Split Air Conditioner Wall Mounted Type Service Manual: AUS-07C (H) 53R010Lx AUS-07C (H) 53R150Lx AUS-09C (H) 53R150Lx

Download as pdf or txt
Download as pdf or txt
You are on page 1of 42

Split air conditioner Wall mounted Type Service manual

AUS-07C(H)53R010Lx AUS-07C(H)53R150Lx AUS-09C(H)53R150Lx AUS-09C(H)53R010Lx AUS-12C(H)53R150Lx AUS-12C(H)53R130Lx (X=1,2,3,4,5,6,14,15,16,........)

CONTENTS
Contents Safety precautions Installation
Block diagram Trouble shooting Fault diagnosis by symptom Control specification To disassemble mechanical parts Exploded views and parts list Wiring diagrams
1 2 2 11 12 13 17 21 25 39

SAFETY PRECAUTIONS
The following safety precautions must be taken when using your air conditioner.
1. Warning: Prior to repair, disconnect the power cord. 2. Use proper parts: use only exact replacement parts. (Also, we recommend replacing parts rather than repairing them.) 3. Use the proper tools: use the proper tools and test equipment, and know how to use them. Using defective tools or test equipment may cause problems later-intermittent contact, for example. 4. Power cord: prior to repair, check the power cord and replace it if necessary. 5. Avoid using an extension cord, and avoid tapping into a power cord. This practice may result in malfunction or fire. 6. After completing repairs and reassembly, check the insulation resistance. Procedure: prior to applying power, measure the resistance between the power cord and the ground terminal. The resistance must be greater than 30 megohms. 7. Make sure that the grounds are adequate. 8. Make sure that the installation conditions are satisfactory. Relocate the unit if necessary. 9. Keep children away from the unit while it is being repaired. 10. Be sure to clean the unit and its surrounding area.

INSTALLATION
Selecting area for installation
Select an area for installation that is suitable to the customers needs.

1 Location of indoor unit


Keep the air inlet and outlet at a far distance from the blockage. Keep the height distance between the indoor and outdoor unit at most 5m. Mount on the wall solid enough to bear the weight of the unit and not cause any shake. Avoid direct sunshine. A place easy for condensate drain and easy for connecting with the outdoor unit. Keep a far distance away from the fluorescent lamp, it may influence the operation of remote controller. Keep at least 1m away from the TV radio and other home appliances.

2 Location of outdoor unit


A place solid enough to bear the weight of the unit and not cause any shake. Good ventilation, less dust, far from direct rain and sunshine. A place where the air discharged out of the outdoor unit or the operation noise will not annoy your neighbours. No blockage near the outdoor unit. Avoid places close to inflammable gas leakage.

Caution:
It is harmful to the air conditioner if it is used in the following environments: greasy areas (including area near machines). Salty area such as coastal areas, areas where sulfuric gas is present such as hot spring areas. Contact your dealer for advice.

INSTALLATION
Installation diagram of indoor unit and outdoor unit
Confirm the installation position by the mark of the indoor mounting plate.

or
above 105m m

above

155mm
above 250mm

or

or

The copper pipe can be led from back, right, underside, or left-back side.

Notice: do not elevate the drain hose.

Above 20mm

back right

front

left back Underside Left-back

While installing the pipeline on the thin armor plate or on the wall of metal mesh, you should use the wooden board to clamp between the wall and the pipeline, or wrap up the pipeline with 7-8 layers of insulating plastic tape.

Cover connecting pipe with adiabatic material.

Sponge plastic adiabatic material with the thickness of 8mm.

abov

above 500mm

e 30

0mm

m m 0 30 m em 0v o 0 b 1 a

abo

ve 5

00m

abo

ve 5

00m

INSTALLATION
1 Securing the mounting plate and drill on the wall
Secure the mounting plate The mounting plate should be attached to the structural part of wall (post etc).
fasten string at the central hole
Fasten string at the central hole

at least 250mm 455mm or more from sidewall

at least 250mm at least 24mm mounting plate


Tapping screw ST4 25(5)

105mm or more from sidewall

155mm or more from sidewall

105mm or more from sidewall

plumb

Tapping screw ST4 25(5)

plumb mounting plate

NOTICE:

The holes at solid arrow position must be secured to avoid the shake of mounting plate. When the expansion bolts are used, two holes ( 11 20 or 11 26 ) that the distance between them is 450mm should be adopted.

Drill on the wall


40mm

fasten string at the central hole


105mm

plumb

45mm Center of hole( 65mm)

Center of hole( 65mm)

NOTICE:

Confirm the position of holes, and drill holes on the wall.


fasten string at the central hole at least 250mm
fasten string at the central hole 440mm 440mm at least250mm at least 120mm 230mm 90mm Pipe hole

at least 140mm

at least 180mm

at least 120mm

40mm

Center of hole( 65mm)

plumb

120mm

Pipe hole Center of hole( 65mm)

90mm

plumb

NOTICE:
The holes at solid arrow position must be secured to avoid the shake of mounting plate. When the expansion bolts are used, two holes ( 11 20 or 11 26 ) that the distance between them is 450mm should be adopted. Confirm the position of holes, and drill holes on the wall.

