Manual Hardw e

Download as pdf or txt
Download as pdf or txt
You are on page 1of 9

ECOLOG TN2, TN3-P, TN4, TN4-L, TP2, TP4-L,TH1, TH2

1. Product Overview
1.1 Display Large LCD display for measured values and status
Time (except for TN2) Alarm (will stay lit until the alarm is reset) Upper / Lower limit value

Date (except for TN2) Menu blinking indicators

Measured value with unit

Sensor number Alarm indicator for sensor 1.. 4 Figure 1 Communication Battery low ( Hints) Normal operation + Wait = IdLE ( Statuscodes)

F F

1.2 Key Pad

4 keys for datalogger operation (except for TN2 & TN3-P)

Figure 2

1.3 Battery

3.6 Volt lithium battery with extended temperature range. For more information about the operating range of the battery and the battery lifetime see chapter 2, Application and Safety Regulations.

DB15 connector

Battery case

Figure 3 Seite - 10 Getting Started ECOLOG

Position of internal temperature sensor (TN2 & TN3-P only) D-EZ-6002Bd 8. 2000

2. Applications and Safety Regulations


2.1 Operating Temperatures - The loggers can be used in the temperature range between -35 and +55C. However, it becomes increasingly difficult to read the display when the temperature falls below -20C. - Battery self-discharging increases at temperatures exceeding 45C and continuous operation at temperatures above 45C can reduce the serviceable life by approx. 1/3. - Lithium battery passivation, due to long-term use at temperatures above 40C, can result in temporary read problems (self-discharge protection). This can be rectified by repeated evaluation. - Long-term use at low temperatures down to -40C does not present any problems. - We can not guarantee that the logger will always function properly if it is implemented at temperatures below -40C. Experience has shown that the battery freezes at approx. -50C, that it is no longer possible to perform measurements and that the timer tracking function can be temporarily interrupted. To make further operation possible, the logger must be reprogrammed when room temperature is reestablished. - Temperatures exceeding 55C can result in permanent discoloration of the display. - Temperatures exceeding 70C can result in deformation of the housing. - A gas explosion can occur at the lithium battery if temperatures exceeding 100C are reached. 2.2 Exceptional Environmental Conditions Pay attention to the following when loggers are used under exceptional environmental conditions: - UV rays diminish the stability of the housing - IR radiation (warmth) and superheated steam can result in deformation of the housing - A vent hole should be drilled at negative pressures of <0.4 bar abs. - There is a risk that the battery may explode if the logger is used in conjunction with microwaves 2.3 Precautionary Measures for Handling Units with Lithium Batteries - Do not short-circuit batteries: Danger of explosions - Do not throw units which contain batteries into fire: Danger of explosions - Do not subject the batteries to mechanical stress and do not dismantle them. The leaking battery fluid is highly corrosive and lithium can generate severe heat when it comes into contact with moisture or it can ignite fire. - Do not heat up battery-driven units to temperatures exceeding 100C: Danger of explosions - Avoid violent knocks and blows - Follow the manufacturers specifications for battery storage - Return the batteries to the supplier for correct waste disposal 2.4 Maintenance To ensure proper functioning of the logger the following steps should be part of a periodical maintenance plan: - Calibration check, for detailed information see also data sheet ECOLOG D-EZ-2001E - Readout of the data logger and saving the file - Check of the alarm function if used - Battery replacement (Part No 2819; Lithium 3.6V, 1900mAh, AM3/LR6/AA) 2.5 Technical Alterations In the interest of our customers, we reserve the right to perform alterations resulting from subsequent technical developments without any particular notice. For this reason, diagrams, descriptions and the information concerning the scope of delivery are not binding. - This product must be certified with CE - The manufacturer guarantees that this product complies with the relevant recommendations
D-EZ-6002Bd Getting Started ECOLOG Seite - 11 8. 2000

English

3. Mounting Instructions
As accessories ELPRO provides a protective housing made of shock proof plastic material with IP66, Part No. 2350-xx and 3 differenterent brackets for simple fixation of dataloggers. 3.1 Fixation Elements Simple fixation bracket Part No. 2804-A
86 for M3

Figure 4 93

Mounting bracket with DB15 socket fixation Part No. 2804-B

57

DB15 connector Part. No. 3032-xx 3215-xx Figure 5 Padlock to prevent unauthorized removal of the logger

for M4 / M5

93

Mounting bracket with screw terminals and cover Part No. TNx: 2804-C 2804-CR 2804-CRA THx: 2805-CR 2805-CRA

57

for M4 / M5 Terminal box Figure 6

xxxx-CR with additional RS232 connector xxxx-CRA with additional RS232 connector and acoustic alarm
Seite - 12 Getting Started ECOLOG D-EZ-6002Bd 8. 2000

3.2 Pin Assignment and Connection Diagram Wire the DB15 connector for the ECOLOG as shown below:
English

TN2

DB15 connector 8 7 6 5 4 3 2 1 GND TXD NTC2 +Ref Res. Res. +Ref. NTC1 15 14 13 12 11 10 9 RXD Busy Res. Start/Inpos Ubat. Alarm Reset Res.

