The principle is based on the CT secondary current circulating
between involved current transformers and not through the IED due to its high
impedance, normally in the range of hundreds of ohms and sometimes above
1MRK505186-UEN D Section 3
IED application
85
Application manual
kohm. When a fault occurs the current cannot circulate and is forced through the
differential circuit causing operation.
Id
IEC05000164-1-en.vsd
IEC05000164 V2 EN
Figure 26: The high impedance principle for one phase with four current
transformer inputs
For a through fault one current transformer might saturate when the other CTs still
will feed current. For such a case a voltage will be developed across the IED. The
calculations are made with the worst situations in mind and a minimum operating
voltage U
R
is calculated according to equation 25
( ) max UR IF Rct Rl > +
EQUATION1531 V1 EN (Equation 25)
where:
IFmax is the maximum through fault current at the secondary side,
Rct is the current transformer secondary resistance and
RI is the maximum loop resistance of the circuit at any CT.
Section 3 1MRK505186-UEN D
IED application
86
Application manual
The maximum operating voltage has to be calculated (all loops) and the IED is set
higher than the highest achieved value (setting U>Trip). As the loop resistance is
the value to the connection point from each CT it is advisable to do all the CT core
summations in the switchgear to have shortest possible loops. This will give lower
setting values and also a better balanced scheme. The connection in to the control
room can then be from the most central bay.
For an internal fault circulation is not possible and due to the high impedance the
current transformers will immediately saturate and rms voltage, depending on the
size of current transformer saturation voltage, will be developed across the IED.
Due to the fast saturation very high peak voltages can be achieved. To prevent the
risk of flashover in the circuit, a voltage limiter must be included. The voltage
limiter is a voltage dependent resistor (Metrosil).
Based on the above calculated operating voltage the IED stabilizing resistor must
be selected. The external unit with stabilizing resistor has a value of either 6800
ohms or 2200 ohms (depending on ordered alternative) with a shorting link to
allow adjustment to the required value. Select a suitable value of the resistor based
on the UR voltage calculated. A higher resistance value will give a higher
sensitivity and a lower value a lower sensitivity.
The function has an operating current range 20 mA to 1.0A for 1 A inputs and 100
mA to 5A for 5A inputs. This, together with the selected and set value, is used to
calculate the required value of current at the set U>Trip and SeriesResitor values.
The CT inputs used for 1Ph High impedance differential protection
HZPDIF function, shall be set to have ratio 1:1
The table below shows the operating voltages for different resistances and the
related operating current. Adjust as required based on this table or to values in
between as required for the application.
Minimum ohms can be difficult to adjust due to the small value
compared to the total value.
Normally the voltage can be increased to higher values than the calculated
minimum U>Trip with a minor change of total operating values as long as this is
done by adjusting the resistor to a higher value. Check the sensitivity calculation
below for reference.
Table 27: Operating voltages for 1A
Operating
voltage
Stabilizing
resistor R
ohms
Operating
current level
1 A
Stabilizing
resistor R
ohms
Operating
current level
1 A
Stabilizing
resistor R
ohms
Operating
current level
1 A
20 V 1000 0.020 A -- -- -- --
40 V 2000 0.020 A 1000 0.040 A -- --
60 V 3000 0.020 A 1500 0.040 A 600 0.100 A
Table continues on next page
1MRK505186-UEN D Section 3
IED application
87
Application manual
Operating
voltage
Stabilizing
resistor R
ohms
Operating
current level
1 A
Stabilizing
resistor R
ohms
Operating
current level
1 A
Stabilizing
resistor R
ohms
Operating
current level
1 A
80 V 4000 0.020 A 2000 0.040 A 800 0.100 A
100 V 5000 0.020 A 2500 0.040 A 1000 0.100 A
150 V 6000 0.020 A 3750 0.040 A 1500 0.100 A
200 V 6800 0.029 A 5000 0.040 A 2000 0.100 A
Table 28: 5 A input with minimum operating down to 100 mA
Operating
voltage
Stabilizing
resistor R1
ohms
Operating
current level
5 A
Stabilizing
resistor R1
ohms
Operating
current level
5 A
Stabilizing
resistor R1
ohms
Operating
current level
5 A
20 V 200 0.100 A 100 0.200 A -- --
40 V 400 0.100 A 200 0.200 A 100 0.400
60 V 600 0.100 A 300 0.200 A 150 0.400 A
80 V 800 0.100 A 400 0.200 A 800 0.100 A
100 V 1000 0.100 A 500 0.200 A 1000 0.100 A
150 V 1500 0.100 A 750 0.200 A 1500 0.100 A
200 V 2000 0.100 A 1000 0.200 A 2000 0.100 A
The current transformer saturating voltage must be at least 2 U>Trip to have
sufficient operating margin. This must be checked after calculation of U>Trip.
When the R value has been selected and the U>Trip value has been set, the
sensitivity of the scheme IP can be calculated. The IED sensitivity is decided by
the total current in the circuit according to equation 26.
( ) IP n IR Ires lmag = + +
2
nd
and 5
th
harmonic analysis
Internal/external fault discriminator
General settings
IBase set in primary Amp
A common IBase shall be set for the protected line (circuit). Most current settings
for the protection function are then related to the IBase. The setting of IBase is
normally made such that it corresponds to the maximum rated CT in any of the line
terminals.
NoOfTerminals
NoOfTerminals indicate to the function the number of three-phase CT sets included
in the protected circuit. Note that one IED can process one or two current
terminals of the protected circuit. This is, for example, the case in 1 breaker
configurations there in the line bay, each of the two CT sets will be represented as
one current terminal. A protected line with 1 breaker configurations at each line
end may consequently have NoOfTerminals = 4.
Current terminals
IEC09000973-1-en.vsd
RED
670
RED
670
IEC09000973 V1 EN
Figure 42: Example when setting NoOfTerminals = 4 in 1 breaker
configurations
Chan2IsLocal
Ch2IsLocal is a Boolean setting. The alternative values are No or Yes. This is
related to the analogue current inputs. There are maximum six current inputs, of
Section 3 1MRK505186-UEN D
IED application
110
Application manual
which four can be from the remote substations. The first local current is always
connected to input channel 1. If there is one more local current, which will be the
case for example, in a 1 breaker bay, then the second local current is connected to
input channel 2. The information whether a second local current source exists, is
needed for the directional evaluation made by the internal/external fault
discriminator. In case of a second local current, this evaluation is made by
comparing the direction of the local negative sequence current, one at a time, with
the sum of all the rest of the negative sequence currents.
Percentage restrained differential operation
Line differential protection is phase segregated where the operate current is the
vector sum of all measured currents taken separately for each phase. The restrain
current, on the other hand, is considered as the greatest phase current in any line
end and it is common for all three phases.
Operation: Line differential protection function is switched on or off with this setting.
The characteristic of the restrained differential function is shown in figure 43. The
restrained characteristic is defined by the settings:
1. IdMin
2. EndSection1
3. EndSection2
4. SlopeSection2
5. SlopeSection3
1MRK505186-UEN D Section 3
IED application
111
Application manual
Section 1
UnrestrainedLimit
Section 2 Section 3
Restrain
Operate
unconditionally
5
4
3
2
1
0
0 1 2 3 4 5
IdMin
EndSection1
EndSection2
Restrain current
[ in pu of IBase]
Operate current
[ in pu of IBase]
SlopeSection2
SlopeSection3
en05000300.vsd
Operate
conditionally
IdMinHigh
A
C
B
IEC05000300 V1 EN
Figure 43: Restrained differential function characteristic
where:
100%
Ioperate
slope
Irestrain
D
=
D
EQUATION1246 V1 EN
Line differential protection is phase segregated where the operate current is the
vector sum of all measured currents taken separately for each phase. The restrain
current, on the other hand, is considered as the greatest phase current in any line
end and it is common for all three phases.
IdMin IBase
This setting must take into account the fundamental frequency line charging
current, and whether a power transformer is included in the protected zone or not.
The positive sequence line charging current is calculated according to equation 34.
Section 3 1MRK505186-UEN D
IED application
112
Application manual
arg
1
1
1
2
3
3
Ch e
U U
I
XC
f C p
=
= = = =
EQUATION1424 V1 EN (Equation 45)
8 The cross-block logic shall always be active when there is a power transformer in the protected
zone.
Section 3 1MRK505186-UEN D
IED application
126
Application manual
3.5.2.3 Setting parameters
Table 32: L3CPDIF Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off / On
IdMin 0.20 - 2.00 IB 0.01 0.30 Oper - restr charact., section 1
sensitivity, multiple IBase
IdMinHigh 0.20 - 10.00 IB 0.01 0.80 Initial lower sensitivity, as multiple of
IBase
tIdMinHigh 0.000 - 60.000 s 0.001 1.000 Time interval of initial lower sensitivity, in
sec
IdUnre 1.00 - 50.00 IB 0.01 10.00 Unrestrained differential current limit,
multiple of IBase
NegSeqDiffEn Off
On
- - On Off/On selection for internal / external
fault discriminator
NegSeqROA 30.0 - 120.0 Deg 1.0 60.0 Internal/external fault discriminator
Operate Angle, degrees
IMinNegSeq 0.01 - 0.20 IB 0.01 0.04 Min. value of neg. seq. curr. as multiple
of IBase
CrossBlockEn No
Yes
- - No Off/On selection of the cross -block logic
ChargCurEnable Off
On
- - Off Off/On selection for compensation of
charging currents
AddDelay Off
On
- - Off Off/On selection for delayed diff. trip
command
IMaxAddDelay 0.20 - 5.00 IB 0.01 1.00 Below limit, extra delay can be applied,
multiple of IBase
tDefTime 0.000 - 6.000 s 0.001 0.000 Definite time additional delay in seconds
tMinInv 0.001 - 6.000 s 0.001 0.010 Inverse Delay Minimum Time. In seconds
CurveType ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Programmable
RI type
RD type
- - IEC Def. Time 19 curve types. Example: 15 for definite
time delay.
k 0.05 - 1.10 - 0.01 1.00 Time Multiplier Setting (TMS) for inverse
delays
IdiffAlarm 0.05 - 1.00 IB 0.01 0.15 Sustained differential current alarm,
factor of IBase
tAlarmdelay 0.000 - 60.000 s 0.001 10.000 Delay for alarm due to sustained
differential current, in s
1MRK505186-UEN D Section 3
IED application
127
Application manual
Table 33: L3CPDIF Group settings (advanced)
Name Values (Range) Unit Step Default Description
EndSection1 0.20 - 1.50 IB 0.01 1.25 End of section 1, as multiple of reference
current IBase
EndSection2 1.00 - 10.00 IB 0.01 3.00 End of section 2, as multiple of reference
current IBase
SlopeSection2 10.0 - 50.0 % 0.1 40.0 Slope in section 2 of operate-restrain
characteristic, in %
SlopeSection3 30.0 - 100.0 % 0.1 80.0 Slope in section 3 of operate- restrain
characteristic, in %
I2/I1Ratio 5.0 - 100.0 % 1.0 10.0 Max. ratio of 2nd harm. to fundamental
harm dif. curr. in %
I5/I1Ratio 5.0 - 100.0 % 1.0 25.0 Max. ratio of 5th harm. to fundamental
harm dif. curr. in %
p 0.01 - 1000.00 - 0.01 0.02 Settable curve parameter, user-
programmable curve type.
a 0.01 - 1000.00 - 0.01 0.14 Settable curve parameter, user-
programmable curve type.
b 0.01 - 1000.00 - 0.01 1.00 Settable curve parameter, user-
programmable curve type.
c 0.01 - 1000.00 - 0.01 1.00 Settable curve parameter, user-
programmable curve type.
OpenCTEnable Off
On
- - On Open CTEnable Off/On
tOCTAlarmDelay 0.100 - 10.000 s 0.001 1.000 Open CT: time in s to alarm after an
open CT is detected
tOCTResetDelay 0.100 - 10.000 s 0.001 0.250 Reset delay in s. After delay, diff.
function is activated
Table 34: L3CPDIF Non group settings (basic)
Name Values (Range) Unit Step Default Description
NoOfTerminals 2
3
- - 2 Number of current terminals of the
protected circuit
Chan2IsLocal No
Yes
- - No 2-nd local current connected to input
channel 2, Yes/ No
IBase 50.0 - 9999.9 A 0.1 3000.0 Base (reference) current of the
differential protection
Table 35: L6CPDIF Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off / On
IdMin 0.20 - 2.00 IB 0.01 0.30 Oper - restr charact., section 1
sensitivity, multiple IBase
IdMinHigh 0.20 - 10.00 IB 0.01 0.80 Initial lower sensitivity, as multiple of
IBase
Table continues on next page
Section 3 1MRK505186-UEN D
IED application
128
Application manual
Name Values (Range) Unit Step Default Description
tIdMinHigh 0.000 - 60.000 s 0.001 1.000 Time interval of initial lower sensitivity, in
sec
IdUnre 1.00 - 50.00 IB 0.01 10.00 Unrestrained differential current limit,
multiple of IBase
NegSeqDiffEn Off
On
- - On Off/On selection for internal / external
fault discriminator
NegSeqROA 30.0 - 120.0 Deg 1.0 60.0 Internal/external fault discriminator
Operate Angle, degrees
IMinNegSeq 0.01 - 0.20 IB 0.01 0.04 Min. value of neg. seq. curr. as multiple
of IBase
CrossBlockEn No
Yes
- - No Off/On selection of the cross -block logic
I2/I1Ratio 5.0 - 100.0 % 1.0 10.0 Max. ratio of 2nd harm. to fundamental
harm dif. curr. in %
I5/I1Ratio 5.0 - 100.0 % 1.0 25.0 Max. ratio of 5th harm. to fundamental
harm dif. curr. in %
ChargCurEnable Off
On
- - Off Off/On selection for compensation of
charging currents
AddDelay Off
On
- - Off Off/On selection for delayed diff. trip
command
IMaxAddDelay 0.20 - 5.00 IB 0.01 1.00 Below limit, extra delay can be applied,
multiple of IBase
tDefTime 0.000 - 6.000 s 0.001 0.000 Definite time additional delay in seconds
tMinInv 0.001 - 6.000 s 0.001 0.010 Inverse Delay Minimum Time. In seconds
CurveType ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Programmable
RI type
RD type
- - IEC Def. Time 19 curve types. Example: 15 for definite
time delay.
k 0.05 - 1.10 - 0.01 1.00 Time Multiplier Setting (TMS) for inverse
delays
IdiffAlarm 0.05 - 1.00 IB 0.01 0.15 Sustained differential current alarm,
factor of IBase
tAlarmdelay 0.000 - 60.000 s 0.001 10.000 Delay for alarm due to sustained
differential current, in s
1MRK505186-UEN D Section 3
IED application
129
Application manual
Table 36: L6CPDIF Group settings (advanced)
Name Values (Range) Unit Step Default Description
EndSection1 0.20 - 1.50 IB 0.01 1.25 End of section 1, as multiple of reference
current IBase
EndSection2 1.00 - 10.00 IB 0.01 3.00 End of section 2, as multiple of reference
current IBase
SlopeSection2 10.0 - 50.0 % 0.1 40.0 Slope in section 2 of operate-restrain
characteristic, in %
SlopeSection3 30.0 - 100.0 % 0.1 80.0 Slope in section 3 of operate- restrain
characteristic, in %
p 0.01 - 1000.00 - 0.01 0.02 Settable curve parameter, user-
programmable curve type.
a 0.01 - 1000.00 - 0.01 0.14 Settable curve parameter, user-
programmable curve type.
b 0.01 - 1000.00 - 0.01 1.00 Settable curve parameter, user-
programmable curve type.
c 0.01 - 1000.00 - 0.01 1.00 Settable curve parameter, user-
programmable curve type.
OpenCTEnable Off
On
- - On Open CT detection feature. Open
CTEnable Off/On
tOCTAlarmDelay 0.100 - 10.000 s 0.001 1.000 Open CT: time in s to alarm after an
open CT is detected
tOCTResetDelay 0.100 - 10.000 s 0.001 0.250 Reset delay in s. After delay, diff.
function is activated
Table 37: L6CPDIF Non group settings (basic)
Name Values (Range) Unit Step Default Description
NoOfTerminals 2
3
4
5
6
- - 2 Number of current terminals of the
protected circuit
Chan2IsLocal No
Yes
- - No 2-nd local current connected to input
channel 2, Yes/ No
IBase 50.0 - 9999.9 A 0.1 3000.0 Base (reference) current of the
differential protection
Table 38: LT3CPDIF Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off / On
IdMin 0.20 - 2.00 IB 0.01 0.30 Oper - restr charact., section 1
sensitivity, multiple IBase
IdMinHigh 0.20 - 10.00 IB 0.01 0.80 Initial lower sensitivity, as multiple of
IBase
tIdMinHigh 0.000 - 60.000 s 0.001 1.000 Time interval of initial lower sensitivity, in
sec
Table continues on next page
Section 3 1MRK505186-UEN D
IED application
130
Application manual
Name Values (Range) Unit Step Default Description
IdUnre 1.00 - 50.00 IB 0.01 10.00 Unrestrained differential current limit,
multiple of IBase
NegSeqDiffEn Off
On
- - On Off/On selection for internal / external
fault discriminator
NegSeqROA 30.0 - 120.0 Deg 1.0 60.0 Internal/external fault discriminator
Operate Angle, degrees
IMinNegSeq 0.01 - 0.20 IB 0.01 0.04 Min. value of neg. seq. curr. as multiple
of IBase
CrossBlockEn No
Yes
- - No Off/On selection of the cross -block logic
ChargCurEnable Off
On
- - Off Off/On selection for compensation of
charging currents
AddDelay Off
On
- - Off Off/On selection for delayed diff. trip
command
IMaxAddDelay 0.20 - 5.00 IB 0.01 1.00 Below limit, extra delay can be applied,
multiple of IBase
tDefTime 0.000 - 6.000 s 0.001 0.000 Definite time additional delay in seconds
tMinInv 0.001 - 6.000 s 0.001 0.010 Inverse Delay Minimum Time. In seconds
CurveType ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Programmable
RI type
RD type
- - IEC Def. Time 19 curve types. Example: 15 for definite
time delay.
k 0.05 - 1.10 - 0.01 1.00 Time Multiplier Setting (TMS) for inverse
delays
IdiffAlarm 0.05 - 1.00 IB 0.01 0.15 Sustained differential current alarm,
factor of IBase
tAlarmdelay 0.000 - 60.000 s 0.001 10.000 Delay for alarm due to sustained
differential current, in s
Table 39: LT3CPDIF Group settings (advanced)
Name Values (Range) Unit Step Default Description
EndSection1 0.20 - 1.50 IB 0.01 1.25 End of section 1, as multiple of reference
current IBase
EndSection2 1.00 - 10.00 IB 0.01 3.00 End of section 2, as multiple of reference
current IBase
SlopeSection2 10.0 - 50.0 % 0.1 40.0 Slope in section 2 of operate-restrain
characteristic, in %
Table continues on next page
1MRK505186-UEN D Section 3
IED application
131
Application manual
Name Values (Range) Unit Step Default Description
SlopeSection3 30.0 - 100.0 % 0.1 80.0 Slope in section 3 of operate- restrain
characteristic, in %
I2/I1Ratio 5.0 - 100.0 % 1.0 10.0 Max. ratio of 2nd harm. to fundamental
harm dif. curr. in %
I5/I1Ratio 5.0 - 100.0 % 1.0 25.0 Max. ratio of 5th harm. to fundamental
harm dif. curr. in %
p 0.01 - 1000.00 - 0.01 0.02 Settable curve parameter, user-
programmable curve type.
a 0.01 - 1000.00 - 0.01 0.14 Settable curve parameter, user-
programmable curve type.
b 0.01 - 1000.00 - 0.01 1.00 Settable curve parameter, user-
programmable curve type.
c 0.01 - 1000.00 - 0.01 1.00 Settable curve parameter, user-
programmable curve type.
OpenCTEnable Off
On
- - On Open CT detection feature. Open
CTEnable Off/On
tOCTAlarmDelay 0.100 - 10.000 s 0.001 1.000 Open CT: time in s to alarm after an
open CT is detected
tOCTResetDelay 0.100 - 10.000 s 0.001 0.250 Reset delay in s. After delay, diff.
function is activated
Table 40: LT3CPDIF Non group settings (basic)
Name Values (Range) Unit Step Default Description
NoOfTerminals 2
3
- - 2 Number of current terminals of the
protected circuit
Chan2IsLocal No
Yes
- - No 2-nd local current connected to input
channel 2, Yes/ No
IBase 50.0 - 9999.9 A 0.1 3000.0 Base (reference) current of the
differential protection
ZerSeqCurSubtr Off
On
- - Off Off/On for elimination of zero seq. from
diff. and bias curr
TraAOnInpCh No Transf A
1
2
3
- - No Transf A Power transformer A applied on input
channel X
RatVoltW1TraA 1.0 - 9999.9 kV 0.1 130.0 Transformer A rated voltage (kV) on
winding 1 (HV winding)
RatVoltW2TraA 1.0 - 9999.9 kV 0.1 130.0 Transformer A rated voltage (kV) on
winding 2 (LV winding)
ClockNumTransA 0 [0 deg]
1 [30 deg lag]
2 [60 deg lag]
3 [90 deg lag]
4 [120 deg lag]
5 [150 deg lag]
6 [180 deg lag]
7 [210 deg lag]
8 [240 deg lag]
9 [270 deg lag]
10 [300 deg lag]
11 [330 deg lag]
- - 0 [0 deg] Transf. A phase shift in multiples of 30
deg, 5 for 150 deg
Table continues on next page
Section 3 1MRK505186-UEN D
IED application
132
Application manual
Name Values (Range) Unit Step Default Description
ZerSeqPassTraA No
Yes
- - No Yes/No for capability of transf A to
transform zero seq curr
TraBOnInpCh No Transf B
1
2
3
- - No Transf B Power transformer B applied on input
channel X
RatVoltW1TraB 1.0 - 9999.9 kV 0.1 130.0 Transformer B rated voltage (kV) on
winding 1 (HV winding)
RatVoltW2TraB 1.0 - 9999.9 kV 0.1 130.0 Transformer B rated voltage (kV) on
winding 2 (LV winding)
ClockNumTransB 0 [0 deg]
1 [30 deg lag]
2 [60 deg lag]
3 [90 deg lag]
4 [120 deg lag]
5 [150 deg lag]
6 [180 deg lag]
7 [210 deg lag]
8 [240 deg lag]
9 [270 deg lag]
10 [300 deg lag]
11 [330 deg lag]
- - 0 [0 deg] Transf. B phase shift in multiples of 30
deg, 2 for 60 deg
ZerSeqPassTraB No
Yes
- - No Yes/No for capability of transf B to
transform zero seq curr
Table 41: LT6CPDIF Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off / On
IdMin 0.20 - 2.00 IB 0.01 0.30 Oper - restr charact., section 1
sensitivity, multiple IBase
IdMinHigh 0.20 - 10.00 IB 0.01 0.80 Initial lower sensitivity, as multiple of
IBase
tIdMinHigh 0.000 - 60.000 s 0.001 1.000 Time interval of initial lower sensitivity, in
sec
IdUnre 1.00 - 50.00 IB 0.01 10.00 Unrestrained differential current limit,
multiple of IBase
NegSeqDiffEn Off
On
- - On Off/On selection for internal / external
fault discriminator
NegSeqROA 30.0 - 120.0 Deg 1.0 60.0 Internal/external fault discriminator
Operate Angle, degrees
IMinNegSeq 0.01 - 0.20 IB 0.01 0.04 Min. value of neg. seq. curr. as multiple
of IBase
CrossBlockEn No
Yes
- - No Off/On selection of the cross -block logic
I2/I1Ratio 5.0 - 100.0 % 1.0 10.0 Max. ratio of 2nd harm. to fundamental
harm dif. curr. in %
I5/I1Ratio 5.0 - 100.0 % 1.0 25.0 Max. ratio of 5th harm. to fundamental
harm dif. curr. in %
ChargCurEnable Off
On
- - Off Off/On selection for compensation of
charging currents
Table continues on next page
1MRK505186-UEN D Section 3
IED application
133
Application manual
Name Values (Range) Unit Step Default Description
AddDelay Off
On
- - Off On/Off selection for delayed diff. trip
command
IMaxAddDelay 0.20 - 5.00 IB 0.01 1.00 Below limit, extra delay can be applied,
multiple of IBase
tDefTime 0.000 - 6.000 s 0.001 0.000 Definite time additional delay in seconds
tMinInv 0.001 - 6.000 s 0.001 0.010 Inverse Delay Minimum Time. In seconds
CurveType ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Programmable
RI type
RD type
- - IEC Def. Time 19 curve types. Example: 15 for definite
time delay.
k 0.05 - 1.10 - 0.01 1.00 Time Multiplier Setting (TMS) for inverse
delays
IdiffAlarm 0.05 - 1.00 IB 0.01 0.15 Sustained differential current alarm,
factor of IBase
tAlarmdelay 0.000 - 60.000 s 0.001 10.000 Delay for alarm due to sustained
differential current, in s
Table 42: LT6CPDIF Group settings (advanced)
Name Values (Range) Unit Step Default Description
EndSection1 0.20 - 1.50 IB 0.01 1.25 End of section 1, as multiple of reference
current IBase
EndSection2 1.00 - 10.00 IB 0.01 3.00 End of section 2, as multiple of reference
current IBase
SlopeSection2 10.0 - 50.0 % 0.1 40.0 Slope in section 2 of operate-restrain
characteristic, in %
SlopeSection3 30.0 - 100.0 % 0.1 80.0 Slope in section 3 of operate- restrain
characteristic, in %
p 0.01 - 1000.00 - 0.01 0.02 Settable curve parameter, user-
programmable curve type.
a 0.01 - 1000.00 - 0.01 0.14 Settable curve parameter, user-
programmable curve type.
b 0.01 - 1000.00 - 0.01 1.00 Settable curve parameter, user-
programmable curve type.
c 0.01 - 1000.00 - 0.01 1.00 Settable curve parameter, user-
programmable curve type.
Table continues on next page
Section 3 1MRK505186-UEN D
IED application
134
Application manual
Name Values (Range) Unit Step Default Description
OpenCTEnable Off
On
- - On Open CTEnable Off/On
tOCTAlarmDelay 0.100 - 10.000 s 0.001 1.000 Open CT: time in s to alarm after an
open CT is detected
tOCTResetDelay 0.100 - 10.000 s 0.001 0.250 Reset delay in s. After delay, diff.
function is activated
Table 43: LT6CPDIF Non group settings (basic)
Name Values (Range) Unit Step Default Description
NoOfTerminals 2
3
4
5
6
- - 2 Number of current terminals of the
protected circuit
Chan2IsLocal No
Yes
- - No 2-nd local current connected to input
channel 2, Yes/ No
IBase 50.0 - 9999.9 A 0.1 3000.0 Base (reference) current of the
differential protection
ZerSeqCurSubtr Off
On
- - Off Off/On for elimination of zero seq. from
diff. and bias curr
TraAOnInpCh No Transf A
1
2
3
4
5
6
- - No Transf A Power transformer A applied on input
channel X
RatVoltW1TraA 1.0 - 9999.9 kV 0.1 130.0 Transformer A rated voltage (kV) on
winding 1 (HV winding)
RatVoltW2TraA 1.0 - 9999.9 kV 0.1 130.0 Transformer A rated voltage (kV) on
winding 2 (LV winding)
ClockNumTransA 0 [0 deg]
1 [30 deg lag]
2 [60 deg lag]
3 [90 deg lag]
4 [120 deg lag]
5 [150 deg lag]
6 [180 deg lag]
7 [210 deg lag]
8 [240 deg lag]
9 [270 deg lag]
10 [300 deg lag]
11 [330 deg lag]
- - 0 [0 deg] Transf. A phase shift in multiples of 30
deg, 5 for 150 deg
ZerSeqPassTraA No
Yes
- - No Yes/No for capability of transf A to
transform zero seq curr
TraBOnInpCh No Transf B
1
2
3
4
5
6
- - No Transf B Power transformer B applied on input
channel X
Table continues on next page
1MRK505186-UEN D Section 3
IED application
135
Application manual
Name Values (Range) Unit Step Default Description
RatVoltW1TraB 1.0 - 9999.9 kV 0.1 130.0 Transformer B rated voltage (kV) on
winding 1 (HV winding)
RatVoltW2TraB 1.0 - 9999.9 kV 0.1 130.0 Transformer B rated voltage (kV) on
winding 2 (LV winding)
ClockNumTransB 0 [0 deg]
1 [30 deg lag]
2 [60 deg lag]
3 [90 deg lag]
4 [120 deg lag]
5 [150 deg lag]
6 [180 deg lag]
7 [210 deg lag]
8 [240 deg lag]
9 [270 deg lag]
10 [300 deg lag]
11 [330 deg lag]
- - 0 [0 deg] Transf. B phase shift in multiples of 30
deg, 2 for 60 deg
ZerSeqPassTraB No
Yes
- - No Yes/No for capability of transf B to
transform zero seq curr
Table 44: LDLPDIF Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - On Operation Off / On
testModeSet Off
On
- - Off Test mode On/Off
ReleaseLocal Block all
Release local
- - Block all Release of local terminal for trip under
test mode
3.6 Impedance protection
3.6.1 Distance measuring zones, quadrilateral characteristic
ZMQPDIS, ZMQAPDIS, ZDRDIR
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Distance protection zone, quadrilateral
characteristic (zone 1)
ZMQPDIS
S00346 V1 EN
21
Distance protection zone, quadrilateral
characteristic (zone 2-5)
ZMQAPDIS
S00346 V1 EN
21
Directional impedance quadrilateral ZDRDIR
Z<->
IEC09000167 V1 EN
21D
Section 3 1MRK505186-UEN D
IED application
136
Application manual
3.6.1.1 Application
Sub-transmission networks are being extended and often become more and more
complex, consisting of a high number of multi-circuit and/or multi terminal lines of
very different lengths. These changes in the network will normally impose more
stringent demands on the fault clearing equipment in order to maintain an
unchanged or increased security level of the power system.
The distance protection function in the IED is designed to meet basic requirements
for application on transmission and sub-transmission lines (solid earthed systems)
although it also can be used on distribution levels.
System earthing
The type of system earthing plays an important role when designing the protection
system. Some hints with respect to distance protection are highlighted below.
Solid earthed networks
In solidly earthed systems, the transformer neutrals are connected solidly to earth
without any impedance between the transformer neutral and earth.
xx05000215.vsd
IEC05000215 V1 EN
Figure 51: Solidly earthed network
The earth-fault current is as high or even higher than the short-circuit current. The
series impedances determine the magnitude of the fault current. The shunt
admittance has very limited influence on the earth-fault current. The shunt
admittance may, however, have some marginal influence on the earth-fault current
in networks with long transmission lines.
The earth-fault current at single phase-to-earth in phase L1 can be calculated as
equation 46:
L1 L1
0
1 2 0 f 1 N f
3 U U
3I
Z Z Z 3Z Z Z Z
= =
+ + + + +
EQUATION1267 V3 EN (Equation 46)
Where:
U
L1
is the phase-to-earth voltage (kV) in the faulty phase before fault
Z
1
is the positive sequence impedance (/phase)
Z
2
is the negative sequence impedance (/phase)
Table continues on next page
1MRK505186-UEN D Section 3
IED application
137
Application manual
Z
0
is the zero sequence impedance (/phase)
Z
f
is the fault impedance (), often resistive
Z
N
is the earth-return impedance defined as (Z
0
-Z
1
)/3
The voltage on the healthy phases is generally lower than 140% of the nominal phase-
to-earth voltage. This corresponds to about 80% of the nominal phase-to-phase
voltage.
The high zero-sequence current in solid earthed networks makes it possible to use
impedance measuring techniques to detect earth faults. However, distance
protection has limited possibilities to detect high resistance faults and should
therefore always be complemented with other protection function(s) that can carry
out the fault clearance in those cases.
Effectively earthed networks
A network is defined as effectively earthed if the earth-fault factor f
e
is less than
1.4. The earth-fault factor is defined according to equation 47.
max
e
pn
U
f
U
=
EQUATION1268 V3 EN (Equation 47)
Where:
U
max
is the highest fundamental frequency voltage on one of the healthy phases at single phase-
to-earth fault.
U
pn
is the phase-to-earth fundamental frequency voltage before fault.
Another definition for effectively earthed network is when the following
relationships between the symmetrical components of the network impedances are
valid, see equation 48 and equation 49.
0 1
X 3 X <
EQUATION2122 V1 EN (Equation 48)
0 1
R R
EQUATION2123 V1 EN (Equation 49)
Where
R
0
is setting of the resistive zero sequence reach
X
0
is setting of the reactive zero sequence reach
R
1
is setting of the resistive positive sequence reach
X
1
is setting of the reactive positive sequence reach
Section 3 1MRK505186-UEN D
IED application
138
Application manual
The magnitude of the earth-fault current in effectively earthed networks is high
enough for impedance measuring elements to detect earth faults. However, in the
same way as for solid earthed networks, distance protection has limited
possibilities to detect high resistance faults and should therefore always be
complemented with other protection function(s) that can carry out the fault
clearance in this case.
High impedance earthed networks
In high impedance networks, the neutral of the system transformers are connected
to the earth through high impedance, mostly a reactance in parallel with a high resistor.
This type of network is many times operated in radial, but can also be found
operating meshed networks.
What is typical for this type of network is that the magnitude of the earth-fault
current is very low compared to the short circuit current. The voltage on the
healthy phases will get a magnitude of 3 times the phase voltage during the fault.
The zero sequence voltage (3U
0
) will have the same magnitude in different places
in the network due to low voltage drop distribution.
The magnitude of the total fault current can be calculated according to equation 50.
( )
2
2
R L C
0
3I I I I = + -
EQUATION1271 V3 EN (Equation 50)
Where:
3I
0
is the earth-fault current (A)
IR is the current through the neutral point resistor (A)
IL is the current through the neutral point reactor (A)
IC is the total capacitive earth-fault current (A)
The neutral point reactor is normally designed so that it can be tuned to a position
where the reactive current balances the capacitive current from the network that is:
1
3
L
C
w
w
=
EQUATION1272 V1 EN (Equation 51)
1MRK505186-UEN D Section 3
IED application
139
Application manual
Ic Ic Ic
IL IR
en05000216.vsd
IEC05000216 V1 EN
Figure 52: High impedance earthing network
The operation of high impedance earthed networks is different compared to solid
earthed networks where all major faults have to be cleared very fast. In high
impedance earthed networks, some system operators do not clear single phase-to-
earth faults immediately; they clear the line later when it is more convenient. In
case of cross-country faults, many network operators want to selectively clear one
of the two earth faults. To handle this type phenomenon, a separate function called
Phase preference logic (PPLPHIZ) is needed, which is not common to be used in
transmission applications.
In this type of network, it is mostly not possible to use distance protection for
detection and clearance of earth faults. The low magnitude of the earth-fault
current might not give start of the zero-sequence measurement elements or the
sensitivity will be too low for acceptance. For this reason a separate high sensitive
earth-fault protection is necessary to carry out the fault clearance for single phase-to-
earth fault.
Fault infeed from remote end
All transmission and most all sub-transmission networks are operated meshed.
Typical for this type of network is that fault infeed from remote end will happen
when fault occurs on the protected line. The fault current infeed will enlarge the
fault impedance seen by the distance protection. This effect is very important to
keep in mind when both planning the protection system and making the settings.
With reference to figure 53, the equation for the bus voltage U
A
at A side is:
UA = IA p ZL + (IA+IB) Rf
EQUATION1273-IEC-650 V1 EN (Equation 52)
If we divide U
A
by I
A
we get Z present to the IED at A side.
IA + IB
UA
IA IA
ZA = = p ZL + Rf
EQUATION1274-IEC-650 V1 EN (Equation 53)
Section 3 1MRK505186-UEN D
IED application
140
Application manual
The infeed factor (I
A
+I
B
)/I
A
can be very high, 10-20 depending on the differences
in source impedances at local and remote end.
Z <
ZL
Z <
E
SA
U
A
U
B
A B
E
SB
I
A
I
B
R
f
p*ZL (1-p)*ZL
Z
SA
Z
SB
IEC09000247-1-en.vsd
IEC09000247 V1 EN
Figure 53: Influence of fault current infeed from remote line end
The effect of fault current infeed from remote line end is one of the most driving
factors for justify complementary protection to distance protection.
When the line is heavily loaded, the distance protection at the exporting end will
have a tendency to overreach. To handle this phenomenon, the IED has an adaptive
built-in algorithm, which compensates the overreach tendency of zone 1, at the
exporting end. No settings are required for this function.
Load encroachment
In some cases the load impedance might enter the zone characteristic without any
fault on the protected line. The phenomenon is called load encroachment and it
might occur when an external fault is cleared and high emergency load is
transferred on the protected line. The effect of load encroachment is illustrated to
the left in figure 54. The entrance of the load impedance inside the characteristic is
of course not allowed and the way to handle this with conventional distance
protection is to consider this with the settings, that is, to have a security margin
between the distance zone and the minimum load impedance. This has the
drawback that it will reduce the sensitivity of the protection, that is, the ability to
detect resistive faults.
The IED has a built in function which shapes the characteristic according to the
right figure of figure 54. The load encroachment algorithm will increase the
possibility to detect high fault resistances, especially for phase-to-earth faults at
remote line end. For example, for a given setting of the load angle ArgLd for Phase
selection with load encroachment, quadrilateral characteristic function
(FDPSPDIS), the resistive blinder for the zone measurement can be expanded
according to the figure 54 given higher fault resistance coverage without risk for
unwanted operation due to load encroachment. This is valid in both directions.
The use of the load encroachment feature is essential for long heavy loaded lines,
where there might be a conflict between the necessary emergency load transfer and
necessary sensitivity of the distance protection. The function can also preferably be
1MRK505186-UEN D Section 3
IED application
141
Application manual
used on heavy loaded medium long lines. For short lines, the major concern is to
get sufficient fault resistance coverage and load encroachment is not a major
problem. So, for short lines, the load encroachment function could preferably be
switched off. See section "Load impedance limitation, without load encroachment
function".
The settings of the parameters for load encroachment are done in FDPSPDIS function.
R
X
Z1
Load impedance
area in forward
direction
RLdRv
R
Z1
ArgLd
ArgLd
ArgLd
ArgLd
RLdFw
IEC09000248_1_en.vsd
X
IEC09000248 V1 EN
Figure 54: Load encroachment phenomena and shaped load encroachment
characteristic defined in Phase selection with load encroachment
function FDPSPDIS
Short line application
In short line applications, the major concern is to get sufficient fault resistance
coverage. Load encroachment is not so common. The line length that can be
recognized as a short line is not a fixed length; it depends on system parameters
such as voltage and source impedance, see table 45.
Table 45: Definition of short and very short line
Line category
Un Un
110 kV 500 kV
Very short line 1.1-5.5 km 5-25 km
Short line 5.5-11 km 25-50 km
The IED's ability to set resistive and reactive reach independent for positive and
zero sequence fault loops and individual fault resistance settings for phase-to-phase
and phase-to-earth fault together with load encroachment algorithm improves the
possibility to detect high resistive faults without conflict with the load impedance,
see figure 54.
Section 3 1MRK505186-UEN D
IED application
142
Application manual
For very short line applications, the underreaching zone 1 can not be used due to
the voltage drop distribution throughout the line will be too low causing risk for
overreaching.
Load encroachment is normally no problem for short line applications.
Long transmission line application
For long transmission lines, the margin to the load impedance, that is, to avoid load
encroachment, will normally be a major concern. It is well known that it is difficult
to achieve high sensitivity for phase-to-earth fault at remote line end of long lines
when the line is heavy loaded.
What can be recognized as long lines with respect to the performance of distance
protection can generally be described as in table 46, long lines have Source
impedance ratio (SIRs) less than 0.5.
Table 46: Definition of long and very long lines
Line category
Un Un
110 kV 500 kV
Long lines 77 km - 99 km 350 km - 450 km
Very long lines > 99 km > 450 km
The IED's ability to set resistive and reactive reach independent for positive and
zero sequence fault loops and individual fault resistance settings for phase-to-phase
and phase-to-earth fault together with load encroachment algorithm improves the
possibility to detect high resistive faults at the same time as the security is
improved (risk for unwanted trip due to load encroachment is eliminated), see
figure 54.
Parallel line application with mutual coupling
General
Introduction of parallel lines in the network is increasing due to difficulties to get
necessary area for new lines.
Parallel lines introduce an error in the measurement due to the mutual coupling
between the parallel lines. The lines need not be of the same voltage in order to
experience mutual coupling, and some coupling exists even for lines that are
separated by 100 meters or more. The mutual coupling does influence the zero
sequence impedance to the fault point but it does not normally cause voltage
inversion.
It can be shown from analytical calculations of line impedances that the mutual
impedances for positive and negative sequence are very small (< 1-2%) of the self
impedance and it is a practice to neglect them.
From an application point of view there exists three types of network
configurations (classes) that must be considered when making the settings for the
protection function.
1MRK505186-UEN D Section 3
IED application
143
Application manual
The different network configuration classes are:
1. Parallel line with common positive and zero sequence network
2. Parallel circuits with common positive but isolated zero sequence network
3. Parallel circuits with positive and zero sequence sources isolated.
One example of class 3 networks could be the mutual coupling between a 400kV
line and rail road overhead lines. This type of mutual coupling is not so common
although it exists and is not treated any further in this manual.
For each type of network class, there are three different topologies; the parallel line
can be in service, out of service, out of service and earthed in both ends.
The reach of the distance protection zone 1 will be different depending on the
operation condition of the parallel line. This can be handled by the use of different
setting groups for handling the cases when the parallel line is in operation and out
of service and earthed at both ends.
The distance protection within the IED can compensate for the influence of a zero
sequence mutual coupling on the measurement at single phase-to-earth faults in the
following ways, by using:
The possibility of different setting values that influence the earth-return
compensation for different distance zones within the same group of setting
parameters.
Different groups of setting parameters for different operating conditions of a
protected multi circuit line.
Most multi circuit lines have two parallel operating circuits.
Parallel line applications
This type of networks is defined as those networks where the parallel transmission
lines terminate at common nodes at both ends.
The three most common operation modes are:
1. Parallel line in service.
2. Parallel line out of service and earthed.
3. Parallel line out of service and not earthed.
Parallel line in service
This type of application is very common and applies to all normal sub-transmission
and transmission networks.
Let us analyze what happens when a fault occurs on the parallel line see figure 55.
From symmetrical components, we can derive the impedance Z at the relay point
for normal lines without mutual coupling according to equation 54.
Section 3 1MRK505186-UEN D
IED application
144
Application manual
ph ph
0 1 ph 0 N
ph 0
1
U U
Z Z I 3I K
I 3I
3 Z
Z = =
- +
+
= + +
-
IECEQUATION1280 V1 EN (Equation 59)
If we finally divide equation 59 with equation 54 we can draw the impedance
present to the IED as
Section 3 1MRK505186-UEN D
IED application
146
Application manual
0
0
3
3 0
2
1
3
m
L
I p
Iph KN I KN
p
Z p Z
Iph I KN
+ +
-
=
+
EQUATION1379 V1 EN (Equation 60)
Calculation for a 400 kV line, where we for simplicity have excluded the
resistance, gives with X1L=0.303 /km, X0L=0.88 /km, zone 1 reach is set to
90% of the line reactance p=71% that is, the protection is underreaching with
approximately 20%.
The zero sequence mutual coupling can reduce the reach of distance protection on
the protected circuit when the parallel line is in normal operation. The reduction of
the reach is most pronounced with no current infeed in the IED closest to the fault.
This reach reduction is normally less than 15%. But when the reach is reduced at
one line end, it is proportionally increased at the opposite line end. So this 15%
reach reduction does not significantly affect the operation of a permissive
underreaching scheme.
Parallel line out of service and earthed
Z
0m
A B
Z< Z<
IEC09000251_1_en.vsd
IEC09000251 V1 EN
Figure 57: The parallel line is out of service and earthed
When the parallel line is out of service and earthed at both line ends on the bus bar
side of the line CTs so that zero sequence current can flow on the parallel line, the
equivalent zero sequence circuit of the parallel lines will be according to figure 58.
A
B
C
IEC09000252_1_en.vsd
I
0
I
0
Z
0m
Z
0
-
Z
0m
Z
0
-
Z
0m
IEC09000252 V1 EN
Figure 58: Equivalent zero sequence impedance circuit for the double-circuit
line that operates with one circuit disconnected and earthed at both
ends
Here the equivalent zero-sequence impedance is equal to Z
0
-Z
0
m in parallel with
(Z
0
-Z
0m
)/Z
0
-Z
0m
+Z
0m
which is equal to equation 61.
1MRK505186-UEN D Section 3
IED application
147
Application manual
2 2
0 m
0E
0
Z Z0
Z
Z
-
=
EQUATION2002 V1 EN (Equation 61)
The influence on the distance measurement will be a considerable overreach, which
must be considered when calculating the settings. It is recommended to use a
separate setting group for this operation condition since it will reduce the reach
considerably when the line is in operation.
All expressions below are proposed for practical use. They assume the value of
zero sequence, mutual resistance R
0m
equals to zero. They consider only the zero
sequence, mutual reactance X
0m
. Calculate the equivalent X
0E
and R
0E
zero
sequence parameters according to equation 62 and equation 63 for each particular
line section and use them for calculating the reach for the underreaching zone.
2
0
0 0 2 2
0 0
1
m
E
X
R R
R X
= +
+
DOCUMENT11520-IMG3502 V1 EN (Equation 62)
2
0
0 0 2 2
0 0
1
m
E
X
X X
R X
= -
+
DOCUMENT11520-IMG3503 V1 EN (Equation 63)
Parallel line out of service and not earthed
Z
0m
A B
Z< Z<
IEC09000254_1_en.vsd
IEC09000254 V1 EN
Figure 59: Parallel line is out of service and not earthed
When the parallel line is out of service and not earthed, the zero sequence on that
line can only flow through the line admittance to the earth. The line admittance is
high which limits the zero-sequence current on the parallel line to very low values.
In practice, the equivalent zero-sequence impedance circuit for faults at the remote
bus bar can be simplified to the circuit shown in figure 59
The line zero sequence mutual impedance does not influence the measurement of
the distance protection in a faulty circuit. This means that the reach of the
underreaching distance protection zone is reduced if, due to operating conditions,
Section 3 1MRK505186-UEN D
IED application
148
Application manual
the equivalent zero sequence impedance is set according to the conditions when the
parallel system is out of operation and earthed at both ends.
A
B
C
IEC09000255_1_en.vsd
I
0
I
0
Z
0m
Z
0
-
Z
0m
Z
0m
Z
0
-
IEC09000255 V1 EN
Figure 60: Equivalent zero-sequence impedance circuit for a double-circuit
line with one circuit disconnected and not earthed
The reduction of the reach is equal to equation 64.
( )
( )
( )
2
1 0
0
1 0
0
1 0
1
2
3
1
1
2 3
2
3
E f
m
U
f
f
Z Z R
Z
K
Z Z Z R
Z Z R
+ +
= = -
+ +
+ +
EQUATION1284 V1 EN (Equation 64)
This means that the reach is reduced in reactive and resistive directions. If the real
and imaginary components of the constant A are equal to equation 65 and
equation 66.
Re( ) 0 (2 1 0 3 ) 0 ( 0 2 1) A R R R Rf X X X = + + - +
EQUATION1285 V1 EN (Equation 65)
0 1 0 1 0 1 0
Im( ) (2 3 ) (2 ) A X R R R R X X = + + + +
EQUATION1286 V1 EN (Equation 66)
The real component of the KU factor is equal to equation 67.
( )
( )
( ) ( )
2
0
2 2
Re
Re 1
Re Im
m
U
A X
K
A A
= +
+
EQUATION1287 V1 EN (Equation 67)
The imaginary component of the same factor is equal to equation 68.
( )
( )
( ) ( )
2
Im
Im
Re
A
K
U
A
=
+
Im A
2
X
m0
2
EQUATION1288 V1 EN (Equation 68)
1MRK505186-UEN D Section 3
IED application
149
Application manual
Ensure that the underreaching zones from both line ends will overlap a sufficient
amount (at least 10%) in the middle of the protected circuit.
Tapped line application
A B
Z< Z<
Z<
C
T
IC
IB
-IB
IEC09000160-2-en.vsd
IA
F
IEC09000160 V2 EN
Figure 61: Example of tapped line with Auto transformer
This application gives rise to similar problem that was highlighted in section
"Fault infeed from remote end" , that is increased measured impedance due to fault
current infeed. For example, for faults between the T point and B station the
measured impedance at A and C will be
ZA =ZAT + ZTF
IA + IC
IA
DOCUMENT11524-IMG3509 V2 EN (Equation 69)
ZC = ZTrf + ( ZCT + ZTF) ( )
2
IA + IC
IC
U2
U1
DOCUMENT11524-IMG3510 V2 EN (Equation 70)
Where:
Z
AT
and Z
CT
is the line impedance from the A respective C station to the T point.
I
A
and I
C
is fault current from A respective C station for fault between T and B.
Table continues on next page
Section 3 1MRK505186-UEN D
IED application
150
Application manual
U2/U1 Transformation ratio for transformation of impedance at U1 side of the transformer to
the measuring side U2 (it is assumed that current and voltage distance function is
taken from U2 side of the transformer).
Z
TF
is the line impedance from the T point to the fault (F).
Z
Trf
Transformer impedance
For this example with a fault between T and B, the measured impedance from the T
point to the fault will be increased by a factor defined as the sum of the currents
from T point to the fault divided by the IED current. For the IED at C, the
impedance on the high voltage side U1 has to be transferred to the measuring
voltage level by the transformer ratio.
Another complication that might occur depending on the topology is that the
current from one end can have a reverse direction for fault on the protected line.
For example, for faults at T the current from B might go in reverse direction from
B to C depending on the system parameters (see the dotted line in figure 61), given
that the distance protection in B to T will measure wrong direction.
In three-end application, depending on the source impedance behind the IEDs, the
impedances of the protected object and the fault location, it might be necessary to
accept zone 2 trip in one end or sequential trip in one end.
Generally for this type of application it is difficult to select settings of zone 1 that
both gives overlapping of the zones with enough sensitivity without interference
with other zone 1 settings, that is, without selectivity conflicts. Careful fault
calculations are necessary to determine suitable settings and selection of proper
scheme communication.
Fault resistance
The performance of distance protection for single phase-to-earth faults is very
important, because normally more than 70% of the faults on transmission lines are
single phase-to-earth faults. At these faults, the fault resistance is composed of
three parts: arc resistance, resistance of a tower construction, and tower-footing
resistance. The arc resistance can be calculated according to Warrington's formula:
1.4
28707 L
Rarc
I
=
EQUATION1456 V1 EN (Equation 71)
where:
L represents the length of the arc (in meters). This equation applies for the distance protection
zone 1. Consider approximately three times arc foot spacing for the zone 2 and wind speed
of approximately 50 km/h
I is the actual fault current in A.
1MRK505186-UEN D Section 3
IED application
151
Application manual
In practice, the setting of fault resistance for both phase-to-earth RFPE and phase-to-
phase RFPP should be as high as possible without interfering with the load
impedance in order to obtain reliable fault detection.
3.6.1.2 Setting guidelines
General
The settings for Distance measuring zones, quadrilateral characteristic (ZMQPDIS)
are done in primary values. The instrument transformer ratio that has been set for
the analog input card is used to automatically convert the measured secondary
input signals to primary values used in ZMQPDIS.
The following basics must be considered, depending on application, when doing
the setting calculations:
Errors introduced by current and voltage instrument transformers, particularly
under transient conditions.
Inaccuracies in the line zero-sequence impedance data, and their effect on the
calculated value of the earth-return compensation factor.
The effect of infeed between the IED and the fault location, including the
influence of different Z
0
/Z
1
ratios of the various sources.
The phase impedance of non transposed lines is not identical for all fault
loops. The difference between the impedances for different phase-to-earth
loops can be as large as 5-10% of the total line impedance.
The effect of a load transfer between the IEDs of the protected fault resistance
is considerable, the effect must be recognized.
Zero-sequence mutual coupling from parallel lines.
Setting of zone 1
The different errors mentioned earlier usually require a limitation of the
underreaching zone (normally zone 1) to 75 - 90% of the protected line.
In case of parallel lines, consider the influence of the mutual coupling according to
section "Parallel line application with mutual coupling" and select the case(s) that
are valid in the particular application. By proper setting it is possible to compensate
for the cases when the parallel line is in operation, out of service and not earthed
and out of service and earthed in both ends. The setting of earth-fault reach should
be selected to be <95% also when parallel line is out of service and earthed at both
ends (worst case).
Setting of overreaching zone
The first overreaching zone (normally zone 2) must detect faults on the whole
protected line. Considering the different errors that might influence the
measurement in the same way as for zone 1, it is necessary to increase the reach of
the overreaching zone to at least 120% of the protected line. The zone 2 reach can
be even higher if the fault infeed from adjacent lines at remote end is considerable
higher than the fault current at the IED location.
Section 3 1MRK505186-UEN D
IED application
152
Application manual
The setting shall generally not exceed 80% of the following impedances:
The impedance corresponding to the protected line, plus the first zone reach of
the shortest adjacent line.
The impedance corresponding to the protected line, plus the impedance of the
maximum number of transformers operating in parallel on the bus at the
remote end of the protected line.
Larger overreach than the mentioned 80% can often be acceptable due to fault
current infeed from other lines. This requires however analysis by means of fault
calculations.
If any of the above gives a zone 2 reach less than 120%, the time delay of zone 2
must be increased by approximately 200ms to avoid unwanted operation in cases
when the telecommunication for the short adjacent line at remote end is down
during faults. The zone 2 must not be reduced below 120% of the protected line
section. The whole line must be covered under all conditions.
The requirement that the zone 2 shall not reach more than 80% of the shortest
adjacent line at remote end is highlighted in the example below.
If a fault occurs at point F see figure 62, the IED at point A senses the impedance:
ZAF = ZAC + ZCF = ZAC + (1+ ) ZCF
IB
IA
IA + IB
IA
EQUATION302 V2 EN (Equation 72)
A B
Z<
C I
A
IB
ZAC ZCB
ZCF
I A+ I B
IEC09000256_1_en.vsd
F
IEC09000256 V1 EN
Figure 62: Setting of overreaching zone
Setting of reverse zone
The reverse zone is applicable for purposes of scheme communication logic,
current reversal logic, weak-end infeed logic, and so on. The same applies to the back-
up protection of the bus bar or power transformers. It is necessary to secure, that it
always covers the overreaching zone, used at the remote line IED for the
telecommunication purposes.
Consider the possible enlarging factor that might exist due to fault infeed from
adjacent lines. Equation 73 can be used to calculate the reach in reverse direction
when the zone is used for blocking scheme, weak-end infeed, and so on.
1MRK505186-UEN D Section 3
IED application
153
Application manual
Zrev 1.2 ZL Z2rem
EQUATION1525 V3 EN (Equation 73)
Where:
ZL is the protected line impedance
Z2rem is zone 2 setting at remote end of protected line.
In many applications it might be necessary to consider the enlarging factor due to
fault current infeed from adjacent lines in the reverse direction in order to obtain
certain sensitivity.
Setting of zones for parallel line application
Parallel line in service Setting of zone 1
With reference to section "Parallel line applications", the zone reach can be set to
85% of protected line.
However, influence of mutual impedance has to be taken into account.
Parallel line in service setting of zone 2
Overreaching zones (in general, zones 2 and 3) must overreach the protected circuit
in all cases. The greatest reduction of a reach occurs in cases when both parallel
circuits are in service with a single phase-to-earth fault located at the end of a
protected line. The equivalent zero sequence impedance circuit for this case is
equal to the one in figure 56 in section "Parallel line in service".
The components of the zero sequence impedance for the overreaching zones must
be equal to at least:
R
0E
R
0
R
m0
+ =
EQUATION553 V1 EN (Equation 74)
X
0E
X
0
X
m0
+ =
EQUATION554 V1 EN (Equation 75)
Check the reduction of a reach for the overreaching zones due to the effect of the
zero sequence mutual coupling. The reach is reduced for a factor:
0
0 1
2 1 0
m
f
Z
K
Z Z R
= -
+ +
EQUATION1426 V1 EN (Equation 76)
If the denominator in equation 76 is called B and Z0m is simplified to X0m, then
the real and imaginary part of the reach reduction factor for the overreaching zones
can be written as:
Section 3 1MRK505186-UEN D
IED application
154
Application manual
2 2
0 Im( )
Re( 0) 1
Re( ) Im( )
X m B
K
B B
= -
+
EQUATION1427 V1 EN (Equation 77)
2 2
0 Re( )
Im( 0) 1
Re( ) Im( )
X m B
K
B B
= -
+
EQUATION1428 V1 EN (Equation 78)
Parallel line is out of service and earthed in both ends
Apply the same measures as in the case with a single set of setting parameters. This
means that an underreaching zone must not overreach the end of a protected circuit
for the single phase-to-earth faults.
Set the values of the corresponding zone (zero-sequence resistance and reactance)
equal to:
R
0E
R
0
1
X
m0
2
R
0
2
X
0
2
+
-------------------------- +
=
EQUATION561 V1 EN (Equation 79)
X
0E
X
0
1
X
m0
2
R
0
2
X
0
2
+
--------------------------
=
EQUATION562 V1 EN (Equation 80)
Setting of reach in resistive direction
Set the resistive reach R1 independently for each zone.
Set separately the expected fault resistance for phase-to-phase faults RFPP and for
the phase-to-earth faults RFPE for each zone. For each distance zone, set all
remaining reach setting parameters independently of each other.
The final reach in resistive direction for phase-to-earth fault loop measurement
automatically follows the values of the line-positive and zero-sequence resistance,
and at the end of the protected zone is equal to equation 81.
( )
1
R 2 R1 R0 RFPE
3
= + +
IECEQUATION2303 V1 EN (Equation 81)
2 X1 X0
arctan
2 R1 R0
loop j
+
=
+
EQUATION2304 V1 EN (Equation 82)
1MRK505186-UEN D Section 3
IED application
155
Application manual
Setting of the resistive reach for the underreaching zone 1 should follow the
condition to minimize the risk for overreaching:
RFPE 4.5 X1
IECEQUATION2305 V1 EN (Equation 83)
The fault resistance for phase-to-phase faults is normally quite low, compared to
the fault resistance for phase-to-earth faults. To minimize the risk for overreaching,
limit the setting of the zone 1 reach in resistive direction for phase-to-phase loop
measurement to:
RFPP 3 X1
IECEQUATION2306 V1 EN (Equation 84)
Load impedance limitation, without load encroachment function
The following instructions are valid when Phase selection with load encroachment,
quadrilateral characteristic function FDPSPDIS is not activated. To deactivate the
function, the setting of the load resistance RLdFw and RLdRv in FDPSPDIS must
be set to max value (3000). If FDPSPDISis to be used for all or some of the
measuring zones, the load limitation for those zones according to this chapter can
be omitted. Check the maximum permissible resistive reach for any zone to ensure
that there is a sufficient setting margin between the boundary and the minimum
load impedance. The minimum load impedance (/phase) is calculated as:
Z
loadmin
U
2
S
------- =
EQUATION571 V1 EN (Equation 85)
Where:
U is the minimum phase-to-phase voltage in kV
S is the maximum apparent power in MVA.
The load impedance [/phase] is a function of the minimum operation voltage and
the maximum load current:
Z
load
U
min
3 I
max
---------------------- =
EQUATION574 V1 EN (Equation 86)
Minimum voltage U
min
and maximum current I
max
are related to the same
operating conditions. Minimum load impedance occurs normally under emergency
conditions.
As a safety margin is required to avoid load encroachment under
three-phase conditions and to guarantee correct healthy phase IED
operation under combined heavy three-phase load and earth faults,
Section 3 1MRK505186-UEN D
IED application
156
Application manual
consider both: phase-to-phase and phase-to-earth fault operating
characteristics.
To avoid load encroachment for the phase-to-earth measuring elements, the set
resistive reach of any distance protection zone must be less than 80% of the
minimum load impedance.
RFPE 0.8 Z
load
EQUATION792 V1 EN (Equation 87)
This equation is applicable only when the loop characteristic angle for the single
phase-to-earth faults is more than three times as large as the maximum expected load-
impedance angle. For the case when the loop characteristic angle is less than three
times the load-impedance angle, more accurate calculations are necessary
according to equation 88.
min
2 1 0
0.8 cos sin
2 1 0
load
R R
RFPE Z
X X
+
-
+
EQUATION578 V3 EN (Equation 88)
Where:
is a maximum load-impedance angle, related to the maximum load power.
To avoid load encroachment for the phase-to-phase measuring elements, the set
resistive reach of any distance protection zone must be less than 160% of the
minimum load impedance.
RFPP 1.6 Zload
load
1.6 Z RFPP
EQUATION579 V2 EN (Equation 89)
Equation 89 is applicable only when the loop characteristic angle for the phase-to-
phase faults is more than three times as large as the maximum expected load-
impedance angle. More accurate calculations are necessary according to
equation 90.
loadmin
R1
RFPP 1.6 Z cos sin
X1
J J -
IECEQUATION2307 V1 EN (Equation 90)
1MRK505186-UEN D Section 3
IED application
157
Application manual
All this is applicable for all measuring zones when no Power swing detection
function ZMRPSB is activated in the IED. Use an additional safety margin of
approximately 20% in cases when a ZMRPSB function is activated in the IED,
refer to the description of Power swing detection function ZMRPSB.
Load impedance limitation, with Phase selection with load
encroachment, quadrilateral characteristic function activated
The parameters for shaping of the load encroachment characteristic are found in the
description of Phase selection with load encroachment, quadrilateral characteristic
function (FDPSPDIS).
Setting of minimum operating currents
The operation of Distance protection zone, quadrilateral characteristic (ZMQPDIS)
can be blocked if the magnitude of the currents is below the set value of the
parameter IMinOpPP and IMinOpPE.
The default setting of IMinOpPP and IMinOpPE is 20% of IBase where IBase is
the chosen current for the analogue input channels. The value has been proven in
practice to be suitable in most of the applications. However, there might be
applications where it is necessary to increase the sensitivity by reducing the
minimum operating current down to 10% of IBase. This happens especially in
cases, when the IED serves as a remote back-up protection on series of very long
transmission lines.
Setting IMinOpIN blocks the phase-to-earth loop if 3I
0
<IMinOpIN. The default
setting of IMinOpIN is 5% of IBase.
The minimum operating fault current is automatically reduced to 75% of its set
value, if the distance protection zone has been set for the operation in reverse
direction.
Directional impedance element for quadrilateral characteristics
The evaluation of the directionality takes place in Directional impedance
quadrilateral function ZDRDIR. Equation 91 and equation 92 are used to classify
that the fault is in forward direction for phase-to-earth fault and phase-to-phase fault.
1 1
1
0.8 1 0.2 1
arg Re
L L M
L
U U
ArgDir ArgNeg s
I
+
- < <
EQUATION725 V2 EN (Equation 91)
For the L1-L2 element, the equation in forward direction is according to.
Section 3 1MRK505186-UEN D
IED application
158
Application manual
1 2 1 2
1 2
0.8 1 0.2 1
arg Re
L L L L M
L L
U U
ArgDir ArgNeg s
I
+
- < <
EQUATION726 V2 EN (Equation 92)
where:
ArgDir is the setting for the lower boundary of the forward directional characteristic, by default
set to 15 (= -15 degrees) and
ArgNegRes is the setting for the upper boundary of the forward directional characteristic, by default
set to 115 degrees, see figure 63.
U1
L1
is positive sequence phase voltage in phase L1
U1
L1M
is positive sequence memorized phase voltage in phase L1
I
L1
is phase current in phase L1
U1
L1L2
is voltage difference between phase L1 and L2 (L2 lagging L1)
U1
L1L2M
is memorized voltage difference between phase L1 and L2 (L2 lagging L1)
I
L1L2
is current difference between phase L1 and L2 (L2 lagging L1)
The setting of ArgDir and ArgNegRes is by default set to 15 (= -15) and 115
degrees respectively (as shown in figure 63). It should not be changed unless
system studies have shown the necessity.
ZDRDIR gives binary coded directional information per measuring loop on the
output STDIRCND.
STDIR= STFWL1*1+STFWL2*2+STFWL3*4+STFWL1L2*8+
+STFWL2L3*16+STFWL3L1*32+STRVL1*64+STRVL2*128+
+STRVL3*256+STRVL1L2*512+STRVL2L3*1024+STRVL3L1*2048
1MRK505186-UEN D Section 3
IED application
159
Application manual
R
X
ArgDir
ArgNegRes
en05000722.vsd
IEC05000722 V1 EN
Figure 63: Setting angles for discrimination of forward and reverse fault in
Directional impedance quadrilateral function ZDRDIR
The reverse directional characteristic is equal to the forward characteristic rotated
by 180 degrees.
The polarizing voltage is available as long as the positive sequence voltage exceeds
5% of the set base voltage UBase. So the directional element can use it for all
unsymmetrical faults including close-in faults.
For close-in three-phase faults, the U1
L1M
memory voltage, based on the same
positive sequence voltage, ensures correct directional discrimination.
The memory voltage is used for 100 ms or until the positive sequence voltage is
restored.
After 100ms the following occurs:
If the current is still above the set value of the minimum operating current
(between 10 and 30% of the set IED rated current IBase), the condition seals in.
If the fault has caused tripping, the trip endures.
If the fault was detected in the reverse direction, the measuring element
in the reverse direction remains in operation.
If the current decreases below the minimum operating value, the memory
resets until the positive sequence voltage exceeds 10% of its rated value.
