Twa Twe
Twa Twe
Twa Twe
Pumps
Split System Heat Pumps
7 1/2 - 20 Tons - 60 Hz
Air Handlers
5 - 20 Tons - 60 Hz
August 2005
SSP-PRC001-EN
Introduction
Filters
The 5, 7 and 10 ton air handlers are
supplied with 1" throwaway filters as
standard. The filter racks were
designed to easily convert for installation of 2" filters. The 15 and 20 ton air
handlers have 2" filters as standard.
UL Listed and ARI Certified
Trane meets or exceeds all nationally
recognized agency safety and design
standards. Each condensing unit is UL
designed, approved and labeled in accordance to UL Standards: UL 1995 for
central cooling air conditioners, refrigeration and air conditioning condensing and compressor units. Each air
handler is designed, approved and labeled in accordance to UL 465 and UL
1995 standard for heat pumps. Each
unit is certified in accordance with ARI
Standard 340/360.
SSP-PRC001-EN
Table of Contents
Introduction
Application Considerations
Selection Procedures
General Data
Performance Data
SSP-PRC001-EN
9
11
11
Fan Performance
21
Controls
30
Electrical Power
31
Dimensional Data
41
Mechanical Specifications
55
Features and
Benefits
Dual compressors are not just for protection, they also save energy costs.
Most buildings are designed for the
peak load requirements yet the building usually operates at less than peak
load. During light load conditions,
only one compressor functions to
maintain the space comfort thus
reducing the need for energy. For
instance, the EER of the 15 ton unit at
ARI conditions is 10.1 and at part load
conditions it is 11.6.
Anti-Short-Cycle Kit
SSP-PRC001-EN
Features and
Benefits
Odyssey air handler versatility is further increased by a complete line of
accessories designed to match and
install smoothly:
Discharge Plenum and Grille
Return Grille
Subbase
Electric Heaters
High Static Evaporator Motor
Isolators both Rubber-in-Shear and
Spring Type
Odyssey Lowers
Installation Costs
Your installation costs are reduced
with Odyssey. Both outdoor units and
air handlers are factory packaged and
assembled so jobsite installation is
quick and easy. You get a complete
unit with all the components, controls
and the internal wiring factory ready
for a smooth jobsite start-up.
Unlike some competitive models the
following components are factoryinstalled in Trane air handlers:
Outdoor Thermostat
Transformer
Contactor
Fan relay
Application
Considerations
Application of this product should be
within the catalogued airflow and performance considerations.
Clearance Requirements
The recommended clearances identified with unit dimensions should be
maintained to assure adequate serviceability, maximum capacity and
peak operating efficiency. Actual
clearances which appear inadequate
should be reviewed with the local
Trane Representative.
180 Blower Rotation
The 5, 7, and 10 ton air handler blower section can be rotated 180 to
change the discharge pattern. This
modification must be done in the field
and requires an addition of kit. See
unit installer's guide.
Low Ambient
Cooling
As manufactured, these units
can operate to
50 F in the cooling mode of operation. An
accessory head
pressure control
will allow operation to 0 F outdoor ambient. When
using these units with
control systems such
as bypass changeover
Variable Air Volume,
make sure you consider the
requirement for a head pressure control to allow low ambient
cooling.
Selection
Procedure
Cooling Capacity
Step 1 Calculate the buildings total
and sensible cooling loads at design
conditions.
Step 2 Size the equipment using
Table PD-1. Match the cooling loads at
design conditions.
Example: The following are the building cooling requirements:
a. Electrical Characteristics: 460/60/3
b. Summer Design Conditions:
Entering Evaporator Coil:
80 F DB/67 F WB
Outdoor Ambient: 95 F
Total Cooling Load: 90 MBh
d. Sensible Cooling Load: 64 MBh
e. Airflow: 3000 cfm
External Static Pressure:
0.77 inches of water gauge
Table PD-1 shows that TWA090A4
with TWE090A has a gross cooling capacity of 91.1 MBh and 65.9 MBh sensible capacity at 95 F DB ambient and
3000 cfm with 80 F DB/67 F WB air
entering the evaporator.
To find the net cooling capacities, fan
motor heat must be subtracted. Determine the total unit static pressure:
External Static0.77 in.
Standard Filter 1 in.0.10 in.
Supplementary Electric Heat 0.23 in.
Total Static Pressure1.10 in.
Note: The Evaporator Fan Performance Table has included the effect of
a 1 in. filter already. Therefore, the actual Total Static Pressure is
1.10 - 0.10 = 1.00 in. With 3000 cfm and
1.00 inches, Table PD-19 shows a 1.17
Bhp.
Note: The formula below the table can
be used to calculate Fan Motor Heat:
3.5 X Bhp = MBh
3.5 X 1.17 = 4.09 MBh
Net Total Cooling Capacity =
91.1 MBh - 4.09 = 87.01 MBh
Net Sensible Cooling Capacity =
65.9 MBh - 4.09 = 61.81 MBh
SSP-PRC001-EN
Heating Capacity
Step 1 Calculate the building heating load using the Trane calculation
form or any other standard accepted
method.
Step 2 Size the equipment using
Table PD-13 to match the heating
loads at design conditions. The following are building heating requirements:
a. Total Heating Load: 95.0 MBh
b. Outdoor Ambient (Winter): 17 F DB
c. Indoor Return Temperature: 70 F
DB
d. Airflow: 3000 cfm
Table PD-13 indicates the mechanical
heating portion of the heat pump will
provide 54.8 MBh for the winter design
conditions.
Step 3 Because 54.8 MBh is less
than the buildings required heating
capacity, a supplementary heater
must be selected. 95.0 - 54.8 = 40.2
MBh minimum heater capacity.
From Table PD-36, the 14.96 kW heater
has a capacity of 51,058 Btuh. From
Table ED-5, the 14.96 kW heater at
460V indicates the heater model number is BAYHTRL415A. This heater will
be adequate to cover the residual heat
capacity needed for the application.
Air Delivery Selection
External static pressure drop through
the air distribution system has been
calculated to be 0.77 inches of water
gauge. From Table PD-35 static pressure drop through the electric heater is
0.12 inches of water (0.77 + 0.12 = .89
in.) Enter Table PD-19 for TWE090A4 at
3000 cfm and .90 static pressure. The
standard motor at 790 RPM will give
the desired airflow.
Model Number
Description
Split System Heat Pump Model Nomenclature
TWA
090
1 2
4 5 6
10
11
12
Digits 8 - Electrical
Characteristics
1 = 208-230/60/1
3 = 208-230/60/3
4 = 460/60/3
W = 575/60/3
TWE 090
1 2
4 5 6
0 0
11
12
10
Digits 8 - Electrical
Characteristics
1 = 208-230/60/1
3 = 208-230/60/3
4 = 460/60/3
W = 575/60/3
Digits 9,10 - Factory Installed
Options
00 = Packed Stock
Digits 11 - Minor Design Sequence
C = Third
Digits 12 - Service Digit
A = First
SSP-PRC001-EN
General
Data
Table GD-1: General Data Heat Pumps
Cooling Performance1
Gross Cooling Capacity
Matched Air Handler
Matched Heat Pump Only2
ARI Net Cooling Capacity3
EER4
Matched Air Handler
Heat Pump Only
Integrated Part Load Value5
System/Condensing Unit Power (kW)
Heating Performance
ARI Heating and Matched Air Handler
High Temperature Capacity
System kW/COP
Low Temperature Capacity
System kW/COP
Compressor
No./Type
No. Motors/HP
Motor RPM
Sound Rating (BELS)6
System Data7
No. Refrigerant Circuits
Suction Line (in.) OD
Liquid Line (in.) OD
Outdoor Coil - Type
Tube Size (in.) OD
Face Area (sq ft)
Rows/FPI
Refrigerant Control
Outdoor Fan - Type
No. Used/Diameter (in.)
Drive Type/No. Speeds
CFM
No. Motor/HP
Motor RPM
Refrigerant Charge (Field Supplied)
(lbs of R-22)8
7 1/2 Ton
Single Compressor
TWA090A3,A4,AW
10 Ton
Single Compressor
TWA120A3,A4,AW
15 Ton
Dual Compressor
TWA180B3,B4,BW
20 Ton
Dual Compressor
TWA240B3,B4,BW
91,000
91,000
89,000
124,000
124,000
120,000
182,000
182,000
176,000
240,000
240,000
234,000
10.1
11.5
8.70/7.95
10.1
11.1
11.91/11.07
9.9
10.9
11.0
17.77/16.62
9.3
10.3
10.5
24.99/23.20
87,000
7.68/3.3
55,000
6.73/2.4
122,000
10.82/3.2
80,000
9.62/2.4
168,000
16.10/3.1
106,000
14.16/2.2
234,000
22.42/3.1
154,000
19.54/2.30
1
1 3/8
1/2
Plate Fin
.375
19.2
2/18
Expansion Valve
Propeller
1/26
Direct/1
5890
1/.50
1100
1
1 3/8
1/2
Plate Fin
.375
29.5
2/18
Expansion Valve
Propeller
1/28
Direct/1
8200
1/1.00
1100
2
1 3/8
1/2
Plate Fin
.375
38.5
2/18
Expansion Valve
Propeller
2/26
Direct/1
11,780
2/.50
1100
2
1 3/8
1/2
Plate Fin
.375
50.2
2/18
Expansion Valve
Propeller
2/28
Direct1
16,240
2/1.00
1100
18.00
31.50
36.00
48.50
Notes:
1 Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor
heat. ARI capacity is net and includes the effect of fan motor heat. Certified in accordance with the Unitary Large Equipment certification program, which is
based on ARI Standard 340/360-00.
2 Condensing unit only gross cooling capacity rated at 45 F saturated suction temperature and at 95 F ambient.
3 ARI net cooling capacity is calculated with matched blower coil and 25 feet of 1 3/8" or 1/2" OD interconnecting tubing.
4 EER is rated at ARI conditions and in accordance with DOE test procedures.
5 Integrated part load value is based on ARI Standard 340/360-00. Units are rated at 80 F ambient, 80 F entering dry bulb (DB), and 67 F entering wet bulb
(WB) at ARI rated cfm.
6 Sound rating shown is tested in accordance with ARI Standard 270 or 370.
7 Refer to refrigerant piping applications manual for line sizing and line length.
8 Refrigerant (operating) charge is for condensing unit (all circuits) with matching blower coils and 25 feet of interconnecting refrigerant lines. All units are
supplied with a small nitrogen holding charge only.
SSP-PRC001-EN
General
Data
Table GD-2: General Data Air Handlers
5 Ton
7 1/2 Ton
Dual Circuit
Single Circuit
Dual Circuit
Single Circuit
1
TWE090B1,B3
TWE060A1,A3,A4,AW TWE060B1,B3,B4 TWE090A1,A3 ,AW
System Data
No. Refrigerant Circuits
Suction Line (in.) OD
Liquid Line (in.) OD
Indoor Coil -Type
Tube Size (in.)
Face Area (sq. ft.)
Rows/FPI
Refrigerant Control
Drain Connection Size (in.)
Indoor Fan - Type
No. Used/Diameter x Width (in.)
Drive Type/No. Speeds
CFM
No. Motors
Motor HP - Standard/Oversized
Motor RPM
Motor Frame Size
Filters - Type/Furnished
(No.)/Size Recommended
1
1 1/8
3/8
Plate Fin
.375
5.0
3/12
Expansion Valve
1 PVC
Centrifugal
1/12 x 12
Belt/Adjustable
2000
1
.75/1.00
1725
56
Throwaway/Yes
(1) 16 x 20 x 1
(1) 20 x 20 x 1
2
3/4
5/16
Plate Fin
.375
5.0
3/12
Expansion Valve
1 PVC
Centrifugal
1/12 x 12
Belt/Adjustable
2000
1
.75/1.00
1725
56
Throwaway/Yes
(1) 16 x 20 x 1
(1) 20 x 20 x 1
1
1 3/8
1/2
Plate Fin
.375
8.1
3/12
Expansion Valve
1 PVC
Centrifugal
1/15 x 15
Belt/Adjustable
3000
1
1.50/2.00
1725
56H
Throwaway/Yes
(3) 16 x 25 x 1
2
1 1/8
3/8
Plate Fin
.375
8.1
3/12
Expansion Valve
1 PVC
Centrifugal
1/15 x 15
Belt/Adjustable
3000
1
1.50/2.00
1725
56H
Throwaway/Yes
(3) 16 x 25 x 1
10 Ton
Single Circuit
Single Circuit
TWE0120A1
TWE120A31,AW
1
1
1 3/8
1 3/8
1/2
1/2
Plate Fin
Plate Fin
.375
.375
11.2
11.2
4/12
4/12
Expansion Valve Expansion Valve
1 PVC
1 PVC
Centrifugal
Centrifugal
1/15 x 15
1/15 x 15
Belt/Adjustable Belt/Adjustable
4000
4000
1
1
2.00/3.00
2.00/3.00
1725
1725
56HZ
56HZ
Throwaway/Yes Throwaway/Yes
(4) 16 x 25 x 1
(4) 16 x 25 x 1
ARI tested and certified with various heat pumps per ARI Standard 340/360-00 certification program. Refer to performance data section in this catalog.
