Auma MWG

Download as pdf or txt
Download as pdf or txt
You are on page 1of 80

Control

Parallel
Profibus DP
Modbus
DeviceNet
Foundation Fieldbus
Multi-turn actuators
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1
Control unit: electronic (MWG)
with actuator controls
AUMATIC AC 01.1 Non-Intrusive
Assembly, operation, commissioning Operation instructions
Read operation instructions first.

Observe safety instructions.

These operation instructions are part of the product.

Preserve operation instructions during product life.

Pass on instructions to any subsequent user or owner of the product.


Purpose of the document:
This document contains information for installation, commissioning, operation and maintenance staff. It is intended
to support device installation and commissioning.
Reference documents:

Manual (Operation and setting) AUMATIC AC 01.1/ACExC 01.1 Modbus

Manual (Device integration Fieldbus) AUMATIC AC 01.1/ACExC 01.1 Modbus


Reference documents can be downloaded from the Internet (www.auma.com) or ordered directly from AUMA
(refer to <Addresses>).
Table of contents Page
5 1. Safety instructions.................................................................................................................
5 1.1. Basic information on safety
5 1.2. Range of application
6 1.3. Applications in Ex zone 22 (option)
6 1.4. Warnings and notes
7 1.5. References and symbols
8 2. Identification...........................................................................................................................
8 2.1. Name plate
9 2.2. Short description
10 3. Transport, storage and packaging........................................................................................
10 3.1. Transport
10 3.2. Storage
10 3.3. Packaging
11 4. Assembly................................................................................................................................
11 4.1. Mounting position
11 4.2. Handwheel fitting
12 4.3. Multi-turn actuator: mount to valve/gearbox
12 4.3.1 Output drive types B, B1 B4 and E
12 4.3.1.1 Multi-turn actuator (with output drive types B1 B4 or E): mount to valve/gearbox
13 4.3.2 Output drive type A
13 4.3.2.1 Stem nut: finish machining
14 4.3.2.2 Multi-turn actuator (with output drive A): mount to valve
15 4.4. Accessories for assembly
15 4.4.1 Stem protection tube for rising valve stem
15 4.5. Mounting positions of local controls
16 4.5.1 Mounting positions: modify
17 5. Electrical connection.............................................................................................................
17 5.1. Basic information
19 5.2. Connection with AUMA plug/socket connector
19 5.2.1 Terminal compartment: open
20 5.2.2 Cable connection
2
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
Table of contents AC 01.1 Non-Intrusive Modbus RTU
21 5.2.3 Terminal compartment: close
21 5.2.4 Bus terminal compartment: open
22 5.2.5 Bus cables: connect
25 5.2.6 Bus terminal compartment: close
25 5.3. Accessories for electrical connection
25 5.3.1 Controls mounted to wall bracket
26 5.3.2 Parking frame
27 5.3.3 Protection cover
27 5.3.4 Double sealed intermediate frame
27 5.3.5 Earth connection, external
28 6. Operation................................................................................................................................
28 6.1. Manual operation
28 6.1.1 Manual operation: engage
28 6.1.2 Manual operation: disengage
29 6.2. Motor operation
29 6.2.1 Local operation
30 6.2.2 Operation from REMOTE
30 6.3. Menu navigation via push buttons (for settings and indications)
31 6.3.1 Short overview: Functions of the push buttons
31 6.3.2 Structural design and navigation
32 6.4. Password entry
32 6.5. Language change in the display
34 7. Indications..............................................................................................................................
34 7.1. Status indications in the display
34 7.1.1 Status indication S0/S6 - operation
35 7.1.2 Status indication S4 - torque
35 7.1.3 Torque indication: edit
35 7.2. Indication lights/LEDs
36 7.3. Mechanical position indicator/running indication
37 8. Signals.....................................................................................................................................
37 8.1. Signals via fieldbus
37 8.2. Feedback signals via output contacts (binary)
37 8.3. Feedback signals (analogue)
38 9. Commissioning (basic settings)...........................................................................................
38 9.1. Heat-up time for low temperature version
38 9.2. Type of seating: check/edit for end positions
42 9.3. Torque switching: check/set
46 9.4. Limit switching: set
48 9.5. Baud rate, parity and bus addres (slave addess): set
51 9.6. Further parameters of the Modbus interface
52 9.7. Test run
52 9.7.1 Direction of rotation: check
53 9.7.2 Limit switching: check
53 9.8. Switch compartment: open
54 9.9. Mechanical position indicator: set
54 9.10. Gear stage of the reduction gearing: test/set
56 9.11. Switch compartment: close
3
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Table of contents
57 10. Corrective action....................................................................................................................
57 10.1. Faults during commissioning
57 10.2. Fault indications and warning indications
57 10.2.1 Status indication S0 - faults and warnings
57 10.2.2 Status indication S1 - faults
58 10.2.3 Status indication S2 - warnings
59 10.2.4 Status indication S3 - causes for not ready remote
60 10.3. Fuses
60 10.3.1 Fuses within the actuator controls
61 10.3.2 Motor protection (thermal monitoring)
62 11. Servicing and maintenance...................................................................................................
62 11.1. Preventive measures for servicing and safe operation
62 11.2. Maintenance
63 11.3. Disposal and recycling
64 12. Technical data.........................................................................................................................
64 12.1. Features and functions of actuator
65 12.2. Features and functions of actuator controls
67 12.3. Modbus interface
69 12.4. Service conditions
70 12.5. Accessories
70 12.6. Further information
71 13. Spare parts.............................................................................................................................
71 13.1. Multi-turn actuators SA 07.1 SA 16.1/SAR 07.1 SAR 16.1
73 13.2. Actuator controls AUMATIC AC 01.1 with AUMA plug/socket connector (SD bus)
75 14. Certificates..............................................................................................................................
75 14.1. Declaration of Incorporation and EC Declaration of Conformity
76 15. Index........................................................................................................................................
78 Addresses...............................................................................................................................
4
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
Table of contents AC 01.1 Non-Intrusive Modbus RTU
1. Safety instructions
1.1 Basic information on safety
Standards/directives AUMA products are designed and manufactured in compliance with recognised
standards and directives. This is certified in a Declaration of Incorporation and an
EC Declaration of Conformity.
The end user or the contractor must ensure that all legal requirements, directives,
guidelines, national regulations and recommendations with respect to assembly,
electrical connection, commissioning and operation are met at the place of installation.
They include among others applicable configuration guidelines for fieldbus
applications.
Safety instructions/war-
nings
All personnel working with this device must be familiar with the safety and warning
instructions in this manual and observe the instructions given. Safety instructions
and warning signs on the device must be observed to avoid personal injury or property
damage.
Qualification of staff Assembly, electrical connection, commissioning, operation, and maintenance must
be carried out exclusively by suitably qualified personnel having been authorised by
the end user or contractor of the plant only.
Prior to working on this product, the staff must have thoroughly read and understood
these instructions and, furthermore, know and observe officially recognised rules
regarding occupational health and safety.
Commissioning Prior to commissioning, it is important to check that all settings meet the requirements
of the application. Incorrect settings might present a danger to the application, e.g.
cause damage to the valve or the installation. The manufacturer will not be held
liable for any consequential damage. Such risk lies entirely with the user.
Operation Prerequisites for safe and smooth operation:

Correct transport, proper storage, mounting and installation, as well as careful


commissioning.

Only operate the device if it is in perfect condition while observing these instruc-
tions.

Immediately report any faults and damage and allow for corrective measures.

Observe recognised rules for occupational health and safety.

Observe the national regulations.

During operation, the housing warms up and surface temperatures > 60 C may
occur. To prevent possible burns, we recommend checking the surface tempe-
rature using an appropriate thermometer and wearing protective gloves, if re-
quired, prior to working on the device.
Protective measures The end user or the contractor are responsible for implementing required protective
measures on site, such as enclosures, barriers, or personal protective equipment
for the staff.
Maintenance To ensure safe device operation, the maintenance instructions included in this manual
must be observed.
Any device modification requires prior consent of the manufacturer.
1.2 Range of application
AUMA multi-turn actuators are designed for the operation of industrial valves, e.g.
globe valves, gate valves, butterfly valves, and ball valves.
Other applications require explicit (written) confirmation by the manufacturer.
The following applications are not permitted, e.g.:

Industrial trucks according to EN ISO 3691

Lifting appliances according to EN 14502


5
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Safety instructions

Passenger lifts according to DIN 15306 and 15309

Service lifts according to EN 81-1/A1

Escalators

Continuous operation

Buried service

Permanent submersion (observe enclosure protection)

Potentially explosive areas, with the exception of zone 22

Radiation exposed areas in nuclear power plants


No liability can be assumed for inappropriate or unintended use.
Observance of these operation instructions is considered as part of the device's
designated use.
Information These operation instructions are only valid for the "clockwise closing" standard
version, i.e. driven shaft turns clockwise to close the valve.
1.3 Applications in Ex zone 22 (option)
Actuators of the indicated series basically meet the requirements for applications in
dust hazardous locations of ZONE 22 in compliance with the ATEX directive 94/9/EC.
The actuators are designed to meet enclosure protection IP 67 or IP 68 and fulfil the
requirements of EN 50281-1-1:1998 section 6 - Electrical apparatus for use in
presence of combustible dust, requirements for category 3 electrical equipment -
protected by enclosures.
To comply with all requirements of EN 50281-1-1:1998, it is imperative that the
following points are observed:

In compliance with the ATEX directive 94/9/EC, the actuators must be equipped
with an additional identification II3D IP6X T150 C.

The maximum surface temperature of the actuators, based on an ambient


temperature of +40 C in accordance with EN 50281-1-1 section 10.4, is +150
C. In accordance with section 10.4, an increased dust deposit on the equipment
was not considered for the determination of the maximum surface temperature.

The correct connection of the thermoswitches or the PTC thermistors as well


as fulfilling the requirements of the duty type and the technical data are prere-
quisites for compliance with the maximum surface temperature of devices.

The connection plug may only be plugged in or pulled out when device is dis-
connected from the mains.

The cable glands used also have to meet the requirements of category II3 D
and must at least comply with enclosure protection IP 67.

The actuators must be connected by means of an external ground connection


(accessory part) to the potential compensation or integrated into an earthed
piping system.

The screw plug (part no. 511.0) or the stem protection tube with protective cap
(part nos. 568.1 and 568.2) for sealing the hollow shaft must imperatively be
mounted to guarantee tightness and therefore the combustible dust hazard
protection.

As a general rule, the requirements of EN 50281-1-1 must be respected in dust


hazardous locations. During commissioning, service, and maintenance, special
care as well as qualified and trained personnel are required for the safe opera-
tion of actuators.
1.4 Warnings and notes
The following warnings draw special attention to safety-relevant procedures in these
operation instructions, each marked by the appropriate signal word (DANGER,
WARNING, CAUTION, NOTICE).
Indicates an imminently hazardous situation with a high level of risk. Failure
to observe this warning could result in death or serious injury.
6
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
Safety instructions AC 01.1 Non-Intrusive Modbus RTU
Indicates a potentially hazardous situation with a medium level of risk. Failure
to observe this warning could result in death or serious injury.
Indicates a potentially hazardous situation with a low level of risk. Failure to
observe this warning may result in minor or moderate injury. May also be used
with property damage.
Potentially hazardous situation. Failure to observe this warning may result in
property damage. Is not used for personal injury.
Arrangement and typographic structure of the warnings
Type of hazard and respective source!
Potential consequence(s) in case of non-observance (option)
Measures to avoid the danger
Further measure(s)
Safety alert symbol warns of a potential personal injury hazard.
The signal word (here: DANGER) indicates the level of hazard.
1.5 References and symbols
The following references and symbols are used in these instructions:
Information The term Information preceding the text indicates important notes and information.
Symbol for CLOSED (valve closed)
Symbol for OPEN (valve open)
Important information before the next step. This symbol indicates what is required
for the next step or what has to be prepared or observed.
Via the menu to parameter
Describes the path within the menu to the parameter. By using the push buttons of
the local controls you may quickly find the desired parameter in the display.
Step by step
Provides a detailed description of each step for setting/viewing the parameter.
Description of the parameter settings/indications
Describes the setting/viewing possibilities of a parameter.
< > Reference to other sections
Terms in brackets shown above refer to other sections of the document which provide
further information on this topic. These terms are either listed in the index, a heading
or in the table of contents and may quickly be found.
7
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Safety instructions
2. Identification
2.1 Name plate
Each device component (actuator, controls, motor) is equipped with a name plate.
Figure 1: Arrangement of name plates
[1] Actuator name plate
[2] Controls name plate
[3] Motor name plate
[4] Additional plate, e.g. KKS plate (Power Plant Classification System)
Data for identification Figure 2: Actuator name plate
[1] Type and size of actuator
[2] Commission number
Figure 3: Controls name plate
[1] Type and size of the controls
[2] Commission number
[3] Wiring diagram
[4] Control
Type and size
These instructions apply to the following devices:
Multi-turn actuators for open-close duty: SA 07.1, 07.5, 10.1, 14.1, 14.5, 16.1
Multi-turn actuators for modulating duty: SAR 07.1, 07.5, 10.1, 14.1, 14.5, 16.1
AC 01.1 = Stellantriebs-Steuerung AUMATIC
8
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
Identification AC 01.1 Non-Intrusive Modbus RTU
Commission number An order-specific commission number is assigned to each device. This commission
number can be used to directly download the wiring diagram, inspection records and
further information regarding the device from the Internet: http://www.auma.com.
Wiring diagram The 7
th
position in the ACP wiring diagram indicates the type of feedback signals
from the actuator:
M = MWG, <Non-Intrusive version>.
P = Potentiometer
R = RWG (electronic position transmitter)
Control
Modbus RTU = Control via Modbus RTU interface.
2.2 Short description
Multi-turn actuator Definition in compliance with EN ISO 5210:
A multi-turn actuator is an actuator which transmits to the valve a torque for at least
one full revolution. It is capable of withstanding thrust.
AUMA multi-turn actuators are driven by an electric motor and are capable of
withstanding thrust in combination with output drive type A. For manual operation,
a handwheel is provided. Switching off in end positions may be either by limit or
torque seating. Controls are required to operate or process the actuator signals.
Actuator controls The AUMATIC actuator controls are used to operate AUMA actuators and are supplied
ready for use. The controls may be mounted directly to the actuator or separately
on a wall bracket.
The functions of the AUMATIC controls include standard valve control in OPEN -
CLOSE duty, positioning, process control, logging of operating data, diagnostic
functions right through control via fieldbus.
Local controls/COM-AC Operation, setting, and display can be performed on site directly at the controls or
alternatively from REMOTE via a fieldbus interface.
On site it is possible to

Operate the actuator via the local controls (push buttons and display) and per-
form settings (contents of these instructions).

