This document discusses strategies for saving energy in rooftop variable air volume (VAV) HVAC systems. It describes optimal start/stop strategies that use a building automation system to determine the optimal times to start and stop the HVAC system in order to bring zone temperatures to the occupied setpoint just before occupancy times. It also discusses fan pressure optimization, which adjusts supply fan static pressure setpoints based on the most open VAV damper to lower fan energy usage. Additionally, it covers supply air temperature reset, which raises supply air temperature at part load to reduce compressor and reheat energy, though it can increase fan energy depending on the system.
This document discusses strategies for saving energy in rooftop variable air volume (VAV) HVAC systems. It describes optimal start/stop strategies that use a building automation system to determine the optimal times to start and stop the HVAC system in order to bring zone temperatures to the occupied setpoint just before occupancy times. It also discusses fan pressure optimization, which adjusts supply fan static pressure setpoints based on the most open VAV damper to lower fan energy usage. Additionally, it covers supply air temperature reset, which raises supply air temperature at part load to reduce compressor and reheat energy, though it can increase fan energy depending on the system.
This document discusses strategies for saving energy in rooftop variable air volume (VAV) HVAC systems. It describes optimal start/stop strategies that use a building automation system to determine the optimal times to start and stop the HVAC system in order to bring zone temperatures to the occupied setpoint just before occupancy times. It also discusses fan pressure optimization, which adjusts supply fan static pressure setpoints based on the most open VAV damper to lower fan energy usage. Additionally, it covers supply air temperature reset, which raises supply air temperature at part load to reduce compressor and reheat energy, though it can increase fan energy depending on the system.
This document discusses strategies for saving energy in rooftop variable air volume (VAV) HVAC systems. It describes optimal start/stop strategies that use a building automation system to determine the optimal times to start and stop the HVAC system in order to bring zone temperatures to the occupied setpoint just before occupancy times. It also discusses fan pressure optimization, which adjusts supply fan static pressure setpoints based on the most open VAV damper to lower fan energy usage. Additionally, it covers supply air temperature reset, which raises supply air temperature at part load to reduce compressor and reheat energy, though it can increase fan energy depending on the system.
to be unoccupied, the system is shut off and the temperature allowed to drift away from the occupied set point. The time at which the system is to restart typically is set to ensure that the indoor temperature reaches the desired occupied set point prior to occupancy on either the coldest or warmest morning of the year. As a result, for most days, the system starts much earlier than needed. In turn, this increases the number of operating hours and system energy use. An alternative approach is a strategy called optimal start. This strategy utilizes a building-automation system (BAS) to determine the length of time required to bring each zone from its current temperature to the occupied set-point temperature. The system waits as long as possible before start- R ooftop variable-air-volume (VAV) systems are used to provide comfort in a wide range of building types and cli- mates. 1 This kind of system consists of a packaged rooftop air conditioner that serves several individ- ually controlled zones. Each zone has a VAV terminal unit that is controlled by a temperature sensor. This article will discuss HVAC- system control strategies that can be used to save energy in rooftop VAV systems. OPTIMAL START/STOP In some buildings, a simple time clock or An applications engineer for Trane, John Murphy, LEED AP, aids engineers in the proper design and application of HVAC systems. He is a member of several American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) technical com- mittees and a contributing author of ASHRAE s recentl y publ i s hed Advanced Energy Design Guide for K-12 School Buildings. By JOHN MURPHY, LEED AP Trane LaCrosse, Wis. 28 May 2008 HPAC Engineering Control strategies can help turn energy savings into operating-cost savings and earn LEED credits E n e r g y - S a v i n g S t r a t e g i e s f o r Occupied set-point temperature Unoccupied set-point temperature System on System off Occupied hours Optimal start Optimal stop Zone temperature Allows 2F drift below set point Starts systems as late as possible Midnight 6 a.m. Noon 6 p.m. Midnight Murphy FIGURE 1. (Size: 27 picas.) FIGURE 1. With an optimal-start strategy, a building-automation system waits as long as possible