12V 15W 1 Phase / Drp012V015W1Az: Cliq Din Rail Power Supply

Download as pdf or txt
Download as pdf or txt
You are on page 1of 11

TECHNICAL DATASHEET

CliQ DIN Rail Power Supply 12V 15W 1 Phase / DRP012V015W1AZ

Highlights & Features


Reliable design, with expected life of 10 years Compact, rugged design for ease of handling and installation Multiple connections to terminals allowed With Conformal Coating (Class I Div. 2 Hazardous Locations Ready) Meets worldwide safety requirements RoHS Directive 2011/65/EU Compliant Worldwide AC input range without power de-rating Overvoltage / Overcurrent / Over Temperature Protections 150% Power Boost (steady state peak load) for 3 seconds

Safety Standards

CB Certified for worldwide use

Model Number: DRP012V015W1AZ Unit Weight: 0.18 kg Dimensions (L x W x D): 100 x 32 x 100.6 mm General Description
The DRP012V015W1AZ is part of the CliQ series of DIN Rail power supplies from one of the worlds largest power supply man ufacturers and solution providers - Delta. This product provides an adjustable output capable of operating from input voltages at 85-264Vac, and a wide temperature range of -20C to 75C. With a rugged, compact plastic case design that meets shock and vibration requirements (in accordance to IEC60068-2-27 and IEC60068-2-6 respectively), and conformal-coated PCB assembly, this state of the art design is well suited to a broad variety of industrial applications worldwide.

Model Information CliQ DIN Rail Power Supply


Model Number DRP012V015W1AZ Input Voltage Range 85-264Vac (120-375Vdc) Output Voltage 12Vdc Output Current 1.25A

Model Numbering
DRP DIN Rail P Power Supply 012V Output Voltage 015W Output Power 1 Single Phase A CliQ Series Z Plastic Case

All parameters are specified at 25C ambient unless otherwise noted. www.DeltaPSU.com (December 2012, Rev. 02)

TECHNICAL DATASHEET

CliQ DIN Rail Power Supply 12V 15W 1 Phase / DRP012V015W1AZ


Specifications Input Ratings / Characteristics
Nominal Input Voltage Input Voltage Range Nominal Input Frequency Input Frequency Range Nominal DC Input Voltage DC Input Voltage Range Input Current Efficiency Max Inrush Current Power Factor Leakage Current 100-240Vac 85-264Vac 50-60Hz 47-63Hz 125-250Vdc 120-375Vdc < 0.37A @ 115Vac, < 0.22A @ 230Vac > 84.0% @ 115Vac, > 83.0% @ 230Vac < 30A @ 115Vac, < 65A @ 230Vac Conform to EN61000-3-2 < 1mA @ 240Vac

Output Ratings / Characteristics


Nominal Output Voltage Output Voltage Tolerance Output Voltage Adjustment Range Output Current Output Power Line Regulation Load Regulation Residual Ripple / PARD (20MHz) Rise Time Start-up Time Hold-up Time Dynamic Response (Overshoot & Undershoot O/P Voltage) Start-up with Capacitive Loads 12Vdc 2% (initial set point tolerance) 11-14Vdc 1.25A 15W < 0.5% typ. (@ 85-264Vac input, 100% input) < 1% typ. (@ 85-264Vac input, 0-100% input) < 100mVpp @ 25C
< 20ms @ nominal input (100% load, 25C)

< 2500ms @ nominal input (100% load, 25C) > 22ms @ 115Vac, > 1100ms @ 230Vac (100% load, 25C) 5% @ 10-100% load 5,000F Max

Mechanical
Case Cover Dimensions (L x W x D) Unit Weight Indicator Cooling System Terminal Wire Mounting Rail Input Output Input Output Aluminium 100 x 32 x 100.6 mm 0.18 kg Green LED (DC OK) Convection M3.5 x 5 Pins (Rated 300V/15A) M3.5 x 5 Pins (Rated 300V/15A)
AWG 22-14 AWG 22-14 Standard TS35 DIN Rail in accordance with EN60715

All parameters are specified at 25C ambient unless otherwise noted. www.DeltaPSU.com (December 2012, Rev. 02)

