Lyngsø Marine: UCS 2100 User Manual
Lyngsø Marine: UCS 2100 User Manual
Title:
970.505.742 2001.06.01
Inspector:
CTR
Pages: 53
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 0 of 53 2001.06.01
Document History: Version 970.505.741 970.505.742 Date 99.04.08 01.06.01 Author CTR CTR Changed pages Changes Control right added pg. 22, 23, 26 Spare Channel, Journals, Adjust time, Change AlmChn, Open DispChan added Minor updates for UCS ver. 4.52
File: Printed:
Lyngs Marine
970.505.742
Lyngs Marine
+45 45 16 62 00 +45 45 16 62 62
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 1 of 53 2001.06.01
Content.
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 1.1 Introduction to the Graphic Operator Station - GOS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 1.2 The GOS components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 General GOS lay out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 2.1 Operating the GOS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 2.2 Description of lists and diagrams in the GOS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 2.2.1 Header Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 2.2.2 Main Menu Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 2.2.3 Alarm List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 2.2.4 Alarm Groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 2.2.5 Additional Lists . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 2.2.6 Display Channel Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 2.2.7 Standard Function Block Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 2.2.8 Mimic Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 2.2.9 Control Right Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 2.2.10 Journals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 2.2.11 Spare Channels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 2.3 How to - - - . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 2.3.1 Open Alarm List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 2.3.2 Open Lists for Cut Out, Simulation, Sensor Fail or Device Fail . . . . . . . . . . . 28 2.3.3 Open Alarm Group Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 2.3.4 Stop Horn . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 2.3.5 Acknowledge oldest unacknowledged alarm . . . . . . . . . . . . . . . . . . . . . . . . . . 29 2.3.6 Acknowledge alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 2.3.7 Open Display Channel Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 2.3.8 Change alarm limits, delays and cut-out state . . . . . . . . . . . . . . . . . . . . . . . . . 30 2.3.9 Key in simulated value for monitoring channels . . . . . . . . . . . . . . . . . . . . . . . 31 2.3.10 Open Mimic diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 2.3.11 Change Over Control Right for a machinery group. . . . . . . . . . . . . . . . . . . . . . 32 2.3.12 Use of Journals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 2.3.12.1 Display and print Journals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 2.3.12.2 Create Journals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 2.3.12.3 Automatic printout of Journals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 2.3.13 Activate spare channels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 2.3.13.1 Activate binary channels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 2.3.13.2 Activate analog channels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 2.3.14 Change definition of alarm channels, e.g. name, texts and scaling. . . . . . . . . . 49 2.3.15 Adjust time and date. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 2 of 53 2001.06.01
Introduction
1.1
1.2
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 3 of 53 2001.06.01
The screen operates in graphic mode at all times (Standard VGA), and any mix of graphic and text information can be presented simultaneously. The keyboard is a standard PC keyboard. In addition to the letter and number keys the keyboard is also equipped with 12 function keys, some of which are used for dedicated purposes in connection with the GOS operation. The pointing device which is used to move the pointing arrow around the screen can be either a tracker ball or a mouse. The tracker ball is permanently mounted into the console and presents one or two buttons and a ball. When rolling the ball with the hand the movement is transferred to the arrow on the screen. The button is used to select/activate the item or function pointed at on the screen. The mouse is a standard PC-mouse which is operated in the same way as the tracker ball.
An optional printer which is used for printing reports can be connected directly to the GOS.
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 4 of 53 2001.06.01
Caption with date and time Menu bar Header Diagram Working Area
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 5 of 53 2001.06.01
Caption:
In the Caption the date and time is displayed, date and time can be displayed as UTC time or as Local time. Additionally the it is possible to indicate the type of time, UTC, LT (local time) or actual time zone.
Menu Bar:
In the Menu Bar various drop down menus can be activated, these menues are used to operate some of the functions of the GOS. The Header Window can contain different header diagrams, the actual header diagram is selected automatically depending of the alarm system definition for the location of the GOS. The header diagram displays important information from the alarm system(s) related to the GOS, such as number of alarms, number of unacknowledged alarms, watch location and duty officer. And most important the oldest unacknowledged alarm The header diagram also includes short cuts (selection buttons) to some often used functions e.g. the Main Menu Diagram, the Alarm List, Stop Horn and Acknowledge.
Header Window:
Working Area:
The working area can contain many different lists or diagrams, the most important is listed below: Lists: Alarm List Alarm Group Failure Lists (sensor fail, device fail) Suppression Lists (cut out, simulated) Journals
Diagrams: Mimic Diagram Function Block Diagram Graph Diagram Bargraph Diagram
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 6 of 53 2001.06.01
2.1
Ball
Used to move the cursor
Left button
Use to select diagrams and objects
Tracker ball
Right button
Used to acknowledge and open Display Channel dialogues
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 7 of 53 2001.06.01
it is unacknowledged a left click on the acknowledge text will acknowledge the alarm, or a left click on the text Display Channel will open a dialogue with detailed information of this alarm. All active areas in a mimic diagram can be shown by activate the function Select all objects in the Edit menu.
