5081505-02-GB Servicemanual ULUF450 - 490 - 850 - 890 - 750 (G-214)
5081505-02-GB Servicemanual ULUF450 - 490 - 850 - 890 - 750 (G-214)
5081505-02-GB Servicemanual ULUF450 - 490 - 850 - 890 - 750 (G-214)
2
Index
1. Working safety
General safety
Electrical safety
Chemical and biological safety
2. Information about the unit
2a. Information about the freezer
2b. Controller G-214
2c. Model information
3. Troubleshooting / Repair
3a. General operating problems
3b. Troubleshooting schedule
3c. Opening of the cooling system
3d. Evacuation of the refrigerant
3e. Changing the drylter
3f. Changing the compressor
3g. Pressure testing and leak detection
3h. Vacuum suction / Vacuum check
3i. Refrigerant lling with EP88
3j. Electrical troubleshooting
3k. Electrical fault - compressor
3l. HST-start relay, start capacitor
3m. Sensor for the controller
3n. Condenser - fan
3o. Controller - demounting the display
3p. Vacuum valve
3q. Heated door frame
4. Maintenance
4a. Rubber gasket of the door
4b. Locks and hinges
4c. Evaporator
4d. Manual defrost, cleaning and maintenance
4e. Noise
4f. Battery backup
5. Wiring-diagrams and safety data sheet
5a. Wiring-diagram ULUF 450/850/490/890/750
5b. Spare parts list ULUF 450/850/490/890/750
5c. Compressor data ULUF 450/850/490/890/750
5d. Safety data sheet EP88
5e. Controller G-214
5f. Default settings
3
1. Working safety
This page provides general safety information for servicing the freezer.
The instruction manual includes additional information about security and cleaning of freezer.
1.1 General safety
To prevent personal and equipment damage, the electrical safety / legislation of your country must be obser-
ved.
1. Never expose the moving parts of the plant to physical overload.
2. When repairing plant parts, safety concerns must be respected.
3. When using tools, spare parts and equipment, the existing security concerns must be met.
4. Maintenance procedures described in this manual must only be performed by trained per-
sonnel.
1.2 Electrical safety
Maintenance procedures may imply a voltage hazard. Follow existing safety instructions, including the low
voltage and current EU directives and other derectives of your country.
Always disconnect the power to the unit before repair or parts replacement is initiated.
Use only electrical equipment which is designed for the freezer.
1.3 Chemical and biological safety
Always observe the requirements for safe handling, as described below.
Read the instruction manual before using, cleaning and servicing the freezer.
Wear eye protection and gloves when working with refrigerants.
Skin contact with liquid refrigerants may cause frostbite.
Good ventilation and air extraction at the work area is required.
Stay in environments with high concentrations of refrigerant vapors is harmful.
Low concentrations may cause narcotic effects.
Symptoms of this may include: headache, shortness of breath, nausea and difculties in concentra-
tion. Possibly: Mobility / consciousness.
Read the safety data sheet section 5d.
4
2. Information about the freezer
ULUF 450/490/750
ULUF 850/890
2a. General information about the freezer
Halogen light
Sub lids
Heated door frame
Castors
Door hinge
Castors
Door handle
Lock
Controller
G-214
Backside
Prepared holes for extra sensors
5
When contacting the supplier it is important to inform the model and serial number.
The label plate is located behind the front panel in the engine compartment.
For technical problems: See troubleshooting schedule (3b).
Furthermore, the device is equipped with:
Heated door frame
Heated vacuum valve
The freezer must be defrosted manually. See Section 4d.
ULUF 490/890 series are equipped with dual cooling system that provides rapid cooling and safety in case of
problems on one of the systems.
Label plate located on the device.
2b. Controller G-214
Serial no. Temp. range Model Filling/Refrigerant Voltage/Hz
The PCB controller board is located in the engine compartment behind
the front panel.
The display is mounted in the front panel.
Data controller:
72 hour battery backup for alarms.
Microprocessor with digital display.
Temperature display and data acquisition during power failures.
Visual and audible alarm.
Adjustable high / low temperature / alarm.
Integrated data logger.
Automatic cycle of sensor failure.
Measurement of the ambient air temperature.
Direct download / upload from the USB memory stick.
Display of battery voltage and ambient temperature.
Integrated memory and data logger.
RS 485/232 Interface.
Contact for remote alarm.
Prepared for GSM alarm.
Alarm for:
High / low temp.
Voltage Fault
Sensor error
Instrument error
Front door
Display G-214
PCB board
Datasheet for controller G-214.
See section 5e.
6
*) Power consumption is monitored over time for each element. Pt. no values .
3. Troubleshooting / Repair
3a. General operating problems
Malfunction of the device, which can arise from improper handling of the device:
Moving or long periods of inactivity of the unit:
When moving or after long periods of inactivity, you must wait 1-2 hours before the freezer is
started.
Loading the freezer
When loading large quantities of items into the freezer, the temperature will rise temporarily.
Repeated door openings
In case of repeated door openings, leaks or faulty gaskets, the humidity will cause rime and possi-
bility of ice formation inside the device and around the door / interior door.
Component failure occurred during operation
Use the troubleshooting table section 3b.
2c. Model information
Model ULUF 490/890 ULUF 450/850/750
Item code DAI 1405/DAI 1409 DAI 1408/DAI 1411/DAI 1416
Temp. range(
0
C) -40/-90 -40/-85
Max. ambient temp.(
0
C) 25 25
Power supply (V) 230 230
Frequency (Hz) 50/60 50/60
Fuse (A) 10 10
AMP (A) 3,8/2x3,8 1,9/2x1,9/5
Power consumpon
(KWh/24h)
23,8/2x23,8 11/2x11/20
Power (KW/Hp) *) *)
Compressor See Spare Parts List See Spare Parts List
No. of compressors 2/2x2 1/2/1
Refrigerant/lling/gram EP88 / see label plate EP88 / see label plate
7
Problem Cause Recommended
equipment
Troubleshoong Acon
The unit does not
freeze and the
compressor does
not start.
The socket or
fuse is defect.
Universal
instrument
test Lamp
Check the instal-
laon.
New fuse / plug.
Power cable is defect. Check power
cables
and wiring in the
engine compart-
ment.
Repair errors. Con-
sider using wiring
diagram secon 5
The controller is defect. Change controller
The sensor is defect. Test sensor. See secon 3m
Faulty windings in
compressor.