Notes:
1 Ships wired for 208-230/60/3. Field convertible to 460/60/3.
2 TWE060A1 has motor RPM of 3450 for oversized motor.
3 TWE120A1 does not have an oversized motor option.
Table GD-2: General Data Air Handlers (continued)
10 Ton
Dual Circuit
Dual Circuit
TWE120B1
TWE120B31,BW
System Data
No. Refrigerant Circuits
2
2
Suction Line (in.) OD
1 1/8
1 1/8
Liquid Line (in.) OD
3/8
3/8
Indoor Coil -Type
Plate Fin
Plate Fin
Tube Size (in.)
.375
.375
Face Area (sq. ft.)
11.2
11.2
Rows/FPI
4/12
4/12
Refrigerant Control
Expansion Valve
Expansion Valve
Drain Connection Size (in.)
1 PVC
1 PVC
Indoor Fan - Type
Centrifugal
Centrifugal
No. Used/Diameter x Width (in.)
1/15 x 15
1/15 x 15
Drive Type/No. Speeds
Belt/Adjustable
Belt/Adjustable
CFM
4000
4000
No. Motors
1
1
Motor HP - Standard/Oversized
2.00/2.00/3.00
Motor RPM
1725
1725
Motor Frame Size
56HZ
56HZ
Filters - Type/Furnished
Throwaway/Yes
Throwaway/Yes
(No.)/Size Recommended
(4) 16 x 25 x 1
(4) 16 x 25 x 1
15 Ton
Dual Circuit
TWE180B3,B4,BW
20 Ton
Dual Circuit
TWE240B3,B4,BW
2
1 3/8
1/2
Plate Fin
.375
16.3
3/12
Expansion Valve
1 PVC
Centrifugal
2/15 x 15
Belt/Adjustable
6000
1
3.00/5.00
1735/1750
145T
Throwaway/Yes
(8) 15 x 20 x 2
2
1 3/8
1/2
Plate Fin
.375
21.6
3/12
Expansion Valve
1 PVC
Centrifugal
2/15 x 15
Belt/Adjustable
8000
1
5.00/7.50
1750/3470
184T
Throwaway/Yes
(4) 16 x 25 x 2
(4) 16 x 20 x 2
ARI tested and certified with various heat pumps per ARI Standard 340/360-00 certification program. Refer to performance data section in this catalog.
Notes:
1 Ships wired for 208-230/60/3. Field convertible to 460/60/3.
10
SSP-PRC001-EN
Performance Data
7 1/2, 10 Tons
Table PD-1: Gross Cooling Capacities (MBh) 7 1/2 Ton TWA090A Heat Pump with 7 1/2 Ton TWE090A Air Handler
Ambient Temperature
CFM
Airflow
2700
3000
3300
3600
Enter.
DB
( F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
85
61
MBH SHC
84.1 67.2
84.6 78.6
86.9 86.9
91.2 91.2
87.5 70.3
86.5 82.9
89.6 89.6
94.1 94.1
87.0 73.3
88.1 87.0
92.0 92.0
96.6 96.6
88.2 76.1
89.3 89.3
94.1 94.1
98.9 98.9
67
MBH SHC
92.8 56.3
93.0 64.5
93.1 75.8
93.7 87.3
94.4 54.8
94.6 67.5
94.7 79.7
95.7 92.4
95.7 56.6
95.8 70.1
96.1 83.4
97.5 97.2
96.8 58.3
96.9 72.7
97.4 87.0
98.9 98.9
95
73
61
MBH SHC MBH SHC
102.1 37.7 81.2 65.7
102.1 49.6 81.8 77.2
102.2 61.3 84.4 84.4
102.3 72.9 88.7 88.7
103.7 38.4 82.7 68.8
103.7 51.2 83.6 81.4
103.8 64.0 87.1 87.1
92.4 103.9 76.4 91.5
104.9 39.0 83.9 71.7
105.0 52.8 84.7 84.7
105.1 66.5 89.3 89.3
105.2 79.9 93.9 93.9
106.0 39.5 85.0 74.6
106.1 54.2 86.6 86.6
106.2 69.0 91.3 91.3
106.4 83.2 96.0 96.0
67
MBH SHC
89.5 55.0
89.8 63.2
89.9 74.4
90.6 85.9
91.1 53.4
91.1 65.9
91.4 78.3
92.5 91.0
92.3 55.2
92.4 68.6
92.8 82.0
93.9 93.9
93.3 56.9
93.4 71.2
94.0 85.6
96.1 96.1
105
Entering WB
73
61
MBH SHC MBH SHC
98.5 36.4 78.0 64.2
98.5 48.3 78.8 75.7
98.7 60.0 81.7 81.7
98.7 71.5 86.0 86.0
100.0 37.1 79.4 67.2
100.0 499 80.5 79.9
100.2 62.6 84.3 84.3
100.3 75.0 88.6 88.6
101.2 37.6 80.6 70.1
101.2 51.4 81.9 81.9
101.4 65.2 86.4 86.4
101.5 78.5 90.9 90.9
102.2 38.1 81.6 73.0
102.3 52.9 83.7 83.7
102.5 67.6 88.3 88.3
102.6 81.8 92.9 92.9
67
MBH SHC
86.1 53.6
86.3. 61.7
86.4 72.9
87.3 84.5
87.5 51.9
87.6 64.4
87.9 76.7
88.7 88.7
88.6 53.7
88.8 67.0
89.2 80.4
91.0 91.9
89.6 55.4
89.8 69.6
90.4 84.0
93.0 93.0
115
73
MBH SHC
94.8 35.2
94.8 46.9
95.0 58.6
95.1 70.0
96.1 35.7
96.2 48.5
96.4 61.3
96.5 73.6
97.3 36.2
97.4 50.0
97.6 63.8
97.7 77.0
98.2 36.7
98.3 51.5
98.4 66.1
98.7 80.3
61
MBH SHC
74.7 62.5
75.6 74.1
78.9 78.9
83.1 83.1
75.9 65.6
77.0 77.0
81.3 81.3
85.6 85.6
77.1 68.5
78.9 78.9
83.3 83.3
87.8 87.8
78.1 71.3
80.6 80.6
85.1 85.1
89.7 89.7
67
MBH SHC
82.4 52.1
82.6 60.0
82.9 71.3
84.0 83.0
83.7 50.4
83.9 62.8
84.3 75.2
85.7 85.7
84.8 52.2
85.0 65.4
85.6 78.9
87.9 87.9
85.7 53.9
85.9 68.0
86.7 82.5
89.8 89.8
73
MBH SHC
90.9 33.8
91.0 45.5
91.1 57.2
91.3 68.5
92.2 34.3
92.3 47.1
92.5 59.9
92.6 72.1
93.3 34.8
93.4 48.6
93.6 62.4
93.7 75.5
94.1 35.3
94.3 50.1
94.4 64.6
94.8 78.8
Notes:
1 Dry coil condition. Total gross capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All temperatures are in F.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities, subtract indoor fan heat.
MBH = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-2: Gross Cooling Capacities (MBh) 10 Ton TWA120A Heat Pump with 10 Ton TWE120A Air Handler
Ambient Temperature
CFM
Airflow
3600
4000
4400
4800
Enter.
DB
( F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
85
95
105
115
Entering WB
61
67
73
61
67
73
61
67
73
61
67
73
MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
114.6 90.1 126.2 76.3 138.8 51.1 110.6 88.1 121.8 74.5 134.0 49.4 106.2 85.9 117.1 72.6 128.9 47.7 101.7 83.6 112.2 70.6 123.4 45.8
115.0 104.8 126.4 85.8 138.8 66.4 111.1 102.8 122.0 83.9 134.0 64.6 106.9 100.7 117.3 81.9 128.9 62.6 102.6 98.5 112.4 79.8 123.5 60.6
117.1 117.1 126.5 100.7 138.8 81.2 113.7 113.7 122.0 98.6 134.0 79.3 110.1 110.1 117.4 96.5 129.0 77.4 106.3 106.3 112.5 94.3 123.6 75.3
122.7 122.7 126.9 115.2 138.9 95.9 119.2 119.2 122.7 113.2 134.2 94.0 115.5 115.5 118.2 111.1 129.1 92.1 111.7 111.7 113.5 109.0 123.7 90.0
116.7 94.0 128.5 73.3 114.1 52.1 112.5 91.9 123.9 71.4 136.1 50.4 108.1 86.7 119.1 69.3 130.8 48.5 103.5 87.5 114.0 67.2 125.2 46.5
117.5 110.2 128.6 89.5 141.1 68.5 113.4 108.1 124.0 87.6 136.1 66.6 109.2 106.0 119.2 85.5 130.8 64.6 104.9 103.8 114.2 83.4 125.3 62.6
120.7 120.7 128.6 105.4 141.1 84.5 117.1 117.1 124.1 103.4 136.2 82.6 113.4 113.4 119.3 101.2 131.0 80.7 109.5 109.5 114.4 99.0 125.4 78.6
126.6 126.6 129.5 121.4 141.2 100.5 122.9 122.9 125.2 119.4 136.3 98.6 119.1 119.1 120.7 117.3 131.1 96.6 115.0 115.0 115.9 115.2 125.5 94.5
118.5 97.7 130.3 75.5 142.9 53.0 114.2 95.6 125.6 73.6 137.8 51.1 109.6 93.4 120.7 71.6 132.4 49.2 105.0 91.1 115.5 69.4 126.7 47.1
119.7 115.3 130.4 93.0 142.9 70.4 115.6 113.2 125.8 91.0 137.8 68.5 11.3 111.1 120.8 89.0 132.5 66.5 106.5 106.5 115.7 86.8 126.8 64.5
123.9 123.9 130.5 110.0 143.0 87.7 120.2 120.2 125.9 107.9 138.0 85.8 116.3 116.3 121.1 105.8 132.6 83.8 112.2 112.2 116.1 103.6 126.9 81.7
129.9 129.9 131.9 127.4 143.1 104.8 126.1 126.1 127.5 125.4 138.1 102.9 122.2 122.2 122.0 122.0 132.7 100.9 117.9 117.9 117.8 117.8 126.9 98.5
120.0 101.3 131.9 77.7 144.5 53.6 115.6 99.1 127.1 75.7 139.4 51.7 111.1 96.9 122.1 73.7 133.8 49.8 106.3 94.7 116.7 71.5 128.0 47.7
121.7 120.2 132.0 96.3 144.5 72.2 116.7 116.7 127.2 94.4 139.3 70.3 112.8 112.8 122.2 92.3 133.9 68.3 108.7 108.7 116.9 89.8 128.0 66.2
126.7 126.7 132.2 114.4 144.6 90.7 122.9 122.9 127.6 112.4 139.5 88.8 118.8 118.8 122.7 110.3 134.0 86.8 114.6 114.6 117.6 108.0 128.2 84.7
132.9 132.9 134.1 133.2 144.7 109.0 129.0 129.0 128.9 128.9 138.5 106.9 124.9 124.9 124.8 124.8 134.1 104.8 120.5 120.5 120.4 120.4 128.2 102.6
Notes:
1 Dry coil condition. Total gross capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All temperatures are in F.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities, subtract indoor fan heat.
MBH = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
SSP-PRC001-EN
11
Performance Data
15, 20 Tons
Table PD-3: Gross Cooling Capacities (MBh) 15 Ton TWA180B Heat Pump with 15 Ton TWE180B Air Handler
Ambient Temperature
CFM
Airflow
Enter.
