ED 01 - 707

- Cooling Only F-Series

ED01-707

Split-System Room Air Conditioners F-Series


50Hz Cooling Only 60Hz
1. 2. 3. 4.

FT50FVM FT60FVM FT50FVM FT60FVM

R50BV1 R60BV1 R50BVL R60BVL

Features ..................................................................................................2 Power Supply ..........................................................................................3 Functions.................................................................................................4 Specifications ..........................................................................................5


4.1 50Hz .........................................................................................................5 4.2 60Hz .........................................................................................................6

5. Dimensions .............................................................................................7
5.1 Indoor Units ..............................................................................................7 5.2 Outdoor Units ...........................................................................................8

6. Wiring Diagrams......................................................................................9
6.1 Indoor Units ..............................................................................................9 6.2 Outdoor Units .........................................................................................10

7. Piping Diagrams....................................................................................12
7.1 Indoor Units ............................................................................................12 7.2 Outdoor Units .........................................................................................12

8. Capacity Tables ....................................................................................13


8.1 Cooling Only...........................................................................................13 8.2 Capacity Correction Factor by the Length of Refrigerant Piping (Reference) ...........................................................................................15

9. Operation Limit......................................................................................16 10.Sound Level ..........................................................................................17


10.1 Measuring Location ................................................................................17 10.2 Octave Band Level .................................................................................18

11.Electric Characteristics..........................................................................19 12.Installation Manual ................................................................................20 13.Operation Manual..................................................................................30 14.Optional Accessories ............................................................................50
14.1 Option List ..............................................................................................50 14.2 Installation Manual .................................................................................51

Room Air Conditioners F-Series

Features

ED01-707

1. Features
Features
FT50/60F

- Energy Saving
Improved COP

- Stylish Design
The stylish flat panel is also available.

06RAG13-4

Healthy and Clean

Titanium Apatite Photocatalytic Air-Purifying Filter


It lasts for three years without replacement if washed about once every six months. Absorbs microscopic particles, decomposes odours and even deactivates bacteria and viruses.

ABSORB

REMOVE

05RAG19A- 31

Room Air Conditioners F-Series

ED01-707

Power Supply

2. Power Supply
Indoor Unit FT50FVM FT60FVM FT50FVM FT60FVM Outdoor Unit R50BV1 R60BV1 R50BVL R60BVL Power Supply 1, 220-240V, 50Hz 1, 220V, 60Hz

Note:

Power Supply Intake ; Outdoor Unit

Room Air Conditioners F-Series

Functions

ED01-707

3. Functions
FT50/60FVM R50/60BV1 FT50/60FVM R50/60BVL FT50/60FVM R50/60BV1

Category

Functions

Category

Functions

Basic Function

Inverter (with Inverter Power Control) Operation Limit for Cooling (CDB) Operation Limit for Heating (CWB) PAM Control

19.4 ~46

19.4 ~46

Health & Clean

Air Purifying Filter with Bacteriostatic, Virustatic Functions Photocatalytic Deodorizing Filter Air Purifying Filter with Photocatalytic Deodorizing Function Titanium Apatite Photocatalytic Air-Purifying Filter Longlife Filter Ultra-Longlife Filter (Option) Mold Proof Air Filter Wipe-clean Flat Panel Washable Grille Filter Cleaning Indicator Good-Sleep Cooling Operation

Compressor

Oval Scroll Compressor Swing Compressor Rotary Compressor Reluctance DC Motor


Comfortable Airflow

Power-Airflow Flap Power-Airflow Dual Flaps Power-Airflow Diffuser Wide-Angle Louvers Vertical Auto-Swing (Up and Down) Horizontal Auto-Swing (Right and Left) 3-D Airflow 3-Step Airflow (H/P Only)


Timer

24-Hour On/Off Timer Night Set Mode

Worry Free Reliability & Durability

Auto-Restart (after Power Failure) Self-Diagnosis (Digital, LED) Display Wiring Error Check Anticorrosion Treatment of Outdoor Heat Exchanger

Comfort Control

Auto Fan Speed Indoor Unit Quiet Operation Night Quiet Mode (Automatic) Outdoor Unit Quiet Operation (Manual) Intelligent Eye Quick Warming Function Hot-Start Function Automatic Defrosting



Flexibility

Multi-Split / Split Type Compatible Indoor Unit Flexible Voltage Correspondence High Ceiling Application Chargeless Either Side Drain (Right or Left) Power Selection

10m

10m

Operation

Automatic Operation Programme Dry Function Fan Only

Remote Control

5-Rooms Centralized Controller (Option) Remote Control Adaptor (Normal Open-Pulse Contact) (Option) Remote Control Adaptor (Normal Open Contact)(Option) DIII-NET Compatible (Adaptor)(Option)

Lifestyle Convenience

New Powerful Operation (Non-Inverter) Inverter Powerful Operation Priority-Room Setting Cooling / Heating Mode Lock Home Leave Operation Indoor Unit On/Off Switch Signal Reception Indicator Temperature Display Another Room Operation



Remote Controller

Wireless Wired

Note: : Holding Functions : No Functions

Room Air Conditioners F-Series

FT50/60FVM R50/60BVL



ED01-707

Specifications

4. Specifications
4.1
Models

50Hz
50Hz 220-230-240V
Indoor Units Outdoor Units kW Btu/h kcal/h A W % W/W mm mm mm m m m g/m FT50FVM R50BV1 5.3 18,090 4,560 7.9-7.6-7.2 1,650 94.9-94.4-95.5 3.21 6.4 15.9 18.0 Both Liquid and Gas Pipes 30 15 10 20 FT50FVM White 16.2 (572) 14.0 (494) 11.9 (420) Cross Flow Fan 43 5 Steps, Auto Right, Left, Horizontal, Downward Removable/Washable/Mildew Proof 0.19-0.18-0.17 40 95.7-96.6-98.0 Microcomputer Control 2901,050238 3371,147366 12 17 45/41/35 R50BV1 Ivory White Hermetically Sealed Rotary Type RC60V1TNRT 1,500 SUNISO 4GSD. I. 0.85 R-22 1.35 40.0-40.5-41.0 (1,412-1,430-1,448) () Propeller 53 7.71-7.42-7.03 1,610 94.9-94.3-95.4 32-33.5-35 685800300 732955390 49 54 54-54-55 3D056213 FT60FVM R60BV1 6.6 22,530 5,630 11.6-11.1-10.6 2,460 96.4-96.4-96.7 2.68 6.4 15.9 18.0 Both Liquid and Gas Pipes 30 15 10 20 FT60FVM White 17.5 (618) 15.0 (530) 12.5 (441) Cross Flow Fan 43 5 Steps, Auto Right, Left, Horizontal, Downward Removable/Washable/Mildew Proof 0.21-0.20-0.19 45 97.4-97.8-98.7 Microcomputer Control 2901,050238 3371,147366 12 17 47/42/36 R60BV1 Ivory White Hermetically Sealed Rotary Type NH41VMDT 2,200 MS-32 1.20 R-22 1.70 40.0-40.5-41.0 (1,412-1,430-1,448) 23.3-24.8-26.2 (823-876-925) Propeller 53 11.39-10.90-10.41 2,415 96.4-96.3-96.7 55-57.5-60 685800300 732955390 61 66 54-54-55 3D056215 Conversion Formulae kcal/h=kW860 Btu/h=kW3414 cfm=m/min35.3

Capacity (Rated) Running Current (Rated) Power Consumption (Rated) Power Factor COP (Rated) Liquid Piping Connections Gas Drain Heat Insulation Max. Interunit Piping Length Max. Interunit Height Difference Chargeless Amount of Additional Charge of Refrigerant Indoor Units Front Panel Color Air Flow Rate m/min (cfm)

H M L W Steps

Type Motor Output Speed Air Direction Control Air Filter Running Current Power Consumption Power Factor Temperature Control Dimensions (HWD) Packaged Dimensions (HWD) Weight Gross Weight Operation H/M/L Sound Outdoor Units Casing Color Type Compressor Model Motor Output Type Refrigerant Oil Charge Type Refrigerant Charge Fan Air Flow Rate m/min (cfm) Type Motor Output Running Current (Rated) Power Consumption (Rated) Power Factor Starting Current Dimensions (HWD) Packaged Dimensions (HWD) Weight Gross Weight Operation Sound Drawing No. Fan

A W % mm mm kg kg dBA

W L kg H L W A W % A mm mm kg kg dBA

Note:

The data are based on the conditions shown in the table below.

Cooling Indoor ; 27CDB/19CWB Outdoor ; 35CDB/24CWB

Piping Length 7.5m

Room Air Conditioners F-Series

Specifications

ED01-707

4.2
Models

60Hz
60Hz 220V
Indoor Units Outdoor Units kW Btu/h kcal/h A W % W/W mm mm mm m m m g/m FT50FVM R50BVL 5.7 19,460 4,900 10.6 2,210 94.8 2.58 6.4 15.9 18.0 Both Liquid and Gas Pipes 30 15 10 20 FT50FVM White 17.9 (632) 14.8 (523) 11.9 (420) Cross Flow Fan 43 5 Steps, Auto Right, Left, Horizontal, Downward Removable/Washable/Mildew Proof 0.19 40 95.7 Microcomputer Control 2901,050238 3371,147366 12 17 45/41/35 R50BVL Ivory White Hermetically Sealed Rotary Type RC60VHTNRT 1,500 SUNISO 4GSD.I. 0.85 R-22 1.25 30.0 (1,059) () Propeller 45 10.41 2,170 94.8 42 540750270 609940360 41 45 52 3D055911 FT60FVM R60BVL 6.9 23,560 5,930 12.5 2,710 98.5 2.55 6.4 15.9 18.0 Both Liquid and Gas Pipes 30 15 10 20 FT60FVM White 19.0 (671) 15.8 (558) 12.5 (441) Cross Flow Fan 43 5 Steps, Auto Right, Left, Horizontal, Downward Removable/Washable/Mildew Proof 0.21 45 97.4 Microcomputer Control 2901,050238 3371,147366 12 17 47/42/36 R60BVL Ivory White Hermetically Sealed Rotary Type RC75VHTR2T 1,800 SUNISO 4GSD.I. 1.00 R-22 1.60 44.0 (1,554) 20.3 (717) Propeller 53 12.29 2,665 98.6 47 635800300 732955390 51 56 55 3D055912 Conversion Formulae kcal/h=kW860 Btu/h=kW3414 cfm=m/min35.3

Capacity (Rated) Running Current (Rated) Power Consumption (Rated) Power Factor COP (Rated) Liquid Piping Gas Connections Drain Heat Insulation Max. Interunit Piping Length Max. Interunit Height Difference Chargeless Amount of Additional Charge of Refrigerant Indoor Units Front Panel Color Air Flow Rate m/min (cfm)

H M L W Steps

Fan

Type Motor Output Speed Air Direction Control Air Filter Running Current Power Consumption Power Factor Temperature Control Dimensions (HWD) Packaged Dimensions (HWD) Weight Gross Weight Operation H/M/L Sound Outdoor Units Casing Color Type Compressor Model Motor Output Type Refrigerant Oil Charge Type Refrigerant Charge Air Flow Rate Fan m/min (cfm)

A W % mm mm kg kg dBA

W L kg H L W A W % A mm mm kg kg dBA

Type Motor Output Running Current (Rated) Power Consumption (Rated) Power Factor Starting Current Dimensions (HWD) Packaged Dimensions (HWD) Weight Gross Weight Operation Sound Drawing No.

Note:

The data are based on the conditions shown in the table below.

