CE-marking, UL approval and C-Tick
Technical Data and Dimension Sheets
2 Technical Data and Dimension Sheets
2.1 CE-marking, UL approval and C-Tick
CE marking Low voltage directive
MOVIDRIVE
MDX60B/61B
inverters, regardless of their type, version, size and performance.
MOVIDRIVE
MDX60B/61B
series, size 0
MOVIDRIVE
MDX61B series,
sizes 1 to 6
51485AXX
Figure 6: MOVIDRIVE
inverter with electrical power from the supply system in motor operation and returns
regenerative power to the supply system in regenerative operation.
UL approval UL and cUL approval has been granted for the entire MOVIDRIVE
MDR60A0370-503-
00 and MDR60A0750-503-00 range of units. cUL is equivalent to CSA approval. The
MOVIDRIVE
MDR60A 0370-503-00
(size 3)
0750-503-00
(size 4)
1320-503-00
(size 6)
Part number 826 658 1 826 556 9 827 952 7
INPUT
Rated mains voltage (according to EN 50160)
V
supply
3 AC 380 V - 500 V
Supply frequency f
supply
50 Hz - 60 Hz 5 % 40 Hz - 60 Hz 10 %
Rated connected load P
N
37 kW 75 kW 132 kW
Rated supply current I
supply
(at V
supply
= 3 AC 400 V)
AC 66 A AC 117 A AC 260 A
DC LINK
Apparent output power S
A
(at U
supply
= 3 AC 380..0.500 V)
50 kVA 90 kVA 173 kVA
DC link voltage U
DC link
DC 560 V - 780 V
Rated DC link current I
DC link
DC 70 A DC 141 A DC 340 A
Max. DC link current I
DClink_max
DC 105 A DC 212 A DC 410 A
GENERAL INFORMATION
Power loss at P
N
P
Vmax
950 W 1700 W 2650 W
Cooling air consumption 180 m
3
/h 360 m
3
/h 700 m
3
/h
Connection for power terminals X1, X2
(L1, L2, L3 for size 6)
Permitted tightening torque
Permitted cable cross section
M6 screw with washer
3.5 Nm (31 in-lb)
25 mm
2
(AWG4)
M10 terminal studs
14 Nm (120 in-lb)
70 mm
2
(AWG2/0)
M10 terminal studs
3.5 Nm
25 mm
2
(AWG4)
Connection for DC link connection UG
Permitted cable cross section
Permitted tightening torque
- - 150 mm
2
(power supply
connection) / 30 Nm
(270 in-lb)
1)
185 mm
2
(power supply
connection) / 32 Nm
(280 in-lb)
1)
Connection for electronics terminalsX3
(X2 for size 6)
Permitted cable cross section:
One conductor per terminal: 0.20...2.5 mm
2
(AWG24...13)
Two conductors per terminal:0.25...1 mm
2
(AWG23...17)
Permitted cable cross
section:
0.8...4 mm
2
(AWG18...12)
Weight 16 kg (35 lb) 24 kg (53 lb) 90 kg (200 lb)
Dimensions W H D 200 mm 465 mm
221 mm
(7.87 in x 18.3 in x 8.7 in)
280 mm 522 mm
205 mm
(11 in x 20.6 in x 8.07 in)
380 mm 937 mm
395 mm
(15 in x 36.9 in x 15.6 in)
Line choke (always required) ND085-013
L
N
= 0.1 mH
Part number 826 014 1
ND200-0033
L
N
= 0.03 mH
Part number 826 579 8
Already installed
Line filter (optional) NF085-503, part number
827 415 0
NF150-503, part number
827 417 7
NF300-503, part number
827 419 3
For MOVIDRIVE
MDX60B/61B...-5_3 0005 ... 0370 0005 ... 0750 0005 ... 1320
1) Important: Do not apply tightening torque directly at terminals L1, L2, L3 and UG; use a second wrench.
P
i
f
kVA
Hz
n
64 System Manual MOVIDRIVE MDX60B/61B Inverter
2
MOVIDRIVE MDR60A regenerative power supply units
Technical Data and Dimension Sheets
Dimension draw-
ings for MDR60A
Provide at least 100 mm clearance above and below the unit. There is no need for
clearance at the sides. You can line up the units directly next to one another. With sizes
4 and 6, do not install any components that are sensitive to high temperatures within
300 mm (11.8 in) of the top of the unit, for example contactors or fuses.
54260CXX
Figure 22: Dimension drawing, MDR60A size 3, dimensions in mm (in)
54261CXX
Figure 23: Dimension drawing, MDR60A size 4, dimensions in mm (in)
4
6
5
(
1
8
.
3
)
4
4
5
(
1
7
.
5
)
1
1
(
0
.
4
3
)
7 (0.3)
105 (4.13)
200 (7.87) 221(8.70)
173 (6.81)
5
2
2
(
2
0
.
6
)
5
0
2
(
1
9
.
8
)
1
1
(
0
.
4
3
)
7 (0.3)
140 (5.51)
280 (11.0) 205 (8.07)
160 (6.30)
P
i
f
kVA
Hz
n
System Manual MOVIDRIVE MDX60B/61B Inverter 65
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
MOVIDRIVE MDR60A regenerative power supply units
Technical Data and Dimension Sheets
DC link
connection
SEW-EURODRIVE recommends using the following cable sets for the DC link connec-
tion. These cable sets offer the appropriate dielectric strength and are also color-coded.
Color coding is necessary because cross-polarity and ground faults could cause irrepa-
rable damage to the connected equipment.
The length of the cables restricts the DC link connection to the permitted length of 5 m.
They can also be cut to length by the customer for connecting several units. The lugs
for connection to the regenerative power supply unit and an inverter are supplied with
the cable set. Use commercially available lugs for connecting additional inverters. The
inverters must then be connected to the regenerative power supply unit in star configu-
ration.
54282CXX
Figure 24: Dimension drawing, MDR60A size 6, dimensions in mm (in)
395 (15.6)
85 (3.3)
1
1
0
(
4
.
3
3
)
8
0
4
(
3
1
.
7
)
3
3
(
1
.
3
)
350 (13.8)
380 (15.0)
8
2
(
3
.
2
)
3
5
0
(
1
3
.
8
)
6
8
0
(
2
6
.
8
)
Cable set type DCP12A DCP13A DCP15A DCP16A
Part number 814 567 9 814 250 5 814 251 3 817 593 4
For connecting MOVIDRIVE
0005 ... 0110 0150 ... 0370 0450 ... 0750 0900 ... 1320
NOTE
Refer to the "MOVIDRIVE
is possible)
Processing of digital and analog input/output signals
With encoder
feedback only
Positioning with selectable travel speed, positioning ramp and jerk limitation
Feedforward for position, speed and torque control loops with minimized lag error
Two touch probe inputs
Ramp types: LINEAR, JERK LIMITED, SINE and SQUARE
Status and monitoring functions: Lag error monitoring, position signal, software and
hardware limit switches
Nine types of reference travel
Possibility of changing the target position, travel speed, positioning ramp and torque
while movement is in progress
Possibility of "Endless positioning"
Override function
Cam control
Synchronous operation and electronic cam
Max. program length of task 1, task 2 and task 3 Total of ca. 3200 program lines
Command processing time per program line Task 1, 2: 1 ... 11 commands/ms can be configured
Task 3: At least 1 command/ms (typical is 40 commands/ms)
Variables 1024, of which 128 (0 ... 127) can be stored to non-volatile memory; range
of values: 2
31
...+(2
31
1)
Touch probe inputs 2 inputs, processing time < 100 s
Sampling interval of digital and analog inputs 1 ms
Digital inputs/outputs 8 inputs / 5 outputs
Analog inputs/outputs 1 input (DC 0...10 V, DC10 V, DC 0...20 mA, DC 4...20 mA)
1 input (DC 0...10 V)
1 output (DC 0...20 mA, DC 4...20 mA)
P
i
f
kVA
Hz
n
System Manual MOVIDRIVE MDX60B/61B Inverter 67
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
DBG60B keypad option
Technical Data and Dimension Sheets
2.10 DBG60B keypad option
Description The basic version of MOVIDRIVE
units.
User-friendly startup menu for VFC mode
Manual control of MOVIDRIVE
B and MOVITRAC
B
Manual operation of MOVIMOT
MDX61B size
2S, the MDX61B size 2S can be fitted on the existing mounting plate with the DMP11B
mounting panel. New retaining holes do not have to be drilled.
54588AXX
DMP11B
P
i
f
kVA
Hz
n
System Manual MOVIDRIVE MDX60B/61B Inverter 71
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
DLB11B touch guard option
Technical Data and Dimension Sheets
2.12 DLB11B touch guard option
Part number 823 111 7 (12 pieces included in the scope of delivery)
Description
Degree of protection IP20 can be achieved with touch guard DLB11B for MOVIDRIVE
encoder card type DEH11B. The encoder card offers one input for the
motor encoder and one input for an external encoder, also referred to as synchronous
encoder. The input for the external encoder can also be used as an output for incremen-
tal encoder simulation.
Electronics data
Option DEH11B
11870AXX
Output for incremental
encoder simulation or
external encoder input
X14:
Output for incremental encoder simu-
lation:
Signal level to RS422
The number of pulses is the
same as on X15 motor encoder
input
External encoder input (max. 200 kHz):
Permitted encoder types:
HIPERFACE
encoder
sin/cos encoder AC 1 V
SS
TTL encoder with negated tracks
Encoder with signal level to RS422
Encoder power supply:
DC+12 V (tolerance range DC 10.5 - 13 V)
I
max
= DC 650 mA
1)
1) Total current load of DC 12 V encoder supply DC 650 mA.
