15kV~27kV Pole mounted Epoxy Molded Automatic Vacuum Recloser with Microprocessor based controller integrated with Remote Terminal Unit(RTU)
1 / 163
www.jinkwang.co.kr
CONTENTS
PART I :
EPOXY MOLDED VACUUM RECLOSER BODY
1. SAFETY INFORMATION.................................................................................................... 6 1.1 Safety for life.............................................................................................................. 6 1.2 Safety Information ..................................................................................................... 6 1.3 Safety Instruction....................................................................................................... 7
2. GENERAL INFORMATION ................................................................................................ 8 2.1 Instruction .................................................................................................................. 8 2.2 Read this Manual First............................................................................................... 8 2.3 Additional Information................................................................................................ 8 2.4 Applied Standards ..................................................................................................... 8 2.5 Quality Standards ...................................................................................................... 8 2.6 Acceptance and Initial Inspection.............................................................................. 8 2.7 Handling and Storage................................................................................................ 9 2.8 Description................................................................................................................. 9 3. RATING & SPECIFICATIONS.......................................................................................... 11
4. CONSTRUCTION ............................................................................................................. 12
5. INSTALLATION PROCEDURE ........................................................................................ 14 5.1 General .................................................................................................................... 14 5.2 Checking items prior to installation.......................................................................... 14 5.3 Installation procedure .............................................................................................. 15 5.3.1 Mount the recloser......................................................................................... 15 5.3.2 Ground the recloser....................................................................................... 17 5.3.3 Install the control ........................................................................................... 18 5.3.4 Ground the controller..................................................................................... 18 5.3.5 Make the high-voltage line connections. ....................................................... 19 5.4 After installation, checking items ............................................................................. 19 5.5 Place the recloser in Service ................................................................................... 19
2 / 163
www.jinkwang.co.kr
6. RECLOER OPERATION .................................................................................................. 20 6.1 Closing Operation.................................................................................................... 20 6.2 Opening Operation .................................................................................................. 20
7. MAINTENANCE ............................................................................................................... 21 7.1 General .................................................................................................................... 21 7.2 Frequency of maintenance ...................................................................................... 21 7.3 Check the recloser visually...................................................................................... 21
1. OVERVIEW....................................................................................................................... 21 1.1 Protection of Distribution Lines................................................................................ 22 1.2 Functions of Automatic Circuit Recloser ................................................................. 22 1.3 Main Features of FTU-R100.................................................................................... 22
2. TECHNICAL DATA........................................................................................................... 24 2.1 Environmental Conditions........................................................................................ 24 2.2 Inputs / Outputs ....................................................................................................... 25 2.3 Measurements......................................................................................................... 27 2.4 Communications...................................................................................................... 29 2.5 Display & Operation panel....................................................................................... 30 2.6 Digital Processor ..................................................................................................... 31 2.7 Settings.................................................................................................................... 33 2.7.1 Fault Detection .............................................................................................. 34 2.7.2 Open Line Detection...................................................................................... 36 2.7.4 Under-frequency detection............................................................................ 37 2.7.5 Setting group select....................................................................................... 37 2.7.6 I/O configuration ............................................................................................ 37 2.7.7 Communication configuration........................................................................ 37
3 / 163
www.jinkwang.co.kr
2.7.8 DNP3.0 protocol configuration ...................................................................... 38 2.7.9 IEC60870-5-101 protocol configuration ........................................................ 38 2.8 Recording ................................................................................................................ 38 2.8.1 Event recording ............................................................................................. 38 2.8.2 Waveform recording ...................................................................................... 39 2.8.3 Counters........................................................................................................ 39 2.9 Maintenance software ............................................................................................. 39
3. CONSTRUCTION AND EXTERNAL CONNECTION ...................................................... 40 3.1 Appearance & Dimension........................................................................................ 40 3.2 Connectors of FTU .................................................................................................. 42 4.1 Button & LED Description........................................................................................ 43 (1) LCD Display............................................................................................... 44 (2) RS232 Communication Port ...................................................................... 44 (3) MENU/UP/DOWN/ENTER Buttons ........................................................... 44 (4) RESET Button ........................................................................................... 44 (5) Run / Error / Rx / Tx / RTS / AC on / Batt. Low LEDs ............................... 44 (6) A-Phase/B-Phase/C-Phase/Ground Fault & SEF LEDs ........................... 44 (7) High Current Trip (HCT) LED .................................................................... 45 (8) Hot Line (Source/Load) LEDs................................................................... 45 (9) Sync. Fail LED ........................................................................................... 45 (10) Reclose Ready LED ................................................................................ 45 (11) Reclose Progress LED............................................................................. 45 (12) Reclose Lockout LED .............................................................................. 45 (13) RECLOSE/PROTECTION/GROUND ENABLE Buttons and LEDs ....... 45 (14) REMOTE CONTROL Button and LED .................................................... 46 (15) BATTERY TEST Button and LED............................................................ 46 (16) SELECT/OPEN/CLOSE Buttons and LEDs ........................................... 46 4.2 LCD Manipulation .................................................................................................... 47 4.2.1 LCD Menus ................................................................................................... 48 (1) Initial Display.............................................................................................. 49 (2) Main Menu Display .................................................................................... 50 (3) Function Setting......................................................................................... 50 (4) Configuration ............................................................................................. 53 (5) Display ....................................................................................................... 56
4 / 163
www.jinkwang.co.kr
(6) Event List ................................................................................................... 57 4.3 Setting & Operation Tool (FTU_SET)...................................................................... 58 (1) Connection between FTU_SET and FTU-R100 ........................................ 59 (2) Setting Window.......................................................................................... 59 (3) Config Window........................................................................................... 61 (4) Event Window............................................................................................ 64 (5) Demand Window ....................................................................................... 65 (6) Sample Recording Window ....................................................................... 66 (7) Measurement Window ............................................................................... 67 (8) Status Window ........................................................................................... 68 (9) Protocol Monitor Window........................................................................... 69 (10) Custom Curve Window ............................................................................ 70
5. PROTECTION FUNCTIONS ............................................................................................ 72 5.1 Auto-Reclosing Sequence ....................................................................................... 72 5.2 HCT (High Current Trip) .......................................................................................... 73 5.3 Cold Load Pickup .................................................................................................... 73 5.4 Inrush Restraints ..................................................................................................... 74 5.5 SEF (Sensitive Earth Fault) Detection..................................................................... 74 5.6 Sequence Coordination ........................................................................................... 75
TC (Time-Current) Characteristic Curves .................................. 80 DNP V3.0 PROTOCOL POINT INDEX .......................................... 93 DNP V3.0 DEVICE PROFILE ...................................................... 117
Implementation Table ....................................................................................................... 122 Appendix 4. Appendix 5. Appendix 6. Appendix 7. DIMENSIONS............................................................................... 126 FTU INSPECTION CHECK LIST................................................. 127 IEC60870-5-101 Interoperability................................................ 134 IEC60870-5-101 Protocol Point Index....................................... 148
5 / 163
www.jinkwang.co.kr
1. SAFETY INFORMATION
1.1 Safety for life Jinkwangs products meet or exceed all applicable industry standards relating to product safety. We actively promote safe practices in the use and maintenance of our products through our technical information, instructional training programs, and the continuous efforts of all Jinkwang employees involved in product design, manufacture, marketing and service.
1.2 Safety Information The instructions in this manual are not intended as a substitute for proper training or adequate experience in the safe operation of the recloser described. Only authorized technicians who are familiar with this recloser should install, operate and service it.
Following is important safety information. For safe installation and operation of the recloser, be sure to read carefully and understand fully followings. Additional statements, related to specific matters and procedures, can be observed throughout this manual.
Danger : Indicates an imminently hazardous situation which, if not avoided, will result in serious injury.
Warning : Indicates a potentially hazardous situation which, if not avoided, could result in serious injury.
Caution : Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury or equipment damage.
6 / 163
www.jinkwang.co.kr
1.3 Safety Instruction Following are general cautions and warning statements that apply to this recloser.
Danger : Follow all locally approved safety procedures when working around high voltage lines and equipment. Contact with hazardous voltage will cause severe personal injury.
Warning : This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply can result in severe personal injury and equipment damage.
The recloser must be selected for the intended application. It must be installed and serviced by proper personal who have been trained and understand proper safety procedures. This instructions are written for such personal and are not a substitute for adequate training and experience in safety procedures. Failure to properly select, install, or maintain this recloser can result in severe personal injury.
Before installing, operating, maintaining or testing this recloser, carefully read and understand the contents of this manual. Improper operation, handling or maintenance may result in severe personal injury, and damage to the recloser.
7 / 163
www.jinkwang.co.kr
2. GENERAL INFORMATION
2.1 Instruction This manual provides installation, operation and maintenance instructions for the JK-REC Type electronically controlled recloser. Before installing and operating this recloser, carefully read and understand the contents of this manual.
2.2 Read this Manual First Read and understand the contents of this manual and follow all locally approved procedures and safety practices before installing and operating this recloser.
2.3 Additional Information This manual cannot cover all details or variations in the recloser, procedures or process described, nor provides directions for meeting every possible contingency during installation, operation or maintenance. When additional information is desired to satisfy a problem not covered sufficiently for the users purpose, please contact your Jin Kwang sales representative.
2.4 Applied Standards The recloser is designed, manufactured and tested in accordance with IEC 60137, IEC 60587, IEC 60707, ANSI C29.11, IEEE C37.60, IEEE C37.71, ANSI C37.85, IEEE C37.90.1, IEEE C37.90.2, IEEE C62.45, and IEEE 1024.
2.5 Quality Standards The recloser shall be manufactured according to ISO9001(1994) quality control system.
2.6 Acceptance and Initial Inspection The recloser is completely assembled, tested, and inspected at the factory. It is good condition when accepted by the carrier for shipment. Upon receipt, inspect the shipping container for signs for damage. Unpack the recloser and inspect it thoroughly for damage incurred during shipment. If damage is discovered, file a claim with carrier immediately.
8 / 163
www.jinkwang.co.kr
2.7 Handling and Storage Be careful during handling and storage of the recloser to minimize the possibility of damage. Only use the lifting lug when lifting the recloser. If the recloser is to be stored for any length of time prior to installation, provide a clean, dry storage area.
2.8 Description New demands for managing distribution systems call for control devices inherently reliable and intelligent. Customers require a built-in capability for data gathering and communication, along with an extremely low maintenance product.
The Jinkwang electronically controlled, three phase automatic recloser (hereinafter referred to as the recloser) provides reliable and economical over-current protection for distribution circuit, ranging from 15 through 27kV.
The recloser senses line current and automatically interrupts the phase of the distribution circuit to which it is connected when line current exceeds the minimum trip level. Next, it automatically recloses to restore ser-vice and monitors the line to determine if the fault has been cleared. If the fault is permanent, the recloser sequences to lockout after one, two, three, or four preset trip operations
Once the recloser sequences to lockout, the recloser must be manually reset to restore service. Should the fault clear before lockout, the recloser will reset automatically for another sequence of operations. The recloser can also be set for non-reclosing operation (lock out after the first trip operation) The recloser can be remotely set for non-reclosing operation via the remote non-reclosing feature. The trip operations of the recloser can be all fast, all delayed, or any combination of fast operations and delayed operations up to a maximum total of four. Fast operations clear temporary faults before branch line fuses are weakened. Delayed operations allow time for fuses or other downline protective devices to clear to limit permanent faults to the smallest section of line.
The recloser meets actively in distribution line protection coordination that change variously by control technology that use microprocessor, and are being operated
9 / 163
www.jinkwang.co.kr
locally or remotely.
The control has a total of 54 built-in T-C curves, and a T-C curve, which has a time multiplier and a minimum response time applied to the fundamental curve and a high current lockout characteristic, allows programming via keypad or RS232
Fault recording for analysis can be backed up using LCD display or handheld controller applying gradually fault recording that need in the maintenance on the distribution lines.
All operating parameters and settings are easily programmable via handheld controller or PC using RS-232 port on the front panel.
The control is equipped with the function of sequence coordination to prevent unnecessary operation of the upstream reclosers when two or more reclosers are being operated in series.
10 / 163
www.jinkwang.co.kr
Description
Unit
Maximum System Voltage Rated Voltage Rated Current Rated Frequency Mechanical Operation(Min.) 4 Breaking Capacity Rated symmetrical interrupting current Short Time Withstand Current(1sec) Making Current(peak) Cable Charging Transformer Magnetizing 5 Impulse Insulation Level(1.250s) Phase to Earth Across Interrupter 6 Power Frequency Insulation Level, dry Phase to Earth Across Interrupter 7 Power Supply Operation Control Circuit 8 Environmental Ambient Temperature Humidity Altitude(*1) 9 Net Weight(Switch Body/ Control Cabinet)
kV kV A Hz C-O
kA kA kA A A
kV kV
150 150
kV kV
60 60
V V
AC127 or AC220 DC 24
C % m kg
11 / 163
www.jinkwang.co.kr
4. CONSTRUCTION
The recloser shall consist of a mechanism housing including magnetic actuator and vacuum interrupter, and controller. The vacuum interrupter provides greatly enhanced long contact life. 2)
1)
3) 4) 10) 5)
6) 7) 8) 9)
1) Polymer bushing part The VI, CT(1000/1) and Voltage sensor are included in polymer bushing part. 2) Terminal connector Universal clamp, NEMA 2 hole terminal or NEMA 4 hole terminal are available. 3) Manual OPEN/LOCK handle Manual OPEN is made with Manual OPEN handle by pulling it down with NEMA hook-stick. When Recloser is trip(open) by means of manual method, Recloser goes to LOCKOUT.
12 / 163
www.jinkwang.co.kr
If you operate the recloser with electric control, the lock handle should be manually returned by hot stick and placed at normal position. 4) Control receptacle to interface with controller 5) Name plate 6) Ground terminal available for 4 ~ 35 mm2 of conductor 7) Operation counter 8) ON/OFF position indicator Position indicator flag is coupled to the recloser mechanism to show the position of the main contacts. When the flag displays Green color, the main contacts are open; When the flag displays Red color, the main contacts are closed. 9) Mounting bracket 10) Lifting & carrying handle
13 / 163
www.jinkwang.co.kr
5. INSTALLATION PROCEDURE
Warning Always use a hot-stick when working with this recloser . Failure to do so could result in contact with high voltage, which will cause severe personal injury.
Solidly ground all equipment. Failure to comply could result in severe personal injury or equipment damage.
Caution Follow all locally approved safety practices when lifting and mounting the recloser. Use the lifting lugs provided. Lift the recloser unit smoothly and do not allow it to shift. Improper lifting can result in its damage.
Do not connect this control to an energized recloser until all control settings have been properly programmed and verified. Refer to the programming information for this control. Failure to comply can result in control and recloser misoperation, equipment damage, and personal injury.
Do not adjust or rotate bushing terminals. The bushing terminals are factorycalibrated to meet the continuous current requirement of the recloser. Adjusting or rotating the bushing terminals can damage the encapsulated interrupter resulting in equipment damage or personal injury.
5.1 General All reclosers are carefully tested and adjusted at the factory to operate according to published data. Well-equipped test facilities, detailed testing procedures, and thoroughly trained personnel assure accurately calibrated equipment. Each recloser leaves the factory ready for installation.
5.2 Checking items prior to installation 1) Check bushings crack and high voltage line connection(bushing terminal).
14 / 163
www.jinkwang.co.kr
Making sure the ratings and settings on the recloser nameplate are correct for the planned installation.
3) Check operation of the switch. Connect control and recloser using the control cable. Connect the control battery Perform several closing/opening pushing close/open buttons and confirm recloser operation via position indicator. The five-digit operations counter should count one operation.
4) Check it thoroughly for damage incurred during storage. Perform high-potential withstand tests. Prior to installing the recloser, perform high potential withstand tests. This test will help discover any shipping damage affecting the dielectric condition of the recloser or the vacuum integrity of the interrupter.
5) Make sure a flash of all lamp status indicators to perform a front-panel lamp test in the control cabinet.
6) Make sure a mounting condition of the control cabinets components such as a batteries, power transformer for power supply, etc.
7) Program the control. FTU-R100 controls are carefully tested at the factory, shipped and ready for operation. Inspect the control and make sure that all TCC program settings are correct for the planned installation. Connect control battery to the battery plug.
Note: The unit should not be stored or shipped with the batteries connected. Even if the recloser is not in service, connected batteries will still expend energy. Disconnect the batteries when the recloser is not in service. Make sure that the control cable is connected between the recloser and control.
5.3.1 Mount the recloser Assembly the mounting frames and then assembly the mounting frames and the recloser Lift the recloser to the pole with suitable lifting ropes and fix the recloser to the pole with hanger bands.
15 / 163
www.jinkwang.co.kr
When lifting the recloser, use the lifting lugs located on the top of the tank and follow approved procedure. At this point, the contacts are opens. Never use its porcelain bushing, bushing terminals nor manual trip handle. These handling will cause the damage to the recloser.
Mounting frames
16 / 163
www.jinkwang.co.kr
No. 1 2 3 4 5 6 7 8 9 10 11
Description
Hex bolt, nut, Spring washer, Plate washer Stud washer Hex bolt, nut, Spring washer, Plate washer Hex bolt, nut, Spring washer, Plate washer Upper band Lower band Vertical bracket Bracket support Vertical bracket Hanger band A Hanger band B
Qty 4 4 4 20 1 1 2 2 2 1 1
5.3.2 Ground the recloser Refer to our typical mounting arrangement as shown in figure. Make ground connections to the recloser with the provided ground connector located on the side of the recloser. Make ground connections in accordance with approved utility standards.
17 / 163
www.jinkwang.co.kr
The following figure shows typical pole type mounting arrangement of the recloser.
5.3.3 Install the control Refer to FTU-R100 microprocessor-based recloser control instruction manual and users guide for complete recommended grounding instruction. Connect the control cable between the control and main body of the recloser.
5.3.4 Ground the controller Ground the control using the ground connector provided at the upper of the control cabinet for connecting 22mm to 60mm stranded grounding cable to a suitable ground. Make ground connections in accordance with approved utility standards. Make sure the control is
2 2
18 / 163
www.jinkwang.co.kr
5.3.5 Make the high-voltage line connections. Provide surge protection to both sides of each recloser. Connect high-voltage lines to the recloser bushing terminals. Connect the high-voltage lines to the bushing terminals with source leads connected to bushings.
5.4 After installation, checking items 1) High voltage wire insulation distance that is connected to bushing terminal should be checked by each phase.(Phase to phase spacing of high voltage wire must keep more than smallest 250 mm). 2) Check installation condition of insulation cover that is mounted to the top end of bushing. 3) Check the work tool remaining and cleanliness condition on the top of main body and mounting hardware. 4) Make sure a position of manual operating and Lock handle (If the lock handle is placed at locking position, it should be manually returned by hot stick and placed at normal position). 5) Make sure a mounting condition of the control cabinets components such as a batteries, power transformer for power supply, etc. 6) Check a charging condition and capacity of batteries using the battery test button in the control. 7) Check a grounding connection of main body and control cabinet. 8) Check a connection condition of the control cable and power cable.
5.5 Place the recloser in Service Always follow locally approved procedures and safety practices when placing the recloser in service. Be sure that 24-volt control back-up battery is properly connected. When the control is connected, the recloser can be placed in service.
19 / 163
www.jinkwang.co.kr
6. RECLOER OPERATION
Warning Do not reply on the open position of the open/lock handle(yellow color) or the contact position indicator; it does not ensure that the line has been de-energized. Always establish a visible disconnect. Failure to follow proper safety practices can result in contact with high voltage, which will cause severe personal injury.
Caution Pushing the yellow manual operating and Lock handle to the closed position will not close the recloser. All close operations are initiated by the FTU-R100 microprocessor-based recloser control.
6.1 Closing Operation Closing operation should be performed with a close button on the control panel. But, before operating the recloser on the control panel, make sure a position of manual OPEN & LOCK handle. Check whether the manual OPEN & LOCK handle indicate LOCK position or not.
