0% found this document useful (0 votes)
295 views88 pages

51864

A fire alarm system may lower insurance rates, but it is not a substitute for fire insurance. A study indicated that smoke detectors may not go off in as many as 35% of all fires. Smoke detectors also may not sense a fire on another level or floor of a building.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
295 views88 pages

51864

A fire alarm system may lower insurance rates, but it is not a substitute for fire insurance. A study indicated that smoke detectors may not go off in as many as 35% of all fires. Smoke detectors also may not sense a fire on another level or floor of a building.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 88

C

P/N 51864:C ECN 05-126


Document 51864
08/05/2005
Fire Alarm Control Panel
IFC-640
Installation Manual

2 IFC-640 Installation Manual P/N 51864:C 08/05/2005
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm systemtypically made up of
smoke detectors, heat detectors, manual pull stations, audible
warning devices, and a fire alarm control panel with remote
notification capabilitycan provide early warning of a develop-
ing fire. Such a system, however, does not assure protection
against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detec-
tors be located throughout a protected premise following the
recommendations of the current edition of the National Fire
Protection Association Standard 72 (NFPA 72), manufacturer's
recommendations, State and local codes, and the recommen-
dations contained in the Guide for Proper Use of System
Smoke Detectors, which is made available at no charge to all
installing dealers. A study by the Federal Emergency Man-
agement Agency (an agency of the United States government)
indicated that smoke detectors may not go off in as many as
35% of all fires. While fire alarm systems are designed to pro-
vide early warning against fire, they do not guarantee warning
or protection against fire. A fire alarm system may not provide
timely or adequate warning, or simply may not function, for a
variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors
also may not sense a fire on another level or floor of a building.
A second-floor detector, for example, may not sense a
first-floor or basement fire.
Particles of combustion or smoke from a developing fire
may not reach the sensing chambers of smoke detectors
because:
Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
Smoke particles may become cold, stratify, and not reach
the ceiling or upper walls where detectors are located.
Smoke particles may be blown away from detectors by air
outlets.
Smoke particles may be drawn into air returns before
reaching the detector.
The amount of smoke present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm at
various levels of smoke density. If such density levels are not
created by a developing fire at the location of detectors, the
detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming
fires, which have little visible smoke. Detectors that have ion-
izing-type sensing chambers tend to detect fast-flaming fires
better than smoldering fires. Because fires develop in different
ways and are often unpredictable in their growth, neither type
of detector is necessarily best and a given type of detector
may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and violent
explosions (caused by escaping gas, improper storage of
flammable materials, etc.).
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a predeter-
mined rate or reaches a predetermined level. Rate-of-rise
heat detectors may be subject to reduced sensitivity over time.
For this reason, the rate-of-rise feature of each detector
should be tested at least once per year by a qualified fire pro-
tection specialist. Heat detectors are designed to protect
property, not life.
IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by the sys-
tem for the connection of alarm transmission wiring, communi-
cations, signaling, and/or power. If detectors are not so
located, a developing fire may damage the alarm system, crip-
pling its ability to report a fire.
Audible warning devices such as bells may not alert people
if these devices are located on the other side of closed or
partly open doors or are located on another floor of a building.
Any warning device may fail to alert people with a disability or
those who have recently consumed drugs, alcohol or medica-
tion. Please note that:
Strobes can, under certain circumstances, cause seizures
in people with conditions such as epilepsy.
Studies have shown that certain people, even when they
hear a fire alarm signal, do not respond or comprehend the
meaning of the signal. It is the property owner's responsi-
bility to conduct fire drills and other training exercise to
make people aware of fire alarm signals and instruct them
on the proper reaction to alarm signals.
In rare instances, the sounding of a warning device can
cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries have
been properly maintained and replaced regularly.
Equipment used in the system may not be technically com-
patible with the control panel. It is essential to use only equip-
ment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a
premise to a central monitoring station may be out of service
or temporarily disabled. For added protection against tele-
phone line failure, backup radio transmission systems are rec-
ommended.
The most common cause of fire alarm malfunction is inade-
quate maintenance. To keep the entire fire alarm system in
excellent working order, ongoing maintenance is required per
the manufacturer's recommendations, and UL and NFPA stan-
dards. At a minimum, the requirements of NFPA 72 shall be
followed. Environments with large amounts of dust, dirt or
high air velocity require more frequent maintenance. A main-
tenance agreement should be arranged through the local man-
ufacturer's representative. Maintenance should be scheduled
monthly or as required by National and/or local fire codes and
should be performed by authorized professional fire alarm
installers only. Adequate written records of all inspections
should be kept.
Precau-L-1-2005.fm
IFC-640 Installation Manual P/N 51864:C 08/05/2005 3
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associ-
ated equipment may be damaged by removing and/or insert-
ing cards, modules, or interconnecting cables while the unit is
energized. Do not attempt to install, service, or operate this
unit until manuals are read and understood.
CAUTION - System Re-acceptance Test after Software
Changes: To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any pro-
gramming operation or change in site-specific software.
Re-acceptance testing is required after any change, addition
or deletion of system components, or after any modification,
repair or adjustment to system hardware or wiring. All compo-
nents, circuits, system operations, or software functions known
to be affected by a change must be 100% tested. In addition,
to ensure that other operations are not inadvertently affected,
at least 10% of initiating devices that are not directly affected
by the change, up to a maximum of 50 devices, must also be
tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49
C/32-120 F and at a relative humidity (non condensing) of
85% at 30C (86F) per NFPA, and 93% 2% at 32C 2C
(89.6F 1.1F) per ULC. However, the useful life of the sys-
tem's standby batteries and the electronic components may be
adversely affected by extreme temperature ranges and humid-
ity. Therefore, it is recommended that this system and its
peripherals be installed in an environment with a normal room
temperature of 15-27 C/60-80 F.
Verify that wire sizes are adequate for all initiating and indi-
cating device loops. Most devices cannot tolerate more than a
10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to light-
ning induced transients. Although no system is completely
immune from lightning transients and interference, proper
grounding will reduce susceptibility. Overhead or outside aerial
wiring is not recommended, due to an increased susceptibility
to nearby lightning strikes. Consult with the Technical Ser-
vices Department if any problems are anticipated or encoun-
tered.
Disconnect AC power and batteries prior to removing or
inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making modifi-
cations, verify that they will not interfere with battery, trans-
former, or printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced ter-
minal contact pressure and difficulty with screw terminal
removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before han-
dling any circuits so that static charges are removed from the
body. Use static suppressive packaging to protect electronic
assemblies removed from the unit.
Follow the instructions in the installation, operating, and pro-
gramming manuals. These instructions must be followed to
avoid damage to the control panel and associated equipment.
FACP operation and reliability depend upon proper installation.
Precau-L-4-2005.fm
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual may
cause interference to radio communications. It has been
tested and found to comply with the limits for class A
computing devices pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when devices are
operated in a commercial environment. Operation of this
equipment in a residential area is likely to cause interfer-
ence, in which case the user will be required to correct
the interference at his or her own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits
for radiation noise emissions from digital apparatus set
out in the Radio Interference Regulations of the Cana-
dian Department of Communications.
Le present appareil numerique n'emet pas de bruits radi-
oelectriques depassant les limites applicables aux appa-
reils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le
ministere des Communications du Canada.
HARSH, NIS, Notifier Integrated Systems, NOTIFIRENET, and ONYXWorks are all trademarks; and FlashScan, NION, NOTIFIER,
ONYX, UniNet, VeriFire, and VIEW are all registered trademarks of Honeywell International Inc. Echelon is a registered trademark and LonWorks
is a trademark of Echelon Corporation. ARCNET is a registered trademark of Datapoint Corporation. Microsoft and Windows are registered trademarks
of the Microsoft Corporation. LEXAN is a registered trademark of GE Plastics, a subsidiary of General Electric Company.
2005 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
4 IFC-640 Installation Manual P/N 51864:C 08/05/2005
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any com-
ments or suggestions about our online Help or printed manuals, you can email us.
Please include the following information:
Product name and version number (if applicable)
Printed manual or online Help
Topic Title (for online Help)
Page number (for printed manual)
Brief description of content you think should be improved or corrected
Your suggestion for how to correct/improve documentation
Send email messages to:
[email protected]
Please note this email address is for documentation feedback only. If you have any technical
issues, please contact Technical Services.

IFC-640 Installation Manual P/N 51864:C 08/05/2005 5
Table of Contents
Section 1: About This Manual ................................................................................................. 9
1.1: Standards and Other Documents....................................................................................................................9
1.2: Supplemental Documentation......................................................................................................................10
1.3: Cautions and Warnings ................................................................................................................................ 11
Section 2: System Overview.................................................................................................. 13
2.1: System Description......................................................................................................................................13
2.1.1: Standard Features ..............................................................................................................................13
2.1.2: Options ..............................................................................................................................................13
2.1.3: System Limitations............................................................................................................................14
2.2: System Components ....................................................................................................................................14
2.2.1: Basic Equipment Required................................................................................................................14
2.2.2: Control Panel Circuit Board .............................................................................................................15
2.2.3: Main Power Supply ...........................................................................................................................15
2.2.4: Circuit Board Components ................................................................................................................16
2.3: System Cabinets...........................................................................................................................................18
2.4: Optional Devices .........................................................................................................................................19
2.5: Intelligent Detectors.....................................................................................................................................20
2.6: Addressable Modules...................................................................................................................................22
2.7: Annunciation Modules.................................................................................................................................23
2.8: Annunciators................................................................................................................................................24
2.8.1: Annunciators with 24- and 48-Point Capacity ..................................................................................24
2.8.2: Annunciators with 16- and 32-Point Capacity ..................................................................................24
2.8.3: Annunciator Fixed Modules .............................................................................................................25
2.9: Peripheral Displays and Printers..................................................................................................................25
2.10: Panel Circuit Modules ..............................................................................................................................26
2.11: Voice Alarm System ..................................................................................................................................27
Section 3: Installation............................................................................................................. 29
3.1: Preparing for Installation .............................................................................................................................29
3.1.1: Standards and Codes..........................................................................................................................29
3.2: Installation Checklist ...................................................................................................................................30
3.3: Mounting a Cabinet .....................................................................................................................................30
3.4: Laying Out Equipment in Cabinet and Chassis...........................................................................................31
3.5: Installing the Control Panel .........................................................................................................................33
3.5.1: Control Panel Circuit Board & Keypad/Display Unit .......................................................................33
3.5.2: Using JNCA as Primary Display.......................................................................................................34
3.5.3: Loop Expander Module.....................................................................................................................35
3.5.4: Network Control Module...................................................................................................................36
3.5.5: Panel Circuit Modules and Other Option Boards..............................................................................37
3.6: Connecting the Power Cables ....................................................................................................................38
3.6.1: Overview ...........................................................................................................................................38
3.6.2: Connecting the Control Panel to AC Power......................................................................................39
3.6.3: Checking AC Power ..........................................................................................................................39
3.6.4: Installing and Connecting the Batteries ............................................................................................40
3.6.5: APS-6R Auxiliary Power Supply Connections.................................................................................40
3.6.6: External DC Power Output Connections...........................................................................................40
3.7: NAC Connections & Releasing Circuits .....................................................................................................41
3.8: Output Relay Connections...........................................................................................................................42
3.9: Backup-Alarm Switches .............................................................................................................................42
3.10: Installing a Transmitter Module TM-4 ......................................................................................................43
3.11: UL Power-limited Wiring Requirements ...................................................................................................43
3.11.1: Labeling Modules and Circuits........................................................................................................43
3.12: Installing Panel Circuit Modules ..............................................................................................................44
3.12.1: Overview .........................................................................................................................................44
6 IFC-640 Installation Manual P/N 51864:C 08/05/2005
3.12.2: Mounting Expander Boards.............................................................................................................44
3.12.3: Connecting Ribbon Cables for a CAB-4 Series Backbox ...............................................................45
3.12.4: Installing the Panel Circuit Modules ...............................................................................................45
3.12.5: Connecting ICM-4RK and ICE-4 Modules.....................................................................................46
Power Supply Connections...................................................................................................................46
Multiple Power Supplies ......................................................................................................................46
3.12.6: Field-Wiring the ICM-4RK and ICE-4 (NFPA Style Y or Z).........................................................47
3.12.7: Connecting CRM-4RK/CRE-4 Modules.........................................................................................48
3.13: Auxiliary Relay Module (ARM-4): Product-Specific Details ...................................................................49
3.13.1: Overview..........................................................................................................................................49
3.13.2: Installation .......................................................................................................................................49
3.13.3: Field Wiring an Auxiliary Relay Module........................................................................................50
3.14: Installing Remote Printers and/or CRT......................................................................................................50
3.14.1: Custom Cable Fabrication ...............................................................................................................50
3.14.2: Installing and Configuring the PRN Series Printer..........................................................................50
Connecting a Remote PRN Series Printer ............................................................................................50
Setting Printer Options .........................................................................................................................51
3.14.3: Installing and Configuring a Keltron Printer ...................................................................................52
Setting up the Keltron Printer ...............................................................................................................52
3.14.4: Installing and Configuring a CRT-2................................................................................................52
Setting CRT-2 Parameters ....................................................................................................................53
3.14.5: Connecting a PC..............................................................................................................................54
3.14.6: Connecting Multiple Printers, CRTs, or CRT/PRN Combination ..................................................54
3.15: Wiring a Signaling Line Circuit (SLC)......................................................................................................55
Section 4: Applications.......................................................................................................... 57
4.1: Overview......................................................................................................................................................57
Municipal Box (Auxiliary) ...................................................................................................................57
4.2: NFPA 72-1999 Central or Remote Station Fire Alarm System (Protected Premises Unit).........................58
4.3: NFPA 72-1999 Proprietary Fire Alarm Systems .........................................................................................59
4.4: Fire/Security Applications ..........................................................................................................................59
4.4.1: General Operation..............................................................................................................................59
4.4.2: Installing a Security Tamper Switch..................................................................................................60
4.4.3: Receiving Unit ...................................................................................................................................60
4.4.4: Programming .....................................................................................................................................61
4.4.5: Wiring for Proprietary Security Alarm Applications ........................................................................61
4.5: Releasing Applications ................................................................................................................................63
4.5.1: Overview............................................................................................................................................63
4.5.2: Programming .....................................................................................................................................63
4.5.3: Wiring................................................................................................................................................63
4.5.4: Connecting a Releasing Device to the Control Panel ........................................................................64
4.5.5: Connecting a Releasing Device to the M300CJ Module...................................................................65
4.5.6: Connecting an NBG-12LRA Agent Release-Abort Station ..............................................................66
Section 5: Testing the System .............................................................................................. 67
5.1: Acceptance Test ...........................................................................................................................................67
5.2: Periodic Testing and Service........................................................................................................................67
5.3: Operational Checks......................................................................................................................................67
5.4: Battery Checks and Maintenance.................................................................................................................68
On-board Memory-Backup Battery......................................................................................................68
Appendix A: Power Supply Calculations ............................................................................. 69
A.1: Calculating AC Branch Circuit Current......................................................................................................69
AC Branch Circuit Installation.............................................................................................................69
A.2: Calculating the System Current Draws ......................................................................................................69
How to Use the Calculating Tables ......................................................................................................69
A.2.1: Calculating the Maximum Secondary Power Fire Alarm Current Draw..........................................72
A.3: Calculating the Battery Requirements ........................................................................................................73
IFC-640 Installation Manual P/N 51864:C 08/05/2005 7
A.3.1: Calculating the Battery Capacity......................................................................................................73
A.3.2: Calculating the Battery Size .............................................................................................................74
Appendix B: Electrical Specifications .................................................................................. 75
B.1: Electrical Specifications..............................................................................................................................75
AC Power ...........................................................................................................................................75
Batteries................................................................................................................................................75
Signaling Line Circuit (SLC) ..............................................................................................................76
Notification Appliance Circuits & Releasing Circuits ........................................................................76
Output Relays .......................................................................................................................................76
Four-wire Smoke Detector Power ........................................................................................................76
Power Output........................................................................................................................................76
Operating Power: AC Branch Circuit...................................................................................................77
Operating Power: Secondary Power Source (Batteries).......................................................................77
B.2: Wire Requirements......................................................................................................................................77
Appendix C: Compatible Equipment..................................................................................... 79
Johnson Controls and Notifier Equipment ..........................................................................................79
System Sensor Equipment ....................................................................................................................80
Appendix D: Canadian Applications..................................................................................... 81
D.1: Standalone Application...............................................................................................................................81
D.1.1: IFC-640 with KDM-2.......................................................................................................................81
D.1.2: IFC-640 with JNCA..........................................................................................................................81
D.2: Local Network Application ........................................................................................................................81
D.3: Automatic Alarm Signal Silence ................................................................................................................81
D.4: Annunciator Applications ...........................................................................................................................81
D.5: Releasing Devices.......................................................................................................................................81
Index......................................................................................................................................... 83
8 IFC-640 Installation Manual P/N 51864:C 08/05/2005
IFC-640 Installation Manual P/N 51864:C 08/05/2005 9
Section 1: About This Manual
1.1 Standards and Other Documents
This Fire Alarm Control Panel complies with the following NFPA standards:
NFPA 12 CO
2
Extinguishing Systems
NFPA 12A Halon 1301 Extinguishing Systems
NFPA 13 Sprinkler Systems
NFPA 15 Water Spray Systems
NFPA 16 Foam/Water Deluge and Foam/Water Spray Systems
NFPA 17 Dry Chemical Extinguishing Systems
NFPA 17A Wet Chemical Extinguishing Systems
NFPA 72-1999 Central Station Fire Alarm Systems (Automatic, Manual and Waterflow)
Protected Premises Unit (requires Notifier UDACT).
NFPA 72-1999 Local (Automatic, Manual, Waterflow and Sprinkler Supervisory) Fire Alarm
Systems.
NFPA 72-1999 Auxiliary (Automatic, Manual and Waterflow) Fire Alarm Systems (requires
TM-4).
NFPA 72-1999 Remote Station (Automatic, Manual and Waterflow) Fire Alarm Systems
NFPA 72-1999 Proprietary (Automatic, Manual and Waterflow) Fire Alarm Systems
(Protected Premises Unit).
NFPA 2001 Clean Agent Fire Extinguishing Systems
The installer should be familiar with the following documents and standards:
NFPA 72-1999 Initiating Devices for Fire Alarm Systems
NFPA 72-1999 Inspection, Testing and Maintenance for Fire Alarm Systems
NFPA 72-1999 Notification Appliances for Fire Alarm Systems
Underwriters Laboratories
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers - Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1971 Visual Signaling Appliances
UL 1076 Proprietary Burglar Alarm Systems
UL 60950 Safety of Information Technology Equipment
Underwriters Laboratories of Canada (ULC)
Standard CAN/ULC-S527-M99
CAN/ULC-S524-M91 Standard for the Installation of Fire Alarm Systems
Other
EIA-485 and EIA-232 Serial Interface Standards
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction
C22.1-98 The Canadian Electrical Code, Part 1
10 IFC-640 Installation Manual P/N 51864:C 08/05/2005
About This Manual Supplemental Documentation
1.2 Supplemental Documentation
Table 1.1 below provides a list of documents referenced in this manual, as well as documents for
selected other compatible devices. The document series chart (DOC-JCI) provides the current
document revision. A copy of this document is included in every shipment.
Compatible Conventional Devices (Non-addressable) Document Number
Device Compatibility Document
Device Compatibility Technical Bulletin
51922
LIT-445180
Fire Alarm Control Panel (FACP) and Main Power Supply Installation Document Number
IFC-640 Installation, Operations, and Programming Manuals 51864, 51865, 51866
Johnson Controls Voice Alarm System Manual 51869
Johnson Controls SLC Wiring Manual 51870
Note: For individual SLC Devices, refer to the SLC Wiring Manual
Off-line Programming Utility Document Number
VeriFire Tools CD help file JVERIFIRE-TCD
Cabinets & Chassis Document Number
CAB-3/CAB-4 Series Cabinet Installation Document 15330
Battery/Peripherals Enclosure Installation Document 50295
Power Supplies, Auxiliary Power Supplies & Battery Chargers Document Number
ACPS-2406 Installation Manual 51304
APS-6R Instruction Manual
APS-6R Auxiliary Power Supply Technical Bulletin
50702
LIT-445205
CHG-120 Battery Charger Manual
CHG-120 Battery Charger Technical Bulletin
50641
LIT-445210
FCPS-24 Field Charger/Power Supply Manual
Field Charger/Power Supply FCPS-24 Technical Bulletin
50059
LIT-445111
FCPS-24S Field Charger/Power Supply Manual (Sync) 51977
Networking Document Number
NotiFireNet Manual, Network Version 4.0 & Higher 51584
NCM-W/F Installation Document 51533
IFW Intelligent Fire Workstation Manual, Network Version 4.0 & Higher 52028
System Components Document Number
Annunciator Control System Manual 15842
Annunciator Fixed Module Manual 15048
AFM-16A Annunciator Fixed Module Manual 15207
ACM-8R Annunciator Control Module Manual
ACM-8R Annunciator Control Module Technical Bulletin
15342
LIT-445125
LCD-80 Manual
LCD-80 Liquid Crystal Display Technical Bulletin
15037
LIT-445151
LCD-80TM Manual 51082
FDU-80 Remote Annunciator Manual 51264
LDM Series Lamp Driver Annunciator Manual
LDM Lamp Driver Modules Technical Bulletin
15885
LIT-445161
JNCA Network Control Annunciator Manual 51868
Table 1.1 Reference Documentation (Sheet 1 of 2)
IFC-640 Installation Manual P/N 51864:C 08/05/2005 11
Cautions and Warnings About This Manual
1.3 Cautions and Warnings
This manual contains cautions and warnings to alert the reader as follows:
SCS Smoke Control Manual (Smoke and HVAC Control Station) 15712
DPI-232 Direct Panel Interface Manual 51499
TM-4 Installation Document (Reverse Polarity Transmitter) 51490
UDACT Manual (Universal Digital Alarm Communicator/Transmitter) 50050
ACT-2 Installation Document
ACT-2 Audio Coupling Transformer Technical Bulletin
51118
LIT-445225
VEC 25/50 Manual 50686
RM-1 Series Remote Microphone Installation Document
RM-1 Series Remote Microphone Technical Bulletin
51138
LIT-445212
RA400Z Remote LED Annunciator Installation Document I56-508
RFX Wireless Interface Manual 51012
UZC-256 Universal Zone Coder Manual 15216
UZC-256 Programming Manual 15976
XP Transponder Manual
XP Transponder Technical Bulletin
15888
LIT-448180
XP10-M Installation Document I56-1803
XP5 Series Manual
XP5 Series Transponders Technical Bulletin
50786
LIT-445230
XP6-C Installation Document I56-1805
XP6-MA Installation Document I56-1806
XP6-R Installation Document I56-1804
XPIQ Audio Transponder Manual
XPIQ Quad Intelligent Audio Transponder Technical Bulletin
51013
LIT-445235
Table 1.1 Reference Documentation (Sheet 2 of 2)
!
CAUTION:
Information about procedures that could cause programming errors, runtime errors, or equipment
damage.
!
WARNING:
Indicates information about procedures that could cause irreversible damage to the control panel,
irreversible loss of programming data or personal injury.
12 IFC-640 Installation Manual P/N 51864:C 08/05/2005
Notes