Motor encoder inputX15: Permitted encoder types:
HIPERFACE
encoder
sin/cos encoder AC 1 V
SS
TTL encoder with negated tracks
Encoder with signal level to RS422
Permitted resolution: 128/256/512/1024/2048 increments
Encoder power supply:
DC+12 V (tolerance range DC 10.5 - 13 V)
I
max
= DC 650 mA
1)
P
i
f
kVA
Hz
n
System Manual MOVIDRIVE MDX60B/61B Inverter 73
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
Absolute encoder card option type DEH21B/DIP11B
Technical Data and Dimension Sheets
2.14 Absolute encoder card option type DEH21B/DIP11B
Part numbers DEH21B: 1820 818 5
DIP11B: 824 969 5
Description The DEH21B and DIP11B options extend the MOVIDRIVE
encoder
sin/cos encoder AC 1 V
SS
TTL encoder with negated tracks
Encoder with signal level to RS422
Permitted resolution: 128/256/512/1024/2048 increments
Encoder power supply: ,
DC+12 V (tolerance range DC 10.5 ... 13 V)
I
max
= DC 650 mA
Encoder connection X62: SSI encoder input
Power supply connection
X60:1
24VIN: DC 24 V power supply for encoder connected to X62
Reference terminal X60:2 Reference potential 24VIN
P
i
f
kVA
Hz
n
74 System Manual MOVIDRIVE MDX60B/61B Inverter
2
Absolute encoder card option type DEH21B/DIP11B
Technical Data and Dimension Sheets
Electronics data for DIP11B
DIP11B option
11884AXX
Connection binary inputs X60:1 ... 8
Internal resistance
Signal level (EN 61131)
Function X60:1 ... 8
DI10 ... DI17 isolated via optocoupler, PLC compatible (EN 61131),
scanning time 1 ms
R
i
3 k , I
E
DC 10 mA
DC+13 V ... +30 V = "1" / DC3 V ... +5 V = "0"
DI10 ... DI17: Selection option Parameter menu P61_
Connection binary outputs X61:1 ... 8
Signal level (EN 61131)
Function X61:1 ... 8
DO10 ... DO17, PLC-compatible (EN 61131), short-circuit proof and
protected against external voltage to DC 30 V
Response time 1 ms
DC +24 V = "1" DC 0 V = "0" Important: Do not apply external voltage!
DO10 ... DO17: Selection option Parameter menu P63_
Encoder connection X62: SSI encoder input
Reference terminals X60:9
X60:10
DCOM: Reference potential for binary inputs (DI10 ... DI17)
DGND: Reference potential for binary signals and 24VIN
without jumper X60:9-X60:10 (DCOM-DGND) isolated binary inputs
With jumper X60:9-X60:10 (DCOM-DGND) non-isolated binary inputs
Permitted line cross section One core per terminal: 0.08 ... 1.5 mm
2
(AWG28 ... 16)
Two cores per terminal: 0.25 ... 1 mm
2
(AWG22 .. 17)
Voltage input X61:9 24VIN: Supply voltage DC+24 V for binary outputs DO10 ... DO17 and
encoder (mandatory)
P
i
f
kVA
Hz
n
System Manual MOVIDRIVE MDX60B/61B Inverter 75
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
Resolver card option type DER11B
Technical Data and Dimension Sheets
2.15 Resolver card option type DER11B
Part number 824 307 7
Description Option-capable MOVIDRIVE
encoder
sin/cos encoder AC 1 V
SS
TTL encoder with negated tracks
Encoder with signal level to RS422
Encoder power supply:
DC+12 V (tolerance range DC 10.5 - 13 V)
I
max
= DC 650 mA
Motor encoder input X15: Resolver
2-pole, U
ref
= AC 3.5 V
eff
, 4 kHz
U
in
/ U
ref
= 0.5
Maximum cable length: 100 m (328 ft)
P
i
f
kVA
Hz
n
76 System Manual MOVIDRIVE MDX60B/61B Inverter
2
Connector adapter for unit replacement MD_60A - MDX60B/61B
Technical Data and Dimension Sheets
2.16 Connector adapter for unit replacement MD_60A - MDX60B/61B
The following adapters are available for rapid replacement of a MOVIDRIVE
A unit with
a MOVIDRIVE
MDX61B, option
DEH11B/DER11B, X14)
Core color in prefabricated
cable
Terminal of the 9-pin
sub D connector
(encoder end)
1 Yellow (YE) 1
2 Red (RD) 2
3 Pink (PK) 3
7 Violet (VT) 4
8 Brown (BN) 5
9 Green (GN) 6
10 Blue (BU) 7
11 Gray (GY) 8
15 White (WH) 9
DAE14B
P
i
f
kVA
Hz
n
78 System Manual MOVIDRIVE MDX60B/61B Inverter
2
Interface adapter option type DWE11B/12B
Technical Data and Dimension Sheets
2.17 Interface adapter option type DWE11B/12B
Part number and
description
DWE11B, part number 188 187 6
The interface adapter DWE11B (HTLTTL) in the form of an adapter cable is used
to connect single-ended HTL encoders to the DEH11B/DEH21B option. Only the
A, B and C tracks are connected. The interface adapter is suitable for all HTL
encoders that were operated on MOVIDRIVE
unit (ST11/ST12).
The UWS11A option requires a DC 24 V voltage supply (I
max
= DC 50 mA).
RS232 interface The connection between UWS11A and PC is made using a commercially available
serial interface cable (shielded!).
RS485 interface Max. 32 MOVIDRIVE
B.
RS232 interface The connection of UWS21B with PC is made using a standard serial interface cable
(shielded).
RS485 interface UWS21B and MOVIDRIVE
B.
CD-ROM with MOVITOOLS
Dimension
drawing
Dimensions in mm (in)
Technical data
58558BXX
25 (0.98)
90 (3.5)
96 (3.8)
4
3
(
1
.
7
)
UWS21B
Part number 1 820 456 2
Ambient temperature 0 ... 40 C
Storage temperature 25 C ... +70 C (according to EN 60721-3-3, class 3K3)
Degree of protection IP20
Weight 300 g (0.7 lb)
Dimensions 96 mm x 43 mm x 25 mm (3.8 in x 1.7 in x 0.98 in)
P
i
f
kVA
Hz
n
82 System Manual MOVIDRIVE MDX60B/61B Inverter
2
Interface adapter option type USB11A
Technical Data and Dimension Sheets
2.20 Interface adapter option type USB11A
Part number 824 831 1
Description Option USB11A enables a PC or laptop with a USB interface to be connected to the XT
slot of MOVIDRIVE
-
USB11A
MOVIDRIVE
B and USB11A are connected using a serial interface cable with RJ10
connectors.
Scope of delivery The scope of delivery for the USB11A option includes:
USB11A interface adapter
USB connection cable to connect USB11A - PC
Serial interface cable with two RJ10 connectors to connect USB11A and
MOVIDRIVE
B
CD-ROM with drivers and MOVITOOLS
Dimension
drawing
Dimensions in mm (in)
Technical data
55732CXX
92.5 (3.64) 25 (0.98)
90 (3.0)
4
3
(
1
.
7
)
USB11A
Part number 824 831 1
Ambient temperature 0 ... 40 C
Storage temperature 25 C ... +70 C (according to EN 60721-3-3, class 3K3)
Degree of protection IP20
Weight 300 g (80.7 lb)
Dimensions 92.5 mm x 43 mm x 25 mm (3.64 in x 1.7 in x 0.98 in)
P
i
f
kVA
Hz
n
System Manual MOVIDRIVE MDX60B/61B Inverter 83
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
DC 5 V encoder power supply option type DWI11A
Technical Data and Dimension Sheets
2.21 DC 5 V encoder power supply option type DWI11A
Part number 822 759 4
Description If you are using an incremental encoder with a DC 5 V encoder power supply, install the
DC 5 V encoder power supply option type DWI11A between the inverter and the
incremental encoder. This option provides a regulated DC 5 V power supply for the
encoder. For this purpose, the DC 12 V power supply for the encoder inputs is converted
to DC 5 V by means of a voltage controller. A sensor line is used to measure the supply
voltage at the encoder and compensate the voltage drop along the encoder cable.
Incremental encoders with DC 5 V encoder power supply are not allowed to be
connected directly to the encoder inputs X14: and X15: . This would cause irreparable
damage to the encoder.
Recommendation Use prefabricated cables from SEW for the encoder connection.
Dimension
drawing
Dimensions in mm (in)
The DWI11A option is mounted on a support rail (EN 50022-35 7.5) in the control
cabinet.
Technical data
NOTE
Note that if a short circuit occurs in the sensor cable, the connected encoder may be
exposed to a voltage higher than permitted.
01315DXX
68 (2.7)
73 (2.9)
5 (0.2)
22.5 (0.886)
7
5
(
3
.
0
)
X
2
:
E
n
c
o
d
e
r
X
1
:
M
O
V
I
D
R
I
V
E
DWI
DC 5 V encoder power supply option type DWI11A
Part number 822 759 4
Voltage input DC 10...30 V, I
max
= DC 120 mA
Encoder power supply DC +5 V (up to U
max
+10 V), I
max
= DC 300 mA
Max. line length that can be
connected
100 m (9,997.44 cm) total
Use a shielded twisted-pair cable (A and A, B and B, C and C) for
connecting the encoder to the DWI11A and the DWI11A to
MOVIDRIVE
.
P
i
f
kVA
Hz
n
84 System Manual MOVIDRIVE MDX60B/61B Inverter
2
Input/output card type DIO11B option
Technical Data and Dimension Sheets
2.22 Input/output card type DIO11B option
Part number 824 308 5
Description The number of inputs/outputs of the basic MOVIDRIVE
B
can be controlled via PLC and PROFIBUS-DP / DP-V1.
Electronics data
DFP21B option
11873AXX
Protocol option
Baud rate
Connection technology
Bus terminator
Station address
GSD file name
DP ID number
Max. number of process data
PROFIBUS-DP and DPV1 to IEC 61158
Automatic detection of baud rate from 9.6 kbaud to 12 Mbaud
9-pin sub D socket, pin assignment to IEC 61158
Not integrated, implement using suitable PROFIBUS connector with terminating
resistors that can be activated
1 ... 125, adjustable via DIP switches
DP: SEW_6003.GSD
DP-V1: SEWA6003.GSD
6003
hex
(24579
dec
)
10 process data
P
i
f
kVA
Hz
n
86 System Manual MOVIDRIVE MDX60B/61B Inverter
2
INTERBUS fieldbus interface option type DFI11B
Technical Data and Dimension Sheets
2.24 INTERBUS fieldbus interface option type DFI11B
Part number 824 309 3
Description MOVIDRIVE
via Ethernet-TCP/IP
Inverter diagnostics using a standard browser (e.g. Internet Explorer) via the
integrated Web server:
Transfer display values
Configure DFE11B (after login)
Option DFE11B
11876AXX
Application protocols MODBUS/TCP (Transmission Control Protocol) to control and set parameters for
the inverter.