Section 3 1MRK505186-UEN D
IED application
160
Application manual
Setting of timers for distance protection zones
The required time delays for different distance protection zones are independent of
each other. Distance protection zone 1 can also have a time delay, if so required for
selectivity reasons. Time delays for all zones can be set in a range of 0 to 60
seconds. The tripping function of each particular zone can be inhibited by setting
the corresponding Operation parameter to Off. Different time delays are possible
for the phase-to-earthtPE and for the phase-to-phase tPP measuring loops in each
distance protection zone separately, to further increase the total flexibility of a
distance protection.
3.6.1.3 Setting parameters
Signals and settings for ZMQPDIS are valid for zone 1 while
signals and settings for ZMQAPDIS are valid for zone 2 - 5
Table 47: ZMQPDIS Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - On Operation Off / On
IBase 1 - 99999 A 1 3000 Base current, i.e. rated current
UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage, i.e. rated voltage
OperationDir Off
Non-directional
Forward
Reverse
- - Forward Operation mode of directionality NonDir /
Forw / Rev
X1 0.10 - 3000.00 ohm/p 0.01 30.00 Positive sequence reactance reach
R1 0.10 - 1000.00 ohm/p 0.01 5.00 Positive seq. resistance for zone
characteristic angle
X0 0.10 - 9000.00 ohm/p 0.01 100.00 Zero sequence reactance reach
R0 0.50 - 3000.00 ohm/p 0.01 15.00 Zero seq. resistance for zone
characteristic angle
RFPP 1.00 - 3000.00 ohm/l 0.01 30.00 Fault resistance reach in ohm/loop, Ph-Ph
RFPE 1.00 - 9000.00 ohm/l 0.01 100.00 Fault resistance reach in ohm/loop, Ph-E
OperationPP Off
On
- - On Operation mode Off / On of Phase-
Phase loops
Timer tPP Off
On
- - On Operation mode Off / On of Zone timer,
Ph-Ph
tPP 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-Ph
OperationPE Off
On
- - On Operation mode Off / On of Phase-Earth
loops
Timer tPE Off
On
- - On Operation mode Off / On of Zone timer,
Ph-E
tPE 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-E
Table continues on next page
1MRK505186-UEN D Section 3
IED application
161
Application manual
Name Values (Range) Unit Step Default Description
IMinOpPP 10 - 30 %IB 1 20 Minimum operate delta current for Phase-
Phase loops
IMinOpPE 10 - 30 %IB 1 20 Minimum operate phase current for
Phase-Earth loops
IMinOpIN 5 - 30 %IB 1 5 Minimum operate residual current for
Phase-Earth loops
Table 48: ZMQAPDIS Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - On Operation Off / On
IBase 1 - 99999 A 1 3000 Base current, i.e. rated current
UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage, i.e. rated voltage
OperationDir Off
Non-directional
Forward
Reverse
- - Forward Operation mode of directionality NonDir /
Forw / Rev
X1 0.50 - 3000.00 ohm/p 0.01 40.00 Positive sequence reactance reach
R1 0.10 - 1000.00 ohm/p 0.01 5.00 Positive seq. resistance for zone
characteristic angle
X0 0.50 - 9000.00 ohm/p 0.01 120.00 Zero sequence reactance reach
R0 0.50 - 3000.00 ohm/p 0.01 15.00 Zero seq. resistance for zone
characteristic angle
RFPP 1.00 - 3000.00 ohm/l 0.01 30.00 Fault resistance reach in ohm/loop, Ph-Ph
RFPE 1.00 - 9000.00 ohm/l 0.01 100.00 Fault resistance reach in ohm/loop, Ph-E
OperationPP Off
On
- - On Operation mode Off / On of Phase-
Phase loops
Timer tPP Off
On
- - On Operation mode Off / On of Zone timer,
Ph-Ph
tPP 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-Ph
OperationPE Off
On
- - On Operation mode Off / On of Phase-Earth
loops
Timer tPE Off
On
- - On Operation mode Off / On of Zone timer,
Ph-E
tPE 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-E
IMinOpPP 10 - 30 %IB 1 20 Minimum operate delta current for Phase-
Phase loops
IMinOpPE 10 - 30 %IB 1 20 Minimum operate phase current for
Phase-Earth loops
Section 3 1MRK505186-UEN D
IED application
162
Application manual
Table 49: ZDRDIR Group settings (basic)
Name Values (Range) Unit Step Default Description
ArgNegRes 90 - 175 Deg 1 115 Angle to blinder in second quadrant for
forward direction
ArgDir 5 - 45 Deg 1 15 Angle to blinder in fourth quadrant for
forward direction
IMinOp 1 - 99999 %IB 1 10 Minimum operate current in % of IBase
IBase 1 - 99999 A 1 3000 Base Current
UBase 0.05 - 2000.00 kV 0.05 400.00 Base Voltage
3.6.2 Distance measuring zone, quadrilateral characteristic for
series compensated lines ZMCPDIS, ZMCAPDIS, ZDSRDIR
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Distance measuring zone, quadrilateral
characteristic for series compensated
lines (zone 1)
ZMCPDIS
S00346 V1 EN
21
Distance measuring zone, quadrilateral
characteristic for series compensated
lines (zone 2-5)
ZMCAPDIS
S00346 V1 EN
21
Directional impedance quadrilateral,
including series compensation
ZDSRDIR
Z<->
IEC09000167 V1 EN
21D
3.6.2.1 Application
Introduction
Sub transmission networks are being extended and often become more and more
complex, consisting of a high number of multi-circuit and/or multi terminal lines of
very different lengths. These changes in the network will normally impose more
stringent demands on the fault clearing equipment in order to maintain an
unchanged or increased security level of the power system.
The distance protection function is designed to meet basic requirements for
application on transmission and sub transmission lines (solid earthed systems)
although it also can be used on distribution levels.
1MRK505186-UEN D Section 3
IED application
163
Application manual
System earthing
The type of system earthing plays an important roll when designing the protection
system. In the following sections, some hints with respect to distance protection are
highlighted.
Solid earthed networks
In solid earthed systems the transformer neutrals are connected solidly to earth
without any impedance between the transformer neutral and earth.
xx05000215.vsd
IEC05000215 V1 EN
Figure 64: Solidly earthed network
The earth fault current is as high or even higher than the short-circuit current. The
series impedances determine the magnitude of the fault current. The shunt
admittance has very limited influence on the earth fault current. The shunt
admittance may, however, have some marginal influence on the earth fault current
in networks with long transmission lines.
The earth fault current at single phase -to-earth in phase L1 can be calculated as
equation 93:
L1 L1
0
1 2 0 f 1 N f
3 U U
3I
Z Z Z 3Z Z Z Z
= =
+ + + + +
EQUATION1267 V3 EN (Equation 93)
Where:
UL1 is the phase-to-earth voltage (kV) in the faulty phase before fault
Z1 is the positive sequence impedance (/phase)
Z2 is the negative sequence impedance (/phase)
Z0 is the zero sequence impedance (/phase)
Zf is the fault impedance (), often resistive
ZN is the earth return impedance defined as (Z0-Z1)/3
The voltage on the healthy phases is generally lower than 140% of the nominal phase-
to-earth voltage. This corresponds to about 80% of the nominal phase-to-phase
voltage.
Section 3 1MRK505186-UEN D
IED application
164
Application manual
The high zero sequence current in solid earthed networks makes it possible to use
impedance measuring technique to detect earth-fault. However, distance protection
has limited possibilities to detect high resistance faults and must, therefore, always
be complemented with other protection function(s) that can carry out the fault
clearance in those cases.
Effectively earthed networks
A network is defined as effectively earthed if the earth-fault factor fe is less than
1.4. The earth-fault factor is defined according to equation 47.
max
e
pn
U
f
U
=
EQUATION1268 V3 EN (Equation 94)
Where:
U
max
is the highest fundamental frequency voltage on one of the healthy phases at single phase-
to-earth fault.
U
pn
is the phase-to-earth fundamental frequency voltage before fault.
Another definition for effectively earthed network is when the following
relationships between the symmetrical components of the network impedances are
valid, as shown in equation 95 and equation 96.
X X
0 1
= 3
EQUATION1269 V3 EN (Equation 95)
R R
0 1
EQUATION1270 V3 EN (Equation 96)
The magnitude of the earth fault current in effectively earthed networks is high
enough for impedance measuring element to detect earth-fault. However, in the
same way as for solid earthed networks, distance protection has limited
possibilities to detect high resistance faults and must, therefore, always be
complemented with other protection function(s) that can carry out the fault
clearance in this case.
Fault infeed from remote end
All transmission and most all sub transmission networks are operated meshed.
Typical for this type of network is that we will have fault infeed from remote end
when fault occurs on the protected line. The fault infeed may enlarge the fault
impedance seen by the distance protection. This effect is very important to keep in
mind when both planning the protection system and making the settings.
With reference to figure 65, we can draw the equation for the bus voltage Va at left
side as:
1MRK505186-UEN D Section 3
IED application
165
Application manual
( ) A A L A B f V I p Z I I R = + +
EQUATION1273 V1 EN (Equation 97)
If we divide Va by IA we get Z present to the IED at A side
a A B
A L f
A A
V I I
Z p Z R
I I
+
= = +
EQUATION1274 V2 EN (Equation 98)
The infeed factor (IA+IB)/IA can be very high, 10-20 depending on the differences
in source impedances at local and remote end.
Z <
ZL
Z <
EsA
VA
VA
A B
EsB
IA IB
Rf
p*ZL (1-p)*ZL
ZSA
ZSB
en05000217.vsd
IEC05000217 V1 EN
Figure 65: Influence of fault infeed from remote end
The effect of fault current infeed from remote end is one of the most driving factors
to justify complementary protection to distance protection.
Load encroachment
Sometimes the load impedance might enter the zone characteristic without any
fault on the protected line. The phenomenon is called load encroachment and it
might occur when an external fault is cleared and high emergency load is
transferred on the protected line. The effect of load encroachment is illustrated to
the left in figure 66. The entrance of the load impedance inside the characteristic is
not allowed and the way to handle this with conventional distance protection is to
consider this with the settings that is, to have a security margin between the
distance zone and the minimum load impedance. This has the drawback that it will
reduce the sensitivity of the protection that is, the ability to detect resistive faults.
The IED has a built in function which shapes the characteristic according to the
right figure 66. The load encroachment algorithm increases the possibility to detect
high fault resistances, especially for line to earth faults at remote end. For example,
for a given setting of the load angle ARGLd for the load encroachment function, the
resistive blinder for the zone measurement can be expanded according to the right
in figure 66 given higher fault resistance coverage without risk for unwanted
operation due to load encroachment. This is valid in both directions.
Section 3 1MRK505186-UEN D
IED application
166
Application manual
The use of the load encroachment feature is essential for long heavy loaded lines,
where there might be a conflict between the necessary emergency load transfer and
necessary sensitivity of the distance protection. The function can also preferably be
used on heavy loaded medium long lines. For short lines the major concern is to get
sufficient fault resistance coverage and load encroachment is not a major problem.
So, for short lines, the load encroachment function could preferable be switched off.
The settings of the parameters for load encroachment are done in the Phase
selection with load enchroachment, quadrilateral characteristic (FDPSPDIS)
function.
R
X
Zm
Load impedance
area in forward
direction
RLdRv
R
Zm
ARGLd
ARGLd
ARGLd
ARGLd
RLdFw
ZL
en05000495.vsd
IEC05000495 V1 EN
Figure 66: Load encroachment phenomena and shaped load encroachment
characteristic
Long transmission line application
For long transmission lines the margin to the load impedance that is, to avoid load
encroachment, will normally be a major concern. It is difficult to achieve high
sensitivity for line to earth-fault at remote end of a long lines when the line is
heavy loaded.
Definition of long lines with respect to the performance of distance protection can
generally be described as in table 50, long lines have SIRs less than 0.5.
Table 50: Definition of long lines
Line category
Un Un
110 kV 500 kV
Long lines 77 km - 99 km 350 km - 450 km
Very long lines > 99 km > 450 km
The possibility in IED to set resistive and reactive reach independent for positive
and zero sequence fault loops and individual fault resistance settings for phase-to-
phase and phase-to-earth fault together with load encroachment algorithm
1MRK505186-UEN D Section 3
IED application
167
Application manual
improves the possibility to detect high resistive faults at the same time as the
security is improved (risk for unwanted trip due to load encroachment is
eliminated), as shown in figure 67.
en05000220.vsd
R
Zm
ARGLd
ARGLd
ARGLd
ARGLd
RLdFw RLdRv
ZL
IEC05000220 V1 EN
Figure 67: Characteristic for zone measurement for long line with load
encroachment activated
Parallel line application with mutual coupling
General
Introduction of parallel lines in the network is increasing due to difficulties to get
necessary area for new lines.
Parallel lines introduce an error in the measurement due to the mutual coupling
between the parallel lines. The lines need not be of the same voltage to experience
mutual coupling, and some coupling exists even for lines that are separated by 100
meters or more. The reason to the introduced error in measuring due to mutual
coupling is the zero sequence voltage inversion that occurs.
It can be shown from analytical calculations of line impedances that the mutual
impedances for positive and negative sequence are very small (< 1-2%) of the self
impedance and it is practice to neglect them.
From an application point of view there exists three types of network
configurations (classes) that must be considered when making the settings for the
protection function. Those are:
Parallel line with common positive and zero sequence network
Parallel circuits with common positive but isolated zero-sequence network
Parallel circuits with positive and zero sequence sources isolated
Section 3 1MRK505186-UEN D
IED application
168
Application manual
One example of class3 networks could be the mutual coupling between a 400 kV
line and rail road overhead lines. This type of mutual coupling is not so common
although it exists and is not treated any further in this manual.
For each type of network class we can have three different topologies; the parallel
line can be in service, out of service, out of service and earthed in both ends.
The reach of the distance protection zone1 will be different depending on the
operation condition of the parallel line. It is therefore recommended to use the
different setting groups to handle the cases when the parallel line is in operation
and out of service and earthed at both ends.
The distance protection within the IED can compensate for the influence of a zero-
sequence mutual coupling on the measurement at single phase-to-earth faults in the
following ways, by using:
The possibility of different setting values that influence the earth-return
compensation for different distance zones within the same group of setting
parameters.
Different groups of setting parameters for different operating conditions of a
protected multi circuit line.
Most multi circuit lines have two parallel operating circuits. The application guide
mentioned below recommends in more detail the setting practice for this particular
type of line. The basic principles also apply to other multi circuit lines.
Parallel line applications
This type of networks are defined as those networks where the parallel
transmission lines terminate at common nodes at both ends. We consider the three
most common operation modes:
parallel line in service
parallel line out of service and earthed
parallel line out of service and not earthed
Parallel line in service
This type of application is very common and applies to all normal sub-transmission
and transmission networks.
Here is the description of what happens when a fault occurs on the parallel line, as
shown in figure 68.
From symmetrical components, it is possible to derive the impedance Z at the IED
point for normal lines without mutual coupling according to equation 99.
1MRK505186-UEN D Section 3
IED application
169
Application manual
ph ph
0 1 ph 0 N
ph 0
1
V V
Z Z I 3I K
I 3I
3 Z
Z = =
- +
+
= +
+
EQUATION1287 V1 EN (Equation 112)
The imaginary component of the same factor is equal to equation 113.
( )
( )
( ) ( )
2
Im
Im
Re
A
K
U
A
=
+
Im A
2
X
m0
2
EQUATION1288 V1 EN (Equation 113)
Ensure that the underreaching zones from both line ends will overlap a sufficient
amount (at least 10%) in the middle of the protected circuit.
Tapped line application
1MRK505186-UEN D Section 3
IED application
175
Application manual
A B
Z< Z<
Z<
C
T
IC
IA IB
-IB
en05000224.vsd
DOCUMENT11524-IMG869 V1 EN
Figure 74: Example of tapped line with Auto transformer
This application gives rise to similar problem that was highlighted in section
"Fault infeed from remote end" that is, increased measured impedance due to fault
current infeed. For example, for faults between the T point and B station the
measured impedance at A and C is as follows:
ZA =ZAT + ZTF
IA + IC
IA
DOCUMENT11524-IMG3509 V2 EN (Equation 114)
ZC = ZTrf + ( ZCT + ZTF) ( )
2
IA + IC
IC
U2
U1
DOCUMENT11524-IMG3510 V2 EN (Equation 115)
Where:
ZAT and ZCT is the line impedance from the B respective C station to the T point.
IA and IC is fault current from A respective C station for fault between T and B.
U2/U1 Transformation ratio for transformation of impedance at U1 side of the transformer to
the measuring side U2 (it is assumed that current and voltage distance function is
taken from U2 side of the transformer).
For this example with a fault between T and B, the measured impedance from the T
point to the fault can be increased by a factor defined as the sum of the currents
Section 3 1MRK505186-UEN D
IED application
176
Application manual
from T point to the fault divided by the IED current. For the IED at C, the
impedance on the high voltage side U1 has to be transferred to the measuring
voltage level by the transformer ratio.
Another complication that might occur depending on the topology is that the
current from one end can have a reverse direction for fault on the protected line.
For example, for faults at T the current from B might go in reverse direction from
B to C depending on the system parameters (as shown in the dotted line in
figure 74), given that the distance protection in B to T will measure wrong direction.
In three-end application, depending on the source impedance behind the IEDs, the
impedances of the protected object and the fault location, it might be necessary to
accept zone2 trip in one end or sequential trip in one end.
Generally for this type of application it is difficult to select settings of zone1 that
both gives overlapping of the zones with enough sensitivity without interference
with other zone1 settings that is, without selectivity conflicts. Careful fault
calculations are necessary to determine suitable settings and selection of proper
scheme communication.
Fault resistance
The performance of distance protection for single phase-to-earth faults is very
important, because normally more than 70% of the faults on transmission lines are
single phase-to-earth faults. At these faults, the fault resistance is composed of
three parts: arc resistance, resistance of a tower construction, and tower-footing
resistance. The arc resistance can be calculated according to Warrington's formula:
1.4
28707 L
Rarc
I
=
EQUATION1456 V1 EN (Equation 116)
where:
L represents the length of the arc (in meters). This equation applies for the distance protection
zone 1. Consider approximately three-times arc foot spacing for the zone 2 and wind speed
of approximately 50 km/h
I is the actual fault current in A.
In practice, the setting of fault resistance for both phase-to-earth (RFPE) and phase-
to-phase (RFPP) must be as high as possible without interfering with the load
impedance to obtain reliable fault detection.
Series compensation in power systems
The main purpose of series compensation in power systems is virtual reduction of
line reactance in order to enhance the power system stability and increase
loadability of transmission corridors. The principle is based on compensation of
distributed line reactance by insertion of series capacitor (SC). The generated
reactive power provided by the capacitor is continuously proportional to the square
of the current flowing at the same time through the compensated line and series
1MRK505186-UEN D Section 3
IED application
177
Application manual
capacitor. This means that the series capacitor has a self-regulating effect. When
the system loading increases, the reactive power generated by series capacitors
increases as well. The response of SCs is automatic, instantaneous and continuous.
The main benefits of incorporating series capacitors in transmission lines are:
Steady state voltage regulation and raise of voltage collapse limit
Increase power transfer capability by raising the transient stability limit
Improved reactive power balance
Increase in power transfer capacity
Active load sharing between parallel circuits and loss reduction
Reduced costs of power transmission due to decreased investment costs for
new power lines
Steady state voltage regulation and increase of voltage collapse limit
A series capacitor is capable of compensating the voltage drop of the series
inductance in a transmission line, as shown in figure 75. During low loading, the
system voltage drop is lower and at the same time, the voltage drop on the series
capacitor is lower. When the loading increases and the voltage drop become larger,
the contribution of the series capacitor increases and therefore the system voltage at
the receiving line end can be regulated.
Series compensation also extends the region of voltage stability by reducing the
reactance of the line and consequently the SC is valuable for prevention of voltage
collapse. Figure 76 presents the voltage dependence at receiving bus B (as shown
in figure 75) on line loading and compensation degree K
C
, which is defined
according to equation 117. The effect of series compensation is in this particular
case obvious and self explanatory.
=
C
C
Line
X
K
X
EQUATION1895 V1 EN (Equation 117)
A typical 500 km long 500 kV line is considered with source impedance
1
0 =
SA
Z
EQUATION1896 V1 EN (Equation 118)
~ EA
ZSA1
Power line
A B
Seires
capacitor
Load
en06000585.vsd
IEC06000585 V1 EN
Figure 75: A simple radial power system
Section 3 1MRK505186-UEN D
IED application
178
Application manual
en06000586.vsd
0 200 400 600 800 1000 1200 1400 1600 1800
100
200
300
400
500
P[MW]
U
[
k
V
]
Ulimit
P
0
P
3
0
P
5
0
P
7
0
IEC06000586 V1 EN
Figure 76: Voltage profile for a simple radial power line with 0, 30, 50 and
70% of compensation
Increased power transfer capability by raising the first swing stability limit
Consider the simple one-machine and infinite bus system shown in figure 77.
en06000587.vsd
~ EA
ZSA1
A B
PMech
+jXLine
-jXC
System
IEC06000587 V1 EN
Figure 77: One machine and infinite bus system
The equal-areas criterion is used to show the effectiveness of a series capacitor for
improvement of first swing transient stability (as shown in figure 78).
In steady state, the mechanical input power to the generator (P
Mech
) is equal to the
electrical output power from the generator (P
E
) and the generator angle is d
0
. If a 3-
phase fault occurs at a point near the machine, the electrical output of the generator
reduces to zero. This means that the speed of the generator increases and the angle
difference between the generator and the infinite bus increases during the fault. At
the time of fault clearing, the angle difference has increased to
C
. After reclosing
of the system, the transmitted power exceeds the mechanical input power and the
generator deaccelerates. The generator decelerates as long as equal area condition
A
ACC
=A
DEC
has not been fulfilled. The critical condition for post-fault system
stability is that the angular displacement after fault clearing and during the
deceleration does not exceed its critical limit
CR
, because if it does, the system
cannot get back to equilibrium and the synchronism is lost. The first swing stability
and the stability margin can be evaluated by studying the different areas in figure
78 for the same system, once without SC and once with series compensation. The
areas under the corresponding P curves correspond to energy and the system
remains stable if the accelerating energy that the generator picks up during the fault
is lower than the decelerating energy that is transferred across the transmission line
during the first system swing upon fault clearing.
1MRK505186-UEN D Section 3
IED application
179
Application manual
en06000588.vsd
0 C EA
AACC
A
DEC
A
SM
CR
PMech PMech
P
[
p
u
]
P
[
p
u
]
with SC without SC
AACC
A
DEC
ASM
0 C EA CR
IEC06000588 V1 EN
Figure 78: Equal area criterion and first swing stability without and with series
compensation
This means that the system is stable if A
ACC
(A
DEC
+ A
SM
). The stability margin
is given by the difference between the available decelerating energy (area between
the P () and P
Mech
and the angular difference between
C
and
CR
) and the
accelerating energy. It is represented in figure 78 by the area A
SM
. Notice that a
substantial increase in the stability margin is obtained by installing a series
capacitor. The series compensation can improve the situation in two ways, it can
decrease the initial angle difference
0
corresponding to a certain power transfer
and it also shifts the P curve upwards.
Improve reactive power balance
A series capacitor increases its output of reactive power instantaneously,
continuously and automatically with increasing line load. It is thus a self-regulating
device, which improves voltage regulation and reduces the need for other means of
voltage control for example, shunt compensation. The reactive power balance of a
series compensated line is shown in figure 79 as an example for 500 km long 500
kV transmission line with 50% compensation degree.
Section 3 1MRK505186-UEN D
IED application
180
Application manual
Capacitive
Inductive
200
400
600
800
1000
200
400
600
Q
(Mvar)
500 1000 1500
Power flow
(MW)
(T.L.)
(S.C.)
(T.L.
+
S.C.)
Transmission
Line
Series
Compensation
500 kV
500 km
k = 50 %
en06000589.vsd
IEC06000589 V1 EN
Figure 79: Self-regulating effect of reactive power balance
Increase in power transfer
The increase in power transfer capability as a function of the degree of
compensation for a transmission line can be explained by studying the circuit
shown in figure 80. The power transfer on the transmission line is given by the
equation 119:
( ) ( )
( )
sin sin
1
d d
= =
- -
A B A B
Line C Line C
U U U U
P
X X X K
EQUATION1897 V1 EN (Equation 119)
The compensation degree K
c
is defined as equation 117
A B
-jXC
P
A
Q
A
P
B
Q
B
U
A
U
B
U
+jXL
U
A
U
B
d
D
en06000590.vsd
IEC06000590 V1 EN
Figure 80: Transmission line with series capacitor
The effect on the power transfer when considering a constant angle difference ()
between the line ends is illustrated in figure 81. Practical compensation degree runs
from 20 to 70 percent. Transmission capability increases of more than two times
can be obtained in practice.
1MRK505186-UEN D Section 3
IED application
181
Application manual
en06000592.vsd
0 0. 1 0. 2 0. 3 0. 4 0. 5 0.6 0. 7
1
1.5
2
2.5
3
3.5
Degree of series compensa tio n [%]
I
n
c
r
e
a
s
e
i
n
p
o
w
e
r
t
r
a
n
s
f
e
r
Powe r transfer with co ns tant ang le diffe rence
Degree of
compensation
Multiple of power over
a non-compensated line
IEC06000592 V1 EN
Figure 81: Increase in power transfer over a transmission line depending on
degree of series compensation
Active load sharing between parallel circuits and loss reduction
A series capacitor can be used to control the distribution of active power between
parallel transmission circuits. The compensation of transmission lines with
sufficient thermal capacity can relieve the possible overloading of other parallel
lines. This distribution is governed by the reactance, while the losses are
determined by the resistance. A properly designed series compensation system can
considerably reduce the total transmission system losses, as shown in figure 82.
en06000593.vsd
RL1 jXL1
-jXC
Line 1
jX
L2
RL2
Line 2
IEC06000593 V1 EN
Figure 82: Two parallel lines with series capacitor for optimized load sharing
and loss reduction
To minimize the losses, the series capacitor must be installed in the transmission
line with the lower resistance. The size of the series capacitor that minimizes the
total losses is given the following expression:
1 1
2 2
-
=
L C L
L L
X X R
X R
EQUATION1899 V1 EN (Equation 120)
Reduced costs of power transmission due to decreased investment costs
for new power line
As shown in figure 81 the line loading can easily be increased 1.5-2 times by series
compensation. Thus, the required number of transmission lines needed for a certain
power transfer can be significantly reduced. The cost of series compensation is
small compared to the cost of a transmission line. When evaluating the cost of a
Section 3 1MRK505186-UEN D
IED application
182
Application manual
transmission system upgrade also the cost of secondary equipment such as eventual
upgrading of line protections on the compensated as well as, adjacent lines should
be considered. The main advantages of series compensation against the new
transmission line within the same corridor are:
Significantly reduced investment costs; the same increase in power
transmission for up to 90% reduced costs
In many cases, the only practical way to increase the transmission capacity of
a corridor
Series compensation shortens the lead times
Environmental impact
~ EA ~ EB
New transmission line
Series compensation
en06000594.vsd
IEC06000594 V1 EN
Figure 83: Series compensation is an important alternative to new
transmission lines
Advancements in series compensation using thyristor switching technology
A thyristor switched series capacitor (TSSC) can be used for power flow control.
This is performed by changing the reactance of the transmission circuit in discrete
steps, as shown in figure 84. A TSSC typically consists of a few segments in series
that can be inserted independently of each other in order to achieve different total
series capacitor reactance.
en06000595.vsd
Fw
Rv
-jX
C
Fw
Rv
-jX
C
Fw
Rv
-jX
C
IEC06000595 V1 EN
Figure 84: Thyristor switched series capacitor
1MRK505186-UEN D Section 3
IED application
183
Application manual
en06000596.vsd
+ -
-jX
C
I
L
UC
jX
L
F
W
R
v
I
V
IEC06000596 V1 EN
Figure 85: Thyristor controlled series capacitor
I
L
Line current
I
V
Current through the thyristor
U
C
Voltage over the series capacitor
X
C
Rated reactance of the series capacitor
A thyristor controlled series capacitor (TCSC) allows continuous control of the
series capacitor reactance. This is achieved by adding current through the capacitor
via the parallel thyristor valve path see figure 85. The main circuit of the TCSC
consists of a capacitor bank and a thyristor controlled inductive branch connected
in parallel. The capacitor bank may have a value of for example, 10...30 /phase
and a rated continuous current of 1500...3000 A. The capacitor bank for each phase
is mounted on a platform providing full insulation towards earth. The thyristor
valve contains a string of series connected high power thyristors with a maximum
total blocking voltage in the range of hundreds of kV. The inductor is an air-core
reactor with a few mH inductance. The wave forms of a TCSC in capacitive boost
mode are shown in figure 86.
en06000597.vsd
U
C
X
C
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2
-2
0
2
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2
-5
0
5
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2
-50
0
50
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2
-40
-20
0
I
L
I
V
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2
-2
2
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2
-5
5
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2
-50
50
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2
-40
-20
0
0
0
0
IEC06000597 V1 EN
Figure 86: TCSC wave forms presented in capacitive boost mode for a typical
50Hz system
The apparent impedance of the TCSC (the impedance seen by the power system)
can typically be increased to up to 3 times the physical impedance of the capacitor,
Section 3 1MRK505186-UEN D
IED application
184
Application manual
see figure 87. This high apparent reactance will mainly be used for damping of
power oscillations.
en06000598.vsd
Imperatriz TCSC, Operating range
-0.4
-0.2
0
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
2
2.2
2.4
2.6
2.8
3
3.2
0 300 600 900 1200 1500 1800 2100 2400 2700 3000
Line current (Arms)
X
t
c
s
c
/
X
c
(
p
u
)
Continuous
30 min. overload
10s overload
Bypass mode
Series5
Continuous 30 min 10s
B C D
E F G
A
IEC06000598 V1 EN
Figure 87: Operating range of a TCSC installed for damping of power
oscillations (example)
During continuous valve bypass the TCSC represents an inductive impedance of
about 20% of the capacitor impedance. Both operation in capacitive boost mode
and valve bypass mode can be used for damping of power swings. The utilization
of valve bypass increases the dynamic range of the TCSC and improves the TCSC
effectiveness in power oscillation damping.
Challenges in protection of series compensated and adjacent power
lines
System planning does not consider any more possible protection issues and
difficulties, when deciding for a particular, non conventional solution of certain
operation and stability problems. It is supposed that modern communication and
state of the art computer technologies provides good basis for the required solution.
This applies also to protection issues in series compensated networks. Different
physical phenomena, which influence conventional principles of IED protection,
like distance protection, phase comparison protection, are well known and
accordingly considered in IED design. Some other issues, like influence of
controlled thyristors in series capacitor banks are getting increased importance,
although not as high as they would deserve.
The most important challenges, which influence the operation of different
protection functions in the greatest extent, are described in this chapter.
1MRK505186-UEN D Section 3
IED application
185
Application manual
Voltage and current inversion
Series capacitors influence the magnitude and the direction of fault currents in
series compensated networks. They consequently influence phase angles of
voltages measured in different points of series compensated networks and this
performances of different protection functions, which have their operation based on
properties of measured voltage and current phasors.
Voltage inversion
Figure 88 presents a part of series compensated line with reactance X
L1
between
the IED point and the fault in point F of series compensated line. The voltage
measurement is supposed to be on the bus side, so that series capacitor appears
between the IED point and fault on the protected line. Figure 89 presents the
corresponding phasor diagrams for the cases with bypassed and fully inserted
series capacitor.
Voltage distribution on faulty lossless serial compensated line from fault point F to
the bus is linearly dependent on distance from the bus, if there is no capacitor
included in scheme (as shown in figure 89). Voltage U
M
measured at the bus is
equal to voltage drop D U
L
on the faulty line and lags the current I
F
by 90 electrical
degrees.
The situation changes with series capacitor included in circuit between the IED
point and the fault position. The fault current I
F
(see figure 89) is increased due to
the series capacitor, generally decreases total impedance between the sources and
the fault. The reactive voltage drop D U
L
on X
L1
line impedance leads the current
by 90 degrees. Voltage drop DU
C
on series capacitor lags the fault current by 90
degrees. Note that line impedance X
L1
could be divided into two parts: one
between the IED point and the capacitor and one between the capacitor and the
fault position. The resulting voltage U
M
in IED point is this way proportional to
sum of voltage drops on partial impedances between the IED point and the fault
position F, as presented by
( )
1
= -
M F L C
U I j X X
EQUATION1901 V1 EN (Equation 121)
Section 3 1MRK505186-UEN D
IED application
186
Application manual
en06000605.vsd
~
Z<
XS XL1
IF
U
UM
Source
Fault voltage
Pre -fault voltage
XC
Source voltage
U
M
With bypassed
capacitor
With inserted
capacitor
F
IEC06000605 V1 EN
Figure 88: Voltage inversion on series compensated line
en06000606.vsd
IF
U
S
U
M
=
x
U
L
x
U
S
IF
x
U
L
U
S
x
U
C
U
M
x
U
S
With bypassed
capacitor
With inserted
capacitor
IEC06000606 V1 EN
Figure 89: Phasor diagrams of currents and voltages for the bypassed and
inserted series capacitor during voltage inversion
It is obvious that voltage U
M
will lead the fault current I
F
as long as X
L1
> X
C
. This
situation corresponds, from the directionality point of view, to fault conditions on
line without series capacitor. Voltage U
M
in IED point will lag the fault current I
F
in case when:
L1 C S L1
X X X X < < +
EQUATION1902 V1 EN (Equation 122)
Where
X
S
is the source impedance behind the IED
The IED point voltage inverses its direction due to presence of series capacitor and
its dimension. It is a common practice to call this phenomenon voltage inversion.
Its consequences on operation of different protections in series compensated
networks depend on their operating principle. The most known effect has voltage
1MRK505186-UEN D Section 3
IED application
187
Application manual
inversion on directional measurement of distance IEDs (see chapter "Distance
protection" for more details), which must for this reason comprise special measures
against this phenomenon.
There will be no voltage inversion phenomena for reverse faults in system with
VTs located on the bus side of series capacitor. The allocation of VTs to the line
side does not eliminate the phenomenon, because it appears again for faults on the
bus side of IED point.
Current inversion
Figure 90 presents part of a series compensated line with corresponding equivalent
voltage source. It is generally anticipated that fault current I
F
flows on non-
compensated lines from power source towards the fault F on the protected line.
Series capacitor may change the situation.
en06000607.vsd
~
Z<
XS XL1
IF
U
UM
Source
Fault voltage
Pre -fault voltage
XC
Source voltage
U
M
With bypassed
capacitor
With inserted
capacitor
F
IEC06000607 V1 EN
Figure 90: Current inversion on series compensated line
The relative phase position of fault current I
F
compared to the source voltage U
S
depends in general on the character of the resultant reactance between the source
and the fault position. Two possibilities appear:
1
1
0
0
- + >
- + <
S C L
S C L
X X X
X X X
EQUATION1935 V1 EN (Equation 123)
The first case corresponds also to conditions on non compensated lines and in
cases, when the capacitor is bypassed either by spark gap or by the bypass switch,
as shown in phasor diagram in figure 91. The resultant reactance is in this case of
inductive nature and the fault currents lags source voltage by 90 electrical degrees.
The resultant reactance is of capacitive nature in the second case. Fault current will
for this reason lead the source voltage by 90 electrical degrees, which means that
reactive current will flow from series compensated line to the system. The system
conditions are in such case presented by equation 124
Section 3 1MRK505186-UEN D
IED application
188
Application manual
1
> +
C S L
X X X
EQUATION1936 V1 EN (Equation 124)
en06000608.vsd
IF
U
S
U
M
=
H
U
L
H
U
S
With bypassed
capacitor
IF
H
U
L
U
S
H
U
C
U
M
H
U
S
With inserted
capacitor
IEC06000608 V1 EN
Figure 91: Phasor diagrams of currents and voltages for the bypassed and
inserted series capacitor during current inversion
It is a common practice to call this phenomenon current inversion. Its
consequences on operation of different protections in series compensated networks
depend on their operating principle. The most known effect has current inversion
on operation of distance IEDs (as shown in section "Distance protection" for more
details), which cannot be used for the protection of series compensated lines with
possible current inversion. Equation 124 shows also big dependence of possible
current inversion on series compensated lines on location of series capacitors. X
L1
= 0 for faults just behind the capacitor when located at line IED and only the source
impedance prevents current inversion. Current inversion has been considered for
many years only a theoretical possibility due to relatively low values of source
impedances (big power plants) compared to the capacitor reactance. The possibility
for current inversion in modern networks is increasing and must be studied
carefully during system preparatory studies.
The current inversion phenomenon should not be studied only for the purposes of
protection devices measuring phase currents. Directional comparison protections,
based on residual (zero sequence) and negative sequence currents should be
considered in studies as well. Current inversion in zero sequence systems with low
zero sequence source impedance (a number of power transformers connected in
parallel) must be considered as practical possibility in many modern networks.
Low frequency transients
Series capacitors introduce in power systems oscillations in currents and voltages,
which are not common in non-compensated systems. These oscillations have
frequencies lower than the rated system frequency and may cause delayed increase
of fault currents, delayed operation of spark gaps as well as, delayed operation of
protective IEDs. The most obvious difference is generally seen in fault currents.
Figure 92 presents a simplified picture of a series compensated network with basic
1MRK505186-UEN D Section 3
IED application
189
Application manual
line parameters during fault conditions. We study the basic performances for the
same network with and without series capacitor. Possible effects of spark gap
flashing or MOV conducting are neglected. The time dependence of fault currents
and the difference between them are of interest.
en06000609.vsd
~ eG(t)
iL(t)
RL jXL
-jXC
F
IEC06000609 V1 EN
Figure 92: Simplified equivalent scheme of SC network during fault conditions
We consider the instantaneous value of generator voltage following the sine wave
according to equation 125
( ) sin w l = +
G G
e E t
EQUATION1904 V1 EN (Equation 125)
The basic loop differential equation describing the circuit in figure 92 without
series capacitor is presented by equation 126
( ) sin w l + = +
L
L L L G
di
L R i E t
dt
EQUATION1905 V1 EN (Equation 126)
The solution over line current is presented by group of equations 127
( )
( )
( )
( )
0
2
2
sin sin w l j l j
w
w
j
-
=
= + - + - -
= +
=
L
L
R
t
L G G
L L t
L L
L
L
E E
i t I e
Z Z
Z R L
L
atg
R
EQUATION1906 V1 EN (Equation 127)
The line fault current consists of two components:
The steady-state component which magnitude depends on generator voltage
and absolute value of impedance included in the circuit
The transient DC component, which magnitude depends on the fault incident
angle decays with the circuit time constant
[ ]
L L
L R s
EQUATION1907 V1 EN (Equation 128)
Section 3 1MRK505186-UEN D
IED application
190
Application manual
The basic loop differential equation describing the circuit in figure 92 with series
capacitor is presented by equation 129.
( )
2
2
1
( ) cos w w l + + = +
l L
L L L G
L
d i di
L R i t E t
dt dt C
EQUATION1908 V1 EN (Equation 129)
The solution over line current is in this case presented by group of equations 130.
The fault current consists also here from the steady-state part and the transient part.
The difference with non-compensated conditions is that
The total loop impedance decreases for the negative reactance of the series
capacitor, which in fact increases the magnitude of the fault current
The transient part consists of the damped oscillation, which has an angular
frequency b and is dying out with a time constant a
( ) ( ) ( ) [ ]
( )
( ) ( )
( )
1 2
2
2
1 ( 0)
( 0) ( 0)
2
2
sin cos sin
1
sin
sin cos
2
1
sin
2
2
1
4
a
w l j b b
w
w
l j
w
l l j
b
l j
a
b
-
=
= =
= + - + +
= + -
= - -
- - - - -
=
- -
= -
t G
L
SC
SC L L
L
G
L t
SC
G L L
G C t L t
SC
G L L
SC
L
L
L
L L
E
i t K t K t e
Z
Z R L
C
E
K I
Z
E L R
E U I
Z
K
E R L
Z
R
L
R
L C L
2
L
EQUATION1909 V1 EN (Equation 130)
The transient part has an angular frequency b and is damped out with the time-
constant .
The difference in performance of fault currents for a three-phase short circuit at the
end of a typical 500 km long 500 kV line is presented in figure 93.
The short circuit current on a non-compensated line is lower in magnitude, but
comprises at the beginning only a transient DC component, which diminishes
completely in approximately 120ms. The final magnitude of the fault current on
compensated line is higher due to the decreased apparent impedance of a line (60%
1MRK505186-UEN D Section 3
IED application
191
Application manual
compensation degree has been considered for a particular case), but the low
frequency oscillation is also obvious. The increase of fault current immediately
after the fault incidence (on figure 93 at approximately 21ms) is much slower than
on non-compensated line. This occurs due to the energy stored in capacitor before
the fault.
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2
10
5
5
10
t[ms ]
I
[
p
u
]
en06000610.vsd
IEC06000610 V1 EN
Figure 93: Short circuit currents for the fault at the end of 500 km long 500 kV
line without and with SC
Location of instrument transformers
Location of instrument transformers relative to the line end series capacitors plays
an important role regarding the dependability and security of a complete protection
scheme. It is on the other hand necessary to point out the particular dependence of
those protection schemes, which need for their operation information on voltage in
IED point.
Protection schemes with their operating principle depending on current
measurement only, like line current differential protection are relatively
independent on CT location. Figure 94 shows schematically the possible locations
of instrument transformers related to the position of line-end series capacitor.
- jX
C
CT1 CT2
VT1 VT 2
en06000611.vsd
IEC06000611 V1 EN
Figure 94: Possible positions of instrument transformers relative to line end
series capacitor
Bus side instrument transformers
Section 3 1MRK505186-UEN D
IED application
192
Application manual
CT1 and VT1 on figure 94 represent the case with bus side instrument
transformers. The protection devices are in this case exposed to possible voltage
and current inversion for line faults, which decreases the required dependability. In
addition to this may series capacitor cause negative apparent impedance to distance
IEDs on protected and adjacent lines as well for close-in line faults (see also figure
96 LOC=0%), which requires special design of distance measuring elements to
cope with such phenomena. The advantage of such installation is that the
protection zone covers also the series capacitor as a part of protected power line, so
that line protection will detect and cleared also parallel faults on series capacitor.
Line side instrument transformers
CT2 and VT2 on figure 94 represent the case with line side instrument
transformers. The protective devices will not be exposed to voltage and current
inversion for faults on the protected line, which increases the dependability.
Distance protection zone 1 may be active in most applications, which is not the
case when the bus side instrument transformers are used.
Distance IEDs are exposed especially to voltage inversion for close-in reverse
faults, which decreases the security. The effect of negative apparent reactance must
be studied seriously in case of reverse directed distance protection zones used by
distance IEDs for teleprotection schemes. Series capacitors located between the
voltage instruments transformers and the buses reduce the apparent zero sequence
source impedance and may cause voltage as well as current inversion in zero
sequence equivalent networks for line faults. It is for this reason absolutely
necessary to study the possible effect on operation of zero sequence directional
earth-fault overcurrent protection before its installation.
Dual side instrument transformers
Installations with line side CT2 and bus side VT1 are not very common. More
common are installations with line side VT2 and bus side CT1. They appear as de
facto installations also in switchyards with double-bus double-breaker and 1
breaker arrangement. The advantage of such schemes is that the unit protections
cover also for shunt faults in series capacitors and at the same time the voltage
inversion does not appear for faults on the protected line.
Many installations with line-end series capacitors have available voltage
instrument transformers on both sides. In such case it is recommended to use the
VTs for each particular protection function to best suit its specific characteristics
and expectations on dependability and security. The line side VT can for example
be used by the distance protection and the bus side VT by the directional residual
OC earth fault protection.
Apparent impedances and MOV influence
Series capacitors reduce due to their character the apparent impedance measured by
distance IEDs on protected power lines. Figure 95 presents typical locations of
capacitor banks on power lines together with corresponding compensation degrees.
Distance IED near the feeding bus will see in different cases fault on remote end
bus depending on type of overvoltage protection used on capacitor bank (spark gap
or MOV) and SC location on protected power line.
1MRK505186-UEN D Section 3
IED application
193
Application manual
en06000612.vsd
~ E
A
0%
33 %
50%
66 %
K
C
= 80% 33% 33 % 50 %
Z<
100 %
80 %
IEC06000612 V1 EN
Figure 95: Typical locations of capacitor banks on series compensated line
Implementation of spark gaps for capacitor overvoltage protection makes the
picture relatively simple, because they either flash over or not. The apparent
impedance corresponds to the impedance of non-compensated line, as shown in
figure 96 case K
C
= 0%.
en06000613.vsd
j X
R
KC = 0%
KC = 80%
LOC = 0%
KC = 50%
LOC = 50%
j X
j X
R R
KC = 2 x 33%
LOC = 33%, 66%
KC = 80%
LOC = 100%
j Xj X
R R
IEC06000613 V1 EN
Figure 96: Apparent impedances seen by distance IED for different SC
locations and spark gaps used for overvoltage protection
Section 3 1MRK505186-UEN D
IED application
194
Application manual
en06000614.vsd
MOV protected series capacitor
MOV
iL iC
iM
uC
-jXC
0 10 20 30 40 50 60
20
10
10
20
0 10 20 30 40 50 60
100
50
50
100
0 10 20 30 40 50 60
20
10
10
20
0 10 20 30 40 50 60
20
10
10
20
Line current as a function of time Capacitor voltage as a function of time
Capacitor current as a function of time MOV current as a function of time
IEC06000614 V1 EN
Figure 97: MOV protected capacitor with examples of capacitor voltage and
corresponding currents
The impedance apparent to distance IED is always reduced for the amount of
capacitive reactance included between the fault and IED point, when the spark gap
does not flash over, as presented for typical cases in figure 96. Here it is necessary
to distinguish between two typical cases:
Series capacitor only reduces the apparent impedance, but it does not cause
wrong directional measurement. Such cases are presented in figure 96 for 50%
compensation at 50% of line length and 33% compensation located on 33%
and 66% of line length. The remote end compensation has the same effect.
The voltage inversion occurs in cases when the capacitor reactance between
the IED point and fault appears bigger than the corresponding line reactance,
Figure 23, 80% compensation at local end. A voltage inversion occurs in IED
point and the distance IED will see wrong direction towards the fault, if no
special measures have been introduced in its design.
The situation differs when metal oxide varistors (MOV) are used for capacitor
overvoltage protection. MOVs conduct current, for the difference of spark gaps,
only when the instantaneous voltage drop over the capacitor becomes higher than
the protective voltage level in each half-cycle separately, see figure 97.
Extensive studies at Bonneville Power Administration in USA ( ref. Goldsworthy,
D,L A Linearized Model for MOV-Protected series capacitors Paper 86SM357
8 IEEE/PES summer meeting in Mexico City July 1986) have resulted in
1MRK505186-UEN D Section 3
IED application
195
Application manual
construction of a non-linear equivalent circuit with series connected capacitor and
resistor. Their value depends on complete line (fault) current and protection factor
k
p
. The later is defined by equation 131.
=
MOV
p
NC
U
k
U
EQUATION1910 V1 EN (Equation 131)
Where
U
MOV
is the maximum instantaneous voltage expected between the capacitor immediately before
the MOV has conducted or during operation of the MOV, divaded by 2
U
NC
is the rated voltage in RMS of the series capacitor
en06000615.vsd
R
j
X
1
I
R
j
X
2
I
=
R
j
X
10
I
=
Kp In Kp In
Kp In
IEC06000615 V1 EN
Figure 98: Equivalent impedance of MOV protected capacitor in dependence
of protection factor K
P
Figure 98 presents three typical cases for series capacitor located at line end (case
LOC=0% in figure 96).
Series capacitor prevails the scheme as long as the line current remains lower
or equal to its protective current level (I k
p
I
NC
). Line apparent impedance
is in this case reduced for the complete reactance of a series capacitor.
50% of capacitor reactance appears in series with resistance, which
corresponds to approximately 36% of capacitor reactance when the line
current equals two times the protective current level (I 2 k
p
I
NC
). This
information has high importance for setting of distance protection IED reach in
resistive direction, for phase to earth fault measurement as well as for phase to
phase measurement.
Series capacitor becomes nearly completely bridged by MOV when the line
current becomes higher than 10-times the protective current level (I 10 k
p
I
NC
).
Section 3 1MRK505186-UEN D
IED application
196
Application manual
Impact of series compensation on protective IED of adjacent lines
Voltage inversion is not characteristic for the buses and IED points closest to the
series compensated line only. It can spread also deeper into the network and this
way influences the selection of protection devices (mostly distance IEDs) on
remote ends of lines adjacent to the series compensated circuit, and sometimes
even deeper in the network.
en06000616.vsd
~
~
F
B
E
B
E
A
Z
SA
U
A
A
Z
LA
I
A
U
D
D
Z
LB
I
B
U
B
Z
SB
Z
LF
I
F
-jX
C
IEC06000616 V1 EN
Figure 99: Voltage inversion in series compensated network due to fault
current infeed
Voltage at the B bus (as shown in figure 99) is calculated for the loss-less system
according to the equation below.
( ) ( ) = + = + - +
B D B LB A B LF C B LB
U U I jX I I j X X I jX
EQUATION1911 V1 EN (Equation 132)
Further development of equation 132 gives the following expressions:
( ) 1 = + + -
A
B B LB LF C
B
I
U jI X X X
I
EQUATION1912 V1 EN (Equation 133)
( ) 0
1
= = +
+
LB
C B LF
A
B
X
X U X
I
I
EQUATION1913 V1 EN (Equation 134)
Equation 133 indicates the fact that the infeed current I
A
increases the apparent
value of capacitive reactance in system: bigger the infeed of fault current, bigger
the apparent series capacitor in a complete series compensated network. It is
possible to say that equation 134 indicates the deepness of the network to which it
will feel the influence of series compensation through the effect of voltage inversion.
It is also obvious that the position of series capacitor on compensated line
influences in great extent the deepness of voltage inversion in adjacent system.
Line impedance X
LF
between D bus and the fault becomes equal to zero, if the
capacitor is installed near the bus and the fault appears just behind the capacitor.
This may cause the phenomenon of voltage inversion to be expanded very deep
into the adjacent network, especially if on one hand the compensated line is very
1MRK505186-UEN D Section 3
IED application
197
Application manual
long with high degree of compensation, and the adjacent lines are, on the other
hand, relatively short.
Extensive system studies are necessary before final decision is made on
implementation and location of series capacitors in network. It requires to correctly
estimate their influence on performances of (especially) existing distance IEDs. It
is possible that the costs for number of protective devices, which should be
replaced by more appropriate ones due to the effect of applied series compensation,
influences the future position of series capacitors in power network.
Possibilities for voltage inversion at remote buses should not be studied for short
circuits with zero fault resistance only. It is necessary to consider cases with higher
fault resistances, for which spark gaps or MOVs on series capacitors will not
conduct at all. At the same time this kind of investigation must consider also the
maximum sensitivity and possible resistive reach of distance protection devices,
which on the other hand simplifies the problem.
Application of MOVs as non-linear elements for capacitor overvoltage protection
makes simple calculations often impossible. Different kinds of steady-state
network simulations are in such cases unavoidable.
Distance protection
Distance protection due to its basic characteristics, is the most used protection
principle on series compensated and adjacent lines worldwide. It has at the same
time caused a lot of challenges to protection society, especially when it comes to
directional measurement and transient overreach.
Distance IED in fact does not measure impedance or quotient between line current
and voltage. Quantity 1= Operating quantity - Restraing quantity Quantity 2=
Polarizing quantity. Typically Operating quantity is the replica impedance drop.
Restraining quantity is the system voltage Polarizing quantity shapes the
characteristics in different way and is not discussed here.
Distance IEDs comprise in their replica impedance only the replicas of line
inductance and resistance, but they do not comprise any replica of series capacitor
on the protected line and its protection circuits (spark gap and or MOV). This way
they form wrong picture of the protected line and all solutions related to distance
protection of series compensated and adjacent lines are concentrated on finding
some parallel ways, which may help eliminating the basic reason for wrong
measurement. The most known of them are decrease of the reach due to presence
of series capacitor, which apparently decreases the line reactance, and introduction
of permanent memory voltage in directional measurement.
Series compensated and adjacent lines are often the more important links in a
transmission networks and delayed fault clearance is undesirable. This makes it
necessary to install distance protection in combination with telecommunication.
The most common is distance protection in Permissive Overreaching Transfer Trip
mode (POTT).
Section 3 1MRK505186-UEN D
IED application
198
Application manual
Underreaching and overreaching schemes
It is a basic rule that the underreaching distance protection zone should under no
circumstances overreach for the fault at the remote end bus, and the overreaching
zone should always, under all system conditions, cover the same fault. In order to
obtain section selectivity, the first distance (underreaching) protection zone must
be set to a reach less than the reactance of the compensated line in accordance with
figure 100.
en06000618.vsd
X
11
X
12
-j X
C
A B
D
A
D
B
Zone 1
A
Zone 1
B
Zone 2
A
Zone 2
B
G
IEC06000618 V1 EN
Figure 100: Underreaching (Zone 1) and overreaching (Zone 2) on series
compensated line
The underreaching zone will have reduced reach in cases of bypassed series
capacitor, as shown in the dashed line in figure 100. The overreaching zone (Zone
2) can this way cover bigger portion of the protected line, but must always cover
with certain margin the remote end bus. Distance protection Zone 1 is often set to
( )
1 11 12
= + -
Z S C
X K X X X
EQUATION1914 V1 EN (Equation 135)
Here K
S
is a safety factor, presented graphically in figure 101, which covers for
possible overreaching due to low frequency (sub-harmonic) oscillations. Here it
should be noted separately that compensation degree K
C
in figure 101 relates to
total system reactance, inclusive line and source impedance reactance. The same
setting applies regardless MOV or spark gaps are used for capacitor overvoltage
protection.
Equation 135 is applicable for the case when the VTs are located on the bus side of
series capacitor. It is possible to remove X
C
from the equation in cases of VTs
installed in line side, but it is still necessary to consider the safety factor K
S
.
If the capacitor is out of service or bypassed, the reach with these settings can be
less than 50% of protected line dependent on compensation degree and there will
be a section, G in figure 100, of the power line where no tripping occurs from
either end.
1MRK505186-UEN D Section 3
IED application
199
Application manual
en06000619.vsd
K
S
1.0
0.8
0.6
0.4
0.2
0 20 40 60 80 100
K
C
[%]
IEC06000619 V1 EN
Figure 101: Underreaching safety factor K
S
in dependence on system
compensation degree K
C
For that reason permissive underreaching schemes can hardly be used as a main
protection. Permissive overreaching distance protection or some kind of directional
or unit protection must be used.
The overreach must be of an order so it overreaches when the capacitor is bypassed
or out of service. Figure 102 shows the permissive zones. The first underreaching
zone can be kept in the total protection but it only has the feature of a back-up
protection for close up faults. The overreach is usually of the same order as the
permissive zone. When the capacitor is in operation the permissive zone will have
a very high degree of overreach which can be considered as a disadvantage from a
security point of view.
en06000620.vsd
X11
X
12
- jX
C
A B
DA DB
Permissive Zone A
Permissive Zone B
IEC06000620 V1 EN
Figure 102: Permissive overreach distance protection scheme
Negative IED impedance, positive fault current (voltage inversion)
Assume in equation 136
11 11
< < +
C S
X X X X
EQUATION1898 V1 EN (Equation 136)
and in figure 103
a three phase fault occurs beyond the capacitor. The resultant IED impedance seen
from the D
B
IED location to the fault may become negative (voltage inversion)
until the spark gap has flashed.
Distance protections of adjacent power lines shown in figure 103 are influenced by
this negative impedance. If the intermediate infeed of short circuit power by other
lines is taken into consideration, the negative voltage drop on X
C
is amplified and a
Section 3 1MRK505186-UEN D
IED application
200
Application manual
protection far away from the faulty line can maloperate by its instantaneous
operating distance zone, if no precaution is taken. Impedances seen by distance
IEDs on adjacent power lines are presented by equations 137 to 140.
1 2 3
= + + I I I I
EQUATION1915 V1 EN (Equation 137)
( )
1 1 11
1
= - -
F
DA A C
A
I
X X X X
I
EQUATION1916 V1 EN (Equation 138)
( )
2 2 11
2
= - -
F
DA A C
A
I
X X X X
I
EQUATION1917 V1 EN (Equation 139)
( )
3 3 11
3
= - -
F
DA A C
A
I
X X X X
I
EQUATION1918 V1 EN (Equation 140)
en06000621.vsd
B A1
A2
A3
D
B
D
A3
DA2
DA1
jX11
I
A1
I
A2
I
A3
I
F
-jXC
jX
1
jX
2
jX
3
F
IEC06000621 V1 EN
Figure 103: Distance IED on adjacent
power lines are influenced by
the negative impedance
Normally the first zone of this protection must be delayed until the gap flashing has
taken place. If the delay is not acceptable, some directional comparison must also
be added to the protection of all adjacent power lines. As stated above, a good
protection system must be able to operate correctly both before and after gap
flashing occurs. Distance protection can be used, but careful studies must be made
for each individual case. The rationale described applies to both conventional spark
gap and MOV protected capacitors.
Special attention should be paid to selection of distance protection on shorter
adjacent power lines in cases of series capacitors located at the line end. In such
case the reactance of a short adjacent line may be lower than the capacitor
1MRK505186-UEN D Section 3
IED application
201
Application manual
reactance and voltage inversion phenomenon may occur also on remote end of
adjacent lines. Distance protection of such line must have built-in functionality
which applies normally to protection of series compensated lines.
It usually takes a bit of a time before the spark gap flashes, and sometimes the fault
current will be of such a magnitude that there will not be any flashover and the
negative impedance will be sustained. If equation 141
11 11
< < +
C S
X X X X
EQUATION1898 V1 EN (Equation 141)
in figure 104, the fault current will have the same direction as when the capacitor is
bypassed. So, the directional measurement is correct but the impedance measured
is negative and if the characteristic crosses the origin shown in figure 104 the IED
cannot operate. However, if there is a memory circuit designed so it covers the
negative impedance, a three phase fault can be successfully cleared by the distance
protection. As soon as the spark gap has flashed the situation for protection will be
as for an ordinary fault. However, a good protection system should be able to
operate correctly before and after gap flashing occurs.
en06000625.vsd
jX
R
X11
X12
XC
ZS
IEC06000625 V1 EN
Figure 104: Cross-polarized
quadrilateral
characteristic
en06000584_small.vsd
jX
R
X11
X12
XC
ZS
X
F
W
X
R
V
RFW
RRV
IEC06000584-SMALL V1 EN
Figure 105: Quadrilateral
characteristic with
separate impedance
and directional
measurement
If the distance protection is equipped with an earth-fault measuring unit, the
negative impedance occurs when
1_11 0 _11
3 2 > +
C
X X X
EQUATION1919 V1 EN (Equation 142)
Cross-polarized distance protection (either with mho or quadrilateral characteristic)
will normally handle earth-faults satisfactory if the negative impedance occurs
Section 3 1MRK505186-UEN D
IED application
202
Application manual
inside the characteristic. The operating area for negative impedance depends upon
the magnitude of the source impedance and calculations must be made on a case by
case basis, as shown in figure 104. Distance IEDs with separate impedance and
directional measurement offer additional setting and operational flexibility when it
comes to measurement of negative apparent impedance (as shown in figure 105).
Negative IED impedance, negative fault current (current inversion)
If equation 143
S l1
XC X X > +
EQUATION2036 V1 EN (Equation 143)
in figure 90 and a fault occurs behind the capacitor, the resultant reactance
becomes negative and the fault current will have an opposite direction compared
with fault current in a power line without a capacitor (current inversion). The
negative direction of the fault current will persist until the spark gap has flashed.
Sometimes there will be no flashover at all, because the fault current is less than
the setting value of the spark gap. The negative fault current will cause a high
voltage on the network. The situation will be the same even if a MOV is used.
However, depending upon the setting of the MOV, the fault current will have a
resistive component.
The problems described here are accentuated with a three phase or phase-to-phase
fault, but the negative fault current can also exist for a single-phase fault. The
condition for a negative current in case of an earth fault can be written as follows:
1_ 1 0 _ 1 0 _ 1_
3 2 2 > + + +
C L L S S
X X X X X
EQUATION1920 V1 EN (Equation 144)
All designations relates to figure 90. A good protection system must be able to
cope with both positive and negative direction of the fault current, if such
conditions can occur. A distance protection cannot operate for negative fault
current. The directional element gives the wrong direction. Therefore, if a problem
with negative fault current exists, distance protection is not a suitable solution. In
practice, negative fault current seldom occurs. In normal network configurations
the gaps will flash in this case.
Double circuit, parallel operating series compensated lines
Two parallel power lines running in electrically close vicinity to each other and
ending at the same busbar at both ends (as shown in figure 106) causes some
challenges for distance protection because of the mutual impedance in the zero
sequence system. The current reversal phenomenon also raises problems from the
protection point of view, particularly when the power lines are short and when
permissive overreach schemes are used.
1MRK505186-UEN D Section 3
IED application
203
Application manual
en06000627.vsd
-jXC
-jXC
ZAC ZCB
ZAC ZCB
A B
Zm0AC Zm0CB
IEC06000627 V1 EN
Figure 106: Double circuit, parallel operating line
Zero sequence mutual impedance Z
m0
cannot significantly influence the operation
of distance protection as long as both circuits are operating in parallel and all
precautions related to settings of distance protection on series compensated line
have been considered. Influence of disconnected parallel circuit, which is earthed
at both ends, on operation of distance protection on operating circuit is known.
Series compensation additionally exaggerates the effect of zero sequence mutual
impedance between two circuits, see figure 107. It presents a zero sequence
equivalent circuit for a fault at B bus of a double circuit line with one circuit
disconnected and earthed at both IEDs. The effect of zero sequence mutual
impedance on possible overreaching of distance IEDs at A bus is increased
compared to non compensated operation, because series capacitor does not
compensate for this reactance. The reach of underreaching distance protection zone
1 for phase-to-earth measuring loops must further be decreased for such operating
conditions.
en06000628.vsd
jX
m0
j(X0L-Xm0)
j(X
0L
-X
m0
)
-jXC
-jXC
A B
IEC06000628 V1 EN
Figure 107: Zero sequence equivalent circuit of a series compensated double
circuit line with one circuit disconnected and earthed at both IEDs
Zero sequence mutual impedance may disturb also correct operation of distance
protection for external evolving faults, when one circuit has already been
disconnected in one phase and runs non-symmetrical during dead time of single
pole autoreclosing cycle. All such operating conditions must carefully be studied in
advance and simulated by dynamic simulations in order to fine tune settings of
distance IEDs.
If the fault occurs in point F of the parallel operating circuits, as presented in figure
108, than also one distance IED (operating in POTT teleprotection scheme) on
parallel, healthy circuit will send a carrier signal CSAB to the remote line end,
where this signal will be received as a carrier receive signal CRBB.
Section 3 1MRK505186-UEN D
IED application
204
Application manual
en06000629.vsd
RAA RBA I
FC1
I
FC1
F
RAB RBB I
FC2
CSAB CRBB
RAA RBA I
FC1
F
RAB RBB I
FC2
CSAB CRBB
IEC06000629 V1 EN
Figure 108: Current reversal phenomenon on parallel operating circuits
It is possible to expect faster IED operation and breaker opening at the bus closer
to fault, which will reverse the current direction in healthy circuit. Distance IED
RBB will suddenly detect fault in forward direction and, if CRBB signal is still
present due to long reset time of IED RAB and especially telecommunication
equipment, trip its related circuit breaker, since all conditions for POTT have been
fulfilled. Zero sequence mutual impedance will additionally influence this process,
since it increases the magnitude of fault current in healthy circuit after the opening
of first circuit breaker. The so called current reversal phenomenon may cause
unwanted operation of protection on healthy circuit and this way endangers even
more the complete system stability.
To avoid the unwanted tripping, some manufacturers provide a feature in their
distance protection which detects that the fault current has changed in direction and
temporarily blocks distance protection. Another method employed is to temporarily
block the signals received at the healthy line as soon as the parallel faulty line
protection initiates tripping. The second mentioned method has an advantage in
that not the whole protection is blocked for the short period. The disadvantage is
that a local communication is needed between two protection devices in the
neighboring bays of the same substation.
Distance protection used on series compensated lines must have a high overreach
to cover the whole transmission line also when the capacitors are bypassed or out
of service. When the capacitors are in service, the overreach will increase
tremendously and the whole system will be very sensitive for false teleprotection
signals. Current reversal difficulties will be accentuated because the ratio of mutual
impedance against self-impedance will be much higher than for a non-compensated
line.
If non-unit protection is to be used in a directional comparison mode, schemes
based on negative sequence quantities offer the advantage that they are insensitive
to mutual coupling. However, they can only be used for phase-to-earth and phase-to-
phase faults. For three-phase faults an additional protection must be provided.
3.6.2.2 Setting guidelines
General
The settings for the distance protection function are done in primary values. The
instrument transformer ratio that has been set for the analog input card is used to
automatically convert the measured secondary input signals to primary values used
in the distance protection function.
1MRK505186-UEN D Section 3
IED application
205
Application manual
The following basics should be considered, depending on application, when doing
the setting calculations:
Errors introduced by current and voltage instrument transformers, particularly
under transient conditions.
Inaccuracies in the line zero-sequence impedance data, and their effect on the
calculated value of the earth-return compensation factor.
