Submittal GREENHECK PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 72
At a glance
Powered by AI
The document provides specifications and performance details for an energy recovery ventilator (ERV) model called the Minivent-750. An ERV recovers energy from exhaust air to precondition outdoor air for ventilation.

The ERV consists of an energy recovery cassette with a desiccant wheel, two direct drive blower and motor assemblies, forward curved steel wheels, ball bearing motors, and fan shafts in permanently lubricated rubber mounted ball bearings.

The ERV improves indoor air quality by exchanging heat and moisture between incoming outdoor air and outgoing exhaust air through an enthalpy wheel. It improves energy efficiency by preconditioning the outdoor air to reduce heating and cooling loads.

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.

29 Product Type: Energy Recovery Mark: ERV-1-555

DESCRIPTION Model Minivent-750 Elevation (ft) 11 Qty 1 Approximate Weight (lb) 250

MiniVent

Energy Recovery Ventilator

--Weight does NOT include skid/crating and may vary by 15% based on options selected. OUTDOOR AIR PERFORMANCE Volume External SP Total SP (CFM) (in wg) (in wg) 695 0.41 0.41

FRPM 1320

Motor Size (hp) 1/3

EXHAUST AIR PERFORMANCE Volume External SP Total SP (CFM) (in wg) (in wg) 700 0.41 0.41

FRPM 1328

Motor Size (hp) 1/3

STANDARD CONSTRUCTION FEATURES Exterior housing constructed of galvanized steel Energy recovery cassette with a desiccant wheel Two direct drive blower and motor assemblies Forward curved steel wheels Ball bearing motors Fan shafts in permanently lubricated rubber mounted ball bearings Corrosion resistant fasteners Housing lined with 1 in insulation Pleated 1 in filters (30% efficient) Single point wiring Four factory mounted hanging brackets Removable panels enable easy access to internal components

ARRANGEMENT OA Intake Position Side MOTOR SPECS V/C/P 115/60/1 ELECTRICAL Minimum Circuit Amps (A) 18.3 Max. Over Current Protection (A) 25 Enclosure ODP RPM 1625 Efficiency Standard OA Discharge Position Side EA Intake Position Side EA Discharge Position Side

SELECTED ACCESSORIES Unit Listed to UL-1995 Frost Control: Timed Exhaust Panel Non UL Listed Spare Filter Set 4 Supply, 4 Exhaust Model GRSF-12 (Intake Roof Cap - Flat Flanged) Model GRSF-12 (Discharge Roof Cap - Flat Flanged) Neoprene Vibration Isolation Kit, Base Mounting Solid State Speed Controllers, (2) 10WSSC, Shipped Loose

SUPPLY FAN SOUND PERFORMANCE Supply Outlet Sound Power by Octave Band Lwa 62.5 71.2 125 76 250 62 500 55 1000 50 2000 46.4 4000 39.8 8000 34.8 62.3 50.8 dBA

EXHAUST FAN SOUND PERFORMANCE Exhaust Inlet Sound Power by Octave Band Lwa 62.5 71.3 125 76 250 62 500 55 1000 50 2000 46.4 4000 39.7 8000 34.7 62.3 50.8 dBA

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 2 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-1-555

MiniVent
Energy Recovery Wheel Performance
Energy Recovery Ventilator Summer Design Conditions
OUTDOOR AIR Model Entering Air Dry Bulb (F) Wet Bulb (F) Specific Humidity (gr/lb) Enthalpy (BTU/lb) Leaving Air Dry Bulb (F) Wet Bulb (F) Specific Humidity (gr/lb) 86.4 70 83.8 90 72 89.5 35.7 Leaving Air Dry Bulb (F) Wet Bulb (F) Specific Humidity (gr/lb) Enthalpy (BTU/lb) Entering Air Dry Bulb (F) Rel. Humidity (%) Specific Humidity (gr/lb) 75 50 64.9 78.5 65 70.7 29.9 OA Load w/o Energy Recovery OA Load with Energy Recovery Reduction tons saved Minivent-750 Outdoor Vol. (CFM) 695 OA Wheel Effectiveness 76.8 Exhaust Vol. (CFM) 700 EA Wheel Effectiveness 76.3

OUTDOOR AIR COOLING LOAD REDUCTION (BTU/h) 23,769.0 5,629.0 (tons) 1.98 0.47 1.51

Enthalpy (BTU/lb)

33.9

Enthalpy (BTU/lb)

28.1

EXHAUST AIR

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 3 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-1-555

MiniVent
Energy Recovery Wheel Performance
Energy Recovery Ventilator Winter Design Conditions
OUTDOOR AIR Model Entering Air Dry Bulb (F) Wet Bulb (F) Specific Humidity (gr/lb) Enthalpy (BTU/lb) Leaving Air Dry Bulb (F) Wet Bulb (F) Specific Humidity (gr/lb) 45.1 38.9 25.1 38 31.9 16.8 11.7 Leaving Air Dry Bulb (F) Wet Bulb (F) Specific Humidity (gr/lb) Enthalpy (BTU/lb) Entering Air Dry Bulb (F) Rel. Humidity (%) Specific Humidity (gr/lb) 68 50 51.1 61 52.1 43.5 21.4 OA Load w/o Energy Recovery OA Load with Energy Recovery Reduction BTU/hr. Saved Minivent-750 Outdoor Vol. (CFM) 695 OA Wheel Effectiveness 76.8 Exhaust Vol. (CFM) 700 EA Wheel Effectiveness 76.3

OUTDOOR AIR COOLING LOAD REDUCTION (BTU/h) 22,706.0 5,298.0 17,408.0

Enthalpy (BTU/lb)

14.7

Enthalpy (BTU/lb)

24.3

EXHAUST AIR

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 4 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-1-555

Volume (L/sec) Model Supply Minivent-750 695 Exhaust 700

OA Wheel Efficiency 76.8

Minivent
Cooling Load w/o Energy Recovery (kJ) 0 0 0 0 1,007,993 23,148,503 51,271,606 16,528,839 994,545 Cooling Totals

Energy Saving Analysis

Cooling Range (C) 112 107 102 97 92 87 82 77 72

Total Hours Annually 0 0 0 0 25 587 1690 762 64

Enthalpy (kJ/kg) 0.0 0.0 0.0 0.0 41.0 40.7 37.8 35.0 33.1

Cooling Load with Energy Recover (kJ) 0 0 0 0 233,854 5,370,453 11,895,013 3,834,691 230,734

Annual Savings (kJ) 0 0 0 0 774,139 17,778,050 39,376,593 12,694,148 763,811

Annual Savings (Dollars) 0 0 0 0 8 189 420 135 8

92,951,486

21,564,745

71,386,741

$ 760

Heating Range (C) 62 57 52 47 42 37 32 27 22 17 12 7 2 -3 -8 -13 -18

Total Hours Annually 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Heating Totals

Heating Load w/o Energy Recovery (kJ) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Heating Load with Energy Recover (kJ) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Annual Savings (kJ) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Annual Savings (Dollars) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

$ Energy Savings Cost $ 760

Design Conditions Outdoor Dry Bulb (C) Summer Winter 90.0 38.0 Indoor Relative Humidity (%) 50.0

Notes: Location 1. Operating Time 2. Electric Cost ($) 3. Heat Source 72.0 31.9 75.0 68.0 4. Heating Cost ($) 50.0 Caracas (Venezuela) 12 hours/day 5 days/week 0.08 Gas 0.8

Wet Bulb Dry Bulb (C) (C)

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 6 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-1-555

Type: WHEEL Tilt Angle (Heating/Cooling): N / A Deg Pressure Drop: (in wg) 1

Nominal Airflow: (CFM)

900

Leakage Ratings
Pressure Differential Test 1: Test 2: Test 3: Optional Add'l Test(s): -0.5 0.0 0.5 EATR 0.1 0.0 0.0 OACF 1.11 1.28 1.42 Purge Angle or Setting 0 0 0

Thermal Effectiveness Ratings at 0" Pressure Differential


Sensible
100% Airflow Heating Condition: 75% Airflow Heating Condition: 100% Airflow Cooling Condition: 75% Airflow Cooling Condition:

Latent
60 70 60 70

Total
70 70 70 70

70 80 70 80

Net Sensible
100% Airflow Heating Condition: 75% Airflow Heating Condition: 100% Airflow Cooling Condition: 75% Airflow Cooling Condition:

Net Latent
60 70 60 70

Net Total
70 70 70 70 Minivent-750

70 80 70 80

Trademark:

Greenheck

Model Number:

NOTE:

scfm = Standard Cubic Feet per Minute EATR = Exhaust Air Transfer Ratio OACF = Outdoor Air Correction Factor N / A = Not Applicable Energy Recovery component certified in accordance with ARI Standard 1060-2001. Actual performance in packaged equipment may vary.

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 7 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-1-555

MiniVent
Supply Air Performance Curve Minivent-750 Energy Recovery Ventilator
OUTDOOR AIR PERFORMANCE Volume (CFM) 695 External SP (in wg) 0.41 Total SP (in wg) 0.41 FRPM 1320 Motor Size (hp) 1/3

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 8 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-1-555

MiniVent
Exhaust Air Performance Curve Minivent-750 Energy Recovery Ventilator
EXHAUST AIR PERFORMANCE Volume (CFM) 700 External SP (in wg) 0.41 Total SP (in wg) 0.41 FRPM 1328 Motor Size (hp) 1/3

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 9 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-1-555

System EER Analysis


These calculations, per ARI Guideline V-2003, should be used to assist the designer in calculating the energy efficiency impact of applied energy recovery ventilation equipment.

Recovery Efficiency of Energy Wheel


Recovery Efficiency Ratio (RER) Energy Recovery Coefficient of Performance (ER COP) 53.91 15.8

Energy Efficiency of System


Unitary Net Cooling (tons) Equipment EER 1.00 11 21.06

Combined Efficiency (CEF)

Recovery Efficiency Ratio (RER): The ratio of energy recovered by the energy recovery wheel to the energy expended in the recovery process. Energy Efficiency Ratio (EER): The ratio of the cooling capacity in Btu/h to the power input of air conditioning equipment. This number is given by the unitary or condensing unit manufacturer. Coefficient of Performance (COP): A ratio of the cooling / heating capacity in watts [W] to the power input values in watts[W]. Combined Efficiency (CEF): The efficiency of a system combining an ERV component with a unitary packaged air conditioner, heat pump, etc.

