Crouse Hinds Control Stations

Download as pdf or txt
Download as pdf or txt
You are on page 1of 127
At a glance
Powered by AI
The document discusses different types of explosion proof control units and control stations, including their material composition, panel mounting options, and installation techniques. A variety of control stations are made from impact-resistant thermoplastics, glass-fiber reinforced polyester, light alloys or stainless steel to withstand chemicals and adverse conditions. They can be integrated into panels up to 5mm thick and include pre-wired connection terminals for easy installation.

The control stations are made from impact-resistant thermoplastics, glass-fiber reinforced polyester, light alloys or stainless steel. These materials are robust and resistant to chemicals, fulfilling the surface resistance specification. They can withstand indoor and outdoor installations, especially in chemical and offshore environments with all metal parts being stainless steel.

Control and indicating elements such as signal lamps, pushbuttons and switches can be integrated into panels with a thickness up to 5mm via a bayonet-ring fitting. They can be plugged in directly and installed with single wires in a clear and simple way. Retrofitting for cable connection is also possible with a slip-on strain relief and protective cap.

1

EX-CONTROL UNITS AND C O N T R O L S TAT I O N S

2 3 4 5 6 7 8

Cooper Crouse-Hinds 2008 - all rights reserved


E X - C O N T R O L U N I T S A N D C O N T R O L S TAT I O N S

9.211

9 10

E X - I N S TA L L AT I O N S W I T C H

9.411

E X - C O N T R O L S TAT I O N S

9.611

I N D I V I D U A L E X - C O N T R O L S TAT I O N S

9.321

E X - C O N T R O L A N D S I G N A L U N I T S F O R PA N E L M O U N T I N G

9.801

EX-CONTROL-SWITCHES

9.112

11 12

F L A M E P R O O F L I G H T A L L O Y C O N T R O L S TAT I O N S

9.126

Ex-control units and control stations

Material selection

Cooper Crouse-Hinds 2008 - all rights reserved

At the heart of every electrical system is the control station. Even under the most adverse conditions, CEAG control stations can be used and operated reliably. The enclosures consist of impact-resistant thermoplastic, glassfibre-reinforced polyester, light alloy or stainless steel. The robust materials, thermoplastic and polyester, fulfil the specification for surface resistance < 10 9 required by EN 60079. The well-tried enclosure materials have proven their high resistance to chemicals in indoor and outdoor installations especially in the chemical and off-shore industries. All metal parts are made of stainless steel.

Combination of moulded plastic enclosures


The modular design of the GHG 44x control-station series lets you combine distri bution modules with screwless snap-on mounting logically and at low cost. Standard sizes enable enclosure mounting via flanged joints. The screwless snap-on mounting system also allows the attachment of plastic or brass flanges on the enclosures. This mounting technique also lets you quickly and easily retrofit cable entries on the flanges. System modifications and extensions can thus be implemented in short time and with little effort.

9.2

COOPER CROUSE-HINDS GMBH

Ex-control units and control stations

1 2
with a slip-on strain relief and protec -

Cooper Crouse-Hinds 2008 - all rights reserved

tive cap and is then completely certified. Planning and procurement of panel-mounted apparatus with different cable lengths is a thing of the past.

3 4 5 6 7 8 9 10 11 12

Installation technology Panel mounting


CEAG control and indicating elements can be integrated in panels with a wall thick ness of up to 5 mm. The CEAG components for panel mounting, such as signal lamps, pushbuttons and switches, can be instantly plugged into the control and indicating elements on the panel via a bayonet-ring fitting. The single-wire installation is clear and simple. All panel-mounted apparatus can be retrofitted for cable connection CEAG control stations have a well thought out design concept. The flameproof built-in components, such as signal lamps, pushbuttons and switches, are snap-on mounted to a rail moulded in the enclosure. They can be snapped out of the enclosure to facilitate cableentry feeding. Notches in the mounting rails define the position of the built-in components and prevent them from being twisted out of place. Low-cut side walls allow a quick and optimised cable connection. CEAG control stations feature standard M25 moulded-plastic cable entries with an 8 to 17 mm clamping diameter. Alternatively, metal screws and flanges can be used for mounting. The metal flanges enable external earthing. The CEAG control stations are installed using pre-wired connection terminals. The wired built-in components are snap-on mounted on a stainless-steel fold-out mounting frame. To connect the control and indicating elements, the mounting frame is folded out, the cables are quickly and easily fed into enclosure and attached logically to the terminals.

COOPER CROUSE-HINDS GMBH

9.3

E X - I N S T A L L A T I O N
16 A, 250 V Plastic version for Zone 21

S W I T C H

The explosion-protected installation switches are for use in the Zones 1, 2, 21 and 22. The materials used have proved to be safe and reliable for both indoor and outdoor installations, in particular in chemical and off-shore plants. The robust

Cooper Crouse-Hinds 2008 - all rights reserved


9.4

housings are made of a modified polyamide material. The large actuator surface of the installation switch allows perfect operation, even when wearing working gloves. A protective collar prevents inadvertent operation. The toggle has a luminescent label which is in accordance with 7 of the Workshop Regulations and is also free from radioactive additives. Due to the external fixing facility, the switch can be installed easily while the cover is closed. Cable entry from the top is made possible by turning the base. In special cases a through wiring is possible as one can see on the illustration opposite. International approvals.

