Spaj160c Tob 750420enc

Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

Capacitor Protection Relay

Product Guide

SPAJ 160 C

Capacitor Protection Relay


Product Guide

SPAJ 160 C
1MRS750420-MBG
Issued: April 1999 Status: Updated Version: C/19.04.2006 Data subject to change without notice

Features

One-, two- and three-phase overload stage with definite time characteristic One-, two- and three-phase overload stage with inverse (ANSI) time characteristic Phase unbalance protection stage with definite time characteristic Phase unbalance protection stage with inverse time characteristic Undercurrent protection for detection of capacitor disconnection. Reconnection time with wide setting range Compensation for natural unbalance current Fully user-selectable output relay configuration Easy selection of appropriate operational scheme for various applications

Numerical display of setting values, measured current values, memorized values, etc. Continuous self-supervision of hardware and software Serial interface for connecting the relay to the fibre-optic SPA bus and further to higher-level data acquisition, reporting and/or control systems Powerful software support for parameterization of the relay, for reading measured and recorded values, events, etc., and for storing readings Member of the SPACOM product family and ABBs Distribution Automation system CE marking according to the EC directive for EMC

Application

The numerical capacitor relay SPAJ 160 C is an integrated current measuring multi-function relay designed to be used for the protection of capacitor banks. Capacitor banks are used in the power system for compensating the reactive power and for filtering harmonics. The capacitor banks are usually protected against overload caused by harmonic currents and overvoltage caused by internal faults in the bank. Protection against unintentional

reconnection of a charged capacitor to an energized network is also to be included. All these functions are incorporated in the capacitor protection relay. A complete protection system for capacitor banks should also include overcurrent, short circuit and earth-fault protection. The capacitor protection relay SPAJ 160 C is easily supplemented with adequate overcurrent and earth-fault relays from the SPACOM product range.

Capacitor Protection Relay


Product Guide

SPAJ 160 C
1MRS750420-MBG

Design

The capacitor protection relay includes a three-phase, two-stage overload unit, a twostage unbalance unit, an undercurrent unit and a reconnection inhibit timer. The relay measures the phase currents of the capacitor bank. The relay also measures the unbalance current of a split capacitor bank. The current transformer output can be adapted to the rated current of the relay by means of a matching setting. Equally, the unbalance unit is provided with a compensation feature which allows the natural unbalance current of a capacitor bank to be eliminated from the calculations. The phase currents measured by the relay are transformed to voltage images describing the voltages of the capacitor bank. Because harmonic components cause overloading of capacitor banks the relay measures harmonic components up to and including the 13th harmonic. The overload unit protects the capacitors against overvoltage. The first stage of the overload unit operates with inverse time operation characteristic, whereas the second overload protection stage has a definite time characteristic. The inverse time curve is based on ANSI/IEEE C37.99 and IEC 871-1 recommendations for voltage withstand related to time for capacitor banks. The slope of the curve is adjustable. The unbalance unit is also provided with two operation stages. i.e. an inverse time stage according to BS 142 and a definite time stage. The former is normally used for tripping and the latter for signalling. The purpose of the undercurrent protection unit is to detect disconnection of the capacitor bank and to prevent a charged capacitor bank from being switched to the network. The start value, the operate time and the reconnection inhibit time are adjustable. The capacitor protection relay is provided with one external control input. The control input can be used for blocking one or more of the protection stages, for carrying out an external trip command, for inhibiting a recon-

nection attempt and/or for resetting a latched output relay in the manual reset mode of operation.

Data communication
The feeder protection relay is provided with a serial interface on the rear panel. By means of a bus connection module type SPA-ZC 21 or SPA-ZC 17 the feeder protection relay can be connected to the fibre-optic SPA bus. The bus connection module SPA-ZC 21 is powered from the host relay, whereas the bus connection module type SPA-ZC 17 is provided with a built-in power unit, which can be fed from an external secured power source. The relay communicates with higher-level data acquisition and control systems over the SPA bus.

Self-supervision
The relay incorporates a sophisticated selfsupervision system with auto-diagnosis, which increases the availability of the relay and the reliability of the system. The selfsupervision system continuously monitors the hardware and the software of the relay. The system also supervises the operation of the auxiliary supply module and the voltages generated by the module. When a permanent internal relay fault is detected, the IRF indicator on the relay front panel is lit. At the same time the output relay of the self-supervision system operates and a fault message is transmitted to the higherlevel system over the serial bus. Further, in most fault situations, a fault code is shown in the display of the protection relay module. The fault code indicates the type of the fault that has been detected.

Auxiliary supply voltage


The auxiliary supply of the relay is obtained from an internal plug-in type power supply module. Two auxiliary power module versions are available: type SPTU 240R2 for the supply voltage range 80265 V ac/dc and type SPTU 48R2 for the supply voltage range 1880 V dc. The power supply module forms the internal voltages required by the protection relay and the I/O module.