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 10 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-1-555

550

1163

221
"SIDE B" DISCHARGE 9" X 10"
02/29/08 FOLTA

XXXXXX

179

ELECTRICAL CONNECTION

892

ACCESS PANEL

"SIDE A" INTAKE 7" X 18" "SIDE A" DISCHARGE 9" X 10"

359

115

"SIDE B" INTAKE 7" X 18"

114 179 218

BLOWER "B"

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

BLOWER "A"

WHEEL

359

Page 11 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-1-555

ELECTRICAL CONNECTION BLOWER "B"

892

1163

BLOWER "A"

550

WHEEL

ACCESS PANEL

FOLTA 02/29/08

XXXXXX

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 12 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-1-555

Unit Warranty
Limited Warranty
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of 1 year(s) from the purchase date. The energy recovery wheel is warranted to be free from defects in material and workmanship for a period of five years from the purchase date. Any component which proves defective during the warranty period will be repaired, or replaced, at Greenheck's sole option when returned to our factory, transportation prepaid. The warranty does not include labor costs associated with troubleshooting, removal, or installation. Greenheck will not be liable for any consequential, punitive, or incidental damages resulting from use, repair, or operation of any Greenheck product. This warranty is exclusive, and is in lieu of all other warranties, whether written, oral or implied, including the warranty of merchantability and the warranty of fitness for a particular purpose.

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 13 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-2-555

DESCRIPTION Model Minivent-750 Elevation (ft) 11 Qty 1 Approximate Weight (lb) 250

MiniVent

Energy Recovery Ventilator

--Weight does NOT include skid/crating and may vary by 15% based on options selected. OUTDOOR AIR PERFORMANCE Volume External SP Total SP (CFM) (in wg) (in wg) 570 0.67 0.67

FRPM 1232

Motor Size (hp) 1/3

EXHAUST AIR PERFORMANCE Volume External SP Total SP (CFM) (in wg) (in wg) 485 0.67 0.67

FRPM 1124

Motor Size (hp) 1/3

STANDARD CONSTRUCTION FEATURES Exterior housing constructed of galvanized steel Energy recovery cassette with a desiccant wheel Two direct drive blower and motor assemblies Forward curved steel wheels Ball bearing motors Fan shafts in permanently lubricated rubber mounted ball bearings Corrosion resistant fasteners Housing lined with 1 in insulation Pleated 1 in filters (30% efficient) Single point wiring Four factory mounted hanging brackets Removable panels enable easy access to internal components

ARRANGEMENT OA Intake Position Side MOTOR SPECS V/C/P 115/60/1 ELECTRICAL Minimum Circuit Amps (A) 18.3 Max. Over Current Protection (A) 25 Enclosure ODP RPM 1625 Efficiency Standard OA Discharge Position Side EA Intake Position Side EA Discharge Position Side

SELECTED ACCESSORIES Unit Listed to UL-1995 Frost Control: Timed Exhaust Panel Non UL Listed Spare Filter Set 4 Supply, 4 Exhaust Neoprene Vibration Isolation Kit, Base Mounting Solid State Speed Controllers, (2) 10WSSC, Shipped Loose

SUPPLY FAN SOUND PERFORMANCE Supply Outlet Sound Power by Octave Band Lwa 62.5 74.5 125 74.4 250 62 500 49.6 1000 51.1 2000 48.6 4000 45.3 8000 41.3 61.5 50 dBA

EXHAUST FAN SOUND PERFORMANCE Exhaust Inlet Sound Power by Octave Band Lwa 62.5 74.9 125 73.3 250 62 500 45.9 1000 51.8 2000 49.7 4000 47.5 8000 44.3 61.1 49.6 dBA

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 14 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-2-555

MiniVent
Energy Recovery Wheel Performance
Energy Recovery Ventilator Summer Design Conditions
OUTDOOR AIR Model Entering Air Dry Bulb (F) Wet Bulb (F) Specific Humidity (gr/lb) Enthalpy (BTU/lb) Leaving Air Dry Bulb (F) Wet Bulb (F) Specific Humidity (gr/lb) 87.6 70.7 85.8 90 72 89.5 35.7 Leaving Air Dry Bulb (F) Wet Bulb (F) Specific Humidity (gr/lb) Enthalpy (BTU/lb) Entering Air Dry Bulb (F) Rel. Humidity (%) Specific Humidity (gr/lb) 75 50 64.9 79.3 65.5 72 30.3 OA Load w/o Energy Recovery OA Load with Energy Recovery Reduction tons saved Minivent-750 Outdoor Vol. (CFM) 570 OA Wheel Effectiveness 71.5 Exhaust Vol. (CFM) 485 EA Wheel Effectiveness 84

OUTDOOR AIR COOLING LOAD REDUCTION (BTU/h) 19,494.0 5,643.0 (tons) 1.62 0.47 1.15

Enthalpy (BTU/lb)

34.5

Enthalpy (BTU/lb)

28.1

EXHAUST AIR

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 15 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-2-555

MiniVent
Energy Recovery Wheel Performance
Energy Recovery Ventilator Winter Design Conditions
OUTDOOR AIR Model Entering Air Dry Bulb (F) Wet Bulb (F) Specific Humidity (gr/lb) Enthalpy (BTU/lb) Leaving Air Dry Bulb (F) Wet Bulb (F) Specific Humidity (gr/lb) 42.8 36.7 22.2 38 31.9 16.8 11.7 Leaving Air Dry Bulb (F) Wet Bulb (F) Specific Humidity (gr/lb) Enthalpy (BTU/lb) Entering Air Dry Bulb (F) Rel. Humidity (%) Specific Humidity (gr/lb) 68 50 51.1 59.5 50.8 41.4 20.7 OA Load w/o Energy Recovery OA Load with Energy Recovery Reduction BTU/hr. Saved Minivent-750 Outdoor Vol. (CFM) 570 OA Wheel Effectiveness 71.5 Exhaust Vol. (CFM) 485 EA Wheel Effectiveness 84

OUTDOOR AIR COOLING LOAD REDUCTION (BTU/h) 18,622.0 5,276.0 13,346.0

Enthalpy (BTU/lb)

13.7

Enthalpy (BTU/lb)

24.3

EXHAUST AIR

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 16 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-2-555

Volume (L/sec) Model Supply Minivent-750 570 Exhaust 485

OA Wheel Efficiency 71.5

Minivent
Cooling Load w/o Energy Recovery (kJ) 0 0 0 0 826,699 18,985,104 42,050,094 13,556,026 815,670 Cooling Totals

Energy Saving Analysis

Cooling Range (C) 112 107 102 97 92 87 82 77 72

Total Hours Annually 0 0 0 0 25 587 1690 762 64

Enthalpy (kJ/kg) 0.0 0.0 0.0 0.0 41.0 40.7 37.8 35.0 33.1

Cooling Load with Energy Recover (kJ) 0 0 0 0 235,609 5,410,755 11,984,277 3,863,467 232,466

Annual Savings (kJ) 0 0 0 0 591,090 13,574,349 30,065,817 9,692,559 583,204

Annual Savings (Dollars) 0 0 0 0 6 145 320 103 6

76,233,593

21,726,574

54,507,019

$ 580

Heating Range (C) 62 57 52 47 42 37 32 27 22 17 12 7 2 -3 -8 -13 -18

Total Hours Annually 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Heating Totals

Heating Load w/o Energy Recovery (kJ) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Heating Load with Energy Recover (kJ) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Annual Savings (kJ) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Annual Savings (Dollars) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

$ Energy Savings Cost $ 580

Design Conditions Outdoor Dry Bulb (C) Summer Winter 90.0 38.0 Indoor Relative Humidity (%) 50.0

Notes: Location 1. Operating Time 2. Electric Cost ($) 3. Heat Source 72.0 31.9 75.0 68.0 4. Heating Cost ($) 50.0 Caracas (Venezuela) 12 hours/day 5 days/week 0.08 Gas 0.8

Wet Bulb Dry Bulb (C) (C)

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 18 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-2-555

Type: WHEEL Tilt Angle (Heating/Cooling): N / A Deg Pressure Drop: (in wg) 1

Nominal Airflow: (CFM)

900

Leakage Ratings
Pressure Differential Test 1: Test 2: Test 3: Optional Add'l Test(s): -0.5 0.0 0.5 EATR 0.1 0.0 0.0 OACF 1.11 1.28 1.42 Purge Angle or Setting 0 0 0

Thermal Effectiveness Ratings at 0" Pressure Differential


Sensible
100% Airflow Heating Condition: 75% Airflow Heating Condition: 100% Airflow Cooling Condition: 75% Airflow Cooling Condition:

Latent
60 70 60 70

Total
70 70 70 70

70 80 70 80

Net Sensible
100% Airflow Heating Condition: 75% Airflow Heating Condition: 100% Airflow Cooling Condition: 75% Airflow Cooling Condition:

Net Latent
60 70 60 70

Net Total
70 70 70 70 Minivent-750

70 80 70 80

Trademark:

Greenheck

Model Number:

NOTE:

scfm = Standard Cubic Feet per Minute EATR = Exhaust Air Transfer Ratio OACF = Outdoor Air Correction Factor N / A = Not Applicable Energy Recovery component certified in accordance with ARI Standard 1060-2001. Actual performance in packaged equipment may vary.

