Electric Power Transmission
Electric Power Transmission
Electric Power Transmission
System
Most transmission lines use high-voltage three-phase alternating current (AC), although single phase AC is sometimes used in railway electrification systems. High-voltage direct-current (HVDC) technology is used for greater efficiency in very long distances (typically hundreds of miles (kilometres)), or in submarine power cables (typically longer than 30 miles (50km)). HVDC links are also used to stabilize against control problems in large power distribution networks where sudden new loads or blackouts in one part of a network can otherwise result in synchronization problems and cascading failures. Electricity is transmitted at high voltages (120kV or above) to reduce the energy lost in long-distance transmission. Power is usually transmitted through overhead power lines. Underground power transmission has a significantly higher cost and greater operational limitations but is sometimes used in urban areas or sensitive locations.
A key limitation in the distribution of electric power is that, with minor exceptions, electrical energy cannot be stored, and therefore must be generated as needed. A sophisticated control system is required to ensure electric generation very closely matches the demand. If the demand for power exceeds the supply, generation plants and
Electric power transmission transmission equipment can shut down which, in the worst cases, can lead to a major regional blackout, such as occurred in the US Northeast blackouts of 1965, 1977, 2003, and other regional blackouts in 1996 and 2011. To reduce the risk of such failures, electric transmission networks are interconnected into regional, national or continental wide networks thereby providing multiple redundant alternative routes for power to flow should (weather or equipment) failures occur. Much analysis is done by transmission companies to determine the maximum reliable capacity of each line (ordinarily less than its physical or thermal limit) to ensure spare capacity is available should there be any such failure in another part of the network.
Overhead transmission
High-voltage overhead conductors are not covered by insulation. The conductor material is nearly always an aluminium alloy, made into several strands and possibly reinforced with steel strands. Copper was sometimes used for overhead transmission but aluminium is lighter, yields only marginally reduced performance and costs much less. Overhead conductors are a commodity supplied by several companies worldwide. Improved conductor material and shapes are regularly used to allow increased capacity and modernize The electric power transmission grid of the contiguous United States consists of transmission circuits. Conductor sizes range 300,000km of lines operated by 500 companies. 2 from 12mm (#6 American wire gauge) to 2 750mm (1,590,000 circular mils area), with varying resistance and current-carrying capacity. Thicker wires would lead to a relatively small increase in capacity due to the skin effect, that causes most of the current to flow close to the surface of the wire. Because of this current limitation, multiple parallel cables (called bundle conductors) are used when higher capacity is needed. Bundle conductors are also used at high voltages to reduce energy loss caused by corona discharge.
Today, transmission-level voltages are usually considered to be 110kV and above. Lower voltages such as 66kV and 33kV are usually considered subtransmission voltages but are occasionally used on long lines with light loads. Voltages less than 33kV are usually used for distribution. Voltages above 230kV are considered extra high voltage and require different designs compared to equipment used at lower voltages. Since overhead transmission wires depend on air for insulation, design of these lines requires minimum clearances to be observed to maintain safety. Adverse weather conditions of high wind and low temperatures can lead to power outages. Wind speeds as low as 23 knots (43km/h) can permit conductors to encroach operating clearances, resulting in a flashover and loss of supply.[1] Oscillatory motion of the physical line can be termed gallop or flutter depending on the frequency and amplitude of oscillation.
Underground transmission
Electric power can also be transmitted by underground power cables instead of overhead power lines. Underground cables take up less right-of-way than overhead lines, have lower visibility, and are less affected by bad weather. However, costs of insulated cable and excavation are much higher than overhead construction. Faults in buried transmission lines take longer to locate and repair. Underground lines are strictly limited by their thermal capacity, which permits less overload or re-rating than overhead lines. Long underground cables have significant capacitance, which may reduce their ability to provide useful power to loads.
