ACI 350 3 06 Appendix BRev00 29 Sep 2013
ACI 350 3 06 Appendix BRev00 29 Sep 2013
ACI 350 3 06 Appendix BRev00 29 Sep 2013
Rev0
Designed by:- M. Abu Shady Checked by:- M. Abu Shady 11-Feb-14 Date:M.A.S. tr= 0.20 m
General Input :-
L= 9.30 m
tw= 0.30 m
Hw= 2.95 m
B= 9.30 m Rectangular Tank Plan c= 24.0 KN/m3 fc= 35.0 N/mm2 g= 9.81 m/sec2 Importance factor I Rc Ri SEISMIC ZONE Z factor Soil Profile Soil Profile Type Na For Zone 4 only Nv For Zone 4 only Ca Cv Ts =0.40Cv/Ca = 1.00 = 1.00 = 2.00 2B 0.2 Very Dense SC 1 1 0.240 0.320 0.533
ACI 350.3-06, Table 4.1.1(a) ACI 350.3-06, Table 4.1.1(b) ACI 350.3-06, Table 4.1.1(b) UBC 97, TABLE 16-I UBC 97, TABLE 16-J UBC 97, TABLE 16-S UBC 97, TABLE 16-T UBC 97, TABLE 16-Q UBC 97, TABLE 16-R sec, UBC 97, FIGURE 16-3
1-Calculation the Equivalent Weight for impulsive Wi & convective Wc component: WL = 1902.8 KN , L / HL = 4.23 = 0.27 WL = 519.1 KN ,Ww = 2718.7 KN ACI 350.3-06, Eq 9-1 ,Wr = 442.4 KN
= 0.71 WL
2-Calculation the Height of center of gravity for impulsive hi & convective hc components:
= 0.825 m
= 1.149 m
3-Calculation the fundamental period of oscillation of the tank for impulsive Ti & convective Tc components: = 3680.2 KN = 1.37 m = 0.45 sec , , ACI 350.3-06, Eq 9-11 = 4.43 = 4.32 sec ACI 350.3-06, Eq 9-13,14 = 1.48 m , = 72865.3 KN/m = 3.05 m ACI 350.3-06, R9.2.4
Page 1 of 11
Seismic Loads for Liquid-Containing Rectangular RC Tank, According ACI 350.3-06 , Appendix B Method Based on 1997 Uniform Building Code
Project :Building :Element:Location:Project Building Element Location
Rev0
Designed by:- M. Abu Shady Checked by:- M. Abu Shady 11-Feb-14 Date:M.A.S.
= 132.7 KN ACI 350.3-06, Appendix B, Eq B-6,7 = 103.7 KN ACI 350.3-06, Appendix B, Eq B-8,9
6-Dynamic force distribution above base per Wall perpendicular to ground motion: Pi Top Pi Bottom Pc Top Pc Bottom = 14.4 KN/m2 = 14.4 KN/m2 = 1.0 KN/m2 = 2.9 KN/m2 = 14.4 KN/m2 = 18.2 KN/m2 = 1.0 KN/m2 = 6.7 KN/m2 = 2.9 KN/m2 = 2.2 KN/m2 ACI 350.3-06, R5.3.1
= 23.3 KN/m2 Total Seismic Force E per Wall perpendicular to ground motion
Dynamic force distribution above base per Wall perpendicular to ground motion 7- Load Cominations: Note that, the Calculated Seismic Force E above is based on Strength-level Forces (ultimate loads). For allowable stresses Design (ASD) Method (service loads) , the design seismic forces shall be reduced by a factor of 1.4 ACI 350.3-06, Appendix B, Clause B.5 For Ultimate Strength Design method (factored loads), follow ACI 350-06, Clause 9.2.1 load combinations.
Page 2 of 11
Rock
UBC 97 Tables TABLE 16-ISEISMIC ZONE FACTOR Z Z Zone 0.075 1 0.15 2A 0.2 2B 0.3 3 0.4 4 Ct Values 0.0853 (0.035 in ft)for steel moment-resisting frames 0.0731 (0.030 in ft)for andRC eccentrically moment-resisting braced frames frames 0.0488 (0.020 in ft)for all other buildings TABLE 16-JSOIL PROFILE TYPES Soil Profile Descripti Soil Profile Type on Hard SA Rock SB Rock Very SC Dense SD Stiff Soil SE Soft Soil Weak Soil SF TABLE 16-QSEISMIC COEFFICIENT Ca Z Seismic Zone Factor SOIL PROFILE TYPE 0.075 0.15 SA 0.06 0.12 SB 0.08 0.15 SC 0.09 0.18 SD 0.12 0.22 SE 0.19 0.3 SF 0 0 TABLE 16-RSEISMIC COEFFICIENT Cv Z Seismic Zone Factor SOIL PROFILE TYPE 0.075 0.15 SA 0.06 0.12 SB 0.08 0.15
SC SD SE SF
QSEISMIC COEFFICIENT Ca Z Seismic Zone Factor 0.2 0.3 0.16 0.24 0.2 0.3 0.24 0.33 0.28 0.36 0.34 0.36 0 0
use External calculated for K use ACI 350.3-06, R9.2.4 expression for K
RSEISMIC COEFFICIENT Cv Z Seismic Zone Factor 0.2 0.3 0.16 0.24 0.2 0.3
References 1-ACI 350.3_06 Seismic Design of Liquid-Containing Concrete Structures and Commentary 2-SP-2002 IBC2000 ACI 350.3R-01 Design_of_liquid_containing_concrete_structures_for_earthquake_forcesby Javeed A. Munshi-2 3- Tank Wall Stiffness Calculation K : a- using ACI 350.3-06, R9.2.4 which developed For fixed-base, free-top cantilever walls, such as in open-top tanks - on my opinion- the same expression can be used for fixed wall in tank base and hinged at roof slab, as below b- using analysis model with assuming Lateral Force F= 10 KN (e.g) at C.G of tank to obtain a deflection , thus tank stiffness K = F for more information see Guidelines for Seismic Design of Liquid Storage Tanks, Example 1/Page 59 which you can download
ection , thus tank stiffness K = F/ http://www.iitk.ac.in/nicee/IITK-GSDMA/EQ08.pdf for more useful pdf (IITK-GSDMA Project on Review of Seismic Codes, & Preparation of Commentary and Handbooks) http://www.nicee.org/IITK-GSDMA_Codes.php