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 19 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-2-555

MiniVent
Supply Air Performance Curve Minivent-750 Energy Recovery Ventilator
OUTDOOR AIR PERFORMANCE Volume (CFM) 570 External SP (in wg) 0.67 Total SP (in wg) 0.67 FRPM 1232 Motor Size (hp) 1/3

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 20 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-2-555

MiniVent
Exhaust Air Performance Curve Minivent-750 Energy Recovery Ventilator
EXHAUST AIR PERFORMANCE Volume (CFM) 485 External SP (in wg) 0.67 Total SP (in wg) 0.67 FRPM 1124 Motor Size (hp) 1/3

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 21 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-2-555

System EER Analysis


These calculations, per ARI Guideline V-2003, should be used to assist the designer in calculating the energy efficiency impact of applied energy recovery ventilation equipment.

Recovery Efficiency of Energy Wheel


Recovery Efficiency Ratio (RER) Energy Recovery Coefficient of Performance (ER COP) 56.33 16.5

Energy Efficiency of System


Unitary Net Cooling (tons) Equipment EER 1.00 11 19.45

Combined Efficiency (CEF)

Recovery Efficiency Ratio (RER): The ratio of energy recovered by the energy recovery wheel to the energy expended in the recovery process. Energy Efficiency Ratio (EER): The ratio of the cooling capacity in Btu/h to the power input of air conditioning equipment. This number is given by the unitary or condensing unit manufacturer. Coefficient of Performance (COP): A ratio of the cooling / heating capacity in watts [W] to the power input values in watts[W]. Combined Efficiency (CEF): The efficiency of a system combining an ERV component with a unitary packaged air conditioner, heat pump, etc.

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 22 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-2-555

550

1163

221
"SIDE B" DISCHARGE 9" X 10"
02/29/08 FOLTA

XXXXXX

179

ELECTRICAL CONNECTION

892

ACCESS PANEL

"SIDE A" INTAKE 7" X 18" "SIDE A" DISCHARGE 9" X 10"

359

115

"SIDE B" INTAKE 7" X 18"

114 179 218

BLOWER "B"

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

BLOWER "A"

WHEEL

359

Page 23 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-2-555

ELECTRICAL CONNECTION BLOWER "B"

892

1163

BLOWER "A"

550

WHEEL

ACCESS PANEL

FOLTA 02/29/08

XXXXXX

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 24 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-2-555

Unit Warranty
Limited Warranty
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of 1 year(s) from the purchase date. The energy recovery wheel is warranted to be free from defects in material and workmanship for a period of five years from the purchase date. Any component which proves defective during the warranty period will be repaired, or replaced, at Greenheck's sole option when returned to our factory, transportation prepaid. The warranty does not include labor costs associated with troubleshooting, removal, or installation. Greenheck will not be liable for any consequential, punitive, or incidental damages resulting from use, repair, or operation of any Greenheck product. This warranty is exclusive, and is in lieu of all other warranties, whether written, oral or implied, including the warranty of merchantability and the warranty of fitness for a particular purpose.

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 25 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-3-555

DESCRIPTION Model Minivent-750 Elevation (ft) 11 Qty 1 Approximate Weight (lb) 250

MiniVent

Energy Recovery Ventilator

--Weight does NOT include skid/crating and may vary by 15% based on options selected. OUTDOOR AIR PERFORMANCE Volume External SP Total SP (CFM) (in wg) (in wg) 555 0.51 0.51

FRPM 1148

Motor Size (hp) 1/3

EXHAUST AIR PERFORMANCE Volume External SP Total SP (CFM) (in wg) (in wg) 460 0.51 0.51

FRPM 1028

Motor Size (hp) 1/3

STANDARD CONSTRUCTION FEATURES Exterior housing constructed of galvanized steel Energy recovery cassette with a desiccant wheel Two direct drive blower and motor assemblies Forward curved steel wheels Ball bearing motors Fan shafts in permanently lubricated rubber mounted ball bearings Corrosion resistant fasteners Housing lined with 1 in insulation Pleated 1 in filters (30% efficient) Single point wiring Four factory mounted hanging brackets Removable panels enable easy access to internal components

ARRANGEMENT OA Intake Position Side MOTOR SPECS V/C/P 115/60/1 ELECTRICAL Minimum Circuit Amps (A) 18.3 Max. Over Current Protection (A) 25 Enclosure ODP RPM 1625 Efficiency Standard OA Discharge Position Side EA Intake Position Side EA Discharge Position Side

SELECTED ACCESSORIES Unit Listed to UL-1995 Frost Control: Timed Exhaust Panel Non UL Listed Spare Filter Set 4 Supply, 4 Exhaust Neoprene Vibration Isolation Kit, Base Mounting Solid State Speed Controllers, (2) 10WSSC, Shipped Loose

SUPPLY FAN SOUND PERFORMANCE Supply Outlet Sound Power by Octave Band Lwa 62.5 74.3 125 75.1 250 62 500 52 1000 50.6 2000 47.9 4000 43.8 8000 39.4 61.8 50.3 dBA

EXHAUST FAN SOUND PERFORMANCE Exhaust Inlet Sound Power by Octave Band Lwa 62.5 74.7 125 73.8 250 62 500 47.8 1000 51.4 2000 49.2 4000 46.3 8000 42.8 61.2 49.7 dBA

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 26 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-3-555

MiniVent
Energy Recovery Wheel Performance
Energy Recovery Ventilator Summer Design Conditions
OUTDOOR AIR Model Entering Air Dry Bulb (F) Wet Bulb (F) Specific Humidity (gr/lb) Enthalpy (BTU/lb) Leaving Air Dry Bulb (F) Wet Bulb (F) Specific Humidity (gr/lb) 87.8 70.9 86.1 90 72 89.5 35.7 Leaving Air Dry Bulb (F) Wet Bulb (F) Specific Humidity (gr/lb) Enthalpy (BTU/lb) Entering Air Dry Bulb (F) Rel. Humidity (%) Specific Humidity (gr/lb) 75 50 64.9 79.4 65.5 71.8 30.3 OA Load w/o Energy Recovery OA Load with Energy Recovery Reduction tons saved Minivent-750 Outdoor Vol. (CFM) 555 OA Wheel Effectiveness 70.5 Exhaust Vol. (CFM) 460 EA Wheel Effectiveness 85

OUTDOOR AIR COOLING LOAD REDUCTION (BTU/h) 18,981.0 5,494.0 (tons) 1.58 0.46 1.12

Enthalpy (BTU/lb)

34.6

Enthalpy (BTU/lb)

28.1

EXHAUST AIR

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 27 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-3-555

MiniVent
Energy Recovery Wheel Performance
Energy Recovery Ventilator Winter Design Conditions
OUTDOOR AIR Model Entering Air Dry Bulb (F) Wet Bulb (F) Specific Humidity (gr/lb) Enthalpy (BTU/lb) Leaving Air Dry Bulb (F) Wet Bulb (F) Specific Humidity (gr/lb) 42.5 36.4 22 38 31.9 16.8 11.7 Leaving Air Dry Bulb (F) Wet Bulb (F) Specific Humidity (gr/lb) Enthalpy (BTU/lb) Entering Air Dry Bulb (F) Rel. Humidity (%) Specific Humidity (gr/lb) 68 50 51.1 59.2 50.7 41.2 20.6 OA Load w/o Energy Recovery OA Load with Energy Recovery Reduction BTU/hr. Saved Minivent-750 Outdoor Vol. (CFM) 555 OA Wheel Effectiveness 70.5 Exhaust Vol. (CFM) 460 EA Wheel Effectiveness 85

OUTDOOR AIR COOLING LOAD REDUCTION (BTU/h) 18,132.0 5,319.0 12,813.0

Enthalpy (BTU/lb)

13.6

Enthalpy (BTU/lb)

24.3

EXHAUST AIR

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 28 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-3-555

Volume (L/sec) Model Supply Minivent-750 555 Exhaust 460

OA Wheel Efficiency 70.5

Minivent
Cooling Load w/o Energy Recovery (kJ) 0 0 0 0 804,944 18,485,496 40,943,512 13,199,289 794,205 Cooling Totals

Energy Saving Analysis

Cooling Range (C) 112 107 102 97 92 87 82 77 72

Total Hours Annually 0 0 0 0 25 587 1690 762 64

Enthalpy (kJ/kg) 0.0 0.0 0.0 0.0 41.0 40.7 37.8 35.0 33.1

Cooling Load with Energy Recover (kJ) 0 0 0 0 237,458 5,453,221 12,078,336 3,893,790 234,290

Annual Savings (kJ) 0 0 0 0 567,486 13,032,275 28,865,176 9,305,499 559,915

Annual Savings (Dollars) 0 0 0 0 6 139 308 99 6

74,227,446

21,897,095

52,330,351

$ 558

Heating Range (C) 62 57 52 47 42 37 32 27 22 17 12 7 2 -3 -8 -13 -18

Total Hours Annually 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Heating Totals

Heating Load w/o Energy Recovery (kJ) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Heating Load with Energy Recover (kJ) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Annual Savings (kJ) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Annual Savings (Dollars) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

$ Energy Savings Cost $ 558

Design Conditions Outdoor Dry Bulb (C) Summer Winter 90.0 38.0 Indoor Relative Humidity (%) 50.0

Notes: Location 1. Operating Time 2. Electric Cost ($) 3. Heat Source 72.0 31.9 75.0 68.0 4. Heating Cost ($) 50.0 Caracas (Venezuela) 12 hours/day 5 days/week 0.08 Gas 0.8

Wet Bulb Dry Bulb (C) (C)

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 30 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-3-555

Type: WHEEL Tilt Angle (Heating/Cooling): N / A Deg Pressure Drop: (in wg) 1

Nominal Airflow: (CFM)

900

Leakage Ratings
Pressure Differential Test 1: Test 2: Test 3: Optional Add'l Test(s): -0.5 0.0 0.5 EATR 0.1 0.0 0.0 OACF 1.11 1.28 1.42 Purge Angle or Setting 0 0 0

Thermal Effectiveness Ratings at 0" Pressure Differential


Sensible
100% Airflow Heating Condition: 75% Airflow Heating Condition: 100% Airflow Cooling Condition: 75% Airflow Cooling Condition:

Latent
60 70 60 70

Total
70 70 70 70

70 80 70 80

Net Sensible
100% Airflow Heating Condition: 75% Airflow Heating Condition: 100% Airflow Cooling Condition: 75% Airflow Cooling Condition:

Net Latent
60 70 60 70

Net Total
70 70 70 70 Minivent-750

70 80 70 80

Trademark:

Greenheck

Model Number:

NOTE:

scfm = Standard Cubic Feet per Minute EATR = Exhaust Air Transfer Ratio OACF = Outdoor Air Correction Factor N / A = Not Applicable Energy Recovery component certified in accordance with ARI Standard 1060-2001. Actual performance in packaged equipment may vary.

