Application Note
Megger provide a range of lead sets and clips of different sizes and electrical characteristics for use with Megger 5 kV and 10 kV insulation resistance testers, enabling the user to choose the most applicable lead set for the work in hand. The design of the lead sets is intended to facilitate connection to a variety of de-energised systems for the purpose of making insulation resistance measurements. In all cases it is the responsibility of the user to employ safe working practices and verify that the system is safe before connection. Even electrically isolated systems may exhibit significant capacitance which will become highly charged during the application of the insulation test. This charge can be lethal and connections, including the leads and clips, should never be touched during the test. The system must be safely discharged before touching connections.
Megger test leads designed for the real world Providing Safety, Reliability and Practicality
At Megger we recognise that test leads are a key component of any precision instrument and that safety, long life, and the ability to provide reliable connections to the wide variety of test pieces found in real applications are of utmost importance. Careful design ensures repeatable connections, which are practical and safe to use. Only the best materials and most appropriate materials are used, to provide the essential blend of performance and safety. As an example the careful specification of the cable ensures it remains flexible in all conditions and has extremely good insulation properties which will not effect the measurements made. Megger uses only the best quality double insulated silicon cable; the inner insulation is specifically manufactured in a different colour to the outer sheath so to instantly highlight any damaged areas; a factor important not just for reliable measurements but safety too.
All of the lead sets in this application note are suitable for use with all current Megger 5 kV and 10 kV insulation resistance testers.
Using an insulation tester with poor or electrically leaky test leads can provide misleading measurements and may result in perfectly good insulation being diagnosed faulty, wasting both time and money on unnecessary repairs. This is especially so when using long test leads.
Megger test clip being tested with a IEC standard test finger for creepage and clearance
The electrical test environment in which Megger products are used often poses significant hazards and safety risks to users requiring high levels of training and competence. In these environments application of safe working practices is essential to ensure the safety of both operators and others. At Megger, we take product safety extremely seriously and pride ourselves on our reputation for high quality practical equipment designed to minimise the risk to the user. Whether a complex test instrument or a set of test leads the same rigorous process is employed. Insulation testing in HV, high energy, environments poses a number of unique hazards against which Megger has implemented innovative solutions to provided added protection. These hazards and protective features are summarised below and listed in order of importance:-
with
fully
In addition to the overall insulation requirements of a clip Megger considered the challenge of providing this protection without compromising the usability of the design. An insulated clip is great, but if the added insulation impedes the operation and ability to make reliable connection to the wide variety of bus bars, wires and terminals that are needed the design is useless and the operator may be tempted to remove the additional insulation to make connection. Meggers unique solution has been achieved by the addition of moving jaw covers that flex back when the clip is applied to a test piece. A simple but effective design. Simply align the arrows on the plug finger guard with the padlock symbols on the instrument to lock, and twist 90 to align with the open padlocks to un-lock. In addition, for the same reason, the test clips are not removable from the test lead.
4. Protection from instrument output (5kV or 10kV) Many people fear the electrical output from their insulation tester which may be 5 or 10kV. However, in reality the current available from the instrument is generally limited to a few milliamprers and in itself presents a relatively low hazard. Whilst highly unpleasant a low current shock from an insulation tester will make you jump but under most conditions is only a serious hazard to those with a heart condition or fitted with a pace maker. The hazard here is not so much the output of the instrument but more the working environment. If the connected load is capacitive, a long cable perhaps, this can provide very significant energy when charged to high voltage by the instrument, and could prove lethal if touched. Additionally when testing insulation in many HV environments, it is not uncommon to have to climb ladders to reach connections
Fins
Cable strain relief at both clip and plug designed to withstand 5000 flexes with 10N pull force applied
TEST LEADS AVAILABLE FOR MEGGER 5kV AND 10kV INSULATION TESTERS
Cable details: Lead lengths available: 3 m, 10 m and 15 m Insulation rating: 12 kV d.c. (Marked on cable) Cable type: Flexible dual insulated silicon (inner insulation layer coloured white to highlight damage) Application notes: These clips are designed for clamping on larger diameter test pieces but where space is at a premium. The insulation is designed only to protect the user from the output of Megger 5 kV and 10 kV (set below 6 kV) insulation resistance testers. Part numbers: 3m (10ft) 5m (16ft) 8m (26ft) 10m (33ft) 15m (50ft) 1002-531 1002-641 1002-642 1002-643 1002-644 The clips cannot in any circumstance be relied on to protect the user from live systems above 600V a.c. in a CATIV environment, or 1000V a.c. in a CATIII environment.