Read in or out data or modify and save settings via the COM-AC software (op-
tion), using a computer (laptop or PC). Depending on the version, the connec-
tion between computer and AUMATIC can be made with cable (infra-red inter-
face) or without cable (Bluetooth interface) (not included in these instructions).
Intrusive - Non-Intrusive

Intrusive version (control unit: electromechanical):
Limit and torque setting is performed via switches in the actuator.

Non-Intrusive version (control unit: electronic):


Limit and torque setting is performed via the controls, actuator and controls
housings do not have to be opened. For this purpose, the actuator is equipped
with an MWG (magnetic limit and torque transmitter), also supplying analogue
torque feedback signals/torque indication and analogue position feedback si-
gnals/position indication.
9
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Identification
3. Transport, storage and packaging
3.1 Transport
For transport to place of installation, use sturdy packaging.
Hovering load!
Risk of death or serious injury.
Do NOT stand below hovering load.
Attach ropes or hooks for the purpose of lifting by hoist only to housing and NOT
to handwheel.
Actuators mounted on valves: Attach ropes or hooks for the purpose of lifting
by hoist to valve and NOT to actuator.
Actuators mounted to gearboxes: Attach ropes or hooks for the purpose of lifting
by hoist only to the gearbox using eyebolts and NOT to the actuator.
Actuators mounted to controls: Attach ropes or hooks for the purpose of lifting
by hoist only to the actuator and NOT to the controls.
3.2 Storage
Danger of corrosion due to inappropriate storage!
Store in a well-ventilated, dry room.
Protect against floor dampness by storage on a shelf or on a wooden pallet.
Cover to protect against dust and dirt.
Apply suitable corrosion protection agent to uncoated surfaces.
Damage on display caused by temperatures below permissible level!
The AUMATIC actuator controls must NOT be stored below 30 C.
Long-term storage If the device must be stored for a long period (more than 6 months) the following
points must be observed in addition:
1. Prior to storage:
Protect uncoated surfaces, in particular the output drive parts and mounting
surface, with long-term corrosion protection agent.
2. At an interval of approx. 6 months:
Check for corrosion. If first signs of corrosion show, apply new corrosion protec-
tion.
3.3 Packaging
Our products are protected by special packaging for transport when leaving the
factory. The packaging consists of environmentally friendly materials which can easily
be separated and recycled. We use the following packaging materials: wood,
cardboard, paper, and PE foil. For the disposal of the packaging material, we
recommend recycling and collection centres.
10
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
Transport, storage and packaging AC 01.1 Non-Intrusive Modbus RTU
4. Assembly
4.1 Mounting position
AUMA actuators and actuator controls can be operated without restriction in any
mounting position.
4.2 Handwheel fitting
Information For transport purposes, handwheels from a diameter of 400 mm are supplied sepa-
rately.
Damage at the change-over mechanism due to incorrect assembly!
Only pivot change-over lever manually.
Do NOT use extensions as lever for operation.
First engage manual operation correctly, then mount handwheel.
1. Manually lift the red change-over lever while slightly turning the shaft back and
forth until manual operation engages.
The manual operation is correctly engaged if the change-over lever can be lifted
by approx. 85.
2. Attach handwheel over the red change-over lever then on to the shaft.
3. Release change-over lever (should snap back into initial position by spring ac-
tion, if necessary, push it back manually).
4. Secure handwheel using the circlip supplied.
11
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Assembly
4.3 Multi-turn actuator: mount to valve/gearbox
Danger of corrosion due to damage to paint finish and condensation!
Touch up damage to paint finish after work on the device.
After mounting, connect the device immediately to electrical mains to ensure
that heater minimises condensation.
4.3.1 Output drive types B, B1 B4 and E
Application

For rotating, non-rising valve stem

Not capable of withstanding thrust


Design Output drive bore with keyway:

Types B1 B4 with bore according to ISO 5210

Types B and E with bore according to DIN 3210

Later change from B1 to B3, B4, or E is possible.


Figure 6: Output drives
[1] Output drive types B1/B2 and B
[2] Hollow shaft with keyway
[3] Output drive types B3/B4 and E
[4] Output drive sleeve/plug sleeve with bore and keyway
Information Spigot at flanges should be loose fit.
4.3.1.1 Multi-turn actuator (with output drive types B1 B4 or E): mount to valve/gearbox
1. Check if mounting flanges fit together.
2. Check whether bore and keyway match the input shaft.
3. Apply a small quantity of grease to the input shaft.
4. Place multi-turn actuator.
Information: Ensure that the spigot fits uniformly in the recess and that the
mounting faces are in complete contact.
5. Fasten multi-turn actuator with screws according to table.
Information: We recommend applying liquid thread sealing material to the
screws to avoid contact corrosion.
12
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
Assembly AC 01.1 Non-Intrusive Modbus RTU
6. Fasten screws crosswise to a torque according to table.
Table 1: Tightening torques for screws
Tightening torque T
A
[Nm] Screws
Strength class 8.8 Threads
25 M8
51 M10
87 M12
214 M16
431 M20
4.3.2 Output drive type A
Application

Output drive for rising, non-rotating valve stem

Capable of withstanding thrust


4.3.2.1 Stem nut: finish machining
This working step is only required if stem nut is supplied unbored or with pilot
bore.
Figure 7: Design of output drive type A
[1] Stem nut
[2] Bearing
[2.1] Bearing race
[2.2] Bearing rim
[3] Spigot ring
1. Remove spigot ring [3] from output drive.
2. Remove stem nut [1] together with bearings [2].
3. Remove bearing races [2.1] and bearing rims [2.2] from stem nut [1].
4. Drill and bore stem nut [1] and cut thread.
Information: When fixing in the chuck, make sure stem nut runs true!
5. Clean the machined stem nut [1].
6. Apply sufficient Lithium soap EP multi-purpose grease to bearing rims [2.2] and
bearing races [2.1], ensuring that all hollow spaces are filled with grease.
7. Place greased bearing rims [2.2] and bearing races [2.1] onto stem nut [1].
8. Re-insert stem nut [1] with bearings [2] into output drive.
Information: Ensure that dogs or splines are placed correctly in the keyway of
the hollow shaft.
9. Screw in spigot ring [3] until it is firm against the shoulder.
13
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Assembly
4.3.2.2 Multi-turn actuator (with output drive A): mount to valve
Figure 8: Assembly with output drive type A
[1] Valve stem
[2] Output drive type A
[3] Screws to actuator
[4] Valve flange
[5] Screws to output drive
1. If the output drive type A is already mounted to the multi-turn actuator: Loosen
screws [3] and remove output drive type A [2].
2. Check if the flange of output drive type A matches the valve flange [4].
3. Apply a small quantity of grease to the valve stem [1].
4. Place output drive type A on valve stem and turn until it is flush on the valve
flange.
5. Turn output drive type A until alignment of the fixing holes.
6. Screw in fastening screws [5], however do not completely tighten.
7. Fit multi-turn actuator on the valve stem so that the stem nut dogs engage into
the output drive sleeve.
The flanges are flush with each other if properly engaged.
8. Adjust multi-turn actuator until alignment of the fixing holes.
9. Fasten multi-turn actuator with screws [3].
10. Fasten screws [3] crosswise with a torque according to table.
Table 2: Tightening torques for screws
Tightening torque T
A
[Nm] Screws
Strength class 8.8 Threads
11 M6
25 M8
51 M10
87 M12
214 M16
431 M20
11. Turn multi-turn actuator with handwheel in direction OPEN until valve flange
and output drive A are firmly placed together.
12. Tighten fastening screws [5] between valve and output drive type A crosswise
applying a torque according to table.
14
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
Assembly AC 01.1 Non-Intrusive Modbus RTU
4.4 Accessories for assembly
4.4.1 Stem protection tube for rising valve stem
Option
Figure 9: Assembly of the stem protection tube
[1] Cap for stem protection tube
[2] Stem protection tube
[3] Sealing ring
1. Seal thread with hemp, Teflon tape, or thread sealing material.
2. Screw stem protection tube [2] into thread and tighten it firmly.
3. Push down the sealing ring [3] onto the housing.
4. Check whether cap for stem protection tube [1] is available and in perfect con-
dition.
4.5 Mounting positions of local controls
The mounting position of the local controls is selected according to the order. If, after
mounting the actuator to the valve or the gearbox on site, the local controls are in
an unfavourable position, the mounting position can be changed at a later date. Four
mounting positions are possible.
Figure 10: Mounting positions A and B
15
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Assembly
Figure 11: Mounting positions C and D
4.5.1 Mounting positions: modify
Hazardous voltage!
Risk of electric shock.
Disconnect device from the mains before opening.
1. Loosen screws and remove the local controls.
2. Check whether O-ring is in good condition, correctly insert O-ring.
3. Turn local controls into new position and re-place.
Cable damage due to twisting or pinching!
Risk of functional failures.
Turn local controls by a maximum of 180.
Carefully assemble local controls to avoid pinching the cables.
4. Fasten screws evenly crosswise.
16
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
Assembly AC 01.1 Non-Intrusive Modbus RTU
5. Electrical connection
5.1 Basic information
Danger due to incorrect electrical connection
Failure to observe this warning can result in death, serious injury, or property damage.
The electrical connection must be carried out exclusively by suitably qualified
personnel.
Prior to connection, observe basic information contained in this chapter.
After connection but prior to applying the voltage, observe the <Commissioning>
and <Test run> chapters.
Wiring diagram/terminal
plan
The pertaining wiring diagram/terminal plan is attached to the device in a
weather-proof bag, together with these operation instructions. It can also be obtained
from AUMA (state commission no., refer to name plate) or downloaded directly from
the Internet (www.auma.com).
Protection on site
For short-circuit protection and for disconnecting the actuator from the mains, fuses
and disconnect switches have to be provided by the customer.
The current values for respective sizing is derived from the current consumption of
the motor (refer to electrical data sheet) plus the current consumption of the controls.
Table 3: Current consumption controls
Max. current consumption Mains voltage
650 mA 100 to 120 V AC (10 %)
325 mA 208 to 240 V AC (10 %)
190 mA 380 to 500 V AC (10 %)
500 mA, filter capacitor 2,200 F 24 V DC (+10 %/-15 %) and AC motor
750 mA, filter capacitor 2,200 F 24 V DC (+10 %/10 %) and DC motor
Table 4: Maximum permissible protection
max. protection Rated power Switchgear
16 A (gL/gG) up to 1.5 kW Reversing contactor
32 A (gL/gG) up to 7.5 kW Reversing contactor
63 A (gL/gG) up to 11 kW Reversing contactor
16 A (g/R) It<1,500As up to 1.5 kW Thyristor
32 A (g/R) It<1,500As up to 3 kW Thyristor
63 A (g/R) It<5,000As up to 5.5 kW Thyristor
If controls are mounted separately from actuator (controls on wall bracket): Consider
length and cross section of connecting cable when defining the protection required.
Power supply for the
controls (electronics)
If the controls (electronics) are supplied externally with 24 V DC and DC motors (24
V DC, 48 V DC, 60 V DC, 110 V DC, 220 V DC) are used simultaneously, the 24 V
DC voltage supply for the controls should be ensured via the XK25/26 terminals,
separately from the power supply (U1, V1). In case of common supply using a single
cable (links from U1, V1 with XK25/26, for 24 V DC only !!!), short-term excess or
falling below the permissible voltage limits can be the consequence during switching
(24 V DC +10 %/10 %). Any possibly incoming operation commands are not
executed outside the admissible limit values. The controls briefly signal a fault
condition.
Safety standards All externally connected devices shall comply with the relevant safety standards.
Cable installation in ac-
cordance with EMC
Signal and bus cables are susceptible to interference.
Motor cables are interference sources.
17
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Electrical connection

Lay cables being susceptible to interference or sources of interference at the


highest possible distance from each other.

The interference immunity of signal and bus cables increases if the cables are
laid close to the earth potential.

If possible, avoid laying long cables and make sure that they are installed in
areas being subject to low interference.

Avoid long parallel paths with cables being either susceptible to interference or
interference sources.

For the connection of remote position transmitters, screened cables must be


used.
Type of current, mains
voltage and mains fre-
quency
Type of current, mains voltage and mains frequency must match the data on the
motor name plate.
Figure 12: Motor name plate (example)
[1] Type of current
[2] Mains voltage
[3] Mains frequency (for 3-ph and 1-ph AC motors)
Connecting cables

For device insulation, appropriate (voltage-proof) cables must be used. Specify
cables for the highest occurring rated voltage.

Use connecting cable with appropriate minimum rated temperature.

For connecting cables exposed to UV radiation (outdoor installation), use UV


resistant cables.
Bus cables
Only cables complying with the recommendations of EIA 485 specifications should
be used for Modbus wiring.
Cable recommendation:
Impedance:
135 to 165 Ohm, at a measurement frequency bet-
ween 3 and 20 MHz
Cable capacity:
< 30 pF per metre
Wire diameter
> 0.64 mm
Wire cross section:
0.34 mm, corresponds to AWG 22
Loop resistance:
< 110 Ohm per km
Screening:
CU shielding braid or shielding braid and shielding
foil
Prior to installation, please note:

Connect maximum 32 devices to one segment.

If more devices are to be connected:


- Connect several segments using repeaters.

Respect a distance of minimum 20 cm between the bus cable and other cables.

If possible, bus cables should be laid in a separate, conductive, and earthed


cable tray.