2.2 2.2.1
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 8 of 53 2001.06.01
W hen the header includes two alarm systems the upper part of the header is divided in 3 columns the first (left side) is the legend for the information, the second column contains information from first alarm system and the third column contain information for the second alarm system. When the header includes more than one alarm system it has two lines of oldest unacknowledged alarm , the upper is for the passive alarm system(s) and the lower is for the active alarm system(s). Passive alarm systems means the alarm systems that this GOS has access to but are not watch station for. Active alarm systems means the alarm systems that this GOS is watch station for (are able to acknowledge). When the header includes tree alarm systems the upper part of the header is divided in 4 columns the first (left side) is the legend for the information, the second column contains
information from first alarm system, the third column contain information for the second alarm system and the fourth column contain information for the third alarm system.
When the header includes four alarm systems the upper part of the header is divided in 5 columns the first (left side) is the legend for the information, the second column contains
information from first alarm system, the third column contain information for the second alarm system, the fourth column contain information for the third alarm system, and the fifth column contain information for the fourth alarm system.
2.2.2
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 9 of 53 2001.06.01
diagram there is connection to all other mimic diagrams in the system. Depending of the size of the system (number of diagrams) it is possible to open mimic diagrams and alarm groups directly from the Main Menu diagram or to open other overview diagrams for smaller parts of the system. Each alarm group, mimic diagram and sub-overview diagram is indicated by an active area in the Main Menu diagram, the active area normally looks like this: . To open the matching diagram make a left click on the square or on the text. If there is an unacknowledged alarm in the matching diagram the square will flash red, and if there is acknowledged alarms and no unacknowledged alarms in the matching diagram the square will turn to steady red. The layout of the Main Menu diagram is normally like shown in Fig. 2-1, but the layout can be different due to requests from the customer during commissioning of the system.
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 10 of 53 2001.06.01
2.2.3
Alarm List
An Alarm List is a list of all standing alarms, both acknowledged and unacknowledged, in the alarm system. The UCS2100 system can include from 1 to 4 alarm systems (e.g. Machinery Alarms and Bridge Alarms), each alarm system has its own alarm list. One alarm is taking up one line in the alarm list. The alarms are sorted after starting time, so the oldest alarm is in the top and the newest alarm is in the bottom of the list. If the alarm is more than 24 hours old the starting time is exchanged with the starting date.
Identifier for the alarm, max. 8 characters. Description of the alarm, max. 30 characters. Alarm state:
ALM (standing alarm) NORM (no alarm) FAIL (sensor fail or device fail) Message text for the current alarm state Current value for analog alarms Starting time for the alarm
Acknowledge all alarms on the current page of the alarm list. Red when enabled. Acknowledge one selected alarm. Red when enabled. Scroll buttons( page up / page down). Update list, only used to remove acknowledge alarms when normal again. Select a new Alarm System.
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 11 of 53 2001.06.01
The alarm list can display all alarms defined in the alarm system. Normally up to 20 alarm lines can be shown on the screen, if the actual number of alarms is greater than this it is indicated in the bottom of the list. Indicates that alarm number 1-20 (the 20 oldest alarms) is displayed on the screen right now and that there totally are 45 alarms. The rest of the alarms can be seen by scrolling in the alarm list using the <Page Up> and <Page Down> keys or by making a left click on one of the scroll buttons: . The colour of the text in the alarm list is normally green, except for the State text, the colour of the State text is controlled by the priority of the alarm, for priority 1 the colour is red, for priority 2 the colour is magenta and for priority 3 the colour is yellow. The State text is flashing as long as the alarm is unacknowledged. A right click on an alarm line will bring up a small menu with two texts, Display Channel, and Acknowledge. The Acknowledge text is disabled (not possible to select, shown in grey) if the alarm is acknowledged, if the horn is not silenced or if this GOS does not have the rights to acknowledge the alarm. If the Acknowledge text is enabled ( possible to use, shown in black) you can acknowledge the alarm by making a left click on the Acknowldge text. A left click on the Display Channel text will open the Display Channel diagram for this alarm channel. The Display Channel diagram shows detailed information for the alarm channel setup, such as alarm delay, alarm limits, connection terminals, cut out and simulation status, some of the setup can also be changed from the Display Channel diagram e.g. delays and limits. In the following the lay out of the alarm line is described for the different states of an alarm. A: New unacknowledged alarm. The alarm line marked A in fig. 2.1.1 is a new unacknowledged alarm which started at 10:14:13, the State text is flashing read. The alarm can be acknowledged by left clicking on the button, this will also acknowledge all other unacknowledged alarms visible in the current page of the alarm list. Note that alarms can not be acknowledged as long as the horn is sounding. B: New unacknowledged alarm, selected. The alarm line marked B in fig. 2.1.1 is a new unacknowledged alarm that has been selected by a left click somewhere on the line, the selected alarm is indicated by a blue background colour. A selected alarm can be acknowledged by left clicking on the button, this will only affect the selected alarm. Note that alarms can not be acknowledged as long as the horn is sounding.