Cooling Indoor ; 27CDB/19CWB Outdoor ; 35CDB/24CWB

Piping Length 7.5m

Room Air Conditioners F-Series

ED01-707

Dimensions

5. Dimensions
5.1 Indoor Units
FT50FVM, FT60FVM
THE MARK () SHOWS PIPING DIRECTION REAR LEFT 1050 REAR RIGHT MIN. 30 (SPACE FOR PERFORMANCE) MIN. 50 (SPACE FOR MAINTENANCE) 155.5 35 5 35 60 WALL HOLE FOR EMBEDDED PIPING 80 HOLE 99.5 WALL HOLE 80 HOLE 52 FAN 5 55 5 55
50 50

AIR FLOW(INDOOR) (FOR PERFORMANCE AND MAINTENANCE)

(SPACE FOR MAINTENANCE) MIN. 50 INCLUDING ( INSTALLATION PLATE ) 240 238 OPERATION LAMP SIGNAL RECEIVER INDOOR UNIT ON/OFF SWITCH ROOM TEMP. THERMISTOR (INSIDE) TIMER LAMP FLAPS FRONT GRILLE FIXING SCREWS (INSIDE) 290 MODEL NAME PLATE TERMINAL BLOCK WITH EARTH TERMINAL (INSIDE)

REQUIRED SPACE

GAS PIPE 15.9 CuT (THE LENGTH OF PIPE OUTSIDE THE UNIT : ABOUT 430)

SIGNAL TRANSMITTER 58 18 HORIZONTAL BLADE (AUTOMATIC) COOLING 163

DRAIN HOSE FOR VP13 (CONNECTING PART I. D. 14.0, O. D. 18.0) (THE HOSE LENGTH OF LIQUID PIPE 6.4 CuT OUTSIDE THE UNIT : (THE LENGTH OF PIPE OUTSIDE ABOUT 530) THE UNIT : ABOUT 480) 1050 30 290 893.5 52.5

BLADE ANGLES
DRY 14.5 52

10 40 10 40

WIRELESS REMOTE CONTROLLER


(ARC433A73)

VERTICAL BLADE(MANUAL)

STANDARD LOCATIONS OF WALL HOLES

3D056087A

Room Air Conditioners F-Series

Dimensions

ED01-707

5.2

Outdoor Units

R50BV1, R60BV1, R60BVL


HOLES FOR ANCHOR BOLTS (M8 OR M10)

269

31 540 130 2-DRAIN OUTLET (I.D. 15.9 HOSE FOR CONNECTION) OUTDOOR AIR THERMOSTAT TERMINAL COVER 98 330 350

800 EARTH TERMINAL (M4)

15

300

POWER INTAKE

NAME PLATE LIQUID PIPE (6.4CuT)

685

645

LIQUID STOP VALVE

75

GAS STOP VALVE 100

GAS PIPE (15.9CuT) A

MINIMUM SPACE FOR AIR PASSAGE H H H H A 50


< 1000 = = 1000

95 70

SERVICE PORT

150

A 300 600

50

50

100

3D004856K

R50BVL
HOLES FOR ANCHOR BOLTS ( M8 OR M10 ) 3-DRAIN OUTLETS ( I. D. 15. 9 HOSE FOR CONNECTION ) 237 700 520 190 170 60 27

290 530 750 95 100 34 72

213

48

306

15

270

TERMINAL COVER EARTH TERMINAL ( M4 )

540

POWER INTAKE NAME PLATE GAS STOP VALVE ( 15. 9CuT )

34

105 SERVICE PORT

58

LIQUID STOP VALVE ( 6. 4CuT )

27

MINIMUM SPACE FOR AIR PASSAGE

150

SPACE 50 LESS THAN 1000 MORE THAN 1000 MORE THAN 300 MORE THAN 600

50

100

50

3D004855F

Room Air Conditioners F-Series

ED01-707

Wiring Diagrams

6. Wiring Diagrams
6.1 Indoor Units
FT50FVM, FT60FVM

FIELD WIRING. PCB3 S27 S26 PCB1 ~ RECTIFIER ~ V1 t R1T S38 SA1 PCB4 S37 LED1 H1P LED2 H2P 1 S28 S32 1 S6 5 BLU BRN ORG WHT S21 7 S1 RED MR2 H3 V2 FG Fu 3.15A H2 H1 RED WHT BLK GRN/ YLW X1M 1 2 3 CAUTION NOTE THAT OPERATION WILL RESTART AUTOMATICALLY IF THE MAIN POWER SUPPLY IS TURNED OFF AND THEN BACK ON AGAIN. 1 2 3 OUTDOOR

M
M1F

PCB2 SIGNAL RECEIVER WIRELESS REMOTE CONTROLLER S1W S29

t R2T

INDOOR M M1S

FG Fu H1~H3 H1P, H2P M1F M1S MR2 PCB1~PCB4 R1T, R2T S1~S38 S1W SA1 V1, V2 X1M

: FRAME GROUND : FUSE : HARNESS : PILOT LAMP : FAN MOTOR : SWING MOTOR : MAGNETTIC RELAY : PRINTED CIRCUIT BOARD : THERMISTOR : CONNECTOR : OPERATION SWITCH : SURGE ARRESTER : VARISTOR : TERMINAL STRIP : PROTECTIVE EARTH

RED ORG YLW PNK BLU

3D038655E

Room Air Conditioners F-Series

Wiring Diagrams

ED01-707

6.2
R50BV1

Outdoor Units

X1M TO INDOOR UNIT 1

RED RED 1 2 BLU

2 RED

WHT YLW 5 6 RED C11R 3.15A BLK RED S

M
1~ M

M1C

BLK F1U

BLK

13

14

BLK

M
N POWER SUPPLY RED BLK A1 ORG K1M A2 RED C12R RED WHT X11A 1~

M1F

F1S Q1L

C11R, C12R : RUNNING CAPACITOR F1U : FUSE F1S : SURGE ARRESTER K1M : COMPRESSOR RELAY L : LIVE M1C : COMPRESSOR MOTOR

M1F : FAN MOTOR N : NEUTRAL Q1L : OVERLOAD PROTECTOR X11A : CONNECTOR X1M : TERMINAL STRIP

NOTES 1. REFER TO THE NAMEPLATE FOR THE POWER REQUIREMENTS.

3D040743A

R60BV1

X1M TO INDOOR UNIT 1

RED 1 2 C11R YLW

RED

BLU S RED L H S1T L BLK ORG H RED

C M 1~ R

2 RED

WHT

RED

M1C

3 3.15A L BLK BLK F1U BLK RED A1 K1M A2 RED C12R BLK

13

14

WHT

M 1~

N POWER SUPPLY

WHT M1F X11A

F1S

C11R, C12R F1S F1U K1M L M1C

: RUNNING CAPACITOR : SURGE ARRESTER : FUSE : COMPRESSOR RELAY : LIVE : COMPRESSOR MOTOR

M1F : FAN MOTOR : NEUTRAL N S1T : THERMOSTAT X11A : CONNECTOR X1M : TERMINAL STRIP

NOTES 1.REFER TO THE NAMEPLATE FOR THE POWER REQUIREMENTS.

3D032200A

10

Room Air Conditioners F-Series

ED01-707

Wiring Diagrams

R50BVL

X1M TO INDOOR UNIT 1

RED

1
RED

BLU

C 2
RED WHT YLW

M 1~

3 3.15A
BLK

RED

RED

C11R L
BLK BLK

M1C

13

14

BLK

BLK

F1U
BLK RED

X11A
RED

M 1~

N POWER SUPPLY

A1
ORG

A2 K1M

RED

WHT

C12R

M1F

Q1L F1S

C11R, C12R F1U F1S K1M L M1C

: RUNNING CAPACITOR : FUSE : SURGE ARRESTER : COMPRESSOR RELAY : LIVE : COMPRESSOR MOTOR

M1F N Q1L X11A X1M

: FAN MOTOR : NEUTRAL : OVERLOAD PROTECTOR : CONNECTOR : TERMINAL STRIP

NOTES 1.REFER TO THE NAMEPLATE FOR THE POWER REQUIREMENTS.

3D032199B

R60BVL

INDOOR

X1M 1

RED 1 2 C11R

OUTDOOR BLU YLW S M

RED

C M 1~ M1C

2 RED

WHT

RED L H S1T L

RED

3 BLK 3.15A BLK RED F1U BLK A1 ORG K1M A2 RED C12R BLK

BLK ORG

BLK ORG RED WHT M1F X11A M 1~

13

14

WHT

C H

RED WHT

POWER SUPPLY ~220V 60Hz

F1S

Q1L

FIELD WIRING. C11R,C12R F1S F1U K1M L N :RUNNING CAPACITOR : SURGE ARRESTER : FUSE : COMPRESSOR RELAY : LIVE : NEUTRAL

M1C S1T M1F Q1L X1M X11A

: COMPRESSOR MOTOR : THERMOSTAT : FAN MOTOR : OVERLOAD PROTECTOR : TERMINAL STRIP : CONNECTOR

NOTE REFER TO THE NAMEPLATE FOR THE POWER REQUIREMENTS.

PROTECTIVE EARTH

3D032198C

Room Air Conditioners F-Series

11

Piping Diagrams

ED01-707

7. Piping Diagrams
7.1 Indoor Units
FT50FVM, FT60FVM

INDOOR UNIT

(7.9CuT)

HEAT EXCHANGER

THERMISTOR ON HEAT EXCH. FIELD PIPING (6.4CuT) FIELD PIPING (15.9CuT) CROSS FLOW FAN

M
FAN MOTOR (12.7CuT)

REFRIGERANT FLOW COOLING


4D050919E

7.2

Outdoor Units
R60BVL

R50BV1, R60BV1, R50BVL

OUTDOOR UNIT

OUTDOOR UNIT

HEAT EXCHANGER

HEAT EXCHANGER

M
M LIQUID STOP VALVE FIELD PIPING (6.4CuT) CAPILLARY TUBE PROPELLER FAN ACCUMULATOR GAS STOP VALVE WITH SERVICE PORT
COMPRESSOR LIQUID STOP VALVE PROPELLER FAN CAPILLARY TUBE FIELD PIPING (6. 4CuT) FIELD PIPING (15. 9CuT) GAS STOP VALVE WITH SERVICE PORT

FIELD PIPING (15.9CuT)

HPV ACCUMULATOR

COMPRESSOR REFRIGERANT FLOW COOLING


REFRIGERANT FLOW COOLING

DW527-236D

DW521-856N

12

Room Air Conditioners F-Series

ED01-707

Capacity Tables

8. Capacity Tables
8.1 Cooling Only
FT50FVM + R50BV1 (50Hz 220-240V)
AFR BF 16.2 0.27

INDOOR EWB EDB C 14.0 16.0 18.0 19.0 22.0 24.0 C 20 22 25 27 30 32 TC 5.36 5.52 5.67 5.75 5.98 6.14 20 SHC 3.67 3.71 3.74 3.76 3.81 3.84 PI 1.30 1.33 1.35 1.37 1.40 1.43 TC 5.21 5.37 5.52 5.60 5.83 5.99 25 SHC 3.60 3.64 3.67 3.69 3.74 3.77 PI 1.40 1.42 1.45 1.46 1.50 1.53

OUTDOOR TEMPERATURE(CDB) 30 TC 5.06 5.22 5.37 5.45 5.68 5.84 SHC 3.53 3.57 3.60 3.62 3.67 3.70 PI 1.49 1.52 1.54 1.56 1.59 1.62 TC 5.00 5.16 5.31 5.39 5.62 5.78 32 SHC 3.50 3.54 3.57 3.59 3.64 3.67 PI 1.53 1.55 1.58 1.59 1.63 1.66 TC 4.91 5.07 5.22 5.30 5.53 5.69 35 SHC 3.46 3.50 3.53 3.55 3.60 3.63 PI 1.59 1.61 1.64 1.65 1.69 1.72 TC 4.76 4.92 5.07 5.15 5.38 5.54 40 SHC 3.39 3.43 3.46 3.48 3.53 3.56 PI 1.68 1.71 1.73 1.75 1.78 1.81

Symbols AFR BF EWB EDB TC SHC PI : Air flow rate : Bypass factor : Entering wet bulb temp. : Entering dry bulb temp. : Total capacity : Sensible heat capacity : Power input (C) (C) (kW) (kW) (kW) (m/min.)

NOTE: 1. Capacities are based on the following conditions. Corresponding refrigerant piping length : 7.5m Level difference : 0m 2. shows nominal(rated) capacities and power input.

3D040933B

FT60FVM + R60BV1 (50Hz 220-240V)


AFR BF 17.5 0.23

INDOOR EWB EDB C 14.0 16.0 18.0 19.0 22.0 24.0 C 20 22 25 27 30 32 TC 6.66 6.82 6.97 7.05 7.28 7.44 20 SHC 4.40 4.43 4.47 4.48 4.53 4.57 PI 2.11 2.14 2.16 2.18 2.21 2.24 TC 6.51 6.67 6.82 6.90 7.13 7.29 25 SHC 4.33 4.36 4.40 4.41 4.46 4.50 PI 2.21 2.23 2.26 2.27 2.31 2.34

OUTDOOR TEMPERATURE(CDB) 30 TC 6.36 6.52 6.67 6.75 6.98 7.14 SHC 4.26 4.29 4.33 4.34 4.39 4.43 PI 2.30 2.33 2.35 2.37 2.40 2.43 TC 6.30 6.46 6.61 6.69 6.92 7.08 32 SHC 4.23 4.26 4.30 4.31 4.37 4.40 PI 2.34 2.36 2.39 2.40 2.44 2.47 TC 6.21 6.37 6.52 6.60 6.83 6.99 35 SHC 4.19 4.22 4.26 4.27 4.32 4.36 PI 2.40 2.42 2.45 2.46 2.50 2.53 TC 6.06 6.22 6.37 6.45 6.68 6.84 40 SHC 4.12 4.15 4.19 4.20 4.25 4.29 PI 2.49 2.52 2.54 2.56 2.59 2.62

Symbols AFR BF EWB EDB TC SHC PI : Air flow rate : Bypass factor : Entering wet bulb temp. : Entering dry bulb temp. : Total capacity : Sensible heat capacity : Power input (C) (C) (kW) (kW) (kW) (m/min.)