IFC-640 Installation Manual P/N 51864:C 08/05/2005 13
Section 2: System Overview
2.1 System Description
The IFC-640(E) control panel is a modular, intelligent fire alarm control panel (FACP) with an
extensive list of powerful features. The control panel integrates a central processing unit (CPU), a
6 amp power supply, and a battery charger. This is combined with a mounting chassis and cabinet
to create a complete fire alarm control system. The panel supports FlashScan protocol and has
network capabilities. A single SLC loop is supported with the basic equipment package; a second
SLC loop can be added by attaching an optional loop expander module (LEM-320).
Modular devices mount to the chassis to provide additional output circuits, including voice and
telephone modules to form a complete voice evacuation system. Five cabinet options for enclosing
system components are available.
The control panel has the capacity for installing up to 636 addressable points; 159 detectors and
159 monitor/control modules per SLC (Signaling Line Circuit).
2.1.1 Standard Features
Uses the VIEW early warning fire detection and the FlashScan or Classic Loop Interface
Protocol (CLIP) families of detectors and modules
Four standard Notification Appliance Circuits (NAC), Class A or B
Alarm, Trouble, Supervisory and Security relays
Support for 32 annunciator addresses, with 10 special annunciator groups
Supports Style 4, Style 6, Style 7 SLC loops
Connections to easily mount an expander board to add a second SLC loop
Releasing service using on-board NACs or M300CJ modules
Logic Equations
Display scroll selection
Alarm verification supervisory indication (NYC)
Supervisory duct detectors
Supports Advanced Warning Addressable Combustion Sensing (AWACS) algorithms
Network operation
Battery charger supports 12-55 amp hour sealed lead-acid batteries
EIA-485 connections for wiring ACS annunciators (including LDM custom graphic
annunciators), TM-4 transmitter
EIA-232 connections for printer, CRT, printer/CRT, or network operation
Autoprogram feature for faster programming of new devices
The control panel provides 6.0 amps of usable output power in an alarm condition; it provides
3.0 amps of usable output power in normal or continuous operating conditions
Diagnostic LEDs and switches
Ground fault detection
Battery and battery-charger supervision, voltage-monitoring, and current-monitoring
Panel circuit modules support up to 64 circuits
Programmable for strobe synchronization
2.1.2 Options
Refer to Section 2.2 System Components for descriptions of the various optional modules.
14 IFC-640 Installation Manual P/N 51864:C 08/05/2005
System Overview System Components
QWERTY silicone-rubber keypad with a 2x40 LCD display and eight indicator LEDs
Optional LEM-320 provides a second SLC loop that is electrically identical to the one on the
main board
Optional devices include: UDACT Universal Digital Alarm Communicator/Transmitter,
ACM-8R remote relay module to increase point capacity, audio and voice components, and
panel circuit modules
Optional LCD-80 connected through an EIA-485 interface allows monitoring the systemup
to 6,000 feet (1,829 meters) from the control panel
2.1.3 System Limitations
System expansion must take into consideration the following:
1. The physical limitations of the cabinet configuration.
2. The electrical limitations of the system power supply.
3. The capacity of the secondary power source (standby batteries).
2.2 System Components
2.2.1 Basic Equipment Required
A basic IFC-640 system requires at least the following components:
1. The control panel. JCPU-640 (120V operation) or JCPU-640E (240V operation).
This printed circuit board is the control panel itself and the heart of the system. It also
includes an expander cable for connecting panel modules, a grounding cable, battery
interconnect cables, and document kit.
2. One or more chassis. CHS-M2 mounts the JCPU-640/JCPU-640E.
To mount additional rows of optional equipment, order one or more chassis from this list:
CHS-M2, CHS-4N (included in shipkit CHS-4MB), CHS-4L.
3. A primary display. Generally this is a KDM-2 keypad/display, a DP-DISP dress panel, and
two BMP-1 blank module panels. For information on using JNCA as primary display instead
of KDM-2, see Section 3.5.2 Using JNCA as Primary Display and the JNCA Manual.
4. A backbox and door:
SBB-A4 and JDR-A4 (one row of equipment) or
SBB-B4 and JDR-B4 (two rows of equipment) or
SBB-C4 and JDR-C4 (three rows of equipment) or
SBB-D4 and JDR-D4 (four rows of equipment)
(For a solid-metal door add B to the part number; for a red door add R.)
5. A battery dress panel BP-4
6. Batteries (Refer to Appendix A.3 Calculating the Battery Requirements for system
current-draw calculations; CAB-4 series backboxes holds batteries up to 24 AH maximum.)
IFC-640 Installation Manual P/N 51864:C 08/05/2005 15
System Components System Overview
2.2.2 Control Panel Circuit Board
The control panel electronics are contained on one four-layer printed circuit board (PCB) that
incorporates a 6 amp power supply with battery charger, a signaling line circuit (SLC) and the
central processing unit. A keypad/display unit can be installed over the power supply as shown
Figure 2.1.
2.2.3 Main Power Supply
The main power supply is an integral part of the
control panels circuit board. It provides a total of
3 A (6 A in alarm) and contains an integral battery
charger. This can be used for many functions
including:
Powering the IFC-640
Powering a variety of UL-listed 24 VDC
notification appliances from four built-in NAC
outputs
Providing up to 1.25 A of resettable power for
four-wire smoke detectors
Providing up to 1.25 A of non-resettable power
for external devices such as the TM-4
Transmitter Module.
Z X C V B N M
A S D F G H J K L
Q W E R T Y U I O P
*
#
&
/
+

(
)
1 2 3 4 5 6 7 8 9 0
! @ =
,
% : . ?
NEXT
SELECTION
PREVIOUS
SELECTION
DETECTOR
MODULE
OUTPUT
RECALL
LAST
ENTRY
INCREMENT
NUMBER
BATTERY
LEVELS SPACE
FIRE
ALARM
ACKNOWLEDGE
SCROLL DISPLAY
SIGNAL
SILENCE
PRE-ALARM SECURITY SUPERVISORY SYSTEM
TROUBLE
POINT
DISABLED
SIGNALS
SILENCED
POWER
DRILL
HOLD 2 SECONDS
SYSTEM
RESET
LAMP
TEST
Esc
Enter
n
f
s
6
4
0
-
p
a
n
e
l
.
c
d
r
Figure 2.1 IFC-640 Control Panel with Optional Keypad/Display Unit Installed
n
f
s
-
6
4
0
-
p
a
n
e
l
-
i
s
o
.
c
d
r
Figure 2.2 Main Power Supply on
Control Panel
16 IFC-640 Installation Manual P/N 51864:C 08/05/2005
System Overview System Components
2.2.4 Circuit Board Components
The following two figures illustrate the location of the various connections, switches, jumpers and
LEDs on the circuit board. Figure 2.3 shows wiring connections. Figure 2.4 shows jumpers, LEDs
and switches. See Section 3 Installation for more details.
NO NO NO NO NC NC NC NC C C C C + - + - + - + - + - TX RX REFTX RX REF B+ A+ B- A-
E
A
R
T
H
N
T
R
L
H
O
T
B
A
T
T
+
B
A
T
T
-
B
+
B
-
A
+
A
-
B
+
B
-
A
+
A
-
B
+
B
-
A
+
A
-
B
+
B
-
A
+
A
-
J3 - LEM-320
Connector
(SLC Loop #2)
J5 - Panel Circuits (supervised)
J10 - Security Tamper Switch
J4 - KDM-2
Connection
TB1 - Battery Connection
(over-current protected)
TB6 - NAC#1
TB5 - NAC#2
TB4 - NAC#3
TB3 - NAC#4
10 Amp Slo-Blow Fuse
P/N 12067
J7 - Accessory Power Connection
TB2 - AC Power Connection
n
f
s
6
4
0
-
b
o
a
r
d
2
.
c
d
r
All NAC Circuits: power-limited, supervised
TB16 - SLC #1 Connections (Detectors,
Modules) (supervised)
TB15 - EIA-232 PC/Terminal Connection (CRT)
J1 - Network/Service Connection (NUP)
(power-limited, supervised)
TB14 - EIA-232 Printer Connection
TB12 - EIA-485 Terminal Mode Connection (supervised)
TB13 - EIA-485 ACS Mode Connection (supervised)
TB7 - DC Power (24 VDC power-limited, non-resettable)
TB7 - DC Power (24 VDC power-limited, resettable)
J8 - Zone Code Input
TB8 - Alarm Relay
TB9 - Trouble Relay
TB10 - Supervisory Relay
TB11 - Security Relay
See Section 3.8 Output Relay
Connections for details.
J6 - Panel Circuits (supervised)
J11 - Auxiliary Trouble Input
Figure 2.3 Circuit Board Components: Wiring Connections
IFC-640 Installation Manual P/N 51864:C 08/05/2005 17
System Components System Overview

