Product Data: 40QNC / 38HDF 40QNQ / 38QRF High - Wall Duct Free Split System Sizes 018 To 036
Product Data: 40QNC / 38HDF 40QNQ / 38QRF High - Wall Duct Free Split System Sizes 018 To 036
40QNQ / 38QRF
High---Wall Duct Free Split System
Sizes 018 to 036
Product Data
INDUSTRY LEADING
FEATURES / BENEFITS
AN INEXPENSIVE AND CREATIVE
SOLUTION TO DESIGN PROBLEMS.
The 38HDF(QRF) / 40QNC (QNQ) series duct--free split systems
are a matched combination of an outdoor condensing unit and an
indoor fan coil unit connected only by refrigerant tubing and wires.
The fan coil is mounted on the wall, near the ceiling. This
selection of fan coils permits inexpensive and creative solutions to
design problems such as:
These compact indoor fan coil units take up very little space in the
room and do not obstruct windows. The fan coils are attractively
styled to blend with most room decors. Advanced system
components incorporate innovative technology to provide reliable
cooling performance at low sound levels.
BUILT--IN RELIABILITY
When noise is a concern, the duct--free split systems are the answer.
The indoor units are whisper quiet. There are no compressors
indoors, either in the conditioned space or directly over it, and
there is none of the noise usually generated by air being forced
through ductwork.
When sound ordinances and proximity to neighbors demand quiet
operation, the 38HDF/QRF unit is the right choice: The advanced,
horizontal blow--through airflow design distributes air more evenly
over the coil.
40QNC,QNQ/38HDF,QRF
SECURE OPERATION
If security is an issue, outdoor and indoor units are connected only
by refrigerant piping and wiring to prevent intruders from crawling
through ductwork. In addition, since 38HDF/QRF units can be
installed close to an outside wall, coils are protected from vandals
and severe weather.
FAST INSTALLATION
The small footprint of the outdoor unit provides additional
benefits. Because they require minimal service and airflow
clearances, the outdoor units can be located virtually anywhere -on the ground, roof, balcony, under a deck, or even mounted to an
outside wall.
The indoor hi--wall units are simple to install. A mounting bracket
is standard with the indoor units and only control wires and piping
need to be run between indoor and outdoor units. These units are
fast and easy to install ensuring minimal disruption to customers in
the home or workplace. This makes the 38HDF (QRF) /40QNC
(QNQ) duct--free split systems the equipment of choice, especially
in retrofit situations.
ECONOMICAL OPERATION
The duct--free split system design allows individual room heating
or cooling when required. There is no need to run large supply--air
fans or chilled water pumps to handle a few spaces with unique
load patterns. In addition, because air is moved only in the space
required, no energy is wasted moving air through ducts.
EASY--TO--USE CONTROLS
The high--wall units have microprocessor--based controls to
provided the ultimate in comfort and efficiency. The user friendly
wireless remote control provides the interface between user and the
unit.
FLEXIBILITY
AGENCY LISTINGS
All systems are listed with AHRI (Air Conditioning, Heating &
Refrigeration Institute), and UL.
QNC
---
018
3--- 01
Voltage
3 --- 208/230 ---1 ---60
Unit Type
QNC --- Cooling Only
QNQ --- Heat Pump
OUTDOOR UNIT
38
HDF
018
3--- 01
---
Voltage
3 --- 208/230 ---1 ---60
5 --- 208/230 ---3 ---60*
6 --- 460 ---3 ---60*
Nominal Capacity
018 --- 1 ---1/2 Tons
024 --- 2 Tons
030 --- 2 ---1/2 Tons
036 --- 3 Tons
Unit Type
HDF --- Cooling Only
QRF --- Heat Pump
Indoor Section
Standard CFM
Outdoor
Indoor
1720
645
1720
645
1720
730
3900
900
3900
900
3900
900
1720
645
1720
645
3900
730
3900
900
3900
900
3900
900
SEER
EER
13
13
13
13
13
13
13
13
13
13
13
13
11.8
11.3
11.7
11.3
11.3
11.3
11.3
11.5
11.7
10.9
10.9
10.9
High Heat
BTUH
HSPF
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
17,000
7.7
22,000
7.7
28,200
7.7
35,600
7.7
35,600
7.7
35,600
7.7
40QNC,QNQ/38HDF,QRF
Nominal Capacity
018 --- 1 ---1/2 Tons
024 --- 2 Tons
030 --- 2 ---1/2 Tons
036 --- 3 Tons
40QNC,QNQ/38HDF,QRF
S
A
A
S
S
S
S
S
S
S
S
S
S
S
A
S
S
S
S
S
S
S
S
A07892
A
S
A
A
A
A
S
S
O
O
O
Legend
S Standard
A Accessory
O Optional
A08432
Zone Manager
For applications where more sophisticated controls are required, a
Zone Manager that permits the connection of up to 32 different
indoor units, divided into a maximum of eight different zones, can
be used.
S
S
S
24 hour timer
Zone Manager
ZONE ..
PM
Remote Control
ZONE 8
A08443
A0451
Stacking Kit
(304.8)
(304.8)
The Isolation Relay must be used when Low Ambient Kit is used
with heat pumps to ensure the pressure switch is bypassed when
unit is running in heat pump mode.
Crankcase Heater
(304.8)
(304.8)
A06417
Wind Baffles
The Wind Baffle is a sheet metal shield used to provide improved
unit operation during high winds and is recommended whenever
the low ambient accessory is used.
D06006
40QNC,QNQ/38HDF,QRF
Isolation Relay
DIMENSIONS -- INDOOR
W
A08433
W
in. (mm)
42.5 (1080)
42.5 (1080)
57.5 (1461)
57.5 (1461)
Model Size
40QNC,QNQ/38HDF,QRF
18K
24K
30K
36K
H
in. (mm)
11.6 (295)
11.6 (295)
13.4 (340)
13.4 (340)
D
in. (mm)
7.9 (201)
7.9 (201)
9.5 (241)
9.5 (241)
(14.1)
(14.1)
(23.2)
(23.2)
DIMENSIONS - OUTDOOR
UNIT SIZE
38HDF
38QRF
UNIT MODELS
38QRF
Unit Size
38HDF
Unit Size
018
018
CHASSIS
SIZE
(Reference)
0
024,030
024
0.6
036
030,036
1.0
2-11/8
3-015/16
16
(436.6)
1-53/16
(436.6)
1-75/8
(498.5)
1-51/8
(638.2)
(938.2)
16
(369.9)
1-4
(406.4)
2-71/8
(790.6)
3-13/16
(944.6)
3-015/16
(938.2)
1-29/16
(369.9)
1-4
(406.4)
16
(595.3)
1-117/16
(595.3)
3-89/16
(1131.9)
1-51/16
(433.4)
1-67/16
(468.3)
2-61/2
(774.7)
1-29/
1-117/
1-53/
OPERATING WT
lb
kg
in.
mm
018
5/
15.88
166
75.3
024
5/
15.88
176
79.8
030
3/
19.05
187
84.8
036
3/
19.05
250
113.4
018
5/
15.88
166
75.3
024
5/
15.88
176
79.8
030
3/
19.05
187
84.8
036
3/
19.05
232
105.2
0-111/4
0-215/
(435)
1-10
(559.1)
1-111/8
(587.4)
2-4
(711.5)
1-1
(330.2)
1-2
(355.6)
8
(168.3)
0-63/4
(171.5)
(285.8)
0-115/8
(295.3)
16
(75)
0-215/16
(75)
0-6
(152.4)
0-6
(152.4)
2-53/16
(741)
2-101/16
(865.5)
1-111/16
(347.7)
0-81/8
(206.4)
1-37/8
(403.2)
0-37/16
(88)
0-61/2
(165.4)
0-65/
A08434
CLEARANCES -- INDOOR
4 in.
(101.6 mm)
min.
8 in.
(203.2 mm)
min.
4 in.
(101.6 mm)
min.
A08357
CLEARANCES - OUTDOOR
A
Air-outlet
E
Air-inlet
A08436
UNIT
A
B
C
D
E
40QNC,QNQ/38HDF,QRF
80 in
(2032 mm)
min.