NOTE: 3. Capacities are based on the following conditions. Corresponding refrigerant piping length : 7.5m Level difference : 0m 4. shows nominal(rated) capacities and power input.

3D040934A

Room Air Conditioners F-Series

13

Capacity Tables

ED01-707

FT50FVM + R50BVL (60Hz 220V)


AFR BF 17.9 0.27

INDOOR EWB EDB C 14.0 16.0 18.0 19.0 22.0 24.0 C 20 22 25 27 30 32 TC 5.76 5.92 6.07 6.15 6.38 6.54 20 SHC 3.99 4.02 4.05 4.07 4.12 4.16 PI 1.86 1.89 1.91 1.93 1.96 1.99 TC 5.61 5.77 5.92 6.00 6.23 6.39 25 SHC 3.92 3.95 3.98 4.00 4.05 4.09 PI 1.96 1.98 2.01 2.02 2.06 2.09

OUTDOOR TEMPERATURE(CDB) 30 TC 5.46 5.62 5.77 5.85 6.08 6.24 SHC 3.85 3.88 3.91 3.93 3.98 4.02 PI 2.05 2.08 2.10 2.12 2.15 2.18 TC 5.40 5.56 5.71 5.79 6.02 6.18 32 SHC 3.82 3.85 3.89 3.90 3.95 3.99 PI 2.09 2.11 2.14 2.15 2.19 2.22 TC 5.31 5.47 5.62 5.70 5.93 6.09 35 SHC 3.78 3.81 3.84 3.86 3.91 3.95 PI 2.15 2.17 2.20 2.21 2.25 2.28 TC 5.16 5.32 5.47 5.55 5.78 5.94 40 SHC 3.71 3.74 3.77 3.79 3.84 3.88 PI 2.24 2.27 2.29 2.31 2.34 2.37

Symbols AFR BF EWB EDB TC SHC PI : Air flow rate : Bypass factor : Entering wet bulb temp. : Entering dry bulb temp. : Total capacity : Sensible heat capacity : Power input (C) (C) (kW) (kW) (kW) (m/min.)

NOTE: 1. Capacities are based on the following conditions. Corresponding refrigerant piping length : 7.5m Level difference : 0m 2. shows nominal(rated) capacities and power input.

3D040935A

FT60FVM + R60BVL (60Hz 220V)


AFR BF 19.0 0.29

INDOOR EWB EDB C 14.0 16.0 18.0 19.0 22.0 24.0 C 20 22 25 27 30 32 TC 6.96 7.12 7.27 7.35 7.58 7.74 20 SHC 4.54 4.58 4.61 4.63 4.68 4.71 PI 2.36 2.39 2.41 2.43 2.46 2.49 TC 6.81 6.97 7.12 7.20 7.43 7.59 25 SHC 4.47 4.51 4.54 4.56 4.61 4.64 PI 2.46 2.48 2.51 2.52 2.56 2.59

OUTDOOR TEMPERATURE(CDB) 30 TC 6.66 6.82 6.97 7.05 7.28 7.44 SHC 4.40 4.44 4.47 4.49 4.54 4.57 PI 2.55 2.58 2.60 2.62 2.65 2.68 TC 6.60 6.76 6.91 6.99 7.22 7.38 32 SHC 4.37 4.41 4.44 4.46 4.51 4.54 PI 2.59 2.61 2.64 2.65 2.69 2.72 TC 6.51 6.67 6.82 6.90 7.13 7.29 35 SHC 4.33 4.37 4.40 4.42 4.47 4.50 PI 2.65 2.67 2.70 2.71 2.75 2.78 TC 6.36 6.52 6.67 6.75 6.98 7.14 40 SHC 4.26 4.30 4.33 4.35 4.40 4.43 PI 2.74 2.77 2.79 2.81 2.84 2.87

Symbols AFR BF EWB EDB TC SHC PI : Air flow rate : Bypass factor : Entering wet bulb temp. : Entering dry bulb temp. : Total capacity : Sensible heat capacity : Power input (C) (C) (kW) (kW) (kW) (m/min.)

NOTE: 1. Capacities are based on the following conditions. Corresponding refrigerant piping length : 7.5m Level difference : 0m 2. shows nominal(rated) capacities and power input.

3D040936A

14

Room Air Conditioners F-Series

ED01-707

Capacity Tables

8.2

Capacity Correction Factor by the Length of Refrigerant Piping (Reference)


The cooling capacity of the unit has to be corrected in accordance with the length of refrigerant piping. (The distance between the indoor unit and the outdoor unit)
Cooling (R-22) 1

Capacity correction factor

0.9

Range of the Refrigerant Additional Charge 0.8

10

15 Piping length (m)

20

25

30
(R6693)

Note:

The graph shows the factor when additional refrigerant of the proper quantity is charged.

Room Air Conditioners F-Series

15

Operation Limit

ED01-707

9. Operation Limit
R50BV1, R60BV1, R50BVL, R60BVL

50 46

40 Outdoor temp.(CDB) Continuous operation

30

20 19.4 0

10

14

20

23

Pull-down period 28 30 Indoor temp.(CWB)

Notes: The graph is based on the following conditions. Equivalent piping length Level difference Air flow rate

5m 0m High
4D000888R

16

Room Air Conditioners F-Series

ED01-707

Sound Level

10. Sound Level


10.1 Measuring Location
Indoor Unit
Wall Mounted Type

Outdoor Unit

1m 0.8m

1m

(R1759)

(R1003)

Note:

1. Operation sound is measured in an anechoic chamber. 2. The data are based on the conditions shown in the table below.
Cooling Indoor ; 27CDB/19CWB Outdoor ; 35CDB/24CWB Piping Length 7.5m

Room Air Conditioners F-Series

17

Sound Level

ED01-707

10.2 Octave Band Level


10.2.1 Indoor Units
FT50FVM (50Hz)
70 OVER ALL ( dB ) OCTAVE BAND SOUND PRESSURE LEVEL dB(0dB=0.0002 bar) NC-60 SCALE NC-50 50 NC-40 40 NC-30 30 NC-20 20 APPROXIMATE THRESHOLD HEARING FOR CONTINUOUS NOISE 63 250 500 1000 2000 4000 125 OCTAVE BAND CENTER FREQUENCY (Hz) 8000 A 50Hz 220V(H) 230V(H) 240V(H) 43 50Hz 220V(L) 230V(L) 240V(L) 35

FT60FVM (50Hz)
70 OVER ALL ( dB ) NC-60 60 NC-50 50 NC-40 40 NC-30 30 NC-20 20 APPROXIMATE THRESHOLD HEARING FOR CONTINUOUS NOISE 63 250 500 1000 2000 4000 125 OCTAVE BAND CENTER FREQUENCY (Hz) 8000 SCALE A 50Hz 220V(H) 230V(H) 240V(H) 46 50Hz 220V(L) 230V(L) 240V(L) 36

OCTAVE BAND SOUND PRESSURE LEVEL dB(0dB=0.0002 bar)

60

( B.G.N IS ALREADY RECTIFIED ) OPERATING CONDITIONS POWER SOURCE 220-240V 50Hz

( B.G.N IS ALREADY RECTIFIED ) OPERATING CONDITIONS POWER SOURCE 220-240V 50Hz

JIS STANDARD 50Hz 220-240V(H) 50Hz 220-240V(L)

JIS STANDARD 50Hz 220-240V(H) 50Hz 220-240V(L)

4D045894A

4D045895A

FT50FVM (60Hz)
70 OVER ALL ( dB )

FT60FVM (60Hz)
70 60Hz 220V (L) 35 OVER ALL ( dB ) NC-60 60 NC-50 50 NC-40 40 NC-30 30 NC-20 20 APPROXIMATE THRESHOLD HEARING FOR CONTINUOUS NOISE 63 125 250 500 1000 2000 4000 OCTAVE BAND CENTER FREQUENCY (Hz) 8000 60Hz 220V (H) 47 60Hz 220V (L) 36

OCTAVE BAND SOUND PRESSURE LEVEL dB(0dB=0.0002 bar)

60

SCALE A

OCTAVE BAND SOUND PRESSURE LEVEL dB(0dB=0.0002 bar)

NC-60

60Hz 220V (H) 45

SCALE A

NC-50 50 NC-40 40

( B.G.N IS ALREADY RECTIFIED ) OPERATING CONDITIONS POWER SOURCE 220V 60Hz

( B.G.N IS ALREADY RECTIFIED ) OPERATING CONDITIONS POWER SOURCE 220V 60Hz

JIS STANDARD NC-30 60Hz 220V(H) 60Hz 220V(L) NC-20

JIS STANDARD 60Hz 220V(H) 60Hz 220V(L)

30

20

APPROXIMATE THRESHOLD HEARING FOR CONTINUOUS NOISE 63 125 250 500 1000 2000 4000 OCTAVE BAND CENTER FREQUENCY (Hz) 8000

4D056235

4D056236

10.2.2 Outdoor Units


R50BV1, R60BV1
70
NC-60

R50BVL
OVER ALL ( dB )
OCTAVE BAND SOUND PRESSURE LEVEL dB(0dB=0.0002 bar) 50Hz 220V 54 50Hz 230V 54 50Hz 240V 55 70 OVER ALL(dB)

OCTAVE BAND SOUND PRESSURE LEVEL dB(0dB=0.0002 bar)

NC-60
60

60
NC-50

SCALE A

SCALE A

60Hz 220V 52

NC-50
50

50
NC-40

( B.G.N IS ALREADY RECTIFIED ) OPERATING CONDITIONS

(B.G.N IS ALREADY RECTIFIED) OPERATING CONDITIONS POWER SOURCE 220V 60Hz

40
NC-30

POWER SOURCE

220-240V 50Hz

NC-40
40

JIS STANDARD 60Hz 220V

JIS STANDARD
50Hz 220V 230V 50Hz 240V NC-20

NC-30
30

30

NC-20
20 APPROXIMATE THRESHOLD HEARING FOR CONTINUOUS NOISE 63 125 250 500 1000 2000 4000 OCTAVE BAND CENTER FREQUENCY (Hz) 8000

20

APPROXIMATE THRESHOLD HEARING FOR CONTINUOUS NOISE 63 250 500 1000 2000 4000 125 OCTAVE BAND CENTER FREQUENCY (Hz) 8000

DW527-217H

DW525-587C

R60BVL
70 OVER ALL(dB)

OCTAVE BAND SOUND PRESSURE LEVEL dB(0dB=0.0002 bar)

NC-60
60

SCALE A

60Hz 220V 55

NC-50
50

(B.G.N IS ALREADY RECTIFIED) OPERATING CONDITIONS POWER SOURCE 220V 60Hz

NC-40
40

JIS STANDARD 60Hz 220V

NC-30
30

NC-20
20 APPROXIMATE THRESHOLD HEARING FOR CONTINUOUS NOISE 63 125 250 500 1000 2000 4000 OCTAVE BAND CENTER FREQUENCY (Hz) 8000

DW527-237B

18

Room Air Conditioners F-Series

ED01-707

Electric Characteristics

11. Electric Characteristics


Representative Unit Combination Indoor Unit FT50FVM Outdoor Unit R50BV1 Hz-Volts 50Hz - 220V 50Hz - 230V 50Hz - 240V Power Supply Voltage Range MCA 9.7 MAX. 50Hz 264V MIN. 50Hz 198V 14.3 25 MFA 15 COMP LRA 32 33.5 35 55 57.5 60 42 RLA 7.17 6.88 6.49 10.87 10.38 9.89 10.0 W 53 OFM FLA 0.53 43 53 0.53 W IFM FLA 0.20 0.19 0.18 0.20 0.19 0.18

FT60FVM

R60BV1

FT50FVM

R50BVL 60Hz - 220V MAX. 60Hz 242V MIN. 60Hz 198V

13.1

20

45

0.40 43 0.20

FT60FVM

R60BVL

15.5

25

47

11.7

53

0.63

SYMBOLS: MCA MFA RHz RLA OFM IFM FLA W : MIN. CIRCUIT AMPS (A) : MAX. FUSE AMPS (A) : RATED OPERATING FREQUENCY (Hz) : RATED LOAD AMPS (A) : OUTDOOR FAN MOTOR : INDOOR FAN MOTOR : FULL LOAD AMPS (A) : FAN MOTOR RATED OUTPUT (W)

NOTE: 1. RLA is based on the following conditions. Indoor temp. 27CDB/19CWB Outdoor temp. 35CDB. 2. Maximum allowable voltage variation between phases is 2%. 3. Select wire size based on the larger value of MCA. 4. Instead of fuse, use circuit breaker. 5. MCA / MFA MCA = 1.25 RLA + ea.FLA MFA 2.25 RLA + ea.FLA (Next lower standard fuse rating.Min.15A)

3D040942C

Room Air Conditioners F-Series

19

Installation Manual

ED01-707

12. Installation Manual


Safety Precautions
Read these Safety Precautions carefully to ensure correct installation. This manual classifies the precautions into WARNING and CAUTION. Be sure to follow all the precautions below: they are all important for ensuring safety.
WARNING CAUTION Failure to follow any of WARNING is likely to result in such grave consequences as death or serious injury. Failure to follow any of CAUTION may result in grave consequences in some cases.

