WDG Insitu 210 Obsolete
WDG Insitu 210 Obsolete
WDG Insitu 210 Obsolete
THERMOX
WDG 210/INSITU
OBSOLETE
FEATURES AND BENEFITS
Microprocessor-based controller Menu-driven software NEMA 4X controller and probe Field-serviceable components Field-configurable alarms Field-configurable current output System diagnostics Zirconium oxide technology Cost-effective solution when minimum features required
The WDG 210/Insitu is a costeffective, rugged and reliable flue gas analyzer for net oxygen. It uses industry-proven zirconium oxide sensor technology and has built-in diagnostics and over-temperature cell protection circuitry. The outer probe is highly corrosion resistant and designed for continuous use with minimum attention. The unique design of the Insitu sensor allows the inner tube structure, where the oxygen cell and thermocouple/ furnace assembly are housed, to be easily removed from the outer protection tube, which remains in the process. Since the unit is field serviceable with easy access to all components, there is no need to return the probe to the factory, eliminating extensive downtime and expensive repairs. This analyzer is ideal for anyone looking for a cost effective solution to their oxygen monitoring needs.
Response: 63% of a step change in < 20 seconds Drift: < 0.1% of cell output per month (less than 0.005% O2 per month with 2% O2 applied) Linearity: 1% of output span Repeatability: 1% of output span Max. Flue Gas Temp: 1250F (677C) Environment: Indoor/Outdoor Use Ambient Temp: -5F to 160F (-20C to 71C) Relative Humidity: 10% to 80%, noncondensing Enclosure: NEMA 4X. Optional: CE 0081, Ex II 2 G, EEx d IIC T3 (.5 m, 1 m, 2 m probe lengths only), or NEC explosion proof and purged versions available. (Purged version for subatmospheric process pressure only.) Calibration Gas Requirements: Use all calibration gases @ 10 psig, 3 to 6 scfh (0.70 kg/cm2, 1.41 to 2.82 L/min.)
APPLICATIONS
Package boiler manufacturers Combustion control systems Gas, oil, or coal-fired boilers NOx reduction systems Shipboard boilers
O2 Span Gas: Air or from 1.0% to 100% O2, balance N2 O2 Zero Gas: 2% or from 0.1 to 10% O2, balance N2 www.ametekpi.com
OBSOLETE
INCHES CM
THERMOX
Probe
NEMA 4X Enclosure 2" NPT(M) X 6" (15.24 cm) Add for optional Fliter & Deflector
1.50 3.81
1.50 3.81
3/4" NPT(F) for a temporary support pipe to facilitate installation of long probes
S Customer's Flange
Process Wall
Mounting Flange
Gasket
8.25 20.96
6.00 15.24
X INCHES / CM 8.75 / 22.2 17.75 / 45.1 38.75 / 98.4 74.75 / 189.9 110.75 / 281.3
S INCHES / CM 7.0 / 17.8 16.0 / 40.6 37.0 / 94.0 73.0 / 185.4 109.0 / 276.8
50 / 22.7
3.50 8.89
*APPROX. WEIGHT INCLUDES PROBE + FLANGE. 108 PROBE MUST HAVE INTERNAL SUPPORT PROVIDED BY CUSTOMER. STANDARD THERMOX MOUNTING FLANGES: 3 300# AND 4 150#. OTHER CONFIGURATIONS ARE AVAILABLE UPON REQUEST.
NOTES:
1. All static performance characteristics are with operating variables constant. 2. System accuracy referenced to 0.1 to 10% calibrated range. 3. Response is to calibration gas. SALES AND MANUFACTURING: USA - Delaware USA - Oklahoma
455 Corporate Blvd., Newark DE 19702 Tel: +1-302-456-4400, Fax: +1-302-456-4444 2001 N. Indianwood Ave., Broken Arrow OK 74012 Tel: +1-918-250-7200, Fax: +1-918-459-0165
CANADA - Alberta
2876 Sunridge Way N.E., Calgary, AB T1Y 7H9 Tel: +1-403-235-8400, Fax: +1-403-248-3550
www.ametekpi.com
2012, by AMETEK, Inc. All rights reserved. Printed in the U.S.A. F-0153 Rev. 3 (0312)
One of a family of innovative process analyzer solutions from AMETEK Process Instruments. Specifications subject to change without notice.
8.25 20.96