Cable sample: mid 7 conductors steel & the bulk being aluminium; This conductor is usually referred to as ACSR (Aluminum conductor, steel reinforced)
History
In the early days of commercial electric power, transmission of electric power at the same voltage as used by lighting and mechanical loads restricted the distance between generating plant and consumers. In 1882, generation was with direct current (DC), which could not easily be increased in voltage for long-distance transmission. Different classes of loads (for example, lighting, fixed motors, and traction/railway systems) required different voltages, and so used different generators and circuits.Wikipedia:Citing sources Due to this specialization of lines and because transmission was inefficient for low-voltage high-current circuits, generators needed to be near their loads. It seemed at the time, that the industry would develop into what is now known as a distributed generation system with large numbers of small generators located near their loads. In 1886, in Great Barrington, Massachusetts, a 1kV alternating current (AC) distribution system was installed. New York City streets in 1890. Besides telegraph lines, That same year, AC power at 2kV, transmitted 30km, was multiple electric lines were required for each class of device installed at Cerchi, Italy. At an AIEE meeting on May 16, requiring different voltages 1888, Nikola Tesla delivered a lecture entitled A New System of Alternating Current Motors and Transformers, describing the equipment which allowed efficient generation and use of polyphase alternating currents. The transformer, and Tesla's polyphase and single-phase induction motors, were essential for a combined AC distribution system for both lighting and machinery. Ownership of the rights to the Tesla patents was a key advantage to the Westinghouse Company in offering a complete alternating current power system for both lighting and power. Regarded as one of the most influential electrical innovations, the universal system used transformers to step-up voltage from generators to high-voltage transmission lines, and then to step-down voltage to local distribution circuits or industrial customers. By a suitable choice of utility frequency, both lighting and motor loads could be served. Rotary converters and later mercury-arc valves and other rectifier equipment allowed DC to be provided where needed. Generating stations and loads using different frequencies could be interconnected using rotary converters. By using common generating plants for every type of load, important economies of scale were achieved, lower overall capital investment was required, load factor on each plant was increased allowing for higher efficiency, a lower cost for the consumer and increased overall use of electric power.
5 By allowing multiple generating plants to be interconnected over a wide area, electricity production cost was reduced. The most efficient available plants could be used to supply the varying loads during the day. Reliability was improved and capital investment cost was reduced, since stand-by generating capacity could be shared over many more customers and a wider geographic area. Remote and low-cost sources of energy, such as hydroelectric power or mine-mouth coal, could be exploited to lower energy production cost.
The first transmission of three-phase alternating current using high voltage took place in 1891 during the international electricity exhibition in Frankfurt. A 25kV transmission line, approximately 175km long, connected Lauffen on the Neckar and Frankfurt. Voltages used for electric power transmission increased throughout the 20th century. By 1914, fifty-five transmission systems each operating at more than 70kV were in service. The highest voltage then used was 150kV.[2] The rapid industrialization in the 20th century made electrical transmission lines and grids a critical infrastructure item in most industrialized nations. Interconnection of local generation plants and small distribution networks was greatly spurred by the requirements of World War I, with large electrical generating plants built by governments to provide power to munitions factories. Later these generating plants were connected to supply civil loads through long-distance transmission.[3]
Nikola Tesla's alternating current polyphase generators on display at the 1893 World's Fair in Chicago. Tesla's polyphase innovations revolutionized transmission
