hen designing for thinner oors, using post-tensioning to resist loads and deections provides a more optimal solution than conventionally reinforced oors. This fact is primarily due to the loadbalancing effect of the draped posttensioned tendons. How it works When considered together, uniform and banded tendons act like a net stretched from all four edges of the slab; see Figure 1. This net exerts the load-balancing forces on the concrete. In the span, the forces caused by the uniform and banded tendons act on the concrete to oppose gravity; see Figure 2. Where the tendon curvature is inverted (such as over the grid lines between the columns), the forces in the uniform tendons act downward, inserting concentrated loads on the banded tendons (which typically run along the grid lines). These concentrated forces are balanced by the upward-acting forces from the banded tendons that, in turn, apply downward-acting forces on the columns. As a follow-up to Floor framing system selection: Applications of post-tensioning in buildings, by John Crigler printed in the August issue of Structural Engineer, this article offers tips for starting post-tensioned designs with more accuracy.
Determining pre-stressing amounts To estimate the amount of prestressing steel needed for a oor design, assume that the draped tendons provide sufcient distribution of forces to balance a certain percentage of the oor self-weight. This percentage depends on the ratio of total load to permanent load and is typically between 70 and 130 percent. For typical ofce oors with live loads of 50 to 100 pounds per square foot (psf ) or residential oors with live loads of 40 to 100 psf, the pre-stressing steel would normally balance 70 to 90 percent of the self weight. For oors with higher live loads, 100 percent of the self weight, plus any additional live loads, should be balanced. The other effect responsible for the improved deection and cracking behavior of post-tensioned oors is the in-plane compression stress eld in the concrete stemming from the anchorages of the pre-stressing tendons. Provided that there are no sig-
nicant restraints, these compression stresses neutralize a part of the exural tensile stresses caused by the portion of the loading not balanced by forces from the tendon drape. Typically, the post-tensioning in oors provides an average in-plane compression stress of 125 to 500 pounds per square inch (psi). Span-to-depth ratios For light loading, which typically ranges from 40 to 70 psf where punching shear is not critical, a post-tensioned at plate can be designed with a span-to-depth ratio of approximately 1-to-45 of the larger span dimension (for interior panels), compared with approximately 1-to-30 for a at plate in reinforced concrete. If drop panels are provided over the columns, the span-to-depth ratio can be increased to approximately 1-to-50 for the interior panels of post-tensioned slabs and 1-to-35 for the interior panels of reinforced concrete slabs.
(left) For regular, unrestrained oor plates with normal to light loading, simple rules of thumb can provide an excellent starting point for posttensioned, at plate concrete oor designs. (right) Figure 1: Typical tendon conguration forms a net that exerts the load-balancing forces on the concrete. (below) Figure 2: In the span, the forces caused by the uniform and banded tendons act on the concrete to oppose gravity.
www.gostructural.com
43
MATERIAL MATTERS
For greater super-imposed loading, the span-to-depth ratio decreases, particularly if the super-imposed load is predominantly variable in location and time. In these instances, the amount of post-tensioning cannot simply be increased to balance the super-imposed load. Instead, a greater oor thickness is required to meet deection and stress requirements. Figure 3 shows where the spanto-depth ratios of a number of posttensioned at plates and at slabs with drop panels are plotted against the total load, normalized by the slab self weight. In spite of the resulting large scatter, the diagram clearly shows a trend that the span-depth ratio decreases markedly with increasing super-imposed load. The large scatter can be explained by the following four main factors:
Figure 3: Span-depth ratio decreases with increasing super-imposed load. (Source: Data from internal VSL
records and from references)
many different requirements for deection and cracking; s ever-present trade-off between slab thickness and the quantity of both the mild reinforcement and the prestressed steel; s treatment of punching shear by increasing the slab thickness or providing shear reinforcement; and s dependence of the total load-to-self weight ratio on the span length, which also affects the span-to-depth ratio. With the exception of a few extreme cases in the graph, the data fall within an optimal curved band with that variation of approximately 10 feet/ inch. To use these graphs for a preliminary estimate of the slab thickness, an engineer has to assume a reasonable thickness, calculate the total load-to-self weight ratio, and then check whether the resulting span falls within the band in the corresponding graph. For short spans (such as 20 feet) the span-to-depth ratio may be closer to the upper edge of the band. In the case of a very long span (such
Enter #162 at gostructural.com/infodirect
Structural Engineer OCTOBER 2008
44
www.gostructural.com
MATERIAL MATTERS
%ULGJLQJ&KDOOHQJHV :LWK6ROXWLRQV
ZZZ QOH\HQJLQHHULQJJURXSFRP
Enter #232 at gostructural.com/infodirect
Thanks to our dedicated employees for making CKC one of the Best Firms To Work For!