Large toggle also for working gloves Safety standard IP66 Cable entry from the top or bottom Connecting terminals easily accessible

Ex-Installation switch

1 2
Switch/Pushbutton

Cooper Crouse-Hinds 2008 - all rights reserved

Technical data
Ex-installation switches and Ex-pushbuttons Marking to 94/9/EC EC-Type Examination Certificate IECEx Certificate of conformity Marking acc. IECEx Permissible ambient temperature Rated voltage Rated current Connecting terminals Degree of protection accd. to EN 60529 Cable glands1) Weight Enclosure material II 2 G EEx de IIC T6 / PTB 98 ATEX 3121 IECEx BKI 07.0036 Ex ed IIC T6 Ex tD A21 IP66 T67 C 20 C to +40 C 55 C to +55 C (option) 250 V, 50 - 60 Hz 16 A Switch terminals: 2 x 2.5 mm2 / PE-terminals: 4 x 2.5 mm2 IP66 Ex-e cable glands M25 for cables from 8 - 17 mm 0.32 kg Polyamide II 2 D T 67 C

3 4 5 6
Cable glands1) 1 x M25
L L( N )

Ordering details
Type ON-OFF switch 2-pole Contact arrangement Order No. GHG 273 2000 R0017 GHG 273 2000 R0018 GHG 273 2000 R0003 GHG 273 6000 R0011 GHG 273 6000 R0003 GHG 273 6000 R0014 GHG 273 4000 R0004 GHG 273 4000 R0007

2 x M25 2 x M202) 1 x M25 2 x M202) 2 x M25 1 x M25 2 x M25

7 8 9

Change-over switch
L

Pushbutton
L
1) 2)

L( N )

Base enclosure can be rotated afterwards (entry from top or down) Threaded only

Other versions available on request

Dimension drawing
85 X75 85 X75 64 55

X52

X52

85

85

115

115

10
20
Dimensions in mm

53

35

Switch/pushbutton

X = fixing dimension

11 12

COOPER CROUSE-HINDS GMBH

9.5

T A T

Moulded plastic Ve r s i o n f o r Z o n e 1

Even under the most adverse conditions, CEAG control stations can be used and operated reliably. The enclosures consist of low-temperature impact-resistant thermoplastic which fulfils the requirements of EN 60079 and provides a high resistance to chemicals. The well thought out

Cooper Crouse-Hinds 2008 - all rights reserved


9.6

design with low side walls allows optimum cable connection. Quick fixing allows up to three CEAG built-in components, such as signal lamps, pushbuttons and switches, to be snapped on a rail in the enclosure. They can be snapped out of the enclosure to facilitate cable-entry feeding. Notches in the mounting rails prevent the built-in components from being twisted out of place. Wall mounting can be carried out via easily accessible fixing apertures when the enclosure cover is sealed. CEAG mounting pla tes offer a time-saving fixing tech nique. CEAG control stations feature standard M25 moulded-plastic cable entries with an 8 to 17 mm clamping diameter. Coupling pieces link enclosures to each other and prevent them from being twisted out of place. Alternatively, metal screws and flanges can be used for mounting the metal flanges also enable external earthing. Free mounting areas can be provided for retrofitting certified CEAG components. These are then factory sealed with blanking elements. Internationally approved.

Flat side walls Quick fixing of all built-in components High chemical resistance Different enclosures can be combined

Ex-control stations

1 2
Type 411 83 Type 411 82 Type 411 81

Cooper Crouse-Hinds 2008 - all rights reserved

Technical data
Ex-Control stations Type 411 81 Type 411 82 Type 411 83 Marking to 94/9/EC EC-Type Examination Certificate IECEx Certificate of conformity Marking acc. to IECEx Permissible ambient temperature Rated voltage Rated current Connecting terminals Insulation class Degree of protection accd. EN 60529 Cable glands/Gland plates/Enclosure drilling Enclosure material Enclosure colour Type 411 81 Dimensions (L x W x H) Weight (empty) Type 411 82 Dimensions (L x W x H) Weight (empty) Type 411 83 Dimensions (L x W x H) Weight (empty) 165 x 85 x 77.5 mm 0.45 kg 125 x 85 x 77.5 mm 0.35 kg 85 x 85 x 77.5 mm 0.25 kg II 2 G EEx e II T6 / EEx e ib IIC T6 / EEx ed IIC T6 / EEx ed ib IIC T6 II 2 D IP66 T 48 C PTB 00 ATEX 3117 IECEx BKI 04.0003 Ex e II T6, Ex e ib IIC T6, Ec ed IIC T6 or Ec ed ib IIC T6 20 C to +40 C 55 C to +55 C (option) 690 V AC 16 A 2 x 2.5 mm2 I IP66 (standard) IP65 (measuring instrument AM45, double pushbutton) 1 x M25 EEx-e cable gland for cables from 8 - 17 mm or 1 x M20 thread Polyamide Black

3 4 5 6 7 8
Moving coil II G EEx ib IIC Class 1.5 10-fold -5 sec.