018
208/230 ---1 ---60
18000
166 (75.3)
024
208/230 ---1 ---60
24000
176 (79.8)
030
036
208/230 ---1 ---60
208/230 ---1 ---60
30000
36000
187 (84.8)
250 (113.4)
R---410A
Accurator at Outdoor Unit
63
70
5(2.3)
8.5(3.9)
49
4.8(2.2)
55
5.3(2.4)
6.0(2.7)
6.3(2.9)
7.4(3.2)
1.2(.5)
1.0(.5)
2.4(.9)
40QNC,QNQ/38HDF,QRF
036
460 ---3 ---60
36000
250 (113.4)
70
8.5(3.9)
70
8.5(3.9)
8.5(3.9)
8.5(3.9)
8.5(3.9)
0.0
0.0
0.0
ZP34K5E ---PFV
42
ZP34KE ---TF5
42
ZP34KE ---TFD
42
Scroll
Type
Model
Oil Charge (POE ---oz)
Accumulator
Outdoor Fan
CFM/RPM
Diameter (in) .. No. of Blades
Motor HP
Outdoor Coil
Face Area (sq. ft)
No. Rows
Fins per inch
Circuits
High Pressure Switch
Cut---In (psig)
Cut---Out (psig)
Low Pressure Switch
Cut---In (psig)
Cut---Out (psig)
Fusible Plug F ( C)
Refrigerant Lines
Connection Type
Suction/Vapor (in) OD
Mixed Phase * (in) OD
Maximum Length** ft (m)
Max Lift (Fan Coil Above) ft
(m)
Max Drop (Fan Coil Below) ft
(m)
Controls
Control Voltage
External Finish
036
208/230 ---3 ---60
36000
250 (113.4)
ZP16K5E ---PFV
25
ZP21K5E ---PFV
25
ZP25K5E ---PFV
25
Yes
840/1720
183
1/8
840/1720
183
1/8
840/1720
183
1/8
850/3900
243
1/4
850/3900
243
1/4
850/3900
243
1/4
5.82
2
20
2
7.27
3
20
3
7.27
3
20
3
12.1
2
20
6
12.1
2
20
6
12.1
2
20
6
42025
65010
42025
65010
42025
65010
42025
65010
42025
65010
42025
65010
4525
205
4525
205
4525
205
4525
205
4525
205
4525
205
210 (99)
Mixed Phase/Suction --- Sweat
5/8
3/4
3/8
200 (61)
65 (20)
200 (61)
24 vac
Gray
018
024
030
036
036
036
18000
24000
30000
36000
36000
36000
166 (75.3)
176 (79.8)
187 (84.8)
232 (105.2)
232 (105.2)
232 (105.2)
5.5 (2.5)
6.8 (3.1)
10.7 (4.9)
10.0 (4.5)
10.0 (4.5)
10.0 (4.5)
6.3 (2.9)
7.3 (3.3)
10.7 (4.9)
10.0 (4.5)
10.0 (4.5)
10.0 (4.5)
.8 (.36)
.5 (.23)
0.0
0.0
0.0
0.0
Refrigerant Type
R---410A
Metering Device
Cooling Piston
49
55
63
70
70
70
Heating Piston
45
49
53
63
63
63
ZP16K5E ---PFV
ZP21K5E ---PFV
ZP25K5E ---PFV
ZP34K5E ---PFV
ZP34KE ---TF5
ZP34KE ---TFD
25
25
25
42
42
42
NA
NA
40
NA
NA
NA
840/1720
840/1720
850/3900
850/3900
850/3900
850/3900
183
183
183
243
243
243
1/8
1/8
1/4
1/4
1/4
1/4
12.1
Compressor
Model
Scroll
Outdoor Fan
Rpm/CFM
Diameter (in) .. No. of Blades
Motor HP
Outdoor Coil
Face Area (sq. ft)
5.82
7.27
12.1
12.1
12.1
No. Rows
20
20
20
20
20
20
Circuits
Cut---In (psig)
42025
42025
42025
42025
42025
42025
Cut---Out (psig)
65010
65010
65010
65010
65010
65010
4525
4525
4525
4525
4525
4525
205
Fusible Plug F ( C)
210 (99)
Refrigerant Lines
Connection Type
Suction/Vapor (in) OD
3/4
3/8
200 (61)
65 (20)
200 (61)
Controls
Control Voltage
24 vac
External Finish
Gray
40QNC,QNQ/38HDF,QRF
Type
18/24
18/24
30
36
31 (14.1)
31 (14.1)
51 (23.2)
51 (23.2)
Refrigerant Type
R---410A
Metering Device
5.4
7.9*
8.8
13
Indoor Fan
Rpm/Cfm (High)
1335 / 645
1030 / 730
1200 / 900
Rpm/Cfm (Medium)
1120 / 525
930 / 630
1050 / 750
Rpm/Cfm (Low)
1000 / 460
830 / 530
Motor Watts
64
900 / 600
74
14.0 x 33.7
24.2 x 23.5
24.2 x 23.5
4.9
40QNC,QNQ/38HDF,QRF
Indoor Coil
Face Area (sq. ft)
4.9
No. Rows
16
16
18
18
Circuits
212.5 x 16.1
212.5 x 16.1
317.3 x 16.1
317.3 x 16.1
Filters
QuantitySize (in)
Controls
Integrated Microprocessor
Diagnostics
Yes
Fan Mode
High/Medium/Low/Auto
Dehumidification Mode
Yes
Sleep Mode
Yes
Diagnostics
Yes
Timer Mode
Yes
Freeze Protection
Yes
Test Mode
Yes
Auto Restart
Yes
Air Sweep
Yes
Horizontal
Manual
Automatic
Vertical
Automatic
Control Voltage
24vac
Refrigerant Lines
Connection Type
Flare
3/8
5/8
5/8
3/4
3/4
White
White
White
White
Condensate Drain
Size (in)
External Finish
* When matched with 38HDF024
LEGEND
ID --- Internal Diameter
OD --- Outside Diameter
10
18
208/230 ---1 ---60
31 (14.1)
24
30
208/230 ---1 ---60
208/230 ---1 ---60
31 (14.1)
51 (23.2)
R---410A
Accurator At Outdoor Unit
7.9
9.2
5.2
1335 / 645
1120 / 525
1000 / 460
64
12.8
1030 / 730
930 / 630
830 / 530
1200 / 900
1050 / 750
900 / 600
74
14.0 x 33.7
24.2 x 23.5
3
2
16
5
212.5 x 16.1
36
208/230 ---1 ---60
51 (23.2)
3
2
20
5
4.9
2
18
9
4.9
2
18
9
212.5 x 16.1
317.3 x 16.1
317.3 x 16.1
Integrated Microprocessor
Wireless (standard) , Wired (optional), Zone Control (optional)
Yes
Demand Defrost
High/Medium/Low/Auto
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Manual
Automatic
Automatic
24vac
Flare
3/8
5/8
5/8
3/4
3/4
LEGEND
ID --- Internal Diameter
OD --- Outside Diameter
11
40QNC,QNQ/38HDF,QRF
PERFORMANCE DATA
COOLING CAPACITIES
38HDF018 WITH 40QNC01824
Temp F ( C)
Air Entering
Condenser
(Edb)
40QNC,QNQ/38HDF,QRF
55
(12.8)
65
(18.3)
75
(23.9)
85
(29.4)
95
(35.0)
105
(40.6)
115
(46.1)
125
(51.7)
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
460/0.04
57
(13.9)
15.9
14.5
15.7
0.88
0.70
48.8
41.8
15.7
14.8
15.5
1.00
0.81
48.1
41.9
15.2
14.6
15.0
1.12
0.93
48.5
42.5
14.2
14.2
14.0
1.24
1.06
49.4
43.6
13.2
12.3
13.0
1.38
1.19
53.7
44.7
12.6
12.6
12.4
1.53
1.34
52.9
45.3
11.8
11.8
11.6
1.69
1.51
54.7
46.2
11.1
11.1
10.9
1.87
1.69
56.3
46.9
62
(16.7)
16.7
12.3
16.5
0.89
0.70
53.9
47.6
16.6
12.5
16.4
1.00
0.82
53.5
47.7
16.4
12.7
16.2
1.13
0.94
52.9
47.9
15.8
12.7
15.6
1.26
1.08
53.0
48.5
14.7
12.1
14.5
1.40
1.22
54.3
49.6
14.0
12.0
13.8
1.56
1.37
54.4
50.3
12.5
10.7
12.3
1.70
1.52
57.4
51.6
11.5
10.4
11.3
1.88
1.69
57.9
52.5
67
(19.4)
18.0
10.9
17.8
0.89
0.70
57.2
53.2
17.9
11.0
17.7
1.00
0.81
57.0
53.3
17.5
10.8
17.3
1.13
0.94
57.5
53.6
17.1
10.7
16.8
1.27
1.08
57.7
54.0
16.6
10.7
16.4
1.42
1.24
57.5
54.4
15.7
10.4
15.5
1.58
1.40
58.2
55.1
14.1
9.2
13.9
1.74
1.55
60.7
56.5
13.4
9.6
13.2
1.93
1.74
59.9
57.1
72
(22.2)
18.5
9.2
18.3
0.89
0.70
61.2
59.4
18.9
9.2
18.7
1.01
0.82
61.1
59.1
18.8
9.2
18.6
1.13
0.94
61.1
59.2
18.3
9.0
18.1
1.27
1.09
61.6
59.6
17.8
8.7
17.6
1.43
1.24
62.2
60.0
17.1
8.5
16.9
1.59
1.41
62.6
60.5
16.3
8.2
16.1
1.77
1.59
63.2
61.1
15.3
8.0
15.1
1.97
1.78
63.7
61.9
645/0.05
57
(13.9)
16.4
15.1
16.2
0.89
0.70
53.4
44.4
16.3
15.3
16.1
1.00
0.81
53.1
44.5
16.1
16.1
15.9
1.13
0.94
51.6
44.7
15.7
15.7
15.5
1.27
1.08
52.4
45.1
15.0
15.0
14.8
1.41
1.22
53.5
45.6
13.5
13.5
13.3
1.54
1.36
56.3
46.9
12.9
12.9
12.7
1.71
1.52
57.4
47.4
11.9
11.9
11.7
1.88
1.70
59.2
48.2
62
(16.7)
17.5
13.2
17.3
0.89
0.70
57.0
50.0
17.2
13.4
17.0
1.00
0.81
56.8
50.2
16.9
13.4
16.7
1.13
0.94
56.6
50.4
16.3
13.4
16.1
1.27
1.08
56.6
50.8
15.6
13.5
15.4
1.41
1.23
56.5
51.4
14.5
13.2
14.3
1.57
1.38
57.0
52.2
13.3
11.8
13.1
1.72
1.53
59.4
53.1
12.1
11.3
11.9
1.89
1.70
60.4
54.0
67
(19.4)
18.3
11.3
18.1
0.89
0.70
60.7
55.8
18.4
11.5
18.2
1.00
0.81
60.2
55.7
18.1
11.4
17.9
1.13
0.94
60.4
55.9
17.6
11.4
17.4
1.27
1.08
60.5
56.2
16.8
11.0
16.6
1.41
1.22
60.7
56.7
16.3
11.2
16.1
1.59
1.41
60.7
57.1
15.2
10.9
15.0
1.76
1.57
61.3
57.9
14.0
10.4
13.8
1.94
1.75
62.1
58.7
72
(22.2)
18.7
9.4
18.5
0.89
0.70
64.2
61.9
19.0
9.5
18.8
1.00
0.82
64.1
61.7
19.2
9.5
19.0
1.13
0.95
64.1
61.6
18.9
9.4
18.7
1.27
1.09
64.2
61.8
18.4
9.3
18.2
1.43
1.24
64.4
62.1
17.6
9.1
17.4
1.60
1.41
64.8
62.5
16.7
8.7
16.5
1.78
1.59
65.5
63.1
15.7
8.4
15.5
1.97
1.79
65.9
63.7
Rating condition
LEGEND
BF --CMP --Edb --Ewb --kW --LDB --LWB --SHG --TC --TCG ---
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The SHG is based on 80_F (26.67_C) edb temperature of air
entering indoor coil.
Below 80_F (26.67_C) edb, subtract (corr factor x cfm) from
SHG.
Above 80_F (26.67_C) edb, add (corr factor x cfm) to SHG.
Correction Factor = 1.10 x (1 --- BF) x (edb --- 80).