Note: When the recloser is closed, the manual operating and Lock handle should be positioned in free condition(upward).
6.2 Opening Operation The manual operating and Lock handle(yellow color) in the recloser is used to open and lock out the recloser. If the recloser is opened with a manual operating & lock handle, it automatically operates to lockout. So, it disable in the electrical and supervisory closing.
The manual operating and Lock handle is designed to be operated with a hot stick. Pulling down the manual operating and Lock handle open the main contacts of the recloser. Contact position is indicated by the open flag of the contact open indicator. The handle will remain down in the open position and not return upward in the close position. Therefore, when the recloser is closed, the manual operating and Lock handle should be positioned in free condition. Note: When the recloser electrically operates to lockout, the OPEN / LOCK operating handle will not drop by the open position. The handle remains in the open position only after manual operations are performed.
20 / 163
www.jinkwang.co.kr
7. MAINTENANCE
Warning Always use a hotstick when working with the recloser. Failure to do so could result in contact with high voltage, which will cause severe personal injury.
Caution The equipment requires routine inspection and maintenance to ensure proper operation. If it is not maintained it may fail to operate properly. Improper operation may cause equipment damage and possible personal injury.
7.1 GeneralJin Kwangs reclosers require inspection and maintenance to ensure proper operation. If the recloser is not adequately maintained, it may fail to operate properly. Even though the recloser has been designed as a low maintenance unit, maintenance interval depends on the local climatic condition. Jin Kwang recommends that the recloser be inspected and maintained for long life.
7.2 Frequency of maintenanceTo assure proper and trouble-free operation, reclosers must be maintained when they have operated the equivalent of a rated duty cycle.
Note: ANSI C 37.61, Guide fot the application, Operation and Maintenance of Automatic Circuit reclosers, gives a procedure for converting the rated standard duty cycle into an equivalent duty cycle based on the actual operating duty of the recloser 7.3 Check the recloser visuallyInspect each of the bushing for breaks, cracks, burn or heavy pollution and other part of the recloser. 1) If polluted, clean the recloser including epoxy molded bushing. 2) If damaged, replace whole of the recloser with new one.
1. OVERVIEW
21 / 163
www.jinkwang.co.kr
1.1 Protection of Distribution Lines Distribution lines have their own equipment outdoors, the types of loads are various, and the configurations of the networks are flexible and complicated. There are many kinds of fault causes such as direct contact of trees or birds, natural phenomenon of lightning or heavy snow, and fault spread-out due to customers facilities. Among these faults, most of faults are temporary and the dominant fault type is ground-fault.
For rapid fault detection and fault section isolation, blackout area minimization, many protection devices such as Recloser, Sectionalizer, and Line Fuse are adopted. Among these devices, Automatic Circuit Recloser is the most important protection device, whose main functions are fault current trip and auto-reclosing.
One distribution line has over 2 Reclosers of serial connections or Recloser Sectionalizer - Line Fuse of serial connections. This configuration is the concept of Primary Protection and Back-up Protection. In other words, protection coordination is required in the way that a protection device nearer to fault point operates first to eliminate the fault and other devices farther from fault point are configured to operate later with time delays.
1.2 Functions of Automatic Circuit Recloser When a fault occurs on the load side of Recloser installed location, Recloser detects fault current, trips fault current at high speed, and does reclosing actions after the set time to reactivate the faulted section. In case of temporary fault, the fault can be removed by itself according to high-speed trip and dead time before reclosing actions. But, in case of permanent fault, because fault current is still detected after trip and reclosing actions of preset counts, Recloser is locked out finally as opened.
Recloser has the time delay element in protection function of its controller and can be freely configured for protection coordination with other protection devices.
1.3 Main Features of FTU-R100 Recloser body is connected serially to distribution line to operate open / close of the line, and Recloser Controller is in charge of measurements of currents, voltages, and other
FTU-R100 is a kind of IEDs (Intelligent Electronic Device) for power system automation,
22 / 163
www.jinkwang.co.kr
which is a fully digitalized and microprocessor-based control device, and through connecting with this control device, Recloser can play a role of automated protection device.
Measurements : Magnitude and phase angle of voltages & currents (Fundamental frequency) Sequence components of 3-phase voltages & currents True RMS, Harmonics and THD of voltages and currents Active, reactive and apparent power for 3-phase and 3-phase Energy (4-quadrant metering) Displacement Power Factor Frequency
Control : Manual Recloser Open / Close at local or remote (SBO operation) Interlocking (Handle lock, Operator place, Sync. Fail, Live Load) Battery test External Trip and Close by contact input (Option) Enable or disable reclosing & protection function
Protection : 3-stage over current protection - Fast and Delayed TC trip elements for phase and earth fault : 54types of Built-in TC Curves & 4 Customized TC Curves - Definite time over-current element - Definite time HCT (High Current Trip) SEF (Sensitive Earth Fault) Detection Auto-Reclosing (up to 4 shots)
Cold Load protection (pickup adjustment) Magnetizing Inrush Restraints Sequence Coordination
23 / 163
www.jinkwang.co.kr
Status Monitoring : 10 Contacts inputs - Recloser Open / Closed, - Locked - External AC Power Loss - Battery over-discharged, - Enclosure Door Open - Spare (3 points : Optionally external trip and close command)
Recording : Event recording with time-stamp - I/O, Functional, System, Fault, Demand Current & Demand Power Fault Waveforms - 8 faults, 32 samples/cycle, 10 cycles FTU Restart Count Switch Open Count Fault Detection Count
Communication Protocols : SCADA Port : DNP3.0, IEC60870-5-101 (optional) with modem control Maintenance Port : MODBUS-RTU
2. TECHNICAL DATA
2.1 Environmental Conditions
24 / 163
www.jinkwang.co.kr
Altitude Wind speed Ambient Temperature Storage Temperature Humidity Dielectric withstand Impulse voltage
< 2,000m < 40m/s - 25 ~ +70C, KSC 0220/1 - 40 ~ +85C < 95%RH IEC 60255-5, 2kV IEC 60255-5, 6kV for current input circuit IEC 60255-5, 4kV for voltage, power input & Contacts I/O IEC 60255-5, >500M (DC500V) IEC 61000-4-12 class 3 (2.5kV) IEC61000-4-4 class 4 (4kV) IEC 61000-4-3 10V/m IEC 60255-21-1 class 2 IEC 60255-21-2 class 2
Insulation resistance High frequency disturbance Fast transient noise Radio frequency noise Vibrations Mechanical Shock Enclosure protection IP54
DC 24V biased in the control box Opto-isolation (Viso) : 2,000Vrms Delay time setting (10~500ms, 5ms step) for each contact input to suppress bouncing Signals Recloser Open Recloser Closed Recloser Locked External AC power fail Battery discharged Control box door open
25 / 163
www.jinkwang.co.kr
DC 24V Aux. Relay Contact Pulse Output Opto-isolation between aux. relay and logic (Viso) : 2,000Vrms Pulse width of output is variable Signals & contact rating Switch Open or Trip, Close Rated current Rated voltage/max. breaking voltage AC Maximum breaking capacity AC Make current (max. 4s at duty cycle 10%) 30 A Dielectric strength coil-contacts open contact circuit Mechanical Life Operate Time 5,000 Vrms 1,000 Vrms > 30 x 106 operations typical 7ms 16 A 250Vac/440Vac 4,000 VA
Battery Test / Spare Rated current 10 A at 250VAC/30VDC (PF=1) 5 A at 250VAC/30VDC (PF=0.4 L/R=7ms) Make current Max. Operating voltage Max. switching capacity 10 A 380 VAC, 125 VDC 2,500VA, 300W (PF=1) 1,250VA, 220W (PF=0.4 L/R=7ms) Dielectric strength coil-contacts open contact circuit Mechanical Life Operate Time 2,000 Vrms 1,000 Vrms typical 50 x 106 operations 10ms max. (typical 5ms)
12.5A maximum (external CT Ratio is 1,000:1 normally) Burden : below than 1VA
26 / 163
www.jinkwang.co.kr
3-phase currents and neutral currents Isolation by auxiliary CT of RTU (Viso) : 2,000Vrms Surge withstand voltage : 6kV Signals - Ia : A-phase current - Ib : B-phase current - Ic : C-Phase current - In : Neutral current
4Vrms at rated phase voltages Burden : below than 0.01VA Maximum input range : ~ 200% Isolation by auxiliary PT of RTU (Viso) : 2,000Vrms Surge withstand voltage : 4kV Signals - Va : A-phase voltage - Vb : B-phase voltage - Vc : C-Phase voltage
2.3 Measurements
Current
27 / 163
www.jinkwang.co.kr
RMS (A) & Phase angle (o) Sequence Component True RMS Reading range Accuracy
Ia, Ib, Ic, In I1 ,I2 , I0 Ia, Ib, Ic 2 ~ 12,500A (External CT ratio 1000:1) 2 ~ 600A 600~12,000A : 0.5% or 1A : 3%
Va, Vb, Vc
Sequence Component V1S (positive seq.), V2S (negative seq.),V0S (zero seq.) V1L (positive seq.), V2L(negative seq.),V0L (zero seq.) True RMS Reading range Accuracy Va, Vb, Vc 0.1 ~ 26kV 0.5% or 0.1kV
Power
Active power (kW) Reactive power (kVAR) Apparent power (kVA) Reading range Accuracy
A phase, B phase, C phase, 3 phase total A phase, B phase, C phase, 3 phase total A phase, B phase, C phase, 3 phase total 0 ~ 32767 1%
Power factor
A phase, B phase, C phase, 3 phase total Lead/lag display Reading range Accuracy 0 ~ 1.00 2%
Frequency
Reading range
28 / 163
www.jinkwang.co.kr
Accuracy
0.02Hz
Energy
Export active energy (kWh) Import active energy (kWh) Capacitive reactive energy (kVARh) Inductive reactive energy (kVARh) Reading range Accuracy
A phase, B phase, C phase, 3 phase total A phase, B phase, C phase, 3 phase total A phase, B phase, C phase, 3 phase total A phase, B phase, C phase, 3 phase total 0 ~ 65535 (Rollover) 2%
Harmonics
Total harmonic distortion (THD, %) 3-phase currents THD (Ia, Ib, Ic, I3ph) Source side 3-phase voltages THD (Vsa, Vsb, Vsc, Vs3ph) 2 ~ 8 harmonics RMS (A, kV)
nd th
Ia,Ib,Ic,Va,Vb,Vc,
Configurable demand interval 5, 10, 15min Ia, Ib, Ic, Pa, Pb, Pc, P3ph, Qa, Qb, Qc, Q3ph Daily max. currents and power are stored.
2.4 Communications
Physical Layer
29 / 163
www.jinkwang.co.kr
RS232C, 9-pin male connector DCD(1), RX(2), TX(3), DTR(4), GND(5) DSR(6), RTS(7), CTS(8), NC(9) Speed (Baud rate) Supports modem control 1200, 2400, 4800, 9600, 19200 BPS RTS, CTS, DCD, DTR, DSR CTS, DCD signal timeout configurable RTS off-delay configurable Optical isolation ESD, Transient noise protection
Supports DNP 3.0 Subset level 2 Class of each point is settable Supports multi-frame transmission (multi-frame interval is configurable) Enable/Disable unsolicited message class Supports file transfer function for uploading fault waveform or local event history Non-transmitted events are stored on non-volatile memory during communication fail Event buffer size : BI (254), AI(127), Counter(19) Supports direct operate or select before operate (SBO) for control output Supports report by exception for analog values Protocol frame monitor was built in FTU
20 characters * 4 lines LCD with LED backlight Button : Menu, Increase, Decrease, Enter Function setting (4 setting groups), FTU configuration
Control Buttons
30 / 163
www.jinkwang.co.kr
Operator place select button : Local / Remote Two step switch control buttons : Select, Open, Close Battery test button Annunciator reset button Reclosing enable button, Protection enable button, Ground protection enable button
LED indicators
Switch status : open, closed Control status : selected, remote position, battery testing Function status : A phase fault, B phase fault, C phase fault, ground fault, SEF(selective earth fault), high current trip, live line (source-side) Reclosing status : ready, progress, lockout FTU status : CPU run, System error, AC power on, battery low Communication status : Rx, Tx, RTS
Serial port
32-bit RISC type micro-controller with on-chip flash program memory 32-bit floating-point digital signal processor Dual-port memory for communication between two processors
Data memory (SRAM) Non-volatile memory (128kBytes) for storing events and parameters Flash Memory for storing fault waveforms Real-time clock
31 / 163
www.jinkwang.co.kr
Analog/Digital conversion
16-bit A/D converter Sampling rate : 64 samples/cycle Anti-aliasing analog filter Two different gain channel for each current input : effective 16-bit resolution for current measurements
DSP
Correction of analog input error Discrete Fourier Transform: phasor calculation Electric quantities calculation & fault decision
CPU
Status monitoring & control Local Human-Machine Interface Event & fault recording Remote communication Self-diagnosis
32 / 163
www.jinkwang.co.kr
MUX.
3 CTs (Ia,Ib,Ic,Io) ZeroCrossing Detector AC 220V Power Transfomer Recursive Discrete Fourier Transform (I, V Phasors Calculation)
Self-Diagnostics
LBS Status
Opto-isolation
Debounce
Remote Station
Waveform Recording MODEM (Optical, Wireless, Leased Line, PLC, CDMA/GSM/ GPRS, Etc.)
LBS Motor
RS232C
Main Processor
2.7 Settings
33 / 163
www.jinkwang.co.kr
2.7.1 Fault Detection Phase fault detection FTU detects the phase fault and trip the breaker. The fastest operating time is within 45ms including auto-recloser operating time. There are 58 trip curves, which can be selected for fast and delayed operation respectively. The curve can be edited by using several parameters, i.e. time multiplier, time adder, minimum response time. And high current trip element can be used for instantaneous trip. Its definite time characteristics. During cold-load condition, pickup multiplied by coldload multiplier. During this condition, time-delayed curve is applied instead of fast curve. This function can be enabled or disabled by protection enable button.
Pickup current (I>) Fast TC curve Fast time multiplier Fast time adder Fast min. response time Fast reset type Fast reset definite time Delayed TC curve Delayed time multiplier Delayed time adder Delayed min. response time Delayed reset type Delayed reset definite time Definite time OC on/off Definite time OC pickup (I>>) Definite time OC response time High current pickup (I>>>) High current trip response time Cold-load multiplier Inrush restraint
10 ~ 900A (1A step) 1 ~ 58 (1 step) 0.10 ~ 2.00 (0.01 step) 0.00 ~ 1.00sec (0.01sec step) 0.00 ~ 1.00sec (0.01sec step) RDMT(Definite)/RIDMT(Inverse time) 0.00 ~ 100.00sec (0.01sec step) 1 ~ 58 (1 step) 0.10 ~ 2.00 (0.01 step) 0.00 ~ 1.00sec (0.01sec step) 0.00 ~ 1.00sec (0.01sec step) RDMT(Definite)/RIDMT(Inverse time) 0.00 ~ 100.00sec (0.01sec step) ON/OFF 50 ~ 10,000A (1A step) 0.00 ~ 1.00sec (0.01sec step) 50 ~ 10,000A (1A step) 0.00 ~ 1.00sec (0.01sec step) 0 ~ 10 (1 step) Yes/No
Earth fault detection Earth fault detection has the same characteristics as the phase fault detection.
34 / 163
www.jinkwang.co.kr
Pickup current (Io>) Fast TC curve Fast time multiplier Fast time adder Fast min. response time Fast reset type Fast reset definite time Delayed TC curve Delayed time multiplier Delayed time adder Delayed min. response time Delayed reset type Delayed reset definite time Definite time OC on/off Definite time OC pickup (Io>>) Definite time OC response time High current pickup (Io>>>) High current trip response time Cold-load multiplier Inrush restraint
5 ~ 900A (1A step) 1 ~ 58 (1 step) 0.10 ~ 2.00 (0.01 step) 0.00 ~ 1.00sec (0.01sec step) 0.00 ~ 1.00sec (0.01sec step) RDMT(Definite)/RIDMT(Inverse time) 0.00 ~ 100.00sec (0.01sec step) 1 ~ 58 (1 step) 0.10 ~ 2.00 (0.01 step) 0.00 ~ 1.00sec (0.01sec step) 0.00 ~ 1.00sec (0.01sec step) RDMT(Definite)/RIDMT(Inverse time) 0.00 ~ 100.00sec (0.01sec step) ON/OFF 50 ~ 10,000A (1A step) 0.00 ~ 1.00sec (0.01sec step) 50 ~ 10,000A (1A step) 0.00 ~ 1.00sec (0.01sec step) 0 ~ 10 (1 step) Yes/No
Sensitive earth fault (SEF) detection FTU can decide whether the earth fault occurred in its own feeder or not selectively in ungrounded network. It has directional elements which is polarized by the calculated zero sequence voltage. It can be used only for alarm
Pickup current (Io) Pickup voltage (Vo) Max. torque angle Detection time Inrush restraint
2 ~ 20A (1A step) 10 ~ 80% of rated phase voltage (1% step) 0,30,60,90,270,300,330 Leading 0.1 ~ 30.00 sec (0.1sec step) Yes/No
Operation select
Off/Alarm/Trip
35 / 163
www.jinkwang.co.kr
Inrush detection This function can be used to detect magnetizing inrush condition by comparing 2nd harmonic component to fundamental frequency component of current. 2nd harmonic pickup (%) Detection time Operation select
Phase Total Operation Count Ground Total Operation Count Phase Inst. Total Operation Count Ground Inst. Total Operation Count Phase HCT Operation Count Ground HCT Operation Count 1 dead time (reclosing time) 2nd dead time (reclosing time) 3 dead time (reclosing time) 4th dead time (reclosing time) Reset time Cold-load duration Cold-load pickup restore time Sequence Coordination
rd st
1 ~ 4 times (1 step) 1 ~ 4 times (1 step) 0 ~ 4 times (1 step) 0 ~ 4 times (1 step) 0 ~ 4 times (1 step) 0 ~ 4 times (1 step) 0.5 ~ 180sec (0.1sec step) 1 ~ 60sec (1sec step) 1 ~ 60sec (1sec step) 1 ~ 60sec (1sec step) 3 ~ 180sec (1sec step) 0.00 ~ 60.00sec (0.01sec step) 0.00 ~ 30.00sec (0.01sec step) On / Off
50 ~ 90% (5% step) 35 ~ 75% (5% step) 0.1 ~ 30.0 sec (0.1sec step)
Operation select
On/Off
36 / 163
www.jinkwang.co.kr
1 ~ 4 (step : 1)
System frequency Rated phase voltage External CT ratio External neutral CT ratio Demand interval DI debounce delay time for DI1..10 DO pulse width for DO1..4 FI (Fault Indicator) reset Phase rotation
50 or 60Hz 3.80 ~ 21.00kV (0.01kV step) 200 ~ 2000 (10 step) 200 ~ 2000 (10 step) 5 ~ 15min. (5min. step) 10 ~ 500ms (5ms step) 10 ~ 2000ms (10ms step) Manual/Auto A-B-C / A-C-B
1200,2400,4800,9600,19200 Bps DNP / IEC (Factory setting) 2 wires (half-duplex) / 4 wires (full-
10 ~ 500ms (5ms step) 1 ~ 255s (1s step) 0.1 ~ 30.0s (0.1s step)
37 / 163
www.jinkwang.co.kr
Data link retry count Data link timeout Data link confirm Application retry count Application retry timeout Initial unsolicited message Unsolicited message delay SBO timeout
0 ~ 2 (1 step) 1 ~ 255s (1s step) Yes/No/Sometimes 0 ~ 2 (1 step) 1 ~ 255s (1s step) Yes/No 0 ~ 60s (1s step) 1 ~ 255s (1s step)
Unsolicited destination address 0 ~ 65534 (1 step) Frame interval 10 ~ 500ms (10ms step)
Class for BI objects (BI0~BI31) 0 ~ 3 (1 step) Class for AI objects (AI0~AI31) 0 ~ 3 (1 step) Class for Special AI objects Class for CNT objects (CNT0~22) 0 ~ 3 (1 step) 0 ~ 3 (1 step)
VOC for AI objects (AI0~AI31) 0 ~ 50% (1% step) VOC lower limit for AI objects 0 ~ 65535 (1 step) 0 ~ 65535 (1 step)
2.8 Recording
5msec Sequence-of-events are stored on non-volatile memory Storage size I/O events Function events System events Fault current events 1023 1023 63 127
38 / 163
www.jinkwang.co.kr
511 31
2.8.3 Counters
Microsoft Windows based application S/W connected to the serial port of front panel
The software can be connected at remote station via DNP3.0 (optional IEC60870-5-101)
Function setting upload & change FTU configuration upload & change Event upload & display Status monitoring & switch control Measurements display Waveform data uploading & graphical display Protocol monitor File & print operation Custom curve editing
39 / 163
www.jinkwang.co.kr
Front panel of FTU-R100 has an operational LCD display, a RS232C port for setting and maintenance, indicating LEDs, and push buttons.