HTTP (Hypertext Transfer Protocol) for diagnostics using a Web browser.
SMLP (Simple Movilink Protocol), protocol used by MOVITOOLS
.
DHCP (Dynamic Host Configuration Protocol) to assign address parameter auto-
matically.
Port numbers used 502 (MODBUS)
300 (SMLP)
80 (HTTP)
67 / 68 (DHCP)
Ethernet services ARP
ICMP (Ping)
Automatic baud rate detection 10 MBaud / 100 MBaud
Max. number of process data 10 process data
Connection technology RJ45 plug connector
Addressing 4 byte IP address
Tools for startup MOVITOOLS
MotionStudio software
DBG60B keypad
P
i
f
kVA
Hz
n
System Manual MOVIDRIVE MDX60B/61B Inverter 89
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
PROFINET IO RT type DFE12B fieldbus interface option
Technical Data and Dimension Sheets
2.27 PROFINET IO RT type DFE12B fieldbus interface option
Part number 1820 563 1
Description The MOVIDRIVE
via Ethernet-TCP/IP
Inverter diagnostics using a standard browser (e.g. Internet Explorer) via the
integrated Web server:
Transfer display values
DFE11B configuration (after login)
Option DFE12B
11877AXX
Application protocols PROFINET IO to control and configure the drive inverter.
HTTP (Hypertext Transfer Protocol) for diagnostics using a Web browser.
SMLP (Simple Movilink Protocol), protocol used by MOVITOOLS
.
Port numbers used 34962 - 34964 (PROFINET IO)
300 (SMLP)
80 (HTTP)
Ethernet services ICMP (ping)
ARP
Transmission rate 100 MBit full duplex
Transmission process 100BASETX
Max. number of process data 10 process data
Connection technology RJ45 plug connector
Auto-negation Yes
GSD file GSDML-V1.0-SEW-DFE12B-xxxxxxxx.xml
(xxxxxxxx is a placeholder for year/month/day)
SEW manufacturer ID 010A
hex
Device ID 0001
hex
Alarms Diagnostic alarm in the event of a unit fault (can be activated)
Diagnostics Yes
Configuration via PROFINET In preparation
Max. number of connections 3
Tools for startup MOVITOOLS
MotionStudio software
DBG60B keypad
P
i
f
kVA
Hz
n
90 System Manual MOVIDRIVE MDX60B/61B Inverter
2
PROFINET IO RT type DFE32B fieldbus interface option
Technical Data and Dimension Sheets
2.28 PROFINET IO RT type DFE32B fieldbus interface option
Part number 1821 345 6
Description The MOVIDRIVE
via Ethernet-TCP/IP
Inverter diagnostics using a standard browser (e.g. Internet Explorer) via the
integrated Web server:
Transfer display values
DFE32B configuration (after login)
DFE32B option
11878AXX
Application protocol PROFINET IO (Ethernet frames with frame identification 8892
hex
) to con-
trol and set parameters for the inverter.
HTTP (Hypertext Transfer Protocol) for diagnostics using a Web browser.
SMLP (Simple Movilink Protocol), protocol used by MOVITOOLS
.
Port numbers used 300 (SMLP)
80 (HTTP)
Ethernet services ARP
ICMP (Ping)
ISO / OSI layer 2 Ethernet II
Baud rate 100 Mbaud in full duplex process
Connection technology Two RJ45 plug connectors with integrated switch and auto-crossing
Addressing 4 byte IP address or MAC-ID (00:0F:69:xx:xx:xx)
Manufacturer ID
(vendor ID)
010A
hex
Tools for startup MOVITOOLS
MDX61B
Firmware version 824 854 0.17 or higher ( display with P076)
P
i
f
kVA
Hz
n
System Manual MOVIDRIVE MDX60B/61B Inverter 91
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
DFE13B EtherNet/IP fieldbus interface option
Technical Data and Dimension Sheets
2.29 DFE13B EtherNet/IP fieldbus interface option
Part number 1820 565 8
Description The MOVIDRIVE
via Ethernet-TCP/IP
Inverter diagnostics using a standard browser (e.g. Internet Explorer) via the
integrated Web server:
Transfer display values
DFE13B configuration (after login)
Option DFE13B
11879AXX
Application protocols EtherNet/IP (Industrial Protocol) to control and set parameters for the drive
inverter.
HTTP (Hypertext Transfer Protocol) for diagnostics using a Web browser.
SMLP (Simple Movilink Protocol), protocol used by MOVITOOLS
.
DHCP (Dynamic Host Configuration Protocol) to assign address parameter
automatically.
Port numbers used 44818 (Ethernet/IP TCP)
2222 (EtherNet/IP UDP)
300 (SMLP)
80 (HTTP)
67 / 68 (DHCP)
Ethernet services ARP
ICMP (Ping)
Automatic baud rate detection 10 MBaud / 100 MBaud
Max. number of process data 10 process data
Connection technology RJ45 plug connector
Addressing 4 byte IP address
Manufacturer ID 013B
hex
Tools for startup MOVITOOLS
MotionStudio software
DBG60B keypad
P
i
f
kVA
Hz
n
92 System Manual MOVIDRIVE MDX60B/61B Inverter
2
DFE33B EtherNet/IP fieldbus interface option
Technical Data and Dimension Sheets
2.30 DFE33B EtherNet/IP fieldbus interface option
Part number 1821 346 4
Description The MOVIDRIVE
.
DHCP (Dynamic Host Configuration Protocol) to assign address parameter
automatically.
Port numbers used 44818 (EtherNet/IP TCP)
2222 (EtherNet/IP UDP)
300 (SMLP)
80 (HTTP)
67 / 68 (DHCP)
Ethernet services ARP
ICMP (Ping)
ISO / OSI layer 2 Ethernet II
Automatic baud rate detection 10 MBaud / 100 MBaud
Connection technology Two RJ45 plug connectors with integrated switch and auto-crossing
Addressing 4 byte IP address or MAC-ID (00-0F-69-xx-xx-xx)
Manufacturer ID
(vendor ID)
013B
hex
Tools for startup MOVITOOLS
MDX61B
Firmware version 824 854 0.17 or higher ( display with P076)
P
i
f
kVA
Hz
n
System Manual MOVIDRIVE MDX60B/61B Inverter 93
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
EtherCAT fieldbus interface option type DFE24B
Technical Data and Dimension Sheets
2.31 EtherCAT fieldbus interface option type DFE24B
Part number 1821 126 7
Description The MOVIDRIVE
MotionStudio software
DBG60B keypad
P
i
f
kVA
Hz
n
System Manual MOVIDRIVE MDX60B/61B Inverter 95
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
CANopen fieldbus interface option type DFC11B
Technical Data and Dimension Sheets
2.33 CANopen fieldbus interface option type DFC11B
Part number 824 317 4
Description The MOVIDRIVE
is made available. The DFC11B option enables communication with the machine control
for a maximum of 10 process data. You need an EDS file to be able to integrate the
DFC11B in the higher-level CANopen control. You can download this file from the SEW
homepage in the Software section.
Electronics data
Functions CAN Layer 2 and communication profile MOVILINK
or CANopen
Electrical isolation via optocoupler
DFC11B option
11883AXX
Communication profile SEW-MOVILINK
CANopen
CAN Layer 2
Number of process data words 1 ... 10 process data words
Baud rate Setting using parameter P894:
125 kBaud / 250 kBaud / 500 kBaud / 1 MBaud
Connection technology 9-pole Sub-D plug connector X30 (plug assigned to CIA standard) or
terminal X31
Permitted line cross section X31
(CAN-Bus connection)
One core per terminal: 0.20 ... 2.5 mm
2
(AWG24 ... 12)
Two cores per terminal: 0.25 ...1 mm
2
(AWG22 ... 17)
Terminating resistor 120 (set using DIP switch S1-R)
Addressing Setting via parameter P891 (SBus MOVILINK) or P896 (CANopen)
Tools for startup MOVITOOLS
MotioStudio software
DBG60B keypad
NOTE
If electrical isolation is not required, the CAN-Bus can be connected directly to the basic
unit at X12:SC11/SC12 without the DFC11B option. This does not effect the
functionality.
P
i
f
kVA
Hz
n
96 System Manual MOVIDRIVE MDX60B/61B Inverter
2
Synchronous operation board option type DRS11B
Technical Data and Dimension Sheets
2.34 Synchronous operation board option type DRS11B
Part number 824 672 6
Description The DRS11B option enables a group of motors to run in angular synchronous operation
or in an adjustable proportional relationship. For detailed information, refer to the "Syn-
chronous Operation Board Type DRS11B" manual, which can be ordered from SEW-
EURODRIVE. The basis for synchronous operation is the continuous comparison of the
rotor angle positions of the master and slave motors. The motors must be equipped with
encoders. The DRS11B option is plugged into the expansion slot.
Option DRS11B
11885AXX
Binary inputs X40:1...X40:6
Internal resistance
EING...EING5: isolated (opto-coupler)
PLC compatible (EN 61131)
R
i
3 k, I
E
DC 10 mA
Sampling interval 5 ms
Signal level
DC+13 V...+30 V= "1" = Contact closed
DC3 V...+5 V = "0" = Contact open
Function Fixed assignment with:
EING = Free-running
INP1 = Offset 1
INP2 = Offset 2
INP3 = Offset 3
INP4 = IPOS
plus
variable H477.0
INP5 = IPOS
plus
variable H477.1
Binary outputs X40:9/X40:10 OUTP/OUTP1: PLC compatible (EN 61131-2)
Response time 5 ms
Signal level
"0" = DC 0 V "1" = DC+24 V
Caution: Do not apply external voltage!