Capacitor Protection Relay


Product Guide

SPAJ 160 C
1MRS750420-MBG

Technical data

Table 1: Energizing inputs


Phase current inputs Unbalance current inputs Rated current In Thermal current withstand Dynamic current withstand Input impedance Phase current monitoring range Phase unbalance current monitoring range Rated frequency fn continuously for 1 s Half-wave value 1-3, 4-6, 7-9 25-27 1A 4A 100 A 250 A <100 m 08.5 x In 0212% In 50 Hz or 60 Hz 1-2, 4-5, 7-8 25-26 5A 20 A 500 A 1250 A <20 m

Table 2: Output contact ratings


Type of contact Terminals Rated voltage Thermal withstand capability Breaking capacity for dc, when the control circuit time constant L/R 40 ms, at the control voltage levels Carry continuously Make and carry for 0.5 s Make and carry for 3 s 220 V dc 110 V dc 48 V dc Tripping 65-66, 74-75 250 V ac/dc 5A 30 A 15 A 1A 3A 5A 5A 10 A 8A 0.15 A 0.25 A 1A Signalling 70-71-72, 68-69, 77-78, 80-81

Table 3: External control input


Blocking and control input External control voltage level Typical control current of activated input circuit 10-11 18265 V dc or 80265 V ac 220 mA

Table 4: Data communication


Transmission mode Data code Transfer rates, selectable Optional bus connection module, powered from an external power source Optional bus connection module, powered from the host relay for plastic core cables for glass fibre cables Fibre-optic serial bus ASCII 4800 or 9600 Bd SPA-ZC17BB SPA-ZC17MM

for plastic core cables for glass fibre cables

SPA-ZC21BB SPA-ZC21MM

Capacitor Protection Relay


Product Guide

SPAJ 160 C
1MRS750420-MBG

Technical data (contd)

Table 5: Capacitor protection relay module SPCJ 4D40


Overload stage Ib> Start current Ib> Start time Operation characteristic Time multiplier k Reset time Drop-off/pick-up ratio, typically Operate time accuracy Operation accuracy Overload stage Ia> Start current Ia> Operate time Reset time Drop-off/pick-up ratio, typically Operate time accuracy Operation accuracy Undercurrent stage I< Start current I< Operate time Reconnection inhibit time trec Reset time Drop-off/pick-up ratio, typically Operate time accuracy Operation accuracy within the range of 0.250.70 In Phase unbalance I1 > Start current I1> Operate time t1 Reset time Drop-off/pick-up ratio, typically Operate time accuracy Operation accuracy within the range of 1.5100% In Phase unbalance I2 > Start current I2> Start time Operation characteristic Time multiplier k2 Reset time Drop-off/pick-up ratio, typically Operate time accuracy of theoretical characteristic Operation accuracy Shortest possible operate time Unbalance compensation Compensation current Ics Operation accuracy 0.301.50 In <80 s ANSI inverse 0.22.0 <100 ms 0.95 3% of set value 3% of set value 80120% of Ib> 0.5100 s <250 ms 0.95 2% of set value 3% of set value 0.100.70 In 1.0100 s 0.5100 min <80 ms 1.1 2% of set value or 75 ms 3% of set value 1.0100% of In 1.0300 s <100 ms 0.90 2% of set value or 75 ms 3% of set value 2.080.0% of In <70 s Inverse time characteristic 0.11.0 <100 ms 0.90 7.5% or 35 ms 3% of set value ~100 ms 0.020.0% of In <3% of In

Table 6: Auxiliary supply modules


Supply and output relay module SPTU 240R2 Supply and output relay module SPTU 48R2 operative voltage range operative voltage range 80265 V ac/dc 1880 V dc

Power consumption, quiescent/operation conditions ~4 W/~6 W

Capacitor Protection Relay


Product Guide

SPAJ 160 C
1MRS750420-MBG

Technical data (contd)

Table 7: Tests and standards


Test voltages Dielectric test voltage (IEC 60255-5) Impulse test voltage (IEC 60255-5) Insulation resistance (IEC 60255-5) Interference tests High-frequency (1 MHz) disturbance test (IEC 60255-22-1), common mode 2.0 kV, 50 Hz, 1 min 5 kV, 1.2/50 s, 0.5 J >100 M, 500 V dc 2.5 kV

High-frequency (1 MHz) disturbance 1.0 kV test (IEC 60255-22-1), differential mode Fast transients (IEC 60255-22-4, class III and IEC 61000-4-4), power supply inputs Fast transients (IEC 60255-22-4, class III and IEC61000-4-4), other inputs Electrostatic discharge (IEC 60255-22-2 and IEC 61000-4-2), air discharge Electrostatic discharge (IEC 60255-22-2 and IEC 61000-4-2), contact discharge Environmental conditions Service temperature range Transport and storage temperature range (IEC 60068-2-8) Damp heat test (IEC 60068-2-3) Degree of protection by enclosure when panel mounted Weight 4 kV, 5/50 ns