The effect of infeed between the IED and the fault location, including the
influence of different Z0/Z1 ratios of the various sources.
The phase impedance of non transposed lines is not identical for all fault
loops. The difference between the impedances for different phase-to-earth
loops can be as large as 5-10% of the total line impedance.
The effect of a load transfer between the IEDs of the protected fault resistance
is considerable, the effect must be recognized.
Zero-sequence mutual coupling from parallel lines.
Setting of zone1
The different errors mentioned earlier usually require a limitation of the
underreaching zone (normally zone 1) to 75 - 90% of the protected line.
In case of parallel lines, consider the influence of the mutual coupling according to
section "Parallel line application with mutual coupling" and select the case(s) that
are valid in your application. We recommend to compensate setting for the cases
when the parallel line is in operation, out of service and not earthed and out of
service and earthed in both ends. The setting of earth fault reach should be selected
to be <85% also when parallel line is out of service and earthed at both ends (worst
case).
Setting of overreaching zone
The first overreaching zone (normally zone2) must detect faults on the whole
protected line. Considering the different errors that might influence the
measurement in the same way as for zone1, it is necessary to increase the reach of
the overreaching zone to at least 120% of the protected line. The zone2 reach can
be even higher if the fault infeed from adjacent lines at remote end are considerable
higher than the fault current at the IED location.
The setting must not exceed 80% of the following impedances:
The impedance corresponding to the protected line, plus the first zone reach of
the shortest adjacent line.
The impedance corresponding to the protected line, plus the impedance of the
maximum number of transformers operating in parallel on the bus at the
remote end of the protected line.
If the requirements in the bulletlisted paragraphs above gives a zone2 reach less
than 120%, the time delay of zone2 must be increased by approximately 200ms to
avoid unwanted operation in cases when the telecommunication for the short
adjacent line at remote end is down during faults. The zone2 must not be reduced
Section 3 1MRK505186-UEN D
IED application
206
Application manual
below 120% of the protected line section. The whole line must be covered under all
conditions.
The requirement that the zone 2 shall not reach more than 80% of the shortest
adjacent line at remote end is highlighted with a simple example below.
If a fault occurs at point F (as shown in figure 109, also for the explanation of all
abbreviations used), the IED at point A senses the impedance:
ZAF = ZAC + ZCF = ZAC + (1+ ) ZCF
IB
IA
IA + IB
IA
EQUATION302 V2 EN (Equation 145)
A B
Z<
C IA
I
B
Z AC Z CD
Z CF
I A+IB
en05000457.vsd
IEC05000457 V1 EN
Figure 109:
Setting of reverse zone
The reverse zone is applicable for purposes of scheme communication logic,
current reversal logic, weak-end-infeed logic, and so on. The same applies to the back-
up protection of the bus bar or power transformers. It is necessary to secure, that it
always covers the overreaching zone, used at the remote line IED for the
telecommunication purposes.
Consider the possible enlarging factor that might exist due to fault infeed from
adjacent lines. Equation 146 can be used to calculate the reach in reverse direction
when the zone is used for blocking scheme, weak-end infeed and so on.
Zrev 1.2 ZL Z2rem
EQUATION1525 V3 EN (Equation 146)
Where:
ZL is the protected line impedance
Z2rem is zone2 setting at remote end of protected line.
1MRK505186-UEN D Section 3
IED application
207
Application manual
In some applications it might be necessary to consider the enlarging factor due to
fault current infeed from adjacent lines in the reverse direction to obtain certain
sensitivity.
Series compensated and adjacent lines
Directional control
The directional function (ZDSRDIR) which is able to cope with the condition at
voltage reversal, shall be used in all IEDs with conventional distance protection
(ZMCPDIS,ZMCAPDIS). This function is necessary in the protection on
compensated lines as well as all non-compensated lines connected to this busbar
(adjacent lines). All protections that can be exposed to voltage reversal must have
the special directional function, including the protections on busbar where the
voltage can be reversed by series compensated lines not terminated to this busbar.
The directional function is controlled by faulty phase criteria. These criteria must
identify all forward and reverse faults that can cause voltage reversal. Setting of the
corresponding reach of the impedance measuring elements is separate for reactive
and resistive reach and independent of each other for phase-to-earth and for phase-
to-phase measurement.
It is also necessary to consider the minimum load impedance limiting conditions:
Setting of zone 1
A voltage reversal can cause an artificial internal fault (voltage zero) on faulty line
as well as on the adjacent lines. This artificial fault always have a resistive
component, this is however small and can mostly not be used to prevent tripping of
a healthy adjacent line.
An independent tripping zone 1 facing a bus which can be exposed to voltage
reversal have to be set with reduced reach with respect to this false fault. When the
fault can move and pass the bus, the zone 1 in this station must be blocked.
Protection further out in the net must be set with respect to this apparent fault as the
protection at the bus.
Different settings of the reach for the zone (ZMCPDIS) characteristic in forward
and reverse direction makes it possible to optimize the settings in order to
maximize dependability and security for independent zone1.
Due to the sub-harmonic oscillation swinging caused by the series capacitor at fault
conditions the reach of the under-reaching zone 1 must be further reduced. Zone 1
can only be set with a percentage reach to the artificial fault according to the curve
in 110
Section 3 1MRK505186-UEN D
IED application
208
Application manual
99000202.vsd
p
100
80
60
40
20
0
100 % 80 60 40 20
C
%
IEC99000202 V1 EN
Figure 110: Reduced reach due to the expected sub-harmonic oscillations at
different degrees of compensation
c
l
X
c degreeof compensation
X
=
EQUATION1894 V1 EN (Equation 147)
X
c
is the reactance of the series capacitor
p is the maximum allowable reach for an under-reaching zone with respect to the sub-
harmonic swinging related to the resulting fundamental frequency reactance the
zone is not allowed to over-reach.
The degree of compensation C in figure 110 has to be interpreted as the relation
between series capacitor reactance X
C
and the total positive sequence reactance X1
to the driving source to the fault. If only the line reactance is used the degree of
compensation will be too high and the zone 1 reach unnecessary reduced. The
highest degree of compensation will occur at three phase fault and therefore the
calculation need only to be performed for three phase faults.
The compensation degree in earth return path is different than in phases. It is for
this reason possible to calculate a compensation degree separately for the phase-to-
phase and three-phase faults on one side and for the single phase-to-earth fault
loops on the other side. Different settings of the reach for the ph-ph faults and ph-E
loops makes it possible to minimise the necessary decrease of the reach for
different types of faults.
1MRK505186-UEN D Section 3
IED application
209
Application manual
Reactive Reach
Compensated lines with the capacitor into the zone 1 reach :
X
C
A
X
LLOC
X
L
B
en07000063.vsd
IEC07000063 V1 EN
Figure 111: Simplified single line diagram of series capacitor located at X
LLOC
ohm from A station
Section 3 1MRK505186-UEN D
IED application
210
Application manual
jX
R
X
11
X
12
X
C
ZS
X
F
W
X
R
V
RFW
R
RV
Z
S
en06000584.vsd
IEC06000584 V1 EN
Figure 112: Measured impedance at voltage inversion
Forward direction:
Where
X
LLoc
equals line reactance up to the series capacitor(in the
picture approximate 33% of XLine)
X1 is set to (XLindex-XC) p/100.
p is defined according to figure 110
1,2 is safety factor for fast operation of Zone 1
Compensated line with the series
capacitor not into the reach of zone 1.
The setting is thus:
X1 is set to (XLine-XC) p/100.
When the calculation of XFw gives a negative value the zone 1
must be permanently blocked.
For protection on non compensated lines facing series capacitor on next line. The
setting is thus:
1MRK505186-UEN D Section 3
IED application
211
Application manual
X1 is set to (XLine-XC K) p/100.
K equals side infeed factor at next busbar.
When the calculation of XFw gives a negative value the zone 1
must be permanently blocked.
Fault resistance
The resistive reach is, for all affected applications, restricted by the set reactive
reach and the load impedance and same conditions apply as for a non-compensated
network.
However, special notice has to be taken during settings calculations due to the ZnO
because 50% of capacitor reactance appears in series with resistance, which
corresponds to approximately 36% of capacitor reactance when the line current
equals two times the protective current level. This information has high importance
for setting of distance protection IED reach in resistive direction, for phase to
earth- fault measurement as well as, for phase-to-phase measurement.
Overreaching zone 2
In series compensated network where independent tripping zones will have reduced
reach due to the negative reactance in the capacitor and the sub-harmonic swinging
the tripping will to a high degree be achieved by the communication scheme.
With the reduced reach of the under-reaching zones not providing effective
protection for all faults along the length of the line, it becomes essential to provide
over-reaching schemes like permissive overreach transfer trip (POTT) or blocking
scheme can be used.
Thus it is of great importance that the zone 2 can detect faults on the whole line
both with the series capacitor in operation and when the capacitor is bridged (short
circuited). It is supposed also in this case that the reactive reach for phase-to-phase
and for phase-to-earth faults is the same. The X1Fw, for all lines affected by the
series capacito, are set to:
X1 >= 1,5 XLine
The safety factor of 1.5 appears due to speed requirements and possible under
reaching caused by the sub harmonic oscillations.
The increased reach related to the one used in non compensated system is
recommended for all protections in the vicinity of series capacitors to compensate
for delay in the operation caused by the sub harmonic swinging.
Settings of the resistive reaches are limited according to the minimum load
impedance.
Section 3 1MRK505186-UEN D
IED application
212
Application manual
Reverse zone
The reverse zone that is normally used in the communication schemes for functions
like fault current reversal logic, weak-in-feed logic or issuing carrier send in
blocking scheme must detect all faults in the reverse direction which is detected in
the opposite IED by the overreaching zone 2. The maximum reach for the
protection in the opposite IED can be achieved with the series capacitor in operation.
The reactive reach can be set according to the following formula:
X1=1.3X1
2Rem
-0.5(X1
L
-X
C
)
Settings of the resistive reaches are according to the minimum load impedance:
Optional higher distance protection zones
When some additional distance protection zones (zone 4, for example) are used
they must be set according to the influence of the series capacitor.
Setting of zones for parallel line application
Parallel line in service Setting of zone1
With reference to section "Parallel line application with mutual coupling", the
zone reach can be set to 85% of protected line.
Parallel line in service setting of zone2
Overreaching zones (in general, zones 2 and 3) must overreach the protected circuit
in all cases. The greatest reduction of a reach occurs in cases when both parallel
circuits are in service with a single phase-to-earth fault located at the end of a
protected line. The equivalent zero-sequence impedance circuit for this case is
equal to the one in figure 69 in section "Parallel line in service".
The components of the zero-sequence impedance for the overreaching zones must
be equal to at least:
R
0E
R
0
R
m0
+ =
EQUATION553 V1 EN (Equation 148)
X
0E
X
0
X
m0
+ =
EQUATION554 V1 EN (Equation 149)
Check the reduction of a reach for the overreaching zones due to the effect of the
zero sequence mutual coupling. The reach is reduced for a factor:
0
0 1
2 1 0
m
f
Z
K
Z Z R
= -
+ +
EQUATION1426 V1 EN (Equation 150)
If the denominator in equation 150 is called B and Z0m is simplified to X0m, then
the real and imaginary part of the reach reduction factor for the overreaching zones
can be written as:
1MRK505186-UEN D Section 3
IED application
213
Application manual
2 2
0 Im( )
Re( 0) 1
Re( ) Im( )
X m B
K
B B
= -
+
EQUATION1427 V1 EN (Equation 151)
2 2
0 Re( )
Im( 0) 1
Re( ) Im( )
X m B
K
B B
= -
+
EQUATION1428 V1 EN (Equation 152)
Parallel line is out of service and earthed in both ends
Apply the same measures as in the case with a single set of setting parameters. This
means that an underreaching zone must not overreach the end of a protected circuit
for the single phase-to-earth-faults. Set the values of the corresponding zone (zero-
sequence resistance and reactance) equal to:
R
0E
R
0
1
X
m0
2
R
0
2
X
0
2
+
-------------------------- +
=
EQUATION561 V1 EN (Equation 153)
X
0E
X
0
1
X
m0
2
R
0
2
X
0
2
+
--------------------------
=
EQUATION562 V1 EN (Equation 154)
Setting of reach in resistive direction
Set the resistive reach independently for each zone, and separately for phase-to-
phase (R1PP), and phase-to-earth loop (R1PE) measurement.
Set separately the expected fault resistance for phase-to-phase faults (R1PP) and
for the phase-to-earth faults (RFPE) for each zone. Set all remaining reach setting
parameters independently of each other for each distance zone.
The final reach in resistive direction for phase-to-earth fault loop measurement
automatically follows the values of the line-positive and zero-sequence resistance,
and at the end of the protected zone is equal to equation 155.
R
1
3
--- 2 R1PE R0PE + ( ) RFPE + =
EQUATION567 V1 EN (Equation 155)
2 X1PE+X0
arctan
2 R1PE+R0
loop j
=
EQUATION1457 V1 EN (Equation 156)
Setting of the resistive reach for the underreaching zone1 must follow the
following condition:
Section 3 1MRK505186-UEN D
IED application
214
Application manual
4.5 1 RFPE X
EQUATION569 V2 EN (Equation 157)
The fault resistance for phase-to-phase faults is normally quite low, compared to
the fault resistance for phase-to-earth faults. Limit the setting of the zone1 reach in
resistive direction for phase-to-phase loop measurement to:
3 1 RFPP X
EQUATION570 V2 EN (Equation 158)
Load impedance limitation, without load encroachment function
The following instructions is valid when the load encroachment function is not
activated, which is done by setting the parameter Rld for the Phase Selector to its
upper limit. If the load encroachment function is to be used for all or some of the
measuring zones, the load limitation for those zones according to this chapter can
be omitted. Check the maximum permissible resistive reach for any zone to ensure
that there is a sufficient setting margin between the IED boundary and the
minimum load impedance. The minimum load impedance (/phase) is calculated as:
Z
loadmin
U
2
S
------- =
EQUATION571 V1 EN (Equation 159)
Where:
U is the minimum phase-to-phase voltage in kV
S is the maximum apparent power in MVA.
The load impedance [/phase] is a function of the minimum operation voltage and
the maximum load current:
Z
load
U
min
3 I
max
---------------------- =
EQUATION574 V1 EN (Equation 160)
Minimum voltage Umin and maximum current Imax are related to the same
operating conditions. Minimum load impedance occurs normally under emergency
conditions.
Because a safety margin is required to avoid load encroachment
under three-phase conditions and to guarantee correct healthy phase
IED operation under combined heavy three-phase load and earth
faults, consider both: phase-to-phase and phase-to-earth fault
operating characteristics.
1MRK505186-UEN D Section 3
IED application
215
Application manual
To avoid load encroachment for the phase-to-earth measuring elements, the set
resistive reach of any distance protection zone must be less than 80% of the
minimum load impedance.
RFPE 0.8 Z
load
EQUATION792 V1 EN (Equation 161)
This equation is applicable only when the loop characteristic angle for the single
phase-to-earth faults is more than three times as large as the maximum expected load-
impedance angle. More accurate calculations are necessary according to the
equation below:
min
2 1 0
0.8 cos sin
2 1 0
load
R R
RFPE Z
X X
+
-
+
EQUATION578 V3 EN (Equation 162)
Where:
is a maximum load-impedance angle, related to the minimum load impedance conditions.
To avoid load encroachment for the phase-to-phase measuring elements, the set
resistive reach of any distance protection zone must be less than 160% of the
minimum load impedance.
RFPP 1.6 Zload
load
1.6 Z RFPP
EQUATION579 V2 EN (Equation 163)
Equation 163 is applicable only when the loop characteristic angle for the phase-to-
phase faults is more than three times as large as the maximum expected load-
impedance angle. More accurate calculations are necessary according to
equation 164.
RFPP 1.6 Z
loadmin
cosJ
R1PP
X1PP
--------------- sinJ
EQUATION580 V1 EN (Equation 164)
All this is applicable for all measuring zones when no power swing detection
element is in the protection scheme. Use an additional safety margin of
approximately 20% in cases when a power swing detection element is in the
protection scheme, refer to the description of Power swing detection (ZMRPSB)
function.
Section 3 1MRK505186-UEN D
IED application
216
Application manual
Load impedance limitation, with load encroachment function activated
The parameters for load encroachment shaping of the characteristic are found in the
description of the phase selection with load encroachment function, section
"Setting guidelines". If the characteristic for the impedance measurement is shaped
with the load encroachment algorithm, the parameter RLdFw and the
corresponding load angle ArgLd must be set according to the minimum load
impedance.
Setting of minimum operating currents
The operation of the distance function can be blocked if the magnitude of the
currents is below the set value of the parameter IMinOpPP and IMinOpPE.
The default setting of IMinOpPP and IMinOpPE is 20% of IBase where IBase is
the chosen base current for the analog input channels. The value has been proven in
practice to be suitable in most of the applications. However, there might be
applications where it is necessary to increase the sensitivity by reducing the
minimum operating current down to 10% of IED base current. This happens
especially in cases, when the IED serves as a remote back-up protection on series
of very long transmission lines.
If the load current compensation is activated, there is an additional criteria
IMinOpIN that will block the phase-earth loop if the 3I0<IMinOpIN. The default
setting of IMinOpIN is 5% of the IED base current IBase.
The minimum operating fault current is automatically reduced to 75% of its set
value, if the distance protection zone has been set for the operation in reverse
direction.
Setting of timers for distance protection zones
The required time delays for different distance-protection zones are independent of
each other. Distance protection zone1 can also have a time delay, if so required for
selectivity reasons. One can set the time delays for all zones (basic and optional) in
a range of 0 to 60 seconds. The tripping function of each particular zone can be
inhibited by setting the corresponding Operation parameter to Off. Different time
delays are possible for the ph-E (tPE) and for the ph-ph (tPP) measuring loops in
each distance protection zone separately, to further increase the total flexibility of a
distance protection.
3.6.2.3 Setting parameters
Settings for ZMCPDIS are valid for zone 1, while settings for
ZMCAPDIS are valid for zone 2 - 5
1MRK505186-UEN D Section 3
IED application
217
Application manual
Table 51: ZMCPDIS Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - On Operation Off / On
IBase 1 - 99999 A 1 3000 Base current, i.e. rated current
UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage, i.e. rated voltage
OperationDir Off
Non-directional
Forward
Reverse
- - Forward Operation mode of directionality NonDir /
Forw / Rev
OperationPP Off
On
- - On Operation mode Off / On of Phase-
Phase loops
X1FwPP 0.50 - 3000.00 ohm/p 0.01 30.00 Positive sequence reactance reach, Ph-
Ph, forward
R1PP 0.10 - 1000.00 ohm/p 0.01 5.00 Positive seq. resistance for characteristic
angle, Ph-Ph
RFFwPP 1.00 - 3000.00 ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, forward
X1RvPP 0.50 - 3000.00 ohm/p 0.01 30.00 Positive sequence reactance reach, Ph-
Ph, reverse
RFRvPP 1.00 - 3000.00 ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, reverse
Timer tPP Off
On
- - On Operation mode Off / On of Zone timer,
Ph-Ph
tPP 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-Ph
OperationPE Off
On
- - On Operation mode Off / On of Phase-Earth
loops
X1FwPE 0.50 - 3000.00 ohm/p 0.01 30.00 Positive sequence reactance reach, Ph-
E, forward
R1PE 0.10 - 1000.00 ohm/p 0.01 5.00 Positive seq. resistance for characteristic
angle, Ph-E
X0PE 0.50 - 9000.00 ohm/p 0.01 100.00 Zero sequence reactance reach, Ph-E
R0PE 0.50 - 3000.00 ohm/p 0.01 47.00 Zero seq. resistance for zone
characteristic angle, Ph-E
RFFwPE 1.00 - 9000.00 ohm/l 0.01 100.00 Fault resistance reach, Ph-E, forward
X1RvPE 0.50 - 3000.00 ohm/p 0.01 30.00 Positive sequence reactance reach, Ph-
E, reverse
RFRvPE 1.00 - 9000.00 ohm/l 0.01 100.00 Fault resistance reach, Ph-E, reverse
Timer tPE Off
On
- - On Operation mode Off / On of Zone timer,
Ph-E
tPE 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-E
IMinOpPP 10 - 30 %IB 1 20 Minimum operate delta current for Phase-
Phase loops
IMinOpPE 10 - 30 %IB 1 20 Minimum operate phase current for
Phase-Earth loops
IMinOpIN 5 - 30 %IB 1 5 Minimum operate residual current for
Phase-Earth loops
Section 3 1MRK505186-UEN D
IED application
218
Application manual
Table 52: ZMCAPDIS Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - On Operation Off / On
IBase 1 - 99999 A 1 3000 Base current, i.e. rated current
UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage, i.e. rated voltage
OperationDir Off
Non-directional
Forward
Reverse
- - Forward Operation mode of directionality NonDir /
Forw / Rev
OperationPP Off
On
- - On Operation mode Off / On of Phase-
Phase loops
X1FwPP 0.50 - 3000.00 ohm/p 0.01 30.00 Positive sequence reactance reach, Ph-
Ph, forward
R1PP 0.10 - 1000.00 ohm/p 0.01 5.00 Positive seq. resistance for characteristic
angle, Ph-Ph
RFFwPP 1.00 - 3000.00 ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, forward
X1RvPP 0.50 - 3000.00 ohm/p 0.01 30.00 Positive sequence reactance reach, Ph-
Ph, reverse
RFRvPP 1.00 - 3000.00 ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, reverse
Timer tPP Off
On
- - On Operation mode Off / On of Zone timer,
Ph-Ph
tPP 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-Ph
OperationPE Off
On
- - On Operation mode Off / On of Phase-Earth
loops
X1FwPE 0.50 - 3000.00 ohm/p 0.01 30.00 Positive sequence reactance reach, Ph-
E, forward
R1PE 0.10 - 1000.00 ohm/p 0.01 5.00 Positive seq. resistance for characteristic
angle, Ph-E
X0PE 0.50 - 9000.00 ohm/p 0.01 100.00 Zero sequence reactance reach, Ph-E
R0PE 0.50 - 3000.00 ohm/p 0.01 47.00 Zero seq. resistance for zone
characteristic angle, Ph-E
RFFwPE 1.00 - 9000.00 ohm/l 0.01 100.00 Fault resistance reach, Ph-E, forward
X1RvPE 0.50 - 3000.00 ohm/p 0.01 30.00 Positive sequence reactance reach, Ph-
E, reverse
RFRvPE 1.00 - 9000.00 ohm/l 0.01 100.00 Fault resistance reach, Ph-E, reverse
Timer tPE Off
On
- - On Operation mode Off / On of Zone timer,
Ph-E
tPE 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-E
IMinOpPP 10 - 30 %IB 1 20 Minimum operate delta current for Phase-
Phase loops
IMinOpPE 10 - 30 %IB 1 20 Minimum operate phase current for
Phase-Earth loops
1MRK505186-UEN D Section 3
IED application
219
Application manual
Table 53: ZDSRDIR Group settings (basic)
Name Values (Range) Unit Step Default Description
OperationSC NoSeriesComp
SeriesComp
- - SeriesComp Special directional criteria for voltage
reversal
IBase 1 - 99999 A 1 3000 Base setting for current level
UBase 0.05 - 2000.00 kV 0.05 400.00 Base setting for voltage level
IMinOpPE 5 - 30 %IB 1 5 Minimum operate phase current for
Phase-Earth loops
IMinOpPP 5 - 30 %IB 1 10 Minimum operate delta current for Phase-
Phase loops
ArgNegRes 90 - 175 Deg 1 130 Angle of blinder in second quadrant for
forward direction
ArgDir 5 - 45 Deg 1 15 Angle of blinder in fourth quadrant for
forward direction
INReleasePE 10 - 100 %IPh 1 20 3I0 limit for releasing phase-to-earth
measuring loops
INBlockPP 10 - 100 %IPh 1 40 3I0 limit for blocking phase-to-phase
measuring loops
OperationLdCh Off
On
- - On Operation of load discrimination
characteristic
RLdFw 1.00 - 3000.00 ohm/p 0.01 80.00 Forward resistive reach within the load
impedance area
RLdRv 1.00 - 3000.00 ohm/p 0.01 80.00 Reverse resistive reach within the load
impedance area
ArgLd 5 - 70 Deg 1 30 Load angle determining the load
impedance area
X1FwPP 0.50 - 3000.00 ohm/p 0.01 40.00 Positive sequence reactance reach, Ph-
Ph, forward
R1PP 0.10 - 1000.00 ohm/p 0.01 7.00 Positive seq. resistance for characteristic
angle, Ph-Ph
RFFwPP 0.50 - 3000.00 ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, forward
X1RvPP 0.50 - 3000.00 ohm/p 0.01 40.00 Positive sequence reactance reach, Ph-
Ph, reverse
RFRvPP 0.50 - 3000.00 ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, reverse
X1FwPE 0.50 - 3000.00 ohm/p 0.01 40.00 Positive sequence reactance reach, Ph-
E, forward
R1PE 0.10 - 1000.00 ohm/p 0.01 7.00 Positive seq. resistance for characteristic
angle, Ph-E
X0FwPE 0.50 - 9000.00 ohm/p 0.01 120.00 Zero sequence reactance reach, Ph-E,
forward
R0PE 0.50 - 3000.00 ohm/p 0.01 20.00 Zero seq. resistance for zone
characteristic angle, Ph-E
RFFwPE 1.00 - 9000.00 ohm/l 0.01 100.00 Fault resistance reach, Ph-E, forward
X1RvPE 0.50 - 3000.00 ohm/p 0.01 40.00 Positive sequence reactance reach, Ph-
E, reverse
X0RvPE 0.50 - 9000.00 ohm/p 0.01 120.00 Zero sequence reactance reach, Ph-E,
reverse
RFRvPE 1.00 - 9000.00 ohm/l 0.01 100.00 Fault resistance reach, Ph-E, reverse
Section 3 1MRK505186-UEN D
IED application
220
Application manual
3.6.3 Phase selection, quadrilateral characteristic with fixed
angle FDPSPDIS
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Phase selection with load
encroachment, quadrilateral
characteristic
FDPSPDIS
Z<phs
SYMBOL-DD V1 EN
21
3.6.3.1 Application
The operation of transmission networks today is in many cases close to the stability
limit. The ability to accurately and reliably classify the different types of fault, so
that single pole tripping and autoreclosing can be used plays an important role in
this matter. Phase selection with load encroachment function FDPSPDIS is
designed to accurately select the proper fault loop in the distance measuring
function depending on the fault type.
The heavy load transfer that is common in many transmission networks may in
some cases be in opposite to the wanted fault resistance coverage. Therefore, the
function has a built in algorithm for load encroachment, which gives the possibility
to enlarge the resistive setting of both the Phase selection with load encroachment
and the measuring zones without interfering with the load.
The extensive output signals from FDPSPDIS give also important information
about faulty phase(s), which can be used for fault analysis.
3.6.3.2 Setting guidelines
The following setting guideline consider normal overhead lines applications where
loop and line is greater than 60.
Load encroachment characteristics
The phase selector must at least cover the overreaching zone 2 in order to achieve
correct phase selection for utilizing single-phase autoreclosing for faults on the
entire line. It is not necessary to cover all distance protection zones. A safety
margin of at least 10% is recommended. In order to get operation from distance
zones , the phase selection outputs STCNDZ or STCNDI must be connected to
input STCND on ZMQPDIS, distance measuring block.
For normal overhead lines, the angle for the loop impedance for phase-to-earth
fault is defined according to equation 165.
L
L
X1
arctan
R1
+
j =
+
XN
RN
EQUATION2115 V1 EN (Equation 165)
1MRK505186-UEN D Section 3
IED application
221
Application manual
In some applications, for instance cable lines, the angle of the loop might be less
than 60. In these applications, the settings of fault resistance coverage in forward
and reverse direction, RFFwPE and RFRvPE for phase-to-earth faults and
RFFwPP and RFRvPP for phase-to-phase faults have to be increased to avoid that
FDPSPDIS characteristic shall cut off some part of the zone characteristic. The
necessary increased setting of the fault resistance coverage can be derived from
trigonometric evaluation of the basic characteristic for respectively fault type.
Phase-to-earth fault in forward direction
With reference to figure 113, the following equations for the setting calculations
can be obtained.
Index PHS in images and equations reference settings for Phase
selection with load encroachment function FDPSPDIS and index
Zm reference settings for Distance protection function (ZMQPDIS).
Section 3 1MRK505186-UEN D
IED application
222
Application manual
R
X
60
60
1
2
3 5
6 6
6
6
7
7
8
8
4
IEC09000043_1_en.vsd
W ( / loop)
W ( / loop)
4 3 5
IEC09000043 V1 EN
Figure 113: Relation between distance protection ZMQPDIS and FDPSPDIS
for phase-to-earth fault loop>60 (setting parameters in italic)
1 FDPSPDIS (red line)
2 ZMQPDIS
3 RFRvPE
PHS
4 (X1
PHS
+XN)/tan(60)
5 RFFwPE
PHS
6 RFPE
Zm
7 X1
PHS
+XN
8 loop
9 X1
ZM
+XN
Reactive reach
The reactive reach in forward direction must as minimum be set to cover the
measuring zone used in the Teleprotection schemes, mostly zone 2. Equation 166
and equation 167 gives the minimum recommended reactive reach.
1MRK505186-UEN D Section 3
IED application
223
Application manual
PHS Zm
X1 1.44 X1
EQUATION1309 V1 EN (Equation 166)
PHS Zm
X0 1.44 X0
EQUATION1310 V1 EN (Equation 167)
where:
X1
Zm
is the reactive reach for the zone to be covered by FDPSPDIS, and the constant
1.44 is a safety margin
X0
Zm
is the zero-sequence reactive reach for the zone to be covered by FDPSPDIS
The reactive reach in reverse direction is automatically set to the same reach as for
forward direction. No additional setting is required.
Fault resistance reach
The resistive reach must cover RFPE for the overreaching zone to be covered,
mostly zone 2. Consider the longest overreaching zone if correct fault selection is
important in the application. Equation 168 gives the minimum recommended
resistive reach.
min
1.1
zm
RFFwPE RFPE
EQUATION1312 V2 EN (Equation 168)
where:
RFPE
Zm
is the setting RFPE for the longest overreaching zone to be covered by FDPSPDIS .
The security margin has to be increased to at least 1.2 in the case where
loop<60 to avoid that FDPSPDIS characteristic shall cut off some part of the
zone measurement characteristic.
Phase-to-earth fault in reverse direction
Reactive reach
The reactive reach in reverse direction is the same as for forward so no additional
setting is required.
Resistive reach
The resistive reach in reverse direction must be set longer than the longest reverse
zones. In blocking schemes it must be set longer than the overreaching zone at
remote end that is used in the communication scheme. In equation 169 the index
ZmRv references the specific zone to be coordinated to.
min ZmRv
RFRvPE 1.2 RFPE
EQUATION1316 V1 EN (Equation 169)
Section 3 1MRK505186-UEN D
IED application
224
Application manual
Phase-to-phase fault in forward direction
Reactive reach
The reach in reactive direction is determined by phase-to-earth reach setting X1.
No extra setting is required.
Resistive reach
In the same way as for phase-to-earth fault, the reach is automatically calculated
based on setting X1. The reach will be X1/tan(60) =X1/(3).
Fault resistance reach
The fault resistance reaches in forward direction RFFwPP, must cover RFPP
Zm
with at least 25% margin. RFPP
Zm
is the setting of fault resistance for phase-to-
phase fault for the longest overreaching zone to be covered by FDPSPDIS, see
figure 114. The minimum recommended reach can be calculated according to
equation 170.
1.25 zm RFFwPP RFPP
where:
RFPP
Zm
is the setting of the longest reach of the overreaching zones that must be covered by
FDPSPDIS .
Equation 170 modified is applicable also for the RFRvPP as follows:
min
1.25
zmRv
RFRvPP RFPP
EQUATION2264 V1 EN
Equation 170 is also valid for three-phase fault. The proposed margin of 25% will
cater for the risk of cut off of the zone measuring characteristic that might occur at
three-phase fault when FDPSPDIS characteristic angle is changed from 60 degrees
to 90 degrees (rotated 30 anti-clock wise).
1MRK505186-UEN D Section 3
IED application
225
Application manual
R
X
60
60
1
2
3 5 4
6 6
6 6
6 6
7
7
W ( / phase)
IEC09000257_1_en.vsd
W ( / phase)
5
3
8
4
8
IEC09000257 V1 EN
Figure 114: Relation between distance protection (ZMQPDIS) and
FDPSPDIScharacteristic for phase-to-phase fault for line>60
(setting parameters in italic)
1 FDPSPDIS (red line)
2 ZMQPDIS
3 0.5 RFRvPP
PHS
4
( ) 60 tan
PHS
X1
5 0.5 RFFwPP
PHS
6 0.5 RFPP
Zm
7 X1
PHS
8 X1
Zm
Section 3 1MRK505186-UEN D
IED application
226
Application manual
Resistive reach with load encroachment characteristic
The procedure for calculating the settings for the load encroachment consist
basically to define the load angle ArgLd, the blinder RLdFw in forward direction
and blinder RLdRv in reverse direction, as shown in figure 115.
R
X
RLdFw
RLdRv
ArgLd
ArgLd ArgLd
ArgLd
IEC09000050-1-en.vsd
IEC09000050 V1 EN
Figure 115: Load encroachment characteristic
The load angle ArgLd is the same in forward and reverse direction, so it could be
suitable to begin to calculate the setting for that parameter. Set the parameter to the
maximum possible load angle at maximum active load. A value bigger than 20
must be used.
The blinder in forward direction, RLdFw, can be calculated according to
equation 171.
2
min
0.8
expmax
U
RLdFw
P
=
where:
Pexp max is the maximum exporting active power
Umin is the minimum voltage for which the Pexp max occurs
0.8 is a security factor to ensure that the setting of RLdFw can be lesser than the calculated
minimal resistive load.
The resistive boundary RLdRv for load encroachment characteristic in reverse
direction can be calculated in the same way as RLdFw, but use maximum
importing power that might occur instead of maximum exporting power and the
relevant Umin voltage for this condition.
Minimum operate currents
FDPSPDIShas two current setting parameters which blocks the respective phase-to-
earth loop and phase-to-phase loop if the RMS value of the phase current (ILn) and
phase difference current (ILmILn) is below the settable threshold.
1MRK505186-UEN D Section 3
IED application
227
Application manual
The threshold to activate the phase selector for phase-to-earth (IMinOpPE) is set to
securely detect a single phase-to-earth fault at the furthest reach of the phase
selection. It is recommended to set IMinOpPP to double value of IMinOpPE.
The threshold for opening the measuring loop for phase-to-earth fault
(INReleasePE) is set securely detect single line-to-earth fault at remote end on the
protected line. It is recommended to set INBlockPP to double value of
INReleasePE.
3.6.3.3 Setting parameters
Table 54: FDPSPDIS Group settings (basic)
Name Values (Range) Unit Step Default Description
IBase 1 - 99999 A 1 3000 Base current, i.e. rated current
UBase 0.05 - 2000.00 kV 0.01 400.00 Base voltage, i.e. rated voltage
INBlockPP 10 - 100 %IPh 1 40 3I0 limit for blocking phase-to-phase
measuring loops
INReleasePE 10 - 100 %IPh 1 20 3I0 limit for releasing phase-to-earth
measuring loops
RLdFw 1.00 - 3000.00 ohm/p 0.01 80.00 Forward resistive reach within the load
impedance area
RLdRv 1.00 - 3000.00 ohm/p 0.01 80.00 Reverse resistive reach within the load
impedance area
ArgLd 5 - 70 Deg 1 30 Load angle determining the load
impedance area
X1 0.50 - 3000.00 ohm/p 0.01 40.00 Positive sequence reactance reach
X0 0.50 - 9000.00 ohm/p 0.01 120.00 Zero sequence reactance reach
RFFwPP 0.50 - 3000.00 ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, forward
RFRvPP 0.50 - 3000.00 ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, reverse
RFFwPE 1.00 - 9000.00 ohm/l 0.01 100.00 Fault resistance reach, Ph-E, forward
RFRvPE 1.00 - 9000.00 ohm/l 0.01 100.00 Fault resistance reach, Ph-E, reverse
IMinOpPP 5 - 30 %IB 1 10 Minimum operate delta current for Phase-
Phase loops
IMinOpPE 5 - 30 %IB 1 5 Minimum operate phase current for
Phase-Earth loops
Table 55: FDPSPDIS Group settings (advanced)
Name Values (Range) Unit Step Default Description
TimerPP Off
On
- - Off Operation mode Off / On of Zone timer,
Ph-Ph
tPP 0.000 - 60.000 s 0.001 3.000 Time delay to trip, Ph-Ph
TimerPE Off
On
- - Off Operation mode Off / On of Zone timer,
Ph-E
tPE 0.000 - 60.000 s 0.001 3.000 Time delay to trip, Ph-E
Section 3 1MRK505186-UEN D
IED application
228
Application manual
3.6.4 Full-scheme distance measuring, Mho characteristic
ZMHPDIS
Function description IEC 61850
identification
IEC 60617 identification ANSI/IEEE
C37.2 device
number
Full-scheme distance protection, mho
characteristic
ZMHPDIS
S00346 V1 EN
21
3.6.4.1 Application
Introduction
Transmission and sub-transmission networks are being extended and often become
more and more complex, consisting of a high number of multi-circuit and/or multi
terminal lines of very different lengths. These changes in the network will normally
impose more stringent demands on the fault clearing equipment in order to
maintain an unchanged or increased security level of the power system.
Full-scheme distance measuring, mho characteristic function (ZMHPDIS) in the
IED is designed to meet basic requirements for application on transmission and sub-
transmission lines (solid earthed systems) although it also can be used on
distribution levels.
System earthing
The type of system earthing plays an important role when designing the protection
system. In the following some hints with respect to distance protection are
highlighted.
Solid earthed networks
In solid earthed systems the transformer neutrals are connected solidly to earth
without any impedance between the transformer neutral and earth.
xx05000215.vsd
IEC05000215 V1 EN
Figure 116: Solidly earthed network
The earth-fault current is as high as or even higher than the short-circuit current.
The series impedances determine the magnitude of the earth-fault current. The
1MRK505186-UEN D Section 3
IED application
229
Application manual
shunt admittance has very limited influence on the earth-fault current. The shunt
admittance may, however, have some marginal influence on the earth-fault current
in networks with long transmission lines.
The earth-fault current at single phase-to-earth in phase L1 can be calculated as
equation 172:
L1 L1
0
1 2 0 f 1 N f
3 U U
3I
Z Z Z 3Z Z Z Z
= =
+ + + + +
EQUATION1267 V3 EN (Equation 172)
Where:
U
L1
is the phase to earth voltage (kV) in the faulty phase before fault
Z
1
is the positive sequence impedance (/phase)
Z
2
is the negative sequence impedance (/phase)
Z
0
is the zero sequence impedance (/phase)
Z
f
is the fault impedance (), often resistive
Z
N
is the earth return impedance defined as (Z
0
-Z
1
)/3
The voltage on the healthy phases is generally lower than 140% of the nominal phase-
to-earth voltage. This corresponds to about 80% of the nominal phase-to-phase
voltage.
The high zero-sequence current in solid earthed networks makes it possible to use
impedance measuring technique to detect earth fault. However, distance protection
has limited possibilities to detect high resistance faults and should therefore always
be complemented with other protection function(s) that can carry out the fault
clearance in those cases.
Effectively earthed networks
A network is defined as effectively earthed if the earth-fault factor f
e
is less than
1.4. The earth-fault factor is defined according to equation 47.
max
e
pn
U
f
U
=
EQUATION1268 V3 EN (Equation 173)
Where:
U
max
is the highest fundamental frequency voltage on one of the healthy phases at single phase-
to-earth fault.
U
pn
is the phase-to-earth fundamental frequency voltage before fault.
Section 3 1MRK505186-UEN D
IED application
230
Application manual
Another definition for effectively earthed network is when the following
relationships between the symmetrical components of the network impedances are
valid, see equation 174 and equation 175.
X X
0 1
= 3
EQUATION1269 V3 EN (Equation 174)
R R
0 1
EQUATION1270 V3 EN (Equation 175)
The magnitude of the earth-fault current in effectively earthed networks is high
enough for impedance measuring element to detect earth fault. However, in the
same way as for solid earthed networks, distance protection has limited
possibilities to detect high resistance faults and should therefore always be
complemented with other protection function(s) that can carry out the fault
clearance in this case.
High impedance earthed networks
In high impedance networks the neutral of the system transformers are connected
to the earth through high impedance, mostly a reactance in parallel with a high resistor.
This type of network is many times operated in radial, but can also be found
operating meshed networks.
What is typical for this type of network is that the magnitude of the earth-fault
current is very low compared to the short-circuit current. The voltage on the
healthy phases will get a magnitude of 3 times the phase voltage during the fault.
The zero-sequence voltage (3U
0
) will have the same magnitude in different places
in the network due to low voltage drop distribution.
The magnitude of the total fault current can be calculated according to equation
176.
( )
2
2
R L C
0
3I I I I = + -
EQUATION1271 V3 EN (Equation 176)
where
3I
0
is the earth-fault current (A)
I
R
is the current through the neutral point resistor (A)
I
L
is the current through the neutral point reactor (A)
I
C
is the total capacitive earth-fault current (A)
The neutral point reactor is normally designed so that it can be tuned to a position
where the inductive current balances the capacitive current from the network that is:
1MRK505186-UEN D Section 3
IED application
231
Application manual
1
3
L
C
w
w
=
EQUATION1272 V1 EN (Equation 177)
Ic Ic Ic
IL IR
en05000216.vsd
IEC05000216 V1 EN
Figure 117: High impedance earthing network
The operation of high impedance earthed networks is different compared to solid
earthed networks where all major faults have to be cleared very fast. In high
impedance earthed networks, some system operators do not clear single phase-to-
earth faults immediately; they clear the line later when it is more convenient. In
case of cross-country faults, many network operators want to selectively clear one
of the two earth faults. To handle this type phenomena Phase preference logic
function (PPLPHIZ) is needed, which is not common to be used in transmission
applications.
In this type of network, it is mostly not possible to use distance protection for
detection and clearance of earth faults. The low magnitude of the earth-fault
current might not give start of the zero-sequence measurement element or the
sensitivity will be too low for acceptance. For this reason a separate high sensitive
earth-fault protection is necessary to carry out the fault clearance for single phase-to-
earth fault.
Fault infeed from remote end
All transmission and most all sub-transmission networks are operated meshed.
Typical for this type of network is that we will have fault infeed from remote end
when fault occurs on the protected line. The fault infeed will enlarge the fault
impedance seen by the distance protection. This effect is very important to keep in
mind when both planning the protection system and making the settings.
With reference to figure 118, we can draw the equation for the bus voltage V
A
at
left side as:
( ) A A L A B f V I p Z I I R = + +
EQUATION1273 V1 EN (Equation 178)
If we divide V
A
by IA we get Z present to the IED at A side
Section 3 1MRK505186-UEN D
IED application
232
Application manual
a A B
A L f
A A
V I I
Z p Z R
I I
+
= = +
EQUATION1274 V2 EN (Equation 179)
The infeed factor (I
A
+I
B
)/I
A
can be very high, 10-20 depending on the differences
in source impedances at local and remote end.
Z <
ZL
Z <
EsA
VA
VA
A B
EsB
IA IB
Rf
p*ZL (1-p)*ZL
ZSA
ZSB
en05000217.vsd
IEC05000217 V1 EN
Figure 118: Influence of fault current infeed from remote end.
The effect of fault current infeed from remote end is one of the most driving factors
for justify complementary protection to distance protection.
Load encroachment
In some cases the load impedance might enter the zone characteristic without any
fault on the protected line. The phenomenon is called load encroachment and it
might occur when an external fault is cleared and high emergency load is
transferred on the protected line. The effect of load encroachment for the mho
circle is illustrated to the left in figure 119. The entrance of the load impedance
inside the characteristic is of course not allowed and the way to handle this with
conventional distance protection is to consider this with the settings, that is, to have
a security margin between the distance zone and the minimum load impedance.
This has the drawback that it will reduce the sensitivity of the protection, that is,
the ability to detect resistive faults.
1MRK505186-UEN D Section 3
IED application
233
Application manual
jX
R
Load
Load
Load
Load
jX
R
Load
Load
Load
Load
No
operation
en06000403.vsd
IEC06000403 V1 EN
Figure 119: Load encroachment phenomena and shaped load encroachment
characteristic
The Faulty phase identification with load encroachment for mho (FMPSPDIS)
function shapes the characteristic according to the diagram on the right in
figure 119. The load encroachment algorithm will increase the possibility to detect
high fault resistances, especially for phase-to-earth faults at remote line end. For
example, for a given setting of the load angle ArgLd (see figure 120) for the Faulty
phase identification with load encroachment for mho function (FMPSPDIS), the
zone reach can be expanded according to the diagram on the right in figure 119
given higher fault resistance coverage without risk for unwanted operation due to
load encroachment. The part of the load encroachment sector that comes inside the
mho circle will not cause a trip if FMPSPDIS is activated for the zone
measurement. This is valid in both directions.
Section 3 1MRK505186-UEN D
IED application
234
Application manual
R
X
RLdFw
RLdRv
ArgLd
ArgLd ArgLd
ArgLd
IEC09000127-1-en.vsd
IEC09000127 V1 EN
Figure 120: Load encroachment of Faulty phase identification with load
encroachment for mho function FMPSPDIS characteristic
The use of the load encroachment feature is essential for long heavy loaded lines,
where there might be a conflict between the necessary emergency load transfer and
necessary sensitivity of the distance protection. The function can also preferably be
used on heavy loaded medium long lines. For short lines the major concern is to get
sufficient fault resistance coverage and load encroachment is not a major problem.
So, for short lines, the load encroachment function could preferably be switched off.
The main settings of the parameters for load encroachment are done in Faulty
phase identification with load encroachment for mho function FMPSPDIS. The
operation of load encroachment function is always activated. To deactivate the
function, setting LoadEnchMode should be set off or the setting of RLdFw and
RLdRv must be set to a value much higher than the maximal load impedance.
Short line application
The definition of short, medium and long lines is found in IEEE Std C37.113-1999.
The length classification is defined by the ratio of the source impedance at the
protected lines terminal to the protected lines impedance (SIR). SIRs of about 4
or greater generally define a short line. Medium lines are those with SIRs greater
than 0.5 and less than 4.
In short line applications, the major concern is to get sufficient fault resistance
coverage. Load encroachment is not so common. The line length that can be
1MRK505186-UEN D Section 3
IED application
235
Application manual
recognized as a short line is not a fixed length; it depends on system parameters
such as voltage and source impedance, see table 45.
Table 56: Definition of short and very short line
Line category
Un Un
110 kV 500 kV
Very short line 1.1-5.5 km 5-25 km
Short line 5-11 km 25-50 km
The use of load encroachment algorithm in Full-scheme distance protection, mho
characteristic function (ZMHPDIS) improves the possibility to detect high
resistive faults without conflict with the load impedance (see to the right of figure
119).
For very short line applications the underreaching zone 1 can not be used due to
that the voltage drop distribution through out the line will be too low causing risk
for overreaching.
Load encroachment is normally no problems for short line applications so the load
encroachment function could be switched off meaning LoadEnchMode = Off. This
will increase the possibility to detect resistive close-in faults.
Long transmission line application
For long transmission lines the load encroachment will normally be a major
concern. It is well known that it is difficult to achieve high sensitivity for phase-to-
earth fault at remote end of a long line when the line is heavy loaded.
What can be recognized as long lines with respect to the performance of distance
protection is noted in table 57.
Table 57: Definition of long lines
Line category
Un Un
110 kV 500 kV
Long lines 77 km - 99 km 350 km - 450 km
Very long lines > 99 km > 450 km
The possibility to use the binary information from the load encroachment algorithm
improves the possibility to detect high resistive faults at the same time as the
security is improved (risk for unwanted trip due to load encroachment is
eliminated). The possibility to also use blinder together with load encroachment
algorithm will considerable increase the security but might also lower the
dependability since the blinder might cut off a larger part of the operating area of
the circle (see to the right of figure 119).
It is recommended to use at least one of the load discrimination functions for long
heavy loaded transmission lines.
Parallel line application with mutual coupling
Section 3 1MRK505186-UEN D
IED application
236
Application manual
General
Introduction of parallel lines in the network is increasing due to difficulties to get
necessary area for new lines.
Parallel lines introduce an error in the measurement due to the mutual coupling
between the lines. The lines need not to be of the same voltage in order to
experience mutual coupling, and some coupling exists even for lines that are
separated by 100 meters or more. The reason to the introduced error in measuring
due to mutual coupling is the zero sequence voltage inversion that occurs.
It can be shown from analytical calculations of line impedances that the mutual
impedances for positive and negative sequence are very small (< 1-2% of the self
impedance) and it is a practice to neglect them.
From an application point of view there exists three types of network
configurations (classes) that must be considered when making the settings for the
protection function. Those are:
1. Parallel line with common positive and zero sequence network
2. Parallel circuits with common positive but isolated zero sequence network
3. Parallel circuits with positive and zero sequence sources isolated.
One example of class3 networks could be the mutual coupling between a 400 kV
line and rail road overhead lines. This type of mutual coupling is not so common
although it exists and is not treated any further in this manual.
For each type of network class we can have three different topologies; the parallel
line can be in service, out of service, out of service and earthed in both ends.
The reach of the distance protection zone 1 will be different depending on the
operation condition of the parallel line. It is therefore recommended to use the
different setting groups to handle the cases when the parallel line is in operation
and out of service and earthed at both ends.
Five zone distance protection, mho characteristic function (ZMHPDIS) can
compensate for the influence of a zero sequence mutual coupling on the
measurement at single phase-to-earth faults in the following ways, by using:
The possibility of different setting values that influence the earth-return
compensation for different distance zones within the same group of setting
parameters.
Different groups of setting parameters for different operating conditions of a
protected multi circuit line.
Most multi circuit lines have two parallel operating circuits. The application guide
mentioned below recommends in more detail the setting practice for this particular
type of line. The basic principles also apply to other multi circuit lines.
1MRK505186-UEN D Section 3
IED application
237
Application manual
Parallel line applications
In this type of networks, the parallel transmission lines terminate at common nodes
at both ends. We consider the three most common operation modes:
1. parallel line in service.
2. parallel line out of service and earthed.
3. parallel line out of service and not earthed.
Parallel line in service
This type of application is very common and applies to all normal sub-transmission
and transmission networks.
Let us analyze what happens when a fault occurs on the parallel line see figure 121.
Z0m
A B
Z< Z<
en05000221.vsd
IEC05000221 V1 EN
Figure 121: Class 1, parallel line in service.
The equivalent circuit of the lines can be simplified, see figure 122.
A
B
C
Z0
m
Z0 Z0
m
-
Z0 Z0
m
-
99000038.vsd
IEC99000038 V1 EN
Figure 122: Equivalent zero sequence impedance circuit of the double-circuit,
parallel, operating line with a single phase-to-earth fault at the
remote busbar.
If the current on the parallel line have negative sign compared to the current on the
protected line, that is, the current on the parallel line has an opposite direction
compare to the current on the protected line, the distance function will overreach. If
the currents have the same direction, the distance protection will underreach.
Calculation for a 400 kV line, where the resistance is excluded, gives with
X1L=0.303 /km, X0L=0.88 /km, zone 1 reach is set to 90% of the line
reactance p=71%, that is, the protection is underreaching with approximately 20%.
Section 3 1MRK505186-UEN D
IED application
238
Application manual
The zero sequence mutual coupling can reduce the reach of distance protection on
the protected circuit when the parallel line is in normal operation. The reduction of
the reach is most pronounced with no infeed in the line terminal closest to the fault.
This reach reduction is normally less than 15%. But when the reach is reduced at
one line end, it is proportionally increased at the opposite line end. So this 15%
reach reduction does not significantly affect the operation of a permissive under-
reach scheme.
Parallel line out of service and earthed
Z0m
A B
Z< Z<
en05000222.vsd
DOCUMENT11520-IMG867 V1 EN
Figure 123: The parallel line is out of service and earthed
When the parallel line is out of service and earthed at both ends on the bus bar side
of the line CT so that zero sequence current can flow on the parallel line, the
equivalent zero sequence circuit of the parallel lines will be according to figure 123.
Z Z0
0 m
Z Z0
0 m
Z0
m
A
B
C
99000039.vsd
I
0
I
0
IEC99000039 V1 EN
Figure 124: Equivalent zero-sequence impedance circuit for the double-circuit
line that operates with one circuit disconnected and earthed at both
ends
Here the equivalent zero-sequence impedance is equal to Z0-Z0m in parallel with
(Z0-Z0m)/Z0-Z0m+Z0m, which is equal to equation 180.
2 2
0 m
0E
0
Z Z0
Z
Z
-
=
EQUATION2002 V1 EN (Equation 180)
The influence on the distance measurement will be a considerable overreach, which
must be considered when calculating the settings. It is a recommendation to use a
1MRK505186-UEN D Section 3
IED application
239
Application manual
separate setting group for this operation condition since it will reduce the reach
considerable when the line is in operation.
Parallel line out of service and not earthed
Z0m
A B
Z< Z<
en05000223.vsd
IEC05000223 V1 EN
Figure 125: Parallel line is out of service and not earthed.
When the parallel line is out of service and not earthed, the zero sequence on that
line can only flow through the line admittance to the earth. The line admittance is
high which limits the zero sequence current on the parallel line to very low values.
In practice, the equivalent zero sequence impedance circuit for faults at the remote
bus bar can be simplified to the circuit shown in figure 125
The line zero sequence mutual impedance does not influence the measurement of
the distance protection in a faulty circuit.
This means that the reach of the underreaching distance protection zone is reduced
if, due to operating conditions, the equivalent zero sequence impedance is set
according to the conditions when the parallel system is out of operation and earthed
at both ends.
Z Z0
0 m
Z Z0
0
m
Z0
m
A
B
C
99000040.vsd
I
0
I
0
IEC99000040 V1 EN
Figure 126: Equivalent zero sequence impedance circuit for a double-circuit
line with one circuit disconnected and not earthed.
The reduction of the reach is equal to equation 181.
Section 3 1MRK505186-UEN D
IED application
240
Application manual
2
1 0
0 1 0
1 0
1
(2
0
3
1
1
(2 3
(2 )
3
E f
m
U
f
f
Z Z R
Z
K
Z Z Z R
Z Z R
+ +
= = -
+ +
+ +
EQUATION2008 V1 EN (Equation 181)
This means that the reach is reduced in reactive and resistive directions.
Ensure that the underreaching zones from both line ends will overlap a sufficient
amount (at least 10%) in the middle of the protected circuit.
Tapped line application
A B
Z< Z<
Z<
C
T
IC
IB
-IB
IEC09000160-2-en.vsd
IA
F
IEC09000160 V2 EN
Figure 127: Example of tapped line with Auto transformer
This application gives rise to similar problem that was highlighted in section
"Fault infeed from remote end", that is, increased measured impedance due to fault
current infeed. For example, for faults between the T point and B station the
measured impedance at A and C will be
A C
A AT TF
A
I I
Z Z Z
I
+
= +
EQUATION2302 V1 EN (Equation 182)
1MRK505186-UEN D Section 3
IED application
241
Application manual
2
A C
C Trf CT TF
C
I I U2
Z Z Z Z
I U1
+
= + +
IECEQUATION1750 V1 EN (Equation 183)
where
Z
AT
and Z
CT
is the line impedance from the A respective C station to the T point.
I
A
and I
C
is fault current from A respective C station for fault between T and B.
U2/U1 Transformation ratio for transformation of impedance at U1 side of the transformer to
the measuring side U2 (it is assumed that current and voltage distance function is
taken from U2 side of the transformer).
For this example with a fault between T and B, the measured impedance from the T
point to the fault will be increased by a factor defined as the sum of the currents
from T point to the fault divided by the IED current. For the IED at C, the
impedance on the high voltage side U1 has to be transferred to the measuring
voltage level by the transformer ratio.
Another complication that might occur depending on the topology is that the
current from one end can have a reverse direction for fault on the protected line.
For example, for faults at T the current from B might go in reverse direction from
B to C depending on the system parameters (see the dotted line in figure 127),
given that the distance protection in B to T will measure wrong direction.
In three-end application, depending on the source impedance behind the IEDs, the
impedances of the protected object and the fault location, it might be necessary to
accept zone 2 trip in one end or sequential trip in one end.
Generally for this type of application it is difficult to select settings of zone 1 that
both gives overlapping of the zones with enough sensitivity without interference
with other zone 1 settings, that is, without selectivity conflicts. Careful fault
calculations are necessary to determine suitable settings and selection of proper
scheme communication.
3.6.4.2 Setting guidelines
General
The settings for Full-scheme distance protection, mho characteristic function
(ZMHPDIS) are done in primary values. The instrument transformer ratio that has
been set for the analog input card is used to automatically convert the measured
secondary input signals to primary values used in ZMHPDIS.
The following basics should be considered, depending on application, when doing
the setting calculations:
Section 3 1MRK505186-UEN D
IED application
242
Application manual
Errors introduced by current and voltage instrument transformers, particularly
under transient conditions.
Inaccuracies in the line zero-sequence impedance data, and their effect on the
calculated value of the earth-return compensation factor.
The effect of infeed between the IED and the fault location, including the
influence of different Z
0
/Z
1
ratios of the various sources.
The phase impedance of non transposed lines is not identical for all fault
loops. The difference between the impedances for different phase-to-earth
loops can be as large as 5-10% of the total line impedance.
The effect of a load transfer between the terminals of the protected fault
resistance is considerable, the effect must be recognized.
Zero-sequence mutual coupling from parallel lines.
The setting values of all parameters that belong to ZMHPDIS must correspond to
the parameters of the protected line and be coordinated to the selectivity plan for
the network.
Use different setting groups for the cases when the parallel line is in operation, out
of service and not earthed and out of service and earthed in both ends. In this way it
is possible to optimize the settings for each system condition.
When Directional impedance element for mho characteristic
(ZDMRDIR) is used together with Fullscheme distance protection,
mho characteristic (ZMHPDIS) the following settings for parameter
DirEvalType in ZDMRDIR is vital:
alternative Comparator is strongly recommended
alternative Imp/Comp should generally not be used
alternative Impedance should not be used. This alternative is
intended for use together with Distance protection zone,
quadrilateral characteristic (ZMQPDIS)
Setting of zone 1
The different errors mentioned earlier usually require a limitation of the
underreaching zone (normally zone 1) to 75 - 90% of the protected line.
In case of parallel lines, consider the influence of the mutual coupling according to
section "Parallel line application with mutual coupling" and select the case(s) that
are valid in your application. We recommend to compensating the setting for the
cases when the parallel line is in operation, out of service and not earthed and out
of service and earthed in both ends. The setting of earth-fault reach should be
selected to be <95% also when parallel line is out of service and earthed at both
ends (worst case).
Setting of overreaching zone
The first overreaching zone (normally zone 2) must detect faults on the whole
protected line. Considering the different errors that might influence the
1MRK505186-UEN D Section 3
IED application
243
Application manual
measurement in the same way as for zone 1, it is necessary to increase the reach of
the overreaching zone to at least 120% of the protected line. The zone 2 reach can
be even higher if the fault infeed from adjacent lines at remote end is considerable
higher than the fault current at the IED location.
The setting shall generally not exceed 80% of the following impedances:
The impedance corresponding to the protected line, plus the first zone reach of
the shortest adjacent line.
The impedance corresponding to the protected line, plus the impedance of the
maximum number of transformers operating in parallel on the bus at the
remote end of the protected line.
If the requirements in the bullet list above gives a zone 2 reach that gives non-
selectivity between the overreaching zone and the shortest outgoing line at the
remote end, the time delay of zone 2 must be increased by approximately 200ms to
avoid unwanted operation in cases when the telecommunication for the short
adjacent line at remote end is down during faults. The zone 2 must not be reduced
below 120% of the protected line section. The whole line must be covered under all
conditions.
The requirement that the zone 2 shall not reach more than 80% of the shortest
adjacent line at remote end is highlighted in the example below.
If a fault occurs at point F (see figure 128, also for the explanation of all
abbreviations used), the IED at point A senses the impedance:
ZAF = ZAC + ZCF = ZAC + (1+ ) ZCF
IB
IA
IA + IB
IA
EQUATION302 V2 EN (Equation 184)
A B
Z<
C I
A
I
B
Z
AC Z
CB
Z
CF
I
A
+ I
B
IEC09000256_1_en.vsd
F
IEC09000256 V1 EN
Figure 128: Setting of overreaching zone
Setting of reverse zone
The reverse zone is applicable for purposes of scheme communication logic,
current reversal logic, weak-end infeed logic, and so on. The same applies to the back-
up protection of the bus bar or power transformers. It is necessary to secure, that it
Section 3 1MRK505186-UEN D
IED application
244
Application manual
always covers the overreaching zone, used at the remote line terminal for the
telecommunication purposes.
Consider the possible enlarging factor that might exist due to fault infeed from
adjacent lines. Equation 185 can be used to calculate the reach in reverse direction
when the zone is used for blocking scheme, weak-end infeed, and so on.
Zrev 1.2 ZL Z2rem
EQUATION1525 V3 EN (Equation 185)
Where:
ZL is the protected line impedance
Z2rem is zone 2 setting at remote end of protected line.
In some applications it might be necessary to consider the enlarging factor due to
fault current infeed from adjacent lines in the reverse direction in order to obtain
certain sensitivity.
Setting of zones for parallel line application
Parallel line in service Setting of zone 1
With reference to section "Parallel line application with mutual coupling", the
zone reach can be set to 85% of protected line.
Parallel line in service Setting of zone 2
Overreaching zones (in general, zones 2 and 3) must overreach the protected circuit
in all cases. The greatest reduction of a reach occurs in cases when both parallel
circuits are in service with a single phase-to-earth fault located at the end of a
protected line.
The equivalent zero-sequence impedance circuit for this case is equal to the one in
figure 122 in section "Parallel line application with mutual coupling".
The components of the zero-sequence impedance for the overreaching zones must
be equal to at least:
0 0
0
E m
R R R = +
EQUATION2009 V1 EN (Equation 186)
0 0
0
E m
X X X = +
EQUATION2010 V1 EN (Equation 187)
Check the reduction of a reach for the overreaching zones due to the effect of the
zero-sequence mutual coupling. The reach is reduced for a factor:
1MRK505186-UEN D Section 3
IED application
245
Application manual
0
0 1
2 1 0
m
f
Z
K
Z Z R
= -
+ +
EQUATION1426 V1 EN (Equation 188)
If needed, enlarge the zone reach due to the reduction by mutual coupling.
Consider also the influence on the zone reach due to fault current infeed from
adjacent lines.
Parallel line is out of service and earthed in both ends
Apply the same measures as in the case with a single set of setting parameters. This
means that an underreaching zone must not overreach the end of a protected circuit
for the single phase-to-earth faults.
The equivalent impedance will be according to equation 180.
Load impedance limitation, without load encroachment function
The following instruction is valid when the load encroachment function or blinder
function is not activated (BlinderMode=Off).The load encroachment function will
not be activated if RLdFw and RLdRv is set to a value higher than expected
minimal load impedance. If the load encroachment or blinder function is to be used
for all or some of the measuring zones, the load limitation for those zones
according to this chapter can be omitted. Check the maximum permissible resistive
reach for any zone to ensure that there is a sufficient setting margin between the
relay boundary and the minimum load impedance. The minimum load impedance
(/phase) is calculated as:
Z
loadmin
U
2
S
------- =
EQUATION571 V1 EN (Equation 189)
Where:
U is the minimum phase-to-phase voltage in kV
S is the maximum apparent power in MVA.
The load impedance [/phase] is a function of the minimum operation voltage and
the maximum load current:
Z
load
U
min
3 I
max
---------------------- =
EQUATION574 V1 EN (Equation 190)
Minimum voltage U
min
and maximum current I
max
are related to the same
operating conditions. Minimum load impedance occurs normally under emergency
conditions.
Section 3 1MRK505186-UEN D
IED application
246
Application manual
To avoid load encroachment for the phase-to-earth measuring elements, the set
impedance reach of any distance protection zone must be less than 80% of the
minimum load impedance.
For setting of the earth-fault loop, the following formula can be used:
Load
Z
ZPE 1.6
2(1 cos( )) b
-
EQUATION1604 V1 EN (Equation 191)
where:
Z
load
= magnitude of minimum load impedance
jPE = 180-2g =1802(ArgPE-Q
Load
)
The formula is derived by trigonometric analyze of the figure 129. The length of
the vector from the origin O to the point F on the circle is defined by the law of
cosine. The result gives the maximum diameter (RFPE) for which the load
impedance touch the circle with the given load condition. Use an extra margin of
20% to give sufficient distance between the calculated minimum load impedance
and relay boundary.
jX
R
ZPE/2
ArgLd
(Ref)
?
O
rc
F
Load
|Z
lo
a
d
|
|Z
lo
a
d
|/2 Ohm/phase
en06000406.vsd
IEC06000406 V1 EN
Figure 129: Definition of the setting condition to avoid load encroachment for
earth-fault loop
The maximum setting for phase-to-phase fault can be defined by trigonometric
analyze of the same figure 129. The formula to avoid load encroachment for the phase-
to-phase measuring elements will thus be according to equation 192.
1MRK505186-UEN D Section 3
IED application
247
Application manual
Load
Z
ZPP 1.6
2 (1 cos( PP)) j
-
EQUATION1605 V1 EN (Equation 192)
where:
jPP = 1802(ArgPP-Q
Load)
All this is applicable for all measuring zones when no power swing detection
element or blinder is activated for the protection zones. Use an additional safety
margin of approximately 20% in cases when a power swing detection element is in
the protection scheme, refer to the description of the power swing detection function.