Function
Fixed assignment with:
OUTP = IPOS
plus
variable H476.0
OUTP1 = IPOS
plus
variable H476.1
I
max
= DC 50 mA, short-circuit proof, protected against external voltage to
DC 30 V
Reference terminals X40:11
X40:7
Voltage output X40:8
DGND: Reference potential for binary signals
DCOM: Reference potential for binary inputs X40:1...X40:6 (INP...INP5)
VO24: Voltage output DC +24 V, max. DC 100 mA
Synchronous encoder input X41:
Encoder power supply
Max. 200 kHz, signal level according to RS422 or sin/cos
DC +24 V, I
max
= 650 mA
1)
9-pin D-sub socket
Master encoder input X42:
Encoder power supply
Max. 200 kHz, signal level according to RS422 or sin/cos
DC+24 V, I
max
= DC 650 mA
1)
9-pin D-sub socket
Encoder simulation output X43: Signal level to RS422
9-pin D-sub connector
Voltage input X44:1
X44:2
X44:3
GND
DC+24 V supply voltage for binary outputs X40:9/X40:10 and encoder
GND
Permitted line cross section
One core per terminal: 0.08 ... 1.5 mm
2
(AWG28 ... 16)
Two cores per terminal: 0.25 ... 1 mm
2
(AWG22 .. 17)
1) Total current load (X41 and X42) of the DC 24 V encoder supply DC 650 mA
P
i
f
kVA
Hz
n
System Manual MOVIDRIVE MDX60B/61B Inverter 97
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
PROFIBUS DP-V1 with PROFIsafe fieldbus interface option type DFS11B
Technical Data and Dimension Sheets
2.35 PROFIBUS DP-V1 with PROFIsafe fieldbus interface option type DFS11B
Part number 1820 962 9
Description MOVIDRIVE
MotionStudio software
DBG60B keypad
F address 1 ... 1022 DIP switch for setting the failsafe address
Ambient temperature 0 to 55 C
P
i
f
kVA
Hz
n
98 System Manual MOVIDRIVE MDX60B/61B Inverter
2
PROFIBUS DP-V1 with PROFIsafe fieldbus interface option type DFS11B
Technical Data and Dimension Sheets
Safety part
Safety characteristics
Highest possible safety category SIL 3 according to EN 61508
Category 4 according to EN 954-1
Performance level e according to EN ISO 13849-1
System structure 2 channels with diagnostics (1002D)
Type of operating mode "High demand" rate according to EN 61508
Probability of dangerous failure per
hour (PFH value)
<1.00E-09 (1 FIT)
Proof test interval (EN61508) 10 years, after which the component must be replaced with a new one
Repair time 100 hours
Safe status Value "0" for all safety-oriented F-DO process values (output disabled)
Safe output
P-M switch
(from load voltage supply)
DC 24 V output according to EN 61131-2, protected against short circuits and overloads
Rated current 1A
Leakage current (at "0" signal) Typically 2 mA (with 2 V / 1 k load resistance)
(Note: Current flows from F-DO_M to F-DO_P)
Internal voltage drop
(P and M output)
max. 3 V
Short circuit protection Electronic, response value: 2.8 A ... 9 A
Overload protection Response value: 1.4 A ... 1.6 A
Load resistance range 24 k ... 1 k
Voltage limitation when switching off
inductive loads
Typically 70 V
Response time (command via
PROFIsafe output switches)
25 ms
Maximum line length 30 m
P
i
f
kVA
Hz
n
System Manual MOVIDRIVE MDX60B/61B Inverter 99
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
PROFIBUS DP-V1 with PROFIsafe fieldbus interface option type DFS12B
Technical Data and Dimension Sheets
2.36 PROFIBUS DP-V1 with PROFIsafe fieldbus interface option type DFS12B
Part number 1820 963 7 (in preparation)
Description MOVIDRIVE
are
available from the SEW homepage (http://www.sew-eurodrive.de) under "Software" to
help with project planning and facilitate startup.
For more detailed information, refer to the "Fieldbus Interface DFS12B PROFIBUS DP-
V1 with PROFIsafe" manual. You can order this manual from SEW-EURODRIVE.
Electronics data
DFS12B option
11893AXX
PROFIBUS protocol options PROFIBUS DP and DP-V1 according to IEC 61158
Automatic baud rate detection 9.6 kBaud ... 12 MBaud
Connection technology 9-pin D-sub socket
Pin assignment acc. to IEC 61158
Bus terminator Not integrated, implement using suitable PROFIBUS plug with terminating
resistors that can be switched on.
Station address 1 ... 125, adjustable via DIP switches
GSD file name SEW_600C.GSD
DP ID number 600C = 24588
hex
Diagnostics data Max. 8 bytes
Standard diagnostics: 6 bytes
Tools for startup MOVITOOLS
MotionStudio software
DBG60B keypad
F address The failsafe address is set using the DCS21B option
Ambient temperature 0 to 55 C
P
i
f
kVA
Hz
n
100 System Manual MOVIDRIVE MDX60B/61B Inverter
2
PROFINET IO with PROFIsafe fieldbus interface option, type DFS21B
Technical Data and Dimension Sheets
2.37 PROFINET IO with PROFIsafe fieldbus interface option, type DFS21B
Part number 1821 183 6
Description The MOVIDRIVE
.
Port numbers used 300 (SMLP)
80 (HTTP)
Ethernet services ARP
ICMP (Ping)
ISO / OSI layer 2 Ethernet II
Baud rate 100 Mbaud in full duplex process
Connection technology Two RJ45 plug connectors with integrated switch and auto-crossing
Addressing 4 byte IP address or MAC-ID (00:0F:69:xx:xx:xx)
Manufacturer ID
(vendor ID)
010A
hex
Tools for startup MOVITOOLS
MDX61B
Firmware version 824 854 0.17 or higher ( display with P076)
Ambient temperature 0 to 55 C
P
i
f
kVA
Hz
n
System Manual MOVIDRIVE MDX60B/61B Inverter 101
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
PROFINET IO with PROFIsafe fieldbus interface option, type DFS21B
Technical Data and Dimension Sheets
Safety part
Safety characteristics
Highest possible safety category SIL 3 according to EN 61508
Category 4 according to EN 954-1
Performance level e according to EN ISO 13849-1
System structure 2 channels with diagnostics (1oo2D)
Type of operating mode "High demand" rate according to EN 61508
Probability of dangerous failure per
hour (PFH value)
<1.00E-09 (1 FIT)
Proof test interval (EN61508) 10 years, after which the component must be replaced with a new one
Repair time 100 hours
Safe status Value "0" for all safety-oriented F-DO process values (output disabled)
Safe output
P-M switch
(from load voltage supply)
DC 24 V output according to EN 61131-2, protected against short circuits and overloads
Rated current 1A
Leakage current (at "0" signal) Typically 2 mA (with 2 V / 1 k load resistance)
(Note: Current flows from F-DO_M to F-DO_P)
Internal voltage drop
(P and M output)
max. 3 V
Short circuit protection Electronic, response value: 2.8 A ... 9 A
Overload protection Response value: 1.4 A ... 1.6 A
Load resistance range 24 k ... 1 k
Voltage limitation when switching off
inductive loads
Typically 70 V
Response time (command via
PROFIsafe
output switches)
25 ms
Maximum line length 30 m
P
i
f
kVA
Hz
n
102 System Manual MOVIDRIVE MDX60B/61B Inverter
2
PROFINET IO with PROFIsafe fieldbus interface option, type DFS22B
Technical Data and Dimension Sheets
2.38 PROFINET IO with PROFIsafe fieldbus interface option, type DFS22B
Part number 1821 184 4
Description The MOVIDRIVE
software to
change parameters and IPOS
plus
programs. An integrated Web server makes it
possible for the user to access diagnostic values quickly and easily using a standard
browser (e.g. Internet Explorer).
For more detailed information, refer to the "Fieldbus Interface DFS22B PROFINET IO
with PROFIsafe" manual. You can order this manual from SEW-EURODRIVE.
Electronics data
DFS22B option
11895AXX
Application protocol PROFINET IO (Ethernet frames with frame identification 8892
hex
) to control and
set parameters for the inverter.
HTTP (Hypertext Transfer Protocol) for diagnostics using a Web browser.
SMLP (Simple Movilink Protocol), protocol used by MOVITOOLS
.
Port numbers used 300 (SMLP)
80 (HTTP)
Ethernet services ARP
ICMP (Ping)
ISO / OSI layer 2 Ethernet II
Baud rate 100 Mbaud in full duplex process
Connection technology Two RJ45 plug connectors with integrated switch and auto-crossing
Addressing 4 byte IP address or MAC-ID (00:0F:69:xx:xx:xx)
Manufacturer ID
(vendor ID)
010A
hex
Tools for startup MOVITOOLS
MDX61B
Firmware version 824 854 0.17 or higher ( display with P076)
Ambient temperature 0 ... 55 C
P
i
f
kVA
Hz
n
System Manual MOVIDRIVE MDX60B/61B Inverter 103
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
MOVISAFE DCS21B/31B safety module option
Technical Data and Dimension Sheets
2.39 MOVISAFE
B/compact, MOVITRAC
07/B, MOVIAXIS
, MOVIMOT
).
Electronics data
Part number MOVI-PLC
basic DHP11B..
unit version
Description
1820 472 4 DHP11B-T0 MOVI-PLC
basic controller
1820 822 3 DHP11B-T1 Application version I (in addition to version T0, enables
additional functions including electronic cam and
synchronous operation)
1820 823 1 DHP11B-T2 Application version II (in addition to version T1, enables
additional functions including handling)
MOVI-PLC
protocol
Baud rate: 125 kBaud ... 1 MBaud
External bus terminator
Address range: 0 ... 127
Engineering Via RS485, PROFIBUS and the system buses
Panel operation Via RS485 and CAN 2 (in preparation)
Connection technology PROFIBUS: 9-pin Sub-D connector to IEC61158
System buses and I/Os: plug-in terminals
RS485: RJ10
Binary inputs / outputs 8 I/Os to IEC 61131-2; can be configured as inputs or outputs. Five are interrupt-
capable
Memory Program: 512 kByte
Data: 128 kByte
Retain: 24 kByte
Tools for startup MOVITOOLS
basic
DHP11B.. in terminal design or as an engineering interface. Only use option OST11B in
conjunction with MOVI-PLC
basic DHP11B...