Test compressor
windings.
See secon 3k
Start relay defect. Test start relay. See secon 3l
Fault in electrical instal-
laon.
Use wiring-dia-
gram.
See secon 5
The unit does not
freeze. The com-
pressor tries to
start, but fails.
Low voltage
Voltmeter Check voltage Find the cause.
Defect or faulty start
relay/capacitor.
See secon 3m See secon 3m Change start relay/
capacitor
Defect compressor
windings.
Ohmmeter Check for electrical
failure in the com-
pressor.
Change the compr.
See secon 3f
Defect rotor (compres-
sor failure)
Change the compr.
See secon 3f
High pressure in the
cooling system.
Tapping valve
Manometer
Filter
Open the system
and rinse the sy-
stem with nitrogen.
Remove 5cm of
the capillary tube.
Change lter.
See secon 3e
The unit has been
transported horizon-
tally.
The unit must rest
a few hours before
start.
Ambient temp. low.
Compr.oil too cold.
Eksternal thermo-
meter.
Check the temp. Find a beer place-
ment.
May be general, if the
venlaon is not suf-
cient.
___________________
Ambient temp. high.
Eksternal thermo-
meter.
_______________
Thermometer
Check, that the
compressor not
exceeds 70C.
________________
Check ambient
temp.
Find a beer pla-
cement or venla-
on.
______________
Find a beer pla-
cement or venla-
on.
3b. Troubleshooting schedule
8
Problem Cause Recommended
equipment
Troubleshoong Acon
The compressor
runs constantly.
The unit freezes
normal or colder.
The sensor is in-
correctly installed.
Sensor is defect.
Controller is dama-
ged.
Icing on the frame. Check the door for
leaks.
See secon 4a.
The temperature is
set too low.
Check the se ngs
in the controller.
Set new values.
See secon 5f.
The compressor
starts normally,
but stops again.
Too high voltage. Voltmeter Meassure the vol-
tage.
Inform.
Too high ambient
temperature.
external thermometer Check the tempe-
rature and venla-
on.
Beer placement
or venlaon.
The unit cools too
much, too lile or
not at all.
The compressor
may run con-
nuously.
Leakage in the sy-
stem.
Electronic leak-seeking,
soapy water, leak se-
eking spray.
First check the solder
points, comp,
capacitor, etc.
See secon 3.
The fan is not run-
ning.
Voltmeter Check for errors. Replace the fan.
See secon 3n.
The evaporator is
blocked by ice.
The unit cools too
much or not at all.
Compressor run-
ning constant.
Lile or no com-
pressor
capacity.
service valve
Manometer
Mount the valve
and check pressure.
Change compres-
sor.
See secon 3f.
Insu cient
cooling.
The device has
recently been l-
led up with a large
amount of heat.
Inform the user.
In addion, tem-
perature of the air
is too high.
external thermometer Check temperature. Find beer venla-
on or placement.
In addion, the air
temperature is too
low.
external thermometer Check temperature. Find beer venla-
on or placement.
3b. Troubleshooting schedule
9
Examples of troubleshooting with a manometer connected to the process piping of the cooling sy-
stem. The system is blocked:
Suction pressure is very low.
Pressure equalization takes place very slowly or not at all.
Reason: Icing or dirt in the capillary tube or lter, or blockings in the system due to other reasons.
Reason: No compressor capacity
The suction pressure is too high.
The suction pressure does not change noticeably when the compressor stops.
This can be tested with a volumetric meter.
Leakage in the system
The pressure gauge indicating insufcient suction pressure.
On the pressure side the temperature increases.
Pressure equalization time is short.
Countervailing pressure is lower than expected.
Be sure that the pressure is sufcient for a pressure test.
10
3c. Opening of the cooling system
To prevent moisture from penetrating under repair, the system must not be open for more
than 15 minutes.
Prepare spare parts components before the system is opened.
The new connector is soldered to a tube with valve.
Verify that the new lter packaging is intact and that the lter is not damaged.
If the packaging has been broken for a longer period, the lter will bee moist
3d. Evacuation of the refrigerant
It is recommended that the compressor is running at least 25 min. before refrigerant eva-
cuation is undertaken. This ensures that the system is hot, so that the refrigerant easier can
be pulled out of the compressor oil.
A drilling tongs with valve is placed on the process pipe.
The refrigerant is evacuated.
Install a valve on the pressure tube and process pipe.
11
The cooling system is evacuated with a two-stage vacuum pump for at least 30 minutes.
Both from the pressure piping and process piping.
Blow the system with nitrogen, both from the suction and the pressure side.
3e. Changing the dry lter
The dry lter must pick up moisture in the system during operation and function as the ca-
pillary tube in front of the capilary tube, in order to avoid clogging. Clogged lter or capillary
tube causes a pressure drop, by this the lter becomes colder and ice will block the system.
The compressor is overloaded with a possibility of crash.
The dry lter is placed after the condenser outlet, immediately before the capillary. Any
opening of the cooling system, dry lter change to ensure the function and lifetime of the
freezer.
It is therefore recommended always to order a new lter drier, along with a new service cy-
linder with cooling agent.
To prevent moisture from penetrating during the repair, the drying lter must not be open
for more than 10 minutes.
After evacuation and blowing with nitrogen, the tubes must be cleaned on both sides of the
lter drier, before cutting. By doing this the pipe ends are free from impurities and metal pie-
ces and ready for soldering.
Cut off the pressure pipe close to the lter with a pipe cutter.
Cut off the capillary tube with a capillary tube scissors.
It is recommended to use a special tongs to create a wave on the capillary tube which en-
sures the correct positioning in the lter.
Process pipe and pressure
tube tted with a valve.
12
A
a
Right
B
Wrong
In the gure A the capillary tube is correctly installed in a dry lter. In order to ensure efcient
use of the lter, it must be positioned with an inclination of at least 150 and the capillary tube
must be underneath.
In the gure B the capillary tube is too close too the web of the lter. It provides great resistan-
ce and lter blocking after a short time. Or too far away, so it will be lled with ux or solder.
Solder the new lter.
Clean the solder points with a wire brush.
Flush the system with nitrogen.
If only the dry lter is to be replaced, the system must be pressure tested. See section 3g.
13
3f. Changing the compressor
Evacuate the refrigerant of the system. See section 3d.
All tubes are cut with a pipe cutter. Do NOT solder of.