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 31 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-3-555

MiniVent
Supply Air Performance Curve Minivent-750 Energy Recovery Ventilator
OUTDOOR AIR PERFORMANCE Volume (CFM) 555 External SP (in wg) 0.51 Total SP (in wg) 0.51 FRPM 1148 Motor Size (hp) 1/3

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 32 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-3-555

MiniVent
Exhaust Air Performance Curve Minivent-750 Energy Recovery Ventilator
EXHAUST AIR PERFORMANCE Volume (CFM) 460 External SP (in wg) 0.51 Total SP (in wg) 0.51 FRPM 1028 Motor Size (hp) 1/3

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 33 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-3-555

System EER Analysis


These calculations, per ARI Guideline V-2003, should be used to assist the designer in calculating the energy efficiency impact of applied energy recovery ventilation equipment.

Recovery Efficiency of Energy Wheel


Recovery Efficiency Ratio (RER) Energy Recovery Coefficient of Performance (ER COP) 55.74 16.33

Energy Efficiency of System


Unitary Net Cooling (tons) Equipment EER 1.00 11 19.14

Combined Efficiency (CEF)

Recovery Efficiency Ratio (RER): The ratio of energy recovered by the energy recovery wheel to the energy expended in the recovery process. Energy Efficiency Ratio (EER): The ratio of the cooling capacity in Btu/h to the power input of air conditioning equipment. This number is given by the unitary or condensing unit manufacturer. Coefficient of Performance (COP): A ratio of the cooling / heating capacity in watts [W] to the power input values in watts[W]. Combined Efficiency (CEF): The efficiency of a system combining an ERV component with a unitary packaged air conditioner, heat pump, etc.

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 34 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-3-555

550

1163

221
"SIDE B" DISCHARGE 9" X 10"
02/29/08 FOLTA

XXXXXX

179

ELECTRICAL CONNECTION

892

ACCESS PANEL

"SIDE A" INTAKE 7" X 18" "SIDE A" DISCHARGE 9" X 10"

359

115

"SIDE B" INTAKE 7" X 18"

114 179 218

BLOWER "B"

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

BLOWER "A"

WHEEL

359

Page 35 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-3-555

ELECTRICAL CONNECTION BLOWER "B"

892

1163

BLOWER "A"

550

WHEEL

ACCESS PANEL

FOLTA 02/29/08

XXXXXX

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 36 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-3-555

Unit Warranty
Limited Warranty
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of 1 year(s) from the purchase date. The energy recovery wheel is warranted to be free from defects in material and workmanship for a period of five years from the purchase date. Any component which proves defective during the warranty period will be repaired, or replaced, at Greenheck's sole option when returned to our factory, transportation prepaid. The warranty does not include labor costs associated with troubleshooting, removal, or installation. Greenheck will not be liable for any consequential, punitive, or incidental damages resulting from use, repair, or operation of any Greenheck product. This warranty is exclusive, and is in lieu of all other warranties, whether written, oral or implied, including the warranty of merchantability and the warranty of fitness for a particular purpose.

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 37 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-1-3307

DESCRIPTION Model ERV-361S-15-A Elevation (ft) 11 Qty 1 Approximate Weight (lb) 729

ERV

Energy Recovery Ventilator

--Weight does NOT include skid/crating and may vary by 15% based on options selected. OUTDOOR AIR PERFORMANCE Volume (CFM) 1157 External SP (in wg) 0.77 Total SP (in wg) 0.875 FRPM 1274 Operating Motor Size Power (hp) (hp) 0.591 3/4 STANDARD CONSTRUCTION FEATURES FRPM 1154 Operating Motor Size Power (hp) (hp) 0.377 1/2 Exterior housing constructed of galvanized steel Energy recovery cassette with a desiccant wheel Two blower and motor assemblies Forward curved steel wheels Ball bearings motors Fan shafts in permanently lubricated rubber mounted ball bearings Mounted on unit base with neoprene isolators Corrosion resistant fasteners Housing lined with 1 inch-3# density foil faced insulation Single point wiring Internally mounted control center with door interlocking disconnect, motor starters, 24 VAC control transformer, control circuit fusing when required Motor mounted on adjustable plate Adjustable motor pulleys Static free belts SELECTED ACCESSORIES Listed to UL-1995 Outdoor Air Filter - 2" MERV 8 Exhaust Air Filter(s) - 2" MERV 8

EXHAUST AIR PERFORMANCE Volume (CFM) 950 External SP (in wg) 0.77 Total SP (in wg) 0.841

ARRANGEMENT OA Intake Position End MOTOR SPECS V/C/P 208/60/3 ELECTRICAL Minimum Circuit Amps (A) 8.3 Max. Over Current Protection (A) 15 Enclosure ODP RPM 1725 Supply Efficiency SE Exhaust Efficiency SE OA Discharge Position End EA Intake Position End EA Discharge Position End

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 38 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-1-3307

ERV
Energy Recovery Wheel Performance
Energy Recovery Ventilator Summer Design Conditions
OUTDOOR AIR Model Entering Air Dry Bulb (F) Wet Bulb (F) Specific Humidity (gr/lb) Enthalpy (BTU/lb) Leaving Air Dry Bulb (F) Wet Bulb (F) Specific Humidity (gr/lb) 88 71 86.5 90 72 89.5 35.7 Leaving Air Dry Bulb (F) Wet Bulb (F) Specific Humidity (gr/lb) Enthalpy (BTU/lb) Entering Air Dry Bulb (F) Rel. Humidity (%) Specific Humidity (gr/lb) 75 50 64.9 79.4 65.5 71.8 30.3 OA Load w/o Energy Recovery OA Load with Energy Recovery Reduction tons saved ERV-361S-15-A Outdoor Vol. (CFM) 1157 OA Wheel Effectiveness 71 Exhaust Vol. (CFM) 950 EA Wheel Effectiveness 86.5

OUTDOOR AIR COOLING LOAD REDUCTION (BTU/h) 39,569.0 11,454.0 (tons) 3.30 0.95 2.34

Enthalpy (BTU/lb)

34.7

Enthalpy (BTU/lb)

28.1

EXHAUST AIR

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 39 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-1-3307

ERV
Energy Recovery Wheel Performance
Energy Recovery Ventilator Winter Design Conditions
OUTDOOR AIR Model Entering Air Dry Bulb (F) Wet Bulb (F) Specific Humidity (gr/lb) Enthalpy (BTU/lb) Leaving Air Dry Bulb (F) Wet Bulb (F) Specific Humidity (gr/lb) 42.3 35.5 19.8 38 31.9 16.8 11.7 Leaving Air Dry Bulb (F) Wet Bulb (F) Specific Humidity (gr/lb) Enthalpy (BTU/lb) Entering Air Dry Bulb (F) Rel. Humidity (%) Specific Humidity (gr/lb) 70 35 38.2 60.7 48.7 31.8 19.5 OA Load w/o Energy Recovery OA Load with Energy Recovery Reduction BTU/hr. Saved ERV-361S-15-A Outdoor Vol. (CFM) 1157 OA Wheel Effectiveness 71 Exhaust Vol. (CFM) 950 EA Wheel Effectiveness 86.5

OUTDOOR AIR HEATING LOAD REDUCTION (BTU/h) 40,319.0 11,718.0 28,601.0

Enthalpy (BTU/lb)

13.2

Enthalpy (BTU/lb)

22.7

EXHAUST AIR

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 40 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-1-3307

Volume (L/sec) Model Supply ERV-361S-15 1157 Exhaust 950

OA Wheel Efficiency 71

ERV
Cooling Load w/o Energy Recovery (kJ) 0 0 0 0 1,678,055 38,536,430 85,354,313 27,516,355 1,655,667 Cooling Totals

Energy Saving Analysis

Cooling Range (C) 112 107 102 97 92 87 82 77 72

Total Hours Annually 0 0 0 0 25 587 1690 762 64

Enthalpy (kJ/kg) 0.0 0.0 0.0 0.0 41.0 40.7 37.8 35.0 33.1

Cooling Load with Energy Recover (kJ) 0 0 0 0 486,636 11,175,565 24,752,751 7,979,743 480,143

Annual Savings (kJ) 0 0 0 0 1,191,419 27,360,865 60,601,562 19,536,612 1,175,524

Annual Savings (Dollars) 0 0 0 0 13 292 646 208 13

154,740,820

44,874,838

109,865,982

$ 1,172

Heating Range (C) 62 57 52 47 42 37 32 27 22 17 12 7 2 -3 -8 -13 -18

Total Hours Annually 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Heating Totals

Heating Load w/o Energy Recovery (kJ) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Heating Load with Energy Recover (kJ) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Annual Savings (kJ) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Annual Savings (Dollars) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

$ Energy Savings Cost $ 1,172

Design Conditions Outdoor Dry Bulb (C) Summer Winter 90.0 38.0 Indoor Relative Humidity (%) 50.0

Notes: Location 1. Operating Time 2. Electric Cost ($) 3. Heat Source 72.0 31.9 75.0 70.0 4. Heating Cost ($) 35.0 Caracas (Venezuela) 12 hours/day 5 days/week 0.08 Gas 0.8

Wet Bulb Dry Bulb (C) (C)

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 42 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-1-3307

ERV
Exhaust Air Performance Curve ERV-361S-15-A Energy Recovery Ventilator
EXHAUST AIR PERFORMANCE Volume (CFM) 950 External SP (in wg) 0.77 Total SP (in wg) 0.841 FRPM 1154 Operating Power (hp) 0.377 Motor Size (hp) 1/2

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 43 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-1-3307

ERV
Supply Air Performance Curve ERV-361S-15-A Energy Recovery Ventilator
OUTDOOR AIR PERFORMANCE Volume (CFM) 1157 External SP (in wg) 0.77 Total SP (in wg) 0.875 FRPM 1274 Operating Power (hp) 0.591 Motor Size (hp) 3/4

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 44 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-1-3307
EXHAUST AIR DISCHARGE EXHAUST AIR FILTERS RETURN AIR INTAKE

EXHAUST AIR

EXHAUST FAN ENERGY RECOVERY WHEEL

OUTDOOR AIR FILTERS

SUPPLY FAN

SUPPLY AIR

OUTDOOR AIR INTAKE

SUPPLY AIR DISCHARGE

STANDARD FACTORY PROVIDED CONTROLS ITEM DESCRIPTION UNIT MOUNTED CONTROL CENTER DOOR INTERLOCKING DISCONNECT SWITCH SUPPLY MOTOR STARTER EXHAUST MOTOR STARTER CONTROL CIRCUIT FUSING CONTROL TRANSFORMER FOR 24 VAC CONTROL TERMINAL STRIP FOR FIELD WIRING TYPE -

OPTIONAL FACTORY PROVIDED CONTROLS ITEM DESCRIPTION TYPE

Manufacturer reserves the right to change, modify, or improve this product at any time.