C:
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 12 of 53 2001.06.01
The alarm line marked C is a unacknowledged alarm that has turned normal again. This state is indicated by removing the start time and the state text is changed to NORM but still flashing. The alarm can be acknowledged by left clicking on the button or the button, as described in A or B. Note that alarms can not be acknowledged as long as the horn is sounding. D: Standing alarm The alarm line marked D is a standing acknowledged alarm, the State text is steady red, and the starting of the alarm is indicated as hh:mm:ss.c 10:12:22.0. E: Standing alarm, older than 24 hours The alarm line marked E is a standing acknowledged alarm , the State text is steady red, and the starting time is indicated as yyyy/mm/dd, 1999/01/23, this is the starting date of the alarm. If needed the time can be found in the Event Log. F: Alarm that has turned normal again. The alarm line marked F in fig. 2.1.1 is an acknowledged alarm that has turned normal again. This is indicated by grey text, the State text NORM and no starting time indication. This line is not removed automatically as this could cause confusion when the other lines are moving while you are looking at it. The line is removed if you left click on the button, if another page are selected or if the alarm list is closed.
2.2.4
Alarm Groups
An Alarm Group list is a list of all alarms included in this group, independent of the alarm state. The UCS2100 system can have up to 100 alarm groups. The layout of the list and the alarm lines are the same as for the Alarm List, but the list is sorted alphabetically after the ID. Alarms in an Alarm Group can have more states than in the Alarm List, because some of the states of the alarm channel is moved to separate lists e.g. Cut Out List or List of Simulated channels. The possible states (state texts) for an alarm channel in a Alarm Group are listed below: state - NORM - ALM - ALM appearance steady green flashing red steady red description The alarm channel in normal sate i.e. no alarms and no failures. Unacknowledged alarm, priority 1. Acknowledged standing alarm, priority 1.
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 13 of 53 2001.06.01
flashing magenta
steady magenta Acknowledged standing alarm, priority 2. flashing yellow Unacknowledged alarm, priority 3. steady yellow flashing red steady red Acknowledged standing alarm, priority 3. Unacknowledged alarm for sensor fail. Acknowledged sensor fail, outside normal range. Alarm channel with standing alarm, where the alarm is suppressed by a Cut Out. Some of the UCS2100 hardware for this channel is not working. I.e. hardware failure in the Gamma PLC outstation, or power failure in the Gamma outstation, or failure in the network between the GOS and the Gamma outstation. In this state the hole line in the list is displayed steady white.
All state texts can be extended with a S in the beginning, e.g. S NORM or S ALM. This S indicates that the alarm channel is in simulation mode, in simulation mode the displayed value is manually keyed in, and has no connection to the input from the sensor.
2.2.5
Additional Lists
Additional lists is a set of lists for alarm channels in a certain state, there is one set of additional lists for each alarm system. The layout of the Additional lists is the same as for the Alarm List. Additional lists include the following lists: Suppression Lists - Simulated channels - Automatic Suppressed - Manual Suppressed Failure Lists - Device Fail List List of all channels with device fail (hardware fail in the Gamma PLC or power fail to the Gamma PLC). List of all channels that are in simulation mode. List of all channels that are suppressed by automatic cut out. List of all channels that are manually suppressed (manual cut out).
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 14 of 53 2001.06.01
List of all channels with sensor fail (input from sensor is outside the defined range). Alarm List only including alarms with priority 1. Alarm List only including alarms with priority 1 or 2.
Alarm List, only high priority alarms - Alarm List priority 1 - Alarm List priority 1+2
Additional Lists has the same layout as the Alarm List and Alarm Group Lists and the operation of the list is the same, i.e. it is possible to acknowledge alarms and open the Display Channel diagram.
2.2.6
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 15 of 53 2001.06.01
The various functions in the Display Channel diagram are described below: - The top line is the same line as displayed in the Alarm Group / Alarm List for this alarm. This line includes ID for the alarm channel, description, alarm state, message text, value (only for analogue channels) and start time for the alarm (if active). - Configuration includes: Type: Alarm System: Outstation: Addr.: analog / binary The name of the Alarm System that this alarm channel belongs to. The name of the outstation where the Gamma PLC is located. The address (unit number) for the Gamma PLC on the Stella Network.
- Alarm Groups: Each alarm channel can be included in 0 to 4 alarm groups. The alarm groups which this alarm is included in is indicated in the Alarm Group field. If a left click is made on the button at the right of the name of the alarm group, the matching Alarm Group diagram is opened.