Cary Kopczynski & Company 10500 NE 8th Street, Ste 800 Bellevue, WA 98004-4351 Phone: (425) 455-2144 Fax: (425) 455-2091
www.ckcps.com
STRUCTURAL ENGINEERS
as 36 feet), the span-to-depth ratio is closer to the lower edge. This reects the dependence of the span-to-depth ratio on the absolute span length. Note that the graph is only meant to give some guidance in selecting a rst estimate of the slab thickness. Other steps in the design such as calculating the punching shear capacity or the expected deection may dictate selection of a different thickness. For total load-to-self weight ratios greater than approximately 2.5-to-1 and spans in excess of 30 feet, at plates and at slabs with drop panels will normally be uneconomical. Other oor systems with greater structural efciency that is, stiffness and exural strength for a given average weight per unit oor area should then be considered. One-way slab and beams, one-way slab with shallow beams, wide beams with skip joists, or wafe slabs with drops are all lighter than an equivalent at slab. Determining guidelines for the span-to-depth ratio is much more difcult for these systems. This is due to additional variables such as the spacing of band beams, the beam width, the slab thickness between the beams, et cetera. This circumstance usually necessitates study of a number of options before deciding on the dimensions. Typically, wide shallow beam widths that are 1/4th to 1/5th of the beam center line spacing and beam depths of 2.0 to 2.5 times the slab thickness result in economical designs for oors with light to moderate loading. As a crude guideline for posttensioned, one-way slab and beam systems designed to support superimposed loads of 60 to 80 psf, the slab thickness may be assumed to be 1/35th to 1/45th of the clear span between beams unless governed by minimum thickness requirements. The span-todepth ratio of the beams will most often be between 1-to-20 and 1-to30. With 60 to 80 psf oor loading, a value of 1-28 is a reasonable estimate
www.gostructural.com
Zuming Xia, Ph.D., P.E., is an engineer in VSLs Washington, D.C., ofce. Xia is an associate member of the joint committee ACI-ASCE 423 Pre-stressed Concrete and an associate member of ACI committee 362 Parking Structures. He can be reached at [email protected].
For new concrete road & bridge construction . . . specify epoxy-coated steel reinforcing bars and rely on a long life with low maintenance
BENEFITS
References
s
Less traffic interruption Less congestion Smoother riding surface Enhanced safety Reduced maintenance Reduced costs
Design Guide For Long-Span Concrete Floors, Cement and Concrete Association of Australia in collaboration with Steel Reinforcement Promotion Group, June 1988, ISBN 0 947 132 06 6
Fanella, D.A., Concrete Floor Systems Guide to Estimating and Economizing, Portland Cement Association, 2nd Edition, 2000
Fanella, D.A., and Munshi, J.A., Long-Span Concrete Floor Systems, Portland Cement Association, 2000
Fintel, M., and Ghosh, S.K., Economics of Long-Span Concrete Slab Systems for Ofce Buildings A Survey, Portland Cement Association, 1982
Heres an example of the typical issues found by an eastern state. During the past 35 years, VMT vehicle counts have increased VEHICLES by 200% and Vehicles Miles Lane Miles Traveled (VMT) by 300%, Traffic congestion build up vs. lane miles built while lane miles have increased less than over the past 35 years 10%. With the low precentage of lane mile additions, critical decisions on materials and methods must focus on the best. Readily available, quality, epoxy-coated steel reinforcing bars are the right choice with virtually no maintenance required. Find out more, go to www.crsi.org/epoxy.