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 45 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-1-3307

Controls By Others
BASIC UNIT CONTROLS: The Energy Recovery Unit will be provided from the factory with an integral control center including: a single non-fused disconnect, 24 VAC transformer, terminal strip, fan starters (contactor and overload) and an energy wheel contactor. COOLING CONTROL HEATING CONTROL ON/OFF CONTROL: Within the unit control center, a digital signal must be field wired into the terminal strip (connecting terminals R and G) to control unit startup or shutdown. This on/off signal is coming from: Startup (Digital Contact Closes) Outdoor air damper actuator is energized and powers open Exhaust air damper actuator is energized and powers open Exhaust blower starts Supply blower starts Energy Wheel is energized Shutdown (Digital Contact Opens) Supply blower is de-energized Exhaust blower is de-energized Outside air damper actuator de-energized, damper spring-return closed Exhaust air damper actuator de-energized, damper spring-return closed Energy Wheel de-energized FROST CONTROL OPTION None: No frost control option is being provided by factory. WHEEL CONTROL (ECONOMIZER) OPTION None: No wheel control is provided by the factory. The energy wheel will run at full speed during operation of unit.

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 46 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-1-3307

Type: WHEEL Tilt Angle (Heating/Cooling): N / A Deg Pressure Drop: (in wg) 1

Nominal Airflow: (CFM)

1,400

Leakage Ratings
Pressure Differential Test 1: Test 2: Test 3: Optional Add'l Test(s): -0.5 0.0 0.5 EATR 3.1 0.9 0.4 OACF 1.03 1.08 1.12 Purge Angle or Setting 0 0 0

Thermal Effectiveness Ratings at 0" Pressure Differential


Sensible
100% Airflow Heating Condition: 75% Airflow Heating Condition: 100% Airflow Cooling Condition: 75% Airflow Cooling Condition:

Latent
72 77 72 77

Total
77 81 76 80

80 83 80 83

Net Sensible
100% Airflow Heating Condition: 75% Airflow Heating Condition: 100% Airflow Cooling Condition: 75% Airflow Cooling Condition:

Net Latent
72 77 72 77

Net Total
77 81 76 80 ERV-361S-15-A

80 83 80 83

Trademark:

Greenheck

Model Number:

NOTE:

scfm = Standard Cubic Feet per Minute EATR = Exhaust Air Transfer Ratio OACF = Outdoor Air Correction Factor N / A = Not Applicable Energy Recovery component certified in accordance with ARI Standard 1060-2001. Actual performance in packaged equipment may vary.

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 47 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-1-3307

System EER Analysis


These calculations, per ARI Guideline V-2003, should be used to assist the designer in calculating the energy efficiency impact of applied energy recovery ventilation equipment.

Recovery Efficiency of Energy Wheel


Recovery Efficiency Ratio (RER) Energy Recovery Coefficient of Performance (ER COP) 49.54 14.52

Energy Efficiency of System


Unitary Net Cooling (tons) Equipment EER 1.00 11 24.15

Combined Efficiency (CEF)

Recovery Efficiency Ratio (RER): The ratio of energy recovered by the energy recovery wheel to the energy expended in the recovery process. Energy Efficiency Ratio (EER): The ratio of the cooling capacity in Btu/h to the power input of air conditioning equipment. This number is given by the unitary or condensing unit manufacturer. Coefficient of Performance (COP): A ratio of the cooling / heating capacity in watts [W] to the power input values in watts[W]. Combined Efficiency (CEF): The efficiency of a system combining an ERV component with a unitary packaged air conditioner, heat pump, etc.

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 48 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-1-3307
2.0" EXHAUST FILTERS ENERGY WHEEL CONTROL PANEL

EXHAUST AIR END DISCHARGE

SUPPLY AIR END INTAKE

SUPPLY AIR END DISCHARGE PLAN 2.0" SUPPLY FILTERS

1301 266 68 219 89 298 486 53 1579

ENERGY WHEEL SUPPLY AIR DISCHARGE

195 457 281

336 461 865 298

457

EXHAUST AIR DISCHARGE SUPPLY AIR INTAKE

219
LEFT ELEVATION

EXHAUST AIR INTAKE

179

RIGHT

ELECTRICAL KNOCKOUT

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 49 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-1-3307

SUPPLY AIR DISCHARGE

EXHAUST AIR INTAKE

2.0" SUPPLY AIR FILTERS

CONTROL PANEL SUPPLY AIR INTAKE

2.0" EXHAUST AIR FILTERS

EXHAUST AIR DISCHARGE

Back Right Isometric

EA CL

RA

CE

SUPPLY AIR INTAKE

1117.6 mm
EXHAUST AIR DISCHARGE

762.0 mm

CL
SUPPLY AIR DISCHARGE

E NC RA A E

LIFT OFF ACCESS DOOR

EXHAUST AIR INTAKE

LIFT OFF ELECTRICAL ACCESS DOOR ELECTRICAL DISCONNECT

Front Left Isometric


CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 50 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-1-3307

DS1 L1 MAIN POWER TO UNIT GROUND L2 L3

ST1 O.L.

GREENHECK
SUPPLY FAN MOTOR ST2 O.L.

Building Value in Air.


Wiring Diagram Code:

G320000XXXXXXXE04
EXHAUST FAN MOTOR

CAUTION
UNIT SHALL BE GROUNDED IN ACCORDANCE WITH N.E.C. POWER MUST BE OFF WHILE SERVICING.

R1

NOTES
USE COPPER CONDUTORS ONLY 60 C FOR TERMINALS RATED LESS THAN 100 AMPS. 75 C FOR TERMINALS RATED 100 AMPS OR MORE. FIELD CONTROL WIRING RESISTANCE SHOULD NOT EXCEED 0.75 OHM. FIELD WIRED FACTORY SUPPLIED AND WIRED

ENERGY WHEEL MOTOR(S)

TR1 MULTI-VOLTAGE PRIMARY 24 SECONDARY R


BLUE

WIRE COLOR CODE


BK GY PK W BLACK GRAY PINK WHITE BL BLUE LT BL LIGHT BLUE PR PURPLE Y YELLOW BR O R BROWN ORANGE RED

C
WHITE

LEGEND
C1 COOLING STAGE 1 RELAY C2 COOLING STAGE 2 RELAY CC COMPRESSOR CONTACTOR CF CONDENSING FAN CONTACTOR CH COMPRESSOR SUMP HEATER DAMPER * D DB POWER DISTRIBUTION BLOCK DL DAMPER LIMIT SWITCH *DS DISCONNECT SWITCH EC ECONOMIZER CONTROLLER FCS CONDENSOR FAN CYCLE SWITCH FU FUSES FU5 CONTROL TRANSFORMER FUSES - NOT ON CLASS II HG HOT GAS REHEAT VALVE HPS HIGH PRESSURE SWITCH - MANUAL RESET LPS LOW PRESSURE SWITCH LT LOW TEMP SENSOR PM PHASE MONITOR PS1 WHEEL FROST PRESSURE SWITCH PS2 SUPPLY DIRTY FILTER PRESSURE SWITCH PS3 EXHAUST DIRTY FILTER PRESSURE SWITCH ENERGY WHEEL RELAY-CONTACTOR *R1 R2 OCCUPIED-UNOCCUPIED RELAY R3 EXHAUST BLOWER VFD RELAY R4 SUPPLY BLOWER VFD RELAY R5 MODULATING WHEEL FROST CONTROL RELAY R6 ECONOMIZER RELAY R7 COMPRESSOR INTERLOCK RELAY R8 COMPRESSOR INTERLOCK RELAY R9 COMPRESSOR 1 RELAY R10 COMPRESSOR 2 RELAY R11 POST HEAT RELAY R12 DEHUMIDIFICATION RELAY R13 COOLING CHANGEOVER RELAY R14 ROTATION SENSOR RELAY R15 ROTATION SENSOR RELAY R16 UNIT RELAY R17 FROST CONTROL RELAY FAN SWITCH oS1 S2 ROTATION SENSOR - LOCATED BY WHEEL S3 ROTATION SENSOR - LOCATED BY WHEEL S4 CALL FOR HEAT SWITCH S5 OCC-UNOCC SWITCH - CLOSED=OCCUPIED-OPEN=UNOCCUPIED S6 CALL FOR COOL S7 CALL FOR COOL S8 CALL FOR MOTOR STARTER * ST T1 FROST CONTROL TIMER TYPICAL SETTINGS T4 ECONOMIZER WHEEL JOG TIMER TYPICAL SETTINGS t1(OFF) = 3 HRS., t2(ON) = 10 SEC. T5 EVAP DELAY OFF TIMER T6 COMPRESSOR MINIMUM OFF TIMER - TYPICAL 3 MIN. T7 COMPRESSOR MINIMUM OFF TIMER - TYPICAL 3 MIN. * TR TRANSFORMER TS1 FROST CONTROL THERMOSTAT - JUMPER TS2 ECONOMIZER LOW LIMIT THERMOSTAT - JUMPER COOL CLOSES ON RISING TEMP. TYPICAL SETTING 50 TS3 ECONOMIZER UPPER LIMIT THERMOSTAT - JUMPER COOL OPENS ON RISING TEMP. TYPICAL SETTING 65 - 2 DIFF. TS5 MODULATING HOT GAS REHEAT THERMOSTAT TS6 INLET AIR COMPRESSOR LOCKOUT TSTAT - JUMPER COOL CLOSES ON RISING TEMP. TYPICAL SETTING 60 - 2 DIFF.