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 16 of 53 2001.06.01
- Channel Parameters: Limit: Binary alarm channels has only one limit. Analog alarm channels has from 1 to 3 limits, if more than one limit is active at the same time, the message text for the highest number will be displayed in the Alarm List. Type: Message: Prio.: binary / low limit / high limit. Displays the message text that is defined for this limit, defined during commissioning. Priority of the alarm channel, 1 - 3 for alarms and 4 for event. Priority is used to select the colour of the state text and indication in mimic diagrams, priority 1 is red, priority 2 is magenta, priority 3 is yellow and priority 4 white. The priority is also used to select which alarm to include in the alarm list if Only priority 1 alarms or Only priority 1 + 2 alarms are selected in the Additional List dialogue. Alarms with priority 4 is not shown in the alarm list, but can be included in an alarm group and shown on a mimic diagram. Value: Limit value for analog channels, not used for binary channels. The adjust dialogue can be opened by a left click on the button at the end of the line. Delay on/off: Delay on is the time from the limit is exceeded (analog) or the input is activated (binary) till the alarm is announced by horn and displayed in the alarm list. Delay off is the time from the limit is no longer exceeded (analog) or the input is passivated (binary) till the alarm removed from the alarm list. The adjust dialogue can be opened by a left click on the button at the end of the line. M.cut: Manual cutout indicates a ON if the alarm is suppressed by a manual cutout. This feature can be uses if there is a sensor fail or the machinery system is under repair to avoid false alarms. Manual cutout can be switched on and off from the adjust dialogue, this can be opened by a left click on the button at the end of the line. Normally cutout for all limits of the alarm channel is done from limit 1, and the on/off text is only displayed for limit 1. But in some cases there can be separated cut out for each limit this is indicated by a on/off text in each limit.
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 17 of 53 2001.06.01
- Channel Calculation: In the channel calculation field is displayed which signal are used to calculate the state of the alarm channel. For analog channels 1 - 3 inputs signals can be used, a main signal, one signal that are added to the main signal and one signal that are subtracted from the main signal. For binary channels 1 or 2 signals can be used, the calculated signal is a logical operation between the two signals, AND, OR, XOR and XNOR can be used. Each signal is specified in one line with the following information: Signal: Indicates how this signal shall be used in the calculation, Main, Add, Subtract analog channels, and Main, NOT, AND, OR, XOR or XNOR for binary channels. Indicates the type of signal, the following types are available sensor input, another monitoring channel, constant, serial input, SLS point and an alarm group. The ID and name for the signal. ID for input module of the Gamma PLC, only for sensor inputs. Connection terminals on the input module of the Gamma PLC, only for sensor inputs. Sensor range.
Type:
- Channel Time Channel time is the time for latest change of state for this alarm channel. The following state changes will set the time: alarm occurs, alarm turns normal, cut out activated and channel set in simulation. - Simulation All alarm channels can be set in simulation mode, in this mode there is no connection to input signals for the alarm channel, but the input value can be set manually. This feature can e.g. be used when you have sensor failure but you know the correct value anyhow, he you can set the channel in simulation mode and key in the correct reading. A left click on the button will open the simulation dialogue.
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 18 of 53 2001.06.01
Simulation dialogue.
- Data Log The UCS2100 system offers the possibility to print a log of the actual values for selected alarm channels, this function is called the Data Log. The selection of each alarm channel can be changed in the Data Log selection dialogue, which can be opened by a left click on the button. There is one data log for each alarm system. Printing of the Data Log can only be started from the Basic Alarm Panel, press the key Printer Control, softkey MORE and softkey DATALOG.
- Toolbar In the bottom of the Display Channel window there is a toolbar. From this it is possible to carry out various functions described below.
Toolbar for Display Channels Window.
Edit channel parameters Change to last channel Change to next channel Change to previous channel Change to first channel Acknowledge alarm Enter adjust mode Find mimic diagram with this channel Open channel selection list
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 19 of 53 2001.06.01
A click on this button will change the content of the display channel window to the last channel in the system. Channels are sorted alphabetically after the channel ID.
A click on this button will change the content of the display channel window to the next channel in the system. Channels are sorted alphabetically after the channel ID.
Change to previous channel A click on this button will change the content of the
display channel window to the previous channel in the system. Channels are sorted alphabetically after the channel ID. Change to first channel
A click on this button will change the content of the display channel window to the first channel in the system. Channels are sorted alphabetically after the channel ID.
Acknowledge alarm
A click on this button will acknowledge alarm for this channel. The button indicates a red exclamation mark if the channel has an unacknowledged alarm.
After a click on this button you will be asked for password level 1. After you have keyed in the correct password all adjustments in the display channel window are open (can be changed without keying in password again). The password will be disabled when the window is closed. A click on this button will open the mimic diagram that includes this channel. If more mimic diagrams include this channel a list will be displayed and you will have to select a diagram form this list.