Electric power transmission The optimum size of a conductor for a given voltage and current can be estimated by Kelvin's law for conductor size which states that the size is at its optimum when the annual cost of energy wasted in the resistance is equal to the annual capital charges of providing the conductor. At times of lower interest rates Kelvin's law indicates that thicker wires are optimal, while when metals are expensive thinner conductors are indicated: however power lines are designed for long-term usage so Kelvin's law has to be used in conjunction with long-term estimates of the price of copper and aluminium as well as interest rates for capital. The increase in voltage is achieved in AC circuits by using a step-up transformer. HVDC systems require relatively costly conversion equipment which may be economically justified for particular projects such as submarine cables and longer distance high capacity point to point transmission. HVDC is necessary for the import and export of energy between grid systems that are not synchronised with each other. A transmission grid is a network of power stations, transmission lines, and substations. Energy is usually transmitted within a grid with three-phase AC. Single-phase AC is used only for distribution to end users since it is not usable for large polyphase induction motors. In the 19th century, two-phase transmission was used but required either four wires or three wires with unequal currents. Higher order phase systems require more than three wires, but deliver little or no benefit. The price of electric power station capacity is high, and electric demand is variable, so it is often cheaper to import some portion of the needed power than to generate it locally. Because loads are often regionally correlated (hot weather in the Southwest portion of the US might cause many people to use air conditioners), electric power often comes from distant sources. Because of the economic benefits of load sharing between regions, wide area transmission grids now span countries and even continents. The web of interconnections between power producers and consumers should enable power to flow, even if some links are inoperative. The unvarying (or slowly varying over many hours) portion of the electric demand is known as the base load and is generally served by large facilities (which The synchronous grids of the European Union. are more efficient due to economies of scale) with fixed costs for fuel and operation. Such facilities are nuclear, coal-fired or hydroelectric, while other energy sources such as concentrated solar thermal and geothermal power have the potential to provide base load power. Renewable energy sources such as solar photovoltaics, wind, wave, and tidal are, due to their intermittency, not considered as supplying "base load" but will still add power to the grid. The remaining or 'peak' power demand, is supplied by peaking power plants, which are typically smaller, faster-responding, and higher cost sources, such as combined cycle or combustion turbine plants fueled by natural gas. Long-distance transmission of electricity (thousands of kilometers) is cheap and efficient, with costs of US$0.0050.02/kWh (compared to annual averaged large producer costs of US$0.010.025/kWh, retail rates upwards of US$0.10/kWh, and multiples of retail for instantaneous suppliers at unpredicted highest demand moments). Thus distant suppliers can be cheaper than local sources (e.g., New York often buys over 1000 MW of electricity from Canada). Multiple local sources (even if more expensive and infrequently used) can make the transmission grid more fault tolerant to weather and other disasters that can disconnect distant suppliers.
Long-distance transmission allows remote renewable energy resources to be used to displace fossil fuel consumption. Hydro and wind sources cannot be moved closer to populous cities, and solar costs are lowest in remote areas where local power needs are minimal. Connection costs alone can determine whether any particular renewable alternative is economically sensible. Costs can be prohibitive for transmission lines, but various proposals for massive infrastructure investment in high capacity, very long distance super grid transmission networks could be recovered with modest usage fees.
Grid input
At the power stations the power is produced at a relatively low voltage between about 2.3kV and 30kV, depending on the size of the unit. The generator terminal voltage is then stepped up by the power station transformer to a higher voltage (115kV to 765kV AC, varying by the transmission system and by country) for transmission over long distances.