S1 G ST2 O.L.
PINK

ST2 95 96 A2 A1

EXHAUST FAN

ST2 13 14

ST1 O.L.
LT. BLUE

ST1 95
ORANGE

96

A2

A1

SUPPLY FAN

R1 A2 A1

ENERGY WHEEL

Template Drawing: E02

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 51 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-1-3307

Unit Warranty
Limited Warranty
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of 1 year(s) from the purchase date. The energy recovery wheel is warranted to be free from defects in material and workmanship for a period of five years from the purchase date. Any component which proves defective during the warranty period will be repaired, or replaced, at Greenheck's sole option when returned to our factory, transportation prepaid. The warranty does not include labor costs associated with troubleshooting, removal, or installation. Greenheck will not be liable for any consequential, punitive, or incidental damages resulting from use, repair, or operation of any Greenheck product. This warranty is exclusive, and is in lieu of all other warranties, whether written, oral or implied, including the warranty of merchantability and the warranty of fitness for a particular purpose.

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 52 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-2-3307REN

DESCRIPTION Model Minivent-750 Elevation (ft) 11 Qty 1 Approximate Weight (lb) 250

MiniVent

Energy Recovery Ventilator

--Weight does NOT include skid/crating and may vary by 15% based on options selected. OUTDOOR AIR PERFORMANCE Volume External SP Total SP (CFM) (in wg) (in wg) 420 0.61 0.61

FRPM 1017

Motor Size (hp) 1/3

EXHAUST AIR PERFORMANCE Volume External SP Total SP (CFM) (in wg) (in wg) 400 0.61 0.61

FRPM 991

Motor Size (hp) 1/3

STANDARD CONSTRUCTION FEATURES Exterior housing constructed of galvanized steel Energy recovery cassette with a desiccant wheel Two direct drive blower and motor assemblies Forward curved steel wheels Ball bearing motors Fan shafts in permanently lubricated rubber mounted ball bearings Corrosion resistant fasteners Housing lined with 1 in insulation Pleated 1 in filters (30% efficient) Single point wiring Four factory mounted hanging brackets Removable panels enable easy access to internal components

ARRANGEMENT OA Intake Position Side MOTOR SPECS V/C/P 115/60/1 ELECTRICAL Minimum Circuit Amps (A) 18.3 Max. Over Current Protection (A) 25 Enclosure ODP RPM 1625 Efficiency Standard OA Discharge Position Side EA Intake Position Side EA Discharge Position Side

SELECTED ACCESSORIES Unit Listed to UL-1995 Frost Control: Timed Exhaust Panel Non UL Listed Spare Filter Set 4 Supply, 4 Exhaust Neoprene Vibration Isolation Kit, Base Mounting Solid State Speed Controllers, (2) 10WSSC, Shipped Loose

SUPPLY FAN SOUND PERFORMANCE Supply Outlet Sound Power by Octave Band Lwa 62.5 75.1 125 72.6 250 62 500 43.7 1000 52.3 2000 50.4 4000 48.8 8000 46 61.1 49.6 dBA

EXHAUST FAN SOUND PERFORMANCE Exhaust Inlet Sound Power by Octave Band Lwa 62.5 75.2 125 72.3 250 62 500 42.6 1000 52.5 2000 50.7 4000 49.4 8000 46.9 61.1 49.6 dBA

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 53 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-2-3307REN

MiniVent
Energy Recovery Wheel Performance
Energy Recovery Ventilator Summer Design Conditions
OUTDOOR AIR Model Entering Air Dry Bulb (F) Wet Bulb (F) Specific Humidity (gr/lb) Enthalpy (BTU/lb) Leaving Air Dry Bulb (F) Wet Bulb (F) Specific Humidity (gr/lb) 87.6 70.7 85.8 90 72 89.5 35.7 Leaving Air Dry Bulb (F) Wet Bulb (F) Specific Humidity (gr/lb) Enthalpy (BTU/lb) Entering Air Dry Bulb (F) Rel. Humidity (%) Specific Humidity (gr/lb) 75 50 64.9 78 64.6 69.5 29.6 OA Load w/o Energy Recovery OA Load with Energy Recovery Reduction tons saved Minivent-750 Outdoor Vol. (CFM) 420 OA Wheel Effectiveness 79.9 Exhaust Vol. (CFM) 400 EA Wheel Effectiveness 83.9

OUTDOOR AIR COOLING LOAD REDUCTION (BTU/h) 14,364.0 2,835.0 (tons) 1.20 0.24 0.96

Enthalpy (BTU/lb)

34.5

Enthalpy (BTU/lb)

28.1

EXHAUST AIR

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 54 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-2-3307REN

MiniVent
Energy Recovery Wheel Performance
Energy Recovery Ventilator Winter Design Conditions
OUTDOOR AIR Model Entering Air Dry Bulb (F) Wet Bulb (F) Specific Humidity (gr/lb) Enthalpy (BTU/lb) Leaving Air Dry Bulb (F) Wet Bulb (F) Specific Humidity (gr/lb) 42.8 36.7 22.2 38 31.9 16.8 11.7 Leaving Air Dry Bulb (F) Wet Bulb (F) Specific Humidity (gr/lb) Enthalpy (BTU/lb) Entering Air Dry Bulb (F) Rel. Humidity (%) Specific Humidity (gr/lb) 68 50 51.1 62 52.8 44.5 21.8 OA Load w/o Energy Recovery OA Load with Energy Recovery Reduction BTU/hr. Saved Minivent-750 Outdoor Vol. (CFM) 420 OA Wheel Effectiveness 79.9 Exhaust Vol. (CFM) 400 EA Wheel Effectiveness 83.9

OUTDOOR AIR COOLING LOAD REDUCTION (BTU/h) 13,721.0 2,744.0 10,977.0

Enthalpy (BTU/lb)

13.7

Enthalpy (BTU/lb)

24.3

EXHAUST AIR

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 55 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-2-3307REN

Volume (L/sec) Model Supply Minivent-750 420 Exhaust 400

OA Wheel Efficiency 79.9

Minivent
Cooling Load w/o Energy Recovery (kJ) 0 0 0 0 609,147 13,989,024 30,984,280 9,988,651 601,020 Cooling Totals

Energy Saving Analysis

Cooling Range (C) 112 107 102 97 92 87 82 77 72

Total Hours Annually 0 0 0 0 25 587 1690 762 64

Enthalpy (kJ/kg) 0.0 0.0 0.0 0.0 41.0 40.7 37.8 35.0 33.1

Cooling Load with Energy Recover (kJ) 0 0 0 0 122,439 2,811,794 6,227,840 2,007,719 120,805

Annual Savings (kJ) 0 0 0 0 486,708 11,177,230 24,756,440 7,980,932 480,215

Annual Savings (Dollars) 0 0 0 0 5 119 264 85 5

56,172,122

11,290,597

44,881,525

$ 478

Heating Range (C) 62 57 52 47 42 37 32 27 22 17 12 7 2 -3 -8 -13 -18

Total Hours Annually 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Heating Totals

Heating Load w/o Energy Recovery (kJ) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Heating Load with Energy Recover (kJ) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Annual Savings (kJ) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Annual Savings (Dollars) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

$ Energy Savings Cost $ 478

Design Conditions Outdoor Dry Bulb (C) Summer Winter 90.0 38.0 Indoor Relative Humidity (%) 50.0

Notes: Location 1. Operating Time 2. Electric Cost ($) 3. Heat Source 72.0 31.9 75.0 68.0 4. Heating Cost ($) 50.0 Caracas (Venezuela) 12 hours/day 5 days/week 0.08 Gas 0.8

Wet Bulb Dry Bulb (C) (C)

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 57 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-2-3307REN

Type: WHEEL Tilt Angle (Heating/Cooling): N / A Deg Pressure Drop: (in wg) 1

Nominal Airflow: (CFM)

900

Leakage Ratings
Pressure Differential Test 1: Test 2: Test 3: Optional Add'l Test(s): -0.5 0.0 0.5 EATR 0.1 0.0 0.0 OACF 1.11 1.28 1.42 Purge Angle or Setting 0 0 0

Thermal Effectiveness Ratings at 0" Pressure Differential


Sensible
100% Airflow Heating Condition: 75% Airflow Heating Condition: 100% Airflow Cooling Condition: 75% Airflow Cooling Condition:

Latent
60 70 60 70

Total
70 70 70 70

70 80 70 80

Net Sensible
100% Airflow Heating Condition: 75% Airflow Heating Condition: 100% Airflow Cooling Condition: 75% Airflow Cooling Condition:

Net Latent
60 70 60 70

Net Total
70 70 70 70 Minivent-750

70 80 70 80

Trademark:

Greenheck

Model Number:

NOTE:

scfm = Standard Cubic Feet per Minute EATR = Exhaust Air Transfer Ratio OACF = Outdoor Air Correction Factor N / A = Not Applicable Energy Recovery component certified in accordance with ARI Standard 1060-2001. Actual performance in packaged equipment may vary.