INSTALLATION
2 Wiring
Open the front grille; Remove the screw from electrical box cover, pull the Screw electrical box cover away from the unit and set aside. Remove the screw from fastener, pull the fastener away from the unit and set aside. Connect the cable. Indoor unit terminal Replace the fastener and electrical box cover. Diagram

Connecting cable

NOTE:
The appliance shall be installed in accordance with national wiring regulations. The appliance must not be installed in the laundry. The appliance must be installed 2.3m above the floor. The appliance must be positioned so that the plug is accessible. For some models whose cooling capacity are above 4600W (17000BTU/h), an all-pole disconnection device which has at least 3mm separation distance in all pole and a residual current device(RCD)with the rating of above 10mA shall be incorporated in the fixed wiring according to the national rule.

3 Installation of the drain hose


NOTE:
The drain hose must be arranged beneath the copper pipe. The drain hose must not be hunched or twisted. While wrapping up the drain hose, do not pull it. The drain hose through the room must be wrapped up by the thermal insulation materials. The copper pipe and the drain hose must be wrapped up by felt strip. Adiabatic pad should be used at where the pipe contacts the wall. Liquid pipe Drain hose Adiabatic underlay felt gaspipe

ROUTE OF PIPE
If pipe comes out of the right side of the indoor unit, cut part 1 of the unit; If pipe comes out of the lower-right side of the indoor unit, cut part 2 of the unit; If pipe comes out of the left side of the indoor unit, cut part 3 of the unit.

1 2

REFIT OF DRAIN HOSE


If pipe comes out of the left side of the indoor unit, the drain hose must be refitted, otherwise water leakage may occur. Refit methods: Interchange the position of drain hose and drain rubber plug. Clearance is not allowed after refit, it would lead to water leakage.

drain hose

Drain rubber plug

INSTALLATION
Arrangement of the drain hose
To drain the condensate water easily, the drain hose should be declined downwards. The following 5 arrangement methods are incorrect. Decline downward Water leak (Fig. 1) (Fig. 2) Decline downward Water leak (Fig. 3) Standing water air Water leak (Fig. 4)
(Fig. 5)

Dip hose into water

50mm or less above floor

If you find the drain hose not long enough to connect with the indoor unit, you can extend it with the hoses in the accessory box. The drain hose through the room must be wrapped up with the special adiabatic material.

Drain hose

Hose(ID 15cm) PVC hard

4 Installation of the indoor unit


Let pipe go through the wall hole and attach the indoor unit to the mounting plate.(Press the rib of indoor unit inside the hook of the mounting plate.)

Indoor unit the mounting plate Bottom the rib of indoor unit

5 Pipe Connection
The number of bent position of the pipe in the indoor unit should not exceed 10. The number of bent position of the pipe in the indoor unit and the outdoor unit should not exceed 15. The radius of bent position should be more than 10cm. Please break the evaporator craft tube with pincers before connecting. After exhausting the inside air, use the wrench to twist down the nut of connecting tube of the evaporator. Put some seal oil to cover the joint and the flare. Align the centre of joint in line with that of flare and tighten the nut of connecting pipe with wrench. Attention: Do not exhaust the inside air just by loosing the nut since there is the air of certain pressure inside the tube of indoor unit. Please do not make extra effort for fear of damaging the flare.
DIAMETER OF PIPE 6.35mm ( 1/4 ) 9.52mm ( 3/8 ) 12.7mm ( 1/2 ) 15.88mm ( 5/8 ) TORQUE(N m) 13.7---17.6 34.3---41.2 49.0---56.4 73.0---78.0
Evaporator craft tube

6 Wall sealing and Pipe fastening


Use putty to seal the wall hole. Use clamp (pipe fastener) to secure the pipe at specified position.
seal with putty secure the connecting pipe with clamp get rid of unwanted part clamp

Indoor unit

screw

INSTALLATION
Installation diagram of indoor unit and outdoor unit

1 Wiring
Outdoor unit terminal
Connecting cable

Outdoor unit terminal


Connecting cable

or

Wiring For Above 6000W Model (Above 21000BTU/h Model)


1 Remove the self-tapping screws (2 pcs) on the maintenance board and take out the maintenance board. The cable wire can be led from the back hole of the piping hole or ejecting hole. Please utilize outdoor pipe support when the cable wire is led from the backside.

Terminal board Fix the cable wire with anchor cable Maintenance board Piping cover 2 Loosen the self-tapping screws (2 pcs) on the fixing clip to loosen the fixing clip. 3 Loosen the fixing screw of the wire terminal board, pass the power wire and signal wire through the fixing clip. Then firmly fix the power wire and signal wire on the terminal board with the fixing screw. (Earth wire must be connected firmly.)

Outdoor pipe support (Outdoor pipe support is not required when leading the cable wire from other places). 4 Tighten the self-tapping screw on the fixing clip. 5 Install the maintenance board. After the pipes and cable wire are installed, please seal the sponge block as per drawing indication.