DB
( F)
5400
75
80
85
90
6000
75
80
85
90
6600
75
80
85
90
75
80
85
90
7200
85
61
67
MBH SHC MBH SHC
167.8 134.1 185.1 112.3
168.7 157 185.4 128.9
173.3 173.31 185.7 151.5
182 182.01 186.8 174.4
95
73
61
67
MBH SHC MBH SHC MBH SHC
203.6 75.2 161.9 131.2 178.6 109.7
203.7 99.1 163 154.1 178.9 126.2
203.9 122.5 168.4 168.41 179.2 148.6
105
Entering WB
73
61
67
MBH SHC MBH SHC MBH SHC
196.4 72.7 155.5 128 171.6 106.9
196.5 96.4 156.9 151.1 171.8 122.9
196.8 119.8 163 163.01 172.3 145.5
197 142.7 171.4 171.41 174 168.7
115
73
MBH SHC
188.9 70.1
189.1 93.7
189.4 117.1
61
67
MBH SHC MBH SHC
148.8 124.7 164.3 104
150.4 147.9 164.6 119.8
157.3 157.31 165.1 142.4
189.6 139.8 165.7 165.71 167.2 165.6
73
MBH SHC
181.1 67.5
181.4 90.8
181.8 114.3
Notes:
1 Dry coil condition. Total gross capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All temperatures are in F.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities, subtract indoor fan heat.
MBH = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-4: Gross Cooling Capacities (MBh) 20 Ton TWA240B Heat Pump with 20 Ton TWE240B Air Handler
Ambient Temperature
Enter.
CFM
DB
Airflow
( F)
7200
8000
8800
9600
85
95
90
75
80
61
67
MBH SHC MBH SHC
223.8 177.3 246 148.8
224.8 206.8 246.2 169
229.6 229.61 246.4 198.1
240.5 240.51 247.6 227.3
227.8 185.1 250.2 143.9
229.4 217.4 250.4 176.3
73
61
67
MBH SHC MBH SHC MBH SHC
269.9 99.5 215.5 173.1 237 145.1
269.9 130 216.8 202.6 237.3 165.1
270 159.6 222.6 222.61 237.5 194
270.3 189 233.4 233.41 238.9 223.2
274.2 101.4 219.3 180.8 240.9 139.9
274.1 134 221.2 213.2 241.2 172.4
85
90
75
80
203.5
235.6
144.4
178.8
85
90
75
80
85
90
212.7
247.6
148.6
185.2
221.6
75
80
85
207.6
239.7
148.3
183.3
251.81
105
Entering WB
73
61
67
MBH SHC MBH SHC MBH SHC
260.1 96.1 206.9 168.8 227.5 141.3
260.1 126.2 208.5 198.4 227.9 161
260.3 155.8 215.3 215.31 228.1 189.7
260.6 185.2 225.9 225.91 230 219.1
264.1 98 210.4 176.4 231.1 135.9
264.1 130.3 212.8 208.9 231.2 167.9
115
73
61
67
73
MBH SHC MBH SHC MBH SHC MBH SHC
249.8 92.5 198 164.3 217.7 137.3 238.9 88.8
249.8 122.3 199.9 194.1 218.1 156.9 238.9 118.3
250 151.9 207.7 207.71 218.4 185.3 239.2 147.8
250.3 181.3 218 218.01 220.7 214.8 239.3 176.7
253.4 94.1 201.2 171.9 221 131.7 242.2 90
253.4 126.3 203 203.01 221.2 163.5 242.3 122.3
264.3 162.4 221.6 221.61 231.9 199.2 253.7 158.5 213.6 213.61 222 194.8 242.6 154.4
264.4 193.9 232.6 232.61 234.7 231.4 253.8 189.7 224.3 224.31 224.1 224.11 242.8 185.4
267.4 99.3 213.4 183.7 234.1 140.3 256.4 95.3 204 179.2 223.7 136.1 244.9 91.2
267.3 134.1 215.8 215.81 234.3 174.5 256.5 130.1 207.8 207.81 224 170.1 245 126
267.6 168.7 227.1 227.11 235.2 208.4 256.8 164.7 218.8 218.81 225.1 204 245.4 160.6
267.8 202.3 238.4 238.41 238.2 238.21 257 198.1 229.8 229.81 229.6 229.61 245.6 193.7
270.1 100.5 216 190.8 236.7 144.5 258.9 96.5 206.6 186.2 226.1 140.3 247.2 92.4
270.1 137.7 220.3 220.31 236.9 180.9 259 133.7 212 212.01 226.4 176.4 247.3 129.6
270.5 174.7 231.9 231.91 238.2 217.2 259.4 170.7 223.3 223.31 228 212.8 247.7 166.6
270.7 210.4 243.5 243.51 243.4 243.41 259.6 206.2 234.6 234.61 234.5 234.51 248 201.7
Notes:
1 Dry coil condition. Total gross capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All temperatures are in F.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities, subtract indoor fan heat.
MBH = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
12
SSP-PRC001-EN
Performance Data
7 1/2 Ton
Table PD-5: Gross Cooling Capacities (MBh) 7 1/2 Ton TWA090A Heat Pump Only
Suction Temperature Degrees F
Outdoor
Temperature
30
35
40
45
50
55
In Degrees F
65
Head press PSIG
168
173
179
185
191
197
Cap. Btuh/1000
81
89
97.2
105.8
114.5
123.4
Unit KW
5.56
5.69
5.83
5.97
6.13
6.28
75
Head press PSIG
194
199
205
211
217
224
Cap. Btuh/1000
77.8
85.3
93.1
101.1
109.4
117.8
Unit KW
6.09
6.23
6.38
6.54
6.7
6.87
85
Head press PSIG
221
227
234
240
247
254
Cap. Btuh/1000
74.1
81.3
88.7
96.3
104.2
112.3
Unit KW
6.71
6.87
7.03
7.2
7.38
7.56
95
Head press PSIG
252
258
265
272
279
286
Cap. Btuh/1000
70.3
77.1
84.1
91.4
98.9
106.7
Unit KW
7.43
7.6
7.77
7.95
8.14
8.33
105
Head press PSIG
285
292
299
306
314
322
Cap. Btuh/1000
66.1
72.6
79.3
86.3
93.5
101.1
Unit KW
8.23
8.41
8.6
8.79
8.98
9.18
115
Head press PSIG
321
328
336
343
351
360
Cap. Btuh/1000
61.8
67.9
74.3
81
88.1
95.5
Unit KW
9.12
9.32
9.51
9.71
9.91
10.12
Performance data calculated at 15 F subcooling and 20% superheat and does not include capacity loss
.
due to refrigerant lines.
Table PD-6: Capacity Curves 7 1/2 Ton TWA090A Heat Pump Only
SSP-PRC001-EN
13
Performance Data
10 Ton
Table PD-7: Gross Cooling Capacities (MBh) 10 Ton TWA120A Heat Pump Only
Suction Temperature Degrees F
Outdoor
Temperature
30
35
40
45
50
55
In Degrees F
65
Head press PSIG
167
172
178
183
189
195
Cap. Btuh/1000
110.6
121.1
132.1
143.7
155.9
168.6
Unit KW
7.87
8.04
8.22
8.41
8.61
8.83
75
Head press PSIG
192
197
202
208
214
221
Cap. Btuh/1000
105.4
115.4
126.1
137.3
149.1
161.4
Unit KW
8.56
8.75
8.95
9.16
9.38
9.62
85
Head press PSIG
219
224
230
236
243
250
Cap. Btuh/1000
100
109.6
119.9
130.7
142
153.9
Unit KW
9.38
9.59
9.82
10.05
10.3
10.55
95
Head press PSIG
248
254
260
267
274
281
Cap. Btuh/1000
94.5
103.7
113.5
123.8
134.7
146.1
Unit KW
10.35
10.58
10.82
11.07
11.59
105
Head press PSIG
281
287
293
300
307
315
Cap. Btuh/1000
88.8
97.6
107
116.8
127.1
137.8
Unit KW
11.45
11.7
11.96
12.22
12.48
12.74
115
Head press PSIG
316
322
329
336
343
351
Cap. Btuh/1000
83.1
91.4
100.3
109.6
119.2
129.2
Unit KW
12.69
12.95
13.21
13.48
13.73
13.98
Performance data calculated at 15 F subcooling and 20% superheat and does not include capacity loss
due to refrigerant lines.
14
SSP-PRC001-EN
Performance Data
15 Ton
Table PD-9: Gross Cooling Capacities (MBh) 15 Ton TWA180B Heat Pump Only
Suction Temperature Degrees F
Outdoor
Temperature
30
35
40
45
50
55
In Degrees F
65
Head pressure PSIG
168
173
179
185
191
197
Capacity BTUH/1000
161.3
177.1
193.6
210.6
228.1
245.8
Unit KW
10.9
11.16
11.43
11.71
12.01
12.32
75
Head pressure PSIG
193
199
205
211
217
224
Capacity BTUH/1000
154.9
169.9
185.5
201.5
218
234.8
Unit KW
11.94
12.22
12.51
12.82
13.14
13.47
85
Head pressure PSIG
221
227
233
240
247
254
Capacity BTUH/1000
147.7
162
176.8
192.1
207.8
224
Unit KW
13.16
13.46
13.78
14.11
14.46
14.81
95
Head pressure PSIG
252
258
265
272
279
286
Capacity BTUH/1000
140.1
153.7
167.8
182.4
197.5
213.1
Unit KW
14.56
14.89
15.23
15.59
15.95
16.32
105
Head pressure PSIG
285
292
299
306
313
321
Capacity BTUH/1000
131.9
144.8
158.2
172.2
186.8
202.1
Unit KW
16.14
16.49
16.85
17.23
17.61
18
115
Head pressure PSIG
321
328
335
343
351
360
Capacity BTUH/1000
123.3
135.5
148.3
161.8
176
190.9
Unit KW
17.88
18.25
18.64
19.03
19.43
19.83
Performance data calculated at 15 F subcooling and 20% superheat and does not include capacity loss
due to refrigerant lines.
SSP-PRC001-EN
15
Performance Data
20 Ton
Table PD-11: Gross Cooling Capacities (MBh) 20 Ton TWA240B Heat Pump Only
Suction Temperature Degrees F
Outdoor
Temperature
30
35
40
45
50
55
In Degrees F
65
Head pressure PSIG
183
190
196
203
211
219
Capacity BTUH/1000
217.4
237.4
258.4
280.5
303.5
327.5
Unit KW
16.09
16.51
16.96
17.44
17.96
18.5
75
Head pressure PSIG
209
216
223
231
239
248
Capacity BTUH/1000
206.8
226
246.3
267.6
290
313.3
Unit KW
17.58
18.05
18.56
19.11
19.68
20.28
85
Head pressure PSIG
238
245
253
261
270
279
Capacity BTUH/1000
196
214.4
233.9
254.5
276
298.3
Unit KW
19.35
19.88
20.44
21.03
21.65
22.27
95
Head pressure PSIG
269
277
285
294
303
313
Capacity BTUH/1000
185
202.6
221.3
240.9
261.4
282.6
Unit KW
21.39
21.97
22.57
23.2
23.83
24.47
105
Head pressure PSIG
304
312
320
329
339
349
Capacity BTUH/1000
173.8
190.6
208.4
227.1
246.5
266.5
Unit KW
23.68
24.31
24.95
25.6
26.24
26.87
115
Head pressure PSIG
341
349
358
368
378
388
Capacity BTUH/1000
162.4
178.5
195.4
213
231.2
249.9
Unit KW
26.23
26.89
27.56
28.22
28.86
29.46
Performance data calculated at 15 F subcooling and 20% superheat and does not include capacity loss
due to refrigerant lines.