The following safety symbols are used throughout this manual:


Be sure to observe this instruction. Be sure to establish an earth connection. Never attempt.

After completing installation, test the unit to check for installation errors. Give the user adequate instructions concerning the use and cleaning of the unit according to the Operation Manual.

WARNING
Installation should be left to the dealer or another professional. Improper installation may cause water leakage, electrical shock, or fire. Install the air conditioner according to the instructions given in this manual. Incomplete installation may cause water leakage, electrical shock, or fire. Be sure to use the supplied or specified installation parts. Use of other parts may cause the unit to come to lose, water leakage, electrical shock, or fire. Install the air conditioner on a solid base that can support the weight of the unit.
An inadequate base or incomplete installation may cause injury in the event the unit falls off the base.

Electrical work should be carried out in accordance with the installation manual and the national electrical wiring rules or code of practice. Insufficient capacity or incomplete electrical work may cause electrical shock or fire. Be sure to use a dedicated power circuit. Never use a power supply shared by another appliance. For wiring, use a cable length enough to cover the entire distance with no connection. Do not use an extension cord. Do not put other loads on the power supply, use a dedicated power circuit. (Failure to do so may cause abnormal heat, electric shock or fire.) Use the specified types of wires for electrical connections between the indoor and outdoor units.
Firmly clamp the interconnecting wires so their terminals receive no external stresses. Incomplete connections or clamping may cause terminal overheating or fire.

After connecting interconnecting and supply wiring be sure to shape the cables so that they do not put undue force on the electrical covers or panels. Install covers over the wires. Incomplete cover installation may cause terminal overheating, electrical shock, or fire. When installing or relocating the system, be sure to keep the refrigerant circuit free from substances other than the specified refrigerant (R22), such as air. (Any presence of air or other foreign substance in the refrigerant circuit causes an abnormal pressure rise or rupture, resulting in injury.) The installation height from the floor must be over 1.8m. If any refrigerant has leaked out during the installation work, ventilate the room.
(The refrigerant produces a toxic gas if exposed to flames.)

After all installation is complete, check to make sure that no refrigerant is leaking out.
(The refrigerant produces a toxic gas if exposed to flames.)

During pump-down, stop the compressor before removing the refrigerant piping. If the compressor is still running and the stop valve is open during
pump-down, air will be sucked in when the refrigerant piping is removed, causing abnormal pressure in the freezer cycle which will lead to breakage and even injury.

During installation, attach the refrigerant piping securely before running the compressor.
If the compressor is not attached and the stop valve is open during pump-down, air will be sucked in when the compressor is run, causing abnormal pressure in the freezer cycle which will lead to breakage and even injury.

Be sure to establish an earth. Do not earth the unit to a utility pipe, arrester, or telephone earth.
Incomplete earth may cause electrical shock, or fire. A high surge current from lightning or other sources may cause damage to the air conditioner.

Be sure to install an earth leakage breaker. Failure to install an earth leakage breaker may result in electric shocks, or fire.

CAUTION
Do not install the air conditioner in a place where there is danger of exposure to inflammable gas leakage.
If the gas leaks and builds up around the unit, it may catch fire.

Establish drain piping according to the instructions of this manual. Inadequate piping may cause flooding. Tighten the flare nut according to the specified method such as with a torque wrench.
If the flare nut is tightened too hard, the flare nut may crack after a long time and cause refrigerant leakage.

Make sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small animals.
Small animals making contact with electrical parts can cause malfunctions, smoke or fire. Please instruct the customer to keep the area around the unit clean.

20

Room Air Conditioners F-Series

ED01-707

Installation Manual

Accessories
A Mounting plate

1 9 2

D Wireless remote controller E Remote controller holder F

1 1 2 2

Indoor unit fixing screws M4 12L

2 1 1 2

Mounting plate fixing screws B M4 25L


C Titanium Apatite

J Insulation tape K Operation manual L Installation manuals

Photocatalytic Air-Purifying Filter

Fixing screws for remote controller holder M3 20L

G AAA dry-cell batteries

Choosing a Site
Before choosing the installation site, obtain user approval.
Indoor unit
The indoor unit should be sited in a place where: the restrictions on installation specified in the indoor unit installation drawings are met, both air intake and exhaust have clear paths met, the unit is not in the path of direct sunlight, the unit is away from the source of heat or steam, there is no source of machine oil vapour (this may shorten indoor unit life), cool air is circulated throughout the room, the unit is away from electronic ignition type fluorescent lamps (inverter or rapid start type) as they may shorten the remote control range, the unit is at least 1 metre away from any television or radio set (unit may cause interference with the picture or sound)

Outdoor unit
The outdoor unit should be sited in a place where: the restrictions on installation specified in the outdoor unit installation diagram are met, drain water causes no trouble or problem in particular, both air intake and exhaust have clear paths of air (they should be free of snow in snowy districts), the unit is in a clear path of air but not directly exposed to rain, strong winds, or direct sunlight, there is no fear of inflammable gas leakage, the unit is no directly exposed to salt, sulfidized gases, or machine oil vapour (they may shorten outdoor unit life). operation noise or hot air flow does not cause trouble to neighbours, the unit is at least 3 metres away from any television or radio antenna. condensation dripping from the stop valve cannot damage anything during operation.

Wireless Remote Controller


Turn on all the fluorescent lamps in the room, if any, and find the site where remote controller signals are properly received by the indoor unit (within 7 metres).

Installation Tips
1. Removing and installing front panel <When there is no work space because the unit is close to ceiling>

Removal method
Hook fingers on the panel protrusions on the left and right of the main body, and open until the panel stops. Slide the front panel sideways to disengage the rotating shaft. Then pull the front panel toward you to remove it.

CAUTION
1) Push up.

Be sure to wear protection gloves. Place both hands under the center of the front grille, and while pushing up, pull it toward you.
2) Pull toward you.

Installation method
Align the tabs of the front panel with the grooves, and push all the way in. Then close slowly. Push the center of the lower surface of the panel firmly to engage the tabs.
Push the rotating shaft of the front panel into the groove.

Installation method
1) Install the front grille and firmly engage the upper hooks (3 locations). 2) Install 3screws of the front grill. 3) Install the air filter and then mount the front panel.

3. How to set the different addresses


mark area (3 locations)

Removal method
1) Remove front panel to remove the air filter. 2) Remove the front grille. (3 screws) 3) In front of the mark of the front grille, there are 3 upper hooks. Lightly pull the front grille toward you with one hand, and push down on the hooks with the fingers of your other hand.

Upper hook

JA Address
EXIST CUT 1 2

Lightly pull the front grille toward you with one hand, and push down on the hooks with the fingers of your other hand. (3 locations)

Push down.

Upper hook

Upper hook

JA

Address

2. Removing and installing front grille

When two indoor units are installed in one room, the two wireless remote controllers can be set for different addresses. 1) In the same way as when connecting to an HA system, remove the metal plate electrical wiring cover. 2) Cut the address jumper (JA). 3) Cut the address jumper (J4).

J4

J4 Address
EXIST CUT 1 2

Room Air Conditioners F-Series

21

Installation Manual

ED01-707

Indoor / Outdoor Unit Installation Drawings


A Mounting plate

How to attach the indoor unit. Hook the claws of the bottom frame to the mounting plate. If the claws are difficult to hook, remove the front grille. How to remove the indoor unit. Push up the marked area (at the lower part of the front grille) to release the claws. If it is difficult to release, remove the front grille.

A Mounting plate Clip Bottom frame Front grille Mark (rear side)

B Mounting plate fixing screws M4 25L (9)

The mounting plate should be installed on a wall which can support the weight of the indoor unit.

30mm or more from ceiling

Caulk pipe hole gap with putty.

Front grille

Cut thermal insulation pipe to an appropriate length and wrap it with tape, making sure that no gap is left in the insulation pipes cut line.

With a multi indoor unit , install as described in the installation manual supplied with the Multi outdoor unit.

50mm or more from walls (on both sides)

Model Max. allowable length

R50/60BV1, R60BVL, R50/60CV1A 30m 15m

R50BVL

Air filters

M4 16L

Wrap the insulation pipe with the finishing tape from bottom to top. Service lid Opening service lid Service lid is opening/closing type. Opening method 1) Remove the service lid screws. 2) Pull out the service lid diagonally down in the direction of the arrow. 3) Pull down.

Max. allowable height Additional refrigerant required for refrigerant pipe exceeding 10m in length. X Y Z Gas pipe 540mm 130mm 330mm

20g/m

C Titanium Apatite Photocatalytic Air-Purifying Filter (2) Tabs (upper 3 locations)

530mm 100mm 290mm

M4 16L

O.D. 15.9mm O.D. 6.4mm

Tabs (lower 3 locations) Insert the upper side of the C Titanium Apatite Photocatalytic Air-Purifying Filter into the tabs (upper 3 locations), push the lower side of the filters up a little and into the tabs (lower 3 locations).

Liquid pipe * Appearance of the outdoor unit may differ from some models.

* Be sure to add the proper amount of additional refrigerant. Failure to do so may result in reduced performance.

D Wireless
remote controller

Before screwing the remote controller holder to the wall, make sure that control signals are properly received by indoor unit.

Service lid

Stop valve cover

E
Insert. Remote controller holder

250m m from

wall

F Fixing screws for


remote controller holder M3 20L (2)

Z
X
bolt-h ole ce ntres)

o lt-h bo ot Fo ntres ce

le

Allow space for piping and electrical servicing.

In sites with poor drainage, use block bases for outdoor unit. Adjust foot height until the unit is leveled. Otherwise, water leakage or pooling of water may occur.

(Foot

Y
(From units side)

Where there is a danger of the unit falling, use foot bolts, or wires.

Appearance of the outdoor unit may differ from some models.

22

Room Air Conditioners F-Series

ED01-707

Installation Manual

Outdoor Unit Installation Guidelines


Where a wall or other obstacle is in the path of outdoor units intake or exhaust airflow, follow the installation guidelines below. With a Multi indoor unit , install as described in the installation manual supplied with the Multi outdoor unit.

Wall facing one side


More than A

Walls facing two sides

More than B

Exhaust More than Top view C

Side view

Walls facing three sides


More than E More than More than D H More than E

More than F Top view

Side view

(mm)
A
R50/60

(mm)
note H 1000 600 300

B 100

C 50

50

150 note 50 H 1000

When Connecting to an HA System


HA cord Tab Tab Push Notched part

Push

Slide HA connector (S21)

Main body

Metal plate electrical cover Screw 1) Remove the metal plate electrical wiring cover. Push Tab 2) Attach the connection cord to the S21 connector and pull the harness out through the notched part in the figure. 3) Replace the electrical wiring cover as it was, and pull the harness around, as shown in the figure.

Room Air Conditioners F-Series

23

Installation Manual

ED01-707

Indoor Unit

INSTALLING THE MOUNTING PLATE

The mounting plate should be installed on a wall which can support the weight of the indoor unit. (1) Temporarily secure the mounting plate to the wall, make sure that the panel is completely level, and mark the boring points on the wall. (2) Secure the mounting plate to the wall with screws.