[Fig. 3-1]
40 / 163
www.jinkwang.co.kr
[Fig. 3-2]
The next drawing is Side-view of FTU-R100 panel, and there are measurement module connector, control module connector, monitoring module connector, power connectors, and RS232 port for SCADA communication on the right side of FTU panel.
[Fig. 3-3]
41 / 163
www.jinkwang.co.kr
3.2 Connectors of FTU On the right side of FTU-R100 panel, there are RS232 communication port to SCADA, control source power connector, DI (Status Monitoring) connector, DO (Control) connector, AI (Measurement) connectors for Voltage and Current from top to bottom. RS232C port is DB9 male-type connector.
DC-
3 1 8 1
FG COM3 COM1 COM2 Handle Lock Spare Close Trip Cmd.* Close Battery Test Open Vcom (Source) Vc
DI (Status) Connector
DO (Control) Connector
Spare Close
5 1
AI (Voltage) Connector
Vt Vs
6 1
AI (Current) Connector
Io (-) Io (-)
Ib Ib
Ia Ia
7 1
* Optional [Fig. 3-4] Pin Connectors on the Right Side of FTU-R1004. FRONT PANEL OPERATIONS
42 / 163
www.jinkwang.co.kr
On the front panel, there are LEDs indicating Reclosers status, function buttons and LEDs, control buttons and LEDs, LCD buttons, and a RS232 port for maintenance.
43 / 163
www.jinkwang.co.kr
(1) LCD Display 4 lines * 20 characters LCD is used and through MENU / UP / DOWN / ENTER / RESET buttons, operators can survey all data and correct set values.
(2) RS232 Communication Port Engineering tool on Notebook computer is connected to this port for maintenance. RS232C port for maintenance is DB9 female-type connector.
(3) MENU/UP/DOWN/ENTER Buttons These buttons are used to operate FTU-R100 in local position. Refer to Section 4.2 LCD Manipulation for detailed methods.
(4) RESET Button This button is used for Annunciator LED Reset (LED Off). Annunciator LED represents all the LEDs related to Protection, Reclosing, and Self-diagnosis Error.
(5) Run / Error / Rx / Tx / RTS / AC on / Batt. Low LEDs These LEDs indicate status of FTU-R100.
Run LED is on, when normal operation of FTU (CPU OK). Error LED is on, when Self-diagnosis Error & Communication Trouble. Rx LED is on, when communication data are received. Tx LED is on, when transmitting communication data. RTS LED is on, on data transmission request. AC On LED is on, when External AC Power is supplied. Batt. Low LED is on, when battery voltage is low (discharged).
(6) A-Phase/B-Phase/C-Phase/Ground Fault & SEF LEDs Each LED is on, when a fault related to each faulted phase occurs. For earth fault of nongrounded networks, SEF LED is on. In Auto FI Reset mode, after fault restoration, these fault indicating LEDs are automatically reset (off). On the other hand, in Manual FI Reset mode, operators should do command action for Reset, locally or remotely, to extinguish
44 / 163
www.jinkwang.co.kr
these LEDs. Manual FI Reset mode is for the operators acknowledgement purpose.
(7) High Current Trip (HCT) LED When tripped by a fault current over the set HCT pickup level, this LED is on. HCT function is similar to Instantaneous Protection Element in protective relays.
(8) Hot Line (Source/Load) LEDs These LEDs indicate if the lines to source side and load side are activated or deactivated. LEDs are on, when the line voltage goes up the set Voltage On Level and LEDs are off, when the voltage goes down the set Voltage Off Level.
(9) Sync. Fail LED This LED is on, when the phase angle difference between Source-side voltage (Va) and Load-side voltage (Vr) is over the set value. In this case, Close control command should be inhibited.
(10) Reclose Ready LED This LED is on, when the reclosing action is normally operated. This represents the normal stand-by status for reclosing action.
(11) Reclose Progress LED This LED indicates the status that reclosing action is normally processed according to the preset tripping and reclosing operation sequences.
(12) Reclose Lockout LED This LED is on, when the reclosing action is locked out to open according to the operation sequences or the Recloser is opened by the manual control command.
(13) RECLOSE/PROTECTION/GROUND ENABLE Buttons and LEDs Push the Enable buttons and makes the respective LEDs on to fulfill the Reclosing and Protection functions. These buttons are toggled between Enable and Disable.
45 / 163
www.jinkwang.co.kr
RECLOSE ENABLE button enables or disables the Reclosing Function. In Disable mode, the Recloser is locked out right after the 1st trip.
PROTECTION ENABLE button enables or disables Phase Fault Detection and Earth Fault Detection Functions, simultaneously.
GROUND ENABLE button enables or disables Earth Fault Detection Function only.
(14) REMOTE CONTROL Button and LED To decide the control position to Remote, push this button and make the LED on. This button and LED are also toggled between Remote and Local. But, the manipulation of this button is possible only in the local for operators safety.
(15) BATTERY TEST Button and LED To test the battery and charger circuit, push this button. When the test result is OK, green color LED is on for 3 seconds and off thereafter. Otherwise, LED is not on.
(16) SELECT/OPEN/CLOSE Buttons and LEDs These buttons are used to locally control (Open / Close) the Recloser. Before local control command, check first if the control position is Local. SELECT button is a two-phase safety & confirmation check mechanism, and this concept is similar to SBO (Select Before Operate) in communication protocol. To manually and locally control the Recloser, SELECT button should be pushed down to make the corresponding LED on, and this SELECT function can be expanded to the scheme of Multiple Reclosers Control in the future. SELECT CLOSE : Push this button to control the Recloser manually to be closed. After closing, normal fault detection functions are re-performed. In case that Cold Load Pickup function is off or the load current is below the Cold Load Pickup Level, normal Phase & Ground Fault Detection is functioned. SELECT OPEN : Manual open control opens the Recloser and makes the switch locked out to open.
46 / 163
www.jinkwang.co.kr
MENU / UP / DOWN / ENTER buttons are used to manipulate the LCD. The following table explains the common roles of 4 buttons.
Button
Description
MENU -
To toggle between Main Menu Display from Initial Display To come back to Parent Menu from Child Menu Be careful, because all the set value changes are canceled when this button is pushed down during the change of set values.
ENTER -
To select and enter into each menu item To enter the changed set value and configuration After entering the changed set value, this button again goes out from each item to menu tree. (Toggle between menu tree and each menu item)
After changing the set values, be sure to save the changed values in the Set Value Change Save Menu.
UP -
To move up the cursor in the menu tree To increment the set values The set values are rolled up and UP button at the highest value goes to the lowest value.
DOWN -
To move down the cursor in the menu tree To decrement the set values The set values are rolled down and DOWN button at the lowest value goes to the highest value.
47 / 163
www.jinkwang.co.kr
Ia : 00.0/00.0 Ia : 00.0/00.0 Ia :
A A A
<MENU
[ SETTING MENU ] 1. Group1 2. Group2 3. Group3 4. Group4 5. Select Act. Group [ CONFIG MENU ] 1. I/O 2. Communication 3. App. Objects 4. Event 5. Time
<UP/DOWN
[ DISPLAY MENU ] 1. Measurements 2. Status 3. Counter [ EVENT LIST ] 1. I/O events 2. Function events 3. System events 4. Fault I events 5. Demand I events 6. Demand P events 7. Demand Q events 8. Max. I events 9. Max P events 10. Max Q events
<MENU
48 / 163
www.jinkwang.co.kr
MENU button at [Initial Display] goes to [Main Menu Display]. MENU button toggles between [Initial Display] and [Main Menu Display].
UP or DOWN button at [Initial Display] goes to [Current / Voltage Measurement Display]. UP / DOWN button toggles between [Initial Display] and [Current / Voltage Measurement Display].
I I I I
a b c n
: : : :
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
A A A A
0 0 0 <
0 . 0 / 0 0 . 0 0 . 0 / 0 0 . 0 0 . 0 / 0 0 . 0 ABC>
: CLOSE / OPEN / TROUBLE (No Status Input) : Each Phase Instantaneous Current Value (unit : A) : Source Side Voltage (Va,Vb,Vc) /
49 / 163
www.jinkwang.co.kr
(2) Main Menu Display [Main Menu Display] shows up 4 main menu items. And UP & DOWN buttons move up and down the main menu trees. > symbol indicates the cursor position and ENTER button enters into the selected main menus sub items.
[Table 4-1]
Sub Items Group1, Group2, Group3, Group4, Select Act. Group I/O, Communication, App. Objects, Event, Time Measurements, Status, Counter I/O events, Function events, System events, Fault I events, Demand I
Event List
events, Demand P events, Demand Q events, Max. I events, Max. P events, Max. Q events,
(3) Function Setting In Function Setting, there are 4 different setting groups and the different setting values can be stored individually in 4 different setting groups. Select Act. Group determines one of 4 setting groups, whose setting values are now applied. From Group1 to Group4, each group has the same setting items and the following table describes only the detailed setting items of Group 1. For other groups, the same setting items as Group 1 can be referred to.
[Table 4-2]
Function Setting
Setting Items
Setting Ranges <step> 10-900 <1A> 1-58 <1> 0.10-2.00 <0.01> 0.00-1.00 <0.01s> 0.00-1.00 <0.01s>
Group1
Fault Detection
Phase
F : Fast D : Delayed
Time
50 / 163
www.jinkwang.co.kr
F-Reset Type F-Reset time D TCC Type D Multiplier D Time Adder D Min. Resp.
0(RDMT)/1(RIDMT) 0.00-10.00 <0.01s> 1-58 <1> 0.10-2.00 <0.01> 0.00-1.00 <0.01s> 0.00-1.00 <0.01s> 0(RDMT)/1(RIDMT) 0.00-10.00 <0.01s> 50-10000 <1> 0.00-1.00 <0.01s> 0-10 <1> 1(Yes) or 0(No) 5-900 <1A> 1-58 <1> 0.10-2.00 <0.01> 0.00-1.00 <0.01s> 0.00-1.00 <0.01s> 0(RDMT)/1(RIDMT) 0.00-10.00 <0.01s> 1-58 <1> 0.10-2.00 <0.01> 0.00-1.00 <0.01s> 0.00-1.00 <0.01s> 0(RDMT)/1(RIDMT) 0.00-10.00 <0.01s> 50-10000 <1> 0.00-1.00 <0.01s> 0-10 <1> 1(Yes) or 0(No) 2-20 <1A> 10-80 <1%> +/- 0,30,60,90
0(RDMT) 0.00 2 1.00 0.00 0.00 0(RDMT) 0.00 2000 0.00 4 1(Yes) 60 20 1.00 0.00 0.00 0(RDMT) 0.00 21 1.00 0.00 0.00 0(RDMT) 0.00 2000 0.00 2 1(Yes) 5 30 90
Time D-Reset Type D-Reset time HCT Level HCT Resp. Time Cold L Multi Inrush Block Pickup Level Ground F TCC Type F Multiplier F Time Adder F Min. Resp.
Time F-Reset Type F-Reset time D TCC Type D Multiplier D Time Adder D Min. Resp.
Time D-Reset Type D-Reset time HCT Level HCT Resp. Time Cold L Multi Inrush Block I-Pickup SEF V-Pickup Angle
51 / 163
www.jinkwang.co.kr
Detect Time Inrush Block Func. In Use 2nd Harmonic Inrush Detection Detect Time Func. In Use Volt On Open Line Detect Volt Off Delay Time Func. In Use Pickup Level Under frequency Detect Func. In Use Ph. Oper Cnt (Phase Time-delayed) Trip & Reclosing Gnd Oper Cnt (Ground TimeDetect Time
0.1-30.0 <0.1s> 1(Yes) / 0(No) 0(Off)/1(Alarm)/ 2(Trip) 5-50 <1%> 0.02-1.00 <0.01s> 1(On) / 0(Off) 50-90 <5%> 35-75 <5%> 0.1-30.0 <0.1s> 1(On) / 0(Off) 47.00~59.98<0.01> 0.03~10.00<0.01s> Off/Alarm/Trip 1-5 <1> 1-5 <1> 0-5 <1> 0-5 <1> 0-5 <1> 0-5 <1> 0.5-60 <0.1s> 1-60 <1s> 1-60 <1s> 1-60 <1s> 3-180 <1s> 0.00-60.00 <0.01s> 0.00-30.00 <0.01s> 1(On) / 0(Off)
1.0 1(Yes) 0(Off) 20 0.02 1(On) 80 50 0.4 1(On) 49.80Hz 0.1s Off 4 4 2 2 0 0 0.6 2 15 15 30 3.00 0.30 0(Off)
delayed) PF Oper Cnt (Phase Instantaneous) GF Oper Cnt (Ground Instantaneous) Ph. HCT Op Cnt (Phase HCT) Gnd HCT Op Cnt (Ground HCT) Dead Time 1st (Reclose Interval) Dead Time 2nd Dead Time 3rd Dead Time 4th Reset Time (Reclosing Reset Time) Cold L Time (Cold Load Duration) Reset. PC Time (Cold Load Pk Restore Time) Seq. Coordi.
Group2 Group3 Group4 Select Act. Group Active Setting Group Selection 1-4 <1> 1 Same Setting Items and Sub Setting Items as Group 1
52 / 163
www.jinkwang.co.kr
After finishing the set value change, when MENU button is pushed to return to [Main Menu Display], [Set Value Change Save Display] shows up to determine Yes or No. If selecting Yes and pushing ENTER button, the changed set values are all saved. However, if selecting No and ENTER button, or MENU button again, the changed set values are not saved and the existing set values are still applied. * CAUTION: Be careful not to push down MENU buttons repeatedly! Then, the newly changed set values are neither saved nor applied.
Sa v e
Ch a n g e d Ye s
Se t
Se t t i ng
Sa v i ng!
[ MA I >1 . Fun 2 . Co n 3 . Di s
N c t f i pl
ME N U ] i on Se t t i ng gur a t i on a y
(4) Configuration Configuration menu has the setting items for communication, I/O, and system configuration. Setting items are I/O, Communication, App. Objects, Event, and Time. The
53 / 163
www.jinkwang.co.kr
following table describes each setting item and the corresponding setting range.
Configuration
Setting Items
Sub Setting Items Frequency Rated Volt. CT Ratio NCT Ratio Average Interval
Setting Ranges <step> 50 or 60 3.80-21.00 <0.01kV> 100-2000 <10> 100-2000 <10> 5-15 <5min> 10-500 <5ms> 10-2000 <10ms> 0(Manu.) / 1(Auto) 0(No) / 1(Yes) 0(No) / 1(Yes) 1200/2400/4800/9600/19200 0-65534 <1> 0(DNP) / 1(IEC) 2 or 4 wire 10-500 <10ms> 1-255 <1s> 0.1-30.0 <0.1s> 0-2 <1> 1-255 <1s> 0(No)/1(Yes)/2(Sometime) 0-2 <1> 1-255 <1s> 0(No) / 1(Yes) 0-60 <1s> 1-255 <1s> 0-65534 <1> 10-500 <10ms> 0-3 <1> 0-3 <1> 0-3 <1> 0-3 <1> 0-3 <1> 0-3 <1> 0-3 <1>
I/O
AC Rating
DI1 ~ DI10 DO1 ~ DO4 FI Reset Live load Sync. Fail Comm. Speed Slave Addr. Protocol Comm. Line RTS Off Delay CTS Timeout DCD Timeout D/L Retry D/L Timeout D/L Confirm A/L Retry A/L Timeout Initial Unsol. Unsol. Delay SBO Timeout Master Address Frame Interval
Modem Control
Protocol Parameter
BI.0 ~ BI.31 AI.0 ~ AI.31 Fault I Event Max. I Ev. Demand I Ev. Max. P Ev. Demand P Ev.
54 / 163
www.jinkwang.co.kr
Max. Q Ev. Demand Q Ev. CNT Object Class AI Object VOC AI Obj. VOC-Limit CNT Object VOC Set S/W Counter Event Time Clear Events Clear Faults <SETTING TIME> CNT.0 ~ CNT.15 AI.0 ~ AI.31 AI.0 ~ AI.31 CNT.0 ~ CNT.15 S/W Count Clear all events? Clear all faults?
0-3 <1> 0-3 <1> 0-3 <1> 0-50 <1%> 0-65535 <1> 0-65535 <1> 0-65535 <1> Yes / No Yes / No yyyy/mm/dd hh:nn:ss
After finishing the set value change, when MENU button is pushed to return to [Main Menu Display], [Set Value Change Save Display] shows up to determine Yes or No. If selecting Yes and pushing ENTER button, the changed set values are all saved. However, if selecting No and ENTER button, or MENU button again, the changed set values are not saved and the existing set values are still applied. * CAUTION: Be careful not to push down MENU buttons repeatedly! Then, the newly changed set values are neither saved nor applied.
Sa v e
Ch a n g e d y e s
Se t
Se t t i ng
Sa v i ng!
55 / 163
www.jinkwang.co.kr
[ MA I 1 . Fun > 2 . Co n 3 . Di s
N c t f i pl
ME N U ] i on Se t t i ng gur a t i on a y
(5) Display
In Display menu, measurement values, monitored status, and counter values are displayed.
Display
Measurements Currents
sequence) : Magnitude [A] & Phase Angle [Deg] Va, Vb, Vc[kV]
Voltages
Zero-sequence : VoS, (S: Source-side) Positive-sequence : V1S Negative-sequence : V2S : Magnitude [A] & Phase Angle [Deg]
Active Power Reactive Power Apparent Power Power factor Energy Status Switch Handle AC Power Battery Door Spare #1, #2, #3
Pa, Pb, Pc, P3p [MW] Qa, Qb, Qc, Q3p [MVAR] VAa, VAb, VAc, VA3 [MVA] PFa, PFb, PFc, PF3 : Lead / Lag (Lead = 1) PEa, PEb, PEc, PE3 [MWh], QEa, QEb, QEc, QE3 [Mvarh] OPEN / CLOSE / TROUBLE LOCK / UNLOCK NORMAL / OFF (External AC Power Loss) NORMAL / Low CLOSED / OPEN ON / OFF (Spare #1,2 : Trip, Close command)
56 / 163
www.jinkwang.co.kr
Loc / Rem FRTU Addr Master Addr Ver. Counter Restart S/W Count All Faults
LOCAL / REMOTE FTU-R100 Slave Address Control System Master Address FTU-R100 Firmware Version FTU-R100 Restart Count Recloser Body Open Count All Faults Detection Count (Each Phase Fault Count + Reclosing Count)
Faults (A) Faults (B) Faults (C) Faults (N) Each Phase Fault Detection Count
In Event List menu, all types of events are displayed with occurred time and event description. Using UP & DOWN buttons, event list can be scrolled up and down in the LCD display.