16
SSP-PRC001-EN
Performance Data
7 1/2 Ton
Table PD-13: Gross Heating Capacities (MBh) 7 1/2 Ton TWA090A Heat Pump with 7 1/2 Ton
TWE090A Air Handler at 3000 CFM
Outdoor
Heating Capacity (BTUH/1000) at
Total Power in Kilowatts at
Temperature in
Indicated Indoor Dry Bulb Temperature Indicated Indoor Dry Bulb Temperature
Degrees F
60
70
75
80
60
70
75
80
-18
35.2
32
30.9
30.1
5.4
5.9
6.2
6.5
-13
36.8
34
33.1
32.5
5.5
6
6.3
6.6
-8
38.7
36.4
35.7
35.2
5.6
6.1
6.4
6.7
-3
41.1
39.2
38.7
38.3
5.7
6.2
6.5
6.8
2
44.1
42.5
42
41.8
5.8
6.3
6.6
6.9
7
47.5
46.3
45.9
45.7
5.9
6.5
6.8
7.1
12
51.3
50.3
50
49.9
6
6.6
6.9
7.2
17
55.6
54.8
54.5
54.3
6.2
6.7
7.1
7.4
22
60.3
59.6
59.3
59.1
6.3
6.9
7.2
7.6
27
65.5
64.7
64.4
64.2
6.4
7
7.4
7.7
32
71
70.2
69.9
69.6
6.6
7.2
7.5
7.9
37
76.7
75.8
75.4
75
6.7
7.4
7.7
8.1
42
82.7
81.7
81.2
80.7
6.9
7.5
7.9
8.3
47
89
87.8
87.3
86.7
7
7.7
8.1
8.5
52
95.7
94.4
93.7
93.1
7.2
7.9
8.3
8.7
57
102.7
101.2
100.5
99.7
7.3
8
8.4
8.9
62
109.9
108.2
107.4
106.6
7.5
8.2
8.6
9.1
67
117.3
115.5
114.6
113.8
7.7
8.4
8.8
9.3
72
124.8
122.9
122
121.1
7.9
8.6
9
9.5
Correction Factors Other Airflows
(Table Value X Correction Factor = Value at New
Airflow)
Airflow
Heating Capacity
Compressor Kw
2625
.99
1.02
3375
x 1.01
x 0.98
SSP-PRC001-EN
17
Performance Data
10 Ton
Table PD-14: Gross Heating Capacities (MBh) 10 Ton TWA120A Heat Pump with 10 Ton
TWE120A Air Handler at 4000 CFM
Outdoor
Heating Capacity (BTUH/1000) at
Total Power in Kilowatts at
Temperature in
Indicated Indoor Dry Bulb Temperature Indicated Indoor Dry Bulb Temperature
Degrees F
60
70
75
80
60
70
75
80
-18
29.9
42.3
46.5
49.9
7.4
8.4
9
9.5
-13
39.4
47.5
50.6
53
7.7
8.6
9.1
9.6
-8
46.9
52.6
54.8
56.7
7.9
8.8
9.2
9.7
-3
53.7
57.8
59.4
60.7
8.1
9
9.4
9.9
2
60.3
63.1
64.2
65
8.3
9.1
9.6
10
7
66.9
68.6
69.2
69.7
8.5
9.3
9.7
10.2
12
73.4
74.3
74.6
74.7
8.7
9.5
9.9
10.3
17
80.2
80.3
80.2
80.2
8.9
9.6
10.1
10.5
22
87.1
86.6
86.3
86
9
9.8
10.2
10.7
27
94.2
93.2
92.6
92.2
9.2
10
10.4
10.9
32
101.7
100.2
99.5
98.9
9.4
10.2
10.6
11.1
37
109.1
107.2
106.4
105.6
9.5
10.4
10.9
11.4
42
116.7
114.4
113.5
112.7
9.7
10.6
11.1
11.6
47
124.6
122.1
121.1
120.1
9.9
10.8
11.3
11.9
52
132.8
130.1
129
127.9
10.1
11.1
11.6
12.1
57
141.1
138.3
137.1
136
10.4
11.3
11.9
12.4
62
149.6
146.7
145.3
144.1
10.6
11.6
12.1
12.7
67
158.3
155.2
153.8
152.5
10.9
11.9
12.4
13.1
72
167.4
164.1
162.6
161.2
11.2
12.2
12.8
13.4
Correction Factors Other Airflows
(Table Value X Correction Factor = Value at New
Airflow)
Airflow
Heating Capacity
Compressor Kw
3500
.99
1.02
4500
x 1.01
x 0.98
18
SSP-PRC001-EN
Performance Data
15 Ton
Table PD-15: Gross Heating Capacities (MBh) 15 Ton TWA180B Heat Pump with 15 Ton
TWE180B Air Handler at 6000 CFM
Outdoor
Heating Capacity (BTUH/1000) at
Total Power in Kilowatts at
Temperature in
Indicated Indoor Dry Bulb Temperature Indicated Indoor Dry Bulb Temperature
Degrees F
60
70
75
80
60
70
75
80
18
71
65.3
63.5
62.2
11.6
12.6
13.1
13.5
-13
73.8
69
67.5
66.5
11.8
12.7
13.2
13.8
-8
77.4
73.4
72.2
71.5
11.9
12.9
13.5
14
-3
81.8
78.7
77.8
77.3
12.1
13.2
13.7
14.3
2
87
84.6
84
83.7
12.3
13.4
14
14.6
7
93.1
91.2
90.8
90.7
12.6
13.6
14.2
14.9
12
100
98.6
98.3
98.3
12.8
13.9
14.5
15.2
17
107.8
106.7
106.4
106.5
13
14.2
14.8
15.5
22
116.5
115.5
115.3
115.3
13.3
14.5
15.1
15.8
27
126
125.1
124.9
124.8
13.6
14.8
15.5
16.2
32
136.3
135.4
135.1
134.9
13.9
15.1
15.8
16.6
37
146.8
145.8
145.4
145
14.1
15.4
16.1
16.9
42
157.9
156.7
156.1
155.6
14.4
15.8
16.5
17.3
47
169.7
168.2
167.5
166.8
14.7
16.1
16.9
17.7
52
182.2
180.4
179.6
178.8
15.1
16.5
17.2
18.1
57
195.2
193.2
192.2
191.2
15.4
16.8
17.6
18.5
62
208.7
206.4
205.3
204.2
15.7
17.2
18
18.9
67
222.6
220
218.8
217.6
16.1
17.6
18.4
19.3
72
237
234.2
232.9
231.7
16.5
18
18.8
19.7
Correction Factors Other Airflows
(Table Value X Correction Factor = Value at New
Airflow)
Airflow
Heating Capacity
Compressor Kw
5250
.99
1.02
6750
x 1.01
x 0.98
SSP-PRC001-EN
19
Performance Data
20 Ton
Table PD-16: Gross Heating Capacities (MBh) 20 Ton TWA240B Heat Pump with 20 Ton
TWE240B Air Handler at 8000 CFM
Outdoor
Heating Capacity (BTUH/1000) at
Total Power in Kilowatts at
Temperature in
Indicated Indoor Dry Bulb Temperature Indicated Indoor Dry Bulb Temperature
Degrees F
60
70
75
80
60
70
75
80
-18
64.1
89.6
97.7
103.6
14.7
17.1
18.3
19.4
-13
81.2
97.6
103.4
107.6
15.4
17.4
18.5
19.5
-8
94.5
106.1
110.1
113.1
15.9
17.8
18.8
19.8
-3
106.6
114.7
117.5
119.5
16.3
18.1
19.1
20.1
2
118.3
123.8
125.6
126.9
16.7
18.5
19.4
20.4
7
130.1
133.4
134.5
135.1
17.1
18.8
19.7
20.7
12
141.9
143.6
144
144.2
17.5
19.2
20.1
21.1
17
154.1
154.4
154.4
154.2
17.9
19.6
20.5
21.6
22
166.7
166
165.5
165
18.2
20
21
22
27
179.9
178.3
177.6
176.8
18.6
20.4
21.4
22.5
32
193.7
191.5
190.5
189.5
19
20.9
21.9
23.1
37
207.6
204.8
203.6
202.5
19.4
21.4
22.4
23.6
42
221.9
218.8
217.4
216.2
19.9
21.9
23
24.2
47
237
233.5
232
230.7
20.4
22.4
23.6
24.8
52
253
249.3
247.6
246.2
20.9
23
24.2
25.5
57
269.6
265.7
263.9
262.3
21.4
23.6
24.9
26.2
62
286.8
282.6
280.6
278.9
22
24.3
25.5
26.9
67
304.4
299.9
297.8
295.8
22.7
25
26.3
27.6
72
322.8
317.9
315.6
313.4
23.4
25.8
27
28.4
Correction Factors Other Airflows
(Table Value X Correction Factor = Value at New
Airflow)
Airflow
Heating Capacity
Compressor Kw
7000
.99
1.02
9000
x 1.01
x 0.98
20
SSP-PRC001-EN
Performance Data
5 Ton
Table PD-17: Evaporator Fan Performance 5 Ton TWE060A, TWE060B - Air Handler
External Static Pressure (Inches of Water Gauge)
.10"
.20"
.30"
.40"
.50"
.60"
.70"
.80"
.90"
1.00"
1.10"
1.20"
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
.75 HP Standard Motor and
Field Supplied Low Static Drive
1600
1700
1800
1900
2000
2100
2200
2300
2400
578
601
625
642
659
674
689
710
730
0.34
0.35
0.36
0.4
0.44
0.48
0.52
0.57
0.61
625
648
671
687
703
722
741
761
780
0.38
0.4
0.41
0.45
0.49
0.54
0.59
0.63
0.68
676
696
716
731
746
770
793
812
830
0.43
0.44
0.46
0.5
0.54
0.6
0.65
0.7
0.75
727
744
762
776
790
817
845
863
880
0.48
0.49
0.51
0.55
0.6
0.65
0.71
0.76
0.82
778
792
807
820
833
857
881
897
913
0.52
0.54
0.56
0.6
0.65
0.7
0.76
0.81
0.87
828
841
853
865
877
897
917
932
946
0.57
0.59
0.61
0.66
0.7
0.75
0.8
0.86
0.91
879
889
898
909
920
936
953
966
979
995
1005
1015
1023
1031
1046
1060
0.74
0.77
0.8
0.84
0.89
0.94
1
1028
1039
1050
1059
1069
1082
1096
0.77
0.81
0.84
0.89
0.93
0.99
104
1060
1073
1085
1095
1106
1119
0.8
0.84
0.88
0.93
0.98
1.04
Nominal
RPM
752
708
663
619
574
530
Note:
1 Field supplied components required:
Blower Sheave: Fixed Pitch (7.8 inch Pitch Diameter),
Blower Sheave: 0.625 inch Bore, Single Groove, "A" Belt.
Belt: A48
SSP-PRC001-EN
21
Performance Data
7 1/2 Ton
Table PD-19: Evaporator Fan Performance 7 1/2 Ton TWE090A, TWE090B - Air Handler
External Static Pressure (Inches of Water Gauge)
.10"
.20"
.30"
.40"
.50"
.60"
.70"
.80"
.90"
1.00"
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1.5 HP Standard Motor and Low Static Drive Kit
1.5 HP Standard
Motor and Sheaves
2400
522 0.58 569 0.65 615 0.71 662 0.78 708 0.84 755 0.91 783 0.98 811 1.05
2550
539 0.61 582 0.68 626 0.74 669 0.81 712 0.87 756 0.94 785
1
814 1.08
2700
556 0.65 596 0.71 636 0.77 676 0.83 716 0.9 758 0.96 787 1.02 816 1.11
2850
573 0.68 610 0.74 646 0.8 683 0.86 720 0.92 759 0.99 788 1.05 819 1.14
3000
590 0.71 624 0.77 657 0.83 690 0.89 723 0.95 760 1.01 790 1.07 821 1.17
3150
609 0.75 640 0.81 672 0.87 703 0.94 735 1.00 768 1.07 798 1.15 829 1.25
3300
628 0.79 657 0.85 687 0.92 717 0.99 746 1.05 776 1.12 807 1.22 837 1.33
3450
647 0.83 676 0.91 705 0.99 733 1.07 762 1.15 791 1.23 820 1.33 849 1.42
3600
666 0.88 694 0.97 722 1.06 750 1.16 778 1.25 806 1.34 834 1.43 862 1.51
Note:
1 Field Supplied Low Static Drive (use Table PD-21)
Data includes pressure drop due to wet coil and 1" filter.
Fan motor heat (MBh) = 3.15 x BHP.
Tranes factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping
or premature motor failure. Our products warranty will not be affected.