Recommended mounting-plate retention spots and Dimensions


Recommended mounting plate retention spots (9 spots in all) Place a leveler on raised tab. 125 (Bolt size : M10) (Bolt size : M10) 100 Use tape measure as shown. Position the end of tape measure at .

290

80 52 60

80

83

413.5

44.5 1050

100

99.5

Through the wall Drain hose position hole 80mm

Gas pipe end Liquid pipe end

52

90

(Unit: mm)

BORING A WALL HOLE AND INSTALLING WALL EMBEDDED PIPE

For walls containing metal frame or metal board, be sure to use a wall embedded pipe and wall cover in the feed-through hole to prevent possible heat, electrical shock, or fire. Be sure to caulk the gaps around the pipes with caulking material to prevent water leakage. Inside Outside (1) Bore a feed-through hole of 80mm in the Wall embedded pipe Caulking wall so it has a down slope toward the outside. (field supply) (2) Insert a wall pipe into the hole. (3) Insert a wall cover into wall pipe. 80 Wall hole cover (4) After completing refrigerant piping, wiring, (field supply) and drain piping, caulk pipe hole gap Wall embedded pipe (field supply) with putty.

INSTALLING INDOOR UNIT

Right-Side, Right-Back, or Right-Bottom Piping

(1) Attach the drain hose to the underside of the refrigerant pipes with adhesive vinyl tape. (2) Wrap the refrigerant pipes and drain hose together with insulation tape J .

Remove pipe port cover here for right-side piping Right-bottom piping Remove pipe port cover here for right-bottom piping

Right-back piping Bind coolant pipe and drain hose together with insulating tape.

(3) Pass the drain hose and refrigerant pipes through the wall hole, then set the indoor unit on the mounting plate hooks by using the markings at the top of the indoor unit as a guide.

A Mounting plate

24

Room Air Conditioners F-Series

ED01-707

Installation Manual

(4) Open the front panel, then open the service lid. (Refer to Installation tips.) (5) Pass the inter-unit wiring from the outdoor unit through the feed-through wall hole and then through the back of the indoor unit. Pull them through the front side. Bend the ends of tie wires upward in advance for easier work. (If the inter-unit wiring ends are to be stripped first, bundle wire ends with adhesive tape.) (6) Press the indoor units bottom panel with both hands to set it on the mounting plate hooks. Make sure the wires do not catch on the edge of the indoor unit.

Hang indoor units hook here.

A Mounting plate When stripping the ends of inter-unit wiring in advance, bind right ends of wires with insulating tape.

Inter-unit wiring

Left-Side, Left-Back, or Left-Bottom Piping


(1) Attach the drain hose to the underside of the refrigerant pipes with adhesive vinyl tape.
Remove pipe port cover here for left-side piping Left-side piping Remove pipe port cover here for left-bottom piping Left-bottom piping Left-back piping

(2) Be sure to connect the drain hose to the drain port in place of a drain plug.

How to set drain plug


No g ap
Do not apply lubricating oil (refrigerant oil) when inserting. Application of causes deterioration and drain leakage of the plug. Insert a hexagon wrench (4mm).

(3) Shape the refrigerant pipe along the pipe path marking on the mounting plate. (4) Pass drain hose and refrigerant pipes through the wall hole, then set the indoor unit on mounting plate hooks, using the markings at the top of indoor unit as a guide. (5) Pull in the inter-unit wiring. (6) Connect the inter-unit piping.

Drain hose Caulk this hole with putty or caulking material.

A Mounting plate Wrap insulating tape around the bent portion of refrigerant pipe. Overlap at least half the width of the tape J with each turn.

Bind with plastic tape.

(7) Wrap the refrigerant pipes and drain hose together with insulation tape J . (8) While exercising care so that the inter-unit wiring do not catch indoor unit, press the bottom edge of indoor unit with both hands until it is firmly caught by the mounting plate hooks. Secure indoor unit to the mounting plate with screws (M4 12L).

Drain hose

A Mounting plate Refrigerant pipes

Bottom frame H M4 12L (2 points)

Wall Embedded Piping

Insert drain hose to this depth so it wont be pulled out of drain pipe.

Inner wall

Follow the instructions given under Left-Side, Left-Back, or Left-Bottom pipng . (1) Insert the drain hose to this depth so it wont be pulled out of the drain pipe.

50mm or more

Drain hose Vinyl chloride drain pipe (VP-30)

Outer wall

Room Air Conditioners F-Series

25

Installation Manual

ED01-707

WIRING

With a multi indoor unit , install as described in the installation manual supplied with the Multi outdoor unit.
Terminal block (1) Strip wire ends (15mm). Electrical component box (2) Match wire colours with terminal Shape wires so numbers on indoor and outdoor units that the service lid will fit securely. terminal blocks and firmly screw wires to the corresponding terminals. Firmly secure wire retainer (3) Connect the earth wires to the so that wires sustain no Use the external stress. corresponding terminals. specified Wire retainer wire type. (4) Pull wires to make sure that they are securely latched up, then retain wires with wire retainer. (5) In case of connecting to an adapter system. Run the remote control cable and attach the S21. (Refer to when connecting to an HA system.) (6) Shape the wires so that the service lid fits securely, then close service lid.

Outdoor unit Firmly fix the wires with the terminal screws. When wire length exceeds 10m, use 2.0mm diameter wires. Indoor 1 2 unit 3 H05VV Firmly fix the wires with the terminal screws.
1 23 LN

R50 Max. Fuse Amps 15A

R60 25A

Safety breaker Earth

Earth leakage circuit breaker

Power supply 50Hz 220-240V~ R50/60BV1 R50/60CV1A 60Hz 220V~ : R50/60BVL

WARNING
1) Do not use tapped wires, stranded wires, extensioncords, or starburst connections, as they may cause overheating, electrical shock, or fire. 2) Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the terminal block.) Doing so may cause electric shock or fire.

DRAIN PIPING
(2) Remove the air filters and pour some water into the drain pan to check the water flows smoothly.

(1) Connect the drain hose, as described below


The drain hose should be inclined downward.

No trap is permitted. Do not put the end of the hose in water.

(3) When drain hose requires extension, obtain an extension hose commercially available. Be sure to thermally insulate the indoor section of the extension hose.
Indoor unit drain hose Extension drain hose

Heat insulation tube (Field supply)

(4) When connecting a rigid polyvinyl chloride pipe (nominal diameter 13mm) directly to the drain hose attached to the indoor unit as with embedded piping work, use any commercially available drain socket (nominal diameter 13mm) as a joint.

Drain hose supplied with the indoor unit

Commercially available Commercially available rigid drain socket polyvinyl chloride pipe (nominal diameter 13mm) (nominal diameter 13mm)

26

Room Air Conditioners F-Series

ED01-707

Installation Manual

Outdoor Unit

1 2

INSTALLING OUTDOOR UNIT

For outdoor unit installation, see Choosing a Site , Outdoor unit and Indoor/outdoor Unit Installation Drawings .

FLARING THE PIPE END


(Cut exactly at right angles.) Remove burrs

1. Cut the pipe end with a pipe cutter. 2. Remove burrs with the cut surface facing downward so that the chips do not enter the pipe. 3. Put the flare nut on the pipe. 4. Flare the pipe. 5. Check that the flaring is properly made. WARNING
Incomplete flaring may cause refrigerant gas leakage.

Flaring
Set exactly at the position shown below. A RIGID Die IMPERIAL A 0.5mm 1.0mm

Check
Flares inner surface must be flaw-free.

The pipe end must be evenly flared in a perfect circle. Make sure that the flare nut is fitted.

REFRIGERANT PIPING
Flare nut tightening torque Gas side Liquid side 5/8 inch 61.8-75.4N m (630-770kgf cm) Gas side 5/8 inch 44.1-53.9N m (450-550kgf cm) 1/4 inch 14.2-17.2N m (144-175kgf cm) Liquid side 1/4 inch 21.6-27.4N m (220-280kgf cm) 10.8-14.7N m (110-150kgf cm)

1. Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand. Then tighten them fully with the torque wrenches. Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and escaping gas. 2. To prevent gas leakage, apply refrigeration oil on both inner and outer surfaces of the flare.

Valve cap tightening torque

Service port cap tightening torque

Cautions on Pipe Handling


Protect the open end of the pipe against dust and moisture. All pipe bends should be as gentle as possible. Use a pipe bender for bending. (Bending radius should be 30 to 40mm or larger.)
Be sure to place a cap. Rain If no flare cap is available, cover the flare mouth with tape to keep dirt or water out. Wall

Selection of Copper and Heat Insulation materials


When using commercial copper pipes and fittings, observe the following: Insulation material: Polyethylene foam Heat transfer rate: 0.041 to 0.052W/mK (0.035 to 0.045kcal/mhC) Refrigerant gas pipes surface temperature reaches 110C max. Choose heat insulation materials that will withstand this temperature. Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below.
Gas side O.D.15.9mm Thickness 1.0mm Liquid side O.D.6.4mm Thickness 0.8mm Gas pipe thermal insulation I.D.16-20mm Liquid pipe thermal insulation I.D.8-10mm

Thickness 10mm min


Gas pipe Inter-unit wiring Liquid pipe

Use separate thermal insulation pipes for gas and liquid refrigerant pipes.

Gas pipe insulation

Liquid pipe insulation Finishing tape Drain hose

Room Air Conditioners F-Series

27

Installation Manual

ED01-707

PURGING AIR AND CHECKING GAS LEAKAGE


WARNING
Refrigerant gas leaks during air purging, ventilate the room as soon as possible.

WARNING
Do not mix any substance other than the specified refrigerant (R22) into the refrigeration cycle.

To prevent air pollution, a vacuum pump should be used for air purging wherever possible.

If using additional refrigerant, perform air purging from the refrigerant pipes and indoor unit using a vacuum pump, then charge additional refrigerant. Use a hexagonal wrench (4mm) to operate the stop valve rod. All refrigerant pipe joints should be tightened with a torque wrench at the specified tightening torque.

Pressure meter Compound pressure gauge Gauge manifold High-pressure valve Valve caps Liquid stop valve

Low-pressure valve Charging hoses

Vacuum pump *1. Pipe length vs. vacuum pump run time Pipe length Run time Up to 15 metres More than 15 metres

Service port

Gas stop valve

*2. If the compound pressure gauge pointer swings back, refrigerant may have water content or a loose pipe joint may exists. Check all pipe joints and retighten nuts as Not less than 10 min. Not less than 15 min. needed, then repeat steps (2) through (4).

(1) Connect projection side of charging hose (which comes from gauge manifold) to gas stop valves service port.

(2) Fully open gauge manifolds low-pressure valve (Lo) and completely close its high-pressure valve (Hi). (High-pressure valve subsequently requires no operation.)

(3) Do vacuum pumping and make sure that the compound pressure gauge reads -0.1MPa (-76cmHg)*1.

(4) Close gauge manifolds low-pressure valve (Lo) and stop vacuum pump. (Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not swing back.)*2

(5) Remove covers from liquid stop value and gas stop valve.

(6) Turn the liquid stop valves rod 90 degrees counterclockwise with a hexagonal wrench to open valve. Close it after 5 seconds, and check for gas leakage. Using soapy water, check for gas leakage from indoor units flare and outdoor units flare and valve rods. After the check is complete, wipe all soapy water off.

(7) Disconnect charging hose from gas stop valves service port, then fully open liquid and gas stop valves. (Do not attempt to turn valve rod beyond its stop.)

(8) Tighten valve caps and service port caps for the liquid and gas stop valves with a torque wrench at the specified torques.

5
Firmly tighten terminal screws. For wire termination at terminal block, see the figure at right. For wire stripping, see the figure at rigth.
Strip wire and this point. Excessive strip length may cause electrical shock or leskage. Wire

WIRING
Terminal block inter-unit wiring terminal block Supply terminal block

For inter-unit wiring connections, see Indoor Unit , 4. WIRING .


Firmly secure wire retainer so wire teminations will not receive external stress. Use the specified wire type for all connecitions.

Wire retaine

Shape wires so that the service lid fits securely.

Be sure to estabish. Do not earth the utiilty pipe, arrester, or telephone earth.

28

Room Air Conditioners F-Series

ED01-707

Installation Manual

DRAIN WORK

If the drain port is covered by a mounting base or floor surface, place additional foot bases of at least 30mm in height under the outdoor units feet. In cold areas, do not use a drain hose with the outdoor unit. (Otherwise, drain water may freeze, impairing heating performance.)

