Technical Specification of Transformer Oil
Technical Specification of Transformer Oil
Technical Specification of Transformer Oil
TECHNICAL SPECIFICATIONS
FOR
SPECIAL INSTRUCTIONS TO BIDDER Please read following instructions carefully before submitting your bid.
1. All the drawings, i.e. elevation, side view, plan, cross sectional view etc., in AutoCAD format and manuals in PDF format, for offered item shall be submitted. Also the hard copies as per specification shall be submitted. The bidder shall submit Quality Assurance Plan for manufacturing process and Field Quality Plan with the technical bid. The bidder shall have to submit all the required type test reports for the offered item. However, in the event of partial submission or reports older than specified limit, bidder must submit his confirmation for those type test report/s to be submitted in the event of an order, without affecting delivery schedule, before commencement of supply, free of cost. In absence of this confirmation, the evaluation shall be carried out accordingly as non submission of type test reports. The bidder must fill up all the point of GTP for offered item/s. Instead of indicating refer drawing, or as per IS/IEC, the exact value/s must be filled in. All the points other than GTP, which are asked to confirm in technical specifications must be submitted separately with the bid. The bidder is required to impart training in view of manufacture, assembly, erection, operation and maintenance for offered item, at his works, to the person/s identified by GETCO, in the event of an order, free of cost. The cost of logistics will be bear by GETCO. Please note that the evaluation will be carried out on the strength of content of bid only. No further correspondence will be made. The bidder shall bring out all the technical deviation/s only at the specified annexure. The bidder should indicate manufacturing capacity by submitting latest updated certificate of a Chartered Engineer (CE).
2. 3.
4. 5. 6.
7.
8. 9.
of certain metals used in transformer. There should be no significant quantity of furanic compounds detected in new oil. The oil shall have ability to resist transient voltage stresses caused by lightning strokes and high voltage switching surges. Good oxidation stability is principal requirement for longer service life of oil. It shall not contain detectable amounts of polychlorinated biphenyls. The specification of oil shall be as per Annexure - A attached with this specification. 5.0 TESTS: The test reports for the all the tests listed in Annexure - A shall be submitted with technical bid to justify technical particulars guaranteed by supplier. Type Test Certificates shall be of accredited laboratory (accredited based on ISO/IEC Guide 25 / 17025 or EN 45001 by the National accredition body of the country where laboratory is located), as per IEC / IS / technical specification. The type test reports shall not be older than FIVE years and shall be valid up to expiry of validity of offer. However, supplier shall carry out following tests at NABL approved laboratory on the samples selected from the each lot offered for inspection, in presence of GETCO representative, as listed in Annexure A, before dispatch. All the test reports shall be complied and submitted to GETCO for approval for dispatch clearance in spiral bound volume for each offered lot. Also, the same shall be sent to each consignee after dispatch clearance is issued. 6.0 QAP & FQP: QUALITY ASSURANCE PLAN: The bidder shall invariably furnish following information's along with his offer, failing which his offer shall be liable for rejection. Information shall be separately given for individual type of equipments offered. 1. QAP for incoming material, in process and final checks and testing. 2. Statement giving list of important raw materials, names of sub suppliers for the raw materials, list of standard according to which the raw materials are tested. List of tests normally carried out on raw materials in presence of bidder's representatives, copies of test certificates. 3. Information and copies of test certificates as in (i) above in respect of bought out accessories. 4. List of manufacturing facilities available. 5. Level of automation achieved and list of areas where manual processing exists. 6. List of areas in manufacturing process, where stage inspections are normally carried out for quality control and details of such tests and inspections. 7. Special features provided in the equipment to make it maintenance free.