When replacing the compressor the dry lter must also be replaced. See section 3e.
The suction and pressure pipes of the compressor must be cleaned and cut with a pipe cut-
ter just above the soldering pipe.
Demount the compressor.
Install the new compressor, which is prepared as described before. (3c)
In order to avoid decomposition of refrigerants which may remain in the system during the
soldering operation, the system is blown with dry nitrogen, respectively, from the suction
side respectively pressure side.
Solder the tubes on to the compressor.
Pressure test the system.
3g. Pressure testing and leak detection
Pressure test the system with nitrogen. The pressure must be 10 bar during a period of 2
hours.
Check the solder points with soapy water or leak detection spray.
In case of any leaks, empty the system for nitrogen.
Repair and pressure test again.
During operation leak detection must be performed on the pressure side with the compres-
sor running. The suction side must be tested while the compressor is stopped, and the
pressures are equalized.
The nitrogen must slowly be emptied from the system.
14
3h. Vacuum suction / Vacuum check
A vacuum is made on two locations on the system, one on the process tube and one on the pipe branch
used for testing located on the pressure tube with an explosion-proof 2-stage vacuum pump.
The pressure should be 2 mBar or lower for at least 12 hours.
The system is now ready for the lling of the refrigerant.
3i. Refrigerant lling with EP88
Before lling the refrigerant, a vacuum must be suched. See section 3h.
Note that EP88 is to be supplied from a bottle containing a specic amount of refrigerant.
Common procedures for other refrigerants can not be used.
Further it is important that the entire contents of the bottle is introduced into system to ensure optimal perfor-
mance.
The contents of the bottle must be mixed before use by shaking the bottle for at least 1 minute before the
lling.
In order to perform the lling operation properly, it is necessary to use a capillary tube with the valve before
the lling site, instead of a conventional feeding tube. The reason is that the capillary tube ensures that the
entire quantity of refrigerant is introduced to the system. If an ordinary ller hose is used, it must be as short
as possible.
WARNING! EP88 is ammable!
The refrigerant cylinder is weighed before use.
The cylinder must be shaken for 1 min. before use.
During the lling procedure the cylinder must be upside down.
15
Cylinder with manometer Vacuum suction of the lling hose
Loading procedure
Make vaccum. See section 3h.
The cylinder with manometer is connected to the coupler of the process piping.
Remember to rst made vacuum in the lling hose to empty it.
Fill the refrigerant into the system until the pressure gauge on the pressure tube shows approx. 5 bar.
Start the compressor and let it run for 2-3 min. Open to the cylinder again to get out the remaining refrigerant.
When the pressure in the bottle shows 1 bar, the bottle is empty.
It is important that the valve is closed immediately, in order to avoid that the refrigerant runs back into the cylinder.
Now the cooling system is lled with refrigerant and only needs to be closed.
Disconnect the lling hose with pressure gauge from the process piping.
Push the process piping and pressure pipes together with a special tongs.
Cut off valve with a pipe cutter.
Closing the process tube on systems with ammable refrigerants must be performed by professionals with a Lok
Ring end sleeve. It is recommended NOT to solder system.
Clean the pipe with steel wool or emery cloth. Use rotational movement in order to avoid scratching the length of
the tube.
Apply LokPreb to the end of the tube.
Turn the end sleeve 360 so that the LokPreb is placed around the tube.
Squeeze the end sleeve together with the special tool as shown in the illustration.
Start the freezer and control the function of the unit.
16
3j. Electrical troubleshooting
Before starting systematic troubleshooting, check the following:
Proper voltage is present.
Electrical equipment used, is suitable for the compressor.
The wires are properly installed according to wiring diagram.
There is no transition between the live parts and ground.
Control of the transition to ground.
In order to check whether there is a transition between the conducting components and the chas-
sis, the insulation resistance is tested by using an ohmmeter or the second high-voltage equip-
ment. An ohmmeter can be used for a rough check. Ohmmeterets one clamp is placed on the com-
pressors ground terminal. The second clamp on the compressor fllesben (see sketch). Showing
ohmmeter a transition, the compressor is replaced.
Uses high voltage test systems with ammable refrigerants, ensure that the system is completely
drained of coolant, as this can cause sparks during the test.
Plug on the compressor
Shared leg Ground terminal
17
3k. Electrical fault - compressor
Remove the start relay from the compressor and use an ohmmeter to test the compressor head
and start recovery. Connect ohmmeter between the common connector and start winding, then ho-
vedviklingen to debug. See the picture below.
Dimensions of the compressor connections to determine whether driving and startvikling are intact.
This is done by measuring the resistance of these. Carry out three resistance measurements on
compressor penetrations. The sum of the two smallest measurements, the intact windings will be
equal to the highest. Find if the current values of the compressor data sheet.
By measuring the compressors with built viklingsbeskytter it
is extremely important to measure between K and S, as this
measure will tell if this is burnt windings or an open winding
protector.
Since it is relatively small value to be measured, it would be
a great advantage to use a digital ohm-meter.
Indicates the measurement error, the compressor is replaced.
Ohm-measurement
Winding
protector
18
3l. HST-start relay, start capacitor
Connect a voltmeter between terminals 10 and 13 at the start of the relay. If no voltage is present,
there is either a faulty cable or also start relay is defective.
Connect a voltmeter between terminals 10 and 14 If no voltage is present, the temperature sensor
or its cable is defective.
19
When replacing the compressor should start relay and start capacitor also replaced.
Start relay is placed on the compressors three terminalben and clamped.
The voltage connected to terminals 10 and 14
Startkondensatoren connected to terminals 11 and 13 and clamped.
A relay can be checked with an indicator light as
shown in the sketch maintain end. The relay is usu-
ally ok, when in standing position is not lit, and when
it is lit when the relay is upside down.
The start capacitor can be checked by injecting the
normal voltage for a few seconds and than shorting
it. When sparks are generated, the capacitor is in
order.
b. Cover e. The compressor blades c. Start capacitor
a2. Start relay d. Wire hanger
20
3m. Sensor for the controller
PT 1000
A faulty sensor will typically prevent the compressor from starting.
If the sensor is covered with ice, the compressor will run more than usual and cool too much.
The easiest way to check the function of the sensor, is to place your hand around the sensor. If the
temperature recorded on the display in the front panel does not rise, the sensor is faulty and needs
to be replaced.
The sensor can also be tested with an ohmmeter.