Losses
Transmitting electricity at high voltage reduces the fraction of energy lost to resistance, which varies depending on the specific conductors, the current flowing, and the length of the transmission line. For example, a 100mile 765kV line carrying 1000 MW of energy can have losses of 1.1% to 0.5%. A 345kV line carrying the same load across the same distance has losses of 4.2%.[4] For a given amount of power, a higher voltage reduces the current and thus the resistive losses in the conductor. For example, raising the voltage by a factor of 10 reduces the current by a corresponding factor of 10 and therefore the I2R losses by a factor of 100, provided the same sized conductors are used in both cases. Even if the conductor size (cross-sectional area) is reduced 10-fold to match the lower current the I2R losses are still reduced 10-fold. Long-distance transmission is typically done with overhead lines at voltages of 115 to 1,200kV. At extremely high voltages, more than 2,000kV exists between conductor and ground, corona discharge losses are so large that they can offset the lower resistive losses in the line conductors. Measures to reduce corona losses include conductors having larger diameters; often hollow to save weight,[5] or bundles of two or more conductors. Transmission and distribution losses in the USA were estimated at 6.6% in 1997 and 6.5% in 2007. In general, losses are estimated from the discrepancy between power produced (as reported by power plants) and power sold to end customers; the difference between what is produced and what is consumed constitute transmission and distribution losses, assuming no theft of utility occurs. As of 1980, the longest cost-effective distance for direct-current transmission was determined to be 7,000km (4,300mi). For alternating current it was 4,000km (2,500mi), though all transmission lines in use today are substantially shorter than this.[] In any alternating current transmission line, the inductance and capacitance of the conductors can be significant. Currents that flow solely in 'reaction' to these properties of the circuit, (which together with the resistance define the impedance) constitute reactive power flow, which transmits no 'real' power to the load. These reactive currents however are very real and cause extra heating losses in the transmission circuit. The ratio of 'real' power (transmitted
Electric power transmission to the load) to 'apparent' power (sum of 'real' and 'reactive') is the power factor. As reactive current increases, the reactive power increases and the power factor decreases. For transmission systems with low power factor, losses are higher than for systems with high power factor. Utilities add capacitor banks, reactors and other components (such as phase-shifting transformers; static VAR compensators; physical transposition of the phase conductors; and flexible AC transmission systems, FACTS) throughout the system to compensate for the reactive power flow and reduce the losses in power transmission and stabilize system voltages. These measures are collectively called 'reactive support'.
Subtransmission
Subtransmission is part of an electric power transmission system that runs at relatively lower voltages. It is uneconomical to connect all distribution substations to the high main transmission voltage, because the equipment is larger and more expensive. Typically, only larger substations connect with this high voltage. It is stepped down and sent to smaller substations in towns and neighborhoods. Subtransmission circuits are usually arranged in loops so that a single line failure does not cut off service to a large number of customers for more than a short time. While subtransmission circuits are usually carried on overhead lines, in urban areas buried cable may be used. There is no fixed cutoff between subtransmission and transmission, or subtransmission and distribution. The voltage ranges overlap somewhat. Voltages of 69 kV, 115 kV and 138 kV are often used for subtransmission in North America. As power systems evolved, voltages formerly used for transmission were used for subtransmission, and subtransmission voltages became distribution voltages. Like transmission, subtransmission moves relatively large amounts of power, and like distribution, subtransmission covers an area instead of just point to point.[6]
Electric power transmission HVDC. (2) Use HVDC for the three thousand miles of cross-country transmission. Then (3) convert the HVDC to locally synchronized AC in Boston, (and possibly in other cooperating cities along the transmission route). Such a system could be less prone to failure if parts of it were suddenly shut down. One example of a long DC transmission line is the Pacific DC Intertie located in the Western United States.
Capacity
The amount of power that can be sent over a transmission line is limited. The origins of the limits vary depending on the length of the line. For a short line, the heating of conductors due to line losses sets a thermal limit. If too much current is drawn, conductors may sag too close to the ground, or conductors and equipment may be damaged by overheating. For intermediate-length lines on the order of 100km (62mi), the limit is set by the voltage drop in the line. For longer AC lines, system stability sets the limit to the power that can be transferred. Approximately, the power flowing over an AC line is proportional to the cosine of the phase angle of the voltage and current at the receiving and transmitting ends. Since this angle varies depending on system loading and generation, it is undesirable for the angle to approach 90 degrees. Very approximately, the allowable product of line length and maximum load is proportional to the square of the system voltage. Series capacitors or phase-shifting transformers are used on long lines to improve stability. High-voltage direct current lines are restricted only by thermal and voltage drop limits, since the phase angle is not material to their operation. Up to now, it has been almost impossible to foresee the temperature distribution along the cable route, so that the maximum applicable current load was usually set as a compromise between understanding of operation conditions and risk minimization. The availability of industrial distributed temperature sensing (DTS) systems that measure in real time temperatures all along the cable is a first step in monitoring the transmission system capacity. This monitoring solution is based on using passive optical fibers as temperature sensors, either integrated directly inside a high voltage cable or mounted externally on the cable insulation. A solution for overhead lines is also available. In this case the optical fiber is integrated into the core of a phase wire of overhead transmission lines (OPPC). The integrated Dynamic Cable Rating (DCR) or also called Real Time Thermal Rating (RTTR) solution enables not only to continuously monitor the temperature of a high voltage cable circuit in real time, but to safely utilize the existing network capacity to its maximum. Furthermore it provides the ability to the operator to predict the behavior of the transmission system upon major changes made to its initial operating conditions.