These test leads may also be supplied in none standard lengths to suit a particular application. Please contact Megger for a quotation. Minimum order quantities may apply.
Cable details: Lead lengths available: 3 m, 10 m and 15 m Insulation rating: 12 kV d.c. (Marked on cable) Cable type: Flexible dual insulated silicon (inner insulation layer coloured white to highlight damage)
Application notes: These clips are designed for clamping on larger diameter test pieces. The insulation is designed only to protect the user from the output of Megger 5 kV and 10 kV insulation resistance testers and systems below 600V to the category rating above. The clips cannot in any circumstance be relied on to protect the user from live systems above 600V a.c. in a CATIV environment, or 1000V a.c. in a CATIII environment.
These test leads may also be supplied in none standard lengths to suit a particular application. Please contact Megger for a quotation. Minimum order quantities may apply.
Clip details: Dimensions: 58 (L) X 25 (closed) mm Lead lengths available: 3 m, 10 m and 15 m Jaw opening: 18 mm diameter max Number in set: 3 Double insulation rating: None Basic insulation rating: None CAT rating: Not applicable
Cable details: Lead lengths available: 3 m, 10 m and 15 m Insulation rating: 12 kV d.c. (Marked on cable) Cable type: Flexible dual insulated silicon (inner insulation layer coloured white to highlight damage) Part numbers: 3 m 8m 15 m 8101-181 8101-182 8101-183
Application notes: These clips are designed for clamping on test pieces where access is limited. There is no insulation on these clips. Extreme care must be taken to avoid electric shock when connecting/disconnecting due to the bare metallic clips.
Clip details: Dimensions: 58 (L) X 25 (closed) mm Jaw opening: 20 mm dia max (clip) Number in set: 2 Double insulation rating: 1 kV d.c. CAT Rating: 600V a.c. CATIII
Probe details: Number in set: 2 Double insulation rating: 1 kV d.c. CAT Rating: 600V a.c. CATIV
Cable details: Lead length: 3 m Insulation rating: 1 kV d.c. Cable type: Flexible double insulated silicon (inner insulation layer coloured white to highlight damage
Application notes: These clips are designed for testing low voltage circuits with test voltages up to 1 kV. The insulation is designed only to protect the user from the output of Megger 5 kV and 10 kV insulation resistance testers set to a maximum output voltage of 1 kV. Do not use this lead set at voltages above 1 kV.
Large
Medium
Compact
Control circuit
Large
Medium
Compact
Control circuit
Clip details: Dimensions: 90 (L) X 41 (closed) mm Jaw opening: 20 mm dia max (clip) Number in set: 2 Double insulation rating: 1 kV d.c. CAT Rating: 600V a.c. CATIV
The clips cannot in any circumstance be relied on to protect the user from live systems above 600V a.c. in a CATIV environment, or 1000V a.c. in a CATIII environment. It is important to check fuse continuity before and after a test
Probe details: Number in set: 2 Double insulation rating: 1 kV d.c. CAT Rating: 600V a.c. CATIV
Cable details: Lead length: 1.25 m Insulation rating: 1 kV d.c. Cable type: Flexible double insulated silicon (inner insulation layer coloured white to highlight damage Fuse rating: FF500mA 50 kA see notes below Part number: 1002-913
Application notes: This fused probe and clip leadset is designed for testing low voltage circuits with test voltages up to 1 kV. The leadset is GS38 compliant, fitted with FF500mA 50 kA fuses, which allows voltage measurements to be made in safety when using the user selectable voltage measuring range on the MIT515, MIT525 and MIT1025 instruments. These clips are designed for testing low voltage circuits with test voltages up to 1 kV. The insulation is designed only to protect the user from the output of Megger 5 kV and 10 kV insulation resistance testers up to a maximum instrument test voltage of 1 kV.
