Grouping Factors For Cables Laid Direct in The Ground

The document provides grouping factors for cables laid directly in the ground or in single way ducts. It gives the factors for different voltages of single core cables and multicore cables arranged in trefoil or flat formations at varying spacings. The factors range from 0.52 to 0.96 depending on the number of circuits, configuration, spacing and voltage of the cables. Closer spacings and multicore arrangements have higher factors.

Uploaded by

nksuthar5399
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
630 views4 pages

Grouping Factors For Cables Laid Direct in The Ground

The document provides grouping factors for cables laid directly in the ground or in single way ducts. It gives the factors for different voltages of single core cables and multicore cables arranged in trefoil or flat formations at varying spacings. The factors range from 0.52 to 0.96 depending on the number of circuits, configuration, spacing and voltage of the cables. Closer spacings and multicore arrangements have higher factors.

Uploaded by

nksuthar5399
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

GROUPING FACTORS FOR CABLES

LAID DIRECT IN THE GROUND


Three Single Core Cables
In trefoil and laid flat touching horizontal formation
(average values)
Spacing
No of
circuits

Spacing

Spacing of circuits
Touching
Trefoil

Flat

0.15m*

0.3m

0.45m

0.6m

600/1000 volt cables

2
3
4
5
6

0.77
0.65
0.59
0.55
0.52

0.80
0.68
0.63
0.58
0.56

0.82
0.72
0.67
0.63
0.60

0.88
0.79
0.75
0.72
0.70

0.90
0.83
0.81
0.78
0.77

0.93
0.87
0.85
0.83
0.82

1900/3300 to
12700/22000 volt
cables

2
3
4
5
6

0.78
0.66
0.59
0.55
0.52

0.80
0.68
0.62
0.58
0.55

0.81
0.71
0.65
0.61
0.58

0.85
0.76
0.72
0.68
0.66

0.88
0.80
0.76
0.73
0.72

0.90
0.83
0.80
0.77
0.76

2
3
4
5
6

0.79
0.67
0.62
0.57
0.54

0.81
0.70
0.65
0.60
0.57

0.81
0.71
0.65
0.60
0.57

0.85
0.76
0.72
0.68
0.66

0.88
0.80
0.76
0.73
0.72

0.90
0.83
0.80
0.77
0.76

19000/33000
volt cables

* This configuration at 0.15m spacing, may not be practical for the larger
size cables.

13

13:45

GROUPING FACTORS FOR CABLES


LAID DIRECT IN THE GROUND

Multicore Cables
In horizontal formation
(average values)
Spacing
No of
cables in
group

Spacing of circuits

600/1000 volt cables

2
3
4
5
6

Touching
0.81
0.70
0.63
0.59
0.55

0.15m
0.87
0.78
0.74
0.70
0.67

0.3m
0.91
0.84
0.81
0.78
0.76

0.45m
0.93
0.87
0.86
0.83
0.82

0.6m
0.94
0.90
0.89
0.87
0.86

1900/3300 to
12700/22000 volt
cables

2
3
4
5
6

0.80
0.68
0.62
0.57
0.55

0.85
0.75
0.70
0.66
0.63

0.89
0.80
0.77
0.73
0.71

0.90
0.84
0.80
0.78
0.76

0.92
0.86
0.84
0.81
0.80

19000/33000
volt cables

2
3
4
5
6

0.80
0.70
0.64
0.59
0.56

0.83
0.73
0.68
0.63
0.60

0.87
0.78
0.74
0.70
0.68

0.89
0.82
0.78
0.75
0.74

0.91
0.85
0.82
0.79
0.78

13

13:46

GROUPING FACTORS FOR CABLES


IN SINGLE WAY DUCTS
Three Single Core Cables
In trefoil single way ducts, horizontal formation (average values)

Spacing
No of circuits

Spacing of circuits
0.45m
0.6m
0.90
0.93
0.83
0.87
0.81
0.85
0.78
0.83
0.77
0.82

600/1000 volt cables

2
3
4
5
6

Touching
0.86
0.77
0.73
0.70
0.68

1900/3300 to
12700/22000 volt
cables

2
3
4
5
6

0.85
0.75
0.70
0.67
0.64

0.88
0.80
0.76
0.73
0.71

0.90
0.83
0.80
0.77
0.76

19000/33000
volt cables

2
3
4
5
6

0.85
0.76
0.71
0.67
0.65

0.88
0.80
0.76
0.73
0.71

0.90
0.83
0.80
0.77
0.76

13

13:48

GROUPING FACTORS FOR CABLES


IN SINGLE WAY DUCTS

Multicore Cables
In single way ducts, horizontal formation (average values)
Spacing
No of ducts
in group

13

13:49

Spacing of circuits

600/1000 volt cables

2
3
4
5
6

Touching
0.90
0.82
0.78
0.75
0.72

0.3m
0.93
0.87
0.85
0.82
0.81

0.45m
0.95
0.90
0.89
0.87
0.86

0.6m
0.96
0.93
0.91
0.90
0.90

1900/3300 to
12700/22000 volt
cables

2
3
4
5
6

0.88
0.80
0.75
0.71
0.69

0.91
0.84
0.81
0.77
0.75

0.93
0.87
0.84
0.82
0.80

0.94
0.89
0.87
0.85
0.84

19000/33000
volt cables

2
3
4
5
6

0.87
0.78
0.73
0.69
0.67

0.89
0.82
0.78
0.75
0.73

0.92
0.85
0.82
0.79
0.78

0.93
0.87
0.85
0.83
0.82