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 58 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-2-3307REN

MiniVent
Supply Air Performance Curve Minivent-750 Energy Recovery Ventilator
OUTDOOR AIR PERFORMANCE Volume (CFM) 420 External SP (in wg) 0.61 Total SP (in wg) 0.61 FRPM 1017 Motor Size (hp) 1/3

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 59 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-2-3307REN

MiniVent
Exhaust Air Performance Curve Minivent-750 Energy Recovery Ventilator
EXHAUST AIR PERFORMANCE Volume (CFM) 400 External SP (in wg) 0.61 Total SP (in wg) 0.61 FRPM 991 Motor Size (hp) 1/3

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 60 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-2-3307REN

System EER Analysis


These calculations, per ARI Guideline V-2003, should be used to assist the designer in calculating the energy efficiency impact of applied energy recovery ventilation equipment.

Recovery Efficiency of Energy Wheel


Recovery Efficiency Ratio (RER) Energy Recovery Coefficient of Performance (ER COP) 57.74 16.92

Energy Efficiency of System


Unitary Net Cooling (tons) Equipment EER 1.00 11 18.23

Combined Efficiency (CEF)

Recovery Efficiency Ratio (RER): The ratio of energy recovered by the energy recovery wheel to the energy expended in the recovery process. Energy Efficiency Ratio (EER): The ratio of the cooling capacity in Btu/h to the power input of air conditioning equipment. This number is given by the unitary or condensing unit manufacturer. Coefficient of Performance (COP): A ratio of the cooling / heating capacity in watts [W] to the power input values in watts[W]. Combined Efficiency (CEF): The efficiency of a system combining an ERV component with a unitary packaged air conditioner, heat pump, etc.

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 61 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-2-3307REN

550

1163

221
"SIDE B" DISCHARGE 9" X 10"
02/29/08 FOLTA

XXXXXX

179

ELECTRICAL CONNECTION

892

ACCESS PANEL

"SIDE A" INTAKE 7" X 18" "SIDE A" DISCHARGE 9" X 10"

359

115

"SIDE B" INTAKE 7" X 18"

114 179 218

BLOWER "B"

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

BLOWER "A"

WHEEL

359

Page 62 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-2-3307REN

ELECTRICAL CONNECTION BLOWER "B"

892

1163

BLOWER "A"

550

WHEEL

ACCESS PANEL

FOLTA 02/29/08

XXXXXX

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 63 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-2-3307REN

Unit Warranty
Limited Warranty
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of 1 year(s) from the purchase date. The energy recovery wheel is warranted to be free from defects in material and workmanship for a period of five years from the purchase date. Any component which proves defective during the warranty period will be repaired, or replaced, at Greenheck's sole option when returned to our factory, transportation prepaid. The warranty does not include labor costs associated with troubleshooting, removal, or installation. Greenheck will not be liable for any consequential, punitive, or incidental damages resulting from use, repair, or operation of any Greenheck product. This warranty is exclusive, and is in lieu of all other warranties, whether written, oral or implied, including the warranty of merchantability and the warranty of fitness for a particular purpose.

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 64 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-3-3307REN

DESCRIPTION Model ERV-251H-20-A Elevation (ft) 11 Qty 1 Approximate Weight (lb) 298

ERV

Energy Recovery Ventilator

--Weight does NOT include skid/crating and may vary by 15% based on options selected. OUTDOOR AIR PERFORMANCE Volume (CFM) 940 External SP (in wg) 0.49 Total SP (in wg) 0.66 FRPM 1455 Operating Motor Size Power (hp) (hp) 0.404 1/2 STANDARD CONSTRUCTION FEATURES FRPM 1374 Operating Motor Size Power (hp) (hp) 0.337 1/2 Exterior housing constructed of galvanized steel Energy recovery cassette with a desiccant wheel Two blower and motor assemblies Forward curved steel wheels Ball bearings motors Fan shafts in permanently lubricated rubber mounted ball bearings Mounted on unit base with neoprene isolators Corrosion resistant fasteners Housing lined with 1 inch-3# density foil faced insulation Single point wiring Internally mounted control center with door interlocking disconnect, motor starters, 24 VAC control transformer, control circuit fusing when required Motor mounted on adjustable plate Adjustable motor pulleys Static free belts SELECTED ACCESSORIES Listed to UL-1995 Outdoor Air Filter - 2" MERV 8 Exhaust Air Filter(s) - 2" MERV 8 Solid State Spd Control-10WSSC, Mntd and Wired Internally

EXHAUST AIR PERFORMANCE Volume (CFM) 880 External SP (in wg) 0.49 Total SP (in wg) 0.639

ARRANGEMENT OA Intake Position End MOTOR SPECS V/C/P 208/60/1 ELECTRICAL Minimum Circuit Amps (A) 12.8 Max. Over Current Protection (A) 15 Enclosure ODP RPM 1725 Supply Efficiency SE Exhaust Efficiency SE OA Discharge Position End EA Intake Position End EA Discharge Position End

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 65 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-3-3307REN

ERV
Energy Recovery Wheel Performance
Energy Recovery Ventilator Summer Design Conditions
OUTDOOR AIR Model Entering Air Dry Bulb (F) Wet Bulb (F) Specific Humidity (gr/lb) Enthalpy (BTU/lb) Leaving Air Dry Bulb (F) Wet Bulb (F) Specific Humidity (gr/lb) 86 69.8 83.1 90 72 89.5 35.7 Leaving Air Dry Bulb (F) Wet Bulb (F) Specific Humidity (gr/lb) Enthalpy (BTU/lb) Entering Air Dry Bulb (F) Rel. Humidity (%) Specific Humidity (gr/lb) 75 50 64.9 79.7 65.8 72.6 30.5 OA Load w/o Energy Recovery OA Load with Energy Recovery Reduction tons saved ERV-251H-20-A Outdoor Vol. (CFM) 940 OA Wheel Effectiveness 68.6 Exhaust Vol. (CFM) 880 EA Wheel Effectiveness 73.3

OUTDOOR AIR COOLING LOAD REDUCTION (BTU/h) 32,148.0 10,152.0 (tons) 2.68 0.85 1.83

Enthalpy (BTU/lb)

33.7

Enthalpy (BTU/lb)

28.1

EXHAUST AIR

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 66 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-3-3307REN

ERV
Energy Recovery Wheel Performance
Energy Recovery Ventilator Winter Design Conditions
OUTDOOR AIR Model Entering Air Dry Bulb (F) Wet Bulb (F) Specific Humidity (gr/lb) Enthalpy (BTU/lb) Leaving Air Dry Bulb (F) Wet Bulb (F) Specific Humidity (gr/lb) 46.5 38.7 22.3 37.9 31.8 16.7 11.7 Leaving Air Dry Bulb (F) Wet Bulb (F) Specific Humidity (gr/lb) Enthalpy (BTU/lb) Entering Air Dry Bulb (F) Rel. Humidity (%) Specific Humidity (gr/lb) 70 35 38.2 59.9 48.1 31 19.2 OA Load w/o Energy Recovery OA Load with Energy Recovery Reduction BTU/hr. Saved ERV-251H-20-A Outdoor Vol. (CFM) 940 OA Wheel Effectiveness 68.6 Exhaust Vol. (CFM) 880 EA Wheel Effectiveness 73.3

OUTDOOR AIR HEATING LOAD REDUCTION (BTU/h) 32,859.0 10,339.0 22,520.0

Enthalpy (BTU/lb)

14.6

Enthalpy (BTU/lb)

22.7

EXHAUST AIR

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 67 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-3-3307REN

Volume (L/sec) Model Supply ERV-251H-20 940 Exhaust 880

OA Wheel Efficiency 68.6

ERV
Cooling Load w/o Energy Recovery (kJ) 0 0 0 0 1,363,329 31,308,767 69,345,769 22,355,552 1,345,140 Cooling Totals

Energy Saving Analysis

Cooling Range (C) 112 107 102 97 92 87 82 77 72

Total Hours Annually 0 0 0 0 25 587 1690 762 64

Enthalpy (kJ/kg) 0.0 0.0 0.0 0.0 41.0 40.7 37.8 35.0 33.1

Cooling Load with Energy Recover (kJ) 0 0 0 0 428,085 9,830,953 21,774,571 7,019,643 422,374

Annual Savings (kJ) 0 0 0 0 935,244 21,477,814 47,571,198 15,335,909 922,766

Annual Savings (Dollars) 0 0 0 0 10 229 507 163 10

125,718,557

39,475,626

86,242,931

$ 919

Heating Range (C) 62 57 52 47 42 37 32 27 22 17 12 7 2 -3 -8 -13 -18

Total Hours Annually 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Heating Totals

Heating Load w/o Energy Recovery (kJ) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Heating Load with Energy Recover (kJ) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Annual Savings (kJ) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Annual Savings (Dollars) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

$ Energy Savings Cost $ 919

Design Conditions Outdoor Dry Bulb (C) Summer Winter 90.0 37.9 Indoor Relative Humidity (%) 50.0

Notes: Location 1. Operating Time 2. Electric Cost ($) 3. Heat Source 72.0 31.8 75.0 70.0 4. Heating Cost ($) 35.0 Caracas (Venezuela) 12 hours/day 5 days/week 0.08 Gas 0.8

Wet Bulb Dry Bulb (C) (C)

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 69 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-3-3307REN

ERV
Exhaust Air Performance Curve ERV-251H-20-A Energy Recovery Ventilator
EXHAUST AIR PERFORMANCE Volume (CFM) 880 External SP (in wg) 0.49 Total SP (in wg) 0.639 FRPM 1374 Operating Power (hp) 0.337 Motor Size (hp) 1/2

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 70 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-3-3307REN

ERV
Supply Air Performance Curve ERV-251H-20-A Energy Recovery Ventilator
OUTDOOR AIR PERFORMANCE Volume (CFM) 940 External SP (in wg) 0.49 Total SP (in wg) 0.66 FRPM 1455 Operating Power (hp) 0.404 Motor Size (hp) 1/2

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 71 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-3-3307REN
EXHAUST AIR DISCHARGE EXHAUST AIR FILTERS RETURN AIR INTAKE

EXHAUST AIR

EXHAUST FAN ENERGY RECOVERY WHEEL

OUTDOOR AIR FILTERS

SUPPLY FAN

SUPPLY AIR

OUTDOOR AIR INTAKE

SUPPLY AIR DISCHARGE

OPTIONAL FACTORY PROVIDED SENSORS ITEM DESCRIPTION TYPE

STANDARD FACTORY PROVIDED CONTROLS ITEM DESCRIPTION UNIT MOUNTED CONTROL CENTER DOOR INTERLOCKING DISCONNECT SWITCH SUPPLY MOTOR STARTER EXHAUST MOTOR STARTER CONTROL CIRCUIT FUSING CONTROL TRANSFORMER FOR 24 VAC CONTROL TERMINAL STRIP FOR FIELD WIRING TYPE -

OPTIONAL FACTORY PROVIDED CONTROLS ITEM DESCRIPTION TYPE

Manufacturer reserves the right to change, modify, or improve this product at any time.