Make sure to avoid potential differences between the individual devices on the
bus (perform an equipotential earth bonding).
18
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
Electrical connection AC 01.1 Non-Intrusive Modbus RTU
5.2 Connection with AUMA plug/socket connector
Cross sections AUMA plug/socket connector:

Power terminals (U1, V1, W1, U2, V2, W2): max. 6 mm flexible/10 mm solid

PE connection : max. 6 mm flexible/10 mm solid

Control contacts (1 to 50): max. 2.5 mm


Information For some special motors, the connection of the power terminals (U1, V1, W1, U2,
V2, W2) is not performed via the AUMA plug/socket connector but via a terminal
board at the motor.
5.2.1 Terminal compartment: open
Information The bus connection can be separately accessed from the mains connection (refer
to <Bus terminal compartment: open>).
Figure 13: Mains connection AUMA plug/socket connector SD bus
[1] Connection housing
[2] Screws for connection housing
[3] O-ring
[4] Screws for socket carrier
[5] Socket carrier
[6] Cable entry for mains
[7] Blanking plug
[8] Cable gland (not included in delivery)
Information Bus operation is not interrupted when removing the connection housing [1].
Hazardous voltage!
Risk of electric shock.
Disconnect device from the mains before opening.
1. Loosen screws [2] and remove connection housing [1].
2. Loosen screws [4] and remove socket carrier [5] from connection housing [1].
19
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Electrical connection
3. Insert cable glands [8] suitable for connecting cables.
The enclosure protection IP... stated on the name plate is only ensured if suitable
cable glands are used. Example: Name plate shows enclosure protection IP
68.
4. Seal unused cable entries [6] with suitable blanking plugs [7].
5. Insert the cables into the cable glands [8].
5.2.2 Cable connection
Observe permissible cross sections.
1. Remove cable sheathing.
2. Strip wires.
3. For flexible cables: Use end sleeves according to DIN 46228.
4. Connect cables according to order-related wiring diagram.
In case of a fault: Hazardous voltage while protective earth conductor is NOT
connected!
Risk of electric shock.
Connect all protective earth conductors.
Connect PE connection to external protective earth conductor of connecting
cables.
Start running the device only after having connected the protective earth con-
ductor.
5. Tighten PE conductors firmly to PE connection using ring lugs (flexible cables)
or loops (rigid cables).
Figure 15: PE connection
[1] Socket carrier
[2] Screw
[3] Washer
[4] Lock washer
[5] Protective earth with ring lugs/loops
[6]
PE connection, symbol:
Danger of corrosion: Damage due to condensation!
After mounting, commission the device immediately to ensure that heater mini-
mises condensation.
20
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
Electrical connection AC 01.1 Non-Intrusive Modbus RTU
Information Some actuators are equipped with an additional motor heater. The motor heater
minimises condensation within the motor and improves the start-up behaviour for
extremely low temperatures.
5.2.3 Terminal compartment: close
Figure 16: AUMA plug/socket connector SD bus
[1] Connection housing
[2] Screws for connection housing
[3] O-ring
[4] Screws for socket carrier
[5] Socket carrier
[6] Cable entry for mains
[7] Blanking plug
[8] Cable gland (not included in delivery)
Short-circuit due to pinching of cables!
Risk of electric shock and functional failures.
Carefully fit socket carrier to avoid pinching the cables.
1. Insert the socket carrier [5] into the cover [1] and fasten with screws [4].
2. Clean sealing faces of connection housing [1] and housing.
3. Check whether O-ring [3] is in good condition, replace if damaged.
4. Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and
insert it correctly.
5. Fit connection housing [1] and fasten screws [2] evenly crosswise.
6. Fasten cable glands [8] applying the specified torque to ensure the required
enclosure protection.
5.2.4 Bus terminal compartment: open
The AUMA plug/socket connector (SD bus) is equipped with a connection board for
connecting the bus cables. When removing the cover [1] the connection board is
easily accessible.
21
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Electrical connection
Figure 17: AUMA plug/socket connector SD bus
[1] Cover (bus terminal compartment)
[2] Screws for cover
[3] O-ring
[4] Cable entries for bus cables
[5] Blanking plug
Hazardous voltage!
Risk of electric shock.
Disconnect device from the mains before opening.
Electrostatic discharge ESD!
Risk of damage to electronic components.
Earth both operators and devices.
1. Loosen screws [2] and remove cover [1].
2. Insert cable glands suitable for bus cables.
The enclosure protection IP stated on the name plate is only ensured if suita-
ble cable glands are used.
Example: Name plate shows enclosure protection IP 68.
3. Seal unused cable entries [4] with suitable blanking plugs [5].
4. Insert the wires into the cable glands.
5.2.5 Bus cables: connect
Versions The bus connection described in this chapter applies to the following versions of the
connection board:

Standard version (1-channel)

Versions with overvoltage protection (up to 4 kV)

Versions for redundancy (2-channel)


Information For loop redundancy, automatic termination is performed as soon as the AUMATIC
is connected to the power supply. When interrupting the power supply, e.g. after re-
moving the AUMA plug/socket connector, both RS-485 loop segments are automa-
tically connected to each other.
22
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
Electrical connection AC 01.1 Non-Intrusive Modbus RTU
Figure 19: Connection board (standard version)
[S1] Bus termination channel 1
[X1] Channel 1, from the previous device
[X2] Channel 1, to the next device
[X3] Shielding clamp
Figure 20: Connection boards (versions with overvoltage protection)
[A] Board for line topology
[B] Board for loop topology (loop redundancy)
[S1] Bus termination channel 1
[S2] Bus termination channel 2
[S3] Redundancy
[X1] Channel 1: from the previous device to the next device
[X2] Channel 2: from the previous device to the next device
[X3] Shielding clamps
23
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Electrical connection
Figure 21: Connection baords (versions for redundancy)
[A] Board for line topology
[B] Board for loop topology (loop redundancy)
[S1] Bus termination channel 1
[S2] Bus termination channel 2
[S3] Redundancy
[X1] Channel 1: from the previous device
[X2] Channel 1: to the next device
[X3] Shielding clamps
[X4] Channel 2: from the previous device
[X5] Channel 2: to the next device
Table 5: Functions for switches S1 S3
Bus termination channel 1 ON ON S1
Bus termination channel 1 OFF OFF
Bus termination channel 2 ON (option) ON S2
Bus termination channel 2 OFF (option) OFF
one fieldbus board 1SPC S3
two fieldbus boards (redundancy, option) 2SPC
Information Switches S1 and S2 are supplied in OFF position.
Connecting bus cables:
1. Connect cables.
Table 6: Assignment of fieldbus cables
Colour SUB-D 9 plug pin (for other
fieldbus devices)
AUMA labelling at the
connection
Fieldbus cables
green 8 N/A A
red 3 P/B B
2. If the actuator is the final device in the bus segment:
2.1 Switching on the termination resistor for channel 1 using switch S1 (ON
position).
2.2 For component redundancy: Switching on the termination resistor for
channel 2 using switch S2 (ON position). Refer to table <Functions for
switches S1 S3>.
Information: As soon as the termination resistors are switched on, the
connection to the next Fieldbus device is automatically interrupted to avoid
multiple terminations (not applicable for overvoltage protection).
3. Connect cable shield largely to shielding clamp [X3].
24
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
Electrical connection AC 01.1 Non-Intrusive Modbus RTU
5.2.6 Bus terminal compartment: close
Figure 22: AUMA plug/socket connector SD bus
[1] Cover
[2] Screws for cover
[3] O-ring
[4] Cable entries for bus cables
[5] Blanking plug
1. Clean sealing faces of cover [1] and housing.
2. Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the sealing faces.
3. Check whether O-ring [3] is in good condition, correctly insert O-ring.
4. Fit cover [1] and fasten screws [2] evenly crosswise.
5. Fasten cable glands with the specified torque to ensure the required enclosure
protection.
5.3 Accessories for electrical connection
Option
5.3.1 Controls mounted to wall bracket
The wall bracket allows separate mounting of controls and actuator.
Application

If the actuator cannot be accessed.

If the actuator is subject to high temperatures.

In case of heavy vibration of the valve.


25
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Electrical connection
Design Figure 23: Design principle with wall bracket
[1] Wall bracket
[2] Connecting cables
[3] Electrical connection of wall bracket (XM)
[4] Electrical connection of actuator (XA)
[5] Electrical connection/bus connection of controls (XK) - customer plug
Observe prior to
connection

Permissible length of connecting cables: max. 100 m.

Permissible length of connecting cables for later separation of actuator and


controls: max. 10 m.

We recommend: AUMA cable set LSW20.

If the AUMA cable set is not used:


- Use suitable flexible and screened connecting cables.
- Use separate, CAN bus cable for MWG of 120 Ohm character impedance
(e.g. UNITRONIC BUS-FD P CAN UL/CSA - 2 x 2 x 0.5 mm, manufacturer:
Lapp).
- Data cable connection: XM2-XA2 = CAN L, XM3-XA3 = CAN H.
- MWG voltage supply if the AUMATIC has been ordered and delivered with
wall bracket: XM6-XA6 = GND, XM7-XA7 = + 24 V DC (refer to wiring
diagram).
- MWG voltage supply if AUMATIC has been subsequently separated from
the actuator: XM6-XA6 = GND, XM11-XA117 = + 5 V DC (refer to wiring
diagram).
- For the electrical connection at wall bracket [3], the terminals are made
as crimp connections.
- Use a suitable four indent crimp tool for crimping.
- Cross sections for flexible wires:
- Control cables: max. 0.75 to 1.5 mm
- Mains connection: max. 2.5 to 4 mm

When using connecting cables, e.g. of the heater, requiring direct wiring from
the actuator to the XK customer plug (XA-XM-XK, refer to wiring diagram),
these connecting cables must be subject to an insulation test in compliance
with EN 50178. Connecting cables for MWG do not belong to this group. They
may not be subject to an insulation test.
5.3.2 Parking frame
Application Parking frame for safe storage of a disconnected plug.
26
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
Electrical connection AC 01.1 Non-Intrusive Modbus RTU
For protection against touching the bare contacts and against environmental
influences.
Figure 24: Parking frame
5.3.3 Protection cover
Protection cover for plug compartment when plug is removed.
The open terminal compartment can be closed using a protective cover (not
illustrated).
5.3.4 Double sealed intermediate frame
When removing the electrical connection or due to leaky cable glands, ingress of
dust and water into the housing may occur. This is prevented effectively by inserting
the double sealed intermediate frame [2] between the plug/socket connector [1] and
the housing of the device. The enclosure protection of the device (IP 68) will not be
affected, even if the electrical connection [1] is removed.
Figure 25: Electrical connection with double sealed intermediate frame
[1] Electrical connection
[2] Double sealed intermediate frame
5.3.5 Earth connection, external
As an option, the housing is equipped with an external earth connection (U-bracket)
to connect the device to the equipotential earth bonding.
Figure 26: Earth connection
27
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Electrical connection
6. Operation
6.1 Manual operation
For purposes of setting and commissioning, in case of motor failure or power failure,
the actuator may be operated manually. Manual operation is engaged by an internal
change-over mechanism.
6.1.1 Manual operation: engage
Information When using brake motors, note that the motor is disengaged during manual operation.
For this reason, the brake motor cannot sustain any load during manual operation.
The load must be sustained via the handwheel.
Damage at the change-over mechanism due to faulty operation!
Engage manual operation only during motor standstill.
Only pivot change-over lever manually.
Do NOT use extensions as lever for operation.
1. Pivot change-over lever manually to approx. 85while slightly turning the
handwheel back and forth until manual operation engages.
2. Release change-over lever (should snap back into initial position by spring ac-
tion, if necessary, push it back manually).
3. Turn handwheel in desired direction.
To close the valve, turn handwheel clockwise:
Drive shaft (valve) turns clockwise in direction CLOSE.
6.1.2 Manual operation: disengage
Manual operation is automatically disengaged when motor is started again. The
handwheel does not rotate during motor operation.
28
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
Operation AC 01.1 Non-Intrusive Modbus RTU
6.2 Motor operation
Perform all commissioning settings and the test run prior to motor operation.
6.2.1 Local operation
The local operation of the actuator is performed using the push buttons of the local
controls.
Figure 30: Local controls
[1] Push button OPEN
[2] Push button STOP
[3] Push button CLOSE
[4] Push button Reset
[5] Selector switch
[6] Indication lights/LEDs
Hot surfaces, e.g. possibly caused by high ambient temperatures or strong
direct sunlight!
Danger of burns
Check surface temperature and wear protective gloves, if required.

Set selector switch [5] to position Local control (LOCAL).


The actuator can now be operated using the push buttons [1 3].
- Run actuator in direction OPEN: Press push button OPEN [1].
- Stop actuator: Press push button STOP [2].
- Run actuator in direction CLOSE: Press push button CLOSE [3].
Information The OPEN - CLOSE operation commands can be given either in push-to-run opera-
tion mode or in self-retaining mode. In self-retaining mode, the actuator runs to the
defined end position after pressing the button, unless another command has been
received beforehand. For further information, please refer to the Manual (Operation
and setting).
29
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Operation
6.2.2 Operation from REMOTE

Set selector switch to Remote control (REMOTE).


Now, the actuator can be remote-controlled via fieldbus.
Information For actuators equipped with a positioner, it is possible to select between open-close
control (Remote OPEN-CLOSE) and setpoint control (Remote SETPOINT). For
further information, please refer to the Manual (Operation and setting).
6.3 Menu navigation via push buttons (for settings and indications)
The push buttons of the local controls are used to view, edit, and show various
indications on the display.
Figure 33: Local controls
[1] Push button
[2] Push button
[3] Push button
[4] Push button C
[5] Selector switch
[6] Display

Set selector switch [5] to position 0 (OFF).