Type 411 82 with measuring instrument AM 72 Moving iron Marking to 94/9/EC Accuracy Overload range II G EEx e II Class 2.5 10-fold -25 sec. 25-fold - 4 sec. 50-fold - 1 sec. Measuring range Li Ci Ui Ii Connecting terminals Weight
1)

9 10 11 12

n / 1A 0 - 25 A direct 2 x 1.5 - 4 mm2 0.70 kg

0 - 20 mA 4 - 20 mA max. 0.1 mH max. 0.1 nF max. 30 V max. 150 mA

Base enclosure can be rotated afterwards (entry from top or down)

Other versions available on request

COOPER CROUSE-HINDS GMBH

9.7

Ex-control stations

Type 411 81...01

Type 411 81...12

Type 411 81...18

Type 411 81...04

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering details type 411 81 with 1 built-in component


Version
13 21

Built-in components 1 x pushbutton DRT 1 NO + 1 NC label: 0, I, START, STOP 1 x mushroom-head pushbutton SGT 1 NO + 1 NC Emergency stop 1 x mushroom-head pushbutton SGT 1 NO + 1 NC Emergency stop with key unlocking

Weight approx.

Order No.

14 13

22 21

0.40 kg

GHG 411 8100 R0001

14 13 () 14 13 I 0 14

22 21

0.45 kg

GHG 411 8100 R0002

22 21

0.50 kg

GHG 411 8101 R0012

1 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 1 x key-operated switch 2 NO


14 24

22
13 23

0.45 kg

GHG 411 8100 R0009

II

()

SW 5 engaging-engaging-engaging label: I 0 II 0.52 kg GHG 411 8100 R0018 1 x control switch SCT

I II

21 13

1 change-over SW 6 engaging-engaging label: HAND AUTO label: 0 label: I I II 0.45 kg 0.45 kg 0.45 kg GHG 411 8100 R0003 GHG 411 8100 R0004 GHG 411 8100 R0005

22/14

1 x control switch SCT


I 0 II 13 23

2 NO SW 5 engaging-engaging-engaging label: HAND 0 AUTO label: I 0 II label: Local Remote Auto 0.45 kg 0.45 kg 0.45 kg GHG 411 8100 R0006 GHG 411 8100 R0007 GHG 411 8100 R0008

14/24

9.8

COOPER CROUSE-HINDS GMBH

Ex-control stations

1 2
Type 411 82...18 Type 411 82...17 Type 411 82...03 Type 411 82...01

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering details type 411 82 with 2 built-in components


Version
13 21

3
Order No. GHG 411 8200 R0001

Built-in components 2 x pushbutton DRT 1 NO + 1 NC each label: 0, I, START, STOP

Weight approx.

14 22 13 21

0.54 kg

4 5

14 X1

22 X2

1 x signal lamp SIL 20-250 V AC/DC coloured lens cover: white, red, green, yellow

13 I 0 14

21

1 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 1 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 1 x mushroom-head pushbutton SGT 1 NO + 1 NC Emergency stop 0.57 kg GHG 411 8200 R0016 0.65 kg GHG 411 8200 R0003

22

13 I 0 14 13

21

6 7 8 9
0.65 kg GHG 411 8200 R0018

22 21

14 0I

22 21 13

1 x control switch SCT 1 change-over SW 6 engaging-engaging label: 0 I 1 x mushroom-head pushbutton SGT 1 NO + 1 NC Emergency stop 1 x signal lamp SIL 20-250 V AC/DC coloured lens cover: white, red, green, yellow 1 x key-operated switch 0.57 kg GHG 411 8200 R0017

22/14 13 21

14

22

X1

X2

II

13

23

2 NO SW 5 engaging-engaging-engaging label: I 0 II

()
14 24

10 11 12
COOPER CROUSE-HINDS GMBH

9.9

Ex-control stations

Type 411 83...01

Type 411 83...03

Type 411 83...23

Type 411 83...04

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering details type 411 83 with 3 built-in components


Version
X1 13 X2 21

Built-in components 1 x signal lamp SIL 20-250 V AC/DC coloured lens cover: white, red, green, yellow 2 x pushbutton DRT 1 NO + 1 NC each label: 0, I, START, STOP

Weight approx.

Order No.

