Rectier
R48-3200
Key Features
n 3200 watt rectifier designed for -48V DC power applications n Optimized depth reduced footprint allows installation in short-depth racks and cabinets n DSP (Digital Signaling Processor) means fewer components, optimized operation and active load sharing for increased reliability n Compliant with global standards delivers quality, performance and reliability no matter what the application or location demands n High efficiency, up to 92%, reduces power consumption for lower operating costs n Hot pluggable facilitates future extensions n Wide input voltage range operates in the most demanding environments where input voltage changes n Wide temperature operating range (-40C / -40F to +75C / 167F) meets the harshest climatic environment requirements
The reliable and efficient R48-3200 rectifier reduces power consumption, lowering operating cost.
Description
The 3200 watt rectifier (R48-3200) is designed to convert standard AC supply voltages into stable nominal -48V DC voltage that is adjustable to application needs. The R48-3200 is a constant power rectifier designed with the latest patented switch-mode technology using DSP (Digital Signaling Processor) functionality for efficient operation. For a higher load capacity, rectifiers can be connected in parallel, and intelligent control can be added with the help of a separate controller.
2012.09
Rectier R48-3200
Technical Specifications
AC Input Input Voltage, Nominal Input Voltage, Permitted Variation Line Frequency Max Input Current Power Factor THD (Total Harmonic Distortion) DC Output Output Voltage, Adjustment Range Output Power Output Power, Derated for Input Voltage Output Current Output Current Limit Set Point Efficiency Psophometric Noise (system) Temperature Derating Control and Monitoring Rectifier Alarm and Signaling Visual Indications 200 to 250 V AC 85 to 290 V AC 45 to 55 Hz 20A 0.99 <5% from 50 to 100% of rated load
Diagrams
Output Power vs. Temperature 264V Vin 176VAC
% of max output power 120 100 80 60 40 20 0 -40 -20 0 20 40 60 80 100 45 50 55 65 70
Temperature (C)
Alarm and status reported via CAN bus to system controller Green LED: Normal Operation Yellow LED: Alarm Red LED: Failure Flashing Red LED: Fan Failure
Output Voltage (V)
Environmental Temperature Range, Operating Temperature Range, Storage Relative Humidity Altitude EMC Safety Mechanics Dimensions (H x W x D) Weight Other Parts Controller Units
-40 to +75C, -40 to +167F -40 to +75C, -40 to +167F 0 to 95% 2000 m, 6560 ft at full power ETSI EN 300 386 class B, FCC CFR 47 Part 15 class B, Telcordia GR-1089-CORE class B IEC 60950, EN 60950, UL 60950
10 15 20
25 30 35 40
45
50 55
60 65 70
75
Ordering Information
Model Number 1R483200XXX Description Rectifier 48V, 3200W
EmersonNetworkPower.com/EnergySystems (North America) EmersonNetworkPower.eu/EnergySystems (EMEA) Emerson Network Power Energy Systems North America 2012.
Business-Critical Continuity, Emerson Network Power, the Emerson Network Power logo, Emerson and Consider it Solved are service marks and trademarks of Emerson Electric Co. EnergyMaster, eSure, NetPerform, NetReach, NetSpan, NetSure and NetXtend are trademarks of Emerson Network Power Energy Systems North America.