The PT 1000 sensor is located on the right side between shelf 2 and 3 ans is secured with strips.
Note that the tip of the sensor must not be in direct contact with the evaporator tubes.
This will result in an erroneous temperature measurement.
The sensor must be introduced together with the evaporator tubes in the top of the engine com-
partment.
The holes are sealed with putty. Electrically, the sensor is connected to the PBC board. See the
wiring diagram section 5a.
Mounting of the sensor in the freezer
Introduction of the sensor from the top
of the engine compartment
Change of probe:
Disconnect the power supply.
Remove the engine grille.
Remove the sealing material around the wire of the sensor on both sides of the hole.
Remove the strips.
Pull the sensor into the engine compartment.
Disconnect the electrical connection of the sensor in the CBS module.
Mount the new sensor in reverse order.
Remember! The sensor must be replaced with a sensor with the same characteristics as the
original.
21
3n. Condenser - fan
The condensor is placed in the engine compartment of the freezer behind the front panel. It is xed with
4 bolts.
The rst part is a double tube condenser with fan, followed by condenser coils.
Check that the bolts are well tightened and that the rubber gaskets at the fan are not hard or defective.
It is important that the cooling ribs are kept clean and the ambient temperature does not exceed 25C.
Physically, the fan is placed on the frame of the capacitor.
Electrically, the fan is connected to terminal 10 and 14 on the start relay. See wiring diagram section 5a.
Condenser coil Fan
If the ventilator stops, it can cause insufcient cooling of condenser and compressors.
Higher condensing temperature means that the compressor must work more with less efciency as a
result. At worst, the compressors stops due to high temperature.
ULUF 490 /890
with
2 compressors
Condenser
22
3p. Vacuum valve
The freezer is equipped with a heated vacuum valve in order to avoid vacuum in case of repeated
door openings.
Electrically, the heater (12V) is supplied from the PCB board. See the wiring diagram section 5a.
Introduction of the cable is carried out at the back of the engine compartment. A tube leads to the
bottom of the freezer where the vacuum valve is located.
Mounting device Wire connectors Mounting device
The top of the engine compartment
The bottom of the freezer Under the freezer
3o. Controller - demounting the display
Demount of display
Disconnect the wire connector on the bottom of the display.
Squeeze the mounting devices at the bottom and top together and push out the display.
23
3q. Heated door frame.
2 pcs. heaters are installed in the door frame.
One is connected electrically. The second is as a spare heater.
Electrically, the cable (220V) is supplied by the PCB board and assembled in the controller box.
See the wiring diagram section 5a.
The cable is introduced to the door frame on the front of the engine compartment behind the front
panel.
Introduction of cable
Spare cable
24
4. Maintenance
4a. Rubber gasket of the door
4b. Locks and hinges
Make sure the hinges are not loose and the door easily can be opened and closed.
Make sure the lock works easily and safely. If nesessary, use a lubricant for locks.
If there is ice around the door frame, the door must be adjusted.
Rub the gasket with a suitable product, so that it stays exible and the optimal function and tight-
ness is secured.
Make sure the door closes tightly so that no ice forms around the door frame.
Open the door and place a piece of paper. Close the door.
Pull the paper.
If the paper can not be pushed back, the adjustment is OK.
The test is made at both the left and right side.
In case that the gasket do not close properly, see section 4b.
The adjustment screw is turned clockwise to tighten the door.
Adjustment screw
25
4c. Evaporator
The evaporator tubes are integrated into each shelf.
The ULUF 490/890 models have dual evaporator tubes, since there is one system for each com-
pressor.
The door frame, inner doors and the sensor must be checked for ice.
In case of large ice formation, the freezer must be defrosted.
4d. Manual defrost, cleaning and maintenance
There will be some ice formation on the sub lids of the freezer.
The ice must be removed with a scraper on a regular basis (Remember safety gloves).
Ice on the inside of the cabinet must be removed as required.
This is done by manual defrost:
Remove the contents of the freezer.
Unplug the unit.
Leave the door open until the ice can be removed.
Wipe the interior cabinet and shelves with a cloth until it is dry.
Ice formed on the inside of the door, must be removed with a wooden / plastic scraper. This ice is
formed due to the low temperatures inside the cabinet, and if the ice is not removed, it will cause
that the door does not close tightly.
26
4e. Noise
The following must be checked in case of noise:
The compressor is not tightened well.
The rubber feet are defect or too hard.
The compressor process tube is too long.
The fan blades are damaged or dirty.
The fan is not tightened well.
The fan bushings are worn.
The freezer is not positioned on a at surface.
Long pipes can cause resonance vibrations.
4f. Battery backup
The battery (12V 7Ah) is located in the engine compartment behind the front panel.
It has a lifespan of 3 years, but should be checked every six months.
Check the voltage with a voltmeter.
The controller G-214 has built-in measurer for the battery voltage.