Event List I/O events Function events System events Fault I events Demand I events Demand events Demand events Max. I events Max. P events Max. Q events Q P
Description Status Change of Binary Input/Output Operated Status of Protection Functions Setting Change, Reset Latest Fault Current, Faulted Phase, Time Each Phase Daily Average Load Current, Time Each Phase & 3-phase Daily Average Active Power, Time
Each Phase & 3-phase Daily Average Reactive Power, Time Each Phase Daily Peak Load Current, Time Each Phase & 3-phase Daily Peak Active Power, Time Each Phase & 3-phase Daily Peak Reactive Power, Time
511 31 31 31
57 / 163
www.jinkwang.co.kr
FTU-R100 has a dedicated setting and operation tool, FTU_SET. This tool is operated on PC or Notebook computer, and through RS232 port on front panel of FTU-R100, setting & configuration changes, event list & fault waveform view, firmware download, communication protocol & data frame monitor, measurement & status display, and correction factor calibration are possible. For this communication, MODBUS protocol is used. Main menus of this tool are File(F), Option(O), Help(H).
File New File Open File Save Report Upload from FTU Download to FTU Connect Disconnect Protocol Monitor Help
[File Menu] - Connect - Disconnect - File New - File Open - File Save - Report : to start communication with FTU-R100 : to quit communication : to create a new setting file : to load a setting file (*.str) to use previously saved setting values : to save edited values to a setting file for next use : to save a report text file(*.rpt) from converted setting value : to upload data from FTU-R100 (setting, event, fault) : to download edited set values to FTU-R100 : to delete all event data stored in FTU-R100
- Clear All Fault Records: to delete all fault data stored in FTU-R100 - Exit : to quit the program
58 / 163
www.jinkwang.co.kr
[Option Menu] - Comm. - Protocol monitor : to open a window for communication configuration of the tool : to open a window for communication status monitoring
(1) Connection between FTU_SET and FTU-R100 Before starting to connect to FTU-R100, communication options are firstly configured in the menu [Option Comm.]. In this menu window, select a serial port of Notebook. MODBUS protocol has RTU mode
In Setting Window, existing setting values of FTU-R100 can be viewed through Upload button, or setting values are edited and downloaded to FTU-R100 by clicking Download button to apply new setting values to FTU-R100. In some cases, operators require to save and reuse these edited setting values. To satisfy this request, FTU_REC_SET tool has
59 / 163
www.jinkwang.co.kr
New, Open and Save menu items in [File] menu. The file extension name is *.str (setting file) and Report menu item save to report file the edited setting values.
60 / 163
www.jinkwang.co.kr
To facilitate operators TC curve editing, FTU_REC_SET provides Recloser Curve Window. As Setting Window is activated, click TC Curve button to open Recloser Curve Window. Through this Window, operators can refer to the shape of TC curves, which is now formed by some parameters.
FTU-R100 can simultaneously store 4 different setting groups setting values in memory. All the setting items in each group are exactly the same and operators can select one group to apply as an Active Group.
In Config Window, there are I/O Config Window, Communication Config Window, and App. Object Config Window. Current configuration values of FTU-R100 can be viewed through Upload button, or configuration values are edited and downloaded to FTU-R100 by clicking Download button to apply new configuration values to FTU-R100.
61 / 163
www.jinkwang.co.kr
In I/O Config Window, Analog Circuit Ratings and Binary I/O setting values are configured.
62 / 163
www.jinkwang.co.kr
In Communication Config Window (Fig. 4-17 on the next page), communication speed, protocol, slave address, modem control data, and protocol parameters are configured.
63 / 163
www.jinkwang.co.kr
In App Object Config Window, all kinds of Application Object Classes for binary input, analog input, counter input and VOC (Value of Change) in DNP v3.0 communication protocol are configured.
(4) Event Window In Event Window, operators can list up all the event records, which are stored in the memory of FTU-R100 by clicking Upload button. All types of events can be uploaded or each type of event can be separately uploaded from FTU-R100. The kinds of event types are I/O Event (1023), Function Event (1023), System Event (63), Fault Event (127), Demand Event (511), Max Current Event (31), and Max Power Event (31). Each event type and descriptions are explained in the Section 4.2.1. Time Resolution for event recording is 5msec and Scanning Interval is 1msec.
64 / 163
www.jinkwang.co.kr
Demand Window displays Daily Average Demand Current and Power in the list form and waveform. When the Graph check box is unchecked, Demand Current and Power are listed as in the Event Window. Averaging Interval is between 5 and 15 minutes, and maximally 128 data are stored for each measurement. Demand Current Window displays average currents of Ia, Ib, Ic, In, and Demand Power Window displays the averages of active demand power and reactive demand power for each phase and 3 phases.
65 / 163
www.jinkwang.co.kr
Sample Recording Window displays Fault Waveforms stored in FTU-R100. At first, click Read Fault Count to upload the recorded fault data to FTU_REC_SET tool, and select one of 8 recorded faults to view. As in Demand Window, fault data are listed or fault waveforms are drawn. Fault waveform drawings are displayed for each phase current and each phase voltage. And, each graph is distinguished by different color. FTU-R100 can record and store the data for up to 8 faults, and each waveform has the data of 10 cycles (7 cycles before line deactivation and 3 cycles after line deactivation). Sampling Rate is 32 sample/cycle.
66 / 163
www.jinkwang.co.kr
Operators can monitor all kinds of measurement values such as current, voltage, power, and energy, etc. on-line in I & V & Power Measurement Window. And, FTU-R100 has the function of Harmonic Analysis, therefore up to 8th harmonics RMS values and THD (Total Harmonic Distortion) for Ia, Ib, Ic, Va, Vb, Vc are measured and displayed in Harmonics Measurement Window. Lastly, in Counter Measurement Window, counter values (FTU Restart Count, Recloser Trip Count, Fault Count) and accumulation data (MWattHour, MVarHour) are displayed.
67 / 163
www.jinkwang.co.kr
In Status Window, all the status indications and FTU-R100s firmware version and model ID, and modem control status data are displayed.
68 / 163
www.jinkwang.co.kr
With FTU-R100 connected to the control center system (Master), through this Window, operators can check communication protocol and data frames. This Windows can be saved in a log file using Capture button
69 / 163
www.jinkwang.co.kr
The FTU-R100 has 4 custom editing curves. In Custom Curve Window, the current custom curve data of FTU-R100 can be viewed through Upload button, and those can be edited and downloaded to FTU-R100. Then the new custom curve data is applied. To open and save the curve data from or to a file, File Open and File Save button can be used. The file format is CSV that can be open in the MS-Excel.
70 / 163
www.jinkwang.co.kr
71 / 163
www.jinkwang.co.kr
5. PROTECTION FUNCTIONS
5.1 Auto-Reclosing Sequence For permanent fault, under the condition of reclosing enabled, no other restraints such as Cold Load and Inrush, and no HCT, recloser will be locked out to open after the Reclosing Count repeating trip and reclose according to the preset settings.
For example in the below figure, the reclosing sequence is organized in 2F2D, which means the Recloser protection function operates as Instantaneous (Fast) element during first 2 reclosing shots and operates as Time-delayed element during last 2 reclosing shots. This composition also can be configured.
For temporary fault, if the fault is removed before the preset Reclosing Count and no fault is detected during the preset Reset Time, then the reclosing sequence is initialized to normal operation standby mode. When a fault is detected again during the Reset Time, the Recloser will be locked out after the remaining reclosing counts excluding the previously operated reclosing counts. 4 5 7 8
[A]
Fault Current
Lockout
Pickup Current
Normal Load Cur
[Time]
1,3 5,7 2, 4, 6 8
72 / 163
www.jinkwang.co.kr
[A]
Fault Current
3 (Reset Time)
Pickup Current
Normal Load Cur
[Time]
1,3 : Instantaneous Operation 2 : 1st Shot Reclosing Interval [Fig. 5-2] Temporary Fault: Fault Removal During 1st Reclosing Interval
5.2 HCT (High Current Trip) Very high valued current can cause serious damage to the Recloser and the resultant fault spread-out, therefore HCT element should operate faster than Instantaneous or Timedelayed TC curves operation time and its priority must be higher than the normal autoreclosing sequence. HCT can be configured up to 4 times for phase fault and ground fault, respectively. HCT Count setting value 0 means HCT element disabled.
5.3 Cold Load Pickup On the line to which loads are connected, when the line is re-activated after deactivation (in case of first time line activation after line installation or re-activation after lockout-to-open due to a permanent fault), there can be such a phenomenon that the load current higher than fault detection pickup level flows instantly and goes down the pickup level. This is called Cold Load and Cold Load Pickup function is to prevent and distinguish Cold Load from the real fault current.
In Cold Load mode, without changing operational characteristics, pickup level is changed by the times of Cold Load Multiplier (1~10) and the characteristics of time-delayed element
73 / 163
www.jinkwang.co.kr
operate even if the setting is in the Instantaneous element. If the transient current goes down and retains below the pickup level within Cold Load Duration, then the normal sequence mode is restored after Cold Load Restore Time. These settings exist for both phase fault and earth fault separately, and the value 0 of Cold Load Multiplier means this Cold Load Pickup function disabled. (Normal Reclosing Sequence mode is applied.)
5.4 Inrush Restraints Inrush Current is an over-current higher than pickup level, which is mainly caused by transformers excitation current at closing action. To distinguish inrush current from load current, 2nd harmonics percentage is adopted as a criterion.
When, in the setting menu, [Fault Detection Phase/Ground - Inrush Block] is set to Yes and [Fault Detection Inrush Detection Function In Use] is set to On, inrush current over pickup level is considered as normal load current and reclosing sequence is not processed.
5.5 SEF (Sensitive Earth Fault) Detection On the non-grounded network, it is hard to detect fault current because ground current of non-grounded network is much low. Therefore, FTU-R100 is designed to measure zerosequence values from either external Core Balanced Current Transformer (or ZCT) or Residual Connection of 3 Phase Current Transformers to detect earth fault in the nongrounded network. This function is generally called SEF detection.
In case of earth fault in the non-grounded network, since very small fault current due to line capacitance component flows into the fault point from both sides, SEF detection also considers the fault direction even in the radial network. Maximum Torque Angle is for setting the phase difference between zero-sequence voltage and zero-sequence current, and the protection zone is between -90 and +90 on the basis of Maximum Torque Angle.
74 / 163
www.jinkwang.co.kr
3I0
Min Torq Ang
Op Current
Operated Non-Op
5.6 Sequence Coordination In case that there are over 2 Reclosers which operate in serial connections, Sequence Coordination function prevents unnecessary trip of source-side Recloser by instantaneous element due to load-side fault. When this function is set to on and the fault is restored to normal state by load-side Recloser during source-side Reclosers time-delayed operation, source-side Recloser only increments the reclosing counts without tripping. However, source-side Recloser performs tripping at the last reclosing count. If the Reclosing function is disabled, Sequence Coordination function is no longer carried out.
For Sequence Coordination, the following setting items should be issued and checked precisely between serially connected Reclosers.
Identical Protection Characteristics such as TC Curves, Total Operation Count, Instantaneous Operation Count
Identical Reclosing Interval (Dead Time) Source-side TC Curve Time Delay Over 100msec Than Load-side Source-side Reset Time Longer Than Load-side Longest Reclosing Interval (To Prevent Source-side Recloser Reset During Load-side Reclosing Action)
75 / 163
www.jinkwang.co.kr
6. TC CURVE SETTING
FTU-R100 has 54 types of built-in TC curves including ANSI, IEC standard curves. And customer can define additional 4 curves as his own curves by using PC software. Basically, built-in curves have inverse time characteristics, but can be easily adjusted by three parameters such as multiplier, time adder and minimum response time. In engineering step, the selection and adjustments of TC curve shall be done for the protection coordination with other protection devices in the feeder. The following parameters are related to change and editing of TC curves characteristics. Time Dial Multiplier Time Adder Minimum Response Time
Time Multiplier is multiplied to the operating time of basic curve (TDM=1.0), Then Time Adder is added to the resulting operating time of the curve adjusted by multiplier. Minimum response time defines the fastest operating time of the curve. The following section 6.1 shows an example of TC curve adjustments. The following tables describe the built-in TC curve types and the corresponding numbers in the setting. TC curve graphs are shown in the appendix. [Table 6-1] Built-in TC Curves and Corresponding Setting Code
Setting No. Curve Setting No. Curve Setting No. Curve Setting No. Curve Setting No. Curve Setting No. Curve
1 A 11 NI 21 2 31 13 41 G 51 IV
2 B 12 P 22 3 32 14 42 H 52 IE
3 C 13 R 23 4 33 15 43 J 53 U8
4 D 14 T 24 5 34 16 44 LI 54 U2
5 E 15 V 25 6 35 18 45 8+ 55 C1
6 EI 16 VI 26 7 36 N1 46 17 56 C2
7 K(P) 17 W 27 8 37 N2 47 K(G) 57 C3
8 L 18 Y 28 8* 38 N3 48 A* 58 C4
9 M 19 Z 29 9 39 N4 49 SI
10 N 20 1 30 11 40 F 50 IM
76 / 163
www.jinkwang.co.kr
Curve Name A, A*, B, C, D, E, F, G, H, J, K-P, K-G, L, M, N, P, R, T, V, W, Y, Z, 1, 2, 3, 4, 5, 6, 7, 8, 8*, 8+, 9, 11, 13, 14, 15, 16, 17, 18, Standard inverse (NI), Very inverse (VI), Extremely inverse (EI), Long-time inverse (LI), Short-time inverse (SI) Moderately inverse (IM), Very inverse (IV), Extremely inverse (IE), Long-time inverse (U8), Short-time inverse (U2) N1, N2, N3, N4 C1, C2, C3, C4
ANSI/IEEE Curve
Standard
T = Operate Time TDM = Multiplier Setting TRESET = Reset Time 0.14 13.5 IEC 80.0 0.05 120 19.61 IEEE 28.2 0.0515 CO2 CO8 0.2394 5.95 0.02 1 2 0.04 1 2 2 0.02 0.02 2 0.491 0.1215 0.114 0.01694 0.18 21.6 29.1 4.85 2.261 5.95
Curve Type Standard Inverse (NI) Very Inverse (VI) Extremely Inverse (EI) Short -Time Inverse (SI) Long -Time Inverse (LI) Very Inverse (IV) Extremely Inverse (IE) Moderately Inverse (IM) Short -Time Inverse (U2) Long -Time Inverse(U8)
Standard
77 / 163
www.jinkwang.co.kr
3 parameters are applied in the following order. The values in the parenthesis are examples. (1) Time Multiplier (1.5) (2) Time Adder (0.03) (3) Minimum Response Time (0.1)
In the next figure, for example, the curve A is the basic curve. Assume the operating time of the basic curve (A) at 16 times pickup current is 0.04 sec. When applying Multiplier, Curve A changes its shape, that is, the curve becomes less steep in time axis and operation time becomes longer by a multiplier at the same current value like B in the figure. The operating time at 16 times pickup becomes 0.06sec. Then Time Adder shall be applied. The operating time over all current range becomes longer by that value. In this example the operating time of the resulting curve C is 0.09sec. Finally Minimum Response Time cuts the curve part, which is shorter than this time. Then the actual operating time of the example at 16 times becomes 0.1 sec.
There are two additional definite-time over-current elements in the controller. The next figure shows 3-stage over-current protection characteristics. The third stage is prepared for instantaneous protection. Therefore the harmonic restraint is not applied to third stage
78 / 163
www.jinkwang.co.kr
79 / 163
www.jinkwang.co.kr
Appendix 1.
[Fig. A-1-1]
A, B, C, D curves
80 / 163
www.jinkwang.co.kr
[Fig. A-1-2]
81 / 163
www.jinkwang.co.kr
[Fig. A-1-3]
E, L, M, N curves
82 / 163
www.jinkwang.co.kr
[Fig. A-1-4]
K(P), P, R, T curves
83 / 163
www.jinkwang.co.kr
[Fig. A-1-5]
V, W, Y, Z curves
84 / 163
www.jinkwang.co.kr
[Fig. A-1-6]
1, 2, 3, 4 curves
85 / 163
www.jinkwang.co.kr
[Fig. A-1-7]
5, 6, 7, 8 curves
86 / 163
www.jinkwang.co.kr
[Fig. A-1-8]
87 / 163
www.jinkwang.co.kr
[Fig. A-1-9]
88 / 163
www.jinkwang.co.kr
[Fig. A-1-10]
89 / 163
www.jinkwang.co.kr
[Fig. A-1-11]
F, G, H, J curves
90 / 163
www.jinkwang.co.kr
[Fig. A-1-12]
91 / 163
www.jinkwang.co.kr
[Fig. A-1-13]
92 / 163
www.jinkwang.co.kr
Appendix 2.