Control
To ensure safe and predictable operation the components of the transmission system are controlled with generators, switches, circuit breakers and loads. The voltage, power, frequency, load factor, and reliability capabilities of the transmission system are designed to provide cost effective performance for the customers.
Load balancing
The transmission system provides for base load and peak load capability, with safety and fault tolerance margins. The peak load times vary by region largely due to the industry mix. In very hot and very cold climates home air conditioning and heating loads have an effect on the overall load. They are typically highest in the late afternoon in the hottest part of the year and in mid-mornings and mid-evenings in the coldest part of the year. This makes the power requirements vary by the season and the time of day. Distribution system designs always take the base load and the peak load into consideration. The transmission system usually does not have a large buffering capability to match the loads with the generation. Thus generation has to be kept matched to the load, to prevent overloading failures of the generation equipment. Multiple sources and loads can be connected to the transmission system and they must be controlled to provide orderly transfer of power. In centralized power generation, only local control of generation is necessary, and it
Electric power transmission involves synchronization of the generation units, to prevent large transients and overload conditions. In distributed power generation the generators are geographically distributed and the process to bring them online and offline must be carefully controlled. The load control signals can either be sent on separate lines or on the power lines themselves. Voltage and frequency can be used as signalling mechanisms to balance the loads. In voltage signaling, the variation of voltage is used to increase generation. The power added by any system increases as the line voltage decreases. This arrangement is stable in principle. Voltage-based regulation is complex to use in mesh networks, since the individual components and setpoints would need to be reconfigured every time a new generator is added to the mesh. In frequency signaling, the generating units match the frequency of the power transmission system. In droop speed control, if the frequency decreases, the power is increased. (The drop in line frequency is an indication that the increased load is causing the generators to slow down.) Wind turbines, vehicle-to-grid and other distributed storage and generation systems can be connected to the power grid, and interact with it to improve system operation.
10
Failure protection
Under excess load conditions, the system can be designed to fail gracefully rather than all at once. Brownouts occur when the supply power drops below the demand. Blackouts occur when the supply fails completely. Rolling blackouts (also called load shedding) are intentionally engineered electrical power outages, used to distribute insufficient power when the demand for electricity exceeds the supply.
Communications
Operators of long transmission lines require reliable communications for control of the power grid and, often, associated generation and distribution facilities. Fault-sensing protective relays at each end of the line must communicate to monitor the flow of power into and out of the protected line section so that faulted conductors or equipment can be quickly de-energized and the balance of the system restored. Protection of the transmission line from short circuits and other faults is usually so critical that common carrier telecommunications are insufficiently reliable, and in remote areas a common carrier may not be available. Communication systems associated with a transmission project may use: Microwaves Power line communication Optical fibers Rarely, and for short distances, a utility will use pilot-wires strung along the transmission line path. Leased circuits from common carriers are not preferred since availability is not under control of the electric power transmission organization. Transmission lines can also be used to carry data: this is called power-line carrier, or PLC. PLC signals can be easily received with a radio for the long wave range. Optical fibers can be included in the stranded conductors of a transmission line, in the overhead shield wires. These cables are known as optical ground wire (OPGW). Sometimes a standalone cable is used, all-dielectric self-supporting (ADSS) cable, attached to the transmission line cross arms. Some jurisdictions, such as Minnesota, prohibit energy transmission companies from selling surplus communication bandwidth or acting as a telecommunications common carrier. Where the regulatory structure permits, the utility can sell capacity in extra dark fibers to a common carrier, providing another revenue stream.