NO NO NO NO NC NC NC NC C C C C + - + - + - + - + - TX RX REF TX RX REF B+ A+ B- A-
E
A
R
T
H
N
T
R
L
H
O
T
B
A
T
T
+
B
A
T
T
-
B
+
B
-
A
+
A
-
B
+
B
-
A
+
A
-
B
+
B
-
A
+
A
-
B
+
B
-
A
+
A
-
JP6 - Ground
Fault Jumper
(SLC #1)
D67 -LEM-320
Ground Fault LED
D55 - Main SLC Ground
Fault LED
JP7 - Charger
Disable Jumper
SW1, SW5 -
Relay Switches
NAC LEDs
System Switches - No
Keyboard Operation
SW2 - Acknowledge
SW3 - Silence
SW4 - Reset
Disable - Enable
Switches for
Backup Alarm
n
f
s
6
4
0
-
b
o
a
r
d
2
.
c
d
r
D72 - General
Board Ground
Fault LED
JP12 - 200MA
Jumper
JP13 - General Board
Ground Fault Jumper
D82 - Power-on LED
(AC or battery)
D54 - AC ON / Power LED
D76 - Pre-Alarm LED
D77 - Security LED
D81 - Point Disabled LED
D78 - Supervisory LED
D80 - Signals Silenced LED
D79 - System Trouble LED
D75 - Fire Alarm LED
Figure 2.4 Circuit Board Components: Jumpers, LEDs and Switches
18 IFC-640 Installation Manual P/N 51864:C 08/05/2005
System Overview System Cabinets
2.3 System Cabinets
The control panel and modules are installed in a CAB-4 series backbox. There are four different
sizes available, holding from one to four rows of equipment plus batteries (up to two 25AH
batteries). Backboxes are ordered separately from doors. The doors can be mounted on the left or
the right side of the cabinet; reversible hinges are provided so that this choice can be made in the
field. Doors open a full 180 degrees and have locks. Mounting methods include surface-mounting
or semi-flush mounting on a wall between 16 inch (40.64 cm) on-center studs. A trim ring option is
available for semi-flush mounting.
External measurements for each backbox are provided below; door dimensions are larger. Refer to
CAB-3/CAB-4 Series Cabinet Installation Document (shipped with the cabinet) for specific
mounting drawings and door dimensions.
The control panel and adjacent first-row modules mount in chassis CHS-M2, typically in the
first/top row of the backbox. Additional rows of modules can be mounted in chassis CHS-4N
and/or CHS-4L.
Some additional components available in the CAB-4 series include:
DP-DISP An Inner Dress Panel for covering the backbox area surrounding display panels and
various modules (required for Canadian installations).
BMP-1 Blank Module Plate for covering an unused dress-panel position. Provides another option
for mounting modules such as TM-4, NCM-W, or NCM-F.
BP-4 Battery dress panel
A-size backbox
(one row)
24.00 in (60.96 cm) wide
20.00 in (50.8 cm) tall
5.218 in (13.254 cm) deep
Uses optional trim ring TR-A4
Optional trim ring TR-A4
Opening: 24.062 in (61.118 cm) wide;
20.062 in (50.881 cm) tall.
Molding width: 1.375 in (3.493 cm)
B-size backbox
(two rows)
24.00 in (60.96 cm) wide
28.5 in (72.39 cm) tall
5.218 in (13.254 cm) deep
Uses optional trim ring TR-B4
Optional trim ring TR-B4
Opening: 24.062 in (61.118 cm) wide;
28.562 in (72.548 cm) tall.
Molding width: 1.375 in (3.493 cm)
C-size backbox
(three rows)
24.00 in (60.96 cm) wide
37.125 in (94.297 cm) tall
5.218 in (13.254 cm) deep
Uses optional trim ring TR-C4
Optional trim ring TR-C4
Opening: 24.062 in (61.118 cm) wide;
37.187 in (94.455 cm) tall.
Molding width: 1.375 in (3.493 cm)
D-size backbox
(four rows)
24.00 in (60.96 cm) wide
45.75 in (1162.05 cm) tall
5.218 in (13.254 cm) deep
Uses optional trim ring TR-D4
Optional trim ring TR-D4
Opening: 24.062 in (61.118 cm) wide;
45.812 in (114.775 cm) tall.
Molding width: 1.375 in (3.493 cm)
Trim Rings: When using trim rings, mount backbox with at least 1 inch (2.54 cm) between wall surface and
front of backbox, to allow door to open fully past the trim ring.
NOTE: If using the new CHS-M2 in a CAB-3 series backbox or in a CAB-4 series backbox
manufactured before October 2002, verify stud height and cut any stud that exceeds 0.375 in.
(9.525 mm) if a CPU is being mounted above it. See warning and instructions in Section 3.5.1
Control Panel Circuit Board & Keypad/Display Unit. In retrofit applications, the CAB-3 series
backbox may be used, but a DR-4 series door is required.
NOTE: For use with JNCA, KDM-2, and primary displays.
IFC-640 Installation Manual P/N 51864:C 08/05/2005 19
Optional Devices System Overview
VP-2B or MP-1B (with DP-1B) For covering top row(s) of backbox if control panel is mounted
in a lower row. MP-1B is also used to mount panel circuit modules.
2.4 Optional Devices
Several optional components can be installed within the IFC-640 system. This list provides only a
sample of common equipment; for a complete list of what is available, refer to Appendix C
Compatible Equipment and for a list of conventional equipment, refer to the Device
Compatibility Chart.
Network Control Annunciator - JNCA. Provides a text-based, 24 VDC powered, display
and control device for NotiFireNet. It incorporates a large LCD display and a silicone-rubber
QWERTY keypad. It will display all events from the system.
Network Control Module - NCM-W/F. The NCM is an interface between the panel and
NotiFireNet. It comes in two models: wire and fiber-optic cable. Refer to the NCM-W/F
Installation Document for more information and installation instructions.
Loop Expander Module - LEM-320. The LEM plugs into the control panel, expanding the
boards function to control two Signaling Line Circuits (SLCs). Each IFC-640 can have one LEM.
Refer to Section 3.5 Installing the Control Panel for installation instructions.
Auxiliary Power Supply - APS-6R. The optional Auxiliary Power Supply is a 150W
cabinet-mounted power supply, designed to power devices that require filtered, non-resettable
power, such as XP Transponder modules, NAC modules, and addressable Johnson Controls
appliance circuit modules. The APS-6R provides three 24 VDC output circuits (6 A total in alarm,
4 A continuous): two power-limited circuits (3 A each) and one non-power-limited circuit (6 A).
Refer to the APS-6R Instruction Manual for further information and installation instructions.
Addressable Charger/Power Supply - ACPS-2406. The optional ACPS-2406 is an
addressable loop-based power supply and battery charger. This cabinet-mounted unit provides four
individually addressable Notification Appliance Circuits. In addition, each circuit can provide
notification appliance synchronization without an additional module. The unit charges 7 to 25 AH
batteries with full supervision. The ACPS-2406 provides up to four 24 VDC (filtered) output
circuits (2.5 A max each, 5.0 A total continuous, 6.0 A during a fire alarm). Refer to the
ACPS-2406 Instruction Manual for further information, installation instructions, and battery
calculations.
Batteries and Battery Boxes. The control panel uses only sealed lead-acid batteries for
standby power. Maximum battery capacity is 55 AH (ampere-hour). Minimum battery capacity
depends upon the system configuration; absolute minimum is 12 AH. CAB-4 Series backboxes
provide space for two 25 AH (or smaller) batteries. Use external battery boxes if the installation
requires larger capacity batteries. Battery boxes mount directly below the main cabinet. Battery box
model JCI-LBB holds batteries up to 55 AH. Refer to Section 4.2 NFPA 72-1999 Central or
Remote Station Fire Alarm System (Protected Premises Unit) and Section A.3 Calculating the
Battery Requirements for further information. See Battery/Peripherals Enclosure document for
backbox measurements and installation instructions.
Universal Digital Alarm Communicator/Transmitter (UDACT). Transmits system status to
UL-listed Central Station Receivers over a public switched telephone network. Mounting is in a
CAB-4 Series backbox or remotely in the ABS-8R enclosure. The unit connects to the EIA-485
annunciator port and 24 VDC (nominal) power. Refer to the UDACT Instruction Manual for further
information and installation instructions.
Transmitter Module - TM-4. The TM-4 includes three reverse polarity outputs and a Fire
Municipal Box Trip in a single module. It provides a means for the FACP to control Alarm,
Trouble, and Supervisory reverse polarity outputs (15 mA, 24 VDC nominal) or a Fire Municipal
Box Trip output. All output circuits are supervised. The Transmitter Module communicates over
20 IFC-640 Installation Manual P/N 51864:C 08/05/2005
System Overview Intelligent Detectors
the standard EIA-485 connection like an ACS device and mounts easily in standard module
locations within the cabinet or external boxes. Refer to the Transmitter Module TM-4 installation
document for further information and installation instructions.
Universal Zone Coder - UZC-256. A circuit board, used for NAC coding applications, that
provides three NAC output circuits and up to 256 zone codes. Refer to the UZC-256 Universal
Zone Coder and UZC-256 Programming manuals for further information and installation
instructions.
Field Charger/Power Supply - FCPS-24, FCPS-24S6, FCPS-24S8. Compact,
cost-effective remote power supply and battery charger with a filtered, 24 VDC output that can
drive up to four Notification Appliance Circuits (NACs). The FCPS-24S6/FCPS-24S8 can also
synchronize the NACs. Refer to the FCPS-24 Field Charger/Power Supply Manual or the
FCPS-24S Field Charger/Power Suppply Manual for further information and installation
instructions.
Battery Charger - CHG-120. Designed to charge lead-acid batteries that provide emergency
standby power for a Fire Alarm Control Panel. Provides two (2) output circuits for connection to
multiple loads. Can be mounted into the CAB-4 Series backbox or the JCI-LBB Battery Box. Refer
to the CHG-120 Battery Charger manual for further information and installation instructions.
Liquid Crystal Display - LCD-80. An alphanumeric display module that is an ancillary device
which has two basic modes of operation. In Terminal Mode it acts as a display interface and in ACS
Mode as an alphanumeric annunciator. The LCD-80TM is also available and provides Terminal
Mode only. Refer to the LCD-80 or LCD-80TM Liquid Crystal Display manuals for further
information and installation instructions.
Remote Fire Annunciator - FDU-80. An 80-character LCD that displays all panel
information remotely. Refer to the FDU-80 Manual for further information and installation
information.
SCS-8 Series Smoke Control System. The Smoke Control Station (SCS-8) module uses
eight groups of four annunciator points for fan shutdown control or other heating, ventilation or air
conditioning functions. The Smoke Control Expander (SCE-8) is used to expand the SCS-8 by an
additional eight groups of four annunciator points. Only one expander can be used per SCS-8. The
Smoke Control Lamp Driver Station (SCS-8L) module uses eight groups of four annunciator points
for fan shutdown control or other heating, ventilation or air conditioning functions. Must be
mounted in custom graphic annunciator panel. The Smoke Control Expander (SCE-8L) is used to
expand the SCS-8L by an additional eight groups of four annunciator points. Only one expander
can be used per SCS-8L. Must be mounted in custom graphic annunciator panel. For more details
on the SCS Smoke Control System, refer to the SCS Manual.
2.5 Intelligent Detectors
Introduction
Intelligent, addressable detectors provide analog information to the control panel on a Signaling
Line Circuit (SLC). This allows the control panel to continually process this information to
determine the status (alarm, trouble, maintenance, or normal) of each detector. Each detector
responds to an SLC address that is set in the detector head using built-in rotary switches. Each SLC
loop can support up to 159 detectors. The sensitivity of each intelligent detector can be
programmed (refer to Appendix C in the IFC-640 Programming Manual for details).
NOTE: A blinking LED on an intelligent detector indicates communication between the detector
and the control panel.
IFC-640 Installation Manual P/N 51864:C 08/05/2005 21
Intelligent Detectors System Overview
Detectors
The FlashScan algorithm provides high-speed communication between analog intelligent
devices, by polling in groups unless new information is reported. If one of the devices within the
group has new information, the control panel stops the group poll and concentrates on single points.
CLIP (Classic Loop Interface Protocol) is standard polling of each intelligent devices.
2951TMJ (Acclimate) Intelligent detector that combines a photoelectric sensing chamber and
fixed temperature heat detection (135F/57.2C). FlashScan capable.
FSB-200S Addressable, intelligent, single-ended beam smoke detector with built-in sensitivity
testing. The FSB-200 is the same except that it does not provide sensitivity testing. Both models
support FlashScan and CLIP mode.
1951J Addressable, intelligent smoke detector that incorporates an ionization sensing chamber.
Designed to provide open area protection. FlashScan capable.
2951J Analog, addressable intelligent smoke detector that uses a photoelectric sensing chamber.
Listed for use in ducts. Designed to provide open area protection. FlashScan capable. The 2951TJ
adds thermal sensors that will alarm at a fixed temperature of 135F (57C).
5951J Intelligent thermistor sensing circuit for fast response. Designed to provide open area
protection with 50 foot spacing capability. A fixed temperature sensor with 135F fixed
temperature alarm. FlashScan capable. The 5951RJ incorporates a thermal rate of rise of 15F
(9.4C). FlashScan capable. The 5951HJ is a high temperature sensor with 190F (87.8C) fixed
temperature alarm.
1351J Analog, addressable, low profile intelligent smoke detector that incorporates an ionization
sensing chamber. Designed to provide open area protection.
2351J Same as 1351J, but uses a photoelectric sensing chamber. The 2351TJ adds thermal
sensors that will alarm at a fixed temperature of 135F (57C). Designed to provide open area
protection.
5351J Intelligent thermistor sensing circuit for fast response. Designed to provide open area
protection with 50 foot (15.24 m) spacing capability. The 5351RJ incorporates a thermal rate of
rise of 15F (9.4C).
DH300P Photoelectric Duct Detector. The DH300RP includes an alarm relay. The DH300PL and
DH300RPL are low-flow detectors.
FTX-P1J (HARSH) A special smoke detector that provides early warning smoke detection in
hostile environments where traditional smoke detectors are not practical. CLIP mode only.
FTX-P2J (HARSH) A special smoke detector that provides early warning smoke detection in
hostile environments where traditional smoke detectors are not practical. FlashScan capable.
3251J A microprocessor-based intelligent smoke detector that uses a combination of
photoelectric, ionization, and thermal sensing technologies. CLIP mode only.
2351TMJ Acclimate is a Combination Photoelectric/Heat Detector. This intelligent,
addressable, multi-sensing, low-profile detector can automatically adjust its sensitivity. It uses a
combination of photoelectric and thermal sensing technologies that are designed to increase
immunity to false alarms.
7251J Early detection laser detector, similar to the 7351J VIEW, but limited to CLIP mode
operation only.
7351J VIEW Low Profile Laser Detector An advanced intelligent photoelectric detector
that uses a laser diode, special optics, and signal processing to obtain extremely high sensitivity.
FlashScan capable.
22 IFC-640 Installation Manual P/N 51864:C 08/05/2005
System Overview Addressable Modules
Bases
Several bases, to which the detectors are affixed, are available:
B210LPJ Standard U.S. Low-Profile base
B501J Standard European flangeless base
B501BH, B501BHT Sounder base, includes B501J Sounder base with temporal sounder
B224RB Low Profile Intelligent relay base
B224BI Low Profile Intelligent isolator base
B510B-FTXJ HARSH base.
Accessories
RA400Z A Remote Single LED Annunciator that can be wired directly off of an addressable
detector for annunciation of that detector's alarm status.
2.6 Addressable Modules
Control Modules and Monitor Modules provide an interface between the control panel and
conventional notification and initiating devices. Each module can be set to respond to an address
with built-in rotary switches with the ability to select up to 159 addresses. An LED will blink on a
monitor module to indicate communication between the module and the control panel.
Monitor and Zone Interface Modules - M300MJ, M302MJ & M300DJ Addressable
monitor modules for monitoring conventional initiating devices. The M300MJ is used for normally
open contact alarm initiating devices, such as manual pull stations, four-wire smoke detectors, heat
detectors, waterflow, and supervisory devices. Use the M302MJ for interface to two-wire smoke
detectors in addition to normally open contacts. The M300DJ provides two independent 2-wire
Initiating Device Circuits (IDCs) at two separate, consecutive addresses. Wire supervised IDCs as
NFPA Style B (Class B) or Style D (Class A) circuits. The modules come with a thermoplastic
cover for mounting to a 4-inch (10.16 cm) square mounting box.
Monitor Module - M301MJ An addressable module that is functionally similar to the M300MJ
Monitor Modulebut offered in a smaller package for mounting directly in the electrical box of
the device being monitored. (Class B input circuit only.)
Control Module, NAC - M300CJ Addressable Control Module used as Notification Appliance
Circuits (NACs) to power and supervise compatible, UL-listed notification appliances. Wired
supervised NACs as NFPA Style Y (Class B) or Style Z (Class A). The modules come with a
thermoplastic cover for mounting to a 4-inch (10.16 cm) square mounting box.
Control Module, Relay - M300RJ Similar to the M300CJ except used as a Form-C control
relay module.
Fault Isolator Module - M500XJ This module is not addressable, but listed here due to its use
in an SLC. Protects the system against wire-to-wire short circuits on the SLC. It should be placed
between groups of sensors in a Style 6 or Style 7 SLC to isolate short- and open-circuit problems
and protect the rest of the loop so it can continue to operate normally.
Pull Station - JBG-12LX An addressable manual pull station with key-lock reset feature. The
addressable module is housed within the pull station.
Transponder - XP5-M Supervises five Class-B addressable Initiating Device Circuits each
with a maximum loop resistance of 1,200 ohms. These circuits monitor normally open contact
initiating devises (manual pull stations, heat detectors, four-wire smoke detectors, security contacts,
NOTE: For a list of approved notification and initiating devices, refer to the Device Compatibility
Document.
IFC-640 Installation Manual P/N 51864:C 08/05/2005 23
Annunciation Modules System Overview
etc.). One XP5-M occupies five consecutive addresses on the signaling line circuit (SLC). Each
circuit has one red LED status indicator that blinks when it is not active, and produces a steady
glow when active. For more information see the XP5 Series Transponder Manual.
Transponder - XP5-C Each of the five circuits of the XP5-C can act as a notification appliance/
speaker/telephone circuit (Class B only) or a Form-C relay. A push-button switch changes the
circuit to a Form-C relay. One XP5-C occupies five consecutive addresses on the SLC. Each circuit
has one green LED status indicator that blinks when it is not active, and produces a steady glow
when active. For more information see the XP5 Series Transponder Manual.
Quad Intelligent Audio Transponder - XPIQ The XPIQ is an integrated audio amplification
and distribution subsystem that can direct up to four low-level audio signals through four audio
amplifiers to integrated, continuously supervised speaker circuits. An on-board power supply
charges and supervises battery backup.
Multi-Input/Output Modules - XP6-C, XP6-R, XP10-M, XP6-MA FlashScan capable
multi-input/output modules are available for use on the SLC loop. All are FlashScan capable.
XP6-C controls six NAC or speaker/telephone circuits. Applications are equivalent to those for
XP5-C set as a notification appliance/speaker/telephone circuit. (Not listed for use in releasing
applications.)
XP6-R controls six Form-C relays. Applications are equivalent to those for XP5-C set as a
Form-C relay.
XP10-M supervises ten Class-B addressable Initiating Device Circuits (IDC) which monitor
normally open contact initiating devices. Applications are equivalent to those for XP5-M.
XP6-MA enables an intelligent alarm system to monitor six zones of conventional two-wire
detectors.
For installation instructions, refer to the documentation provided with the modules.
2.7 Annunciation Modules
Introduction
This section contains brief descriptions and model numbers of annunciator modules that can be
connected to the control panel. Communication between the control panel and annunciators takes
place over a two-wire serial interface connected to the control panels EIA-485 ACS Mode
connection. Section 2.8 Annunciators contains more detailed information.
Description
Below are descriptions of the Annunciator Modules and Expander Modules used with the control
panel.
Annunciator Control Module - ACM-8R Provides the control panel with a mappable relay
control module. Relays can be selected for mapping anywhere in the system memory (in groups of
eight). Provides eight Form-C relays with 5 A @ 125 VAC (resistive) or 5 A @ 30 VDC (resistive)
or 2 A @ 125 VAC (inductive) contacts. Tracks any group of eight zones within the system.
Refer to ACM-8R Annunciator Control Module manual for more information.
Lamp Driver Annunciator Module - LDM-32 Provides 32 alarm lamp driver outputs for
connection to a custom graphic annunciator. DIP switch selectable for 32 alarm outputs or 16
alarm/16 trouble outputs, and 16 switch inputs for control of system control functions as Signal
Silence and System Reset.
Refer to the LDM Series Lamp Driver Annunciator Modules manual for more information.
Lamp Driver Annunciator Expander Module - LDM-E32 Expands the LDM-32 by 32
system points, to a maximum of 64 points.
24 IFC-640 Installation Manual P/N 51864:C 08/05/2005
System Overview Annunciators
Lamp Driver Relay Expander Module - LDM-R32 Provides the LDM-32 or LDM-E32 with
32 dry Form-A (normally open) contacts.
2.8 Annunciators
The Annunciator Control System provides the control panel with 32 remote annunciators. The
number of points a particular annunciator can support is reflected in the part number. For example,
an ACM-24AT has 24 points and an ACM-48A has 48 points. The number of points on an
Annunciator Expander Module must match the number of points on the Annunciator Control
Module it is expanding. One Annunciator Fixed Module can also be used per system. Connections
are through an EIA-485 ACS Mode connection on the Control Panel.
Brief descriptions follow of specific modules used with the control panel. For detailed information,
refer to the specified product manual.
2.8.1 Annunciators with 24- and 48-Point Capacity
For specific installation information, refer to the Annunciator Control Module manual. For
Canadian requirements, see Appendix D Canadian Applications.
Annunciator Control Module - ACM-24AT A one-channel Class-B unit with 24 switch
controlled annunciator points. Each point is controlled by a silicone-rubber switch with indicator
LED. Multi-color LEDs can be programmed to produce one of three colors: red, green or yellow.
Annunciator Expander Module - AEM-24AT An expander board for the ACM-24AT that
provides an additional 24 points and is identical in size and appearance. Up to three expanders can
be used with an ACM-24AT.
Annunciator Control Module - ACM-48A A one-channel Class- B unit with 48 annunciator
points for indicating current system status. Each annunciator point has a red LED for alarm, and a
green LED for normal; each module has a yellow unit-trouble LED at the top.
Annunciator Expander Module - AEM-48A An expander board for the ACM-48A that
provides an additional 48 points and is identical in size and appearance. One expander can be used
with an ACM-48A.
2.8.2 Annunciators with 16- and 32-Point Capacity
Models with several other LED color combinations are available for use in areas with specific color
requirements. Refer to the Annunciator Control System manual for detailed information. For
Canadian requirements, see Appendix D Canadian Applications.
Annunciator Control Module - ACM-16AT Provides features for audible and visual
indication of alarm and trouble conditions at each annunciator point. They include:16 red alarm
LEDs, 16 yellow trouble LEDs, 16 momentary touch-pad switches for controlling each point,
System trouble LED, Online/Power LED, Local sounder, Silence/Acknowledge switch, and
Remote functions.
NOTE: The IFC-640 can only support 64 points per annunciator address regardless of the
model used.
NOTE: An AEM-24AT cannot be used to expand an ACM-48A.
NOTE: An AEM-48A cannot be used to expand an ACM-24AT.
IFC-640 Installation Manual P/N 51864:C 08/05/2005 25
Peripheral Displays and Printers System Overview
Annunciator Expander Module - AEM-16AT Expands the ACM-16AT by 16 system points
and is identical in size and appearance. Three expander modules are supported by one control
module providing a maximum of 64 system points.
Annunciator Control Module - ACM-32A Provides features for audible and visual indication
of alarm and trouble conditions at each annunciator point. They include: 32 red alarm LEDs,
System trouble LED, Online/Power LED, Local sounder, and Silence/Acknowledge switch.
Annunciator Expander Module - AEM-32A Expands the ACM-32A by 32 system points and
is identical in size and appearance. One expander module is supported by the control module
providing a maximum of 64 system points.
2.8.3 Annunciator Fixed Modules
Introduction
Provide the control panel with discrete display and control points. Fixed modules turn their LEDs
on and off as directed by the control panel, and also report switch activations to the control panel
for action. You can only use one fixed module in a system. Each annunciators address is fixed at
address 1.
Refer to the Annunciator Fixed Module manual for further information.
Description
Annunciator Fixed Module - AFM-16AT Contains 16 red alarm and 16 yellow trouble LEDs,
a system trouble LED, an Online/Power LED, and a local sounder, and switches for control panel
Acknowledge, Alarm Silence, and System Reset. Use the AFM-16AT for systems that require 16 or
fewer annunciation points.
Annunciator Fixed Module - AFM-32A Contains 32 red alarm LEDs, a system trouble LED,
an ON LINE/POWER LED, and a local panel sounder with a silence/acknowledge switch. The
AFM-32A is fixed at address 1, and will not accept expander modules.
2.9 Peripheral Displays and Printers
The control panel is compatible with the following printers and display devices:
PRN Series Printer
Keltron Remote Printer VS4095
CRT-2 Display Terminal
All EIA-232 devices must be located in the same room within 50 feet (15.24 m) of the control
panel.
Printer - PRN Series Printer The PRN is an optional printer that connects directly to the
control panel through an EIA-232 interface (TB14) and can be located up to 50 feet (15.24 m) from
the control panel. It creates a printed record (80 columns of data on standard 9" x 11" tractor-feed
paper) of all system events (alarm, trouble) and status changes within the system. The printout is
time-stamped with the current time-of-day and date.
NOTE: An AEM-16AT cannot be used to expand an ACM-32A.
NOTE: An AEM-32A cannot be used to expand an ACM-16AT.
26 IFC-640 Installation Manual P/N 51864:C 08/05/2005
System Overview Panel Circuit Modules
Keltron Remote Printer The VS4095 is a two-color (red/black), 40-column, 24 VDC printer
that can print 50 messages in 90 seconds. This printer connects to the control panel through an
EIA-232 interface (TB14) and mounts in a separate cabinet next to the control panel. The VS4095
meets UL fire and security requirements for an ancillary device.
For more information, contact the manufacturer (Keltron Corp., Waltham, MA)
Display Terminal - CRT-2 This optional display terminal connects to the control panel through
an EIA-232 interface (TB15). The terminal can control and view events, points and history reports,
control the system (Acknowledge, Alarm Silence, and System Reset). The terminal displays 26
lines by 80 columns and can be located up to 50 feet (15.24 m) from the control panel within the
same room.
2.10 Panel Circuit Modules
Introduction
The control panel supports the following modules to control external circuits and relays:
Indicating Circuit Module (ICM-4RK) & Indicating Circuit Expander (ICE-4)
Control Relay Module (CRM-4RK) & Control Relay Expander (CRE-4)
Auxiliary Relay Module (ARM-4)
Voice Control Module (VCM-4RK), Dual Channel Module (DCM-4RK) & Voice Control
Expander (VCE-4)
Up to eight of these modules (in any combination) can be controlled by the panel. Below are brief
descriptions of the modules; for a description of VCM-4RK and DCM-4RK, see Section 2.11
Voice Alarm System.
Indicating Circuit Module - ICM-4RK Provides four (4) NACs for Style Y (Class B) or Style
Z (Class A) operation. Circuits are field-programmable to respond to a single initiating zone, a
group of zones, or all initiating zones. Maximum signaling current is 3 A per circuit or 6 A per
module, limited by the power supply.
An Auxiliary Power Harness (P/N 71091) is provided. Note: ICM-4RK is not listed for use with
IFC-640 in releasing applications.
Indicating Circuit Expander - ICE-4 An attaching circuit board that expands the ICM-4RK to
a total of eight Style Y (Class B) or Style Z (Class A) NACs. Maximum signaling current is 3 A
per circuit or 6 A per module, limited by the power supply. An Auxiliary Power Harness (P/N
71091) is provided.
Control Relay Module - CRM-4RK Provides four (4) standard dry Form-C relay contacts.
Each relay is field-programmable to respond to a single initiating device circuit, a group of circuits,
or all initiating device circuits. Each relay features manual On/Off control switches and can be
disabled or enabled. Contacts rated for 5 A at 120 VAC or 28 VDC (resistive). Note: CRM-4RK is
not listed for use with IFC-640 in releasing applications.
Control Relay Expander - CRE-4 An attaching circuit board that expands the capacity of the
Control Relay Module (CRM-4RK) to eight (8) Form-C alarm relays. May also be used to expand
the ICM-4RK to provide four (4) Form-C control relays. Contacts rated for 5 A at 120 VAC or 28
VDC (resistive).
Auxiliary Relay Module - ARM-4 Provides four (4) auxiliary Form-C relays that can be
controlled by a CRM-4RK or CRE-4 relay module. Normally-open contacts rated for 20 A and the
normally-closed contacts are rated for 10 A at 125 VAC and 30 VDC (resistive). An Auxiliary
Power Harness (P/N 71092) is provided.
NOTE: The CRT cannot be connected at the same time as the network.
IFC-640 Installation Manual P/N 51864:C 08/05/2005 27
Voice Alarm System System Overview
2.11 Voice Alarm System
Introduction
Voice Alarm equipment provides a manual or automatic supervised paging system for transmitting
voice messages (information, instructions, directions) on a selective or all call basis. For more
information and installation instructions refer to the Voice Alarm System manual.
Configuration
JVCC-1B Voice Control Center Basic equipment package for single-channel audio evacuation
system that includes: AMG-1 Audio Message Generator (with microphone), CHS-4L Chassis,
DPSW-1B Single-well Dress Panel, and Cable assemblies required to connect to control panel.
JVTCC-1B Voice/Telephone Control Center Basic equipment package for single-channel
audio evacuation system employing a Fire Fighters Telephone system that includes: FFT-7 Fire
Fighters Telephone, AMG-1 Audio Message Generator (with microphone), CHS-4L Chassis,
DPDW-1B Double-well Dress Panel, and Cable assemblies required to connect to control panel.
JTCC-1B Telephone Control Center Basic equipment package for a Fire Fighters Telephone
system with no voice evacuation or paging capabilities that includes: FFT-7 Fire Fighters
Telephone, CHS-4L Chassis, TBP-1B Blank Panels (2), DPDW-1B Double-well Dress Panel, and
Cable assemblies required to connect to control panel.
Descriptions
Audio Message Generator (AMG-1 & AMG-E) Provides a variety of tones and a built-in
microphone allows for paging through speaker circuits. Optionally, you can install up to four
digitally-recorded voice messages into the AMG-1: two factory prerecorded voice messages, two
user-defined messages. You can create both user-defined messages through the AMG-1 built-in
microphone, or download messages from a standard audio cassette recorder.
The AMG-E is an AMG-1 without a microphone. It is used for applications that require multiple
Audio Message Generators.
Fire Fighters Telephone (FFT-7 and FFT-7S) Provides the Voice Alarm System with fire
fighter's telephone capability. With these units, up to seven telephones can be used to hold a
simultaneous conversation. The FFT-7S does not provide paging capability.
Voice Control Module (VCM-4RK) Provides the system with up to four (4) Style Y (Class B)
or Style Z (Class A) speaker circuits, or up to four Style Y (Class B) telephone circuits. Moving a
jumper on the module configures it for driving FFT-7 circuits. When configured for telephone
circuits, the VCM-4RK accepts its signal directly from a Fire Fighters Telephone. Add an optional
Voice Control Expander (VCE-4) to the back of the module to provide four additional telephone or
speaker circuits.
Dual Channel Module (DCM-4RK) Provides the system with the capability to select one of
two types of audio sources for switching to a specified speaker circuit. The module provides up to
four circuits.
Audio Amplifiers The control panel uses three types of audio amplifiers with an installed Voice
Alarm System:
AA-30 Provides up to 30 watts of audio power for driving 25 Vrms speaker circuits.
AA-100 Provides 100 watts of audio power for driving 25 Vrms and 70.7 Vrms speaker
circuits.
AA-120 Provides 120 watts of audio power for driving 25 Vrms speakers.
Each AA amplifies the audio signal coming in from an Audio Message Generator (AMG-1 or
AMG-E).
28 IFC-640 Installation Manual P/N 51864:C 08/05/2005
System Overview Voice Alarm System
Audio Coupling Transformer ACT-1 Couples low-level audio to audio amplifiers or other
audio inputs, such as the AMG-1 Audio Message Generator. Provides Common Mode Noise
Rejection (CMNR), greatly reducing crosstalk from the SLCs. For more information and
installation instructions refer to the Voice Alarm System manual.
Audio Coupling Transformer ACT-2 When used with an AMG-1/-E, RM-1 and AA-30 this
unit provides a means to drive thousands of amplifiers in large audio system applications. The
ACT-2 provides electrical isolation between its input & output and attenuates the signal from
high-level audio to low-level audio. For more information and installation instructions refer to the
ACT-2 Product Installation Drawing.
Additional Devices
The following devices are not part of the Voice Control System, but are listed here for continuity.
Remote Microphone (RM-1 and RM-1SA) Provides paging capabilities to speaker systems
driven by the low level audio source of the AMG-1. The RM-1 assembly can be installed in a
CAB-4 Series backbox, while the RM-1SA is installed in a CAB-RM cabinet. For more
information and installation instructions see the RM-1 Series Remote Microphone installation
document.
Quad Intelligent Audio Transponder - XPIQ See product description on page 23.
IFC-640 Installation Manual P/N 51864:C 08/05/2005 29
Section 3: Installation
3.1 Preparing for Installation
Choose a location for the fire alarm system that is clean, dry, and vibration-free with moderate
temperature. The area should be readily accessible with sufficient room to easily install and
maintain it. There should be sufficient space for cabinet door(s) to open completely.
Carefully unpack the system and inspect for shipping damage. Count the number of conductors
needed for all devices and find the appropriate knockouts. (Refer to Section 3.11 UL
Power-limited Wiring Requirements for selection guidelines.)
Before installing the fire alarm system, read the following:
Review the installation precautions at the front of this manual, including temperature and
humidity limits for the system (Page 3).
All wiring must comply with the National and Local codes for fire alarm systems.
Do not draw wiring into the bottom 9 inches (22.86 cm) of the cabinet except when using a
separate battery cabinet; this space is for internal battery installation.
Review installation instructions in Section 3.2 Installation Checklist.
3.1.1 Standards and Codes
In addition, installers should be familiar with the following standards and codes:
NEC Article 300 Wiring Methods.
NEC Article 760 Fire Protective Signaling Systems.
Applicable Local and State Building Codes.
Requirements of the Local Authority Having Jurisdiction.
C22.1-98 The Canadian Electrical Code, Part 1.
CAN/ULC-S5524-01 Standard for the Installation of Fire Alarm Systems.
!
CAUTION:
Make sure to install system components in the sequence listed below. Failure to do so can damage
the control panel and other system components.
!
WARNING:
This system contains static-sensitive components. Always ground yourself with a proper wrist strap
before handling any circuits. Use static-suppressive packaging to protect electronic assemblies
removed from the unit.
30 IFC-640 Installation Manual P/N 51864:C 08/05/2005
Installation Installation Checklist
3.2 Installation Checklist
Table 3.1 provides an installation checklist for installing, wiring, and testing the IFC-640 system. It
has references to installation information included in manuals listed in Section 1.2 Supplemental
Documentation.
3.3 Mounting a Cabinet
This section provides instructions for mounting an CAB-4 Series backbox to a wall. Follow these
guidelines when mounting the backbox:
Locate the backbox so that the top edge is 66 inches (1.6764 m) above the surface of the
finished floor.
Allow sufficient clearance around cabinet for door to swing freely. (See Section 2.3 System
Cabinets.)
Use the four holes in the back surface of the backbox to provide secure mounting. (See
Figure 3.1.)
Mount the backbox on a surface that is in a clean, dry, vibration-free area.
Seq Task Refer to
1. Mount the cabinet backbox to the wall. Section 3.3 Mounting a Cabinet
2. Install all required chassis in cabinet. Section 3.5 Installing the Control Panel
3. Install control panel onto chassis. Section 3.5.1 Control Panel Circuit Board & Keypad/
Display Unit
4. Optional: Install auxiliary power supply and/or external
battery charger
Auxiliary power manuals
5. Calculate the proper battery rating. Appendix A Power Supply Calculations
6. Connect AC wiring, place batteries into backbox without
connecting them, and run cable to optional power supplies,
DC power outputs, NACs, and relays.
CAUTION: Do not apply AC or DC power at this time.
Section 3.6 Connecting the Power Cables
7. Set switches for backup alarm (SW6-SW9). Section 3.9 Backup-Alarm Switches
8. Optional: Install and wire Auxiliary Relay Module (ARM-4). Section 3.13 Auxiliary Relay Module (ARM-4):
Product-Specific Details
9. Optional: Install Panel Circuit Modules (ICM-4RK,
CRM-4RK, VCM-4RK, DCM-4RK) and Voice Alarm System
components (AMG-1, FFT-7, Audio Amplifiers)
Section 3.12 Installing Panel Circuit Modules, and Voice
Alarm System Manual
10. Optional: Install output devices such as a printer, or CRT
terminal.
Section 3.14 Installing Remote Printers and/or CRT
11. Optional: Install JNCA or IFW. JNCA Manual or IFW Manual
12. Secure any unused mounting holes in control panel circuit
board.
Figure 3.4
13. Wire the Signaling Line Circuits. Section 3.15 Wiring a Signaling Line Circuit (SLC)
14. Connect wire shielding as instructed. SLC Wiring Manual
15. Apply AC power to the control panel by placing the external circuit breaker to the ON position.
Do NOT connect batteries.
16. Check AC power. Table 3.3 in Section 3.6 Connecting the Power Cables
17. Connect the batteries using interconnect cable, P/N 75560 and 75561.
18. Install the CAB-4 series door. CAB-3/CAB-4 Series
Cabinet Installation Document
19. Program the control panel. IFC-640 Programming Manual.
20. Field test the system. Section 5 Testing the System
Table 3.1 Installation Checklist
!
CAUTION:
Unless you are familiar with the placement of components within this backbox, only use the knockout
locations provided for conduit entry.
IFC-640 Installation Manual P/N 51864:C 08/05/2005 31
Laying Out Equipment in Cabinet and Chassis Installation
Follow the instructions below.
1. Mark and pre-drill holes for the top two keyhole mounting bolts (0.25 inch, 0.635 cm). Use
mounting hardware appropriate for the mounting surfaces; see UL 2017 Pull-Test
Requirements.
2. Select and punch open the appropriate knock-outs. (For selection guidelines, see Section 3.11
UL Power-limited Wiring Requirements.)
3. Using the keyholes, mount the backbox over the two screws.
4. Mark the location for the two lower holes, remove the backbox and drill the mounting holes.
5. Mount the backbox over the top two screws, then install the remaining fasteners. Tighten all
fasteners securely.
6. Feed wires through appropriate knockouts.
7. Install control panel and other components according to Section 3.5 Installing the Control
Panel before installing hinges and door according to CAB-3/CAB-4 Series Cabinet
Installation Document.
3.4 Laying Out Equipment in Cabinet and Chassis
The IFC-640 allows for flexible system design. Follow these guidelines when deciding where to
locate equipment in the backbox.
The first row of equipment mounts in chassis CHS-M2. Mount second, third, or fourth rows of
equipment in chassis CHS-4N (panel circuit modules, see Section 3.12 Installing Panel Circuit
Modules), or in chassis CHS-4L (voice components, see the Voice Alarm System Manual). Some
equipment, such as the JNCA and annunciators, may be door-mounted; refer to the equipments
documentation for instructions.
There are four basic positions available on a chassis (side-by-side); the number of modules that can
be mounted in each position depends on the chassis model and the module size.
The CHS-M2 accepts four layers of equipment, including the control panel. The control panel fills
three positions in the first-installed layer, its integral power supply occupies two positions in the
next two layers, and the optional display occupies the two left-most slots in the fourth layer (flush
with the door). Panel circuit modules and other modules of the same sizing can be mounted in
several layers, depending on the desired configuration; see Table 3.2 to determine hardware. Some
equipment, such as the JNCA, may be door-mounted directly in front of the control panel. The
BMP-1 Blank Module Plate covers unused positions in a dress-panel, providing another mounting
location for some modules, such as TM-4 (see BMP-1 Product Installation Drawing for details).
Keyholes
2 places
Mounting holes
2 places
CAB-4
Series
Backbox,
A-size
(one-row)