Table PD-19: (Continued)
External Static Pressure (Inches of Water Gauge)
1.10"
1.20"
1.30"
1.40"
1.50"
1.60"
1.70"
1.80"
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1.5 HP Standard Motor and Sheaves
2400
2550
2700
2850
3000
3150
3300
3450
3600
840
843
846
849
853
860
868
879
890
1.11
1.15
1.19
1.23
1.27
1.35
1.43
1.52
1.6
868
872
876
880
884
891
898
908
918
1.18
1.23
1.28
1.33
1.37
1.45
1.54
1.61
1.69
896
901
905
910
915
922
929
937
945
1.25
1.31
1.36
1.42
1.48
1.56
1.64
1.71
1.78
924
930
935
941
946
958
959
966
973
1.32 952
1.38 959
1.45 965
1.51 971
1.58 978
1.66 984
1.74 990
1.8 995
1.87 1001
1.39
1.46
1.53
1.6
1.68
1.76
1.85
1.9
1.96
890
988
995
1002
1009
1014
1020
1025
1.46
1.54
1.62
1.7
1.78
1.86
1.95
2
1009
1016
1024
1032
1040
1044
1049
1.52
1.61
1.7
1.79
1.88
1.94
2.01
1037
1045
1054
1063
1071
1.59
1.69
1.79
1.88
1.98
22
SSP-PRC001-EN
Performance Data
10 Ton
Table PD-22: Evaporator Fan Performance 10 Ton TWE120A1, TWE120B1 - Air Handler
External Static Pressure (Inches of Water Gauge)
.10"
.20"
.30"
.40"
.50"
.60"
.70"
.80"
.90"
1.00"
1.20"
1.40"
1.60"
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor and Field Supplied
Low Static Drive1
3200
570 0.67 603 0.75 636 0.83 670 0.91 703 1.00 736 1.08 756 1.14 784 1.2 838 1.32 890 1.49 942 1.66
3400
560 0.71 592 0.79 623 0.88 652 0.95 685 1.04 716 1.12 743 1.18 762 1.24 790 1.3 844 1.43 895 1.59 948 1.8
3600 557 0.77 583 0.84 613 0.92 643 1.01 667 1.07 700 1.16 730 1.23 750 1.27 768 1.34 797 1.41 850 1.55 900 1.69 954 1.94
3800 579 0.94 605 1.01 634 1.09 663 1.18 683 1.24 710 1.29 738 1.37 762 1.42 785 1.49 813 1.56 861 1.72 911 1.87
4000 602 1.11 628 1.17 656 1.26 683 1.35 698 1.4 720 1.43 747 1.5 773 1.58 801 1.64 829 1.71 872 1.89 922 2.04
4200 626 1.23 651 1.31 677 1.4 703 1.48 714 1.53 741 1.59 765 1.66 790 1.72 815 1.81 841 1.9 888 2.08
4400 649 1.36 674 1.45 698 1.53 723 1.62 729 1.65 761 1.76 784 1.81 807 1.87 830 1.98 852 2.09
4600 669 1.52 692 1.62 714 1.69 735 1.77 747 1.82 782 1.92 798 1.99 815 2.06
4800 689 1.69 711 1.79 729 1.85 746 1.92 764 1.98 802 2.09
Note:
1 Field Supplied Low Static Drive (use Table PD-23)
Data includes pressure drop due to wet coil and 1" filter.
Fan motor heat (MBh) = 3.15 x BHP.
Tranes factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping
or premature motor failure. Our products warranty will not be affected.
Table PD-23: Low Static Fan Drive 10 Ton
TWE120A1,B1 Air Handler1
Motor Sheave
Nominal
Turns Open
RPM
0
745
1
706
2
666
3
627
4
588
5
549
Note:
1 Field supplied components required:
Blower Sheave: Fixed Pitch (8.8 inch Pitch Diameter),
Blower Sheave: 1.00 inch Bore, Single Groove, "A" Belt.
Belt: A54
SSP-PRC001-EN
23
Performance Data
10 Ton
Table PD-24: Evaporator Fan Performance 10 Ton TWE120A3, AW; TWE120B3, BW - Air Handler
External Static Pressure (Inches of Water Gauge)
.10"
.20"
.30"
.40"
.50"
.60"
.70"
.80"
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor and Field Supplied
Low Static Drive1
3200
3400
3600
3800
4000
4200
4400
4700
4800
557
579
602
626
649
669
689
0.77
0.94
1.11
1.23
1.36
1.52
1.69
560
583
605
628
651
674
792
711
0.71
0.84
1.01
1.17
1.31
1.45
1.62
1.79
570
592
613
634
656
677
698
714
729
0.67
0.79
0.92
1.09
1.26
1.4
1.53
1.69
1.85
603
623
643
663
683
703
723
735
746
0.75
0.88
1.01
1.18
1.35
1.48
1.62
1.77
1.92
636
652
667
683
698
714
729
747
764
0.83
0.95
1.07
1.24
1.40
1.53
1.65
1.82
1.98
670
685
700
710
720
741
761
782
802
0.91
1.04
1.16
1.29
1.43
1.59
1.76
1.92
2.09
.90"
RPM BHP
1.00"
RPM BHP
1.20"
RPM BHP
703
716
730
738
747
765
784
798
812
1.00
1.12
1.23
1.37
1.5
1.66
1.81
1.99
2.17
736
743
750
762
773
790
807
815
822
1.08
1.18
1.27
1.42
1.58
1.72
1.87
2.06
2.24
756
762
768
785
801
815
830
837
844
1.14
1.24
1.34
1.49
1.64
1.81
1.98
2.18
2.39
784
790
797
813
829
841
852
862
872
1.2
1.3
1.41
1.56
1.71
1.9
2.09
2.29
2.48
838
844
850
861
872
888
904
922
939
1.32
1.43
1.55
1.72
1.89
2.08
2.27
2.45
2.64
890
895
900
911
922
941
960
979
997
1.49
1.59
1.69
1.87
2.04
2.29
2.53
2.67
2.8
942
948
954
959
965
984
1003
1020
1036
1.66
1.80
1.94
2.15
2.36
2.54
2.71
2.86
3.02
2.40"
RPM BHP
1001
1009
1016
1024
1031
1039
1047
1061
1.84
1.98
2.13
2.35
2.57
2.73
2.89
3.06
1051
1057
1065
1070
1077
1083
1090
2.03
2.17
2.31
2.54
2.76
2.91
3.06
1106
1111
1115
1120
1124
1129
2.24
2.37
2.51
2.73
2.95
3.10
1162
1165
1167
1169
2.44
2.57
2.7
2.92
24
SSP-PRC001-EN
Performance Data
15 Ton
.90"
RPM BHP
637
642
647
652
653
655
658
663
670
677
1.4
1.42
1.45
1.47
1.48
1.49
1.51
1.54
1.62
1.7
662
667
672
677
679
681
687
693
700
707
1.44
1.51
1.52
1.54
1.56
1.59
1.63
1.68
1.77
1.86
687
692
697
702
706
709
716
723
735
747
1.49
1.54
1.57
1.6
1.67
1.74
1.79
1.84
1.98
2.12
701
706
713
719
725
731
741
750
767
785
1.53
1.63
1.66
1.69
1.75
1.8
1.89
1.97
2.15
2.33
717
722
726
730
741
752
765
778
799
819
1.58
1.64
1.68
1.72
1.80
1.87
1.98
2.09
2.29
2.49
732
737
740
742
758
774
792
811
832
853
1.00"
RPM BHP
1.20"
RPM BHP
1.63
1.65
1.70
1.75
1.84
1.94
2.09
2.24
2.44
2.65
747
752
761
769
786
803
823
843
865
888
1.64
1.66
1.72
1.78
1.92
2.05
2.22
2.39
2.61
2.83
754
767
783
798
815
831
853
875
900
926
1.65
1.68
1.77
1.87
2.02
2.17
2.35
2.53
2.79
3.05
782
795
811
827
843
860
883
906
934
963
1.67
1.73
1.85
1.98
2.14
2.29
2.49
2.69
2.98
3.27
817
831
843
856
872
889
913
936
967
997
1.76
1.82
1.96
2.09
2.27
2.44
2.64
2.84
3.16
3.49
873
887
900
914
932
950
974
997
1019
1041
1.96
2.02
2.19
2.37
2.57
2.78
2.96
3.15
3.48
3.81
929
943
957
972
990
1008
1025
1042
1063
1085
2.19
2.29
2.48
2.67
2.89
3.11
3.3
3.49
3.81
4.14
986
999
1012
1024
1038
1052
1069
1087
1107
1127
2.46
2.56
2.76
2.96
3.18
3.39
3.61
3.83
4.15
4.47
1035
1046
1058
1070
1083
1096
1113
1130
1146
2.74
2.83
3.04
3.24
3.46
3.68
3.92
4.16
4.49
SSP-PRC001-EN
2.40"
RPM BHP
1084
1095
1105
1116
1127
1138
1152
3.01
3.11
3.31
3.51
3.74
3.96
4.21
1132
1143
1152
3.28
3.38
3.57
Note:
1 Field supplied components required:
Motor Sheave: Variable Pitch (4.3-5.5 inch Pitch Diameter),
0.875 inch Bore, Single Groove, "B" Belt.
Blower Sheave: Fixed Pitch (12.4 inch Pitch Diameter),
1.4375 inch Bore, Single Groove, "B" Belt.
Belt: B67
25
Performance Data
20 Ton
Table PD-28: Evaporator Fan Performance 20 Ton TWE240B - Air Handler
External Static Pressure (Inches of Water Gauge)
.10"
.20"
.30"
.40"
.50"
.60"
.70"
.80"
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5 HP Standard Motor and Field
Supplied Low STatic Drive1
6400
6800
7200
7600
8000
8400
8800
9200
9600
585
619
652
682
711
1.97
2.2
2.43
2.76
3.08
573
603
633
657
680
723
766
1.58
1.84
2.11
2.35
2.60
2.98
3.36
570
593
615
651
686
710
733
760
787
1.41
1.58
1.75
1.98
2.21
2.54
2.86
3.19
3.52
612
635
657
694
730
752
773
790
807
1.57
1.74
1.92
2.15
2.39
2.73
3.07
3.37
3.67
654
677
700
731
761
778
794
811
828
1.7
1.90
2.09
2.38
2.66
2.94
3.22
3.52
3.82
696
722
747
766
785
801
816
834
852
.90"
RPM BHP
1.00"
RPM BHP
1.20"
RPM BHP
1.83
2.08
2.33
2.57
2.81
3.09
3.36
3.68
3.99
743
762
781
795
809
823
837
858
878
2.06
2.29
2.52
2.74
2.95
3.23
3.50
3.84
4.17
781
794
806
819
832
848
863
884
904
2.25
2.46
2.66
2.88
3.09
3.39
3.68
4.01
4.35
808
820
831
844
857
873
889
909
929
2.4
2.61
2.81
3.02
3.23
3.55
3.86
4.2
4.53
835
846
856
869
882
899
915
932
949
2.55
2.76
2.96
3.17
3.37
3.71
4.04
4.4
4.75
883
894
904
919
933
947
960
975
990
2.86
3.07
3.29
3.55
3.8
4.14
4.47
4.83
5.2
7.5 HP Oversized
Motor and Sheaves
Note:
1 Field Supplied Low Static Drive (use Table PD-30)
Data includes pressure drop due to wet coil and 2" filter.
Fan motor heat (MBh) = 3.15 x BHP.
Tranes factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping
or premature motor failure. Our products warranty will not be affected.
Table PD-28: (Continued)
External Static Pressure (Inches of Water Gauge)
CFM
1.40"
RPM BHP
1.60"
RPM BHP
1.80"
RPM BHP
2.00"
RPM BHP
3.16
3.4
3.65
3.94
4.23
4.57
4.92
5.28
5.65
976
986
995
1007
1018
1032
1045
1058
1071
3.52
3.78
4.04
4.34
4.65
5.01
5.36
5.73
6.09
1021
1030
1039
1050
1060
1074
1087
1099
1111
26
Nominal
RPM
857
831
805
779
753
727
701
3.89
4.16
4.44
4.75
5.07
5.44
5.81
6.17
6.54
2.20"
RPM BHP
2.40"
RPM BHP
2.60"
RPM BHP
4.26
4.55
4.84
5.16
5.49
5.87
6.26
6.62
6.99
1111
1119
1127
1136
1145
1159
1172
1182
1192
4.62
4.93
5.23
5.57
5.91
6.31
6.70
7.07
7.43
1156
1164
1171
1179
1187
1200
4.99
5.31
5.63
5.98
6.34
6.73
1201
5.36
Nominal
RPM
712
686
660
634
609
583
557
Note:
1 Field supplied components required:
Motor Sheave: Variable Pitch (4.3-5.5 inch
Pitch Diameter),
1.125 inch Bore, Single Groove, "B" Belt.