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 72 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-3-3307REN

Controls By Others
BASIC UNIT CONTROLS: The Energy Recovery Unit will be provided from the factory with an integral control center including: a single non-fused disconnect, 24 VAC transformer, terminal strip, fan starters (contactor and overload) and an energy wheel contactor. COOLING CONTROL HEATING CONTROL ON/OFF CONTROL: Within the unit control center, a digital signal must be field wired into the terminal strip (connecting terminals R and G) to control unit startup or shutdown. This on/off signal is coming from: Startup (Digital Contact Closes) Outdoor air damper actuator is energized and powers open Exhaust air damper actuator is energized and powers open Exhaust blower starts Supply blower starts Energy Wheel is energized Shutdown (Digital Contact Opens) Supply blower is de-energized Exhaust blower is de-energized Outside air damper actuator de-energized, damper spring-return closed Exhaust air damper actuator de-energized, damper spring-return closed Energy Wheel de-energized FROST CONTROL OPTION None: No frost control option is being provided by factory. WHEEL CONTROL (ECONOMIZER) OPTION None: No wheel control is provided by the factory. The energy wheel will run at full speed during operation of unit.

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 73 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-3-3307REN

Type: WHEEL Tilt Angle (Heating/Cooling): N / A Deg Pressure Drop: (in wg) 1

Nominal Airflow: (CFM)

900

Leakage Ratings
Pressure Differential Test 1: Test 2: Test 3: Optional Add'l Test(s): -0.5 0.0 0.5 EATR 0.1 0.0 0.0 OACF 1.11 1.28 1.42 Purge Angle or Setting 0 0 0

Thermal Effectiveness Ratings at 0" Pressure Differential


Sensible
100% Airflow Heating Condition: 75% Airflow Heating Condition: 100% Airflow Cooling Condition: 75% Airflow Cooling Condition:

Latent
60 70 60 70

Total
70 70 70 70

70 80 70 80

Net Sensible
100% Airflow Heating Condition: 75% Airflow Heating Condition: 100% Airflow Cooling Condition: 75% Airflow Cooling Condition:

Net Latent
60 70 60 70

Net Total
70 70 70 70 ERV-251H-20-A

70 80 70 80

Trademark:

Greenheck

Model Number:

NOTE:

scfm = Standard Cubic Feet per Minute EATR = Exhaust Air Transfer Ratio OACF = Outdoor Air Correction Factor N / A = Not Applicable Energy Recovery component certified in accordance with ARI Standard 1060-2001. Actual performance in packaged equipment may vary.

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 74 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-3-3307REN

System EER Analysis


These calculations, per ARI Guideline V-2003, should be used to assist the designer in calculating the energy efficiency impact of applied energy recovery ventilation equipment.

Recovery Efficiency of Energy Wheel


Recovery Efficiency Ratio (RER) Energy Recovery Coefficient of Performance (ER COP) 39.78 11.66

Energy Efficiency of System


Unitary Net Cooling (tons) Equipment EER 1.00 11 20.76

Combined Efficiency (CEF)

Recovery Efficiency Ratio (RER): The ratio of energy recovered by the energy recovery wheel to the energy expended in the recovery process. Energy Efficiency Ratio (EER): The ratio of the cooling capacity in Btu/h to the power input of air conditioning equipment. This number is given by the unitary or condensing unit manufacturer. Coefficient of Performance (COP): A ratio of the cooling / heating capacity in watts [W] to the power input values in watts[W]. Combined Efficiency (CEF): The efficiency of a system combining an ERV component with a unitary packaged air conditioner, heat pump, etc.

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 75 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-3-3307REN
2.0" EXHAUST FILTERS CONTROL PANEL ENERGY WHEEL

EXHAUST AIR END DISCHARGE

SUPPLY AIR END INTAKE

2.0" SUPPLY FILTERS

SUPPLY AIR END DISCHARGE PLAN

376

861 254 82 1175 89

ENERGY WHEEL

82 254 178
SUPPLY AIR DISCHARGE

EXHAUST AIR DISCHARGE

406 686

406 178 92

178 92 171 124


SUPPLY AIR INTAKE LEFT ELEVATION

171 124
RIGHT EXHAUST AIR INTAKE

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 76 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-3-3307REN

SUPPLY AIR DISCHARGE

EXHAUST AIR INTAKE

2.0" SUPPLY AIR FILTERS

2.0" EXHAUST AIR FILTERS

CONTROL PANEL

SUPPLY AIR INTAKE

EXHAUST AIR DISCHARGE

Back Right Isometric

A LE

NC RA

E
SUPPLY AIR INTAKE

812.8 mm
EXHAUST AIR DISCHARGE

SERVICE DISCONNECT

762.0 mm
N RA CE

CL
SUPPLY AIR DISCHARGE LIFT OFF ACCESS DOOR

EA

EXHAUST AIR INTAKE

Front Left Isometric


CAPS 4.10.1964 C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj Page 77 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-3-3307REN

DS1 L1 MAIN POWER TO UNIT C1 SS L1 T1 L2 SC S M1 SUPPLY FAN Wiring Diagram Code:

GREENHECK
Building Value in Air.

G220000XXXXXXSB01
CAUTION
UNIT SHALL BE GROUNDED IN ACCORDANCE WITH N.E.C. POWER MUST BE OFF WHILE SERVICING.

GROUND

C1 SC L2 T2 E M2 EXHAUST FAN

NOTES
USE COPPER CONDUTORS ONLY 60 C FOR TERMINALS RATED LESS THAN 100 AMPS. 75 C FOR TERMINALS RATED 100 AMPS OR MORE. FIELD CONTROL WIRING RESISTANCE SHOULD NOT EXCEED 0.75 OHM. FIELD WIRED FACTORY SUPPLIED AND WIRED

C1 L2 L3 T3 C1 M3 13 14 ENERGY WHEEL BK GY PK W BLACK GRAY PINK WHITE

WIRE COLOR CODE


BL BLUE LT BL LIGHT BLUE PR PURPLE Y YELLOW BR O R BROWN ORANGE RED

LEGEND
C1 UNIT CONTACTOR * D1 SUPPLY INTAKE DAMPER D2 EXHAUST INTAKE DAMPER DS1 MAIN UNIT DISCONNECT SWITCH * EC ENTHALPY ECONOMIZER CONTROL M1 SUPPLY MOTOR * M2 EXHAUST MOTOR * M3 ENERGY WHEEL MOTOR * PS2 SUPPLY DIRTY FILTER PRESSURE SWITCH PS3 EXHAUST DIRTY FILTER PRESSURE SWITCH R1 ECONOMIZER RELAY R14 ROTATION SENSOR RELAY o S1 FAN SWITCH S2 ROTATION SENSOR (LOCATED BY WHEEL) S6 ECON SWITCH SC SPEED CONTROLLERS * T1 FROST CONTROL TIMER TYPICAL SETTINGS t1(OFF) = 5 MIN., t2(ON) = 30 MIN. T4 ECONOMIZER WHEEL JOG TIMER TYPICAL SETTINGS t1(OFF) = 3 HRS., t2(ON) = 10 SEC. TR TRANSFORMER * TS1 FROST CONTROL THERMOSTAT (JUMPER - COOL) OPENS ON RISING TEMP. TYPICAL SETTING 5 TS2 ECONOMIZER LOW LIMIT THERMOSTAT (JUMPER - COOL) CLOSES ON RISING TEMP. TYP. SETTING 50 TS3 ECONOMIZER UPPER LIMIT THERMOSTAT (JUMPER - COOL) OPENS ON RISING TEMP. TYPICAL SETTING 65 - 2 DIFF.

TR1 MULTI-VOLTAGE PRIMARY 24 SECONDARY C

S1 R G

PINK

C1 A2 A1

WHITE

BLUE

MOTOR CONTACTOR

MOTOR HOUSING 230 VOLT INPUT POWER

BLUE

RED

ORANGE BLACK 230 VOLT INPUT POWER

WHITE BROWN

MOTOR CAPACITOR

BROWN

208/230 VOLT SUPPLY POWER

CAPS 4.10.1964

C:\Users\Fernando Farias\Documents\CAPS\Jobs\GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29.gfcj

Page 78 of 79

Printed Date: 2/13/2013 Job: GEOSA - ROTA - BASE NAVAL2013-02-11 14.57.29 Product Type: Energy Recovery Mark: ERV-3-3307REN

Unit Warranty
Limited Warranty
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of 1 year(s) from the purchase date. The energy recovery wheel is warranted to be free from defects in material and workmanship for a period of five years from the purchase date. Any component which proves defective during the warranty period will be repaired, or replaced, at Greenheck's sole option when returned to our factory, transportation prepaid. The warranty does not include labor costs associated with troubleshooting, removal, or installation. Greenheck will not be liable for any consequential, punitive, or incidental damages resulting from use, repair, or operation of any Greenheck product. This warranty is exclusive, and is in lieu of all other warranties, whether written, oral or implied, including the warranty of merchantability and the warranty of fitness for a particular purpose.