14 13

22 21

0.76 kg

GHG 411 8300 R0001

14 X1

22 X2

1 x signal lamp SIL 20-250 V AC/DC coloured lens cover: white, red, green, yellow

13 I 0

21

1 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 1 x mushroom-head pushbutton SGT 1 NO + 1 NC Emergency stop 1 x measuring instrument AM72 CT connection n/1A Scale 0 100%/150% 0.80 kg GHG 411 8300 R0003

14 22 13 21

14 1

22 2

13 21

1 x control switch SCT 1 NO + 1 NC SW 8 engaging-engaging-spring label: 0 I 0.92 kg GHG 411 8300 R0023

14

22

X1

X2

1 x signal lamp SIL 20-250 V AC/DC coloured lens cover: white, red, green, yellow

13 I 0

21

1 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 1 x control switch SCT 1 change-over SW 6 engaging-engaging label: HAND - AUTO 0.80 kg GHG 411 8300 R0004

HA

14 22 21 13

22/14

9.10

COOPER CROUSE-HINDS GMBH

Ex-control stations

1 2
Measuring AM72

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering details measuring instrument AM72, type 411 82


Version Version direct measurement with 1 x cable entry M25 0-1 0-5 / 1.5 A / 7.5 A 0.70 kg 0.70 kg 0.70 kg 0.70 kg 0.70 kg 0.80 kg 0.80 kg GHG 411 8281 R0002 GHG 411 8281 R0003 GHG 411 8281 R0004 GHG 411 8281 R0005 GHG 411 8281 R0007 GHG 411 8285 R0033 GHG 411 8286 R0035 0 - 2.5 / 3.75 A 0 - 10 / 15 A 0 - 16 / 24 A 0 - 20 / 24 mA 0-100% / 120% (Ri =320 ) 4 - 20 / 24 mA 0-100% / 120% (Ri =320 ) Version CT connection n/1A with 1 x entry M25 0-1 0-5 / 1.5 A / 7.5 A 0.70 kg 0.70 kg 0.70 kg 0.70 kg 0.70 kg 0.70 kg 0.70 kg 0.70 kg 0.70 kg 0.70 kg 0.70 kg 0.70 kg 0.70 kg GHG 411 8282 R0002 GHG 411 8282 R0003 GHG 411 8282 R0004 GHG 411 8282 R0005 GHG 411 8282 R0007 GHG 411 8282 R0008 GHG 411 8282 R0009 GHG 411 8282 R0010 GHG 411 8282 R0011 GHG 411 8282 R0012 GHG 411 8282 R0013 GHG 411 8282 R0014 GHG 411 8282 R0001 0 - 2.5 / 3.75 A 0 - 10 / 15 A 0 - 15 / 22,5 A 0 - 20 / 30 A 0 - 30 / 45 A 0 - 40 / 60 A 0 - 50 / 75 A 0 - 60 / 90 A 0 - 75 / 112.5 A 0 - 100 / 150 A 0 100% / 150% Weight Order No.

3 4 5 6 7 8
X92 73

Dimension drawing
85 38 85 38
85 38

85

115 85

X52

155 125

40 X92

40 40 X132

195 165

155

125

9
75 77.5 5

X75 X75
X75

Type 411 81

Type 411 82

Type 411 83

5.6 73

10
Dimensions in mm

22

11 12

X = fixing dimension

Measuring instrument AM 72

COOPER CROUSE-HINDS GMBH

9.11

Ex-control stations

Size 1

Size 2

Size 4

Cooper Crouse-Hinds 2008 - all rights reserved

Accessories
Mounting plate for type 411 81 Type Size 1 Size 1 Size 1 Size 4 Size 4 Size 4 Application Wall mounting Pipe mounting Trellis-work mounting Wall mounting Trellis-work mounting Pipe mounting Mounting technique screw-on screw-on screw-on snap-on1) snap-on1) snap-on1) OU 1 1 1 1 1 1 Order No. GHG 610 1953 R0101 GHG 610 1953 R0102 GHG 610 1953 R0103 GHG 610 1953 R0126 GHG 610 1953 R0126 GHG 610 1953 R0130

Mounting plate for type 411 82 and 411 83 Type Application Mounting technique OU 1 1 1 1 1 1 10 Order No. GHG 610 1953 R0104 GHG 610 1953 R0105 GHG 610 1953 R0106 GHG 610 1953 R0126 GHG 610 1953 R0126 GHG 610 1953 R0130 GHG 610 1953 R0041 Size 2 Wall mounting screw-on Size 2 Pipe mounting screw-on Size 2 Trellis-work mounting screw-on Size 4 Wall mounting snap-on1) Size 4 Trellis-work mounting snap-on1) Size 4 Pipe mounting snap-on1) Snap-on mounting for CEAG apparatus with 5.5 mm and 11 mm mounting size per 4 pieces
1)

snap-on with snap-on mounting 5.5 mm

Dimension drawing
134.5 9 134.5 82

118.5

X54 X66
Size 1 Wall mounting Size 1 Pipe mounting

X51 X62

23 134.5

118.5

134.5

27

118.5

Size 1 Trellis-work mounting

237

X = fixing dimension

Size 4 Wall mounting

9.12

COOPER CROUSE-HINDS GMBH

Dimensions in mm

Ex-control stations

1 2
Type 434... Type 432...