When the MOVI-PLC
basic DHP11B...
Electronics data
OST11B option
11887AXX
RS485 interface COM2
X35:1 ... X35:4
X36:1 ... X36:3
For connection of an Engineering PC, a DOP11A/B operator terminal or a gear-
motor with integrated frequency inverter MOVIMOT
I/O standard, 57.6 kBaud, max. total cable length 200 m, integrated dynamic
terminating resistor permanently installed
Potential level COM2 is isolated from the MOVI-PLC
B and
MOVITRAC
servo inverters
compact controller MOVI-PLC
advanced DHE41B/UOH11B or
DHF41B/UOH21B prepared for installation on a DIN rail. As a compact controller, it
is designed for controlling inverters.
Description MOVI-PLC
advanced DH.41B
Fieldbus interfaces
1821 160 7 DHE41B Ethernet TCP/IP, UDP
1821 161 5 DHF41B Ethernet TCP/IP, UDP, PROFIBUS DP-V1
P
i
f
kVA
Hz
n
108 System Manual MOVIDRIVE MDX60B/61B Inverter
2
MOVI-PLC advanced controller option DH.41B
Technical Data and Dimension Sheets
Electronics data for DHE41B
MOVI-PLC
MDX61B:
Power consumption: P
max
= 6.8 W
The MOVI-PLC
MDX61B
via backplane connector.
In the case of disconnection from the power supply, continued function is guaranteed by
DC 24 backup (external DC 24 V supply to X10:9/10 of MOVIDRIVE
MDX61B
required).
Installed in the MOVIAXIS
switched mode power supply module (MXS) or from an external voltage supply. For this
purpose, connect X5 between the individual devices.
If the MOVI-PLC
advanced DHE41B.. controller is maintained after disconnection from the line voltage
(external DC 24 V supply at X16 of the MOVIAXIS
protocol.
System bus CAN 1
X33:1 ... X33:3
Ethernet 1 X36 System bus, reserved
Ethernet 2 X37 TCP/IP
Connection options: Engineering PC, other controller, Intranet
USB USB 1.0 for connecting an engineering PC (in preparation)
RS485 Interface
COM1/2
X34:1 ... X34:4
For connection of an engineering PC, a DOP11A/B operator terminal or a MOVIMOT
gearmotor with integrated frequency inverter
I/O standard, 57.6 / 9.6 kBaud, max. cable length 200 m
Dynamic terminating resistor with fixed installation
SD memory card PC readable
Includes:
Firmware
IEC program
Data
At least 128 MB memory
Designs, part numbers, and functions:
OMH41B-T0: 1821 204 2
Functions: Handling of speed control, positioning, e.g. with the MPLCMotion_MDX
library
OMH41B-T1: 1821 205 0
Functions: Additional: cam disk, electronic gear, cam controller, for example
OMH41B-T2: 1821 206 9
Functions: Additional: material handling, for example
Engineering Engineering takes place via one of the following interfaces:
Ethernet 2 (X37)
In preparation: USB (X35)
The engineering of all SEW components connected to the MOVI-PLC
advanced DHE41B
controller can be carried out using the MOVI-PLC
inverters.
Take account of a power reduction of 4 % per 10 K from an ambient temperature of
40 C. Do not exceed a maximum ambient temperature of 80 C.
PTC resistor
BW090-P52B
Direct installation on MOVIDRIVE
MDX60B")
The MOVIDRIVE
inverters.
P
i
f
kVA
Hz
n
112 System Manual MOVIDRIVE MDX60B/61B Inverter
2
Braking resistor type BW... option / BW...-T / BW...-P
Technical Data and Dimension Sheets
Parallel
connection
Two braking resistors with the same value must be connected in parallel for some
inverter/resistor combinations. In this case, the trip current must be set on the bimetallic
relay to twice the value of I
F
entered in the table. For the BW...-T BW...-P braking
resistors, the temperature switch/overcurrent relay must be connected in series.
Assignment to AC 400/500 V units (...-5_3)
Braking resistor type BW...
BW090-
P52B
BW100-
005
BW100-006
BW072-
003
BW072-
005
BW168 BW268
Part number 824 563 0 826 269 1 821 701 7 826 058 3 826 060 5 820 604 X 820 715 1
Braking resistor type BW...-T BW100-006-T BW168-T BW268-T
Part number 1820 419 8 1820 133 4 1820 417 1
Continuous braking power
(= 100% cdf)
Load capacity 50 % cdf
1)
at 25 % cdf
12 % cdf
6 % cdf
1) cdf = Cyclic duration factor of the braking resistor in relation to a cycle duration T
D
120 s.
0.10 kW
0.15 kW
0.2 kW
0.4 kW
0.7 kW
0.45 kW
0.60 kW
0.83 kW
1.11 kW
2.00 kW
0.6 kW
1.1 kW
1.9 kW
3.6 kW
5.7 kW
0.23 kW
0.31 kW
0.42 kW
0.58 kW
1.00 kW
0.45 kW
0.60 kW
0.83 kW
1.11 kW
2.00 kW
0.8 kW
1.4 kW
2.6 kW
4.8 kW
7.6 kW
1.2 kW
2.2 kW
3.8 kW
7.2 kW
11 kW
Observe regenerative power limit of the inverter!
(= 150 % of the recommended motor power technical data)
Resistance value R
BW
90 35 % 100 10 % 72 10 % 68 10 %
Trip current (of F16) I
F
- 0.8 A
RMS
2.4 A
RMS
0.6 A
RMS
1 A
RMS
3.4 A
RMS
4.2 A
RMS
Design PTC Flat-design
Wire resistor
on ceramic
core
Flat-design
Wire resistor on ceramic
core
Connections /
Tightening torque
Cable Cable
Ceramic termi-
nals 2.5 mm
2
(AWG13)
0.5 Nm
Cable
Ceramic terminals 2.5
mm
2
(AWG13)
0.5 Nm
Degree of protection IP20 IP54
IP20 (when
installed)
IP54 IP20 (when installed)
Ambient temperature
U
20 ... +40 C
Type of cooling KS = Self-cooling
For MOVIDRIVE
(recommended)
0005 ...
0014
0005 ...
0022
0015 ... 0040 0005 ... 0014
0005 ...
0040
0015 ...
0040
P
i
f
kVA
Hz
n
System Manual MOVIDRIVE MDX60B/61B Inverter 113
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
Braking resistor type BW... option / BW...-T / BW...-P
Technical Data and Dimension Sheets
Braking resistor type BW... BW147 BW247 BW347 BW039-012
Part number 820 713 5 820 714 3 820 798 4 821 689 4
Braking resistor type BW...-T BW147-T BW247-T BW347-T BW039-012-T BW039-026-T BW039-050-T
Part number 1820 134 2 1820 084 2 1820 135 0 1820 136 9 1820 415 5 1820 137 7
Continuous braking power
(= 100% cdf)
Load capacity 50 % cdf
1)
at 25 % cdf
12 % cdf
6 % cdf
1.2 kW
2.2 kW
3.8 kW
7.2 kW
11 kW
2.0 kW
3.6 kW
6.4 kW
12 kW
19 kW
4.0 kW
7.2 kW
12.8 kW
20 kW
2)
20 kW
2)
1.2 kW
2.1 kW
3.8 kW
7.2 kW
11.4 kW
2.6 kW
4.7 kW
8.3 kW
15.6 kW
24.0 kW
2)
5.0 kW
8.5 kW
15.0 kW
24.0 kW
2)
24.0 kW
2)
Observe regenerative power limit of the inverter!
(= 150 % of the recommended motor power technical data)
Resistance value R
BW
47 10 % 39 10 %
Trip current (of F16) I
F
5 A
RMS
6.5 A
RMS
9.2 A
RMS
5.5 A
RMS
8.1 A
RMS
11.3 A
RMS
Design Wire resistor on ceramic core Grid resistor
Connections /
tightening torque
Ceramic terminals 2.5 mm
2
(AWG13) / 0.5 Nm
BW347-T: Ceramic terminals 10 mm
2
(AWG18) / 1.6 Nm
M8 stud /
6 Nm
Degree of protection IP20 (when installed)
Ambient temperature
U
20 ... +40 C
Type of cooling KS = Self-cooling
For MOVIDRIVE
(recommended) 0300
0370...0750 and 2 parallel with
0900/1100/1320
2)
1) cdf = Cyclic duration factor of the braking resistor in relation to a cycle duration T
D
120 s.
2) When connected in parallel, the load capacity and trip current are doubled.
P
i
f
kVA
Hz
n
System Manual MOVIDRIVE MDX60B/61B Inverter 115
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
Braking resistor type BW... option / BW...-T / BW...-P
Technical Data and Dimension Sheets
Assignment to AC 230 V units (...-2_3)
Technical data of
the braking resis-
tor BW...-T /
BW...-P
Braking resistor type BW... BW039-
003
BW039-
006
BW039-
012
BW027-
006
BW027-
012
Part number 821 687 8 821 688 6 821 689 4 822 422 6 822 423 4
Braking resistor type BW...-T BW039-
012-T
BW039-
026-T
BW018-
015-P
BW018-
035-T
Part number 1820 136 9 1820 415 5 1820 416 3 1820 138 5
Continuous braking power
(= 100% cdf)
Load capacity 50 % cdf
1)
at 25 % cdf
12 % cdf
6 % cdf
1) cdf = Cyclic duration factor of the braking resistor in relation to a cycle duration T
D
120 s.
0.3 kW
0.5 kW
1.0 kW
1.8 kW
2.8 kW
0.6 kW
1.1 kW
1.9 kW
3.6 kW
5.7 kW
1.2 kW
2.1 kW
3.8 kW
6.0 kW
2)
6.0 kW
2)
2) Physical power limit due to DC link voltage and resistance value.
