Current protection
Relay
INGEPACTM PL70 offers protection for a wide variety of applications. The PL70 family offers the most characteristic protection functions applicable to electric systems, economic and simple equipments. Apart from the main protection and automation functions (overcurrent, voltage, breaker failure, frequency, phase shift, eld loss, autoreclose, synchrocheck), these devices offer a series of additional functions, such as communications, event recording, logic programming, breaker monitoring, etc., making of these machines an economic alternative for the automation of electric systems.
1 74TC 74CC
52
24
79 3
51V
50
51
46
50BF
67IN
67N
37 1
50R
51R
46BC
49
TANK
50G
51G
50N
51N
50SN
51SN
50G
51G
87G
Software
All of the equipment in the INGEPACTM family can be accessed using powerful software tools developed by Ingeteam and which run on Windows. Application software is specically designed for simple and user-friendly access to the equipment.
Protection functions 50/51, 50/51N Three-phase and earth overcurrent 67N Directional neutral overcurrent 50/51SN Sensitive neutral detection 46 Reverse sequence overcurrent (unbalance) 46BC Broken conductor 67N Directional isolated neutral overcurrent 50/51R Residual overcurrent 37 Minimum current 49 Thermal image 51V Voltage controlled overcurrent 50BF Breaker failure 87N Restricted earth protection 24 Overexcitation
End fault protection Cold load pickup Other functions 79 Recloser Breaker monitoring 74TC/CC trip and close circuit supervision Openings, closures, kI2 counter Excessive number of trips alarm Command failure Pulse opening/closure command or change of status detection (latch) Flashover Data Acquisition Functions Measurements historical report (maximum/ minimum) Event, fault and oscillographic recorder
Current measurement (fundamental and sequences), voltage and power measurement, demand maximeter Digital inputs and outputs Communications DB9 RS232 PROCOME protocol front port Up to 2 rear ports: RS232, RS485, Glass Fibre Optic, Plastic Fibre Optic, Ethernet PROCOME, Modbus, DNP 3.0, IEC60870-5101 protocols Synchronisation Via communications protocol or via demodulated IRIG-B input. Local interface Keypad + local display (2 rows x 8 characters)
General Description
Main Features
Insulation and Electromagnetic Tests
Dielectric strength IEC 60255-5 Insulation resistance IEC 60255-5 Impulse voltage IEC 60255-5 DC power supply terminal conducted radiolectrical emissions measurement IEC 60255-25/ EN55022 Radiated radioelectrical emission measurement IEC 60255-5/ EN55022/EN5511 Electrostatic discharge immunity test IEC 61000-4-2 Immunity to radiofrequency-radiated elds ENV 50204/ IEC 61000-4-3 Electrical fast transients immunity test IEC 61000-4-4 Surge pulses immunity test IEC 61000-4-5 Immunity to radiofrequency induced signals IEC 61000-4-6 Damped oscillatory wave immunity test IEC 61000-4-12 1 MHz damped wave immunity test IEC 60255-22-1 Immunity to interruptions, dips and variations in DC power supply IEC 61000-4-29/ IEC 60255-11 Immunity to 50Hz magnetic elds IEC 61000-4-8 Immunity to industrial frequencies IEC 60255-22-7 Surge Withstand capability test IEEE C37.90-1
Options
Connections Connector for pin or ring type terminals Field interfaces
Conguration 0 1 2 Digital inputs 2 8 7 Digital outputs 6 11 11 IRIG-B Others
Climatic
Cold low temperature test Dry heat test Humid heat continuous test Thermal shock
Mechanical
Power supply; 12 Vcc; 24/48 Vcc; 125/220 Vcc; 220 Vca Power supply voltage measurement Communications ports All of the pieces of equipment have a front RS232 port for local access and additionally: 1 serial; 2 serial; 1 serial + 1 Ethernet Communication ports connection types: Serial: RS232, RS485, Glass Fibre Optic, Plastic Fibre Optic Ethernet: RJ45 IP54 front lid Models by protection functions: PL70IT (3xI phases + 1xI neutral): 50/51, 50/51N, 50/51R, 46, 46FA, 37, 50FI, 79, Cold load, 74TC/ CC PL70IS (3xI phases + 1xI neutral): 50/51, 50/51N, 50/51R, 46, 46FA, 37, 50FI, 79, Cold load, 74TC/ CC PL70IA (1xI + 1xV): 67NA, 74TC/CC PL70ID (1xI + 1xV): 67N, 50FI, 74TC/CC PL70IP (3xI phases + 1xI neutral): 50/51, 50/51N, 50/51R, 49, 46, 46FA,87N, 74TC/CC PL70IM (1xI): 50/51, 49, 50FI, 74TC/CC PL70FI (3xI phases + 1xI neutral): 50FI (mono/three-pole), Flashover (by current measurement), End fault, 74TC/CC PL70IV (3xI phases + 1xV): 50/51, 50/51R, 49, 46, 46FA, 51V, 50FI, 74TC/CC
Applications
Protection for feeders with or without autoreclose Motor protection Backup protection for transformers Electric machines earthing protection Breaker protection Isolated neutral grids earthing protection
The technical data in this catalogue is subject to change without prior notice. FY03IPTT01_A
Wide variety of protection functions in models designed for specic applications Intuitive conguration and monitoring software supplied with the equipment. It does not require a previous conguration to communicate with the equipment. User-dened logic signals Digital inputs and outputs and programmable LED indicators Serial and Ethernet communication Real time monitoring and recording of the parameters of the breaker Events and faults recording Automatic reclosing functions 4 setting groups for the automatic adaptation of the relays programming to the grid conditions. Synchronisation via demodulated IRIG-B or global reference through communication protocols UL Certicate