Rubber feet Process tube (too far)
Backup battery
27
28
5a. Wiring-diagram ULUF450/850/750 with G-214 controller
29
5a. Wiring-diagram ULUF490/890 with G-214 controller
30
5b. Spare parts list ULUF 450 with G-214 controller
35
34
15
14
1
19
38 6 9
20 13 36 3 37 2 4
5
12
10
22
24
25
21
26
16
18 28 27 31 29 33 32
17
7
11
23
8
30
31
5b. Spare parts list ULUF 450 with G-214 controller
Pos. no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24a
24b
24c
25
26
27a
27b
28a
28b
28c
29
30
31
32
33
34
35
36
37
38
-
-
-
-
-
-
-
-
-
-
e r i w l c n i ) c i t e n g a M ( r o s n e s r o o D 1 0 - 5 0 0 9 4 0 5
r e l l o r t n o c r o f e t a l p l a t e M 1 0 - 4 2 0 1 3 0 5
5019003-01 Transformer 230V 50/60 Hz 12 Vac / 4 amp 1
1
1 e m a r F r o f t e k s a G 1 0 - 5 1 0 2 5 0 5
) 4 1 2 G ( r o s s e r p m o C r o f e b o r P C T N 1 0 - 0 1 0 2 4 0 5
) 4 1 2 G ( r e b m a h C r o f e b o r P C T N 1 0 - 1 1 0 2 4 0 5
5070001-01
5070027-01
Compressor SC21CNX.2 Complete
Start relay 117U7013
1
1
. n o i t c e n n o c d r o b B C P r o f x o B 1 0 - 6 0 0 9 4 0 5
1 ) H A 7 , V 2 1 ( 2 1 - 7 P B y r e t t a B 1 0 - 1 0 0 4 4 0 5
5041006-01
d e d n e m m o c e R t r a P . o n e d o C
1 t e k s a g c i t e n g a M r o o D 1 0 - 4 1 0 2 5 0 5
F U L U s e g n i h f o t e S 1 0 - 5 2 0 1 3 0 5
Body Cabinet
t e k s a g h t i w e t e l p m o C r o o D 1 0 - 1 0 0 2 5 0 5
Valve heater
. s c p 2 , e k a r b h t i w l e v i w s r o t s a c t n o r F 1 0 - 7 0 0 3 5 0 5
. s c p 1 f l e h S 1 0 - 1 1 0 0 6 0 5
e v l a v m u c a V 1 0 - 7 0 0 4 7 0 5
Door Hinge, Lower subdoor
r o o d b u s r e p p U , m m 0 7 4 * 0 6 2 r o o d b u S 1 0 - 6 1 0 2 5 0 5
. c s p 2 , e k a r b t u o h t i w l e v i w s r o t s a c k c a B 1 0 - 6 0 0 3 5 0 5
Door Hinge, Upper subdoor
F U L U r e g n a h c x e t a e H 1 0 - 5 0 0 4 7 0 5
Front Panel Sleeve
r o o d b u s r e w o L , m m 0 7 4 * 0 3 3 r o o d b u S 1 0 - 7 1 0 2 5 0 5
1 ) 0 0 0 1 T P ( e b o r P 1 0 - 3 0 0 2 4 0 5
t r o p p u s r e w o l l e n a p t n o r F 1 0 - 6 2 0 1 3 0 5
t r o p p u s r e p p u l e n a p t n o r F 1 0 - 7 2 0 1 3 0 5
r o t a r o p a v E 1 0 - 1 0 0 3 7 0 5
e r i w l c n i ) c i t e n g a M ( r o s n e s r o o D 1 0 - 5 0 0 9 4 0 5
Hidden Latch
r o o d b u S r o f h c t a l c i t e n g a M 1 0 - 3 1 0 1 3 0 5
l e n a p t n o r F 1 0 - 9 4 0 0 5 0 5
s t h g i l t o p s r o f e r i W 1 0 - 6 0 0 9 1 0 5
1 4 1 2 - G y a l p s i D 1 0 - 7 0 0 3 4 0 5
1 . c s p 2 s b l u b s t h g i l t o p S 1 0 - 4 0 0 9 1 0 5
s p l u b s t h g i l t o p s r o f r e d l o H 1 0 - 2 1 0 0 5 0 5
1 e d a l b n a f . l c n i n a f r e s n e d n o C 1 0 - 7 0 0 0 1 0 5
1 2 1 0 5 U 7 1 1 r o t i c a p a c g n i t r a t S 1 0 - 4 3 0 0 7 0 5
Front Panel Bush
r e s n e d n o C 1 0 - 2 0 0 1 7 0 5
1 r e l l o r t n o C 4 1 2 - G d r a o B - B C P
1 4 1 2 - G y l p p u S r e w o P 1 0 - 7 0 0 1 4 0 5
t n e m r a p e d r o s s e r p m o c r e v o C 2 0 - 3 2 0 1 3 0 5
s y e k f o t e S . l c n i k c o l r o o D 1 0 - 6 0 0 1 5 0 5
l a r i p s r e s n e d n o C 1 0 - 3 0 0 4 7 0 5
Main Lead
e l d n a H r o o D 1 0 - 8 0 0 1 5 0 5
1 t e k s a G r o o D 1 0 - 4 1 0 2 5 0 5
5074006-01
5072000-01
5079000-01
Pipe for water outlet in bottom
Cylinder deposit for refrigerant
Service dryfilter
1
1
Refrigerant 315 g EP88
32
5b. Spare parts list ULUF 850 with G-214 controller
33
5b. Spare parts list ULUF 850 with G-214 controller
Pos. no.
1
2
3
4
5
6
7
8
9
10a
10b
11
12
14
16
17a
17b
17c
18
19a
19b
20
21
22a
22b
23
24
26
27
28
29
30
31
-
-
-
-
-
-
-
-
-
-
Code no. Part Recommended
Cabinet
5053006-01 Back castor swivel with out brake, 4 psc.
5053007-01 Front castor swivel with brake, 4 pcs.
5052001-01 Door Complete with gasket, 1 pcs
5051006-01 1 pcs Door lock incl set of keys
5051008-01 Door handle, 1 pcs
5031025-01 Set of hinges
5030030-01 Front panel hinge
5030031-01 Gas spring set of 2
5052016-01 Subdoor 260 * 470 mm
5052017-01 Subdoor 330 * 470 mm Lowest subdoor
5031013-01 Magnetic latch for Sub door
5050050-01 Front panel
5043007-01 Display G-214 1
5049005-01 Door sensor (Magnetic) incl wire
5019004-01 Spot lights bulbs 2 psc.