Load impedance limitation, with load encroachment function activated
The parameters for load encroachment shaping of the characteristic are found in the
description of Faulty phase identification with load encroachment for mho
(FMPSPDIS), refer to section "Load encroachment characteristics".
Setting of minimum operating currents
The operation of the distance function will be blocked if the magnitude of the
currents is below the set value of the parameter IMinOpPP and IMinOpPE.
The default setting of IMinOpPP and IMinOpPE is 20% of IBase where IBase is
the chosen base current for the analog input channels. The values have been proven
in practice to be suitable in most of the applications. However, there might be
applications where it is necessary to increase the sensitivity by reducing the
minimum operating current down to 10% of IBase.
The minimum operating fault current is automatically reduced to 75% of its set
value, if the distance protection zone has been set for the operation in reverse
direction.
Setting of directional mode
Setting of the directional mode is by default set to forward by setting the parameter
DirMode to Forward.
The selection of Offset mho can be used for sending block signal in blocking
teleprotection scheme, switch onto fault application etc.
The Reverse mode might be use in comparison schemes where it is necessary to
absolute discriminate between forward and reverse fault.
Setting of direction for offset mho
If offset mho has been selected, one can select if the offset mho shall be Non-
Directional, Forward or Reverse by setting the parameter OfffsetMhoDir.
Section 3 1MRK505186-UEN D
IED application
248
Application manual
When forward or reverse operation is selected, then the operation characteristic
will be cut off by the directional lines used for the mho characteristic. The setting is
by default set to Non-Directional.
Setting of timers for distance protection zones
The required time delays for different distance protection zones are independent of
each other. Distance protection zone 1 can also have a time delay, if so required for
selectivity reasons. One can set the time delays for all zones in a range of 0 to 60
seconds. The tripping function of each particular zone can be inhibited by setting
the corresponding Operation parameter to Off. Different time delays are possible
for the phase-to-earthtPE and for the phase-to-phase tPP measuring loops in each
distance protection zone separately, to further increase the total flexibility of a
distance protection.
3.6.4.3 Setting parameters
Table 58: ZMHPDIS Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - On Operation Off/On
IBase 1 - 99999 A 1 3000 Base current
UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage
DirMode Off
Offset
Forward
Reverse
- - Forward Direction mode
LoadEnchMode Off
On
- - Off Load enchroachment mode Off/On
ReachMode Overreach
Underreach
- - Overreach Reach mode Over/Underreach
OpModePE Off
On
- - On Operation mode Off / On of Phase-Earth
loops
ZPE 0.005 - 3000.000 ohm/p 0.001 30.000 Positive sequence impedance setting for
Phase-Earth loop
ZAngPE 10 - 90 Deg 1 80 Angle for positive sequence line
impedance for Phase-Earth loop
KN 0.00 - 3.00 - 0.01 0.80 Magnitud of earth return compensation
factor KN
KNAng -180 - 180 Deg 1 -15 Angle for earth return compensation
factor KN
ZRevPE 0.005 - 3000.000 ohm/p 0.001 30.000 Reverse reach of the phase to earth
loop(magnitude)
tPE 0.000 - 60.000 s 0.001 0.000 Delay time for operation of phase to
earth elements
IMinOpPE 10 - 30 %IB 1 20 Minimum operation phase to earth current
OpModePP Off
On
- - On Operation mode Off / On of Phase-
Phase loops
ZPP 0.005 - 3000.000 ohm/p 0.001 30.000 Impedance setting reach for phase to
phase elements
Table continues on next page
1MRK505186-UEN D Section 3
IED application
249
Application manual
Name Values (Range) Unit Step Default Description
ZAngPP 10 - 90 Deg 1 85 Angle for positive sequence line
impedance for Phase-Phase elements
ZRevPP 0.005 - 3000.000 ohm/p 0.001 30.000 Reverse reach of the phase to phase
loop(magnitude)
tPP 0.000 - 60.000 s 0.001 0.000 Delay time for operation of phase to phase
IMinOpPP 10 - 30 %IB 1 20 Minimum operation phase to phase
current
Table 59: ZMHPDIS Group settings (advanced)
Name Values (Range) Unit Step Default Description
OffsetMhoDir Non-directional
Forward
Reverse
- - Non-directional Direction mode for offset mho
OpModetPE Off
On
- - On Operation mode Off / On of Zone timer,
Ph-E
OpModetPP Off
On
- - On Operation mode Off / On of Zone timer,
Ph-ph
3.6.5 Full-scheme distance protection, quadrilateral for earth
faults ZMMPDIS, ZMMAPDIS
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Fullscheme distance protection,
quadrilateral for earth faults (zone 1)
ZMMPDIS
S00346 V1 EN
21
Fullscheme distance protection,
quadrilateral for earth faults (zone 2-5)
ZMMAPDIS
S00346 V1 EN
21
3.6.5.1 Application
Introduction
Sub transmission networks are being extended and often become more and more
complex, consisting of a high number of multi-circuit and/or multi terminal lines of
very different lengths. These changes in the network will normally impose more
stringent demands on the fault clearing equipment in order to maintain an
unchanged or increased security level of the power system.
The distance protection function in IED is designed to meet basic requirements for
application on transmission and sub transmission lines (solid earthed systems)
although it also can be used on distribution levels.
Section 3 1MRK505186-UEN D
IED application
250
Application manual
System earthing
The type of system earthing plays an important roll when designing the protection
system. In the following some hints with respect to distance protection are
highlighted.
Solid earthed networks
In solid earthed systems the transformer neutrals are connected solidly to earth
without any impedance between the transformer neutral and earth.
xx05000215.vsd
IEC05000215 V1 EN
Figure 130: Solidly earthed network
The earth fault current is as high or even higher than the short-circuit current. The
series impedances determine the magnitude of the earth fault current. The shunt
admittance has very limited influence on the earth fault current. The shunt
admittance may, however, have some marginal influence on the earth fault current
in networks with long transmission lines.
The earth fault current at single phase-to-earth in phase L1 can be calculated as
equation193:
L1 L1
0
1 2 0 f 1 N f
3 U U
3I
Z Z Z 3Z Z Z Z
= =
+ + + + +
EQUATION1267 V3 EN (Equation 193)
Where:
UL1 is the phase-to-earth voltage (kV) in the faulty phase before fault
Z1 is the positive sequence impedance (/phase)
Z2 is the negative sequence impedance (/phase)
Z0 is the zero sequence impedance (/phase)
Zf is the fault impedance (), often resistive
ZN is the earth return impedance defined as (Z0-Z1)/3
The voltage on the healthy phases is generally lower than 140% of the nominal phase-
to-earth voltage. This corresponds to about 80% of the nominal phase-to-phase
voltage.
1MRK505186-UEN D Section 3
IED application
251
Application manual
The high zero sequence current in solid earthed networks makes it possible to use
impedance measuring technique to detect earth fault. However, distance protection
has limited possibilities to detect high resistance faults and should therefore always
be complemented with other protection function(s) that can carry out the fault
clearance in those cases.
Effectively earthed networks
A network is defined as effectively earthed if the earth fault factor fe is less than
1.4. The earth fault factor is defined according to equation "".
max
e
pn
U
f
U
=
EQUATION1268 V3 EN (Equation 194)
Where:
U
max
is the highest fundamental frequency voltage on one of the healthy phases at single phase-
to-earth fault.
U
pn
is the phase-to-earth fundamental frequency voltage before fault.
Another definition for effectively earthed network is when the following
relationships between the symmetrical components of the network impedances are
valid, see equation 195 and equation 196.
X X
0 1
= 3
EQUATION1269 V3 EN (Equation 195)
R R
0 1
EQUATION1270 V3 EN (Equation 196)
The magnitude of the earth fault current in effectively earthed networks is high
enough for impedance measuring element to detect fault. However, in the same
way as for solid earthed networks, distance protection has limited possibilities to
detect high resistance faults and should therefore always be complemented with
other protection function(s) that can carry out the fault clearance in this case.
High impedance earthed networks
In high impedance networks the neutral of the system transformers are connected
to the earth through high impedance, mostly a reactance in parallel with a high resistor.
This type of network is many times operated in radial, but can also be found
operating meshed.
Typically, for this type of network is that the magnitude of the earth fault current is
very low compared to the short circuit current. The voltage on the healthy phases
Section 3 1MRK505186-UEN D
IED application
252
Application manual
will get a magnitude of 3 times the phase voltage during the fault. The zero
sequence voltage (3U0) will have the same magnitude in different places in the
network due to low voltage drop distribution.
The magnitude of the total fault current can be calculated according to the formula
below:
( )
2
2
R L C
0
3I I I I = + -
EQUATION1271 V3 EN (Equation 197)
Where:
3I0 is the earth-fault current (A)
IR is the current through the neutral point resistor (A)
IL is the current through the neutral point reactor (A)
IC is the total capacitive earth-fault current (A)
The neutral point reactor is normally designed so that it can be tuned to a position
where the reactive current balances the capacitive current from the network that is:
1
3
L
C
w
w
=
EQUATION1272 V1 EN (Equation 198)
Ic Ic Ic
IL IR
en05000216.vsd
IEC05000216 V1 EN
Figure 131: High impedance earthing network
The operation of high impedance earthed networks is different compare to solid
earthed networks where all major faults have to be cleared very fast. In high
impedance earthed networks, some system operators do not clear single phase-to-
earth faults immediately; they clear the line later when it is more convenient. In
case of cross country faults, many network operators want to selectively clear one
of the two earth-faults. To handle this type phenomena a separate function called
Phase preference logic (PPLPHIZ) is needed, which is not common to be used in
transmission applications.
1MRK505186-UEN D Section 3
IED application
253
Application manual
In this type of network, it is mostly not possible to use distance protection for
detection and clearance of earth-faults. The low magnitude of the earth-fault
current might not give start of the zero sequence measurement element or the
sensitivity will be too low for acceptance. For this reason a separate high sensitive
earth-fault protection is necessary to carry out the fault clearance for single phase-to-
earth fault.
Fault infeed from remote end
All transmission and most all sub transmission networks are operated meshed.
Typical for this type of network is that we will have fault infeed from remote end
when fault occurs on the protected line. The fault infeed will enlarge the fault
impedance seen by the distance protection. This effect is very important to keep in
mind when both planning the protection system and making the settings.
With reference to figure 132, we can draw the equation for the bus voltage Va at
left side as:
( ) A A L A B f V I p Z I I R = + +
EQUATION1273 V1 EN (Equation 199)
If we divide Va by IA we get Z present to the IED at A side
a A B
A L f
A A
V I I
Z p Z R
I I
+
= = +
EQUATION1274 V2 EN (Equation 200)
The infeed factor (IA+IB)/IA can be very high, 10-20 depending on the differences
in source impedances at local and remote end.
Z <
ZL
Z <
EsA
VA
VA
A B
EsB
IA IB
Rf
p*ZL (1-p)*ZL
ZSA
ZSB
en05000217.vsd
IEC05000217 V1 EN
Figure 132: Influence of fault infeed from remote end.
The effect of fault current infeed from remote end is one of the most driving factors
for justify complementary protection to distance protection.
Section 3 1MRK505186-UEN D
IED application
254
Application manual
Load encroachment
In some cases the load impedance might enter the zone characteristic without any
fault on the protected line. The phenomenon is called load encroachment and it
might occur when an external fault is cleared and high emergency load is
transferred on the protected line. The effect of load encroachment is illustrated to
the left in figure 133. The entrance of the load impedance inside the characteristic
is of cause not allowed and the way to handle this with conventional distance
protection is to consider this with the settings that is, to have a security margin
between the distance zone and the minimum load impedance. This has the
drawback that it will reduce the sensitivity of the protection that is, the ability to
detect resistive faults.
The IED has a built in function which shapes the characteristic according to the
right figure 4. The load encroachment algorithm will increase the possibility to
detect high fault resistances, especially for phase-to-earth faults at remote end. For
example for a given setting of the load angle ARGLd for the load encroachment
function, the resistive blinder for the zone measurement can be expanded according
to the right in figure 133 given higher fault resistance coverage without risk for
unwanted operation due to load encroachment. This is valid in both directions.
The use of the load encroachment feature is essential for long heavy loaded lines,
where there might be a conflict between the necessary emergency load transfer and
necessary sensitivity of the distance protection. ZMMPDIS function can also
preferably be used on heavy loaded medium long lines. For short lines the major
concern is to get sufficient fault resistance coverage and load encroachment is not a
major problem. So, for short lines, the load encroachment function could preferable
be switched off.
The settings of the parameters for load encroachment are done in the Phase
selection with load enchroachment, quadrilateral characteristic (FDPSPDIS).
R
X
Zm
Load impedance
area in forward
direction
RLdRv
R
Zm
ARGLd
ARGLd
ARGLd
ARGLd
RLdFw
ZL
en05000495.vsd
IEC05000495 V1 EN
Figure 133: Load encroachment phenomena and shaped load encroachment
characteristic
1MRK505186-UEN D Section 3
IED application
255
Application manual
Short line application
In short line applications, the major concern is to get sufficient fault resistance
coverage. Load encroachment is not so common. The line length that can be
recognized as a short line is not a fixed length; it depends on system parameters
such as voltage and source impedance, see table "Short line application".
Table 60: Definition of short and very short line
Line category
Un Un
110 kV 500 kV
Very short line
Short line
1.1-5.5 km 5-25 km
5.5-11 km 25-50 km
The possibility in IED to set resistive and reactive reach independent for positive
and zero sequence fault loops and individual fault resistance settings for phase-to-
phase and phase-to-earth fault together with load encroachment algorithm
improves the possibility to detect high resistive faults without conflict with the load
impedance, see figure 133.
For very short line applications the underreaching zone 1 can not be used due to
that the voltage drop distribution through out the line will be too low causing risk
for overreaching.
Load encroachment is normally no problems for short line applications so the load
encroachment function could be switched off (OperationLdCmp = Off). This will
increase the possibility to detect resistive close-in faults.
Long transmission line application
For long transmission lines the margin to the load impedance that is, to avoid load
encroachment, will normally be a major concern. It is difficult to achieve high
sensitivity for phase-to-earth fault at remote end of a long lines when the line is
heavy loaded.
The definition of long lines with respect to the performance of distance protection
is noted in table 61.
Table 61: Definition of long lines
Line category
Un Un
110 kV 500 kV
Long lines 77 km - 99 km 350 km - 450 km
Very long lines > 99 km > 450 km
As mentioned in the previous chapter, the possibility in IED to set resistive and
reactive reach independent for positive and zero sequence fault loops and
individual fault resistance settings for phase-to-phase and phase-to-earth fault
together with load encroachment algorithm improves the possibility to detect high
Section 3 1MRK505186-UEN D
IED application
256
Application manual
resistive faults at the same time as the security is improved (risk for unwanted trip
due to load encroachment is eliminated).
Parallel line application with mutual coupling
General
Introduction of parallel lines in the network is increasing due to difficulties to get
necessary area for new lines.
Parallel lines introduce an error in the measurement due to the mutual coupling
between the parallel lines. The lines need not to be of the same voltage in order to
experience mutual coupling, and some coupling exists even for lines that are
separated by 100 meters or more. The reason to the introduced error in measuring
due to mutual coupling is the zero sequence voltage inversion that occurs.
It can be shown from analytical calculations of line impedances that the mutual
impedances for positive and negative sequence are very small (< 1-2%) of the self
impedance and it is practice to neglect them.
From an application point of view there exists three types of network
configurations (classes) that must be considered when making the settings for the
protection function. Those are:
1. Parallel line with common positive and zero sequence network
2. Parallel circuits with common positive but isolated zero-sequence network
3. Parallel circuits with positive and zero sequence sources isolated.
One example of class3 networks could be the mutual coupling between a 400 kV
line and rail road overhead lines. This type of mutual coupling is not so common
although it exists and is not treated any further in this manual.
For each type of network class we can have three different topologies; the parallel
line can be in service, out of service, out of service and earthed in both ends.
The reach of the distance protection zone1 will be different depending on the
operation condition of the parallel line. It is therefore recommended to use the
different setting groups to handle the cases when the parallel line is in operation
and out of service and earthed at both ends.
The distance protection within the IED can compensate for the influence of a zero-
sequence mutual coupling on the measurement at single phase-to-earth faults in the
following ways, by using:
The possibility of different setting values that influence the earth-return
compensation for different distance zones within the same group of setting
parameters.
Different groups of setting parameters for different operating conditions of a
protected multi circuit line.
1MRK505186-UEN D Section 3
IED application
257
Application manual
Most multi circuit lines have two parallel operating circuits. The application guide
mentioned below recommends in more detail the setting practice for this particular
type of line. The basic principles also apply to other multi circuit lines.
Parallel line applications
This type of networks are defined as those networks where the parallel
transmission lines terminate at common nodes at both ends. We consider the three
most common operation modes:
1. parallel line in service.
2. parallel line out of service and earthed.
3. parallel line out of service and not earthed.
Parallel line in service
This type of application is very common and applies to all normal sub-transmission
and transmission networks.
A simplified single line diagram is shown in figure 134.
ph ph
0 1 ph 0 N
ph 0
1
V V
Z Z I 3I K
I 3I
3 Z
Z = =
- +
+
= +
+
EQUATION1287 V1 EN (Equation 208)
The imaginary component of the same factor is equal to equation 209.
( )
( )
( ) ( )
2
Im
Im
Re
A
K
U
A
=
+
Im A
2
X
m0
2
EQUATION1288 V1 EN (Equation 209)
Ensure that the underreaching zones from both line ends will overlap a sufficient
amount (at least 10%) in the middle of the protected circuit.
Tapped line application
Section 3 1MRK505186-UEN D
IED application
262
Application manual
A B
Z< Z<
Z<
C
T
IC
IA IB
-IB
en05000224.vsd
DOCUMENT11524-IMG869 V1 EN
Figure 140: Example of tapped line with Auto transformer
This application gives rise to similar problem that was highlighted in section
"Fault infeed from remote end" that is, increased measured impedance due to fault
current infeed. For example for faults between the T point and B station the
measured impedance at A and C will be
ZA =ZAT + ZTF
IA + IC
IA
DOCUMENT11524-IMG3509 V2 EN (Equation 210)
ZC = ZTrf + ( ZCT + ZTF) ( )
2
IA + IC
IC
U2
U1
DOCUMENT11524-IMG3510 V2 EN (Equation 211)
Where:
ZAT and ZCT is the line impedance from the B respective C station to the T point.
IA and IC is fault current from A respective C station for fault between T and B.
U2/U1 Transformation ratio for transformation of impedance at U1 side of the transformer to
the measuring side U2 (it is assumed that current and voltage distance function is
taken from U2 side of the transformer).
For this example with a fault between T and B, the measured impedance from the T
point to the fault will be increased by a factor defined as the sum of the currents
1MRK505186-UEN D Section 3
IED application
263
Application manual
from T point to the fault divided by the IED current. For the IED at C, the
impedance on the high voltage side U1 has to be transferred to the measuring
voltage level by the transformer ratio.
Another complication that might occur depending on the topology is that the
current from one end can have a reverse direction for fault on the protected line.
For example for faults at T the current from B might go in reverse direction from B
to C depending on the system parameters (see the dotted line in figure 140), given
that the distance protection in B to T will measure wrong direction.
In three-end application, depending on the source impedance behind the IEDs, the
impedances of the protected object and the fault location, it might be necessary to
accept zone2 trip in one end or sequential trip in one end.
Generally for this type of application it is difficult to select settings of zone1 that
both gives overlapping of the zones with enough sensitivity without interference
with other zone1 settings that is, without selectivity conflicts. Careful fault
calculations are necessary to determine suitable settings and selection of proper
scheme communication.
Fault resistance
The performance of distance protection for single phase-to-earth faults is very
important, because normally more than 70% of the faults on transmission lines are
single phase-to-earth faults. At these faults, the fault resistance is composed of
three parts: arc resistance, resistance of a tower construction, and tower-footing
resistance. The arc resistance can be calculated according to Warrington's formula:
1.4
28707 L
Rarc
I
=
EQUATION1456 V1 EN (Equation 212)
where:
L represents the length of the arc (in meters). This equation applies for the distance protection
zone 1. Consider approximately three-times arc foot spacing for the zone 2 and wind speed
of approximately 50 km/h
I is the actual fault current in A.
In practice, the setting of fault resistance for both phase-to-earth (RFPE) and phase-
to-phase (RFPP) should be as high as possible without interfering with the load
impedance in order to obtain reliable fault detection.
3.6.5.2 Setting guidelines
General
The settings for the Full-scheme distance protection, quadrilateral for earth faults
(ZMMPDIS) function are done in primary values. The instrument transformer ratio
Section 3 1MRK505186-UEN D
IED application
264
Application manual
that has been set for the analogue input card is used to automatically convert the
measured secondary input signals to primary values used in ZMMPDIS function.
The following basics should be considered, depending on application, when doing
the setting calculations:
Errors introduced by current and voltage instrument transformers, particularly
under transient conditions.
Inaccuracies in the line zero-sequence impedance data, and their effect on the
calculated value of the earth-return compensation factor.
The effect of infeed between the IED and the fault location, including the
influence of different Z0/Z1 ratios of the various sources.
The phase impedance of non transposed lines is not identical for all fault
loops. The difference between the impedances for different phase-to-earth
loops can be as large as 5-10% of the total line impedance.
The effect of a load transfer between the IEDs of the protected fault resistance
is considerable, the effect must be recognized.
Zero-sequence mutual coupling from parallel lines.
Setting of zone1
The different errors mentioned earlier usually require a limitation of the
underreaching zone (normally zone 1) to 75 - 90% of the protected line.
In case of parallel lines, consider the influence of the mutual coupling according
tosection "Parallel line application with mutual coupling" and select the case(s) that
are valid in your application. We recommend to compensate setting for the cases
when the parallel line is in operation, out of service and not earthed and out of
service and earthed in both ends. The setting of earthed fault reach should be
selected to be <95% also when parallel line is out of service and earthed at both
ends (worst case).
Setting of overreaching zone
The first overreaching zone (normally zone2) must detect faults on the whole
protected line. Considering the different errors that might influence the
measurement in the same way as for zone1, it is necessary to increase the reach of
the overreaching zone to at least 120% of the protected line. The zone2 reach can
be even higher if the fault infeed from adjacent lines at remote end are considerable
higher than the fault current at the IED location.
The setting shall generally not exceed 80% of the following impedances:
The impedance corresponding to the protected line, plus the first zone reach of
the shortest adjacent line.
The impedance corresponding to the protected line, plus the impedance of the
maximum number of transformers operating in parallel on the bus at the
remote end of the protected line.
If the requirements in the dotted paragraphs above gives a zone2 reach less than
120%, the time delay of zone2 must be increased by approximately 200ms to avoid
1MRK505186-UEN D Section 3
IED application
265
Application manual
unwanted operation in cases when the telecommunication for the short adjacent
line at remote end is down during faults. The zone2 must not be reduced below
120% of the protected line section. The whole line must be covered under all
conditions.
The requirement that the zone 2 shall not reach more than 80% of the shortest
adjacent line at remote end is highlighted wit a simple example below.
If a fault occurs at point F (see figure 11, also for the explanation of all
abbreviations used), the IED at point A senses the impedance:
ZAF = ZAC + ZCF = ZAC + (1+ ) ZCF
IB
IA
IA + IB
IA
EQUATION302 V2 EN (Equation 213)
A B
Z<
C IA
I
B
Z AC Z CD
Z CF
I A+IB
en05000457.vsd
IEC05000457 V1 EN
Figure 141:
Setting of reverse zone
The reverse zone is applicable for purposes of scheme communication logic,
current reversal logic, weak-end-infeed logic, and so on. The same applies to the back-
up protection of the bus bar or power transformers. It is necessary to secure, that it
always covers the overreaching zone, used at the remote line IED for the
telecommunication purposes.
Consider the possible enlarging factor that might exist due to fault infeed from
adjacent lines. Equation 214 can be used to calculate the reach in reverse direction
when the zone is used for blocking scheme, weak-end infeed and so on.
Zrev 1.2 ZL Z2rem
EQUATION1525 V3 EN (Equation 214)
Where:
ZL is the protected line impedance
Z2rem is zone2 setting at remote end of protected line
Section 3 1MRK505186-UEN D
IED application
266
Application manual
In some applications it might be necessary to consider the enlarging factor due to
fault current infeed from adjacent lines in the reverse direction in order to obtain
certain sensitivity.
Setting of zones for parallel line application
Parallel line in service Setting of zone1
With reference to section "Parallel line applications", the zone reach can be set to
85% of protected line.
Parallel line in service setting of zone2
Overreaching zones (in general, zones 2 and 3) must overreach the protected circuit
in all cases. The greatest reduction of a reach occurs in cases when both parallel
circuits are in service with a single phase-to-earth fault located at the end of a
protected line. The equivalent zero-sequence impedance circuit for this case is
equal to the one in figure 135 in section "Parallel line applications".
The components of the zero-sequence impedance for the overreaching zones must
be equal to at least:
R
0E
R
0
R
m0
+ =
EQUATION553 V1 EN (Equation 215)
X
0E
X
0
X
m0
+ =
EQUATION554 V1 EN (Equation 216)
Check the reduction of a reach for the overreaching zones due to the effect of the
zero sequence mutual coupling. The reach is reduced for a factor:
0
0 1
2 1 0
m
f
Z
K
Z Z R
= -
+ +
EQUATION1426 V1 EN (Equation 217)
If the denominator in equation 217 is called B and Z0m is simplified to X0m, then
the real and imaginary part of the reach reduction factor for the overreaching zones
can be written as:
2 2
0 Im( )
Re( 0) 1
Re( ) Im( )
X m B
K
B B
= -
+
EQUATION1427 V1 EN (Equation 218)
2 2
0 Re( )
Im( 0) 1
Re( ) Im( )
X m B
K
B B
= -
+
EQUATION1428 V1 EN (Equation 219)
1MRK505186-UEN D Section 3
IED application
267
Application manual
Parallel line is out of service and earthed in both ends
Apply the same measures as in the case with a single set of setting parameters. This
means that an underreaching zone must not overreach the end of a protected circuit
for the single phase-to-earth faults. Set the values of the corresponding zone (zero-
sequence resistance and reactance) equal to:
R
0E
R
0
1
X
m0
2
R
0
2
X
0
2
+
-------------------------- +
=
EQUATION561 V1 EN (Equation 220)
X
0E
X
0
1
X
m0
2
R
0
2
X
0
2
+
--------------------------
=
EQUATION562 V1 EN (Equation 221)
Setting of reach in resistive direction
Set the resistive reach independently for each zone, for phase-to-earth loop (RIPE)
measurement.
Set separately the expected fault resistance for the phase-to-earth faults (RFPE) for
each zone. Set all remaining reach setting parameters independently of each other
for each distance zone.
The final reach in resistive direction for phase-to-earth fault loop measurement
automatically follows the values of the line-positive and zero-sequence resistance,
and at the end of the protected zone is equal to equation 222.
R
1
3
--- 2 R1PE R0PE + ( ) RFPE + =
EQUATION567 V1 EN (Equation 222)
2 X1PE+X0
arctan
2 R1PE+R0
loop j
=
EQUATION1457 V1 EN (Equation 223)
Setting of the resistive reach for the underreaching zone1 should follow the condition:
4.5 1 RFPE X
EQUATION569 V2 EN (Equation 224)
Load impedance limitation, without load encroachment function
The following instructions is valid when the load encroachment function is not
activated (OperationLdCmp is set to Off). If the load encroachment function is to
be used for all or some of the measuring zones, the load limitation for those zones
according to this chapter can be omitted. Check the maximum permissible resistive
Section 3 1MRK505186-UEN D
IED application
268
Application manual
reach for any zone to ensure that there is a sufficient setting margin between the
IED boundary and the minimum load impedance. The minimum load impedance
(/phase) is calculated as:
Z
loadmin
U
2
S
------- =
EQUATION571 V1 EN (Equation 225)
Where:
U is the minimum phase-to-phase voltage in kV
S is the maximum apparent power in MVA.
The load impedance [/phase] is a function of the minimum operation voltage and
the maximum load current:
Z
load
U
min
3 I
max
---------------------- =
EQUATION574 V1 EN (Equation 226)
Minimum voltage U
min
and maximum current Imax are related to the same
operating conditions. Minimum load impedance occurs normally under emergency
conditions.
Because a safety margin is required to avoid load encroachment
under three-phase conditions and to guarantee correct healthy phase
IED operation under combined heavy three-phase load and earth
faults, consider both: phase-to-phase and phase-to-earth fault
operating characteristics.
To avoid load encroachment for the phase-to-earth measuring elements, the set
resistive reach of any distance protection zone must be less than 80% of the
minimum load impedance.
RFPE 0.8 Z
load
EQUATION792 V1 EN (Equation 227)
This equation is applicable only when the loop characteristic angle for the single
phase-to-earth faults is more than three times as large as the maximum expected load-
impedance angle. More accurate calculations are necessary according to the
equation below:
1MRK505186-UEN D Section 3
IED application
269
Application manual
min
2 1 0
0.8 cos sin
2 1 0
load
R R
RFPE Z
X X
+
-
+
EQUATION578 V3 EN (Equation 228)
Where:
is a maximum load-impedance angle, related to the minimum load impedance conditions.
All this is applicable for all measuring zones when no power swing detection
element is in the protection scheme. Use an additional safety margin of
approximately 20% in cases when a power swing detection element is in the
protection scheme, refer to the description of the power swing detection
(ZMRPSB) function.
Load impedance limitation, with load encroachment function activated
The parameters for load encroachment shaping of the characteristic are found in the
description of the phase selection with load encroachment function, section
"Resistive reach with load encroachment characteristic". If the characteristic for the
impedance measurement shall be shaped with the load encroachment algorithm, the
parameter OperationLdCmp in the phase selection has to be switched On.
Setting of minimum operating currents
The operation of the distance function will be blocked if the magnitude of the
currents is below the set value of the parameter IMinOpPE.
The default setting of IMinOpPE is 20% of IBase where IBase is the chosen base
current for the analog input channels. The value have been proven in practice to be
suitable in most of the applications. However, there might be applications where it
is necessary to increase the sensitivity by reducing the minimum operating current
down to 10% of the IED base current. This happens especially in cases, when the
IED serves as a remote back-up protection on series of very long transmission lines.
If the load current compensation is activated, there is an additional criteria
IMinOpIN that will block the phase-earth loop if the 3I0<IMinOpIN. The default
setting of IMinOpIN is 5% of the IED base current IBase.
The minimum operating fault current is automatically reduced to 75% of its set
value, if the distance protection zone has been set for the operation in reverse
direction.
Setting of timers for distance protection zones
The required time delays for different distance-protection zones are independent of
each other. Distance protection zone1 can also have a time delay, if so required for
selectivity reasons. One can set the time delays for all zones (basic and optional) in
a range of 0 to 60 seconds. The tripping function of each particular zone can be
inhibited by setting the corresponding Operation parameter to Off. Different time
Section 3 1MRK505186-UEN D
IED application
270
Application manual
delays are possible for the ph-E (tPE) measuring loops in each distance protection
zone separately, to further increase the total flexibility of a distance protection.
3.6.5.3 Setting parameters
Table 62: ZMMPDIS Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - On Operation Off / On
IBase 1 - 99999 A 1 3000 Base current, i.e. rated current
UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage, i.e. rated voltage
OperationDir Off
Non-directional
Forward
Reverse
- - Forward Operation mode of directionality NonDir /
Forw / Rev
X1 0.50 - 3000.00 ohm/p 0.01 30.00 Positive sequence reactance reach
R1 0.10 - 1000.00 ohm/p 0.01 5.00 Positive seq. resistance for zone
characteristic angle
X0 0.50 - 9000.00 ohm/p 0.01 100.00 Zero sequence reactance reach
R0 0.50 - 3000.00 ohm/p 0.01 15.00 Zero seq. resistance for zone
characteristic angle
RFPE 1.00 - 9000.00 ohm/l 0.01 100.00 Fault resistance reach in ohm/loop, Ph-E
Timer tPE Off
On
- - On Operation mode Off / On of Zone timer,
Ph-E
tPE 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-E
IMinOpPE 10 - 30 %IB 1 20 Minimum operate phase current for
Phase-Earth loops
IMinOpIN 5 - 30 %IB 1 5 Minimum operate residual current for
Phase-Earth loops
Table 63: ZMMAPDIS Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - On Operation Off / On
IBase 1 - 99999 A 1 3000 Base current, i.e. rated current
UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage, i.e. rated voltage
OperationDir Off
Non-directional
Forward
Reverse
- - Forward Operation mode of directionality NonDir /
Forw / Rev
X1 0.50 - 3000.00 ohm/p 0.01 40.00 Positive sequence reactance reach
R1 0.10 - 1000.00 ohm/p 0.01 5.00 Positive seq. resistance for zone
characteristic angle
X0 0.50 - 9000.00 ohm/p 0.01 120.00 Zero sequence reactance reach
R0 0.50 - 3000.00 ohm/p 0.01 15.00 Zero seq. resistance for zone
characteristic angle
Table continues on next page
1MRK505186-UEN D Section 3
IED application
271
Application manual
Name Values (Range) Unit Step Default Description
RFPE 1.00 - 9000.00 ohm/l 0.01 100.00 Fault resistance reach in ohm/loop, Ph-E
Timer tPE Off
On
- - On Operation mode Off / On of Zone timer,
Ph-E
tPE 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-E
IMinOpPE 10 - 30 %IB 1 20 Minimum operate phase current for
Phase-Earth loops
3.6.6 Additional distance protection directional function for earth
faults ZDARDIR
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Additional distance protection
directional function for earth faults
ZDARDIR
S00346 V1 EN
-
3.6.6.1 Application
The phase-to-earth impedance elements can be optionally supervised by a phase
unselective directional function based on symmetrical components.
3.6.6.2 Setting guidelines
AngleRCA and AngleOp: these settings define the operation characteristic. Setting
AngleRCA is used to turn the directional characteristic, if the expected fault current
angle does not coincide with the polarizing quantity to produce the maximum
torque. The angle is positive, if operating quantity lags the polarizing quantity and
negative if it leads the polarizing quantity. The setting AngleOp (max. 180
degrees) defines the wideness of the operating sector. The sector is mirror-
symmetric along the MTA (Maximum Torque Axis).
Directional elements for earth-faults must operate at fault current values below the
magnitude of load currents. As phase quantities are adversely affected by load, the
use of sequence quantities are preferred as polarizing quantities for earth
directional elements. Optionally six possibilities are available:
Zero-sequence voltage polarized (-U
0
)
Negative-sequence voltage polarized (-U2)
Zero-sequence current (I
0
)
Dual polarization (-U
0
/I
0
)
Zero-sequence voltage with zero-sequence current compensation (-U0Comp)
Negative-sequence voltage with negative-sequence current compensation (-
U2Comp)
Section 3 1MRK505186-UEN D
IED application
272
Application manual
The zero-sequence voltage polarized earth directional unit compares the phase
angles of zero sequence current I
0
with zero sequence voltage -U
0
at the location of
the protection.
The negative-sequence voltage polarized earth directional unit compares
correspondingly I
2
with -U2.
In general zero sequence voltage is higher than the negative sequence voltage at the
fault, but decreases more rapidly the further away from the fault it is measured.
This makes the -U
0
polarization preferable in short line applications, where no
mutual coupling problems exist.
Negative sequence polarization has the following advantages compared to zero
sequence polarization:
on solidly earthed systems U2 may be larger than U
0
. If the bus behind the
IED location is a strong zero-sequence source, the negative sequence voltage
available at the IED location is higher than the zero-sequence voltage.
negative sequence polarization is not affected by zero sequence mutual
coupling (zero sequence polarized directional elements may misoperate in
parallel lines with high zero-sequence mutual coupling and isolated zero
sequence sources).
negative sequence polarization is less affected by the effects of VT neutral
shift (possible caused by unearthed or multiple earths on the supplying VT
neutral)
no open-delta winding is needed in VTs as only 2 VTs are required (U
2
=
(U
L12
- a U
L23
)/3)
The zero sequence current polarized earth directional unit compares zero sequence
current I0 of the line with some reference zero-sequence current, for example the
current in the neutral of a power transformer. The relay characteristic AngleRCA is
fixed and equals 0 degrees. Care must be taken to ensure that neutral current
direction remains unchanged during all network configurations and faults, and
therefore all transformer configurations/constructions are not suitable for
polarization.
In dual polarization, zero sequence voltage polarization and zero sequence current
polarization elements function in an OR-mode. Typically when zero sequence
current is high, then zero sequence voltage is low and vice versa. Thus combining a
zero sequence voltage polarized and a zero sequence current polarized (neutral
current polarized) directional element into one element, the IED can benefit from
both elements as the two polarization measurements function in an OR mode
complementing each other. Flexibility is also increased as zero sequence voltage
polarization can be used, if the zero sequence current polarizing source is switched
out of service. When the zero sequence polarizing current exceeds the set value for
startPolCurrLevel, zero sequence current polarizing is used. For values of zero
sequence polarizing current less than the set value for startPolCurrLevel, zero
sequence voltage polarizing is used.
1MRK505186-UEN D Section 3
IED application
273
Application manual
Zero-sequence voltage polarization with zero-sequence current compensation (-
U0Comp) compares the phase angles of zero sequence current I
0
with zero-
sequence voltage added by a phase-shifted portion of zero-sequence current (see
equation 229) at the location of the protection. The factor k = setting K
mag
. This
type of polarization in intended for use in applications where the zero sequence
voltage can be too small to be used as the polarizing quantity, and there is no zero
sequence polarizing current (transformer neutral current) available. The zero
sequence voltage is boosted by a portion of the measured line zero sequence
current to form the polarizing quantity. This method requires that a significant
difference must exist in the magnitudes of the zero sequence currents for close-up
forward and reverse faults, that is, it is a requirement that |U0| >> |k I0| for reverse
faults, otherwise there is a risk that reverse faults can be seen as forward.
AngleRCA
0 0
U k I e - +
EQUATION1638 V2 EN (Equation 229)
The negative-sequence voltage polarization with negative-sequence current
compensation (-U2Comp) compares correspondingly I
2
with (see equation 230),
and similarly it must be ensured that |U
2
| >> |k I
2
| for reverse faults.
AngleRCA
2 2
U k I e - +
EQUATION1639 V2 EN (Equation 230)
3.6.6.3 Setting parameters
Table 64: ZDARDIR Group settings (basic)
Name Values (Range) Unit Step Default Description
IBase 1 - 99999 A 1 3000 Base setting for current values
UBase 0.05 - 2000.00 kV 0.05 400.00 Base setting for voltage level in kV
PolMode -3U0
-U2
IPol
Dual
-3U0Comp
-U2comp
- - -3U0 Polarization quantity for opt dir function
for P-E faults
AngleRCA -90 - 90 Deg 1 75 Characteristic relay angle (= MTA or
base angle)
I> 1 - 200 %IB 1 5 Minimum operation current in % of IBase
UPol> 1 - 100 %UB 1 1 Minimum polarizing voltage in % of UBase
IPol> 5 - 100 %IB 1 10 Minimum polarizing current in % of IBase
Section 3 1MRK505186-UEN D
IED application
274
Application manual
Table 65: ZDARDIR Group settings (advanced)
Name Values (Range) Unit Step Default Description
AngleOp 90 - 180 Deg 1 160 Operation sector angle
Kmag 0.50 - 3000.00 ohm 0.01 40.00 Boost-factor in -U0comp and -U2comp
polarization
3.6.7 Mho impedance supervision logic ZSMGAPC
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Mho Impedance supervision logic ZSMGAPC - -
3.6.7.1 Application
The Mho impedance supervision logic (ZSMGAPC) includes features for fault
inception detection and high SIR detection. It also includes the functionality for
loss of potential logic as well as for the pilot channel blocking scheme.
One part of ZSMGAPC function identifies a loss of phase potential that is the
result of a long term (steady state) condition such as a blown fuse or an open
voltage transformer winding or connection. This will block all trips by the distance
protection since they are based on voltage measurement.
In the pilot channel blocking scheme a fault inception detected by a fast acting
change detector is used to send a block signal to the remote end in order to block
an overreaching zone. If the fault is later detected as a forward fault the earlier sent
blocking signal is stopped.
The blocking scheme is very dependable because it will operate for faults
anywhere on the protected line if the communication channel is out of service.
Conversely, it is less secure than permissive schemes because it will trip for
external faults within the reach of the tripping function if the communication
channel is out of service. Inadequate speed or dependability can cause spurious
tripping for external faults. Inadequate security can cause delayed tripping for
internal faults.
ZSMGAPC function also includes functionality for blocking the sample based
distance protection due to high SIR. SIR directly influences the fault voltage level
for a given voltage level, and this is the major factor that affects the severity of
CVT transients. Therefore, in cases where the SIR value is too high, further
filtering of the measured signals will be needed.
3.6.7.2 Setting guidelines
IBase: IBase is normally set to the current value of the primary winding of the CT,
but can also be set to the rated current of the bay. IBase shall be adapted to the
actual application.
1MRK505186-UEN D Section 3
IED application
275
Application manual
UBase: UBase is set to the voltage value of the primary winding of the VT. It is by
default set to 400 kV and shall be adapted to the actual application.
PilotMode: Set PilotMode to On when pilot scheme is to be used. In this mode
fault inception function will send a block signal to remote end to block the
overreaching zones, when operated.
DeltaI: The setting of DeltaI for fault inception detection is by default set to 10%
of IBase, which is suitable in most cases.
Delta3I0: The setting of the parameter Delta3I0 for fault inception detection is by
default set to 10% of UBase, which is suitable in most cases.
DeltaU: The setting of DeltaU for fault inception detection is by default set to 5%
of IBase, which is suitable in most cases.
Delta3U0: The setting of Delta3U0 for fault inception detection is by default set to
5% of UBase, which is suitable in most cases.
Zreach: The setting of Zreach must be adopted to the specific application. The
setting is used in the SIR calculation for detection of high SIR.
SIRLevel: The setting of the parameter SIRLevel is by default set to 10. This is a
suitable setting for applications with CVT to avoid transient overreach due to the
CVT dynamics. SIRLevel = 10 is a suitable setting for applications with CVT to
avoid transient overreach due to the CVT dynamics. If magnetic voltage
transformers are used, set SIRLevel to 15 the highest level
IMinOp: The minimum operate current for the SIR measurement is by default set
to 20% of IBase.
3.6.7.3 Setting parameters
Table 66: ZSMGAPC Group settings (basic)
Name Values (Range) Unit Step Default Description
IBase 1 - 99999 A 1 3000 Base value for current measurement
UBase 0.05 - 2000.00 kV 0.05 400.00 Base value for voltage measurement
PilotMode Off
On
- - Off Pilot mode Off/On
Zreach 0.1 - 3000.0 ohm 0.1 38.0 Line impedance
IMinOp 10 - 30 %IB 1 20 Minimum operating current for SIR
measurement
Section 3 1MRK505186-UEN D
IED application
276
Application manual
Table 67: ZSMGAPC Group settings (advanced)
Name Values (Range) Unit Step Default Description
DeltaI 0 - 200 %IB 1 10 Current change level in %IB for fault
inception detection
Delta3I0 0 - 200 %IB 1 10 Zero seq current change level in % of IB
DeltaU 0 - 100 %UB 1 5 Voltage change level in %UB for fault
inception detection
Delta3U0 0 - 100 %UB 1 5 Zero seq voltage change level in % of UB
SIRLevel 5 - 15 - 1 10 Settable level for source impedance ratio
3.6.8 Faulty phase identification with load encroachment
FMPSPDIS
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Faulty phase identification with load
encroachment for mho
FMPSPDIS
S00346 V1 EN
21
3.6.8.1 Application
The operation of transmission networks today is in many cases close to the stability
limit. Due to environmental considerations the rate of expansion and reinforcement
of the power system is reduced for example, difficulties to get permission to build
new power lines.
The ability to accurate and reliable classifying the different types of fault so that
single pole tripping and autoreclosing can be used plays an important roll in this
matter.
Faulty phase identification with load encroachment for mho (FMPSPDIS) function
is designed to accurately select the proper fault loop in the Distance protection
function dependent on the fault type.
The heavy load transfer that is common in many transmission networks may in
some cases be in opposite to the wanted fault resistance coverage. Therefore,
FMPSPDIS has an built-in algorithm for load encroachment, which gives the
possibility to enlarge the resistive setting of both the Phase selection with load
encroachment and the measuring zones without interfering with the load.
The load encroachment algorithm and the blinder functions are always activated in
the phase selector. The influence from these functions on the zone measurement
characteristic has to be activated by switching the setting parameter
LoadEnchMode for the respective measuring zone(s) to On.
1MRK505186-UEN D Section 3
IED application
277
Application manual
3.6.8.2 Setting guidelines
IBase: IBase is normally set to the current value of the primary winding of the CT,
but can also be set to the rated current of the bay. It is by default set to 3000 A and
shall be adapted to the actual application.
UBase: UBase is set to the voltage value of the primary winding of the VT. It is by
default set to 400 kV and shall be adapted to the actual application.
INRelPE: The setting of INRelPE for release of the phase-to-earth loop is by
default set to 20% of IBase. The default setting is suitable in most applications.
The setting must normally be set to at least 10% lower than the setting of
IINBlockPPto give priority to open phase-to-earth loop. INRelPE must be above
the normal un-balance current (3I
0
) that might exist due to un-transposed lines.
The setting must also be set higher than the 3I
0
that occurs when one pole opens in
single pole trip applications.
IINBlockPP: The setting of IINBlockPP is by default set to 40% of UBase, which
is suitable in most applications.
I1LowLevel: The setting of the positive current threshold I1LowLevel used in the
sequence based part of the phase selector for identifying three-phase fault, is by
default set to 10% of IBase.
The default setting is suitable in most cases, but must be checked against the
minimum three-phase current that occurs at remote end of the line with reasonable
fault resistance.
IMaxLoad: The setting IMaxLoad must be set higher than the maximum load
current transfer during emergency conditions including a safety margin of at least
20%. The setting is proposed to be according to equation 231:
IMaxLoad =1.2 ILoad
EQUATION1614 V2 EN (Equation 231)
where:
1.2 is the security margin against the load current and
ILoad is the maximal load current during emergency conditions.
The current ILoad can be defined according to equation 232.
Section 3 1MRK505186-UEN D
IED application
278
Application manual
max
3
S
ILoad
ULmn
=
---------------------- =
EQUATION574 V1 EN (Equation 233)
Z
loadmin
U
2
S
------- =
EQUATION571 V1 EN (Equation 234)
Where:
U is the minimum phase-to-phase voltage in kV
S is the maximum apparent power in MVA.
1MRK505186-UEN D Section 3
IED application
279
Application manual
The load angle can be derived according to equation 235:
max
cos
max
P
ArgLd a
S
=
EQUATION1623 V1 EN (Equation 235)
where:
Pmax is the maximal active power transfer during emergency conditions and
Smax is the maximal apparent power transfer during emergency conditions.
The RLd can be calculated according to equation 236:
cos( ) RLd ZLoad ArgLd =
EQUATION1624 V1 EN (Equation 236)
The setting of RLd and ArgLd is by default set to 80 ohm/phase and 20 degrees.
Those values must be adapted to the specific application.
3.6.8.3 Setting parameters
Table 68: FMPSPDIS Group settings (basic)
Name Values (Range) Unit Step Default Description
IBase 1 - 99999 A 1 3000 Base current
UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage
IMaxLoad 10 - 5000 %IB 1 200 Maximum load for identification of three
phase fault in % of IBase
RLd 1.00 - 3000.00 ohm/p 0.01 80.00 Load encroachment resistive reach in
ohm/phase
ArgLd 5 - 70 Deg 1 20 Load encroachment inclination of load
angular sector
Table 69: FMPSPDIS Group settings (advanced)
Name Values (Range) Unit Step Default Description
DeltaIMinOp 5 - 100 %IB 1 10 Delta current level in % of IBase
DeltaUMinOp 5 - 100 %UB 1 20 Delta voltage level in % of UBase
U1Level 5 - 100 %UB 1 80 Pos seq voltage limit for identification of 3-
ph fault
I1LowLevel 5 - 200 %IB 1 10 Pos seq current level for identification of
3-ph fault in % of IBase
U1MinOp 5 - 100 %UB 1 20 Minimum operate positive sequence
voltage for ph sel
Table continues on next page
Section 3 1MRK505186-UEN D
IED application
280
Application manual
Name Values (Range) Unit Step Default Description
U2MinOp 1 - 100 %UB 1 5 Minimum operate negative sequence
voltage for ph sel
INRelPE 10 - 100 %IB 1 20 3I0 limit for release ph-e measuring
loops in % of max phase current
INBlockPP 10 - 100 %IB 1 40 3I0 limit for blocking phase-to-phase
measuring loops in % of max phase
current
3.6.9 Power swing detection ZMRPSB
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Power swing detection ZMRPSB
Zpsb
SYMBOL-EE V1 EN
68
3.6.9.1 Application
General
Various changes in power system may cause oscillations of rotating units. The
most typical reasons for these oscillations are big changes in load or changes in
power system configuration caused by different faults and their clearance. As the
rotating masses strive to find a stable operate condition, they oscillate with damped
oscillations until they reach the final stability.
The extent of the oscillations depends on the extent of the disturbances and on the
natural stability of the system.
The oscillation rate depends also on the inertia of the system and on the total
system impedance between different generating units. These oscillations cause
changes in phase and amplitude of the voltage difference between the oscillating
generating units in the power system, which reflects further on in oscillating power
flow between two parts of the system - the power swings from one part to another -
and vice versa.
Distance IEDs located in interconnected networks see these power swings as the
swinging of the measured impedance in relay points. The measured impedance
varies with time along a locus in an impedance plane, see figure 143. This locus
can enter the operating characteristic of a distance protection and cause, if no
preventive measures have been considered, its unwanted operation.
1MRK505186-UEN D Section 3
IED application
281
Application manual
R
jX
Operating characteristic
Impedance locus at
power swing
IEC09000224_1_en.vsd
IEC09000224 V1 EN
Figure 143: Impedance plane with Power swing detection operating
characteristic and impedance locus at power swing
Basic characteristics
Power swing detection function (ZMRPSB) detects reliably power swings with
periodic time of swinging as low as 200 ms (which means slip frequency as high as
10% of the rated frequency on the 50 Hz basis). It detects the swings under normal
system operate conditions as well as during dead time of a single-pole automatic
reclosing cycle.
ZMRPSB function is able to secure selective operation for internal faults during
power. The operation of the distance protection function remains stable for external
faults during the power swing condition, even with the swing (electrical) centre
located on the protected power line.
The operating characteristic of the ZMRPSB function is easily adjustable to the
selected impedance operating characteristics of the corresponding controlled
distance protection zones as well as to the maximum possible load conditions of
the protected power lines. See the corresponding description in Technical
reference manual for the IEDs.
3.6.9.2 Setting guidelines
Setting guidelines are prepared in the form of a setting example for the protected
power line as part of a two-machine system presented in figure 144.
Section 3 1MRK505186-UEN D
IED application
282
Application manual
99001019.vsd
~ ~
E
A
d
A
= const
d
B
= f(t)
E
B
A B
Z
SA
Z
SB
Z
L
R
IEC99001019 V1 EN
Figure 144: Protected power line as part of a two-machine system
Reduce the power system with protected power line into equivalent two-machine
system with positive sequence source impedances Z
SA
behind the IED and Z
SB
behind the remote end bus B. Observe a fact that these impedances can not be
directly calculated from the maximum three-phase short circuit currents for faults
on the corresponding busbar. It is necessary to consider separate contributions of
different connected circuits.
The required data is as follows:
400
r
U kV =
EQUATION1321 V1 EN
Rated system voltage
min
380 U kV =
EQUATION1322 V1 EN
Minimum expected system voltage under critical system
conditions
50
r
f Hz =
EQUATION1323 V1 EN
Rated system frequency
400
3
p
U kV =
EQUATION1324 V1 EN
Rated primary voltage of voltage protection transformers used
0.11
3
s
U kV =
EQUATION1325 V1 EN
Rated secondary voltage of voltage instrument transformers used
1200
p
I A =
EQUATION1326 V1 EN
Rated primary current of current protection transformers used
1
s
I A =
EQUATION1327 V1 EN
Rated secondary current of current protection transformers used
( )
1
10.71 75.6
L
Z j = + W
EQUATION1328 V1 EN
Line positive sequence impedance
Table continues on next page
1MRK505186-UEN D Section 3
IED application
283
Application manual
( )
1
1.15 43.5
SA
Z j = + W
EQUATION1329 V1 EN
Positive sequence source impedance behind A bus
( )
1
5.3 35.7
SB
Z j = + W
EQUATION1330 V1 EN
Positive sequence source impedance behind B bus
max
1000 S MVA =
EQUATION1331 V1 EN
Maximum expected load in direction from A to B (with minimum
system operating voltage U
min
)
( )
max
cos 0.95 j =
EQUATION1332 V1 EN
Power factor at maximum line loading
max
25 j =
EQUATION1333 V1 EN
Maximum expected load angle
2.5
si
f Hz =
EQUATION1334 V1 EN
Maximum possible initial frequency of power oscillation
7.0
sc
f Hz =
EQUATION1335 V1 EN
Maximum possible consecutive frequency of power oscillation
The impedance transformation factor, which transforms the primary impedances to
the corresponding secondary values is calculated according to equation 237.
Consider a fact that all settings are performed in primary values. The impedance
transformation factor is presented for orientation and testing purposes only.
1200 0.11
0.33
1 400
p
s
s p
I
U
KIMP
I U
= = =
EQUATION1336 V1 EN (Equation 237)
The minimum load impedance at minimum expected system voltage is equal to
equation 238.
2 2
min
min
max
380
144.4
1000
L
U
Z
S
= = = W
EQUATION1337 V1 EN (Equation 238)
The minimum load resistance R
Lmin
at maximum load and minimum system
voltage is equal to equation 239.
( )
min min max
cos 144.4 0.95 137.2
L L
R Z j = = = W
EQUATION1338 V1 EN (Equation 239)
Section 3 1MRK505186-UEN D
IED application
284
Application manual
The system impedance Z
S
is determined as a sum of all impedance in an equivalent
two-machine system, see figure 144. Its value is calculated according to
equation 240.
( )
1 1 1
17.16 154.8
S SA L SB
Z Z Z Z j = + + = + W
EQUATION1339 V1 EN (Equation 240)
The calculated value of the system impedance is of informative nature and helps
determining the position of oscillation center, see figure 145, which is for general
case calculated according to equation 241.
1
1
S
CO SA
B
A
Z
Z Z
E
E
= -
+
EQUATION1340 V1 EN (Equation 241)
In particular cases, when
A B
E E =
EQUATION1342 V1 EN (Equation 242)
resides the center of oscillation on impedance point, see equation 243.
( )
1
7.43 33.9
2
S
CO SA
Z
Z Z j = - = + W
EQUATION1341 V1 EN (Equation 243)
1MRK505186-UEN D Section 3
IED application
285
Application manual
R
j
X
ArgLd
(ZMRPSB)
ArgLd
(FDPSPDIS)
Z
S
1
j
X
Z
S
A
1
Z
L
1
Z
S
B
1
I
m
p
e
d
a
n
c
e
lo
c
u
s
f
o
r
|
E
A|
=
|
E
B|
R
Z
C
O
IEC09000225-1-en.vsd
IEC09000225 V1 EN
Figure 145: Impedance diagrams with corresponding impedances under
consideration
The outer boundary of oscillation detection characteristic in forward direction
RLdOutFw should be set with certain safety margin K
L
compared to the minimum
expected load resistance R
Lmin
. When the exact value of the minimum load
resistance is not known, the following approximations may be considered for lines
with rated voltage 400 kV:
Section 3 1MRK505186-UEN D
IED application
286
Application manual
K
L
= 0.9 for lines longer than 150 km
K
L
= 0.85 for lines between 80 and 150 km
K
L
= 0.8 for lines shorter than 80 km
Multiply the required resistance for the same safety factor K
L
with the ratio
between actual voltage and 400kV when the rated voltage of the line under
consideration is higher than 400kV. The outer boundary RLdOutFw obtains in this
particular case its value according to equation 244.
min
0.9 137.2 123.5
L L
RLdOutFw K R = = = W
EQUATION1343 V1 EN (Equation 244)
It is a general recommendation to set the inner boundary RLdInFw of the
oscillation detection characteristic to 80% or less of its outer boundary. Exceptions
are always possible, but must be considered with special care especially when it
comes to settings of timers tP1 and tP2 included in oscillation detection logic. This
requires the maximum permitted setting values of factor kLdRFw = 0.8.
Equation 245 presents the corresponding maximum possible value of RLdInFw.
RLdInFw = kLdRFwRLdOutFw = 98.8W
EQUATION1344 V2 EN (Equation 245)
The load angles, which correspond to external
Out
and internal
In
boundary of
proposed oscillation detection characteristic in forward direction, are calculated
with sufficient accuracy according to equation 246 and 247 respectively.
155.75
2 arc tan 2 arc tan 64.5
2 2 123.5
d
= = =
S
Out
Z
RLdOutFw
EQUATION1345 V1 EN (Equation 246)
max
155.75
2 arc tan 2 arc tan 76.5
2 2 98.8
d
= = =
S
In
Z
RLdInFw
EQUATION1346 V1 EN (Equation 247)
The required setting tP1 of the initial oscillation detection timer depends on the
load angle difference according to equation 248.
76.5 64.5
1 13.3
360 2.5 360
In Out
si
tP ms
f
d d - -
= = =
EQUATION1347 V1 EN (Equation 248)
The general tendency should be to set the tP1 time to at least 30 ms, if possible.
Since it is not possible to further increase the external load angle
Out
, it is
1MRK505186-UEN D Section 3
IED application
287
Application manual
necessary to reduce the inner boundary of the oscillation detection characteristic.
The minimum required value is calculated according to the procedure listed in
equation 249, 250, 251 and 252.
min
1 30 tP ms =
EQUATION1348 V1 EN (Equation 249)
min min
360 1 360 2.5 0.030 64.5 91.5
In si Out
f tP d d
-
= + = + =
EQUATION1349 V1 EN (Equation 250)
max1
min
155.75
75.8
91.5
2 tan 2 tan
2 2
d
-
= = = W
S
in
Z
RLdInFw
EQUATION1350 V1 EN (Equation 251)
max1
75.8
0.61
123.5
= = =
RLdInFw
kLdRFw
RLdOutFw
EQUATION1351 V1 EN (Equation 252)
Also check if this minimum setting satisfies the required speed for detection of
consecutive oscillations. This requirement will be satisfied if the proposed setting
of tP2 time remains higher than 10 ms, see equation 253.
max
91.5 64.5
2 10.7
360 7 360
In Out
sc
tP ms
f
d d - -
= = =
EQUATION1352 V1 EN (Equation 253)
The final proposed settings are as follows:
RLdOutFw = 123.5
kLdRFw = 0.61
tP1 = 30 ms
tP2 = 10 ms
Consider RLdInFw = 75.0.
Do not forget to adjust the setting of load encroachment resistance
RLdFw in Phase selection with load encroachment (FDPSPDIS or
FRPSPDIS) to the value equal to or less than the calculated value
RLdInFw. It is at the same time necessary to adjust the load angle
in FDPSPDIS or FRPSPDIS to follow the condition presented in
equation 254.
Section 3 1MRK505186-UEN D
IED application
288
Application manual
Index PHS designates correspondence to FDPSPDIS or FRPSPDIS
function and index PSD the correspondence to ZMRPSB function.
( )
tan
arc tan
PSD
PHS
ArgLd
ArgLd
kLdRFw
EQUATION1353 V2 EN (Equation 254)
Consider equation 255,
max
25
PSD
ArgLd j = =
EQUATION1354 V1 EN (Equation 255)
then it is necessary to set the load argument in FDPSPDIS or FRPSPDIS function
to not less than equation 256.
( ) ( ) tan tan 25
arc tan arc tan 37.5
0.61
= =
PSD
PHS
ArgLd
ArgLd
kLdRFw
EQUATION1355 V1 EN (Equation 256)
It is recommended to set the corresponding resistive reach parameters in reverse
direction (RLdOutRv and kLdRRv) to the same values as in forward direction,
unless the system operating conditions, which dictate motoring and generating
types of oscillations, requires different values. This decision must be made on basis
of possible system contingency studies especially in cases, when the direction of
transmitted power may change fast in short periods of time. It is recommended to
use different setting groups for operating conditions, which are changing only
between different periods of year (summer, winter).
System studies should determine the settings for the hold timer tH. The purpose of
this timer is, to secure continuous output signal from Power swing detection
function (ZMRPSB) during the power swing, even after the transient impedance
leaves ZMRPSB operating characteristic and is expected to return within a certain
time due to continuous swinging. Consider the minimum possible speed of power
swinging in a particular system.
The tR1 inhibit timer delays the influence of the detected residual current on the
inhibit criteria for ZMRPSB. It prevents operation of the function for short
transients in the residual current measured by the IED.
The tR2 inhibit timer disables the output START signal from ZMRPSB function, if
the measured impedance remains within ZMRPSB operating area for a time longer
than the set tR2 value. This time delay was usually set to approximately two
seconds in older power-swing devices.
1MRK505186-UEN D Section 3
IED application
289
Application manual
The setting of the tEF timer must cover, with sufficient margin, the opening time of
a circuit breaker and the dead-time of a single-phase autoreclosing together with
the breaker closing time.
3.6.9.3 Setting parameters
Table 70: ZMRPSB Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Mode On / Off
X1InFw 0.10 - 3000.00 ohm 0.01 30.00 Inner reactive boundary, forward
R1LIn 0.10 - 1000.00 ohm 0.01 30.00 Line resistance for inner characteristic
angle
R1FInFw 0.10 - 1000.00 ohm 0.01 30.00 Fault resistance coverage to inner
resistive line, forward
X1InRv 0.10 - 3000.00 ohm 0.01 30.00 Inner reactive boundary, reverse
R1FInRv 0.10 - 1000.00 ohm 0.01 30.00 Fault resistance line to inner resistive
boundary, reverse
OperationLdCh Off
On
- - On Operation of load discrimination
characteristic
RLdOutFw 0.10 - 3000.00 ohm 0.01 30.00 Outer resistive load boundary, forward
ArgLd 5 - 70 Deg 1 25 Load angle determining load impedance
area
RLdOutRv 0.10 - 3000.00 ohm 0.01 30.00 Outer resistive load boundary, reverse
kLdRFw 0.50 - 0.90 Mult 0.01 0.75 Multiplication factor for inner resistive
load boundary, forward
kLdRRv 0.50 - 0.90 Mult 0.01 0.75 Multiplication factor for inner resistive
load boundary, reverse
tEF 0.000 - 60.000 s 0.001 3.000 Timer for overcoming single-pole
reclosing dead time
IMinOpPE 5 - 30 %IB 1 10 Minimum operate current in % of IBase
IBase 1 - 99999 A 1 3000 Base setting for current level settings
Table 71: ZMRPSB Group settings (advanced)
Name Values (Range) Unit Step Default Description
tP1 0.000 - 60.000 s 0.001 0.045 Timer for detection of initial power swing
tP2 0.000 - 60.000 s 0.001 0.015 Timer for detection of subsequent power
swings
tW 0.000 - 60.000 s 0.001 0.250 Waiting timer for activation of tP2 timer
tH 0.000 - 60.000 s 0.001 0.500 Timer for holding power swing START
output
tR1 0.000 - 60.000 s 0.001 0.300 Timer giving delay to inhibit by the
residual current
tR2 0.000 - 60.000 s 0.001 2.000 Timer giving delay to inhibit at very slow
swing
Section 3 1MRK505186-UEN D
IED application
290
Application manual
3.6.10 Power swing logic ZMRPSL
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Power swing logic ZMRPSL - -
3.6.10.1 Application
Power Swing Logic (ZMRPSL) is a complementary function to Power Swing
Detection (ZMRPSB) function. It enables a reliable fault clearing for different
faults on protected lines during power swings in power systems.
It is a general goal, to secure fast and selective operation of the distance protection
scheme for the faults, which occur on power lines during power swings. It is
possible to distinguish between the following main cases:
A fault occurs on a so far healthy power line, over which the power swing has
been detected and the fast distance protection zone has been blocked by
ZMRPSB element.
The power swing occurs over two phases of a protected line during the dead
time of a singlepole auto-reclosing after the Ph-E fault has been correctly
cleared by the distance protection. The second fault can, but does not need to,
occur within this time interval.
Fault on an adjacent line (behind the B substation, see figure 146) causes the
measured impedance to enter the operate area of ZMRPSB function and, for
example, the zone 2 operating characteristic (see figure 147). Correct fault
clearance initiates an evolving power swing so that the locus of the measured
impedance continues through zone 1 operating characteristic and causes its
unwanted operation, if no preventive measures have been taken, see figure 147.
E
A
A B
C
D
F
Z
SA RA
E
C
E
D
xx06000238.vsd
Z
SC
Z
SD
IEC06000238 V1 EN
Figure 146: Fault on adjacent line and its clearance causes power swinging
between sources A and C
ZMRPSL function and the basic operating principle of ZMRPSB function operate
reliably for different faults on parallel power lines with detected power swings. It
is, however, preferred to keep the distance protection function blocked in cases of
single phase-to-earth faults on so far healthy lines with detected power swings. In
1MRK505186-UEN D Section 3
IED application
291
Application manual
these cases, it is recommended to use an optionally available directional
overcurrent earth-fault protection with scheme communication logic.