REVISIONS
1.2 1.3
02-Sep-02 03-Mar-13
NS Yoon NS Yoon
Binary Inputs 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Ext. AC Power Loss Battery Discharged Door Open DI Spare #1 DI Spare #2 DI Spare #3 Fault Indicator (A) Fault Indicator (B) Fault Indicator (C) Fault Indicator (N) Fault Indicator (SEF) 1 1 1 1 1 1 3 3 3 3 3 01/01,01/02,02/02 01/01,01/02,02/02 01/01,01/02,02/02 01/01,01/02,02/02 01/01,01/02,02/02 01/01,01/02,02/02 01/01,01/02,02/02 01/01,01/02,02/02 01/01,01/02,02/02 01/01,01/02,02/02 01/01,01/02,02/02 Contact closed = 1 Contact closed = 1 Contact closed = 1 Switch Status Control Mode Handle Locked 1 1 1 01/01,01/02,02/02 01/01,01/02,02/02 01/01,01/02,02/02 Closed = 1 Local = 1
93 / 163
www.jinkwang.co.kr
ISO 9001 certified 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 System Error Inrush Detected Reclosing Blocked Protection Blocked Ground Protection Blocked High Current Trip Sequence Lockout Reserved Under frequency detect 3 3 1 1 1 3 3 0 0 Reverse Direction Fault Open Line Detection A Open Line Detection B Open Line Detection C 3 3 3 3
Binary Outputs CLOSE=Close, 0 1 2 3 4 5 Switch Open/Close Control Battery Test DO spare Output Annunciator Manual Reset Reserved Enable/Disable Reclosing Pulse Pulse Pulse Pulse Pulse Pulse 12/01 TRIP=Open 12/01 12/01 12/01 12/01 12/01 Dis. CLOSE=En.,TRIP= 6 Enable/Disable Protection Pulse 12/01 Dis. CLOSE=En.,TRIP= 7 8 Enable/Disable Ground Protection Reserved Pulse Pulse 12/01 Dis. 12/01 CLOSE CLOSE CLOSE CLOSE CLOSE CLOSE=En.,TRIP=
94 / 163
www.jinkwang.co.kr
ISO 9001 certified 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 Reserved (Frequency) Reserved (Temperature) Reserved Ia phase angle Ib phase angle Ic phase angle In phase angle Source side Va phase angle Source side Vb phase angle 0 0 0 0 0 0 0 0 0 KVAa KVAb KVAc kVA3ph KWa KWb KWc kW3ph KVARa KVARb KVARc kVAR3ph PFa PFb PFc PF3ph 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 In RMS Source side Va RMS Source side Vb RMS Source side Vc RMS Source side Vo RMS 0 0 0 0 0
Epoxy molded Automatic Vacuum Recloser 30/02,30/04,32/02 30/02,30/04,32/02 30/02,30/04,32/02 30/02,30/04,32/02 30/02,30/04,32/02 A kV100 kV100 kV100 kV100
30/02,30/04,32/02 30/02,30/04,32/02 30/02,30/04,32/02 30/02,30/04,32/02 30/02,30/04,32/02 30/02,30/04,32/02 30/02,30/04,32/02 30/02,30/04,32/02 30/02,30/04,32/02 30/02,30/04,32/02 30/02,30/04,32/02 30/02,30/04,32/02 30/02,30/04,32/02 30/02,30/04,32/02 30/02,30/04,32/02 30/02,30/04,32/02
kVA kVA kVA kVA kW kW kW kW kVAR kVAR kVAR kVAR X100 X100 X100 X100
HZ100
o o o o o o
10 10 10 10 10 10
95 / 163
www.jinkwang.co.kr
ISO 9001 certified 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 PFa lead PFb lead PFc lead PF3ph lead Last Fault Ia Last Fault Ib Last Fault Ic Last Fault In Last Fault vo Reserved (Last Fault location) Reserved (Last Fault I2t) Reserved Demand I Ia Demand I Ib Demand I Ic Demand I In Demand P kWa 0 0 0 0 3 3 3 3 0 0 0 0 2 2 2 2 2 I1 RMS I1 phase angle I2 RMS I2 phase angle Source side V1 RMS Source side V1 phase angle Source side V2 RMS Source side V2 phase angle 0 0 0 0 0 0 0 0 Source side Vc phase angle Source side Vo phase angle 0 0
10 10
A
o
10
A
o
10
kV100
o
10
kV100
o
10
30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04,32/04 30/02,30/04,32/04 30/02,30/04,32/04 30/02,30/04,32/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04,32/04 30/02,30/04,32/04 30/02,30/04,32/04 30/02,30/04,32/04 30/02,30/04,32/04
A A A A kW
96 / 163
www.jinkwang.co.kr
ISO 9001 certified 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 Ia true RMS Ib true RMS Ic true RMS Va true RMS Demand P kWb Demand P kWc Demand P kW3ph Demand P kVARa Demand P kVARb Demand P kVARc Demand P kVAR3ph Max. I Ia Max. I Ib Max. I Ic Max. I In Max. P1 kWa Max. P1 kWb Max. P1 kWc Max. P1 kW3ph Max. P1 kVARa Max. P1 kVARb Max. P1 kVARc Max. P1 kVAR3ph 3-phase currents THD Ia THD Ib THD Ic THD Source side 3-phase voltages THD Source side Va THD Source side Vb THD Source side Vc THD 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 -
Epoxy molded Automatic Vacuum Recloser 30/02,30/04,32/04 30/02,30/04,32/04 30/02,30/04,32/04 30/02,30/04,32/04 30/02,30/04,32/04 30/02,30/04,32/04 30/02,30/04,32/04 30/02,30/04,32/04 30/02,30/04,32/04 30/02,30/04,32/04 30/02,30/04,32/04 30/02,30/04,32/04 30/02,30/04,32/04 30/02,30/04,32/04 30/02,30/04,32/04 30/02,30/04,32/04 30/02,30/04,32/04 30/02,30/04,32/04 30/02,30/04,32/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 kW kW kW kVAR kVAR kVAR kVAR A A A A kW kW kW kW kVAR kVAR kVAR kVAR % % % % % % % %
A A A kV100
97 / 163
www.jinkwang.co.kr
ISO 9001 certified 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 Ia 2nd harmonic RMS Ib 2nd harmonic RMS Ic 2
nd
30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04
harmonic RMS
Ia 3rd harmonic RMS Ib 3 harmonic RMS Ic 3 harmonic RMS Ia 4th harmonic RMS Ib 4 harmonic RMS Ic 4th harmonic RMS Ia 5th harmonic RMS Ib 5 harmonic RMS Ic 5th harmonic RMS Ia 6 harmonic RMS Ib 6 harmonic RMS Ic 6th harmonic RMS Ia 7 harmonic RMS Ib 7th harmonic RMS Ic 7th harmonic RMS Ia 8 harmonic RMS Ib 8th harmonic RMS Ic 8 harmonic RMS Source side Va 2
nd th th th th th th th rd rd
harmonic RMS
harmonic RMS
Source side Va 3rd harmonic RMS Source side Vb 3rd harmonic RMS Source side Vc 3 harmonic RMS Source side Va 4th harmonic RMS Source side Vb 4 harmonic RMS Source side Vc 4 harmonic RMS
th th rd
98 / 163
www.jinkwang.co.kr
ISO 9001 certified 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 In True RMS In THD Source side Va 5th harmonic RMS Source side Vb 5 harmonic RMS Source side Vc 5 harmonic RMS Source side Va 6th harmonic RMS Source side Vb 6 harmonic RMS Source side Vc 6th harmonic RMS Source side Va 7th harmonic RMS Source side Vb 7 harmonic RMS Source side Vc 7th harmonic RMS Source side Va 8 harmonic RMS Source side Vb 8 harmonic RMS Source side Vc 8th harmonic RMS
th th th th th th
Epoxy molded Automatic Vacuum Recloser 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 KV100 KV100 KV100 KV100 KV100 KV100 KV100 KV100 KV100 KV100 KV100 KV100
30/02,30/04 30/02,30/04
KV100 KV100
99 / 163
www.jinkwang.co.kr
ISO 9001 certified 178 179 180 181 182 183 184 In 2nd harmonic RMS In 3 harmonic RMS In 4 harmonic RMS In 5th harmonic RMS In 6 harmonic RMS In 7th harmonic RMS In 8th harmonic RMS
th th rd
Epoxy molded Automatic Vacuum Recloser 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 KV100 KV100 KV100 KV100 KV100 KV100 KV100
Counters 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 Restart Count Switch Trip (or Open) Count All Faults Count A-phase Fault Count B-phase Fault Count C-phase Fault Count N-phase Fault Count kWattHour-a Export kWattHour-b Export kWattHour-c Export kWattHour-3ph Export kVarHour-a Export kVarHour-b Export kVarHour-c Export kVarHour-3ph Export kWattHour-a Import kWattHour-b Import kWattHour-c Import kWattHour-3ph Import kVarHour-a Import kVarHour-b Import kVarHour-c Import kVarHour-3ph Import 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 20/02,20/06 20/02,20/06 20/02,20/06 20/02,20/06 20/02,20/06 20/02,20/06 20/02,20/06 20/02,20/06,22/08 20/02,20/06,22/08 20/02,20/06,22/08 20/02,20/06,22/08 20/02,20/06,22/08 20/02,20/06,22/08 20/02,20/06,22/08 20/02,20/06,22/08 20/02,20/06,22/08 20/02,20/06,22/08 20/02,20/06,22/08 20/02,20/06,22/08 20/02,20/06,22/08 20/02,20/06,22/08 20/02,20/06,22/08 20/02,20/06,22/08 -------kWh kWh kWh kWh kVarh kVarh kVarh kVarh kWh kWh kWh kWh kVarh kVarh kVarh kVarh
Analog outputs Setting Group1 0 1 Phase Pickup Current Phase Fast TCC type 40/02,41/02 40/02,41/02 10~900A 1~58
100 / 163
www.jinkwang.co.kr
ISO 9001 certified 2 3 4 5 6 7 8 Time 9 10 Time Phase 11 Multiplier 12 13 14 15 16 17 Time 18 19 20 21 Time 22 23 Time Ground 24 Multiplier 25 26 27 28 29 30 Ground Inrush Restraint SEF -Pickup Current(Io) SEF -Pickup Voltage(Vo) SEF -Max. Torque Angle SEF -Detection Time SEF -Inrush restraint Cold Load Pickup Ground High Current Pickup Ground High Current Response Ground Delay TCC type Ground Delay Time Adder Ground Delay Time Multiplier Ground Delay Min Response Phase Inrush Restraint Ground Pickup Current Ground Fast TCC type Ground Fast Time Adder Ground Fast Time Multiplier Ground Fast Min Response Cold Load Pickup Phase High Current Pickup Phase High Current Response Phase Fast Time Adder Phase Fast Time Multiplier Phase Fast Min Response Time Phase Delay TCC type Phase Delay Time Adder Phase Delay Time Multiplier Phase Delay Min Response
Epoxy molded Automatic Vacuum Recloser 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 0.00~1.00sec,step:0.01 0.10~2.00,step:0.01 0.00~1.00sec,step:0.01 1~58 0.00~1.00sec,step:0.01 0.10~2.00,step:0.01 0.00~1.00sec,step:0.01 50~10000A 0.00~1.00sec,step:0.01
40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02
0~10 0(OFF), 1(ON) 5~900A 1~58 0.00~1.00sec,step:0.01 0.10~2.00,step:0.01 0.00~1.00sec,step:0.01 1~58 0.00~1.00sec,step:0.01 0.10~2.00,step:0.01 0.00~1.00sec,step:0.01 50~10000A 0.00~1.00,step:0.01
0~10 0(OFF), 1(ON) 2 - 20A 10~80% 0,30,60,90,270,300,330 0.1~30.0 step:0.1 Sec No(0),Yes(1)
101 / 163
www.jinkwang.co.kr
ISO 9001 certified 31 32 level 33 34 35 36 37 38 39 40 41 42 43 44 45 Inrush restraint-Detection Time Inrush restraint -On/Off Oper. To Lockout Phase Oper. To Lockout Ground Oper. Fast Curve Phase Oper. Fast Curve Ground High Current Phase Active High Current Ground Active Reclose Interval 1st Reclose Interval 2
nd
Epoxy molded Automatic Vacuum Recloser harmonic 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 step:0.01 0.00~60.00sec 5~50% 0.02~1.00,step:0.01 0(Off),1(On) 1~5 1~5 0~5 0~5 0~5 0~5 0.5~60sec, step:0.1 1~60sec 1~60sec 3~180sec 0.00~30.00sec 40/02,41/02 0(Off),1(Alarm),2(Trip)
Reclose Interval 3rd Reset Time Cold Load Pickup Restore Time
46 47 48 49 50 51 52 53 54
Cold Load Duration Seq. Coordination Active Phase Loss -Volt On level Phase Loss -Volt Off level Phase Loss -Delay Time Phase Loss -On/Off -
40/02,41/02 step:0.01 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 ON(1),OFF(0) 50~90,step:5% 35~75,step:5% 1~30Sec 0(Off),1(On)
Setting Group2 55 56 57 58 59 60 61 Phase Pickup Current Phase Fast TCC type Phase Fast Time Adder Phase Fast Time Multiplier Phase Fast Min Response Time Phase Delay TCC type Phase Delay Time Adder 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 10~900A 1~58 0.00~1.00sec,step:0.01 0.10~2.00,step:0.01 0.00~1.00sec,step:0.01 1~58 0.00~1.00sec,step:0.01
102 / 163
www.jinkwang.co.kr
ISO 9001 certified 62 63 Time 64 65 Time Phase 66 Multiplier 67 68 69 70 71 72 Time 73 74 75 76 Time 77 78 Time Ground 79 Multiplier 80 81 82 83 84 85 86 87 level 88 89 Inrush restraint-Detection Time Inrush restraint -On/Off Ground Inrush Restraint SEF -Pickup Current(Io) SEF -Pickup Voltage(Vo) SEF -Max. Torque Angle SEF -Detection Time SEF -Inrush restraint SEF Output select Inrush restraint-2nd harmonic Cold Load Pickup Ground High Current Pickup Ground High Current Response Ground Delay TCC type Ground Delay Time Adder Ground Delay Time Multiplier Ground Delay Min Response Phase Inrush Restraint Ground Pickup Current Ground Fast TCC type Ground Fast Time Adder Ground Fast Time Multiplier Ground Fast Min Response Cold Load Pickup Phase High Current Pickup Phase High Current Response Phase Delay Time Multiplier Phase Delay Min Response
Epoxy molded Automatic Vacuum Recloser 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 0.10~2.00,step:0.01 0.00~1.00sec,step:0.01 50~10000A 0.00~1.00sec,step:0.01
40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02
0~10 0(OFF), 1(ON) 5~900A 1~58 0.00~1.00sec,step:0.01 0.10~2.00,step:0.01 0.00~1.00sec,step:0.01 1~58 0.00~1.00sec,step:0.01 0.10~2.00,step:0.01 0.00~1.00sec,step:0.01 50~10000A 0.00~1.00,step:0.01
40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02
0~10 0(OFF), 1(ON) 2 - 20A 10~80% 0,30,60,90,270,300,330 0.1~30.0 step:0.1 Sec No(0),Yes(1) 0(Off),1(Alarm),2(Trip) 5~50% 0.02~1.00,step:0.01 0(Off),1(On)
103 / 163
www.jinkwang.co.kr
ISO 9001 certified 90 91 92 93 94 95 96 97 98 99 100 Oper. To Lockout Phase Oper. To Lockout Ground Oper. Fast Curve Phase Oper. Fast Curve Ground High Current Phase Active High Current Ground Active Reclose Interval 1st Reclose Interval 2
nd
Epoxy molded Automatic Vacuum Recloser 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 step:0.01 0.00~60.00sec 1~5 1~5 0~5 0~5 0~5 0~5 0.5~60sec, step:0.1 1~60sec 1~60sec 3~180sec 0.00~30.00sec
Reclose Interval 3rd Reset Time Cold Load Pickup Restore Time
Cold Load Duration Seq. Coordination Active Phase Loss -Volt On level Phase Loss -Volt Off level Phase Loss -Delay Time Phase Loss -On/Off -
40/02,41/02 step:0.01 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 ON(1),OFF(0) 50~90,step:5% 35~75,step:5% 1~30Sec 0(Off),1(On)
Setting Group3 110 111 112 113 114 115 116 117 118 Time 119 120 Phase High Current Pickup Phase High Current Response 40/02,41/02 40/02,41/02 50~10000A 0.00~1.00sec,step:0.01 Phase Pickup Current Phase Fast TCC type Phase Fast Time Adder Phase Fast Time Multiplier Phase Fast Min Response Time Phase Delay TCC type Phase Delay Time Adder Phase Delay Time Multiplier Phase Delay Min Response 40/02,41/02 0.00~1.00sec,step:0.01 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 10~900A 1~58 0.00~1.00sec,step:0.01 0.10~2.00,step:0.01 0.00~1.00sec,step:0.01 1~58 0.00~1.00sec,step:0.01 0.10~2.00,step:0.01
104 / 163
www.jinkwang.co.kr
ISO 9001 certified Time Phase 121 Multiplier 122 123 124 125 126 127 Time 128 129 130 131 Time 132 133 Time Ground 134 Multiplier 135 136 137 138 139 140 141 142 level 143 144 145 146 147 148 Inrush restraint-Detection Time Inrush restraint -On/Off Oper. To Lockout Phase Oper. To Lockout Ground Oper. Fast Curve Phase Oper. Fast Curve Ground Ground Inrush Restraint SEF -Pickup Current(Io) SEF -Pickup Voltage(Vo) SEF -Max. Torque Angle SEF -Detection Time SEF -Inrush restraint SEF Output select Inrush restraint-2
nd
Cold
Load
Pickup 40/02,41/02 0~10 0(OFF), 1(ON) 5~900A 1~58 0.00~1.00sec,step:0.01 0.10~2.00,step:0.01 0.00~1.00sec,step:0.01 1~58 0.00~1.00sec,step:0.01 0.10~2.00,step:0.01 0.00~1.00sec,step:0.01 50~10000A 0.00~1.00,step:0.01
Phase Inrush Restraint Ground Pickup Current Ground Fast TCC type Ground Fast Time Adder Ground Fast Time Multiplier Ground Fast Min Response
Ground Delay TCC type Ground Delay Time Adder Ground Delay Time Multiplier Ground Delay Min Response
40/02,41/02 40/02,41/02
Cold
Load
Pickup 40/02,41/02 40/02,41/02 harmonic 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 5~50% 0.02~1.00,step:0.01 0(Off),1(On) 1~5 1~5 0~5 0~5 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 0~10 0(OFF), 1(ON) 2 - 20A 10~80% 0,30,60,90,270,300,330 0.1~30.0 step:0.1 Sec No(0),Yes(1) 0(Off),1(Alarm),2(Trip)
105 / 163
www.jinkwang.co.kr
ISO 9001 certified 149 150 151 152 153 154 155 High Current Phase Active High Current Ground Active Reclose Interval 1
st
Epoxy molded Automatic Vacuum Recloser 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 step:0.01 0.00~60.00sec 0~5 0~5 0.5~60sec, step:0.1 1~60sec 1~60sec 3~180sec 0.00~30.00sec
Reclose Interval 2nd Reclose Interval 3 Reset Time Cold Load Pickup Restore Time
rd
Cold Load Duration Seq. Coordination Active Phase Loss -Volt On level Phase Loss -Volt Off level Phase Loss -Delay Time Phase Loss -On/Off -
40/02,41/02 step:0.01 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 ON(1),OFF(0) 50~90,step:5% 35~75,step:5% 1~30Sec 0(Off),1(On)
Setting Group4 165 166 167 168 169 170 171 172 173 Time 174 175 Time Phase 176 Multiplier 177 Phase Inrush Restraint 40/02,41/02 0(OFF), 1(ON) Cold Load Pickup 40/02,41/02 0~10 Phase High Current Pickup Phase High Current Response 40/02,41/02 0.00~1.00sec,step:0.01 40/02,41/02 50~10000A Phase Pickup Current Phase Fast TCC type Phase Fast Time Adder Phase Fast Time Multiplier Phase Fast Min Response Time Phase Delay TCC type Phase Delay Time Adder Phase Delay Time Multiplier Phase Delay Min Response 40/02,41/02 0.00~1.00sec,step:0.01 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 10~900A 1~58 0.00~1.00sec,step:0.01 0.10~2.00,step:0.01 0.00~1.00sec,step:0.01 1~58 0.00~1.00sec,step:0.01 0.10~2.00,step:0.01
106 / 163
www.jinkwang.co.kr
ISO 9001 certified 178 179 180 181 182 Time 183 184 185 186 Time 187 188 Time Ground 189 Multiplier 190 191 192 193 194 195 196 197 level 198 199 200 201 202 203 204 205 206 207 Inrush restraint-Detection Time Inrush restraint -On/Off Oper. To Lockout Phase Oper. To Lockout Ground Oper. Fast Curve Phase Oper. Fast Curve Ground High Current Phase Active High Current Ground Active Reclose Interval 1st Reclose Interval 2
nd
Epoxy molded Automatic Vacuum Recloser 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 5~900A 1~58 0.00~1.00sec,step:0.01 0.10~2.00,step:0.01 0.00~1.00sec,step:0.01 1~58 0.00~1.00sec,step:0.01 0.10~2.00,step:0.01 0.00~1.00sec,step:0.01 50~10000A 0.00~1.00,step:0.01
Ground Pickup Current Ground Fast TCC type Ground Fast Time Adder Ground Fast Time Multiplier Ground Fast Min Response
Ground Delay TCC type Ground Delay Time Adder Ground Delay Time Multiplier Ground Delay Min Response