Now, settings and indications can be performed via the push buttons [1 4].
30
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
Operation AC 01.1 Non-Intrusive Modbus RTU
6.3.1 Short overview: Functions of the push buttons
Functions Push but-
tons
Scrolling within a group
(The triangles in the display show which direction of scrolling is possible)
Change values
Enter figures from 0 to 9
Confirm the selection to go to a new menu/subgroup
Cancel process C
Return to previous display: press briefly
Change to another group (S, M, D):
hold down for approx. 3 seconds until group M0 is displayed.
hold down for longer than 3 seconds until group D0 is displayed (thereby,
group M is skipped).
6.3.2 Structural design and navigation
The indications on the display are divided into 3 groups:

Group S = Status indications

Group M = Menu (settings)

Group D = Diagnostic indications


The active group is displayed in the top right corner of the display.
Change from group S to group M:
1. Press push button C and hold it down for approx. 3 seconds until group M0
appears.
Change from group S to group D:
2. Press push button C and hold it down until group D0 is displayed.
(Thereby, group M is skipped.)
Return from group M or group D to group S:
3. Briefly press C .
Scrolling within a group:
4. Press or .
The triangles in the top left corner of the display indicate which direction of
scrolling (within one group) is possible.
31
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Operation
6.4 Password entry
In the menu (group M), the settings are password protected. To change the
parameters, a password must be entered first. The following default password is set
in the factory: 0000.
After selecting EDIT, the following is displayed:
ENTER PASSWORD
0 * * *
:EDIT :OK C:ESC
Step by step:
1. Select figures 0 to 9: Press .
2. Move to the next position: Press .
3. Repeat steps 1 and 2 for all four digits.
4. To cancel a process: Press C.
Information If no input is received over a longer period of time (approx. 10 min.), the controls
automatically return to status indication S0.
6.5 Language change in the display
Via the menu to parameter:
MAIN MENU (M0)
LANGUAGE/CONTRAS (M00)
VIEW (M00)
EDIT (M01)
LANGUAGE (M010)
Default value: ENGLISH
Setting range: ENGLISH, GERMAN, MAGYAR, POLSKI, TUERKCE,
PORTUGUESE, ITALIAN, SPANISH, FRENCH
Step by step:
1. Set selector switch to position 0 (OFF).
2. Press C and hold it down for approx. 3 seconds.
Display indicates:
MAIN MENU M0
LANGUAGE/CONTRAST
SETTINGS
OPERATIONAL DATA
3. Press .
Display indicates:
LANGUAGE/CONTRAS M00
VIEW
EDIT
32
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
Operation AC 01.1 Non-Intrusive Modbus RTU
4. Press .
Display indicates:
LANGUAGE/CONTRAS M01
VIEW
EDIT
5. Press .
Display indicates:
ENTER PASSWORD
0 * * *
:EDIT :OK C:ESC
6. Enter password:
Press 4 x = 0000 (default factory password).
Display indicates:
EDIT M010
LANGUAGE
LCD CONTRAST
7. Press .
Display shows the set value:
EDIT M010
LANGUAGE
ENGLISH
:EDIT C:ESC
8. Press again to enter the edit mode.
Display indicates:
EDIT M010
LANGUAGE
ENGLISH
:EDIT :OK C:ESC
9. Set new value:
Press .
10. Accept value or cancel?
Accept value: Press .
Cancel process without accepting the value: Press C .
33
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Operation
7. Indications
7.1 Status indications in the display
The status indications in the display locally indicate the current operation states as
well as faults and warnings.
This section describes the indications for the operation states. Descriptions of faults
and warnings are described in the <Faults and warnings> chapter.
7.1.1 Status indication S0/S6 - operation
Information For actuators equipped with process controllers, status indication S6 is displayed
instead of status indication S0 in selector switch position REMOTE. The description
below applies to both indications (S0 and S6).
Operation mode display
Line 1 indicates the current operation mode (LOCAL MODE, OFF, REMOTE MODE,
).
LOCAL MODE S0
OPEN
E2 100 %
RUNNING OPEN
Operation command/set-
point display
Line 2 indicates currently incoming operation commands (OPEN, STOP, CLOSE)
or the setpoints E1 or E7 (for actuators equipped with positioner/process controller)
in % of the total travel.
LOCAL MODE S0
OPEN
E2 100 %
RUNNING OPEN
Valve position display
Line 3 indicates the valve position in % of the travel. This indication is only available
if the actuator is equipped with a position transmitter.
LOCAL MODE S0
OPEN
E2 100 %
RUNNING OPEN
0 % = Actuator is in end position CLOSED
100 % = Actuator is in end position OPEN
End position/running in-
dication
Line 4 indicates the current actuator status.
LOCAL MODE S0
OPEN
E2 100 %
RUNNING OPEN
Description of indications in line 4:
RUNNING OPEN
Actuator runs logically OPEN (remains set during operation pauses).
RUNNING CLOSE
Actuator runs logically CLOSE (remains set during operation pauses).
OPEN POSITION
34
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
Indications AC 01.1 Non-Intrusive Modbus RTU
End position OPEN reached.
CLOSED POSITION
End position CLOSED reached.
SETPOINT POSITION
Setpoint (modulating actuators only).
7.1.2 Status indication S4 - torque
A deflection to the left side indicates torque in direction CLOSE.
A deflection to the right side indicates torque in direction OPEN.
TORQUE S4
TORQUE 50 %
Example: SA 07.5 with 20 60 Nm.
100 % corresponds to 60 Nm of nominal torque.
50 % corresponds to 30 Nm of nominal torque.
Information It is possible to change the unit displayed (%, Nm or Lbs/ft.). For further information,
please refer to the Manual (Operation and setting).
7.1.3 Torque indication: edit
The torque value can be displayed in percent, Newtonmeter (Nm) or in Lbs/ft.
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
LOCAL CONTROLS (M13)
TORQUE INDICATION (M1317)
EDIT M1317
TORQUE INDICATION
NEWTONMETER
:EDIT

:OK C:ESC
Description of the parameter settings:
PERCENT
Indication of the nominal torque in percent
NEWTONMETER
Indication in Nm
LBS.FT.
Indication in Lbs/ft.
7.2 Indication lights/LEDs
The indication lights/LEDs locally display the different operation states as optical
signals. The signals can be freely assigned.
35
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Indications
Figure 38: Indication lights/LEDs on local controls
[1] Marking with symbols (standard)
[2] Marking with figures (option)
Table 7: Meaning of signals
Meaning of signal Behaviour (default) Indication light
Actuator is in end position CLOSED illuminated
LED 1 ( )
Running indication: Actuator runs in direction
CLOSE
blinking
Torque fault CLOSE illuminated LED 2 (T)
Motor protection tripped illuminated LED 3 (Th)
Torque fault OPEN illuminated LED 4 (T)
Actuator is in end position OPEN illuminated
LED 5 ( )
Running indication: Actuator runs in direction
OPEN
blinking
Bluetooth connection available illuminated LED 6 (BT) (option)
Information The behaviour (blinking/illuminated) can be changed via the BLINKER (M1311)
parameter.
7.3 Mechanical position indicator/running indication
Option
Mechanical position indicator:

Continuously indicates the valve position


(For complete travel from OPEN to CLOSED or vice versa, the indicator disc
[2] rotates by approximately 180to 230.)

Indicates whether the actuator is running (running indication)

Indicates that the end positions are reached (via indicator mark [3])
Figure 39: Mechanical position indicator
[1] Cover
[2] Indicator disc
[3] Mark
[4] Symbol for position OPEN
[5] Symbol for position CLOSED
36
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
Indications AC 01.1 Non-Intrusive Modbus RTU
8. Signals
8.1 Signals via fieldbus
The feedback signals via Modbus RTU can be read using the appropriate Modbus
function codes.
For further information, please refer to the Manual (Device integration fieldbus).
8.2 Feedback signals via output contacts (binary)
(Option)
Feedback signals via output contacts are only available if a parallel interface is
provided in addition to the fieldbus interface.
The output contacts can be used to indicate operation modes of the actuator or the
controls as binary signals. The signals can be freely assigned. Example:
Output contact open = no thermal fault
Output contact closed = thermal fault in actuator
The output contacts are denominated in the wiring diagram as follows:

Output contacts 1 to 5: DOUT1 to DOUT5

Alarm contacts: NC fault/NO ready


Signal assignment is made via the parameters: OUTPUT CONTACT 1 to OUTPUT
CONTACT 5 and ALARM CONTACT.
Alarm contact default value:
FAULT GROUP 3 = fault signal (includes: torque fault, thermal fault, phase failure
and internal faults)
Default values OUTPUT CONTACT 1 to OUTPUT CONTACT 5:
OUTPUT CONTACT 1 = CLOSED POSITION
OUTPUT CONTACT 2 = OPEN POSITION
OUTPUT CONTACT 3 = REMOTE SW. POSITION
OUTPUT CONTACT 4 = TORQUE FAULT (CLOSE)
OUTPUT CONTACT 5 = TORQUE FAULT (OPEN)
8.3 Feedback signals (analogue)
(Option)
Analogue feedback signals are only available if a parallel interface is provided in
addition to the fieldbus interface.
Valve position Signal: E2 = 0/4 20 mA (galvanically isolated)
Designation in the wiring diagram:
ANOUT1 (position)
Torque feedback Signal: E6 = 0/4 20 mA (galvanically isolated)
Designation in the wiring diagram:
ANOUT2 (torque)
For further information to this topic, please refer to the Manual (Operation and setting).
37
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Signals
9. Commissioning (basic settings)
1. Set selector switch to position 0 (OFF).
Information: The selector switch is not a mains switch. When positioned to 0
(OFF), the actuator cannot be operated. The controls' power supply is
maintained.
2. Switch on the power supply.
Information: Please consider the heat-up time for ambient temperatures below
20 C.
3. Perform basic settings.
9.1 Heat-up time for low temperature version
Please note that for low temperature versions, the controls require a heat-up time.
This heat-up time is applicable in case the actuator and the controls are not live and
have cooled down to ambient temperature. Under these conditions and after
connection to the voltage supply, the following heat-up times must be complied with
prior to commissioning:
For 40 C = 30 min.
For 50 C = 60 min.
For 60 C = 100 min.
Figure 41: Sketch illustrating the heat-up time
[t] Heat-up time in minutes
[] Ambient temperature in C
9.2 Type of seating: check/edit for end positions
Valve damage due to incorrect setting!
The torque must suit the valve.
Only change the setting with the consent of the valve manufacturer.
Limit seating The limit switching is set in such a way that the actuator switches off at the desired
switching points. The torque switching acts as overload protection for the valve.
Torque seating The torque switching is set to the desired tripping torque. After reaching the tripping
torque the actuator is turned off.
38
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
Commissioning (basic settings) AC 01.1 Non-Intrusive Modbus RTU
The limit seating is used to signal that the limit switching will trip shortly before
reaching the set tripping torque. If this is not the case, one of the following fault
signals is displayed: TSO FAULTS or TSC FAULTS (menu S1).
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
SEATING MODE (M11)
VIEW (M110)
EDIT (M111)
OPEN POSITION (M11_0)
CLOSED POSITION (M11_1)
Default value: LIMIT
Step by step:
1. Set selector switch to position 0 (OFF).
2. Press C and hold it down for approx. 3 seconds.
Display indicates:
MAIN MENU M0
LANGUAGE/CONTRAST
SETTINGS
OPERATIONAL DATA
3. Press .
Display indicates:
MAIN MENU M1
LANGUAGE/CONTRAST
SETTINGS
OPERATIONAL DATA
4. Press .
Display indicates:
SETTINGS M10
SET LIMIT SWITCHES
SEATING MODE
TORQUE
5. Press .
Display indicates:
SETTINGS M11
SET LIMIT SWITCHES
SEATING MODE
TORQUE
39
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Commissioning (basic settings)
6. Press .
Display indicates:
SEATING MODE M110
VIEW
EDIT
Use and to select between VIEW and EDIT.
7. View or edit?
Display seating mode: continue with 8.
Change seating mode: continue with 11.
Display type of seating: 8. Press .
Display indicates:
VIEW M1100
OPEN POSITION
CLOSED POSITION
VIEW M1101
OPEN POSITION
CLOSED POSITION
Use and to select between OPEN POSITION and CLOSED POSITION.
9. Press .
Display indicates:
VIEW
OPEN POSITION
LIMIT
C:ESC
VIEW
CLOSED POSITION
LIMIT
C:ESC
Use and to also select here between OPEN POSITION and CLOSED
POSITION.
10. Return to the VIEW/EDIT menu:
Press C twice.
Change seating mode: 11. Press .
Display indicates:
SEATING MODE M111
VIEW
EDIT
40
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
Commissioning (basic settings) AC 01.1 Non-Intrusive Modbus RTU
12. Press .
Display indicates:
ENTER PASSWORD
0 * * *
:EDIT :OK C:ESC
13. Enter password:
Press 4 x = 0000 (default factory password).

EDIT M1110
OPEN POSITION
CLOSED POSITION
EDIT M1111
OPEN POSITION
CLOSED POSITION
Use and to select between OPEN POSITION and CLOSED POSITION.
14. Press .
Display shows the set value:
EDIT M1110
OPEN POSITION
LIMIT

:EDIT C:ESC
EDIT M1111
CLOSED POSITION
LIMIT
:EDIT C:ESC
Use and to select between OPEN POSITION and CLOSED POSITION.
15. Press again to enter the edit mode.
Display indicates:
EDIT M1110
OPEN POSITION
LIMIT
:EDIT :OK C:ESC
EDIT M1111
CLOSED POSITION
LIMIT
:EDIT :OK C:ESC
16. Set new value:
Press .
41
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Commissioning (basic settings)
17. Accept value or cancel?
Accept value: Press .
Cancel process without accepting the value: Press C .
Display indicates:
EDIT M1110
OPEN POSITION
LIMIT
:EDIT C:ESC
AENDERN M1111
CLOSED POSITION
LIMIT
:EDIT C:ESC
Use and to select between OPEN POSITION and CLOSED POSITION.
18. Return to status display:
Press C several times until S0 is displayed.
9.3 Torque switching: check/set
Once the set torque is reached, the torque switches will be tripped (overload protection
of the valve). .
Information The torque switches may also trip during manual operation.
Valve damage due to excessive tripping torque limit setting!
The tripping torque must suit the valve.
Only change the setting with the consent of the valve manufacturer.
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
TORQUE (M12)
VIEW (M120)
EDIT (M121)
OPENING (M12_0)
CLOSING (M12_1)
Default value: according to order data
Setting range: according to torque setting range, refer to actuator name plate
Step by step:
1. Set selector switch to position 0 (OFF).
2. Press C and hold it down for approx. 3 seconds.
Display indicates:
MAIN MENU M0
LANGUAGE/CONTRAST
SETTINGS
OPERATIONAL DATA
42
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
Commissioning (basic settings) AC 01.1 Non-Intrusive Modbus RTU
3. Press .
Display indicates:
MAIN MENU M1
LANGUAGE/CONTRAST
SETTINGS
OPERATIONAL DATA
4. Press .
Display indicates:
SETTINGS M10
SET LIMIT SWITCHES
SEATING MODE
TORQUE
5. Press twice.
Display indicates:
SETTINGS M12
SET LIMIT SWITCHES
SEATING MODE
TORQUE
6. Press .
Display indicates:
TORQUE M120
VIEW
EDIT
Use and to select between VIEW and EDIT.
7. View or edit?
Display torque setting: continue with 8.
Edit torque setting: continue with 11.
Display torque setting: 8. Press .
Display indicates:
VIEW M1200
OPENING
CLOSING
BY-PASS DURATION
VIEW M1201
OPENING
CLOSING
BY-PASS DURATION
Use and to select between OPENING and CLOSING.
43
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Commissioning (basic settings)
9. Press .
Display indicates:
VIEW
OPENING
65%
C:ESC
VIEW
CLOSING
65%
C:ESC
Use and to also select here between OPENING and CLOSING.
10. Return to the VIEW/EDIT menu:
Press C twice.
Edit torque setting: 11. Press .
Display indicates:
TORQUE M121
VIEW
EDIT
12. Press .
Display indicates:
ENTER PASSWORD
0 * * *
:EDIT :OK C:ESC
13. Enter password:
Press 4 x = 0000 (default factory password).