Open channel selection list A click on this button will open a list of all monitoring
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 20 of 53 2001.06.01
channels in the system, from this list you can select a channel to display. Edit channel parameters
A click on this button will open a window where it is possible to change parameters for the channel. Before opening this window you will be prompted for password level 3. The parameters that can be changed are: - Name of the channel - Membership of Alarm System - Membership of Alarm Groups - Input definition NO or NC for binary channels - Input scaling block for analog channels - Message text - Alarm priority For some channels some of the parameters are locked e.g. if the channel is used by the control system. For details se section 2.3.14.
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 21 of 53 2001.06.01
2.2.7
The tree indications (name, state and icon) can be displayed all together, only two of them or only one of them. On Standard Function Block diagrams we normally display all tree. From a digital object it is possible to send commands to the machinery component. Both name, state text and the icon are active areas, a left click on one of these areas will open a command menu, with the available commands shown as text. A left click on one of the command texts will send this command to the machinery component.
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 22 of 53 2001.06.01
- Analog object:
Used to indicate a numeric value of a measurement or an adjustable value in the Gamma PLC. A analog object can display one static indication and two dynamic indications in the diagram. The static part is the ID/Name of the object (measurement). Both dynamic indications shows the actual value of the measurement. One shows the value as a number, and the other as an graphic symbol e.g. a bargraph or a pie. The tree indications (name, value and graphic symbol) can be displayed all together, only two of them or only one of them. On Standard Function Block diagrams we normally display all tree.
A Standard Function Block normally consists of more objects e.g. there are 3 for a pump. - one object showing the actual state, stopped/running and failure. - one object showing the control mode, local/remote/automatic. - one object showing if there are interlocks or the pump is blocked due to a failure. Below is an example of the layout for a Standard Function Block diagram including function blocks for pumps, standby pumps, valves and tank measurements.
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 23 of 53 2001.06.01
2.2.8
Mimic Diagrams
A mimic diagram shows a part of the machinery system with a static background drawing and dynamic objects representing the machinery components and measurements of the system. Mimic diagrams are use to give a better overview for a part of the machinery system e.g. the fuel oil supply, this is achieved by placing the machinery component object on a background drawing (e.g. a pipeline diagram) showing the interaction between the various components. The dynamic objects are normally Standard Function Blocks but also customized objects can exist. On mimic diagram normally only the icon for digital objects and the value for analog objects are shown. This is because indication of the names and state texts will make the diagram crowded and harder to overview, and the function of the object can be seen from the diagram. The identifier for the objects can be shown by a click on the object.
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 24 of 53 2001.06.01
2.2.9
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 25 of 53 2001.06.01
Overview of the actual control locations can be seen from the Control Right Change Over mimic diagram, this diagram can be opened by a left click on the Control Right button in the header. From this diagram it is also possible to change the control location for the machinery groups. The Control Right Change Over diagram includes a table where the number of columns are determined by the number of control locations and the number of rows is determined by the number of machinery groups in the control right system. The leftmost column shows the name of the machinery group, column number two shows the actual selected control location, and then there is one column for each control location. In the columns for the control locations there is a button if this control location is valid for the machinery group in this row. Change over of control location for a machinery group is carried out by making a left click on the button placed in the row for the machinery group and the column for the new control location. Fig. 2.2.9-1 shows an example of a Control Right Change Over diagram. In this example there is 9 machinery groups (PMS, AUX ENGINES, BALLAST TANKS etc.) in the control right system and there is 4 control locations (ECR, Ships Office, Bridge and Cargo). For example is the Power Management System (PMS) currently controlled from the ECR. Valid control location for the PMS is ECR and Ships Office. To change the control of PMS from ECR to Ships Office simply make a left click on the Ships Office button in the row for the PMS machinery group. Then the name in the column Actual Control Location will change from ECR to Ships Office, control from ECR will be disabled and control from Ships Office will be enabled.
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 26 of 53 2001.06.01
2.2.10 Journals
A Journal is a list or a set lists of monitoring channels. A Journal has the same layout as the Alarm List. The content of this list can be defined online by the operator. One Journal can consist of up to 10 pages, each with 32 monitoring channels. Up to 15 different Journals can be defined. Journals are unique for each operator station, this means that the total number of possible journals are 15 multiplied with the number of operator stations in the system. It means also that journals defined on one operator station can not be seen on the other operator stations.
Journals can be use for display on the screen or for printing on a printer connected to the operator station. Printout of journals can be handled manually or automatically. Automatically printout can be either cyclic or at predefined times. Automatic printout is only possible on a tractor feed printer. However Journals can be printed manually to either a tractor feed printer or a graphical printer.
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 27 of 53 2001.06.01
If the spare channel option is not included in the system the Spare Channel button will be greyed, and then spare channels can not be activated in the running system.
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 28 of 53 2001.06.01
2.3 How to - - In this section will be explained how to carry out the most common actions.
2.3.1
2.3.2
Open Lists for Cut Out, Simulation, Sensor Fail or Device Fail
These lists can be opened for, the dialogue Additional Lists, Additional Lists can be opened in the following way: Click with the left tracker ball/mouse key on the Additional List button in the header. - Press the <F5> function key at the keyboard. - Click with the left tracker ball/mouse key on the text Diagram in the Menu bar, this will open a drop down list of diagrams select AddList with the cursor and click with the left key.