Maintenance board

Back wiring

Piping cover
Right wiring Piping cover Ejecting hole

Sponge

INSTALLATION
Notice:
If the signal wire has to be bought separately, choose electric wire above 0.75mm. If the interconnection cord for power supply has to be replaced, please see the following table for reference.
2

MODEL 2700W(10000BTU/h) 3000W(11000BTU/h) -4000W(15000BTU/h) 4500W(18000BTU/h) -8000W(28000BTU/h)

SPECS (Interconnection cord) 1.0mm 1.5mm 2.5mm


2 2 2

WARNING:
Please take the electric circuit diagram attached to the indoor/outdoor units as major reference while installing. The power wire and signal wire between the indoor/outdoor units must be connected one by one as per corresponding number on the wiring terminal board. The connecting cables must be clipped together. Special cable must be used to connect indoor unit and outdoor unit. It should be ensured that the terminals are not influenced by external force. Poor connection may cause fire. The electric box cover must be mounted and secured in position, otherwise fire or electrical shock may occur because of dust or moisture. The temperature of refrigerant circuit will be high, please keep the interconnection cable away from the copper tube. All the models shall be connected with the mains which has system impedance limitations. While installing the unit, please see the following table for impedance information or consult with the supply authority. R410A series 3500W (12000BTU/h) 5100W (18000BTU/h) 6800W (18000BTU/h) 0.219 0.186 0.124

INSTALLATION
2 Installation of the drain joint(only for heat pump type)
Insert the outdoor double-channel drain joint in one of the bottom holes of the suitable size then connect drain hose and joint together. Bottom Double-channel drain joint

Drain hose

3 Joint of the connecting pipe


Put some seal oil to cover the joint and the flare. Align the centre of joint in line with that of flare and tighten the nut of connecting pipe with wrench. ( Adjust the torque by the same method of connecting pipe for indoor unit.)

4 Air exhausting
Screw down the cap of both gas shut-off valve and liquid shut-off valve as well as the nut of service port. Use Allen wrench to turn the valve cork of liquid side at 90 counter-clockwise, and close it after 10 seconds. Use soapy water to check the gas leakage especially at all joint. If there is no gas leakage, please turn the valve cork of liquid side at 90 counter-clockwise again. Press the cork of service port at gas shut-off valve, 10 seconds later, when you see foggy gas discharged, that means inner air is exhausted out. Use Allen wrench to turn the valve cork of both liquid shut-off valve and gas shut-off valve counter-clockwise until they are completely open and then replace the valve caps and tighten them.
liquid connecting pipe liquid shut-off valve allen wrench gas connecting pipe valve nuts service port service port cap

gas shut-off valve

5 Process of flared tube


Use the pipe cutter to cut off the broken part of flare. Remove burrs at the cut of the flare. Insert a nut into the connecting pipe and do flaring with specified flaring tools, reamers for example. Remove burrs at the cut of the flare.
Copper pipe 90 Oblique Roughness Burr

Burr
A(mm) 2.0--2.5 3.0--3.5 3.5--4.0

Reamer

Outer diameter 6.35mm ( 1/4 )


9.52mm ( 3/8 ) 12.7mm ( 1/2 ) 15.88mm(5/8 )

4.0--4.5

Check the quality of flaring technique.

INSTALLATION
6 Adding refrigerant
If the connecting pipe is longer than 7 metres, add refrigerant as needed. (Cool only type) added amount A=(Lm-7m) 15g/m ; (Heat pump type)added amount A= (Lm-7m) of added refrigerant, L: the length of connecting pipe) 50g/m. ( A: amount

The length of connecting pipe (m) (Cool only type)added amount (g) (Heat pump type)added amount (g)

7 0 0

8 15 50

9 30 100

10 45 150

Exhaust the air as the above-mentioned method. Screw the gas shut-off valve to close, connect charging hose(low pressure) to the service valve and then open gas shut-off valve again. Set the unit to cool operation mode. Connect the refrigerant bottle to the charging hose and then convert it. Fill in liquid refrigerant as the above table. Stop operation of the air conditioner. Disconnect the manifold gauge after turning off the shut-off valve, and then open gas shut-off valve again. Tighten nuts and caps of each valve.

Manifold gauge Low pressure valve

Pressure meter High pressure valve

Charging line

Service port

7 Relocation of the air conditioner.


Refer to this procedure when the unit is relocated. 1. Carry out the pump down procedure. 2. Remove the power cord. 3. Disconnect the assembly cable from the indoor and outdoor units. 4. Remove the flare nut connecting the indoor unit and the pipe. At this time, cover the pipe of the indoor unit and the other pipe using a cap or vinyl plug to avoid foreign material entering. 5. Disconnect the pipe connected to the outdoor unit. 6. Make sure you do not bend the connection pipes in the middle and store together with the cables. 7. Move the indoor and outdoor units to a new location. 8. Remove the mounting plate for the indoor unit and move it to a new location.

