Hybrid Masonry Design 2.13.01 - 12.29.09
Hybrid Masonry Design 2.13.01 - 12.29.09
Hybrid Masonry Design 2.13.01 - 12.29.09
d
[Eqn. 4]
Figure 5Type IIb Force Distribution
P
axial
SHEAR
H
C
top
kd
P
wall
M
C
bottom
kd
l
w
Deflected shape
Figure 5- Type IIb Force Distribution
The axial load imparted to the wall is a function of the
construction sequence. This should be stated in the
construction documents. For example, if the steel is
designed for only the slab and framing dead load and
the lateral load effects, the masonry walls must be
constructed tight to the framing above after the slab is
in place but before the wall above is started. The steel
framing and the masonry must be designed using similar
assumptions.
Type III Hybrid Walls
This wall type is fully confned within the framing (Figure
6). It is most similar to the transitional buildings from
the early 1900s. However in this modernized version, the
masonry is engineered and reinforced to support axial and
shear loads in addition to the out-of-plane loads. As with
the Type II hybrid wall, the designer has the option to
design the columns and beams/girders for the portion of
the gravity loads installed before the masonry.
Currently, there are no standards in the United States
that govern the design of this type of wall. Research is
underway to help defne the behavior of these walls which
should lead to code requirements. Designers should only
use this system at their own discretion. Statics can be
used to generate formulas comparable to the Equations 1
though 4 for Type I and Type II hybrid walls.
Figures 7 and 8 show the two variations (Type IIIa and Type
IIIb) based upon how the overturning force is handled.
Figure 6Type III Hybrid Wall
NO GAP NO GAP
NO GAP
TYPE
III
BEAM OR
GIRDER
COLUMN
SHEAR WALL
SHEAR (IN-PLANE)
COLUMN
SHEAR
(IN-PLANE)
SHEAR
(IN-PLANE)
AXIAL LOAD
Note: Type lll not yet included in building codes
Figure 6 - Type III Hybrid Wall
( )
2 3
( )
2 3
- -
AIR BARRIER UPDATE - page 2
IMI 2009. ALL RIGHTS RESERVED.
C
This document is intended for the use of industry professionals who are competent to evaluate the significance and limitations of
the information provided herein. This publication should not be used as the sole guide for masonry design and construction, and
IMI disclaims any and all legal responsibility for the consequences of applying the information.
International Masonry Institute 42 East Street Annapolis, MD 21401 1-800-IMI-0988 www.imiweb.org
HYBRID MASONRY DESIGN - page 5
HYBRID DESIGN
As discussed, the masonry in hybrid structures can carry
out-of-plane loads in addition to in-plane loads. The
masonry design can be performed based upon the code
for reinforced masonry using allowable stress (based upon
linear elastic methods). As strength design procedures
gain acceptance, load factor design with non-linear elastic
evaluation of the masonry will be possible.
While there are three hybrid types that dictate the
loadings (Type I, II, and III), there are three shear wall
types available for the design of the walls themselves.
The shear wall type is dependent upon the minimum
prescriptive reinforcement and grouting. The Building
Code Requirements for Masonry Structures and the
International Building Code (IBC) [Ref. 3, 4] classify shear
walls as ordinary reinforced, intermediate reinforced,
or special reinforced. Therefore, there are three
combinations of hybrid types to choose from.
The structural steel system design and the in-plane loads
to the masonry are based upon the IBC using seismic factors
for R (response modifcation coeffcient),
0
(system over-
strength factor), and C
d
(defection amplifcation factor)
applicable to the type of shear walls used with building
frames. These factors are given in Table 2:
Table 2 Factors Based On
Shear Wall Type [Ref. 9]
Shear Wall Type R
o
C
d
Ordinary Reinforced 3 2.5 2.25
Intermediate Reinforced 4 2.5 2.5
Special Reinforced 5.5 2.5 4
Ordinary reinforced shear walls are permitted in Seismic
Design Categories (SDC) A, B, and C. The building height is
unlimited for SDC A and B and limited to 160 feet (48.8 m)
for SDC C.
Intermediate reinforced shear walls are permitted in SDC
A, B, and C. The building height is unlimited.
Special reinforced shear walls are permitted in all seismic
design categories. The building height is unlimited for SDC
A, B, and C, limited to 160 feet (48.8 m) for SDC D and E,
and limited to 100 feet (30.5 m) for SDC F.
While these are the permitted types and classes, most
hybrid projects thus far have been in SDC A, B and C. This
has been convenient in that an R=3 type structural steel
design has been used in accordance with AISC. Designs in
SDC D and higher would require use of the AISC Seismic
Design Manual AISC 327-05 (Ref. 9). Research is on-going for
various aspects of the systems in higher seismic classes.
COMPUTER SOFTWARE
Several commercial software companies have masonry
design packages [Ref. 5, 6] which have included hybrid
masonry in their packages. This allows the masonry
and steel to be modeled and designed as a system.