TECHNICAL DATASHEET

CliQ DIN Rail Power Supply 12V 15W 1 Phase / DRP012V015W1AZ


Environment
Surrounding Air Temperature Power De-rating Operating Humidity Operating Altitude Shock Test (Non-Operating) Vibration (Non-Operating) Bump Pollution Degree Operating Storage -20C to +75C -25C to +85C > 50C de-rate power by 2.5% / C > 70C de-rate power by 4% / C < 95% RH (Non-Condensing) 3,000 Meters IEC60068-2-27, 30G (300m/S) for a duration of 18ms IEC60068-2-6, 10Hz to 150Hz @ 50m/S (5G peak); 90 min per axis for all X, Y, Z direction IEC60068-2-29; 11ms / 10gn 2

Protections
Overvoltage Overload / Overcurrent Over Temperature Short Circuit Degree of Protection Protection Against Shock
*PE: Primary Earth

16V +10% / -5%, SELV Output, Hicc-up Mode, Non-Latching (Auto-Recovery) > 150% of rated load current, Hicc-up Mode, Non-Latching (Auto-Recovery) < 80C Surrounding Air Temperature @ 100% load, Non-Latching (Auto-Recovery) Hicc-up Mode, Non-Latching (Auto-Recovery when the fault is removed) IPX0 Class I without PE* connection

Reliability Data
MTBF Expected Cap Life Time > 1,000,000 hrs. as per Telcordia SR-332 10 years (115Vac & 230Vac, 50% load @ 40C)

All parameters are specified at 25C ambient unless otherwise noted. www.DeltaPSU.com (December 2012, Rev. 02)

TECHNICAL DATASHEET

CliQ DIN Rail Power Supply 12V 15W 1 Phase / DRP012V015W1AZ


Safety Standards / Directives
Electronic Equipment in Power Installations Electrical Safety EN50718 / IEC62103 TUV Bauart to EN60950-1, UL/cUL recognized to UL60950-1, CSA C22.2 No. 60950-1, CB scheme to IEC60950-1 UL/cUL listed to UL508 and CSA C22.2 No. 107.1-01, CSA to CSA C22.2 No. 107.1-01 Pending In conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC RoHS Directive 2011/65/EU Compliant Input to Output Input to Ground Output to Ground 4.0KVac 1.5KVac 1.5KVac

Industrial Control Equipment Hazardous Location / ATEX CE Material and Parts Galvanic Isolation

EMC
EMC / Emissions Immunity to Electrostatic Discharge EN61000-4-2 Level 4 Criteria A Air Discharge: 15kV Contact Discharge: 8kV 1) Level 3 Criteria A 80MHz1GHz, 10V/M with 1kHz tone / 80% modulation Level 3 Criteria A 2kV
1) 1)

CISPR22, EN55022, EN55011, FCC Title 47: Class B

Radiated Field Electrical Fast Transient / Burst Surge

EN61000-4-3 EN61000-4-4 IEC6100-4-5

Level 3 Criteria A 2) Common Mode : 2kV 3) Differential Mode : 1kV Level 3 Criteria A 150kHz-80MHz, 10Vrms Level 3 Criteria A 10A/Meter
1) 1)

1)

Conducted Power Frequency Magnetic Fields Voltage Dips Low Energy Pulse Test (Ring Wave)

EN61000-4-6 EN61000-4-8 EN61000-4-11 IEC61000-4-12

Level 3 Criteria A 100% dip; 1 cycle (20ms); Self Recoverable Level 3 Criteria A 2) Common Mode : 2kV 3) Differential Mode : 1kV
1)

1)

1) Criteria A: Normal performance within the specification limits 2) Asymmetrical: Common mode (Line to earth) 3) Symmetrical: Differential mode (Line to line)

All parameters are specified at 25C ambient unless otherwise noted. www.DeltaPSU.com (December 2012, Rev. 02)

TECHNICAL DATASHEET

CliQ DIN Rail Power Supply 12V 15W 1 Phase / DRP012V015W1AZ


Block Diagram

Device Description

1) 2) 3) 4)

Input & Output terminal block connector DC voltage adjustment potentiometer DC OK control LED (Green) Universal mounting rail system

All parameters are specified at 25C ambient unless otherwise noted. www.DeltaPSU.com (December 2012, Rev. 02)

TECHNICAL DATASHEET

CliQ DIN Rail Power Supply 12V 15W 1 Phase / DRP012V015W1AZ


Dimensions
L x W x D: 100 x 32 x 100.6 mm

Engineering Data De-rating


Note 1. Power supply components may degrade, or be damaged, when the power supply is continuously used outside the shaded region, refer to the graph shown in Fig. 1.1. If the output capacity is not reduced when the surrounding air temperature >50C, the device will run into Over Temperature Protection. When activated, the output voltage will go into bouncing mode and will recover when the surrounding air temperature is lowered or the load is reduced as far as necessary to keep the device in working condition. If the device has to be mounted in any other orientation, please do not hesitate to contact [email protected] for more details. In order for the device to function in the manner intended, it is also necessary to keep a safety distance of 20mm with adjacent units while the device is in operation. Depending on the surrounding air temperature and output load delivered by the power supply, the device housing can be very hot!