Connection diagram NTC +Ref NTC - Sensor

Ubat Start/Inpos

Start/Inpos Connector

Ubat Alarm Reset

Alarm Reset Connector

TN3-P

DB15 connector 8 7 6 5 4 3 2 1 GND TXD NTC2 +Ref Res. NTC3 +Ref. NTC1 15 14 13 12 11 10 9 RXD Busy Res. Start/Inpos Ubat. Alarm Reset Alarm

Connection diagram NTC +Ref NTC - Sensor

Ubat Start/Inpos

Start/Inpos Connector

Ubat Alarm Reset

Alarm Reset Connector

TN4 TN4-L

DB15 connector 8 7 6 5 4 3 2 1 GND TXD NTC2 +Ref NTC4 NTC3 +Ref. NTC1 15 14 13 12 11 10 9 RXD Busy Res. DigitIn1 Ubat. DigitIn2 Alarm

Connection diagram NTC +Ref Ubat DigitIn Alarm GND NTC - Sensor

Contact Input

+
0..50VDC max 200mA Alarm Output

TP4-L TP2 (only 2 sensors)

DB15 connector 8 7 6 5 4 3 2 1 GND TXD Ubat A1 A1 B1 B1 B2 15 14 13 12 11 10 9 RXD Busy A2 A2 B2 DigitIn Alarm

LEMO Connector (soldering side)


A A B B

Connection diagram A A B B Ubat DigitIn Alarm GND

PT100 - Sensor

Contact Input

+
0..50VDC max 200mA Alarm Output

TH1 TH2

DB15 connector 8 7 6 5 4 3 2 1 GND TXD +Ref. A1 A2 B1,2 D2 C1,2 15 14 13 12 11 10 9 RXD Busy NTC1 NTC2 D1 DigitIn Alarm

Connection diagram NTC2 +Ref NTC2 - Sensor

+Ref DigitIn Alarm GND

Contact Input

+
0..50VDC max 200mA Alarm Output

D-EZ-6002Bd Getting Started ECOLOG

Seite - 13 8. 2000

4. Operation
4.1 Main Menu
Start (only appears when the logger is in external start/ stop mode and is waiting for the external start signal) Resetting the alarm display (only appears when an alarm display exists) No function (exit menu) THx: Time Stamp marked as D2 TNx: No function (exit menu) TPx: No function (exit menu) Printing the short protocol Scrolling the measured values

Submenu A

Scrolling the alarms Printing the measured values

Submenu B Prints: Backwards starting with displayed measured value Stop: Press menu button

Printing the alarm protocol

Prints: Entire alarm protocol Stop: Switches printer off

Printing the logger status

For TNx only, see also chapter 6.2

Setting the internal clock

Submenu C

LCD display test

OFF ON Alarm output test


Exit menu Error 5, Module does not respond, during data reading - The datalogger is not in the measurement mode - To exit the menu press F1/F3 Seite - 14 Getting Started ECOLOG D-EZ-6002Bd 8. 2000

4.2 Submenu A: Menu for Displaying and Printing Measurement Data

Step size: 1 measurement

1x backward

1x forward

Step size: 10 measurements 10x backward Step size: 100 measurements 100x backward Print data and exit menu

10x forward

100x forward

4.3 Submenu B: Menu for Displaying Alarm Messages

Start of alarm list at last alarm On Step size: 1 change

backward

forward

Corresponds to submenu A

4.4 Submenu C: Menu for Setting Internal Clock and Calendar

Year minus Month Day Hour Minute Load settings and exit menu plus

minus

plus

D-EZ-6002Bd Getting Started ECOLOG

Seite - 15 8. 2000

English

5. Definition of Alarm Parameters


The dataloggers ECOLOG have an alarm indication feature and all models except the TN2 are also equipped with an alarm contact. The alarm parameters are defined in the Setup of Alarm Parameters window. - Alarmindication The alarm indication is independent of the sensor number, but all sensors that may cause an alarm have to be selected in the measurement function. The alarm indication has to be reset manually. It is possible to reset the alarm indication by the PC software, the keyboard or the alarm reset connector. - Alarm contact In case of an alarm indication, the alarm contact is closed (except for a TN2). The alarm contact is independent of the sensor number, but all sensors that may cause an alarm have to be selected in the measurement function.
- Hysteresis is used for controlling external processes (P-Controller) only. Set to 0 for alarm function with time delay - Example: a) Alarmfunction with time delay: Hysteresis = 0C b) Controlfunction for P-Controller: Hysteresis = 1C Overstepping the limit value Hysteresis Limit value Over/Understepping the limit value Measurement values within the limits Understepping the limit value Limit value Hysteresis