R
jX
B
A
Measured
impedance at initital
fault position
Impedance locus at initial power
swing after the fault clearance
ZMRPSB operating characteristic
Zone 2
Zone 1
IEC99000181_2_en.vsd
IEC99000181 V2 EN
Figure 147: Impedance trajectory within the distance protection zones 1 and 2
during and after the fault on line B D
3.6.10.2 Setting guidelines
Scheme communication and tripping for faults occurring during
power swinging over the protected line
The IED includes generally up to five distance protection zones. It is possible to
use one or two of them intentionally for selective fault clearing during power
swings only. Following are the basic conditions for the operation of the so called
(underreaching and overreaching) power-swing zones:
They must generally be blocked during normal operation and released during
power swings.
Their operation must be time delayed but shorter (with sufficient margin) than
the set time delay of normal distance protection zone 2, which is generally
blocked by the power swing.
Their resistive reach setting must secure, together with the set time delay for
their operation, that the slowest expected swings pass the impedance operate
area without initiating their operation.
Section 3 1MRK505186-UEN D
IED application
292
Application manual
Communication and tripping logic as used by the power swing distance protection
zones is schematically presented in figure 148.
The operation of the power swing zones is conditioned by the operation of Power
swing detection (ZMRPSB) function. They operate in PUTT or POTT
communication scheme with corresponding distance protection zones at the remote
line end. It is preferred to use the communication channels over the optionally
available Line Data Communication Module - LDCM and the Binary signal
transfer to remote end function. It is also possible to include, in an easy way (by
means of configuration possibilities), the complete functionality into regular
scheme communication logic for the distance protection function. The
communication scheme for the regular distance protection does not operate during
the power-swing conditions, because the distance protection zones included in the
scheme are normally blocked. The powerswing zones can for this reason use the
same communication facilities during the power-swing conditions.
Only one power swing zone is necessary in distance protection at each line
terminal, if the POTT communication scheme is applied. One underreaching power
swing zone, which sends the time delayed carrier signal, and one overreaching
power swing zone, which performs the local tripping condition, are necessary with
PUTT schemes.
The operation of the distance protection zones with long time delay (for example,
zone 3) is in many cases not blocked by the power swing detection elements. This
allows in such cases the distance protection zone 3 (together with the full-scheme
design of the distance protection function) to be used at the same time as the
overreaching power-swing zone.
STDEF
AR1P1 &
STPSD
BLOCK & t
tCS
&
CSUR
CS
t
tBlkTr
&
t
tTrip
CR
CACC
>1
&
BLKZMPS
TRIP
en06000236.vsd
IEC06000236 V1 EN
Figure 148: Simplified logic diagram - power swing communication and tripping
logic
1MRK505186-UEN D Section 3
IED application
293
Application manual
Configuration
Configure the BLOCK input to any combination of conditions, which are supposed
to block the operation of logic. Connection to detected fuse failure conditions is
required as a minimum.
The STDEF functional input should be configured to the START signal of any line
earth fault overcurrent protection function within the IED. When the directional
earth fault O/C function is used an OR combination of forward and reverse
operation should be used.
Connect the AR1P1 to the output signal of the autoreclosing function, which
signals the activation of the single pole autoreclosing dead time.
The STPSD input should be connected to the starting signal of the power swing
detection (ZMRPSB) function, which becomes active in cases of detected system
oscillations.
The CSUR functional input should be connected to the starting output of the power
swing distance protection zone, which is used as a local tripping criteria during
power swings in PUTT schemes. When the POTT scheme is used (also on series
compensated networks) the local criteria and the carrier sending zone are one and
the same. It is preferred to use separate communication facilities for distance
protection and for power swing communication logic, but combination of
functionality within the same communication channel is possible as well.
Connect the CACC functional input to start output signal of the local overreaching
power swing distance protection zone, which serves as a local criteria at receiving
of carrier signal during the power swing cycle.
The CR signal should be configured to the functional input which provides the
logic with information on received carrier signal sent by the remote end power
swing distance protection zone.
The CS functional output signal should be configured to either output relay or to
corresponding input of the Binary signal transfer to remote end function.
The BLKZMPS output signal should be configured to BLOCK input of the power
swing distance protection zones.
The TRIP signal should be connected correspondingly towards the tripping
functionality of the complete distance protection within the IED.
Setting calculations
Time delay of power swing carrier send distance protection zones
Time delay for the underreaching or overreaching carrier send power swing zone
should be set shorter (with sufficient margin) than the time delay of normal
distance protection zone 2 to obtain selective time grading also in cases of faults
during power swings. The necessary time difference depends mostly on the speed
of the communication channel used, speed of the circuit breaker used, etc. Time
difference between 100 ms and 150 ms is generally sufficient.
Reactive reach setting of power swing distance protection zones
Section 3 1MRK505186-UEN D
IED application
294
Application manual
Set the reactive reach for the power swing zones according to the system selectivity
planning. The reach of the underreaching zone should not exceed 85% of the
protected line length. The reach of the overreaching zone should be at least 120%
of the protected line length.
Resistive reach setting of carrier send power swing distance protection zone
Determine the minimum possible speed of impedance Z / t in primary / s of
the expected power swings. When better information is not available from system
studies, the following equation may be used:
min min
2
z L s
v Z f =
EQUATION1537 V1 EN (Equation 257)
Where:
v
z
is a minimum expected speed of swing impedance in / s
Z
Lmin
is a minimum expected primary load impedance in
f
smin
is a minimum expected oscillation (swing) frequency in Hz
Calculate the maximum permissible resistive reach for each power swing zone
separately according to the following equations.
0.8
n z
RFPP v tnPP =
EQUATION1538 V1 EN (Equation 258)
0.8
2
z
n
v tnPE
RFPE
=
EQUATION1539 V1 EN (Equation 259)
Here is factor 0.8
considered for safety
reasons and:
RFPE
n
phase-to-earth resistive reach setting for a power swing distance protection
zone n in
RFPP
n
phase-to-phase resistive reach setting for a power swing distance
protection zone n in
tnPE time delay for phase-to-earth fault measurement of power swing distance
protection zone n in s
tnPP time delay for phase-to-phase fault measurement of power swing distance
protection zone n in s
Time-delay for the overreaching power swing zone
Time delay for the overreaching power swing zone is not an important parameter,
if the zone is used only for the protection purposes at power-swings.
1MRK505186-UEN D Section 3
IED application
295
Application manual
Consider the normal time grading, if the overreaching zone serves as a time
delayed back-up zone, which is not blocked by the operation of Power swing
detection (ZMRPSB) function.
Timers within the power swing logic
Settings of the timers within Power swing logic (ZMRPSL) depend to a great
extent on the settings of other time delayed elements within the complete
protection system. These settings differ within different power systems. The
recommended settings consider only the general system conditions and the most
used practice at different utilities. It is always necessary to check the local system
conditions.
The carrier send timer tCS is used for safety reasons within the logic. It requires
continuous presence of the input signal STPSD, before it can issue a carrier send
signal. A time delay between 50 and 100 ms is generally sufficient.
The trip timer tTrip is used for safety reasons within the logic. It requires
continuous presence of the input signal STPSD, before it can issue a tripping
command during the power swings. A time delay between 50 and 100 ms is
generally sufficient.
The blocking timer tBlkTr prolongs the presence of the BLKZMOR output signals,
which can be used to block the operation of the power swing zones after the
detected single-phase-to-earth faults during the power swings. It is necessary to
permit the O/C EF protection to eliminate the initial fault and still make possible
for the power swing zones to operate for possible consecutive faults. A time delay
between 150 and 300 ms is generally sufficient.
Blocking and tripping logic for evolving power swings
The second part of a complete Power swing logic (ZMRPSL) functionality is a
blocking and tripping logic for evolving power swings, see figure 146 and figure
147. The simplified logic is presented in figure 149. The logic controls the
operation of the underreaching distance protection zone (Zone 1) at power swings,
caused by the faults and their clearance on the adjacent power lines. The logic
should generally be configured between distance protection zones 1 and 2.
Configuration
The fault impedance should be detected within the external boundary of Power
Swing Detection (ZMRPSB) function without power swing detected during the
entire fault duration. Configure for this reason the STZMPSD to the functional
output signal of ZMRPSB function, which indicates the measured impedance
within its external boundaries.
Section 3 1MRK505186-UEN D
IED application
296
Application manual
STZML
BLOCK
&
STMZH
STZMPSD
STPSD
t
tDZ
t
tZL
&
>1
&
&
&
-loop
>1
STZMLL
BLKZMH
&
en06000237.vsd
IEC06000237 V1 EN
Figure 149: Blocking and tripping logic for evolving power swings
No system oscillation should be detected in power system. Configure for this
reason the STPSD functional input to the START functional output of ZMRPSB
function or to any binary input signal indicating the detected oscillations within the
power system.
Configure the functional input STZMUR to the start output of the instantaneous
underreaching distance protection zone (usually START of distance protection
zone 1). The function will determine whether the start signal of this zone is
permitted to be used in further logic or not, dependent on time difference on
appearance of overreaching distance protection zone (usually zone 2).
Configure for this reason the functional output signal STZMURPS to the start
output of the overreaching distance protection zone (usually START of distance
protection zone 2).
Functional output PUZMLL replaces the start (and trip) signals of the distance
protection zone 1 in all following logic. Configure it accordingly within the logic.
Functional output signal BLKZMOR should be configured to block the overreach
distance protection zone (generally zone 2) in order to prevent its maloperation
during the first swinging of the system. Configure it accordingly to BLOCK
functional input of distance protection zone 2.
Setting calculations
Setting of the differentiating timer tDZ influences to a great extent the performance
of the protection during the power swings, which develops by occurrence and
clearance of the faults on adjacent power lines. It is necessary to consider the
possibility for the faults to occur close to the set reach of the underreaching
distance protection zone, which might result in prolonged operate times of zone 1
(underreaching zone) compared to zone 2 starting time (overreaching zone). A
setting between 80 and 150 ms is generally sufficient.
1MRK505186-UEN D Section 3
IED application
297
Application manual
The release timer tZL permits unconditional operation of the underreaching zone, if
the measured impedance remains within its operate characteristic longer than the
set time tZL. Its setting depends on the expected speed of the initial swings and on
the setting of the time delay for the overreaching zone 2. The release timer must
still permit selective tripping of the distance protection within the complete
network. A setting between 200 and 300 ms is generally sufficient.
3.6.10.3 Setting parameters
Table 72: ZMRPSL Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off / On
tDZ 0.000 - 60.000 s 0.001 0.050 Permitted max oper time diff between
higher and lower zone
tDZMUR 0.000 - 60.000 s 0.001 0.200 Delay for oper of underreach zone with
detected diff in oper time
tCS 0.000 - 60.000 s 0.001 0.100 Conditional timer for sending the CS at
power swings
tTrip 0.000 - 60.000 s 0.001 0.100 Conditional timer for tripping at power
swings
tBlkTr 0.000 - 60.000 s 0.001 0.300 Timer for blocking the overreaching
zones trip
3.6.11 Pole slip protection PSPPPAM
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Pole slip protection PSPPPAM
<
SYMBOL-MM V1 EN
78
3.6.11.1 Application
Normally, the generator operates synchronously with the power system, that is, all
the generators in the system have the same angular velocity and approximately the
same phase angle difference. If the phase angle between the generators gets too
large the stable operation of the system cannot be maintained. In such a case the
generator loses the synchronism (pole slip) to the external power system.
The situation with pole slip of a generator can be caused by different reasons.
A short circuit occurs in the external power grid, close to the generator. If the fault
time is too long, the generator will accelerate so much, so the synchronism cannot
Section 3 1MRK505186-UEN D
IED application
298
Application manual
be maintained. The relative generator phase angle at a fault and pole slip, relative
to the external power system, is shown in figure 150.
en06000313.vsd
IEC06000313 V1 EN
Figure 150: Relative generator phase angle at a fault and pole slip relative to
the external power system
The relative angle of the generator is shown for different fault duration at a three-
phase short circuit close to the generator. As the fault duration increases the angle
swing amplitude increases. When the critical fault clearance time is reached the
stability cannot be maintained.
Un-damped oscillations occur in the power system, where generator groups at
different locations, oscillate against each other. If the connection between the
generators is too weak the amplitude of the oscillations will increase until the
angular stability is lost. At the moment of pole slip there will be a centre of this
pole slip, which is equivalent with distance protection impedance measurement of a
three-phase. If this point is situated in the generator itself, the generator should be
tripped as fast as possible. If the locus of the out of step centre is located in the
power system outside the generators the power system should, if possible, be split
into two parts, and the generators should be kept in service. This split can be made
at predefined locations (trip of predefined lines) after function from pole slip
protection (PSPPPAM) in the line protection IED.
1MRK505186-UEN D Section 3
IED application
299
Application manual
en06000314.vsd
IEC06000314 V1 EN
Figure 151: Undamped oscillations causing pole slip
The relative angle of the generator is shown a contingency in the power system,
causing un-damped oscillations. After a few periods of the oscillation the swing
amplitude gets to large and the stability cannot be maintained.
If the excitation of the generator gets too low there is a risk that the generator
cannot maintain synchronous operation. The generator will slip out of phase and
operate as an induction machine. Normally the under-excitation protection will
detect this state and trip the generator before the pole slip. For this fault the under-
excitation protection and PSPPPAM function will give mutual redundancy.
The operation of a generator having pole slip will give risk of damages to the
generator block.
At each pole slip there will be significant torque impact on the generator-
turbine shaft.
In asynchronous operation there will be induction of currents in parts of the
generator normally not carrying current, thus resulting in increased heating.
The consequence can be damages on insulation and stator/rotor iron.
At asynchronous operation the generator will absorb a significant amount of
reactive power, thus risking overload of the windings.
Section 3 1MRK505186-UEN D
IED application
300
Application manual
PSPPPAM function shall detect out of step conditions and trip the generator as fast
as possible if the locus of the pole slip is inside the generator. If the centre of pole
slip is outside the generator, situated out in the power grid, the first action should
be to split the network into two parts, after line protection action. If this fails there
should be operation of the generator pole slip protection, to prevent further
damages to the generator block.
3.6.11.2 Setting guidelines
Operation: With the parameter Operation the function can be set On or Off.
IBase: The parameter IBase is set to the generator rated current in A, according to
equation 260.
3
N
N
S
IBase
U
=
+
EQUATION1943 V1 EN (Equation 302)
Where
U
phase
is the phase voltage in the fault point before the fault,
R
f
is the resistance to earth in the fault point and
Z
0
is the system zero sequence impedance to earth
The fault current, in the fault point, can be calculated as:
phase
j 0
0 f
3 U
I 3I
Z 3 R
= =
+
EQUATION1944 V1 EN (Equation 303)
The impedance Z
0
is dependent on the system earthing. In an isolated system
(without neutral point apparatus) the impedance is equal to the capacitive coupling
between the phase conductors and earth:
phase
0 c
j
3 U
Z jX j
I
= - = -
EQUATION1945 V1 EN (Equation 304)
Where
I
j
is the capacitive earth-fault current at a non-resistive phase to earth-fault
X
c
is the capacitive reactance to earth
In a system with a neutral point resistor (resistance earthed system) the impedance
Z
0
can be calculated as:
c n
0
c n
jX 3R
Z
jX 3R
-
=
- +
EQUATION1946 V1 EN (Equation 305)
Where
R
n
is the resistance of the neutral point resistor
Section 3 1MRK505186-UEN D
IED application
364
Application manual
In many systems there is also a neutral point reactor (Petersen coil) connected to
one or more transformer neutral points. In such a system the impedance Z
0
can be
calculated as:
( )
n n c
0 c n n
n c n n c
9R X X
Z jX // 3R // j3X
3X X j3R 3X X
= - =
+ -
EQUATION1947 V1 EN (Equation 306)
Where
X
n
is the reactance of the Petersen coil. If the Petersen coil is well tuned we have 3X
n
= X
c
In
this case the impedance Z
0
will be: Z
0
= 3R
n
Now consider a system with an earthing via a resistor giving higher earth-fault
current than the high impedance earthing. The series impedances in the system can
no longer be neglected. The system with a single phase to earth-fault can be
described as in figure 183.
Substation A
Substation B
Z
lineAB,1
(pos. seq)
Z
lineAB,0
(zero seq)
Z
lineBC,1
(pos. seq)
Z
lineBC,0
(zero seq)
U
0A
U
0B
3I
0
Phase to earth fault
R
N
Z
T,1
(pos. seq)
Z
T,0
(zero seq)
Source impedance
Z
sc
(pos. seq)
en06000654.vsd
IEC06000654 V1 EN
Figure 183: Equivalent of power system for calculation of setting
The residual fault current can be written:
1MRK505186-UEN D Section 3
IED application
365
Application manual
phase
0
1 0 f
3U
3I
2 Z Z 3 R
=
+ +
EQUATION1948 V1 EN (Equation 307)
Where
U
phase
is the phase voltage in the fault point before the fault
Z
1
is the total positive sequence impedance to the fault point. Z
1
= Z
sc
+Z
T,1
+Z
lineAB,1
+Z
lineBC,1
Z
0
is the total zero sequence impedance to the fault point. Z
0
= Z
T,0
+3R
N
+Z
lineAB,0
+Z
lineBC,0
R
f
is the fault resistance.
The residual voltages in stations A and B can be written:
( )
0A 0 T,0 N
U 3I Z 3R = +
EQUATION1949 V1 EN (Equation 308)
OB 0 T,0 N lineAB,0
U 3I (Z 3R Z ) = + +
EQUATION1950 V1 EN (Equation 309)
The residual power, measured by the sensitive earth-fault protections in A and B
will be:
0A 0A 0
S 3U 3I =
EQUATION1951 V1 EN (Equation 310)
0B 0B 0
S 3U 3I =
EQUATION1952 V1 EN (Equation 311)
The residual power is a complex quantity. The protection will have a maximum
sensitivity in the characteristic angle RCA. The apparent residual power
component in the characteristic angle, measured by the protection, can be written:
0A, prot 0A 0 A
S 3U 3I cosj =
EQUATION1953 V1 EN (Equation 312)
0B, prot 0B 0 B
S 3U 3I cosj =
EQUATION1954 V1 EN (Equation 313)
The angles
A
and
B
are the phase angles between the residual current and the
residual voltage in the station compensated with the characteristic angle RCA.
Section 3 1MRK505186-UEN D
IED application
366
Application manual
The protection will use the power components in the characteristic angle direction
for measurement, and as base for the inverse time delay.
The inverse time delay is defined as:
0 0
inv
0 0
kSN (3I 3U cos (reference))
t
3I 3U cos (measured)
j
=
j
EQUATION1942 V2 EN (Equation 314)
The function can be set On/Off with the setting of Operation.
The setting IBase gives the base current in A. Normally the primary rated current
of the CT feeding the protection should be chosen.
The setting UBase gives the base voltage in kV. Normally the system phase to
earth voltage is chosen.
The setting SBase gives the base voltage in kVA. Normally IBase UBase is chosen.
With the setting OpMode the principle of directional function is chosen.
With OpMode set to 3I0cosfi the current component in the direction equal to the
characteristic angleRCADir is measured. The characteristic for RCADir is equal to
0 is shown in figure 184.
,
= =
o o
0 , 0 RCADir ROADir
ref
U
0
3I
j = -
0 ref
ang(3I ) ang(3U )
- =
0 ref
3U U
0
3I cos j
IEC06000648_2_en.vsd
IEC06000648 V2 EN
Figure 184: Characteristic for RCADir equal to 0
The characteristic is for RCADir equal to -90 is shown in figure 185.
1MRK505186-UEN D Section 3
IED application
367
Application manual
IEC06000649_2_en.vsd
ref
U
= - =
o o
90 , 90 RCADir ROADir
0
3I
0
3 j I cos
j = -
0
(3 ) ( )
ref
ang I ang U
-
0
3U
IEC06000649 V2 EN
Figure 185: Characteristic for RCADir equal to -90
When OpMode is set to 3U03I0cosfi the apparent residual power component in the
direction is measured.
When OpMode is set to 3I0 and fi the function will operate if the residual current is
larger than the setting INDir> and the residual current angle is within the sector
RCADir ROADir.
The characteristic for RCADir = 0 and ROADir = 80 is shown in figure 186.
-3U
0
80 80
Operate area
3I
0
en06000652.vsd
RCADir = 0
ROADir = 80
IEC06000652 V2 EN
Figure 186: Characteristic for RCADir = 0 and ROADir = 80
Section 3 1MRK505186-UEN D
IED application
368
Application manual
DirMode is set Forward or Reverse to set the direction of the trip function from the
directional residual current function.
All the directional protection modes have a residual current release level setting
INRel> which is set in % of IBase. This setting should be chosen smaller than or
equal to the lowest fault current to be detected.
All the directional protection modes have a residual voltage release level setting
UNRel> which is set in % of UBase. This setting should be chosen smaller than or
equal to the lowest fault residual voltage to be detected.
tDef is the definite time delay, given in s, for the directional residual current
protection if definite time delay is chosen.
tReset is the reset time for definite time delay, given in s. With a tReset time of
several periods there is increased possibilities to clear intermittent earth-faults
correctly. The setting shall be much shorter than the set trip delay.
The characteristic angle of the directional functions RCADir is set in degrees.
RCADir is normally set equal to 0 in a high impedance earthed network with a
neutral point resistor as the active current component is appearing out on the
faulted feeder only. RCADir is set equal to -90 in an isolated network as all
currents are mainly capacitive.
The relay open angle ROADir is set in degrees. For angles differing more than
ROADir fromRCADir the function from the protection is blocked. The setting can
be used to prevent unwanted function for non-faulted feeders, with large capacitive
earth-fault current contributions, due to CT phase angle error.
INCosPhi> is the operate current level for the directional function when OpMode
is set 3I0Cosfi. The setting is given in % of IBase. The setting should be based on
calculation of the active or capacitive earth-fault current at required sensitivity of
the protection.
SN> is the operate power level for the directional function when OpMode is set
3I03U0Cosfi. The setting is given in % of IBase. The setting should be based on
calculation of the active or capacitive earth-fault residual power at required
sensitivity of the protection.
The input transformer for the Sensitive directional residual over current and power
protection function has the same short circuit capacity as the phase current
transformers.
If the time delay for residual power is chosen the delay time is dependent on two
setting parameters. SRef is the reference residual power, given in % of SBase. kSN
is the time multiplier. The time delay will follow the following expression:
inv
0 0
kSN Sref
t
3I 3U cos (measured) j
=
EQUATION1957 V1 EN (Equation 315)
1MRK505186-UEN D Section 3
IED application
369
Application manual
INDir> is the operate current level for the directional function when OpMode is set
3I0 and fi. The setting is given in % of IBase. The setting should be based on
calculation of the earth-fault current at required sensitivity of the protection.
OpINNonDir> is set On to activate the non-directional residual current protection.
INNonDir> is the operate current level for the non-directional function. The setting
is given in % of IBase. This function can be used for detection and clearance of cross-
country faults in a shorter time than for the directional function. The current setting
should be larger than the maximum single-phase residual current out on the
protected line.
TimeChar is the selection of time delay characteristic for the non-directional
residual current protection. Definite time delay and different types of inverse time
characteristics are available:
Table 90: Inverse time characteristics
Curve name
ANSI Extremely Inverse
ANSI Very Inverse
ANSI Normal Inverse
ANSI Moderately Inverse
ANSI/IEEE Definite time
ANSI Long Time Extremely Inverse
ANSI Long Time Very Inverse
ANSI Long Time Inverse
IEC Normal Inverse
IEC Very Inverse
IEC Inverse
IEC Extremely Inverse
IEC Short Time Inverse
IEC Long Time Inverse
IEC Definite Time
User Programmable
ASEA RI
RXIDG (logarithmic)
The different characteristics are described in Technical Manual.
tPCrv, tACrv, tBCrv, tCCrv: Parameters for customer creation of inverse time
characteristic curve (Curve type = 17). The time characteristic equation is:
Section 3 1MRK505186-UEN D
IED application
370
Application manual
[ ] = +
-
>
p
A
t s B InMult
i
C
in
EQUATION1958 V1 EN (Equation 316)
tINNonDir is the definite time delay for the non directional earth-fault current
protection, given in s.
OpUN> is set On to activate the trip function of the residual voltage protection.
tUN is the definite time delay for the trip function of the residual voltage
protection, given in s.
3.7.5.3 Setting parameters
Table 91: SDEPSDE Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off / On
OpMode 3I0Cosfi
3I03U0Cosfi
3I0 and fi
- - 3I0Cosfi Selection of operation mode for protection
DirMode Forward
Reverse
- - Forward Direction of operation forward or reverse
RCADir -179 - 180 Deg 1 -90 Relay characteristic angle RCA, in deg
RCAComp -10.0 - 10.0 Deg 0.1 0.0 Relay characteristic angle compensation
ROADir 0 - 90 Deg 1 90 Relay open angle ROA used as release
in phase mode, in deg
INCosPhi> 0.25 - 200.00 %IB 0.01 1.00 Set level for 3I0cosFi, directional res
over current, in %Ib
SN> 0.25 - 200.00 %SB 0.01 10.00 Set level for 3I03U0cosFi, starting inv
time count, in %Sb
INDir> 0.25 - 200.00 %IB 0.01 5.00 Set level for directional residual over
current prot, in %Ib
tDef 0.000 - 60.000 s 0.001 0.100 Definite time delay directional residual
overcurrent, in sec
SRef 0.03 - 200.00 %SB 0.01 10.00 Reference value of res power for inverse
time count, in %Sb
kSN 0.00 - 2.00 - 0.01 0.10 Time multiplier setting for directional
residual power mode
OpINNonDir> Off
On
- - Off Operation of non-directional residual
overcurrent protection
INNonDir> 1.00 - 400.00 %IB 0.01 10.00 Set level for non directional residual over
current, in %Ib
tINNonDir 0.000 - 60.000 s 0.001 1.000 Time delay for non-directional residual
over current, in sec
Table continues on next page
1MRK505186-UEN D Section 3
IED application
371
Application manual
Name Values (Range) Unit Step Default Description
TimeChar ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
- - IEC Norm. inv. Operation curve selection for IDMT
operation
tMin 0.000 - 60.000 s 0.001 0.040 Minimum operate time for IEC IDMT
curves, in sec
kIN 0.00 - 2.00 - 0.01 1.00 IDMT time mult for non-dir res over
current protection
OpUN> Off
On
- - Off Operation of non-directional residual
overvoltage protection
UN> 1.00 - 200.00 %UB 0.01 20.00 Set level for non-directional residual over
voltage, in %Ub
tUN 0.000 - 60.000 s 0.001 0.100 Time delay for non-directional residual
over voltage, in sec
INRel> 0.25 - 200.00 %IB 0.01 1.00 Residual release current for all
directional modes, in %Ib
UNRel> 0.01 - 200.00 %UB 0.01 3.00 Residual release voltage for all direction
modes, in %Ub
Table 92: SDEPSDE Group settings (advanced)
Name Values (Range) Unit Step Default Description
tReset 0.000 - 60.000 s 0.001 0.040 Time delay used for reset of definite
timers, in sec
tPCrv 0.005 - 3.000 - 0.001 1.000 Setting P for customer programmable
curve
tACrv 0.005 - 200.000 - 0.001 13.500 Setting A for customer programmable
curve
tBCrv 0.00 - 20.00 - 0.01 0.00 Setting B for customer programmable
curve
tCCrv 0.1 - 10.0 - 0.1 1.0 Setting C for customer programmable
curve
ResetTypeCrv Immediate
IEC Reset
ANSI reset
- - IEC Reset Reset mode when current drops off.
Table continues on next page
Section 3 1MRK505186-UEN D
IED application
372
Application manual
Name Values (Range) Unit Step Default Description
tPRCrv 0.005 - 3.000 - 0.001 0.500 Setting PR for customer programmable
curve
tTRCrv 0.005 - 100.000 - 0.001 13.500 Setting TR for customer programmable
curve
tCRCrv 0.1 - 10.0 - 0.1 1.0 Setting CR for customer programmable
curve
Table 93: SDEPSDE Non group settings (basic)
Name Values (Range) Unit Step Default Description
IBase 1 - 99999 A 1 100 Base Current, in A
UBase 0.05 - 2000.00 kV 0.05 63.50 Base Voltage, in kV Phase to Neutral
SBase 0.05 -
200000000.00
kVA 0.05 6350.00 Base Power, in kVA. IBase*Ubase
Table 94: SDEPSDE Non group settings (advanced)
Name Values (Range) Unit Step Default Description
RotResU 0 deg
180 deg
- - 180 deg Setting for rotating polarizing quantity if
necessary
3.7.6 Thermal overload protection, one time constant LPTTR
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Thermal overload protection, one time
constant
LPTTR
SYMBOL-A V1 EN
26
3.7.6.1 Application
Lines and cables in the power system are designed for a certain maximum load
current level. If the current exceeds this level the losses will be higher than
expected. As a consequence the temperature of the conductors will increase. If the
temperature of the lines and cables reaches too high values the equipment might be
damaged:
The sag of overhead lines can reach unacceptable value.
If the temperature of conductors, for example aluminium conductors, get too
high the material will be destroyed.
In cables the insulation can be damaged as a consequence of the
overtemperature. As a consequence of this phase to phase or phase to earth
faults can occur
1MRK505186-UEN D Section 3
IED application
373
Application manual
In stressed situations in the power system it can be required to overload lines and
cables for a limited time. This should be done without risks.
The thermal overload protection provides information that makes a temporary
overloading of cables and lines possible. The thermal overload protection estimates
the conductor temperature continuously. This estimation is made by using a
thermal model of the line/cable based on the current measurement.
If the temperature of the protected object reaches a set warning level AlarmTemp, a
signal ALARM can be given to the operator. This enables actions in the power
system to be taken before dangerous temperatures are reached. If the temperature
continues to increase to the trip value TripTemp, the protection initiates trip of the
protected line.
3.7.6.2 Setting guideline
The parameters for the Thermal overload protection LPTTR are set via the local
HMI or PCM600.
The following settings can be done for the thermal overload protection.
Operation: Off/On
IBase: Base current in primary A. This current is used as reference for current
setting. It can be suitable to set this parameter to the rated primary current of the
protected object.
Imult: If the protection measures one of a number of parallel line currents the
number of parallel circuits is given in this setting.
IRef: Reference, steady state current, given in % of IBase that will give a steady
state (end) temperature TRef. It is suggested to set this current to the maximum
steady state current allowed for the line/cable under emergency operation (a few
hours per year).
TRef: Reference temperature (end temperature) corresponding to the steady state
current IRef. From cable manuals current values with corresponding conductor
temperature are often given. These values are given for conditions such as earth
temperature, ambient air temperature, way of laying of cable and earth thermal
resistivity. From manuals for overhead conductor temperatures and corresponding
current is given.
Tau: The thermal time constant of the protected circuit given in minutes. Please
refer to manufacturers manuals for details.
TripTemp: Temperature value for trip of the protected circuit. For cables a
maximum allowed conductor temperature is often stated to be 90C. For overhead
lines the critical temperature for aluminium conductor is about 90 - 100C. For a
copper conductor a normal figure is 70C.
Section 3 1MRK505186-UEN D
IED application
374
Application manual
AlarmTemp: Temperature level for alarm of the protected circuit. ALARM signal
can be used as a warning before the circuit is tripped. Therefore the setting shall be
lower than the trip level. It shall at the same time be higher than the maximum
conductor temperature at normal operation. For cables this level is often given to
65C. Similar values are stated for overhead lines. A suitable setting can be about
15C below the trip value.
ReclTemp: Temperature where lockout signal LOCKOUT from the protection is
released. When the thermal overload protection trips a lock-out signal is activated.
This signal is intended to block switch in of the protected circuit as long as the
conductor temperature is high. The signal is released when the estimated
temperature is below the set value. This temperature value should be chosen below
the alarm temperature.
3.7.6.3 Setting parameters
Table 95: LPTTR Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off / On
IBase 0 - 99999 A 1 3000 Base current in A
TRef 0 - 600 Deg 1 90 End temperature rise above ambient of
the line when loaded with IRef
IRef 0 - 400 %IB 1 100 The load current (in %of IBase) leading
to TRef temperature
IMult 1 - 5 - 1 1 Current multiplier when function is used
for two or more lines
Tau 0 - 1000 Min 1 45 Time constant of the line in minutes.
AlarmTemp 0 - 200 Deg 1 80 Temperature level for start (alarm)
TripTemp 0 - 600 Deg 1 90 Temperature level for trip
ReclTemp 0 - 600 Deg 1 75 Temperature for reset of lockout after trip
tPulse 0.05 - 0.30 s 0.01 0.1 Operate pulse length. Minimum one
execution cycle
AmbiSens Off
On
- - Off External temperature sensor availiable
DefaultAmbTemp -50 - 250 Deg 1 20 Ambient temperature used when
AmbiSens is set to Off.
DefaultTemp -50 - 600 Deg 1 50 Temperature raise above ambient
temperature at startup
3.7.7 Breaker failure protection CCRBRF
1MRK505186-UEN D Section 3
IED application
375
Application manual
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Breaker failure protection CCRBRF
3I>BF
SYMBOL-U V1 EN
50BF
3.7.7.1 Application
In the design of the fault clearance system the N-1 criterion is often used. This
means that a fault needs to be cleared even if any component in the fault clearance
system is faulty. One necessary component in the fault clearance system is the
circuit breaker. It is from practical and economical reason not feasible to duplicate
the circuit breaker for the protected component. Instead a breaker failure protection
is used.
Breaker failure protection (CCRBRF) will issue a back-up trip command to
adjacent circuit breakers in case of failure to trip of the normal circuit breaker for
the protected component. The detection of failure to break the current through the
breaker is made by means of current measurement or as detection of remaining trip
signal (unconditional).
CCRBRF can also give a re-trip. This means that a second trip signal is sent to the
protected circuit breaker. The re-trip function can be used to increase the
probability of operation of the breaker, or it can be used to avoid back-up trip of
many breakers in case of mistakes during relay maintenance and test.
3.7.7.2 Setting guidelines
The parameters for Breaker failure protection CCRBRF are set via the local HMI
or PCM600.
The following settings can be done for the breaker failure protection.
Operation: Off/On
IBase: Base current in primary A. This current is used as reference for current
setting. It can be suitable to set this parameter to the rated primary current of the
current transformer where the current measurement is made.
FunctionMode This parameter can be set Current or Contact. This states the way
the detection of failure of the breaker is performed. In the mode current the current
measurement is used for the detection. In the mode Contact the long duration of
breaker position signal is used as indicator of failure of the breaker. The mode
Current&Contact means that both ways of detections are activated. Contact mode
can be usable in applications where the fault current through the circuit breaker is
small. This can be the case for some generator protection application (for example
reverse power protection) or in case of line ends with weak end infeed.
Section 3 1MRK505186-UEN D
IED application
376
Application manual
RetripMode: This setting states how the re-trip function shall operate. Retrip Off
means that the re-trip function is not activated. CB Pos Check (circuit breaker
position check) and Current means that a phase current must be larger than the
operate level to allow re-trip. CB Pos Check (circuit breaker position check) and
Contact means re-trip is done when circuit breaker is closed (breaker position is
used). No CB Pos Check means re-trip is done without check of breaker position.
Table 96: Dependencies between parameters RetripMode and FunctionMode
RetripMode FunctionMode Description
Retrip Off N/A the re-trip function is not
activated
CB Pos Check Current a phase current must be larger
than the operate level to allow
re-trip
Contact re-trip is done when breaker
position indicates that breaker
is still closed after re-trip time
has elapsed
Current&Contact both methods are used
No CB Pos Check Current re-trip is done without check of
breaker position
Contact re-trip is done without check of
breaker position
Current&Contact both methods are used
BuTripMode: Back-up trip mode is given to state sufficient current criteria to detect
failure to break. For Current operation 2 out of 4 means that at least two currents,
of the three-phase currents and the residual current, shall be high to indicate
breaker failure. 1 out of 3 means that at least one current of the three-phase currents
shall be high to indicate breaker failure. 1 out of 4 means that at least one current of
the three-phase currents or the residual current shall be high to indicate breaker
failure. In most applications 1 out of 3 is sufficient. For Contact operation means
back-up trip is done when circuit breaker is closed (breaker position is used).
IP>: Current level for detection of breaker failure, set in % of IBase. This
parameter should be set so that faults with small fault current can be detected. The
setting can be chosen in accordance with the most sensitive protection function to
start the breaker failure protection. Typical setting is 10% of IBase.
I>BlkCont: If any contact based detection of breaker failure is used this function
can be blocked if any phase current is larger than this setting level. If the
FunctionMode is set Current&Contact breaker failure for high current faults are
safely detected by the current measurement function. To increase security the
contact based function should be disabled for high currents. The setting can be
given within the range 5 200% of IBase.
IN>: Residual current level for detection of breaker failure set in % of IBase. In
high impedance earthed systems the residual current at phase- to-earth faults are
normally much smaller than the short circuit currents. In order to detect breaker
1MRK505186-UEN D Section 3
IED application
377
Application manual
failure at single-phase-earth faults in these systems it is necessary to measure the
residual current separately. Also in effectively earthed systems the setting of the
earth-fault current protection can be chosen to relatively low current level. The
BuTripMode is set 1 out of 4. The current setting should be chosen in accordance to
the setting of the sensitive earth-fault protection. The setting can be given within he
range 2 200 % of IBase.
t1: Time delay of the re-trip. The setting can be given within the range 0 60s in
steps of 0.001 s. Typical setting is 0 50ms.
t2: Time delay of the back-up trip. The choice of this setting is made as short as
possible at the same time as unwanted operation must be avoided. Typical setting is
90 200ms (also dependent of re-trip timer).
The minimum time delay for the re-trip can be estimated as:
_
2 1 + + +
cbopen BFP reset margin
t t t t t
EQUATION1430 V1 EN (Equation 317)
where:
t
cbopen
is the maximum opening time for the circuit breaker
t
BFP_reset
is the maximum time for breaker failure protection to detect correct breaker function (the
current criteria reset)
t
margin
is a safety margin
It is often required that the total fault clearance time shall be less than a given
critical time. This time is often dependent of the ability to maintain transient
stability in case of a fault close to a power plant.
Section 3 1MRK505186-UEN D
IED application
378
Application manual
Time
The fault
occurs
Protection
operate time
Trip and Start
CCRBRF
Normal t
cbopen
Margin
Retrip delay t1 t
cbopen
after re-trip
tBFPreset
Minimum back-up trip delay t2
Critical fault clearance time for stability
IEC05000479_2_en.vsd
IEC05000479 V2 EN
Figure 187: Time sequence
t2MPh: Time delay of the back-up trip at multi-phase start. The critical fault
clearance time is often shorter in case of multi-phase faults, compared to single phase-
to-earth faults. Therefore there is a possibility to reduce the back-up trip delay for
multi-phase faults. Typical setting is 90 150 ms.
t3: Additional time delay to t2 for a second back-up trip TRBU2. In some
applications there might be a requirement to have separated back-up trip functions,
tripping different back-up circuit breakers.
tCBAlarm: Time delay for alarm in case of indication of faulty circuit breaker.
There is a binary input CBFLT from the circuit breaker. This signal is activated
when internal supervision in the circuit breaker detect that the circuit breaker is
unable to clear fault. This could be the case when gas pressure is low in a SF6
circuit breaker, of others. After the set time an alarm is given, so that actions can be
done to repair the circuit breaker. The time delay for back-up trip is bypassed when
the CBFLT is active. Typical setting is 2.0 seconds.
tPulse: Trip pulse duration. This setting must be larger than the critical impulse
time of circuit breakers to be tripped from the breaker failure protection. Typical
setting is 200 ms.
1MRK505186-UEN D Section 3
IED application
379
Application manual
3.7.7.3 Setting parameters
Table 97: CCRBRF Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off / On
IBase 1 - 99999 A 1 3000 Base current
FunctionMode Current
Contact
Current&Contact
- - Current Detection principle for back-up trip
BuTripMode 2 out of 4
1 out of 3
1 out of 4
- - 1 out of 3 Back-up trip mode
RetripMode Retrip Off
CB Pos Check
No CBPos Check
- - Retrip Off Operation mode of re-trip logic
IP> 5 - 200 %IB 1 10 Operate phase current level in % of IBase
IN> 2 - 200 %IB 1 10 Operate residual current level in % of
IBase
t1 0.000 - 60.000 s 0.001 0.000 Time delay of re-trip
t2 0.000 - 60.000 s 0.001 0.150 Time delay of back-up trip
t2MPh 0.000 - 60.000 s 0.001 0.150 Time delay of back-up trip at multi-phase
start
tPulse 0.000 - 60.000 s 0.001 0.200 Trip pulse duration
Table 98: CCRBRF Group settings (advanced)
Name Values (Range) Unit Step Default Description
I>BlkCont 5 - 200 %IB 1 20 Current for blocking of CB contact
operation in % of IBase
t3 0.000 - 60.000 s 0.001 0.030 Additional time delay to t2 for a second
back-up trip
tCBAlarm 0.000 - 60.000 s 0.001 5.000 Time delay for CB faulty signal
3.7.8 Stub protection STBPTOC
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Stub protection STBPTOC
3I>STUB
SYMBOL-T V1 EN
50STB
Section 3 1MRK505186-UEN D
IED application
380
Application manual
3.7.8.1 Application
In a 1-breaker switchyard the line protection and the busbar protection normally
have overlap when a connected object is in service. When an object is taken out of
service it is normally required to keep the diagonal of the 1-breaker switchyard in
operation. This is done by opening the disconnector to the protected object. This
will, however, disable the normal object protection (for example the distance
protection) of the energized part between the circuit breakers and the open
disconnector.
Stub protection STBPTOC is a simple phase overcurrent protection, fed from the
two current transformer groups feeding the object taken out of service. The stub
protection is only activated when the disconnector of the object is open.
STBPTOCenables fast fault clearance of faults at the section between the CTs and
the open disconnector.
IEC05000465 V2 EN
Figure 188: Typical connection for STBPTOC in 1-breaker arrangement.
3.7.8.2 Setting guidelines
The parameters for Stub protection STBPTOC are set via the local HMI or PCM600.
1MRK505186-UEN D Section 3
IED application
381
Application manual
The following settings can be done for the stub protection.
Operation: Off/On
IBase: Base current in primary A. This current is used as reference for current
setting. It can be suitable to set this parameter to the rated primary current of the
current transformer where the current measurement is made.
ReleaseMode: This parameter can be set Release or Continuous. With theRelease
setting the function is only active when a binary release signal RELEASE into the
function is activated. This signal is normally taken from an auxiliary contact
(normally closed) of the line disconnector and connected to a binary input
RELEASE of the IED. With the settingContinuous the function is activated
independent of presence of any external release signal.
I>: Current level for the Stub protection, set in % of IBase. This parameter should
be set so that all faults on the stub can be detected. The setting should thus be based
on fault calculations.
t: Time delay of the operation. Normally the function shall be instantaneous.
3.7.8.3 Setting parameters
Table 99: STBPTOC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off / On
IBase 1 - 99999 A 1 3000 Base current
ReleaseMode Release
Continuous
- - Release Release of stub protection
I> 1 - 2500 %IB 1 200 Operate current level in % of IBase
Table 100: STBPTOC Group settings (advanced)
Name Values (Range) Unit Step Default Description
t 0.000 - 60.000 s 0.001 0.000 Time delay
3.7.9 Pole discordance protection CCRPLD
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Pole discordance protection CCRPLD
PD
SYMBOL-S V1 EN
52PD
Section 3 1MRK505186-UEN D
IED application
382
Application manual
3.7.9.1 Application
There is a risk that a circuit breaker will get discordance between the poles at
circuit breaker operation: closing or opening. One pole can be open and the other
two closed, or two poles can be open and one closed. Pole discordance of a circuit
breaker will cause unsymmetrical currents in the power system. The consequence
of this can be:
Negative sequence currents that will give stress on rotating machines
Zero sequence currents that might give unwanted operation of sensitive earth-
fault protections in the power system.
It is therefore important to detect situations with pole discordance of circuit
breakers. When this is detected the breaker should be tripped directly.
The Pole discordance protection CCRPLD will detect situation with deviating
positions of the poles of the protected circuit breaker. The protection has two
different options to make this detection:
By connecting the auxiliary contacts in the circuit breaker so that logic is
created, a signal can be sent to the protection, indicating pole discordance.
This logic can also be realized within the protection itself, by using opened
and close signals for each circuit breaker pole, connected to the protection.
Each phase current through the circuit breaker is measured. If the difference
between the phase currents is larger than a CurrUnsymLevel this is an
indication of pole discordance, and the protection will operate.
3.7.9.2 Setting guidelines
The parameters for the Pole discordance protection CCRPLD are set via the local
HMI or PCM600.
The following settings can be done for the pole discordance protection.
Operation: Off or On
IBase: Base current in primary A. This current is used as reference for current
setting. It can be suitable to set this parameter to the rated primary current of the
protected object where the current measurement is made.
tTrip: Time delay of the operation.
ContSel: Operation of the contact based pole discordance protection. Can be set:
Off/PD signal from CB/Pole pos aux cont. If PD signal from CB is chosen the logic
to detect pole discordance is made in the vicinity to the breaker auxiliary contacts
and only one signal is connected to the pole discordance function. If the Pole pos
aux cont. alternative is chosen each open close signal is connected to the IED and
the logic to detect pole discordance is realized within the function itself.
1MRK505186-UEN D Section 3
IED application
383
Application manual
CurrSel: Operation of the current based pole discordance protection. Can be set:
Off/CB oper monitor/Continuous monitor. In the alternative CB oper monitor the
function is activated only directly in connection to breaker open or close command
(during 200 ms). In the alternative Continuous monitor function is continuously
activated.
CurrUnsymLevel: Unsymmetrical magnitude of lowest phase current compared to
the highest, set in % of the highest phase current. Natural difference between phase
currents in 1 1/2 breaker installations must be considered. For circuit breakers in 1
1/2 breaker configured switch yards there might be natural unbalance currents
through the breaker. This is due to the existence of low impedance current paths in
the switch yard. This phenomenon must be considered in the setting of the parameter.
CurrRelLevel: Current magnitude for release of the function in % of IBase.
3.7.9.3 Setting parameters
Table 101: CCRPLD Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off / On
IBase 1 - 99999 - 1 3000 Base current
tTrip 0.000 - 60.000 s 0.001 0.300 Time delay between trip condition and
trip signal
ContSel Off
PD signal from CB
Pole pos aux cont.
- - Off Contact function selection
CurrSel Off
CB oper monitor
Continuous monitor
- - Off Current function selection
CurrUnsymLevel 0 - 100 % 1 80 Unsym magn of lowest phase current
compared to the highest.
CurrRelLevel 0 - 100 %IB 1 10 Current magnitude for release of the
function in % of IBase
3.7.10 Directional underpower protection GUPPDUP
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Directional underpower protection GUPPDUP
P <
SYMBOL-LL V1 EN
37
Section 3 1MRK505186-UEN D
IED application
384
Application manual
3.7.10.1 Application
The task of a generator in a power plant is to convert mechanical energy available
as a torque on a rotating shaft to electric energy.
Sometimes, the mechanical power from a prime mover may decrease so much that
it does not cover bearing losses and ventilation losses. Then, the synchronous
generator becomes a synchronous motor and starts to take electric power from the
rest of the power system. This operating state, where individual synchronous
machines operate as motors, implies no risk for the machine itself. If the generator
under consideration is very large and if it consumes lots of electric power, it may
be desirable to disconnect it to ease the task for the rest of the power system.
Often, the motoring condition may imply that the turbine is in a very dangerous
state. The task of the reverse power protection is to protect the turbine and not to
protect the generator itself.
Steam turbines easily become overheated if the steam flow becomes too low or if
the steam ceases to flow through the turbine. Therefore, turbo-generators should
have reverse power protection. There are several contingencies that may cause
reverse power: break of a main steam pipe, damage to one or more blades in the
steam turbine or inadvertent closing of the main stop valves. In the last case, it is
highly desirable to have a reliable reverse power protection. It may prevent damage
to an otherwise undamaged plant.
During the routine shutdown of many thermal power units, the reverse power
protection gives the tripping impulse to the generator breaker (the unit breaker). By
doing so, one prevents the disconnection of the unit before the mechanical power
has become zero. Earlier disconnection would cause an acceleration of the turbine
generator at all routine shutdowns. This should have caused overspeed and high
centrifugal stresses.
When the steam ceases to flow through a turbine, the cooling of the turbine blades
will disappear. Now, it is not possible to remove all heat generated by the windage
losses. Instead, the heat will increase the temperature in the steam turbine and
especially of the blades. When a steam turbine rotates without steam supply, the
electric power consumption will be about 2% of rated power. Even if the turbine
rotates in vacuum, it will soon become overheated and damaged. The turbine
overheats within minutes if the turbine loses the vacuum.
The critical time to overheating of a steam turbine varies from about 0.5 to 30
minutes depending on the type of turbine. A high-pressure turbine with small and
thin blades will become overheated more easily than a low-pressure turbine with
long and heavy blades. The conditions vary from turbine to turbine and it is
necessary to ask the turbine manufacturer in each case.
Power to the power plant auxiliaries may come from a station service transformer
connected to the primary side of the step-up transformer. Power may also come
from a start-up service transformer connected to the external network. One has to
1MRK505186-UEN D Section 3
IED application
385
Application manual
design the reverse power protection so that it can detect reverse power independent
of the flow of power to the power plant auxiliaries.
Hydro turbines tolerate reverse power much better than steam turbines do. Only
Kaplan turbine and bulb turbines may suffer from reverse power. There is a risk
that the turbine runner moves axially and touches stationary parts. They are not
always strong enough to withstand the associated stresses.
Ice and snow may block the intake when the outdoor temperature falls far below
zero. Branches and leaves may also block the trash gates. A complete blockage of
the intake may cause cavitations. The risk for damages to hydro turbines can justify
reverse power protection in unattended plants.
A hydro turbine that rotates in water with closed wicket gates will draw electric
power from the rest of the power system. This power will be about 10% of the
rated power. If there is only air in the hydro turbine, the power demand will fall to
about 3%.
Diesel engines should have reverse power protection. The generator will take about
15% of its rated power or more from the system. A stiff engine may require
perhaps 25% of the rated power to motor it. An engine that is well run in might
need no more than 5%. It is necessary to obtain information from the engine
manufacturer and to measure the reverse power during commissioning.
Gas turbines usually do not require reverse power protection.
Figure 189 illustrates the reverse power protection with underpower protection and
with overpower protection. The underpower protection gives a higher margin and
should provide better dependability. On the other hand, the risk for unwanted
operation immediately after synchronization may be higher. One should set the
underpower protection to trip if the active power from the generator is less than
about 2%. One should set the overpower protection to trip if the power flow from
the network to the generator is higher than 1%.
Underpower protection Overpower protection
Q Q
P P
Operating point
without
turbine torque
Margin Margin
Operate
Line
Operate
Line
Operating point
without
turbine torque
IEC09000019-2-en.vsd
IEC09000019 V2 EN
Figure 189: Reverse power protection with underpower or overpower protection
Section 3 1MRK505186-UEN D
IED application
386
Application manual
3.7.10.2 Setting guidelines
Operation: With the parameter Operation the function can be set On/Off.
IBase: The parameter IBase is set to the generator rated current in A, see
equation 318.
3
N
N
S
IBase
U
=
=
EQUATION1320 V1 EN (Equation 357)
where:
ILoadmin is the minimum load current on the line during normal operation conditions.
The timer tLoadOn is used to increase the security of the loss-of-load function for
example to avoid unwanted release due to transient inrush current when energizing
the line power transformer. The loss-of-load function will be released after the
timer tLoadOn has elapsed at the same time as the load current in all three phases
are above the setting LoadCurr. In normal acceleration applications there is no
need for delaying the release, so set the tLoadOn to zero.
The drop-out timer tLoadOff is used to determine the window for the current
release conditions for Loss-of-load. The timer is by default set to 300ms, which is
judged to be enough to secure the current release.
Section 3 1MRK505186-UEN D
IED application
584
Application manual
The setting of the minimum current detector, MinCurr, should be set higher than
the unsymmetrical current that might flow on the non faulty line, when the breaker
at remote end has opened (three-phase). At the same time it should be set below the
minimum load current transfer during normal operations that the line can be
subjected to. By default, MinCurr is set to 5% of IBase.
The pick-up timer tLowCurr determine the window needed for pick-up of the
minimum current value used to release the function. The timer is by default set to
200 ms, which is judged to be enough to avoid unwanted release of the function
(avoid unwanted trip).
3.13.4.3 Setting parameters
Table 180: ZCLCPLAL Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off / On
IBase 1 - 99999 A 1 3000 Base setting for current values
LoadCurr 1 - 100 %IB 1 10 Load current before disturbance in % of
IBase
LossOfLoad Off
On
- - Off Enable/Disable operation of Loss of load.
ZoneExtension Off
On
- - Off Enable/Disable operation of Zone
extension
MinCurr 1 - 100 %IB 1 5 Lev taken as curr loss due to remote CB
trip in % of IBase
tLowCurr 0.000 - 60.000 s 0.001 0.200 Time delay on pick-up for MINCURR
value
tLoadOn 0.000 - 60.000 s 0.001 0.000 Time delay on pick-up for load current
release
tLoadOff 0.000 - 60.000 s 0.001 0.300 Time delay on drop off for load current
release
3.13.5 Scheme communication logic for residual overcurrent
protection ECPSCH
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Scheme communication logic for
residual overcurrent protection
ECPSCH - 85
3.13.5.1 Application
To achieve fast fault clearance of earth faults on the part of the line not covered by
the instantaneous step of the residual overcurrent protection, the directional
residual overcurrent protection can be supported with a logic that uses
communication channels.
1MRK505186-UEN D Section 3
IED application
585
Application manual
One communication channel is used in each direction, which can transmit an on/off
signal if required. The performance and security of this function is directly related
to the transmission channel speed and security against false or lost signals.
In the directional scheme, information of the fault current direction must be
transmitted to the other line end.
With directional, comparison in permissive schemes, a short operate time of the
protection including a channel transmission time, can be achieved. This short
operate time enables rapid autoreclosing function after the fault clearance.
During a single-phase reclosing cycle, the autoreclosing device must block the
directional comparison earth-fault communication scheme.
The communication logic module enables blocking as well as permissive under/
overreaching schemes. The logic can also be supported by additional logic for weak-
end infeed and current reversal, included in the Current reversal and weak-end
infeed logic for residual overcurrent protection (ECRWPSCH) function.
Metallic communication paths adversely affected by fault generated noise may not
be suitable for conventional permissive schemes that rely on signal transmitted
during a protected line fault. With power line carrier, for example, the
communication signal may be attenuated by the fault, especially when the fault is
close to the line end, thereby disabling the communication channel.
To overcome the lower dependability in permissive schemes, an unblocking
function can be used. Use this function at older, less reliable, power line carrier
(PLC) communication, where the signal has to be sent through the primary fault.
The unblocking function uses a guard signal CRG, which must always be present,
even when no CR signal is received. The absence of the CRG signal during the
security time is used as a CR signal. This also enables a permissive scheme to
operate when the line fault blocks the signal transmission. Set the tSecurity to 35 ms.
3.13.5.2 Setting guidelines
The parameters for the scheme communication logic for residual overcurrent
protection function are set via the local HMI or PCM600.
The following settings can be done for the scheme communication logic for
residual overcurrent protection function:
Operation: Off or On.
SchemeType: This parameter can be set to Off , Intertrip, Permissive UR,
Permissive OR or Blocking.
tCoord: Delay time for trip from ECPSCH function. For Permissive under/
overreaching schemes, this timer can be set to 0. For Blocking scheme, the setting
should be minimum: the maximum signal transmission time +10 ms.
Section 3 1MRK505186-UEN D
IED application
586
Application manual
Unblock: Select Off if unblocking scheme with no alarm for loss of guard is used.
Set to Restart if unblocking scheme with alarm for loss of guard is used.
3.13.5.3 Setting parameters
Table 181: ECPSCH Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off / On
SchemeType Off
Intertrip
Permissive UR
Permissive OR
Blocking
- - Permissive UR Scheme type, Mode of Operation
tCoord 0.000 - 60.000 s 0.001 0.035 Communication scheme coordination
time
tSendMin 0.000 - 60.000 s 0.001 0.100 Minimum duration of a carrier send signal
Table 182: ECPSCH Group settings (advanced)
Name Values (Range) Unit Step Default Description
Unblock Off
NoRestart
Restart
- - Off Operation mode of unblocking logic
tSecurity 0.000 - 60.000 s 0.001 0.035 Security timer for loss of carrier guard
detection
3.13.6 Current reversal and weak-end infeed logic for residual
overcurrent protection ECRWPSCH
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Current reversal and weak-end infeed
logic for residual overcurrent protection
ECRWPSCH - 85
3.13.6.1 Application
Fault current reversal logic
Figure 273 and figure 274 show a typical system condition, which can result in a
fault current reversal.
Note that the fault current is reversed in line L2 after the breaker opening.
This can cause an unselective trip on line L2 if the current reversal logic does not
block the permissive overreaching scheme in the IED at B:2.
1MRK505186-UEN D Section 3
IED application
587
Application manual
Strong
source
L1
L2
A:1
A:2
B:1
B:2
A B
Weak
source
99000043.vsd
IEC99000043 V1 EN
Figure 273: Initial condition
Strong
source
L1
L2
A:1
A:2
B:1
B:2
A B
Weak
source
99000044.vsd
IEC99000044 V1 EN
Figure 274: Current distribution after the breaker at B:1 is opened
When breaker on the parallel line operates, the fault current on the non faulty line
is reversed. The IED at B:2 recognizes now the fault in forward direction. Together
with the remaining received signal it will trip the breaker in B:2. To ensure that this
does not occur, the permissive overreaching function needs to be blocked by IRVL,
until the received signal is reset.
The IED at remote end, where the forward direction element was initially activated,
must reset before the send signal is initiated from B:2. The delayed reset of output
signal IRVL also ensures the send signal from IED B:2 is held back until the
forward direction element is reset in IED A:2.
Weak-end infeed logic
Figure 275 shows a typical system condition that can result in a missing operation.
Note that there is no fault current from node B. This causes that the IED at B
cannot detect the fault and trip the breaker in B. To cope with this situation, a
selectable weak-end infeed logic is provided for the permissive overreaching scheme.
L1
A B
Strong
source
Weak
source
99000054.vsd
IEC99000054 V1 EN
Figure 275: Initial condition
Section 3 1MRK505186-UEN D
IED application
588
Application manual
3.13.6.2 Setting guidelines
The parameters for the current reversal and weak-end infeed logic for residual
overcurrent protection function are set via the local HMI or PCM600.
Current reversal
The current reversal function is set on or off by setting the parameter CurrRev to
On or Off. Time delays shall be set for the timers tPickUpRev and tDelayRev.
tPickUpRev is chosen shorter (<80%) than the breaker opening time, but minimum
20 ms.
tDelayRev is chosen at a minimum to the sum of protection reset time and the
communication reset time. A minimum tDelayRev setting of 40 ms is recommended.
The reset time of the directional residual overcurrent protection (EF4PTOC) is
typically 25 ms. If other type of residual overcurrent protection is used in the
remote line end, its reset time should be used.
The signal propagation time is in the range 3 10 ms/km for most types of
communication media. In communication networks small additional time delays
are added in multiplexers and repeaters. Theses delays are less than 1 ms per
process. It is often stated that the total propagation time is less than 5 ms.
When a signal arrives or ends there is a decision time to be added. This decision
time is highly dependent on the interface between communication and protection
used. In many cases external interface (teleprotection equipment) is used. This
equipment makes a decision and gives a binary signal to the protection device. In
case of analog teleprotection equipment typical decision time is in the range 10
30 ms. For digital teleprotection equipment this time is in the range 2 10 ms.
If the teleprotection equipment is integrated in the protection IED the decision time
can be slightly reduced.
Below the principle time sequence of signaling at current reversal is shown.
1MRK505186-UEN D Section 3
IED application
589
Application manual
Protection
Function
Protection
Function
Tele-
Protection
Equipment
Tele-
Protection
Equipment
Tele-
communication
System
CS from the
protection
function,
operating and
reset time
CS initiation to
the
communication
system, operating
and reset time
CS propagation,
propagation
CR selection and
decision,
operating and
reset time
CR to the
protection
function,
operating and
reset time
Time
Fault
occurs
Protection
pick-up
CS initiation
CR to
teleprot.
eq.
CR to
prot.
func
Fault current
reversal
Sending
protection
reset
CS to
communication
drop
CR
reception
drop
CR to
prot.
func
drop
Minimum setting of tDelay en05000536.vsd
IEC05000536 V1 EN
Figure 276: Time sequence of signaling at current reversal
Weak-end infeed
The weak-end infeed can be set by setting the parameter WEI to Off, Echo or Echo
& Trip. Operating zero sequence voltage when parameter WEI is set to Echo &
Trip is set with 3U0>.
The zero sequence voltage for a fault at the remote line end and appropriate fault
resistance is calculated.
To avoid unwanted trip from the weak-end infeed logic (if spurious signals should
occur), set the operate value of the broken delta voltage level detector (3U
0
) higher
than the maximum false network frequency residual voltage that can occur during
normal service conditions. The recommended minimum setting is two times the
false zero-sequence voltage during normal service conditions.
3.13.6.3 Setting parameters
Table 183: ECRWPSCH Group settings (basic)
Name Values (Range) Unit Step Default Description
CurrRev Off
On
- - Off Operating mode of Current Reversal
Logic
tPickUpRev 0.000 - 60.000 s 0.001 0.020 Pickup time for current reversal logic
tDelayRev 0.000 - 60.000 s 0.001 0.060 Time Delay to prevent Carrier send and
local trip
WEI Off
Echo
Echo & Trip
- - Off Operating mode of WEI logic
Table continues on next page
Section 3 1MRK505186-UEN D
IED application
590
Application manual
Name Values (Range) Unit Step Default Description
tPickUpWEI 0.000 - 60.000 s 0.001 0.000 Coordination time for the WEI logic
UBase 0.05 - 2000.00 kV 0.05 400.00 Base setting for voltage level
3U0> 5 - 70 %UB 1 25 Neutral voltage setting for fault
conditions measurement
3.13.7 Current reversal and weak-end infeed logic for phase
segregated communication ZC1WPSCH
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Current reversal and weak-end infeed
logic for phase segregated
communication
ZC1WPSCH - 85
3.13.7.1 Application
To achieve fast fault clearing for a fault on the part of the line not covered by the
instantaneous zone 1, the stepped distance protection function can be supported
with logic that uses communication channels.
For the phase segregated communication logic three channels in each direction,
which can transmit an on/off signal is required.
The performance and security of this function is directly related to the transmission
channels speed, and security against false or lost signals. For this reason special
communication channels are used for this purpose. When power line carrier is used
for communication, these special channels are strongly recommended due to the
communication disturbance caused by the primary fault.
Communication speed, or minimum time delay, is always of utmost importance
because the purpose for using communication is to improve the total tripping speed
of the scheme. To avoid false signals that could cause false tripping, it is necessary
to pay attention to the security of the communication channel. At the same time it
is important pay attention to the communication channel dependability to ensure
that proper signals are communicated during power system faults, the time during
which the protection schemes must perform their tasks flawlessly.
The logic supports the following communications schemes; -blocking scheme, -
permissive schemes (overreach and underreach) and - direct intertrip.
A permissive scheme is inherently faster and has better security against false
tripping than a blocking scheme. On the other hand, permissive scheme depends on
a received CR signal for a fast trip, so its dependability is lower than that of a
blocking scheme.
When single-phase tripping is required on parallel lines, an unwanted three-phase
trip can occur for simultaneous faults near the line end (typical last 20%).
1MRK505186-UEN D Section 3
IED application
591
Application manual
Simultaneous faults are one fault on each of the two lines but in different phases,
see figure 277. When simultaneous faults occur, the phase selectors at the remote
protection IED - relative to the faults - cannot discriminate between the fault on the
protected line and on the parallel line. The phase selector must be set to cover the
whole line with a margin and will also detect a fault on the parallel line.
Instantaneous phase-selective tripping for simultaneous faults close to line end is
not possible with the information that is available locally in the remote protection
IEDs relative to the faults. The protection IED near the faults detects the faults on
the protected line as a forward fault, and on the parallel line in reverse direction.
The directional phase selector in the two IEDs near the faults can discriminate
between the faults and issue correct single-phase tripping commands. [Flowing
Object]
L1N
Load
G
G L1N
en06000476.vsd
IEC06000476 V1 EN
Figure 277: Simultaneous faults on two parallel lines.
By using phase-segregated channels for the communication scheme, the correct
phase information in the protection IED near the faults can be transferred to the
other side protection IED. A correct single-phase trip can be achieved on both lines
and at both line IEDs.
The phase-segregated communication scheme requires three individual channels
between the protection IEDs on each line in both directions. In case of single-phase
faults, only one channel is activated at a time. But in case of multi-phase faults, two
or three channels are activated simultaneously.
The below description for the schemes generally presents one of the three identical
phases.
When only one channel is available in each direction, use the
optionally available three phase communication scheme logic
(ZCOM). Note that this logic can issue an unwanted three-phase
trip at the described simultaneous faults close to one line end.
Section 3 1MRK505186-UEN D
IED application
592
Application manual
Blocking schemes
In blocking scheme a reverse looking zone is used to send a block signal to remote
end to block an overreaching zone. Since the scheme is sending the blocking signal
during conditions where the protected line is healthy, it is common to use the line
itself as communication media (PLC). The scheme can be used on all types of line
length.
The blocking scheme is very dependable because it will operate for faults
anywhere on the protected line if the communication channel is out of service.