Cooper Crouse-Hinds 2008 - all rights reserved

Technical data
Ex-Control stations Type 432 Type 434 Marking to 94/9/EC EC-Type Examination Certificate IECEx Certificate of conformity Marking accd. to IECEx Permissible ambient temperature Rated voltage Rated current Switch rating control switch GHG 23 Connecting terminals Insulation class Degree of protection accd. EN 60529 Cable glands/Gland plates/Enclosure drilling Enclosure material Enclosure colour Type 432 Dimensions (L x W x H) Weight (empty) Type 434 Dimensions (L x W x H) Weight (empty)
1)

3
II 2 G EEx e II T6 / EEx e ib IIC T6 / EEx ed IIC T6 / EEx ed ib IIC T6 II 2 D IP66 T 48 C / T53 C PTB 00 ATEX 3117 IECEx BKI 04.0003 Ex e II T6, Ex e ib IIC T6, Ex ed IIC T6 or Ex ed ib IIC T6 20 C to +40 C 55 C to +55 C (option) 690 V AC (with control switch GHG 23 to 500 V) 16 A (with control switch GHG 23 max. 10 A) AC 15: 230 V/10 A / 500 V/6 A DC 13: 24 V/ 2 A / 230 V/0.4 A 2 x 4 mm2 I IP66 (standard) IP65 (measuring instrument AM45, double pushbutton) 2 x M25 EEx-e cable gland for cables from 8 - 17 mm incl. 1 blanking plug or 2 x M20 thread Polyamide Black

4 5 6 7 8 9 10 11 12

156 x 100 x 90 mm 0.47 kg

245 x 100 x 90 mm 0.70 kg

Base enclosure can be rotated afterwards (entry from top or down)

Other versions available on request

COOPER CROUSE-HINDS GMBH

9.13

Ex-control stations

Type 432...01

Type 432...02

Type 432...03

Type 432...05

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering details type 432 with 2 built-in components


Version
13 21

Built-in components 2 x pushbutton DRT 1 NO + 1 NC each label: 0, I, START, STOP

Weight approx.

Order No.

14 22 13 21

0.85 kg

GHG 432 0011 R0001

14 X1

22 X2

1 x signal lamp SIL 20-250 V AC/DC coloured lens cover: white, red, green, yellow 1 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 0.90 kg GHG 432 0011 R0002 1 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 1 x mushroom-head pushbutton SGT 1 NO + 1 NC Emergency stop 1 x measuring instrument AM45 CT connection n/1A Scale 0 100%/150% 0.85 kg GHG 432 0011 R0003

13 I 0 14 13 I 0

21

22 21

14 22 13 21

14

22

13 I 0 14

21

1 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 0.95 kg GHG 432 0011 R0005

22

9.14

COOPER CROUSE-HINDS GMBH

Ex-control stations

1 2
Type 432...17 Type 432...05 Type 432...03

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering details type 432 with 1 control switch GHG 23


Version
5/7

3
Order No. GHG 432 0001 R0003 GHG 432 0001 R0004

Built-in components 1 x control switch GHG 23 1 change-over SW 6 engaging-engaging


6 8

Weight approx.

45 135

label: HAND - AUTO label: 0 2 NO SW 5 engaging-engaging-engaging label: HAND 0 AUTO label: I 1 NO + 1 NC SW 8 engaging-engaging-spring return label: 0 label: 0 IN I START 0 II 1 x control switch GHG 23 I 1 x control switch GHG 23

0.70 kg 0.70 kg

4 5 6 7 8

II

5/7 6 8

45 90 135

0.70 kg 0.70 kg

GHG 432 0001 R0005 GHG 432 0001 R0006

I 6

5 7

45 90 135

0.70 kg 0.70 kg 0.70 kg

GHG 432 0001 R0012 GHG 432 0001 R0013 GHG 432 0001 R0014

label: AUS-Betrieb-EIN 1 x control switch GHG 23

II

1/3

5/7

2 change-over SW 6 engaging-engaging label: I II I AUTO 0.70 kg 0.70 kg GHG 432 0001 R0015 GHG 432 0001 R0016

45 135

2 4 6 8

label: HAND
I II III 1 3 5

1 x control switch GHG 23 2 NO + 1 NC SW 5 engaging-engaging-engaging label: I 2 NO + 1 NC SW 8 engaging-engaging-spring return label: 0 label: 0 IN I START 0.86 kg 0.86 kg 0.86 kg GHG 432 0001 R0018 GHG 432 0001 R0019 GHG 432 0001 R0020 II III 0.86 kg GHG 432 0001 R0017 1 x control switch GHG 23

45 90 135

3 5

45 90 135

label: AUS-Betrieb-EIN

9 10 11 12
COOPER CROUSE-HINDS GMBH

9.15

Ex-control stations

Type 432...10

Type 432...09

Type 432...08

Type 432...06

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering details type 432 with 2 built-in components


Version
1 2

Built-in components 1 x measuring instrument AM45 CT connection n/1A Scale 0 100%/150%


5/7

Weight approx.

Order No.