TRIAL OPERATION AND TESTING


Trial Operation and Testing
(1) Measure the supply voltage and make sure that it falls in the specified range. (2) Trial operation should be carried out in either cooling mode.

Trial operation from Remote Controller


(1) Press ON/OFF button to turn on the system. (2) Simultaneously press center of TEMP button and MODE button. (3) Press MODE button twice. ( will appear on the display to indicate that Trial Operation mode is selected.) (4) Trial run mode terminates in approx. 30 minutes and switches into normal mode. To quit a trial operation, press ON/OFF button.

Select the lowest programmable temperature Trial operation in cooling mode may be disabled depending on the room temperature. Use the remote control for trial operation as described below. After trial operation is complete, set the temperature to a normal level (26C to 28C). For protection, the system disables restart operation for 3 minutes after it is turned off. (3) Carry out the test operation in accordance with the Operation Manual to ensure that all functions and parts, such as louver movement, are working properly. * The air conditioner requires a small amount of power in its standby mode. If the system is not to be used for some time after installation, shut off the circuit breaker to eliminate unnecessary power consumption. * If the circuit breaker trips to shut off the power to the air conditioner, the system will restore the original operation mode when the circuit breaker is opened again.

Test Items
Test Items Indoor and outdoor units are installed properly on solid bases. No refrigerant gas leaks. Refrigerant gas and liquid pipes and indoor drain hose extension are thermally insulated. Draining line is properly installed. System is properly earthed. The specified wires are used for inter-unit wiring connections. Indoor or outdoor units air intake or exhaust has clear path of air. Stop valves are opened. Indoor unit properly receives remote control commands. Symptom (diagnostic display on RC) Fall, vibration, noise Incomplete cooling function Water leakage Water leakage Electrical leakage Inoperative or burn damage (U4) Incomplete cooling function (E5) Inoperative Check

3P192027-4

Room Air Conditioners F-Series

29

Operation Manual

ED01-707

13. Operation Manual

Safety precautions
Keep this manual where the operator can easily find them. Read this manual attentively before starting up the unit. For safety reason the operator must read the following cautions carefully. This manual classifies precautions into WARNING and CAUTION. Be sure to follow all precautions below: they are all important for ensuring safety.

WARNING

CAUTION

If you do not follow these instructions exactly, the unit may If you do not follow these instructions exactly, the unit may cause property damage, personal injury or loss of life. cause minor or moderate property damage or personal injury.

Never do. Be sure to earth the air conditioner. Never touch the air conditioner (including the remote controller) with a wet hand.

Be sure to follow the instructions. Never cause the air conditioner (including the remote controller) to get wet.

WARNING
In order to avoid fire, explosion or injury, do not operate the unit when harmful, among which flammable or corrosive gases, are detected near the unit. It is not good for health to expose your body to the air flow for a long time. Do not put a finger, a rod or other objects into the air outlet or inlet. As the fan is rotating at a high speed, it will cause injury. Do not attempt to repair, relocate, modify or reinstall the air conditioner by yourself. Incorrect work will cause electric shocks, fire etc. For repairs and reinstallation, consult your Daikin dealer for advice and information. The refrigerant used in the air conditioner is safe. Although leaks should not occur, if for some reason any refrigerant happens to leak into the room, make sure it does not come in contact with any flame as of gas heaters, kerosene heaters or gas range. If the air conditioner is not cooling properly, the refrigerant may be leaking, so call your dealer. When carrying out repairs accompanying adding refrigerant, check the content of the repairs with our service staff. Do not attempt to install the air conditioner by your self. Incorrect work will result in water leakage, electric shocks or fire. For installation, consult the dealer or a qualified technician. In order to avoid electric shock, fire or injury, if you detect any abnormally such as smell of fire, stop the operation and turn off the breaker. And call your dealer for instructions.

CAUTION
The air conditioner must be earthed. Incomplete earthing may result in electric shocks. Do not connect the earth line to a gas pipe, water pipe, lightning rod, or a telephone earth line. In order to avoid any quality deterioration, do not use the unit for cooling precision instruments, food, plants, animals or works of art. Never expose little children, plants or animals directly to the air flow. Do not place appliances which produce open fire in places exposed to the air flow from the unit or under the indoor unit. It may cause incomplete combustion or deformation of the unit due to the heat. Do not block air inlets nor outlets. Impaired air flow may result in insufficient performance or trouble.

30

Room Air Conditioners F-Series

ED01-707

Operation Manual

Do not stand or sit on the outdoor unit. Do not place any object on the unit to avoid injury. Do not place anything under the indoor or outdoor unit that must be kept away from moisture. In certain conditions, moisture in the air may condense and drip. After a long use, check the unit stand and fittings for damage. Do not touch the air inlet and alminum fins of outdoor unit. It may cause injury. The appliance is not intended for use by young children or infirm persons without supervision. Young children should be supervised to ensure that they do not play with the appliance. To avoid oxygen deficiency, ventilate the room sufficiently if equipment with burner is used together with the air conditioner. Before cleaning, be sure to stop the operation, turn the breaker off or pull out the supply cord. Do not connect the air conditioner to a power supply different from the one as specified. It may cause trouble or fire. Depending on the environment, an earth leakage breaker must be installed. Lack of an earth leakage breaker may result in electric shocks. Arrange the drain hose to ensure smooth drainage. Incomplete draining may cause wetting of the building, furniture etc. Do not place objects in direct proximity of the outdoor unit and do not let leaves and other debris accumulate around the unit. Leaves are a hotbed for small animals which can enter the unit. Once in the unit, such animals can cause malfunctions, smoke or fire when making contact with electrical parts. Do not operate the air conditioner with wet hands.

Do not wash the indoor unit with excessive water, only use a slightly wet cloth. Do not place things such as vessels containing water or anything else on top of the unit. Water may penetrate into the unit and degrade electrical insulations, resulting in an electric shock.

Installation site.
To install the air conditioner in the following types of environments, consult the dealer. Places with an oily ambient or where steam or soot occurs. Salty environment such as coastal areas. Places where sulfide gas occurs such as hot springs. Places where snow may block the outdoor unit. The drain from the outdoor unit must be discharged to a place of good drainage.

Consider nuisance to your neighbours from noises.


For installation, choose a place as described below. A place solid enough to bear the weight of the unit which does not amplify the operation noise or vibration. A place from where the air discharged from the outdoor unit or the operation noise will not annoy your neighbours.

Electrical work.
For power supply, be sure to use a separate power circuit dedicated to the air conditioner.

System relocation.
Relocating the air conditioner requires specialized knowledge and skills. Please consult the dealer if relocation is necessary for moving or remodeling.

Room Air Conditioners F-Series

31

Operation Manual

ED01-707

Names of parts
Indoor Unit

3 2 1

10

8 7

11 12

14 13

32

Room Air Conditioners F-Series

ED01-707

Operation Manual

Outdoor Unit
15

17 16 19 18 20

Indoor Unit
1. Air filter 2. Titanium Apatite Photocatalytic Air-Purifying Filter 3. Air inlet 4. Front panel 5. Panel tab 6. Room temperature sensor: It senses the air temperature around the unit. 7. Display 8. Air outlet 9. Flap (horizontal blade): (page 12.) 10. Louvers (vertical blades): The Louvers are inside of the air outlet. (page 12.) 11. Operation lamp (green) 12. TIMER lamp (yellow): (page 14.) 13. Indoor Unit ON/OFF switch: Push this switch once to start operation. Push once again to stop it. The operation mode refer to the following table. Mode
COOL

Temperature setting 22C

Air flow rate


AUTO

This switch is useful when the remote controller is missing. 14. Signal receiver: It receives signals from the remote controller. When the unit receives a signal, you will hear a short beep. Operation start .............beep-beep Settings changed..........beep Operation stop ..............beeeeep

Outdoor Unit
15. Air inlet: (Back and side) 16. Air outlet 17. Refrigerant piping and inter-unit cable 18. Drain hose 19. Earth terminal: It is inside of this cover. 20. Stop valve: Dew condensation may form on the stop valve during operation. This does not indicate any type of malfunction in the outdoor unit.

Appearance of the outdoor unit may differ from some models.

Room Air Conditioners F-Series

33

Operation Manual

ED01-707

Remote Controller
1

4 3 6 5 7 8

12 14

11 10

13

< ARC433A73 >


1. Signal transmitter: It sends signals to the indoor unit. 2. Display: It displays the current settings. (In this illustration, each section is shown with all its displays ON for the purpose of explanation.) 3. POWERFUL button: POWERFUL operation (page 13.) 4. TEMPERATURE adjustment buttons: It changes the temperature setting. 5. ON/OFF button: Press this button once to start operation. Press once again to stop it. 6. MODE selector button: It selects the operation mode. (DRY/COOL/FAN) (page 10.) 7. FAN setting button: It selects the air flow rate setting. 8. SWING button: (page 12.) Flap (Horizontal blade) 9. ON TIMER button: (page 15.) 10. OFF TIMER button: (page 14.) 11. TIMER Setting button: It changes the time setting. 12. TIMER CANCEL button: It cancels the timer setting. 13. CLOCK button: (page 9.) 14. RESET button: Restart the unit if it freezes. Use a thin object to push.

34

Room Air Conditioners F-Series

ED01-707

Operation Manual

Preparation Before Operation


To set the batteries
1. Slide the front cover to take it off. 2. Set two dry batteries (AAA). 3. Set the front cover as before.
Position + and correctly!

3 1

ATTENTION
About batteries When replacing the batteries, use batteries of the same type, and replace the two old batteries together. When the system is not used for a long time, take the batteries out. We recommend replacing once a year, although if the remote controller display begins to fade or if reception deteriorates, please replace with new alkali batteries. Using manganese batteries reduces the lifespan. The attached batteries are provided for the initial use of the system. The usable period of the batteries may be short depending on the manufactured date of the air conditioner.

Room Air Conditioners F-Series

35

Operation Manual

ED01-707

Preparation Before Operation


To operate the remote controller
To use the remote controller, aim the transmitter at the indoor unit. If there is anything to block signals between the unit and the remote controller, such as a curtain, the unit will not operate. Do not drop the remote controller. Do not get it wet. The maximum distance for communication is about 7m.

Receiver

To fix the remote controller holder on the wall


1. Choose a place from where the signals reach the unit. 2. Fix the holder to a wall, a pillar, or similar location with the screws procured locally. 3. Place the remote controller in the remote controller holder.
To remove, pull it upwards. Remote controller holder Set.

ATTENTION
About remote controller Never expose the remote controller to direct sunlight. Dust on the signal transmitter or receiver will reduce the sensitivity. Wipe off dust with soft cloth. Signal communication may be disabled if an electronic-starter-type fluorescent lamp (such as inverter-type lamps) is in the room. Consult the shop if that is the case. If the remote controller signals happen to operate another appliance, move that appliance to somewhere else, or consult the shop.

36

Room Air Conditioners F-Series

ED01-707

Operation Manual

To set the clock


1. Press CLOCK button.
is displayed. blinks.

2. Press TIMER setting button to set the clock to the present time.
Holding down or button rapidly increases or decreases the time display.

3. Press CLOCK button.


blinks.

Turn the breaker ON


Turning ON the breaker opens the flap, then closes it again. (This is a normal procedure.)

1, 3

NOTE
Tips for saving energy
Be careful not to cool the room too much. Keeping the temperature setting at a moderate level helps save energy. Cover windows with a blind or a curtain. Blocking sunlight and air from outdoors increases the cooling effect. Clogged air filters cause inefficient operation and waste energy. Clean them once in about every two weeks.
Recommended temperature setting For cooling: 26C 28C

Please note
The air conditioner always consumes 15-35 watts of electricity even while it is not operating. If you are not going to use the air conditioner for a long period, for example in spring or autumn, turn the breaker OFF. Use the air conditioner in the following conditions.
Mode COOL Operating conditions Outdoor temperature: 20 to 46C Indoor temperature: 18 to 32C Indoor humidity: 80% max. Outdoor temperature: 20 to 46C Indoor temperature: 18 to 32C Indoor humidity: 80% max. If operation is continued out of this range A safety device may work to stop the operation. Condensation may occur on the indoor unit and drip. A safety device may work to stop the operation. Condensation may occur on the indoor unit and drip.

DRY

Operation outside this humidity or temperature range may cause a safety device to disable the system.

Room Air Conditioners F-Series

37

Operation Manual

ED01-707

DRY COOL FAN Operation


The air conditioner operates with the operation mode of your choice. From the next time on, the air conditioner will operate with the same operation mode.