2.

3.

4.

Fig. 1.1 De-rating for Vertical Mounting Orientation > 50C de-rate power by 2.5% / C, > 70C de-rate power by 4% / C

5.

All parameters are specified at 25C ambient unless otherwise noted. www.DeltaPSU.com (December 2012, Rev. 02)

TECHNICAL DATASHEET

CliQ DIN Rail Power Supply 12V 15W 1 Phase / DRP012V015W1AZ


Output De-rating VS. Input Voltage No output power de-rating across the entire input voltage range

Assembly & Installation


The power supply unit (PSU) can be mounted on 35mm DIN rails in accordance with EN60715. The device should be installed horizontally with input terminal blocks on the bottom. Each device is delivered ready to install.

Mounting
Snap on the DIN rail as shown on the left: 1. Pull the DIN rails latch OUT. 2. Tilt the unit upwards, hook the top end of onto the DIN rail and push downwards until stopped. 3. Position the bottom front end against the DIN rail. 4. Push the units latch DIN rail IN to lock.

Dismounting
To uninstall: 1. Pull the units DIN rail latch OUT. 2. Tilt the bottom part of the unit out. 3. Push the unit up and pull out from the DIN rail.

All parameters are specified at 25C ambient unless otherwise noted. www.DeltaPSU.com (December 2012, Rev. 02)

TECHNICAL DATASHEET

CliQ DIN Rail Power Supply 12V 15W 1 Phase / DRP012V015W1AZ


Safety Instructions
ALWAYS switch mains of input power OFF before connecting and disconnecting the input voltage to the unit. If mains are not turned OFF, there is risk of explosion / severe damage. To guarantee sufficient convection cooling, keep a distance of 50mm above and below the device as well as a lateral distance of 20mm to other units. Note that the enclosure of the device can become very hot depending on the surrounding air temperature and load of the power supply. Risk of burns! Only plug in and unplug connectors when power is turned off! DO NOT insert any objects into the unit. Hazardous voltages may be present for up to 5 minutes after the input mains voltage is disconnected. Do not touch the unit during this time. The power supplies unit should be installed in minimum IP54 rated enclosure. The power supplies are built in units and must be installed in a cabinet or room (condensation free environment and indoor location) that is relatively free of conductive contaminants.

Functions
Graph illustrating the Start-up Time, Rise Time, and Hold-up Time

Start-up Time
The time required for the output voltage to reach 90% of its set value, after the input voltage is applied.

Rise Time
The time required for the output voltage to change from 10% to 90% of its set value.

Hold-up Time
Hold up time is the time when the AC input collapses and output voltage retains regulation for a certain period of time. The time required for the output to reach 95% of its set value, after the input voltage is removed.

All parameters are specified at 25C ambient unless otherwise noted. www.DeltaPSU.com (December 2012, Rev. 02)

TECHNICAL DATASHEET

CliQ DIN Rail Power Supply 12V 15W 1 Phase / DRP012V015W1AZ


Inrush Current
Inrush current is the peak, instantaneous, input current measured and, occurs when the input voltage is first applied. For AC input voltages, the maximum peak value of inrush current will occur during the first half cycle of the applied AC voltage. This peak value decreases exponentially during subsequent cycles of AC voltage.

Surge Load
It is the reserve power available constantly that allows reliable startup of loads with high inrush current. After the output has reached its steady state set value, the power supply can support surge loads of up to 150% of maximum rated load (Io Max), for a maximum duration of 3 seconds. The maximum allowed rate of load change is 0.1amps per microseconds, and the voltage can vary 5% from the set value during the duration of the surge load.

Step Load Response


The power supply output voltage will remains within 5% of its steady state value, when subjected to a dynamic load from 10 to 100% of its rated current.

Overload & Overcurrent Protections


The power supplys Overload (OLP) and Over current (OCP) Protections will be activated when output current exceeds 150% of IO (Max load). In such occurrence, the VO will start to droop and once the power supply has reached its maximum power limit, the protection is activated and the power supply will go into Hiccup mode (Auto-Recovery). The power supply will recover once the fault condition of the OLP and OCP is removed and IO is back within the specifications.