Bypass Factor
Compressor
Entering Dry Bulb
Entering Wet Bulb
Total Power
Leaving Dry Bulb
Leaving Wet Bulb
Gross Sensible Capacity (1000 Btu/hour)
Total Net Cooling Capacity (1000 Btu/hour)
Gross Cooling Capacity (1000 Btu/hour)
12
55
(12.8)
65
(18.3)
75
(23.9)
85
(29.4)
95
(35.0)
105
(40.6)
115
(46.1)
125
(51.7)
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
460/0.04
57
(13.9)
20.1
17.5
19.9
1.10
0.91
48.3
40.6
20.3
18.5
20.1
1.25
1.07
46.4
40.4
18.5
16.4
18.3
1.4
1.2
50.4
42.4
18.4
17.6
18.2
1.6
1.4
48.0
42.4
16.9
15.8
16.7
1.74
1.56
51.4
43.6
16.7
15.0
16.5
1.95
1.76
52.9
43.8
15.3
15.3
15.1
2.15
1.97
52.3
45.0
14.4
14.4
14.2
2.38
2.19
53.9
45.8
62
(16.7)
21.6
15.5
21.4
1.10
0.91
52.3
46.2
21.5
15.8
21.3
1.25
1.07
51.7
46.2
20.3
14.8
20.1
1.41
1.23
53.6
47.2
20.2
14.8
20.0
1.6
1.4
53.6
47.4
19.8
15.0
19.6
1.8
1.6
53.1
47.8
19.9
13.5
19.7
2.0
1.8
56.0
47.9
16.5
13.5
16.3
2.17
1.99
55.9
50.4
15.3
13.1
15.1
2.40
2.21
56.6
51.3
67
(19.4)
23.0
13.7
22.8
1.10
0.91
55.9
51.9
22.8
13.6
22.6
1.26
1.07
56.1
52.1
22.7
13.6
22.5
1.43
1.25
56.0
52.2
22.1
13.4
21.9
1.62
1.44
56.3
52.6
21.6
13.5
21.4
1.83
1.64
56.1
52.9
20.6
13.1
20.4
2.04
1.86
56.9
53.7
19.2
12.6
19.0
2.25
2.06
57.7
54.8
17.9
12.1
17.7
2.48
2.29
58.7
55.7
72
(22.2)
23.6
11.6
23.4
1.10
0.91
59.9
58.4
24.1
11.7
23.9
1.26
1.07
59.7
58.0
24.3
11.7
24.0
1.43
1.25
59.7
57.9
23.8
11.4
23.6
1.63
1.44
60.3
58.2
23.2
11.2
23.0
1.83
1.65
60.7
58.7
22.2
10.8
22.0
2.06
1.87
61.4
59.3
21.3
10.5
21.1
2.30
2.12
61.9
59.9
20.2
10.1
20.0
2.56
2.37
62.6
60.6
645/0.05
57
(13.9)
21.1
18.9
20.9
1.10
0.91
52.1
43.2
21.2
19.6
21.0
1.25
1.07
50.9
43.2
20.6
19.5
20.3
1.42
1.23
51.0
43.7
19.3
17.4
19.1
1.58
1.39
45.9
43.7
18.5
17.8
18.3
1.8
1.6
53.8
44.7
17.3
15.8
17.1
2.0
1.8
54.8
45.6
16.3
16.3
16.1
2.17
1.99
55.8
46.7
15.4
15.4
15.2
2.40
2.22
57.2
47.4
62
(16.7)
22.5
16.6
22.3
1.10
0.91
55.7
48.8
22.3
16.7
22.1
1.26
1.07
55.6
49.0
21.9
16.9
21.7
1.43
1.24
55.2
49.2
21.6
16.9
21.4
1.6
1.4
55.3
49.6
20.7
16.5
20.5
1.81
1.62
55.8
50.7
18.6
14.9
18.4
1.98
1.79
58.2
51.4
17.5
14.3
17.3
2.2
2.0
59.0
52.1
15.9
14.1
15.7
2.41
2.23
59.3
53.0
67
(19.4)
23.4
14.1
23.2
1.10
0.91
59.7
54.8
23.7
14.4
23.5
1.26
1.07
59.3
54.6
23.5
14.5
23.3
1.43
1.25
59.2
54.7
23.0
14.4
22.8
1.62
1.44
59.3
55.1
22.2
14.2
22.0
1.83
1.64
59.5
55.5
21.4
14.0
21.2
2.06
1.87
59.7
56.0
20.1
13.6
19.9
2.28
2.10
60.4
56.7
18.7
13.0
18.5
2.52
2.33
61.3
57.5
72
(22.2)
23.8
11.8
23.6
1.10
0.92
63.4
61.1
24.4
12.0
24.2
1.26
1.07
63.1
60.7
24.7
12.1
24.5
1.43
1.25
63.0
60.6
24.6
12.0
24.4
1.63
1.44
63.0
60.7
23.9
11.8
23.7
1.84
1.65
63.4
61.0
17.6
9.1
17.4
1.60
1.41
64.8
62.5
21.9
11.0
21.7
2.30
2.12
64.4
62.0
20.8
10.6
20.6
2.56
2.37
65.0
62.6
Rating condition
LEGEND
BF --CMP --Edb --Ewb --kW --LDB --LWB --SHG --TC --TCG ---
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The SHG is based on 80_F (26.67_C) edb temperature of air
entering indoor coil.
Below 80_F (26.67_C) edb, subtract (corr factor x cfm) from
SHG.
Above 80_F (26.67_C) edb, add (corr factor x cfm) to SHG.
Correction Factor = 1.10 x (1 --- BF) x (edb --- 80).
Bypass Factor
Compressor
Entering Dry Bulb
Entering Wet Bulb
Total Power
Leaving Dry Bulb
Leaving Wet Bulb
Gross Sensible Capacity (1000 Btu/hour)
Total Net Cooling Capacity (1000 Btu/hour)
Gross Cooling Capacity (1000 Btu/hour)
13
40QNC,QNQ/38HDF,QRF
Temp F ( C)
Air Entering
Condenser
(Edb)
40QNC,QNQ/38HDF,QRF
55
(12.8)
65
(18.3)
75
(23.9)
85
(29.4)
95
(35.0)
105
(40.6)
115
(46.1)
125
(51.7)
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
530/0.04
57
(13.9)
26.6
26.0
26.5
1.44
1.25
41.8
39.2
26.4
25.7
26.2
1.63
1.44
42.3
39.4
25.5
24.7
25.4
1.83
1.63
43.8
40.1
24.2
24.2
24.1
2.04
1.84
44.4
41.1
23.1
23.1
22.9
2.27
2.07
46.1
42.0
22.0
22.0
21.9
2.52
2.32
47.7
42.7
20.8
20.8
20.7
2.78
2.59
49.5
43.6
19.3
19.3
19.1
3.07
2.87
51.7
44.7
62
(16.7)
27.8
21.8
27.6
1.45
1.25
48.4
45.4
27.6
22.3
27.4
1.64
1.44
47.5
45.5
26.9
22.3
26.8
1.85
1.65
47.6
46.0
26.1
22.0
25.9
2.07
1.88
47.9
46.6
24.7
21.1
24.5
2.30
2.10
49.2
47.5
23.1
20.2
23.0
2.54
2.34
50.6
48.6
21.5
19.6
21.4
2.80
2.60
51.5
49.6
19.8
18.8
19.7
3.07
2.88
52.6
50.7
67
(19.4)
28.6
17.6
28.5
1.46
1.26
54.8
51.8
28.7
18.1
28.6
1.65
1.45
54.2
51.8
28.2
18.1
28.0
1.86
1.66
54.0
52.1
27.7
18.3
27.6
2.09
1.89
53.7
52.4
27.0
18.2
26.8
2.33
2.14
53.9
52.8
25.8
17.9
25.6
2.60
2.40
54.3
53.5
24.0
17.0
23.9
2.86
2.67
55.6
54.6
22.1
16.1
22.0
3.14
2.94
56.9
55.7
72
(22.2)
29.6
13.8
29.4
1.46
1.26
60.7
58.2
29.8
14.2
29.6
1.65
1.45
60.1
58.1
29.3
14.1
29.1
1.86
1.67
60.3
58.3
28.7
14.0
28.6
2.09
1.90
60.4
58.6
28.1
14.0
27.9
2.34
2.15
60.4
59.0
27.2
13.9
27.0
2.61
2.42
60.5
59.5
25.9
13.6
25.8
2.90
2.70
60.9
60.1
24.2
13.0
24.0
3.19
2.99
61.8
61.0
730/0.05
57
(13.9)
27.6
27.5
27.3
1.45
1.25
48.5
43.2
27.7
27.5
27.4
1.64
1.44
48.5
43.1
27.1
27.1
26.9
1.85
1.65
49.0
43.4
26.5
26.5
26.2
2.08
1.88
49.7
43.8
25.4
25.4
25.2
2.32
2.12
51.0
44.4
24.1
24.1
23.9
2.57
2.38
52.4
45.1
22.7
22.7
22.4
2.84
2.64
54.1
45.9
21.2
21.2
20.9
3.12
2.93
55.8
46.7
62
(16.7)
28.5
22.6
28.2
1.45
1.25
54.4
49.2
28.5
23.6
28.3
1.64
1.45
53.3
49.2
27.8
24.2
27.6
1.85
1.66
52.6
49.5
27.1
24.5
26.8
2.08
1.88
52.3
49.9
26.0
24.6
25.7
2.32
2.13
52.1
50.5
24.4
23.5
24.1
2.57
2.38
53.3
51.2
22.9
22.4
22.6
2.84
2.64
54.7
52.0
21.4
20.7
21.2
3.12
2.93
56.6
52.7
67
(19.4)
29.3
18.4
29.0
1.46
1.26
59.6
55.3
29.5
19.1
29.2
1.65
1.46
58.8
55.2
28.9
19.0
28.6
1.86
1.66
58.9
55.5
28.3
19.4
28.0
2.09
1.89
58.4
55.8
27.3
19.4
27.0
2.31
2.11
58.0
56.1
26.5
19.5
26.2
2.60
2.41
58.2
56.5
25.1
19.2
24.9
2.88
2.69
58.5
57.1
23.3
18.6
23.0
3.18
2.98
59.1
57.9
72
(22.2)
30.4
14.7
30.1
1.46
1.27
64.1
61.3
30.5
15.0
30.3
1.65
1.46
63.7
61.2
30.0
15.0
29.7
1.87
1.67
63.7
61.4
29.3
15.0
29.1
2.10
1.90
63.7
61.7
28.6
14.9
28.3
2.35
2.15
63.8
62.0
17.7
9.2
17.4
1.60
1.40
64.8
62.5
26.4
14.5
26.1
2.90
2.71
64.2
62.8
24.7
14.0
24.4
3.19
3.00
64.8
63.5
Rating condition
LEGEND
BF --CMP --Edb --Ewb --kW --LDB --LWB --SHG --TC --TCG ---
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The SHG is based on 80_F (26.67_C) edb temperature of air
entering indoor coil.