Blower Sheave: Fixed Pitch (13.4 inch
Pitch Diameter),
1.4375 inch Bore, Single Groove, "B" Belt.
Belt: B67
SSP-PRC001-EN
Performance Data
5 - 20 Ton
Table PD-31: Standard Motor and Sheave/Fan Speed (RPM) - Air Handler
Sheave Position
6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turns Closed
Tons
Unit Model No.
Open
Open
Open
Open
Open
Open
5
TWE060A1
714
773
833
892
952
1011
TWE060B
726
787
847
908
968
1029
7 1/2
TWE090A3
TWE090B3
10
702
760
819
877
936
994
TWE120A1, B12
710
761
812
863
913
964
TWE120A3, AW3
TWE120B3, BW3
15
760
TWE180B3
862
20
TWE240B4
Notes:
1 Factory setting is 3.0 turns open.
2 Factory setting is 4.0 turns open.
3 Factory setting is 4.5 turns open.
4 Factory setting is 6.0 turns open.
795
894
831
926
866
958
902
990
937
1022
1054
Table PD-32: Oversized Motor and Sheave/Fan Speed (RPM) - Air Handler
Sheave Position
6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turns Closed
Tons
Unit Model No.
Open
Open
Open
Open
Open
Open
5
TWE060A1
828
897
966
1035
1104
1173
TWE060B
TWE060A3, A4, AW
863
934
1006
1078
1150
1222
TWE060B3, B4
7
TWE090A1
845
915
986
1056
1127
1197
TWE090A3, AW
847
908
968
1029
1089
1150
10
TWE120A1, B1
878
941
1004
1066
1129
1192
TWE120A3, AW1
915
969
1023
1077
1131
1185
TWE120B3, BW1
TWE120A3, AW2
733
776
819
863
906
949
TWE120B3, BW2
15
TWE180B
946
981
1016
1052
1087
1122
1157
20
TWE240B
991
1040
1091
1140
1190
1239
Notes:
1 High Static Motor with 6 1/2" Fan Sheave.
2 High Static Motor with 8 Fan Sheave.
SSP-PRC001-EN
27
Performance Data
5 - 20 Ton
Table PD-33: Electric Heat Discharge Plenum and Grille Airflow (CFM)
Tons
TWE060A1, B1
TWE060A3, B3
TWE060A4, B4
TWE090A1, B1
7 1/2
TWE090A3, B3
TWE090A3, B3
10
TWE120A1, B1
TWE120A3, B3
TWE120A3, B31
15
TWE180B3
TWE180B4
TWE240B3
TWE240B4
20
Electric Heater
Model No.
BAYHTRL117A
BAYHTRL315A
BAYHTRL415A
BAYHTRL117A
BAYHTRL123A
BAYHTRL315A
BAYHTRL325A
BAYHTRL415A
BAYHTRL425A
BAYHTRL117A
BAYHTRL123A
BAYHTRL315A
BAYHTRL325A
BAYHTRL415A
BAYHTRL425A
BAYHTRM330A
BAYHTRM430A
BAYHTRM330A
BAYHTRM430A
Airflow (CFM)
Minimum
Maximum
2000
2400
2000
2400
2000
2400
3000
3600
3375
3600
2625
3600
3000
3600
2625
3600
2625
3600
3500
4800
4000
4800
4000
4800
3500
4800
3500
4800
3500
4800
5250
7200
5250
7200
7000
9600
7000
9600
Notes:
1 When wired for 460 Volt.
2 10 Ton with 6.5 inch sheave.
3 10 Ton with 8 inch sheave.
Table PD-34: Discharge Plenum and Grille Assembly Throw Distance (ft) - Air Handler
Unit Tons
Model No.
CFM
Louver Angle Deflection Position
Straight
20
40
55
5
TWE060A
1600
42
31
26
20
1800
46
37
29
22
TWE060B
2000
48
43
33
24
2200
51
50
36
25
2400
54
57
39
29
TWE090A
2400
52
43
35
29
2700
55
48
38
31
TWE090B
3000
58
53
42
32
3300
62
57
46
35
3600
66
60
50
37
TWE120A
3200
56
46
38
30
3600
62
51
42
33
TWE120B
4000
66
57
47
35
4400
71
62
52
38
4800
76
67
56
42
15
TWE180B
4900
47
38
32
25
5400
52
44
37
29
6000
57
49
41
32
6600
61
53
43
34
7200
65
57
46
35
20
TWE240B
6400
56
46
38
30
7200
62
51
42
33
8000
66
57
47
35
8800
71
62
52
38
9600
76
67
56
42
Throw distance values are based on a terminal velocity of 75 FPM.
Throw distance values at other terminal velocities may be established by multiplying throw distances in
the table above by throw factor:
Terminal Velocity
50 FPM
100 FPM
150 FPM
28
x
x
x
Throw Factor
1.50
.75
.50
SSP-PRC001-EN
Performance Data
5 - 20 Ton
Table PD-35: Static Pressure Drop Through Accessories (inches of water column)1 - Air Handlers
Tons
Unit Model No.
CFM
Return Grille
Discharge
5-10
Plenum and
5
TWE060A
TWE060B
7
TWE090A
TWE090B
10
TWE120A
TWE120B
15
TWE180B
20
TWE240B
1600
2000
2400
2400
3000
3600
3200
4000
4800
4800
6000
7200
6400
8000
9600
0.12
0.18
0.28
0.08
0.13
0.18
0.07
0.11
0.15
0.09
0.15
0.2
0.11
0.17
0.23
Grille2
0.21
0.33
0.47
0.27
0.4
0.58
0.43
0.66
0.95
0.23
0.34
0.49
0.43
0.66
0.95
0.08
0.13
0.19
0.03
0.06
0.08
0.06
0.1
0.14
0.03
0.06
0.08
0.06
0.1
0.14
0.14
0.19
0.37
0.08
0.17
0.24
0.19
0.3
0.42
0.06
0.12
0.16
0.13
0.2
0.28
35-50
0.12
0.23
0.32
0.26
0.4
0.57
0.08
0.17
0.24
0.19
0.3
0.42
Notes:
1 Return air filter ESP included in Fan Performance Table data.
2 At louver opening angle of 42 degrees. For ESP at other angle openings, see accessory Installers Guide.
Table PD-36: Auxiliary Electric Heat Capacity - Air Handler
Unit Model No.
Total
No. of Stages
Stage 1
KW Input
BTUH Output
kW
5.00
1
5.00
17,065
TWE060A3, A4, AW
9.96
1
9.96
33,993
TWE060B3, B4
14.96
1
14.96
51,058
24.92
2
14.96
51,058
5.00
1
5.00
17,065
TWE090,120A3,AW
9.96
1
9.96
33,993
TWE120B3, BW
14.96
1
14.96
51,058
TWE090B3
24.92
2
14.96
51,058
TWE060,090,120A1
5.76
1
5.76
19,659
TWE060B1
11.52
1
11.52
39,318
TWE090B1
17.28
1
17.28
58,977
TWE120B1
23.04
2
11.52
39,318
TWE090,120A1
28.8
2
17.28
58,977
TWE120B1
TWE090,120A3, AW
34.88
2
19.92
67,987
TWE120B3, BW
10.00
1
10.00
34,130
19.92
1
19.92
67,987
TWE180, 240B
29.92
2
19.92
67,987
49.84
2
29.92
102,117
Heaters are rated at 240V, 480V and 600V. For other than rated voltage, capacity = (
SSP-PRC001-EN
Voltage
Stage 2
KW Input
BTUH Output
9.96
33,993
9.96
33,993
11.52
39,318
11.52
39,318
14.96
10.00
19.92
51,058
34,130
67,987
KW Input
5.00
9.96
14.96
24.92
5.00
9.96
14.96
24.92
5.76
11.52
17.28
23.04
28.8
34.88
10.00
19.92
29.92
49.84
Total
BTUH Output
17,065
33,993
51,058
85,051
17,065
33,993
51,058
85,051
19,659
39,318
58,977
78,636
98,295
119,045
34,130
67,987
102,117
170,104
)2 x Rated Capacity.
Rated Voltage
29
Controls
Thermostats - Two stage heating/
cooling or one stage heating/cooling
thermostats are available in either
manual or automatic changeover.
30
SSP-PRC001-EN
Electrical
Data
Table ED-1: Unit Wiring - Heat Pumps
Tons
10
15
20
Unit
Model No.
Unit Operating
Voltage Range
Minimum
Circuit
Ampacity
TWA090A3
TWA090A4
TWA090AW
TWA120A3
TWA120A4
TWA120AW
TWA180B3
TWA180B4
TWA180BW
TWA240B3
TWA240B4
TWA240BW
187-253
414-506
518-632
187-253
414-506
518-632
187-253
414-506
518-632
187-253
414-506
518-632
34.5
18.1
14.5
48.1
23.3
18.8
62.7
32.9
26.3
87.8
42.5
34.2
Maximum Fuse
Size or Maximum
Circuit Breaker1
50
25
20
70
35
25
80
45
35
100
50
45
NOTES:
1 HACR type circuit breaker per NEC.
Table ED-2: Electrical Characteristics
Tons
Unit
Model No.
No.
TWA090A3
1
7
TWA090A4
1
TWA090AW
1
TWA120A3
1
10
TWA120A4
1
TWA120AW
1
TWA180B3
2
15
TWA180B4
2
TWA180BW
2
TWA240B3
2
20
TWA240B4
2
TWA240BW
2
SSP-PRC001-EN
Phase
3
3
3
3
3
3
3
3
3
3
3
3
FLA
25.1
13.2
10.6
33.7
16.5
13.4
25.1
13.2
10.6
33.7
16.5
13.4
No.
1
1
1
1
1
1
2
2
2
2
2
2
Volts
208-230
460
575
208-230
460
575
208-230
460
575
208-230
460
575
Phase
1
1
1
1
1
1
1
1
1
1
1
1
FLA (ea.)
3.1
1.6
1.2
6
2.7
2
3.1
1.6
1.2
6
2.7
2
LRA (ea.)
8.1
3.7
3
17
7
5.7
8.1
3.7
3
17
7
5.7
31
Electrical
Data
Table ED-3: Unit Wiring - Air Handler
Tons
10
15
20
Minimum
Unit
Model No.
TWE060A1,B1
TWE060A3,B3
TWE060A4,B4
TWE060AW
TWE090A1, B1
TWE090A3, B31
TWE090A4, B42
TWE090AW
TWE120A1,B1
TWE120A3,B31
TWE120A4,B42
TWE120AW,BW
TWE180B3
TWE180B4
TWE180BW
TWE240B3
TWE240B4
TWE240BW
Maximum Fuse
Unit Operating
Voltage Range
187-253
187-253
414-506
518-632
187-253
187-253
Circuit
Ampacity
Size or Maximum
7
4
2
2
8
7
15
15
15
15
15
15
414-506
518-632
187-253
187-253
4
4
11
8
15
15
15
15
414-506
518-632
187-253
414-506
518-632
187-253
414-506
518-632
5
4
12
6
5
19
9
7
15
15
20
15
15
30
15
15
Circuit Breaker3
NOTES:
1 When wired for 208-230 volt.
2 When wired for 460 volt.
3 HACR type circuit breaker per NEC.
Table ED-4: Electrical Characteristics - Motors - 60 Cycle - Air Handler
Tons
Unit
Standard Evaporator Fan Motor
Amps
Model No.
No.