Alarm on Alarm Thresholds Hysteresis

By activating this check box, the alarm function is switched on. Data entry field for lower and uper limit values. The switching hysteresis is used to avoid uncontrolled on/off switching of the contact. To move the contact, the measurement value has to differ from the limit value by the value defined in this field. Alarm Delay Time - normal To close the alarm contact, the duration of a measurement value, outside the limit values, has to be longer than the delay time defined in the "normal" data entry field. - defrost on If the "check defrost" function is selected and the defrost contact D1 is closed, then the duration of a measurement value, outside the limit values, has to be longer than the delay time defined in the "defrost on" data entry field. Alarm Output - no selection This mode is used for all applications where the alarm contact is used to control any external devices like a flash light or a telephon dailing unit. The contact will be closed as long as a limit value is exeded. - using CRA bracket This mode is used in combination with a 280x-CRA bracket only. - self-sustaining This mode is used for all applications where the alarm contact is used to control any external devices like a flash light or a telephon dailing unit. The contact will be closed till the alarm is reseted by the user . Close / Download / Print Status These boutons are used to program the logger, to printout the current status of the logger and to close the Setup of Alarm Parameters window. Seite - 16 Getting Started ECOLOG D-EZ-6002Bd 8. 2000

6. Print- and Special- Functions


6.1 Measurement Values
English
ECOLOG TH1 ECOLOG TN1

All dataloggers except TN2 and TN3-P are able to printout complete measurement value tables on a protocol printer. Customer Module Tag

N.C.: No sensor connected

6.2 Alarm- and Status- Information


Dataloggers of the TNx-Family (except TN2 and TN3-P) are printing an alarm or a status protocol, dataloggers of the THx and TPx-Family are printing a combined alarm and status protocol. TNx: Alarm = Prn AIAI Status = Prn StSt THx: Alarm = Prn AlAl Status = Prn AIAI TPx: Alarm = Prn AIAI Status = Prn AIAI

6.3 Function F2 - Time Stamp


All dataloggers of the THx-Family will mark the actual measurement value with a time stamp, as input D2, by pressing F2. Also this time stamp is visible under PC data evaluation as D2 (graphics and table mode).

6.4 Function F3 - Short Protocol


All dataloggers except TN2 are able to printout measurement values in a short protocol (up to 250 values). TN3-P: Printing starts by power up of the printer. At the time of data printing, MarkPos marking in the measurement value table.

6.5 Legend of Markings at the Line End


* a b c = = = = Alarm Input D1 Input D2 Input D1 + D2 A = Alarm and Input D1 B = Alarm and Input D2 C = Alarm and Input D1 + D2 Seite - 17 8. 2000

D-EZ-6002Bd Getting Started ECOLOG

7. Status- and Error-Codes


CAL IdLE Calibration active Datalogger is in Idle-Mode Idle-Mode is reached if the logger is in the Start/Stop mode and the memory is full. Logging has been stopped. For a new logging period, the logger has to be reprogrammed. This is the delivery status of the PT100 loggers TP2 and TP4-L. The calibration parameters of the rH/T sensor are automatically uploaded when the sensor is connected to the logger. Data are printed Battery voltage is too low Error during calibration Datalogger is faulty Error during printing Logger key pad is defective Datalogger is faulty Error during upload of rH/T sensor parameters No sensor is connected Sensor has a short circuit Over flow of measurement value Under flow of measurement value

Ld. Prn b.F. CAL.E. C.F. Err HHHH L.C. Ld.F. n.c. S.C. O.F. U.F.

8. Hints
TNx TH1 & TH2 TP1 & TP2 Battery low Software CD-ROM Battery life-span approx. 2 years Please do not calibrate with 2 connected rH/T sensors Battery life-span approx. 2 years Battery life-span approx. 1.5 years, depending on measurement interval and resolution. This indicator (see page 10) is going to be switched on about 6 month before the battery life ends. Please change the battery at your next possibility. ECOLOG data loggers require an evaluation software of version 2.05 or higher. For more product information please see elproLOG WIN CD-ROM.

9. Measuring Ranges
Temperature TNx and THx with sensor Range -20C.. +50C -50C.. +90C +90C.. +140C Range -100C.. +400C -200C.. -100C +400C.. +500C +500C.. +550C Range 0% rH .. 100% rH Resolution 0.1C 0.2C 0.2C Accuracy 0.2C 0.4C 1C

Temperature PTx without sensor

Resolution max. 0.1C 0.2C 0.1C 0.2C Resolution 0.2% rH Accuracy At room temperature, 23C: 1.5%rH Hysteresis 10-90-10%rH: <1%rH Temp. coefficient: 0.05% rH/C D-EZ-6002Bd 8. 2000

Rel. Humidity THx

Seite - 18 Getting Started ECOLOG

You might also like