40/02,41/02 40/02,41/02
Cold
Load
Pickup 40/02,41/02 0~10 0(OFF), 1(ON) 2 - 20A 10~80% 0,30,60,90,270,300,330 0.1~30.0 step:0.1 Sec No(0),Yes(1) 0(Off),1(Alarm),2(Trip) 5~50% 0.02~1.00,step:0.01 0(Off),1(On) 1~5 1~5 0~5 0~5 0~5 0~5 0.5~60sec, step:0.1 1~60sec
Ground Inrush Restraint SEF -Pickup Current(Io) SEF -Pickup Voltage(Vo) SEF -Max. Torque Angle SEF -Detection Time SEF -Inrush restraint SEF Output select Inrush restraint-2nd harmonic -
40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02
107 / 163
www.jinkwang.co.kr
ISO 9001 certified 208 209 210 Reclose Interval 3rd Reset Time Cold Load Pickup Restore Time
Epoxy molded Automatic Vacuum Recloser 40/02,41/02 40/02,41/02 40/02,41/02 step:0.01 0.00~60.00sec 1~60sec 3~180sec 0.00~30.00sec
Cold Load Duration Seq. Coordination Active Phase Loss -Volt On level Phase Loss -Volt Off level Phase Loss -Delay Time Phase Loss -On/Off -
40/02,41/02 step:0.01 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 ON(1),OFF(0) 50~90,step:5% 35~75,step:5% 1~30Sec 0(Off),1(On)
Common Setting 220 221 222 223 Active setting group Reversed Reserved Reserved 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 1~4
VOC Setting 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 AI.0 VOC AI.1 VOC AI.2 VOC AI.3 VOC AI.4 VOC AI.5 VOC AI.6 VOC AI.7 VOC AI.8 VOC AI.9 VOC AI.10 VOC AI.11 VOC AI.12 VOC AI.13 VOC AI.14 VOC 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 0~50% 0~50% 0~50% 0~50% 0~50% 0~50% 0~50% 0~50% 0~50% 0~50% 0~50% 0~50% 0~50% 0~50% 0~50%
108 / 163
www.jinkwang.co.kr
ISO 9001 certified 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255 256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 272 273 AI.15 VOC AI.16 VOC AI.17 VOC AI.18 VOC AI.19 VOC AI.20 VOC AI.21 VOC AI.22 VOC AI.23 VOC AI.24 VOC AI.25 VOC AI.26 VOC AI.27 VOC AI.28 VOC AI.29 VOC AI.30 VOC AI.31 VOC AI.0 VOC Limit AI.1 VOC Limit AI.2 VOC Limit AI.3 VOC Limit AI.4 VOC Limit AI.5 VOC Limit AI.6 VOC Limit AI.7 VOC Limit AI.8 VOC Limit AI.9 VOC Limit AI.10 VOC Limit AI.11 VOC Limit AI.12 VOC Limit AI.13 VOC Limit AI.14 VOC Limit AI.15 VOC Limit AI.16 VOC Limit AI.17 VOC Limit -
Epoxy molded Automatic Vacuum Recloser 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 0~50% 0~50% 0~50% 0~50% 0~50% 0~50% 0~50% 0~50% 0~50% 0~50% 0~50% 0~50% 0~50% 0~50% 0~50% 0~50% 0~50% 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535
109 / 163
www.jinkwang.co.kr
ISO 9001 certified 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 289 290 291 292 293 294 295 296 297 298 299 300 301 302 303 304 305 306 307 308 AI.18 VOC Limit AI.19 VOC Limit AI.20 VOC Limit AI.21 VOC Limit AI.22 VOC Limit AI.23 VOC Limit AI.24 VOC Limit AI.25 VOC Limit AI.26 VOC Limit AI.27 VOC Limit AI.28 VOC Limit AI.29 VOC Limit AI.30 VOC Limit AI.31 VOC Limit CNT.0 VOC CNT.1 VOC CNT.2 VOC CNT.3 VOC CNT.4 VOC CNT.5 VOC CNT.6 VOC CNT.7 VOC CNT.8 VOC CNT.9 VOC CNT.10 VOC CNT.11 VOC CNT.12 VOC CNT.13 VOC CNT.14 VOC CNT.15 VOC CNT.16 VOC CNT.17 VOC CNT.18 VOC CNT.19 VOC CNT.20 VOC -
Epoxy molded Automatic Vacuum Recloser 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535 0~65535
110 / 163
www.jinkwang.co.kr
Additional Function Setting Group 1 311 312 313 314 315 316 317 Response Time 318 319 320 321 322 323 324 Response Time 325 326 327 328 ON/OFF Additional Function Setting Group 2 329 330 331 332 Phase Fast Reset type Phase Fast Reset Time Phase Delayed Reset type Phase Delayed Reset Time 40/02,41/02 40/02,41/02 step :0.01s 40/02,41/02 40/02,41/02 step :0.01s 0(RDMT), 1(RIDMT) 0.00-100.00s:, 0(RDMT), 1(RIDMT) 0.00-100.00s:, Reclose Interval 4th Under-frequency pickup Under-frequency detection time Under-frequency detection 40/02,41/02 0(Off),1(Alarm),2(On) 40/02,41/02 40/02,41/02 step :0.01Hz 40/02,41/02 0.03-10.00s, step: 0.01s 1~60sec 47.00-59.98, Ground Fast Reset type Ground Fast Reset Time Ground Delayed Reset type Ground Delayed Reset Time Ground Definite Time OC On/Off Ground Definite Time OC Pickup Ground Definite Time OC 40/02,41/02 0.00-1.00s, step : 0.01s 40/02,41/02 40/02,41/02 step :0.01s 40/02,41/02 40/02,41/02 step :0.01s 40/02,41/02 40/02,41/02 0(OFF), 1(ON) 50 - 10000A , step : 1A 0(RDMT), 1(RIDMT) 0.00-100.00s:, 0(RDMT), 1(RIDMT) 0.00-100.00s:, Phase Fast Reset type Phase Fast Reset Time Phase Delayed Reset type Phase Delayed Reset Time Phase Definite Time OC On/Off Phase Definite Time OC Pickup Phase Definite Time OC 40/02,41/02 0.00-1.00s, step : 0.01s 40/02,41/02 40/02,41/02 step :0.01s 40/02,41/02 40/02,41/02 step :0.01s 40/02,41/02 40/02,41/02 0(OFF), 1(ON) 50 - 10000A , step : 1A 0(RDMT), 1(RIDMT) 0.00-100.00s:, 0(RDMT), 1(RIDMT) 0.00-100.00s:,
111 / 163
www.jinkwang.co.kr
ISO 9001 certified 333 334 335 Response Time 336 337 338 339 340 341 342 Response Time 343 344 345 346 ON/OFF Additional Function Setting Group 3 347 348 349 350 351 352 353 Response Time 354 355 356 357 Ground Fast Reset type Ground Fast Reset Time Ground Delayed Reset type Ground Delayed Reset Time Phase Fast Reset type Phase Fast Reset Time Phase Delayed Reset type Phase Delayed Reset Time Phase Definite Time OC On/Off Phase Definite Time OC Pickup Phase Definite Time OC Reclose Interval 4th Under-frequency pickup Under-frequency detection time Under-frequency detection Ground Fast Reset type Ground Fast Reset Time Ground Delayed Reset type Ground Delayed Reset Time Ground Definite Time OC On/Off Ground Definite Time OC Pickup Ground Definite Time OC Phase Definite Time OC On/Off Phase Definite Time OC Pickup Phase Definite Time OC
Epoxy molded Automatic Vacuum Recloser 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 step :0.01s 40/02,41/02 40/02,41/02 step :0.01s 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 40/02,41/02 step :0.01Hz 40/02,41/02 40/02,41/02 0.03-10.00s, step: 0.01s 0(Off),1(Alarm),2(On) 0(OFF), 1(ON) 50 - 10000A , step : 1A 0.00-1.00s, step : 0.01s 1~60sec 47.00-59.98, 0(RDMT), 1(RIDMT) 0.00-100.00s:, 0(OFF), 1(ON) 50 - 10000A , step : 1A 0.00-1.00s, step : 0.01s 0(RDMT), 1(RIDMT) 0.00-100.00s:,
40/02,41/02 40/02,41/02
40/02,41/02 40/02,41/02
0(OFF), 1(ON) 50 - 10000A , step : 1A 0.00-1.00s, step : 0.01s 0(RDMT), 1(RIDMT) 0.00-100.00s:, step :0.01s
40/02,41/02 40/02,41/02
112 / 163
www.jinkwang.co.kr
Ground Definite Time OC On/Off Ground Definite Time OC Pickup Ground Definite Time OC
Response Time 361 362 363 364 ON/OFF Additional Function Setting Group 4 365 366 367 368 369 370 371 Response Time 372 373 374 375 376 377 378 Response Time 379 380 381 Reclose Interval 4th Under-frequency pickup Under-frequency detection time 40/02,41/02 40/02,41/02 step :0.01Hz 40/02,41/02 0.03-10.00s, step: 0.01s 1~60sec 47.00-59.98, Ground Fast Reset type Ground Fast Reset Time Ground Delayed Reset type Ground Delayed Reset Time Ground Definite Time OC On/Off Ground Definite Time OC Pickup Ground Definite Time OC 40/02,41/02 0.00-1.00s, step : 0.01s 40/02,41/02 40/02,41/02 step :0.01s 40/02,41/02 40/02,41/02 step :0.01s 40/02,41/02 40/02,41/02 0(OFF), 1(ON) 50 - 10000A , step : 1A 0(RDMT), 1(RIDMT) 0.00-100.00s:, 0(RDMT), 1(RIDMT) 0.00-100.00s:, Phase Fast Reset type Phase Fast Reset Time Phase Delayed Reset type Phase Delayed Reset Time Phase Definite Time OC On/Off Phase Definite Time OC Pickup Phase Definite Time OC 40/02,41/02 0.00-1.00s, step : 0.01s 40/02,41/02 40/02,41/02 step :0.01s 40/02,41/02 40/02,41/02 step :0.01s 40/02,41/02 40/02,41/02 0(OFF), 1(ON) 50 - 10000A , step : 1A 0(RDMT), 1(RIDMT) 0.00-100.00s:, 0(RDMT), 1(RIDMT) 0.00-100.00s:, Reclose Interval 4th Under-frequency pickup Under-frequency detection time Under-frequency detection 40/02,41/02 0(Off),1(Alarm),2(On) 40/02,41/02 40/02,41/02 step :0.01Hz 40/02,41/02 0.03-10.00s, step: 0.01s
113 / 163
www.jinkwang.co.kr
ISO 9001 certified Under-frequency 382 ON/OFF File transfer EV_BIO EV_FUNC EV_SYS EV_FAULT EV_DMD_I EV_DMD_P EV_MAX_I EV_MAX_P FI_WAVE_0 FI_WAVE_1 FI_WAVE_2 FI_WAVE_3 FI_WAVE_4 FI_WAVE_5 FI_WAVE_6 FI_WAVE_7 I/O Event File Record format I/O Event ID I/O Event Date & Time I/O Event Status Flags Function Event File Record format Function Event ID Function Event Date & Time Function Event Status Flags System Event File Record format System Event ID System Event Date & Time System Event Status Flags Fault Event File Record format Fault Event Date & Time Fault Event Status detection -
40/02,41/02
0(Off),1(Alarm),2(On)
I/O Event History Function Event History System Event History Fault Event History Demand I History Demand P History Daily Peak I History Daily Peak P History Fault waveform (most recent)
Fault waveform Fault waveform Fault waveform Fault waveform Fault waveform Fault waveform Fault waveform (Oldest)
114 / 163
www.jinkwang.co.kr
ISO 9001 certified Fault Event Ia Fault Event Ib Fault Event Ic Fault Event In Fault Event Vo Fault Event Reserved Fault Event Reserved Fault Event Reserved Demand I Event File Record format Demand I Date & Time Demand I Ia Demand I Ib Demand I Ic Demand I In Demand P Event File Record format Demand P Date & Time Demand P kWa Demand P kWb Demand P kWc Demand P kW3ph Demand P kVARa Demand P kVARb Demand P kVARc Demand P kVAR3ph Max. I Event File Record format Max. I Date & Time Max .I Ia Max. I Ib Max. I Ic Max. I In Demand P Event File Record format Max. P Date & Time Max. P kWa Max. P kWb Max. P kWc
Epoxy molded Automatic Vacuum Recloser Unsigned short Unsigned short Unsigned short Unsigned short Unsigned short Unsigned short Unsigned short Unsigned short
DNP Time format Unsigned short Unsigned short Unsigned short Unsigned short
DNP Time format short short short short short short short short
DNP Time format Unsigned short Unsigned short Unsigned short Unsigned short
115 / 163
www.jinkwang.co.kr
ISO 9001 certified Max. P kW3ph Max. P kVARa Max. P kVARb Max. P kVARc Max. P kVAR3ph Fault waveform File Record format Fault waveform Date & Time Fault Status
Epoxy molded Automatic Vacuum Recloser short short short short short
DNP Time format Unsigned short Record 0 Unsigned short 10 bytes Unsigned short short short short short x=Record 1-320 short short short short Unsigned short
Sampling Rate = 32 Reserved Sample Op. Status[x] Sample Ia[x] Sample Ib[x] Sample Ic[x] Sample In[x] Sample Va[x] Sample Vb[x] Sample Vc[x] SampleVo[x] Sample reserved
116 / 163
www.jinkwang.co.kr
Appendix 3.
DNP V3.0
DEVICE PROFILE
& Implementation Table (V3.1)
DNP V3.00 DEVICE PROFILE DOCUMENT This document must be accompanied by a table having the following headings:
Device Function:
For Requests
Level 2
Master
Slave
For Responses
Level 2
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported (the complete list is described in the attached table):
117 / 163
www.jinkwang.co.kr
Transmitted ____292____________
(if>2048,must
Received
Never Always (not recommended) When reporting Event Data (Slave devices only) When sending multi-fragment responses (Slave devices only)
118 / 163
www.jinkwang.co.kr
Configurable
Data Link Confirm Complete Appl. Fragment Application Confirm Complete Appl. Response
None
Fixed at ___
Others ______________________________________________________________
Always
Never Never
Configurable Configurable
119 / 163
www.jinkwang.co.kr
Either time-tagged or non-time-tagged for a single event Both time-tagged and non-time-tagged for a single event Configurable (attach explanation)
Reports time-tagged Binary Input Change Events when no specific variation requested:
Never Only time-tagged Only non-time-tagged Configurable to send both, one or the other (attach explanation)
Never Binary Input Change With Time Binary Input Change With Relative Time Configurable (attach explanation)
Never Configurable (attach explanation) Only certain objects Sometimes (attach explanation)
120 / 163
www.jinkwang.co.kr
Epoxy molded Automatic Vacuum Recloser 32 Bits Other Value _____________ Point-by-point list attached
Yes
No
121 / 163
www.jinkwang.co.kr
Implementation Table
Version 3.1 REQUEST OBJECT (slave must parse) Func Codes Qual Obj 1 1 1 2 2 2 2 10 10 10 12 12 12 12 20 20 20 20 20 20 20 20 20 21 21 21 Var 0 1 2 0 1 2 3 0 1 2 0 1 2 3 0 1 2 3 4 5 6 7 8 0 1 2 Description (dec) Binary Input - All Variations Binary Input Binary Input with Status Binary Input Change - All Variations Binary Input Change without Time Binary Input Change with Time Binary Input Change with Relative Time Binary Output - All Variations Binary Output Binary Output Status Control Block - All Variations echo of Control Relay Output Block Pattern Control Block Pattern Mask Binary Counter - All Variations 32-bit Binary Counter 16-bit Binary Counter 32-bit Delta Counter 16-bit Delta Counter 32-bit Binary Counter without Flag 16-bit Binary Counter without Flag 32-bit Delta Counter without Flag 16-bit Delta Counter without Flag Frozen Counters - All Variations 32-bit Frozen Counter 16-bit Frozen Counter 1 00, 01, 06 129, 130 00, 01 1 00, 01, 06 129 00, 01 1 00, 01, 06 3, 4, 5, 6 17, 28 129 request 1 00, 01, 06 129 00, 01 1 1 1 1 1 1 1 1 (hex) 00, 01, 06 00, 01, 06 00, 01, 06 06, 07, 08 06, 07, 08 06, 07, 08 06, 07, 08 Var 3 , NULL Response 00, 01, 06 129, 130 129, 130 17, 28 17, 28 129 129 00, 01 00, 01 (dec) (hex) (master must parse) CodesFunc Codes Qual Codes RESPONSE
122 / 163
www.jinkwang.co.kr
ISO 9001 certified 21 21 21 21 21 3 4 5 6 7 Freeze 16-bit Frozen Delta Counter with Time of 21 21 21 21 21 22 22 22 22 8 Freeze 9 10 11 12 0 1 2 3 Time 16-Bit Delta Counter Change Event without 22 22 22 22 4 Time 5 6 7 Time 16-Bit Delta Counter Change Event with 22 23 23 23 23 8 Time 0 1 2 3 Time 16-Bit Frozen Delta Counter Event without 23 23 23 23 23 4 Time 5 6 7 8 32-Bit Frozen Counter Event with Time 16-Bit Frozen Counter Event with Time 32-Bit Frozen Delta Counter Event with Time 16-Bit Frozen Delta Counter Event with Time Frozen Counter Events - All Variations 32-Bit Frozen Counter Event without Time 16-Bit Frozen Counter Event without Time 32-Bit Frozen Delta Counter Event without 1 32-Bit Counter Change Event with Time 16-Bit Counter Change Event with Time 32-Bit Delta Counter Change Event with 32-bit Frozen Counter without Flag 16-bit Frozen Counter without Flag 32-bit Frozen Delta Counter without Flag 16-bit Frozen Delta Counter without Flag Counter Change Event - All Variations 32-Bit Counter Change Event without Time 16-Bit Counter Change Event without Time 32-Bit Delta Counter Change Event without 1 32-bit Frozen Delta Counter 16-bit Frozen Delta Counter 32-bit Frozen Counter with Time of Freeze 16-bit Frozen Counter with Time of Freeze 32-bit Frozen Delta Counter with Time of
06, 07, 08
06, 07, 08
129, 130
17, 28
123 / 163
www.jinkwang.co.kr
ISO 9001 certified 30 30 30 30 30 31 31 31 31 0 1 2 3 4 0 1 2 3 Freeze 16-Bit Frozen Analog Input with Time of 31 31 31 32 32 32 32 32 33 33 33 33 33 40 40 40 41 41 41 50 4 Freeze 5 6 0 1 2 3 4 0 1 2 3 4 0 1 2 0 1 2 0 32-Bit Frozen Analog Input without Flag 16-Bit Frozen Analog Input without Flag Analog Change Event - All Variations 32-Bit Analog Change Event without Time 16-Bit Analog Change Event without Time 32-Bit Analog Change Event with Time 16-Bit Analog Change Event with Time Frozen Analog Event - All Variations 32-Bit Frozen Analog Event without Time 16-Bit Frozen Analog Event without Time 32-Bit Frozen Analog Event with Time 16-Bit Frozen Analog Event with Time Analog Output Status - All Variations 32-Bit Analog Output Status 32-Bit Analog Output Status Analog Output Block - All Variations 32-Bit Analog Output Block 1 1 1 1 1 Analog Input - All Variations 32-Bit Analog Input 16-Bit Analog Input 32-Bit Analog Input without Flag 16-Bit Analog Input without Flag Frozen Analog Input - All Variations 32-Bit Frozen Analog Input 16-Bit Frozen Analog Input 32-Bit Frozen Analog Input with Time of 1 1 1
00, 01, 06
129
00, 01
00, 01, 06
129
00, 01
06, 07, 08
06, 07, 08
129, 130
17, 28
06, 07, 08
129, 130
17, 28
00, 01, 06
00, 01, 06
129
00, 01
echo of 16-Bit Analog Output Block Time and Date - All Variations 07 2 quantity=1 50 1 Time and Date 07 1 quantity=1 129 quantity=1 07 3, 4, 5, 6 17, 28 129 request
124 / 163
www.jinkwang.co.kr
ISO 9001 certified 50 51 51 2 0 1 Time and Date with Interval Time and Date CTO - All Variations
07, Time and Date CTO 129 quantity=1 07, 51 52 52 2 0 1 Unsynchronized Time and Date CTO Time Delay - All Variations 07, Time Delay Coarse 129 quantity=1 07, 52 60 60 60 2 0 1 2 Time Delay Fine Not Defined Class 0 Data Class 1 Data 20, 21 1 60 3 Class 2 Data 20, 21 1 60 70 80 81 82 83 83 90 100 100 100 101 101 101 4 1 1 1 1 1 2 1 1 2 3 1 2 3 Class 3 Data 20, 21 File Identifier 00, Internal Indications Storage Object Device Profile Private Registration Object Private Registration Object Descriptor Application Identifier Shot Floating Point Long Floating Point Extended Floating Point Small Packed Binary-Coded Decimal Medium Packed Binary-Coded Decimal Large Packed Binary-Coded Decimal 13 14 23 2 index=7 06 06 06, 07, 08 06 06, 07, 08 1 1 06 06, 07, 08 129 quantity=1 129 quantity=1
125 / 163
www.jinkwang.co.kr
Appendix 4.
DIMENSIONS
126 / 163
www.jinkwang.co.kr
Appendix 5.
1. Connections check
- Check if all connectors except Battery in the control box are plugged.