10

INSTALLATION
8 Operation test
Before test operation, wiring safety inspection must be carried out carefully again. 1. Emergency switch operation: Every press of emergency switch, the air conditioner runs as in the following order: Cool only type: Cool Heat pump type: Cool Shut off Heat Shut off

2. Remote controller operation: If the indoor unit sounds like Di, Di when pressing I/O button, that indicates the air conditioner is under the operation of remote controller. After that, press every button to test their functions. 3.Check switch operation: Open the front grille and press the check button. Switch on the power source and then the operation test is activated. If the indicator lamps light up at first and then go out in succession or the LED window of the indoor unit illuminates at first and then goes out, the system is under normal operation. If one of the indicator lamps is flashing at all times, or failure codes are displayed on the LED window of the indoor unit, the system has something wrong and please check malfunction immediately.

BLOCK DIAGRAM
Refrigerant Cycle Block Diagram
INDOOR UNIT
Capillary tube Check valve 2-way valve Liquid side Heat exchanger (Evaporator) Propeller fan Capillary tube Heat exchanger (Condenser)

OUTDOOR UNIT

Cross fan

Gas side 3-way valve Accumulator Compressor 4-way valve Cooling Heating Gas leak check point

11

TROUBLE SHOOTING
Items to be checked first
1. Is the voltage of the power correct? The input voltage shall be rating voltage 10%. The air conditioner may not operate properly if the voltage is out of this range. 2. Is the link cable connecting the indoor unit and the outdoor unit linked properly? Please refer to the wiring diagram Check the terminals if the indoor unit and outdoor unit are properly linked by the same number of cables. 3. When a problem occurs due to the contents illustrated in the table below, it is symptom not related to the malfunction of the air conditioner.
Operation of air conditioner In COOL operation mode, the compressor does not operate at a room temperature higher than the setting temperature that the indoor fan should operate. In a HEAT operation mode, the compressor does not operate at a room temperature lower than the setting temperature that indoor fan should operate. Explanation It happens after a delay of 3 minutes when the compressor is reoperated. The same phenomenon occurs when a power is on. As a phenomenon that the compressor is reoperated after a delay of 3 minutes, the indoor fan is adjusted automatically with reference to a temperature of the air blow.

Fan speed setting is not allowed in AUTO or DRY mode.

The speed of the indoor fan is set to low in DRY mode. Fan speed of 3 steps is selected automatically in AUTO mode.

Compressor stops operation intermittently in DRY mode.

Compressor operation is automatically controlled in DRY mode depending on the room temperature and humidity.

Compressor of the outdoor unit is operating although it is turned off in HEAT mode.

When the unit is turned off while de-ice is activated, the compressor continues operation for up to 10 minutes(maximum) until the deice is completed. Timer is being activated and the unit is in ready mode. The unit operates normally if the timer operation is cancelled.

Timer indicator lamp lights up and the air conditioner does not operate.

The compressor and indoor fan stop intermittently in HEAT mode.

The compressor and indoor fan stop intermittently if room temperature exceeds a setting temperature in order to protect the compressor from overheated air in HEAT mode. The compressor operates in a reverse cycle to remove exterior ice in HEAT mode, and indoor fan and outdoor fan do not operate intermittently for within 20% of the total heat operation. The compressor stops intermittently or the fan speed of the indoor unit decreases to prevent inside/outside air frozen depending on the inside/outside air temperature.

Indoor fan and outdoor fan stop intermittently in HEAT mode.

The compressor stops intermittently in COOL mode or DRY mode, and fan speed of the indoor unit decreases.

SELF DIAGNOSIS FUNCTION


Our company provides the end-users with thoughtful services by installing various diagnostic systems to indicate the following irregular performances.

Check code
FAULT F6 FAULT F7 FAULT F8 FAULT F9

Diagnosis of malfunction
PG motor faults Indoor TEMP sensor faults Indoor coil pipe TEMP sensor faults Outdoor coil pipe TEMP sensor faults

Note: When the outdoor coil pipe TEMP sensor is out of order or removed, the air conditioner will set to defrost automatically in order to prevent it not working normally while the outdoor coil pipe TEMP sensor is malfunction.

12

FAULT DIAGNOSIS BY SYMPTOM


Fan motor or its capacitor faults. Fan motor error No cooling Loose connection or badly contact. Control circuit error. Voltage may appear a little lower or higher. compressor does not operate No cooling effect at all Leakage of refrigerant Block of the cooling system Loose or wrong connection. Compressor faults or jumps for overloading. Control circuit error. Recharge the refrigerant at leaking place. The capillary, pipeline are blocked or the valve is not open or the connecting tube is folded flat.

Some leakage in the valve. Insufficient refrigerant Some cracks, welding failure in the system. Extra fluorin is added during mounting. Air filter is blocked No periodical cleaning. Accumulated lampblack, dust or contaminated ambient environment. Mounting location is not suitable, such as near the wall. Air outlet is blocked or accumulated lampblack or dust is attached to the vane. The outdoor unit gets exposed to the sun for too long period. Not for residential use. Air conditioning burden is not adequate for the room The doors and windows are not closed well; too weak of input cooling power or too many heat resources in the room. Low fan motor frequency or capacitor is not functional. Low fan speed or the fan motor faults. The four-way valve error The distributing air of the four-way valve may have mixed together; the valve core or solenoid valve faults. The valve is not completely open; the capillary or Pipeline is half blocked. Connecting tube is folded flat.

