Delta Es48 200 Uqa02
Delta Es48 200 Uqa02
Delta Es48 200 Uqa02
Main features
Up to 10.8 kW installed maximum power User friendly user(LCD) operation interface Wide input voltage range Module design, front access for simple maintenance Compact design, saves valuable floor space Intelligent remote system monitoring and control
Applications
Telecom, wireless, datacomm Medium power system 2G/ 3G site power application
Description
Delta DPR 2700 series power system, consisting of compact rack enclosures, 2700W rectifier modules, 1000W converter modules and related power distribution units, is under the control of Control and Supervisory Unit. User can operate the system via the user friendly LCD interface. Meanwhile, with the Delta power system management software, the remote power system management function is also available through internet, intranet or telephone line. Delta DPR 2700 series power system is designed to meet the demands of todays and tomorrows wireless and wire-line network applications. It combines a compact, modular design and intelligent power features. The DPR 2700 series power module is UL, TUV approved and manufactured in our modern ISO 9001 and TL 9000 certified facility.
www.deltaww.com
LVDL Mechanics Construction Height, overall Width, body Depth, overall Weight, system
L1 L2 L3 - N + PE : 380 /220VRMS 184 ... 300 VRMS 90 ... 184 VRMS 45 ... 65 Hz 3P L1 L2 L3 - N + PE: 380 VRMS/32 ARMS @ 2.0kW X 4 < 21 Apeak per rectifier <5% 3P with N-PE Surge Protect 40 KA 8/20 S AC Terminal (Optional AC Breaker)
Weight, rectifiers Weight, converters Environment Ambient temperature Storage temperature Relative humidity Rectifier Type DPR2000 series DCM1000W Control and monitoring Power system controller Display Function
Power Shelf Application 260.5 mm / 10.25 inch (6U) 584.2mm / 23 inch 391.6 mm / 15.4 inch 60 kg / 132 lb (w/o Rectifier and Converter) 2.0 kg / 4.4. lb 1 kg / 2.2. lb
Float: 54.0 VDC Equalize: 56.0 VDC Voltage range 40 ... 59.5 VDC Voltage regulation < 0.1 % Overvoltage protection 59.5 VDC Ripple + spikes 100 mVp-p Psophometric noise 2.0 mVRMS (weighted) Output current 200 ADC @ 54 VDC Bus-Bar rating DPR 2700 rectifier X4 Output Output current 200 ADC @ 54 VDC 224 ADC @ 48 VDC Power, maximum 10.8 kW DCM 1000W converter X4 Output Output current 160ADC @ 24 VDC Power, maximum 4.0 kW Load distribution System Configuration:
ESR-48/56A B DCS-24/40A A
Remote Interface
Delta New Smart CSU LCD 128 x 64 dots display System monitoring (remote/local) Parameter setting Temperature compensation Boost / Equalize charge Alarm relay definable Battery test RS-232
Accessories Rectifier blank panel Delta remote management software Web/ SNMP extended board Subject to change due to technical progress.
1. 2. 3.
Main AC Terminal (Top -Rear) 3P with N+PE AC Surge Protection -48V O/P Load Breaker X 17 (DIN Rail C60 Type) 63A x2; 32A x11; 10A x2;
DELTA ELECTRONICS, INC. 3, Tung Yuan Road, Chungli Industral Park, Taoyuan Hsien 320 Taiwan, R.O.C. Phone: +886 3 452-6107 Fax: +886 3 452-7314
www.deltaww.com