Clip details Dimensions: 58 (L) X 25 (closed) mm Jaw opening: 18 mm diameter max Number in set: 3 Double insulation rating: None Basic insulation rating: None CAT rating: Not applicable
Application notes:
The test clips are designed for clamping on test pieces where access is limited. There is no insulation on these clips. Extreme care must be taken to avoid electric shock when connecting/disconnecting due to the bare metallic clips. The screened test lead set consists of: A black/negative test lead that has been screened. The screen is connected to the guard terminal of the instrument and terminated with a bare clip. A red/positive test lead that is not screened. Normal practice means that the positive lead is connected to ground (usually to limit the effects of electro-endosmosis), meaning any induced noise current goes straight to earth and not into the instrument.
Cable details: Lead lengths available: 5 kV rated 3 m, 15 m 10 kV rated 3m, 10m, 15m Insulation rating: 5kv or 10 kV d.c. Cable type: Flexible screened PVC Part numbers: 5 kV 5 kV 10 kV 10 kV 10 kV 3m 15 m 3m 10m 15m 6220-835 6311-080 6220-834 6220-861 6220-833
Screened cable
Screened cable running down the side of a transformer to the insulation tester.
Guard lead connected to remove the effects of leakage (In this case winding to transformer case measuring between windings)
Screened test leads are an important accessory for those working in high noise environments, and/or locations where test lead leakage could be a problem.
Clip type
lead
lead
Compact clip
6220-835
6311-080
6220-834
6220-861
6220-833
3m (10ft), BARE COMPACT clip, 5 kV SCREENED black lead, 3 clips, 2 leads 15m (50ft), BARE COMPACT clip, 5 kV SCREENED black lead, 3 clips, 2 leads 3m (10ft), BARE COMPACT clip, 10 kV SCREENED black lead, 3 clips, 2 leads 10m (33ft), BARE COMPACT clip, 10 kV SCREENED black lead, 3 clips, 2 leads 15m (50ft), BARE COMPACT clip, 10 kV SCREENED black lead, 3 clips, 2 leads
6220-822
3m (10ft), 1kV insulated probe and clip set for CONTROL CIRCUIT TESTING, set of 2
1002-913
1.25m (4ft) 1kV insulated FUSED probe and clip set for <1 kV voltage measurements, set of 2.
Application Note
* These test leads may also be supplied in non-standard lead lengths to suit a particular
= Optional
= Supplied as standard
application / requirement. Please contact Megger for a quotation, minimum order quatities may apply
The circuit under test must be switched off, de-energised, isolated and checked to be safe before insulation test connections are made. Make sure the circuit is not reenergised whilst the instrument is connected. Circuit connections must not be touched during an insulation test. After completing a test, capacitive circuits must be completely discharged before disconnecting the test leads. Capacitive charges can be lethal. Tested items should be firmly shorted out with a shorting link, after discharge, until required for use. This is to guard against any stored dielectric absorption charge subsequently being released thereby raising the voltage to potentially dangerous levels. Test leads, including crocodile clips, must be in good order, clean, dry and with no broken or cracked insulation. The lead set should not be used if any part of it is damaged. These accessories are not designed to provide full levels of safety isolation to the operator if touched. The required physical dimensions would render this impractical. Safe working practices must be used. All safety warnings in the instruments user guide must be fully read and observed during use.
UK Archcliffe Road Dover CT17 9EN England T +44 (0) 1304 502101 F +44 (0) 1304 207342 [email protected]
UNITED STATES 4271 Bronze Way Dallas TX 75237-1019 USA T 800 723 2861 (USA only) T +1 214 333 3201 F +1 214 331 7399 [email protected]
OTHER TECHNICAL SALES OFFICES Valley Forge USA, College Station USA, Sydney AUSTRALIA, Tby SWEDEN, Ontario CANADA, Trappes FRANCE, Oberursel GERMANY, Aargau SWITZERLAND, Kingdom of BAHRAIN, Mumbai INDIA, Johannesburg SOUTH AFRICA, Chonburi THAILAND, Malaga SPAIN
CERTIFICATION ISO Registered to ISO 9001:2008 Cert. no. Q 09250 Registered to ISO 14001-2004 Cert. no. EMS 61597
5kV_10kV_test_lead_AN_en_V01 www.megger.com
Megger is a registered trademark