1 6

1 x control switch GHG 23 1 change-over SW 6 spring return-engaging label: 0 I 1.35 kg GHG 432 0011 R0006 1 x measuring instrument AM45 CT connection n/1A Scale 0 100%/150%
5/7

45 135

II

1 x control switch GHG 23 2 NO SW 5 engaging-engaging-engaging label: I 0 II 1.35 kg GHG 432 0011 R0008 1 x measuring instrument AM45 CT connection n/1A Scale 0 100%/150%

45 90 135

6 8

I 6

5 7

1 x control switch GHG 23 1 NO + 1 NC SW 8 engaging-engaging-spring label: 0 I 1.35 kg GHG 432 0011 R0009 1 x measuring instrument AM45 CT connection n/1A Scale 0 100%/150%

45 90 135

II III

1 x control switch GHG 23 1 NO + 1 NC SW 5 engaging-engaging-engaging label: I II III 1.35 kg GHG 432 0011 R0010

45 90 135

9.16

COOPER CROUSE-HINDS GMBH

Ex-control stations

1 2
Type 434...11 Type 434...10 Type 434...02

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering details type 434 with 4 built-in components


Version
1 2

3
Weight approx. Order No.

Built-in components 1 x measuring AM72 CT connection n/1A Scale 0 100%/150%

13 I 0

21

1 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 1 x mushroom-head pushbutton SGT 1 NO + 1 NC Emergency stop 1 x measuring AM72 CT connection n/1A Scale 0 100%/150% 1.40 kg GHG 434 0111 R0002

4 5 6
1.55 kg GHG 434 0111 R0010

14 22 13 21

14 1

22 2

13

21

1 x mushroom-head pushbutton SGT 1 NO + 1 NC Emergency stop


5/7

14
0 1

22

1 x control switch GHG 23 1 change-over SW 6 engaging-engaging label: 0 I 1 x measuring AM72 CT connection n/1A Scale 0 100%/150%

45 135

7 8
1.55 kg GHG 434 0111 R0011

13

21

1 x mushroom-head pushbutton SGT 1 NO + 1 NC Emergency stop


5 7

14
0

22
I 6

1 x control switch GHG 23 1 NO + 1 NC SW 8 engaging-engaging-spring return label: 0 I

9 10 11 12
COOPER CROUSE-HINDS GMBH

9.17

Ex-control stations

Type 434...04

Type 434...05

Type 434...09

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering details type 434 with 4 built-in components


Version
X1 13 X2 21

Built-in components 1 x signal lamp SIL 20-250 V AC/DC coloured lens cover: white, red, green, yellow 2 x pushbutton DRT 1 NO + 1 NC label: 0, I, START, STOP 1 x mushroom-head pushbutton SGT 1 NO + 1 NC Emergency stop

Weight approx.

Order No.

14 13

22 21

14 13

22 21

1.45 kg

GHG 434 1111 R0004

14 X1 13 I 0 14 X1 13 I 0 14 X1 13 I 0 14 13

22 X2 21

2 x signal lamp SIL 20-250 V AC/DC coloured lens cover: white, red, green, yellow 2 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 1.45 kg GHG 434 1111 R0005

22 X2 21

22

X2 21

1 x signal lamp SIL 20-250 V AC/DC coloured lens cover: white, red, green, yellow 1 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 1 x mushroom-head pushbutton SGT 1 NO + 1 NC Emergency stop
13 23

22 21

14

22

1 x key-operated switch 2 NO SW 5 engaging-engaging-engaging label: I 0 II 1.55 kg GHG 434 1111 R0009

II

()
14 24

9.18

COOPER CROUSE-HINDS GMBH

Ex-control stations

1 2
Size 5 Size 3 Size 2

Cooper Crouse-Hinds 2008 - all rights reserved

Accessories
Mounting plate for type 432 Type Size 2 Size 2 Size 2 Size 5 Size 5 Size 5 Application Wall mounting Pipe mounting Trellis-work mounting Wall mounting Trellis-work mounting Pipe mounting Mounting technique screw-on screw-on screw-on snap-on * snap-on * snap-on * OU 1 1 1 1 1 1 Order No. GHG 610 1953 R0104 GHG 610 1953 R0105 GHG 610 1953 R0106 GHG 610 1953 R0128 GHG 610 1953 R0128 GHG 610 1953 R0132

3 4 5 6 7 8 9

Mounting plate for type 434 Type Application Mounting technique OU 1 1 1 1 1 1 10 Order No. GHG 610 1953 R0118 GHG 610 1953 R0110 GHG 610 1953 R0118 GHG 610 1953 R0128 GHG 610 1953 R0128 GHG 610 1953 R0132 GHG 610 1953 R0041 Size 3 Wall mounting screw-on Size 3 Pipe mounting screw-on Size 3 Trellis-work mounting screw-on Size 5 Wall mounting snap-on * Size 5 Trellis-work mounting snap-on * Size 5 Pipe mounting snap-on * Snap-on mounting for CEAG apparatus with 5.5 mm and 11 mm mounting size per 4 pieces * snap-on with snap-on mounting 5.5 mm