Overvoltage Protection
The power supplys overvoltage circuit will be activated when its internal feedback circuit fails. The output voltage shall not exceed its specifications defined on Page 3 under Protections. Additionally, if the IO is <150% but >100% for a prolong period of time (depending on the load), the Over Temperature Protection (OTP) will be activated due to high temperature on critical components. The power supply will then go into Hiccup mode until the fault is removed.

All parameters are specified at 25C ambient unless otherwise noted. www.DeltaPSU.com (December 2012, Rev. 02)

TECHNICAL DATASHEET

CliQ DIN Rail Power Supply 12V 15W 1 Phase / DRP012V015W1AZ


Over Temperature Protection
As mentioned above, the power supply also has Over Temperature Protection (OTP). This is activated when the overload condition persists for an extended duration and the output current is below the overload trigger point but >100% load. In the event of a higher operating condition at 100% load, the power supply will run into OTP when the surrounding air temperature is >80C. When activated, the output voltage will go into bouncing mode until the operating surrounding air temperature drops to 50C or output capacity is reduced as recommended in the derating graph.

Short Circuit Protection


The power supplys output OLP/OCP function also provides protection against short circuits. When a short circuit is applied, the output current will operate in Hiccup mode, as shown in the illustration in the OLP/OCP section on this page. The power supply will return to normal operation after the short circuit is removed.

Operating Mode
Redundancy Operation In order to ensure proper redundancy operation for the power supply unit (PSU), ensure that the output voltage difference between the two units is kept at 0.20~0.25V for 12V supplies. Follow simple steps given below to verify: Step 1. Measure output voltage of PSU 1 and PSU 2. If PSU 1 is the master unit, then Vo of PSU 1 must be higher than PSU 2. In order to set the output voltage, connect the power supply to 50% load and set the PSU 1 and PSU 2 output voltage. Step 2. Connect the right DRR module, 20A as per the system requirement to the power supply units PSU 1 and PSU 2 at Vin 1 & Vin 2 respectively. Step 3. Connect the system load from Vout. Please note that output voltage Vout from DRR module will be = VO (output voltage of power supply) Vdrop* (in DRR module).

Fig. 2.1 Redundancy / Parallel Operation Connection Diagram

*Vdrop will vary from 0.40V to 0.60V (Typical 0.45V) depending on the load current and surrounding air temperature. Parallel Operation

These DRR modules can also be used for Parallel function in order to increase the output power by N+1 (e.g. 2.5A + 2.5A = 5A or 2.5A + 2.5A + 2.5A = 7.5A) or current sharing, and thus increasing the power supply and system reliability. Though the DRP012V015W1AZ is not designed for current sharing, a good current sharing between two power supplies can be achieved by following simple st eps as below (Refer to Fig. 2.1 for the Connection Diagram). Step 1. Set output load condition for both supplies at 50% and measure the output voltages. Step 2. Adjust output voltages to the same level or within 25mV difference. Step 3. Connect PSU 1 and PSU 2 with the DRR-20A module and measure at Vin 1 & Vin 2 to verify the voltage difference. Ensure the voltages are within 25mV. Step 4. Output voltage from DRR module Vout will be = VO (output voltage of power supply) Vdrop* (in DRR module).

*Vdrop will vary from 0.40V to 0.60V (Typical 0.45V) depending on the load current and surrounding air temperature.

10

All parameters are specified at 25C ambient unless otherwise noted. www.DeltaPSU.com (December 2012, Rev. 02)

TECHNICAL DATASHEET

CliQ DIN Rail Power Supply 12V 15W 1 Phase / DRP012V015W1AZ


Others Delta RoHS Compliant
Restriction of the usage of hazardous substances The European directive 2011/65/EC limits the maximum impurity level of homogeneous materials such as lead, mercury, cadmium, chrome, polybrominated flame retardants PBB and PBDE for the use in electrical and electronic equipment. RoHS is the abbreviation for Restriction of the use of certain hazardous substances in electrical and electronic equipment. This product conforms to this standard.

Conformal Coating
The Protective Coating Technology Delta Electronics Group has designed the perfect dipping technique which penetrates everywhere including under device, and prevents leakage. The conformal coating dipping can be applied to PCBs or circuit board. The coating preserves the performance of precision electronic primarily by preventing ionizable contaminants such as salt from reaching circuit nodes, where the material slumps around sharp edges. This can be a problem especially in highly conversing atmosphere.

11

All parameters are specified at 25C ambient unless otherwise noted. www.DeltaPSU.com (December 2012, Rev. 02)