n
f
s
6
4
0
c
a
b
i
n
e
t
m
o
u
n
t
i
n
g
h
o
l
e
s
.
c
d
r
CAB-4
Series
Backbox,
D-size
(four-row)
Figure 3.1 Mounting Holes of a Backbox
32 IFC-640 Installation Manual P/N 51864:C 08/05/2005
Installation Laying Out Equipment in Cabinet and Chassis
n
f
s
6
4
0
-
c
h
s
-
m
2
-
1
1
-
0
3
.
w
m
f
Panel circuit module mounted
on flanges above control panel
Available mounting slots for
panel circuit modules, TM-4,
and NCM-W/F.
Typical mounting location
for NCM-W/F or TM-4
Mounting location
for LEM-320
KDM-2
Figure 3.2 Equipment Mounting Locations (First-Row Chassis CHS-M2)
NOTE: When designing the cabinet layout, consider separation of power-limited and
non-power-limited wiring as discussed in Section 3.11 UL Power-limited Wiring Requirements.
From To Required Stand-off or Hardware
Chassis CHS-M2 Control panel or
module on first layer
Not applicable; integral to the chassis.
Control panel or
Option board, 1st layer
Option board, 2nd layer
(includes LEM-320)
4 male-female stand-offs of length 0.937 inch (23.8 mm) P/N 42166.
Option board, 2nd layer Option board, 3rd layer 4 male-female stand-offs of length 0.937 inch (23.8 mm) P/N 42166.
Chassis Option board, 4th layer
(flush with door)
Attaches directly to flanges on chassis. (Screws provided with option
boards & panel circuit modules)
Chassis Panel circuit module
(flush with door)
Attaches directly to flanges on chassis. (Screws provided with option
boards & panel circuit modules)
Control panel KDM-2 (upper edge) 2 stacks of male-female stand-offs:
P/N 42185 (2.0 inch, 50.8 mm) and
P/N 42186 (1.312 inch, 33.33 mm)
Chassis rail KDM-2 (lower edge) 2 male-female stand-offs of length 0.937 inch (23.8 mm) P/N 42166.
Dress panel
DP-DISP or ADP-4B
JNCA Attaches directly to dress panel.
(Nuts provided with JNCA.)
Dress panel
DP-DISP or ADP-4B
Option board BMP-1 attaches to dress panel; option module attaches to BMP-1
(screws provided with option module).
Note: The initial release of chassis CHS-M2 used L-brackets and stand-offs of different lengths than the current model; refer to
Doc. 51864, Rev A.
Table 3.2 Stand-off Lengths
IFC-640 Installation Manual P/N 51864:C 08/05/2005 33
Installing the Control Panel Installation
3.5 Installing the Control Panel
3.5.1 Control Panel Circuit Board & Keypad/Display Unit
The control panel mounts in chassis CHS-M2, which is usually positioned in the top row of the
backbox. The control panels CPU occupies three positions at the back of the chassis; the KDM-2
occupies two positions flush with the door. The JNCA may be door-mounted directly in front of the
control panel if no KDM-2 is being used; see the JNCA Manual for details and restrictions.
1. Verify height of the mounting stud in the backbox. In older backboxes, the stud must be
shortened to prevent damage to the JCPU-640. All electronics must be removed from the
backbox before shortening. See instructions in the warning below.
2. Screw chassis to the backbox.
3. Attach JCPU-640 to the chassis. Slide control-panel tabs into slots on chassis and lay the
board onto stand-offs so that mounting holes line up with those on the chassis. Secure with
six (6) screws (four across the top of the board, and two to the left of the power supply)
provided with the chassis. (See Figure 3.4.)
NOTE: For initial release of IFC-640, mounting instructions were different. Refer to the
installation manual shipped with the panel (Rev A).
!
WARNING:
For retrofit applications, verify the height of the backboxs mounting stud on left side under CPU, as
shown in Figure 3.3 below. Stud height must not exceed 0.375 in. (9.525 mm). Early versions of the
CAB-4 Series backboxes and all CAB-3 Series backboxes have studs that require shortening.
Failure to shorten this 0.625 in. (15.875 mm) mounting stud will cause damage to the control panels
CPU. Remove electronics from backbox, permanently mount empty CHS-M2 chassis to backbox,
apply nut to mounting stud to protect threading, then cut stud to proper length. Reinstall electronics
as discussed in the steps below.
!
WARNING:
Do not cut without washers and nuts in place to protect threading. Wear protective eye covering.
If using a new CHS-M2 in a CAB-3
series backbox or in a CAB-4 series
backbox manufactured before October
2002, verify stud height and cut any stud
that exceeds 0.375 in. (9.525 mm) as
per Step 1 above if a CPU is being
mounted above it. Reinstall electronics
as discussed in the steps below.
C
H
S
-
M
2
-
1
1
-
0
3
-
C
A
B
-
3
.
w
m
f
Figure 3.3 Using the Redesigned CHS-M2 with Older Backboxes
34 IFC-640 Installation Manual P/N 51864:C 08/05/2005
Installation Installing the Control Panel
4. If installing KDM-2, install the stand-offs included with the keyboard kit. (See Figure 3.4.)
The upper edge of the keyboard mounting plate rests on two stacked pairs of male-female
stand-offs. Connect P/N 42185 (2.0 inch, 50.8 mm) to P/N 42186 (1.312 inch, 33.33 mm).
Thread the stacked pairs of stand-offs through mounting holes on the control panel as shown in
Figure 3.4.
Thread two P/N 42166 (0.937 inch, 23.8 mm) male-female stand-offs through mounting holes
in the chassis rail.
Attach ribbon cable from keypad to J4 connector on control panel. (See Figure 2.3.)
Align the keypad with the stand-offs and screw it down.
5. If using the JNCA instead of the KDM-2, refer to Section 3.5.2 Using JNCA as Primary
Display and the JNCA Installation Manual.
6. If not using an LEM-320, secure the last 4 mounting holes with screws.

3.5.2 Using JNCA as Primary Display
The IFC-640 can be set up to use a JNCA instead of a KDM-2. In this system design, connect the
network/service port on the IFC-640 (J1) directly to the network/service port on the JNCA (J3); see
the JNCA Manual for specific instructions.
If the IFC-640 and JNCA are being used as a stand-alone pair, each device must be programmed
separately using VeriFire Tools in its off-line programming mode. Because the VeriFire Tools
computer also uses the network/service port, IFC-640 and JNCA must be temporarily disconnected
!
CAUTION:
It is critical that all mounting holes of the IFC-640 are secured with a screw or standoff to insure
continuity of Earth Ground.
Stack of two male-female stand-offs:
connect P/N 42185 (2.0 inch, 50.8 mm)
to P/N 42186 (1.312 inch, 33.33 mm).
Note: If not using this location,
secure these mounting holes
with screws.
Attach two (0.937 inch, 23.8 mm) stand-offs
to chassis rail; screw keypad mounting
plate to the stand-offs.
Lower edge of panel circuit modules slide into chassis slots,
and upper edge mounts onto PEM studs on the chassis flange.
C
H
S
-
M
2
-
0
6
0
4
-
a
s
s
y
.
w
m
f
Figure 3.4 Locating and Aligning Stand-offs for Keypad/Display and Panel Circuits
(Chassis CHS-M2 shown)
NOTE: This system design is required in Canadian stand-alone applications.
IFC-640 Installation Manual P/N 51864:C 08/05/2005 35
Installing the Control Panel Installation
for programming. If the IFC-640 with JNCA is connected to a network, there are two additional
options for programming: either connect the VeriFire Tools programming PC to the network port
on the NCM board, or program the IFC-640 through another network node. (See VeriFire Tools
on-line help for details.)
3.5.3 Loop Expander Module
Installing a Loop Expander Module adds a
second SLC loop to the control panel. Refer
to the Figure 3.6 for connector illustrations.
1. Thread four (4) 0.937 inch (23.8 mm)
stand-offs through indicated holes in the
JCPU-640 board.
2. Plug stacker-connector into J3 on the
JCPU-640.
3. Lay the LEM onto the standoffs and
connect the Loop Expander Module
(LEM) into the stacker-connector
attached to J3.
4. Attach LEM using screws provided with
the module.
5. After LEM is mounted on the control
panel, connect the SLC loops to TB1 on
the LEM and TB16 on the JCPU-640.
This system supports either FlashScan or
CLIP mode devices. Refer to the SLC
loop manual for wiring requirements and specific details.
J1
B+ A+ B- A-
LEM-320PCA
T
B
1
B+ A+ B- A-
T
B
1
L
e
m
-
s
l
c
.
c
d
r
Figure 3.5 SLC Connections for LEM-320
36 IFC-640 Installation Manual P/N 51864:C 08/05/2005
Installation Installing the Control Panel
3.5.4 Network Control Module
If networking two or more control panels (including JNCAs), each unit requires a Network Control
Module (NCM); wire and fiber versions are available. The NCM-W/F can be installed in any panel
circuit module position (see Section 3.5.5 Panel Circuit Modules and Other Option Boards); the
default position is immediately to the right of the control panel.
1. Mount the NCM in the selected position. If another board is going to be mounted in the slot
immediately in front of it, use stand-offs provided with the next board to secure it in place.
Otherwise use the screws provided with the NCM.
2. Connect J1 on the control panel to J3 on the NCM using the network cable provided (P/N
75556) as described in the NCM Installation Document. Do not connect two NCMs via NUP
ports (aka NUP to NUP).
3. Connect Channel A and/or Channel B as described in the NCM Installation Document.
JCPU-640
Stacker-connector
LEM-320
J1
J3
The long-pin end
plugs into the back
of the LEM board.
The short-pin end plugs
directly into the top of the
JCPU-640 plug.
!
CAUTION:
If the stacker-connector is installed incorrectly, the short-pin end of the plug can fail to make a secure
connection when plugged through the back of the LEM.
Figure 3.6 Mounting LEM-320 with the Stacker-connector
NOTE: See the NotiFireNet Manual and NCM Installation Document for wiring diagrams and
system configuration information. See the BMP-1 Product Installation Drawing if considering
mounting the module behind blank module plate in a dress plate or annunciator backbox.
IFC-640 Installation Manual P/N 51864:C 08/05/2005 37
Installing the Control Panel Installation
3.5.5 Panel Circuit Modules and Other Option Boards
If installing option boards into a CAB-4 Series backbox, mount and connect those boards at this
time. General instructions follow; the sections about individual option boards contain any
module-specific instructions. Option boards can be mounted in the front (fourth) layer of CHS-M2
(see flanges as shown in Figure 3.4), or in any position on the other row(s) of equipment, using
0.937" (23.8 mm) standoffs between layers.
1. Slide the tabs at the bottom of the option board into slots on the chassis as shown in Figure 3.7.
2. Lay the board back onto the flanges so that the studs line up with mounting holes on the option
board.
3. Attach the option board using screws provided with the module.

NOTE: An option board can be mounted above a Loop Expander Module or Network Control
Module; for ease of access, be sure to complete installation of those devices before mounting a
second layer.
NOTE: See the BMP-1 Product Installation Drawing for details if considering mounting the
module behind blank module plate in a dress plate or annunciator backbox. This dress plate is
suitable for modules that do not need to be visible or accessible when the door is closed.
n
f
s
6
4
0
-
m
n
t
i
c
m
.
c
d
r
Shown with CHS-M2
Module
Screw
Slots
Shown with CHS-4N
Figure 3.7 Inserting a Module into a Chassis
38 IFC-640 Installation Manual P/N 51864:C 08/05/2005
Installation Connecting the Power Cables
3.6 Connecting the Power Cables
3.6.1 Overview
Complete all mounting procedures and check all wiring before applying power. Electrical
connections include the following:
Primary AC power source 120 VAC, 50/60 Hz, 3.0 A (IFC-640E uses 240 VAC, 50/60 Hz,
1.5 A) from line voltage source. Overcurrent protection for this circuit must comply with
C
H
S
-
4
s
t
u
d
p
o
s
.
c
d
r
Install stand-offs on these
two (2) studs in any one of
four positions along chassis.
Chassis CHS-4N
Figure 3.8 Location of Stand-offs on Module Chassis
!
WARNING:
Remove all power sources to equipment while connecting electrical components. Leave the
external, main power breaker OFF until installation of the entire system is complete.
!
WARNING:
Several sources of power can be connected to the control panel. Before servicing the control panel,
disconnect all sources of input power including the battery. While energized, the control panel and
associated equipment can be damaged by removing and/or inserting cards, modules, or
interconnecting cables.
Single-space
blank plate
Fasten optional module to
the plate with four screws
(included).
t
m
4
a
d
p
4
.
c
d
r
Mount optional module
onto standoffs on the
blank plate
Mount single-space blank plate
onto compatible dress panel or
backbox trim ring
Figure 3.9 Mounting Single-space Blank Plate with Optional Module
IFC-640 Installation Manual P/N 51864:C 08/05/2005 39
Connecting the Power Cables Installation
Article 760 of the National Electrical Code (NEC) and/or local codes. Use 12 AWG (3.1 mm
2
)
wire (maximum) with a 600-volt rating.
Secondary power source 24 VDC from batteries, installed in the control panel (or in an
optional battery cabinet). Secondary (battery) power is required to support the system during
loss of primary power.
External power sources 24 VDC power for Smoke Detectors (4 wire), NACs, and
Annunciators.
See Appendix B Electrical Specifications for details and overall installation guidelines.
3.6.2 Connecting the Control Panel to AC Power
Connect primary power as follows (see Figure 3.10 below):
1. Turn off the circuit breaker at the main power distribution panel.
2. Remove the plastic insulating cover from TB2.
3. Connect the service ground to terminal marked EARTH.
4. Connect the primary neutral line to terminal marked NEUTRAL and the primary Hot line to
terminal marked HOT.
5. Reinstall the plastic insulating cover over TB2.

3.6.3 Checking AC Power
Table 3.3 contains a checklist for checking the system with AC power applied:
E
A
R
T
H
H
O
T
N
E
U
T
R
A
L
B
A
T
T

B
A
T
T
+
TB1
TB2
n
f
s
6
4
0
-
a
c
d
c
.
c
d
r
Hot
Neutral
Ground
(Earth)
Battery (-)
Battery (+)
Figure 3.10 AC & DC Power Connections
!
CAUTION:
While checking AC power, make sure batteries are not connected.
Follow the sequence of steps in Section 3.2 Installation Checklist, Table 3.1; this is Step 16.
Component Status
Control panel circuit
board
The green AC Power indicator on; the system Trouble indicator on because batteries are not connected.
Each panel circuit
module
The yellow Trouble indicator may come on for approximately 10 seconds after applying AC power. (This
only applies to an unconfigured system.)
Each auxiliary power
supply
The yellow Trouble indicator comes on because batteries are not connected.
Table 3.3 AC Power Checklist
40 IFC-640 Installation Manual P/N 51864:C 08/05/2005
Installation Connecting the Power Cables
3.6.4 Installing and Connecting the Batteries
Batteries (2) are installed in the control panel cabinet or in a separate battery cabinet which can be
mounted below the control panel or up to 20 feet (6.096 m) away from the control panel, in the
same room.
Connect the battery as follows (see Figure 3.10 above):
1. Install batteries (2) into bottom of cabinet or into separate battery cabinet.
2. Connect the red cable from TB1(+) on the control panel to the positive (+) terminal of one
battery.
3. Connect the black cable from TB1() on the control panel to the negative () terminal of the
other battery.
4. Connect the remaining cable between the negative (-) terminal on the first battery to the
positive (+) terminal on the second battery.
3.6.5 APS-6R Auxiliary Power Supply Connections
If an optional APS-6R power supply is installed in the cabinet, connect it with no power applied;
follow sequence of steps in Section 3.2 Installation Checklist, Table 3.1; this is Step 4. For all
information pertaining to these connections see the APS-6R Instruction Manual.
3.6.6 External DC Power Output Connections
Terminal TB7 provides two (2) power outputs, resettable and non-resettable. Each output is
power-limited. Follow sequence of steps in Section 3.2 Installation Checklist, Table 3.1; this is
part of Step 6.

24 VDC Resettable Power Circuit (Four-Wire Smoke Detectors). The power supply
provides a single 24 VDC filtered, power-limited, resettable power circuit for devices that require
resettable power (such as four-wire smoke detectors). This circuit is power-limited, but must be
supervised. To provide supervision, install a UL-listed end-of-line power supervision relay (such as
the EOLR-1) after the last device. Connect the power supervision relay normally open contact in
!
w
WARNING:
Battery contains sulfuric acid which can cause severe burns to the skin and eyes, and can destroy
fabrics. If contact is made with sulfuric acid, immediately flush skin or eyes with water for 15 minutes
and seek immediate medical attention.
!
WARNING:
Do not connect the Battery Interconnect Cables (P/N 75560 and 75561) at this time. Make this
connection AFTER initial system primary powerup. Follow sequence of steps in Section 3.2
Installation Checklist, Table 3.1; this is Step 17.
+ +
T
B
7
Non-resettable
Power
n
f
s
6
4
0
-
d
c
o
u
t
.
c
d
r
Resettable
Power
Figure 3.11 Power Supply DC Outputs - TB7
IFC-640 Installation Manual P/N 51864:C 08/05/2005 41
NAC Connections & Releasing Circuits Installation
series with an Initiating Device Circuit (IDC). The four-wire power circuit energizes the power
supervision relay. When you reset the system, the control panel removes power from these
terminals for approximately 15 seconds.
Connect external field wires to the power supply terminals TB7 RESET(+) and () to provide up to
1.25 A of current for powering four-wire smoke detectors. See Figure 3.11 above.
24 VDC Non-resettable Power Circuit. The power supply provides one 24 VDC filtered,
power-limited, non-resettable power output, capable of up to 1.25 A. Use this circuit to power
devices that require low-noise 24 VDC power (such as annunciators or the TM-4).
Connect external field wires to power supply terminals TB7 NONRST(+)and() to provide up to
1.25 A of non-resettable current for powering external devices such as annunciators. See
Figure 3.11 above.
3.7 NAC Connections & Releasing Circuits
The control panel provides four NAC terminals as shown in Figure 3.12. Each can be configured as
Style Y (Class B) or Style Z (Class A) as shown in Figure 3.13. Each circuit can provide 2.5 A of
current, but the total current drawn from the main power supply cannot exceed 6.0 A in alarm
condition (refer to Table A.2). NAC circuits are supervised and power-limited. Use UL-listed
24 VDC notification appliances only (refer to the Device Compatibility Document).

!
CAUTION:
During system reset, power remains at terminals TB7 NONRST(+)and().
B
+
B
-
A
+
A
-
B
+
B
-
A
+
A
-
B
+
B
-
A
+
A
-
B
+
B
-
A
+
A
-
Figure 3.12 NAC Terminals
TB6 - NAC#1
TB5 - NAC#2
TB4 - NAC#3
TB3 - NAC#4
n
f
s
6
4
0
-
N
A
C
S
.
c
d
r
B+ B A+ A B+ B A+ A B+ B A+ A
n
f
s
6
4
0
-
n
a
c
o
u
t
.
c
d
r
Style Y (Class B)
Connection
Style Z (Class A)
Connection
Unused Circuits
UL-listed ELR-2.2K,
1/2 W (supplied)
Figure 3.13 Notification Appliance Circuit
Connections
NOTE: Any NAC can be programmed as a releasing circuit, but only one releasing device
per circuit is allowed. For more information, refer to Section 4.5 Releasing Applications in this
manual and the IFC-640 Programming Manual. Refer to the Device Compatibility Document for
UL-listed compatible releasing devices. Sample connections for NAC terminals are shown in
Figure 3.13. Follow sequence of steps in Section 3.2 Installation Checklist, Table 3.1; this is part
of Step 6.
42 IFC-640 Installation Manual P/N 51864:C 08/05/2005
Installation Output Relay Connections
3.8 Output Relay Connections
The panel provides a set of Form-C relays. These are rated for 2.0 A at 30 VDC (resistive):
Alarm - TB8
Trouble - TB9
Supervisory - TB10
Security - TB11
The Supervisory and Security contacts can also be configured as Alarm contacts by setting
switches SW1 and SW5 away from the factory default positions shown in Figure 3.14. Follow
sequence of steps in Section 3.2 Installation Checklist, Table 3.1; this is part of Step 6.
3.9 Backup-Alarm Switches
Backup alarm switches are provided that enable NACs
and the alarm relay to activate during a backup alarm
condition. If the main boards microcontroller fails and
an alarm is reported by any detector or a monitor
module that has backup reporting enabled, the NAC
will turn on if the corresponding switch was enabled.
The alarm will activate during microcontroller failure
regardless of the settings of Switch 6-9.
Switch 6 - NAC#1
Switch 7 - NAC#2
Switch 8 - NAC#3
Switch 9 - NAC#4
So, for example, if Switch 6 and Switch 8 were enabled at the time of an alarm during
microcontroller failure, NAC#1 and NAC#3 would activate. Follow sequence of steps in Section
3.2 Installation Checklist, Table 3.1; this is Step 7.
!
WARNING:
Do not enable the BACKUP option switch for any of the four Notification Appliance Circuits (NACs) if
they are used for releasing functions!
ALARM RELAY
NO NC C
TROUBLE RELAY
NO NC C
SUPERVISORY RELAY
NO NC C
SECURITY RELAY
NO NC C
TB8 TB9 TB10
T
B
1
1
SW1 SW5
SUPV ALARM SECUR ALARM
SW1 is set to Supervisory
SW5 is set to Security
Move switch to opposite
position to set to Alarm.
n
f
s
6
4
0
-
r
e
l
a
y
.
c
d
r
Figure 3.14 Form-C Relay Connections
Figure 3.15 Backup Alarm
Switches
S
W
6
NAC
S
W
7
E
N
A
B

D
I
S
A
B
S
W
8
S
W
9
1 3
2 4
n
f
s
6
4
0
-
s
w
6
-
9
.
c
d
r
IFC-640 Installation Manual P/N 51864:C 08/05/2005 43
Installing a Transmitter Module TM-4 Installation
3.10 Installing a Transmitter Module TM-4
TM-4 is power-limited. Connections are on TB7 nonresettable output and TB13 EIA-485 ACS
Mode. Refer to the Transmitter Module TM-4 installation document for installation details.
3.11 UL Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All
power-limited circuit wiring must remain at least 0.25 inches (6.35 mm) from any
nonpower-limited circuit wiring. All power-limited and nonpower-limited circuit wiring must enter
and exit the cabinet through different knockout and or conduits. To maintain separation, group
non-power limited modules together, i.e., group modules on the same side of the enclosure or in
separate rows.
Figure 3.16 shows one configuration that meets these UL requirements. The first two rows of
modules are configured with at least a 0.25 inch (6.35 mm) separation between power-limited and
nonpower-limited wiring; AC and battery wiring is routed away from power-limited wiring.
3.11.1 Labeling Modules and Circuits
At the time of installation, each nonpower-limited circuit connected to ACM-8R, ARM-4,
CRM-4RK, CRE-4, and LDM-R32 modules must be identified in the space provided on the cabinet
door label when connected to a non-power-limited source of power.
The label lists all compatible power-limited modules and circuits; also see Figure 2.3 at the start of
this manual.
The following devices are power-limited only when connected to power-limited sources: ARM-4,
CRM-4RK, CRE-4, LDM-R32. When one of these devices is connected to a non-power-limited
source, the power-limited marking must be removed.
Power-limited Circuits
Power-limit
ed
circuits
Nonpower-
limited
circuits
n
f
s
6
4
0
-
p
w
r
l
m
t
w
i
r
.
c
d
r
To cabinet-mounted battery
Figure 3.16 Typical Wiring for UL Power-limited Wiring Requirements
NOTE: AC and battery wiring are not power-limited. Maintain at least 0.25 inches (6.35 mm)
between power-limited and non power-limited circuit wiring. Install tie wraps and adhesive squares
to secure the wiring. Use a power-limited source for relay output on terminals TB8 TB11.
44 IFC-640 Installation Manual P/N 51864:C 08/05/2005
Installation Installing Panel Circuit Modules
3.12 Installing Panel Circuit Modules
3.12.1 Overview
Installation of a panel circuit module is divided into five (5) operations:
Mounting an optional expander board to the module (e.g. mounting ICE-4 onto an ICM-4RK).
Connecting communication ribbon cables from Control Panel to the module.
Installing the module onto a chassis.
Connecting modules to the power supply.
Field wiring the module.
Refer to Section 2.10 Panel Circuit Modules for a complete list of modules and their expanders.
3.12.2 Mounting Expander Boards
Expander Board Modules, such as ICE-4 or CRE-4, need to be mounted onto their respective
modules (ICM-4RK, CRM-4RK) prior to installation onto a chassis. Figure 3.17 illustrates the
steps to mount an Expander Module:
1. Remove one module support screw and set it aside for later use.
2. Replace the module support screw with one module stand-off.
3. Repeat Steps 1 and 2 for the three remaining module support screws.
4. Insert pins on the front of the expander board into connector on the back of the module. Make
sure the pins are in line; then, press the two units together until they snap into place.
5. Install the four module support screws (removed earlier) through the back of the expander
board and into the stand-offs. Tighten securely.