Poor cooling efficiency

Poor efficiency of heat dissipating on the outdoor unit

Too high ambient temperature

Low airflow volume

Blockage in the system

13

FAULT DIAGNOSIS BY SYMPTOM


Fan motor or its capacitor faults. Fan motor error No heating Loose connection or badly contact. Control circuit error. Voltage may appear a little lower or higher. compressor does not operate No heating effect at all Leakage of refrigerant Block of the cooling system The four-way valve or solenoid valve faults. Loose or wrong connection. Compressor faults or jumps for overloading. Control circuit error. Recharge the refrigerant at leaking place. The capillary, pipeline are blocked or the valve is not open or the connecting tube is folded flat. The four-way valve did not commutate or the distributing air of the four-way valve may have mixed together. Some leakage in the valve. Insufficient refrigerant Some cracks, welding failure in the system. Extra fluorin is added during mounting. Air filter is blocked No periodical cleaning. contaminated ambient environment.

Poor heating efficiency

Too low ambient temperature Too thick frost generated on the condenser. Extra refrigerant or mixing air in the system Air conditioning burden is not adequate for the room The condenser is too dirty

Below 0 .

The condenser does not defrost, no smooth air circulation. Discharge the redundant refrigerator recharge the refrigerant after vacuum extraction. The doors and windows are not closed well; too weak of input cooling/heating power. Accumulated lampblack or dust is attached to the vane. Not satisfy the conditions for electric heater running. Plug cords may be loose.

The electric heater is not working

Low airflow volume

Low fan motor frequency or capacitor is not functional. Low fan speed or the fan motor faults.

The four-way valve error

The distributing air of the four-way valve may have mixed together; the valve core or solenoid valve faults. The valve is not completely open; the capillary or Pipeline is half blocked. Connecting tube is folded flat.

Blockage in the system

14

FAULT DIAGNOSIS BY SYMPTOM


Collision sound of the machine Noisy Fixing bolts somewhere may loose or rub, some spare parts may not match very well.

Flowing sound of the liquid Noise from indoor unit Sound of the running fan motor

Refrigerant circulation or pressure change of refrigerant while switch on/off.

Vane imbalance or distortion, rupture; loose screw of vane.

Sound of plastic pieces rubbing or deforming

Plastic pieces deform due to expansion when hot and shrink when cold. Or some spare parts may not match very well.

Collision sound of the machine

Collision of the pipeline, fixing screws loose or deform caused by rubbing.

Noise from Outdoor unit

Oscillation sound

Inappropriate installation method; the unit does not match with the installation kit very well or the compressor quivers acutely. Vane imbalance or distortion.

Sound of running fan motor Sound made by cooling operation Sound of running compressor

Refrigerant circulation or vane distortion.

Something wrong with the compressor, such as oil shortage, valve slice distortion.

The unit does not match with the installation kit very well Resonance sound The whole unit resonates thedoor and window.

Collision sound of the machine Noise from the whole unit

Collision of the pipeline, fixing screws loose or plastic pieces deform.

Sound made by compressor or motor Flowing sound of condensed water

The compressor or motor makes abnormal noise.

Condensed water is attached to the vane.

Sound of running fan motor

Vane imbalance or distortion.

15

FAULT DIAGNOSIS BY SYMPTOM


Switching on the air conditioner

The current leakage switch jumps to turn off

Junction wire looses and collides with the outer cover. Degraded capability of wire insulation. Insulation capability of some components has lowered.
Check the resistance of every component by multimeter

Water comes into the plug or electric components.

The fuse is blown or air limit switch jumps to turn off

Is the voltage of power supply lower than 15% of rated voltage (220V)?

Yes

The voltage is low, please add manostat.

No

Short circuit somewhere.

Short circuit in the electric wire or connection wire. Partially short circuit in some components.

Yes Fuse capacity is adequate or not? No

Check as the above -mentioned method.

Replace with adequate fuse.

Strong circuit breaks the circulation.

Without any response

Check whether the receptacle has power or not.

The transformer faults.

The main control board faults. Power supply error

16

CONTROL SPECIFICATION

ABBREVIATION
ST: Setting Temperature PT: Indoor coil Pipe Temperature RT: Room Temperature OT: Outdoor coil pipe temperature OFAN: Outdoor fan IFAN: Indoor fan COMP: Compressor

OPERATION OF MAIN BOARD


COOL MODE
The ST at cool mode is adjustable within16 -31 . When RT ST, both the compressor and the outdoor fan start; When RT<ST-1 , the compressor stops and 18 seconds later, the outdoor fan will stop. But the indoor fan keeps running at predetermined speed. Once turning on the unit while set at cool mode, the indoor fan immediately runs at predetermined speed; if all the conditions meet with the requirement of compressor operation, both the outdoor fan and compressor start running. If not, either the outdoor fan or compressor could start. The four-way valve keeps being off all the time at cool mode.