Dimension drawing
100 X88 90 100 X88 90

156 X 97 5.2

Type 432
134.5 9 134.5

Type 434
82 134.5 23

245 X 186

5.2

10
186 186 X94 X105 186 X30
Dimensions in mm

11 12

X54 X66

Size 2 Pipe mounting X = fixing dimension

Size 2 Trellis-work mounting

Size 2 Wall mounting

COOPER CROUSE-HINDS GMBH

9.19

E X - C O N T R O L
Light alloy Ve r s i o n f o r Z o n e 1

S T A T I O N S

Light-alloy control stations in explosionprotected design are equipped with up to four components. These control stations are made of high-quality cast aluminium-silicon (AlSi). A robust plastic powder coating according to RAL 7031 protects the CEAG control stations

Cooper Crouse-Hinds 2008 - all rights reserved


9.20

against aggres sive atmospheres and chemicals. Cover screws as well as all internal and external metal parts are made of stainless steel. CEAG flameproof built-in components, such as signal lamps, pushbuttons and switches, provide snap-on mounting on rails screwed into the enclosures. To facilitate insertion of cables into the entries, the built-in components can be snapped out of the enclosures. Notches in the mounting rails define the position of the built-in components and prevent them from being twisted out of place. Free mounting areas can be provided for retrofitting certified CEAG components. These are then factory sealed with blanking elements. Internationally approved.

High mechanical, chemical and thermal resistance Individual configuration Impact-resistant plastic powder coating

Ex-control stations

1 2
Measuring AM72 Type 413 85 Type 413 84

Cooper Crouse-Hinds 2008 - all rights reserved

Technical data
Ex-Control stations Type 413 84 Type 413 85 Marking to 94/9/EC EC-Type Examination Certificate IECEx Certificate of conformity Marking accd. to IECEx Permissible ambient temperature Rated voltage Rated current Switch rating control switch GHG 23 Connecting terminals Insulation class Degree of protection accd. EN 60529 Cable glands/Gland plates/Enclosure drilling Enclosure material Enclosure colour Type 413 84 Dimensions (L x W x H) Weight (empty) Type 413 85 Dimensions (L x W x H) Weight (empty) 122 x 120 x 81 mm 1.45 kg 122 x 120 x 81 mm 0.85 kg II 2 G EEx e II T6 / EEx e ib IIC T6 / EEx ed IIC T6 / EEx ed ib IIC T6 II 2 D IP66 T 48 C / T 53 C PTB 00 ATEX 3117 IECEx BKI 04.0003 Ex e II T6, Ex e ib IIC T6, Ec ed IIC T6 or Ex ed ib IIC T6 20 C to +40 C 55 C to +55 C (option) 690 V AC (with control switch GHG 23 to 500 V) 35 A (with control switch GHG 23 max. 10 A) AC 15: 230 V/10 A / 500 V/6 A DC 13: 24 V/ 2 A / 230 V/0.4 A 2 x 4 mm2 I IP66 (standard) IP65 (measuring instrument AM45, double pushbutton) 1 x M20 threaded entry High quality cast aluminium-silicone (AISi) Grey RAL 7031

3 4 5 6 7 8
Moving coil II G EEx ib IIC Class 1.5 10-fold -5 sec.

Type 413 84 with measuring instrument AM 72 Moving iron Marking to 94/9/EC Accuracy Overload range II G EEx e II Class 2.5 10-fold -25 sec. 25-fold - 4 sec. 50-fold - 1 sec. indicated 1:1.5 Measuring range Li Ci Ui Ii Connecting terminals Weight
1)

9 10 11 12

n / 1A 0 - 25 A direct 2 x 1.5 - 4 mm2 1.25 kg

0 - 20 mA 4 - 20 mA max. 0.1 mH max. 0.1 nF max. 30 V max. 150 mA

Base enclosure can be rotated afterwards (entry from top or down)

Other versions available on request

COOPER CROUSE-HINDS GMBH

9.21

Ex-control stations

Type 413 84...01

Type 413 84...02

Type 413 84...03

Type 413 84...04

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering details type 413 84 with 2 built-in components


Version
13 21

Built-in components 2 x pushbutton DRT 1 NO + 1 NC each label: 0, I, START, STOP

Weight approx.

Order No.

14 22 13 21

1.25 kg

GHG 413 8400 R0001

14 X1

22 X2

1 x signal lamp SIL 20-250 V AC/DC coloured lens cover: white, red, green, yellow 1 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 1 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 1 x mushroom-head pushbutton SGT 1 NO + 1 NC Emergency stop 1 x measuring instrument AM45 CT connection n/1A Scale 0 100%/150% 1 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 1.35 kg GHG 413 8400 R0004 1.30 kg GHG 413 8400 R0003 1.30 kg GHG 413 8400 R0002

13 I 0 14 13 I 0

21

22 21

14 22 13 21

14 1 13 I 0 14

22 2 21

22

9.22

COOPER CROUSE-HINDS GMBH

Ex-control stations

1 2
Type 413 85...03 Type 413 85...02 Type 413 85...01

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering details type 413 85 with 4 built-in components


Version
X1 13 X2 21

3
Order No.

Built-in components 1 x signal lamp SIL 20-250 V AC/DC coloured lens cover: white, red, green, yellow 2 x pushbutton DRT 1 NO + 1 NC label: 0, I, START, STOP 1 x mushroom-head pushbutton SGT 1 NO + 1 NC Emergency stop

Weight approx.