1
5050012-01 Holder for spot lights bulps
5019006-01 Wire for spot lights
5031023-02 Cover compressor deparment
5070027-01 Start relay 117U7013
5070034-01 Starting capacitor 117U5012
5070001-01 Compressor SC21CNX.2 Complete
5074003-01 Condenser spiral
5071002-01 Condenser
5010007-01 Condenser fan incl. fan blade
5031024-01 Metal plate for controller
5044001-01 Battery BP 7-12 (12V, 7AH) 1
5041006-01 PCB Board G-214 Controller 1
5074005-01 Heat exchanger
5060011-01 Shelf
5073001-01 Evaporator
5074007-01 Vacum valve
5031038-01 Body connector with screws
5052015-01 Gasket for frame 1
5052014-01 Door gasket 1
5042003-01 Probe (PT 1000) 1
5049006-01 Box for 230 V connections
5074006-01 Pipe for water outlet in bottom
Finans no. Refrigerant EP-88
5072000-01 Cylinder deposit for refrigerant
5079000-01 Service Filter Dryer
5010007-01 Condenser fan incl. fan blade
NTC Probe for Compressor (G-214)
NTC Probe for Chamber (G-214)
5042010-01
5042011-01
-
34
5b. Spare parts list ULUF 490
35
34
15
14
1
19
38 6 9
20 13 36 3 37 2 4
5
12
10
22
24
25
21
26
16
18 28 27 31 29 33 32
17
7
11
23
8
30
35
5b. Spare parts list ULUF 490
Pos. no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
15c
16
17
18
19
20
21
22
23
24a
24b
24c
25
26
27a
27b
28a
28b
28c
29
30
31
32
33
34
35
36
37
38
-
-
-
-
-
-
- 1
1 e m a r F r o f t e k s a G 1 0 - 5 1 0 2 5 0 5
4 1 - 2 G ( r o s s e r p m o C r o f e b o r P C T N 1 0 - 0 1 0 2 4 0 5
4 1 - 2 G ( r e b m a h C r o f e b o r P C T N 1 0 - 1 1 0 2 4 0 5
5070001-01
5070027-01
Compressor SC21CNX.2 Complete
Start relay 117U7013
1
1
. n o i t c e n n o c d r o b B C P r o f x o B 1 0 - 6 0 0 9 4 0 5
1 ) H A 7 , V 2 1 ( 2 1 - 7 P B y r e t t a B 1 0 - 1 0 0 4 4 0 5
5041006-01
d e d n e m m o c e R t r a P . o n e d o C
1 t e k s a g c i t e n g a M r o o D 1 0 - 4 1 0 2 5 0 5
F U L U s e g n i h f o t e S 1 0 - 5 2 0 1 3 0 5
Body Cabinet
t e k s a g h t i w e t e l p m o C r o o D 1 0 - 1 0 0 2 5 0 5
Valve heater
. s c p 2 , e k a r b h t i w l e v i w s r o t s a c t n o r F 1 0 - 7 0 0 3 5 0 5
. s c p 1 f l e h S 1 0 - 1 1 0 0 6 0 5
e v l a v m u c a V 1 0 - 7 0 0 4 7 0 5
Door Hinge, Lower subdoor
r o o d b u s r e p p U , m m 0 7 4 * 0 6 2 r o o d b u S 1 0 - 6 1 0 2 5 0 5
. c s p 2 , e k a r b t u o h t i w l e v i w s r o t s a c k c a B 1 0 - 6 0 0 3 5 0 5
Door Hinge, Upper subdoor
F U L U r e g n a h c x e t a e H 1 0 - 5 0 0 4 7 0 5
Front Panel Sleeve
r o o d b u s r e w o L , m m 0 7 4 * 0 3 3 r o o d b u S 1 0 - 7 1 0 2 5 0 5
1 ) 0 0 0 1 T P ( e b o r P 1 0 - 3 0 0 2 4 0 5
s p l u b s t h g i l t o p s r o f r e d l o H 1 0 - 2 1 0 0 5 0 5
s t h g i l t o p s r o f e r i W 1 0 - 6 0 0 9 1 0 5
t r o p p u s r e w o l l e n a p t n o r F 1 0 - 6 2 0 1 3 0 5
t r o p p u s r e p p u l e n a p t n o r F 1 0 - 7 2 0 1 3 0 5
5019003-01 Transformer 230V 50/60 Hz 12 Vac / 4 amp 1
r o t a r o p a v E 1 0 - 1 0 0 3 7 0 5
e r i w l c n i ) c i t e n g a M ( r o s n e s r o o D 1 0 - 5 0 0 9 4 0 5
r e l l o r t n o c r o f e t a l p l a t e M 1 0 - 4 2 0 1 3 0 5
e r i w l c n i ) c i t e n g a M ( r o s n e s r o o D 1 0 - 5 0 0 9 4 0 5
Hidden Latch
r o o d b u S r o f h c t a l c i t e n g a M 1 0 - 3 1 0 1 3 0 5
l e n a p t n o r F 1 0 - 9 4 0 0 5 0 5
s t h g i l t o p s r o f e r i W 1 0 - 6 0 0 9 1 0 5
1 4 1 2 - G y a l p s i D 1 0 - 7 0 0 3 4 0 5
1 . c s p 2 s b l u b s t h g i l t o p S 1 0 - 4 0 0 9 1 0 5
s p l u b s t h g i l t o p s r o f r e d l o H 1 0 - 2 1 0 0 5 0 5
1 e d a l b n a f . l c n i n a f r e s n e d n o C 1 0 - 7 0 0 0 1 0 5
1 2 1 0 5 U 7 1 1 r o t i c a p a c g n i t r a t S 1 0 - 4 3 0 0 7 0 5
Front Panel Bush
r e s n e d n o C 1 0 - 2 0 0 1 7 0 5
1 r e l l o r t n o C 4 1 2 - G d r a o B - B C P
1 4 1 2 - G y l p p u S r e w o P 1 0 - 7 0 0 1 4 0 5
t n e m r a p e d r o s s e r p m o c r e v o C 2 0 - 3 2 0 1 3 0 5
s y e k f o t e S . l c n i k c o l r o o D 1 0 - 6 0 0 1 5 0 5
l a r i p s r e s n e d n o C 1 0 - 3 0 0 4 7 0 5
Main Lead
e l d n a H r o o D 1 0 - 8 0 0 1 5 0 5
1 t e k s a G r o o D 1 0 - 4 1 0 2 5 0 5
5074006-01
5072000-01
5079000-01
Pipe for water outlet in bottom
Cylinder deposit for refrigerant
Service dryfilter
1
1
Refrigerant 315 g EP88
36
5b. Spare parts list ULUF 890
35
34
15
17
1
14
7 19 38 6 9 8 5 20 10 11 12 13 4 3 36 37 2
22
25
24
21
23
18
16
28 31 27 33 32 29 30
26
37