Install module
stand-off
Remove existing
module support
screw
Plug in the expander board
Secure with module
support screws
n
f
s
6
4
0
-
p
c
m
o
d
s
.
c
d
r
Steps 1 & 2
Steps 4 & 5
Figure 3.17 Expander Module Installation
IFC-640 Installation Manual P/N 51864:C 08/05/2005 45
Installing Panel Circuit Modules Installation
3.12.3 Connecting Ribbon Cables for a CAB-4 Series Backbox
Expander Row Ribbon Cables connect panel circuit modules to the Control Panel.
Figure 3.18 shows a typical wiring setup using two Expander Row Ribbon Cables (P/N 71088) to
connect the control panel to two rows of four (4) panel circuit modules each below the Control
Panel in a CAB-4 Series backbox.
3.12.4 Installing the Panel Circuit Modules
To install a panel circuit module such as a ICM-4RK or CRM-4RK into the chassis:
1. Angle the module into the chassis so that the lower board edge slips into the chassis slots as
shown in Figure 3.7.
2. Push the upper end of the module into the upper opening in the chassis.
3. Secure the module to the chassis with the two module screws (provided with the module).
Tighten securely.
4. Connect the Ribbon Cable to the module.
MODULE
TYPE
LAMPS
SWITCH
MODULE
TYPE
LAMPS
SWITCH
MODULE
TYPE
LAMPS
SWITCH
MODULE
TYPE
LAMPS
SWITCH
MODULE
TYPE
LAMPS
SWITCH
MODULE
TYPE
LAMPS
SWITCH
MODULE
TYPE
LAMPS
SWITCH
MODULE
TYPE
LAMPS
SWITCH
MODULE
TYPE
LAMPS
SWITCH
MODULE
TYPE
LAMPS
SWITCH
MODULE
TYPE
LAMPS
SWITCH
MODULE
TYPE
LAMPS
SWITCH
MODULE
TYPE
LAMPS
SWITCH
MODULE
TYPE
LAMPS
SWITCH
MODULE
TYPE
LAMPS
SWITCH
MODULE
TYPE
LAMPS
SWITCH
P1.1P1.8 P2.1P2.8 P3.1P3.8 P4.1P4.8
n
f
s
6
4
0
-
i
c
m
r
i
b
b
o
n
.
c
d
r
Expander Row Ribbon Cable (P/N 71088)
Expander Row Ribbon Cable (P/N 71088)
Group of panel
modules in third
cabinet row
J5 - Second Row
P5.1P5.8 P6.1P6.8 P7.1P7.8 P8.1P8.8
J6 - Third Row
Group of panel
modules in second
cabinet row
Figure 3.18 Expander Row Ribbon Cable Setup
46 IFC-640 Installation Manual P/N 51864:C 08/05/2005
Installation Installing Panel Circuit Modules
3.12.5 Connecting ICM-4RK and ICE-4 Modules
The total current available for any group of Notification Appliance Circuits (NACs), other than the
four NACs on the control panel, cannot exceed the following:
6.0 A when powered from the APS-6R
1.25 A when powered from a IFC-640 DC power output terminal
Figure 3.19 shows the wire connectors on the bottom of the ICM-4RK and the ICE-4 modules.
Power Supply Connections
Figure 3.20 illustrates typical connections from main power supply.
Multiple Power Supplies
Cut JP1 and JP2 on ICM-4RK when supplying 24V power from two separate sources to the
ICM-4RK. ICM-4RK circuits 1-2 will receive their power from J5; ICM-4RK circuits 3-4 will
receive their power from J6.
Cut JP1 and JP2 on ICE-4 when supplying power from separate sources to expander circuits 5-8.
ICM-4RK circuits 5-6 will receive power from J5 on the ICE-4 and ICM-4RK circuits 7-8 will
receive power from J6 on the ICE-4.
See Figure 3.21 for jumper locations.
n
f
s
6
4
0
-
i
c
m
c
o
n
n
.
c
d
r
ICM-4RK
ICE-4
J5
J6
J5
J6
Figure 3.19 ICM-4RK/ICE-4 Connectors
J5
ICM-4
J6
ICE-4
J5
T
B
7
24V 24V RESET NONRST
+ +
Power Cable P/N 71091
n
f
s
6
4
0
-
i
c
m
n
a
c
.
c
d
r
Eight NACs that
share 1.25 A
TB7 on Control Panel
Bell power cable (P/N 75400) or
alternate Power Harness (P/N 71093, with
lugs removed and wires stripped)
Black wire (), Blue wire (+)
Figure 3.20 Main Power Supply Connection
IFC-640 Installation Manual P/N 51864:C 08/05/2005 47
Installing Panel Circuit Modules Installation
3.12.6 Field-Wiring the ICM-4RK and ICE-4 (NFPA Style Y or Z)
Guidelines for field-wiring:
Notification Appliance Circuits (NACs) are supervised, power-limited, and can connect to an
energy-limited cable.
Use only the compatible, UL-listed notification appliances listed in the Device Compatibility
Document.
Wire notification appliances according to the manufacturer's instructions.
Maximum current per circuit is 3.0 A. Maximum current per module depends on the type of
power supply (standard or auxiliary).
Canadian installations require model N-ELR End-of-Line Resistor Assembly (Style Y only).
Size NAC wiring so the voltage drop does not exceed the minimum rated voltage of the
notification appliance used as the last device on the circuit.
For zone coded applications, refer to the UZC-256 Universal Zone Coder manual.
The ICM-4RK is California Code programmable (microprocessor P/N 34077 Rev. B or
higher). To program for California Code, cut diode D35 as shown in Figure 3.23. (See
appendix section of the Programming Manual for more detail.)
ICM-4RK/ICE-4 Jumpers
APS-6R #1
APS-6R #2
J6
J5
JP1
JP2
ICM-4RK
J6
J5
Two circuits that
share 3 A of one
APS-6R (#1)
Two circuits that
share 3 A of one
APS-6R (#2)
Figure 3.21 Sample ICM-4RK Configuration for Multiple Power Supplies
B+ A+ A B B+ A+ A B B+ A+ A B B+ A+ A B
Jumpers for
unused circuits
4.7K,
1/2 watt ELR
P/N 71252
UL-listed 24 VDC
Polarized Devices
I
C
M
4
w
i
r
e
-
Y
B
.
c
d
r
Typical NFPA
Style Z (Class A) NAC
Typical NFPA
Style Y (Class B) NAC
Jumpers for
unused circuits
Figure 3.22 Field-Wiring an ICM-4RK/ICE-4
48 IFC-640 Installation Manual P/N 51864:C 08/05/2005
Installation Installing Panel Circuit Modules
3.12.7 Connecting CRM-4RK/CRE-4 Modules
Guidelines for field-wiring the CRM-4RK and the CRE-4:
Form-C relay contacts (silver alloy) used for medium duty switching or pilot duty.
Terminals will accept wire sizes from 12 AWG to 18 AWG (3.1 to 0.78 mm
2
).
Activation of a module or expander relay occurs automatically when an alarm is detected on a
programmed IDC.
UL contact ratings are 5 A at 125 VAC (resistive) or 30 VDC (resistive) and 2 A at 125 VAC
(inductive).
For more information, refer to Section 3.11 UL Power-limited Wiring Requirements.
For typical field-wiring connections, refer to Figure 3.24.
Cut D35 on the circuit board to
produce California code.
i
c
m
-
4
r
k
-
d
3
5
.
c
d
r
Figure 3.23 Location of D35 on ICM-4RK Circuit Board
CONTROL
RELAY
CONTROL
RELAY
Optional CRE-4 Control
Relay Expander
C
R
E
E
X
P
C
O
-
R
K
.
c
d
r
CRM-4RK
Typical connections for a
Form-C control relay in
normal position.
Figure 3.24 Field-Wiring a CRM-4RK or CRE-4 Module
IFC-640 Installation Manual P/N 51864:C 08/05/2005 49
Auxiliary Relay Module (ARM-4): Product-Specific Details Installation
3.13 Auxiliary Relay Module (ARM-4): Product-Specific
Details
3.13.1 Overview
If a CRM-4RK/CRE-4 is to be incorporated into the control panel and an ARM-4 is being driven by
it, note the following:
Each ARM-4 must be supported by one CRM-4RK or one CRE-4.
If using ARM-4s for both modules, mount two ARM-4s in separate positions.
If mounted in FACP enclosure keep all non-power limited wiring separate from power limited
wiring.
For ease of installation, service, and wiring mount the ARM-4 module in a position on the chassis
that will not have any other module or expander board in front of it. However, you can install the
ARM-4 directly behind the CRM-4RK or CRE-4.
ARM-4 mounts in the second, third or fourth row of a CAB-4 series backbox, against the back of a
chassis CHS-4 or CHS-4L. The ARM-4 may be mounted in any of the 8 adjacent backbox
positions the cable can reach.
3.13.2 Installation
To install the Auxiliary Relay Module in the chassis:
Select a mounting position for the module on the chassis.
Install two (2) mounting stand-offs onto the studs of the chassis, at the selected location, as
shown in Figure 3.8 on page 38 and Figure 3.25. Tighten securely.
Install three (3) support stand-offs, with screws, onto the PC board in the locations shown in
Figure 3.8 or in the two right-hand positions on the first row. Tighten securely.
Position module over the stand-offs on the chassis; fasten the module to the chassis with the
two (2) retaining screws. Tighten securely.
Connect one end of the Cable (P/N 71092) to plug P1 on the ARM-4.
Note: The other end of the cable is connected to jumper JP5 on the CRM-4RK or CRE-4.
Connect all available external wiring at this time. Refer to Section 3.13.3 Field Wiring an
Auxiliary Relay Module.
P2
P1
NC NO C
NC NO C NC NO C
NC NO C Com K1 K2 K3 K4
+ + + +
A
R
M
-
4
.
c
d
r
P-1
Connection for
Cable P/N 71092
These 3 holes for
support stand-offs.
(Also see Figure 3.8
on page 38 for
chassis drawing.)
These 2 holes for
mounting stand-offs.
Terminal
Assignments
(typ. 4 places)
Figure 3.25 ARM-4 Stand-off and Terminal Locations
50 IFC-640 Installation Manual P/N 51864:C 08/05/2005
Installation Installing Remote Printers and/or CRT
3.13.3 Field Wiring an Auxiliary Relay Module
The figure above shows terminal assignments for ARM-4 module control relays K1-K4, which
control nonpower-limited circuits. Power-limited and nonpower-limited circuit wiring must remain
separated by at least 0.25 inch (6.35 mm) within the cabinet and exit the cabinet through different
knockouts, conduits, or both.
The table contains contact ratings for relays K1-K4 on the ARM-4 module:
3.14 Installing Remote Printers and/or CRT
3.14.1 Custom Cable Fabrication
A custom cable needs to be fabricated to connect the PRN Printer, Keltron Printer or the CRT-2
Monitor to the system. Length of the cable will vary with each installation, but should not exceed a
maximum length of 50 feet (15.24 meters). Printer must be installed in the same room as panel.
Construct cable as follows:
1. Using overall foil/braided-shield twisted-pair cable, properly connect one end to the DB-25
Connector using the wiring specifications shown in the table below. (Custom cable kit P/N
90106 is provided.)
2. Tighten clamp on connector to secure cable.

3.14.2 Installing and Configuring the PRN Series Printer
When connected to the Control Panel via an EIA-232 interface, the PRN prints a copy of all status
changes within the control panel and time-stamps the printout with the time of day and date the
event occurred. It provides 80 columns of data on standard 9" by 11" tractor-feed paper.
This section contains information on connecting a printer to the control panel and for setting the
printer options.
Connecting a Remote PRN Series Printer
Remote printers require a 120 VAC, 50/60 Hz primary power source. If required for the fire alarm
system configuration (for example, a Proprietary Fire Alarm System), a remote printer requires a
secondary power source (battery backup). Because a secondary power source is not provided, use a
NOTE: For more information, refer to Section 3.11 UL Power-limited Wiring Requirements.
Resistive Load
Contacts
Normally Open (N.O.) Normally Closed (N.C.)
125 VAC 20 A 10 A
30 VDC 20 A 10 A
Table 3.4 Contact Ratings for K1-K4 on the ARM-4 Module
DB-25 Connector
(Custom cable kit 90106)
TB14 on Control Panel
Pin 3 TX
Pin 2 RX
Pin 7 REF
NOTE: You can also use the EIA-232 printer interface with UL-listed information technology
equipment, such as personal computers, to monitor the control panel for supplementary
purposes.
IFC-640 Installation Manual P/N 51864:C 08/05/2005 51
Installing Remote Printers and/or CRT Installation
separate Uninterruptable Power Supply (UPS) that is UL-listed for Fire Protective Signaling. You
may use your building emergency power supply, so long as it meets the power continuity
requirements of NFPA 72. Refer to NFPA 72 for further details.
Connect the remote printer to the Control Panel as follows:
1. Connect the three (3) open leads of the custom cable to the TB14 terminal block on the control
panel as shown in Figure 3.26.
2. Plug the DB-25 connector end of the custom cable into the EIA-232 port of the remote printer.
Tighten securely.
Setting Printer Options
Refer to the documentation supplied with the PRN series printer for instructions on using the
printer menu controls. Set the printer options (under the menu area) according to the settings listed
in Table 3.5.
TB14 TB15
PRINTER
TX RX REF
PC/CRT
TX RX REF
Note: Outputs are
power-limited but
are not supervised.
n
f
s
6
4
0
-
p
r
n
5
c
o
n
n
.
c
d
r
DB-25 connector
on PRN series
printer (female
socket shown)
Control Panel
Terminate one end of
shield at backbox
Figure 3.26 Remote Printer Connections
Option Setting Option Setting
Font
LPI
ESC Character
Bidirectional Copy
HS Draft
6 LPI
ESC
ON
CPI
Skip
Emulate
I/O
Buffer
Serial
Baud
Format
Protocol
Character Set
Sl.Zero
Auto LF
PAPER
BIN 1
BIN 2
SINGLE
PUSH TRA
PULL TRA
PAP ROLL
10 CPI
0.5
Epson FX-850
40K
9600 or 2400
7 Bit, Even, 1 Stop
XON/XOFF
Standard
On
Off
12/72"
12/72"
12/72"
12/72"
12/72"
12/72"
CG-TAB
Country
Auto CR
Graphic
E-US ASCII
OFF
Color Option
Formlen
Lines
Standard
Not Installed
6LPI=60
Exec 10.5
Table 3.5 PRN Setup Options
52 IFC-640 Installation Manual P/N 51864:C 08/05/2005
Installation Installing Remote Printers and/or CRT
3.14.3 Installing and Configuring a Keltron Printer
Connect the remote printer to the Control Panel as follows:
1. Connect the three (3) open leads of the custom cable to the TB14 terminal block on the control
panel as shown in Figure 3.27.
2. Connect DC power from TB7 terminal block on the control panel as shown in Figure 3.27.
3. Plug the DB-25 connector end of the custom cable into the EIA-232 port of the Keltron printer.
Tighten securely.
Setting up the Keltron Printer
Set up a Keltron printer as follows:
1. The printer communicates using the following protocol:
Baud Rate: 9600 Parity: Even Data bits: 7
2. Set the printer DIP switches SP1 and SP2 according to settings in Table 3.6.
Table 3.6 Keltron DIP Switch Settings
3.14.4 Installing and Configuring a CRT-2
A CRT-2 can only be used in a non-networked application when used with the IFC-640. For further
details on setting up the CRT-2, refer to the IFC-640 Operations Manual.
Connect a CRT-2 to the Control Panel as follows:
1. Connect the three (3) open leads of the custom cable to the TB15 terminal block on the control
panel as shown in Figure 3.28.
2. Plug the DB-25 connector end of the custom cable into the EIA-232 port of the CRT-2. Tighten
securely.
3. Set parameters as discussed in Table 3.28.
TB14 TB15
PRINTER
TX RX REF
PC/CRT
TX RX REF
24V 24V NONRST RESET
+ +
T
B
7
n
f
s
6
4
0
-
k
e
l
t
c
o
n
n
.
c
d
r
DB-25 connector
on Keltron Printer
(female socket
shown)
Keltron printer
24 VDC
connections
(14 AWG,
2.00 mm
2
)
Control Panel
Terminate one end of
shield at backbox
Figure 3.27 Keltron Printer Connections
SP1 On Off
1 X
2 X
3 X
4 X
5 X
6 X
7 X
8 X
SP2 On Off
1 X
2 X
3 X
4 X
5 X
6 X
7 X
8 X
IFC-640 Installation Manual P/N 51864:C 08/05/2005 53
Installing Remote Printers and/or CRT Installation
Setting CRT-2 Parameters
The CRT-2 communicates with the control panel through a protocol defined by thirteen groups of
parameters. To access a parameter group, press the corresponding function key (F1-F12) as shown
in Table 3.7 below. You can then program parameters in each group.
Enter the CRT-2 setup menu by pressing and holding the <Ctrl> key while pressing the <Scroll
Lock> key. Use arrow keys to move through the selections in each setup group; press the space bar
to view the options for each parameter. When finished programming all setup groups, press the
<Pause> key. To save all changes, press <Y>.
Table 3.7 shows the standard settings for using the CRT-2 with the IFC-640; for one instance where
these settings may change slightly see Section 3.14.6 Connecting Multiple Printers, CRTs, or
CRT/PRN Combination. The basic settings for using the CRT-2 with IFC-640 are:
Baud Rate 9600 Data format 8 1 N Protocol xon/off.

TB14 TB15
PRINTER
TX RX REF
PC/CRT
TX RX REF
DB-25 connector
on CRT-2 (female
socket shown)
Control
Panel
n
f
s
6
4
0
-
c
r
t
2
c
o
n
n
.
c
d
r
Terminate one end of
shield at backbox
Figure 3.28 Connecting a CRT-2
NOTE: This section covers installation only; for information on how the CRT-2 functions as part
of the fire alarm system, see the IFC-640 Operations Manual.
Function Key CRT-2 Parameters
F1: Quick
(Read Status key)
Emulation=CRT-2
Comm Mode=Full Duplex
Enhanced=On
EIA Baud Rate=9600
Aux Baud Rate=9600
Language=U.S.
EIA Data Format=8/1/N
Aux Data Format=8/1/N
Host/Printer=EIA/Aux
F2:Genrl
(Alter Status key)
Emulation=CRT-2
Auto Font Load=On
Monitor Mode=Off
Host/Printer=EIA/Aux
Enhanced=On
Auto Page=Off
Bell Volume=09
Auto Wrap=Off
Auto Scroll=On
Warning Bell=On
F3: Displ
(Prog key)
Page Length=24
Display Cursor=On
Columns=80
Scroll=Jump
Screen Length=26 Lines
Cursor=Blink Line
Width Change Clear=Off
Refresh Rate=60 Hz
Screen Video=Normal
Auto Adjust Cursor=On
Speed=Normal
Overscan Borders=Off
F4: Kybd
(Spl Funct key)
Language=U.S.
Keyclick=Off
Key Lock=Caps
Char Set Mode=ASCII
Key Repeat=Off
Keyboard Present=Yes
Key Mode=ASCII
Margin Bell=Off
F5: Keys
(Prior key)
Enter Key=<CR>
Alt Key=Meta
Pound Key=U.S.
Return Key=<CR>
Disconnect=Pause
Backspace=<BS>/<DEL>
Desk Acc=Disabled
F6: Ports
(Next key)
EIA Baud Rate=9600
Aux Baud Rate=9600
EIA Xmt=Xon-Xoff
Aux Xmt=Xon-Xoff
EIA Break=Off
Aux Break=Off
EIA Data Format=8/1/N
Aux Data Format=8/1/N
EIA Recv=Xon-Xoff(XPC)
Aux Recv=Xon-Xoff(XPC)
EIA Modem Control=Off
Aux Modem Control=Off
EIA Parity Check=On
Aux Parity Check=On
EIA Xmt Pace=Baud
Aux Xmt Pace=Baud
EIA Disconnect=2 sec
Aux Disconnect=2 sec
Table 3.7 Standard CRT-2 Settings for Use with IFC-640 (Sheet 1 of 2)
54 IFC-640 Installation Manual P/N 51864:C 08/05/2005
Installation Installing Remote Printers and/or CRT
3.14.5 Connecting a PC
A PC can be hooked up to the Control Panel EIA-232 port (J1) to allow the VeriFire Tools
programming utility to upload and download the operating program of the control panel. Refer to
the insert in the VeriFire Tools CD and to the programs on-line help function for instructions.
3.14.6 Connecting Multiple Printers, CRTs, or CRT/PRN
Combination
Connecting multiple devices requires changing the CRT-2 setup using the F1(Quick) menu:
Set Host/Printer=EIA/AUX.
Set EIA Data Format=8/1/N.
If the AUX device is a printer, set the Printer and AUX Data Format=7/1/E.
If the AUX device is a second CRT-2, set the AUX Data Format=8/1/N.
Connect multiple devices as shown in Figure 3.29.