EDIT M1210
OPENING
CLOSING
BY-PASS DURATION
EDIT M2111
OPENING
CLOSING
BY-PASS DURATION
Use and to select between OPENING and CLOSING.
44
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
Commissioning (basic settings) AC 01.1 Non-Intrusive Modbus RTU
14. Press .
Display shows the set value:
EDIT M1210
OPENING
100%
:EDIT C:ESC
EDIT M1211
CLOSING
100%
:EDIT C:ESC
Use and to select between OPENING and CLOSING.
Information: The value can be displayed in percent, Newtonmeter (Nm), or in
Lbs/ft. To display in percent: 100 % equals the max. torque indicated on the
name plate of the actuator. Example: SA 07.5 with 20 60 Nm: 100 % = 60
Nm (33 % = 20 Nm).
15. Press again to enter the edit mode.
Display indicates:
EDIT M1210
OPENING
100%
:EDIT :OK C:ESC
EDIT M1211
CLOSING
100%
:EDIT :OK C:ESC
16. Set new value:
Press .
17. Accept value or cancel?
Accept value: Press .
Cancel process without accepting the value: Press C .
Display indicates:
EDIT M1210
OPENING
100%
:EDIT C:ESC
EDIT M1211
CLOSING
100%
:EDIT C:ESC
Use and to select between OPENING and CLOSING.
18. Return to status display:
Press C several times until S0 is displayed.
45
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Commissioning (basic settings)
Information The following fault signals are sent if the torque setting performed has been reached
in mid-travel:

Status indication S0: Operation mode OFF/LOCAL = FAULT IND.

Status indication S0/S6: Operation mode REMOTE = FAULT IND.

Status indication S1: TORQUE FAULT (OPEN) or TORQUE FAULT


(CLOSE) (torque fault)
The fault has to be acknowledged before the operation can be resumed. The
acknowledgement is made:

either by an operation command in the opposite direction.


- For TORQUE FAULT (CLOSE): Operation command in direction OPEN
- For TORQUE FAULT (OPEN): Operation command in direction CLOSE

or, in case the torque applied is lower than the preset tripping torque:
- via the Reset push button in selector switch position LOCAL.
- or with the reset command via fieldbus.
9.4 Limit switching: set
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
SET LIMIT SWITCHES (M10)
CLOSED POSITION (M100)
OPEN POSITION (M101)
Step by step:
1. Set selector switch to position 0 (OFF).
2. Press C and hold it down for approx. 3 seconds.
Display indicates:
MAIN MENU M0
LANGUAGE/CONTRAST
SETTINGS
OPERATIONAL DATA
3. Press .
Display indicates:
MAIN MENU M1
LANGUAGE/CONTRAST
SETTINGS
OPERATIONAL DATA
4. Press .
Display indicates:
SETTINGS M10
SET LIMIT SWITCHES
SEATING MODE
TORQUE
46
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
Commissioning (basic settings) AC 01.1 Non-Intrusive Modbus RTU
5. Press .
Display indicates:
ENTER PASSWORD
0 * * *
:EDIT :OK C:ESC
6. Enter password:
Press 4 x = 0000 (default factory password).
The current actuator position is displayed:
SET LIMIT SWITC M100
CLOSED POSITION
63.3 %
:EDIT C:ESC
SET LIMIT SWITC M101
OPEN POSITION
63.3 %
:EDIT C:ESC
Use and to select between OPEN POSITION and CLOSED POSITION.
7. Set end position CLOSED or end position OPEN?
Set end position CLOSED: continue with 8.
Set end position OPEN: continue with 13.
Set end position CLO-
SED
8. Press to enter the edit mode.
Display indicates:
SET LIMIT SWITC M100
CLOSED POSITION
:ACCEPT C:ESC
9. Engage manual operation.
10. Turn handwheel until valve is closed.
11. Turn handwheel by approximately half a turn (overrun) in the opposite direction.
12. Press to accept new end position setting.
LEDs and display indicate that the new end position has been accepted:
- The left LED is illuminated (default setting).
- Display indicates: 0.0 %

SET LIMIT SWITC M100


CLOSED POSITION
0.0 %
:EDIT C:ESC
Use to select OPEN POSITION.
47
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Commissioning (basic settings)
Setting end position
OPEN:
13. Press to enter the edit mode.
Display indicates:
SET LIMIT SWITC M101
OPEN POSITION
:ACCEPT C:ESC
14. Engage manual operation.
15. Turn handwheel until valve is open.
16. Turn handwheel by approximately half a turn (overrun) in the opposite direction.
17. Press to accept new end position setting.
LEDs and display indicate that the new end position has been accepted:
- The right LED is illuminated (default setting).
- Display indicates: 100.0 %.

SET LIMIT SWITC M101


OPEN POSITION
100.0 %
:EDIT C:ESC
Use to select CLOSED POSITION.
18. Return to status display:
Press C several times until S0 is displayed.
Information: If an end position cannot be set: Check the type of control unit in
actuator.
Information The end positions can be approached (via push buttons and selector switch in posi-
tion LOCAL) even during motor operation. Position the selector switch to 0 (OFF)
for setting. Direct approaching of the mechanical end stops during motor operation
may cause valve damage. Consequently, during motor operation, the travel to the
mechanical end stop of valve/gearbox must be interrupted prior to reaching the
preset position (press push button STOP).
9.5 Baud rate, parity and bus addres (slave addess): set
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
MODBUS 1 (M1F)
BAUDRATE (M1F11)
PARITY (M1F12)
SLAVEADDRESS (M1F14)
Setting ranges and default values:
BAUDRATE: 300 38 400 BAUD (4 800 BAUD)
PARITAET: (EVEN, 1 STOPBIT)
ODD, 1 STOPBIT
NO, 2 STOPBITS
SLAVEADRESSE: 1 247 (247)
48
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
Commissioning (basic settings) AC 01.1 Non-Intrusive Modbus RTU
Step by step:
1. Set selector switch to position 0 (OFF).
2. Press C and hold it down for approx. 3 seconds.
Display indicates:
MAIN MENU M0
LANGUAGE/CONTRAST
SETTINGS
OPERATIONAL DATA
3. Press .
Display indicates:
MAIN MENU M1
LANGUAGE/CONTRAST
SETTINGS
OPERATIONAL DATA
4. Press .
Display indicates:
SETTINGS M10
SET LIMIT SWITCHES
SEATING MODE
TORQUE
5. Select MODBUS 1 (M1F): Press several times.
Display indicates:
SETTINGS M1B
MONITOR TRIGGERS
POSITIONER ENABLED
MODBUS 1
6. Press .
Display indicates:
MODBUS 1 M1F0
VIEW
EDIT
7. View or edit?
Check settings (view): continue with 8.
Change settings: continue with 11.
49
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Commissioning (basic settings)
Check settings (view): 8. Press .
Display indicates:
MODBUS 1 M1F01
BAUDRATE
PARITY
CONNECT-CONTROL TIME
9. Use to select BAUDRATE, PARITY or SLAVEADDRESS and confirm se-
lection with .
Display shows the selected value. Example SLAVEADDRESS:
VIEW
SLAVEADDRESS
1
C:ESC
10. Return to the VIEW/EDIT menu:
Press C twice.
Change settings: 11. Press .
Display indicates:
MODBUS 1 M1F1
VIEW
EDIT
12. Press .
Display indicates:
ENTER PASSWORD
0 * * *
:EDIT :OK C:ESC
13. Enter password:
Press 4 x = 0000 (default factory password).
Display indicates:
EDIT M1F11
BAUDRATE
PARITY
CONNECT-CONTROL TIME
50
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
Commissioning (basic settings) AC 01.1 Non-Intrusive Modbus RTU
14. Use to select BAUDRATE, PARITY or SLAVEADDRESS and confirm se-
lection with .
Display shows the selected value. Example SLAVEADDRESS:
EDIT M1F14
SLAVEADDRESS
1
:EDIT C:ESC
15. Press again to enter the edit mode.
Display indicates:
EDIT M1F14
SLAVEADDRESS
1
:EDIT :OK C:ESC
16. Set new value:
Press .
17. Accept value or cancel?
Accept value: Press .
Cancel process without accepting the value: Press C .
Display indicates: Example SLAVEADDRESS:
EDIT M1F14
SLAVEADDRESS
1
:EDIT C:ESC
18. Return to status display:
Press C several times until S0 is displayed.
Information: For component redundancy (option), the bus address for the 2nd
fieldbus interface can be set in the same way as the 1st field interface. The
menu for the second fieldbus interface has to be selected from the descriptions
Via the menu to parameter, e.g. MODBUS 2 instead MODBUS 1.
9.6 Further parameters of the Modbus interface
Connection monitoring
time
Parameter: CONNECT-CONTROL TIME (M1F_3)
Default value: 3.0
This time should exceed the cycle time of the Modbus data transmission to all
connected devices. If no valid Modbus telegram was received within this time, the
DATA EX status is left and the failure behaviour or the change-over of the
communication channel is initiated, if applicable.
Parameters for cable
redundancy
Parameters:
CABLE REDUNDANCY (M1F_5)
CHANNEL CHECK TIME (M1F_6)
Default values:
CABLE REDUNDANCY = OFF
CHANNEL CHECK TIME = 5.0 S
These parameters define the behaviour for cable redundancy. For further information
to this topic, please refer to the Manual (Operation and setting).
51
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Commissioning (basic settings)
9.7 Test run
Perform test run only once all settings previously described have been performed.
9.7.1 Direction of rotation: check
Valve damage due to incorrect direction of rotation!
If the direction of rotation is wrong, switch off immediately (press STOP).
Eliminate cause, i.e. correct phase sequence for cable set wall bracket.
Repeat test run.
1. Move actuator manually to intermediate position or to sufficient distance from
end position.
2. Set selector switch to position Local control (LOCAL).
3. Switch on actuator in running direction CLOSE and observe the direction of
rotation:
with indicator disc: step 4
without indicator disc: step 5 (hollow shaft)
Switch off before reaching the end position.
4. With indicator disc:
Observe direction of rotation.
The direction of rotation is correct, if actuator runs in direction
CLOSE and indicator disc turns counterclockwise.
52
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
Commissioning (basic settings) AC 01.1 Non-Intrusive Modbus RTU
5. Without the indicator disc:
Unscrew screw plug [1] and seal [2] or cap for stem protection tube [4]
and observe direction of rotation at hollow shaft [3] or the stem [5].
The direction of rotation is correct, if actuator runs in direction CLOSE and
hollow shaft or stem turn clockwise.
Figure 50: Hollow shaft/stem
[1] Screw plug
[2] Seal
[3] Hollow shaft
[4] Cap for stem protection tube
[5] Stem
[6] Stem protection tube
9.7.2 Limit switching: check
1. Set selector switch to position Local control (LOCAL).
2. Operate actuator using push buttons OPEN - STOP - CLOSE.
The limit switching is set correctly if (default indication):
- The yellow indication light/LED1 is illuminated in end position CLOSED
- The green indication light/LED5 is illuminated in end position OPEN
- The indication lights go out after travelling into opposite direction.
The limit switching is set incorrectly, if:
- The actuator comes to a standstill before reaching the end position
- One of the red indication lights/LEDs is illuminated (torque fault), or the following
fault signals are displayed:
- Status indication S0: FAULT IND.
- Status indication S1: TORQUE FAULT (OPEN) or TORQUE FAULT
(CLOSE)
3. If the end position setting is incorrect: Reset limit switching.
9.8 Switch compartment: open
The switch compartment must be opened to perform the following settings (options).
53
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Commissioning (basic settings)

