This document provides installation and maintenance instructions for GEA Searle KEC/KMe, KECX, KMCX, KECP, and KMCP equipment. It outlines important health and safety considerations for installation and maintenance. It also provides detailed instructions on location, handling, pipework, electrical, and defrost system setup for low temperature models. Routine maintenance of inspecting for ice buildup and checking security of fixings is recommended every 12 months.
This document provides installation and maintenance instructions for GEA Searle KEC/KMe, KECX, KMCX, KECP, and KMCP equipment. It outlines important health and safety considerations for installation and maintenance. It also provides detailed instructions on location, handling, pipework, electrical, and defrost system setup for low temperature models. Routine maintenance of inspecting for ice buildup and checking security of fixings is recommended every 12 months.
This document provides installation and maintenance instructions for GEA Searle KEC/KMe, KECX, KMCX, KECP, and KMCP equipment. It outlines important health and safety considerations for installation and maintenance. It also provides detailed instructions on location, handling, pipework, electrical, and defrost system setup for low temperature models. Routine maintenance of inspecting for ice buildup and checking security of fixings is recommended every 12 months.
This document provides installation and maintenance instructions for GEA Searle KEC/KMe, KECX, KMCX, KECP, and KMCP equipment. It outlines important health and safety considerations for installation and maintenance. It also provides detailed instructions on location, handling, pipework, electrical, and defrost system setup for low temperature models. Routine maintenance of inspecting for ice buildup and checking security of fixings is recommended every 12 months.
KECX, KMCX, KECP, KMCP 1.HEALTH AND SAFETY This concerns the hazards, which may be encountered when installing and maintaining this equipment. It is therefore important that these instructions are followed. 1.1 Before installation Ensure that: a) The voltage, working fuid and the maximum working pressure stated on the product nameplate are suitable for the working environment. b) The proposed method of mounting is adequate to support the total operational weight of the units.
1.2 During installation and maintenance Ensure that: a) The unit is installed and maintained by qualifed personnel only. b) The electrical supply is isolated and secured from accidental reconnection. c) The working area is adequately ventilated. d) The temperature of coils with vinyl coated fns does not exceed 150C (e.g. during brazing) as toxic fumes would be produced. 2. INSTALLATION 2.1 General Upon receipt, the units should be visually inspected and the sup- plier notifed (within seven days) of any damage or shortages. The units are designed for ceiling mounting using the fxing holes provided. Units are not portable and are only for per- manent installation. Knockouts in the side of the unit give access for the connection of services. 2.2 Location The location of the unit should be carefully selected to ensure that: a) Air distribution from the cooler is not adversely affected by obstructions and is appropriate for the size and shape of the room, optimum air distribution should be targeted. Product loading must be in ac cordance with good refrigeration practice. b) Air entering the cooler is not obstructed c) The unit must be installed level in both directions d) Maintenance access should be considered when locating the product, including adequate space for heater withdrawal when appropriate e) The unit is not subjected to physical loads
2.3 Handling For transportation the unit is inverted and bolted to the base of the packing case. Care must be taken while removing the pack- aging and installing to prevent damage, particularly of the fnned coil. The drainpan is ftted to the unit (in its transit/lifting position) for transportation. Remove the draintray by removing the four fxings and then ft the hexagonal drain connection and gasket into the hexagonal well inside the draintray. Hand tighten this assembly using the knurled nut on the outside. Reft the draintray in its transit position (fxings loose) making use of the slots in the tray so that it moves into contact with the underside of the cooler bottom plate so that the weight is transferred directly to the chassis of the unit when lifng into po- sition. When the cooler is in position ensure that the drainpan is dropped down into the operating position before tightening its fxings. 2.4 Pipework Refrigeration Pipework Pipework to and from the unit should be selected to suit the application and not the connection size of the unit. It should be supported independently from the unit and in a way that pre- vents the transmission of vibration to the unit . A competent engineer should install refrigeration pipwork to a high standard of refrigeration practice. The distributor must be vertical. Condensate Drainage Once the unit is in place the drain tray MUST slope downwards towards the drain connection. On the KEC and KMe the fxings at the rear of the drain tray should be loosened to allow the back of the drain tray to drop into its operating position. The drain con- nection is 1 BSP (M) nylon on the KMe and KEC and should be hand tightened when connected to the drain. Ensure that drain- line size is equivalent to that of the drain connection and that it has an adequate fall. It is essential that the drainline includes a trap, ftted outside the coldroom. TEV Selection It is important that the TEV is correctly sized. The TEV size should be determined using the maximum design capacity and the minimum valve pressure drop. This occurs at the minimum condensing pressure. An externally equalised TEV must be used. When calculating the minimum valve pressure drop, al- lowance must be made for the coolers distributor system. R404A, R407C, R410A, R507A , R744 1.5 bar R134a 1.0 bar Evacuation To avoid potential moisture related problems; it is necessary to evacuate the complete system to a minimum of 1 torr (1.3mbar). All parts of the system must be above freezing and ideally higher than +10C during evacuation. 