F7: Host
(Auto Step key)
Comm Mode=Full Duplex
Recv <DEL>=Ignore
Send Block Term=<CR>
Local=Off
Send ACK=On
Null Suppress=On
Recv <CR>=<CR>
Send Line Term=<CR><LF>
F8: Print
(Activ Signal key)
Prnt Line Term=<CR><LF> Prnt Block Term=<CR> Secondary Recv=Off
F9: Emul Attribute=Page
WPRT Intensity=Dim
WPRT Blink=Off
Status Line=Off
Bright Video=Off
WPRT Reverse=Off
Display NV Labels=Off
Fkey Speed=Normal
Page Edit=Off
WPRT Underline=Off
Save Labels=On
F10 Setup Group F10 does not affect communications with the control panel.
F11 Setup Group F11 does not affect communications with the control panel.
F12: Prog
(Ack Step key)
Program the function keys as follows: F1 ~A F2 ~B F3 ~C F4 ~D F5 ~E F6 ~F F7 ~G
F8 ~H F9 ~I F10 ~J F11 ~K F12 ~L F13 ~M F14 ~N F15 ~O F16 ~P Shift F13 ~Q
Function Key CRT-2 Parameters
F1: Quick
(Read Status key)
Emulation=CRT-2
Comm Mode=Full Duplex
Enhanced=On
EIA Baud Rate=9600
Aux Baud Rate=9600
Language=U.S.
EIA Data Format=8/1/N
Aux Data Format=8/1/N
Host/Printer=EIA/Aux
Table 3.7 Standard CRT-2 Settings for Use with IFC-640 (Sheet 2 of 2)
NOTE: Download operations that change the basic program of the control panel must be
performed by responsible service personnel in attendance at the control panel. After downloading
a program, test the control panel in accordance with NFPA 72-1999.
7 3 2
7 3 2
7 3 2
To Control Panel
TB15-REF
TB15-TX
TB15-RX
To EIA-232 port of CRT-2
(female socket shown)
To AUX Port of CRT-2
(female socket shown)
To EIA-232 port of next
CRT-2 or PRN (female socket shown)
p
r
n
c
r
t
-
c
o
n
n
.
c
d
r
Note: For wire requirements, see Table B.1 in Appendix B Electrical Specifications.
Figure 3.29 Connecting Multiple Devices on the EIA-232 Circuit
IFC-640 Installation Manual P/N 51864:C 08/05/2005 55
Wiring a Signaling Line Circuit (SLC) Installation
3.15 Wiring a Signaling Line Circuit (SLC)
Overview
Communication between the control panel and intelligent and addressable initiating, monitor, and
control devices takes place through a Signaling Line Circuit (SLC). You can wire an SLC to meet
the requirements of NFPA Style 4, Style 6, or Style 7 circuits. This manual provides requirements
and performance details specific to this control panel; for installation information and general
information, refer to the SLC Wiring Manual.
Wiring
Maximum wiring distance of an SLC using 12 AWG (3.1 mm
2
) wire is 12,500 feet (3810 meters)
total twisted-pair for Style 4, Style 6 and Style 7 circuits.
Capacity
The IFC-640 provides one (1) SLC, with a total capacity of 318 intelligent/addressable devices:
01-159 intelligent detectors
01-159 monitor and control modules
An optional expander board provides one (1) additional SLC, with the same capacity.
Installation
This control panel supports one or two SLC loops; a second SLC loop is obtained by installing an
LEM-320 module. SLC loop #1 connects to TB16 on the control panel; SLC loop #2 connects to
TB1 on the LEM-320. For details on designing, installing and configuring SLC loops, see the SLC
Wiring Manual.
B+ A+ B- A- B+ A+ B- A-
T-Tapping is not allowed
on a four-wire SLC.
SLC B (output loop)
SLC A (loop return)
SLC B SLC A
Style 4 SLC Loops Style 6 SLC Loops
TB1
B+ A+ B- A-
SLC1
B+ A+ B- A-
TB16
SLC Loop #2 Connections
on Loop Expander Module
SLC Loop #1 Connections
on FACPs main circuit board
Use either
SLC Loop #1
or SLC Loop #2
n
f
s
6
4
0
-
s
l
c
l
o
o
p
s
.
c
d
r
,

n
f
s
6
4
0
-
s
l
c
-
t
b
.
c
d
r
,

L
E
M
3
2
0
-
s
l
c
-
t
b
.
c
d
r
Figure 3.30 SLC Loop Connections and Wiring
56 IFC-640 Installation Manual P/N 51864:C 08/05/2005
Notes

IFC-640 Installation Manual P/N 51864:C 08/05/2005 57
Section 4: Applications
4.1 Overview
Municipal Box (Auxiliary)
Municipal Box applications require a TM-4 Transmitter module. Refer to the Transmitter Module
TM-4 installation document for installation details.
Chapter Covers the following topics
Section 4.2 NFPA 72-1999
Central or Remote Station Fire
Alarm System (Protected
Premises Unit)
How to install UDACT with the control panel for use as a NFPA
Central or Remote Station Fire Alarm System (Protected
Premises Unit)
Section 4.3 NFPA 72-1999
Proprietary Fire Alarm Systems
How to set up a Protected Premises Unit to communicate with a
listed compatible Protected Premises Receiving Unit.
Section 4.4 Fire/Security
Applications
How to use the control panel as a combination Fire/Security
system, including the following:
Installing a Security Tamper Switch into the cabinet
Circuit Wiring
Section 4.5 Releasing
Applications
How to install the following releasing applications:
Releasing Device to the Control Panel (NAC integral circuits)
Releasing Device to the M300CJ Module
NBG-12LRA Agent Release-Abort Station
58 IFC-640 Installation Manual P/N 51864:C 08/05/2005
Applications NFPA 72-1999 Central or Remote Station Fire Alarm System (Protected Premises Unit)
4.2 NFPA 72-1999 Central or Remote Station Fire Alarm
System (Protected Premises Unit)
Figure 4.1 shows typical wiring diagram for a NFPA 72-1999 Central Station Fire Alarm System
(Protected Premises Unit) or a Remote Station Fire Alarm System (Protected Premises Unit) using
the Universal Digital Alarm Communicator/Transmitter (UDACT) and control panel. This
provides typical wiring only; connect and program the UDACT according to the directions given in
the UDACT Instruction Manual.
NOTE: An NFPA 72-1999 Central Station requires 24 hours of standby power; an
NFPA 72-1999 Remote Station requires 60 hours of standby power.
NOTE: This application can also be done with the TM-4 Transmitter; refer to the Transmitter
Module TM-4 document for more details.
T
B
1
3
EIA-485
+ ACS
24V NONRST 24V RESET
+ +
T
B
7
UDACT in ABS-8R
(shown with cover removed)
Solid earth
ground
To supervised
phone lines
Ferrite cores
P/N 29090
FACP Cabinet
EIA-485
(ACS Mode)
24 VDC
Nonresettable power
Supervised and power-limited
EIA-485 and power wiring
n
f
s
6
4
0
-
u
d
a
c
t
.
c
d
r
Figure 4.1 Typical Wiring Diagram for a Central Station Fire Alarm System
NOTE: Install a UL-listed 120 ohm End-of-Line resistor (P/N 71244) UDACT TB1 terminals 3
and 4 if this is the last or only device on EIA-485 line.
IFC-640 Installation Manual P/N 51864:C 08/05/2005 59
NFPA 72-1999 Proprietary Fire Alarm Systems Applications
4.3 NFPA 72-1999 Proprietary Fire Alarm Systems
When connected and configured as a protected premises unit with UDACT, the IFC-640 will
automatically transmit General Alarm, General Trouble, and General Supervisory signals to a listed
compatible Protected Premises Receiving Unit. See the UDACT Manual for compatible receiving
units. A simplified drawing of connections between a receiving unit and an IFC-640 protected
premises unit is shown in Figure 4.2.
Connect the receiving unit to the protected premises unit as shown in Section 4.2 NFPA 72-1999
Central or Remote Station Fire Alarm System (Protected Premises Unit).
For information on installing and programming the Receiving unit, refer to the documentation for
that control panel.
4.4 Fire/Security Applications
4.4.1 General Operation
The control panel can be used as a combination Fire/Security system when installed and operated
according to the instructions in this section.
For security applications, program one or more monitor modules (listed for security applications)
with the SECURITY Type Code, and wire as shown in Figure 4.4. Activating this type of module
lights the SECURITY LED, and displays a security alarm condition on the control panel LCD display.
The panel sounder will sound until the Security alarm is acknowledged. You can also program
additional sounders or output devices to activate with the security alarm initiating device. The
SECURITY Type Code is designed to indicate an alarm as follows: (a) on an open or short circuit; or
(b) on a 50% change in resistance value from the End-of-Line resistor value.
A tamper switch installed in the cabinet door will indicate a door tamper condition whenever the
door is open. If the control panel indicates a Security alarm, you can acknowledge, silence, and
reset the condition from the control panel.
When the system resets, a 30-second exit timer starts. During this time the tamper switch and all
Security alarms are ignored. There is no entrance delay timer.
NOTE: IFC-640 is not approved for use in security applications in Canada.
IFC-640
Protected Premises Unit
Compatible Receiving Unit
(see UDACT Manual)
Telephone line & backup
UDACT
IFC-640
Figure 4.2 Typical Proprietary Fire Alarm Systems Wiring Connections
60 IFC-640 Installation Manual P/N 51864:C 08/05/2005
Applications Fire/Security Applications
For bypass of security zones, use the DISABLE routine (covered in the Status Change section of
the IFC-640 Operations Manual) for Security type devices.
4.4.2 Installing a Security Tamper Switch
To wire the cabinet with a Security Tamper Switch kit model STS-1, refer to Figure 4.3:
1. Install the STS-1 Tamper Switch onto the side of the backbox opposite the door hinge, pushing
the switch through the opening until it snaps into place.
2. Install the magnet on the same side of the cabinet door as the lock. Push the magnet through
the opening in the door until it snaps into place.
3. Connect the STS-1 connector to J10 (Tamper) on the Control Panel.
4.4.3 Receiving Unit
For applications requiring transmission of security alarm information to a central receiving unit, the
control panel may be connected via a UDACT to a compatible receiving unit (see the UDACT
Manual). For information on configuring the Receiving unit for Combination Fire/Security
applications, refer to the documentation for that control panel.
!
WARNING:
Damage can result from incorrect wiring connections.
n
f
s
6
4
0
-
s
t
s
1
.
c
d
r
STS-1 mounting location
(side opposite of door hinges)
Connect to
J10 Tamper
Figure 4.3 Installing the STS-1 Security Tamper Switch
IFC-640 Installation Manual P/N 51864:C 08/05/2005 61
Fire/Security Applications Applications
4.4.4 Programming
The control panel can communicate with any number of security devices. To do so, program the
points as follows:
1. Select the address of the module(s) to be used for security.
2. Select the Type Code SECURITY.
4.4.5 Wiring for Proprietary Security Alarm Applications
Table 4.4 shows typical wiring for proprietary security alarm applications with M300MJ modules
or XP5-M modules. Note the following:
The module is programmed with software SECURITY Type Code.
Supplementary use only applies to UL-listed systems.
NAC devices used for security cannot be shared with fire NAC devices.
Refer to the Device Compatibility Document for compatible NAC devices.
All monitor modules used for security application must be installed in the IFC-640 cabinet
with STS-1 Security Tamper Switch.
NOTE: For detailed instruction on programming Type Codes, refer to the IFC-640 Programming
Manual.
62 IFC-640 Installation Manual P/N 51864:C 08/05/2005
Applications Fire/Security Applications


8
9 8
8
9
9
10
11
12
13
14
15 0
0
1
1
2
2
3
3
4
4
5
5
6
6
7
7
0
1
2
3
4
7
6
5
TENS
ONES
ADDRESS LOOP

+
M300MJ
UL-listed, normally-closed
security switch
UL-listed,
normally-open
security switch
SW101
O
N
O
N
O
N
O
N
SW201 SW301 SW401
O
N
SW501
E
n
a
b
le
E
n
a
b
le
E
n
a
b
l e
E
n
a
b
le
SW102
SW1
SW2
Base Address
SW202 SW302 SW402
E
n
a
b
l e
SW502
1
0 5
7
8
6
2
3 4 9
15
13
12
14
10
T
B
4
T
B
1
T
B
5
T
B
2
T
B
6
T
B
3
SLC B- B+ A- A+ B+ B- B+ B- B+ B- B+ B- B+ B-
0 5
(+)
(-)
UL-listed, normally-closed
security switch
UL-listed,
normally-open
security switch
UL-listed,
normally-open
security switch
UL-listed, normally-closed
security switch
XP5-M
SLC
Channel
A or B
UL-listed
47K
End-of-Line
Resistor
(provided
with module)
SLC
Channel
A or B
IFC-640 Protected Premises Unit
IFC-640 Protected Premises Unit
n
f
s
6
4
0
-
b
u
r
g
l
a
r
x
p
5
m
.
c
d
r
n
f
s
6
4
0
-
b
u
r
g
.
c
d
r
UL-listed 47K
End-of-Line Resistor
(provided with module)
Figure 4.4 Wiring Diagram for Proprietary Security Alarm Applications
IFC-640 Installation Manual P/N 51864:C 08/05/2005 63
Releasing Applications Applications
4.5 Releasing Applications
4.5.1 Overview
This control panel can be used for agent release or preaction/deluge control applications. In a
properly configured system with compatible, listed actuating and initiating devices, this control
panel complies with the following NFPA standards for installation in accordance with the
acceptable standard:
4.5.2 Programming
The control panel supports up to ten releasing software zones. You can map these zones to activate
Control Panel releasing outputs and M300CJ modules. Program the M300CJ module for the
appropriate type code according to the chart below:
For more information, refer to the IFC-640 Programming Manual.
4.5.3 Wiring
References to wiring diagrams for releasing applications:
!
WARNING:
When used for CO
2
releasing applications, observe proper precautions as stated in NFPA 12.
Do not enter the protected space unless physical lockout and other safety procedures are fully
completed. Do not use software disable functions in the panel as lockout.
!
WARNING:
Do not enable the BACKUP option switch for any of the four Notification Appliance Circuits (NACs) if
they are used for releasing functions!
Standard Covers
NFPA 12 CO
2
Extinguishing Systems
NFPA 12A Halon 1301 Extinguishing Systems
NFPA 13 Sprinkler Systems
NFPA 15 Water Spray Systems
NFPA 16 Foam-Water Deluge and Foam-water Spray Systems
NFPA 17 Dry Chemical Extinguishing Systems
NFPA 17A Wet Chemical Extinguishing Systems
NFPA 2001 Clean Agent Fire Extinguishing Systems
Table 4.1 NFPA Standards for Releasing Applications
Type Code: RELEASE CKT
For use in UL applications.
Do not use REL device at the solenoid.
Cannot use power-limited wiring.
Supervised for open circuit only.
Supervised for power loss with
power-supervision relay.
Type Code: REL CKT ULC
For use in UL or ULC applications.
Requires REL device at solenoid.
Power-limited wiring.
Supervised for open circuit and shorts.
Supervised for power loss with
power-supervision relay.
To connect Refer to
A releasing device to the control panel. Section 4.5.4 Connecting a Releasing Device to the Control Panel.
A releasing device to the M300CJ Module. Section 4.5.5 Connecting a Releasing Device to the M300CJ Module.
An NBG-12LRA Agent Release-Abort Station. Section 4.5.6 Connecting an NBG-12LRA Agent Release-Abort Station.
64 IFC-640 Installation Manual P/N 51864:C 08/05/2005
Applications Releasing Applications
4.5.4 Connecting a Releasing Device to the Control Panel
Use TB3 (NAC#4), TB4 (NAC#3), TB5 (NAC#2), or TB6 (NAC#1) on the control panel for
NACReleasing Circuits. Only one listed, compatible releasing device can be installed per NAC.

Circuit Requirements. When connecting a releasing device, note the following:
1. The control panel provides four NAC/Releasing Circuits (Style Y or Z). Each circuit can
provide 2.5 A. Total current drawn from the power supply cannot exceed 6 A in an alarm
condition (refer to Table A.2, System Draw Current Calculations, on page 71). Use
compatible UL-listed 24 VDC appliances only. For more information on compatible
appliances, refer to the Device Compatibility Document.
2. Refer to the IFC-640 Programming Manual for instructions on setting the Soak Timer.
3. For applications using power-limited circuits:
a) Use an End-of-Line device (P/N REL-2.2K) with control panel releasing circuits. Connect
the End-of-Line device as shown in Figure 4.5.
b) Program the releasing circuit for Type Code REL CKT ULC.
c) Circuits are supervised against opens and shorts.
4. For applications not requiring power-limited circuits
a) If the application does not require supervising the releasing device against shorts,
End-of-Line devices (P/N REL-2.2K) are not required.
b) In non-power-limited applications, program the releasing circuit for Type Code
RELEASE CKT.
c) Limited energy cable cannot be used to wire a non-power-limited releasing device circuit
d) Maintain a 0.25 inch (6.35 mm) spacing between the non-power-limited releasing circuit
device wiring and any power-limited circuit wiring.)
5. The releasing circuit must be programmed with a releasing type code listed in the IFC-640
Programming Manual.
!
WARNING:
Do not enable the BACKUP option switch for any of the four Notification Appliance Circuits (NACs) if
they are used for releasing functions!
+

n
f
s
6
4
0
-
r
e
l
c
o
n
n
1
.
c
d
r
REL-2.2K (Use with Type Code
Rel Ckt ULC, or see Circuit
Requirement 4.)
Compatible UL-listed
24 VDC releasing device
B+ NAC/Releasing output (source)
B NAC/Releasing output (source)
A+ Class A (return for NAC only)
A Class A (return for NAC only)
Note: See text below for circuit requirements.
Figure 4.5 Typical Style 4 Connection of a Releasing Device to Control Panel
IFC-640 Installation Manual P/N 51864:C 08/05/2005 65
Releasing Applications Applications
4.5.5 Connecting a Releasing Device to the M300CJ Module
The module can control 1 A of current. Make sure to keep total system current within the limits of
the power supply. You can power the module from the power supply of the Control Panel or any
UL -listed 24 VDC regulated power-limited power supply for Fire Protective Signaling. For more
information, refer to the Device Compatibility Document.

Circuit Requirements. When connecting a releasing device to the M300CJ module, note the
following:
1. Refer to the IFC-640 Programming Manual for instructions on setting the Soak Timer.
2. For applications using power-limited circuits:
a) Use an in-line supervisory device (P/N REL-47K) with the M300CJ module. Connect the
in-line supervisory device as shown in Figure 4.6.
b) Program the releasing circuit for Type Code REL CKT ULC.
c) Circuits are supervised against opens and shorts.
3. For applications not requiring power-limited circuits:
a) in-line supervisory devices (P/N REL-47K) are not required; however, the releasing device
circuit is not supervised against shorts.
b) In non-power-limited applications, program the releasing circuit for Type Code
RELEASE CKT.
c) Limited energy cable cannot be used to wire a non-power-limited releasing device circuit.
d) Maintain a 0.25 inch (6.35 mm) spacing between the non-power-limited releasing circuit
device wiring and any power-limited circuit wiring.
+

8
9 8
8
9
9
10
11
12
13
14
15 0
0
1
1
2
2
3
3
4
4
5
5
6
6
7
7
0
1
2
3
4
7
6
5
TENS
ONES
ADDRESS LOOP
Compatible UL-listed
24 VDC releasing device
REL-47K
(Use with Type Code
Rel Ckt ULC,
or see Circuit
Requirement 3.)
Brown Red
Non-resettable
24 VDC Power
Power Supervision
Relay (EOLR-1)
R
e
l
c
o
n
n
-
f
c
m
.
c
d
r

+
M300CJ

+
SLC from FACP
or LEM-320
Note: See text for circuit requirements.
N.C. Supervision
Relay Contact
Part of EOLR-1
Figure 4.6 Typical Connection of a 24 VDC Releasing Device to the M300CJ Module
66 IFC-640 Installation Manual P/N 51864:C 08/05/2005
Applications Releasing Applications
4.5.6 Connecting an NBG-12LRA Agent Release-Abort Station


NOTE: If using the on-board NACs, see Circuit Requirements for Section 4.5.4 Connecting a
Releasing Device to the Control Panel on page 64. If using M300CJ, see Circuit Requirements
for Section 4.5.5 Connecting a Releasing Device to the M300CJ Module on page 65.
+
+

+
+
+
1
2
4
6
5
7 -
6 +
1
2
3
4
0

+
+

+
SLC loop to
FACP or LEM-320
M300CJ

M300RJ

M300MJ

M301MJ
Black
Red
Yellow
Violet
Black
Red
Yellow
Violet
Non-resettable +24 VDC
from main power supply
Manual Abort
Manual Release
Normal
Release
NBG-12LRA
See Document 51369
for installation details.
ELR mode R-47K
supervised and
power-limited
Red Brown
24 VDC UL-listed
releasing device
C.
N.O.
REL-47K
(use with Type Code
Rel Ckt ULC)
N
B
G
6
4
0
-
N
B
G
1
2
L
R
A
.
c
d
r





System
Common ()
24 VDC power
from FACPs
main power supply
N.C.
Power Supervision
Relay (EOLR-1)
N.C. Supervision
Relay Contact
Figure 4.7 Typical Connections for an NBG-12LRA Agent Release-Abort Station
IFC-640 Installation Manual P/N 51864:C 08/05/2005 67
Section 5: Testing the System
5.1 Acceptance Test
When finished with the original installation and all modifications, conduct a complete operational
test on the entire installation to verify compliance with applicable NFPA standards. Testing should
be conducted by a factory-trained fire alarm technician in the presence of a representative of the
Authority Having Jurisdiction and the owner's representative. Follow procedures outlined in NFPA
Standard 72-1999, Chapter 7, Inspection, Testing and Maintenance.
5.2 Periodic Testing and Service
Periodic testing and servicing of the control panel, all initiating and notification devices, and any
other associated equipment is essential to ensure proper and reliable operation. Test and service the
control panel according to the schedules and procedures outlined in the following documents:
NFPA Standard 72-1999, Chapter 7, Inspection, Testing and Maintenance.
Service manuals and instructions for the peripheral devices installed in the system. Correct any
trouble condition or malfunction immediately.
5.3 Operational Checks
Between formal periodic testing and servicing intervals, the following operation checks should be
performed monthly, or more frequently when required by the Authority Having Jurisdiction.
Before proceeding: a) notify the fire department and the central alarm receiving station if
transmitting alarm conditions; b) notify facility personnel of the test so that alarm sounding
devices are disregarded during the test period; and c) when necessary, disable activation of
alarm notification appliances and speakers to prevent their sounding.
Disconnect all releasing devices to prevent accidental activation.
Check that the green POWER LED lights.
Check that all status LEDs are off.
Press and hold the LAMP TEST key. Verify that all LEDs and all LCD display segments work.
Activate an Initiating Device Circuit using an alarm initiating device or an addressable
initiating device on the SLC and check that all programmed active notification appliances
function. Reset the alarm initiating device, the control panel, and any other associated
equipment. In voice alarm applications, confirm that the proper tone(s) and/or messages sound
during alarm conditions. Select the paging function and confirm that the message can be heard
in the affected fire zones. Repeat the above step with each Initiating Device Circuit and each
addressable device.
On systems equipped with a fire fighters telephone circuit, make a call from a telephone
circuit and confirm a ring tone. Answer the call and confirm communication with the incoming
caller. End the call and repeat for each telephone circuit in the system.
Remove AC power, activate an Initiating Device Circuit through an alarm initiating device or
an addressable initiating device on the SLC, and check that programmed active notification
appliances sound, and alarm indicators illuminate. Measure the battery voltage with
Continued on next page...
!
WARNING:
Do not rely on disable/enable software settings to lockout releasing devices.
68 IFC-640 Installation Manual P/N 51864:C 08/05/2005
Testing the System Battery Checks and Maintenance
notification appliances active. Replace any battery with a terminal voltage less than 21.6 VDC
and reapply AC Power.
Return all circuits to their pretest condition.
Check that all status LEDs are off and the green POWER LED is on.
Notify fire, central station and/or building personnel when you finish testing the system.
5.4 Battery Checks and Maintenance
Maintenance-free sealed lead-acid batteries used in the system do not require the addition of water
or electrolyte. These batteries are charged and maintained in a fully charged state by the main
power supply's float charger during normal system operation. A discharged battery typically
charges at 1.51.8 A and reaches the float voltage of 27.6 VDC within 48 hours.
Follow the local AHJ and manufacturer recommendations for battery replacement intervals.
Minimal replacement battery capacity appears on the control panel marking label. Immediately
replace a leaking or damaged battery. You can get replacement batteries from the manufacturer.
If a battery leaks and contact is made with the Sulfuric Acid, immediately flush skin and/or
eyes with water for at least 15 minutes. Water and household baking soda provides a good
neutralizing solution for Sulfuric Acid.
If Sulfuric Acid gets into eyes, seek immediate medical attention.
Ensure proper handling of the battery to prevent short circuits.
Take care to avoid accidental shorting of the leads from uninsulated work benches, tools,
bracelets, rings, and coins.
On-board Memory-Backup Battery
A snap-in lithium battery on the CPU provides backup of the CPUs on-board memory during
power loss. The expected shelf-life for this battery is 10+ years. However if battery connections are
damaged or the battery does lose power, a system trouble message will appear: Bat. Backup
RAM.
NOTE: The battery test requires fully charged batteries. If batteries are new or discharged due
to a recent power outage, allow the batteries to charge for 48 hours before testing.
!
WARNING:
Batteries contain Sulfuric Acid which can cause severe burns to the skin and eyes and damage to
fabrics.
!
WARNING:
Shorting the battery leads can damage the battery, equipment, and could cause injury to personnel.
IFC-640 Installation Manual P/N 51864:C 08/05/2005 69
Appendix A: Power Supply Calculations
Calculations must be done to determine standby and alarm DC current loads. Ampere-hour
requirements must be calculated as well to determine battery size.
The on-board power supply provides filtered 24VDC power that may be used for operating external
devices. Use Table A.2 to determine if external loading is within the capabilities of the power
supply.
A.1 Calculating AC Branch Circuit Current
Use Table A.1 below to determine the total amount of current, in AC amperes, that a 120 VAC, 50/
60 Hz service must be able to supply to the fire alarm system. Devices rated for 240 VAC operation
will draw approximately one-half the current listed in Table A.1.