11
Merchant transmission
Merchant transmission is an arrangement where a third party constructs and operates electric transmission lines through the franchise area of an unrelated utility. Operating merchant transmission projects in the United States include the Cross Sound Cable from Shoreham, New York to New Haven, Connecticut, Neptune RTS Transmission Line from Sayreville, N.J., to Newbridge, N.Y, ITC Holdings, Inc. transmission system in the midwest, and Path 15 in California. Additional projects are in development or have been proposed throughout the United States. There is only one unregulated or market interconnector in Australia: Basslink between Tasmania and Victoria. Two DC links originally implemented as market interconnectors Directlink and Murraylink have been converted to regulated interconnectors. NEMMCO [10] A major barrier to wider adoption of merchant transmission is the difficulty in identifying who benefits from the facility so that the beneficiaries will pay the toll. Also, it is difficult for a merchant transmission line to compete when the alternative transmission lines are subsidized by other utility businesses.
Health concerns
Some large studies, including a large United States study, have failed to find any link between living near power lines and developing any sickness or diseases such as cancer. One old study from 1997 found that it did not matter how close one was to a power line or a sub-station, there was no increased risk of cancer or illness.[11] The mainstream scientific evidence suggests that low-power, low-frequency, electromagnetic radiation associated with household currents and high transmission power lines does not constitute a short or long term health hazard. Some studies, however, have found statistical correlations between various diseases and living or working near power lines. No adverse health effects have been substantiated for people not living close to powerlines.[12] There are established biological effects for acute high level exposure to magnetic fields well above 100T (1G). In a residential setting, there is "limited evidence of carcinogenicity in humans and less than sufficient evidence for carcinogenicity in experimental animals", in particular, childhood leukaemia, associated with average exposure to residential power-frequency magnetic field above 0.3T (3mG) to 0.4T (4mG). These levels exceed average
Electric power transmission residential power-frequency magnetic fields in homes which are about 0.07T (0.7mG) in Europe and 0.11T (1.1mG) in North America. Tree Growth Regulator and Herbicide Control Methods may be used in transmission line right of ways[13] which may have health effects.
12
Special transmission
Grids for railways
In some countries where electric locomotives or electric multiple units run on low frequency AC power, there are separate single phase traction power networks operated by the railways. These grids are fed by separate generators in some traction powerstations or by traction substations from the public three phase AC network.
Superconducting cables
High-temperature superconductors (HTS) promise to revolutionize power distribution by providing lossless transmission of electrical power. The development of superconductors with transition temperatures higher than the boiling point of liquid nitrogen has made the concept of superconducting power lines commercially feasible, at least for high-load applications. It has been estimated that the waste would be halved using this method, since the necessary refrigeration equipment would consume about half the power saved by the elimination of the majority of resistive losses. Some companies such as Consolidated Edison and American Superconductor have already begun commercial production of such systems.[14] In one hypothetical future system called a SuperGrid, the cost of cooling would be eliminated by coupling the transmission line with a liquid hydrogen pipeline. Superconducting cables are particularly suited to high load density areas such as the business district of large cities, where purchase of an easement for cables would be very costly.[15]