Conversely, it is less secure than permissive schemes because it will trip for
external faults within the reach of the tripping function if the communication
channel is out of service. Inadequate speed or dependability can cause spurious
tripping for external faults. Inadequate security can cause delayed tripping for
internal faults. To secure that the carrier send signal will arrive before the zone
used in the communication scheme will trip, the trip is released first after the time
delay tCoord has elapsed. The setting of tCoord must be set longer than the
maximum transmission time of the channel. A security margin of at least 10 ms
should be considered.
The timer tSendMin for prolonging the carrier send signal is proposed to set to zero
in blocking schemes.
Permissive schemes
In permissive scheme, permission to trip is sent from local end to remote end(s)
that is, protection at local end has detected a fault on the protected object. The
received signal(s) is combined with an overreaching zone and gives an
instantaneous trip if the received signal is present during the time the chosen zone
is detected a fault in forward direction. Either end may send a permissive (or
command) signal to trip to the other end(s), and the teleprotection equipment needs
to be able to receive while transmitting.
Depending on if the sending signal(s) is issued by underreaching or overreaching
zone, it is divided into Permissive underreach (PUR) or Permissive overreach
(POR) scheme.
Permissive underreach scheme
Permissive underreach scheme is not suitable to use on short line length due to
difficulties for distance protection measurement in general to distinguish between
internal and external faults in those applications. The underreaching zones at local
and remote end(s) must overlap in reach to prevent a gap between the protection
zones where faults would not be detected. If the underreaching zone do not meet
required sensitivity due to for instance fault infeed from remote end blocking or
permissive overreach scheme should be considered.
The carrier received signal (CR) must be received when the overreaching zone is
still activated to achieve an instantaneous trip. In some cases, due to the fault
current distribution, the overreaching zone can operate only after the fault has been
cleared at the IED nearest to the fault.
1MRK505186-UEN D Section 3
IED application
593
Application manual
There is a certain risk that in case of a trip from an independent tripping zone, the
zone issuing the carrier send signal (CS) resets before the overreaching zone has
operated at the remote IED. To assure a sufficient duration of the received signal
(CR), the send signal (CS), can be prolonged by a tSendMin reset timer. The
recommended setting of tSendMin is 100 ms. Since the received communication
signal is combined with the output from an overreaching zone, there is less concern
about false signal causing an incorrect trip. Therefore set the timer tCoord to zero.
Failure of the communication channel does not affect the selectivity, but delays
tripping at one end(s) for certain fault locations.
Permissive overreach scheme
In permissive overreach scheme there is an overreaching zone that issue the carrier
send signal. At remote end the received signal together with activating of an
overreaching zone gives instantaneous trip of the protected object. The
overreaching zone used in the teleprotection scheme must be activated at the same
time as the received signal is present. The scheme can be used for all type line lengths.
In permissive overreach schemes, the communication channel plays an essential
roll to obtaining fast tripping at both ends. Failure of the communication channel
may affect the selectivity and delay tripping at one end at least, for faults anywhere
along the protected circuit. Teleprotection operating in permissive overreach
scheme must beside the general requirement of fast and secure operation also
requirement on dependability must be considered. Inadequate security can cause
unwanted tripping for external faults. Inadequate speed or dependability can cause
delayed tripping for internal faults or even unwanted operations.
This scheme may use virtually any communication media that is not adversely
affected by electrical interference from fault generated noise or by electrical
phenomena, such as lightning, that cause faults. Communication media that uses
metallic path are particularly subjected to this type of interference, therefore, they
must be properly shielded or otherwise designed to provide an adequate
communication signal during power system faults. At the permissive overreaching
scheme, the carrier send signal (CS) might be issued in parallel both from an
overreaching zone and an underreaching, independent tripping zone. The CS signal
from the overreaching zone must not be prolonged while the CS signal from zone 1
can be prolonged.
To secure correct operations of current reversal logic in case of parallel lines, when
applied, the carrier send signal CS shall not be prolonged. So set the tSendMin to
zero in this case. There is no need to delay the trip at receive of the carrier signal,
so set the timer tCoord to zero.
Unblocking scheme
Unblocking scheme cannot be used at phase segregated communication schemes as
a failure of the communication channel cannot give any information about which
phase/phases have a fault.
Section 3 1MRK505186-UEN D
IED application
594
Application manual
Intertrip scheme
In some power system applications, there is a need to trip the remote end breaker
immediately from local protections. This applies, for instance, when transformers
or reactors are connected to the system without circuit-breakers or for remote
tripping following operation of breaker failure protection.
In intertrip scheme, the carrier send signal is initiated by an underreaching zone or
from an external protection (transformer or reactor protection). At remote end, the
received signals initiate a trip without any further protection criteria. To limit the
risk for unwanted trip due to spurious sending of signals, the timer tCoord should
be set to 10-30 ms dependant on type and security of the communication channel.
The general requirement for teleprotection equipment operating in intertripping
applications is that it should be very secure and very dependable, since both
inadequate security and dependability may cause unwanted operation. In some
applications the equipment shall be able to receive while transmitting, and
commands may be transmitted over longer time period than for other teleprotection
systems.
3.13.7.2 Setting guideline
The parameters for the scheme communication logic function are set via the local
HMI or PCM600.
Configure the zones used for the CS carrier send and for scheme communication
tripping by using the Application configuration tool.
The recommended settings of tCoord timer are based on maximal recommended
transmission time for analog channels according to IEC 60834-1. It is
recommended to coordinate the proposed settings with actual performance for the
teleprotection equipment to get optimized settings.
Permissive underreach scheme
Set Operation = On
Set Scheme type = Permissive UR
Set tCoord = 0 ms
Set tSendMin = 0.1 s
Set Unblock = Disable
Set Unblock = (Loss of guard signal will give both trip and alarm, chose NoRestart if only trip is required)
Set tSecurity = 0.035 s
Permissive overreach scheme
Set Operation = On
Set Scheme type = Permissive OR
Set tCoord = 0 ms
Table continues on next page
1MRK505186-UEN D Section 3
IED application
595
Application manual
Set tSendMin = 0.1 s
Set Unblock = Disable
Set Unblock = Restart (Loss of guard signal will give both trip and alarm, chose NoRestart if only trip is
required)
Set tSecurity = 0.035 s
Blocking scheme
Set Operation = On
Set Scheme type = Blocking
Set tCoord 25 ms (10ms + maximal transmission time)
Set tSendMin = 0 s
Set Unblock = Disable
Set tSecurity = 0.035 s
Intertrip scheme
Set Operation = On
Set Scheme type = Intertrip
Set tCoord 50 ms (10 ms + maximum transmission time)
Set tSendMin = 0.1 s
Set Unblock = Disable
Set tSecurity = 0.015 s
3.13.7.3 Setting parameters
Table 184: ZC1WPSCH Group settings (basic)
Name Values (Range) Unit Step Default Description
UBase 0.05 - 2000.00 kV 0.05 400.00 Base setting for Voltage level
OperCurrRev Off
On
- - Off Operating mode of Current Reversal
Logic
tPickUpRev 0.000 - 60.000 s 0.001 0.020 Pickup time for current reversal logic
tDelayRev 0.000 - 60.000 s 0.001 0.060 Time Delay to prevent Carrier send and
local trip
OperationWEI Off
Echo
Echo & Trip
- - Off Operating mode of WEI logic
UPE< 10 - 90 %UB 1 70 Phase to Earth voltage for detection of
fault condition
UPP< 10 - 90 %UB 1 70 Phase to Phase voltage for detection of
fault condition
tPickUpWEI 0.000 - 60.000 s 0.001 0.010 Coordination time for the WEI logic
Section 3 1MRK505186-UEN D
IED application
596
Application manual
3.14 Logic
3.14.1 Tripping logic SMPPTRC
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Tripping logic SMPPTRC
I->O
SYMBOL-K V1 EN
94
3.14.1.1 Application
All trip signals from the different protection functions shall be routed through the
trip logic. In its simplest alternative the logic will only link the TRIP signal and
make sure that it is long enough.
Tripping logic SMPPTRC offers three different operating modes:
Three-phase tripping for all fault types (3ph operating mode)
Single-phase tripping for single-phase faults and three-phase tripping for multi-
phase and evolving faults (1ph/3ph operating mode). The logic also issues a
three-phase tripping command when phase selection within the operating
protection functions is not possible, or when external conditions request three-
phase tripping.
Two-phase tripping for two-phase faults.
The three-phase trip for all faults offers a simple solution and is often sufficient in
well meshed transmission systems and in sub-transmission systems. Since most
faults, especially at the highest voltage levels, are single phase-to-earth faults, single-
phase tripping can be of great value. If only the faulty phase is tripped, power can
still be transferred on the line during the dead time that arises before reclosing. Single-
phase tripping during single-phase faults must be combined with single pole
reclosing.
To meet the different double, 1 breaker and other multiple circuit breaker
arrangements, two identical SMPPTRC function blocks may be provided within
the IED.
One SMPPTRC function block should be used for each breaker, if the line is
connected to the substation via more than one breaker. Assume that single-phase
tripping and autoreclosing is used on the line. Both breakers are then normally set
up for 1/3-phase tripping and 1/3-phase autoreclosing. As an alternative, the
breaker chosen as master can have single-phase tripping, while the slave breaker
could have three-phase tripping and autoreclosing. In the case of a permanent fault,
only one of the breakers has to be operated when the fault is energized a second
1MRK505186-UEN D Section 3
IED application
597
Application manual
time. In the event of a transient fault the slave breaker performs a three-phase
reclosing onto the non-faulted line.
The same philosophy can be used for two-phase tripping and autoreclosing.
To prevent closing of a circuit breaker after a trip the function can block the closing.
The two instances of the SMPPTRC function are identical except, for the name of
the function block (SMPPTRC1 and SMPPTRC2). References will therefore only
be made to SMPPTRC1 in the following description, but they also apply to
SMPPTRC2.
Three-phase tripping
A simple application with three-phase tripping from the logic block utilizes a part
of the function block. Connect the inputs from the protection function blocks to the
input TRIN. If necessary (normally the case) use a logic OR block to combine the
different function outputs to this input. Connect the output TRIP to the digital Output/
s on the IO board.
This signal can also be used for other purposes internally in the IED. An example
could be the starting of Breaker failure protection. The three outputs TRL1, TRL2,
TRL3 will always be activated at every trip and can be utilized on individual trip
outputs if single-phase operating devices are available on the circuit breaker even
when a three-phase tripping scheme is selected.
Set the function block to Program = 3Ph and set the required length of the trip
pulse to for example, tTripMin = 150ms.
For special applications such as Lock-out refer to the separate section below. The
typical connection is shown below in figure 278. Signals that are not used are dimmed.
BLOCK
BLKLKOUT
TRIN
TRINL1
TRINL2
TRINL3
PSL1
PSL2
PSL3
1PTRZ
1PTREF
P3PTR
SETLKOUT
RSTLKOUT
SMPPTRC
TRIP
TRL1
TRL2
TRL3
TR1P
TR2P
TR3P
CLLKOUT
1
Impedance protection zone 1 TRIP
EF4PTOC TRIP
en05000544.vsd
Impedance protection zone 3 TRIP
Impedance protection zone 2 TRIP
IEC05000544 V2 EN
Figure 278: Tripping logic SMPPTRC is used for a simple three-phase tripping
application
Section 3 1MRK505186-UEN D
IED application
598
Application manual
Single- and/or three-phase tripping
The single-/three-phase tripping will give single-phase tripping for single-phase
faults and three-phase tripping for multi-phase fault. The operating mode is always
used together with a single-phase autoreclosing scheme.
The single-phase tripping can include different options and the use of the different
inputs in the function block.
The inputs 1PTRZ and 1PTREF are used for single-phase tripping for distance
protection and directional earth fault protection as required.
The inputs are combined with the phase selection logic and the start signals from
the phase selector must be connected to the inputs PSL1, PSL2 and PSL3 to
achieve the tripping on the respective single-phase trip outputs TRL1, TRL2 and
TRL3. The Output TRIP is a general trip and activated independent of which phase
is involved. Depending on which phases are involved the outputs TR1P, TR2P and
TR3P will be activated as well.
When single-phase tripping schemes are used a single-phase autoreclosing attempt
is expected to follow. For cases where the autoreclosing is not in service or will not
follow for some reason, the input Prepare Three-phase Trip P3PTR must be
activated. This is normally connected to the respective output on the Synchrocheck,
energizing check, and synchronizing function SESRSYN but can also be connected
to other signals, for example an external logic signal. If two breakers are involved,
one TR block instance and one SESRSYN instance is used for each breaker. This
will ensure correct operation and behavior of each breaker.
The output Trip 3 Phase TR3P must be connected to the respective input in
SESRSYN to switch SESRSYN to three-phase reclosing. If this signal is not
activated SESRSYN will use single-phase reclosing dead time.
Note also that if a second line protection is utilizing the same
SESRSYN the three-phase trip signal must be generated, for
example by using the three-trip relays contacts in series and
connecting them in parallel to the TR3P output from the trip block.
The trip logic also has inputs TRINL1, TRINL2 and TRINL3 where phase-selected
trip signals can be connected. Examples can be individual phase inter-trips from
remote end or internal/external phase selected trip signals, which are routed
through the IED to achieve, for example SESRSYN, Breaker failure, and so on.
Other back-up functions are connected to the input TRIN as described above. A
typical connection for a single-phase tripping scheme is shown in figure 279.
1MRK505186-UEN D Section 3
IED application
599
Application manual
BLOCK
BLKLKOUT
TRIN
TRINL1
TRINL2
TRINL3
PSL1
PSL2
PSL3
1PTRZ
1PTREF
P3PTR
SETLKOUT
RSTLKOUT
SMPPTRC
TRIP
TRL1
TRL2
TRL3
TR1P
TR2P
TR3P
CLLKOUT
TR3P
SESRSYN
PREP3P
1
TR3P
Phase Selection
PSL1
PSL2
PSL3
Distance protection zone 1 TRIP
Distance protection zone 2 TRIP
Distance protection zone 3 TRIP
Overcurrent protection TRIP
IEC05000545-2-en.vsd
IEC05000545 V2 EN
Figure 279: The trip logic function SMPPTRC used for single-phase tripping
application
Single-, two- or three-phase tripping
The single-/two-/three-phase tripping mode provides single-phase tripping for single-
phase faults, two-phase tripping for two-phase faults and three-phase tripping for
multi-phase faults. The operating mode is always used together with an
autoreclosing scheme with setting Program = 1/2/3Ph or Program = 1/3Ph attempt.
The functionality is very similar to the single-phase scheme described above.
However SESRSYN must in addition to the connections for single phase above be
informed that the trip is two phase by connecting the trip logic output TR2P to the
respective input in SESRSYN.
Lock-out
This function block is provided with possibilities to initiate lock-out. The lock-out
can be set to only activate the block closing output CLLKOUT or initiate the block
closing output and also maintain the trip signal (latched trip).
The lock-out can then be manually reset after checking the primary fault by
activating the input reset Lock-Out RSTLKOUT.
If external conditions are required to initiate Lock-out but not initiate trip this can
be achieved by activating input SETLKOUT. The setting AutoLock = Off means
that the internal trip will not activate lock-out so only initiation of the input
SETLKOUT will result in lock-out. This is normally the case for overhead line
protection where most faults are transient. Unsuccessful autoreclose and back-up
zone tripping can in such cases be connected to initiate Lock-out by activating the
input SETLKOUT.
Section 3 1MRK505186-UEN D
IED application
600
Application manual
Blocking of the function block
The function block can be blocked in two different ways. Its use is dependent on
the application. Blocking can be initiated internally by logic, or by the operator
using a communication channel. Total blockage of the trip function is done by
activating the input BLOCK and can be used to block the output of the trip logic in
the event of internal failures. Blockage of lock-out output by activating input
BLKLKOUT is used for operator control of the lock-out function.
3.14.1.2 Setting guidelines
The parameters for Tripping logic SMPPTRC are set via the local HMI or PCM600.
The following trip parameters can be set to regulate tripping.
Operation: Sets the mode of operation. Off switches the tripping off. The normal
selection is On.
Program: Sets the required tripping scheme. Normally 3Ph or 1/2Ph are used.
TripLockout: Sets the scheme for lock-out. Off only activates lock-out output. On
activates the lock-out output and latching output contacts. The normal selection is
Off.
AutoLock: Sets the scheme for lock-out. Off only activates lock-out through the
input SETLKOUT. On also allows activation from trip function itself. The normal
selection is Off.
tTripMin: Sets the required minimum duration of the trip pulse. It should be set to
ensure that the breaker is tripped and if a signal is used to start Breaker failure
protection CCRBRF longer than the back-up trip timer in CCRBRF. Normal
setting is 0.150s.
3.14.1.3 Setting parameters
Table 185: SMPPTRC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - On Operation Off / On
Program 3 phase
1ph/3ph
1ph/2ph/3ph
- - 1ph/3ph Three ph; single or three ph; single, two
or three ph trip
tTripMin 0.000 - 60.000 s 0.001 0.150 Minimum duration of trip output signal
Table 186: SMPPTRC Group settings (advanced)
Name Values (Range) Unit Step Default Description
TripLockout Off
On
- - Off On: activate output (CLLKOUT) and trip
latch, Off: only outp
AutoLock Off
On
- - Off On: lockout from input (SETLKOUT) and
trip, Off: only inp
1MRK505186-UEN D Section 3
IED application
601
Application manual
3.14.2 Trip matrix logic TMAGGIO
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Trip matrix logic TMAGGIO - -
3.14.2.1 Application
Trip matrix logic (TMAGGIO) function is used to route trip signals and/or other
logical output signals to different output contacts on the IED.
TMAGGIO output signals and the physical outputs are available in PCM600 and
this allows the user to adapt the signals to the physical tripping outputs according
to the specific application needs.
3.14.2.2 Setting guidelines
Operation: Operation of function On/off.
PulseTime: Defines the pulse time delay. When used for direct tripping of circuit
breaker(s) the pulse time delay shall be set to approximately 0.150 seconds in order
to obtain satisfactory minimum duration of the trip pulse to the circuit breaker trip
coils.
OnDelay: Used to prevent output signals to be given for spurious inputs. Normally
set to 0 or a low value.
OffDelay: Defines a minimum on time for the outputs. When used for direct
tripping of circuit breaker(s) the off delay time shall be set to approximately 0.150
seconds in order to obtain satisfactory minimum duration of the trip pulse to the
circuit breaker trip coils.
ModeOutputx: Defines if output signal OUTPUTx (where x=1-3) is steady or pulsed.
3.14.2.3 Setting parameters
Table 187: TMAGGIO Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - On Operation Off / On
PulseTime 0.050 - 60.000 s 0.001 0.150 Output pulse time
OnDelay 0.000 - 60.000 s 0.001 0.000 Output on delay time
OffDelay 0.000 - 60.000 s 0.001 0.000 Output off delay time
Table continues on next page
Section 3 1MRK505186-UEN D
IED application
602
Application manual
Name Values (Range) Unit Step Default Description
ModeOutput1 Steady
Pulsed
- - Steady Mode for output ,1 steady or pulsed
ModeOutput2 Steady
Pulsed
- - Steady Mode for output 2, steady or pulsed
ModeOutput3 Steady
Pulsed
- - Steady Mode for output 3, steady or pulsed
3.14.3 Configurable logic blocks
3.14.3.1 Application
A set of standard logic blocks, like AND, OR etc, and timers are available for
adapting the IED configuration to the specific application needs.
There are no settings for AND gates, OR gates, inverters or XOR gates.
For normal On/Off delay and pulse timers the time delays and pulse lengths are set
from the local HMI or via the PST tool.
Both timers in the same logic block (the one delayed on pick-up and the one
delayed on drop-out) always have a common setting value.
For controllable gates, settable timers and SR flip-flops with memory, the setting
parameters are accessible via the local HMI or via the PST tool.
Configuration
Logic is configured using the ACT configuration tool.
Execution of functions as defined by the configurable logic blocks runs according
to a fixed sequence with different cycle times.
For each cycle time, the function block is given an serial execution number. This is
shown when using the ACT configuration tool with the designation of the function
block and the cycle time, see example below.
1MRK505186-UEN D Section 3
IED application
603
Application manual
IEC09000695-1-en.vsd
IEC09000695 V1 EN
Figure 280: Example designation, serial execution number and cycle time for
logic function
The execution of different function blocks within the same cycle is determined by
the order of their serial execution numbers. Always remember this when
connecting two or more logical function blocks in series.
Always be careful when connecting function blocks with a fast
cycle time to function blocks with a slow cycle time.
Remember to design the logic circuits carefully and always check
the execution sequence for different functions. In other cases,
additional time delays must be introduced into the logic schemes to
prevent errors, for example, race between functions.
3.14.3.2 Setting parameters
Table 188: TIMER Non group settings (basic)
Name Values (Range) Unit Step Default Description
T 0.000 - 90000.000 s 0.001 0.000 Time delay of function
Table 189: PULSETIMER Non group settings (basic)
Name Values (Range) Unit Step Default Description
T 0.000 - 90000.000 s 0.001 0.010 Time delay of function
Table 190: SRM Group settings (basic)
Name Values (Range) Unit Step Default Description
Memory Off
On
- - On Operating mode of the memory function
Section 3 1MRK505186-UEN D
IED application
604
Application manual
Table 191: GATE Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off/On
Table 192: TIMERSET Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off/On
t 0.000 - 90000.000 s 0.001 0.000 Delay for settable timer n
3.14.4 Fixed signal function block FXDSIGN
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Fixed signals FXDSIGN - -
3.14.4.1 Application
The Fixed signals function (FXDSIGN) generates a number of pre-set (fixed)
signals that can be used in the configuration of an IED, either for forcing the
unused inputs in other function blocks to a certain level/value, or for creating
certain logic.
Example for use of GRP_OFF signal in FXDSIGN
The Restricted earth fault function REFPDIF can be used both for auto-
transformers and normal transformers.
When used for auto-transformers, information from both windings parts, together
with the neutral point current, needs to be available to the function. This means that
three inputs are needed.
I3PW1CT1
I3PW2CT1
I3P
REFPDIF (87N)
IEC09000619-2-en.vsd
IEC09000619 V2 EN
Figure 281: REFPDIF function inputs for autotransformer application
For normal transformers only one winding and the neutral point is available. This
means that only two inputs are used. Since all group connections are mandatory to
1MRK505186-UEN D Section 3
IED application
605
Application manual
be connected, the third input needs to be connected to something, which is the
GRP_OFF signal in FXDSIGN function block.
I3PW1CT1
I3PW2CT1
I3P
REFPDIF (87N)
GRP_OFF
FXDSIGN
IEC09000620-2-en.vsd
IEC09000620 V2 EN
Figure 282: REFPDIF function inputs for normal transformer application
3.14.4.2 Setting parameters
The function does not have any parameters available in Local HMI or Protection
and Control IED Manager (PCM 600)
3.14.5 Boolean 16 to Integer conversion B16I
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Boolean 16 to integer conversion B16I - -
3.14.5.1 Application
Boolean 16 to integer conversion function B16I is used to transform a set of 16
binary (logical) signals into an integer. It can be used for example, to connect
logical output signals from a function (like distance protection) to integer inputs
from another function (like line differential protection). B16I does not have a
logical node mapping.
3.14.5.2 Setting parameters
The function does not have any parameters available in Local HMI or Protection
and Control IED Manager (PCM600)
Section 3 1MRK505186-UEN D
IED application
606
Application manual
3.14.6 Boolean 16 to Integer conversion with logic node
representation B16IGGIO
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Boolean 16 to integer conversion with
logic node representation
B16IGGIO - -
3.14.6.1 Application
Boolean 16 to integer conversion with logic node representation function
B16IGGIO is used to transform a set of 16 binary (logical) signals into an integer.
B16IGGIO can receive an integer from a station computer for example, over IEC
61850. These functions are very useful when you want to generate logical
commands (for selector switches or voltage controllers) by inputting an integer
number. B16IGGIO has a logical node mapping in IEC 61850.
3.14.6.2 Setting parameters
The function does not have any parameters available in the local HMI or Protection
and Control IED Manager (PCM600)
3.14.7 Integer to Boolean 16 conversion IB16
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Integer to boolean 16 conversion IB16 - -
3.14.7.1 Application
Integer to boolean 16 conversion function (IB16) is used to transform an integer
into a set of 16 binary (logical) signals. It can be used for example, to connect
integer output signals from a function (like distance protection) to binary (logical)
inputs in another function (like line differential protection). IB16 function does not
have a logical node mapping.
3.14.7.2 Setting parameters
The function does not have any parameters available in the local HMI or Protection
and Control IED Manager (PCM600)
3.14.8 Integer to Boolean 16 conversion with logic node
representation IB16GGIO
1MRK505186-UEN D Section 3
IED application
607
Application manual
Function description IEC 61850
identification
ANSI/IEEE C37.2
device number
Integer to boolean 16 conversion with
logic node representation
IB16GGIO - -
3.14.8.1 Application
Integer to boolean 16 conversion with logic node representation function
(IB16GGIO) is used to transform an integer into a set of 16 binary (logical) signals.
IB16GGIO function can receive an integer from a station computer for example,
over IEC 61850. These functions are very useful when the user wants to generate
logical commands (for selector switches or voltage controllers) by inputting an
integer number. IB16GGIO function has a logical node mapping in IEC 61850.
3.14.8.2 Setting parameters
The function does not have any parameters available in the local HMI or Protection
and Control IED Manager (PCM600)
3.15 Monitoring
3.15.1 Measurement
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Measurements CVMMXU
P, Q, S, I, U, f
SYMBOL-RR V1 EN
-
Phase current measurement CMMXU
I
SYMBOL-SS V1 EN
-
Phase-phase voltage measurement VMMXU
U
SYMBOL-UU V1 EN
-
Table continues on next page
Section 3 1MRK505186-UEN D
IED application
608
Application manual
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Current sequence component
measurement
CMSQI
I1, I2, I0
SYMBOL-VV V1 EN
-
Voltage sequence measurement VMSQI
U1, U2, U0
SYMBOL-TT V1 EN
-
Phase-neutral voltage measurement VNMMXU
U
SYMBOL-UU V1 EN
-
3.15.1.1 Application
Measurement functions is used for power system measurement, supervision and
reporting to the local HMI, monitoring tool within PCM600 or to station level for
example, via IEC 61850. The possibility to continuously monitor measured values
of active power, reactive power, currents, voltages, frequency, power factor etc. is
vital for efficient production, transmission and distribution of electrical energy. It
provides to the system operator fast and easy overview of the present status of the
power system. Additionally, it can be used during testing and commissioning of
protection and control IEDs in order to verify proper operation and connection of
instrument transformers (CTs and VTs). During normal service by periodic
comparison of the measured value from the IED with other independent meters the
proper operation of the IED analog measurement chain can be verified. Finally, it
can be used to verify proper direction orientation for distance or directional
overcurrent protection function.
The available measured values of an IED are depending on the
actual hardware (TRM) and the logic configuration made in PCM600.
All measured values can be supervised with four settable limits that is, low-low
limit, low limit, high limit and high-high limit. A zero clamping reduction is also
supported, that is, the measured value below a settable limit is forced to zero which
reduces the impact of noise in the inputs.
Dead-band supervision can be used to report measured signal value to station level
when change in measured value is above set threshold limit or time integral of all
changes since the last time value updating exceeds the threshold limit. Measure
value can also be based on periodic reporting.
The measurement function, CVMMXU, provides the following power system
quantities:
1MRK505186-UEN D Section 3
IED application
609
Application manual
P, Q and S: three phase active, reactive and apparent power
PF: power factor
U: phase-to-phase voltage amplitude
I: phase current amplitude
F: power system frequency
The measuring functions CMMXU, VNMMXU and VMMXU provide physical
quantities:
I: phase currents (amplitude and angle) (CMMXU)
U: voltages (phase-to-earth and phase-to-phase voltage, amplitude and angle)
(VMMXU, VNMMXU)
It is possible to calibrate the measuring function above to get better then class 0.5
presentation. This is accomplished by angle and amplitude compensation at 5, 30
and 100% of rated current and at 100% of rated voltage.
The power system quantities provided, depends on the actual
hardware, (TRM) and the logic configuration made in PCM600.
The measuring functions CMSQI and VMSQI provide sequential quantities:
I: sequence currents (positive, zero, negative sequence, amplitude and angle)
U: sequence voltages (positive, zero and negative sequence, amplitude and
angle).
The CVMMXU function calculates three-phase power quantities by using
fundamental frequency phasors (DFT values) of the measured current respectively
voltage signals. The measured power quantities are available either, as
instantaneously calculated quantities or, averaged values over a period of time (low
pass filtered) depending on the selected settings.
3.15.1.2 Zero clamping
The measuring functions, CMMXU, VMMXU, VNMMXU and CVMMXN have
no interconnections regarding any setting or parameter.
Zero clampings are also entirely handled by the ZeroDb for each and every signal
separately for each of the functions. For example, the zero clamping of U12 is
handled by UL12ZeroDb in VMMXU, zero clamping of I1 is handled by
IL1ZeroDb in CMMXU ETC.
Example how CVMMXN is operating:
The following outputs can be observed on the local HMI under Monitoring/
Servicevalues/SRV1
Section 3 1MRK505186-UEN D
IED application
610
Application manual
S Apparent three-phase power
P Active three-phase power
Q Reactive three-phase power
PF Power factor
ILAG I lagging U
ILEAD I leading U
U System mean voltage, calculated according to selected mode
I System mean current, calculated according to selected mode
F Frequency
The settings for this function is found under Setting/General setting/Monitoring/
Service values/SRV1
It can be seen that:
When system voltage falls below UGenZeroDB, the shown value for S, P, Q,
PF, ILAG, ILEAD, U and F on the local HMI is forced to zero
When system current falls below IGenZeroDB, the shown value for S, P, Q,
PF, ILAG, ILEAD, U and F on the local HMI is forced to zero
When the value of a single signal falls below the set dead band for that specific
signal, the value shown on the local HMI is forced to zero. For example, if
apparent three-phase power falls below SZeroDb the value for S on the local
HMI is forced to zero.
3.15.1.3 Setting guidelines
The available setting parameters of the measurement function CVMMXU,
CMMXU, VMMXU, CMSQI, VMSQI, VNMMXU are depending on the actual
hardware (TRM) and the logic configuration made in PCM600.
The parameters for the Measurement functions CVMMXU, CMMXU, VMMXU,
CMSQI, VMSQI, VNMMXU are set via the local HMI or PCM600.
Operation: Off/On. Every function instance (CVMMXU, CMMXU, VMMXU,
CMSQI, VMSQI, VNMMXU) can be taken in operation (On) or out of operation
(Off).
The following general settings can be set for the Measurement function
(CVMMXU).
PowAmpFact: Amplitude factor to scale power calculations.
PowAngComp: Angle compensation for phase shift between measured I & U.
Mode: Selection of measured current and voltage. There are 9 different ways of
calculating monitored three-phase values depending on the available VT inputs
connected to the IED. See parameter group setting table.
1MRK505186-UEN D Section 3
IED application
611
Application manual
k: Low pass filter coefficient for power measurement, U and I.
UGenZeroDb: Minimum level of voltage in % of UBase used as indication of zero
voltage (zero point clamping). If measured value is below UGenZeroDb calculated
S, P, Q and PF will be zero.
IGenZeroDb: Minimum level of current in % of IBase used as indication of zero
current (zero point clamping). If measured value is below IGenZeroDb calculated
S, P, Q and PF will be zero.
UBase: Base voltage in primary kV. This voltage is used as reference for voltage
setting. It can be suitable to set this parameter to the rated primary voltage
supervised object.
IBase: Base current in primary A. This current is used as reference for current
setting. It can be suitable to set this parameter to the rated primary current of the
supervised object.
UAmpCompY: Amplitude compensation to calibrate voltage measurements at Y%
of Ur, where Y is equal to 5, 30 or 100.
IAmpCompY: Amplitude compensation to calibrate current measurements at Y% of
Ir, where Y is equal to 5, 30 or 100.
IAngCompY: Angle compensation to calibrate angle measurements at Y% of Ir,
where Y is equal to 5, 30 or 100.
The following general settings can be set for the Phase-phase current
measurement (CMMXU).
IAmpCompY: Amplitude compensation to calibrate current measurements at Y% of
Ir, where Y is equal to 5, 30 or 100.
IAngCompY: Angle compensation to calibrate angle measurements at Y% of Ir,
where Y is equal to 5, 30 or 100.
The following general settings can be set for the Phase-phase voltage
measurement (VMMXU).
UAmpCompY: Amplitude compensation to calibrate voltage measurements at Y%
of Ur, where Y is equal to 5, 30 or 100.
UAngCompY: Angle compensation to calibrate angle measurements at Y% of Ur,
where Y is equal to 5, 30 or 100.
The following general settings can be set for all monitored quantities included in
the functions (CVMMXU, CMMXU, VMMXU, CMSQI, VMSQI, VNMMXU) X
in setting names below equals S, P, Q, PF, U, I, F, IL1-3, UL1-3UL12-31, I1, I2,
3I0, U1, U2 or 3U0.
Xmin: Minimum value for analog signal X set directly in applicable measuring unit.
Section 3 1MRK505186-UEN D
IED application
612
Application manual
Xmax: Maximum value for analog signal X.
XZeroDb: Zero point clamping. A signal value less than XZeroDb is forced to zero.
Observe the related zero point clamping settings in Setting group N for CVMMXU
(UGenZeroDb and IGenZeroDb). If measured value is below UGenZeroDb and/or
IGenZeroDb calculated S, P, Q and PF will be zero and these settings will override
XZeroDb.
XRepTyp: Reporting type. Cyclic (Cyclic), amplitude deadband (Dead band) or
integral deadband (Int deadband). The reporting interval is controlled by the
parameter XDbRepInt.
XDbRepInt: Reporting deadband setting. Cyclic reporting is the setting value and is
reporting interval in seconds. Amplitude deadband is the setting value in % of
measuring range. Integral deadband setting is the integral area, that is, measured
value in % of measuring range multiplied by the time between two measured values.
XHiHiLim: High-high limit. Set in applicable measuring unit.
XHiLim: High limit.
XLowLim: Low limit.
XLowLowLim: Low-low limit.
XLimHyst: Hysteresis value in % of range and is common for all limits.
All phase angles are presented in relation to defined reference channel. The
parameter PhaseAngleRef defines the reference, see section "Analog inputs".
Calibration curves
It is possible to calibrate the functions (CVMMXU, CMMXU, VNMMXU and
VMMXU) to get class 0.5 presentations of currents, voltages and powers. This is
accomplished by amplitude and angle compensation at 5, 30 and 100% of rated
current and voltage. The compensation curve will have the characteristic for
amplitude and angle compensation of currents as shown in figure 283 (example).
The first phase will be used as reference channel and compared with the curve for
calculation of factors. The factors will then be used for all related channels.
1MRK505186-UEN D Section 3
IED application
613
Application manual
IEC05000652 V2 EN
Figure 283: Calibration curves
Setting examples
Three setting examples, in connection to Measurement function (CVMMXU), are
provided:
Measurement function (CVMMXU) application for a 400 kV OHL
Measurement function (CVMMXU) application on the secondary side of a
transformer
Measurement function (CVMMXU) application for a generator
For each of them detail explanation and final list of selected setting parameters
values will be provided.
The available measured values of an IED are depending on the
actual hardware (TRM) and the logic configuration made in PCM600.
Measurement function application for a 400 kV OHL
Single line diagram for this application is given in the figure 284:
Section 3 1MRK505186-UEN D
IED application
614
Application manual
400kV Busbar
400kV OHL
P Q
800/1 A
400 0,1
/
3 3
kV
IEC09000039-1-en.vsd
IED
IEC09000039-1-EN V1 EN
Figure 284: Single line diagram for 400 kV OHL application
In order to monitor, supervise and calibrate the active and reactive power as
indicated in the above figure it is necessary to do the following:
1. Set correctly CT and VT data and phase angle reference channel
PhaseAngleRef (see section "Analog inputs") using PCM600 for analog input
channels
2. Connect, in PCM600, measurement function to three-phase CT and VT inputs
3. Set under General settings parameters for the Measurement function:
general settings as shown in table 193.
level supervision of active power as shown in table 194.
calibration parameters as shown in table 195.
1MRK505186-UEN D Section 3
IED application
615
Application manual
Table 193: General settings parameters for the Measurement function
Setting Short Description Selected
value
Comments
Operation Operation Off/On On Function must be On
PowAmpFact Amplitude factor to scale power
calculations
1.000 It can be used during
commissioning to achieve higher
measurement accuracy.
Typically no scaling is required
PowAngComp Angle compensation for phase
shift between measured I & U
0.0 It can be used during
commissioning to achieve higher
measurement accuracy.
Typically no angle compensation
is required. As well here required
direction of P & Q measurement
is towards protected object (as
per IED internal default direction)
Mode Selection of measured current
and voltage
L1, L2, L3 All three phase-to-earth VT
inputs are available
k Low pass filter coefficient for
power measurement, U and I
0.00 Typically no additional filtering is
required
UGenZeroDb Zero point clamping in % of
Ubase
25 Set minimum voltage level to
25%. Voltage below 25% will
force S, P and Q to zero.
IGenZeroDb Zero point clamping in % of Ibase 3 Set minimum current level to 3%.
Current below 3% will force S, P
and Q to zero.
UBase Base setting for voltage level in
kV
400.00 Set rated OHL phase-to-phase
voltage
IBase Base setting for current level in A 800 Set rated primary CT current
used for OHL
Table 194: Settings parameters for level supervision
Setting Short Description Selected
value
Comments
PMin Minimum value -750 Minimum expected load
PMax Minimum value 750 Maximum expected load
PZeroDb Zero point clamping in 0.001% of
range
3000 Set zero point clamping to 45
MW that is, 3% of 1500 MW
PRepTyp Reporting type db Select amplitude deadband
supervision
PDbRepInt Cycl: Report interval (s), Db: In
% of range, Int Db: In %s
2 Set db=30 MW that is, 2%
(larger changes than 30 MW will
be reported)
PHiHiLim High High limit (physical value) 600 High alarm limit that is, extreme
overload alarm
PHiLim High limit (physical value) 500 High warning limit that is,
overload warning
PLowLim Low limit (physical value) -800 Low warning limit. Not active
PLowLowlLim Low Low limit (physical value) -800 Low alarm limit. Not active
PLimHyst Hysteresis value in % of range
(common for all limits)
2 Set Hysteresis MW that is, 2%
Section 3 1MRK505186-UEN D
IED application
616
Application manual
Table 195: Settings for calibration parameters
Setting Short Description Selected
value
Comments
IAmpComp5 Amplitude factor to calibrate
current at 5% of Ir
0.00
IAmpComp30 Amplitude factor to calibrate
current at 30% of Ir
0.00
IAmpComp100 Amplitude factor to calibrate
current at 100% of Ir
0.00
UAmpComp5 Amplitude factor to calibrate
voltage at 5% of Ur
0.00
UAmpComp30 Amplitude factor to calibrate
voltage at 30% of Ur
0.00
UAmpComp100 Amplitude factor to calibrate
voltage at 100% of Ur
0.00
IAngComp5 Angle calibration for current at
5% of Ir
0.00
IAngComp30 Angle pre-calibration for current
at 30% of Ir
0.00
IAngComp100 Angle pre-calibration for current
at 100% of Ir
0.00
Measurement function application for a power transformer
Single line diagram for this application is given in figure 285.
1MRK505186-UEN D Section 3
IED application
617
Application manual
110kV Busbar
200/1
35/ 0,1kV
35kV Busbar
500/5
P Q
31,5 MVA
110/36,75/(10,5) kV
Yy0(d5)
U
L1L2
IEC09000040-1-en.vsd
IED
IEC09000040-1-EN V1 EN
Figure 285: Single line diagram for transformer application
In order to measure the active and reactive power as indicated in figure 285, it is
necessary to do the following:
1. Set correctly all CT and VT and phase angle reference channel PhaseAngleRef
(see section "Analog inputs") data using PCM600 for analog input channels
2. Connect, in PCM600, measurement function to LV side CT & VT inputs
3. Set the setting parameters for relevant Measurement function as shown in the
following table:
Section 3 1MRK505186-UEN D
IED application
618
Application manual
Table 196: General settings parameters for the Measurement function
Setting Short description Selected
value
Comment
Operation Operation Off/On On Function must be On
PowAmpFact Amplitude factor to scale power
calculations
1.000 Typically no scaling is required
PowAngComp Angle compensation for phase
shift between measured I & U
180.0 Typically no angle compensation
is required. However here the
required direction of P & Q
measurement is towards busbar
(Not per IED internal default
direction). Therefore angle
compensation have to be used in
order to get measurements in
aliment with the required
direction.
Mode Selection of measured current
and voltage
L1L2 Only UL1L2 phase-to-phase
voltage is available
k Low pass filter coefficient for
power measurement, U and I
0.00 Typically no additional filtering is
required
UGenZeroDb Zero point clamping in % of
Ubase
25 Set minimum voltage level to 25%
IGenZeroDb Zero point clamping in % of Ibase 3 Set minimum current level to 3%
UBase Base setting for voltage level in
kV
35.00 Set LV side rated phase-to-
phase voltage
IBase Base setting for current level in A 495 Set transformer LV winding rated
current
Measurement function application for a generator
Single line diagram for this application is given in figure 286.
1MRK505186-UEN D Section 3
IED application
619
Application manual
220kV Busbar
300/1
15/ 0,1kV
4000/5
100 MVA
242/15,65 kV
Yd5
U
L1L2
, U
L2L3
G
P Q
100MVA
15,65kV
IEC09000041-1-en.vsd
IED
IEC09000041-1-EN V1 EN
Figure 286: Single line diagram for generator application
In order to measure the active and reactive power as indicated in figure 286, it is
necessary to do the following:
1. Set correctly all CT and VT data and phase angle reference channel
PhaseAngleRef(see section "Analog inputs") using PCM600 for analog input
channels
2. Connect, in PCM600, measurement function to the generator CT & VT inputs
3. Set the setting parameters for relevant Measurement function as shown in the
following table:
Section 3 1MRK505186-UEN D
IED application
620
Application manual
Table 197: General settings parameters for the Measurement function
Setting Short description Selected
value
Comment
Operation Operation Off/On On Function must be On
PowAmpFact Amplitude factor to scale power
calculations
1.000 Typically no scaling is required
PowAngComp Angle compensation for phase
shift between measured I & U
0.0 Typically no angle compensation
is required. As well here required
direction of P & Q measurement
is towards protected object (as
per IED internal default direction)
Mode Selection of measured current
and voltage
Arone Generator VTs are connected
between phases (V-connected)
k Low pass filter coefficient for
power measurement, U and I
0.00 Typically no additional filtering is
required
UGenZeroDb Zero point clamping in % of
Ubase
25% Set minimum voltage level to 25%
IGenZeroDb Zero point clamping in % of Ibase 3 Set minimum current level to 3%
UBase Base setting for voltage level in
kV
15,65 Set generator rated phase-to-
phase voltage
IBase Base setting for current level in A 3690 Set generator rated current
3.15.1.4 Setting parameters
The available setting parameters of the measurement function (MMXU, MSQI) are
depending on the actual hardware (TRM) and the logic configuration made in
PCM600.
Table 198: CVMMXU Non group settings (basic)
Name Values (Range) Unit Step Default Description
SLowLim 0.000 -
10000000000.000
VA 0.001 0.000 Low limit (physical value)
SLowLowLim 0.000 -
10000000000.000
VA 0.001 0.000 Low Low limit (physical value)
SMin 0.000 -
10000000000.000
VA 0.001 0.000 Minimum value
SMax 0.000 -
10000000000.000
VA 0.001 1000000000.000 Maximum value
SRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
PMin -10000000000.000
- 10000000000.000
W 0.001 -1000000000.000 Minimum value
PMax -10000000000.000
- 10000000000.000
W 0.001 1000000000.000 Maximum value
PRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
Table continues on next page
1MRK505186-UEN D Section 3
IED application
621
Application manual
Name Values (Range) Unit Step Default Description
QMin -10000000000.000
- 10000000000.000
VAr 0.001 -1000000000.000 Minimum value
Operation Off
On
- - Off Operation Off / On
IBase 1 - 99999 A 1 3000 Base setting for current level in A
QMax -10000000000.000
- 10000000000.000
VAr 0.001 1000000000.000 Maximum value
QRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
UBase 0.05 - 2000.00 kV 0.05 400.00 Base setting for voltage level in kV
Mode L1, L2, L3
Arone
Pos Seq
L1L2
L2L3
L3L1
L1
L2
L3
- - L1, L2, L3 Selection of measured current and
voltage
PowAmpFact 0.000 - 6.000 - 0.001 1.000 Amplitude factor to scale power
calculations
PowAngComp -180.0 - 180.0 Deg 0.1 0.0 Angle compensation for phase shift
between measured I & U
k 0.00 - 1.00 - 0.01 0.00 Low pass filter coefficient for power
measurement, U and I
PFMin -1.000 - 0.000 - 0.001 -1.000 Minimum value
PFMax 0.000 - 1.000 - 0.001 1.000 Maximum value
PFRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
UMin -10000000000.000
- 10000000000.000
V 0.001 0.000 Minimum value
UMax -10000000000.000
- 10000000000.000
V 0.001 400000.000 Maximum value
URepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
IMin -10000000000.000
- 10000000000.000
A 0.001 0.000 Minimum value
IMax -10000000000.000
- 10000000000.000
A 0.001 1000.000 Maximum value
IRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
Table continues on next page
Section 3 1MRK505186-UEN D
IED application
622
Application manual
Name Values (Range) Unit Step Default Description
FrMin -10000000000.000
- 10000000000.000
Hz 0.001 0.000 Minimum value
FrMax -10000000000.000
- 10000000000.000
Hz 0.001 70.000 Maximum value
FrRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
Table 199: CVMMXU Non group settings (advanced)
Name Values (Range) Unit Step Default Description
SDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
SZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
SHiHiLim 0.000 -
10000000000.000
VA 0.001 900000000.000 High High limit (physical value)
SHiLim 0.000 -
10000000000.000
VA 0.001 800000000.000 High limit (physical value)
SLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (common
for all limits)
PDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
PZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
PHiHiLim -10000000000.000
- 10000000000.000
W 0.001 900000000.000 High High limit (physical value)
PHiLim -10000000000.000
- 10000000000.000
W 0.001 800000000.000 High limit (physical value)
PLowLim -10000000000.000
- 10000000000.000
W 0.001 -800000000.000 Low limit (physical value)
PLowLowLim -10000000000.000
- 10000000000.000
W 0.001 -900000000.000 Low Low limit (physical value)
PLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (common
for all limits)
QDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
QZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
QHiHiLim -10000000000.000
- 10000000000.000
VAr 0.001 900000000.000 High High limit (physical value)
QHiLim -10000000000.000
- 10000000000.000
VAr 0.001 800000000.000 High limit (physical value)
QLowLim -10000000000.000
- 10000000000.000
VAr 0.001 -800000000.000 Low limit (physical value)
QLowLowLim -10000000000.000
- 10000000000.000
VAr 0.001 -900000000.000 Low Low limit (physical value)
QLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (common
for all limits)
PFDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
Table continues on next page
1MRK505186-UEN D Section 3
IED application
623
Application manual
Name Values (Range) Unit Step Default Description
PFZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
UGenZeroDb 1 - 100 % 1 5 Zero point clamping in % of Ubase
PFHiHiLim -3.000 - 3.000 - 0.001 3.000 High High limit (physical value)
IGenZeroDb 1 - 100 % 1 5 Zero point clamping in % of Ibase
PFHiLim -3.000 - 3.000 - 0.001 2.000 High limit (physical value)
PFLowLim -3.000 - 3.000 - 0.001 -2.000 Low limit (physical value)
PFLowLowLim -3.000 - 3.000 - 0.001 -3.000 Low Low limit (physical value)
PFLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (common
for all limits)
UDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
UZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
UHiHiLim -10000000000.000
- 10000000000.000
V 0.001 460000.000 High High limit (physical value)
UHiLim -10000000000.000
- 10000000000.000
V 0.001 450000.000 High limit (physical value)
ULowLim -10000000000.000
- 10000000000.000
V 0.001 380000.000 Low limit (physical value)
ULowLowLim -10000000000.000
- 10000000000.000
V 0.001 350000.000 Low Low limit (physical value)
ULimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (common
for all limits)
IDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
IZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
IHiHiLim -10000000000.000
- 10000000000.000
A 0.001 900.000 High High limit (physical value)
IHiLim -10000000000.000
- 10000000000.000
A 0.001 800.000 High limit (physical value)
ILowLim -10000000000.000
- 10000000000.000
A 0.001 -800.000 Low limit (physical value)
ILowLowLim -10000000000.000
- 10000000000.000
A 0.001 -900.000 Low Low limit (physical value)
ILimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (common
for all limits)
FrDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
FrZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
FrHiHiLim -10000000000.000
- 10000000000.000
Hz 0.001 65.000 High High limit (physical value)
FrHiLim -10000000000.000
- 10000000000.000
Hz 0.001 63.000 High limit (physical value)
FrLowLim -10000000000.000
- 10000000000.000
Hz 0.001 47.000 Low limit (physical value)
FrLowLowLim -10000000000.000
- 10000000000.000
Hz 0.001 45.000 Low Low limit (physical value)
Table continues on next page
Section 3 1MRK505186-UEN D
IED application
624
Application manual
Name Values (Range) Unit Step Default Description
FrLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (common
for all limits)
UAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at
5% of Ur
UAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at
30% of Ur
UAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at
100% of Ur
IAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at
5% of Ir
IAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at
30% of Ir
IAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at
100% of Ir
IAngComp5 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 5% of Ir
IAngComp30 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 30% of Ir
IAngComp100 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 100% of Ir
Table 200: CMMXU Non group settings (basic)
Name Values (Range) Unit Step Default Description
IL1DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
Operation Off
On
- - Off Operation Mode On / Off
IBase 1 - 99999 A 1 3000 Base setting for current level in A
IL1Max 0.000 -
10000000000.000
A 0.001 1000.000 Maximum value
IL1RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
IL1AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
IL2DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
IL2Max 0.000 -
10000000000.000
A 0.001 1000.000 Maximum value
IL2RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
IL2AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
IL3DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
Table continues on next page
1MRK505186-UEN D Section 3
IED application
625
Application manual
Name Values (Range) Unit Step Default Description
IL3Max 0.000 -
10000000000.000
A 0.001 1000.000 Maximum value
IL3RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
IL3AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
Table 201: CMMXU Non group settings (advanced)
Name Values (Range) Unit Step Default Description
IL1ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
IL1HiHiLim 0.000 -
10000000000.000
A 0.001 900.000 High High limit (physical value)
IL1HiLim 0.000 -
10000000000.000
A 0.001 800.000 High limit (physical value)
IAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at
5% of Ir
IAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at
30% of Ir
IL1LowLim 0.000 -
10000000000.000
A 0.001 0.000 Low limit (physical value)
IL1LowLowLim 0.000 -
10000000000.000
A 0.001 0.000 Low Low limit (physical value)
IAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at
100% of Ir
IAngComp5 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 5% of Ir
IL1Min 0.000 -
10000000000.000
A 0.001 0.000 Minimum value
IAngComp30 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 30% of Ir
IAngComp100 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 100% of Ir
IL1LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
IL2ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
IL2HiHiLim 0.000 -
10000000000.000
A 0.001 900.000 High High limit (physical value)
IL2HiLim 0.000 -
10000000000.000
A 0.001 800.000 High limit (physical value)
IL2LowLim 0.000 -
10000000000.000
A 0.001 0.000 Low limit (physical value)
IL2LowLowLim 0.000 -
10000000000.000
A 0.001 0.000 Low Low limit (physical value)
IL2Min 0.000 -
10000000000.000
A 0.001 0.000 Minimum value
IL2LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
IL3ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
Table continues on next page
Section 3 1MRK505186-UEN D
IED application
626
Application manual
Name Values (Range) Unit Step Default Description
IL3HiHiLim 0.000 -
10000000000.000
A 0.001 900.000 High High limit (physical value)
IL3HiLim 0.000 -
10000000000.000
A 0.001 800.000 High limit (physical value)
IL3LowLim 0.000 -
10000000000.000
A 0.001 0.000 Low limit (physical value)
IL3LowLowLim 0.000 -
10000000000.000
A 0.001 0.000 Low Low limit (physical value)
IL3Min 0.000 -
10000000000.000
A 0.001 0.000 Minimum value
IL3LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
Table 202: VNMMXU Non group settings (basic)
Name Values (Range) Unit Step Default Description
UL1DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
Operation Off
On
- - Off Operation Mode On / Off
UBase 0.05 - 2000.00 kV 0.05 400.00 Base setting for voltage level in kV
UL1Max 0.000 -
10000000000.000
V 0.001 300000.000 Maximum value
UL1RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
UL1LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
UL1AnDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
UL2DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
UL2Max 0.000 -
10000000000.000
V 0.001 300000.000 Maximum value
UL2RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
UL2LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
UL2AnDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
UL3DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
UL3Max 0.000 -
10000000000.000
V 0.001 300000.000 Maximum value
Table continues on next page
1MRK505186-UEN D Section 3
IED application
627
Application manual
Name Values (Range) Unit Step Default Description
UL3RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
UL3LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
UL3AnDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
Table 203: VNMMXU Non group settings (advanced)
Name Values (Range) Unit Step Default Description
UL1ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
UL1HiHiLim 0.000 -
10000000000.000
V 0.001 260000.000 High High limit (physical value)
UL1HiLim 0.000 -
10000000000.000
V 0.001 240000.000 High limit (physical value)
UL1LowLim 0.000 -
10000000000.000
V 0.001 220000.000 Low limit (physical value)
UL1LowLowLim 0.000 -
10000000000.000
V 0.001 200000.000 Low Low limit (physical value)
UAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at
100% of Ur
UL1Min 0.000 -
10000000000.000
V 0.001 0.000 Minimum value
UL2ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
UL2HiHiLim 0.000 -
10000000000.000
V 0.001 260000.000 High High limit (physical value)
UL2HiLim 0.000 -
10000000000.000
V 0.001 240000.000 High limit (physical value)
UL2LowLim 0.000 -
10000000000.000
V 0.001 220000.000 Low limit (physical value)
UL2LowLowLim 0.000 -
10000000000.000
V 0.001 200000.000 Low Low limit (physical value)
UL2Min 0.000 -
10000000000.000
V 0.001 0.000 Minimum value
UL3ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
UL3HiHiLim 0.000 -
10000000000.000
V 0.001 260000.000 High High limit (physical value)
UL3HiLim 0.000 -
10000000000.000
V 0.001 240000.000 High limit (physical value)
UL3LowLim 0.000 -
10000000000.000
V 0.001 220000.000 Low limit (physical value)
UL3LowLowLim 0.000 -
10000000000.000
V 0.001 200000.000 Low Low limit (physical value)
UL3Min 0.000 -
10000000000.000
V 0.001 0.000 Minimum value
Section 3 1MRK505186-UEN D
IED application
628
Application manual
Table 204: VMMXU Non group settings (basic)
Name Values (Range) Unit Step Default Description
UL12DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
Operation Off
On
- - Off Operation Mode On / Off
UBase 0.05 - 2000.00 kV 0.05 400.00 Base setting for voltage level in kV
UL12Max 0.000 -
10000000000.000
V 0.001 500000.000 Maximum value
UL12RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
UL12AnDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
UL23DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
UL23Max 0.000 -
10000000000.000
V 0.001 500000.000 Maximum value
UL23RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
UL23AnDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
UL31DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
UL31Max 0.000 -
10000000000.000
V 0.001 500000.000 Maximum value
UL31RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
UL31AnDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
Table 205: VMMXU Non group settings (advanced)
Name Values (Range) Unit Step Default Description
UL12ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
UL12HiHiLim 0.000 -
10000000000.000
V 0.001 450000.000 High High limit (physical value)
UL12HiLim 0.000 -
10000000000.000
V 0.001 420000.000 High limit (physical value)
UL12LowLim 0.000 -
10000000000.000
V 0.001 380000.000 Low limit (physical value)
UL12LowLowLim 0.000 -
10000000000.000
V 0.001 350000.000 Low Low limit (physical value)
UAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at
100% of Ur
UL12Min 0.000 -
10000000000.000
V 0.001 0.000 Minimum value
Table continues on next page
1MRK505186-UEN D Section 3
IED application
629
Application manual
Name Values (Range) Unit Step Default Description
UL12LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
UL23ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
UL23HiHiLim 0.000 -
10000000000.000
V 0.001 450000.000 High High limit (physical value)
UL23HiLim 0.000 -
10000000000.000
V 0.001 420000.000 High limit (physical value)
UL23LowLim 0.000 -
10000000000.000
V 0.001 380000.000 Low limit (physical value)
UL23LowLowLim 0.000 -
10000000000.000
V 0.001 350000.000 Low Low limit (physical value)
UL23Min 0.000 -
10000000000.000
V 0.001 0.000 Minimum value
UL23LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
UL31ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
UL31HiHiLim 0.000 -
10000000000.000
V 0.001 450000.000 High High limit (physical value)
UL31HiLim 0.000 -
10000000000.000
V 0.001 420000.000 High limit (physical value)
UL31LowLim 0.000 -
10000000000.000
V 0.001 380000.000 Low limit (physical value)
UL31LowLowLim 0.000 -
10000000000.000
V 0.001 350000.000 Low Low limit (physical value)
UL31Min 0.000 -
10000000000.000
V 0.001 0.000 Minimum value
UL31LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
Table 206: CMSQI Non group settings (basic)
Name Values (Range) Unit Step Default Description
3I0DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
3I0Min 0.000 -
10000000000.000
A 0.001 0.000 Minimum value
3I0Max 0.000 -
10000000000.000
A 0.001 1000.000 Maximum value
3I0RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
3I0LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
3I0AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
Operation Off
On
- - Off Operation Mode On / Off
3I0AngMin -180.000 - 180.000 Deg 0.001 -180.000 Minimum value
Table continues on next page
Section 3 1MRK505186-UEN D
IED application
630
Application manual
Name Values (Range) Unit Step Default Description
3I0AngMax -180.000 - 180.000 Deg 0.001 180.000 Maximum value
3I0AngRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
I1DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
I1Min 0.000 -
10000000000.000
A 0.001 0.000 Minimum value
I1Max 0.000 -
10000000000.000
A 0.001 1000.000 Maximum value
I1RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
I1AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
I1AngMax -180.000 - 180.000 Deg 0.001 180.000 Maximum value
I1AngRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
I2DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
I2Min 0.000 -
10000000000.000
A 0.001 0.000 Minimum value
I2Max 0.000 -
10000000000.000
A 0.001 1000.000 Maximum value
I2RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
I2LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
I2AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
I2AngMin -180.000 - 180.000 Deg 0.001 -180.000 Minimum value
I2AngRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
Table 207: CMSQI Non group settings (advanced)
Name Values (Range) Unit Step Default Description
3I0ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
3I0HiHiLim 0.000 -
10000000000.000
A 0.001 900.000 High High limit (physical value)
3I0HiLim 0.000 -
10000000000.000
A 0.001 800.000 High limit (physical value)
3I0LowLim 0.000 -
10000000000.000
A 0.001 0.000 Low limit (physical value)
3I0LowLowLim 0.000 -
10000000000.000
A 0.001 0.000 Low Low limit (physical value)
Table continues on next page
1MRK505186-UEN D Section 3
IED application
631
Application manual
Name Values (Range) Unit Step Default Description
3I0AngZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
I1ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
I1HiHiLim 0.000 -
10000000000.000
A 0.001 900.000 High High limit (physical value)
I1HiLim 0.000 -
10000000000.000
A 0.001 800.000 High limit (physical value)
I1LowLim 0.000 -
10000000000.000
A 0.001 0.000 Low limit (physical value)
I1LowLowLim 0.000 -
10000000000.000
A 0.001 0.000 Low Low limit (physical value)
I1LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
I1AngZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
I1AngMin -180.000 - 180.000 Deg 0.001 -180.000 Minimum value
I2ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
I2HiHiLim 0.000 -
10000000000.000
A 0.001 900.000 High High limit (physical value)
I2HiLim 0.000 -
10000000000.000
A 0.001 800.000 High limit (physical value)
I2LowLim 0.000 -
10000000000.000
A 0.001 0.000 Low limit (physical value)
I2LowLowLim 0.000 -
10000000000.000
A 0.001 0.000 Low Low limit (physical value)
I2AngZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
I2AngMax -180.000 - 180.000 Deg 0.001 180.000 Maximum value
Table 208: VMSQI Non group settings (basic)
Name Values (Range) Unit Step Default Description
3U0DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
3U0Min 0.000 -
10000000000.000
V 0.001 0.000 Minimum value
3U0Max 0.000 -
10000000000.000
V 0.001 300000.000 Maximum value
3U0RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
3U0LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
3U0AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
Operation Off
On
- - Off Operation Mode On / Off
3U0AngZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
3U0AngMin -180.000 - 180.000 Deg 0.001 -180.000 Minimum value
Table continues on next page
Section 3 1MRK505186-UEN D
IED application
632
Application manual
Name Values (Range) Unit Step Default Description
3U0AngMax -180.000 - 180.000 Deg 0.001 180.000 Maximum value
3U0AngRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
U1DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
U1Min 0.000 -
10000000000.000
V 0.001 0.000 Minimum value
U1Max 0.000 -
10000000000.000
V 0.001 300000.000 Maximum value
U1RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
U1LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
U1AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
U2DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
U2Min 0.000 -
10000000000.000
V 0.001 0.000 Minimum value
U2Max 0.000 -
10000000000.000
V 0.001 300000.000 Maximum value
U2RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
U2LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
U2AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
U2AngMin -180.000 - 180.000 Deg 0.001 -180.000 Minimum value
U2AngMax -180.000 - 180.000 Deg 0.001 180.000 Maximum value
U2AngRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
UAmpPreComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to pre-calibrate voltage
at 5% of Ir
UAmpPreComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to pre-calibrate voltage
at 30% of Ir
UAmpPreComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to pre-calibrate voltage
at 100% of Ir
1MRK505186-UEN D Section 3
IED application
633
Application manual
Table 209: VMSQI Non group settings (advanced)
Name Values (Range) Unit Step Default Description
3U0ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
3U0HiHiLim 0.000 -
10000000000.000
V 0.001 260000.000 High High limit (physical value)
3U0HiLim 0.000 -
10000000000.000
V 0.001 240000.000 High limit (physical value)
3U0LowLim 0.000 -
10000000000.000
V 0.001 220000.000 Low limit (physical value)
3U0LowLowLim 0.000 -
10000000000.000
V 0.001 200000.000 Low Low limit (physical value)
U1ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
U1HiHiLim 0.000 -
10000000000.000
V 0.001 260000.000 High High limit (physical value)
U1HiLim 0.000 -
10000000000.000
V 0.001 240000.000 High limit (physical value)
U1LowLim 0.000 -
10000000000.000
V 0.001 220000.000 Low limit (physical value)
U1LowLowLim 0.000 -
10000000000.000
V 0.001 200000.000 Low Low limit (physical value)
U1AngZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
U1AngMin -180.000 - 180.000 Deg 0.001 -180.000 Minimum value
U1AngMax -180.000 - 180.000 Deg 0.001 180.000 Maximum value
U1AngRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
U2ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
U2HiHiLim 0.000 -
10000000000.000
V 0.001 260000.000 High High limit (physical value)
U2HiLim 0.000 -
10000000000.000
V 0.001 240000.000 High limit (physical value)
U2LowLim 0.000 -
10000000000.000
V 0.001 220000.000 Low limit (physical value)
U2LowLowLim 0.000 -
10000000000.000
V 0.001 200000.000 Low Low limit (physical value)
U2AngZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
3.15.2 Event counter CNTGGIO
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Event counter CNTGGIO
S00946 V1 EN
-
Section 3 1MRK505186-UEN D
IED application
634
Application manual
3.15.2.1 Application
Event counter (CNTGGIO) has six counters which are used for storing the number
of times each counter has been activated. CNTGGIO can be used to count how
many times a specific function, for example the tripping logic, has issued a trip
signal. All six counters have a common blocking and resetting feature.
3.15.2.2 Setting parameters
The function does not have any parameters available in Local HMI or Protection
and Control IED Manager (PCM600)
3.15.3 Event function EVENT
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Event function EVENT
S00946 V1 EN
-
3.15.3.1 Introduction
When using a Substation Automation system with LON or SPA communication,
time-tagged events can be sent at change or cyclically from the IED to the station
level. These events are created from any available signal in the IED that is
connected to the Event function (EVENT). The event function block is used for
LON and SPA communication.
Analog and double indication values are also transferred through EVENT function.
3.15.3.2 Setting guidelines
The parameters for the Event (EVENT) function are set via the local HMI or PCM600.
EventMask (Ch_1 - 16)
The inputs can be set individually as:
NoEvents
OnSet, at pick-up of the signal
OnReset, at drop-out of the signal
OnChange, at both pick-up and drop-out of the signal
AutoDetect
LONChannelMask or SPAChannelMask
Definition of which part of the event function block that shall generate events:
1MRK505186-UEN D Section 3
IED application
635
Application manual
Off
Channel 1-8
Channel 9-16
Channel 1-16
MinRepIntVal (1 - 16)
A time interval between cyclic events can be set individually for each input
channel. This can be set between 0.0 s to 1000.0 s in steps of 0.1 s. It should
normally be set to 0, that is, no cyclic communication.
It is important to set the time interval for cyclic events in an
optimized way to minimize the load on the station bus.