Below 80_F (26.67_C) edb, subtract (corr factor x cfm) from
SHG.
Above 80_F (26.67_C) edb, add (corr factor x cfm) to SHG.
Correction Factor = 1.10 x (1 --- BF) x (edb --- 80).
Bypass Factor
Compressor
Entering Dry Bulb
Entering Wet Bulb
Total Power
Leaving Dry Bulb
Leaving Wet Bulb
Gross Sensible Capacity (1000 Btu/hour)
Total Net Cooling Capacity (1000 Btu/hour)
Gross Cooling Capacity (1000 Btu/hour)
14
55
(12.8)
65
(18.3)
75
(23.9)
85
(29.4)
95
(35.0)
105
(40.6)
115
(46.1)
125
(51.7)
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
600/0.04
57
(13.9)
33.6
31.3
33.4
1.96
1.64
40.0
37.2
32.7
31.2
32.5
2.19
1.87
40.1
37.8
31.6
30.2
31.4
2.44
2.11
41.5
38.6
30.3
29.3
30.1
2.71
2.38
42.6
39.4
29.2
28.2
29.0
3.00
2.68
43.9
40.2
28.1
27.3
27.9
3.32
3.00
45.2
40.9
26.4
26.4
26.2
3.67
3.35
46.3
42.1
24.4
24.4
24.2
4.07
3.74
48.8
43.3
62
(16.7)
34.5
26.1
34.3
1.97
1.65
47.0
43.8
34.9
26.9
34.7
2.21
1.89
45.9
43.5
34.7
27.4
34.5
2.47
2.15
45.4
43.6
33.3
26.7
33.1
2.74
2.41
46.2
44.5
31.7
25.6
31.5
3.04
2.71
47.7
45.5
30.1
24.4
29.9
3.36
3.03
49.1
46.5
28.4
23.5
28.2
3.71
3.38
50.2
47.5
26.2
22.7
26.0
4.08
3.76
51.3
48.8
67
(19.4)
35.2
21.2
35.0
1.98
1.65
53.7
50.5
36.3
22.2
36.1
2.22
1.89
52.4
49.9
36.5
22.9
36.3
2.48
2.16
51.4
49.8
36.0
22.7
35.8
2.78
2.45
51.7
50.1
35.2
22.7
35.0
3.10
2.78
51.7
50.5
33.5
21.8
33.3
3.43
3.10
52.8
51.5
31.4
20.7
31.2
3.78
3.45
54.2
52.6
29.2
19.6
29.0
4.16
3.83
55.5
53.8
72
(22.2)
36.3
16.5
36.1
1.99
1.66
59.9
57.1
37.3
17.0
37.1
2.22
1.89
59.4
56.6
37.6
17.3
37.4
2.49
2.17
58.9
56.4
37.3
17.9
37.1
2.79
2.47
58.2
56.5
36.9
18.1
36.7
3.12
2.79
57.9
56.8
35.9
17.8
35.7
3.47
3.14
58.3
57.2
34.8
17.5
34.6
3.85
3.53
58.6
57.8
33.0
16.9
32.8
4.27
3.95
59.3
58.6
900/0.05
57
(13.9)
34.2
32.2
33.9
1.97
1.64
46.8
41.2
34.5
34.5
34.2
2.21
1.88
44.4
41.1
33.9
33.9
33.6
2.47
2.15
45.0
41.4
33.1
31.7
32.7
2.75
2.42
47.3
41.8
31.3
31.3
31.0
3.05
2.72
47.7
42.7
29.9
29.9
29.5
3.37
3.04
49.2
43.5
28.3
28.3
28.0
3.72
3.39
50.8
44.3
26.4
26.4
26.1
4.09
3.77
52.8
45.3
62
(16.7)
35.4
26.9
35.1
1.97
1.65
52.6
47.4
35.9
28.5
35.6
2.21
1.89
50.9
47.2
35.7
29.2
35.4
2.48
2.15
50.2
47.3
34.9
29.3
34.6
2.77
2.45
50.0
47.6
33.4
28.6
33.1
3.08
2.75
50.7
48.3
31.5
27.5
31.2
3.39
3.07
51.9
49.2
29.6
26.4
29.2
3.74
3.41
53.0
50.1
27.1
25.1
26.8
4.11
3.78
54.4
51.2
67
(19.4)
36.0
22.0
35.6
1.98
1.66
58.0
53.9
36.8
23.1
36.5
2.22
1.89
56.8
53.5
37.2
23.7
36.9
2.49
2.17
56.2
53.3
36.7
24.0
36.4
2.79
2.46
55.9
53.5
36.0
24.0
35.7
3.11
2.78
55.8
53.8
35.1
24.0
34.7
3.46
3.14
55.8
54.2
33.0
23.2
32.7
3.82
3.49
56.6
55.1
30.5
22.1
30.2
4.19
3.87
57.7
56.1
72
(22.2)
37.0
17.6
36.7
1.99
1.66
62.8
60.1
37.8
18.1
37.5
2.23
1.90
62.2
59.8
38.2
18.7
37.9
2.50
2.17
61.6
59.6
37.9
18.7
37.6
2.79
2.47
61.6
59.7
37.4
18.7
37.0
3.12
2.79
61.7
59.9
17.8
9.2
17.4
1.60
1.27
61.6
60.2
35.5
18.5
35.1
3.86
3.54
61.8
60.6
33.8
17.9
33.5
4.28
3.95
62.3
61.2
Rating condition
LEGEND
BF --CMP --Edb --Ewb --kW --LDB --LWB --SHG --TC --TCG ---
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The SHG is based on 80_F (26.67_C) edb temperature of air
entering indoor coil.
Below 80_F (26.67_C) edb, subtract (corr factor x cfm) from
SHG.
Above 80_F (26.67_C) edb, add (corr factor x cfm) to SHG.
Correction Factor = 1.10 x (1 --- BF) x (edb --- 80).
Bypass Factor
Compressor
Entering Dry Bulb
Entering Wet Bulb
Total Power
Leaving Dry Bulb
Leaving Wet Bulb
Gross Sensible Capacity (1000 Btu/hour)
Total Net Cooling Capacity (1000 Btu/hour)
Gross Cooling Capacity (1000 Btu/hour)
15
40QNC,QNQ/38HDF,QRF
Temp F ( C)
Air Entering
Condenser
(Edb)
40QNC,QNQ/38HDF,QRF
55
(12.8)
65
(18.3)
75
(23.9)
85
(29.4)
95
(35.0)
105
(40.6)
115
(46.1)
125
(51.7)
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
460/0.04
57
(13.9)
16.9
15.6
16.6
0.95
0.77
48.9
42.1
16.4
15.5
16.2
1.08
0.89
49.0
42.6
15.8
15.2
15.6
1.21
1.02
49.7
43.1
15.1
15.1
14.9
1.35
1.16
49.9
43.8
14.5
14.5
14.3
1.50
1.32
51.1
44.4
13.8
13.8
13.6
1.67
1.48
52.6
45.2
13.0
13.0
12.8
1.85
1.66
54.1
45.9
12.1
12.1
11.9
2.04
1.85
55.9
46.7
62
(16.7)
17.9
13.3
17.7
0.96
0.78
53.8
47.8
17.5
13.3
17.3
1.08
0.90
53.7
48.1
17.1
13.5
16.9
1.22
1.03
53.4
48.5
16.3
13.1
16.1
1.37
1.18
54.1
49.2
15.4
12.8
15.2
1.52
1.33
54.8
50.0
14.5
12.4
14.3
1.68
1.50
55.5
50.8
13.4
12.0
13.2
1.86
1.67
56.3
51.7
12.4
11.7
12.1
2.04
1.86
56.9
52.6
67
(19.4)
19.3
11.7
19.1
0.96
0.78
57.2
53.3
18.8
11.4
18.6
1.09
0.91
57.8
53.6
18.4
11.4
18.2
1.23
1.04
57.9
54.0
17.8
11.3
17.6
1.38
1.19
58.1
54.5
17.1
11.2
16.9
1.54
1.35
58.3
55.0
16.1
10.8
15.9
1.72
1.53
59.1
55.9
15.0
10.3
14.8
1.90
1.71
60.0
56.7
13.8
9.8
13.6
2.09
1.90
60.9
57.6
72
(22.2)
20.4
10.1
20.2
0.96
0.78
60.8
59.1
20.3
9.9
20.1
1.09
0.91
61.2
59.2
19.9
9.8
19.7
1.23
1.05
61.5
59.5
19.3
9.5
19.1
1.38
1.20
62.1
59.9
18.6
9.2
18.4
1.55
1.36
62.6
60.4
17.7
8.9
17.5
1.73
1.54
63.1
61.0
16.8
8.6
16.6
1.92
1.74
63.7
61.7
15.5
8.2
15.3
2.13
1.94
64.5
62.6
645/0.05
57
(13.9)
17.5
16.2
17.3
0.96
0.78
53.6
44.6
17.3
17.3
17.1
1.08
0.89
51.8
44.8
16.8
16.8
16.6
1.22
1.03
52.5
45.1
16.2
16.2
16.0
1.37
1.18
53.6
45.6
15.5
15.5
15.3
1.52
1.33
54.8
46.2
14.7
14.7
14.5
1.69
1.50
56.0
46.8
13.9
13.9
13.7
1.87
1.68
57.4
47.4
12.9
12.9
12.7
2.06
1.87
58.9
48.1
62
(16.7)
18.6
14.3
18.4
0.96
0.78
57.0
50.2
18.1
14.2
17.9
1.09
0.90
57.1
50.5
17.6
14.3
17.4
1.22
1.04
57.0
50.9
17.0
14.3
16.8
1.37
1.19
56.9
51.3
16.0
13.9
15.8
1.53
1.34
57.5
52.0
15.1
13.7
14.9
1.69
1.51
57.9
52.6
14.1
13.3
13.9
1.87
1.69
58.5
53.3
13.0
13.0
12.8
2.06
1.87
59.0
54.1
67
(19.4)
19.8
12.2
19.6
0.97
0.79
60.7
55.7
19.6
12.4
19.4
1.09
0.90
60.3
55.9
19.0
12.0
18.8
1.23
1.04
60.9
56.3
18.4
12.0
18.2
1.38
1.19
60.9
56.6
17.6
11.9
17.4
1.54
1.36
61.2
57.1
16.7
11.6
16.5
1.72
1.54
61.5
57.7
15.5
11.2
15.3
1.91
1.72
62.2
58.4
14.2
10.7
14.0
2.10
1.91
63.0
59.2
Rating condition
Not recommended for long---term operation.