- <Caution> The connector to Battery should be unplugged when the box is stored or delivered to site. If not so, the battery can be discharged by the power consumption of the Power & Control Board regardless of MCCB or RTU power switch.
- Plug-in the Battery connector to the connector on the Power & Control Board
- Press the Battery Start button on the panel inside the box.
- Check if RTU is powered on and runs without error and check the Battery voltage and current through Battery Test Terminal on the panel by using portable Meter. - <Caution> Be careful of avoiding short of voltage test terminal.
- <Caution> The connector to Battery should be unplugged when the box is stored or delivered to site.
127 / 163
www.jinkwang.co.kr
- For protection of circuits in the control box, there are some fuses. AC(220V) input circuit, Battery voltage test terminal, 3 fuses on the Power & Control Board. (AC input/DC output for FTU & Control /DC output for Modem)
- Use fuse of the specified rating for exchange. - Modem power output voltage is 24V. The voltage is adjustable for 13V~24V range. For the adjustment, you have to remove the upper case of the Power & Control Board. You should be very careful.
4 . Insulation Test
- <Caution> Before Test, Disconnect two frame ground jumper wires on I/O Board in the RTU and one on Power & Control Board * Use cables connected to the control & power connector outside control box and earth-terminal of the control box. Refer to the external connection diagram.
4.1 DC Resistance
- Measure the DC resistance of the following circuits by DC 500V Mega Ohm Tester
Criteria 10M
4.2 AC Insulation
- Leakage current should be below 5mA under the following test condition. Circuit All Circuit Earth Criteria AC 2kV, 1min Test Result OK Fail
128 / 163
www.jinkwang.co.kr
* The insulation test between the circuits shall be performed after MOVs in the RTU or on Power & Control Board and also the biased connections are removed. This test shall be performed with our engineer as type test.
5. RTU Run Status Check - Check if RUN LED blinks, Sys Error LED is lit off.
- Check if BPS, Address, Modem control of RTU was set appropriately. BPS setting change needs the restart of RTU.
- Check if RTU responds to the request from master by looking at RTS, TX LED. * If only RTS LED is turned on during CTS checkout time, please check CTS signal from MODEM.
- Protocol Monitor built in the RTU can be used to check if the RTU receives or transmits data correctly.
129 / 163
www.jinkwang.co.kr
- Check Interlock condition: Local/Remote, Switch Status, Gas Low, Handle Lock
Gas low, handle lock condition interlocks switch open/close operation. Switch status is determined by double binary inputs (open/closed contact inputs). If the statuses of double binary inputs are identical, the control operation is blocked. The same operation to the current switch status is inhibited. At local the control can be executed after select. (SELECT button/LED) Select state is canceled at SBO timeout. - Type of open/close command output is pulsed-on contact. Pulse width can be set through setting. (Configuration Menu.) In case of control operation from master, the pulse width is given through DNP object O12V1. Long trip pulse time may block the correct reclosing and lockout the Recloser. The trip pulse time shall be shorter than the dead time for the fast reclosing.
130 / 163
www.jinkwang.co.kr
- The control command is transmitted to the Recloser Switch as battery-voltage biased contact. No drive interlock scheme is equipped in the control box.
131 / 163
www.jinkwang.co.kr
8. Measurements Check
- Check the settings of Analog input rating. Frequency, CT Ratio, Rated Phase voltage
- Inject the accurate 3-phase voltages and currents to the Cable instead of switch, and check the value through the measurements window or LCD. The value of voltages and currents that are injected is the secondary value of sensor installed inside the Recloser Switch. For 1000A, inject 1A on the terminals of the control box in case of 1000:1 CT ratio. For Rated phase voltage, 4V~10V shall be applied to the control box. The exact value depends on the calibrating state of the Recloser Switch.
132 / 163
www.jinkwang.co.kr
- Check if the status monitored by RTU is correct through Display/Status Menu on LCD or Status Page on PC Tool.
- The physical dry contacts from Recloser Switch is biased in the control box and transmitted to the binary input circuits of RTU.
133 / 163
www.jinkwang.co.kr
Appendix 6.
1.
IEC60870-5-101 Interoperability
X
Controlled station definition (Slave) 2. Network configuration
Multipoint-partyline Multipoint-star
3.
Physical layer
Transmission speed (control direction) Unbalanced interchange Circuit V.24/V.28 Standard 100 bits/sec 200 bits/sec Unbalanced interchange Circuit V.24/V.28 Recommended if >1 200 bit/s Balanced interchange Circuit X.24/X.27 2400 bits/sec
300 bits/sec
600 bits/sec
X 1200 bits/sec
64000 bits/sec
Balanced interchange
Circuit V.24/V.28
134 / 163
www.jinkwang.co.kr
100 bits/sec 200 bits/sec 300 bits/sec 600 bits/sec X 1200 bits/sec
2400 bits/sec 4800 bits/sec 9600 bits/sec 19200 bits/sec 38400 bits/sec 56000 bits/sec 64000 bits/sec
4.
Link layer
Frame format FT 1.2, single character 1 and the fixed time out interval are used exclusively in this companion standard. Link transmission procedure Address field of the link
Not present (balanced transmission only) One octet Two octets Structured
Unstructured
When using an unbalanced link layer, the following ASDU types are returned in class 2 messages (low priority) with the indicated causes of transmission:
135 / 163
www.jinkwang.co.kr
NOTE In response to a class 2 poll, a controlled station may respond with class 1 data when there is no class 2 data available.
136 / 163
www.jinkwang.co.kr
5.
Application layer
One octet
Two octets
Unstructured
One octet
Two octets (with originator address) Set to zero in case of no originator address
X X X X
<1> := Single-point information <2> := Single-point information with time tag <3>:= Double-point information <4> := Double-point information with time tag <5> := Step position information <6>:= Step position information with time tag <7> := Bitstring of 32 bit <8> := Bitstring of 32 bit with time tag <9> := Measured value, normalized value
137 / 163
www.jinkwang.co.kr
M_ME_TA_1 M_ME_NB_1 M_ME_TB_1 M_ME_NC_1 M_ME_TC_1 M_IT_NA_1 M_IT_TA_1 M_EP_TA_1 M_EP_TB_1 M_EP_TC_1 M_PS_NA_1 M_ME_ND_1 M_SP_TB_1 M_DP_TB_1 M_ST_TB_1 M_BO_TB_1 M_ME_TD_1 M_ME_TE_1 M_ME_TF_1 M_IT_TB_1 M_EP_TD_1 M_EP_TE_1 M_EP_TF_1
X X
<11>:= Measured value, scaled value <12>:=Measured value, scaled value with time tag <13>:=Measured value, short floating point value <14>:=Measured value, short floating point value with time tag
X X
<15>:=Integrated totals <16>:=Integrated totals with time tag <17>:=Event of protection equipment with time tag <18>:=Packed start events of protection equipment with time tag <19>:=Packed output circuit information of protection equipment with time tag <20>:=Packed single-point information with status change detection <21>:=Measured value, normalized value without quality descriptor <30>:=Single-point information with time tag CP56Time2a <31>:=Double-point information with time tag CP56Time2a <32>:=Step position information with time tag CP56Time2a <33>:=Bitstring of 32 bit with time tag CP56Time2a <34>:=Measured value, normalized value with time tag CP56Time2a <35>:=Measured value, scaled value with time tag CP56Time2a <36>:=Measured value, short floating point value with time tag CP56Time2a <37>:=Integrated totals with time tag CP56Time2a <38>:=Event of protection equipment with time tag CP56Time2a <39>:=Packed start events of protection equipment with time tag CP56Time2a <40>:=Packed output circuit information of protection equipment with time tag CP56Time2a
Either ASDUs of the set <2>, <4>, <6>, <8>, <10>, <12>, <14>, <16>, <17>, <18>, <19> or of the set <30 40> are used.
138 / 163
www.jinkwang.co.kr
X X
<45>:=Single command <46>:=Double command <47>:=Regulating step command <48>:=Set point command, normalized value
<49>:=Set point command, scaled value <50>:=Set point command, short floating point value <51> :=Bitstring of 32 bit
<70>:=End of initialization
M_EI_NA_1
X X X X X X X
<100>:=Interrogation command <101>:=Counter interrogation command <102>:=Read command <103>:=Clock synchronization command <104>:=Test command <105>:=Reset process command <106>:=Delay acquisition command
139 / 163
www.jinkwang.co.kr
File transfer
F_FR_NA_1 F_SR_NA_1
<122>:=Call directory, select file, call file, call section <123>:=Last section, last segment
F_SC_NA_1 F_LS_NA_1
F_AF_NA_1
F_SG_NA_1 F_DR_TA_1
Shaded boxes are not required. Blank = function or ASDU is not used. " X " if used only in the standard direction
Type identification 1 2 3 4 5 6
Cause of transmission 7 8 9 1 0 1 1 1 2 1 3 2 0 3 7 4 4 4 5 4 6 4 7
to to 3 6 <1> <2> <3> <4> <5> <6> <7> <8> <9> M_SP_NA_1 M_SP_TA_1 M_DP_NA_1 M_DP_TA_1 M_ST_NA_1 M_ST_TA_1 M_BO_NA_1 M_BO_TA_1 M_ME_NA_1 X X X X X X X X X X 4 1
140 / 163
www.jinkwang.co.kr
to to 3 6 <10> M_ME_TA_1 <11> M_ME_NB_1 <12> M_ME_TB_1 <13> M_ME_NC_1 <14> M_ME_TC_1 <15> M_IT_NA_1 <16> M_IT_TA_1 <17> M_EP_TA_1 <18> M_EP_TB_1 <19> M_EP_TC_1 <20> M_PS_NA_1 <21> M_ME_ND_1 <30> M_SP_TB_1 <31> M_DP_TB_1 <32> M_ST_TB_1 <33> M_BO_TB_1 <34> M_ME_TD_1 <35> M_ME_TE_1 <36> M_ME_TF_1 <37> M_IT_TB_1 <38> M_EP_TD_1 <39> M_EP_TE_1 <40> M_EP_TF_1 <45> C_SC_NA_1 <46> C_DC_NA_1 <47> C_RC_NA_1 <48> C_SE_NA_1 X X X X X X X X X X X X X X X X X 4 1
141 / 163
www.jinkwang.co.kr
to to 3 6 <49> C_SE_NB_1 <50> C_SE_NC_1 <51> C_BO_NA_1 <70> M_EI_NA_1 <100 C_IC_NA_1 > <101 C_CI_NA_1 > <102 C_RD_NA_1 > <103 C_CS_NA_1 > <104 C_TS_NA_1 > <105 C_RP_NA_1 > <106 C_CD_NA_1 > <110 P_ME_NA_1 > <111 > <112 P_ME_NC_1 > <113 P_AC_NA_1 > P_ME_NB_1 X X X X X X X X X X X X X X X X X X X X X X X X 4 1
142 / 163
www.jinkwang.co.kr
to to 3 6 <120 F_FR_NA_1 > <121 F_SR_NA_1 > <122 F_SC_NA_1 > <123 F_LS_NA_1 > <124 F_AF_NA_1 > <125 F_SG_NA_1 > <126 F_DR_TA_1* > * Blank or X only. 4 1
Remote initialization X
Read procedure
Read procedure
143 / 163
www.jinkwang.co.kr
Spontaneous transmission
Spontaneous transmission
Double transmission of information objects with cause of transmission spontaneous The following type identifications may be transmitted in succession caused by a single status change of an information object. The particular information object addresses for which double transmission is enabled are defined in a project-specific list.
Bitstring of 32 bit M_BO_NA_1, M_BO_TA_1 and M_BO_TB_1(if defined for a specific project) Measured value, normalized value M_ME_NA_1, M_ME_TA_1, M_ME_ND_1 and M_ME_TD_1 Measured value, scaled value M_ME_NB_1, M_ME_TB_1 and M_ME_TE_1
Measured value, short floating point number M_ME_NC_1, M_ME_TC_1 and M_ME_TF_1
Station interrogation
X X X X X X
global group 1
X X
X X X X
group 2
X X X
group 3
group 4 group 5
group 6
144 / 163
www.jinkwang.co.kr
Clock synchronization
X Clock synchronization
Command transmission
X C_SE ACTTERM used X No additional definition X X Long-pulse duration (duration determined by a system parameter in the controlled station)
Persistent output Short-pulse duration (duration determined by a system parameter in the controlled station)
X Mode A: local freeze with spontaneous transmission X Mode B: local freeze with counter interrogation X Mode C: freeze and transmit by counter interrogation commands X Mode D: freeze by counter interrogation command, frozen values reported spontaneously
145 / 163
www.jinkwang.co.kr
Test procedure
X Counter read X Counter freeze without reset X Counter freeze with reset X Counter reset
request counter X General Test procedure
X Request counter group 1 X Request counter group 2 Parameter loading counter X Request Threshold value group 3
Request counter X Smoothing factor group 4 Low limit for transmission of measured value High limit for transmission of measured value
Parameter activation
Act/deact of persistent cyclic or periodic transmission of the addressed object
File transfer
Transparent file
Transmission of disturbance data of protection equipment Transmission of sequences of events Transmission of sequences of recorded analog values
Transparent file
146 / 163
www.jinkwang.co.kr
147 / 163
www.jinkwang.co.kr
Appendix 7.
Point Address
M_SP_NA_1 points 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 System Error Inrush Detected Reclosing Blocked Protection Blocked Ext. AC Power Loss Door Open DI Spare #1 DI Spare #2 DI Spare #3 Fault Indicator (A) Fault Indicator (B) Fault Indicator (C) Fault Indicator (N) Fault Indicator (SEF) Reverse Direction Fault Open Line Detection A Open Line Detection B Open Line Detection C Contact closed = 1 Contact closed = 1 Contact closed = 1 Reserved Battery Discharged Control Mode Handle Locked Local = 1
148 / 163
www.jinkwang.co.kr
ISO 9001 certified 127 128 129 130 131 Ground Protection Blocked High Current Trip Sequence Lockout Reserved #1 Reserved #2
C_SC_NA_1 points 1000 1001 Annunciator Manual Reset Battery Test Output No Select Required No Select Required
C_DC_NA_1 points Select 1200 Switch Open/Close Control Execute M_ME_NB_1 points 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 KVAa KVAb KVAc kVA3ph KWa KWb KWc kW3ph KVARa kVA kVA kVA kVA kW kW kW kW kVAR Ia RMS Ib RMS Ic RMS In RMS Source side Va RMS Source side Vb RMS Source side Vc RMS Source side Vo RMS A A A A V V V V Required Before
149 / 163
www.jinkwang.co.kr
ISO 9001 certified 2021 2022 2023 2024 2025 2026 2027 2028 2029 2030 2031 2032 2033 2034 2035 2036 2037 2038 2039 2040 2041 2042 2043 2044 2045 2046 2047 2048 2049 2050 2051 2052 2053 2054 2055 I1 RMS I1 phase angle I2 RMS I2 phase angle Source side V1 RMS Source side V1 phase angle Source side V2 RMS Source side V2 phase angle KVARb KVARc kVAR3ph PFa PFb PFc PF3ph Va-Vr Phase Angle Diff Frequency Temperature Reserved Ia phase angle Ib phase angle Ic phase angle In phase angle Source side Va phase angle Source side Vb phase angle Source side Vc phase angle Source side Vo phase angle
Epoxy molded Automatic Vacuum Recloser kVAR kVAR kVAR X100 X100 X100 X100
o
10
HZ100 Degree
o o o o o o o o
10 10 10 10 10 10 10 10
A
o
10
A
o
10
V
o
10
V
o
10
150 / 163
www.jinkwang.co.kr
ISO 9001 certified 2056 2057 2058 2059 2060 2061 2062 2063 2064 2065 2066 2067 2068 2069 2070 2071 2072 2073 2074 2075 2076 2077 2078 2079 2080 2081 2082 2083 2084 2085 2086 2087 2088 2089 2090 PFa lead PFb lead PFc lead PF3ph lead Last Fault Ia Last Fault Ib Last Fault Ic Last Fault In Last Fault vo Reserved Reserved Reserved Demand I Ia Demand I Ib Demand I Ic Demand I In Demand P kWa Demand P kWb Demand P kWc Demand P kW3ph Demand P kVARa Demand P kVARb Demand P kVARc Demand P kVAR3ph Max. I Ia Max. I Ib Max. I Ic Max. I In Max. P1 kWa Max. P1 kWb Max. P1 kWc Max. P1 kW3ph Max. P1 kVARa Max. P1 kVARb Max. P1 kVARc
151 / 163
www.jinkwang.co.kr
ISO 9001 certified 2091 2092 2093 2094 2095 2096 2097 2098 2099 2100 2101 2102 2103 2104 2105 2106 2107 2108 2109 2110 2111 2112 2113 2114 2115 2116 2117 2118 2119 2120 2121 2122 2123 2124 2125 Ia 2nd harmonic RMS Ib 2
nd
Epoxy molded Automatic Vacuum Recloser Max. P1 kVAR3ph 3-phase currents THD Ia THD Ib THD Ic THD Source side 3-phase voltages THD Source side Va THD Source side Vb THD Source side Vc THD kVAR % % % % % % % %
Ia true RMS Ib true RMS Ic true RMS Va true RMS Vb true RMS Vc true RMS
A A A V V V
A A A A A A A A A A A A A
harmonic RMS
Ic 2nd harmonic RMS Ia 3 harmonic RMS Ib 3 harmonic RMS Ic 3rd harmonic RMS Ia 4 harmonic RMS Ib 4th harmonic RMS Ic 4th harmonic RMS Ia 5 harmonic RMS Ib 5th harmonic RMS Ic 5 harmonic RMS Ia 6 harmonic RMS
th th th th rd rd
152 / 163
www.jinkwang.co.kr
ISO 9001 certified 2126 2127 2128 2129 2130 2131 2132 2133 2134 2135 2136 2137 2138 2139 2140 2141 2142 2143 2144 2145 2146 2147 2148 2149 2150 2151 2152 2153 2154 2155 2156 2157 2158 2159 2160 Ib 6th harmonic RMS Ic 6 harmonic RMS Ia 7 harmonic RMS Ib 7th harmonic RMS Ic 7 harmonic RMS Ia 8th harmonic RMS Ib 8th harmonic RMS Ic 8 harmonic RMS
th th th th
nd