2.6 kW
4.6 kW
6.0 kW
2)
6.0 kW
2)
6.0 kW
2)
0.6 kW
1.1 kW
1.9 kW
3.6 kW
5.7 kW
1.2 kW
2.1 kW
3.8 kW
7.2 kW
8.7 kW
2)
1.5 kW
2.5 kW
4.5 kW
6.7 kW
11.4 kW
3.5 kW
5.9 kW
10.5 kW
13.0 kW
2)
13.0 kW
2)
Observe regenerative power limit of the inverter!
(= 150 % of the recommended motor power technical data)
Resistance value R
BW
39 10 % 27 10 % 18 10 %
Trip current (of F16) I
F
2.7 A
RMS
3.9 A
RMS
5.5 A
RMS
8.1 A
RMS
4.7 A
RMS
6.6 A
RMS
9.1 A
RMS
13.9 A
RMS
Design Wire resistor Grid resistor
Connections /
tightening torque
Ceramic terminals 2.5 mm
2
(AWG12) /
0.5 Nm
M8 stud /
6 Nm
Degree of protection IP20 (when installed)
Ambient temperature
U
20 ... +40 C
Type of cooling KS = Self-cooling
For MOVIDRIVE
inverters.
Dimension
drawings for ND...
Line choke type ND020-013 ND030-023
1)
ND045-013 ND085-013 ND150-013 ND200-
0033
ND300-0053
Part number 826 012 5 827 151 8 826 013 3 826 014 1 825 548 2 826 579 8 827 721 4
Rated power supply
voltage V
supply
(according to EN 50160)
3 AC 380 V - 500 V, 50/60 Hz
Rated current
2)
I
N
AC 20 A AC 30 A AC 45 A AC 85 A AC 150 A AC 200 A AC 300 A
Power loss at bei I
N
P
V
10 W 30 W 15 W 25 W 65 W 100 W 280 W
Inductance L
N
0.1 mH 0.2 mH 0.1 mH 0.1 mH 0.1 mH 0.03 mH 0.05 mH
Ambient temperature
U
25 ... +45 C
Degree of protection IP 00 (EN 60529)
Connections
Terminal strips
4 mm
2
(AWG12)
Terminal strips
2.5 mm
2
... 10 mm
2
(AWG13 ... AWG8)
Terminal
strips
10 mm
2
(AWG8)
Terminal strips
35 mm
2
(AWG2)
M10 stud
PE: M8 stud
M12 stud
PE: 2 M10
Tightening torque 0.6 ... 0.8 Nm max. 2.5 Nm 3.2 ... 3.7 Nm M10 stud: 10 Nm
PE: 6 Nm
M12 stud:
15.5 Nm
PE: 10 Nm
Assignment to AC 400/500 V units (MDX60/61B...-5_3)
Rated operation (100 %) 0005...0075 0110...0220
0300...0450
and
MDR60A0370
0550/0750
MDR60A
0750
0900...1320
Increased power (125 %) 0005...0075 0110/0150 0220...0370 0450...0750
Assignment to 230 V units (MDX61B...-2_3)
Rated operation (100 %) 0015...0055 - 0075/0110 0150/0220 0300 - -
Increased power (125 %) 0015...0037 - 0055/0075 0110/0150 0220/0300 - -
1) Use ND030-023 for DC link connection without regenerative power supply unit in connection type A or B (see system manual
MOVIDRIVE
is connected to a line choke, the total value of the rated currents of the connected units must not
exceed the rated current of the line choke!
58699AXX
Figure 28: Dimension drawing for line chokes ND020.. / ND030.. / ND045.. / ND085..
[1] Space for installation terminals Input: 1U1, 1V1, 1W1
Any mounting position Output: 1U2, 1V2, 1W2
a
c
c
C
A
[1]
[1]
1U1 1U2 1V1 1V2 1W1 1W2
B
b
P
i
f
kVA
Hz
n
120 System Manual MOVIDRIVE MDX60B/61B Inverter
2
Line choke option type ND..
Technical Data and Dimension Sheets
58315AXX
Figure 29: Dimension drawing for line chokes ND150.. / ND200.. / ND300..
B
a
c c
b
C
A
Line choke
type
Main dimensions mm (in) Mounting dimensions mm (in)
Hole dimension
mm (in)
Weight
A B C a b c kg (lb)
ND020-013 85 (3.3) 60 (2.4) 120 (4.72) 50 (2) 31 - 42 (1.2 - 1.7) 5 - 10 (0.2 - 0.39) 0.5 (1)
ND030-023
ND045-013
125 (4.92) 95 (3.7) 170 (6.69) 84 (3.3) 55-75 (2.2 - 3) 6 (0.24) 2.5 (5.5)
ND085-013 185 (7.28) 115 (4.53) 235 (9.25) 136 (5.35) 56 - 88 (2.2 - 3.5) 7 (0.28) 8 (18)
ND150-013 255 (10) 140 (5.51) 230 (9.06) 170 (6.69) 77 (3) 8 (0.31) 17 (37)
ND200-0033 250 (9.84) 160 (6.3) 230 (9.06) 180 (7.09) 98 (3.9) 8 (0.31) 15 (33)
ND300-0053 300 (11.8) 190 (7.48) 295 (11.6) 255 (10) 145 (5.71) 11 (0.43) 35 (77)
P
i
f
kVA
Hz
n
System Manual MOVIDRIVE MDX60B/61B Inverter 121
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
Line filter type NF...-... option
Technical Data and Dimension Sheets
2.45 Line filter type NF...-... option
To suppress interference emission on the line side of inverters.
Do not switch between the NF... line filter and MOVIDRIVE
.
NF.. line filters have cRUus approval independent of the MOVIDRIVE
inverters.
Line filter type NF009-503 NF014-503 NF018-503 NF035-503 NF048-503
Part number 827 412 6 827 116 X 827 413 4 827 128 3 827 117 8
Rated mains voltage V
N
(according to EN 50160)
3 AC 380 V - 500 V, 50/60 Hz
Rated current I
N
AC 9 A AC 14 A AC 18 A AC 35 A AC 48 A
Power loss at bei I
N
P
V
6 W 9 W 12 W 15 W 22 W
Earth-leakage current at V
N
< 25 mA < 25 mA < 25 mA < 25 mA < 40 mA
Ambient temperature
U
25 ... +40 C
Degree of protection IP20 (EN 60529)
Connections L1-L3/L1-L3
Tightening torque L1-L3/L1-L3
Connection PE
Tightening torque PE
4 mm
2
(AWG 10)
0.8 Nm
M5 stud
3.4 Nm
10 mm
2
(AWG 8)
1.8 Nm
M5 stud
3.4 Nm
10 mm
2
(AWG 8)
1.8 Nm
M6 stud
5.5 Nm
Assignment to AC 400/500 V units (MDX60/61B...-5_3)
Rated operation (100 %) 0005...0040 0055/0075 - 0110/0150 0220
Increased power (125 %) 0005...0030 0040/0055 0075 0110 0150
Assignment to 230 V units (MDX61B...-2_3)
Rated operation (100 %) 0015/0022 0037 - 0055/0075 0110
Increased power (125 %) 0015 0022 0037 0055/0075 -
Line filter type NF063-503 NF085-503 NF115-503 NF150-503 NF210-503 NF300-503
Part number 827 414 2 827 415 0 827 416 9 827 417 7 827 418 5 827 419 3
Rated mains voltage V
N
(according to EN 50160)
3 AC 380 V - 500 V, 50/60 Hz
Rated current I
N
AC 63 A AC 85 A AC 115 A AC 150 A AC 210 A AC 300 A
Power loss at I
N
P
V
30 W 35 W 60 W 90 W 150 W 180 W
Earth-leakage current at V
N
< 30 mA < 30 mA < 30 mA < 30 mA < 40 mA < 45 mA
Ambient temperature
U
25 ... +40 C
Degree of protection IP20 (EN 60529)
Connections L1-L3/L1-L3
Tightening torque L1-L3/L1-L3
Connection PE
Tightening torque PE
16 mm
2
(AWG 6)
3 Nm
M6
5.5 Nm
35 mm
2
(AWG 2)
3.7 Nm
M8
12.8 Nm
50 mm
2
(AWG1/0)
3.7 Nm
M10
23.8 Nm
50 mm
2
(AWG1/0)
3.7 Nm
M10
23.8 Nm
95 mm
2
(AWG4/0)
20 Nm
M10
23.8 Nm
150 mm
2
(AWG300-2)
30 Nm
M12
36 Nm
Assignment to AC 400/500 V units (MDX60/61B...-5_3)
Rated operation (100 %) 0300 0370/0450 0550 0750 0900/1100 1320
Increased power (125 %) 0220 0300/0370 0450 0550/0750 0900 1100/1320
Assignment to 230 V units (MDX61B...-2_3)
Rated operation (100 %) 0150 0220 0300 - - -
Increased power (125 %) 0110/0150 - 0220/0300 - - -
P
i
f
kVA
Hz
n
122 System Manual MOVIDRIVE MDX60B/61B Inverter
2
Line filter type NF...-... option
Technical Data and Dimension Sheets
Dimension draw-
ing for NF...
Any mounting position
55862ADE
Figure 30: Dimension drawing for NF line filter
A
C
a
B
b
C
L3 L2 L1
L3' L2' L1'
Ausgang
Eingang
Line filter
type
Main dimensions mm (in)
Mounting dimensions mm
(in)
Hole dimension
mm (in)
PE
connection
Weight
A B C a b c kg (lb)
NF009-503
55 (2.2)
195 (7.68)
80 (3.1) 20 (0.78)
180 (7.09)
5.5 (0.22)
M5
0.8 (2)
NF014-503 225 (8.86) 210 (8.27) 0.9 (2)
NF018-503 50 (1.97) 255 (10) 240 (9.45) 1.1 (2.4)
NF035-503
60 (2.36)
275 (10.8)
100 (3.94)
30 (1.18)
255 (10) 1.7 (3.7)
NF048-503 315 (12.4) 295 (11.6)
M6
2.1 (4.6)
NF063-503
90 (3.54)
260 (10.2)
60 (2.36)
235 (9.25)
6.5 (0.26)
2.4 (5.3)
NF085-503 320 (12.6) 140 (5.51)
255 (10)
M8 3.5 (7.7)
NF115-503
100 (3.94) 330 (13) 155 (6.1) 65 (2.56)
M10
4.8 (11)
NF150-503 5.6 (12.3)
NF210-503 140 (5.51) 450 (17.7) 190 (7.48) 102 (4.02) 365 (14.4) 8.9 (20)
NF300-503 170 (6.69) 540 (21.3) 230 (9.06) 125 (4.92) 435 (17.1) M12 12.2 (26.9)
P
i
f
kVA
Hz
n
System Manual MOVIDRIVE MDX60B/61B Inverter 123
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
HD... output choke option
Technical Data and Dimension Sheets
2.46 HD... output choke option
For suppression of interference from the unshielded motor cable. For HD001 to
HD003 we recommend routing the motor cable through the output choke with 5
loops. Only 5 loops are possible if the cable has a large diameter. To make up for
this, 2 or 3 output chokes should be connected in series. Connect in series two output
chokes in case of 4 windings and three output chokes in case of 3 windings.