Condensate dew prevention


If the horizontal air flow louver is set at low angle on COOL mode, after a while, it will auto swing to its maximum angel for system protection. 3 minutes later, the horizontal air flow louver will resume to its original position.

Anti-ice function
When PT=2 , the compressor does not stop and indoor fan runs at high speed. When PT -1 high speed. for 1 minute, the compressor and outdoor fan stop and indoor fan runs at

When PT 8 for 5 minutes, anti-ice protection deactivates, both the compressor and the outdoor fan start operation.

8 2 -1 5 mins

OFAN

ON OFF ON

ON ON

COMP

3 mins

OFF High speed


IFAN

Set speed

Set speed

17

CONTROL SPECIFICATION
HEAT MODE
If the air conditioner is off and then turned on while set at COOL ,HEAT or DRY mode, it will take approximately 3 minutes for the compressor to start. The ST at heat mode is adjustable within16 -31 . When RT ST, the compressor stops; when RT<ST-1 , the compressor starts. Once turning on the unit while set at heat mode, if all the conditions meet with the requirement of compressor operation, the four-way valve gets charged and 8 seconds later, the compressor and outdoor fan start running.

Strong-wing prevention :
A.PT<27,the indoor fan stops running, the swing louver cannot be controlled by the remote controller. B.34>PT 27,the indoor fan runs at low speed, the sweep louver erects. C.PT 34,the indoor fan and the swing louver can be controlled normally.

Heat overload protection:


For 7000BTU/h Model, when PT 47 , the outdoor fan stops; when PT 42 , the outdoor fan starts; when PT 60 , the compressor stops. For 9000BTU/h Model, when PT 50 , the outdoor fan stops; when PT 47 , the outdoor fan starts; when PT 63 , the compressor stops. For 9000 BTU/h Model, when PT 55 , the outdoor fan stops; when Pt 50 , the outdoor fan starts; when PT 63 , the compressor stops.

Deice control:
Conditions for activating deice: a. The working hours of compressor accumulates to be 40 minutes. b. When OT -4 for 1 minute. Conditions for terminating deice: a. When OT 15 for 1 minute. b. Over 10 minutes of deicing operation.

Electric-heat control:
Conditions for initiating electric-heat function: a. RT 23 ; b. RT+3 ST; c. The indoor fan runs; d. Turn on the electric-heat key; e. PT<50 Conditions for terminating electric-heat function: a. PT 50 ; b. RT 26 ; c. The indoor fan stops running; d. Turn off the electric-heat key; e. Mode change. Conditions for terminating electric-heat function: a. PT 50 ; b. RT 26 ; c. The indoor fan stops running; d. Turn off the electric-heat key; e. Mode change.
15
OT

-4
COMP ON OFF ON OFF ON OFF 30S TIME 10 minutes at most
15S

OFAN

4-way valve

30S

15S

18

CONTROL SPECIFICATION
DRY MODE
In this mode, the air conditioner automatically sets the room temperature and this temperature is incontrollable by remote controller. The initial ST =RT-2 . Control during dry mode: a. When RT<15 , dry mode is not available; when RT 15 , the compressor intermittently runs under the influence of TS and RT. b. When RT 23 , if RT ST, the compressor runs intermittently as this: Run for 8 minutes Stop for 3 minutes If RT<ST, the compressor runs intermittently as this: Stop for 4 minutes Run for 1 minute

c. When RT<23 , if RT ST, the compressor runs intermittently as this: Run for 2 minutes Stop for 3 minutes If RT<ST, the compressor runs intermittently as this: Stop for 4 minutes Run for 1 minute

d. In this mode, the indoor fan keeps running at low speed with the same pace as the compressor, and this speed can not be controlled by remote controller.

AUTO MODE
In this mode, the air conditioner can automatically adjust the room temperature to decide the most suitable temperature. At the start of operation, the unit will automatically select the operation mode according to the room temperature. The following table shows the conditions which are set at start up.
Room Temperature (RT) RT 26 26 RT 25 25 RT 23 RT 23 Cool only type Mode Cool Dry Initial Setting Temperature 24 RT-2 RT-2 21 Mode Cool Dry Heat Heat pump type Initial Setting Temperature 24 RT-2 RT-2 26

Auto mode entering a. Once some operation mode is determined, it can not be changed even if the RT has altered. b. You can change the operation mode by remote controller. If restart within 2 hours, the unit will resume the same operation mode as before. If restart after 2 hours, the unit will select the operation mode according to the initial room temperature. At auto mode the ST can only be set + or - 2 of the RT.

19

CONTROL SPECIFICATION
FAN MODE
Indoor fan runs at the set speed while compressor and outdoor fan are turned off. Indoor fan speed can be adjusted for low, medium and high.