LEGEND
BF --CMP --Edb --Ewb --kW --LDB --LWB --SHG --TC --TCG ---
Bypass Factor
Compressor
Entering Dry Bulb
Entering Wet Bulb
Total Power
Leaving Dry Bulb
Leaving Wet Bulb
Gross Sensible Capacity (1000 Btu/hour)
Total Net Cooling Capacity (1000 Btu/hour)
Gross Cooling Capacity (1000 Btu/hour)
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The SHG is based on 80_F (26.67_C) edb temperature of air
entering indoor coil.
Below 80_F (26.67_C) edb, subtract (corr factor x cfm) from SHG.
Above 80_F (26.67_C) edb, add (corr factor x cfm) to SHG.
Correction Factor = 1.10 x (1 --- BF) x (edb --- 80).
16
72
(22.2)
20.7
10.4
20.5
0.96
0.78
63.8
61.6
20.8
10.2
20.6
1.10
0.91
64.2
61.6
20.5
10.1
20.3
1.24
1.05
64.3
61.7
20.0
10.1
19.8
1.39
1.20
64.4
62.0
19.2
9.8
19.0
1.56
1.37
64.8
62.4
18.3
9.4
18.1
1.73
1.55
65.5
63.0
17.3
9.1
17.0
1.93
1.74
65.9
63.5
16.1
8.7
15.8
2.13
1.94
66.5
64.2
55
(12.8)
65
(18.3)
75
(23.9)
85
(29.4)
95
(35.0)
105
(40.6)
115
(46.1)
125
(51.7)
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
460/0.04
57
(13.9)
21.3
19.2
21.1
1.11
0.93
41.8
37.4
19.6
17.4
19.4
1.26
1.08
45.4
39.2
19.1
17.4
18.9
1.42
1.23
45.4
39.8
18.5
17.1
18.2
1.59
1.40
45.9
40.4
17.7
16.7
17.5
1.78
1.59
46.7
41.2
16.9
16.1
16.7
1.99
1.80
47.8
42.0
15.8
15.8
15.6
2.20
2.02
48.6
43.2
14.8
14.8
14.6
2.45
2.26
50.5
44.1
62
(16.7)
22.3
16.3
22.1
1.12
0.93
47.9
43.6
21.8
16.0
21.6
1.28
1.09
48.6
44.1
21.2
15.8
21.0
1.45
1.27
48.9
44.7
20.1
15.3
19.9
1.62
1.44
49.8
45.7
19.3
15.0
19.1
1.81
1.63
50.4
46.5
18.3
14.6
18.1
2.01
1.83
51.3
47.4
17.2
14.2
17.0
2.24
2.05
52.0
48.4
15.9
13.7
15.7
2.47
2.28
52.9
49.6
67
(19.4)
23.5
13.9
23.3
1.13
0.95
53.1
49.7
23.5
14.2
23.3
1.28
1.09
52.4
49.7
22.3
13.0
22.0
1.46
1.27
54.9
50.8
22.8
14.3
22.6
1.65
1.46
52.2
50.3
21.9
14.0
21.7
1.86
1.68
52.8
51.1
20.2
12.8
20.0
2.07
1.88
55.2
52.5
19.1
12.3
18.9
2.29
2.11
56.0
53.5
17.8
11.9
17.6
2.53
2.34
57.0
54.5
72
(22.2)
25.0
12.3
24.8
1.12
0.94
56.5
55.7
25.5
12.6
25.3
1.28
1.09
55.9
55.3
24.7
12.1
24.5
1.46
1.27
57.0
55.9
24.3
11.6
24.1
1.66
1.47
57.9
56.2
23.6
11.3
23.4
1.86
1.68
58.5
56.8
22.7
11.2
22.5
2.09
1.91
58.8
57.4
21.8
10.8
21.6
2.34
2.15
59.4
58.1
20.4
10.4
20.2
2.60
2.42
60.1
59.2
645/0.05
57
(13.9)
22.1
20.1
21.8
1.12
0.93
46.6
40.5
21.7
20.7
21.5
1.27
1.08
45.6
40.9
20.2
18.8
20.0
1.44
1.25
48.9
42.1
19.5
18.4
19.3
1.61
1.43
49.4
42.7
18.9
17.9
18.7
1.80
1.62
50.4
43.2
17.5
17.5
17.3
2.09
1.90
51.0
44.4
16.9
16.9
16.7
2.23
2.04
51.9
44.8
16.0
16.0
15.7
2.47
2.28
53.6
45.6
62
(16.7)
23.3
17.5
23.1
1.12
0.93
51.3
46.4
22.8
17.0
22.6
1.29
1.10
52.1
46.8
22.4
17.3
22.2
1.45
1.27
51.7
47.1
21.8
17.8
21.6
1.65
1.46
50.8
47.5
20.2
16.3
20.0
1.83
1.65
53.3
48.7
19.1
15.9
18.9
2.04
1.85
53.9
49.6
17.9
15.5
17.7
2.26
2.07
54.5
50.4
16.6
15.1
16.4
2.49
2.31
55.1
51.4
67
(19.4)
24.6
15.0
24.4
1.12
0.94
55.8
52.3
24.8
15.4
24.6
1.28
1.09
55.2
52.2
24.1
14.7
23.9
1.46
1.28
56.2
52.7
23.5
14.8
23.3
1.65
1.47
56.1
53.0
22.4
14.4
22.2
1.95
1.77
56.3
53.6
21.8
14.6
21.5
2.09
1.91
56.3
54.2
20.5
14.2
20.3
2.34
2.15
56.9
55.1
18.5
12.8
18.3
2.56
2.37
59.3
56.4
Rating condition
LEGEND
BF --CMP --Edb --Ewb --kW --LDB --LWB --SHG --TC --TCG ---
Bypass Factor
Compressor
Entering Dry Bulb
Entering Wet Bulb
Total Power
Leaving Dry Bulb
Leaving Wet Bulb
Gross Sensible Capacity (1000 Btu/hour)
Total Net Cooling Capacity (1000 Btu/hour)
Gross Cooling Capacity (1000 Btu/hour)
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The SHG is based on 80_F (26.67_C) edb temperature of air
entering indoor coil.
Below 80_F (26.67_C) edb, subtract (corr factor x cfm) from SHG.
Above 80_F (26.67_C) edb, add (corr factor x cfm) to SHG.
Correction Factor = 1.10 x (1 --- BF) x (edb --- 80).
17
72
(22.2)
25.0
12.4
24.8
1.13
0.94
60.4
58.8
25.3
12.3
25.1
1.30
1.11
60.5
58.6
25.7
12.6
25.5
1.46
1.28
60.0
58.4
25.4
12.5
25.2
1.66
1.47
60.1
58.6
24.7
12.1
24.5
1.87
1.68
60.8
59.0
23.5
11.6
23.3
2.09
1.91
61.6
59.7
22.2
11.1
22.0
2.33
2.15
62.5
60.5
21.0
10.9
20.8
2.60
2.41
62.7
61.2
40QNC,QNQ/38HDF,QRF
Temp F ( C)
Air Entering
Condenser
(Edb)
40QNC,QNQ/38HDF,QRF
55
(12.8)
65
(18.3)
75
(23.9)
85
(29.4)
95
(35.0)
105
(40.6)
115
(46.1)
125
(51.7)
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
530/0.04
57
(13.9)
25.9
25.9
25.7
1.47
1.27
42.0
39.8
26.0
25.5
25.9
1.65
1.46
42.5
39.7
25.2
24.6
25.0
1.85
1.66
43.9
40.4
24.0
24.0
23.8
2.05
1.86
44.8
41.3
22.9
22.9
22.8
2.28
2.08
46.4
42.1
21.7
21.7
21.6
2.53
2.33
48.1
43.0
20.4
20.4
20.3
2.79
2.60
50.0
43.9
19.0
19.0
18.8
3.08
2.89
52.2
45.0
62
(16.7)
26.7
20.4
26.5
1.48
1.28
50.4
46.2
27.1
21.9
27.0
1.66
1.46
48.1
45.9
26.8
22.2
26.6
1.86
1.66
47.7
46.1
25.8
21.8
25.6
2.08
1.89
48.2
46.8
24.4
21.0
24.2
2.31
2.11
49.4
47.7
22.8
20.3
22.7
2.55
2.35
50.5
48.8
21.0
19.5
20.9
2.81
2.61
51.6
49.9
19.2
18.5
19.1
3.09
2.89
53.1
51.1
67
(19.4)
27.4
16.8
27.2
1.48
1.28
55.9
52.6
28.0
17.4
27.9
1.66
1.47
55.1
52.2
27.9
18.0
27.8
1.87
1.67
54.3
52.2
27.7
18.4
27.5
2.09
1.90
53.6
52.4
27.0
18.3
26.9
2.34
2.14
53.7
52.8
25.4
17.6
25.3
2.60
2.41
54.7
53.7
23.6
16.7
23.5
2.86
2.67
56.0
54.8
21.6
15.9
21.5
3.15
2.95
57.2
56.0
72
(22.2)
28.3
13.0
28.1
1.48
1.28
61.9
58.9
28.9
13.6
28.7
1.66
1.47
61.0
58.6
28.9
13.9
28.7
1.87
1.67
60.5
58.5
28.8
14.0
28.6
2.10
1.90
60.4
58.6
28.4
14.3
28.2
2.35
2.15
59.9
58.8
27.7
14.3
27.5
2.62
2.43
59.9
59.2
26.5
14.0
26.3
2.91
2.72
60.3
59.8
24.4
13.2
24.3
3.23
3.03
61.4
60.9
730/0.05
57
(13.9)
26.7
26.7
26.4
1.47
1.28
49.7
43.7
27.2
27.2
27.0
1.66
1.46
49.0
43.4
27.0
27.0
26.7
1.86
1.66
49.3
43.5
26.4
26.4
26.1
2.08
1.89
50.0
43.9
25.2
25.2
24.9
2.32
2.13
51.4
44.6
23.3
23.3
23.0
2.67
2.47
53.5
45.6
22.4
22.4
22.1
2.83
2.64
54.5
46.1
20.8
20.8
20.5
3.13
2.93
56.4
47.0
62
(16.7)
27.3
21.4
27.1
1.48
1.28
56.0
49.8
27.9
22.9
27.6
1.66
1.46
54.2
49.6
27.7
24.1
27.4
1.86
1.67
52.8
49.7
27.1
24.7
26.8
2.09
1.89
52.2
49.9
25.6
24.4
25.3
2.33
2.13
52.4
50.7
24.0
23.3
23.8
2.57
2.37
53.7
51.4
22.5
22.2
22.3
2.84
2.64
55.0
52.2
21.0
20.5
20.7
3.13
2.93
56.8
52.9
67
(19.4)
28.1
17.2
27.8
1.48
1.28
61.0
55.9
28.6
18.5
28.3
1.66
1.47
59.5
55.7
28.6
18.9
28.3
1.87
1.67
59.0
55.7
28.4
19.6
28.1
2.10
1.90
58.2
55.8
27.3
19.6
27.0
2.31
2.12
57.7
56.0
26.8
20.0
26.6
2.61
2.42
57.7
56.4
24.8
19.2
24.6
2.89
2.70
58.7
57.3
22.7
18.2
22.4
3.18
2.98
59.7
58.2
72
(22.2)
28.9
14.0
28.6
1.48
1.29
64.9
61.9
29.5
14.4
29.3
1.67
1.47
64.5
61.7
29.6
14.8
29.3
1.87
1.68
64.0
61.6
29.3
15.1
29.0
2.10
1.91
63.6
61.8
29.0
15.1
28.7
2.35
2.16
63.6
61.9
17.7
9.2
17.4
1.60
1.40
63.4
62.1
27.2
15.1
26.9
2.92
2.72
63.5
62.6
25.5
14.8
25.3
3.23
3.04
63.9
63.2
Rating condition
Not recommended for long---term operation.