Output chokes HD001 to HD003 are allocated using the cable cross sections of the
motor feeders. Consequently, there is no separate assignment table for the
AC 230 V units.
The HD004 output choke is assigned to size 6 units (0900... 1320).
Dimension
drawing for HD
Output choke type HD001
1)
HD002
1)
HD003 output
choke
1)
HD004
2)
Part number 813 325 5 813 557 6 813 558 4 816 885 7
Max. power loss P
Vmax
15 W 8 W 30 W 100 W
For cable cross
sections/connections/
tightening torque
1.5...16 mm
2
(AWG 16...6) 1.5 mm
2
(AWG 16) 16 mm
2
(AWG 6)
M12 terminal stud
20 Nm
Degree of protection - - - IP10
1) The output choke type HD... is not a UL/cUL-relevant component.
2) UL/cUL approval is not available for the HD0044 output choke
58419AXX
d
a
b c
C
A
B
HD001
HD002
HD003
P
i
f
kVA
Hz
n
124 System Manual MOVIDRIVE MDX60B/61B Inverter
2
HD... output choke option
Technical Data and Dimension Sheets
58424AXX
MOVIDRIVE
B
120
150
370
400
3
5
9
1
9
6
9
2
M
~
HD004
Output
choke type
Main dimensions mm (in)
Mounting dimensions mm
(in)
Inside mm (in)
Hole dimen-
sion mm (in)
Weight
A B C a b d c kg (lb)
HD001 121 (4.76) 64 (2.5) 131 (5.16) 80 (3.1) 50 (2.0) 50 (2.0)
5.8 (0.23)
0.5 (1)
HD002 66 (2.6) 49 (1.9) 73 (2.9) 44 (1.7) 38 (1.5) 23 (0.91) 0.2 (0.4)
HD003 170 (6.69) 64 (2.5) 185 (7.28) 120 (4.72) 50 (2.0) 88 (3.5) 7.0 (0.28) 1.1 (2.4)
HD004 150 (5.91) 400 (15.7) 360 (14.2) 120 (4.72) 370 (14.6) - 9.0 (0.35) 12.5 (27.6)
P
i
f
kVA
Hz
n
System Manual MOVIDRIVE MDX60B/61B Inverter 125
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
Output filter option type HF...
Technical Data and Dimension Sheets
2.47 Output filter option type HF...
HF... output filters are sine filters used to smooth output voltage from inverters. HF...
output filters (with the exception of HF450-503) are approved to UL/cUL in combination
with MOVIDRIVE
MDX60/61B system manual, section "Project Planning/Connecting the optional power components."
4) Connect two HF... output filters together in parallel for operation with these MOVIDRIVE
units.
P
i
f
kVA
Hz
n
System Manual MOVIDRIVE MDX60B/61B Inverter 127
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
Output filter option type HF...
Technical Data and Dimension Sheets
Dimension drawings for HF...-503 output filters
HF008 / 015 / 022 / 030-503 HF040/055/075-503
58418AXX
Figure 31: Dimension drawings for output filters HF008...075-503
Only the mounting position shown in the dimension drawing is permitted.
Output filter type
Main dimensions mm (in)
Mounting dimensions
mm (in)
Hole dimen-
sion mm (in)
Ventilation clearances
1)
mm (in)
1) There is no need for clearance at the sides. You can line up the units next to one another.
A B C a b c Top Bottom
HF008/015/022/030-503 80 (3.1) 286 (11.3) 176 (6.93) - 265 (10.4)
7 (0.3) 100 (3.94) 100 (3.94)
HF040/055/075-503 135 (5.31) 296 (11.7) 216 (8.5) 70 (2.8) 283 (11.1)
HF450-503
58417AXX
Figure 32: Dimension drawing for output filter HF450-503
Only the mounting position shown in the dimension drawing is permitted
Output filter
type
Main dimensions mm (in)
Mounting dimensions
mm (in)
Hole dimen-
sion mm (in)
Ventilation clearances
mm (in)
A B C a b c Top Bottom
HF450-503 465 (18.3) 385 (15.2) 240 (9.45) 436 (17.2) 220 (8.66) 8.5 (0.33) 100 (3.94) 100 (3.94)
b b
c a c
C C A A
B B
MOVIDRIVE
MOVIDRIVE
W1
W2
V1
V2
V5
U1
4 5 6 8
U2
MOVIDRIVE
M
~
1
1
1
a
b
B
c
A C
4 5 6 7 U V W
P
i
f
kVA
Hz
n
128 System Manual MOVIDRIVE MDX60B/61B Inverter
2
Output filter option type HF...
Technical Data and Dimension Sheets
Dimension drawing for HF...-403 output filter
58996AXX
Figure 33: Dimension drawing for HF...-403 output filter
Type
Main dimensions mm (in)
Mounting dimensions mm (in)
Hole
dimen-
sion mm
(in)
Ventilation clearances
mm (in)
Standard mounting
position
Horizontal
mounting
position
A B C/C1 a b a1 a2 c
At the
side
Top
Bot-
tom
HF023-403
145
(5.71)
284
(11.2)
365/390
(14.4/15.4)
268
(10.6)
60 (2.4)
210
(8.27)
334
(13.1)
6.5 (0.26)
je 30
(1.2)
150
(5.91)
150
(5.91)
HF033-403
HF047-403
190
(7.48)
300
(11.8)
385/400
(15.2/15.7)
284
(11.2)
80 (3.1)
b
c
a
4
5
6
7
U
V
W
b1
a
1
c
B
A C
C1
P
i
f
kVA
Hz
n
System Manual MOVIDRIVE MDX60B/61B Inverter 129
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
Prefabricated cables
Technical Data and Dimension Sheets
2.48 Prefabricated cables
Overview SEW offers cable sets and prefabricated cables for straightforward and error-free
connection of various system components to MOVIDRIVE
0015...0110 0150...0370 0450...0750 0900...1320
P
i
f
kVA
Hz
n
130 System Manual MOVIDRIVE MDX60B/61B Inverter
2
Prefabricated cables
Technical Data and Dimension Sheets
2. Prefabricated cables and extension cables for connecting CM motors to MDX
Motor cables The cables are equipped with a connector for motor connection and conductor end
sleeves for inverter connection.
Extension cables The cables are equipped with a connector and adapter for extending the CM motor
cable.
Number of cores and line cross section Part number Installation type for motor
41.5 mm
2
199 179 5
Fixed installation
CM..SM51
41.5 mm
2
+ 31.0 mm
2
199 189 2 CM..BR SB51
42.5 mm
2
199 181 7 CM..SM52
42.5 mm
2
+ 31.0 mm
2
199 191 4 CM..BR SB52
44 mm
2
199 183 3 CM..SM54
44 mm
2
+ 31.0 mm
2
199 193 0 CM..BR SB54
46 mm
2
199 185 X CM..SM56
46 mm
2
+ 31.5 mm
2
199 195 7 CM..BR SB56
410 mm
2
199 187 6 CM..SM59
410 mm
2
+ 31.5 mm
2
199 197 3 CM..BR SB59
Number of cores and line cross section Part number Installation type for motor
41.5 mm
2
1 333 114 0
Cable carrier installation
CM..SM51
41.5 mm
2
+ 31.0 mm
2
1 333 116 7 CM..BR SB51
42.5 mm
2
1 333 115 9 CM..SM52
42.5 mm
2
+ 31.0 mm
2
1 333 117 5 CM..BR SB52
44 mm
2
199 184 1 CM..SM54
44 mm
2
+ 31.0 mm
2
199 194 9 CM..BR SB54
46 mm
2
199 186 8 CM..SM56
46 mm
2
+ 31.5 mm
2
199 196 5 CM..BR SB56
410 mm
2
199 188 4 CM..SM59
410 mm
2
+ 31.5 mm
2
199 198 1 CM..BR SB59
Number of cores and line cross section Part number Installation type for motor
41.5 mm
2
199 549 9
Fixed installation
CM..SM51
41.5 mm
2
+ 31.0 mm
2
199 199 X CM..BR SB51
42.5 mm
2
199 551 0 CM..SM52
42.5 mm
2
+ 31.0 mm
2
199 201 5 CM..BR SB52
44 mm
2
199 553 7 CM..SM54
44 mm
2
+ 31.0 mm
2
199 203 1 CM..BR SB54
46 mm
2
199 555 3 CM..SM56
46 mm
2
+ 31.5 mm
2
199 205 8 CM..BR SB56
410 mm
2
199 557 X CM..SM59
410 mm
2
+ 31.5 mm
2
199 207 4 CM..BR SB59
P
i
f
kVA
Hz
n
System Manual MOVIDRIVE MDX60B/61B Inverter 131
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
Prefabricated cables
Technical Data and Dimension Sheets
3. Prefabricated cables and extension cables for connecting DS/CMD/CMP motors
Motor cables The cables are equipped with a connector for motor connection and conductor end
sleeves for inverter connection.
Extension cables The cables are equipped with a connector and adapter for extending the motor cable.