8. List of testing equipments available with the supplier for final testing of transformer specified and test plant limitation, if any, for the special acceptance and routine tests specified in the relevant standards. These limitations shall be very clearly brought out in 'The schedule of divinations' for specified test requirements. Field Quality Plan shall be submitted with the technical bid. 7.0 PACKING & DISPATCH: Special care shall be taken during packing of oil for dispatch. The oil shall be supplied in grade-B, new steel drum/barrels conformity to IS: 1783 (latest) on non refundable basis. The capacity of steel barrels shall be 209 / 210 liters. Each barrel shall carry markings viz., IS:335, suppliers designation, classification, lot no. with date of manufacturing, quantity of oil, GETCO order No. and date, and special instruction for handling, etc. All the oil filled steel barrels shall be properly sealed for any in grease of moisture or contamination such that the oil is delivered free from moisture or any contamination by maintaining uniform quality at user end. Any incident of deterioration of properties at user end is noticed, then it will be at discretion of GETCO, to reject whole/part of supply delivered so far. Each oil delivery shall be accompanied by the documents specifying suppliers designation, oil classification, GETCO order no., and compliance certificate. Quantity verification: From the lot received by consignee, duly verified and checked by GETCO representative, sample will be selected randomly as per IEC 60475 and Gross weight of said drum/barrel will be done. The net weight of oil will be worked out after deducting the tare weight of the drum. Quantity in liters will be work out after considering density of oil at temperature of weighing. The shortages of oil, if any, found during verification will be applicable to whole lot on prorate basis and amount of shortage such arrived will be deducted from bills of the supplier. 8.0 GUARANTEED TECHNICAL PARTICULARS: (to be filled in and submitted with technical bid)
Sr. No. 1 Appearance Characteristics of Transformer Oil
2 3 4
(Closed)
Interfacial Newton/M
tension
at
27
6 7
Pour point Neutralization value a) (Total acidity) mg. (Max) b) Inorganic Acidity/alkalinity
Electric Strength (Break down voltage) a) New Unfiltered Oil b) After filtration
10
11
12
13
Oxidation Stability a) Neutralization value after Oxidation b) Total sludge after oxidation Ageing Characteristics after 96 Hrs accelerated ageing (Open beaker catalyst) a) Specific (Resistivity) 1) @ 27 0C 2) @ 90 0C b) Dielectric Dissipation Factor (Tan delta) @ 90 0C c) Total acidity d) Total sludge value Resistance method with copper
14 15
APPENDIX A
SPECIFICATION OF TRANSFORMER OIL AS IS:335
Sr. No. 1 Appearance Characteristics of Transformer Oil Requirement As per IS 335:1993 The oil shall be clear transparent & free from suspended matter of sediments. 2 3 4 Density, at 29.5 0C, gm/Cm3 Kinematics Viscosity CST at 27 0C Flash (Closed) 5 Interfacial Newton/M 6 7 Pour point Neutralization value c) (Total acidity) mg. (Max) d) Inorganic Acidity/alkalinity 8 Corrosive Sulphur (In terms of classification of copper strips) 9 Electric Strength (Break down voltage) c) New Unfiltered Oil d) After filteration 10 Dielectric Dissipation Factor (Tan delta) at 90 0C 11 Specific Resistance ( Resistively) c) @ 90 0C d) @ 27 0C 12 35 x1012 Ohm-cm (Min.) 1500 x1012 Ohm-cm (Min.) 0.002 Max. 30 kV Min. (rms) 60 kV Min. (rms) 0.03 mg KOH/gm Max. Nil Non corrosive (- 6) 0C Max. tension at 27
0
point
C 0.04 Min.
Oxidation Stability c) Neutralization value after 0.40 mg/ KOH/ gm Max. Oxidation d) Total sludge after oxidation 0.10% by weight max.
Sr. No. 13
Characteristics of Transformer Oil Ageing Characteristics after 96 Hrs accelerated ageing (Open beaker catalyst) e) Specific (Resistivity) 1) @ 27 0C 2) @ 90 0C f) Dielectric Dissipation Factor (Tan delta) @ 90 C g) Total acidity h) Total sludge value
0
Requirement
method
with
copper
Resistance 2.5 X 1012 Ohm-cm-Min. 0.2 X 1012 Ohm-cm min. 0.2 Max. 0.05 mg KOH/gm Max. 0.05 % by weight Max. The oil shall not contain anti oxidant additives.
14
15
50 PPM Max.
SIGNATURE OF BIDDER