The software is primarily based upon allowable stress
design and linear elastic analysis. There are plans are to
incorporate strength design in the future.
Figure 8Type IIIb Force Distribution
SHEAR
P
axial
C
left
H
P
wall
C
bottom
lw
C
right
kd kh
M
kh
C
top
kd
Note: Type lll not yet included in building codes
Figure 8 Type IIIb Force Distribution
Deflected shape
Figure 7Type IIIa Force Distribution
SHEAR
P
axial
C
left
H
P
wall
T
C
lw
C
right
kd kh
M
kh
Figure 7 Type IIIa Force Distribution
Note: Type III not yet included in building codes
Deflected shape
AIR BARRIER UPDATE - page 2
IMI 2009. ALL RIGHTS RESERVED.
C
This document is intended for the use of industry professionals who are competent to evaluate the significance and limitations of
the information provided herein. This publication should not be used as the sole guide for masonry design and construction, and
IMI disclaims any and all legal responsibility for the consequences of applying the information.
International Masonry Institute 42 East Street Annapolis, MD 21401 1-800-IMI-0988 www.imiweb.org
HYBRID MASONRY DESIGN - page 6
CONCLUSIONS
Hybrid masonry offers many benefts and complements
framed construction. By using the masonry as a structural
element for in-plane loads, the constructability of the
masonry with the frames is improved, the lateral stiffness is
increased, the redundancy is improved, and opportunities
for reduced construction costs are created.
Designs indicate that greater stiffness can be achieved
with hybrid masonry systems in comparison with braced
frames or moment frames. The benefcial effect on the
framing through the load-sharing abilities of the system
is also evident. These qualities, stiffness, and redundancy
can be useful in preventing progressive collapse.
For now, Type I and Type II hybrid systems can be designed in
the United States using existing codes and standards. Criteria
for Type III hybrid systems are under development.
Details for the construction of hybrid walls and design
issues related to the top connectors are discussed in IMI
Technology Brief 02.13.02 and NCMA TEK 3-3B (Ref. 7,8).
NOTATIONS:
C = resultant compressive force, lb (N)
C
bottom
= resultant compressive force at bottom
of masonry wall, lb (N)
C
d
= defection amplifcation factor
C
left
= resultant compressive force on left side
of masonry wall, lb (N)
C
right
= resultant compressive force on right side
of masonry wall, lb (N)
C
top
= resultant compressive force at top
of masonry wall, lb (N)
d = distance from extreme compression fber to
centroid of tension reinforcement, in. (mm)
e = eccentricity of the tie-down force, equal
to the distance of the tie-down reinforcement
from the center of the wall, in. (mm)
H = shear force, lb (N)
h = effective height of masonry element, in (mm)
k, k = ratio of distance between compression
face of wall and neutral axis to the
effective depth, d, for the bottom and
top of the wall; and to the height of the
wall, h, for the sides, respectively.
l
w
= length of entire wall or of segment of wall
considered in the direction of shear force,
in. (mm)
M = maximum moment at the section under
consideration, in-lb (N-mm)
P
axial
= axial load, lb (N)
P
wall
= axial load due to wall weight, lb (N)
R = seismic response modifcation factor
T = tension in reinforcement, lb (N)
o
= system over-strength factor
REFERENCES
1. Biggs, D.T., Hybrid Masonry Structures, Proceedings
of the Tenth North American Masonry Conference,
The Masonry Society, Boulder, CO, June 2007.
2. Biggs, D.T., Masonry Aspects of the World Trade Center
Disaster, The Masonry Society, Boulder, CO., 2004.
3. Building Code Requirements for Masonry Structures
(TMS 402-08/ACI 530-08/ASCE 5-08), The Masonry
Society, Boulder, CO.
4. International Building Code (IBC), International Code
Council, Falls Church, VA 22041-3401
5. RAM Elements Version 10., Masonry Wall, RAM
International, Carlsbad, CA
6. RISA 3D Version 8.0, RISA Technologies,
Foothill Ranch, CA.
7. IMI Technology Brief 02.13.02, Hybrid Masonry
Construction, International Masonry Institute,
Annapolis, MD, 2009
8. Hybrid Concrete Masonry Construction Details,
TEK 3-3B, National Concrete Masonry Association,
Herndon, VA, 2009
9. AISC Seismic Design Manual, AISC 327-05,
American Iron and Steel Institute, 2005.
Keywords: hybrid structures, shear walls, frame
structures, infll, tie-down, reinforced masonry
AIR BARRIER UPDATE - page 2
IMI 2009. ALL RIGHTS RESERVED.
C
This document is intended for the use of industry professionals who are competent to evaluate the significance and limitations of
the information provided herein. This publication should not be used as the sole guide for masonry design and construction, and
IMI disclaims any and all legal responsibility for the consequences of applying the information.
International Masonry Institute 42 East Street Annapolis, MD 21401 1-800-IMI-0988 www.imiweb.org