Number of cores and line cross section Part number Installation type for motor
41.5 mm
2
1 333 118 3
Cable carrier installation
CM..SM51
41.5 mm
2
+ 31.0 mm
2
1 333 120 5 CM..BR SB51
42.5 mm
2
1 333 119 1 CM..SM52
42.5 mm
2
+ 31.0 mm
2
1 333 121 3 CM..BR SB52
44 mm
2
199 554 5 CM..SM54
44 mm
2
+ 31.0 mm
2
199 204 X CM..BR SB54
46 mm
2
199 556 1 CM..SM56
46 mm
2
+ 31.5 mm
2
199 206 6 CM..BR SB56
410 mm
2
199 558 8 CM..SM59
410 mm
2
+ 31.5 mm
2
199 208 2 CM..BR SB59
Number of cores and line cross section Part number Installation type for motor
41.5 mm
2
590 454 4
Fixed installation
DS56 / CMD.. / CMP.. SM11
41.5 mm
2
+ 21 mm
2
1 332 485 3 DS56..B / CMD..BP / CMP..BP SB11
42.5 mm
2
590 455 2 DS56 / CMD.. / CMP.. SM12
42.5 mm
2
+ 21 mm
2
1 333 213 9 DS56..B / CMD..BP / CMP..BP SB12
44 mm
2
590 456 0 DS56 / CMD.. / CMP.. SM14
44 mm
2
+ 21 mm
2
1 333 214 7 DS56..B / CMD..BP / CMP..BP SB14
Number of cores and line cross section Part number Installation type for motor
41.5 mm
2
590 624 5
Cable carrier installation
DS56 / CMD.. / CMP.. SM11
41.5 mm
2
+ 21 mm
2
1 333 122 1 DS56..B / CMD..BP / CMP..BP SB11
42.5 mm
2
590 625 3 DS56 / CMD.. / CMP.. SM12
42.5 mm
2
+ 21 mm
2
1 333 215 5 DS56..B / CMD..BP / CMP..BP SB12
44 mm
2
590 480 3 DS56 / CMD.. / CMP.. SM14
44 mm
2
+ 21 mm
2
1 333 216 3 DS56..B / CMD..BP / CMP..BP SB14
Number of cores and line cross section Part number Installation type for motor
41.5 mm
2
1 333 245 7
Cable carrier installation
DS56 / CMD.. / CMP.. SM11
41.5 mm
2
+ 21 mm
2
1 333 248 1 DS56..B / CMD..BP / CMP..BP SB11
42.5 mm
2
1 333 246 5 DS56 / CMD.. / CMP.. SM12
42.5 mm
2
+ 21 mm
2
1 333 250 3 DS56..B / CMD..BP / CMP..BP SB12
44 mm
2
1 333 247 3 DS56 / CMD.. / CMP.. SM14
44 mm
2
+ 21 mm
2
1 333 251 1 DS56..B / CMD..BP / CMP..BP SB14
P
i
f
kVA
Hz
n
132 System Manual MOVIDRIVE MDX60B/61B Inverter
2
Prefabricated cables
Technical Data and Dimension Sheets
4. Prefabricated cables and extension cables for connecting VR forced cooling fans
VR forced cooling fan cable:
Extension cable for the VR forced cooling fan cable:
Number of cores and line cross section Part number Installation type
31 mm
2
198 634 1 Fixed installation
31 mm
2
199 560 X Cable carrier installation
Number of cores and line cross section Part number Installation type
31 mm
2
199 561 8 Fixed installation
31 mm
2
199 562 6 Cable carrier installation
P
i
f
kVA
Hz
n
System Manual MOVIDRIVE MDX60B/61B Inverter 133
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
Prefabricated cables
Technical Data and Dimension Sheets
5. Prefabricated cables for connecting options DEH11B / DEH21B / DER11B
The following overviews show the possible connections for the DEH11B/DEH21B and
DER11B options.
Meaning of the
symbols
The connection cables are assigned a part number and a symbol. The symbols have the
following meaning:
Symbol Meaning
56047AXX
Connection cable connector connector for fixed installation
56051AXX
Extension connection cable connector connector for fixed installation
56048AXX
Connection cable connector connector for cable carrier installation
56052AXX
Extension connection cable connector connector for cable carrier installation
56049AXX
Connection cable connector terminal box for fixed installation
56050AXX
Connection cable connector terminal box for cable carrier installation
56053AXX
Connection cable connector Y connector for fixed installation
56054AXX
Connection cable connector Y connector for cable carrier installation
56489AXX
Connection cable connector connector with crossed A/B track for reversing the
direction of rotation (for fixed installation)
56112AXX
Encoder connection via plug connector
56113AXX
Encoder connection via encoder terminal strip
56114AXX
Connection via plug connector on the motor side
56115AXX
Connection via terminal box on the motor side
P
i
f
kVA
Hz
n
134 System Manual MOVIDRIVE MDX60B/61B Inverter
2
Prefabricated cables
Technical Data and Dimension Sheets
Connection options at X15 X15 DEH11B/DEH21B
62907AXX
DEH11B
DEH21B
X
1
4
X
1
5
15
1
8
9
9
8
1
15
ES1S, ES2S, EV1S, EV2S, EH1S
ES1R, ES2R, EV1R, EV2R, EH1R
5
1
9
6
DIP11B
DEH21B
X
6
2
X62 DIP11B
SSI
1332 813 1
1332 812 3
X2 DWI11A
TTL/5V
198 829 8
198 828 X
AV1Y
593 968 2
X15 DEH.1B
TTL Sin/Cos
1332 459 4
1332 458 6
X15 DEH.1B
Sin/Cos
CM
AS1H, ES1H
DS
AS1H, ES1H
X15 DEH.1B
Hiperface
1332 453 5
1332 455 1
Hiperface
199 539 1
199 540 5
X15 DEH.1B
Hiperface
1332 457 8
1332 454 3
X15 DEH.1B
Hiperface
1332 765 8
1332 766 6
1
5
6
9
5
1
9
6
X
2
:
E
n
c
o
d
e
r
X
1
:
M
O
V
I
D
R
I
V
E
DWI11A
X15 DEH.1B
X1 DWI11A
817 957 3
198 828 X
198 829 8
X15 DEH11B
HTL/TTL
188 180 9
HTL
(DWE12B)
DS, CM, CMD, CMP
DT(E)/DV(E), CT/CV, DZ/DX
AF1H, AK0H, AS1H, AS3H, AS4H
EF1H, EK0H, ES1H, ES3H, ES4H EV1H, AV1H
DT(E)/DV(E), eDT/eDV, CT/CV
DR63, DZ/DX
DT(E)/DV(E), eDT/eDV
DR63, DZ/DX
ES1C, ES2C, EV1C
EH1C, EV2C
ES1T, ES2T, EV1T, EV2T,
EH1T
DT(E)/DV(E), eDT/eDV
DR63, DZ/DX
AV1Y
DT(E)/DV(E), CT/CV
DR63, DZ/DX
NOTE
For the individual wiring diagrams, refer to the section "Installation" in the
MOVIDRIVE
818 015 6
818 165 9
X14 DER11B/DEH11B
TTL, Sin/Cos
817 960 3
818 168 3
X14 DER11B/DEH11B
X1 DWI11A
818 164 0
X14 DER11B/DEH11B
X14 DEH11B
X14 DER11B
817 958 1
X2 DWI11A
TTL/5V
198 829 8
198 828 X
Hiperface
199 539 1
199 540 5
DER11B
DEH11B
X
1
5
9
8
1
15
56130AXX
Type Installation Part number
DEH11B / DER11B X14 AV1H, AS1H, ES1H,
AF1H, EF1H
56047AXX
818 015 6
56048AXX
818 165 9
P
i
f
kVA
Hz
n
System Manual MOVIDRIVE MDX60B/61B Inverter 141
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
Prefabricated cables
Technical Data and Dimension Sheets
Cable to connect external HIPERFACE
encoders
56049AXX
1810 695 1
56050AXX
1810 697 8
56132AXX
Type Installation Part number
DEH11B / DER11B X14 sin/cos encoders
56049AXX
819 869 1
56050AXX
818 168 3
P
i
f
kVA
Hz
n
142 System Manual MOVIDRIVE MDX60B/61B Inverter
2
Prefabricated cables
Technical Data and Dimension Sheets
Cable to connect the DC 5 V encoder power supply type DWI11A via plug connector.
Cable to connect an external DC 5 V TTL sensor to the DC 5 V encoder power supply
type DWI11A via encoder terminal strip.
Cable to connect a master/slave connection.
56109AXX
Type Installation Part number
DEH11B / DER11B X14 DWI11A X1
56047AXX
818 164 0
56132AXX
Type Installation Part number
DC 5 V TTL sensor DWI11A X2
56049AXX
198 829 8
56050AXX
198 828 X
56109AXX
Type Installation Part number
DEH11B/DER11B X14 DER11B/DEH11B X14
56047AXX
817 958 1
P
i
f
kVA
Hz
n
System Manual MOVIDRIVE MDX60B/61B Inverter 143
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
Prefabricated cables
Technical Data and Dimension Sheets
Cable to connect the encoder simulation (DEH11B/DER11B:X14) of the master to
terminal X42 of option DRS11B.
56109AXX
Type Installation Part number
DEH11B/DER11B X14 DRS11B X42
(master and slave turn in the same direction)
56047AXX
0818 166 7
DEH11B/DER11B X14 DRS11B X42
(master and slave turn in opposite directions)
56489AXX
0818 167 5
P
i
f
kVA
Hz
n
144 System Manual MOVIDRIVE MDX60B/61B Inverter
2
Prefabricated cables
Technical Data and Dimension Sheets
Connection options at X15 DER11B
56483BXX
AV1Y
DS, CM, CMD, CMP
RH1M, RH1L
CM
RH1M, RH1L
DS
RH1M, RH1L
DS, CM
RH1M, RH1L
5
1
9
6
DIP11B
X
6
2
X15 DER11B
RH1M/L
199 487 5
199 319 4
RH1M/L
199 542 1
199 541 3
X62 DIP11B
SSI
198 929 4
198 930 8
X15 DER11B
RH1M/L
199 589 8
199 590 1
X15 DER11B
RH1M/L
1332 817 4
1332 844 1
DER11B
X
1
4
X
1
5
15
1
8
9
6
5
1
9
NOTE
For the individual wiring diagrams, refer to the section "Installation" in the
MOVIDRIVE