before starting so each zones temperature can reach the occupied set point just in time for occupancy. VAV Systems Rooftop ing, so the temperature in each zone can reach the occupied set point just in time for occupancy (Figure 1). This optimal starting time is deter- mined using the difference between the actual zone temperature and occupied set point. It compares this difference with the historical performance of the zone warming up or cooling down. The optimal-start strategy reduces the number of system operating hours and saves energy by avoiding the need to maintain the indoor temperature at the occupied set point even though the building is unoccupied. A related strategy is called optimal stop. As mentioned previously, at the end of an occupied period, the HVAC system is shut off and the temperature allowed to drift away from the occu- pied set point. However, the building occupants may not mind if the indoor temperature drifts just a few degrees before they leave for the day. Optimal stop uses a BAS to deter- mine how early heating and cooling can be shut off for each zone so that the indoor temperature drifts only a few degrees from the occupied set point (Figure 1). In this case, only cooling and heating are shut off. The supply fan continues to operate, and the outdoor- air damper remains open to continue ventilating the building. The optimal-stop strategy also reduces the number of system operating hours, saving energy by allowing indoor temperatures to drift early. FAN-PRESSURE OPTIMIZATION As cooling loads change, VAV termi- nals modulate to vary airflow supplied to the zones. This causes the pressure inside the supply ductwork to change. In many systems, a pressure sensor is located approximately two-thirds of the distance along the main supply duct. The rooftop unit varies the capacity of the supply fan to maintain the static pressure in this location at a constant set point. With this approach, however, the system usually generates more static pressure at part load than necessary. When communicating control- lers are used on VAV terminals, it is possi bl e to opti mi ze thi s stati c- pressure control function to minimize duct pressure and save fan energy. Each VAV-unit controller knows the current position of its air-modulation damper. The BAS continually polls these individual controllers, looking for the VAV terminal with the damper that is open the widest (Figure 2). The supply fans set point then is reset to provide just enough pressure so that at least one damper is nearly wide open. This results in the supply fan generat- ing only enough static pressure to push the required quantity of air through this critical VAV-terminal unit. This control strategy, which some- times is called fan-pressure optimiza- tion, has several benefits: Reduced supply-fan energy use. At part-load conditions, the supply fan is able to operate at a lower static pressure 29 HPAC Engineering May 2008 Murphy FIGURE 2. (Size: 27 or 41 picas.) Supply fan Static-pressure sensor Communicating building-automation system Variable-air-volume terminals FIGURE 2. The building-automation system looks for the VAV terminal with the damper that is open the widest. Murphy FIGURE 3. (Size: 27 picas.) S t a t i c
p r e s s u r e Surge Duct static-pressure control Potential energy savings Fan-pressure optimization 1,000 rpm Airow 800 rpm 900 rpm FIGURE 3. Fan-pressure optimization. At part-load condidtions, the supply fan is able to operate at a lower static pressure and consume less energy. and consume less energy (Figure 3). Lower sound levels. The supply fan does not generate as much static pressure and typically generates less noise. In addition, with lower pressures in the supply duct, the dampers in the VAV terminals open wider, resulting in less regenerated noise. Reduced risk of fan surge. With the fan operating at a lower pressure when delivering reduced airflow, the fan operating point is kept farther away from the surge region (Figure 3). Flexibility of sensor location. Because this strategy uses the position of VAV dampers to reset the pressure set point, the static-pressure sensor can be located anywhere in the supply duct. It even can be located at the fans discharge, allowing it to be installed inside the rooftop unit and tested at a factory. In this location, it also can serve as a duct high-pressure sensor, protecting ductwork from damage in the event that a fire damper closes. SUPPLY-AIR-TEMPERATURE RESET In a VAV system, it is tempting to raise the supply-air temperature at part-load conditions to save compres- sor and/or reheat energy. Increas- ing supply-air temperature reduces compressor energy because it allows a compressor to operate at a warmer suction temperature. The correspond- ing higher suction pressure reduces compressor lift, reducing the power required. An air-side economizer is more beneficial when supply-air temperature is reset. When outdoor air is cooler than the supply-air-temperature set point, compressors