Standard Specification for
Weirs and Baffles
1 Scope
1.1 This specification shall govern all work necessary to finish fiberglass weir plates, scum
baffles, mounting brackets, lap plates and cover washers. Fabrication shall be in strict
compliance with the American Water Works Association procedures set forth in standard
ANSI/AWWA F102-91.
2 General (Reference Drawing W-001 attached)
2.1 The contractor shall furnish and install fiberglass weir plates, scum baffle plates, and scum
baffle supports as shown on the plans. Included shall be necessary butt and splice plates at
each weir and baffle plate joint to prevent short circuiting. Necessary fiberglass washers
and stainless steel mounting hardware shall also be included. All hardware shall be type
316 stainless steel unless otherwise specified by the engineers.
3 Materials
3.1 Resin Requirements
The resin shall be a commercial-grade polyester thermosetting resin, which has been determined
to be acceptable for the service conditions. The resin shall contain no fillers or additives except
as follows:
a. A thixotropic agent may be added for viscosity control.
b. Pigments shall be light stable, not soluble in water, and compatible with the resin.
Typical color shall be blue-green.
3.2 Glass Reinforcement
The reinforcing materials used shall be Type E glass mat, with chrome or silane finish and a
styrene-soluble binder compatible with the resin. Surfacing veil shall be Type C veil, with
styrene-soluble binder compatible with the resin.
3.3 Ultraviolet Resistance
Ultraviolet stabilizers are required in all laminates exposed to ultraviolet light, whether it be in
the form of pigmentation or ultraviolet absorbers.
2
3.4 Laminate Minimum Physical Properties
Minimum physical properties for the product shall conform to those presented in Table 1 below:

Table 1. Laminate Minimum Physical Properties

Property @ 70
0
F Value Test Method

Tensile Strength (10
3
psi) 7.5 ASTM D638
Flexural Strength (10
3
psi) 16 ASTM D790
Flexural Modulus (10
6
psi) 0.8 ASTM D790
Barcol Hardness 35 ASTM D2583
Water Absorption, max. (24 hr) 0.2% ASTM D570
Notched Izod Impact Strength (ft-lb/in.) 10 ASTM D256
4 Submittals
4.1 Final approval for incorporation into the project will be made only after the review of shop
drawings, specifications, and data as follows:

a. Shop drawings complete with all dimensions, details of connecting piping, and the size
and location of any required openings.
b. Specifications for all components.
c. Details of the major fabricated components showing the arrangement of components and
labeled with member sizes and materials of construction.
d. Structural calculations for all components.
e. Manufacturers recommended procedures for jobsite storage of equipment, handling, and
erection.
4.2 Design Criteria
4.2.1 Dimensions - The dimensional criteria included in this specification is based on existing
tooling and practice, which have become the industry standard.

a. Weir plates shall be a nominal 1/4 inch thick and shall have 90 degree V-notches,
rectangular notches, or shall be flat crested (straight edge). For 2 or 2- % inch deep V-
notches, the weir plate shall be 9 inches wide. For 3 inch deep V-notches, the weir plate
shall be 10 inches wide. Flat crested weir plates shall be straight, varying not more than
+/- 1/32 inch in 12 feet of length. Other sizes may be produced with agreement between
purchaser and manufacturer.

b. Weir plates shall be provided with 2-5/8 inch diameter holes for mounting hardware. For
curved walls, these holes shall be located a maximum of 24 inches on center. For straight
walls, holes shall be located a maximum of 12 inches on center. The holes shall provide a
minimum of two inches vertical and horizontal adjustment. Weir plate slots for mounting
3
to troughs shall be 1/16 inch wider that the bolts, and shall provide for a minimum
adjustment of %inch after allowing for the diameter of the attachment bolt.

c. Weir plates shall be secured to the walls by anchor bolts and 5 inch diameter fiberglass
washers to prevent short circuiting. The ends of the weir plates shall be covered by 6 inch
wide butt plates, arranged to allow for horizontal expansion.

d. Scum baffle plates shall be a nominal '/inch thick by 12 inches wide. Mounting holes
shall be counter-sunk to a depth that allows the flat head bolts to be flush or below the
surface. Spacing of holes for mounting brackets shall be a maximum of 48 inches for
curved walls, and a maximum of 24 inches for straight walls.

e. Scum baffle mounting brackets shall have a width of not less than 3 inches, a base length
of not less than 6 inches, and a depth of not less than 6 inches. Brackets shall be
fabricated from fiberglass-reinforced material with a nominal thickness of 1/4 inch.

f. All weir plates and baffle plates shall be of standard length not to exceed 12 feet with
closure plates made to length at the factory. Final laminate thickness shall be +/- 10% of
the nominal specified thickness.
4.2.2 Finish and Appearance - All weir plates and baffle plates shall have uniform, smooth,
resin rich surfaces and shall be free of voids and porosity, without dry spots, crazes or un-
reinforced areas. All plates shall have a glass content of 30%, +/- 2%.
5 Quality Assurance
5.1 Qualifications
Contractor shall have a minimum of five (5) years of history of successful installations of similar
design. Past job list with customer contact information will be supplied if required.
5.2 Manufacturers Quality Control
All fabrication shall be carefully inspected at the factory by inspectors who shall use whatever
means necessary to assure the proper fit of all field connections and compliance with all material
and fabrication requirements of the specifications.
5.3 Warranty
Manufacturer shall warrant the Density Current Baffle to be free of defects in materials and
workmanship for a minimum of one (1) year after installation with a maximum of eighteen (18)
months from date of shipment.
5.4 The contractor shall be responsible for verifying all field dimensions to develop and
approve shop drawings.
4
Manufacture
5.5 Materials, equipment, and components in this section shall be the products of:

Fiberglass Fabricators, Incorporated
P.O. Box 17068
964 Douglas Pike
Smithfield, RI 02917
5.6 Manufacturing Procedures
The matched-die molding process shall be used to produce fiberglass-reinforced plastic molded
parts with smooth resin-rich surfaces and edges, dimensional accuracy, and consistency. Weir
plate notches shall be molded within dies to ensure resin-rich edges and notches for increased
corrosion and weather resistance. Weir plates and scum baffle plates produced from fabricated
plate stock with cut edges and notches will not be acceptable. All cut edges shall be sanded and
sealed with nonair-inhibited resin to ensure edges are completely sealed and to prevent water and
chemicals from penetrating the laminate.
6 Installation, Storage, Handling, and Maintenance
6.1 The manufacturer shall provide detailed written instructions for the installation, long term
storage, handling, and maintenance for the products provided.



Figure 1. Drawing W-001