LEGEND
BF --CMP --Edb --Ewb --kW --LDB --LWB --SHG --TC --TCG ---
Bypass Factor
Compressor
Entering Dry Bulb
Entering Wet Bulb
Total Power
Leaving Dry Bulb
Leaving Wet Bulb
Gross Sensible Capacity (1000 Btu/hour)
Total Net Cooling Capacity (1000 Btu/hour)
Gross Cooling Capacity (1000 Btu/hour)
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The SHG is based on 80_F (26.67_C) edb temperature of air
entering indoor coil.
Below 80_F (26.67_C) edb, subtract (corr factor x cfm) from SHG.
Above 80_F (26.67_C) edb, add (corr factor x cfm) to SHG.
Correction Factor = 1.10 x (1 --- BF) x (edb --- 80).
18
55
(12.8)
65
(18.3)
75
(23.9)
85
(29.4)
95
(35.0)
105
(40.6)
115
(46.1)
125
(51.7)
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
TCG
SHG
TC
kW
CMP
LDB
LWB
600/0.04
57
(13.9)
31.0
30.0
30.8
1.89
1.56
39.0
37.5
30.2
29.2
30.0
2.11
1.79
40.1
38.0
29.2
28.4
29.0
2.35
2.03
41.1
38.8
28.0
27.4
27.8
2.61
2.28
42.5
39.7
26.9
26.2
26.7
2.90
2.57
44.2
40.5
25.3
25.3
25.1
3.20
2.88
45.4
41.6
23.9
23.9
23.7
3.54
3.21
47.4
42.6
22.2
22.2
22.0
3.91
3.58
49.6
43.7
62
(16.7)
32.5
25.1
32.3
1.90
1.57
46.0
43.6
32.5
25.7
32.3
2.13
1.80
45.2
43.6
31.8
25.5
31.6
2.38
2.06
45.4
44.1
30.4
24.8
30.2
2.66
2.33
46.4
45.0
28.9
24.0
28.7
2.94
2.62
47.5
46.0
27.2
23.0
27.0
3.24
2.92
48.8
47.1
25.3
22.1
25.1
3.57
3.25
50.1
48.3
23.0
21.1
22.8
3.93
3.60
51.3
49.7
67
(19.4)
33.5
20.4
33.3
1.91
1.58
52.9
50.2
34.0
21.2
33.8
2.14
1.81
51.7
49.9
33.6
21.4
33.4
2.39
2.07
51.4
50.1
33.0
21.2
32.8
2.68
2.35
51.6
50.5
32.0
21.0
31.8
2.99
2.66
52.0
51.1
30.2
20.1
30.0
3.32
2.99
53.1
52.1
28.2
19.3
28.0
3.66
3.33
54.3
53.2
26.0
18.2
25.8
4.01
3.69
55.6
54.5
72
(22.2)
34.6
15.9
34.4
1.91
1.58
59.3
56.7
35.1
16.2
34.9
2.14
1.82
58.8
56.5
35.1
16.8
34.9
2.40
2.08
58.1
56.4
34.5
16.9
34.3
2.69
2.36
57.9
56.7
33.8
16.8
33.6
3.00
2.68
58.0
57.1
32.7
16.5
32.6
3.34
3.02
58.4
57.6
31.2
16.1
31.0
3.70
3.38
59.0
58.4
29.3
15.3
29.1
4.09
3.76
59.9
59.4
900/0.05
57
(13.9)
32.0
32.0
31.8
1.90
1.57
44.4
41.1
32.1
32.1
31.9
2.12
1.80
44.4
41.1
31.6
30.6
31.4
2.38
2.05
46.1
41.4
30.0
30.0
29.9
2.65
2.32
46.7
42.2
28.8
28.8
28.6
2.94
2.61
48.1
43.0
27.4
27.4
27.2
3.25
2.92
49.7
43.7
25.8
25.8
25.6
3.59
3.26
51.4
44.6
24.0
24.0
23.9
3.96
3.63
53.4
45.5
62
(16.7)
33.2
25.9
33.0
1.90
1.58
51.6
47.3
33.3
27.3
33.2
2.13
1.81
50.0
47.2
32.8
27.6
32.6
2.39
2.06
49.7
47.5
31.9
27.5
31.7
2.67
2.34
49.7
47.9
30.2
26.6
30.0
2.97
2.64
50.7
48.8
28.4
25.7
28.2
3.28
2.95
51.7
49.7
26.3
24.9
26.1
3.60
3.27
52.6
50.7
24.2
23.7
24.0
3.96
3.64
53.9
51.7
67
(19.4)
34.1
21.3
33.9
1.91
1.58
57.0
53.6
34.5
21.9
34.3
2.14
1.82
56.3
53.4
34.5
22.5
34.3
2.40
2.07
55.6
53.4
33.7
22.6
33.5
2.68
2.36
55.6
53.7
32.8
22.5
32.6
2.99
2.67
55.6
54.1
31.5
22.2
31.4
3.33
3.00
55.9
54.7
29.4
21.3
29.2
3.68
3.36
56.9
55.7
27.0
20.3
26.8
4.05
3.72
57.9
56.7
72
(22.2)
35.2
16.9
35.0
1.91
1.59
62.2
59.8
35.6
17.4
35.4
2.15
1.82
61.6
59.6
35.7
17.6
35.5
2.41
2.08
61.4
59.6
35.1
17.5
34.9
2.69
2.37
61.4
59.8
34.4
17.6
34.2
3.01
2.68
61.4
60.1
33.4
17.4
33.2
3.35
3.02
61.5
60.5
31.9
17.0
31.7
3.71
3.39
62.0
61.0
30.0
16.4
29.8
4.10
3.77
62.6
61.8
Rating condition
LEGEND
BF --CMP --Edb --Ewb --kW --LDB --LWB --SHG --TC --TCG ---
Bypass Factor
Compressor
Entering Dry Bulb
Entering Wet Bulb
Total Power
Leaving Dry Bulb
Leaving Wet Bulb
Gross Sensible Capacity (1000 Btu/hour)
Total Net Cooling Capacity (1000 Btu/hour)
Gross Cooling Capacity (1000 Btu/hour)
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The SHG is based on 80_F (26.67_C) edb temperature of air
entering indoor coil.
Below 80_F (26.67_C) edb, subtract (corr factor x cfm) from SHG.
Above 80_F (26.67_C) edb, add (corr factor x cfm) to SHG.
Correction Factor = 1.10 x (1 --- BF) x (edb --- 80).
19
40QNC,QNQ/38HDF,QRF
Temp F ( C)
Air Entering
Condenser
(Edb)
65 (18.3)
60 (15.6)
55 (12.8)
Air Temperature
Entering Indoor
Unit F ( C)
20
Total Power Input, includes compressor motor power input, outdoor fan motor power input, and indoor fan motor power input
kW ---
17 ( --- 8.3)
Instant.
Integrated
Rating
Rating
10.77
9.82
1.20
10.81
9.86
1.19
10.92
9.95
1.14
10.54
9.61
1.25
10.64
9.70
1.23
10.74
9.79
1.20
10.31
9.40
1.30
10.43
9.51
1.28
10.63
9.69
1.24
10.08
9.19
1.36
10.18
9.28
1.34
10.40
9.48
1.29
9.79
8.66
1.41
9.89
8.89
1.39
10.12
9.23
1.35
9.47
8.64
1.47
9.58
8.74
1.45
9.82
8.66
1.41
Cap ---
645
525
460
645
525
460
645
525
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Item
16.48
16.05
15.64
16.73
16.35
16.05
17.00
16.64
16.35
17.26
16.91
16.64
17.53
17.17
16.92
17.80
17.43
Instant.
Rating
17.20
40QNC,QNQ/38HDF,QRF
Note: Integrated Capacity is maximum (instantaneous ) capacity less the effect of frost on the outdoor coil and the heat to defrost it.