are shut off and outdoor- and return-air dampers modulate to deliver the desired supply-air tempera- ture. A warmer supply-air-temperature set point allows the compressors to be shut off sooner and increases the num- ber of hours in which the economizer is able to provide all of the necessary cooling. When supply airflow has been re- duced to a VAV terminals minimum setting, raising supply-air temperature decreases the use of reheat in those zones that have very low cooling loads. However, because the supply air is warmer, zones that require cooling will need more air to satisfy the cooling load. This increases supply-fan energy. Finally, in non-arid climates, warmer supply air means less dehumidification at coils and higher humidity levels in zones. If dehumidification is a concern, use caution when implementing this strategy. Table 1 contains some general guidance on determining when this strategy can provide the most benefit. 2 Supply-air-temperature reset should be implemented so that it minimizes overall system energy use. This requires consideration of the tradeoff among compressor, reheat, and fan energy, as well as the impact on space humidity levels. These competing issues often are balanced by first reducing supply ai rfl ow, taki ng advantage of the significant energy savings that come from unloading the fan. Once fan airflow has been reduced, the supply-air temperature can be raised to minimize reheat energy and enhance the benefit of the air-side economizer. Figure 4 is an example of a supply- air-temperature-reset strategy that is based on a changing outdoor dry- bulb temperature. When the outdoor temperature is warmer than 70F, no reset takes place, and the supply-air- temperature set point remains at the design value of 55F. When it is that warm outside, outdoor air provides 30 May 2008 HPAC Engineering R O O F T O P V A V S Y S T E M S Murphy TABLE 1. (In Word document. Size: 27 picas.) Conditions that favor using supply-air-temperature reset Mild climates that have many hours when outdoor dry-bulb temperature is below 60F. Systems with variable-air-volume terminals that have minimum airow settings higher than 30 percent of design airow. Efcient air-distribution-system design. Systems with interior zones that have varying cooling loads. Conditions that reduce the potential to save energy with supply-air-temperature reset Hot climates that have relatively few hours when the outdoor dry-bulb temperature is below 60F. Systems with efcient part-load fan modulation. Inefcient air-distribution-system design. Systems with interior zones that have varying cooling loads. Comments In this type of climate, the economizer-related benets typically outweigh the impact on increased supply-fan energy. Higher minimum airow settings increase the likelihood that reheat will be needed to avoid overcooling the zones. Low pressure losses result in less of a fan-energy penalty for the higher airows that result from raising supply-air temperature. The variable loads might allow these zones to still be satised with a warmer supply-air temperature. Comments In this type of climate, the economizer-related benets are minimal. Using a variable-frequency drive on the supply fan and/or the fan-pressure-optimization control strategy may make it more advantageous to reduce supply airow to save fan energy, rather than increase airow and save compressor energy. High pressure losses result in a signicant fan-energy penalty for the higher airow that accompanies a warmer supply-air temperature. These zones will require near-design airow during all occupied hours, limiting the ability to raise supply-air temperature. Investigate using a separate system to serve these zones. TABLE 1. Guidance concerning supply-air-temperature reset. little or no cooling benefit for econ- omizing. In most zones, the cooling load is likely high enough that reheat is not required to prevent overcooling. In addition, the colder (and drier) supply air allows the HVAC system to pro- vide sufficiently dry air to the zones, improving part-load dehumidification. When the outdoor temperature is between 60F and 70F, the supply- air-temperature set point is reset at a 2-1 ratio. That is, for every 2F change in outdoor temperature, the set point is reset 1F. In this range, supply-air- temperature reset enhances the benefit provided by the economizer and it is likely that some zone-level reheat can be avoided. Finally, when the outdoor tem- perature is colder than 60F, no fur- ther reset occurs, and the supply-air- temperature set point remains at 60F. Limiting the amount of reset to 60F allows the system to satisfy the cooling loads in interior zones without needing to substantially oversize VAV terminals and ductwork. Alternatively, some systems reset the supply-air-temperature set point based on the temperature in the critical zone. (This is the zone at greatest risk of overcooling, which would require activating local reheat.) In these systems, a BAS monitors the temper- ature in all zones, finding the critical zone that is closest to the heating set 32 May 2008 HPAC Engineering R O O F T O P V A V S Y S T E M S Murphy FIGURE 5. (Size: 27 or 41 picas.) Communicating building-automation system Lounge Restroom Time-of-day schedule Mechanical room Storage Ofce Vestibule CO 2 Corridor Occupancy sensor Reception area E l e v a t o r s Ofce Occupancy sensor Conference room CO 2 Computer room FIGURE 5. Zone-level demand-controlled-ventilation strategies. Murphy FIGURE 4. (Size: 27 picas.) S u p p l y - a i r - t e m p e r a t u r e