3.15.3.3 Setting parameters
Table 210: EVENT Non group settings (basic)
Name Values (Range) Unit Step Default Description
SPAChannelMask Off
Channel 1-8
Channel 9-16
Channel 1-16
- - Off SPA channel mask
LONChannelMask Off
Channel 1-8
Channel 9-16
Channel 1-16
- - Off LON channel mask
EventMask1 NoEvents
OnSet
OnReset
OnChange
AutoDetect
- - AutoDetect Reporting criteria for input 1
EventMask2 NoEvents
OnSet
OnReset
OnChange
AutoDetect
- - AutoDetect Reporting criteria for input 2
EventMask3 NoEvents
OnSet
OnReset
OnChange
AutoDetect
- - AutoDetect Reporting criteria for input 3
EventMask4 NoEvents
OnSet
OnReset
OnChange
AutoDetect
- - AutoDetect Reporting criteria for input 4
EventMask5 NoEvents
OnSet
OnReset
OnChange
AutoDetect
- - AutoDetect Reporting criteria for input 5
Table continues on next page
Section 3 1MRK505186-UEN D
IED application
636
Application manual
Name Values (Range) Unit Step Default Description
EventMask6 NoEvents
OnSet
OnReset
OnChange
AutoDetect
- - AutoDetect Reporting criteria for input 6
EventMask7 NoEvents
OnSet
OnReset
OnChange
AutoDetect
- - AutoDetect Reporting criteria for input 7
EventMask8 NoEvents
OnSet
OnReset
OnChange
AutoDetect
- - AutoDetect Reporting criteria for input 8
EventMask9 NoEvents
OnSet
OnReset
OnChange
AutoDetect
- - AutoDetect Reporting criteria for input 9
EventMask10 NoEvents
OnSet
OnReset
OnChange
AutoDetect
- - AutoDetect Reporting criteria for input 10
EventMask11 NoEvents
OnSet
OnReset
OnChange
AutoDetect
- - AutoDetect Reporting criteria for input 11
EventMask12 NoEvents
OnSet
OnReset
OnChange
AutoDetect
- - AutoDetect Reporting criteria for input 12
EventMask13 NoEvents
OnSet
OnReset
OnChange
AutoDetect
- - AutoDetect Reporting criteria for input 13
EventMask14 NoEvents
OnSet
OnReset
OnChange
AutoDetect
- - AutoDetect Reporting criteria for input 14
EventMask15 NoEvents
OnSet
OnReset
OnChange
AutoDetect
- - AutoDetect Reporting criteria for input 15
EventMask16 NoEvents
OnSet
OnReset
OnChange
AutoDetect
- - AutoDetect Reporting criteria for input 16
MinRepIntVal1 0 - 3600 s 1 2 Minimum reporting interval input 1
MinRepIntVal2 0 - 3600 s 1 2 Minimum reporting interval input 2
Table continues on next page
1MRK505186-UEN D Section 3
IED application
637
Application manual
Name Values (Range) Unit Step Default Description
MinRepIntVal3 0 - 3600 s 1 2 Minimum reporting interval input 3
MinRepIntVal4 0 - 3600 s 1 2 Minimum reporting interval input 4
MinRepIntVal5 0 - 3600 s 1 2 Minimum reporting interval input 5
MinRepIntVal6 0 - 3600 s 1 2 Minimum reporting interval input 6
MinRepIntVal7 0 - 3600 s 1 2 Minimum reporting interval input 7
MinRepIntVal8 0 - 3600 s 1 2 Minimum reporting interval input 8
MinRepIntVal9 0 - 3600 s 1 2 Minimum reporting interval input 9
MinRepIntVal10 0 - 3600 s 1 2 Minimum reporting interval input 10
MinRepIntVal11 0 - 3600 s 1 2 Minimum reporting interval input 11
MinRepIntVal12 0 - 3600 s 1 2 Minimum reporting interval input 12
MinRepIntVal13 0 - 3600 s 1 2 Minimum reporting interval input 13
MinRepIntVal14 0 - 3600 s 1 2 Minimum reporting interval input 14
MinRepIntVal15 0 - 3600 s 1 2 Minimum reporting interval input 15
MinRepIntVal16 0 - 3600 s 1 2 Minimum reporting interval input 16
3.15.4 Logical signal status report BINSTATREP
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Logical signal status report BINSTATREP - -
3.15.4.1 Application
The Logical signal status report (BINSTATREP) function makes it possible for a
SPA master to poll signals from various other function blocks.
BINSTATREP has 16 inputs and 16 outputs. The output status follows the inputs
and can be read from the local HMI or via SPA communication.
When an input is set, the respective output is set for a user defined time. If the
input signal remains set for a longer period, the output will remain set until the
input signal resets.
t t
INPUTn
OUTPUTn
IEC09000732-1-en.vsd
IEC09000732 V1 EN
Figure 287: BINSTATREP logical diagram
Section 3 1MRK505186-UEN D
IED application
638
Application manual
3.15.4.2 Setting guidelines
The pulse time t is the only setting for the Logical signal status report
(BINSTATREP). Each output can be set or reset individually, but the pulse time
will be the same for all outputs in the entire BINSTATREP function.
3.15.4.3 Setting parameters
Table 211: BINSTATREP Non group settings (basic)
Name Values (Range) Unit Step Default Description
t 0.000 - 60000.000 s 0.001 10.000 Time delay of function
3.15.5 Fault locator LMBRFLO
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Fault locator LMBRFLO - -
3.15.5.1 Application
The main objective of line protection and monitoring IEDs is fast, selective and
reliable operation for faults on a protected line section. Besides this, information on
distance to fault is very important for those involved in operation and maintenance.
Reliable information on the fault location greatly decreases the downtime of the
protected lines and increases the total availability of a power system.
The fault locator is started with the input CALCDIST to which trip signals
indicating in-line faults are connected, typically distance protection zone 1 and
accelerating zone or the line differential protection. The disturbance report must
also be started for the same faults since the function uses pre- and post-fault
information from the trip value recorder function (TVR).
Beside this information the function must be informed about faulted phases for
correct loop selection (phase selective outputs from differential protection, distance
protection, directional OC protection, and so on). The following loops are used for
different types of faults:
for 3 phase faults: loop L1 - L2.
for 2 phase faults: the loop between the faulted phases.
or 2 phase-to-earth faults: the loop between the faulted phases.
for phase-to-earth faults: the phase-to-earth loop.
The distance to the fault, which is calculated with a high accuracy, is stored
together with the recorded disturbances. This information can be read on the local
HMI, uploaded to PCM600 and is available on the station bus according to IEC 61850.
1MRK505186-UEN D Section 3
IED application
639
Application manual
The distance to fault can be recalculated on the local HMI by using the measuring
algorithm for different fault loops or for changed system parameters.
3.15.5.2 Setting guidelines
The parameters for the Fault locator function are set via the local HMI or PCM600.
The Fault locator algorithm uses phase voltages, phase currents and residual
current in observed bay (protected line) and residual current from a parallel bay
(line, which is mutual coupled to protected line).
The Fault locator has close connection to the Disturbance report function. All
external analog inputs (channel 1-30), connected to the Disturbance report
function, are available to the Fault locator and the function uses information
calculated by the Trip value recorder. After allocation of analog inputs to the
Disturbance report function, the user has to point out which analog inputs to be
used by the Fault locator. According to the default settings the first four analog
inputs are currents and next three are voltages in the observed bay (no parallel line
expected since chosen input is set to zero). Use the Parameter Setting tool within
PCM600 for changing analog configuration.
The list of parameters explains the meaning of the abbreviations. Figure 288 also
presents these system parameters graphically. Note, that all impedance values
relate to their primary values and to the total length of the protected line.
Z
0m
=Z
0m
+jX
0m
R
1A
+jX
1A
R
0L
+jX
0L
R
1L
+jX
1L
R
0L
+jX
0L
R
1L
+jX
1L
R
1B
+jX
1B
DRPRDRE
LMBRFLO
ANSI05000045_2_en.vsd
ANSI05000045 V2 EN
Figure 288: Simplified network configuration with network data, required for
settings of the fault location-measuring function
For a single-circuit line (no parallel line), the figures for mutual zero-sequence
impedance (X
0M
, R
0M
) and analog input are set at zero.
Power system specific parameter settings shown in table 2 are not general settings
but specific setting included in the setting groups, that is, this makes it possible to
change conditions for the Fault locator with short notice by changing setting group.
The source impedance is not constant in the network. However, this has a minor
influence on the accuracy of the distance-to-fault calculation, because only the
phase angle of the distribution factor has an influence on the accuracy. The phase
angle of the distribution factor is normally very low and practically constant,
Section 3 1MRK505186-UEN D
IED application
640
Application manual
because the positive sequence line impedance, which has an angle close to 90,
dominates it. Always set the source impedance resistance to values other than zero.
If the actual values are not known, the values that correspond to the source
impedance characteristic angle of 85 give satisfactory results.
Connection of analog currents
Connection diagram for analog currents included IN from parallel line shown in
figure 289
en07000113.vsd
L1
L2
L3
1
4
2
5
3
6
9
10
1
4
2
5
3
6
9
10
I1
I2
I3
I5
I1
I2
I3
I5
IEC07000113 V1 EN
Figure 289: Example of connection of parallel line IN for Fault locator LMBRFLO
3.15.5.3 Setting parameters
Table 212: LMBRFLO Group settings (basic)
Name Values (Range) Unit Step Default Description
R1A 0.001 - 1500.000 ohm/p 0.001 2.000 Source resistance A (near end)
X1A 0.001 - 1500.000 ohm/p 0.001 12.000 Source reactance A (near end)
R1B 0.001 - 1500.000 ohm/p 0.001 2.000 Source resistance B (far end)
X1B 0.001 - 1500.000 ohm/p 0.001 12.000 Source reactance B (far end)
R1L 0.001 - 1500.000 ohm/p 0.001 2.000 Positive sequence line resistance
X1L 0.001 - 1500.000 ohm/p 0.001 12.500 Positive sequence line reactance
R0L 0.001 - 1500.000 ohm/p 0.001 8.750 Zero sequence line resistance
X0L 0.001 - 1500.000 ohm/p 0.001 50.000 Zero sequence line reactance
Table continues on next page
1MRK505186-UEN D Section 3
IED application
641
Application manual
Name Values (Range) Unit Step Default Description
R0M 0.000 - 1500.000 ohm/p 0.001 0.000 Zero sequence mutual resistance
X0M 0.000 - 1500.000 ohm/p 0.001 0.000 Zero sequence mutual reactance
LineLength 0.0 - 10000.0 - 0.1 40.0 Length of line
Table 213: LMBRFLO Non group settings (basic)
Name Values (Range) Unit Step Default Description
DrepChNoIL1 1 - 30 Ch 1 1 Recorder input number recording phase
current, IL1
DrepChNoIL2 1 - 30 Ch 1 2 Recorder input number recording phase
current, IL2
DrepChNoIL3 1 - 30 Ch 1 3 Recorder input number recording phase
current, IL3
DrepChNoIN 0 - 30 Ch 1 4 Recorder input number recording
residual current, IN
DrepChNoIP 0 - 30 Ch 1 0 Recorder input number recording 3I0 on
parallel line
DrepChNoUL1 1 - 30 Ch 1 5 Recorder input number recording phase
voltage, UL1
DrepChNoUL2 1 - 30 Ch 1 6 Recorder input number recording phase
voltage, UL2
DrepChNoUL3 1 - 30 Ch 1 7 Recorder input number recording phase
voltage, UL3
3.15.6 Measured value expander block RANGE_XP
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Measured value expander block RANGE_XP - -
3.15.6.1 Application
The current and voltage measurements functions (CVMMXU, CMMXU, VMMXU
and VNMMXU), current and voltage sequence measurement functions (CMSQI
and VMSQI) and IEC 61850 generic communication I/O functions (MVGGIO) are
provided with measurement supervision functionality. All measured values can be
supervised with four settable limits, that is low-low limit, low limit, high limit and
high-high limit. The measure value expander block ( RANGE_XP) has been
introduced to be able to translate the integer output signal from the measuring
functions to 5 binary signals, that is below low-low limit, below low limit, normal,
above high-high limit or above high limit. The output signals can be used as
conditions in the configurable logic.
Section 3 1MRK505186-UEN D
IED application
642
Application manual
3.15.6.2 Setting guidelines
There are no settable parameters for the measured value expander block function.
3.15.7 Disturbance report DRPRDRE
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Analog input signals A41RADR - -
Disturbance report DRPRDRE - -
Disturbance report A1RADR - -
Disturbance report A4RADR - -
Disturbance report B1RBDR - -
3.15.7.1 Application
To get fast, complete and reliable information about disturbances in the primary and/
or in the secondary system it is very important to gather information on fault
currents, voltages and events. It is also important having a continuous event-
logging to be able to monitor in an overview perspective. These tasks are
accomplished by the disturbance report function DRPRDRE and facilitate a better
understanding of the power system behavior and related primary and secondary
equipment during and after a disturbance. An analysis of the recorded data
provides valuable information that can be used to explain a disturbance, basis for
change of IED setting plan, improve existing equipment, and so on. This
information can also be used in a longer perspective when planning for and
designing new installations, that is, a disturbance recording could be a part of
Functional Analysis (FA).
Disturbance report DRPRDRE, always included in the IED, acquires sampled data
of all selected analog and binary signals connected to the function blocks that is,
maximum 30 external analog signals,
10 internal derived analog signals, and
96 binary signals.
Disturbance report function is a common name for several functions that is,
Indications (IND), Event recorder (ER), Event list (EL), Trip value recorder
(TVR), Disturbance recorder (DR) and Fault locator (FL).
Disturbance report function is characterized by great flexibility as far as
configuration, starting conditions, recording times, and large storage capacity are
concerned. Thus, disturbance report is not dependent on the operation of protective
functions, and it can record disturbances that were not discovered by protective
functions for one reason or another. Disturbance report can be used as an advanced
stand-alone disturbance recorder.
1MRK505186-UEN D Section 3
IED application
643
Application manual
Every disturbance report recording is saved in the IED. The same applies to all
events, which are continuously saved in a ring-buffer. Local HMI can be used to
get information about the recordings, and the disturbance report files may be
uploaded in the PCM600 using the Disturbance handling tool, for report reading or
further analysis (using WaveWin, that can be found on the PCM600 installation
CD). The user can also upload disturbance report files using FTP or MMS (over
61850) clients.
If the IED is connected to a station bus (IEC 61850-8-1), the disturbance recorder
(record made and fault number) and the fault locator information are available as
GOOSE or Report Control data. The same information is obtainable if
IEC60870-5-103 is used.
3.15.7.2 Setting guidelines
The setting parameters for the Disturbance report function DRPRDRE are set via
the local HMI or PCM600.
It is possible to handle up to 40 analog and 96 binary signals, either internal signals
or signals coming from external inputs. The binary signals are identical in all
functions that is, Disturbance recorder (DR), Event recorder (ER), Indication
(IND), Trip value recorder (TVR) and Event list (EL) function.
User-defined names of binary and analog input signals is set using PCM600. The
analog and binary signals appear with their user-defined names. The name is used
in all related functions (Disturbance recorder (DR), Event recorder (ER), Indication
(IND), Trip value recorder (TVR) and Event list (EL)).
Figure 290 shows the relations between Disturbance report, included functions and
function blocks. Event list (EL), Event recorder (ER) and Indication (IND) uses
information from the binary input function blocks (BxRBDR). Trip value recorder
(TVR) uses analog information from the analog input function blocks (AxRADR),
which is used by Fault locator (FL) after estimation by Trip Value Recorder
(TVR). Disturbance report function acquires information from both AxRADR and
BxRBDR.
Section 3 1MRK505186-UEN D
IED application
644
Application manual
Trip value rec Fault locator
Event list
Event recorder
Indications
Disturbance
recorder
Disturbance Report
Binary signals
Analog signals
A4RADR
B6RBDR
DRPRDRE FL
IEC09000336-2-en.vsd
A1-4RADR
B1-6RBDR
IEC09000336 V2 EN
Figure 290: Disturbance report functions and related function blocks
For Disturbance report function there are a number of settings which also
influences the sub-functions.
Three LED indications placed above the LCD screen makes it possible to get quick
status information about the IED.
Green LED:
Steady light In Service
Flashing light Internal failure
Dark No power supply
Yellow LED:
Steady light A Disturbance Report is triggered
Flashing light The IED is in test mode
Red LED:
Steady light Triggered on binary signal N with SetLEDN = On
Operation
The operation of Disturbance report function DRPRDRE has to be set On or Off. If
Off is selected, note that no disturbance report is registered, and none sub-function
will operate (the only general parameter that influences Event list (EL)).
1MRK505186-UEN D Section 3
IED application
645
Application manual
Operation = Off:
Disturbance reports are not stored.
LED information (yellow - start, red - trip) is not stored or changed.
Operation = On:
Disturbance reports are stored, disturbance data can be read from the local
HMI and from a PC using PCM600.
LED information (yellow - start, red - trip) is stored.
Every recording will get a number (0 to 999) which is used as identifier (local
HMI, disturbance handling tool and IEC 61850). An alternative recording
identification is date, time and sequence number. The sequence number is
automatically increased by one for each new recording and is reset to zero at
midnight. The maximum number of recordings stored in the IED is 100. The oldest
recording will be overwritten when a new recording arrives (FIFO).
To be able to delete disturbance records, Operation parameter has
to be On.
Recording times
The different recording times for Disturbance report are set (the pre-fault time, post-
fault time, and limit time). These recording times affect all sub-functions more or
less but not the Event list (EL) function.
Prefault recording time (PreFaultRecT) is the recording time before the starting
point of the disturbance. The setting should be at least 0.1 s to ensure enough
samples for the estimation of pre-fault values in the Trip value recorder (TVR)
function.
Postfault recording time (PostFaultRecT) is the maximum recording time after the
disappearance of the trig-signal (does not influence the Trip value recorder (TVR)
function).
Recording time limit (TimeLimit) is the maximum recording time after trig. The
parameter limits the recording time if some trigging condition (fault-time) is very
long or permanently set (does not influence the Trip value recorder (TVR) function).
Post retrigger (PostRetrig) can be set to On or Off. Makes it possible to choose
performance of Disturbance report function if a new trig signal appears in the post-
fault window.
PostRetrig = Off
The function is insensitive for new trig signals during post fault time.
PostRetrig = On
Section 3 1MRK505186-UEN D
IED application
646
Application manual
The function completes current report and starts a new complete report that is, the
latter will include:
new pre-fault- and fault-time (which will overlap previous report)
events and indications might be saved in the previous report too, due to overlap
new fault locator and trip value calculations if installed, in operation and started
Operation in test mode
If the IED is in test mode and OpModeTest = Off. Disturbance report function does
not save any recordings and no LED information is displayed.
If the IED is in test mode and OpModeTest = On. Disturbance report function
works in normal mode and the status is indicated in the saved recording.
Binary input signals
Up to 96 binary signals can be selected among internal logical and binary input
signals. The configuration tool is used to configure the signals.
For each of the 96 signals, it is also possible to select if the signal is to be used as a
trigger for the start of Disturbance report and if the trigger should be activated on
positive (1) or negative (0) slope.
OperationN: Disturbance report may trig for binary input N (On) or not (Off).
TrigLevelN: Trig on positive (Trig on 1) or negative (Trig on 0) slope for binary
input N.
Func103N: Function type number (0-255) for binary input N according to
IEC-60870-5-103, that is, 128: Distance protection, 160: overcurrent protection,
176: transformer differential protection and 192: line differential protection.
Info103N: Information number (0-255) for binary input N according to
IEC-60870-5-103, that is, 69-71: Trip L1-L3, 78-83: Zone 1-6.
See also description in the chapter IEC 60870-5-103.
Analog input signals
Up to 40 analog signals can be selected among internal analog and analog input
signals. PCM600 is used to configure the signals.
The analog trigger of Disturbance report is not affected if analog input M is to be
included in the disturbance recording or not (OperationM = On/Off).
If OperationM = Off, no waveform (samples) will be recorded and reported in
graph. However, Trip value, pre-fault and fault value will be recorded and reported.
The input channel can still be used to trig the disturbance recorder.
If OperationM = On, waveform (samples) will also be recorded and reported in graph.
NomValueM: Nominal value for input M.
1MRK505186-UEN D Section 3
IED application
647
Application manual
OverTrigOpM, UnderTrigOpM: Over or Under trig operation, Disturbance report
may trig for high/low level of analog input M (On) or not (Off).
OverTrigLevelM, UnderTrigLevelM: Over or under trig level, Trig high/low level
relative nominal value for analog input M in percent of nominal value.
Sub-function parameters
All functions are in operation as long as Disturbance report is in operation.
Indications
IndicationMaN: Indication mask for binary input N. If set (Show), a status change
of that particular input, will be fetched and shown in the disturbance summary on
local HMI. If not set (Hide), status change will not be indicated.
SetLEDN: Set red TRIP LED on local HMI in front of the IED if binary input N
changes status.
Disturbance recorder
OperationM: Analog channel M is to be recorded by the disturbance recorder (On)
or not (Off).
If OperationM = Off, no waveform (samples) will be recorded and reported in
graph. However, Trip value, pre-fault and fault value will be recorded and reported.
The input channel can still be used to trig the disturbance recorder.
If OperationM = On, waveform (samples) will also be recorded and reported in graph.
Event recorder
Event recorder (ER) function has no dedicated parameters.
Trip value recorder
ZeroAngleRef: The parameter defines which analog signal that will be used as
phase angle reference for all other analog input signals. This signal will also be
used for frequency measurement and the measured frequency is used when
calculating trip values. It is suggested to point out a sampled voltage input signal,
for example, a line or busbar phase voltage (channel 1-30).
Event list
Event list (EL) (SOE) function has no dedicated parameters.
Consideration
The density of recording equipment in power systems is increasing, since the
number of modern IEDs, where recorders are included, is increasing. This leads to
a vast number of recordings at every single disturbance and a lot of information has
to be handled if the recording functions do not have proper settings. The goal is to
optimize the settings in each IED to be able to capture just valuable disturbances
and to maximize the number that is possible to save in the IED.
The recording time should not be longer than necessary (PostFaultrecT and
TimeLimit).
Section 3 1MRK505186-UEN D
IED application
648
Application manual
Should the function record faults only for the protected object or cover more?
How long is the longest expected fault clearing time?
Is it necessary to include reclosure in the recording or should a persistent fault
generate a second recording (PostRetrig)?
Minimize the number of recordings:
Binary signals: Use only relevant signals to start the recording that is,
protection trip, carrier receive and/or start signals.
Analog signals: The level triggering should be used with great care, since
unfortunate settings will cause enormously number of recordings. If
nevertheless analog input triggering is used, chose settings by a sufficient
margin from normal operation values. Phase voltages are not recommended for
trigging.
Remember that values of parameters set elsewhere are linked to the information on
a report. Such parameters are, for example, station and object identifiers, CT and
VT ratios.
3.15.7.3 Setting parameters
Table 214: RDRE Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off/On
PreFaultRecT 0.05 - 1.00 s 0.01 0.10 Pre-fault recording time
PostFaultRecT 0.1 - 10.0 s 0.1 0.5 Post-fault recording time
TimeLimit 0.5 - 10.0 s 0.1 1.0 Fault recording time limit
PostRetrig Off
On
- - Off Post-fault retrig enabled (On) or not (Off)
ZeroAngleRef 1 - 30 Ch 1 1 Trip value recorder, phasor reference
channel
OpModeTest Off
On
- - Off Operation mode during test mode
Table 215: A1RADR Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation01 Off
On
- - Off Operation On/Off
NomValue01 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 1
UnderTrigOp01 Off
On
- - Off Use under level trig for analogue cha 1
(on) or not (off)
UnderTrigLe01 0 - 200 % 1 50 Under trigger level for analogue cha 1 in
% of signal
OverTrigOp01 Off
On
- - Off Use over level trig for analogue cha 1
(on) or not (off)
Table continues on next page
1MRK505186-UEN D Section 3
IED application
649
Application manual
Name Values (Range) Unit Step Default Description
OverTrigLe01 0 - 5000 % 1 200 Over trigger level for analogue cha 1 in
% of signal
Operation02 Off
On
- - Off Operation On/Off
NomValue02 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 2
UnderTrigOp02 Off
On
- - Off Use under level trig for analogue cha 2
(on) or not (off)
UnderTrigLe02 0 - 200 % 1 50 Under trigger level for analogue cha 2 in
% of signal
OverTrigOp02 Off
On
- - Off Use over level trig for analogue cha 2
(on) or not (off)
OverTrigLe02 0 - 5000 % 1 200 Over trigger level for analogue cha 2 in
% of signal
Operation03 Off
On
- - Off Operation On/Off
NomValue03 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 3
UnderTrigOp03 Off
On
- - Off Use under level trig for analogue cha 3
(on) or not (off)
UnderTrigLe03 0 - 200 % 1 50 Under trigger level for analogue cha 3 in
% of signal
OverTrigOp03 Off
On
- - Off Use over level trig for analogue cha 3
(on) or not (off)
OverTrigLe03 0 - 5000 % 1 200 Overtrigger level for analogue cha 3 in %
of signal
Operation04 Off
On
- - Off Operation On/Off
NomValue04 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 4
UnderTrigOp04 Off
On
- - Off Use under level trig for analogue cha 4
(on) or not (off)
UnderTrigLe04 0 - 200 % 1 50 Under trigger level for analogue cha 4 in
% of signal
OverTrigOp04 Off
On
- - Off Use over level trig for analogue cha 4
(on) or not (off)
OverTrigLe04 0 - 5000 % 1 200 Over trigger level for analogue cha 4 in
% of signal
Operation05 Off
On
- - Off Operation On/Off
NomValue05 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 5
UnderTrigOp05 Off
On
- - Off Use under level trig for analogue cha 5
(on) or not (off)
UnderTrigLe05 0 - 200 % 1 50 Under trigger level for analogue cha 5 in
% of signal
OverTrigOp05 Off
On
- - Off Use over level trig for analogue cha 5
(on) or not (off)
OverTrigLe05 0 - 5000 % 1 200 Over trigger level for analogue cha 5 in
% of signal
Operation06 Off
On
- - Off Operation On/Off
Table continues on next page
Section 3 1MRK505186-UEN D
IED application
650
Application manual
Name Values (Range) Unit Step Default Description
NomValue06 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 6
UnderTrigOp06 Off
On
- - Off Use under level trig for analogue cha 6
(on) or not (off)
UnderTrigLe06 0 - 200 % 1 50 Under trigger level for analogue cha 6 in
% of signal
OverTrigOp06 Off
On
- - Off Use over level trig for analogue cha 6
(on) or not (off)
OverTrigLe06 0 - 5000 % 1 200 Over trigger level for analogue cha 6 in
% of signal
Operation07 Off
On
- - Off Operation On/Off
NomValue07 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 7
UnderTrigOp07 Off
On
- - Off Use under level trig for analogue cha 7
(on) or not (off)
UnderTrigLe07 0 - 200 % 1 50 Under trigger level for analogue cha 7 in
% of signal
OverTrigOp07 Off
On
- - Off Use over level trig for analogue cha 7
(on) or not (off)
OverTrigLe07 0 - 5000 % 1 200 Over trigger level for analogue cha 7 in
% of signal
Operation08 Off
On
- - Off Operation On/Off
NomValue08 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 8
UnderTrigOp08 Off
On
- - Off Use under level trig for analogue cha 8
(on) or not (off)
UnderTrigLe08 0 - 200 % 1 50 Under trigger level for analogue cha 8 in
% of signal
OverTrigOp08 Off
On
- - Off Use over level trig for analogue cha 8
(on) or not (off)
OverTrigLe08 0 - 5000 % 1 200 Over trigger level for analogue cha 8 in
% of signal
Operation09 Off
On
- - Off Operation On/Off
NomValue09 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 9
UnderTrigOp09 Off
On
- - Off Use under level trig for analogue cha 9
(on) or not (off)
UnderTrigLe09 0 - 200 % 1 50 Under trigger level for analogue cha 9 in
% of signal
OverTrigOp09 Off
On
- - Off Use over level trig for analogue cha 9
(on) or not (off)
OverTrigLe09 0 - 5000 % 1 200 Over trigger level for analogue cha 9 in
% of signal
Operation10 Off
On
- - Off Operation On/Off
NomValue10 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 10
UnderTrigOp10 Off
On
- - Off Use under level trig for analogue cha 10
(on) or not (off)
Table continues on next page
1MRK505186-UEN D Section 3
IED application
651
Application manual
Name Values (Range) Unit Step Default Description
UnderTrigLe10 0 - 200 % 1 50 Under trigger level for analogue cha 10
in % of signal
OverTrigOp10 Off
On
- - Off Use over level trig for analogue cha 10
(on) or not (off)
OverTrigLe10 0 - 5000 % 1 200 Over trigger level for analogue cha 10 in
% of signal
Table 216: A4RADR Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation31 Off
On
- - Off Operation On/off
NomValue31 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 31
UnderTrigOp31 Off
On
- - Off Use under level trig for analogue cha 31
(on) or not (off)
UnderTrigLe31 0 - 200 % 1 50 Under trigger level for analogue cha 31
in % of signal
OverTrigOp31 Off
On
- - Off Use over level trig for analogue cha 31
(on) or not (off)
OverTrigLe31 0 - 5000 % 1 200 Over trigger level for analogue cha 31 in
% of signal
Operation32 Off
On
- - Off Operation On/off
NomValue32 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 32
UnderTrigOp32 Off
On
- - Off Use under level trig for analogue cha 32
(on) or not (off)
UnderTrigLe32 0 - 200 % 1 50 Under trigger level for analogue cha 32
in % of signal
OverTrigOp32 Off
On
- - Off Use over level trig for analogue cha 32
(on) or not (off)
OverTrigLe32 0 - 5000 % 1 200 Over trigger level for analogue cha 32 in
% of signal
Operation33 Off
On
- - Off Operation On/off
NomValue33 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 33
UnderTrigOp33 Off
On
- - Off Use under level trig for analogue cha 33
(on) or not (off)
UnderTrigLe33 0 - 200 % 1 50 Under trigger level for analogue cha 33
in % of signal
OverTrigOp33 Off
On
- - Off Use over level trig for analogue cha 33
(on) or not (off)
OverTrigLe33 0 - 5000 % 1 200 Overtrigger level for analogue cha 33 in
% of signal
Operation34 Off
On
- - Off Operation On/off
NomValue34 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 34
UnderTrigOp34 Off
On
- - Off Use under level trig for analogue cha 34
(on) or not (off)
Table continues on next page
Section 3 1MRK505186-UEN D
IED application
652
Application manual
Name Values (Range) Unit Step Default Description
UnderTrigLe34 0 - 200 % 1 50 Under trigger level for analogue cha 34
in % of signal
OverTrigOp34 Off
On
- - Off Use over level trig for analogue cha 34
(on) or not (off)
OverTrigLe34 0 - 5000 % 1 200 Over trigger level for analogue cha 34 in
% of signal
Operation35 Off
On
- - Off Operation On/off
NomValue35 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 35
UnderTrigOp35 Off
On
- - Off Use under level trig for analogue cha 35
(on) or not (off)
UnderTrigLe35 0 - 200 % 1 50 Under trigger level for analogue cha 35
in % of signal
OverTrigOp35 Off
On
- - Off Use over level trig for analogue cha 35
(on) or not (off)
OverTrigLe35 0 - 5000 % 1 200 Over trigger level for analogue cha 35 in
% of signal
Operation36 Off
On
- - Off Operation On/off
NomValue36 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 36
UnderTrigOp36 Off
On
- - Off Use under level trig for analogue cha 36
(on) or not (off)
UnderTrigLe36 0 - 200 % 1 50 Under trigger level for analogue cha 36
in % of signal
OverTrigOp36 Off
On
- - Off Use over level trig for analogue cha 36
(on) or not (off)
OverTrigLe36 0 - 5000 % 1 200 Over trigger level for analogue cha 36 in
% of signal
Operation37 Off
On
- - Off Operation On/off
NomValue37 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 37
UnderTrigOp37 Off
On
- - Off Use under level trig for analogue cha 37
(on) or not (off)
UnderTrigLe37 0 - 200 % 1 50 Under trigger level for analogue cha 37
in % of signal
OverTrigOp37 Off
On
- - Off Use over level trig for analogue cha 37
(on) or not (off)
OverTrigLe37 0 - 5000 % 1 200 Over trigger level for analogue cha 37 in
% of signal
Operation38 Off
On
- - Off Operation On/off
NomValue38 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 38
UnderTrigOp38 Off
On
- - Off Use under level trig for analogue cha 38
(on) or not (off)
UnderTrigLe38 0 - 200 % 1 50 Under trigger level for analogue cha 38
in % of signal
OverTrigOp38 Off
On
- - Off Use over level trig for analogue cha 38
(on) or not (off)
Table continues on next page
1MRK505186-UEN D Section 3
IED application
653
Application manual
Name Values (Range) Unit Step Default Description
OverTrigLe38 0 - 5000 % 1 200 Over trigger level for analogue cha 38 in
% of signal
Operation39 Off
On
- - Off Operation On/off
NomValue39 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 39
UnderTrigOp39 Off
On
- - Off Use under level trig for analogue cha 39
(on) or not (off)
UnderTrigLe39 0 - 200 % 1 50 Under trigger level for analogue cha 39
in % of signal
OverTrigOp39 Off
On
- - Off Use over level trig for analogue cha 39
(on) or not (off)
OverTrigLe39 0 - 5000 % 1 200 Over trigger level for analogue cha 39 in
% of signal
Operation40 Off
On
- - Off Operation On/off
NomValue40 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 40
UnderTrigOp40 Off
On
- - Off Use under level trig for analogue cha 40
(on) or not (off)
UnderTrigLe40 0 - 200 % 1 50 Under trigger level for analogue cha 40
in % of signal
OverTrigOp40 Off
On
- - Off Use over level trig for analogue cha 40
(on) or not (off)
OverTrigLe40 0 - 5000 % 1 200 Over trigger level for analogue cha 40 in
% of signal
Table 217: B1RBDR Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation01 Off
On
- - Off Trigger operation On/Off
TrigLevel01 Trig on 0
Trig on 1
- - Trig on 1 Trig on positiv (1) or negative (0) slope
for binary inp 1
IndicationMa01 Hide
Show
- - Hide Indication mask for binary channel 1
SetLED01 Off
On
- - Off Set red-LED on HMI for binary channel 1
Operation02 Off
On
- - Off Trigger operation On/Off
TrigLevel02 Trig on 0
Trig on 1
- - Trig on 1 Trig on positiv (1) or negative (0) slope
for binary inp 2
IndicationMa02 Hide
Show
- - Hide Indication mask for binary channel 2
SetLED02 Off
On
- - Off Set red-LED on HMI for binary channel 2
Operation03 Off
On
- - Off Trigger operation On/Off
TrigLevel03 Trig on 0
Trig on 1
- - Trig on 1 Trig on positiv (1) or negative (0) slope
for binary inp 3
Table continues on next page
Section 3 1MRK505186-UEN D
IED application
654
Application manual
Name Values (Range) Unit Step Default Description
IndicationMa03 Hide
Show
- - Hide Indication mask for binary channel 3
SetLED03 Off
On
- - Off Set red-LED on HMI for binary channel 3
Operation04 Off
On
- - Off Trigger operation On/Off
TrigLevel04 Trig on 0
Trig on 1
- - Trig on 1 Trig on positiv (1) or negative (0) slope
for binary inp 4
IndicationMa04 Hide
Show
- - Hide Indication mask for binary channel 4
SetLED04 Off
On
- - Off Set red-LED on HMI for binary channel 4
Operation05 Off
On
- - Off Trigger operation On/Off
TrigLevel05 Trig on 0
Trig on 1
- - Trig on 1 Trig on positiv (1) or negative (0) slope
for binary inp 5
IndicationMa05 Hide
Show
- - Hide Indication mask for binary channel 5
SetLED05 Off
On
- - Off Set red-LED on HMI for binary channel 5
Operation06 Off
On
- - Off Trigger operation On/Off
TrigLevel06 Trig on 0
Trig on 1
- - Trig on 1 Trig on positiv (1) or negative (0) slope
for binary inp 6
IndicationMa06 Hide
Show
- - Hide Indication mask for binary channel 6
SetLED06 Off
On
- - Off Set red-LED on HMI for binary channel 6
Operation07 Off
On
- - Off Trigger operation On/Off
TrigLevel07 Trig on 0
Trig on 1
- - Trig on 1 Trig on positiv (1) or negative (0) slope
for binary inp 7
IndicationMa07 Hide
Show
- - Hide Indication mask for binary channel 7
SetLED07 Off
On
- - Off Set red-LED on HMI for binary channel 7
Operation08 Off
On
- - Off Trigger operation On/Off
TrigLevel08 Trig on 0
Trig on 1
- - Trig on 1 Trig on positiv (1) or negative (0) slope
for binary inp 8
IndicationMa08 Hide
Show
- - Hide Indication mask for binary channel 8
SetLED08 Off
On
- - Off Set red-LED on HMI for binary channel 8
Operation09 Off
On
- - Off Trigger operation On/Off
TrigLevel09 Trig on 0
Trig on 1
- - Trig on 1 Trig on positiv (1) or negative (0) slope
for binary inp 9
Table continues on next page
1MRK505186-UEN D Section 3
IED application
655
Application manual
Name Values (Range) Unit Step Default Description
IndicationMa09 Hide
Show
- - Hide Indication mask for binary channel 9
SetLED09 Off
On
- - Off Set red-LED on HMI for binary channel 9
Operation10 Off
On
- - Off Trigger operation On/Off
TrigLevel10 Trig on 0
Trig on 1
- - Trig on 1 Trig on positiv (1) or negative (0) slope
for binary inp 10
IndicationMa10 Hide
Show
- - Hide Indication mask for binary channel 10
SetLED10 Off
On
- - Off Set red-LED on HMI for binary channel 10
Operation11 Off
On
- - Off Trigger operation On/Off
TrigLevel11 Trig on 0
Trig on 1
- - Trig on 1 Trig on positiv (1) or negative (0) slope
for binary inp 11
IndicationMa11 Hide
Show
- - Hide Indication mask for binary channel 11
SetLED11 Off
On
- - Off Set red-LED on HMI for binary channel 11
Operation12 Off
On
- - Off Trigger operation On/Off
TrigLevel12 Trig on 0
Trig on 1
- - Trig on 1 Trig on positiv (1) or negative (0) slope
for binary inp 12
IndicationMa12 Hide
Show
- - Hide Indication mask for binary channel 12
SetLED12 Off
On
- - Off Set red-LED on HMI for binary input 12
Operation13 Off
On
- - Off Trigger operation On/Off
TrigLevel13 Trig on 0
Trig on 1
- - Trig on 1 Trig on positiv (1) or negative (0) slope
for binary inp 13
IndicationMa13 Hide
Show
- - Hide Indication mask for binary channel 13
SetLED13 Off
On
- - Off Set red-LED on HMI for binary channel 13
Operation14 Off
On
- - Off Trigger operation On/Off
TrigLevel14 Trig on 0
Trig on 1
- - Trig on 1 Trig on positiv (1) or negative (0) slope
for binary inp 14
IndicationMa14 Hide
Show
- - Hide Indication mask for binary channel 14
SetLED14 Off
On
- - Off Set red-LED on HMI for binary channel 14
Operation15 Off
On
- - Off Trigger operation On/Off
TrigLevel15 Trig on 0
Trig on 1
- - Trig on 1 Trig on positiv (1) or negative (0) slope
for binary inp 15
Table continues on next page
Section 3 1MRK505186-UEN D
IED application
656
Application manual
Name Values (Range) Unit Step Default Description
IndicationMa15 Hide
Show
- - Hide Indication mask for binary channel 15
SetLED15 Off
On
- - Off Set red-LED on HMI for binary channel 15
Operation16 Off
On
- - Off Trigger operation On/Off
TrigLevel16 Trig on 0
Trig on 1
- - Trig on 1 Trig on positiv (1) or negative (0) slope
for binary inp 16
IndicationMa16 Hide
Show
- - Hide Indication mask for binary channel 16
SetLED16 Off
On
- - Off Set red-LED on HMI for binary channel 16
FUNT1 0 - 255 FunT 1 0 Function type for binary channel 1 (IEC
-60870-5-103)
FUNT2 0 - 255 FunT 1 0 Function type for binary channel 2 (IEC
-60870-5-103)
FUNT3 0 - 255 FunT 1 0 Function type for binary channel 3 (IEC
-60870-5-103)
FUNT4 0 - 255 FunT 1 0 Function type for binary channel 4 (IEC
-60870-5-103)
FUNT5 0 - 255 FunT 1 0 Function type for binary channel 5 (IEC
-60870-5-103)
FUNT6 0 - 255 FunT 1 0 Function type for binary channel 6 (IEC
-60870-5-103)
FUNT7 0 - 255 FunT 1 0 Function type for binary channel 7 (IEC
-60870-5-103)
FUNT8 0 - 255 FunT 1 0 Function type for binary channel 8 (IEC
-60870-5-103)
FUNT9 0 - 255 FunT 1 0 Function type for binary channel 9 (IEC
-60870-5-103)
FUNT10 0 - 255 FunT 1 0 Function type for binary channel 10 (IEC
-60870-5-103)
FUNT11 0 - 255 FunT 1 0 Function type for binary channel 11 (IEC
-60870-5-103)
FUNT12 0 - 255 FunT 1 0 Function type for binary channel 12 (IEC
-60870-5-103)
FUNT13 0 - 255 FunT 1 0 Function type for binary channel 13 (IEC
-60870-5-103)
FUNT14 0 - 255 FunT 1 0 Function type for binary channel 14 (IEC
-60870-5-103)
FUNT15 0 - 255 FunT 1 0 Function type for binary channel 15 (IEC
-60870-5-103)
FUNT16 0 - 255 FunT 1 0 Function type for binary channel 16 (IEC
-60870-5-103)
INFNO1 0 - 255 InfNo 1 0 Information number for binary channel 1
(IEC -60870-5-103)
INFNO2 0 - 255 InfNo 1 0 Information number for binary channel 2
(IEC -60870-5-103)
Table continues on next page
1MRK505186-UEN D Section 3
IED application
657
Application manual
Name Values (Range) Unit Step Default Description
INFNO3 0 - 255 InfNo 1 0 Information number for binary channel 3
(IEC -60870-5-103)
INFNO4 0 - 255 InfNo 1 0 Information number for binary channel 4
(IEC -60870-5-103)
INFNO5 0 - 255 InfNo 1 0 Information number for binary channel 5
(IEC -60870-5-103)
INFNO6 0 - 255 InfNo 1 0 Information number for binary channel 6
(IEC -60870-5-103)
INFNO7 0 - 255 InfNo 1 0 Information number for binary channel 7
(IEC -60870-5-103)
INFNO8 0 - 255 InfNo 1 0 Information number for binary channel 8
(IEC -60870-5-103)
INFNO9 0 - 255 InfNo 1 0 Information number for binary channel 9
(IEC -60870-5-103)
INFNO10 0 - 255 InfNo 1 0 Information number for binary channel
10 (IEC -60870-5-103)
INFNO11 0 - 255 InfNo 1 0 Information number for binary channel
11 (IEC -60870-5-103)
INFNO12 0 - 255 InfNo 1 0 Information number for binary channel
12 (IEC -60870-5-103)
INFNO13 0 - 255 InfNo 1 0 Information number for binary channel
13 (IEC -60870-5-103)
INFNO14 0 - 255 InfNo 1 0 Information number for binary channel
14 (IEC -60870-5-103)
INFNO15 0 - 255 InfNo 1 0 Information number for binary channel
15 (IEC -60870-5-103)
INFNO16 0 - 255 InfNo 1 0 Information number for binary channel
16 (IEC -60870-5-103)
3.15.8 Event list
3.15.8.1 Application
From an overview perspective, continuous event-logging is a useful system
monitoring instrument and is a complement to specific disturbance recorder
functions.
The event list (EL), always included in the IED, logs all selected binary input
signals connected to the Disturbance report function. The list may contain of up to
1000 time-tagged events stored in a ring-buffer where, if the buffer is full, the
oldest event is overwritten when a new event is logged.
The difference between the event list (EL) and the event recorder (ER) function is
that the list function continuously updates the log with time tagged events while the
recorder function is an extract of events during the disturbance report time window.
The event list information is available in the IED via the local HMI or PCM600.
Section 3 1MRK505186-UEN D
IED application
658
Application manual
3.15.8.2 Setting guidelines
The setting parameters for the Event list function (EL) are a part of the Disturbance
report settings.
It is possible to event handle up to 96 binary signals, either internal signals or
signals from binary input channels. These signals are identical with the binary
signals recorded by the disturbance recorder.
There is no dedicated setting for the EL function.
3.15.9 Indications
3.15.9.1 Application
Fast, condensed and reliable information about disturbances in the primary and/or
in the secondary system is important. Binary signals that have changed status
during a disturbance are an example of this. This information is used primarily in
the short term (for example, immediate disturbance analysis, corrective actions) to
get information via the local HMI in a straightforward way without any knowledge
of how to handle the IED.
There are three LEDs on the local HMI (green, yellow and red), which will display
status information about the IED (in service, internal failure, and so on) and the
Disturbance report function (trigged).
The Indication function (IND), always included in the IED, shows all selected
binary input signals connected to the Disturbance Report function that have been
activated during a disturbance. The status changes are logged during the entire
recording time, which depends on the set of recording times (pre-, post-fault and
limit time) and the actual fault time. The indications are not time-tagged.
The indication information is available for each of the recorded disturbances in the
IED and the user may use the local HMI to view the information.
3.15.9.2 Setting guidelines
The setting parameters for LEDs and the Indication function (IND) are a part of the
disturbance report settings.
Available signals are identical with the binary signals recorded by the disturbance
report. It is possible to use all binary input signals for the Indication function on the
local HMI, but it is not recommended since the general view will be lost. The
intention is to point out some important signals, not to many, to be shown. If a
more thorough analysis is to be done information from the event recorder should be
used.
To be able to control the red LED in the local HMI:
1MRK505186-UEN D Section 3
IED application
659
Application manual
SetLEDn: Set red LED on LMHI in front of the IED if binary input N changes status.
For the IND function there are a number dedicated settings:
IndicationMaN: Indication mask for binary input N. If set (Show), a status change
of that particular input, will be fetched and shown on the local HMI. If not set
(Hide), status change will not be indicated.
3.15.10 Event recorder
3.15.10.1 Application
Quick, complete and reliable information about disturbances in the primary and/or
in the secondary system is vital, for example, time tagged events logged during
disturbances. This information is used for different purposes in the short term, for
example, disturbance analysis, corrective actions and in the long term, for example,
disturbance analysis, statistics and maintenance, that is Functional Analysis).
The event recorder, always included in the IED, logs all selected binary input
signals connected to the disturbance report function DRPRDRE. Each recording
can contain up to 150 time-tagged events. The events are logged during the total
recording time, which depends on the set of recording times (pre-, post-fault and
limit time) and the actual fault time. During this time, the first 150 events for all 96
binary signals are logged and time-tagged.
The event recorder information is available for each of the recorded disturbances in
the IED and the user may use the local HMI to get the information. The
information is included in the disturbance recorder file, which may be uploaded to
PCM600 and further analyzed using the Disturbance Handling tool.
The event recording information is an integrated part of the disturbance record
(Comtrade file).
3.15.10.2 Setting guidelines
The setting parameters for the Event Recorder (ER) function are a part of the
Disturbance Report settings.
It is possible to event handle up to 96 binary signals, either internal signals or
signals from binary input channels. These signals are identical to the binary signals
recorded by the disturbance report.
For the ER function there is no dedicated setting.
Section 3 1MRK505186-UEN D
IED application
660
Application manual
3.15.11 Trip value recorder
3.15.11.1 Application
Fast, complete and reliable information about disturbances such as fault currents
and voltage faults in the power system is vital. This information is used for
different purposes in the short perspective (for example, fault location, disturbance
analysis, corrective actions) and the long term (for example, disturbance analysis,
statistics and maintenance, that is Functional Analysis).
The trip value recorder (TVR), always included in the IED, calculates the values of
all selected external analog input signals (channel 1-30) connected to the
Disturbance Report function. The estimation is performed immediately after
finalizing each recording and available in the disturbance report. The result is
magnitude and phase angle before and during the fault for each analog input signal.
The information is used as input to the fault location function (FL), if included in
the IED and in operation.
The trip value recorder (TVR) information is available for each of the recorded
disturbances in the IED and the user may use the local HMI to get the information.
The information is included in the disturbance recorder file, which can be uploaded
to PCM600 and further analyzed using the Disturbance Handling tool.
3.15.11.2 Setting guidelines
The trip value recorder (TVR) setting parameters are a part of the disturbance
report settings.
For the trip value recorder (TVR) there is one dedicated setting:
ZeroAngleRef: The parameter defines which analog signal to use as phase-angle
reference for all other input signals. It is suggested to point out a sampled voltage
input signal, for example a line or busbar phase voltage (channel 1-30).
3.15.12 Disturbance recorder
3.15.12.1 Application
To get fast, complete and reliable information about fault current, voltage, binary
signal and other disturbances in the power system is very important. This is
accomplished by the Disturbance Recorder function and facilitates a better
understanding of the behavior of the power system and related primary and
secondary equipment during and after a disturbance. An analysis of the recorded
data provides valuable information that can be used to explain a disturbance, basis
for change of IED setting plan, improvement of existing equipment, and so on.
This information can also be used in a longer perspective when planning for and
1MRK505186-UEN D Section 3
IED application
661
Application manual
designing new installations, that is a disturbance recording could be a part of
Functional Analysis (FA).
The Disturbance Recorder (DR), always included in the IED, acquires sampled
data from all selected analog input and binary signals connected to the function
blocks, that is maximum 30 external analog, 10 internal (derived) analog and 96
binary signals.
The function is characterized by great flexibility as far as configuration, starting
conditions, recording times, and large storage capacity are concerned. Thus, the
disturbance recorder is not dependent on the operation of protective functions, and
it can record disturbances that were not discovered by protective functions.
The disturbance recorder information is saved for each of the recorded disturbances
in the IED and the user may use the local HMI to get some general information
about the recordings. The disturbance recording information is included in the
disturbance recorder files, which may be uploaded to PCM600 for further analysis
using the Disturbance Handling tool. The information is also available on a station
bus according to IEC 61850 and according to IEC 60870-5-103.
3.15.12.2 Setting guidelines
The setting parameters for the Disturbance Recorder function (DR) is a part of the
Disturbance Report settings.
It is possible to handle up to 40 analog and 96 binary signals, either internal signals
or signals coming from external inputs. The binary signals are identical with the
signals recorded by the other functions in the Disturbance Report function, that is
Event recorder (ER), Indication (IND) and Trip value recorder (TVR) function.
For the DR function there is one dedicated setting:
OperationM: Analog channel M is to be recorded by the disturbance recorder (On)
or not (Off). Other disturbance report settings, such as Operation and TrigLevel for
binary signals, will also influence the disturbance recorder.
3.16 Metering
3.16.1 Pulse-counter logic PCGGIO
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Pulse-counter logic PCGGIO
S00947 V1 EN
-
Section 3 1MRK505186-UEN D
IED application
662
Application manual
3.16.1.1 Application
Pulse counter logic function counts externally generated binary pulses, for instance
pulses coming from an external energy meter, for calculation of energy
consumption values. The pulses are captured by the binary input module (BIM),
and read by the pulse counter function. The number of pulses in the counter is then
reported via the station bus to the substation automation system or read via the
station monitoring system as a service value. When using IEC 61850, a scaled
service value is available over the station bus.
The normal use for this function is the counting of energy pulses from external
energy meters. An optional number of inputs from an arbitrary input module in
IED can be used for this purpose with a frequency of up to 40 Hz. The pulse
counter can also be used as a general purpose counter.
3.16.1.2 Setting guidelines
From PCM600, these parameters can be set individually for each pulse counter:
Operation: Off/On
tReporting: 0-3600s
Event Mask: NoEvents/ReportEvents
The configuration of the inputs and outputs of the Pulse counter function block is
made with PCM600.
On the Binary Input Module, the debounce filter time is fixed set to 5 ms, that is,
the counter suppresses pulses with a pulse length less than 5 ms. The input
oscillation blocking frequency is preset to 40 Hz. That means that the counter finds
the input oscillating if the input frequency is greater than 40 Hz. The oscillation
suppression is released at 30 Hz. The values for blocking/release of the oscillation
can be changed in the local HMI and PCM600 under Main menu/Settings/
General settings/I/O-modules
The setting is common for all input channels on a Binary Input
Module, that is, if changes of the limits are made for inputs not
connected to the pulse counter, the setting also influences the inputs
on the same board used for pulse counting.
1MRK505186-UEN D Section 3
IED application
663
Application manual
3.16.1.3 Setting parameters
Table 218: PCGGIO Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off/On
EventMask NoEvents
ReportEvents
- - NoEvents Report mask for analog events from
pulse counter
CountCriteria Off
RisingEdge
Falling edge
OnChange
- - RisingEdge Pulse counter criteria
Scale 1.000 - 90000.000 - 0.001 1.000 Scaling value for SCAL_VAL output to
unit per counted value
Quantity Count
ActivePower
ApparentPower
ReactivePower
ActiveEnergy
ApparentEnergy
ReactiveEnergy
- - Count Measured quantity for SCAL_VAL output
tReporting 0 - 3600 s 1 60 Cycle time for reporting of counter value
3.16.2 Function for energy calculation and demand handling
ETPMMTR
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Energy calculation and demand
handling
ETPMMTR - -
3.16.2.1 Application
Energy calculation and demand handling function ETPMMTR is intended for
statistics of the forward and reverse active and reactive energy. It has a high
accuracy basically given by the measurements function CVMMXU. This function
has a site calibration possibility to further increase the total accuracy.
The function is connected to the instantaneous outputs of CVMMXU as shown in
figure 291.
Section 3 1MRK505186-UEN D
IED application
664
Application manual
IEC07000121-2-en.vsd
PINST
QINST
CVMMXU
ETPMMTR
P
Q
STACC
RSTACC
RSTDMD
TRUE
FALSE
FALSE
IEC07000121 V2 EN
Figure 291: Connection of energy calculation and demand handling function
ETPMMTR to the measurements function CVMMXU
The energy values can be read through communication in MWh and MVarh in
monitoring tool of PCM600 and/or alternatively the values can be presented on the
local HMI. The local HMI graphical display is configured with PCM600 Graphical
display editor tool (GDE) with a measuring value which is selected to the active
and reactive component as preferred. All four values can also be presented.
Maximum demand values are presented in MWh or MVarh in the same way.
Alternatively, the values can be presented with use of the pulse counters function
(PCGGIO). The output values are scaled with the pulse output setting values
EAFAccPlsQty, EARAccPlsQty, ERFAccPlsQty and ERVAccPlsQty of the energy
metering function and then the pulse counter can be set-up to present the correct
values by scaling in this function. Pulse counter values can then be presented on
the local HMI in the same way and/or sent to the SA system through
communication where the total energy then is calculated by summation of the
energy pulses. This principle is good for very high values of energy as the
saturation of numbers else will limit energy integration to about one year with 50
kV and 3000 A. After that the accumulation will start on zero again.
3.16.2.2 Setting guidelines
The parameters are set via the local HMI or PCM600.
The following settings can be done for the energy calculation and demand handling
function ETPMMTR:
Operation: Off/On
tEnergy: Time interval when energy is measured.
StartAcc: Off/On is used to switch the accumulation of energy on and off.
The input signal STACC is used to start accumulation. Input signal
STACC cannot be used to halt accumulation. The energy content is
reset every time STACC is activated. STACC can for example, be
used when an external clock is used to switch two active energy
measuring function blocks on and off to have indication of two tariffs.
1MRK505186-UEN D Section 3
IED application
665
Application manual
tEnergyOnPls: gives the pulse length On time of the pulse. It should be at least 100
ms when connected to the Pulse counter function block. Typical value can be 100 ms.
tEnergyOffPls: gives the Off time between pulses. Typical value can be 100 ms.
EAFAccPlsQty and EARAccPlsQty: gives the MWh value in each pulse. It should
be selected together with the setting of the Pulse counter (PCGGIO) settings to
give the correct total pulse value.
ERFAccPlsQty and ERVAccPlsQty : gives the MVarh value in each pulse. It should
be selected together with the setting of the Pulse counter (PCGGIO) settings to
give the correct total pulse value.
For the advanced user there are a number of settings for direction, zero clamping,
max limit, and so on. Normally, the default values are suitable for these parameters.
3.16.2.3 Setting parameters
Table 219: ETPMMTR Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off/On
StartAcc Off
On
- - Off Activate the accumulation of energy
values
tEnergy 1 Minute
5 Minutes
10 Minutes
15 Minutes
30 Minutes
60 Minutes
180 Minutes
- - 1 Minute Time interval for energy calculation
tEnergyOnPls 0.000 - 60.000 s 0.001 1.000 Energy accumulated pulse ON time in
secs
tEnergyOffPls 0.000 - 60.000 s 0.001 0.500 Energy accumulated pulse OFF time in
secs
EAFAccPlsQty 0.001 - 10000.000 MWh 0.001 100.000 Pulse quantity for active forward
accumulated energy value
EARAccPlsQty 0.001 - 10000.000 MWh 0.001 100.000 Pulse quantity for active reverse
accumulated energy value
ERFAccPlsQty 0.001 - 10000.000 MVArh 0.001 100.000 Pulse quantity for reactive forward
accumulated energy value
ERVAccPlsQty 0.001 - 10000.000 MVArh 0.001 100.000 Pulse quantity for reactive reverse
accumulated energy value
Section 3 1MRK505186-UEN D
IED application
666
Application manual
Table 220: ETPMMTR Non group settings (advanced)
Name Values (Range) Unit Step Default Description
EALim 0.001 -
10000000000.000
MWh 0.001 1000000.000 Active energy limit
ERLim 0.001 -
10000000000.000
MVArh 0.001 1000.000 Reactive energy limit
DirEnergyAct Forward
Reverse
- - Forward Direction of active energy flow Forward/
Reverse
DirEnergyReac Forward
Reverse
- - Forward Direction of reactive energy flow Forward/
Reverse
EnZeroClamp Off
On
- - On Enable of zero point clamping detection
function
LevZeroClampP 0.001 - 10000.000 MW 0.001 10.000 Zero point clamping level at active Power
LevZeroClampQ 0.001 - 10000.000 MVAr 0.001 10.000 Zero point clamping level at reactive
Power
EAFPrestVal 0.000 - 10000.000 MWh 0.001 0.000 Preset Initial value for forward active
energy
EARPrestVal 0.000 - 10000.000 MWh 0.001 0.000 Preset Initial value for reverse active
energy
ERFPresetVal 0.000 - 10000.000 MVArh 0.001 0.000 Preset Initial value for forward reactive
energy
ERVPresetVal 0.000 - 10000.000 MVArh 0.001 0.000 Preset Initial value for reverse reactive
energy
1MRK505186-UEN D Section 3
IED application
667
Application manual
668
Section 4 Station communication
About this chapter
This chapter describes the communication possibilities in a SA-system.
4.1 Overview
Each IED is provided with a communication interface, enabling it to connect to one
or many substation level systems or equipment, either on the Substation
Automation (SA) bus or Substation Monitoring (SM) bus.
Following communication protocols are available:
IEC 61850-8-1 communication protocol
LON communication protocol
SPA or IEC 60870-5-103 communication protocol
DNP3.0 communication protocol
Theoretically, several protocols can be combined in the same IED.
4.2 IEC 61850-8-1 communication protocol
4.2.1 Application IEC 61850-8-1
IEC 61850-8-1 communication protocol allows vertical communication to HSI
clients and allows horizontal communication between two or more intelligent
electronic devices (IEDs) from one or several vendors to exchange information and
to use it in the performance of their functions and for correct co-operation.
GOOSE (Generic Object Oriented Substation Event), which is a part of IEC 61850
81 standard, allows the IEDs to communicate state and control information
amongst themselves, using a publish-subscribe mechanism. That is, upon detecting
an event, the IED(s) use a multi-cast transmission to notify those devices that have
registered to receive the data. An IED can, by publishing a GOOSE message,
report it's status. It can also request a control action to be directed at any device in
the network.
Figure 292 shows the topology of an IEC 6185081 configuration. IEC 618508
1 specifies only the interface to the substation LAN. The LAN itself is left to the
system integrator.
1MRK505186-UEN D Section 4
Station communication
669
Application manual
KIOSK 2
KIOSK 3
Station HSI
Base System
Engineering
Workstation
SMS
Gateway
Printer
CC
IEC09000135_en.v
sd
KIOSK 1
IED
1
IED
2
IED
3
IED
1
IED
2
IED
3
IED
1
IED
2
IED
3
IEC09000135 V1 EN
Figure 292: SA system with IEC 61850
Figure 293 shows the GOOSE peer-to-peer communication.
Control Protection Control Protection Control and protection
GOOSE
en05000734.vsd
Station HSI
MicroSCADA
Gateway
IED
A
IED
A
IED
A
IED
A
IED
A
IEC05000734 V1 EN
Figure 293: Example of a broadcasted GOOSE message
Section 4 1MRK505186-UEN D
Station communication
670
Application manual
4.2.2 Setting guidelines
There are two settings related to the IEC 6185081 protocol:
Operation User can set IEC 61850 communication to On or Off.
GOOSE has to be set to the Ethernet link where GOOSE traffic shall be send and
received.
IEDName That specific IED name in the IEC 6185081 system However, there
are specific settings for the network interface (Ethernet) that are directly related to
the IEC 6185081 (but not only) in case this protocol is used. The IEDName is
not settable through PST. The IEDName is given by the name of the IED in the
PCM Navigation structure. The name shown as the IEDName parameter is a read-
only feedback of the current name of the IED on IEC61850.
4.2.3 Setting parameters
Table 221: IEC61850-8-1 Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off/On
GOOSE Front
OEM311_AB
OEM311_CD
- - OEM311_AB Port for GOOSE communication
Table 222: GOOSEBINRCV Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off/On
4.2.4 IEC 61850 generic communication I/O functions SPGGIO,
SP16GGIO
4.2.4.1 Application
IEC 61850 generic communication I/O functions (SPGGIO) function is used to
send one single logical output to other systems or equipment in the substation. It
has one visible input, that should be connected in ACT tool.
4.2.4.2 Setting guidelines
There are no settings available for the user for SPGGIO. However, PCM600 must
be used to get the signals sent by SPGGIO.
1MRK505186-UEN D Section 4
Station communication
671
Application manual
4.2.4.3 Setting parameters
The function does not have any parameters available in the local HMI or PCM600.
4.2.5 IEC 61850 generic communication I/O functions MVGGIO
4.2.5.1 Application
IEC61850 generic communication I/O functions (MVGGIO) function is used to
send the instantaneous value of an analog output to other systems or equipment in
the substation. It can also be used inside the same IED, to attach a RANGE aspect
to an analog value and to permit measurement supervision on that value.
4.2.5.2 Setting guidelines
The settings available for IEC61850 generic communication I/O functions
(MVGGIO) function allows the user to choose a deadband and a zero deadband for
the monitored signal. Values within the zero deadband are considered as zero.
The high and low limit settings provides limits for the high-high-, high, normal,
low and low-low ranges of the measured value. The actual range of the measured
value is shown on the range output of MVGGIO function block. When a measured
value expander block (RANGE_XP) is connected to the range output, the logical
outputs of the RANGE_XP are changed accordingly.
4.2.5.3 Setting parameters
Table 223: MVGGIO Non group settings (basic)
Name Values (Range) Unit Step Default Description
MV db 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
MV zeroDb 0 - 100000 m% 1 500 Zero point clamping in 0,001% of range
MV hhLim -10000000000.000
- 10000000000.000
- 0.001 90.000 High High limit
MV hLim -10000000000.000
- 10000000000.000
- 0.001 80.000 High limit
MV lLim -10000000000.000
- 10000000000.000
- 0.001 -80.000 Low limit
MV llLim -10000000000.000
- 10000000000.000
- 0.001 -90.000 Low Low limit
MV min -10000000000.000
- 10000000000.000
- 0.001 -100.000 Minimum value
Table continues on next page
Section 4 1MRK505186-UEN D
Station communication
672
Application manual
Name Values (Range) Unit Step Default Description
MV max -10000000000.000
- 10000000000.000
- 0.001 100.000 Maximum value
MV dbType Cyclic
Dead band
Int deadband
- - Dead band Reporting type
MV limHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (common
for all limits)
4.3 LON communication protocol
4.3.1 Application
Control Center
IED IED IED
Gateway
Star coupler
RER 111
Station HSI
MicroSCADA
IEC05000663-1-en.vsd
IEC05000663 V2 EN
Figure 294: Example of LON communication structure for a substation
automation system
An optical network can be used within the substation automation system. This
enables communication with the IEDs in the 670 series through the LON bus from
the operators workplace, from the control center and also from other IEDs via bay-
to-bay horizontal communication.
The fibre optic LON bus is implemented using either glass core or plastic core fibre
optic cables.
1MRK505186-UEN D Section 4
Station communication
673
Application manual
Table 224: Specification of the fibre optic connectors
Glass fibre Plastic fibre
Cable connector ST-connector snap-in connector
Cable diameter 62.5/125 m 1 mm
Max. cable length 1000 m 10 m
Wavelength 820-900 nm 660 nm
Transmitted power -13 dBm (HFBR-1414) -13 dBm (HFBR-1521)
Receiver sensitivity -24 dBm (HFBR-2412) -20 dBm (HFBR-2521)
The LON Protocol
The LON protocol is specified in the LonTalkProtocol Specification Version 3
from Echelon Corporation. This protocol is designed for communication in control
networks and is a peer-to-peer protocol where all the devices connected to the
network can communicate with each other directly. For more information of the bay-
to-bay communication, refer to the section Multiple command function.