80 (26.7)
75 (23.9)
70 (21.1)
460
645
525
460
645
525
460
645
525
460
Indoor
Airflow
(CFM)
L --- M--- H
20
47 (8.3)
Integrated
Rating
17.20
1.53
17.43
1.45
17.80
1.37
16.92
1.60
17.17
1.52
17.53
1.44
16.64
1.68
16.91
1.60
17.26
1.51
16.35
1.76
16.64
1.68
17.00
1.56
16.05
1.84
16.35
1.75
16.73
1.66
15.64
1.98
16.05
1.89
16.48
1.76
19.72
19.19
18.75
20.06
19.55
19.07
20.43
19.90
19.50
20.81
20.26
19.87
21.19
20.63
20.21
21.53
20.99
Instant.
Rating
20.58
57 (13.9)
Integrated
Rating
20.58
1.71
20.99
1.62
21.53
1.51
20.21
1.72
20.63
1.70
21.19
1.58
19.87
1.80
20.26
1.76
20.81
1.64
19.50
1.93
19.90
1.82
20.43
1.72
19.07
2.04
19.55
1.89
20.06
1.76
18.75
2.09
19.19
1.99
19.72
1.85
21
12.47
12.16
11.97
12.86
12.56
12.37
13.21
12.93
12.74
13.52
13.26
13.08
13.78
13.56
13.40
14.01
13.81
Instant.
Rating
13.68
1.84
1.89
1.93
1.76
1.82
1.85
1.68
1.75
1.78
1.61
1.67
1.71
1.54
1.60
1.63
1.48
1.53
1.56
8.66
11.09
10.91
11.72
8.89
8.66
12.04
11.79
11.61
12.33
12.09
11.93
12.57
12.36
12.22
12.77
12.59
Integrated
Rating
12.48
13.82
13.57
13.36
14.07
13.84
13.70
14.29
14.09
13.96
14.50
14.31
14.19
14.74
14.51
14.41
14.97
14.79
18.13
17.75
17.59
18.42
18.04
17.91
18.75
18.37
18.19
19.04
18.69
18.45
19.31
18.99
18.68
19.53
19.25
Instant.
Rating
19.01
2.15
2.24
2.26
2.05
2.17
2.20
1.96
2.09
2.13
1.86
1.98
2.05
1.77
1.89
1.97
1.69
1.79
1.87
16.50
16.16
16.01
16.76
8.89
8.66
17.06
16.72
16.55
17.32
17.01
16.79
17.57
17.28
17.00
17.78
17.52
Integrated
Rating
17.30
37 (2.8)
21.57
21.00
20.43
21.71
21.40
20.76
22.01
21.55
21.10
22.29
21.88
21.49
22.54
22.17
21.80
22.86
22.44
Instant.
Rating
22.17
40QNC,QNQ/38HDF,QRF
Total Power Input, includes compressor motor power input, outdoor fan motor power input, and indoor fan motor power input
1.92
1.98
2.03
1.86
1.91
1.95
1.79
1.85
1.88
1.73
1.79
1.82
1.66
1.73
1.76
1.59
1.64
1.69
Integrated
Rating
14.64
kW ---
15.56
15.28
15.04
15.84
15.58
15.42
16.09
15.86
15.72
16.32
16.11
15.98
16.59
16.33
16.22
16.85
16.65
Instant.
Rating
16.49
27 ( --- 2.8)
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Item
17 ( --- 8.3)
Cap ---
645
525
460
645
525
460
645
525
460
645
525
460
645
525
460
645
525
460
Indoor
Airflow
(CFM)
L --- M--- H
Note: Integrated Capacity is maximum (instantaneous ) capacity less the effect of frost on the outdoor coil and the heat to defrost it.
80 (26.7)
75 (23.9)
70 (21.1)
65 (18.3)
60 (15.6)
55 (12.8)
Air Temperature
Entering Indoor
Unit F ( C)
2.35
2.50
2.58
2.22
2.35
2.46
2.15
2.29
2.37
2.03
2.19
2.28
1.93
2.07
2.19
1.83
1.96
2.07
21.57
21.00
20.43
21.71
21.40
20.76
22.01
21.55
21.10
22.29
21.88
21.49
22.54
22.17
21.80
22.86
22.44
Integrated
Rating
22.17
47 (8.3)
24.21
23.41
23.10
24.63
23.74
23.64
25.02
24.31
23.60
25.51
24.81
24.27
25.88
25.28
24.72
26.24
25.66
Instant.
Rating
25.24
2.50
2.61
2.69
2.50
2.71
2.82
2.35
2.55
2.74
2.26
2.36
2.53
2.13
2.31
2.37
2.03
2.21
2.30
24.21
23.41
23.10
24.63
23.74
23.64
25.02
24.31
23.60
25.51
24.81
24.27
25.88
25.28
24.72
26.24
25.66
Integrated
Rating
25.24
57 (13.9)
65 (18.3)
60 (15.6)
55 (12.8)
Air Temperature
Entering Indoor
Unit F ( C)
22
Total Power Input, includes compressor motor power input, outdoor fan motor power input, and indoor fan motor power input
kW ---
17 ( --- 8.3)
Instant.
Integrated
Rating
Rating
16.73
15.25
1.95
16.92
15.43
1.88
17.18
15.67
1.82
16.44
14.99
2.03
16.61
15.14
1.98
16.81
15.33
1.94
16.20
14.77
2.09
16.40
14.95
2.04
16.48
15.02
2.02
15.75
14.36
2.20
15.91
14.50
2.16
16.29
14.85
2.07
15.39
8.66
2.28
15.63
8.89
2.23
15.86
14.46
2.17
14.94
13.63
2.36
15.25
13.90
2.31
15.53
8.66
2.25
Cap ---
830
700
600
830
700
600
830
700
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Item
27.42
27.01
26.57
27.83
27.47
27.05
28.21
27.88
27.47
28.64
28.26
27.86
29.06
28.67
28.26
29.48
29.09
Instant.
Rating
28.76
40QNC,QNQ/38HDF,QRF
Note: Integrated Capacity is maximum (instantaneous ) capacity less the effect of frost on the outdoor coil and the heat to defrost it.
80 (26.7)
75 (23.9)
70 (21.1)
600
830
700
600
830
700
600
830
700
600
Indoor
Airflow
(CFM)
L --- M--- H
22
47 (8.3)
Integrated
Rating
28.76
2.47
29.09
2.34
29.48
2.24
28.26
2.56
28.67
2.45
29.06
2.35
27.86
2.68
28.26
2.57
28.64
2.47
27.47
2.81
27.88
2.70
28.21
2.58
27.05
2.94
27.47
2.84
27.83
2.72
26.57
3.09
27.01
2.98
27.42
2.85
30.94
30.44
29.91
31.41
30.94
30.40
31.89
31.40
30.89
32.43
31.90
31.39
32.90
32.41
31.88
33.42
32.90
Instant.
Rating
32.29
57 (13.9)
Integrated
Rating
32.29
2.57
32.90
2.43
33.42
2.31
31.88
2.68
32.41
2.55
32.90
2.43
31.39
2.80
31.90
2.67
32.43
2.55
30.89
2.93
31.40
2.80
31.89
2.66
30.40
3.06
30.94
2.93
31.41
2.79
29.91
3.20
30.44
3.07
30.94
2.93
23
34.78
34.26
33.32
35.25
34.74
33.81
35.61
35.20
34.29
36.07
35.55
34.78
36.54
35.99
35.20
37.00
36.46
Instant.
Rating
35.71
40QNC,QNQ/38HDF,QRF
Total Power Input, includes compressor motor power input, outdoor fan motor power input, and indoor fan motor power input
kW ---
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Cap
kW
Item
17 ( --- 8.3)
Instant.
Integrated
Rating
Rating
22.09
20.14
2.62
22.74
20.73
2.48
23.03
21.00
2.39
21.64
19.73
2.73
22.22
20.26
2.60
22.59
20.59
2.51
21.23
19.36
2.82
21.71
19.79
2.72
22.11
20.16
2.63
20.72
18.89
2.92
21.15
19.28
2.84
21.59
19.69
2.75
20.18
8.66
3.03
20.64
8.89
2.94
20.99
19.14
2.87
19.61
17.88
3.13
20.12
18.34
3.04
20.49
8.66
2.97
Cap ---
930
775
620
930
775
620
930
775
620
930
775
620
930
775
620
930
775
620
Indoor
Airflow
(CFM)
L --- M--- H
Note: Integrated Capacity is maximum (instantaneous ) capacity less the effect of frost on the outdoor coil and the heat to defrost it.
80 (26.7)
75 (23.9)
70 (21.1)
65 (18.3)
60 (15.6)
55 (12.8)
Air Temperature
Entering Indoor
Unit F ( C)
39.48
38.75
37.62
40.06
39.34
38.21
40.61
39.91
38.79
41.17
40.46
39.36
41.93
40.98
39.89
42.46
41.74
Instant.
Rating
40.41
57 (13.9)
Integrated
Rating
40.41
3.77
41.74
3.49
42.46
3.29
39.89
3.90
40.98
3.62
41.93
3.43
39.36
4.05
40.46
3.77
41.17
3.56
38.79
4.20
39.91
3.92
40.61
3.72
38.21
4.35
39.34
4.08
40.06
3.88
37.62
4.49
38.75
4.24
39.48
4.04
APPLICATION DATA
UNIT SELECTION
The horizontal units are available as cooling only and heat pumps.
For most applications, the cooling load dictates the size selection.
Select equipment to either match or be slightly less than anticipated
peak load. This provides better humidity control, fewer unit cycles,
and better low load performance.
For units used in spaces with high sensible loads, base equipment
selection on unit sensible load, not on total anticipated load to
avoid oversizing the equipment.
4QNC,QNQ/38HDF,QRF
125 (51.7)
--- ---
55 (12.8)
--- ---
90 (32.2)
74 (23.3)
62 (17.0)
56 (13)
Minimum
DB F ( C)
WB F ( C)
Outdoor
Unit
Indoor
Unit
Minimum
DB F ( C)
WB F ( C)
75 (23.9)
67 (19.4)
17 ( ---8.3)
--- ---
81 (27.2)
--- ---
62 (17.0)
--- ---
Metering Devices
An Accurator installed at the outdoor unit is used as a metering
device. This requires that both refrigerant lines must be insulated.
(A heat pump unit has 2 AccuRaters.)