5b. Spare parts list ULUF 890
Pos. no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
16a
16b
r o t c e n n o c y d o B 7 1
g n i r p s s a G 8 1
19
20
21
22
23
24a
24b
24c
25
26
27
28a
28b
28c
29
30
31
32
33
34
35
36
37
38
-
-
-
-
-
-
-
-
-
-
e r i w l c n i ) c i t e n g a M ( r o s n e s r o o D 1 0 - 5 0 0 9 4 0 5
r e l l o r t n o c r o f e t a l p l a t e M 1 0 - 4 2 0 1 3 0 5
5019003-01 Transformer 230V 50/60 Hz 12 Vac / 4 amp 1
1
1 e m a r F r o f t e k s a G 1 0 - 5 1 0 2 5 0 5
4 1 - 2 G ( r o s s e r p m o C r o f e b o r P C T N 1 0 - 0 1 0 2 4 0 5
4 1 - 2 G ( r e b m a h C r o f e b o r P C T N 1 0 - 1 1 0 2 4 0 5
s y e k f o t e S . l c n i k c o l r o o D 1 0 - 6 0 0 1 5 0 5
5070001-01
5070027-01
Compressor SC21CNX.2 Complete
Start relay 117U7013
1
1
. n o i t c e n n o c d r o b B C P r o f x o B 1 0 - 6 0 0 9 4 0 5
1 ) H A 7 , V 2 1 ( 2 1 - 7 P B y r e t t a B 1 0 - 1 0 0 4 4 0 5
5041006-01
d e d n e m m o c e R t r a P . o n e d o C
1 t e k s a g c i t e n g a M r o o D 1 0 - 4 1 0 2 5 0 5
F U L U s e g n i h f o t e S 1 0 - 5 2 0 1 3 0 5
Body Cabinet
t e k s a g h t i w e t e l p m o C r o o D 1 0 - 1 0 0 2 5 0 5
Valve heater
. s c p 2 , e k a r b h t i w l e v i w s r o t s a c t n o r F 1 0 - 7 0 0 3 5 0 5
. s c p 1 f l e h S 1 0 - 1 1 0 0 6 0 5
e v l a v m u c a V 1 0 - 7 0 0 4 7 0 5
Door Hinge, Lower subdoor
r o o d b u s r e p p U , m m 0 7 4 * 0 6 2 r o o d b u S 1 0 - 6 1 0 2 5 0 5
. c s p 2 , e k a r b t u o h t i w l e v i w s r o t s a c k c a B 1 0 - 6 0 0 3 5 0 5
Door Hinge, Upper subdoor
F U L U r e g n a h c x e t a e H 1 0 - 5 0 0 4 7 0 5
Front Panel Hinge
r o o d b u s r e w o L , m m 0 7 4 * 0 3 3 r o o d b u S 1 0 - 7 1 0 2 5 0 5
1 ) 0 0 0 1 T P ( e b o r P 1 0 - 3 0 0 2 4 0 5
t r o p p u s r e w o l l e n a p t n o r F 1 0 - 6 2 0 1 3 0 5
t r o p p u s r e p p u l e n a p t n o r F 1 0 - 7 2 0 1 3 0 5
r o t a r o p a v E 1 0 - 1 0 0 3 7 0 5
e r i w l c n i ) c i t e n g a M ( r o s n e s r o o D 1 0 - 5 0 0 9 4 0 5
Hidden Latch
r o o d b u S r o f h c t a l c i t e n g a M 1 0 - 3 1 0 1 3 0 5
l e n a p t n o r F 1 0 - 9 4 0 0 5 0 5
s t h g i l t o p s r o f e r i W 1 0 - 6 0 0 9 1 0 5
1 4 1 2 - G y a l p s i D 1 0 - 7 0 0 3 4 0 5
1 . c s p 4 s b l u b s t h g i l t o p S 1 0 - 4 0 0 9 1 0 5
s p l u b s t h g i l t o p s r o f r e d l o H 1 0 - 2 1 0 0 5 0 5
1 e d a l b n a f . l c n i n a f r e s n e d n o C 1 0 - 7 0 0 0 1 0 5
1 2 1 0 5 U 7 1 1 r o t i c a p a c g n i t r a t S 1 0 - 4 3 0 0 7 0 5
r e s n e d n o C 1 0 - 2 0 0 1 7 0 5
1 r e l l o r t n o C 4 1 2 - G d r a o B - B C P
1 4 1 2 - G y l p p u S r e w o P 1 0 - 7 0 0 1 4 0 5
t n e m r a p e d r o s s e r p m o c r e v o C 2 0 - 3 2 0 1 3 0 5
Latch
l a r i p s r e s n e d n o C 1 0 - 3 0 0 4 7 0 5
Main Lead
e l d n a H r o o D 1 0 - 8 0 0 1 5 0 5
1 t e k s a G r o o D 1 0 - 4 1 0 2 5 0 5
5074006-01
5072000-01
5079000-01
Pipe for water outlet in bottom
Cylinder deposit for refrigerant
Service dryfilter
1
1
Refrigerant EP88
38
5b. Spare parts list ULUF 750
35
34
15
14
1
7 19 19 38 9 6 5 20 13 12 11 36 3 2 4
10
25
22
24
21
28 27 31 33
16 18
32
29
30
17 22
26
37 8
39
5b. Spare parts list ULUF 750
Pos. no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24a
24b
24c
25
26
27a
27b
28a
28b
28c
29
30
31
32
33
34
35
36
37
38
-
-
-
-
-
-
-
-
-
-
e r i w l c n i ) c i t e n g a M ( r o s n e s r o o D 1 0 - 5 0 0 9 4 0 5
r e l l o r t n o c r o f e t a l p l a t e M 1 0 - 4 2 0 1 3 0 5
5019003-01 Transformer 230V 50/60 Hz 12 Vac / 4 amp 1
1
1 0 5 7 F U L U e m a r F r o f t e k s a G 1 0 - 5 6 0 2 5 0 5
4 1 - 2 G ( r o s s e r p m o C r o f e b o r P C T N 1 0 - 0 1 0 2 4 0 5
4 1 - 2 G ( r e b m a h C r o f e b o r P C T N 1 0 - 1 1 0 2 4 0 5
5070001-01
5070027-01
Compressor SC21CNX.2 Complete
Start relay 117U7013
1
1
. n o i t c e n n o c d r o b B C P r o f x o B 1 0 - 6 0 0 9 4 0 5
1 ) H A 7 , V 2 1 ( 2 1 - 7 P B y r e t t a B 1 0 - 1 0 0 4 4 0 5
5041006-01
d e d n e m m o c e R t r a P . o n e d o C
1 0 5 7 F U L U t e k s a g c i t e n g a M r o o D
F U L U s e g n i h f o t e S 1 0 - 5 2 0 1 3 0 5
Body Cabinet
0 5 7 F U L U t e k s a g h t i w e t e l p m o C r o o D 1 0 - 3 6 0 2 5 0 5
Valve heater
. s c p 2 , e k a r b h t i w l e v i w s r o t s a c t n o r F 1 0 - 7 0 0 3 5 0 5
0 5 7 F U L U . s c p 1 f l e h S 1 0 - 0 2 0 0 6 0 5