13
Records
Highest capacity system: 6.3GW HVDC Itaipu (Brazil/Paraguay) (600kV DC) Highest transmission voltage (AC): planned: 1.20MV (Ultra High Voltage) on Wardha-Aurangabad line (India) - under construction. Initially will operate at 400 kV. worldwide: 1.15MV (Ultra High Voltage) on Ekibastuz-Kokshetau line (Kazakhstan) Europe (under construction): 750kV (Extra High Voltage) on the Rivne NPP/Khmelnytskyi NPP to Kyivska Substation route (Ukraine)[23] Largest double-circuit transmission, Kita-Iwaki Powerline (Japan). Highest towers: Yangtze River Crossing (China) (height: 345m or 1,132ft)
Electric power transmission Longest power line: Inga-Shaba (Democratic Republic of Congo) (length: 1,700 kilometres or 1,056 miles) Longest span of power line: 5,376m (17,638ft) at Ameralik Span (Greenland, Denmark) Longest submarine cables: NorNed, North Sea (Norway/Netherlands) (length of submarine cable: 580 kilometres or 360 miles) Basslink, Bass Strait, (Australia) (length of submarine cable: 290 kilometres or 180 miles, total length: 370.1 kilometres or 230 miles) Baltic Cable, Baltic Sea (Germany/Sweden) (length of submarine cable: 238 kilometres or 148 miles, HVDC length: 250 kilometres or 155 miles, total length: 262 kilometres or 163 miles) Longest underground cables: Murraylink, Riverland/Sunraysia (Australia) (length of underground cable: 180 kilometres or 112 miles)
14
References
Notes
[1] Hans Dieter Betz, Ulrich Schumann, Pierre Laroche (2009). Lightning: Principles, Instruments and Applications. (http:/ / books. google. com/ books?id=U6lCL0CIolYC& pg=PA187& lpg=PA187& dq=Spatial+ Distribution+ and+ Frequency+ of+ Thunderstorms+ and+ Lightning+ in+ Australia+ wind+ gust& source=bl& ots=93Eto3OuyQ& sig=nB7VACqDBK7xJDGHijfCdny7Ylw& hl=en& ei=DFkLSt2lKJCdlQeTyPjtCw& sa=X& oi=book_result& ct=result& resnum=3#PPA203,M1) Springer, pp. 202203. ISBN 978-1-4020-9078-3. Retrieved on May 13, 2009. [2] Bureau of Census data reprinted in Hughes, pp. 282283 [3] Hughes, pp. 293295 [4] American Electric Power, Transmission Facts, page 4: http:/ / www. aep. com/ about/ transmission/ docs/ transmission-facts. pdf [5] California Public Utilities Commission (http:/ / www. cpuc. ca. gov/ environment/ info/ aspen/ deltasub/ pea/ 16_corona_and_induced_currents. pdf) Corona and induced currents [6] Donald G. Fink and H. Wayne Beaty, Standard Handbook for Electrical Engineers (15th Edition) McGraw-Hill, 2007 ISBN 978-0-07-144146-9 section 18.5 [7] http:/ / www. omel. es [8] What is the cost per kWh of bulk transmission (http:/ / www. claverton-energy. com/ what-is-the-cost-per-kwh-of-bulk-transmission-national-grid-in-the-uk-note-this-excludes-distribution-costs. html) / National Grid in the UK (note this excludes distribution costs) [9] The Electric Power Transmission & Distribution (T&D) Equipment Market 20112021 (http:/ / www. visiongain. com/ Report/ 626/ The-Electric-Power-Transmission-and-Distribution-(T-D)-Equipment-Market-2011-2021) [10] http:/ / www. nemmco. com. au/ psplanning/ psplanning. html#interconnect [11] Power Lines and Cancer (http:/ / www. abc. net. au/ rn/ talks/ 8. 