s e t
p o i n t ,
d e g r e e s
F a h r e n h e i t 55 56 57 58 59 60 61 Outdoor dry-bulb temperature, degrees Fahrenheit 50 55 60 65 70 80 75 FIGURE 4. A supply-air-temperature-reset strategy based on a changing outdoor dry-bulb temperature. point. A rooftop unit then resets the supply-air-temperature set point to prevent the critical zone from needing to activate reheat. When considering using supply-air- temperature reset in a rooftop VAV system, first analyze the system to de- termine if the savings in compressor and reheat energy will outweigh the increase in fan energy. If higher space humidity levels are a concern, consider disabling the reset function when it is humid outside or provide a humidity sensor in one or more zones to override the reset function whenever indoor hu- midity exceeds some maximum limit. For interior zones with near-constant cooling loads during occupied periods, design airflows should be calculated based on the warmer, reset supply-air temperature (60F in the example from Figure 4). While this may require larger VAV terminals and ductwork, it allows R O O F T O P V A V S Y S T E M S 33 HPAC Engineering May 2008 Unoccupied Humidity Control A VAV system typically dehumidifies effectively over a wide range of operating conditions because it continues to deliver cold, dry air at part-load conditions. As long as supply-air-temperature reset is used with caution and reheat is available for those VAV terminals that have high minimum-airflow settings or experience low cooling loads, a VAV system typically will provide supply air at a dew point that is low enough to prevent elevated indoor humidity levels during occupied periods. However, controlling humidity levels always is a priority, not just when a building is occupied. When indoor humidity rises too high during unoccupied times, one option is to turn on the rooftop unit and dehumidify the recirculated air to about 55F. However, there typically is little sensible load in the zones during these periods, so delivering cold air will result in overcooling. Reheat coils in the VAV terminals, and possibly a boiler and hot-water pumps, will need to be activated. An energy-saving alternative is to equip the rooftop unit with hot-gas reheat. When after-hours dehumidification is needed, the rooftop unit turns on and diverts hot refrigerant vapor from the compressor through a refrigerant-to-air heat exchanger located in the air stream following the evaporator coil. Sensible heat is transferred from the hot refrigerant to reheat the dehumidified air leaving the evaporator. This strategy uses heat recovered from refrigeration circuits to reheat centrally and saves energy by avoiding the use of new energy to reheat remotely at VAV terminals. the use of supply-air-temperature reset during cooler weather, while still providing the necessary cooling to weather-independent interior zones. It also is best to design a rooftop VAV systems air-distribution system for low-pressure losses and use the fan-pressure-optimization strategy to minimize the fan-energy penalty that accompanies a warmer supply-air temperature. VENTILATION OPTIMIZATION In a typical VAV system, the roof- top unit delivers fresh outdoor air to several individually controlled zones. Demand-controlled ventilation (DCV) involves resetting intake airflow in response to variations in zone popu- lation. One approach to optimizing ventilation in a multiple-zone VAV system is to combine the various DCV strategies at the zone level (using each where it fits best) with ventilation reset at the system level. Ventilation reset involves resetting intake airflow based on variations in system ventilation efficiency. For this approach, carbon-dioxide (CO 2 ) sensors are installed only in zones that are densely occupied and experience widely varying patterns of occupancy. For the example building in Figure 5, CO 2 sensors are installed only in the conference room and lounge. These zones are the best candidates for CO 2 sensors and provide the biggest bang for the buck. These sensors reset the ventilation requirement for their respective zones based on measured CO 2 . While DCV strategies commonly employ CO 2 sensors, occupancy sensors or time-of-day (TOD) schedules also can be used. Zones that are less densely occupied or have a population that varies only a little (such as private offices, open-plan office spaces, or many classrooms) probably are better suited for