AC Branch Circuit Installation
For guidelines on wiring the AC branch circuit current, see Operating Power: AC Branch Circuit
on page 77 in Appendix B.1 Electrical Specifications.
A.2 Calculating the System Current Draws
The control panels main power supply must be able to power all internal system devices (and
several types of external devices) continuously during non-fire alarm conditions. Use column 1 in
Table A.2 to calculate the Non-Fire Alarm Load on the power supply regulator when applying
primary power. The main power supply must also provide a finite amount of additional current
during a fire alarm condition. Use column 2 in Table A.2 to calculate the additional current needed
during fire alarms. The requirements for non-fire alarm and fire alarm current loads cannot exceed
the capabilities of the power supply as listed below:
3 A at 24 VDC during Standby; and
6 A at 24 VDC during Alarm.
How to Use the Calculating Tables
As used in this section, Primary refers to the control panels on-board power supply, its primary
source of AC power. Secondary refers to the control panels backup batteries (or any other 24
VDC power supply listed for Fire Protective Signaling and connected in place of the batteries). The
term standby refers to the output current required when no fire alarm is present. The term alarm
refers to the output current required when a fire alarm is present.
The Primary Power Source Non-Alarm Current and Alarm Current columns are DC current
calculations. These calculations confirm that the power supply can provide enough current to
support the system during Primary Non-Fire Alarm and Fire Alarm conditions.
Device Type No. of Devices Current (amps) Total Current
Main Power Supply [ 1 ] X 3.0 = 3.0
AA-30 [ ] X 1.00 =
AA-120 [ ] X 1.85 =
ACPS-2406 [ ] X 2.7
*
* Separate calculations are required for any devices powered by the
ACPS-2406. It has its own integral battery charger and batteries can be
connected directly to it. Refer to the ACPS-2406 Installation Manual for its
battery calculations.
=
APS-6R [ ] X 2.5 =
CHG-120 [ ] X 2.0 =
Sum column for AC Branch Current required=amps
Table A.1 120 VAC Fire Alarm Circuit
70 IFC-640 Installation Manual P/N 51864:C 08/05/2005
Power Supply Calculations Calculating the System Current Draws
Quantities List the number of devices powered by the Panel Output (TB2) and the Accessories
Output (TB6). Devices powered by the Accessories Output draw current directly from the panel.
Devices powered by the Panel Output draw current through the fire panels connection to the power
supply. Use these quantities to calculate total current draw of each set of devices in calculation
columns 1, 2, and 3.
Calculation Column 1 (Primary, Non-Fire Alarm Current in amps) Add the contents of
calculation column 1 to get the current drawn from the power supply during a non-alarm condition,
with AC power applied. This current draw cannot exceed 3 A without an auxiliary power supply.
Calculation Column 2 (Primary, Fire Alarm Current in amps) Calculation column 2 lets
the system designer determine the current load that the power supply must support during a fire
alarm. The total current draw during a fire alarm cannot exceed 6 A without an auxiliary power
supply.
Typically, a system should contain capacity to activate all output circuits and relays, and support
fire alarms on no less than 10% of Initiating Device Circuits, subject to the requirements of the
Authority Having Jurisdiction (AHJ).
The Control Panel provides power for Notification Appliance Circuits. Refer to the Device
Compatibility Document for 24 VDC notification appliances that are UL- and ULC-listed for fire
alarm systems.
Calculation Column 3 [Secondary (Battery) Non-Alarm Current] Column 3 lets the
system designer calculate the non-fire alarm current drawn from the secondary source in a non-fire
alarm condition during AC power loss.The non-fire alarm current is required to complete the
standby battery calculations. After summing all current draws, insert the total in Table A.3.
IFC-640 Installation Manual P/N 51864:C 08/05/2005 71
Calculating the System Current Draws Power Supply Calculations

Category
Calculation Column 1
Primary, Non-Fire Alarm
Current (amps)
Calculation Column 2
Primary, Fire Alarm
Current (amps)
Calculation Column 3
Secondary, Non-Fire Alarm
Current (amps)
Qty X [current draw]= Total Qty X [current draw]= Total Qty X [current draw]= Total
JCPU-640/E
KDM-2
LEM-320
1
[ ]
0 / 1
x [0.230] =
x [0.094]=
x [0.100]=
1
[ ]
0 / 1
x [0.230] =
x [0.094]=
x [0.100]=
1
[ ]
0 / 1
x [0.230] =
x [0.040]=
x [0.100]=
SLC loop
*
:
with jumper JP12 cut on CPU
or without jumper JP12 cut on CPU
0/1/2
x [0.200]=
x [0.400]=
0/1/2
x [0.200]=
x [0.400]=
0/1/2
x [0.200]=
x [0.400]=
JNCA (back light on)
NCM-W, NCM-F
TM-4
DPI-232 (Refer to Doc. 51499)
[ ]
[ ]
[ ]
[ ]
x [0.400]=
x [0.110]=
x [0.110]=
x [ ]=
[ ]
[ ]
[ ]
[ ]
x [0.400]=
x [0.110]=
x [0.175]=
x [ ]=
[ ]
[ ]
[ ]
[ ]
x [0.400]=
x [0.110]=
x [0.110]=
x [ ]=
APS-6R
ACPS-2406
[ ]
[ ]
x [0.025]=
x [0.0013]=
ICM-4RK, ICM-4, CRM-4, CRM-4RK
ICE-4
CRE-4
DCM-4RK, DCM-4
VCE-4
VCM-4RK, VCM-4
[ ]
[ ]
[ ]
[ ]
[ ]
x [0.007]=
x [0.001]=
N/A
x [0.008]=
x [0.001]=
x [0.007]=
[ ]
[ ]
[ ]
[ ]
[ ]
x [0.072]=
x [0.065]=
x [0.065]=
x [0.080]=
x [0.040]=
x [0.040]=
[ ]
[ ]
[ ]
[ ]
[ ]
x [0.007]=
x [0.001]=
N/A
x [0.008]=
x [0.001]=
x [0.007]=
ARM-4 Auxiliary Relay [ ] x [0.146]=
AA-30
AA-100, AA-120
[ ]
[ ]
x [0.045]=
x [0.050]=
ACM-24AT
ACM-48A
AEM-24AT
AEM-48A
[ ]
[ ]
[ ]
[ ]
x [0.016]=
x [0.016]=
x [0.002]=
x [0.002]=
[ ]
[ ]
[ ]
[ ]
x [0.070]=
x [0.070]=
x [0.056]=
x [0.056]=
[ ]
[ ]
[ ]
[ ]
x [0.016]=
x [0.016]=
x [0.002]=
x [0.002]=
Maximum number of LEDs illuminated on
these annunciators during non-fire
conditions:
[ ] x [0.0054]= [ ] x [0.0054]=
AFM-16AT, AFM-32A
ACM-16AT, ACM-32A
AEM-16AT, AEM-32A
[ ]
[ ]
[ ]
x [0.040]=
x [0.040]=
x [0.002]=
[ ]
[ ]
[ ]
x [0.056]=
x [0.056]=
x [0.018]=
[ ]
[ ]
[ ]
x [0.040]=
x [0.040]=
x [0.002]=
AFM-16A
LCD-80, LCD-80TM
ACM-8R (refer to Doc. 15342)
LDM (refer to Doc. 15885)
UZC-256
FDU-80
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
x [0.025]=
x [0.100]=
x [ ]=
x [ ]=
x [0.035]=
x [0.0643]=
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
x [0.065]=
x [0.100]=
x [ ]=
x [ ]=
x [0.085]=
x [0.0643]=
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
x [0.025]=
x [0.050]=
x [ ]=
x [ ]=
x [0.035]=
x [0.0643]=
AMG-1, AMG-E
FFT-7, FFT-7S
RM-1
[ ]
[ ]
[ ]
x [0.060]=
x [0.060]=
x [0.020]=
[ ]
[ ]
[ ]
x [0.060]=
x [0.120]=
x [0.020]=
[ ]
[ ]
[ ]
x [0.060]=
x [0.060]=
x [0.020]=
M302MJ, M502MJ [ ] x [0.0094]= [ ] x [0.090]= [ ] x [0.0094]=
XPIQ (Refer to Doc. 51013) [ ] x [ ]= [ ] x [ ]= [ ] x [ ]=
RPT-W, RPT-WF, RPT-F
RPT-485W, RPT-485WF
[ ] x [0.017]= [ ] x [0.017]= [ ] x [0.017]=
RFX (Refer to Doc. 51012) [ ] x [ ]= [ ] x [ ]= [ ] x [ ]=
UDACT Communicator
VEC-25/50
with optional FC-AAM25
[ ]
[ ]
[ ]
x [0.040]=
x [0.215]=
x [0.245]=
[ ]
[ ]
[ ]
x [0.100]=
x [1.215]=
x [2.215]=
[ ]
[ ]
[ ]
x [0.040]=
x [0.215]=
x [0.245]=
Four-Wire Smoke Detectors

[ ]
[ ]
x [ ]=
x [ ]=
[ ]
[ ]
x [ ]=
x [ ]=
[ ]
[ ]
x [ ]=
x [ ]=
Power Supervision Relay
EOLR-1 or A77-716B
[ ] x [0.020]= [ ] x [0.020]= [ ] x [0.020]=
Notification Appliance powered from Main
Power Supply

[ ]
[ ]
x [ ]=
x [ ]=
DHX-501, DH300RP, DH300RPL (Duct
Detectors with internal relays)
Refer to installation document
[ ]
[ ]
x [ ]=
x [ ]=
[ ]
[ ]
x [ ]=
x [ ]=
[ ]
[ ]
x [ ]=
x [ ]=
CHG-120 Battery Charger [ ] x [0.060]=
Local Energy Municipal Box [ ] x [ ]=
Compatable Devices not listed above
**
[ ]
[ ]
x [ ]=
x [ ]=
[ ]
[ ]
x [ ]=
x [ ]=
[ ]
[ ]
x [ ]=
x [ ]=
Sum each column for totals Primary, non-alarm: Primary, alarm: Secondary, non-alarm:
Table A.2 System Draw Current Calculations
* Value represents an SLCs maximum current draw. Refer to device datasheets for individual current draws. If jumper JP12 is cut, total device current cannot
exceed 200 mA; if jumper JP12 is not cut, total device current cannot exceed 400 mA.
The total regulated load current supplied to four-wire smoke detector and power supervision relays cannot exceed 1.25 A.
Enter the total notification appliance draw from the Main Power Supply, excluding the current from APS-6R supplies. Refer to Device Compatibility Document.
** Refer to manual and/or Device Compatibility Document.
72 IFC-640 Installation Manual P/N 51864:C 08/05/2005
Power Supply Calculations Calculating the System Current Draws
A.2.1 Calculating the Maximum Secondary Power Fire Alarm
Current Draw
Use Table A.3 below to determine the maximum current requirements of secondary power source
during fire alarm conditions. The result obtained is the amount of current that the batteries must be
able to supply to the fire alarm system. Use the result in Table A.4 to determine the size of the
batteries needed for the fire alarm system.
Results taken from Table A.3 below assume that, while in a fire alarm condition, batteries must
feed the main power supply (and any additional supplies such as the APS-6R and AA-30) with the
maximum rated power each supply can provide.

Device Quantity
Current
(in amps)
Total Current/Type
Alarm Current, from Table A.2, col 2 =
APS-6R
*
* Actual load current may be used in place of maximum rated supply
current. To calculate actual load current, sum the current draws for each
appliance connected to APS-6R supplies.
[ ] X 6 =
AA-30

Exclude Amplifiers that are employed for backup.


[ ] X 3 =
AA-120
2
[ ] X 7.3 =
Sum Column for Secondary Fire Alarm Load =
Table A.3 Maximum Secondary Power Fire Alarm Current Draw
NOTE: The Secondary Fire Alarm Load cannot exceed the following:
9 A with BAT-12120 batteries (12 V, 12 AH).
12 A with BAT-12250 batteries (12 V, 26 AH).
20 A with BAT-12550 batteries (12 V, 55 AH).
IFC-640 Installation Manual P/N 51864:C 08/05/2005 73
Calculating the Battery Requirements Power Supply Calculations
A.3 Calculating the Battery Requirements
A.3.1 Calculating the Battery Capacity
Use this table to determine the battery capacity needed for the system:
Current (amps) X Time (hours) = AH
Secondary Non-Fire Alarm Current
(from column 3 in Table A.2)
________________ X
Required Secondary Non-Fire Alarm
Standby Time (24 or 60 hours)
________________ = _________AH
APS-6R
Standby Load Current
________________ X
Required Secondary Non-Fire Alarm
Standby Time (24 or 60 hours)
________________ = _________AH
Secondary Fire Alarm Load
(from Table A.3)
________________ X
Required Fire Alarm Standby Time:
(for 5 minutes, enter 0.084; for 15
minutes, enter 0.25)
________________ = _________AH
Sum Column for Total Secondary Amp Hours calculated = _________AH
Multiply by the derating factor x 1.2 (see Note 7) = _________AH
Battery Size Total Secondary Amp Hours Required = _________AH
1. NFPA 72-1999 Local, Proprietary, and Central Station systems requires 24 hours of standby power
followed by 5 minutes in alarm.
2. NFPA 72-1999 Auxiliary and Remote Station Systems require 60 hours or standby power followed by
5 minutes in alarm.
3. Batteries installed in a system powered by an automatic starting engine generator need to provide at
least 4 hours of standby power.
4. Factory Mutual requires 90 hours of standby for deluge-preaction systems.
5. Emergency voice/alarm communications systems require 2 hours of operation in the alarm condition.
Due to the sporadic nature of voice operation, however, NFPA 72-1999 permits 15 minutes of operation
at a maximum connected load to equal 2 hours of normal use.
6. If the total exceeds 25 AH, the system requires a separate JCI-LBB battery enclosure for two BAT-12550,
55 AH batteries in a separate JCI-LBB enclosure. If the total exceeds 55 AH, the system requires an
auxiliary battery charger with sufficient amp-hour capacity; this charger must be UL-listed for
Fire-Protective Signaling. If CHG-120 battery charger is used, it requires a second JCI-LBB enclosure.
7. The following battery derating factors must be used for Canadian installations using IFC-640 charger:
For a 12 AH battery, use derating factor of 1.2
For a 25 AH battery, use derating factor of 1.5
For a 55 AH battery, use derating factor of 1.8
When batteries are charged by CHG-120 charger use a derating factor of 1.2 for 25 AH and 55 AH
batteries.
Table A.4 Secondary Power Standby and Fire Alarm Load
74 IFC-640 Installation Manual P/N 51864:C 08/05/2005
Power Supply Calculations Calculating the Battery Requirements
A.3.2 Calculating the Battery Size
Use this table to choose the battery size, in amp-hours, needed to support the fire alarm system.
Select batteries that meet or exceed the Total Amp-Hours calculated in Table A.4 and that are
within the acceptable battery charger range (12-55 AH). Write the amp-hours requirements on the
Protected Premises label.

Battery Size
Voltage
Rating
Number
Required
Part
Number
Backbox Size
12 AH 12 volts two BAT-12120 SBB-A4*, SBB-B4*,
SBB-C4*, SBB-D4*
25 AH 12 volts two BAT-12250 SBB-A4*, SBB-B4*,
SBB-C4*, SBB-D4*
55 AH 12 volts two BAT-12550 JCI-LBB*
* Red version available; add R to part number listed here
Table A.5 Selecting the Battery Size
IFC-640 Installation Manual P/N 51864:C 08/05/2005 75
Appendix B: Electrical Specifications
B.1 Electrical Specifications
AC Power
Batteries
The control panel uses only sealed lead-acid batteries for secondary standby power. Maximum
battery capacity for the control panels integral main power supply is 55 AH. Batteries larger than
25 AH require the JCI-LBB or other UL-listed battery cabinet. The table below contains
specifications for batteries that can be used with the control panel; see also Appendix A.3.2
Calculating the Battery Size:
Component Values
Main Power Supply 120 VAC, 50/60 Hz, 3.0 A; or
240 VAC, 50/60 Hz, 1.5 A
Wire size Maximum 12 AWG (3.1 mm
2
) with 600 VAC insulation
NOTE: If using an auxiliary power supply such as APS-6R, ACPS-2406, or audio amplifiers,
refer to the documentation for that equipment.
Charger Description Specifications
Main Power Supply An internal battery charger for 12
AH to 55 AH
Dual Rate: High Charge: 29.1 VDC
Normal Float Charge: 27.6 VDC
Charging Current: 2.0 A max (1.5 A typical)
CHG-120
Battery Charger
An external battery charger
designed to charge lead-acid
batteries between 25 AH and 120
AH
Dual Rate: High Charge: 28.1 VDC
Normal Float Charge: 27.6 VDC
Charging Current: 4.5 A
ACPS-2406
Auxiliary Charger/
Power Supply
An internal battery charger for
7AH to 25 AH
Normal Float Charge: 27.6 VDC
Charging Current: 1.1 A max (0.750 A typical)
76 IFC-640 Installation Manual P/N 51864:C 08/05/2005
Electrical Specifications Electrical Specifications
Signaling Line Circuit (SLC)
Notification Appliance Circuits & Releasing Circuits
Output Relays
Output relays for Alarm, Trouble, Supervisory, and Security are available on power supply
terminals TB8, TB9, TB10, and TB11 respectively.
Contact ratings: 2.0 A @ 30 VDC (resistive)
Four-wire Smoke Detector Power
Control Panel terminals TB7 RESET (+) and () supply filtered, low-noise power for four-wire
smoke detectors. Specifications are:
Nominal voltage: 24 VDC
Maximum rated current: 1.25 A DC
Maximum ripple voltage: 176 mVrms
Refer to the Device Compatibility Document for compatible 24 VDC detectors.
Power Output
Control Panel terminals TB7 NONRST (+) and () supply one (1) power-limited circuit available
to power external devices, such as notification appliances and annunciators.
Nominal voltage: 24 VDC
Maximum rated current: 1.25 A DC
Maximum ripple voltage: 176 mVrms
Refer to the Device Compatibility Document for compatible devices and notification appliances.
Item Value
Voltage 24 VDC nominal, 27.6 VDC maximum
Maximum length 12,500 ft. (3810 m) per channel (NFPA Style 4) or 10,000 ft. (3048 m) total
loop or circuit length (NFPA Style 6 and 7)
Note: Refer to Appendix B.2 Wire Requirements for limitations.
Maximum current 400 mA peak, 200 mA average (max short circuit; circuit will shut down until
short is fixed)
Maximum resistance 50 ohms (supervised and power-limited)
Item Value
Max. wiring voltage drop 2 VDC (except M510CJ which is 1.2 VDC)
Nominal operating voltage 24 VDC
Current for all external
devices connected to the
control panels power supply
6.0 A in alarm (3 A continuous)
Optional ACPS-2406 Total 6 A in alarm (5 A continuous)
Optional APS-6R Total 6 A in alarm (4 A continuous)
Maximum signaling current/
circuit per NAC
2.5 A
Note: Some devices have maximum draws less than this; refer to the devices
documentation.
End-of-Line Resistors
(ELRs)
Control Panel NACs (TB3, TB4, TB5, TB6): 2.2K, 1/2 watt
ICM-4RK, ICE-4, VCM-4RK, VCE-4, and DCM-4RK: 4.7K,
1/2 watt (2 watts on 70 Vrms audio)
XP5-C, XP6-C, M300CJ Modules: 47K, 1/2 watt
NOTE: The Control Panel provides a total of 6.0 A of power in alarm (3 A in standby), shared by
all internal circuitry and external provisions (24 V resettable and non-resettable). For power
requirements, refer to the power supply calculation tables in Appendix A.
IFC-640 Installation Manual P/N 51864:C 08/05/2005 77
Wire Requirements Electrical Specifications
Operating Power: AC Branch Circuit
The control panel requires connection to a separate dedicated AC branch circuit. Follow these
guidelines when connecting the AC branch circuit:
Label the branch circuit Fire Alarm. This must be a separate dedicated AC fire alarm circuit.
Connect the branch circuit to the line side of the main power feed of the protected premises.
Do not power other equipment from the fire alarm branch circuit.
Run the AC branch circuit wire continuously, without any disconnect devices except for
overcurrent protection, from the power source to the fire alarm control panel.
Overcurrent protection for the AC branch circuit must comply with Article 760 of the National
Electrical Codes, as well as local codes.
Use 12 AWG (3.1 mm
2
) wire with 600 VAC insulation for the AC branch circuit.
Connect the ground terminal (TB2-Earth) to a solid earth ground (a metallic, cold water pipe may
be suitable in some installations). This connection is vital to maintaining the control panel's
immunity to unwanted transients generated by lightning and electrostatic discharge.
Operating Power: Secondary Power Source (Batteries)
The battery charger is current-limited and can recharge sealed lead-acid type batteries. The battery
charger shuts off when the control panel is in alarm.
B.2 Wire Requirements
Each type of circuit within the Fire Alarm Control System requires use of a specific wire type to
ensure proper circuit operation. The wire gauge of a particular circuit depends on the length of that
circuit and the current traveling through it. Use Table B.1 below to determine the specific wiring
requirements for each circuit.
Compliance with the Federal Communications Commission (FCC) and Canadian Department of
Communication regulations on electrical energy radiation requires the following: Use twisted-pair
shielded wire for any non-SLC-loop wiring entering or exiting the cabinet that is not enclosed in
conduit. Use twisted-pair unshielded wiring for SLC-loop wiring.
NOTE: If running an SLC in conduit with Notification Appliance Circuits, you can reduce
problems by exclusively using electronic sounders (such as the Spectralert or MA/SS-24 Series)
instead of more electronically noisy notification appliances (such as electromechanical bells or
horns).
78 IFC-640 Installation Manual P/N 51864:C 08/05/2005
Electrical Specifications Wire Requirements