Loosen screws [2] and remove cover [1] from the switch compartment.
9.9 Mechanical position indicator: set
Option
1. Move valve to end position CLOSED.
2.
Turn lower indicator disc until symbol (CLOSED) is in alignment with the
mark on the cover.
3. Move actuator to end position OPEN.
4.
Hold lower indicator disc in position and turn upper disc with symbol (OPEN)
until it is in alignment with the mark on the cover.
5. Move valve to end position CLOSED again.
6. Check settings:
If the symbol (CLOSED) is no longer in alignment with mark on the cover:
6.1 Repeat setting procedure.
6.2 Gear stage of the reduction gearing: test/set
9.10 Gear stage of the reduction gearing: test/set
This test/setting is only required if the turns/stroke of the actuator have been modified
after the initial setting.
The control unit may possibly have to be exchanged:
Control unit MS5.2: 1 to 500 turns per stroke
Control unit MS50.2: 10 to 5,000 turns per stroke
54
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
Commissioning (basic settings) AC 01.1 Non-Intrusive Modbus RTU
1. Pull off indicator disc. Open end spanner may be used as lever.
2. Refer to table and check if turns/stroke of the actuator correspond to the setting
of the primary reduction gearing (stages 1 9).
If the setting is not correct: continue with 3.
If the setting is correct: continue with 6.
Control unit MS5.2 (1 to 500 turns per stroke)
Gear stage Turns/stroke above to
1 1.0 1.9
2 1.9 3.9
3 3.9 7.8
4 7.8 15.6
5 15.6 31.5
6 31.5 62.5
7 62.5 125
8 125 250
9 250 500
Control unit MS50.2 (10 to 5,000 turns per stroke)
Gear stage Turns/stroke above to
1 10.0 19.5
2 19.5 39.0
3 39.0 78.0
4 78 156
5 156 315
6 315 625
7 625 1,250
8 1,250 2,500
9 2,500 5,000
3. Loosen screw [1].
4. Set crown wheel [2] to desired level according to table.
5. Fasten screw [1].
6. Place indicator disc on shaft.
7. Set mechanical position indicator.
55
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Commissioning (basic settings)
Figure 56: Control unit with reduction gearing
[1] Screw
[2] Crown wheel
9.11 Switch compartment: close
Danger of corrosion due to damage to paint finish!
Touch up damage to paint finish after work on the device.
1. Clean sealing faces of housing and cover.
2. Check whether O-ring [3] is in good condition, replace if damaged.
3. Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and
insert it correctly.
4. Place cover [1] on switch compartment.
5. Fasten screws [2] evenly crosswise.
56
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
Commissioning (basic settings) AC 01.1 Non-Intrusive Modbus RTU
10. Corrective action
10.1 Faults during commissioning
Table 8: Faults during commissioning
Remedy Possible causes Fault description
Set gear stage of the reduction gearing.
The control unit might have to be exchanged.
Reduction gearing is not suitable for
turns/stroke of the actuator.
Mechanical position indicator
cannot be set.
Determine overrun: Overrun = travel covered
from switching off until complete standstill.
Set limit switching again considering the
overrun (turn handwheel back by the amount
of the overrun).
The overrun was not considered when setting
the limit switching.
The overrun is generated by the inertia of
both the actuator and the valve and the delay
time of the controls.
Fault in end position
Actuator runs to end stop alt-
hough the limit switches work
properly.
For RESTRICTED: A release must be initia-
ted externally via bus or input signal. Refer
to parameter Enable LOCAL MODE.
For EMERGENCY STOP: Release EMER-
GENCY STOP button.
RESTRICTED signifies that the local con-
trols of the AUMATIC have not been released
yet.
EMERGENCY STOP signifies that the
EMERGENCY STOP mode has been activa-
ted via the EMERGENCY STOP button (opti-
on),
Push buttons do not react
The controls may not be operated
via the local controls.
Display indicates: RESTRIC-
TED or EMERGENCY STOP.
10.2 Fault indications and warning indications
Faults interrupt or prevent the electrical actuator operation.
Warnings have no influence on the electrical actuator operation. They only serve
for information purposes.
Fault and warning indications are shown in the display.
10.2.1 Status indication S0 - faults and warnings
Line 4 of status indication S0 displays faults and warnings.
LOCAL MODE S0
OPEN
E2 100 %
FAULT IND.
Table 9: Description of the fault indications
Remedy Description Signal
For further information, press and go to
status indication S1.
A fault has occurred, FAULT IND.
For further information, press and go to
status indication S2.
A warning has occurred, WARNING IND.
For further information, press and go to
status indication S1 (faults) or S2 (warnings).
Faults as well as warnings have occurred. FAULT + WARNING
For further information, press and go to
status indication S3 (cause for fault indicati-
ons).
The actuator cannot be operated from REMO-
TE. The actuator can only be operated via
the local controls.
NOT READY IND.
For further information, press and go to
status indication S1 or S3.
Faults and the NOT READY IND. signal
have occurred.
FLT + NR
For further information, press and go to
status indication S2 or S3.
Warnings and the NOT READY IND. si-
gnal have occurred.
WRN + NR
For further information, press and go to
status indications S1 to S3.
Faults, warnings, and the NOT READY
IND. signal have occurred.
FLT + WRN + NR
10.2.2 Status indication S1 - faults
Faults are indicated within the status indication S1:
57
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Corrective action
FAULT IND. S1
NO FAULT
Table 10: Description of the fault indications
Remedy Description Signal
No fault has occurred. NO FAULT
For further information:
1. Go to group D0: Press C and hold it
down until diagnostic indication D0 is
displayed.
2. Go to diagnostic indication D2: Press
twice.
Internal fault has occurred. INTERNAL FAULT
Operation command in direction OPEN. Torque fault in direction CLOSE. TORQUE FAULT (CLOSE)
Set selector switch to position Local control
(LOCAL) and reset fault indication via Reset
push button.
Or:
Perform reset command via fieldbus.
Operation command in direction CLOSE. Torque fault in direction OPEN. TORQUE FAULT (OPEN)
Set selector switch to position Local control
(LOCAL) and reset fault indication via Reset
push button.
Or:
Perform reset command via fieldbus.
Test/connect phases. One phase is missing. LOSS OF PHASE
Cool down, wait. Motor protection tripped. THERMAL FAULT
If the fault indication display persists after
cooling down:
Set selector switch to position Local control
(LOCAL) or reset fault indication via Reset
push button.
Or:
Perform reset command via fieldbus.
Check fuse F4.
For further information:
1. Go to group D0: Press C and hold it
down until diagnostic indication D0 is
displayed.
2. Go to diagnostic indication D4: Press
4 x.
The controls configuration is incorrect. CONFIGURATION FAULT
10.2.3 Status indication S2 - warnings
Faults are indicated within the status indication S2:
WARNING IND. S2
NO WARNINGS
58
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
Corrective action AC 01.1 Non-Intrusive Modbus RTU
Table 11: Description of the warnings
Remedy Description Signal
No warnings have occurred. NO WARNINGS
Set the operating time (MONITOR TRIG-
GERS parameter) in accordance with the
actual operating time.
Preset running time for a travel between end
position OPEN and end position CLOSED
has been exceeded.
WARNING OPER. TIME
Check tripping behaviour of end position
switches.
Verify actuator mechanics.
Check modulating behaviour. Preset values for max. starts/h or max. run-
ning time/h have been exceeded.
WARNING STARTS/RUN
Increase dead time.
Reduce number of setpoint changes.
Operate actuator into both end positions
(OPEN and CLOSED).
Position transmitter (potentiometer or RWG)
is not standardised.
INTERNAL FEEDBACK
For further information:
1. Go to group D0: Press C and hold it
down until diagnostic indication D0 is
displayed.
2. Go to diagnostic indication D3: Press
3 times.
Internal warnings have occurred. INTERNAL WARNING
Check position transmitter signal.
1. Go to group D0: Press C and hold it
down until diagnostic indication D0 is
displayed.
2. Go to diagnostic indication D7, D8 or
D9: Press either 7, 8 or 9 times.
Signal loss of position transmitter FEEDBACK E2 LOSS
Check position transmitter wiring.
Check POSITION E2 parameter. The
setting must correspond to the wiring dia-
gram.
Check wiring. Signal loss of setpoint SETPOINT E1 LOSS
Check wiring. Signal loss of torque source TORQUE E6 LOSS
Check wiring. Signal loss of the analogue input 1 of the
parallel interface (only for Fieldbus/standard
interface combinations)
I/O ANLOG IN1 LOSS
Check wiring. Signal loss of the analogue input 2 of the
parallel interface (only for Fieldbus/standard
interface combinations)
I/O ANLOG IN2 LOSS
Check wiring. Signal loss of actual process value E4 (only
if PID controller is available and active)
P-FEEDBACK E4 LOSS
Check wiring. Signal loss of FO cable (for bus with FO loop
topology only)
FIBER OPTIC LOSS
Check wiring. Signal loss of analogue input 1 ANALOG IN1 BUS1 LOSS
Check wiring. Signal loss of analogue input 2 ANALOG IN2 BUS1 LOSS
10.2.4 Status indication S3 - causes for not ready remote
The causes for the NOT READY IND. fault signals (from status indication S0) are
displayed within status indication S3.
NOT READY IND. S3
READY
59
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Corrective action
Table 12: Description of the fault indications
Description Signal
Actuator can be operated from REMOTE. READY
Actuator cannot be operated from REMOTE as the selector switch is in position LOCAL
or OFF (0).
NOT REMOTE
The EMERGENCY operation mode is active. EMERGENCY MODE
For combination fieldbus/standard interface function:
Operation via parallel interface.
EXTERNAL CONTROLS
The EMERGENCY STOP button has been operated. EMCY STOP ACTIVE
Actuator locked (only set for special applications e.g. for by-pass function). ACTUATOR LOCKED
10.3 Fuses
10.3.1 Fuses within the actuator controls
Fuses F1 and F2 can be accessed after removing the cover [1] on the rear side.
Fuses F3, F4, and F5 are located on the power supply unit and can be accessed
after removing the electrical connection [2].
Hazardous voltage!
Risk of electric shock.
Disconnect device from the mains before opening.
Figure 58: Access to fuses
[1] Rear cover
[2] Electrical connection
F1/F2 Primary fuses on power supply unit
AUMA Art. No.: F1/F2 G fuses
6.3 x 32 mm Size
K002.277 1 A T; 500 V Reversing contactors
Power supply 500 V
K002.665 2 A FF; 660 V Reversing contactors
Power supply > 500 V
K001.185 16 A FF; 500 V Thyristor units for motor power up to 1.5 kW
K006.965 30 A FF; 500 V Thyristor units for motor power up to 3.0 kW
K002.277 1 A T; 500 V Thyristor units for motor power up to 5.5 kW
F3 Internal 24 V DC supply
F4 Internal 24 V AC supply (115 V AC) for:

Heater, switch compartment, reversing contactors control

PTC tripping device


60
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
Corrective action AC 01.1 Non-Intrusive Modbus RTU

for 115 V AC also control inputs OPEN - STOP - CLOSE


F4 F3 G fuse according to IEC 60127-2/III
5 x 20 mm 5 x 20 mm Size
1.25 A T; 250 V 1.0 A T; 250 V Voltage output (power supply unit) = 24 V
0.315 A T; 250 V 1.0 A T; 250 V Voltage output (power supply unit) = 115 V
F5 Automatic reset fuse as short-circuit protection for external 24 V DC supply for
customer (see wiring diagram)
Information After fuse replacement, replace and fasten cover.
10.3.2 Motor protection (thermal monitoring)
In order to protect against overheating and impermissibly high surface temperatures
at the actuator, PTC thermistors or thermoswitches are embedded in the motor
winding. The thermoswitch is tripped as soon as the max. permissible winding
temperature has been reached.
The actuator is switched off and the following signals are given:

LED 3 (thermal fault) on the local controls is illuminated.

Status indication S0: Operation mode OFF/LOCAL = FLT + NR

Status indication S0/S6: Operation mode REMOTE = FAULT IND.

Status indication S1: THERMAL FAULT


The motor has to cool down before the operation can be resumed. Depending on
the parameter setting, the fault signal is either automatically reset or the fault signal
has to be acknowledged.
The acknowledgement is made:

via the Reset push button in selector switch position LOCAL.

or with the reset command via fieldbus.


For further information to this topic, please refer to the Manual (Operation and setting).
61
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Corrective action
11. Servicing and maintenance
Damage caused by inappropriate maintenance!
Servicing and maintenance must be carried out exclusively by suitably qualified
personnel having been authorised by the end user or the contractor of the plant.
Only perform servicing and maintenance tasks when the device is switched off.
Service
AUMA offers extensive service such as servicing and maintenance as well as
customer product training. For the relevant contact addresses, please refer to
<Addresses> in this document or to the Internet (www.auma.com) .
11.1 Preventive measures for servicing and safe operation
The following measures are required to ensure safe device operation:
6 months after commissioning and then every year

Carry out visual inspection:


Cable entries, cable glands, blanking plugs, etc. have to be checked for correct
tightness and sealing.
Respect torques according to manufacturer's details.

Check fastening screws between actuator and gearbox/valve for tightness. If


required, fasten screws while applying the tightening torques as indicated in
chapter <Assembly>.

When rarely operated: Perform test run.

For devices with output drive A: Press in Lithium soap EP multi-purpose grease
on mineral oil base at the grease nipple with a grease gun.

Lubrication of the valve stem must be done separately.


Figure 59: Output drive type A
[1] Output drive type A
[2] Grease nipple
Table 13: Grease quantities for bearing of output drive type A
A 16.2 A 14.2 A 10.2 A 07.2 Output drive
5 3 2 1.5 Quantity [g]
1)
For grease at density r = 0.9 kg/dm 1)
For enclosure protection IP 68
After continuous immersion:

Check actuator.

In case of ingress of water, locate leaks and repair, dry device correctly and
check for proper function.
11.2 Maintenance
Lubrication

In the factory, the gear housing is filled with grease.
62
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
Servicing and maintenance AC 01.1 Non-Intrusive Modbus RTU

Grease change is performed during maintenance


- Generally after 4 to 6 years for modulating duty.
- Generally after 6 to 8 years if operated frequently (open-close duty).
- Generally after 10 to 12 years if operated rarely (open-close duty).

We recommend exchanging the seals when changing the grease.

No additional lubrication of the gear housing is required during operation.


11.3 Disposal and recycling
Our devices have a long lifetime. However, they have to be replaced at one point in
time. The devices have a modular design and may, therefore, easily be separated
and sorted according to materials used, i.e.:

electronic scrap

various metals

plastics

greases and oils


The following generally applies:

Greases and oils are hazardous to water and must not be released into the
environment.

Arrange for controlled waste disposal of the disassembled material or for sepa-
rate recycling according to materials.

Observe the national regulations for waste disposal.