occupancy sensors. In Figure 5, each of the private offices has an occupancy sensor to indicate when the occupant is present. When unoccupied, the con- troller lowers the ventilation require- ment for the zone. Occupancy sensors are relatively inexpensive, do not need to be calibrated, and already are used in many zones to control lights. Finally, zones that are sparsely occupied or have predictable oc- cupancy patterns can be controlled 34 May 2008 HPAC Engineering R O O F T O P V A V S Y S T E M S There is real potential to save energy in rooftop VAV systems through optimized system-control strategies. Murphy FIGURE 6. (Size: 27 or 41 picas.) Outside air Rooftop unit with controls Reset outdoor airNow Supply air Return air CO 2 Occupancy sensor Occupancy sensor CO 2 Communicating building-automation system hew outsideair set oint Direct-digital controls/ variable-air-volume terminals Required ventilation Actual rimary airNow FIGURE 6. System-level ventilation-reset strategy. efficiently through the use of a TOD schedule. The schedule can indicate when the zone normally will be occu- pied/unoccupied or be used to vary the zone ventilation requirement based on anticipated population. These various zone-level DCV strategies can be used to reset the ventilation requirement for their respective zones for any given hour. The zone-level control then is tied together using ventilation reset at the system level (Figure 6). In addition to resetting a zones ventilation requirement, the controller on each VAV terminal continuously monitors the primary airflow being delivered to the zone. A BAS periodi- cally gathers this data from all of the VAV terminals and solves the venti- lation-reset equations (prescribed by ANSI/ASHRAE Standard 62.1, Ventilation for Acceptable Indoor Air Quality) to determine how much outdoor air must be brought in at the rooftop unit to satisfy all of the zones served. Finally, the BAS sends this outdoor-airflow set point to the roof- top unit, which modulates a flow- measuring outdoor-air damper to maintain the new set point. In a direct-digital-control/VAV system, this strategy is fairly easy to implement because the necessary real- time information already is available digitally. Combining DCV at the zone level with ventilation reset at the system level has many benefits, including: Ensuring that zones are ventilated properly without requiring a CO 2
sensor in each. CO 2 sensors are used only in the zones in which they can have the most benefit. This minimizes installation costs and avoids the peri- odic calibration and cleaning required to ensure proper sensor operation. For the other zones, occupancy sensors and TOD schedules can be used to reduce ventilation. Enabling documentation of actual ventilation-system performance. The VAV controllers communicate each zones ventilation airflow to the BAS, even for the zones that do not have CO 2 sensors. The BAS can be used to generate reports showing ventilation airflow in every zone, hour by hour. Using system-level ventilation- reset equations that are defined in an industrywide standard. Using equations from ASHRAE Standard 62 improves the ability to defend the control strategys use. CONCLUSION The impact of any energy-saving strategy on the operating costs of a specific building depends on climate, building usage, and utility costs. Building-analysis tools can be used to analyze these strategies and convert energy savings to operating-cost savings and help make financial decisions. Figure 7 shows the potential energy savings of using these various strate- gies in an office building with a typical rooftop VAV system. The optimized system uses the optimal-start, supply- air-temperature-reset, and ventilation- optimization strategies discussed in this article. In addition, the supply fan is controlled based on fan-pressure optimization, rather than a constant set point in the ductwork. The optimized rooftop VAV system would reduce HVAC energy use by about 30 percent if the building were located in Atlanta and Los Angeles and by 33 percent if it were located in Minneapolis. There is real potential to save en- ergy in rooftop VAV systems through optimized system-control strategies. This savings can reduce a building owners operating costs and help earn points toward Leadership in Energy and Environmental Design certifica- tion. REFERENCE 1) Murphy, J. (2007). Rooftop VAV systems applications engineering manual (SYS-APM007-EN). La Crosse, WI: Trane. 2) California Energy Commission. (2003). Advanced variable air volume system design guide. Sacramento, CA: California Energy Commission. For past HPAC Engineering feature articles, visit www.hpac.com. 35 HPAC Engineering May 2008 R O O F T O P V A V S Y S T E M S Murphy FIGURE 7. (Size: 27 picas.) H V A C
e n e r g y
c o n s u m p t i o n ,
p e r c e n t a g e
o f
b a s e 0 20 40 60 80 100 Optimized system controls Base system Minneapolis Los Angeles Atlanta FIGURE 7. HVAC energy savings from optimized system controls.