2.3.3
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 29 of 53 2001.06.01
2.3.4
Stop Horn
When the horn is sounding it can be stopped in the following ways: - Press the <F11> function key at the keyboard. - Click with the left tracker ball/mouse key on the Stop Horn button header. in the
- The horn can also be silenced by a press on the STOP HORN key on the Basic Alarm Panel.
2.3.5
2.3.6
Acknowledge alarms
Unacknowledged alarm in lists are indicated by flashing State text, these alarms can be acknowledged in the following way: - Make a right click somewhere in the alarm line, this will open a small pop up menu, from this menu the alarm can be acknowledged by a left click on the Acknowledge text. - Select the alarm line by a left click, the background will change to blue, when the alarm is selected it can be acknowledged by a left click on the button. NB! Alarms can only be acknowledged when the horn is silenced and the GOS is watch station for the actual alarm system.
Unacknowledged alarm in mimic diagrams are indicated by flashing icon background, these alarms can be acknowledged in the following way: - Make a right click on the icon, this will open a small pop up menu, from this menu the alarm can be acknowledged by a left click on the Acknowledge text.
NB!
Alarms can only be acknowledged when the horn is silenced and the GOS is watch station for the actual alarm system.
Unacknowledged alarm in Display Channel diagrams are indicated by flashing State text, these alarms can be acknowledged by a left click on the button.
2.3.7
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 30 of 53 2001.06.01
Open Display Channel diagram for a specific channel is done in different ways depending of which diagram that are currently open. - From the menu bar Click with the left tracker ball/mouse key on the text Diagram in the Menu bar, this will open a drop down list of diagrams, select Display Channel with the cursor and click with the left key. This will open the Display Channel diagram and a list of all channels, select a channel from this list by clicking on the line and click on the OK button (or make a double click on the line). - From the function keys Press the <F8> function key at the keyboard. This will open the Display Channel diagram and a list of all channels, select a channel from this list by clicking on the line and click on the OK button (or make a double click on the line). - From lists (alarm list, alarm group, additional lists and journals) Make a right click somewhere in the channel line, this will open a small pop up menu, from this menu the Display Channel diagram can be opened by a left click on the Display Channel text.
- From a mimic diagram Make a right click on the icon, this will open a small pop up menu, from this menu the Display Channel diagram can be opened by a left click on the Display Channel text.
2.3.8
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 31 of 53 2001.06.01
- Click on the adjust button at the end of the limit that has to be changed, you will be prompted for password level 1, when this is entered the dialogue below will open.
- Change limit, delay or cut-out from the dialogue and click on the OK button. The change will be activated immediately.
2.3.9
Simulation dialogue.
- Enable simulation (On) and key in the value to be display, click the OK button.
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 32 of 53 2001.06.01
If the way through the diagram hierarchy the diagram can also be opened by selecting it by the name: - Click with the left tracker ball/mouse key on the text Edit in the Menu bar, this will open a drop down list, select Open by Name with the cursor and click with the left key. This will open the Open by Name dialogue. Make sure that Diagrams is selected in the Types field, then a list of all diagrams can be obtained by a click on the button in the Name line. Select the desired diagram by a left click on the name in this list, and make a left click on the OK button.
Open by Name dialogue
Find the row for the machinery group in question and click on the button with the name of the new control location. Then the name in the column Actual Control Location will change to the new location, control from the old location will be disabled and control from the new location will be enabled.
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 33 of 53 2001.06.01
Print of Journal. To print a Journal manually it must be opened for display first, se above. When the Journal is displayed in the Journal window it can be printed either form the Menu bar Open and click on Print, or by pressing the Ctrl and the P keys simultaneously. Only the displayed page will be printed.
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 34 of 53 2001.06.01
Under the line already defined Journals are listed, in this case two Journals are defined. To create a new Journal click on Add group... and write the name of the new Journal in the dialogue that appears. Click on Edit again now the name of the new Journal (NewJournal) is added to the list of Journals. Click on the name of the Journal you want to create or change.
A new list appears, click on Add page and write the name of the page in the dialogue that appears.
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 35 of 53 2001.06.01
The selection dialogue consists of a list of available channels in the left side, a list of already selected channels in the right side, some buttons and a name field. Select a channel that shall be included in the Journal from the list of available channels by clicking on the line. Click on the Add button, the channel will be moved from the list of available channels the list of selected channels. Continue in this way until all channels that shall be included in the Journal are moved to the list of selected channels. Channels can be removed from the journal again by selecting the channel in the list of selected channels and click on the Remove button. The order of the channels in the list of selected channels (and in the Journal) can be changed by selecting a channel and then moving it up or down by the up or down button. The name of the page can be changed by editing in the name field. When the list of selected channels is satisfactory click on the OK button, and the final journal page will be displayed.