Circuit Type
Circuit
Function
Wire Requirements
Distance
(feet/meters)
Typical Wire Type
*

SLC
(power limited)
Connects to
intelligent and
addressable
modules.
Twisted-unshielded pair, 12 to 18 AWG
(3.1 to 0.78 mm
2
). 50 ohms maximum per
length of Style 6 & 7 loops. 50 ohms per
branch maximum for Style 4 loop.
12,500 ft. (3,810 m)
9,500 ft. (2,895.6 m)
6,000 ft. (1,828.8 m)
3,700 ft. (1,127.76 m)
12 AWG (3.1 mm
2
)
14 AWG (2.00 mm
2
)
16 AWG (1.30 mm
2
)
18 AWG (0.78 mm
2
)
or Untwisted, unshielded wire, in conduit or
outside of conduit.
Note: Maximum total capacitance of all
SLC wiring (both between conductors and
from any conductor to ground) should not
exceed 0.5 mircofarads.
1,000 ft. (304.8 m) 12 to 18 AWG (3.1 to
0.78 mm
2
)
EIA-485
(power limited)
Connects to
LCD-80, ACS
modules, or
TM-4
Transmitter
Twisted-shielded pair with a characteristic
impedance of 120 ohms. 18 AWG (0.78
mm
2
) minimum.
6,000/1829
(max)
16 AWG (1.30 mm
2
)
EIA-232
(power limited)
Connects to
Printers, CRT,
or PC.
Twisted-shielded pair.
18 AWG (0.78 mm
2
) minimum.
50/15.24
(without modem)
16 AWG (1.30 mm
2
)
IDC
Initiating Device
Circuit
M300MJ,
M301MJ,
XP5-M,
XP10-M,
XP6-MA
(power limited)
12-18 AWG (3.1 to 0.78 mm
2
).
Maximum circuit resistance is 20 ohms.
12 to 18 AWG (3.1 to
0.78 mm
2
)
NAC
Notification
Appliance
Circuit
XP5-C,
M300CJ, XP6-C
(power limited)
12-18 AWG (3.1 to 0.78 mm
2
).
At alarm current level, no more than a 1.2
V drop at the end of the circuit, or sized to
provide the minimum rated operating
voltage of the appliances used.
To meet 1.2 V drop,
or sized to provide
the minimum rated
operating voltage of
the appliances used.
12 to 18 AWG (3.1 to
0.78 mm
2
)
24 VDC Power
Runs
(power-limited)
To TM-4
Transmitter,
Annunciator and
M300CJ
modules
12-18 AWG (3.1 to 0.78 mm
2
).
Size wire so that no more than 1.2 V drop
across wire run from supply source to end
of any branch.
To meet 1.2 volt drop 12 to 18 AWG (3.1 to
0.78 mm
2
)
CHG-120 External battery
charger
12 AWG (3.1 mm
2
) in conduit 20/6.1 (max) 12 AWG (3.1 mm
2
)
Table B.1 Wire Requirements
* Notifier brand cable is recommended; see the product catalog available from Paige Electric.
NOTE: Lightning arresters required on circuits extending between buildings; 999 meter length
maximum to meet UL 1459.
IFC-640 Installation Manual P/N 51864:C 08/05/2005 79
Appendix C: Compatible Equipment
These are the most common devices at time of publishing; the most complete list of compatible
intelligent SLC loop devices is provided in the SLC Wiring Manual; for conventional
non-addressable equipment see the Device Compatibility Document.
Johnson Controls and Notifier Equipment
AA-30 30-Watt Audio Amplifier
AA-100 100-Watt Audio Amplifier
AA-120 120-Watt Audio Amplifier
JABF-1B Annunciator Flush Box
JABF-1DB Annunciator Flush Box with Door
JABF-2B Annunciator Flush Box
JABF-2DB Annunciator Flush Box with Door
JABF-4B Annunciator Flush Box
ABF-4DB Annunciator Flush Box with Door
ABM-16AT Annunciator Blank Module
ABM-32A Annunciator Module Blank
JABS-1TB Annunciator Surface Box
ABS-1B Annunciator Surface Box
ABS-2B Annunciator Surface Box
JABS-4B Annunciator Surface Box
ABS-8R Annunciator Backbox for ACM-8R
ACM-16AT Annunciator Control Module
ACM-24AT Annunciator Control Module
ACM-32A Annunciator Control Module
ACM-48A Annunciator Control Module
ACM-8R Annunciator Control Module
ACPS-2406 Auxiliary Charger/Power Supply
ACT-1 Audio Coupling Transformer
ACT-2 Audio Coupling Transformer
ADP-4B Annunciator Dress Panel
AEM-16AT Annunciator Expander Module
AEM-24AT Annunciator Expander Module
AEM-32A Annunciator Expander Module
AEM-48A Annunciator Expander Module
AFM-16A Annunciator Fixed Module
AFM-16AT Annunciator Fixed Module
AFM-32A Annunciator Fixed Module
AKS-1B Annunciator Key Switch
APJ-1B Annunciator Phone Jack
AMG-1 Audio Message Generator
AMG-E Audio Message Generator
APS-6R Auxiliary Power Supply
ARM-4 Auxiliary Relay Module
AVL-1 Audio Voice Link (Not ULC-listed)
BGX-101L Addressable Manual Pull Station
BMP-1 Blank Module Plate
BP-4 Battery Dress Plate
BX-501 Intelligent Detectors/Sensors Base
B501J Intelligent base
B501BH Sounder base
B210LPJ Intelligent detector base
CAB-4 Series Mounting Hardware (Doors and backboxes are
ordered separately. Black unless R is added to the P/N)
Doors (Add B to the P/N for blank door)
JDR-A4 A-sized door, 1 row of equipment
JDR-B4 B-sized door, 2 rows of equipment
JDR-C4 C-sized door, 3 rows of equipment
JDR-D4 D-sized door, 4 rows of equipment
Backboxes (For red, add R to the P/N)
SBB-A4 A-sized backbox
SBB-B4 B-sized backbox
SBB-C4 C-sized backbox
SBB-D4 D-sized backbox
Trim Rings
TR-A4 A-sized trim ring
TR-B4 B-sized trim ring
TR-C4 C-sized trim ring
TR-D4 D-sized trim ring
CCM-1 Communication Converter Module
CHS-4L Chassis for voice equipment
CHS-M2 Chassis for 1st row (included in basic equipment
package)
CHS-4MB Assembly: CHS-4N with MP-1B
CHS-4N Chassis for 2nd, 3rd, 4th rows
CHG-120 Battery Charger
CMX-1 Addressable Control Module
M510CJ Addressable Control Module
JCPU-640 control panel circuit board
1551J Ionization Smoke Detector
1251J Intelligent Ionization Smoke Detector
CRE-4 Control Relay Expander
CRM-4RK Control Relay Module
CRT-2 Video Display Monitor with Keyboard
DCM-4RK Dual Channel Module
DP-1B Blank Dress Plate
DP-DISP Display Dress Plate
DPDW-1B Double Well Dress Plate
DPSW-1B Single Well Dress Plate
DPI-232 Direct Panel Interface
M300CJ NAC Module
FCPS-24 Field Charger Power Supply
5551J Intelligent Thermal Sensor
FDU-80 Remote Fire Annunciator
FFT-7 Fire Fighters Telephone
FFT-7S Fire Fighters Telephone
FHS Fireman's Handset
M300MJ Monitor Module
M301MJ Mini Monitor Module
FSB-200S Single-ended beam smoke detector with sensitivity
testing
FSB-200 Single-ended beam smoke detector.
DH300P Photoelectric Duct Detector
DH300RP Photoelectric Duct Detector with alarm relay
DH300PL Low-flow DUCT Detector
DH300RPL Low-flow Duct Detector with alarm relay
DHX-501, DHX-502 Duct Detectors
1351J Ion Detector
Acclimate 2351TMJ Combination Photoelectric/Heat
Detector
FTX-P2J HARSH Smoke Detector
FTX-P1J Intelligent HARSH Detector
7351J VIEW Low Profile Laser Detector
M300SMJ Pull Station Monitor Module
FPJ Firefighters Phone Jack
M300RJ Relay Module
2351J Photo Detector
2351TJ Photo/Thermal Detector
continued

80 IFC-640 Installation Manual P/N 51864:C 08/05/2005
Compatible Equipment
System Sensor Equipment
A2143-00 End of Line Resistor Assembly
EOLR-1 End-of-Line Resistor Assembly
FSB-200, FSB-200S Beam Detectors

5351J Thermal Detector
5351RJ Thermal Detector (rate of rise)
High Temperature Detector
M500FPJ Telephone Module
M302MJ Monitor and Zone Interface Module
M300DJ Dual Monitor Module
ICE-4 Indicating Control Expander
ICM-4RK Indicating Control Module
3251J Advanced Multi-Sensor Intelligent Detector
M500XJ Loop Fault Isolator Module
KDM-2 Keypad/Display Unit
L20-300-BX Enclosure; recessed mount
L20-310-BX Enclosure; surface mount
LCD-80 Liquid Crystal Display Module
LCD-80TM Terminal Mode LCD Annunciator
LDM-32 Lamp Driver Module
LDM-E32 Lamp Driver Module
LDM-R32 Lamp Driver Module
LEM-320 Loop Expander Module
7251J VIEW Low Profile Laser Detector (CLIP mode)
M500MJ Addressable Monitor Module
M502MJ Addressable Monitor Module
M501MJ Addressable Mini Monitor Module
MP-1B Panel Module Dress Plate
NBG-12LRA Agent Release-Abort Station
JBG-12 Series Manual Pull Station
JBG-12LX Addressable Manual Pull Station
JNCA Network Control Annunciator
NCM-F Network Control Module (Fiber)
NCM-W Network Control Module (Wire)
IFW Intelligent Fire Workstation
N-ELR Assortment ELR Pack with Mounting Plate
JCI-LBB Battery Box
JCI-LBBR Red Battery Box
P-40 Keltron Printer
P40-KITB Dress plate for Keltron Printer
PRN Series 80-Column Printers (PRN-4, PRN-5, PRN-6)
PS-12120 Battery 12-volt, 12 amp-hour
PS-12180 Battery 12-volt, 18 amp-hour
PS-12250 Battery 12-volt, 25 amp-hour
PS-12550 Battery 12-volt, 55 amp-hour
PS-12600 Battery 12-volt, 60 amp-hour
R-120 120 Ohm End-of-Line Resistor
R-2.2K 2.2K End-of-Line Resistor
R-27K 27K End-of-Line Resistor
R-470 470 End-of-Line Resistor
R-47K 47K End-of-Line Resistor
RA400 Remote Annunciator
RA400Z Remote Annunciator with diode
RFX Wireless Transmitter (version 2.0 and higher): SDRF-751
Wireless Photo/Thermal Smoke Detector; 5817CB Wireless
Monitor Module
RPJ-1 Fireman's Phone Jack
RPT-485F EIA-485 Repeater (Fiber)
RPT-485W EIA-485 Repeater (Wire)
RPT-485WF EIA-485 Repeater (Wire/Fiber)
RM-1 Remote Microphone
RM-1SA Remote Microphone
SCS-8, SCE-8 Smoke Control Station
SCS-8L, SCE-8L Smoke Control Lamp Driver
2551J Intelligent Photoelectric Detector
2251J Intelligent Photoelectric Detector
STS-1 Security Tamper Switch
TM-4 Transmitter Module
UDACT Universal Digital Alarm Communicator Transmitter
UZC-256 Universal Zone Coder
VCE-4 Voice Control Expander
VCM-4RK Voice Control Module
VeriFire Tools Upload/Download Software
VP-2B 2 Filler Dress Plate
XP5-C Transponder Control Module
XP5-M Transponder Monitor Module
XPC-8 Transponder Control Module
XPDP Transponder Dress Panel
XPIQ Quad Intelligent Audio Transponder
XPM-8 Transponder Monitor Module
XPM-8L Transponder Monitor Module
XPP-1 Transponder Processor
XPR-8 Transponder Relay Module
XP6-C Supervised Control Module
XP6-R Six Relay Control Module
XP6-MA Six Zone Interface Module
XP10-M Ten Input Monitor Module

IFC-640 Installation Manual P/N 51864:C 08/05/2005 81
Appendix D: Canadian Applications
D.1 Standalone Application
D.1.1 IFC-640 with KDM-2
If using KDM-2 as the primary display for IFC-640, an ACS series annunciator must be mounted
adjacent to the panel or within IFC-640 enclosure.
D.1.2 IFC-640 with JNCA
Network Control Annunciator (JNCA) with 640-character, multi-line display complies with ULC
requirements when used as the primary display for IFC-640.
D.2 Local Network Application
To meet ULC requirements, the networks Manual Controls may only be operated from one
location at any given time. When panels are networked (using NCM Network Control Modules),
employ AKS-1 Key Switch on each panels Primary Annunciator to enable its functions. JNCA
may be a Primary Annunciator when AKS-1B is installed. Refer to the JNCA Manual for more
information.
A JNCA or Intelligent Fire Workstation (IFW) may be employed as a Display and Control Center.
In the event that communication fails between the panels and the Control Center, the panels will
continue to function in local/standalone mode.
D.3 Automatic Alarm Signal Silence
If selecting this feature for a system requiring annunciators, consult the Authority Having
Jurisdiction.
D.4 Annunciator Applications
1. In Canada, the ACM series annunciator modules must be used to annunciate the fire alarm
input points/zones only, if no multi-line sequential display is installed.
2. For Canadian applications, the following LED colors must be employed:
Red must be used to indicate active alarm inputs.
Yellow must be used to indicate supervisory, burglary or trouble signals.
Green must be used to indicate the presence of power or an activated output.
D.5 Releasing Devices
Supervision for shorts is required; use REL devices and type code REL CKT ULC.
(With on-board NACs, use REL-2.2K; with M300CJ modules use REL-47K. Refer to Section 4.5
Releasing Applications for details.
82 IFC-640 Installation Manual P/N 51864:C 08/05/2005
Notes


IFC-640 Installation Manual P/N 51864:C 08/05/2005 83
Index
Numerics
24 VDC, see also Power:DC 40
5351J 21
A
A77-716B
Replaced by EOLR-1
See power supervision relay
AC, see Power 39
Acceptance Test 67
ACM-16AT 24
ACM-8R
labeling requirements 43
Overview 23
ACPS-2406 (Overview) 19
ACS, see Annunciators 24
Added index marker for monitor module 61
Addressable Modules (Overview) 22
AFM-16AT
Overview 25
AFM-32A
Overview 25
Agent Release-Abort Station 66
Alarm relays, see Form-C relays 42
AMG-1, see also Voice Alarm System 27
Annunciator Fixed Modules (Overview) 25
see Annunciator Fixed Module Manual
Annunciators 23
ACM-16AT, AEM-16AT 25
ACM-24AT, AEM-24AT 24
ACM-32A, AEM-32A 25
ACM-48A, AEM-48A 24
Overview 24
APS-6R 19
See Auxiliary Power 40
ARM-4
Installation steps 49
non-power-limited circuits 43
Stand-off and Terminal Locations 49
Audio Amplifiers (Overview) 27
see also Voice Alarm System
Auxiliary Relay Module, see ARM-4 49
B
B224BI 22
B224RB 22
Backboxes, see Cabinets
Backup-alarm switches 42
Basic Equipment Packages 14
Batteries
Battery Boxes 19
Battery calculations 69, 71, 72, 73, 74
Battery Checks and Maintenance 68
Battery specifications 75
Connections 40
Overview 19
see also Power: DC 40
Blank modules 18
C
Cabinets 18
Battery backboxes 19
Mounting 30
California code 47, 48
Canadian Applications 34, 81
central receiving unit
see also UDACT manual 60
Chassis 18, 37, 49
CHG-120 (Overview) 20
Circuit Board, see CPU
Compatible Equipment 79
Components 16, 17
Control Modules (Overview) 22
Control Panel Circuit Board, see CPU
CPU
drawing 15, 16, 17
Installation steps 33
Overview 15
CRM-4RK, CRE-4
Connections 48
Driving an ARM-4 49
Mounting instructions 44
non-power-limited circuits 43
Overview 26
CRTs 54
CRT/PRN combination 54
CRT-2 Configuration 52
CRT-2 Function Keys and parameters 53
CRT-2 Overview 26
Installation 5054
D
D35 on ICM-4RK 48
DC, see Power 39
Detectors
Detector bases 22
listing 21
Detectors (Overview) 20
Display Terminal (Overview) 26
Dress Panels 18
Dual Channel Module (Overview) 27
see also Voice Alarm System
E
Electrical connections 38
Electrical Specifications 75
EOLR-1 See power supervision relay
84 IFC-640 Installation Manual P/N 51864:C 08/05/2005
FP
Expander boards, see Panel Circuit Modules: Expander
Board Modules 44
F
FCPS-24, FCPS-24S (Overview) 20
Fire Fighters Telephone, see also Voice Alarm System
Manual 27
Fire/Security Applications 5962
FlashScan (Overview) 21
Form-C relays 23, 24, 26, 42, 48, 76
Four-wire Smoke Detector
Specifications 76
FSB-200, FSB-200S 21
I
ICM-4RK (Overview) 26
see also Panel Circuit Modules
Installation
Checklist 30
Preparation 29
J
JBG-12LX 22
JCPU-640 (120V operation), see Basic Equipment Packag-
es 14
JCPU-640E (240V operation), see Basic Equipment Pack-
ages 14
JNCA 34
also see Primary display 14
Overview 19
JTCC-1B, see Voice Alarm System 27
Jumper locations 16, 17
ICM-4RK 46
JVCC-1B, see Voice Alarm System 27
JVTCC-1B, see Voice Alarm System 27
K
KDM-2
Installation steps 33
Keltron printer (Overview) 26
Keltron, see also Printers 52
L
LCD-80
Overview 20
LDM-32 (Overview) 23
LDM-R32
non-power-limited circuits 43
LDM-R32 (Overview) 24
LED locations 17
LEM-320 (Overview) 19
lockout 67
Loop Expander Module
Installation steps 35
M
M300CJ 65
M300MJ 61
Main power supply 15
Maintenance 67
microcontroller failure 42
Monitor Modules (Overview) 22
Mounting
LEM 36
Panel Circuit Modules 45
Multi-Input/Output Modules 23
N
NACs (Notification Appliance Circuits)
Backup option 42
NAC Connections 41
Releasing applications 41, 42, 63, 64
Specifications 76
NBG-12LRA 66
NCM-W/F, see Networking
Networking 36
NCM-W/F (Overview) 19
NFPA Applications
NFPA 72 Central or Remote Station Fire Alarm
System 58
NFPA Applications (Overview) 57
Nonpower-limited circuits
UL wiring requirements 43
Notification Appliance Circuits, see NACs
O
Operating Power 77
Operational Checks 67
Output relays
Connections 23, 24, 26, 42, 48, 76
Specifications 76
P
Panel Circuit Modules
ICM-4RK Connections 46
ICM-4RK Field-wiring 47
ICM-4RK Jumpers 46
ICM-4RK Resistors 48
ICM-4RK/ICE-4 Connections 46
Installation steps 37, 44
Mounting Expander Boards 44
Overview and complete list 26
Ribbon cables 45
see also ICM-4RK, ICE-4, CRM-4RK, CRE-4,
VCM-4RK, DCM-4RK, VCE-4 44
Periodic Testing 67
Power
AC Power Checklist 39
AC power connections 39
AC specifications 75
Auxiliary Power 40
DC power connections 39, 40
Installation steps 38
Power specifications 38, 76
IFC-640 Installation Manual P/N 51864:C 08/05/2005 85
QX
power supervision relay 65, 66
Power supply calculations 69, 71, 72, 73, 74
Power-limited Wiring Requirements 43
primary display 14, 34
Printers 54
Installation 5054
Keltron printer Connections 52
Overview 25
PRN series (overview) 25
PRN series connections 50
PRN settings 51
PRN/CRT combination 54
Proprietary Security Alarm Applications
Wiring 61
Protected Premises Unit 58
Q
Quad Intelligent Audio Transponder
see also XPIQ 23
R
RA400Z 22
Related Documentation 10
Relays, see Form-C relays 42
Releasing Circuits
Connections 41
Releasing Applications 6366
Releasing Applications, Canada 81
Specifications 76
Releasing Device
Connections 64
M300CJ Connections 65
Remote Microphone, see Voice Alarm System 28
Resistor locations
ICM-4RK 48
S
S5000 modules, see Panel Circuit Modules 26
Security relays, see Form-C relays 42
security switch, wiring 62
Security Tamper Switch 60, 61
Service 67
Signaling Line Circuit, see SLC 20
SLC 20, 35
see also SLC Wiring Manual 55
specifications 76
Specifications 76
Stacker-connector 36
Stand-off Lengths 32
STS-1, see also Security Tamper Switch 61
Supervisory and Security contacts
configuring as Alarm contacts 42
Supervisory relays, see Form-C relays 42
Supplemental Documentation 10
Switches
Backup-alarm 42
switch locations 16, 17
System
Description of features 13
Limitations 14
Options 13
System current draws 69, 71, 72, 73, 74
T
Terminal block locations 16, 17
Testing 67
TM-4
see Transmitter Module TM-4 43
TM-4 (Overview) 19
Transponders (Overview) 22
Trouble relays, see Form-C relays 42
U
UDACT (Overview) 19
UL nonpower-limited wiring requirements 43
UL Requirements 43
UZC-256 (Overview) 20
V
VCM-1 (Overview) 27
see also Voice Alarm System
VeriFire 54
Voice Alarm System
Overview 27
see also Voice Alarm System Manual
Voice Alarm System (Overview) 28
W
Wiring
Proprietary Security Alarm Applications 61
Wire Requirements 77
X
XP5-C 23
XP5-M 22, 61, 62
XP6-C, XP6-R, XP10-M, XP6-MA 23
XPIQ (Overview) 23
86 IFC-640 Installation Manual P/N 51864:C 08/05/2005
XX
IFC-640 Installation Manual P/N 51864:C 08/05/2005 87
Controls Group
507 E. Michigan Street
P.O. Box 423
Milwaukee, WI 53201
www.johnsoncontrols.com
Release C
Printed in U.S.A.

You might also like