Volts
Phase
FLA
LRA
TWE060A1, B1
1
208-230
1
5.6
45
TWE060A3, B3
1
208-230
3
2.6
16.4
5
TWE060A4, B4
1
460
3
1.3
8.2
TWE060AW
1
575
3
1.3
6.6
TWE090A1, B1
1
208-230
1
6.2
33
1
208-230/460
3
5.0/2.5
34.3/17.0
7
TWE090A3, B31
TWE090AW
1
575
3
3.1
15
TWE120A1,B1
1
208-230
1
8.3
57.4
1
208-230/460
3
6.0/3.4
49.0/27.5
10
TWE120A3,B31
TWE120AW,BW
1
575
3
2.6
17.5
TWE180B3
1
208-230
3
9.4
74.9
15
TWE180B4
1
460
3
4.6
39.3
TWE180BW
1
575
3
3.4
24.6
TWE240B3
1
208-230
3
14.5
98
20
TWE240B4
1
460
3
6.7
47
TWE240BW
1
575
3
5.4
37.3
NOTES:
1 Ships wired for 208-230/3/60. Field convertible to 460/3/60.
32
Volts
208-230
208-230
460
575
208-230
208-230/460
575
208-230
208-230/460
575
208-230
460
575
208-230
460
575
Phase
1
3
3
3
1
3
3
1
3
3
3
3
3
3
3
3
FLA
6.3
3.6
1.8
1.7
7.7
6.0/3.4
2.6
9.4/4.6
5.4
14.4
6.7
5.4
18
9
7.2
LRA
45
22
11
10.8
57.4
49.0/27.5
17.5
74.9/39.3
37.3
98
47
37.3
122.8
61.4
49.8
SSP-PRC001-EN
Electrical
Data
Table ED-5: Unit Wiring with Electric Heat (Single Point Connection) - 5,7 1/2 and 10 Ton Air Handlers
Heater
Model No.
Maximum Fuse
Heater
To Use
With Unit
Unit
Power Supply
BAYHTRL106A
BAYHTRL112A
BAYHTRL117A
BAYHTRL123A
BAYHTRL106A
BAYHTRL112A
KW Rating1
4.33/5.76
8.65/11.52
12.98/17.28
17.30/23.04
4.33/5.76
8.65/11.52
BAYHTRL117A
BAYHTRL123A
BAYHTRL129A
BAYHTRL106A
BAYHTRL112A
TWE060A1
TWE060B1
208-230/1/60
12.98/17.28
17.30/23.04
21.65/28.80
4.33/5.76
8.65/11.52
TWE090A1
TWE090B1
208-230/1/60
1
2
2
1
1
BAYHTRL117A
BAYHTRL123A
BAYHTRL129A
BAYHTRL305A
BAYHTRL310A
BAYHTRL315A
BAYHTRL325A
BAYHTRL305A
BAYHTRL310A
BAYHTRL315A
BAYHTRL325A
BAYHTRL335A
12.98/17.28
17.30/23.08
21.65/28.80
3.75/5.00
7.45/9.96
11.25/14.96
18.71/24.92
3.75/5.00
7.45/9.96
11.25/14.96
18.71/24.92
26.20/34.88
TWE120A1
TWE120B1
208-230/1/60
TWE060A3
TWE060B3
208-230/3/60
1
2
2
1
1
1
2
1
1
1
2
2
BAYHTRL305A
BAYHTRL310A
BAYHTRL315A
BAYHTRL325A
BAYHTRL335A
BAYHTRL405A
BAYHTRL410A
BAYHTRL415A
BAYHTRL425A
BAYHTRL405A
BAYHTRL410A
BAYHTRL415A
BAYHTRL425A
BAYHTRL435A
BAYHTRL405A
BAYHTRL410A
BAYHTRL415A
BAYHTRL425A
BAYHTRL435A
BAYHTRLW05A
BAYHTRLW10A
BAYHTRLW15A
BAYHTRLW25A
BAYHTRLW05A
BAYHTRLW10A
BAYHTRLW15A
BAYHTRLW25A
BAYHTRLW35A
BAYHTRLW05A
BAYHTRLW10A
BAYHTRLW15A
BAYHTRLW25A
BAYHTRLW35A
3.75/5.00
7.45/9.96
11.25/14.96
18.71/24.92
26.20/34.88
5
9.96
14.96
24.92
5
9.96
14.96
24.92
34.88
5
9.96
14.96
24.92
34.88
5
9.96
14.96
24.92
5
9.96
14.96
24.92
34.88
5
9.96
14.96
24.92
34.88
TWE090A3
TWE090B
Control
Stages
1
1
1
2
1
1
208-230/3/60
TWE120A3
TWE120B3
208-230/3/60
TWE060A4
TWE060B4
460/3/60
TWE090A35
TWE090B35
460/3/60
TWE120A35
TWE120B35
460/3/60
TWE060AW
575/3/60
TWE090AW
575/3/60
TWE120AW
TWE120BW
575/3/60
NOTES:
1
1
1
2
2
1
1
1
2
1
1
1
2
2
1
1
1
2
2
1
1
1
2
1
1
1
2
2
1
1
1
2
2
SSP-PRC001-EN
3
4
5
6
Minimum
or HACR Circuit
Circuit Ampacity2
Breaker Size2, 6
33/37
35/40
60/70
90/100
125/150
35/40
60/70
59/673
88/97
111/1273
34/38
60/683
86/98
112/1283
138/1583
31/41
63/733
89/101
115/1313
141/1613
17/19
30/34
43/49
69/793
20/22
33/37
46/52
72/823
97/1124
21/23
34/38
47/53
73/833
98/1134
10
17
25
40
11
19
26
41
56
12
20
27
42
57
8
15
21
33
11
17
23
36
48
10
16
22
35
47
90/100
125/150
150/175
40/45
70/80
90/110
125/150
150/175
20/20
30/35
45/50
70/80
20/25
35/40
50/60
80/90
100/125
25/25
35/40
50/60
80/90
100/125
15
20
25
40
15
20
30
45
60
15
20
30
45
60
15
15
25
35
15
20
25
40
50
15
20
25
35
50
Any power supply and circuits must be wired and protected in accordance with local codes.
Field wire must be rated at least 75 C.
Field wire must be rated at least 90 C.
With motor field converted to 460V.
The HACR circuit breaker is for U.S.A. installations only.
33
Electrical
Data
Table ED-6: Unit Wiring with Electric Heat (Single Point Connection) - 15 and 20 Ton Air Handlers
Heater
Heater
To Use
Unit
Control
Model No.
With Unit
Power Supply
Stages
KW Rating1
BAYHTRM310A
BAYHTRM320A
BAYHTRM330A
BAYHTRM350A
BAYHTRM310A
BAYHTRM320A
BAYHTRM330A
BAYHTRM350A
7.50/10.00
14.96/19.92
22.50/29.92
37.42/49.84
7.50/10.00
14.96/19.92
22.50/29.92
37.42/49.84
BAYHTRM410A
BAYHTRM420A
BAYHTRM430A
BAYHTRM450A
BAYHTRM410A
BAYHTRM420A
BAYHTRM430A
BAYHTRM450A
BAYHTRMW10A
BAYHTRMW20A
BAYHTRMW30A
BAYHTRMW50A
BAYHTRMW10A
BAYHTRMW20A
BAYHTRMW30A
BAYHTRMW50A
10
19.92
29.92
49.84
10
19.92
29.92
49.84
10
19.92
29.92
49.84
10
19.92
29.92
49.84
TWE180B3
TWE240B3
208-230/3/60
208-230/3/60
TWE180B4
460/3/60
TWE240B4
460/3/60
TWE180BW
575/3/60
TWE240BW
575/3/60
1
1
2
2
1
1
2
2
1
1
2
2
1
1
2
2
1
1
2
2
1
1
2
2
Minimum
Circuit Ampacity2
38/42
64/72
90/102
142/1624
45/49
71/79
97/109
144/1694
21
36
51
81
24
34
54
84
17
30
42
67
20
32
45
70
Maximum Fuse
or HACR Circuit
Breaker Size2,6
40/45
70/80
90/110
150/175
50/50
80/80
100/110
150/175
25
40
60
90
25
40
60
90
20
30
45
70
25
35
50
80
NOTES:
34
SSP-PRC001-EN
Jobsite
Connections
Wiring shown with dashed lines is to
be furnished and installed by the customer. All customer- supplied wiring
must be copper only and must conform to NEC and local electrical
codes. Codes may require line of sight
between disconnect switch and unit.
NOTE:
1. When electric heater accessory is
used single point power entry or dual
point power entry is field optional.
Single point power entry option is
through electric heater only.
TWA060/TWE060A
Field Wiring:
A 3 power wires. Line voltage for
3 phase; 2 wires for single phase.
B 3 power wires. Line voltage for
3 phase; 2 wires for single phase
C Heat pump thermostat: 6 wires,
24 volts.
Electric heat: add 2 additional
wires, 24 volts.
D 2 wires, 24 volts.
Outdoor thermostat: add 1
additional wire per ODT, 24 volts.
TWA090A/TWE090A
TWA120A/TWE120A
Field Wiring:
(2) TW-048/TWE090B
(2) TW-030/TWE060B
(2) TW-060/TWE120B
Field Wiring:
A 3 power wires. Line voltage for 3
phase; 2 wires for single phase.
B 3 power wires. Line voltage for 3
phase; 2 wires for single phase.
C Heat pump thermostat: 7 wires,
24 volts Electric Heat: add 2 additional wires, 24 volts.
D 5 wires, 24 volts to outdoor section "A 2 wires, 24 volts to outdoor section B 2 wires, 24 volts
between outdoor sections A B
Electric heat: add 1 additional
wire, 24 volts.
Outdoor thermostat: add 1
additional wire, 24 volt.
SSP-PRC001-EN
(2) TWA090A/TWE180B
(2) TWA120A/TWE240B
Field Wiring:
A 3 power wires, line voltage.
B 3 power wires, line voltage.
C Heat pump thermostat: 7
wires, 24 volts.
35
Typical Wiring
Heat Pump
Heat Pump Single Compressor
Typical unit wiring diagram. For specific wiring, see individual Service
Facts.
36
SSP-PRC001-EN
Typical Wiring
Heat Pump
SSP-PRC001-EN
37
Typical Wiring
Heat Pump
Heat Pump Dual Compressor
Typical unit wiring diagram. For specific wiring, see individual Service
Facts.
38
SSP-PRC001-EN
Typical Wiring
Heat Pump
SSP-PRC001-EN
39
Typical Wiring
Air Handler
Air Handler
Typical unit wiring diagram. For specific wiring, see individual Service
Facts.
40
SSP-PRC001-EN
Dimensional Data
7 1/2 Ton
Figure DD-1 7 Ton TWA090 Heat Pump
All dimensions are in inches.
SSP-PRC001-EN
41
Dimensional Data
10 Ton
Figure DD-2 10 Ton TWA120A Heat Pump
All dimensions are in inches.
42
SSP-PRC001-EN
Dimensional Data
15 Ton
Figure DD-3 15 Ton TWA180B Heat Pump
All dimensions are in inches.
Note 1
Minimum clearance for proper operation is
36" (914 mm) from walls, shrubbery, privacy
fences, etc. Minimum clearance between adjacent units is 72" (1828 mm).
SSP-PRC001-EN
43
Dimensional Data
20 Ton
Figure DD-4 20 Ton TWA240B Heat Pump
All dimensions are in inches.
Note 1
Minimum clearance for proper operation is 36"
(914 mm) from walls, shrubbery, privacy fences, etc. Minimum clearance between adjacent units is 72" (1828 mm).
44
SSP-PRC001-EN
Dimensional Data
5 Ton
Figure DD-5 5 Ton TWE060A, 060B Air Handlers
All dimensions are in inches.
SSP-PRC001-EN
J
1-7/8
1-1/8
B
38
38
C
22
22
D
8
8
E
19-1/2
19-1/2
F
26
26
G
15-7/8
16-1/4
H
14-1/8
13-1/4
K
42-1/8
42-1/8
Q
34-5/8
34-5/8
S
3/8
5/16
14-3/4
11-1/8
Y
1-1/8
3/4
AA
1-7/8
2
45
Dimensional Data
7 1/2, 10 Ton
Figure DD-6 7 1/2 & 10 Ton TWE090A, 120A; TWE 090B, 120B Air Handlers
All dimensions are in inches.
Model No.
TWE090A
TWE090B
TWE120A
TWE120B
A
54
54
54
54
B
47-1/2
47-1/2
63-12
63-1/2
C
25
25
25
25
D
11-3/4
11-3/4
19-3/4
19-3/4
E
22-3/8
22-3/8
22-3/8
22-3/8
F
22
22
22
22
20-1/8
20-1/8
H
17-3/4
16
17-3/4
16
J
4
2-1/8
4
2-1/8
K
45-1/4
45-1/4
45-1/4
45-1/4
Q
38-1/8
38-1/8
38-1/8
38-1/8
S
1/2
3/8
1/2
3/8
18-3/4
18-3/4
W
15
14
15
14
Y
1-3/8
1-1/8
1-3/8
1-1/8
AA
2
2-1/8
2
2-1/8
46
Model No.