2 2.5 Electrical Motors, and defrost heaters when ftted, are factory wired to a junction box. An internal wiring diagram is affxed to the lid of this box, except aerofoil fans that require the supply to be connected direct to the motors terminal box. Generally cage clamp type terminals are used. These are opened by pushing a correctly sized screwdriver into the square aperture adjacent to the conductor entry. Conductors should be between 1 and 2.5mm. KMe single fan units use a screw type terminal block for motor supply. Internal and site wiring share common terminals, so care must be exercised to ensure that the internal wiring is undisturbed. All single phase motors have automatic internal overload protec- tion, and can be used in conjunction with a high quality triac type speed controller. Three phase motors MUST be protected against overload and single phasing. Overloads must be set to cut out at FLC + 15% @ 10C room temperature and FLC + 25% @ minus 30C room temperature (proportion for other temperatures). Check that the fan rotation of 3 phase units is correct. The standard rotation on KMe and KEC units is clockwise when looking into the fan discharge. On 3 phase units the rotation can be changed by reversing any two phases of the motor supply. Some KMe units with electric defrost have an auxiliary terminal box at the refrigerant connection end of the unit. It is not necessary to make any electrical connection to this box. If RCDs (Residual Current Detectors) are to be used, a trigger level of less than 100 mA is likely to result in nuisance tripping. 2.6 Low temperature models Defrost Natural defrost is not suitable for coolers operating with an air leaving temperature of less than 3C. If the initiation of defrost periods is by a timing device then it is recommended that it be initially set to two defrost periods per 24 hours for KEC units and four for KMe units until operating experience is gained. (Speed controlled units may require more frequent defrosts). System pump down (fans running) is recommended (essential on very low temperature applications) prior to defrost so that the result- ing defrost is neither prolonged nor uneven. Initial Defrost Termination Settings Time/Time defrost system Electric defrost(230/400volts) KMe:30 minutes KEC:30 minutes (220/380volt: + 5min, 240, 240/415volt: - 5min) Time/Temperature termination system Electric defrost: minimum setting 4.5C Time/Pressure termination system Reverse cycle/hot gas defrost Pressure equivalent to 25C SST of the system refrigerant. Drain Down Time A drain down time, with fans off and no cooling, of fve minutes duration should be given immediately following a defrost termination. Fan Delay Setting a) With Thermostat: -7C b) With Pressure Switch: Refrigerant pressure at a saturation temperature of -12C. Defrost Termination Thermostat If a defrost termination thermostat is to be ftted then care must be taken in locating its sensor. It should initially be positioned between the coil fns on the air on side, away from heater elements. It may be secured into position by wrapping the fns around it. Small sensors should be enclosed in a suitable copper tube to slow response. Once the system is in operation it may be necessary to relocate the phial to the area of the coil where ice remains the longest during defrost (possibly air off face). Gener- ally, it is possible to wire an internally located phial through the units internal junction box. Drain Line Heaters Drain line heater cables or tapes should be permanently ener- gised and cover the drain pan connection. 2.7 Air Throwers Air throwers can be ftted to the guards of the 400mm fansets, on KMe units they ft over the terminal box and clip onto the wire mesh guard. 3. INITIAL STARTING Before running the unit for the frst time, check that all guards, motor mountings and electrical covers are secure, all un- necessary terminal block links are removed and fans rotate freely. Ensure that the drainpan has been lowered to the operating position. Once running, check that there are no unu- sual noises or vibrations. After allowing the unit to operate for at least 2 hours at conditions close to design, the TEV must be adjusted to provide the correct level of superheat. This is between 0.6 and 0.75 x cooler TD, to a maximum of 8K. Similarly review all defrost settings. 4. MAINTENANCE (Routine) WARNING! UNIT MUST BE ELECTRICALLY ISOLATED BEFORE MAINTENANCE WORK IS UNDERTAKEN. The following routine maintenance is required: Periodically inspect units for ice build up where the ambient tem- perature is below 5C. 3 KEC Wiring Diagrams
Every 12 months check 1) Security of fxings especially fan motor mountings. 2) Refrigerant pipeline for damage and leaks. 3) Motor(s) rotate freely. 4) Electrical connections for security of attachment. 5) Defrost, if used, is operating effectively. When necessary Clean the fns, guard, drain pan and drain lines and general casework. Care must be taken when cleaning the fns to prevent damage. A soft brush and mild detergent solution is rec- ommended. 1. Loosen end panel screws and lift off end covers 2. Remove all M5 pozi screws (4 off) to remove fan plate 3. Remove M5 countersunk screws (2off) to remove fanset Coil Block Heaters Coil block heaters are either U bent or straight and they have to be disconnected from the terminal box at the electrical connection end and sometimes from the auxiliary terminal box at the refrigeration connection end of the cooler. These heaters are withdrawn and replaced from the refrigeration connection end of the cooler taking care to retain the anti-creep clips. These clips may be re-used but will possibly need retension- ing. To avoid damage to either the coil fns or the heater cable, the heater cable should be inserted into a similar length of 1/4 OD copper tube and fed carefully through the fns with a twist- ing motion. With care the heater element sheaths can be curved through 90 (minimum radius 600mm) for removal and reftting purposes. Before attempting to reft a heater it is essential to en- sure that the coil heater hole has not become obstructed with ice and wherever possible the coil block should be above freezing point. Drain Pan Heaters Replacement is achieved by disconnecting the elements from the terminal box(es) after removing the end cover and drain pan, and unclipping/unscrewing the heater retaining clips. 5. INVALIDATION OF GUARANTEE Failure to install, set up or put to work any part of the equipment in the manner specifed in the Installation and Maintenance Instructions could invalidate the guarantees set out in the Standard Terms and Conditions of Sale.
4 2 1 B R O W N
B L A C K
KMe Wiring Diagrams
GEA Heat Exchangers GEA Searle 20 Davis Way, Newgate Lane, Fareham, Hants, PO141AR Tel. + 44 (0) 1329 823344, Fax + 44 (0) 1329 821242 [email protected], www.searle.co.uk Part Number Oct 2010 272-000-315