To start operation
1. Press MODE selector button and select a operation mode.
Each pressing of the button advances the mode setting in sequence. : DRY : COOL : FAN

4 2, 3 1

2. Press ON/OFF button.


The OPERATION lamp lights up.

To stop operation
3. Press ON/OFF button again.
Then OPERATION lamp goes off.

To change the temperature setting


4. Press TEMPERATURE adjustment button.
DRY or FAN mode COOL mode Press The temperature setting is not variable. to raise the temperature and press

to lower the temperature.

Set to the temperature you like.

10

38

Room Air Conditioners F-Series

ED01-707

Operation Manual

To change the air flow rate setting


5. Press FAN setting button.
DRY mode COOL or FAN mode Five levels of air flow rate setting from plus The air flow rate setting is not variable. are available. to

NOTE
Note on COOL operation This air conditioner cools the room by blowing the hot air in the room outside, so if the outside temperature is high, performance drops. Note on DRY operation The computer chip works to rid the room of humidity while maintaining the temperature as much as possible. It automatically controls temperature and fan strength, so manual adjustment of these functions is unavailable. Note on air flow rate setting At smaller air flow rates, the cooling effect is also smaller.

11

Room Air Conditioners F-Series

39

Operation Manual

ED01-707

Adjusting the Air Flow Direction


You can adjust the air flow direction to increase your comfort.

To adjust the horizontal blade (flap)


1. Press SWING button
is displayed on the LCD.

2. When the flap has reached the desired position, press SWING button once more.
The flap will stop moving. disappears from the LCD.

1, 2

To adjust the vertical blades (louvers)


Hold the knob and move the louvers. (You will find a knob on the left-side and the right-side blades.)

Notes on flaps and louvers angles


When SWING button is selected, the flaps swinging range depends on the operation mode. (See the figure.) ATTENTION Always use a remote controller to adjust the flaps angle. If you attempt to move it forcibly with hand when it is swinging, the mechanism may be broken. Be careful when adjusting the louvers. Inside the air outlet, a fan is rotating at a high speed.
In COOL or DRY mode

STOP COOL approx. 10~40 DRY approx. 5~35

In FAN mode

STOP FAN approx. 5~55

12

40

Room Air Conditioners F-Series

ED01-707

Operation Manual

POWERFUL Operation
POWERFUL operation quickly maximizes the cooling effect in any operation mode. You can get the maximum capacity.

To start POWERFUL operation


1. Press POWERFUL button.
POWERFUL operation ends in 20 minutes. Then the system automatically operates again with the settings which were used before POWERFUL operation. When using Powerful operation, there are some functions which are not available. is displayed on the LCD.

1, 2

To cancel POWERFUL operation


2. Press POWERFUL button again.
disappears from the LCD.

NOTE
Notes on POWERFUL operation POWERFUL Operation can only be set when the unit is running. Pressing the operation stop button causes the settings to be canceled, and the disappears from the LCD. In COOL mode The air flow rate is fixed to the maximum setting. The temperature and air flow settings are not variable. In DRY mode The temperature setting is lowered by 2.5C and the air flow rate is slightly increased. In FAN mode The air flow rate is fixed to the maximum setting.

13

Room Air Conditioners F-Series

41

Operation Manual

ED01-707

TIMER Operation
Timer functions are useful for automatically switching the air conditioner on or off at night or in the morning. You can also use OFF TIMER and ON TIMER in combination.

To use OFF TIMER operation


Check that the clock is correct. If not, set the clock to the present time. (page 9.)

1. Press OFF TIMER button.


is displayed. blinks.

2. Press TIMER Setting button until the time setting reaches the point you like.
Every pressing of either button increases or decreases the time setting by 10 minutes. Holding down either button changes the setting rapidly.

2 4

3. Press OFF TIMER button again.


The TIMER lamp lights up.

1, 3

To cancel the OFF TIMER Operation


4. Press CANCEL button.
The TIMER lamp goes off.

NOTE
When TIMER is set, the present time is not displayed. Once you set ON, OFF TIMER, the time setting is kept in the memory. (The memory is canceled when remote controller batteries are replaced.) When operating the unit via the ON/OFF Timer, the actual length of operation may vary from the time entered by the user. (Maximum approx. 10 minutes) NIGHT SET MODE When the OFF TIMER is set, the air conditioner automatically adjusts the temperature setting (0.5C up in COOL) to prevent excessive cooling for your pleasant sleep.

14

42

Room Air Conditioners F-Series

ED01-707

Operation Manual

To use ON TIMER operation


Check that the clock is correct. If not, set the clock to the present time. (page 9.)

1. Press ON TIMER button.


is displayed. blinks.

2. Press TIMER Setting button until the time setting reaches the point you like.
Every pressing of either button increases or decreases the time setting by 10 minutes. Holding down either button changes the setting rapidly.

3. Press ON TIMER button again.


The TIMER lamp lights up.

1, 3 4 2

To cancel ON TIMER operation


4. Press CANCEL button.
The TIMER lamp goes off.

To combine ON TIMER and OFF TIMER


A sample setting for combining the two timers is shown below.

(Example)
Present time: 11:00 p.m. (The unit operating) OFF TIMER at 0:00 a.m. ON TIMER at 7:00 a.m.
Display

Combined

ATTENTION
In the following cases, set the timer again. After a breaker has turned OFF. After a power failure. After replacing batteries in the remote controller.

15

Room Air Conditioners F-Series

43

Operation Manual

ED01-707

Care and Cleaning


CAUTION Units Indoor unit, Outdoor unit and Remote controller
1. Wipe them with dry soft cloth. Before cleaning, be sure to stop the operation and turn the breaker OFF.

Front panel
1. Open the front panel.
Hold the panel by the tabs on the two sides and lift it until it stops with a click.

2. Remove the front panel.


Open the front panel further while sliding it to either the left or right and pulling it toward you. This will disconnect the rotation dowel on one side. Then disconnect the rotation dowel on the other side in the same manner.

3. Clean the front panel.


Wipe it with a soft cloth soaked in water. Only neutral detergent may be used. In case of washing the panel with water, dry it with cloth, dry it up in the shade after washing.

4. Attach the front panel.


Align the rotation dowels on the left and right of the front panel with the slots, then push them all the way in. Close the front panel slowly. (Press the panel at both sides and the center.)

CAUTION
Dont touch the metal parts of the indoor unit. If you touch those parts, this may cause an injury. When removing or attaching the front panel, use a robust and stable stool and watch your steps carefully. When removing or attaching the front panel, support the panel securely with hand to prevent it from falling. For cleaning, do not use hot water above 40C, benzine, gasoline, thinner, nor other volatile oils, polishing compound, scrubbing brushes, nor other hand stuff. After cleaning, make sure that the front panel is securely fixed.

16

44

Room Air Conditioners F-Series

ED01-707

Operation Manual

Filters
1. Open the front panel. (page 16.) 2. Pull out the air filters.
Push a little upwards the tab at the center of each air filter, then pull it down.

3. Take off the Titanium Apatite Photocatalytic Air-Purifying Filter.


Press the top of the aircleaning filter onto the tabs (3 tabs at top). Then press the bottom of the filter up slightly, and press it onto the tabs (3 at bottom).

tabs (3 tabs at top)

tabs (3 at bottom)

4. Clean or replace each filter.


See figure.

5. Set the air filter and the Titanium Apatite Photocatalytic Air-Purifying Filter as they were and close the front panel.
Press the front panel at both sides and the center.

Air Filter
1. Wash the air filters with water or clean them with vacuum cleaner.
If the dust does not come off easily, wash them with neutral detergent thinned with lukewarm water, then dry them up in the shade. It is recommended to clean the air filters every two weeks.

Titanium Apatite Photocatalytic Air-purifying Filter


The Titanium Apatite Photocatalytic Air-Purifying Filter can be renewed by washing it with water once every 6 months. We recommend replacing it once every 3 years.

[ Maintenance ]
1. 2. 3. 4. Remove dust with a vacuum cleaner and wash lightly with water. If it is very dirty, soak it for 10 to 15 minutes in water mixed with a neutral cleaning agent. After washing, shake off remaining water and dry in the shade. Since the material is made out of polyester, do not wring out the filter when removing water from it.

[ Replacement ]
1. Remove the tabs on the filter frame and replace with a new filter.
Dispose of the old filter as non-flammable waste.

17

Room Air Conditioners F-Series

45

Operation Manual

ED01-707

NOTE
Operation with dirty filters: (1) cannot deodorize the air. (2) cannot clean the air. (3) results in poor cooling. (4) may cause odour. To order Titanium Apatite Photocatalytic Air-Purifying Filter contact to the service shop there you bought the air conditioner. Dispose of old filters as non-flammable waste. Item Titanium Apatite Photocatalytic Air-Purifying Filter (without frame) 1 set Part No. KAF952B42

Check
Check that the base, stand and other fittings of the outdoor unit are not decayed or corroded. Check that nothing blocks the air inlets and the outlets of the indoor unit and the outdoor unit. Check that the drain comes smoothly out of the drain hose during COOL or DRY operation. If no drain water is seen, water may be leaking from the indoor unit. Stop operation and consult the service shop if this is the case.

Before a long idle period


1. Operate the FAN only for several hours on a fine day to dry out the inside.
Press MODE button and select FAN operation. Press ON/OFF button and start operation.

2. After operation stops, turn off the breaker for the room air conditioner. 3. Clean the air filters and set them again. 4. Take out batteries from the remote controller. 18

46

Room Air Conditioners F-Series

ED01-707

Operation Manual

Trouble Shooting
These cases are not troubles.
The following cases are not air conditioner troubles but have some reasons. You may just continue using it.

Case
Operation does not start soon. When ON/OFF button was pressed soon after operation was stopped. When the mode was reselected. The outdoor unit emits water or steam. Mist comes out of the indoor unit.

Explanation
This is to protect the air conditioner. You should wait for about 3 minutes.

In COOL or DRY mode Moisture in the air condenses into water on the cool surface of outdoor unit piping and drips. This happens when the air in the room is cooled into mist by the cold air flow during cooling operation.

The indoor unit gives out odour. This happens when smells of the room, furniture, or cigarettes are absorbed into the unit and discharged with the air flow. (If this happens, we recommend you to have the indoor unit washed by a technician. Consult the service shop where you bought the air conditioner.) The outdoor fan rotates while the air conditioner is not in operation. After operation is stopped: The outdoor fan continues rotating for another 60 seconds for system protection. While the air conditioner is not in operation: When the outdoor temperature is very high, the outdoor fan starts rotating for system protection. For system protection, the air conditioner may stop operating on a sudden large voltage fluctuation. It automatically resumes operation in about 3 minutes.

The operation stopped suddenly. (OPERATION lamp is on.)

19

Room Air Conditioners F-Series

47

Operation Manual

ED01-707

Check again.
Please check again before calling a repair person.

Case
The air conditioner does not operate. (OPERATION lamp is off.) Cooling effect is poor.

Check
Hasnt a breaker turned OFF or a fuse blown? Isnt it a power failure? Are batteries set in the remote controller? Is the timer setting correct?

Are the air filters clean? Is there anything to block the air inlet or the outlet of the indoor and the outdoor units? Is the temperature setting appropriate? Are the windows and doors closed? Are the air flow rate and the air direction set appropriately? Are the air filters clean? Is there anything to block the air inlet or the outlet of the indoor and the outdoor units? Clean the air filters or take all obstacles away and turn the breaker OFF. Then turn it ON again and try operating the air conditioner with the remote controller. If the lamp still blinks, call the service shop where you bought the air conditioner. The air conditioner may malfunction with lightning or radio waves. Turn the breaker OFF, turn it ON again and try operating the air conditioner with the remote controller.

Operation stops suddenly. (OPERATION lamp flashes.)

An abnormal functioning happens during operation.

20

48

Room Air Conditioners F-Series

ED01-707

Operation Manual

Call the service shop immediately.

WARNING
When an abnormality (such as a burning smell) occurs, stop operation and turn the breaker OFF. Continued operation in an abnormal condition may result in troubles, electric shocks or fire. Consult the service shop where you bought the air conditioner. Do not attempt to repair or modify the air conditioner by yourself. Incorrect work may result in electric shocks or fire. Consult the service shop where you bought the air conditioner.

If one of the following symptoms takes place, call the service shop immediately.

After a power failure The air conditioner automatically resumes operation in about 3 minutes. You should just wait for a while.

Lightning If lightning may strike the neighbouring area, stop operation and turn the breaker OFF for system protection.