TWE090A
TWE090B
TWE120A
TWE120B
SSP-PRC001-EN
Dimensional Data
5 - 10 Ton
Figure DD-7 5 - 10Ton TWE060A,090A,120A; TWE060B,090B,120B Air Handlers
All dimensions are in inches.
SSP-PRC001-EN
Model No.
TWE060A,060B
TWE090A, 090B
TWE120A, 120B
L
34-5/8
36-7/8
36-7/8
M
2 7/8
6 5/8
6 5/8
N
35-5/8
45-1/8
61-1/8
P
12 1/4
16-1/8
16-1/8
R
32-1/4
41-3/4
57-3/4
T
12 1/2
16-1/4
16-1/4
X
7 5/8
6 7/8
6 7/8
Z
2
1 3/4
1 3/4
47
Dimensional Data
15, 20 Ton
Figure DD-8 15 & 20 Ton TWE180 and 240B Air Handlers
All dimensions are in inches.
48
SSP-PRC001-EN
Dimensional Data
15, 20 Ton
Figure DD-9 15 & 20 Ton TWE180 and 240B Air Handlers
All dimensions are in inches.
Model No.
TWE180B
TWE240B
A
69
71-7/8
B
79-1/2
92-1/2
C
27-5/8
30-1/2
D
12-3/8
18-7/8
E
1-5/8
4-1/2
F
26
31
G
25-1/8
28
H
49-1/8
51-7/8
J
56-1/4
59-1/8
K
15-1/2
18-1/8
L
19-1/2
20-7/8
M
77-1/4
89-1/4
N
1 1/4
1 3/4
P
48
50-7/8
R
35
39-1/8
S
35
39-1/8
T
2-7/8
4-7/8
U
73-7/8
82-7/8
V
3-3/4
4-5/8
W
3-3/8
3-1/8
Y
18
20-1/8
Z
73-7/8
82-7/8
AA
3-3/4
4-5/8
AB
2-7/8
4-7/8
AC
18
20-1/8
AD
3-5/8
3
AE
35
39-1/8
AF
35
39-1/8
SSP-PRC001-EN
49
Dimensional Data
Accessories
Figure DD-10 Electric Heater for 5, 7 1/2 and 10 Ton Air Handlers
All dimensions are in inches.
50
SSP-PRC001-EN
Dimensional Data
Accessories
Figure DD-12 Discharge Plenum and Grille
Table DD6 Discharge Plenum and Grille Dimensions (in.) For Use w/ Electric Heat
Tons
Model No.
A
B
C
5
BAYPLNM025
37-15/16
21-15/16
29
7
BAYPLNM026
47-1/2
25
29
10
BAYPLNM027
63-1/2
25
29
15
BAYPLNM028
79-1/2
27-11/16
35
20
BAYPLNM029
92-1/2
30-7/16
35
SSP-PRC001-EN
51
Dimensional Data
Accessories
Figure DD-14 Subbase
Table DD8 Subbase Dimensions (in.)
Tons
Model No.
5
BAYBASE001
7
BAYBASE002
10
BAYBASE003
15
BAYBASE004
20
BAYBASE005
52
A
38
47-1/2
63-1/2
79-1/2
92-1/2
B
22
25
25
27-5/8
30-7/16
SSP-PRC001-EN
Weights
Heat Pumps
Table W-1 Unit and Corner Weights (lbs.)
Tons
7
10
15
20
Unit
Model No.
TWA090A
TWA120A
TWA180B
TWA240B
Shipping
Maximum (lbs)
390
502
816
970
Net
Maximum (lbs)
343
443
740
885
1
112
149
195
253
Corner Weights
2
3
89
63
116
78
186
175
250
190
4
79
100
184
192
SSP-PRC001-EN
Unit
Model No.
TWA090A
TWA120A
TWA180B
TWA240B
RIS
Isolators
2
2
2
2
Coil
Guard
8
11
22
34
Thermostats
1
1
1
1
Low
Ambient
23
23
23
23
15 and 20 Ton
TWA180B, 240B
53
Weights
Air Handlers
Table W-3 Unit and Corner Weights (lbs.)
Tons
Unit
Model No.
Shipping
Net
Maximum Maximum
(lbs)
(lbs)
298
232
388
317
439
392
754
692
886
816
1
2
3
4
5
TWE060A, B
59
59
59
59
7
TWE090A, B
79
79
79
79
10
TWE120A, B
98
98
98
98
15
TWE180B
173
173
173
173
20
TWE240B
204
204
204
204
Note:
1 If application requires steam or hot water heating coils, field supplied isolators must be utilized.
Table W-4 Accessory Weights (net lbs.)
Electric
Tons
Unit
Discharge Discharge Return
Plenum Air Grille
Heat
Model No. Plenum
And
Min/Max
And
Grille2
Grille1
5
TWE060A,B
58
93
3
7
TWE090A,B
73
123
5
10
TWE120A,B
92
156
7
15
TWE180B
124
230
10
20
TWE240B
145
264
12
Note:
1 For use when no supplemental heat is supplied.
2 For use with electric heat.
32/43
27/45
27/45
79/100
79/100
Subbase Oversized
Motor
14
19
23
27
31
31
48
50
80
88
A
54
73
95
156
179
RIS
RIS
Isolator
Isolator
Suspended
Floor
Mount
Mount
2
9
2
6
2
7
2
7
2
9
B
64
81
101
174
221
C
64
84
101
190
228
D
54
77
95
170
185
Steel Spring
Isolator
Floor Mount
Steel Spring
Isolator
Suspended
Mount
Control
Transformer
12
12
12
12
12
6
6
6
6
6
4
4
54
SSP-PRC001-EN
Mechanical
Specifications
Heat Pumps
General
Units shall be assembled on heavy
gauge steel mounting/lifting rails and
shall be weather proofed. Unit shall
include a hermetic scroll or reciprocating compressor(s), plate fin condenser coil, fans and motors, controls
and holding charge of nitrogen. Operating Range shall be between 115 F to
50 F in cooling as standard from factory. Units shall be UL 1995 listed and
rated in accordance with ARI Standard
340/360.
Casing
Unit casing shall be constructed of 18
gauge zinc coated heavy gauge, galvanized steel. Exterior surfaces shall
be cleaned, phosphatized and finished
with a weather-resistant baked
enamel finish. Units surface shall be
tested 500 hours in salt spray test.
Units shall have removable end panels which allow access to all major
components and controls.
Refrigeration System Single
Compressor
TWA090A, TWA120A units shall have
a single refrigeration circuit. Each
refrigeration circuit has an integral
subcooling circuit. A refrigeration filter drier, expansion valve and check
valves shall be provided as standard.
The TWA090A, TWA120A units shall
have both a liquid line and suction gas
line service valve with gauge port.
TWA090A, TWA120A units shall have
one direct drive Trane hermetic scroll
compressor with centrifugal oil pump
providing positive lubrication to moving parts. Motor shall be suction gascooled and shall have a voltage utilization range of plus or minus 10 percent of nameplate voltage. Crankcase
heater, internal temperature and current-sensitive motor overloads shall
be included for maximum protection.
Scroll type compressor shall provide
inherently low vibration and noise by
having no suction and discharge
valves. External high and low presSSP-PRC001-EN
55
Mechanical
Specifications
Accessories
Low Ambient Head Pressure Control Shall modulate the RPM of unit
outdoor fan motor in response to outdoor ambient temperatures and liquid
line temperature. Accessory provides
unit cooling operation to outdoor temperatures of 0 F.
Vibration Isolation Packages
Shall reduce transmission of noise
and vibration to building structures,
equipment and adjacent spaces. Packages shall be available in either neoprene-in-shear or spring-flex types.
Time Delay Relay Shall prevent
compressors in dual compressor unit
from coming on line simultaneously.
Timer shall be 24-volt, 60 cycle, with
four minute timing period.
Anti-Short-Cycle Timer Shall prevent rapid on-off compressor cycling
in light load conditions by not allowing
compressor to operate for 5-7 minutes
upon shutdown. Shall consist of a solid state timing device, 24-volt, 60 cycle
with either 5 or 7 minute fixed-off timing period.
Condenser Coil Guard Metal
grille with PVC coating shall be provided to alleviate coil damage.
Black Epoxy Coated Condenser
Coil The black epoxy coils have a
thermoset vinyl coating that is
bonded to the aluminum fin stock
prior to the fin-stamping process. The
pre-coated coils are an economical
option for protection in mildly corrosive environments.
56
Air Handlers
General
Air handler units shall be completely
factory assembled including coil, condensate drain pan, fan motor(s), filters
and controls in an insulated casing
that can be applied in either vertical or
horizontal configuration. Units shall
be rated and tested in accordance
with ARI standard 340/360. Units shall
be UL listed and labeled in accordance with UL 1995 for indoor blower
coil units.
Casing
Unit casing shall be constructed of
zinc coated, heavy gauge, galvanized
steel. Exterior surfaces shall be
cleaned, phosphatized and finished
with a weather-resistant baked
enamel finish. Casing shall be completely insulated with cleanable, foil
faced, fire-retardant, permanent,
odorless glass fiber material. All insulation edges shall be either captured
or sealed. Knockouts shall be provided for unit electrical power and
refrigerant piping connections. Captive screws shall be standard on all
access panels.
Refrigeration System
The TWE060A, TWE090A, TWE120A
units shall have a single refrigeration
circuit and the TWE060B, TWE090B,
TWE120B, TWE180B, TWE240B units
shall have dual refrigeration circuits.
Each refrigeration circuit is controlled
by a factory installed thermal expansion valve.
Evaporator Coil
Configured aluminum fin surface shall
be mechanically bonded to 3/8" internally enhanced copper tubing and factory pressure and leak tested at 375
psig. Coil is arranged for drawthrough airflow and shall provide a
double sloped condensate drain pan
constructed of PVC plastic. The drain
pan shall be removable for cleaning.
The condensate drain pan can be
installed in any of four positions
allowing for vertical or horizontal
application and providing external
connections on either side of the unit.
Evaporator Fan
Double inlet, double width, forward
curved, centrifugal-type fan(s) with
adjustable belt drive shall be standard. Thermal overload protection
shall be standard on motor. Fan and
motor bearings shall be permanently
lubricated. Oversized motors shall be
available as an option for high static
application. All indoor fan motors
meet the U.S. Energy Policy Act of
1992 (EPACT)
Controls
Magnetic evaporator fan contactor,
low voltage terminal strip, check
valve(s), and single point power entry
shall be included. All necessary controls shall be factory-installed and
wired. Evaporator defrost control
shall be included to prevent compressor slugging by temporarily interrupting compressor operation when low
evaporator coil temperatures are
encountered.
SSP-PRC001-EN
Mechanical
Specifications
Filters
One inch, throw-away filters shall be
standard on TWE060A, TWE090A,
TWE060B, TWE090B and TWE120B
model air handlers. Filters shall be accessible from the side coil access panel. Filter rack can be field converted to
two inch capability. Two inch, throwaway filters shall be standard on
TWE180B and TWE240B models.
Accessories
Electric Heaters UL and CSA approved electric heat modules shall be
available for installation directly on
fan discharge. Electric Heaters shall be
available in a wide range of capacities
with one or two stage control, singlepoint electric power connection and
terminal strip connections. Electric
heater elements shall be constructed
of heavy-duty nickel chromium elements internally wye connected on
480/600 volt, three phase and delta
connected on 208/240 volt, three
phase. Each 208/240 volt heater shall
have pilot duty with secondary backup
fuse links for automatic reset of high
limit controls. Each 480/600 volt heater
shall have automatic line break high
limit controls.
57
Trane
A business of American Standard Companies
www.trane.com
For more information, contact your local district
office or e-mail us at [email protected]
SSP-PRC001-EN
File Number
PL-UN-000-SSP-PRC001-EN-0805
Supersedes
PL-UN-000-SSP-PRC001-0205
Stocking Location
Webb/Mason
Trane has a policy of continuous product and data improvement and reserves the right to change design
and specifications without notice.