2 kV, 5/50 ns 8 kV

6 kV

-10+55C -40+70C <95%, +40C, 56 d/a IP 54 ~3.5 kg

Capacitor Protection Relay


Product Guide

SPAJ 160 C
1MRS750420-MBG

Block diagram
L1 L2 L3
0

0
+

Rx
SPA-ZC_

Tx

+ (~) Uaux - (~) OHJAUSCONTROL INPUT BS TULO IRF

+
UUDELLEENRECONNECTION KYTKENNN ENABLE SALLIMINEN + HAVAHT. START SIGNAALI SIGNAL 2 2 SIGNAALI SIGNAL 1 1 LAUK. TRIP

63

1 2 3 4 5 6 7 8 9 25 26 27
5A 1A 5A 1A 5A 1A 5A 1A

11

10

61 62

70 71 72
+

74 75
+

77 78
+

80 81
+

68 69
+

65 66
+

SERIAL SARJAPORTTI PORT

@
+

_
-

U2 SPTU_R2 TS1 U3
1 1

SS1
1 SGR1/1 SGR1/2 SGR1/3 SGR1/4

SS2
1 SGR2/1 SGR2/2 SGR2/3 SGR2/4 SGR2/5 SGR2/6 SGR2/7

SS3
1 SGR1/8 SGR2/8 SGR1/5 SGR1/6 SGR1/7 R SGB1/6 SGB1/7 TRIP LAUK. 1

TS2

3Ia>
SGB_/1

IRF

SGF/1

T8

3Ib> I I

T2

T1 T3

T5

SGB_/2

SGF/2

T4

T6

SGB_/3 SGB_/4 SGB_/5 SGB_/8

3I<
T7
UUDELL.KYTK. RECONN.INHIBIT ESTO ULK. LIIPAISU EXTERNAL TRIP RELEEN RELAY RESET KUITTAUS

T9

SPAJ 160 C

I/O

U1

SPCJ 4D40

SPAJ160C_block

SJAJ160C_BLOCK.FH7

Fig. 1

Block diagram and sample connection diagram

Capacitor Protection Relay


Product Guide

SPAJ 160 C
1MRS750420-MBG

Mounting and dimensions

Flush mounting
142
30

250
216 186 34

129 1

139 1

Panel cutout

162

136

dim100

Fig. 2

Flush-mounting relay case (dimensions in mm)

Semi-flush mounting
a b

Raising frame SPA-ZX 111 SPA-ZX 112 SPA-ZX 113

a 176 136 96

b 74 114 154

SFM100_1

Fig. 3

Semi-flush mounting relay case (dimensions in mm)

Mounting in 19 inch cabinets and frames


An ancillary mounting plate, height 4U (~177 mm), is recommended to be used when the protection relays are to be mounted in 19 inch frames or cabinets. The ancillary mounting plate type SPA-ZX 104 accommodates three relays, type SPA-ZX 105 two relays and type SPA-ZX 106 one relay.
SPA-ZX104 SPA-ZX105 SPA-ZX106
482,6 0 (19")
+0,4

Projecting mounting
When projecting mounting is preferred, a relay case type SPA-ZX 110 is used. The relay case for projecting mounting is provided with front connectors.

SPA-ZX110 SPA-ZX115
158 115 263 6

177 0 (4U)

101,6

+0,4

21,5

312 292

10

6 115

98
104_6_10

Fig. 4

Mounting cabinets and frames as well as projecting mounting (dimensions in mm)

Capacitor Protection Relay


Product Guide

SPAJ 160 C
1MRS750420-MBG

Ordering

When ordering, please specify:


Ordering information 1. Type designation and quantity 2. Order number 3. Rated values 4. Auxiliary voltage 5. Accessories 6. Special requirements Ordering example SPAJ 160 C, 5 pieces RS 611 051-AA In=5 A, fn=50 Hz Uaux=110 V dc -

Order numbers
Capacitor protection relay SPAJ 160 C without test adapter RS 611 051-AA, CA, DA, FA

Capacitor protection relay SPAJ 160 C including test RS 611 251-AA, CA, DA, FA adapter RTXP 18 The last two letters of the order number indicate the rated frequency fn and the auxiliary voltage Uaux of the relay as follows: AA equals fn = 50 Hz and Uaux = 80265 V ac/dc CA equals fn = 50 Hz and Uaux = 1880 V dc DA equals fn = 60 Hz and Uaux = 80265 V ac/dc FA equals fn = 60 Hz and Uaux = 1880 V dc

References

Additional information
Manual Capacitor bank overload and unbalance protection relay SPAJ 160 C 1MRS 750064-MUM EN

10

ABB Oy
Distribution Automation P.O. Box 699 FI-65101 Vaasa, FINLAND Tel +358 10 22 11 Fax +358 10 224 1094 www.abb.com/substationautomation

You might also like