Hardware and software modules
The hardware needed for applying LON communication depends on the
application, but one very central unit needed is the LON Star Coupler and optical
fibres connecting the star coupler to the IEDs. To interface the IEDs from
MicroSCADA, the application library LIB670 is required.
The HV Control 670 software module is included in the LIB520 high-voltage
process package, which is a part of the Application Software Library within
MicroSCADA applications.
The HV Control 670 software module is used for control functions in IEDs in the
670 series. This module contains the process picture, dialogues and a tool to
generate the process database for the control application in MicroSCADA.
Use the LON Network Tool (LNT) to set the LON communication. This is a
software tool applied as one node on the LON bus. To communicate via LON, the
IEDs need to know
The node addresses of the other connected IEDs.
The network variable selectors to be used.
This is organized by LNT.
The node address is transferred to LNT via the local HMI by setting the parameter
ServicePinMsg = Yes. The node address is sent to LNT via the LON bus, or LNT
can scan the network for new nodes.
The communication speed of the LON bus is set to the default of 1.25 Mbit/s. This
can be changed by LNT.
Section 4 1MRK505186-UEN D
Station communication
674
Application manual
4.3.2 Setting parameters
Table 225: HORZCOMM Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation
Table 226: ADE Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation
TimerClass Slow
Normal
Fast
- - Slow Timer class
4.4 SPA communication protocol
4.4.1 Application
SPA communication protocol as an alternative to IEC 60870-5-103. The same
communication port as for IEC 60870-5-103 is used.
SPA communication is applied using the front communication port. For this
purpose, no serial communication module is required in the IED. Only PCM600
software in the PC and a crossed-over Ethernet cable for front connection is required.
When communicating with a PC (as shown in figure 296), using the rear SPA port
on the serial communication module (SLM), the only hardware required for a local
monitoring system is:
Optical fibres for the SPA bus loop
Optical/electrical converter for the PC
PC
A remote monitoring system for communication over the public telephone network
also requires telephone modems and a remote PC.
The software required for a local monitoring system is PCM600, and for a remote
monitoring system it is PCM600 in the remote PC only.
1MRK505186-UEN D Section 4
Station communication
675
Application manual
Local monitoring
system with
PCM600
IED IED IED
Optical to electrical
converter, e.g. SPA-ZC 22
or Fiberdata modem
Teleph
one
modem
Teleph
one
modem
Remote monitoring
system with
PCM600
en05000672.vsd
IEC05000672 V2 EN
Figure 295: SPA communication structure for a monitoring system. The
monitoring system can either be local, remote or a combination of
both
When communicating with a PC connected to the utility substation LAN, via WAN
and the utility office LAN, as shown in figure 296, and using the rear Ethernet port
on the optical Ethernet module (OEM), the only hardware required for a station
monitoring system is:
Optical fibres from the IED to the utility substation LAN.
PC connected to the utility office LAN.
The software required is PCM600.
IED IED IED
Substation LAN
en05000715.vsd
Remote
monitoring
system with
PCM600
Utility LAN
WAN
IEC05000715 V2 EN
Figure 296: SPA communication structure for a remote monitoring system via a
substation LAN, WAN and utility LAN
The SPA communication is mainly used for the Station Monitoring System. It can
include different IEDs with remote communication possibilities. Connection to a
computer (PC) can be made directly (if the PC is located in the substation) or by
telephone modem through a telephone network with ITU (former CCITT)
characteristics or via a LAN/WAN connection.
Section 4 1MRK505186-UEN D
Station communication
676
Application manual
glass <1000 m according to optical budget
plastic <20 m (inside cubicle) according to optical budget
Functionality
The SPA protocol V2.5 is an ASCII-based protocol for serial communication. The
communication is based on a master-slave principle, where the IED is a slave and
the PC is the master. Only one master can be applied on each fibre optic loop. A
program is required in the master computer for interpretation of the SPA-bus codes
and for translation of the data that should be sent to the IED.
For the specification of the SPA protocol V2.5, refer to SPA-bus Communication
Protocol V2.5.
4.4.2 Setting guidelines
The setting parameters for the SPA communication are set via the local HMI.
SPA and IEC 60870-5-103 uses the same rear communication port. Set the
parameter Operation, under Main menu /Settings /General settings /
Communication /SLM configuration /Rear optical SPA-IEC port /Protocol
selection to the selected protocol.
When the communication protocols have been selected, the IED is automatically
restarted.
The most important settings in the IED for SPA communication are the slave
number and baud rate (communication speed). These settings are absolutely
essential for all communication contact to the IED.
These settings can only be done on the local HMI for rear channel communication
and for front channel communication.
The slave number can be set to any value from 1 to 899, as long as the slave
number is unique within the used SPA loop.
The baud rate, which is the communication speed, can be set to between 300 and
38400 baud. Refer to technical data to determine the rated communication speed
for the selected communication interfaces. The baud rate should be the same for the
whole station, although different baud rates in a loop are possible. If different baud
rates in the same fibre optical loop or RS485 network are used, consider this when
making the communication setup in the communication master, the PC.
For local fibre optic communication, 19200 or 38400 baud is the normal setting. If
telephone communication is used, the communication speed depends on the quality
of the connection and on the type of modem used. But remember that the IED does
not adapt its speed to the actual communication conditions, because the speed is set
on the local HMI.
1MRK505186-UEN D Section 4
Station communication
677
Application manual
4.4.3 Setting parameters
Table 227: SPA Non group settings (basic)
Name Values (Range) Unit Step Default Description
SlaveAddress 1 - 899 - 1 30 Slave address
BaudRate 300 Bd
1200 Bd
4800 Bd
9600 Bd
19200 Bd
38400 Bd
- - 9600 Bd Baudrate on serial line
Table 228: LONSPA Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation
SlaveAddress 1 - 899 - 1 30 Slave address
4.5 IEC 60870-5-103 communication protocol
4.5.1 Application
TCP/IP
Control Center
IED IED IED
Gateway
Star coupler
RER 123
Station HSI
en05000660.vsd
IEC05000660 V2 EN
Figure 297: Example of IEC 60870-5-103 communication structure for a
substation automation system
Section 4 1MRK505186-UEN D
Station communication
678
Application manual
IEC 60870-5-103 communication protocol is mainly used when a protection IED
communicates with a third party control or monitoring system. This system must
have software that can interpret the IEC 60870-5-103 communication messages.
Table 229: Max distances between IED/nodes
glass < 1000 m according to optical budget
plastic < 20 m (inside cubicle) according to optical budget
Functionality
IEC 60870-5-103 is an unbalanced (master-slave) protocol for coded-bit serial
communication exchanging information with a control system. In IEC terminology
a primary station is a master and a secondary station is a slave. The communication
is based on a point-to-point principle. The master must have software that can
interpret the IEC 60870-5-103 communication messages. For detailed information
about IEC 60870-5-103, refer to IEC60870 standard part 5: Transmission
protocols, and to the section 103, Companion standard for the informative interface
of protection equipment.
Design
General
The protocol implementation consists of the following functions:
Event handling
Report of analog service values (measurands)
Fault location
Command handling
Autorecloser ON/OFF
Teleprotection ON/OFF
Protection ON/OFF
LED reset
Characteristics 1 - 4 (Setting groups)
File transfer (disturbance files)
Time synchronization
Hardware
When communicating locally with a Personal Computer (PC) or a Remote
Terminal Unit (RTU) in the station, using the SPA/IEC port, the only hardware
needed is: Optical fibres, glass/plastic Opto/electrical converter for the PC/RTU
PC/RTU
Commands
The commands defined in the IEC 60870-5-103 protocol are represented in a
dedicated function blocks. These blocks have output signals for all available
commands according to the protocol.
1MRK505186-UEN D Section 4
Station communication
679
Application manual
IED commands in control direction
Function block with defined IED functions in control direction, I103IEDCMD.
This block use PARAMETR as FUNCTION TYPE, and INFORMATION
NUMBER parameter is defined for each output signal.
Function commands in control direction
Function block with pre defined functions in control direction, I103CMD. This
block includes the FUNCTION TYPE parameter, and the INFORMATION
NUMBER parameter is defined for each output signal.
Function commands in control direction
Function block with user defined functions in control direction, I103UserCMD.
These function blocks include the FUNCTION TYPE parameter for each block in
the private range, and the INFORMATION NUMBER parameter for each output
signal.
Status
The events created in the IED available for the IEC 60870-5-103 protocol are
based on the:
IED status indication in monitor direction
Function block with defined IED functions in monitor direction, I103IED. This
block use PARAMETER as FUNCTION TYPE, and INFORMATION NUMBER
parameter is defined for each input signal.
Function status indication in monitor direction, user-defined
Function blocks with user defined input signals in monitor direction, I103UserDef.
These function blocks include the FUNCTION TYPE parameter for each block in
the private range, and the INFORMATION NUMBER parameter for each input
signal.
Supervision indications in monitor direction
Function block with defined functions for supervision indications in monitor
direction, I103Superv. This block includes the FUNCTION TYPE parameter, and
the INFORMATION NUMBER parameter is defined for each output signal.
Earth fault indications in monitor direction
Function block with defined functions for earth fault indications in monitor
direction, I103EF. This block includes the FUNCTION TYPE parameter, and the
INFORMATION NUMBER parameter is defined for each output signal.
Section 4 1MRK505186-UEN D
Station communication
680
Application manual
Fault indications in monitor direction, type 1
Function block with defined functions for fault indications in monitor direction,
I103FltDis. This block includes the FUNCTION TYPE parameter, and the
INFORMATION NUMBER parameter is defined for each input signal. This block
is suitable for distance protection function.
Fault indications in monitor direction, type 2
Function block with defined functions for fault indications in monitor direction,
I103FltStd. This block includes the FUNCTION TYPE parameter, and the
INFORMATION NUMBER parameter is defined for each input signal.
This block is suitable for line differential, transformer differential, over-current and
earth-fault protection functions.
Autorecloser indications in monitor direction
Function block with defined functions for autorecloser indications in monitor
direction, I103AR. This block includes the FUNCTION TYPE parameter, and the
INFORMATION NUMBER parameter is defined for each output signal.
Measurands
The measurands can be included as type 3.1, 3.2, 3.3, 3.4 and type 9 according to
the standard.
Measurands in public range
Function block that reports all valid measuring types depending on connected
signals, I103Meas.
Measurands in private range
Function blocks with user defined input measurands in monitor direction,
I103MeasUsr. These function blocks include the FUNCTION TYPE parameter for
each block in the private range, and the INFORMATION NUMBER parameter for
each block.
Fault location
The fault location is expressed in reactive ohms. In relation to the line length in
reactive ohms, it gives the distance to the fault in percent. The data is available and
reported when the fault locator function is included in the IED.
Disturbance Recordings
The transfer functionality is based on the Disturbance recorder function. The
analog and binary signals recorded will be reported to the master by polling.
The eight last disturbances that are recorded are available for transfer to the
1MRK505186-UEN D Section 4
Station communication
681
Application manual
master. A file that has been transferred and acknowledged by the master
cannot be transferred again.
The binary signals that are reported by polling are those that are connected to
the disturbance function blocks B1RBDR to B6RBDR. These function blocks
include the function type and the information number for each signal. For
more information on the description of the Disturbance report in the Technical
reference manual. The analog channels, that are reported, are those connected
to the disturbance function blocks A1RADR to A4RADR. The eight first ones
belong to the public range and the remaining ones to the private range.
Settings
Settings from the local HMI
SPA and IEC 60870-5-103 uses the same rear communication port. Set the
parameter Operation, under Main menu/Settings /General settings /
Communication /SLM configuration /Rear optical SPA-IEC port /Protocol
selection to the selected protocol
When the communication protocols have been selected, the IED is automatically
restarted.
The settings for IEC 60870-5-103 communication are the following:
Settings for slave number and baud rate (communication speed)
Setting for invert the light or not
Setting for reporting frequency of mesurands
The settings for communication parameters slave number and baud rate can be
found on the local HMI under: Main menu/Settings /General settings /
Communication /SLM configuration /Rear optical SPA-IEC port /Protocol
selection to the selected protocol
The slave number can be set to any value between 0 to 255.
The baud rate, the communication speed, can be set either to 9600 bits/s or 19200
bits/s.
Settings from PCM600
Event
For each input of the Event (EVENT) function there is a setting for the information
number of the connected signal. The information number can be set to any value
between 0 and 255. To get proper operation of the sequence of events the event
masks in the event function is to be set to ON_CHANGE. For single-command
signals, the event mask is to be set to ON_SET.
In addition there is a setting on each event block for function type. Refer to
description of the Main Function type set on the local HMI.
Commands
Section 4 1MRK505186-UEN D
Station communication
682
Application manual
As for the commands defined in the protocol there is a dedicated function block
with eight output signals. Use PCM600 to configure these signals. To realize the
BlockOfInformation command, which is operated from the local HMI, the output
BLKINFO on the IEC command function block ICOM has to be connected to an
input on an event function block. This input must have the information number 20
(monitor direction blocked) according to the standard.
Disturbance Recordings
For each input of the Disturbance recorder function there is a setting for the
information number of the connected signal. The information number can be set to
any value between 0 and 255.
Furthermore, there is a setting on each input of the Disturbance recorder function
for the function type. Refer to description of Main Function type set on the local HMI.
Function and information types
The function type is defined as follows:
128 = distance protection
160 = overcurrent protection
176 = transformer differential protection
192 = line differential protection
Refer to the tables in the Technical reference manual /Station communication,
specifying the information types supported by the communication protocol IEC
60870-5-103.
To support the information, corresponding functions must be included in the
protection IED.
There is no representation for the following parts:
Generating events for test mode
Cause of transmission: Info no 11, Local operation
EIA RS-485 is not supported. Glass or plastic fibre should be used. BFOC/2.5 is
the recommended interface to use (BFOC/2.5 is the same as ST connectors). ST
connectors are used with the optical power as specified in standard.
For more information, refer to IEC standard IEC 60870-5-103.
4.5.2 Setting parameters
Table 230: I103IEDCMD Non group settings (basic)
Name Values (Range) Unit Step Default Description
FUNTYPE 1 - 255 FunT 1 255 Function type (1-255)
1MRK505186-UEN D Section 4
Station communication
683
Application manual
Table 231: I103CMD Non group settings (basic)
Name Values (Range) Unit Step Default Description
FUNTYPE 1 - 255 FunT 1 1 Function type (1-255)
Table 232: I103USRCMD Non group settings (basic)
Name Values (Range) Unit Step Default Description
PULSEMOD 0 - 1 Mode 1 1 Pulse mode 0=Steady, 1=Pulsed
T 0.200 - 60.000 s 0.001 0.400 Pulse length
FUNTYPE 1 - 255 FunT 1 1 Function type (1-255)
INFNO_1 1 - 255 InfNo 1 1 Information number for output 1 (1-255)
INFNO_2 1 - 255 InfNo 1 2 Information number for output 2 (1-255)
INFNO_3 1 - 255 InfNo 1 3 Information number for output 3 (1-255)
INFNO_4 1 - 255 InfNo 1 4 Information number for output 4 (1-255)
INFNO_5 1 - 255 InfNo 1 5 Information number for output 5 (1-255)
INFNO_6 1 - 255 InfNo 1 6 Information number for output 6 (1-255)
INFNO_7 1 - 255 InfNo 1 7 Information number for output 7 (1-255)
INFNO_8 1 - 255 InfNo 1 8 Information number for output 8 (1-255)
Table 233: I103IED Non group settings (basic)
Name Values (Range) Unit Step Default Description
FUNTYPE 1 - 255 FunT 1 1 Function type (1-255)
Table 234: I103USRDEF Non group settings (basic)
Name Values (Range) Unit Step Default Description
FUNTYPE 1 - 255 FunT 1 5 Function type (1-255)
INFNO_1 1 - 255 InfNo 1 1 Information number for binary input 1
(1-255)
INFNO_2 1 - 255 InfNo 1 2 Information number for binary input 2
(1-255)
INFNO_3 1 - 255 InfNo 1 3 Information number for binary input 3
(1-255)
INFNO_4 1 - 255 InfNo 1 4 Information number for binary input 4
(1-255)
INFNO_5 1 - 255 InfNo 1 5 Information number for binary input 5
(1-255)
INFNO_6 1 - 255 InfNo 1 6 Information number for binary input 6
(1-255)
INFNO_7 1 - 255 InfNo 1 7 Information number for binary input 7
(1-255)
INFNO_8 1 - 255 InfNo 1 8 Information number for binary input 8
(1-255)
Section 4 1MRK505186-UEN D
Station communication
684
Application manual
Table 235: I103SUPERV Non group settings (basic)
Name Values (Range) Unit Step Default Description
FUNTYPE 1 - 255 FunT 1 1 Function type (1-255)
Table 236: I103EF Non group settings (basic)
Name Values (Range) Unit Step Default Description
FUNTYPE 1 - 255 FunT 1 160 Function type (1-255)
Table 237: I103FLTDIS Non group settings (basic)
Name Values (Range) Unit Step Default Description
FUNTYPE 1 - 255 FunT 1 128 Function type (1-255)
Table 238: I103FLTSTD Non group settings (basic)
Name Values (Range) Unit Step Default Description
FUNTYPE 1 - 255 FunT 1 1 Function type (1-255)
Table 239: I103AR Non group settings (basic)
Name Values (Range) Unit Step Default Description
FUNTYPE 1 - 255 FunT 1 1 Function type (1-255)
Table 240: I103MEAS Non group settings (basic)
Name Values (Range) Unit Step Default Description
RatedIL1 1 - 99999 A 1 3000 Rated current phase L1
RatedIL2 1 - 99999 A 1 3000 Rated current phase L2
RatedIL3 1 - 99999 A 1 3000 Rated current phase L3
RatedIN 1 - 99999 A 1 3000 Rated residual current IN
RatedUL1 0.05 - 2000.00 kV 0.05 230.00 Rated voltage for phase L1
RatedUL2 0.05 - 2000.00 kV 0.05 230.00 Rated voltage for phase L2
RatedUL3 0.05 - 2000.00 kV 0.05 230.00 Rated voltage for phase L3
RatedUL1-UL2 0.05 - 2000.00 kV 0.05 400.00 Rated voltage for phase-phase L1-L2
RatedUN 0.05 - 2000.00 kV 0.05 230.00 Rated residual voltage UN
RatedP 0.00 - 2000.00 MW 0.05 1200.00 Rated value for active power
RatedQ 0.00 - 2000.00 MVA 0.05 1200.00 Rated value for reactive power
RatedF 50.0 - 60.0 Hz 10.0 50.0 Rated system frequency
FUNTYPE 1 - 255 FunT 1 1 Function type (1-255)
1MRK505186-UEN D Section 4
Station communication
685
Application manual
Table 241: I103MEASUSR Non group settings (basic)
Name Values (Range) Unit Step Default Description
FUNTYPE 1 - 255 FunT 1 25 Function type (1-255)
INFNO 1 - 255 InfNo 1 1 Information number for measurands
(1-255)
RatedMeasur1 0.05 -
10000000000.00
- 0.05 1000.00 Rated value for measurement on input 1
RatedMeasur2 0.05 -
10000000000.00
- 0.05 1000.00 Rated value for measurement on input 2
RatedMeasur3 0.05 -
10000000000.00
- 0.05 1000.00 Rated value for measurement on input 3
RatedMeasur4 0.05 -
10000000000.00
- 0.05 1000.00 Rated value for measurement on input 4
RatedMeasur5 0.05 -
10000000000.00
- 0.05 1000.00 Rated value for measurement on input 5
RatedMeasur6 0.05 -
10000000000.00
- 0.05 1000.00 Rated value for measurement on input 6
RatedMeasur7 0.05 -
10000000000.00
- 0.05 1000.00 Rated value for measurement on input 7
RatedMeasur8 0.05 -
10000000000.00
- 0.05 1000.00 Rated value for measurement on input 8
RatedMeasur9 0.05 -
10000000000.00
- 0.05 1000.00 Rated value for measurement on input 9
4.6 Multiple command and transmit MULTICMDRCV,
MULTICMDSND
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Multiple command and transmit MULTICMDRCV - -
Multiple command and transmit MULTICMDSND - -
4.6.1 Application
The IED can be provided with a function to send and receive signals to and from
other IEDs via the interbay bus. The send and receive function blocks has 16 outputs/
inputs that can be used, together with the configuration logic circuits, for control
purposes within the IED or via binary outputs. When it is used to communicate
with other IEDs, these IEDs have a corresponding Multiple transmit function block
with 16 outputs to send the information received by the command block.
Section 4 1MRK505186-UEN D
Station communication
686
Application manual
4.6.2 Setting guidelines
4.6.2.1 Settings
The parameters for the multiple command function are set via PCM600.
The Mode setting sets the outputs to either a Steady or Pulsed mode.
4.6.3 Setting parameters
Table 242: MULTICMDRCV Non group settings (basic)
Name Values (Range) Unit Step Default Description
tMaxCycleTime 0.050 - 200.000 s 0.001 11.000 Maximum cycle time between receptions
of input data
tMinCycleTime 0.000 - 200.000 s 0.001 0.000 Minimum cycle time between receptions
of input data
Mode Steady
Pulsed
- - Steady Mode for output signals
tPulseTime 0.000 - 60.000 s 0.001 0.200 Pulse length for multi command outputs
Table 243: MULTICMDSND Non group settings (basic)
Name Values (Range) Unit Step Default Description
tMaxCycleTime 0.000 - 200.000 s 0.001 5.000 Maximum time interval between
transmission of output data
tMinCycleTime 0.000 - 200.000 s 0.001 0.000 Minimum time interval between
transmission of output data
1MRK505186-UEN D Section 4
Station communication
687
Application manual
688
Section 5 Remote communication
About this chapter
This chapter describes the remote end data communication possibilities through
binary signal transferring.
5.1 Binary signal transfer
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Binary signal transfer BinSignReceive - -
Binary signal transfer BinSignTransm - -
5.1.1 Application
The IEDs can be equipped with communication devices for line differential
communication and/or communication of binary signals between IEDs. The same
communication hardware is used for both purposes.
Communication between two IEDs geographically on different locations is a
fundamental part of the line differential function.
Sending of binary signals between two IEDs, one in each end of a power line is
used in teleprotection schemes and for direct transfer trips. In addition to this, there
are application possibilities, for example, blocking/enabling functionality in the
remote substation, changing setting group in the remote IED depending on the
switching situation in the local substation and so on.
When equipped with a LDCM, a 64 kbit/s communication channel can be
connected to the IED, which will then have the capacity of 192 binary signals to be
communicated with a remote IED. For RED670, the number of binary signals is
limited to 8 because the line differential communication is included in the same
telegrams.
5.1.1.1 Communication hardware solutions
The LDCM (Line Data Communication Module) has an optical connection such
that two IEDs can be connected over a direct fibre (multimode), as shown in figure
298. The protocol used is IEEE/ANSI C37.94. The distance with this solution is
typical 110 km.
1MRK505186-UEN D Section 5
Remote communication
689
Application manual
L
D
C
M
L
D
C
M
L
D
C
M
L
D
C
M
L
D
C
M
L
D
C
M
L
D
C
M
L
D
C
M
L
D
C
M
L
D
C
M
L
D
C
M
L
D
C
M
L
D
C
M
L
D
C
M
L
D
C
M
L
D
C
M
en06000519-2.vsd
IEC06000519 V2 EN
Figure 298: Direct fibre optical connection between two IEDs with LDCM
The LDCM can also be used together with an external optical to galvanic G.703
converter or with an alternative external optical to galvanic X.21 converter as
shown in figure 299. These solutions are aimed for connections to a multiplexer,
which in turn is connected to a telecommunications transmission network (for
example, SDH or PDH).
L
D
C
M
L
D
C
M
L
D
C
M
L
D
C
M
Telecom. Network
*) *)
Multiplexer Multiplexer
L
D
C
M
L
D
C
M
L
D
C
M
L
D
C
M
L
D
C
M
L
D
C
M
L
D
C
M
L
D
C
M
L
D
C
M
L
D
C
M
L
D
C
M
L
D
C
M
en05000527.vsd
*) Converting optical to galvanic G.703 or X.21 alternatively
IEC05000527 V1 EN
Figure 299: LDCM with an external optical to galvanic converter and a multiplexer
When an external modem G.703 or X21 is used, the connection between LDCM
and the modem is made with a multimode fibre of max. 3 km length. The IEEE/
ANSI C37.94 protocol is always used between LDCM and the modem.
Alternatively, a LDCM with X.21 built-in converter and micro D-sub 15-pole
connector output can be used.
5.1.2 Setting guidelines
ChannelMode: This parameter can be set On or Off. Besides this, it can be set
OutOfService which signifies that the local LDCM is out of service. Thus, with this
Section 5 1MRK505186-UEN D
Remote communication
690
Application manual
setting, the communication channel is active and a message is sent to the remote
IED that the local IED is out of service, but there is no COMFAIL signal and the
analog and binary values are sent as zero.
TerminalNo: This setting assigns a number to the local IED. Up to 256 IEDs can be
assigned unique numbers. For a line differential protection, maximum 6 IEDs can
be included. The possibility to use the large number of IED designations is
reserved for the case where a high security against incorrect addressing in
multiplexed systems is desired. For each LDCM, the parameter TerminalNo should
be set. It is recommended that each IED in the same station (when more than one)
have different numbers.
RemoteTermNo: This setting assigns a number to the remote IED. For each LDCM,
the parameter RemoteTermNo shall be set to a different value than parameter
TerminalNo, but equal to the TerminalNo of the remote end IED. All IED's in the
protection scheme must have different numbers (TerminalNo).
DiffSync: Here the method of time synchronization, Echo or GPS, for the line
differential function is selected.
GPSSyncErr: If GPS synchronization is lost, the synchronization of the line
differential function will continue during 16 s. based on the stability in the local
IED clocks. Thereafter the setting Block will block the line differential function or
the setting Echo will make it continue by using the Echo synchronization method.
It shall be noticed that using Echo in this situation is only safe as long as there is no
risk of varying transmission asymmetry.
CommSync: This setting decides the Master or Slave relation in the communication
system and shall not be mistaken for the synchronization of line differential current
samples. When direct fibre is used, one LDCM is set as Master and the other one
as Slave. When a modem and multiplexer is used, the IED is always set as Slave, as
the telecommunication system will provide the clock master.
OptoPower: The setting LowPower is used for fibres 0 1 km and HighPower for
fibres >1 km.
TransmCurr: This setting decides which of 2 possible local currents that shall be
transmitted, or if and how the sum of 2 local currents shall be transmitted, or
finally if the channel shall be used as a redundant channel.
In a 1 breaker arrangement, there will be 2 local currents, and the earthing on the
CTs can be different for these. CT-SUM will transmit the sum of the 2 CT groups.
CT-DIFF1 will transmit CT group 1 minus CT group 2 and CT-DIFF2 will
transmit CT group 2 minus CT group 1.
CT-GRP1 or CT-GRP2 will transmit the respective CT group, and the setting
RedundantChannel makes the channel be used as a backup channel.
ComFailAlrmDel: Time delay of communication failure alarm. In communication
systems, route switching can sometimes cause interruptions with a duration up to
1MRK505186-UEN D Section 5
Remote communication
691
Application manual
50 ms. Thus, a too short time delay setting might cause nuisance alarms in these
situations.
ComFailResDel: Time delay of communication failure alarm reset.
RedChSwTime: Time delay before switchover to a redundant channel in case of
primary channel failure.
RedChRturnTime: Time delay before switchback to a the primary channel after
channel failure.
AsymDelay: The asymmetry is defined as transmission delay minus receive delay.
If a fixed asymmetry is known, the Echo synchronization method can be used if the
parameter AsymDelay is properly set. From the definition follows that the
asymmetry will always be positive in one end, and negative in the other end.
AnalogLatency: Local analog latency; A parameter which specifies the time delay
(number of samples) between actual sampling and the time the sample reaches the
local communication module, LDCM. The parameter shall be set to 2 when
transmitting analog data from the local transformer module, TRM. When a
merging unit according to .
RemAinLatency: Remote analog latency; This parameter corresponds to the
LocAinLatency set in the remote IED.
MaxTransmDelay: Data for maximum 40 ms transmission delay can be buffered
up. Delay times in the range of some ms are common. It shall be noticed that if
data arrive in the wrong order, the oldest data will just be disregarded.
CompRange: The set value is the current peak value over which truncation will be
made. To set this value, knowledge of the fault current levels should be known.
The setting is not overly critical as it considers very high current values for which
correct operation normally still can be achieved.
5.1.3 Setting parameters
Table 244: LDCMRecBinStat1 Non group settings (basic)
Name Values (Range) Unit Step Default Description
ChannelMode Off
On
OutOfService
- - On Channel mode of LDCM, 0=OFF, 1=ON,
2=OutOfService
TerminalNo 0 - 255 - 1 0 Terminal number used for line differential
communication
RemoteTermNo 0 - 255 - 1 0 Terminal number on remote terminal
CommSync Slave
Master
- - Slave Com Synchronization mode of LDCM,
0=Slave, 1=Master
OptoPower LowPower
HighPower
- - LowPower Transmission power for LDCM, 0=Low,
1=High
Table continues on next page
Section 5 1MRK505186-UEN D
Remote communication
692
Application manual
Name Values (Range) Unit Step Default Description
ComFailAlrmDel 5 - 500 ms 5 100 Time delay before communication error
signal is activated
ComFailResDel 5 - 500 ms 5 100 Reset delay before communication error
signal is reset
InvertPolX21 Off
On
- - Off Invert polarization for X21 communication
Table 245: LDCMRecBinStat2 Non group settings (basic)
Name Values (Range) Unit Step Default Description
ChannelMode Off
On
OutOfService
- - On Channel mode of LDCM, 0=OFF, 1=ON,
2=OutOfService
TerminalNo 0 - 255 - 1 0 Terminal number used for line differential
communication
RemoteTermNo 0 - 255 - 1 0 Terminal number on remote terminal
DiffSync Echo
GPS
- - Echo Diff Synchronization mode of LDCM,
0=ECHO, 1=GPS
GPSSyncErr Block
Echo
- - Block Operation mode when GPS
synchroniation signal is lost
CommSync Slave
Master
- - Slave Com Synchronization mode of LDCM,
0=Slave, 1=Master
OptoPower LowPower
HighPower
- - LowPower Transmission power for LDCM, 0=Low,
1=High
TransmCurr CT-GRP1
CT-GRP2
CT-SUM
CT-DIFF1
CT-DIFF2
- - CT-GRP1 Summation mode for transmitted current
values
ComFailAlrmDel 5 - 500 ms 5 100 Time delay before communication error
signal is activated
ComFailResDel 5 - 500 ms 5 100 Reset delay before communication error
signal is reset
RedChSwTime 5 - 500 ms 5 5 Time delay before switching in
redundant channel
RedChRturnTime 5 - 500 ms 5 100 Time delay before switching back from
redundant channel
AsymDelay -20.00 - 20.00 ms 0.01 0.00 Asymmetric delay when communication
use echo synch.
MaxTransmDelay 0 - 40 ms 1 20 Max allowed transmission delay
CompRange 0-10kA
0-25kA
0-50kA
0-150kA
- - 0-25kA Compression range
MaxtDiffLevel 200 - 2000 us 1 600 Maximum time diff for ECHO back-up
DeadbandtDiff 200 - 1000 us 1 300 Deadband for t Diff
InvertPolX21 Off
On
- - Off Invert polarization for X21 communication
1MRK505186-UEN D Section 5
Remote communication
693
Application manual
Table 246: LDCMRecBinStat3 Non group settings (basic)
Name Values (Range) Unit Step Default Description
ChannelMode Off
On
OutOfService
- - On Channel mode of LDCM, 0=OFF, 1=ON,
2=OutOfService
TerminalNo 0 - 255 - 1 0 Terminal number used for line differential
communication
RemoteTermNo 0 - 255 - 1 0 Terminal number on remote terminal
DiffSync Echo
GPS
- - Echo Diff Synchronization mode of LDCM,
0=ECHO, 1=GPS
GPSSyncErr Block
Echo
- - Block Operation mode when GPS
synchroniation signal is lost
CommSync Slave
Master
- - Slave Com Synchronization mode of LDCM,
0=Slave, 1=Master
OptoPower LowPower
HighPower
- - LowPower Transmission power for LDCM, 0=Low,
1=High
TransmCurr CT-GRP1
CT-GRP2
CT-SUM
CT-DIFF1
CT-DIFF2
RedundantChannel
- - CT-GRP1 Summation mode for transmitted current
values
ComFailAlrmDel 5 - 500 ms 5 100 Time delay before communication error
signal is activated
ComFailResDel 5 - 500 ms 5 100 Reset delay before communication error
signal is reset
RedChSwTime 5 - 500 ms 5 5 Time delay before switching in
redundant channel
RedChRturnTime 5 - 500 ms 5 100 Time delay before switching back from
redundant channel
AsymDelay -20.00 - 20.00 ms 0.01 0.00 Asymmetric delay when communication
use echo synch.
MaxTransmDelay 0 - 40 ms 1 20 Max allowed transmission delay
CompRange 0-10kA
0-25kA
0-50kA
0-150kA
- - 0-25kA Compression range
MaxtDiffLevel 200 - 2000 us 1 600 Maximum time diff for ECHO back-up
DeadbandtDiff 200 - 1000 us 1 300 Deadband for t Diff
InvertPolX21 Off
On
- - Off Invert polarization for X21 communication
Section 5 1MRK505186-UEN D
Remote communication
694
Application manual
Section 6 Configuration
About this chapter
This chapter describes the IED configurations.
6.1 Introduction
There are four different software alternatives with which the IED can be ordered.
The intention is that these configurations shall suit most applications with minor or
no changes. The few changes required on binary input and outputs can be done
from the Signal Matrix tool in the PCM600 engineering platform.
The main protection functions are switched On and fully operative at delivery
whereas back-up functions not generally used will be set to Off.
The configurations are:
Single-breaker arrangement. Three-phase tripping arrangement.
Single breaker arrangement. Single-phase tripping arrangement.
Multi breaker arrangement. Three-phase tripping arrangement.
Multi breaker arrangement. Single-phase tripping arrangement.
The Multi-breaker arrangement includes One-and-a-half and Ring-breaker
arrangements.
The number of IO must be ordered to the application where more IO is foreseen for
the Single-phase tripping arrangements respectively the Multi-breaker arrangement.
The basic ordering includes one Binary input module and one Binary Output
module, sufficient for the default configured IO to trip and close circuit breaker and
with possible communication interface.
However, all IEDs can be reconfigured with help of the ACT configuration tool,
being part of the PCM platform. This way the IED can be made suitable for special
applications and special logic can be developed, that is logic for automatic opening
of disconnectors and closing ring bays, automatic load transfer from one busbar to
the other, and so on.
ABB will of course, on request, be available to support the re-configuration work,
either direct or to do the design checking.
Optional functions and optional IO ordered will not be configured at delivery. It
should be noted that the standard only includes one binary input and one binary
1MRK505186-UEN D Section 6
Configuration
695
Application manual
output module and only the key functions such as tripping are connected to the
outputs in the Signal Matrix tool. The required total IO must be calculated and
specified at ordering.
After calculating the IO need and ordering of the IED the number of IO must be
correctly set-up under the Application configuration tool menu Edit/Function
selector. Include the IO you have in the IED and Save-Compile before you leave
ACT. This will mean that the available IO will be shown in the Signal Matrix tool.
The Application Configuration tool, which is part of the PCM600 engineering
platform, will further to the four arrangements above include also alternatives for
each of them with all of the software options configured. These can then be used
directly or as assistance of how to configure the options. As the number of options
can vary all alternatives possible cannot be handled.
The configurations are as far as found necessary provided with application
comments to explain why the signals have been connected in the special way. This
is of course for the special application features created, not standard functionality.
Application configuration diagrams and connection diagrams for the maximum
application can be found in separate document, refer to section "Related documents"
The physical terminals for the configured binary inputs and outputs are found in
the connection diagrams for IEC 670 series 1MRK002801-AC.
6.2 Description of configuration RED670
6.2.1 Introduction
6.2.1.1 Description of configuration A31
The connection of the IED is shown in figure 300.
This configuration is used in applications with single breakers with single or
double busbars. The tripping is three poles and the scheme includes a three-pole
autoreclosing with a synchronism check.
The Differential protection is the main function. It is available with communication
modules for single or redundant channels and can be used in two- or multi-terminal
arrangements. Optional distance protection can be provided.
A three-pole autoreclose with synchronism check is provided to restore service.
Multiple steps are available for use.
A phase overcurrent function is included as a time delayed back-up function.
Section 6 1MRK505186-UEN D
Configuration
696
Application manual
Breaker failure function is included and with three-phase starting and re-trip of
own breaker. Back-up trip outputs are available and connected to virtual IO for
connection to trip busbar and remote breakers through intertrip.
A thermal overload function is available to supervise abnormal service.
Voltage protection functions are available as voltage level supervision.
A Loss of voltage function will open circuit breaker and prepare for system
restoration following a system voltage collapse.
The necessary auxiliary functions such as Fuse failure supervision are also included.
The necessary trip logic is provided to trip the breaker.
Measuring functions S, P, Q, I, U, PF, f are available for local presentation on the
local HMI and/or remote presentation. The availability of analog inputs allows
connection to separate metering cores and a built-in calibration on the analog
inputs allows calibration at site to very high accuracy, then involving the
instrument transformer errors and voltage drops in secondary cabling.
Optional functions can be ordered and include functions such as full control, local
and remote, Directional Earth fault, Out of step protection, Frequency protection,
and so on. These optional functions must be added to the configuration and loaded
into the IED after delivery.
Following should be noted. This connection diagram shows the connection with the
basic supplied single binary input and binary output boards. In many cases this is
sufficient, in other cases, for example with full control of all apparatuses included
more IO cards are required. Our proposal for a full version with control is to use
two Binary input modules and one binary output module. For systems without
Substation Automation a second binary output board might be required.
The configuration includes a binary input for IED in test. Normally this is activated
from the test switch NO contact. In test mode functions need to be released from
the local HMI menu. It is then also possible to switch off IEC 61850 communication.
A binary input is also provided to block changes such as setting changes,
configuration changes or local HMI changes. Activation of this input after
commissioning, for example from a openable terminal prevents all changes except
switching between pre-tested setting groups.
1MRK505186-UEN D Section 6
Configuration
697
Application manual
RED670 3Phase trip/Single Breaker
C
C
T
C
T
C
P1
-QB1
-QB2
-QA1
-BI1
CLOSE QA1
TRIP QA1 3PH
QA1 CLOSED
QA1 SPR UNCH
MAIN 2 TRIP
-QB9
BUS A
BUS B
TO MAIN 2 RELAY
TO BUS PROT
MCB OR
FUSE
-BU1
BBPA-TRIP
SPARE
SPARE
SPARE
SPARE
CR DIT
CS DIT T
O
/
F
R
O
M
P
L
C
/
M
U
X
F
A
U
L
T
S
I
G
N
A
L
L
I
N
G
Configuration 1MRK004500-82
+ -
IRF
BB1 TRIP
TRM1:1-3
TRM1:10
TRM1:11
X11.4 5
X11.1
X11.2
3
TEST
CH LOCK
BIM3.15
BIM3.13
BIM3.14
BIM3.9
BIM3.10
BIM3.11
BIM3.2
BOM4.11
BOM4.4
BOM4.1
BOM4.2
BOM4.3
BIM3.1
BIM3.3
BIM3.12
BIM3.4
BOM4.23
BOM4.9
BOM4.12
BOM4.13
BOM4.14
BOM4.10
BOM4.24
BOM4.15
BOM4.16
BOM4.17
BOM4.18
BOM4.19
BOM4.20
BOM4.21
BOM4.22
TRM1:7-9
BB2 TRIP
BIM3.5
BIM3.6
BIM3.7
BIM3.8
QB1 CLOSED
QB1 OPEN
QB2 CLOSED
QB2 OPEN
BIM3.16
BBPB-TRIP
TRM1:4-6
BOM4.7
BOM4.8
BOM4.5
BOM4.6
en05000842.eps
IEC05000842 V1 EN
Figure 300: Connection diagram for configuration A31 with the setting and
signal matrix defined
Section 6 1MRK505186-UEN D
Configuration
698
Application manual
6.2.1.2 Description of configuration A32
The connection of the IED is shown in figure 301.
This configuration is used in applications with single breakers with single or
double busbars. The tripping is single pole and the scheme includes a single and/or
three-pole autoreclosing with a synchronism check.
The Differential protection is the main function. It is available with communication
modules for single or redundant channels and can be used in two- or multi-terminal
arrangements.
A three-pole autoreclose with synchronism check is provided to restore service.
Multiple steps are available for use.
A phase overcurrent function is included as a time delayed back-up function.
Directional Earth fault function with communication alternatives is also included in
the design and prepared for Permissive Overreach or Blocking scheme. The current
reversal is an essential function in the DEF scheme and is thus included.
Breaker failure function is included and with single phase starting and re-trip of
own breaker.
A Pole Discordance function supervises the position of the breaker poles.
A thermal overload function is available to supervise abnormal service.
Voltage protection functions are available as voltage level supervision.
A Loss of voltage function will open circuit breaker and prepare for system
restoration following a system voltage collapse.
The necessary auxiliary functions such as Fuse failure supervision are also included.
The necessary trip logic is provided to trip the breaker.
Measuring functions S, P, Q, I, U, PF, f are available for local presentation on the
local HMI and/or remote presentation. The availability of analog inputs allows
connection to separate metering cores and a built-in calibration on the analog
inputs allows calibration at site to very high accuracy, then involving the
instrument transformer errors and voltage drops in secondary cabling.
Optional functions can be ordered and include functions such as full control, local
and remote, Directional Earth fault, Out of step protection, Frequency protection,
and so on. These optional functions must be added to the configuration and loaded
into the IED after delivery.
Following should be noted. This connection diagram shows the connection with the
basic supplied single binary input and binary output boards. In many cases this is
sufficient, in other cases e.g. with full control of all apparatuses included more IO
1MRK505186-UEN D Section 6
Configuration
699
Application manual
cards are required. Our proposal for a full version with control is to use three
Binary input modules and two binary output module.
For systems without Substation Automation a second binary output board might be
required.
The configuration includes a binary input for IED in test. Normally this is activated
from the test switch NO contact. In test mode functions need to be released from
the local HMI menu. It is then also possible to switch off IEC 61850 communication.
A binary input is also provided to block changes such as setting changes,
configuration changes or local HMI changes. Activation of this input after
commissioning, for example from an openable terminal prevents all changes except
switching between pre-tested setting groups.
Section 6 1MRK505186-UEN D
Configuration
700
Application manual
C
C
T
C
T
C
P1
-QB1
-QB2
-QA1
-BI1
CLOSE QA1
TRIP QA1 L1,L2,L3
MAIN 2 TRIP
-QB9
BUS A
BUS B
TO MAIN 2 RELAY
TO BUS PROT
MCB OR
FUSE
NOTE! CB CLosed is CB
Closed L1&L2&L3
CB Open is CB Open
L1 OR L2 OR L3
-BU1
BBPA-TRIP
SPARE
SPARE
SPARE
SPARE
CR DTT
CS DTT
F
A
U
L
T
S
I
G
N
A
L
L
I
N
G
Configuration 1MRK004500-84
RED670 1Phase trip/Single Breaker
+ -
IRF
BB1 TRIP
TRM1:1-3
TRM1:10
TRM1:11
X11.4 5
X11.1
X11.2
3
TEST
CH LOCK
BIM3.15
BIM3.13
BIM3.14
BIM3.9
BIM3.10
BIM3.11
BIM3.2
BOM4.11
BOM4.4
BOM4.1
BOM4.2
BOM4.3
BIM3.1
BIM3.3
BIM3.12
BIM3.4
BOM4.23
BOM4.9
BOM4.12
BOM4.13
BOM4.14
BOM4.10
BOM4.24
BOM4.15
BOM4.16
BOM4.17
BOM4.18
BOM4.19
BOM4.20
BOM4.21
BOM4.22
TRM1:7-9
BB2 TRIP
BIM3.5
BIM3.6
BIM3.7
BIM3.8
QB1 CLOSED
QB1 OPEN
QB2 CLOSED
QB2 OPEN
BIM3.16
BBPB-TRIP
TRM1:4-6
BOM4.7
BOM4.8
BOM4.5
BOM4.6
T
O
/
F
R
O
M
P
L
C
/
M
U
X
en05000840.eps
QA1-CLOSED
QA1-PD
QA1-SPR UNCH
IEC05000840 V1 EN
Figure 301: Connection diagram for configuration A32 with the setting and
signal matrix defined
1MRK505186-UEN D Section 6
Configuration
701
Application manual
6.2.1.3 Description of configuration B31
The connection of the IED is shown in figure 302.
This configuration is used in applications with Multi-breakers such as one and a
half breaker or Ring busbar arrangements. The tripping is three poles and the
scheme includes a three pole Auto Reclosing with a synchronism check. Due to the
multi-breaker involved there are two auto-reclosers and two Synchronism check
devices with a priority circuit to allow one to close first.
The Differential protection is the main function. It is available with communication
modules for single or redundant channels and can be used in two or multi-terminal
arrangements.
A phase overcurrent function is included as a time delayed back-up function.
Directional Earth fault function with communication alternatives is also included in
the design and prepared for Permissive Overreach or Blocking scheme. The current
reversal is an essential function in the Directional Earth fault scheme and is thus
included.
Breaker failure function is included for both of the breakers and is with three-phase
starting and re-trip of own breaker.
A thermal overload function is available to supervise abnormal service.
Voltage protection functions are available as voltage level supervision.
A Loss of voltage function will open circuit breaker and prepare for system
restoration following a system voltage collapse.
The necessary auxiliary functions such as Fuse failure supervision are also included.
The necessary trip logic is provided to trip the involved breakers.
Measuring functions S, P, Q, I, U, PF, f are available for local presentation on the
local HMI and/or remote presentation. The availability of analog inputs allows
connection to separate metering cores and a built-in calibration on the analog
inputs allows calibration at site to very high accuracy, then involving the
instrument transformer errors and voltage drops in secondary cabling.
Optional functions can be ordered and include functions such as full control, local
and remote, Directional Earth fault, Out of step protection, Frequency protection,
and so on. These optional functions must be added to the configuration and loaded
into the IED after delivery.
Following should be noted. This connection diagram shows the connection with the
basic supplied single binary input and binary output boards. In many cases this is
sufficient, in other cases, for example with full control of all apparatuses included
more IO cards are required. Our proposal for a full version with control is to use
two Binary input modules and one Binary output module. For systems without
Substation Automation a second binary output board might be required.
Section 6 1MRK505186-UEN D
Configuration
702
Application manual
The configuration includes a binary input for IED in test. Normally this is activated
from the test switch NO contact. In test mode functions need to be released from
the local HMI menu. It is then also possible to switch off IEC 61850 communication.
A binary input is also provided to block changes such as setting changes,
configuration changes or Local HMI changes. Activation of this input after
commissioning, for example from an openable terminal prevents alll changes
except switching between pre-tested setting groups.
1MRK505186-UEN D Section 6
Configuration
703
Application manual
C
C
T
C
T
C
=3-QA1
QA1-CLOSED
QA1-SPR UNCH
CLOSE QA1
TRIP QA1 3PH
MAIN 2 TRIP
C
C
T
C
T
C
P1
-QB1
=1-QA1
-BI1
QA1-CLOSED
QA1-SPR UNCH
CLOSE QA1
TRIP QA1 3PH
MAIN 2 TRIP
-QB9
MCB-OK
MCB-OK
BUS A
BUS B
BBP-TRIP
SPARE
SPARE
SPARE
SPARE
CR DIT
CS DIT T
O
/
F
R
O
M
P
L
C
/
M
U
X
F
A
U
L
T
S
I
G
N
A
L
L
I
N
G
Configuration 1MRK004500-83
RED670 3 Phase trip/Multi Breaker
TO MAIN 2 RELAY
TO BUS PROT
MCB OR
FUSE
+ -
IRF
P1
-BI1
TO MAIN 2 RELAY
-QB9
MCB-OK
MCB OR
FUSE
-QB6
MCB OR
FUSE
=2.QA1 CBF
BUSBAR TRIP
TRIP =2-Q1
DIT2 Line 2
=2-QA1
QB9-OPEN
TRM1:1-3
TRM1:4-6
TRM1:7-9
TRM1:10
TRM1:11
TRM1:12
-BU1
-BU1
-BU1
-BU1
-QB61
-QB62
-QB6
-QB2
MCB OR
FUSE
X11.4 5
X11.1
X11.2
3
DTT L2
TEST
CH LOCK
BIM3.15
BIM3.13
BIM3.7
BIM3.16
BIM3.9
BIM3.10
BIM3.11
BIM3.5
BIM3.14
BIM3.6
BIM3.2
BOM4.11
BOM4.8
BOM4.5
BOM4.6
BOM4.7
BOM4.4
BOM4.1
BOM4.2
BOM4.3
BIM3.1
BIM3.3
BIM3.12
BIM3.4
BIM3.8
BOM4.23
BOM4.9
BOM4.12
BOM4.13
BOM4.14
BOM4.10
BOM4.24
BOM4.15
BOM4.16
BOM4.17
BOM4.18
BOM4.19
BOM4.20
BOM4.21
BOM4.22
en05000843.eps
IEC05000843 V1 EN
Figure 302: Connection diagram for configuration B31 with the setting and
signal matrix defined
Section 6 1MRK505186-UEN D
Configuration
704
Application manual
6.2.1.4 Description of configuration B32
The connection of the IED is shown in figure 303.
This configuration is used in applications with Multi-breakers such as One-and-a-
half breaker or Ring-busbar arrangements. The tripping is single and/or three poles
and the scheme includes a single- and/or three-pole autoreclosing with a
synchronism check. Due to the multi-breaker involved, there are two autoreclosers
and two Synchronism check devices with a priority circuit to allow one to close first.
The Differential protection is the main function. It is available with communication
modules for single or redundant channels and can be used in two- or multi-terminal
arrangements.
A phase overcurrent function is included as a time delayed back-up function.
Directional Earth fault function with communication alternatives is also included in
the design and prepared for Permissive Overreach or Blocking scheme. The current
reversal is an essential function in the Directional Earth fault scheme and is thus
included.
Breaker failure function is included for both of the breakers and is with single-
phase starting and a re-trip of own breaker.
A thermal overload function is available to supervise abnormal service.
Voltage protection functions are available as voltage level supervision.
A Loss of voltage function will open circuit breaker and prepare for system
restoration following a system voltage collapse.
A Pole Discordance function supervises the position of the breaker poles for the
two involved breakers.
The necessary auxiliary functions such as Fuse failure supervision are also included.
The necessary trip logic is provided to trip the involved breakers.
Measuring functions S, P, Q, I, U, PF, f are available for local presentation on the
local HMI and/or remote presentation. The availability of analog inputs allows
connection to separate metering cores and a built-in calibration on the analog
inputs allows calibration at site to very high accuracy, then involving the
instrument transformer errors and voltage drops in secondary cabling.
Optional functions can be ordered and include functions such as full control, local
and remote, Directional Earth fault, Out of step protection, Frequency protection,
and so on. These optional functions must be added to the configuration and loaded
into the IED after delivery.
Following should be noted. This connection diagram shows the connection with the
basic supplied single binary input and binary output boards. In many cases this is
sufficient, in other cases, for example with full control of all apparatuses included
1MRK505186-UEN D Section 6
Configuration
705
Application manual
more IO cards are required. Our proposal for a full version with control is to use
two Binary input modules and two Binary output modules. For systems without
Substation Automation a second binary output board might be required.
The configuration includes a binary input for IED in test. Normally this is activated
from the test switch NO contact. In test mode functions need to be released from
the local HMI menu. It is then also possible to switch off IEC 61850 communication.
A binary input is also provided to block changes such as setting changes,
configuration changes or local HMI changes. Activation of this input after
commissioning, for example from an openable terminal prevents all changes except
switching between pre-tested setting groups.
Section 6 1MRK505186-UEN D
Configuration
706
Application manual
C
C
T
C
T
C
=3-QA1
QA1-CLOSED
QA1-SPR UNCH
QA1-PD
CLOSE QA1
TRIP QA1 L1,L2,L3
MAIN 2 TRIP
C
C
T
C
T
C
P1
-QB1
=1-QA1
-BI1
QA1-CLOSED
QA1-SPR UNCH
QA1-PD
CLOSE QA1
TRIP QA1 L1,L2,L3
MAIN 2 TRIP
-QB9
MCB-OK
MCB-OK
BUS A
BUS B
BBP-TRIP
SPARE
SPARE
SPARE
SPARE
CR DTT
CS DTT T
O
/
F
R
O
M
P
L
C
/
M
U
X
F
A
U
L
T
S
I
G
N
A
L
L
I
N
G
Configuration 1MRK004500-85
RED670 1Phase trip/Multi Breaker
TO MAIN 2 RELAY
TO BUS PROT
MCB OR
FUSE
+ -
IRF
P1
-BI1
TO MAIN 2 RELAY
-QB9
MCB-OK
MCB OR
FUSE
-QB6
MCB OR
FUSE
=2.QA1 CBF
BUSBAR TRIP
TRIP =2-Q1
DTT2 Line 2
=2-QA1
QB9-OPEN
TRM1:1-3
TRM1:4-6
TRM1:7-9
TRM1:10
TRM1:11
TRM1:12
NOTE! CB CLosed is CB
Closed L1&L2&L3
CB Open is CB Open
L1 OR L2 OR L3
-BU1
-BU1
-BU1
-BU1
-QB61
-QB62
-QB6
-QB2
MCB OR
FUSE
X11.4 5
X11.1
X11.2
3
DTT L2
TEST
CH LOCK
BIM3.15
BIM3.13
BIM3.7
BIM3.16
BIM3.9
BIM3.10
BIM3.11
BIM3.5
BIM3.14
BIM3.6
BIM3.2
BOM4.11
BOM4.8
BOM4.5
BOM4.6
BOM4.7
BOM4.4
BOM4.1
BOM4.2
BOM4.3
BIM3.1
BIM3.3
BIM3.12
BIM3.4
BIM3.8
BOM4.23
BOM4.9
BOM4.12
BOM4.13
BOM4.14
BOM4.10
BOM4.24
BOM4.15
BOM4.16
BOM4.17
BOM4.18
BOM4.19
BOM4.20
BOM4.21
BOM4.22
en05000841.eps
IEC05000841 V1 EN
Figure 303: Connection diagram for configuration B32 with the setting and
signal matrix defined
1MRK505186-UEN D Section 6
Configuration
707
Application manual
708
Section 7 Glossary
About this chapter
This chapter contains a glossary with terms, acronyms and abbreviations used in
ABB technical documentation.
AC Alternating current
ACT Application configuration tool within PCM600
A/D converter Analog to digital converter
ADBS Amplitude dead-band supervision
ADM Analog digital conversion module, with time synchronization
ANSI American National Standards Institute
AR Autoreclosing
ArgNegRes Setting parameter/ZD/
ArgDir Setting parameter/ZD/
ASCT Auxiliary summation current transformer
ASD Adaptive signal detection
AWG American Wire Gauge standard
BBP Busbar protection
BFP Breaker failure protection
BIM Binary input module
BOM Binary output module
BR External bi-stable relay
BS British standard
BSR Binary signal transfer function, receiver blocks
BST Binary signal transfer function, transmit blocks
C37.94 IEEE/ANSI protocol used when sending binary signals
between IEDs
CAN Controller Area Network. ISO standard (ISO 11898) for
serial communication
CB Circuit breaker
CBM Combined backplane module
1MRK505186-UEN D Section 7
Glossary
709
Application manual
CCITT Consultative Committee for International Telegraph and
Telephony. A United Nations sponsored standards body
within the International Telecommunications Union.
CCM CAN carrier module
CCVT Capacitive Coupled Voltage Transformer
Class C Protection Current Transformer class as per IEEE/ ANSI
CMPPS Combined mega pulses per second
CO cycle Close-open cycle
Co-directional Way of transmitting G.703 over a balanced line. Involves
two twisted pairs making it possible to transmit information
in both directions
COMTRADE Standard format according to IEC 60255-24
Contra-directional Way of transmitting G.703 over a balanced line. Involves
four twisted pairs of with two are used for transmitting data
in both directions, and two pairs for transmitting clock signals
CPU Central processor unit
CR Carrier receive
CRC Cyclic redundancy check
CS Carrier send
CT Current transformer
CVT Capacitive voltage transformer
DAR Delayed auto-reclosing
DARPA Defense Advanced Research Projects Agency (The US
developer of the TCP/IP protocol etc.)
DBDL Dead bus dead line
DBLL Dead bus live line
DC Direct current
DFT Discrete Fourier transform
DIP-switch Small switch mounted on a printed circuit board
DLLB Dead line live bus
DNP Distributed Network Protocol as per IEEE/ANSI Std.
1379-2000
DR Disturbance recorder
DRAM Dynamic random access memory
DRH Disturbance report handler
DSP Digital signal processor
DTT Direct transfer trip scheme
Section 7 1MRK505186-UEN D
Glossary
710
Application manual
EHV network Extra high voltage network
EIA Electronic Industries Association
EMC Electro magnetic compatibility
EMF Electro motive force
EMI Electro magnetic interference
EnFP End fault protection
ESD Electrostatic discharge
FOX 20 Modular 20 channel telecommunication system for speech,
data and protection signals
FOX 512/515 Access multiplexer
FOX 6Plus Compact, time-division multiplexer for the transmission of
up to seven duplex channels of digital data over optical fibers
G.703 Electrical and functional description for digital lines used by
local telephone companies. Can be transported over balanced
and unbalanced lines
GCM Communication interface module with carrier of GPS
receiver module
GDE Graphical display editor within PCM600
GI General interrogation command
GIS Gas insulated switchgear
GOOSE Generic object oriented substation event
GPS Global positioning system
GSM GPS time synchronization module
HDLC protocol High level data link control, protocol based on the HDLC
standard
HFBR connector
type
Plastic fiber connector
HMI Human machine interface
HSAR High speed auto reclosing
HV High voltage
HVDC High voltage direct current
IDBS Integrating dead band supervision
IEC International Electrical Committee
IEC 60044-6 IEC Standard, Instrument transformers Part 6:
Requirements for protective current transformers for
transient performance
1MRK505186-UEN D Section 7
Glossary
711
Application manual
IEC 60870-5-103 Communication standard for protective equipment. A serial
master/slave protocol for point-to-point communication
IEC 61850 Substation Automation communication standard
IEEE Institute of Electrical and Electronics Engineers
IEEE 802.12 A network technology standard that provides 100 Mbits/s on
twisted-pair or optical fiber cable
IEEE P1386.1 PCI Mezzanine card (PMC) standard for local bus modules.
References the CMC (IEEE P1386, also known as Common
mezzanine card) standard for the mechanics and the PCI
specifications from the PCI SIG (Special Interest Group) for
the electrical EMF Electro Motive Force.
IED Intelligent electronic device
I-GIS Intelligent gas insulated switchgear
IOM Binary input/output module
Instance When several occurrences of the same function are available
in the IED they are referred to as instances of that function.
One instance of a function is identical to another of the same
kind but will have a different number in the IED user
interfaces. The word instance is sometimes defined as an
item of information that is representative of a type. In the
same way an instance of a function in the IED is
representative of a type of function.
IP 1. Internet protocol. The network layer for the TCP/IP
protocol suite widely used on Ethernet networks. IP is a
connectionless, best-effort packet switching protocol. It
provides packet routing, fragmentation and re-assembly
through the data link layer.
2. Ingression protection according to IEC standard
IP 20 Ingression protection, according to IEC standard, level 20
IP 40 Ingression protection, according to IEC standard, level 40
IP 54 Ingression protection, according to IEC standard, level 54
IRF Internal fail signal
IRIG-B: InterRange Instrumentation Group Time code format B,
standard 200
ITU International Telecommunications Union
LAN Local area network
LIB 520 High voltage software module
LCD Liquid crystal display
LDCM Line differential communication module
LDD Local detection device
Section 7 1MRK505186-UEN D
Glossary
712
Application manual
LED Light emitting diode
LNT LON network tool
LON Local operating network
MCB Miniature circuit breaker
MCM Mezzanine carrier module
MIM Milli-ampere module
MPM Main processing module
MVB Multifunction vehicle bus. Standardized serial bus originally
developed for use in trains.
NCC National Control Centre
NUM Numerical module
OCO cycle Open-close-open cycle
OCP Overcurrent protection
OEM Optical ethernet module
OLTC On load tap changer
OV Over voltage
Overreach A term used to describe how the relay behaves during a fault
condition. For example a distance relay is over-reaching
when the impedance presented to it is smaller than the
apparent impedance to the fault applied to the balance point,
i.e. the set reach. The relay sees the fault but perhaps it
should not have seen it.
PCI Peripheral component interconnect, a local data bus
PCM Pulse code modulation
PCM600 Protection and control IED manager
PC-MIP Mezzanine card standard
PISA Process interface for sensors & actuators
PMC PCI Mezzanine card
POTT Permissive overreach transfer trip
Process bus Bus or LAN used at the process level, that is, in near
proximity to the measured and/or controlled components
PSM Power supply module
PST Parameter setting tool within PCM600
PT ratio Potential transformer or voltage transformer ratio
PUTT Permissive underreach transfer trip
RASC Synchrocheck relay, COMBIFLEX
1MRK505186-UEN D Section 7
Glossary
713
Application manual
RCA Relay characteristic angle
REVAL Evaluation software
RFPP Resistance for phase-to-phase faults
RFPE Resistance for phase-to-earth faults
RISC Reduced instruction set computer
RMS value Root mean square value
RS422 A balanced serial interface for the transmission of digital
data in point-to-point connections
RS485 Serial link according to EIA standard RS485
RTC Real time clock
RTU Remote terminal unit
SA Substation Automation
SC Switch or push-button to close
SCS Station control system
SCT System configuration tool according to standard IEC 61850
SLM Serial communication module. Used for SPA/LON/IEC
communication.
SMA connector Subminiature version A, A threaded connector with constant
impedance.
SMT Signal matrix tool within PCM600
SMS Station monitoring system
SNTP Simple network time protocol is used to synchronize
computer clocks on local area networks. This reduces the
requirement to have accurate hardware clocks in every
embedded system in a network. Each embedded node can
instead synchronize with a remote clock, providing the
required accuracy.
SPA Strmberg protection acquisition, a serial master/slave
protocol for point-to-point communication
SRY Switch for CB ready condition
ST Switch or push-button to trip
Starpoint Neutral point of transformer or generator
SVC Static VAr compensation
TC Trip coil
TCS Trip circuit supervision
TCP Transmission control protocol. The most common transport
layer protocol used on Ethernet and the Internet.
Section 7 1MRK505186-UEN D
Glossary
714
Application manual
TCP/IP Transmission control protocol over Internet Protocol. The de
facto standard Ethernet protocols incorporated into 4.2BSD
Unix. TCP/IP was developed by DARPA for internet
working and encompasses both network layer and transport
layer protocols. While TCP and IP specify two protocols at
specific protocol layers, TCP/IP is often used to refer to the
entire US Department of Defense protocol suite based upon
these, including Telnet, FTP, UDP and RDP.
TEF Time delayed earth-fault protection function
TNC connector Threaded Neill Concelman, A threaded constant impedance
version of a BNC connector
TPZ, TPY, TPX,
TPS
Current transformer class according to IEC
Underreach A term used to describe how the relay behaves during a fault
condition. For example a distance relay is under-reaching
when the impedance presented to it is greater than the
apparent impedance to the fault applied to the balance point,
i.e. the set reach. The relay does not see the fault but
perhaps it should have seen it. See also Overreach.
U/I-PISA Process interface components that deliver measured voltage
and current values
UTC Coordinated universal time. A coordinated time scale,
maintained by the Bureau International des Poids et Mesures
(BIPM), which forms the basis of a coordinated
dissemination of standard frequencies and time signals. UTC
is derived from International Atomic Time (TAI) by the
addition of a whole number of "leap seconds" to synchronize
it with Universal Time 1 (UT1), thus allowing for the
eccentricity of the Earth"s orbit, the rotational axis tilt (23.5
degrees), but still showing the Earth"s irregular rotation, on
which UT1 is based. The Coordinated Universal Time is
expressed using a 24-hour clock and uses the Gregorian
calendar. It is used for aeroplane and ship navigation, where
it also sometimes known by the military name, "Zulu time".
"Zulu" in the phonetic alphabet stands for "Z" which stands
for longitude zero.
UV Undervoltage
WEI Weak end infeed logic
VT Voltage transformer
X.21 A digital signalling interface primarily used for telecom
equipment
3I
O
Three times zero-sequence current. Often referred to as the
residual or the earth-fault current
1MRK505186-UEN D Section 7
Glossary
715
Application manual
3U
O
Three times the zero sequence voltage. Often referred to as
the residual voltage or the neutral point voltage
Section 7 1MRK505186-UEN D
Glossary
716
Application manual
717
Contact us
ABB AB
Substation Automation Products
SE-721 59 Vsters, Sweden
Phone +46 (0) 21 32 50 00
Fax +46 (0) 21 14 69 18
www.abb.com/substationautomation
1
M
R
K
5
0
5
1
8
6
-
U
E
N
D
C
o
p
y
r
i
g
h
t
2
0
1
0
A
B
B
.
A
l
l
r
i
g
h
t
s
r
e
s
e
r
v
e
d
.