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 36 of 53 2001.06.01
To define automatic printout of a Journal Click on Edit in the Menu bar Select the Journal that shall be printed automatically and click on Printout.
Now the printout definition dialogue appears, in this dialogue you can select
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 37 of 53 2001.06.01
between Cyclic printout or Daily printout. First enable the printout by clicking in the Enable Printout field, and then define the parameters for the printout: Daily printout: - Select daily printout by clicking in the field - Click on the Add button and define the time for printout. - More times can be defined. - Click on the OK button when finished.
Cyclic printout: - Select cyclic printout by clicking in the field - Define the Start and End time for the printout. Printout will only Be carried out within this interval. - Define the size of the interval between two printouts. - Click on the OK button when finished.
The shown settings will printout at the following times: 01:00, 05:00, 09:00, 13:00 and 17:00.
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 38 of 53 2001.06.01
Overall enabling of automatic printout. Printout of Journals will only take place when Scheduled printout is enabled, Scheduled printout will activate automatic printout for all Journals where Cyclic or Daily printout is defined. Enabling of automatic printout is done like described below. - Click with the left tracker ball/mouse key on the text Diagram in the Menu bar, this will open a drop down list of diagrams, select Journals with the cursor and click with the left key. This will open an empty Journal window and add two more texts in the Menu bar, Open and Edit. - Click on Edit and a drop down list appear. Click on Scheduled printout.
Automatic printout is enabled when there is a check mark in front of the Scheduled printout text.
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 39 of 53 2001.06.01
Click on the Spare Channel button (the button is greyed if the activate spare channel option is not included in this system), and the spare channel list will be opened.
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 40 of 53 2001.06.01
As default the list will display all spare channels both channels that currently are vacant and channels that has previously been activated. Remove the checkmark for Activated to se only channels that still are vacant. Select the sensor type you want to connect by removing the checkmark for all other sensor types, now you will se a list of spare channels for the selected sensor type in all PLCs. If you already know to which PLC the sensor should be connected you can select only to display spare channels for this PLC.
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 41 of 53 2001.06.01
Select the channel you want to activate by clicking on the line, and then click on the Edit button, and the window below will appear.
Click on the Activate field , to open the first page of the channel definition, and then the following window will appear.
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 42 of 53 2001.06.01
In this window the following fields can be edited: - ID: - Name: - Type: Write the new ID for this channel, max. 8 characters. Write the new name for this channel, max. 30 characters. Select between BINARY and BACKUP. - BINARY is a normal monitoring channel (alarm channel). - BACKUP channel is a channel that immediately will call the backup officer when the time delay is passed. Use to call backup officer for a external devices e.g. radar. - Alarm System: - Incl in Data Log: - Alarm Groups: Select the alarm system in which the new monitoring channel shall be included. Mark this field if the channel shall be included in the data log on the printer. The channel is always included in the alarm-even list. Select the alarm groups in which the channel shall be included, by selecting a group and then click on the Add button. One channel can be included in up to 4 different alarm groups or none.
After this page is finished click on the Next button and next page will appear.
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 43 of 53 2001.06.01
In this window the following fields can be edited: - Input definition: - Message text / Normal state: Select between Open contact = Alarm and Closed contact = Alarm Click on the button and select one of the texts. The selected text will be displayed when the channel is in normal state. Click on the button and select one of the texts. The selected text will be displayed when the channel is in alarm state due to limit 1. Normally there is only one alarm limit for a binary channel, but it is possible to define more limits with different delays and priority. - Priority: Click on the button and select 1, 2, 3 or 4.
1 is the highest priority, alarms are indicated with red colour. 2 alarms is indicated in magenta colour.
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 44 of 53 2001.06.01
3 alarms is indicated in yellow colour. 4 event is indicated in white colour, priority 4 is only an indication of events and will not be included in the alarm list or alarm announcement, but will be included in the alarm/even list. - Delay on: - Delay off: Delay from the contact goes in alarm state till the alarm is announced, the delay can be set from 0 to 650 seconds. Delay from contact goes to normal state before the alarm channel goes back to normal, the delay can be set from 0 to 650 seconds.
When the fields in this window are corrected click on the Finish button and the definition of the new monitoring channel will be transferred to the Gamma PLC and the other operator stations. The new monitoring channel will be active immediately.
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 45 of 53 2001.06.01
Select the channel you want to activate by clicking on the line, and then click on the Edit button, and the window below will appear.
Click on the Activate field , to open the first page of the channel definition, and then the following window will appear.
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 46 of 53 2001.06.01
In this window the following fields can be edited: - ID: - Name: - Type: - Alarm System: - Incl in Data Log: - Alarm Groups: Write the new ID for this channel, max. 8 characters. Write the new name for this channel, max. 30 characters. Only ANALOG is possible. Select the alarm system in which the new monitoring channel shall be included. Mark this field if the channel shall be included in the data log on the printer. The channel is always included in the alarm-even list. Select the alarm groups in which the channel shall be included, by selecting a group and then click on the Add button. One channel can be included in up to 4 different alarm groups or none.