63
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Servicing and maintenance
12. Technical data
Information The following technical data includes standard and optional features. For detailed
information on the customer-specific version, refer to the order-relevant data sheet.
This data sheet can be downloaded from the Internet at http://www.auma.com (in-
dication of commission number required).
12.1 Features and functions of actuator
Standard:
SA: Short-time duty S2 - 15 min
SAR: Intermittent duty S4 - 25 %
Options:
SA: Short-time duty S2 - 30 min
SAR: Intermittent duty S4 - 50 %
SAR: Intermittent duty S5 25 %
Type of duty
1)
Refer to actuator name plate Torque range
Refer to actuator name plate Output speed
Standard: 3-ph AC asynchronous motor, type IM B9 according to IEC 60034 Motor
Standard: F, tropicalized
Option: H, tropicalized
Insulation class
Standard: Thermoswitches (NC)
Option: PTC thermistors (according to DIN 44082)
Motor protection
Self-locking: Output speeds up to 90 rpm (50 Hz), 108 rpm (60 Hz)
NOT self-locking: Output speeds up to 125 rpm (50 Hz), 150 rpm (60 Hz)
Multi-turn actuators are self-locking, if the valve position cannot be changed from standstill
while torque acts upon the output drive.
Self-locking
Magnetic limit and torque transmitter MWG for 1 to 500 turns per stroke or 10 to 5,000 turns
per stroke
Limit switching
Via MWG (like limit switching) Torque switching
Via MWG Position feedback signal, ana-
logue (option)
Via MWG Torque feedback signal, ana-
logue (option)
Continuous indication, adjustable indicator disc with symbols OPEN and CLOSED Mechanical position indicator
(option)
Blinker transmitter (standard for SA, option for SAR) Running indication
Voltages: 110 220 V AC, 220 240 V AC or 400 V AC
Power depending on the size 12.5 25 W
Motor heater (option)
Manual drive for setting and emergency operation, handwheel does not rotate during electrical
operation.
Option: Handwheel lockable
Manual operation
AUMA plug/socket connector with screw-type connection Connection to controls
Standard: B1 according to EN ISO 5210
Options:
A, B2, B3, B4 according to EN ISO 5210
A, B, D, E according to DIN 3210
C according to DIN 3338
Special output drive types: AF, B3D, ED, DD, IB1, IB3
A with stem lubrication
Valve attachment
For nominal voltage and 40 C ambient temperature and an average load with running torque or modulating torque according to sepa-
rate technical data. The type of duty must not be exceeded.
1)
64
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
Technical data AC 01.1 Non-Intrusive Modbus RTU
12.2 Features and functions of actuator controls
For mains voltage and mains frequency, refer to name plates at the controls and the motor
Permissible variation of the nominal voltage: 10 %
Permissible variation of the mains frequency: 5 %
Power supply, mains frequency
Motor current consumption: Refer to motor name plate
Current consumption of the controls depending on the mains voltage:
100 to 120 V AC = max. 650 mA
208 to 240 V AC = max. 325 mA
380 to 500 V AC = max. 190 mA
Current consumption
24 V DC +20 %/15 %
Current consumption: Basic version approx. 200 mA, with options up to 500 mA
External supply of the electro-
nics (option)
The controls are designed for the rated power of the motor, refer to motor name plate Rated power
Category III according to IEC 60364-4443 Overvoltage category
Standard:
Reversing contactors (mechanically and electrically interlocked) for motor power up to power
class A1
Options:
Reversing contactors (mechanically and electrically interlocked) for motor power up to
power class A2
Thyristor unit for mains voltage up to 500 V AC (recommended for modulating actuators)
for AUMA power classes B1, B2 and B3
Switchgear
1) 2)
Via fieldbus interface Control
Via fieldbus interface Output signals
Standard:
Modbus RTU interface without additional inputs
Options:
Additional inputs. The following version are available:
4 free 24 V DC inputs (current consumption: approx. ca. 5 mA/input) and 2 free 0/4 20
mA inputs. Signal transmission is made via fieldbus interface.
24 V DC control inputs OPEN CLOSE EMERGENY, or alternatively OPEN STOP
CLOSE (current consumption: approx. 5 mA/input). Selection of control mode via 24
V DC BUS/REMOTE input
24 V DC control inputs OPEN - CLOSE (current consumption: approx. 5 mA/input) and
0/4 20 mA input for position setpoint (positioner). Selection of control mode via 24 V
DC inputs BUS/REMOTE and MODE
24 V DC (115 V AC as option) control inputs OPEN - STOP - CLOSE - EMERGENCY
(current consumption: approx. 5mA/input) and 0/4 20 mA input for position setpoint
(positioner)
- Selection of control mode via 24 V DC (optional 115 V AC) BUS/REMOTE and MODE
inputs
- Status signals via 6 programmable output contacts, position feedback signal 0/4
20 mA
Fieldbus interface
Standard:
Auxiliary voltage 24 V DC, max. 100 mA for supply of the control inputs, galvanically isolated
from internal voltage supply
Option:
Auxiliary voltage 115 V AC, max. 30 mA to supply the control inputs
3)
, galvanically isolated
from internal voltage supply
Voltage output
Additional redundant Modbus RTU interface Component redundancy (option)
AUMATIC is equipped with an additional redundant Modbus interface to form a redundant
loop when combined with the SIMA Master Station
Max. number of actuators equipped with AUMATIC actuator controls per redundant loop:
247 units. Max. possible cable length between the actuators equipped with AUMATIC
actuator controls without external repeater: 1,200 m
Max. possible total cable length per redundant loop: approx. 290 km
Redundancy in loop structure
(option)
65
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Technical data
Standard:
Selector switch LOCAL - OFF - REMOTE (lockable in all three positions)
Push buttons OPEN - STOP - CLOSE - RESET
5 indication lights:
- End position CLOSED and running indication CLOSE (yellow), torque fault CLOSE
(red), motor protection tripped (red), torque fault OPEN (red), end position and running
indication OPEN (green)
LC display, illuminated
Programming interface (infra-red)
Options:
Bluetooth programming interface is equipped with a class II Bluetooth chip with a range
of up to 10 m. The interface supports the Bluetooth protocol SPP (Serial Port Profile).
Enabling the local controls using selector switch LOCAL - OFF - REMOTE via fieldbus
This way, actuator operation via push buttons of local controls can be either enabled or
disabled.
Special colours for the 5 indication lights:
- End position CLOSED (green), torque fault CLOSE (blue), torque fault OPEN (yellow),
motor protection tripped (white), end position OPEN
Protection cover, lockable
Protection cover with indicator glass, lockable
Local controls
Standard:
Switch-off mode adjustable
- Limit or torque seating for end position OPEN and end position CLOSED
Torque monitoring over the whole travel
Torque by-pass, adjustable up to 5 seconds (no torque monitoring during this time)
Phase failure monitoring
4)
with automatic phase correction
Running indication via indication lights/LEDs
Programmable behaviour in case of loss of bus communication
Positioner
5)
- Position setpoint via fieldbus interface
- Programmable behaviour on loss of signal
- Automatic adaptation of the dead band (adaptive behaviour can be selected)
- Change-over between open-close duty and modulating duty via fieldbus interface
Options:
Process controller, PID
6)
- Process setpoint via fieldbus interface
- Actual process value via 0/4 20 mA additional input
- Programmable behaviour on loss of signal
- Limitation of the control range
- Change-over between open-close duty and modulating duty via fieldbus interface
Multiport valve function
7)
- Direct approaching of up to 8 intermediate positions via fieldbus and local controls
Functions
Programmable monitoring of the max. number of starts, generates warning signal
Reaction monitoring for operation command (programmable from 1 to 15 seconds), ge-
nerates fault signal and results in switching off
Operating time monitoring (programmable from 4 to 1,800 seconds), generates warning
signal
Monitoring functions
Ordering data:
- AUMATIC commission number, actuator commission number, KKS number (definition
system for power plants), valve number, plant number
Product data:
- Product name, actuator works number, AUMATIC works number, logic software ver-
sion, logic hardware version, date of final test, wiring diagram, terminal plan
Project data:
- Project name, 2 freely definable customer fields with a max. of 19 characters each
Service data:
- Service telephone, Internet address, service text 1, service text 2
Electronic name plate
66
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
Technical data AC 01.1 Non-Intrusive Modbus RTU
A resettable counter and a lifetime counter each for:
Motor running time, number of starts, torque switch trippings in end position CLOSED, limit
switch trippings in end position CLOSED, torque switch trippings in end position OPEN, limit
switch trippings in end position OPEN, torque faults CLOSE, torque faults OPEN, motor
protection trippings
Operating data logging
Standard:
Monitoring of the motor temperature in combination with thermoswitches in the motor
Options:
Additional thermal overload relay in the controls in combination with thermoswitches within
the motor
PTC tripping device in combination with PTC thermistors in the motor
Motor protection evaluation
Standard:
AUMA plug/socket connector (S) with screw-type connection and M-threads
Options:
Pg-threads, NPT-threads, G-threads, special threads
Gold-plated control contacts (pins and sockets)
Parking frame for wall mounting of the disconnected plug
Protection cover for plug compartment (when plug is removed)
Electrical connection
Protection of the actuator and control electronics against overvoltages on the fieldbus cables
of up to 4 kV
Overvoltage protection (option)
Refer to name plate Wiring diagram
The reversing contactors are designed for a lifetime of 2 million starts. 1)
For the assignment of AUMA power classes, please refer to electrical data on actuator. 2)
Not possible in combination with PTC tripping device 3)
During an adjustable period (factory setting 10 seconds), faults in the supply voltage (e.g. voltage drops) will not lead to a fault signal. 4)
Requires position transmitter in actuator 5)
Requires position transmitter in actuator 6)
Requires position transmitter in actuator 7)
Further options for Non-intrusive version with MWG in the actuator
Setting limit and torque switching via the controls local controls
Start and end of stepping mode as well as ON and OFF time (1 up to 300 seconds) can be
programmed individually for the directions OPEN and CLOSE.
Timer
Any 8 intermediate positions between 0 and 100 %, reaction and signal behaviour program-
mable
Intermediate positions
12.3 Modbus interface
Settings/programming the Modbus interface
Baud rate, parity and Modbus address are set via the display of the AUMATIC. Setting the Modbus interface
67
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Technical data
Commands and signals of the fieldbus interface
OPEN, STOP, CLOSE, position setpoint
1)
, RESET Process representation output
(command signals)
End position OPEN, CLOSED
Actual position value
2)
Actual torque value
3)
Selector switch in position LOCAL/REMOTE
Running indication
4)
(directional)
Torque switch OPEN, CLOSE
Limit switch OPEN, CLOSED
Manual operation by handwheel
5)
or via local controls
2 analogue and 4 digital customer inputs
Process representation input
(feedback signals)
Motor protection tripped
Torque switch tripped in mid-travel
One phase missing
Loss of the analogue customer inputs
Process representation input
(fault signals)
The behaviour of the actuator is programmable:
Stops in current position
Travel to end position OPEN or CLOSED
Travel to any intermediate position
6)
Behaviour on loss of communi-
cation
Requires position transmitter in actuator 1)
Requires position transmitter in actuator 2)
Requires magnetic limit and torque transmitter (MWG) in actuator 3)
Requires position transmitter in actuator 4)
Requires position transmitter in actuator 5)
Requires position transmitter in actuator 6)
General fieldbus interface data
Modbus RTU Communication protocol
Line (bus) structure
Active bus termination at both ends
Coupling and uncoupling of devices during operation without affecting other devices is
possible
Network topology
Twisted, screened copper cable according to IEC 61158 Transmission medium
EIA-485 (RS485) Fieldbus interface
Baud rate and maximum cable length (segment length) without repeater:
between 300 and 38,400 bit/s: 1,200 m
Baud rate and possible cable length with repeater (total network cable length):
between 300 and 38,400 bit/s: approx. 10 km
Transmission speed/cable
length
Modbus slave, e.g. devices with digital and/or analogue inputs/outputs such as actuators,
sensors
Device types
68
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
Technical data AC 01.1 Non-Intrusive Modbus RTU
General fieldbus interface data
32 devices in each segment without repeater, with repeaters expandable to 247 Number of devices
Polling between master and slaves (query response) Bus access
01 Read Coil Status
02 Read Input Status
03 Read Holding Registers
04 Read Input Registers
05 Force Single Coil
15 (0FHex) Force Multiple Coils
06 Preset Single Register
16 (10Hex) Preset Multiple Registers
07 Read Exception Status
17 (11Hex) Report Slave ID
08 Diagnostics:
00 00 Loopback
00 10 (0AHex) Clear Counters and Diagnostic Register
00 11 (0BHex) Return Bus Message Count
00 12 (0CHex) Return Bus Communication Error Count
00 13 (0DHex) Return Bus Exception Error Count
00 14 (0EHex) Return Slave Message Count
00 15 (0FHex) Return Slave No Response Count
Supported fieldbus functions
12.4 Service conditions
Any position Mounting position
Indoor and outdoor use permissible Use
Standard:
IP 67 with AUMA 3-ph AC motor/1-ph AC motor
IP 55 with DC motor
For actual version, refer to actuator/controls name plate.
Enclosure protection according
to EN 60529
Standard:
KS: Suitable for installation in industrial units, in water or power plants with a low pollutant
concentration as well as for installation in occasionally or permanently aggressive atmosphere
with a moderate pollutant concentration (e.g. in wastewater treatment plants, chemical indus-
try)
Options:
KX: Suitable for installation in extremely aggressive atmospheres with high humidity and
high pollutant concentration
KX-G : same as KX, however aluminium-free version (outer parts)
Corrosion protection
Standard: 2,000 m above sea level
Option: > 2,000 m above sea level, please contact AUMA
Installation altitude
Up to 100 % relative humidity over the entire permissible temperature range Humidity
Within controls: Pollution degree 2
Outside controls (when closed): Pollution degree 4
Pollution degree
Standard: Paint based on polyurethane (powder coating) Finish coating
Standard: AUMA silver-grey (similar to RAL 7037) Colour
Standard:
25 C to +70 C
For actual version, refer to actuator/controls name plate.
Ambient temperature