SLEEP MODE
Sleep mode in cooling and drying running. A. The indoor fan runs at low speed. B. After one hour of operation the set temperature will increase by 1 . One hour later, the set temperature will increase by 1 once more. The unit will then continue operating at 2 above the set temperature. Sleep mode in heating running. A. The indoor fan runs at low speed. B. After one hour of operation the set temperature will decrease by 2 . One hour later, the set temperature will decrease by 2 once more. The unit will then continue operating at 4 below the set temperature.

20

TO DISASSEMBLE MECHANICAL PARTS


Stop operation of the air conditioner and remove the power cord before repairing the unit. The following pictures taking L1 series as an example are presented just for the purpose of illustration.

Indoor unit
No Parts Procedure Remark

Front grille

1.Stop the air conditioner operation and block the main power. 2.Contract the second finger to the left ,and right handle and pull to open the inlet grille.

3.Draw away signal line.

4.Take the left and right filter out.

5. Loosen two fixing screw of front grille.

6.Put hands at the two ruts of the body, then pull the front panel out .

21

TO DISASSEMBLE MECHANICAL PARTS


No 2 Parts Electrical parts Procedure 1.Loosen the earth screw in evaporator. Remark

2.Loosen the stepping motor line, and pull softly the indoor pipe temperature sensor out from the pipe casing.

3.Push the hook outside to take the electrical box out easily.

4.Separate the electrical box from the indoor unit.

Assy tray drain

1.Push the left and right hooks to make the assy pulled out.

22

TO DISASSEMBLE MECHANICAL PARTS


No Parts Procedure 2.Separete the assy tray drain from the body. Remark

1.Push the left hook and separate the left part out of evaporator.

2.Push the right hook and separate the right part out of evaporator. 4 Evaporator

3.Separate the evaporator from the indoor unit.

Fan motor and 1.Separate the fan motor cross fan from the fan.

23

TO DISASSEMBLE MECHANICAL PARTS


Outdoor unit
No 1 Parts Cabinet Procedure 1.Turn off the unit and remove the power cable. Remark

2.Remove the upper cabinet, the front cabinet and back cabinet. 2 Fan motor & propeller fan 1.Remove the nut flange. (Turn to the right to remove as it a left turned screw ) 2.separate the propeller fan from fan motor. 3.Loosen the fixed screw of fan motor,separate the fan motor from outdoor unit

Ass'y control 1.Loosen the fixing screw of out the base-electrical control .

2.separate the connector.

3.Separate the ass' y control out from the outdoor unit.

24

Exploded Views and Parts List


Indoor unit
AUS-07C(H)53R010Lx AUS-12C(H)53R130Lx AUS-09C(H)53R010Lx AUS-12C(H)53R150Lx AUS-07C(H)53R150Lx AUS-09C(H)53R150Lx

25

Exploded Views and Parts List


Indoor unit
AUS-07C(H)53R010Lx AUS-12C(H)53R130Lx
qty. 2
remark left and right are sameness L14 L15 L16 parted as upper panel and lower panel

AUS-09C(H)53R010Lx AUS-12C(H)53R150Lx
No.

AUS-07C(H)53R150Lx AUS-09C(H)53R150Lx
qty. 1 1
L1 L17(display piece) L15(transparency piece) L15without L1 L3 L16 L18 without L15(decorate tape), L17(decorate board) remark

No. English Part Name 1 air filter

English Part Name

26 Drain hose 27 Electrical control cover

2 Front panel

3 LED

1
L14(control box) L15(display box) L16 without L17without

28

Indoor display panel

4 Electrical control box

29 5 Enclosure 6 Swing louver 7 Water collecting tray 8 Evaporator 9 Indoor unit fan 10 Oil bearing 11 Rubber bear support 12 Bottom enclosure 13 Power supply cord clip 14 Electrical control box 15 Indoor unit terminal block 16 Transformer 17 Mounting plate 18 Main control board 19 Power supply cord 20 Room temperature sensor 21 Pipe temperature sensor 22 Pipe fixing plate 23 fan motor 24 Electrical holder 25 Stepping motor 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Decorate ring

26

Exploded Views and Parts List


Outdoor unit
AUS-07C53R010Lx AUS-09C53R010Lx

27

Exploded Views and Parts List


Outdoor unit
1 2 3 4 5 6 7 8 9 Air outlet grille Front panel Left handle Top cover Outdoor unit fan Outdoor fan motor Outdoor fan motor supporter Condenser Partition
AUS-07C53R010Lx AUS-09C53R010Lx

No. English Part Name

Quantity No. English Part Name Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 1 1 1

10 Electrical install board supporter 11 Left back side plate 12 Back cover 13 right back side plate 14 Electrical install board 15 Capacitor fixing clip 16 Outdoor unit terminal block 17 power supply cord clip 18 capacitor for Compressor 19 Fan motor capacitor 20 Capillary assembly 21 High pressure valve 22 Low pressure valve 23 valve board 24 Compressor screw 25 Compressor 26 Bottom board 27 Right handle