e v l a v m u c a V 1 0 - 7 0 0 4 7 0 5
Door Hinge, Lower subdoor
r o o d b u s r e p p U , 0 5 7 F U L U r o o d b u S 1 0 - 6 6 0 2 5 0 5
. c s p 2 , e k a r b t u o h t i w l e v i w s r o t s a c k c a B 1 0 - 6 0 0 3 5 0 5
Door Hinge, Upper subdoor
0 5 7 F U L U r e g n a h c x e t a e H 1 0 - 9 0 0 4 7 0 5
Front Panel Sleeve
r o o d b u s r e w o L , 0 5 7 F U L U r o o d b u S 1 0 - 7 6 0 2 5 0 5
1 ) 0 0 0 1 T P ( e b o r P 1 0 - 3 0 0 2 4 0 5
t r o p p u s r e w o l l e n a p t n o r F 1 0 - 6 2 0 1 3 0 5
t r o p p u s r e p p u l e n a p t n o r F 1 0 - 7 2 0 1 3 0 5
5073003-01 Evaporator
e r i w l c n i ) c i t e n g a M ( r o s n e s r o o D 1 0 - 5 0 0 9 4 0 5
Hidden Latch
r o o d b u S r o f h c t a l c i t e n g a M 1 0 - 3 1 0 1 3 0 5
0 5 7 F U L U l e n a p t n o r F 1 0 - 0 5 0 0 5 0 5
s t h g i l t o p s r o f e r i W 1 0 - 6 0 0 9 1 0 5
1 4 1 2 - G y a l p s i D 1 0 - 7 0 0 3 4 0 5
1 . c s p 2 s b l u b s t h g i l t o p S 1 0 - 4 0 0 9 1 0 5
s p l u b s t h g i l t o p s r o f r e d l o H 1 0 - 2 1 0 0 5 0 5
1 e d a l b n a f . l c n i n a f r e s n e d n o C 1 0 - 7 0 0 0 1 0 5
1 2 1 0 5 U 7 1 1 r o t i c a p a c g n i t r a t S 1 0 - 4 3 0 0 7 0 5
Front Panel Bush
r e s n e d n o C 1 0 - 2 0 0 1 7 0 5
1 r e l l o r t n o C 4 1 2 - G d r a o B - B C P
1 4 1 2 - G y l p p u S r e w o P 1 0 - 7 0 0 1 4 0 5
0 5 7 F U L U t n e m r a p e d r o s s e r p m o c r e v o C 1 0 - 4 5 0 1 3 0 5
s y e k f o t e S . l c n i k c o l r o o D 1 0 - 6 0 0 1 5 0 5
l a r i p s r e s n e d n o C 1 0 - 3 0 0 4 7 0 5
Main Lead
e l d n a H r o o D 1 0 - 8 0 0 1 5 0 5
1 0 5 7 F U L U t e k s a G r o o D 1 0 - 4 6 0 2 5 0 5
5074006-01
5072000-01
5079000-01
Pipe for water outlet in bottom
Cylinder deposit for refrigerant
Service dryfilter
1
1
Refrigerant EP88
40
5c. Compressor data ULUF 450/850/490/890/750
2 / 1 2 0 . 1 F . 0 4 5 . D E . C H E D 6 0 0 2 r e b m e t p e S
SC21CNX.2
LBP Compressor
R290
220-240V 50Hz
General
6 6 1 8 H 4 0 1 r e b m u n e d o C
4 3 - 2 - 5 3 3 0 6 N E s l a v o r p p A
0 8 t e l l a p n o s r o s s e r p m o C
Application
P B L n o i t a c i l p p A
0 6 0 5 z H y c n e u q e r F
0 1 - o t 0 4 - C e r u t a r e p m e t g n i t a r o p a v E
4 5 2 - 8 9 1 V e g n a r e g a t l o V
Max. condensing temperature continuous (short) C 50 (60)
Max. winding temperature continuous (short) C 125 (135)
Cooling requirements
0 6 0 5 z H y c n e u q e r F
Application LBP MBP HBP LBP MBP HBP
F C 2 3
2
F C 8 3
2
F C 3 4
2
Remarks on application:
Motor
R I S C e p y t r o t o M
LRA (rated after 4 sec. UL984), HST | LST A 23.5
5 . 3 2 A T S L | T S H , t n e r r u C n i t u C
Resistance, main | start winding (25C) 3.3 14.0
Design
m c t n e m e c a l p s i D
3
20.95
m c ) e p y t ( y t i t n a u q l i O
3
600 (polyolester)
0 5 1 g e g r a h c t n a r e g i r f e r m u m i x a M
m c r o s s e r p m o c n i e m u l o v s a g e e r F
3
1410
Weight without electrical equipment kg 13.1
Dimensions
9 1 2 A m m t h g i e H
B 213
B1 193
B2 110
Suction connector location/I.D. mm | angle C 10.2 | 37
material | comment Cu-plated steel | Al caps
Process connector location/I.D. mm | angle D 6.2 | 37
material | comment Cu-plated steel | Al caps
Discharge connector location/I.D. mm | angle E 6.2 | 37
material | comment Cu-plated steel | Al caps
Oil cooler connector location/I.D. mm | angle F
material | comment
9 0 . 0 m m . D . I e c n a r e l o t r o t c e n n o C
Remarks:
104H
8166
SC21CNX.2
8
5
8
4
-
4
DANFOSS COMPRESSORS
Barcode on
white background
Yellow background
Red stripe
Application
Approvals
R290
B A
255
D C
E
16
19
1
5
1
8258 107
115
5
5
6
3
37 37
107
5
5
170
178
204
165
186
7
0
1
5
0
3
5
1
0
1
.
6
1
2
7
127
B2
B1
6
3
3
9.7
218
O = Oil cooling
F
1
= Fan cooling 1.5 m/s
(compressor compartment temperature
equal to ambient temperature)
F
2
= Fan cooling 3.0 m/s necessary
= not applicable in this area
3
-
2
2
1
8
R290
Yellow warning label
41
6 0 0 2 r e b m e t p e S 2 0 . 1 F . 0 4 5 . D E . C H E D 2 / 2
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already
ed.
All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
8222
b
d
a2
c
10
11
13 12
14
c
Main winding
Start winding
Winding protector
CSIR
Accessories for SC21CNX.2 Figure Code number Test conditions EN 12900/CECOMAF(*) ASHRAE LBP(*)
PTC starting device 6.3 mm spade connectors