Source side Va 3rd harmonic RMS Source side Vb 3 harmonic RMS Source side Vc 3rd harmonic RMS Source side Va 4th harmonic RMS Source side Vb 4 harmonic RMS Source side Vc 4th harmonic RMS Source side Va 5 harmonic RMS Source side Vb 5 harmonic RMS Source side Vc 5th harmonic RMS Source side Va 6 harmonic RMS Source side Vb 6th harmonic RMS Source side Vc 6th harmonic RMS Source side Va 7 harmonic RMS Source side Vb 7th harmonic RMS Source side Vc 7 harmonic RMS Source side Va 8 harmonic RMS Source side Vb 8th harmonic RMS Source side Vc 8 harmonic RMS
th th th th th th th th rd
153 / 163
www.jinkwang.co.kr
ISO 9001 certified 2161 2162 2163 2164 2165 2166 2167 2168 2169 2170 2171 2172 2173 2174 2175 2176 2177 2178 2179 2180 2181 2182 2183 2184 In THD In true RMS In 2
nd rd
% A A A A A A A A
harmonic RMS
In 3 harmonic RMS In 4th harmonic RMS In 5 harmonic RMS In 6th harmonic RMS In 7th harmonic RMS In 8 harmonic RMS M_IT_NA_1 points
th th
4000 4001 4002 4003 4004 4005 4006 4007 4008 4009
Restart Count Switch Trip (or Open) Count All Faults Count A-phase Fault Count B-phase Fault Count C-phase Fault Count N-phase Fault Count kWattHour-a Export kWattHour-b Export kWattHour-c Export
154 / 163
www.jinkwang.co.kr
ISO 9001 certified 4010 4011 4012 4013 4014 4015 4016 4017 4018 4019 4020 4021 4022 kWattHour-3ph Export kVarHour-a Export kVarHour-b Export kVarHour-c Export kVarHour-3ph Export kWattHour-a Import kWattHour-b Import kWattHour-c Import kWattHour-3ph Import kVarHour-a Import kVarHour-b Import kVarHour-c Import kVarHour-3ph Import
Epoxy molded Automatic Vacuum Recloser kWh kVarh kVarh kVarh kVarh kWh kWh kWh kWh kVarh kVarh kVarh kVarh
C_SE_NB_1 points (Current Setting : M_ME_NB_1 points) Setting Group1 3000 3001 3002 3003 3004 3005 3006 3007 3008 3009 3010 3011 3012 3013 3014 3015 3016 3017 3018 3019 Phase - Pickup Current Phase Fast - TCC Type Phase Fast - Time Multiplier Phase Fast - Time Adder Phase Fast - Min Response Time Phase Fast - Reset Type Phase Fast - Reset Definite Time Phase Delay - TCC Type Phase Delay - Time Multiplier Phase Delay - Time Adder Phase Delay - Min Response Time Phase Delay - Reset Type Phase Delay - Reset Definite Time Phase Definite Time OC - Active Phase Definite Time OC - Pickup Current Phase Definite Time OC - Response Time Phase High Current - Pickup Phase High Current - Response Time Phase - Cold Load Pickup Multiplier Phase - Inrush Restraint 10~900A 1~58 0.10~2.00,step:0.01 0.00~1.00,step:0.01Sec 0.00~1.00,step:0.01Sec RDMT(0),RIDMT(1) 0.00~100.00,step:0.01Sec 1~58 0.10~2.00,step:0.01 0.00~1.00,step:0.01Sec 0.00~1.00,step:0.01Sec RDMT(0),RIDMT(1) 0.00~100.00,step:0.01Sec 0(Off),1(On) 50~10000A 0.00~1.00,step:0.01Sec 50~10000A 0.00~1.00,step:0.01Sec 1.0~5.0,step:0.1 No(0),Yes(1)
155 / 163
www.jinkwang.co.kr
ISO 9001 certified 3020 3021 3022 3023 3024 3025 3026 3027 3028 3029 3030 3031 3032 3033 3034 3035 3036 3037 3038 3039 3040 3041 3042 3043 3044 3045 3046 3047 3048 3049 3050 3051 3052 3053 3054 Ground - Pickup Current Ground Fast - TCC Type Ground Fast - Time Multiplier Ground Fast - Time Adder
Epoxy molded Automatic Vacuum Recloser 5~900A 1~58 0.10~2.00,step:0.01 0.00~1.00,step:0.01Sec 0.00~1.00,step:0.01Sec RDMT(0),RIDMT(1) 0.00~100.00,step:0.01Sec 1~58 0.10~2.00,step:0.01 0.00~1.00,step:0.01Sec 0.00~1.00,step:0.01Sec RDMT(0),RIDMT(1) 0.00~100.00,step:0.01Sec 0(Off),1(On) 50~10000A 0.00~1.00,step:0.01Sec 50~10000A 0.00~1.00,step:0.01Sec 1.0~5.0,step:0.1 No(0),Yes(1) 2 - 20A 10~80% 0~345,step:15 DEG 0.1~30.0 step:0.1 Sec No(0),Yes(1) 0(Off),Alarm(1),Trip(2) 5~50% 0.02~1.00,step:0.01 0(Off),1(On) 1~5 times 1~5 times 0~5 times 0~5 times 0(OFF), 1~5 times 0(OFF), 1~5 times
Ground Fast - Min Response Time Ground Fast - Reset Type Ground Fast - Reset Definite Time Ground Delay - TCC Type Ground Delay - Time Multiplier Ground Delay - Time Adder Ground Delay - Min Response Time Ground Delay - Reset Type Ground Delay - Reset Definite Time Ground Definite Time OC - Active Ground Definite Time OC - Pickup Current Ground Definite Time OC - Response Time Ground High Current - Pickup Ground High Current - Response Time Ground - Cold Load Pickup Multiplier Ground - Inrush Restraint SEF -Pickup Current(Io) SEF -Pickup Voltage(Vo) SEF -Max. Torque Angle SEF -Detection Time SEF -Inrush restraint SEF -Operation Select Inrush restraint - 2
nd
harmonic Pickup
Inrush restraint - Detection Time Inrush restraint - Operation Select Operation to Lockout Phase Operation to Lockout Ground Operation Fast Curve Phase Operation Fast Curve Ground High Current Phase Active High Current Ground Active
156 / 163
www.jinkwang.co.kr
ISO 9001 certified 3055 3056 3057 3058 3059 3060 3061 3062 3063 3064 3065 3066 3067 3068 3069 3070 3071 3072 Setting Group2 3100 3101 3102 3103 3104 3105 3106 3107 3108 3109 3110 3111 3112 3113 3114 3115 Phase - Pickup Current Phase Fast - TCC Type Phase Fast - Time Multiplier Phase Fast - Time Adder Reclose Interval 1st Reclose Interval 2 Reclose Interval 3
nd rd
Epoxy molded Automatic Vacuum Recloser 0.5~60.0,step:0.1Sec 1~60s 1~60s 1~60s 3~180s 0.00~60.00,step:0.01Sec 0.00~30.00,step:0.01Sec No(0),Yes(1) 50~90,step:5% 35~75,step:5% 0.1~30.0,step:0.1Sec 0(Off),1(On)
Reclose Interval 4th Reset Time Cold Load Duration Cold Load Pickup Restore Time Sequence Coordination Active Phase Loss - Volt On level Phase Loss - Volt Off level Phase Loss - Detection Time Phase Loss - Operation Select
Under Frequency - Frequency Pickup Under Frequency - Detection Time Under Frequency - Operation Select
10~900A 1~58 0.10~2.00,step:0.01 0.00~1.00,step:0.01Sec 0.00~1.00,step:0.01Sec RDMT(0),RIDMT(1) 0.00~100.00,step:0.01Sec 1~58 0.10~2.00,step:0.01 0.00~1.00,step:0.01Sec 0.00~1.00,step:0.01Sec RDMT(0),RIDMT(1) 0.00~100.00,step:0.01Sec 0(Off),1(On) 50~10000A 0.00~1.00,step:0.01Sec
Phase Fast - Min Response Time Phase Fast - Reset Type Phase Fast - Reset Definite Time Phase Delay - TCC Type Phase Delay - Time Multiplier Phase Delay - Time Adder Phase Delay - Min Response Time Phase Delay - Reset Type Phase Delay - Reset Definite Time Phase Definite Time OC - Active Phase Definite Time OC - Pickup Current Phase Definite Time OC - Response Time
157 / 163
www.jinkwang.co.kr
ISO 9001 certified 3116 3117 3118 3119 3120 3121 3122 3123 3124 3125 3126 3127 3128 3129 3130 3131 3132 3133 3134 3135 3136 3137 3138 3139 3140 3141 3142 3143 3144 3145 3146 3147 3148 3149 3150 Phase High Current - Pickup
Epoxy molded Automatic Vacuum Recloser 50~10000A 0.00~1.00,step:0.01Sec 1.0~5.0,step:0.1 No(0),Yes(1) 5~900A 1~58 0.10~2.00,step:0.01 0.00~1.00,step:0.01Sec 0.00~1.00,step:0.01Sec RDMT(0),RIDMT(1) 0.00~100.00,step:0.01Sec 1~58 0.10~2.00,step:0.01 0.00~1.00,step:0.01Sec 0.00~1.00,step:0.01Sec RDMT(0),RIDMT(1) 0.00~100.00,step:0.01Sec 0(Off),1(On) 50~10000A 0.00~1.00,step:0.01Sec 50~10000A 0.00~1.00,step:0.01Sec 1.0~5.0,step:0.1 No(0),Yes(1) 2 - 20A 10~80% 0~345,step:15 DEG 0.1~30.0 step:0.1 Sec No(0),Yes(1) 0(Off),Alarm(1),Trip(2) 5~50% 0.02~1.00,step:0.01 0(Off),1(On) 1~5 times 1~5 times
Phase High Current - Response Time Phase - Cold Load Pickup Multiplier Phase - Inrush Restraint Ground - Pickup Current Ground Fast - TCC Type Ground Fast - Time Multiplier Ground Fast - Time Adder Ground Fast - Min Response Time Ground Fast - Reset Type Ground Fast - Reset Definite Time Ground Delay - TCC Type Ground Delay - Time Multiplier Ground Delay - Time Adder Ground Delay - Min Response Time Ground Delay - Reset Type Ground Delay - Reset Definite Time Ground Definite Time OC - Active Ground Definite Time OC - Pickup Current Ground Definite Time OC - Response Time Ground High Current - Pickup Ground High Current - Response Time Ground - Cold Load Pickup Multiplier Ground - Inrush Restraint SEF -Pickup Current(Io) SEF -Pickup Voltage(Vo) SEF -Max. Torque Angle SEF -Detection Time SEF -Inrush restraint SEF -Operation Select Inrush restraint - 2nd harmonic Pickup Inrush restraint - Detection Time Inrush restraint - Operation Select Operation to Lockout Phase Operation to Lockout Ground
158 / 163
www.jinkwang.co.kr
ISO 9001 certified 3151 3152 3153 3154 3155 3156 3157 3158 3159 3160 3161 3162 3163 3164 3165 3166 3167 3168 3169 3170 3171 3172 Setting Group3 3200 3201 3202 3203 3204 3205 3206 3207 3208 3209 3210 3211 Phase - Pickup Current Phase Fast - TCC Type Phase Fast - Time Multiplier Phase Fast - Time Adder Operation Fast Curve Phase Operation Fast Curve Ground High Current Phase Active High Current Ground Active Reclose Interval 1
st
Epoxy molded Automatic Vacuum Recloser 0~5 times 0~5 times 0(OFF), 1~5 times 0(OFF), 1~5 times 0.5~60.0,step:0.1Sec 1~60s 1~60s 1~60s 3~180s 0.00~60.00,step:0.01Sec 0.00~30.00,step:0.01Sec No(0),Yes(1) 50~90,step:5% 35~75,step:5% 0.1~30.0,step:0.1Sec 0(Off),1(On)
Reclose Interval 2nd Reclose Interval 3rd Reclose Interval 4 Reset Time Cold Load Duration Cold Load Pickup Restore Time Sequence Coordination Active Phase Loss - Volt On level Phase Loss - Volt Off level Phase Loss - Detection Time Phase Loss - Operation Select
th
Under Frequency - Frequency Pickup Under Frequency - Detection Time Under Frequency - Operation Select
10~900A 1~58 0.10~2.00,step:0.01 0.00~1.00,step:0.01Sec 0.00~1.00,step:0.01Sec RDMT(0),RIDMT(1) 0.00~100.00,step:0.01Sec 1~58 0.10~2.00,step:0.01 0.00~1.00,step:0.01Sec 0.00~1.00,step:0.01Sec RDMT(0),RIDMT(1)
Phase Fast - Min Response Time Phase Fast - Reset Type Phase Fast - Reset Definite Time Phase Delay - TCC Type Phase Delay - Time Multiplier Phase Delay - Time Adder Phase Delay - Min Response Time Phase Delay - Reset Type
159 / 163
www.jinkwang.co.kr
ISO 9001 certified 3212 3213 3214 3215 3216 3217 3218 3219 3220 3221 3222 3223 3224 3225 3226 3227 3228 3229 3230 3231 3232 3233 3234 3235 3236 3237 3238 3239 3240 3241 3242 3243 3244 3245 3246
Epoxy molded Automatic Vacuum Recloser Phase Delay - Reset Definite Time Phase Definite Time OC - Active Phase Definite Time OC - Pickup Current Phase Definite Time OC - Response Time Phase High Current - Pickup Phase High Current - Response Time Phase - Cold Load Pickup Multiplier Phase - Inrush Restraint Ground - Pickup Current Ground Fast - TCC Type Ground Fast - Time Multiplier Ground Fast - Time Adder Ground Fast - Min Response Time Ground Fast - Reset Type Ground Fast - Reset Definite Time Ground Delay - TCC Type Ground Delay - Time Multiplier Ground Delay - Time Adder Ground Delay - Min Response Time Ground Delay - Reset Type Ground Delay - Reset Definite Time Ground Definite Time OC - Active Ground Definite Time OC - Pickup Current Ground Definite Time OC - Response Time Ground High Current - Pickup Ground High Current - Response Time Ground - Cold Load Pickup Multiplier Ground - Inrush Restraint SEF -Pickup Current(Io) SEF -Pickup Voltage(Vo) SEF -Max. Torque Angle SEF -Detection Time SEF -Inrush restraint SEF -Operation Select Inrush restraint - 2
nd
0.00~100.00,step:0.01Sec 0(Off),1(On) 50~10000A 0.00~1.00,step:0.01Sec 50~10000A 0.00~1.00,step:0.01Sec 1.0~5.0,step:0.1 No(0),Yes(1) 5~900A 1~58 0.10~2.00,step:0.01 0.00~1.00,step:0.01Sec 0.00~1.00,step:0.01Sec RDMT(0),RIDMT(1) 0.00~100.00,step:0.01Sec 1~58 0.10~2.00,step:0.01 0.00~1.00,step:0.01Sec 0.00~1.00,step:0.01Sec RDMT(0),RIDMT(1) 0.00~100.00,step:0.01Sec 0(Off),1(On) 50~10000A 0.00~1.00,step:0.01Sec 50~10000A 0.00~1.00,step:0.01Sec 1.0~5.0,step:0.1 No(0),Yes(1) 2 - 20A 10~80% 0~345,step:15 DEG 0.1~30.0 step:0.1 Sec No(0),Yes(1) 0(Off),Alarm(1),Trip(2) 5~50%
harmonic Pickup
160 / 163
www.jinkwang.co.kr
ISO 9001 certified 3247 3248 3249 3250 3251 3252 3253 3254 3255 3256 3257 3258 3259 3260 3261 3262 3263 3264 3265 3266 3267 3268 3269 3270 3271 3272 Setting Group4 3300 3301 3302 3303 3304 3305 3306 3307 Phase - Pickup Current Phase Fast - TCC Type Phase Fast - Time Multiplier Phase Fast - Time Adder
Epoxy molded Automatic Vacuum Recloser Inrush restraint - Detection Time Inrush restraint - Operation Select Operation to Lockout Phase Operation to Lockout Ground Operation Fast Curve Phase Operation Fast Curve Ground High Current Phase Active High Current Ground Active Reclose Interval 1st Reclose Interval 2 Reclose Interval 3
nd rd
0.02~1.00,step:0.01 0(Off),1(On) 1~5 times 1~5 times 0~5 times 0~5 times 0(OFF), 1~5 times 0(OFF), 1~5 times 0.5~60.0,step:0.1Sec 1~60s 1~60s 1~60s 3~180s 0.00~60.00,step:0.01Sec 0.00~30.00,step:0.01Sec No(0),Yes(1) 50~90,step:5% 35~75,step:5% 0.1~30.0,step:0.1Sec 0(Off),1(On)
Reclose Interval 4th Reset Time Cold Load Duration Cold Load Pickup Restore Time Sequence Coordination Active Phase Loss - Volt On level Phase Loss - Volt Off level Phase Loss - Detection Time Phase Loss - Operation Select
Under Frequency - Frequency Pickup Under Frequency - Detection Time Under Frequency - Operation Select
Phase Fast - Min Response Time Phase Fast - Reset Type Phase Fast - Reset Definite Time Phase Delay - TCC Type
161 / 163
www.jinkwang.co.kr
ISO 9001 certified 3308 3309 3310 3311 3312 3313 3314 3315 3316 3317 3318 3319 3320 3321 3322 3323 3324 3325 3326 3327 3328 3329 3330 3331 3332 3333 3334 3335 3336 3337 3338 3339 3340 3341 3342 Phase Delay - Time Multiplier Phase Delay - Time Adder
Epoxy molded Automatic Vacuum Recloser 0.10~2.00,step:0.01 0.00~1.00,step:0.01Sec 0.00~1.00,step:0.01Sec RDMT(0),RIDMT(1) 0.00~100.00,step:0.01Sec 0(Off),1(On) 50~10000A 0.00~1.00,step:0.01Sec 50~10000A 0.00~1.00,step:0.01Sec 1.0~5.0,step:0.1 No(0),Yes(1) 5~900A 1~58 0.10~2.00,step:0.01 0.00~1.00,step:0.01Sec 0.00~1.00,step:0.01Sec RDMT(0),RIDMT(1) 0.00~100.00,step:0.01Sec 1~58 0.10~2.00,step:0.01 0.00~1.00,step:0.01Sec 0.00~1.00,step:0.01Sec RDMT(0),RIDMT(1) 0.00~100.00,step:0.01Sec 0(Off),1(On) 50~10000A 0.00~1.00,step:0.01Sec 50~10000A 0.00~1.00,step:0.01Sec 1.0~5.0,step:0.1 No(0),Yes(1) 2 - 20A 10~80% 0~345,step:15 DEG
Phase Delay - Min Response Time Phase Delay - Reset Type Phase Delay - Reset Definite Time Phase Definite Time OC - Active Phase Definite Time OC - Pickup Current Phase Definite Time OC - Response Time Phase High Current - Pickup Phase High Current - Response Time Phase - Cold Load Pickup Multiplier Phase - Inrush Restraint Ground - Pickup Current Ground Fast - TCC Type Ground Fast - Time Multiplier Ground Fast - Time Adder Ground Fast - Min Response Time Ground Fast - Reset Type Ground Fast - Reset Definite Time Ground Delay - TCC Type Ground Delay - Time Multiplier Ground Delay - Time Adder Ground Delay - Min Response Time Ground Delay - Reset Type Ground Delay - Reset Definite Time Ground Definite Time OC - Active Ground Definite Time OC - Pickup Current Ground Definite Time OC - Response Time Ground High Current - Pickup Ground High Current - Response Time Ground - Cold Load Pickup Multiplier Ground - Inrush Restraint SEF -Pickup Current(Io) SEF -Pickup Voltage(Vo) SEF -Max. Torque Angle
162 / 163
www.jinkwang.co.kr
ISO 9001 certified 3343 3344 3345 3346 3347 3348 3349 3350 3351 3352 3353 3354 3355 3356 3357 3358 3359 3360 3361 3362 3363 3364 3365 3366 3367 3368 3369 3370 3371 3372 Common Setting 3400 3401 3402 3403 Active setting group Reversed Reserved Reserved SEF -Detection Time SEF -Inrush restraint SEF -Operation Select
Epoxy molded Automatic Vacuum Recloser 0.1~30.0 step:0.1 Sec No(0),Yes(1) 0(Off),Alarm(1),Trip(2) 5~50% 0.02~1.00,step:0.01 0(Off),1(On) 1~5 times 1~5 times 0~5 times 0~5 times 0(OFF), 1~5 times 0(OFF), 1~5 times 0.5~60.0,step:0.1Sec 1~60s 1~60s 1~60s 3~180s 0.00~60.00,step:0.01Sec 0.00~30.00,step:0.01Sec No(0),Yes(1) 50~90,step:5% 35~75,step:5% 0.1~30.0,step:0.1Sec 0(Off),1(On)
Inrush restraint - 2nd harmonic Pickup Inrush restraint - Detection Time Inrush restraint - Operation Select Operation to Lockout Phase Operation to Lockout Ground Operation Fast Curve Phase Operation Fast Curve Ground High Current Phase Active High Current Ground Active Reclose Interval 1
st
Reclose Interval 2nd Reclose Interval 3rd Reclose Interval 4 Reset Time Cold Load Duration Cold Load Pickup Restore Time Sequence Coordination Active Phase Loss - Volt On level Phase Loss - Volt Off level Phase Loss - Detection Time Phase Loss - Operation Select
th
Under Frequency - Frequency Pickup Under Frequency - Detection Time Under Frequency - Operation Select
1~4
163 / 163