DRAIN CONNECTIONS
For ease of installation, the drains on the 40QNC/QNQ units can
be connected form either the back--left or back--right as shown in
Fig. 11.
Drain Cap
Drain Hose
A08362
24
A08358A
CONTROL SYSTEM
The 40QNC,QNQ unit is equipped with a microprocessor controls
to operate the system and provide optimum levels of comfort and
operating efficiency.
The main microprocessor is located in the control box of the fan
coil unit with thermistors located in the fan coil inlet and on the
indoor coil. These thermistors monitor the system operation and
control the operating mode. To change the settings or the modes of
operation, use the factory supplied wireless remote control or
accessory wired controller or Zone Manager.
The 40QNC,QNQ unit has 5 operating modes:
S Fan Only
S Auto (heat pump models only)
S Heating (heat pump models only)
S Cooling
S Dehumidification (Dry)
FAN ONLY -- In Fan Only mode, the system filters and circulates
the room air without changing the room air temperature.
USER INTERFACE
The units come standard with a wireless remote control. The
wireless remote has a range of 25 ft (8 m) when pointed toward the
unit.
For some applications (commercial), a wired remote may be more
desirable. A wired remote control is offered as an accessory.
For applications that have multiple units, these controls offer
additional flexibility
Zoning
For applications that require zoning, the Zone Manager is offered
as an accessory. This will allow up to 32 units to be connected in
up to 8 zones. Each zone can be programmed for 7 days with each
day having 4 periods.
AIRTHROW DATA
Unit Size
018
024
030
036
25
High
Speed
35 (10.7)
35 (10.7)
40 (12.2)
50 (15.2)
Low
Speed
25 (7.6)
25 (7.6)
27 (8.2)
30 (9.1)
4QNC,QNQ/38HDF,QRF
REFRIGERANT LINES
SOUND RATINGS
Outdoor Units
Model Number
38HDF018 --- --- ---3
38HDF024 --- --- ---3
38HDF030 --- --- ---3
38HDF036 --- --- ---3/5/6
38QRF018 --- --- ---3
38QRF024 --- --- ---3
38QRF030 --- --- ---3
38QRF036 --- --- ---3/5/6
Indoor Units
4QNC,QNQ/38HDF,QRF
High
Medium
Low
Model Number
Sound Power
dBa
Sound Pressure
dBa
Sound Power
dBa
Sound Pressure
dBa
Sound Power
dBa
Sound Pressure
dBa
59
60
62
59/60 (Clg/Htg)
59/60 (Clg/Htg)
60/61(Clg/Htg)
62/63 (Clg/Htg)
48
49
51
48/49 (Clg/Htg)
48/49 (Clg/Htg)
49/50 (Clg/Htg)
51/52 (Clg/Htg)
53
57
60
53/54 (Clg/Htg)
53/54 (Clg/Htg)
57/58 (Clg/Htg)
60/61 (Clg/Htg)
42
46
49
42/43 (Clg/Htg)
42/43 (Clg/Htg)
46/47 (Clg/Htg)
49/50 (Clg/Htg)
49
53
57
49/50 (Clg/Htg)
49/50 (Clg/Htg)
53/55 (Clg/Htg)
57/58 (Clg/Htg)
38
5
46
38/39 (Clg/Htg)
38/39 (Clg/Htg)
42/44 (Clg/Htg)
46/47 (Clg/Htg)
NOTES:
1. Sound power ratings are tested in accordance with ARI standard 270 --- --- ---95 (not listed in ARI) and ARI 350.
2. Sound pressure ratings are estimated sound pressure, 3 feet (.91 m) from the unit, based on sound power data.
WIRING
The indoor and outdoor units have their own power supply. Low voltage control wires run between the indoor and outdoor units. Two wires
are required for cooling only systems and seven wires are required for heat pumps.
ELECTRICAL DATA
38HDF/38QRF ELECTRICAL DATA
38HDF/38QRF
UNIT SIZE
018
024
030
036
V--- PH --- Hz
208/230 ---1 ---60
208/230 ---1 ---60
208/230 ---1 ---60
208/230 ---1 ---60
208/230 ---3 ---60
460 ---3 ---60
COMPRESSOR
VOLTAGE RANGE*
Min
Max
RLA
LRA
FLA
NEC Hp
kW Out
MIN CKT
AMPS
187
187
187
187
187
414
253
253
253
253
253
506
9.0
12.8
14.1
17.9
13.2
6.0
48.0
58.3
73.0
112.0
88.0
44.0
0.80
0.80
1.50
1.45
1.45
0.80
0.125
0.125
0.25
0.25
0.25
0.25
0.09
0.09
0.19
0.19
0.19
0.19
12.1
16.8
18.4
23.8
18.0
8.3
FUSE/
CKT
BKR
AMPS
20
25
30
40
30
15
V--- PH --- Hz
40QNC01824
40QNC030
40QNC036
40QNQ018
40QNQ024
40QNQ030
40QNQ036
FAN
Min
Max
FLA
187
187
187
187
187
187
187
253
253
253
253
253
253
253
0.38
0.38
0.44
0.38
0.38
0.38
0.44
POWER
Motor Power
(Watts)
64
74
74
64
64
74
74
MIN CKT
AMPS
0.48
0.48
0.55
0.48
0.48
0.48
0.55
FUSE/CKT
BKR AMPS
15
15
15
15
15
15
15
*Permissible limits of the voltage range at which unit will operate satisfactorily.
FLA
MCA
NEC
RLA
---------
LEGEND
Full Load Amps
Minimum Circuit Amps per NEC Section 430 ---24
National Electrical Code
Rated Load Amps (Compressor)
NOTES:
1. In compliance with NEC requirements for multi---motor and combination
load equipment (refer to NEC Articles 430 and 440), the overcurrent
protective device for the unit shall be fuse or equipped with a breaker.
2. Motor RLA values are established in accordance with UL (Underwriters
Laboratories) Standard 465.
26
4QNC,QNQ/38HDF,QRF
A11239
27
4QNC,QNQ/38HDF,QRF
A11240
28
4QNC,QNQ/38HDF,QRF
A11238
29
4QNC,QNQ/38HDF,QRF
A11241
30
GUIDE SPECIFICATIONS
INDOOR WALL--MOUNTED
DUCT--FREE UNITS
PART 1 -- GENERAL
1.01 System Description
Indoor, wall--mounted, direct--expansion fan coils are matched with
cooling only or heat pump outdoor unit .
1.04 Warranty
1--year parts limited warranty.
PART 2 -- PRODUCTS
2.01 Equipment
A. General:
Indoor, direct--expansion, wall--mounted fan coil. Unit shall be
complete with cooling/heating (heat pump systems only) coil, fan,
fan motor, piping connectors, electrical controls, microprocessor
control system, and integral temperature sensing. Unit shall be
furnished with integral wall mounting bracket and mounting
hardware.
B. Unit Cabinet:
Cabinet discharge and inlet grilles shall be attractively styled,
high--impact polystyrene. Cabinet shall be fully insulated for
improved thermal and acoustic performance.
C. Fans:
1. Fan shall be tangential direct--drive blower type with air
intake at the top of the unit and discharge at the bottom
front. Automatic, motor--driven vertical air sweep shall be
provided standard. Automatic motor--driven horizontal air
sweep shall be provided standard on sizes 030 and 036.
2. Air sweep operation shall be user selectable. The vertical
sweep may be adjusted (using the remote control) and the
horizontal air direction may be set manually on unit sizes
018 and 024.
D. Coil:
Coil shall be copper tube with aluminum fins and galvanized steel
tube sheets. Fins shall be bonded to the tubes by mechanical
expansion and specially coated for enhanced wetability. A drip
pan under the coil shall have two drain connections for hose
attachment, on either the left or right--hand side, to remove
condensate. Condensate pan shall have internal trap.
E. Motors:
Motors shall be open drip--proof, permanently lubricated ball
bearing with inherent overload protection. Fan motors shall be
3--speed.
F. Controls:
Controls shall consist of a microprocessor--based control system
which shall control space temperature, determine optimum fan
speed, and run self diagnostics. the temperature control range shall
be from 62_F to 84_F (16.67_C to 28.89_C).
User interface with the unit shall be accomplished through the
standard wireless remote control (can be configured for _F or _C)
or an optional wired controller or Zone Manager.
31
4QNC,QNQ/38HDF,QRF
GUIDE SPECIFICATIONS
HORIZ. DISCHARGE OUTDOOR UNITS
PART 1 -- GENERAL
1.01 System Description
A. Outdoor air--cooled split system compressor sections suitable
for on--the--ground, rooftop, wall hung or balcony mounting.
Units shall consist of a scroll compressor, an air--cooled coil,
propeller--type blow--through outdoor fan, reversing valve
(HP), accumulator, Accurator metering device(s), and control
box. Units shall discharge air horizontally as shown on the
contract drawings. Units shall function as the outdoor
component of an air--to--air cooling only, or heat pump system.
B. Units shall be used in a refrigeration circuit matched to
duct--free cooling only or heat pump fan coil units.
4QNC,QNQ/38HDF,QRF
1.04 Warranty
1--year parts, 5--year compressor limited warranty.
PART 2 -- PRODUCTS
2.01 Equipment
A. General:
Factory assembled, single piece, air--cooled outdoor unit.
Contained within the unit enclosure shall be all factory wiring,
piping, controls, and the compressor.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of galvanized steel,
bonderized and coated with a baked--enamel finish on
inside and outside.
2. Unit access panels shall be removable with minimal screws
and shall provide full access to the compressor, fan, and
control components.
3. Outdoor compartment shall be isolated and have an acoustic
lining to assure quiet operation.
4. Compressor compartment shall be isolated to allow
performing diagnostics while the system is running.
C. Fans:
1. Outdoor fans shall be direct--drive propeller type, and shall
discharge air horizontally. Fans shall blow air through the
outdoor coil.
2. Outdoor fan motors shall be totally--enclosed, single phase
motors with class B insulation and permanently--lubricated
bearings. Motor shall be protected by internal thermal
overload protection.
3. Shaft shall have inherent corrosion resistance.
4. Fan blades shall be metallic and shall be statically and
dynamically balanced.
5. Outdoor fan openings shall be equipped with PVC coated
metal protective grille over fan.
NOTES:
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
33
4QNC,QNQ/38HDF,QRF
________________________________________________________________________
4QNC,QNQ/38HDF,QRF