We recommend periodical maintenance.


In certain operating conditions, the inside of the air conditioner may get foul after several seasons of use, resulting in poor performance. It is recommended to have periodical maintenance by a specialist aside from regular cleaning by the user. For specialist maintenance, contact the service shop where you bought the air conditioner. The maintenance cost must be born by the user.

21
3P192025-3

Room Air Conditioners F-Series

49

Optional Accessories

ED01-707

14. Optional Accessories


14.1 Option List
Option Name 1 2 3 4 5 Centralized Control Board-Up to 5 Rooms 1 Wiring Adaptor for Time Clock / Remote Control 2 (Normal Open Pulse Contact / Normal Open Contact) Titanium Apatite Photocatalytic Air-Purifying Filter The Remote Controller Loss Prevention with the Chain Drain Plug Kit Name KRC72 KRP413A1S KAF952B42 KKF917A4 KKP937A4 Applicable Model Indoor Unit Indoor Unit Indoor Unit Indoor Unit Outdoor Unit

Note:

1 Wiring adaptor is also required for each indoor unit. 2 Time clock and other devices ; obtained locally.

50

Room Air Conditioners F-Series

ED01-707

Optional Accessories

14.2 Installation Manual


14.2.1 KRP413A1S
Safety Precautions
Read these safety precautions carefully before installing the unit, and be sure to install the unit properly. This manual classifies precautions to the user into the following two categories. These warnings and cautions are for your safety. Follow them. WARNING CAUTION
Faulty installation can result in death or serious injury Faulty installation can result in serious injury or other serious consequences.

1. Functions and Features


On/Off setting Switching between Instantaneous Contact/Normal Contact Connection with five-room central controller (KRC72 for oversea model) Connection with fan coil remote controller Automatic reset after power failure Output of normal operation signals/malfunction signals

Below is a key to symbols used in this manual.


Be sure to follow instructions. Be sure to perform grounding work. Never attempt.

2. Field Wiring
For interconnecting wiring, use Daikin KDC100A12 cable (not supplied) or other similar cable. The cable should have the specifications shown below. Optional cable KDC100A12 (without connectors) Specifications: 0.2 mm2 4 core (sheathed) Outer diameter: 5.3 Length: 100 m Colour: Grey Other cable (commercially available)
Item Cable for instrumentation (IPVV) 0.3 mm2 4-core Microphone cord (MVVS) 0.3 mm2 4-core Microphone cord (MVVS) 0.2 mm2 4-core Microphone cord (MVVS) 0.15 mm2 4-core Intercom cable 0.65 mm2 dia. 4-core PVC jumper wire (TJVC) (from 0.5 mm dia. 4 pcs.) Not sheathed Outer dia. 7.2 mm 8.0 mm 6.5 mm 4.8 mm Shielded Remarks Hard sheath

After installation is complete, test the unit to confirm that it is working properly, and instruct the owner its proper use.

WARNING
Installation should be left to the dealer from whom you purchased the unit, or another qualified professionals. Install the unit securely according to the installation manual. Faulty installation may lead to electric shock or fire. Be sure to use the supplied or specified parts. Using other parts may lead to electric shock or fire. Install the unit securely in a location that will support its weight. If installed in a poor location or improperly installed, the unit may not work as intended. For electrical work, follow local electric standards and the installation manual. Faulty installation may lead to fire or electric shock. Do not bundle the power cord, or attempt to extend it by splicing it with another cord or by using an extension cord. Do not place any other load on the power circuit used for the unit. Improper wiring may lead to electric shock, heat generation or fire. Use dedicated wiring for all electrical connections, and be sure to arrange the wiring so that force applied to the wiring will not damage the terminals. Poor wiring or installation may cause electric shock, heat generation or fire.

Note 1: Keep any wiring for the control unit away from the power cord to prevent electrical noise. Note 2: Do not use cables shown above for power cord, inter-unit cord/cable or power cord for lamps.

CAUTION
Before installation, unplug the air conditioner to ensure safety. Failure to do so may cause electric shock. Static electricity may damage electric components. Before connecting cables and communication lines, and operating the switches, be sure to discharge any electrical charge from your body (by, for example, touching the earth line) Do not install the unit in a location where it may be exposed to flammable gases. If gas leaks and build up around the unit, it may catch fire. Do not place the wiring close to the power cord, inter-unit cable, or pipes which generate noise. Treat the wiring with care.

Room Air Conditioners F-Series

51

Optional Accessories

ED01-707

Installation
This product is available in two types. The KRP413A1S KRP413AA1S is for installation in a case independent of the indoor unit, and the KRP413A1 is for installation within the indoor unit.

1. KRP413A1S KRP413AA1S
1 Installation diagram
Adaptor case Indoor unit PCB

3. Attaching Adaptor Case Assy (for KRP413A1S KRP413AA1S)


1 Using the screws (to mount on a wall, etc.)

Use the 3 supplied screws to attach the case assy .

S21

Adaptor case Indoor unit


wiring Local wiring or power cord, etc.

Install the adaptor case assy as close to the indoor unit as possible. Removing case front
Case front

Components
Wiring (approx. 0.8 m)
Adaptor PCB

Adaptor case assy (Adaptor (PCB) is attached in the adaptor case.)

Screw Screw cover

Accessories Binding band (4 pcs.) Securing tape for attaching to the indoor unit (2 sets) Screws for attaching the adaptor case (4 pcs.) Screws for attaching to the wall (3 pcs.) Installation manual

Remove the screw cover, one of the screws and then the case front. Attach the case back to the surface by tightening the screws through the screw holes (one round hole, two long holes). After connecting the cables (refer to the following sections), replace the case front. Be careful not to damage the wiring in the case.
Press in so that the prong catches the case back. Wiring

2. KRP413A1
For this type, install the adaptor PCB within the indoor unit. The method of installation and connection vary depending on the model of the air conditioner. See your air conditioner installation manual for details.
Screw

Components
Wiring (approx. 0.25 m)

Screw cover

Adaptor PCB

Using securing tape (to attach on the indoor unit)

Installation manual

Attach the adaptor case with the supplied securing tape. Remove the case front (as for mounting on a wall). After connecting the cables (see the following sections), replace the case front. It can be screwed to the case back from the rear with the four supplied screws. Be careful not to damage the wiring in the case. Attach the hook side (loop side) of the included securing tape to the rear surface of the HA case, then attach the loop side (hook side) to the top of the air conditioner unit spaced at the same intervals.

Securing tape Hook side (loop side)

Securing tape Loop side (hook side) Indoor unit

To prevent the adaptor case assy from falling, do not use the securing tape for attaching it to a wall or other surface.

52

Room Air Conditioners F-Series

ED01-707

Optional Accessories

Wiring
1. Wiring
Connect one end of the wiring to connector S21 of the PCB in the indoor unit. Connect the other end of the wiring to connector S6 of the adaptor PCB. Connect field wiring according to the functions assigned to each connection terminal of the adaptor PCB. Secure all wires.

4. Connection with Remote Controller


Example connections with three kinds of remote controllers are shown bellow.
Note: These connections cannot be used in combination.

Generic remote controller

Set SW1-1 to Off and select Operation Mode 1.


SW1 ON OFF

Securing wires in the adaptor case assy (for KRP413A1S KRP413AA1S)

Fasten with a tie-wrap so that wires will not come loose even if pulled.
If the wire protrudes from this side, cut the cut-off section of the case front.

<Instantaneous Contact>
1 S 1

On/Off

2 1

Inter unit cable (field wiring) Tie-wrap (to prevent the wires from coming loose)

Off

S 2

The remote controller most recently used (local or air conditioner) takes precedence. Use a remote controller with a pulse width of 100 msec or more.

<Normal Contact>
Operation
1 2 S 1

Securing wires in the indoor unit (for KRP413A1)

The method for securing wire varies depending on the model of the air conditioner. See your air conditioner installation manual for details.

On

1 2

S 2

Power On/Off cannot be controlled from the units remote controller. When power is restored after a power failure in this mode, On or Off is determined according to the current settings of the remote controller.

2. Automatic Reset After Power Failure


This PCB stores the following data in the event of a power failure (common features). On/Off (see Note 1) Operation modes Temperature setting Air flow rate On/Off status of remote controller
(Note 1 When SW1-2 is in Off mode, the unit will not be activated.)

Five-room central controller (KRC72)

Set SW1-1 to Off and select Operation Mode 1. The remote controller most recently used takes precedence.
SW1 ON OFF 1 2

Five-room central controller


4

3. Monitor Signal Output (normal operation and malfunction)


Maximum length of the wiring is 100 m.

Terminal blocks A to E

3 2 1

1 S 2 4 1 S 2 1

Monitor signal output for LED


Locally procured parts
R

Fan coil remote controller

1 2
Max 100 m

Item Manufacturer

Type TLG208 (green) TLR208 (red) 1S2473 510 ohm 1/4W

LED

S 4

LED D R

Toshiba Rohm

Monitor signal output (normal operation and malfunction)using external relay contacts
S 8 + L1

Set SW1-1 to On and select Operation Mode 2. Most settings (power On/Off, air flow rate, mode change) cannot be made using the air conditioners remote controller. When power is restored after a power failure in this mode, On or Off is determined according to the current settings of the remote controller. When the Cooling /Heating mode is changed, use the air conditioners remote controller to adjust the temperature.
SW1 ON OFF 1 H M L OFF 2

: Operation light : Malfunction light

DC12V
1 (+) () ()

L2

S 5

MR1 MR1 MR2 MR2 L2 L1

2 3

External power supply for light

1 2 1

S 1

S 2 2 1 S 3

Max 100 m

Field supplied parts

Field procured parts (Recommended external relay contacts)


Manufacturer Omron Matsushita Type MY relay HC relay Coil rated voltage 12 V DC 12 V DC Coil resistance 160 ohm 10% 160 ohm 10%

Fan coil remote controller On (When heating) Off (When cooling)

Cooling/heating switch

Room Air Conditioners F-Series

53

Optional Accessories

ED01-707

Test Operation and Confirmation


1. When the System is Not Working
Is the air conditioner working properly? Are the connectors of the wiring properly connected? Are the remote controller and field wiring properly connected? Are all switch settings correct? If there is nothing apparently wrong, conduct a diagnostic check using the following procedure. Diagnostic check
START Defect in adaptor PCB. Defect in wiring. Defect in indoor units PCB. Transmission error (between remote controller and indoor unit) No

Is the CPU Normal light for the remote controllers PCB flashing? Yes

Is 12 V DC being supplied to No. 4 and No. 5 on S6 of the remote controllers PCB? Yes

No

Is 12 V DC being supplied to No. 4 and No. 5 on S21 of the indoor unit? Yes

No

Is the malfunction light of the remote controllers PCB on? Yes OR

No

2. Switch Settings and Connection Terminals


SW1-1 Selecting the operation mode Selecting On/Off when power is restored after a power failure OFF ON OFF ON Operation mode 1 (Used with the exception of fan coil remote controller settings) Operation mode 2 (Used with fan coil remote controller settings) Always Off Off if operation was in Off mode before power failure; On if operation was in On mode before power failure Instantaneous contact S1 (1) - S2 (1) SW1-1: OFF (Operation mode 1) S1 S2 S3 SW1-1: ON (Operation mode 2) S1 (1) - S1 (2) S2 (2), S3 S1, S2 OPEN S1 (1) - S1 (2) CLOSE S1 (1) - S2 (1) CLOSE S1 (1) - S2 (2) CLOSE S3 (With the remote controller only)
CPU normal operation monitor (Flashes when the operation is normal.)

SW1-2
1 2 1 2 1 2 1 2 S 4 S 1 S 2 S 3 S6 S 1 8 2 1 S 2 5 3 SW1 1 2 OFF ON

Normal contact CLOSE OPEN, Not activated CLOSE, Activated

OPEN Pulse input On/Off switching

Not used Not activated On, airflow: L tap On, airflow: M tap On, airflow: H tap OPEN, Cooling CLOSE, Heating

S4 S5

(1) - (2) (1) - (2) (1) - (3)

Voltage on (DC12 V), normal operation light output Normal operation light output (power for light required) Malfunction light output (power for light required) Connect with connector S21 on the PCB of the indoor unit Relay DC 12 V power supply terminal (Field supplied parts)

S6 connector S8 (+) - ()

2P031616-1B

54

Room Air Conditioners F-Series

Specifications, designs and other content appearing in this brochure are current as of January 2007 but subject to change without notice.

ED 01-707 Printed in Japan 01/2007 B AK