Current Transformer f2
Current Transformer f2
:By
Example
a 1000/1 A CT will produce 1A of secondary
.current when 1000 A flows through the primary
As the primary current changes the secondary
.current will vary accordingly
POLARITY
All CT,s are subtractive polarity .
P
1
S
1
Terminals Marking
general rules
The terminal markings shall identify: the primary
and secondary windings; the winding sections, if
any; the relative polarities of windings and winding
sections; the intermediate tapings, if any
Graphic symbols of current
transformers
The main tasks of instrument transformer are:
intermediate -
zone
Non saturated -
zone
TEST RESULT
Volt (V) Current (mA) Volt (V) Current (mA)
1000
M AG CURVE
100
10
1
0 .1 1 .0 1 0 .0 1 0 0 .0 1 0 0 0 .0 1 0 0 0 0 .0
A C.T consists essentially of an iron core with two windings.
One winding is connected in the circuit whose current is to be
measured.
The flow of current in the primary winding produces an
alternating flux in the core and this flux induces an e.m.f in the
secondary winding which results in the flow of secondary current
when this winding is connected to an external closed circuit .
Ssc
Ik = 3 * Un
Example
MVA SC = 5000 MVA
V = 380 KV
5000
Ik =
3 * 380
Ik = 7.597 KA
Ith = Ik (1+ 0 .0 5 (5 0 /6
) 0
I dyn = 2.5 … 3 I th
Burden
BURDEN RB
=
VA / I² LB
To protect instrument and meters
from high fault currents the metering
cores must be saturated 10-40 times
the rated current depending of the
type of burden.
”The instrument security factor “Fs
Pn + Pi
n= * Fs
Pb + Pi
The main characteristics of protection
CT cores are:
• Lower accuracy than for measuring transformer .
Pn + Pi
n= * ALF
pb + Pi
No. of primary turns = 1 turn
Ip = N * Is
Ideal transformer for (Is) to flow
through R there must be some
potential Es = The E.M.F dφ
Es = Is * R
Es ∝
dt
.Es is produced by an alternating flux in the core
Es = I s * RCT + I s * z B
Flux required to produce Es
φ = B* A
Where
B = Flux density in the core
A = cross-sectional area of core
Ek = 4.44* B * f * A * N Equ. 1
E s = I s ( z B + zC T + z L ) Equ. 2 Required Ek E s
CT 2000/5 , Rs =0.31, Imax =40 KA , MaX Flux density =1.6
Tesla
Find maximum secondary burden permissible if no saturation
is to occur.
Solution
N=2000/5 = 400Turns
Is max = 40000/400 = 100Amps
From Equ.1
Vk = 4.44*1.6*20*60*(400/10000) = 340 Volt
No region un protected
Current transformers
mounted on C.B side only of
breaker fault shown not
cleared by bus bar protection.
Current transformers mounted on bus bar
side only of breaker fault shown not
cleared circuit protection.
RATIO 2000/5 A
POWER 20 VA
CLASS 5P20
MEASURING IEC standard
RATIO 2000/5 A
POWER 20 VA
CLASS 0.5SF5
CT Class X
ANSI/IEEE
KNEE POINT
IEC KNEE POINT
ANSI/IEE
KNEE POINT
Burden
TESTING
Polarity
This test checks the polarity of the CT
Ratio
Insulation test
SATURATION
Abnormal high primary current
High secondary burden
Combination of the above two
factors will result in the creation of
high flux density in the current
transformer iron core.
When this density reaches or
exceeds the design limit of the core ,
saturation results.
SATURATION
The accuracy of the CT becomes
very poor.
The output wave form distorted.
The result secondary current lower
in magnitude.
The greatest dangerous is loss of
protective device coordination
SATURATION
list of CT problems usually found
at site:
•Shorted CT secondaries
• Open-circuited CT secondaries
• Miswired CTs
• CTs that had not been wired
• CTs installed backwards
• Incorrect CTs
• Defective CTs
• CTs with incorrect ratios or on the
wrong taps
THANKS
:ىى ىىىىىى
ى /ىىىى ىىى
ىىىىى