28

Exploded Views and Parts List


Outdoor unit
AUS-07H53R010Lx AUS-09H53R010Lx

29

Exploded Views and Parts List


Outdoor unit
Number Name
AUS-07H53R010Lx AUS-09H53R010Lx
Quantity

Quantity Number Name

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27

Air outlet grille Front panel Left handle Top cover Outdoor unit fan Outdoor fan motor
Outdoor fan motor supporter

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 1 1

28 29

Right handle Outdoor pipe sensor

1 1

Condenser Partition Four way valve


Electrical install board supporter

Left back side plate Back cover Right back side plate Electrical install board Capacitor fixing clip
Outdoor unit terminal block

Power supply cord clip Capacitor for Compressor Fan motor capacitor Capillary assembly High pressure valve Low pressure valve Valve board Compressor screw Compressor Bottom board

30

Exploded Views and Parts List


Outdoor unit
AUS-12C53R150Lx AUS-07C53R150Lx AUS-09C53R150Lx

31

Exploded Views and Parts List


Outdoor unit
No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
AUS-12C53R150Lx AUS-07C53R150Lx AUS-09C53R150Lx

English Part Name Air outlet grille Front panel Outdoor unit fan Partition Valve board Compressor screw Power supply cord fixing Power supply cord clip Capacitor for compressor Electrical install board Right side board Top cover Fan motor capacitor Outdoor unit terminal block High pressure valve Capillary assembly Low pressure valve Compressor Bottom board Condenser Uphold board Capacitor fixing clip Fan motor (out door) Fan screw nut M8 Right handle

Quantity 1 1 1 1 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 1

No. 26

English Part Name Outdoor fan motor supporter

Quantity 1

32

Exploded Views and Parts List


Outdoor unit
AUS-12H53R150Lx AUS-07H53R150Lx AUS-09H53R150Lx

33

Exploded Views and Parts List


Outdoor unit
No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
AUS-12H53R150Lx AUS-07H53R150Lx AUS-09H53R150Lx

English Part Name Air outlet grille Front panel Outdoor unit fan Partition Valve board Compressor screw Power supply cord fixs Power supply cord clip Capacitor for compressor Electrical install board Right side board Top cover fan motor capacitor Outdoor unit terminal block High pressure valve Capillary assembly Low pressure valve Four way valve Compressor Bottom board Condenser Uphold board Capacitor fixing clip Fan screw nut M6 Fan screw nut M8

Quantity 1 1 1 1 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3

No. 26 27

English Part Name Right handle Outdoor fan motor supporter

Quantity 1 1

34

Exploded Views and Parts List


Outdoor unit
AUS-12C53R130Lx

35

Exploded Views and Parts List


Outdoor unit
1 2 3 4 5 6 7 8 9 Air outlet grille Front panel Outdoor unit fan Outdoor fan motor Outdoor fan motor supporter Left handle Left back side board Condenser Back cover
AUS-12C53R130Lx

No. English Part Name

Quantity No. English Part Name Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

10 Fixed board 11 Top cover 12 Fan motor capacitor 13 Capacitor for Compressor 14 Electrical install board 15 Capacitor fixing clip 16 Outdoor unit terminal block 17 Power supply cord clip 18 Right handle 19 Right back side board 20 Capillary assembly 21 High pressure valve 22 Low pressure valve 23 Valve board 24 Compressor 25 Bottom board 26 Partition

36

Exploded Views and Parts List


Outdoor unit
AUS-12H53R130Lx

37

Exploded Views and Parts List


Outdoor unit
1 2 3 4 5 6 7 8 9 Air outlet grille Left handle Front panel Outdoor unit fan Partition Top cover Left back side plate Condenser Right back side plate
AUS-12H53R130Lx

No. English Part Name

Quantity No. English Part Name Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

10 Right handle 11 Fan motor capacitor 12 Capacitor for Compressor 13 Electrical install board 14 Outdoor unit terminal block 15 Power supply cord clip 16 Outdoor fan motor supporter 17 Outdoor fan motor 18 Four way valve 19 Capillary assembly 20 High pressure valve 21 Valve board 22 Low pressure valve 23 Compressor 24 Back board

38

Wiring Diagrams
AUS-07C53R010Lx AUS-09C53R010Lx AUS-12C53R150Lx AUS-07C53R150Lx AUS-09C53R150Lx

Indoor unit

AUS-12C53R130Lx

IFAN

Outdoor unit

AUS-07C53R010Lx AUS-12C53R130Lx

AUS-09C53R010Lx AUS-12C53R150Lx

AUS-07C53R150Lx AUS-09C53R150Lx

39

Wiring Diagrams
Indoor unit
AUS-07H53R010Lx AUS-12H53R130Lx AUS-09H53R010Lx

IFAN

Outdoor unit

AUS-07H53R010Lx AUS-12H53R130Lx AUS-09H53R010Lx

40

Wiring Diagrams
Indoor unit
AUS-12H53R150Lx AUS-07H53R150Lx AUS-09H53R150Lx

IFAN

Outdoor unit

AUS-12H53R150Lx AUS-07H53R150Lx

AUS-09H53R150Lx

41