1 g, from 10 to 200 Hz
Resistant to vibration during start-up or for failures of the plant. However, a fatigue strength
may not be derived from this. Not valid in combination with gearboxes.
Vibration resistance according
to IEC 60068-2-6
Open-close duty (operating cycles (OPEN - CLOSE - OPEN):
SA 07.1/07.5 SA 10.1: 20,000
SA 14.1/14.5 SA 16.1: 15,000
Modulating duty:
1)
SAR 07.1/07.5 SAR 10.1: 5.0 million modulating steps
SAR 14.1/14.5 SAR 16.1: 3.5 million modulating steps
Lifetime
Refer to separate technical data Weight
69
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Technical data
The lifetime depends on the load and the number of starts. A high starting frequency will rarely improve the modulating accuracy. To
reach the longest possible maintenance and fault-free operating time, the number of starts per hour chosen should be as low as permis-
sible for the process.
1)
12.5 Accessories
AUMATIC mounted separately from the actuator, including plug/socket connector. Connecting
cables on request. Recommended for high ambient temperatures, difficult access, or in case
of heavy vibration during service
Wall bracket
1)
The control voltage of the reversing contactors is interrupted by operating the EMERGENCY
STOP button.
EMERGENCY STOP button
2)
COM-AC. An interface cable is required for the standard infra-red programming interface. Programming software for PC
Cable distance between actuator and AUMATIC max. 100 m. Requires separate data cable for MWG. If actuator and AUMATIC are
separated at a later date, the max. cable length is 10 m.
1)
Only in combination with reversing contactors and AUMATIC AC 01.1 in enclosure protection IP 67 or IP 68 2)
12.6 Further information
Electromagnetic Compatibility (EMC): (2004/108/EC)
Low Voltage Directive: (2006/95/EC)
Machinery Directive: (2006/42/EC)
EU Directives
70
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
Technical data AC 01.1 Non-Intrusive Modbus RTU
13. Spare parts
13.1 Multi-turn actuators SA 07.1 SA 16.1/SAR 07.1 SAR 16.1
71
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Spare parts
Information: Please state type and commission no. of the device (see name plate) when ordering spare parts.
Only original AUMA spare parts should be used. Failure to use original spare parts voids the warranty and exempts
AUMA from any liability. Delivered spare parts may slightly vary from the representation.
Type Designation No. Type Designation No.
Output drive shaft D 516.1 Sub-assembly Housing 001.0
Snap ring 535.1 Sub-assembly Bearing flange 002.0
Screw plug 539.0 Sub-assembly Hollow shaft without worm wheel 003.0
Sub-assembly Handwheel with ball handle 542.0 Sub-assembly Worm shaft 005.0
Output drive sleeve B3/B4/E 549.1 Motor coupling 005.1
Parallel key 551.1 Coupling pin 005.2
Sub-assembly Mechanical position indicator 553.0 Manual drive coupling 005.3
Sub-assembly Socket carrier with motor cable har-
ness
554.0 Pull rope 005.4
Sub-assembly Potentiometer for position transmitter 556.0 Worm wheel 006.0
Sub-assembly Potentiometer without slip clutch 556.1 Sub-assembly Planetary gear for manual drive 009.0
Sub-assembly Heater 557.0 Sub-assembly Retaining flange 010.0
Sub-assembly Blinker transmitter including pins at
wires (without impulse disc and insula-
tion plate)
558.0 Sub-assembly Torque lever 017.0
Sub-assembly Control unit without torque switching
heads and switches
559.0-1 Gear segment 018.0
Sub-assembly Control unit with magnetic limit and
torque transmitter (MWG) for Non-in-
trusive version in combination with
AUMATIC integral controls
559.0-2 Sub-assembly Crown wheel 019.0
Sub-assembly Switch stack for direction OPEN 560.0-1 Sub-assembly Swing lever 020.0
Sub-assembly Switch stack for direction CLOSE 560.0-2 Sub-assembly Drive pinion II for torque switching 022.0
Switch for limit/torque switching 560.1 Sub-assembly Output drive wheel for limit switching 023.0
Switch case 560.2 Sub-assembly Drive wheel for limit switching 024.0
Sub-assembly Position transmitter RWG 566.0 Sub-assembly Locking plate 025.0
Sub-assembly Potentiometer for RWG without slip
clutch
566.1 Sub-assembly Wire for protective earth (pin) 058.0
Sub-assembly Electronic board RWG 566.2 Sub-assembly Torque switching head 061.0
Sub-assembly Wire harness for RWG 566.3 Sub-assembly Motor (VD motor incl. no. 079.0) 070.0
Sub-assembly Slip clutch for potentiometer/RWG 567.1 Sub-assembly Planetary gear for motor drive
(SA/SAR 07.1 14.1 for VD motor)
079.0
Stem protection tube (without cap) 568.1 Sub-assembly Planetary gear for motor drive
(SA/SAR 16.1 for AD90 motor)
080.0
Cap for stem protection tube 568.2 Sub-assembly Reduction gearing 155.0
V-Seal 568.3 Sub-assembly Cover for switch compartment 500.0
Change-over lever assy 569.0 Sub-assembly Socket carrier (complete with sockets) 501.0
Change-over lever 569.1 Sub-assembly Pin carrier without pins 502.0
Notched pin 569.2 Sub-assembly Socket for controls 503.0
Radial seal output drive A for ISO
flange
574.1 Sub-assembly Socket for motor 504.0
Stem nut type A 575.1 Sub-assembly Pin for controls 505.0
Set Seal kit, small S1 Sub-assembly Pin for motor 506.0
Set Seal kit, large S2 Sub-assembly Plug cover 507.0
Sub-assembly Screw plug 511.0
Sub-assembly Output drive form A (without stem nut) 514.0
Sub-assembly Axial needle roller bearing 514.1
72
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
Spare parts AC 01.1 Non-Intrusive Modbus RTU
13.2 Actuator controls AUMATIC AC 01.1 with AUMA plug/socket connector (SD bus)
73
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Spare parts
Information: Please state type and commission no. of the device (see name plate) when ordering spare parts.
Only original AUMA spare parts should be used. Failure to use original spare parts voids the warranty and exempts
AUMA from any liability. Delivered spare parts may slightly vary from the representation.
Type Designation No.
Sub-assembly Housing 001.0
Sub-assembly Local controls 002.0
Local controls board 002.3
Sub-assembly Power supply 006.0
Bus-Platine 008.1
Sub-assembly Logic board 009.0
Relay board 011.1
Bus connection board 050.1
Sub-assembly Cover 500.0
Sub-assembly Socket carrier (complete with sockets) 501.0
Sub-assembly Pin carrier without pins 502.0
Sub-assembly Socket for controls 503.0
Sub-assembly Socket for motor 504.0
Sub-assembly Pin for controls 505.0
Sub-assembly Pin for motor 506.0
Sub-assembly Electrical connection for bus without connection board (050.0) 507.0
Sub-assembly Frame 507.1
Sub-assembly Switchgear 508.0
Padlock 509.1
Set Fuse kit 510.0
Set Seal kit S
74
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
Spare parts AC 01.1 Non-Intrusive Modbus RTU
14. Certificates
14.1 Declaration of Incorporation and EC Declaration of Conformity
75
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Certificates
Index
A
Accessories (electrical
connection)
25
Accessories for assembly 15
Actuator operation from remo-
te
30
Ambient temperature 69
Applications 5
Assembly 11
B
Baud rate 48
Bus address 48
Bus cables 18 , 22
C
Cable redundancy 51
Cable set 25
Commission number 9
Commissioning 5
Connecting cable 25
Connection monitoring time 51
Control 9
Corrective action 57
Corrosion protection 10 , 69
Cross section 18
Cross sections 19
Current consumption 17
D
Declaration of Incorporation 75
Direction of rotation 52
Directives 5
Display (indications) 34
Disposal 63
Double sealed 27
E
EC Declaration of Conformity 75
EMC 17
Earth connection 27
Electrical connection 17
Enclosure protection 69
End position(s) reached dis-
play
34
End positions 38
F
Feedback signals (analogue) 37
H
Handwheel 11
Heat-up time 38
I
Identification 8
Indication lights 35
Indications 34
Indicator disc 36 , 54
Inspection record 9
Intermediate frame 27
Intrusive 9
L
LEDs 35
Language in the display 32
Limit switching 46 , 53
Local control 29
Local controls 29
Low temperature version 38
Lubrication 62
M
Mains frequency 18
Mains voltage 18
Maintenance 5 , 62 , 62
Manual operation 28
Mechanical position indicator 36 , 54
Menu navigation via push
buttons
30
Motor heater 21
Motor operation 29
N
Name plate 8 , 18
Non-Intrusive 9
O
Operation 5 , 28
Operation command/setpoint
display
34
Operation mode display 34
Output drive type A 13
Output drive types B, B1, B2,
B3, B4, and E
12
P
Packaging 10
Parity 48
Parking frame 26
Password entry 32
Position indicator 54
Power supply 17 , 18
Protection cover 27
Protection on site 17
Protective measures 5
Push buttons 31
Q
Qualification of staff 5
76
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
Index AC 01.1 Non-Intrusive Modbus RTU
R
Range of application 5
Recycling 63
Reduction gearing 54
Remote actuator operation 30
Running indication 36 , 36
Running indication (in display) 34
S
S0/S6 - operation 34
S4 - torque 35
Safety instructions 5
Safety instructions/warnings 5
Service 62
Service conditions 69
Servicing 62
Short-circuit protection 17
Signals 37
Slave address 48
Spare parts 71
Standards 5
Status indications (in the dis-
play)
34
Stem nut 13
Stem protection tube 15
Storage 10
T
Technical data 64
Terminal plan 17
Test run 52
Torque indication 35 , 35
Torque switching 42
Transport 10
Tripping torque 38
Type and size 8
Type of current 18
Type of seating 38
V
Valve position display 34
Valve stem 15
W
Wall bracket 25
Wire diameter (bus cable) 18
Wiring diagram 9 , 17
77
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Index
Europe
AUMA Riester GmbH & Co. KG
Plant Mllheim
DE 79373 Mllheim
Tel +49 7631 809 - 0
Fax +49 7631 809 - 1250
riester@auma.com
www.auma.com
Plant Ostfildern - Nellingen
DE 73747 Ostfildern
Tel +49 711 34803 - 0
Fax +49 711 34803 - 3034
riester@wof.auma.com
Service-Center Kln
DE 50858 Kln
Tel +49 2234 2037 - 900
Fax +49 2234 2037 - 9099
service@sck.auma.com
Service-Center Magdeburg
DE 39167 Niederndodeleben
Tel +49 39204 759 - 0
Fax +49 39204 759 - 9429
Service@scm.auma.com
Service-Center Bayern
DE 85386 Eching
Tel +49 81 65 9017- 0
Fax +49 81 65 9017- 2018
Riester@scb.auma.com
AUMA Armaturenantriebe GmbH
AT 2512 Tribuswinkel
Tel +43 2252 82540
Fax +43 2252 8254050
office@auma.at
www.auma.at
AUMA (Schweiz) AG
CH 8965 Berikon
Tel +41 566 400945
Fax +41 566 400948
RettichP.ch@auma.com
AUMA Servopohony spol. s.r.o.
CZ 250 01 Brands n.L.-St.Boleslav
Tel +420 326 396 993
Fax +420 326 303 251
auma-s@auma.cz
www.auma.cz
OY AUMATOR AB
FI 02230 Espoo
Tel +358 9 5840 22
Fax +358 9 5840 2300
auma@aumator.fi
www.aumator.fi
AUMA France S.A.R.L.
FR 95157 Taverny Cedex
Tel +33 1 39327272
Fax +33 1 39321755
info@auma.fr
www.auma.fr
AUMA ACTUATORS Ltd.
UK Clevedon, North Somerset BS21 6TH
Tel +44 1275 871141
Fax +44 1275 875492
mail@auma.co.uk
www.auma.co.uk
AUMA ITALIANA S.r.l. a socio unico
IT 20023 Cerro Maggiore (MI)
Tel +39 0331 51351
Fax +39 0331 517606
info@auma.it
www.auma.it
AUMA BENELUX B.V.
NL 2314 XT Leiden
Tel +31 71 581 40 40
Fax +31 71 581 40 49
office@benelux.auma.com
www.auma.nl
AUMA Polska Sp. z o.o.
PL 41-219 Sosnowiec
Tel +48 32 783 52 00
Fax +48 32 783 52 08
biuro@auma.com.pl
www.auma.com.pl
OOO Priwody AUMA
RU 124365 Moscow a/ya 11
Tel +7 495 221 64 28
Fax +7 495 221 64 38
aumarussia@auma.ru
www.auma.ru
ERICHS ARMATUR AB
SE 20039 Malm
Tel +46 40 311550
Fax +46 40 945515
info@erichsarmatur.se
www.erichsarmatur.se
GRNBECH & SNNER A/S
DK 2450 Kbenhavn SV
Tel+45 33 26 63 00
Fax+45 33 26 63 21
GS@g-s.dk
www.g-s.dk
IBEROPLAN S.A.
ES 28027 Madrid
Tel+34 91 3717130
Fax+34 91 7427126
iberoplan@iberoplan.com
D. G. Bellos & Co. O.E.
GR 13671 Acharnai Athens
Tel+30 210 2409485
Fax+30 210 2409486
info@dgbellos.gr
SIGURD SRUM AS
NO 1300 Sandvika
Tel+47 67572600
Fax+47 67572610
post@sigum.no
INDUSTRA
PT 2710-297 Sintra
Tel+351 2 1910 95 00
Fax+351 2 1910 95 99
industra@talis-group.com
MEGA Endstri Kontrol Sistemieri Tic. Ltd.
Sti.
TR 06810 Ankara
Tel+90 312 217 32 88
Fax+90 312 217 33 88
megaendustri@megaendustri.com.tr
www.megaendustri.com.tr
AUMA Technology utomations Ltd.
UA 02099 Kiyiv
Tel+38 044 586-53-03
Fax+38 044 586-53-03
auma-tech@aumatech.com.ua
Africa
AUMA South Africa (Pty) Ltd.
ZA 1560 Springs
Tel +27 11 3632880
Fax +27 11 8185248
aumasa@mweb.co.za
A.T.E.C.
EG Cairo
Tel +20 2 23599680 - 23590861
Fax +20 2 23586621
atec@intouch.com
CMR Contrle Maintenance Rgulation
TN 1002 Tunis
Tel +216 71 903 577
Fax +216 71 903 575
instrum@cmr.com.tn
www.cmr-tunisie.net
MANZ INCORPORATED LTD.
NG Port Harcourt
Tel +234-84-462741
Fax +234-84-462741
mail@manzincorporated.com
www.manzincorporated.com
America
AUMA ACTUATORS INC.
US PA 15317 Canonsburg
Tel +1 724-743-AUMA (2862)
Fax +1 724-743-4711
mailbox@auma-usa.com
www.auma-usa.com
AUMA Argentina Representative Office
AR 1609 Boulogne
Tel/Fax +54 232 246 2283
contacto@aumaargentina.com.ar
AUMA Automao do Brasil Ltda.
BR So Paulo
Tel +55 11 8114-6463
bitzco@uol.com.br
AUMA Chile Representative Office
CL 9500414 Buin
Tel +56 2 821 4108
Fax +56 2 281 9252
aumachile@adsl.tie.cl
TROY-ONTOR Inc.
CA L4N 8X1 Barrie Ontario
Tel +1 705 721-8246
Fax +1 705 721-5851
troy-ontor@troy-ontor.ca
78
AUMA worldwide
Ferrostaal de Colombia Ltda.
CO Bogot D.C.
Tel +57 1 401 1300
Fax+57 1 416 5489
dorian.hernandez@ferrostaal.com
www.ferrostaal.com
PROCONTIC Procesos y Control
Automtico
EC Quito
Tel +593 2 292 0431
Fax +593 2 292 2343
info@procontic.com.ec
Corsusa International S.A.C.
PE Miraflores - Lima
Tel +511444-1200 / 0044 / 2321
Fax +511444-3664
corsusa@corsusa.com
www.corsusa.com
PASSCO Inc.
PR 00936-4153 San Juan
Tel +18 09 78 77 20 87 85
Fax +18 09 78 77 31 72 77
Passco@prtc.net
Suplibarca
VE Maracaibo Estado, Zulia
Tel +58 261 7 555 667
Fax +58 261 7 532 259
suplibarca@intercable.net.ve
Asia
AUMA Actuators (Tianjin) Co., Ltd.
CN 300457 Tianjin
Tel +86 22 6625 1310
Fax +86 22 6625 1320
mailbox@auma-china.com
www.auma-china.com
AUMA INDIA PRIVATE LIMITED
IN 560 058 Bangalore
Tel +91 80 2839 4656
Fax +91 80 2839 2809
info@auma.co.in
www.auma.co.in
AUMA JAPAN Co., Ltd.
JP 2110016 Kawasaki-ku, Kawasaki-shi
Kanagawa
Tel +81 44 863 8371
Fax +81 44 863 8372
mailbox@auma.co.jp
www.auma.co.jp
AUMA ACTUATORS (Singapore) Pte Ltd.
SG 569551 Singapore
Tel +65 6 4818750
Fax +65 6 4818269
sales@auma.com.sg
www.auma.com.sg
AUMA Actuators Middle East W.L.L.
AE 15268 Salmabad 704
Tel +973 17877377
Fax +973 17877355
Naveen.Shetty@auma.com
PERFECT CONTROLS Ltd.
HK Tsuen Wan, Kowloon
Tel +852 2493 7726
Fax +852 2416 3763
joeip@perfectcontrols.com.hk
DW Controls Co., Ltd.
KR 153-702 Seoul
Tel +82 2 2624 3400
Fax +82 2 2624 3401
sichoi@actuatorbank.com
www.actuatorbank.com
Sunny Valves and Intertrade Corp. Ltd.
TH 10120 Yannawa Bangkok
Tel +66 2 2400656
Fax +66 2 2401095
sunnyvalves@inet.co.th
www.sunnyvalves.co.th/
Top Advance Enterprises Ltd.
TW Jhonghe City Taipei Hsien (235)
Tel +886 2 2225 1718
Fax +886 2 8228 1975
support@auma-taiwan.com.tw
www.auma-taiwan.com.tw
Australia
BARRON GJM Pty. Ltd.
AU NSW 1570 Artarmon
Tel +61 294361088
Fax +61 294393413
info@barron.com.au
www.barron.com.au
79
AUMA worldwide
AUMA Riester GmbH & Co. KG
P.O.Box 1362
D 79373 Muellheim
Tel +49 7631 809 - 0
Fax +49 7631 809 - 1250
riester@auma.com
www.auma.com
Y004.705/003/en/3.12
For detailed information on AUMA products refer to the Internet: www.auma.com

You might also like