30/ helthrpt/ stories/ s175. htm), The Health Report / ABC Science Broadcast on 7 June 1997 (Australian Broadcasting Corporation) [12] Electromagnetic fields and public health (http:/ / www. who. int/ mediacentre/ factsheets/ fs322/ en/ ), World Health Organization [13] Transmission Vegetation Management NERC Standard FAC-003-2 Technical Reference Page 14/50. http:/ / www. nerc. com/ docs/ standards/ sar/ FAC-003-2_White_Paper_2009Sept9. pdf [14] 600m superconducting electricity line laid in New York (http:/ / www. newscientist. com/ article/ dn11907-superconducting-power-line-to-shore-up-new-york-grid. html) [15] Superconducting cables will be used to supply electricity to consumers (http:/ / www. futureenergies. com/ print. php?sid=237) [16] Superconductivity's First Century (http:/ / spectrum. ieee. org/ biomedical/ imaging/ superconductivitys-first-century/ 3) [17] Albany HTS Cable Project (http:/ / www. superpower-inc. com/ content/ hts-transmission-cable) [18] High-Temperature Superconductors (http:/ / www-03. ibm. com/ ibm/ history/ ibm100/ us/ en/ icons/ hightempsuperconductors/ ) [19] High-Temperature Superconductor Technology Stepped Up (http:/ / www. powermag. com/ business/ High-Temperature-Superconductor-Technology-Stepped-Up_4412. html) [20] BBC: Spies 'infiltrate US power grid' (http:/ / news. bbc. co. uk/ 2/ hi/ technology/ 7990997. stm) [21] CNN: Video (http:/ / www. cnn. com/ 2009/ TECH/ 04/ 08/ grid. threat/ index. html?iref=newssearch#cnnSTCVideo) [22] Reuters: US concerned power grid vulnerable to cyber-attack (http:/ / in. reuters. com/ article/ oilRpt/ idINN0853911920090408) [23] (http:/ / pda. korrespondent. net/ business/ economics/ 1397420)
Further reading Grigsby, L. L., et al. The Electric Power Engineering Handbook. USA: CRC Press. (2001). ISBN 0-8493-8578-4 Hughes, Thomas P., Networks of Power: Electrification in Western Society 18801930, The Johns Hopkins University Press,Baltimore 1983 ISBN 0-8018-2873-2, an excellent overview of development during the first 50
Electric power transmission years of commercial electric power Reilly, Helen (2008). Connecting the Country New Zealands National Grid 18862007. Wellington: Steele Roberts. pp.376 pages. ISBN978-1-877448-40-9. Pansini, Anthony J, E.E., P.E. undergrounding electric lines. USA Hayden Book Co, 1978. ISBN 0-8104-0827-9 Westinghouse Electric Corporation, "Electric power transmission patents; Tesla polyphase system". (Transmission of power; polyphase system; Tesla patents) The Physics of Everyday Stuff - Transmission Lines (http://www.bsharp.org/physics/transmission)
15
External links
Japan: World's First In-Grid High-Temperature Superconducting Power Cable System (http://www.sei.co.jp/ news_e/press/06/06_09.html) - Link broken A Power Grid for the Hydrogen Economy: Overview/A Continental SuperGrid (http://www.sciam.com/article. cfm?id=a-power-grid-for-the-hydr-2006-07) Global Energy Network Institute (GENI) (http://www.geni.org) The GENI Initiative focuses on linking renewable energy resources around the world using international electricity transmission. Union for the Co-ordination of Transmission of Electricity (UCTE) (http://www.ucte.org/), the association of transmission system operators in continental Europe, running one of the two largest power transmission systems in the world Non-Ionizing Radiation, Part 1: Static and Extremely Low-Frequency (ELF) Electric and Magnetic Fields (2002) (http://monographs.iarc.fr/htdocs/monographs/vol80/80.html) by the IARC Link Broken. A Simulation of the Power Grid (http://tcip.mste.illinois.edu/applet2.php) The Trustworthy Cyber Infrastructure for the Power Grid (TCIP) (http://tcip.mste.illinois.edu/) group at the University of Illinois at Urbana-Champaign (http://illinois.edu) has developed lessons and an applet which illustrate the transmission of electricity from generators to energy consumers, and allows the user to manipulate generation, consumption, and power flow. Map of U.S. electric power generation and transmission (http://www.energy-graph.com/interactive-map.html) Maps Electric power transmission systems (worldwide) based on Openstreetmap-Data (http://www.flosm.de/en/ Power-Grid.html)
16
License
Creative Commons Attribution-Share Alike 3.0 //creativecommons.org/licenses/by-sa/3.0/