After this page is finished click on the Next button and next page will appear.
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 47 of 53 2001.06.01
In this window the following fields can be edited: - Input scaling block: Click on the button and select one of the predefined scaling blocks. Click on the button and select one of the texts. The selected text will be displayed when the channel is in normal state.
- Alarm Limit 1: - Type: Click on the button and select the type of function for this alarm, select between NOT USED, LOW LIMIT and HIGH LIMIT. NOT USED means that there is no alarm based on this limit. LOW LIMIT means that alarm is generated if the value of
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 48 of 53 2001.06.01
the monitoring channel is below the value of this limit for a longer time than specified in Delay on. HIGH LIMIT means that alarm is generated if the value of the monitoring channel is above the value of this limit for a longer time than specified in Delay on.
- Message Text:
Click on the button and select one of the texts. The selected text will be displayed when the channel is in alarm state due to limit 1. Click on the button and select 1, 2, 3 or 4.
- Priority:
1 is the highest priority, alarms are indicated with red colour. 2 alarms is indicated in magenta colour. 3 alarms is indicated in yellow colour. 4 event is indicated in white colour, priority 4 is only an indication of events and will not be included in the alarm list or alarm announcement, but will be included in the alarm/even list. - Limit Value: The value of this limit. Alarm will be generated if the value of the monitoring channel exceeds this limit, alarm for lower value if Type is LOW LIMIT and alarm for higher value if Type is HIGH LIMIT - Delay on: - Delay off: Delay from the contact goes in alarm state till the alarm is announced, the delay can be set from 0 to 650 seconds. Delay from contact gos to normal state before the alarm channel goes back to normal, the delay can be set from 0 to 650 seconds. A monitoring channel can have op to 3 alarm limits. If type for limit 2 is selected different form NOT USED parameters for the second alarm limit can be keyed in, and Limit 3 is made visible. The meaning of parameters for limit 2 and 3 is the same as described above for limit 1. When the fields in this window are corrected click on the Finish button and the definition of the new monitoring channel will be transferred to the Gamma PLC and the other operator stations. The new monitoring channel will be active immediately.
- Limit 2
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 49 of 53 2001.06.01
2.3.14 Change definition of alarm channels, e.g. name, texts and scaling.
From the operator station it is possible to make some changes in definition of alarm channels online. The parameters that can be changed are: - Name of the channel - Membership of Alarm System - Membership of Alarm Groups - Input definition NO or NC for binary channels - Input scaling block for analog channels - Message text - Alarm priority For some channels some of the parameters are locked e.g. if the channel is used by the control system. Changes in a channel will be active immediately after closing the definition window by clicking the OK button. The changes will be transferred to the other operator stations and the PLCs (for printer and panel indication). Changes can be uploaded by a service engineer and imported in the system database, also changes of alarm limits, delays and hour counter values can be uploaded and imported. This means that changes will not get lost in case of a new generation and download of the database. NB: Changes are not included in the backup of the PLC code that is present on the operator stations. This means that changes will be lost if a PLC is loaded from the SystemStatus diagram on the operator station, e.g. after replacement of faulty PLC. On the other hand this can also be use to clean up a system if some unsuccessful changes have been made. Because of this it is important to write down all changes made online, so you are able to remake the changes in case of a new download is needed. Changes in alarm channel definition. - Open the Display Channel Diagram for the channel in question, se section 2.3.7. - Click on the Edit button below will be opened. in the toolbar in the bottom of the window, the diagram
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 50 of 53 2001.06.01
On this page Name, Alarm System, Included in data log and Alarm Groups can be changed. Click on the Input/Limits tab analog channel. to change to next page, shown below for an
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 51 of 53 2001.06.01
On this page Input scaling block and message texts can be changed. The Channel Definition diagrams are the same as used for activation of spare channels, so for details about the parameters refer to the two sections 2.3.13.1 Activate binary channels and 2.3.13.2 Activate analog channels.
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 52 of 53 2001.06.01
- Click on Adjust Date/Time.. button, after keying in the password level 1 the adjust dialogue below will be opened.
Lyngs Marine
970.505.742
UCS 2100, User Manual Operating instruction for Graphic Operator Station (GOS)
Page 53 of 53 2001.06.01
Adjustment can be done via the Time and Date fields or the local time can be moved 20 minutes forwards by clicking on the +20min button or 20 minutes backwards by clicking on the -20min button. - In the display field you can select to use UTC or LT for display in lists and for printouts.
The time displayed in the caption (top of the screen) is not affected by this selection. Selection of which time to display in the caption is done from View in the Menu bar.
If UTC Date/Time is selected the time in caption will be UTC time. If Time Zone is selected the current time zone will be displayed besides the time in caption.
END of DOC
Lyngs Marine
970.505.742