4
2.10 kg GHG 413 8500 R0001

14 22 13 21

14 22 13 21

5 6

14 X1 13 I 0 14 X1 13 I 0 14

22 X2 21

2 x signal lamp SIL 20-250 V AC/DC coloured lens cover: white, red, green, yellow 2 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 2.10 kg GHG 413 8500 R0002

22 X2 21

22

X1

X2

1 x signal lamp SIL 20-250 V AC/DC coloured lens cover: white, red, green, yellow label: I 0 II

7 8 9
2.20 kg GHG 413 8500 R0003

13 I 0

21

1 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 1 x mushroom-head pushbutton SGT 1 NO + 1 NC Emergency stop
13 23

14 22 13 21

14
I 0

22
II

1 x key-operated switch 2 NO SW 5 engaging-engaging-engaging label: I 0 II

()
14 24

10 11 12
COOPER CROUSE-HINDS GMBH

9.23

Ex-control stations

Measuring AM72

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering details type 413 84 with measuring instrument AM72


Version Version direct measurement with 1 x threaded entry M20 01 0-5 / 1.5 A / 7.5 A 1.25 kg 1.25 kg 1.25 kg 1.25 kg 1.25 kg 1.35 kg 1.35 kg GHG 413 8481 R0002 GHG 413 8481 R0003 GHG 413 8481 R0004 GHG 413 8481 R0005 GHG 413 8481 R0007 GHG 413 8481 R0033 GHG 413 8481 R0035 0 - 2.5 / 3.75 A 0 - 10 / 15 A 0 - 16 / 24 A 0 - 20 / 4 - 20 / 24 mA 0-100% / 120% (Ri =320 ) 24 mA 0-100% / 120% (Ri =320 ) Weight approx. Order No.

Version CT connection n/1A with 1 x threaded entry M20 01 0-5 / 1.5 A / 7.5 A
Z

1.25 kg 1.25 kg 1.25 kg 1.25 kg 1.25 kg 1.25 kg


Z Z

GHG 413 8482 R0002 GHG 413 8482 R0003 GHG 413 8482 R0004 GHG 413 8482 R0005 GHG 413 8482 R0007 GHG 413 8482 R0008 GHG 413 8482 R0009 GHG 413 8482 R0010 GHG 413 8482 R0011 GHG 413 8482 R0012 GHG 413 8482 R0013 GHG 413 8482 R0014 GHG 413 8482 R0033

0 - 2.5 / 3.75 A 0 - 10 / 15 A 0 - 15 / 22.5 A 0 - 20 / 30 A 0 - 30 / 45 A 0 - 40 / 60 A 0 - 50 / 75 A 0 - 60 / 90 A 0 - 75 / 112.5 A 0 - 100 / 150 A 0 100% / 150%


Z

1.25 kg 1.25 kg 1.25 kg 1.25 kg 1.25 kg 1.25 kg 1.25 kg

Dimension drawing
Z Z Z Z

122 X 106

X82 120 Z 20.8 7

81

220 X 204

122 X 106

X82 120 Z

90

Z X82 120 Z 20.8 81 7

20.8

Type 413 84

Type 413 84
Dimensions in mm COOPER CROUSE-HINDS GMBH

X = fixing dimension

Type 413 85

9.24

Cooper Crouse-Hinds 2008 - all rights reserved

COOPER CROUSE-HINDS GMBH

9.25

12

11

10

Stainless steel Ve r s i o n f o r Z o n e 1

CEAG explosion-protected control stations made of high-grade 316L stainless steel are designed to accommodate up to four built-in components. These stainless-steel control stations with electro-polished sur faces offer protection for applications in the off-shore industry and at sites

Cooper Crouse-Hinds 2008 - all rights reserved


9.26

with especially severe mechanical, chemical and climatic conditions. CEAG flameproof built-in components, such as signal lamps, pushbuttons and switches, provide snap-on mounting on rails screwed into the enclosures. To facilitate insertion of cables into the entries, the built-in components can be snapped out of the enclosures. Notches in the mounting rails define the position of the built-in components and prevent them from being twisted out of place. Free mounting areas can be provided for retrofitting certified CEAG components. These are then factory sealed with blanking elements. Internationally approved.

High mechanical, chemical and thermal resistance Individual configuration Clean-room applications

Ex-control stations

1 2
Type 414 81.. Housing GHG 414 82 Housing GHG 414 81

Cooper Crouse-Hinds 2008 - all rights reserved

Technical data
Ex-Control stations Type 414 81 Type 414 82 Marking to 94/9/EC EC-Type Examination Certificate IECEx Certificate of conformity Marking accd. to IECEx Permissible ambient temperature Rated voltage Rated current Switch rating control switch GHG 23 II 2 G EEx e II T6 / EEx e ib IIC T6 / EEx ed IIC T6 / EEx ed ib IIC T6 II 2 D IP66 T 48 C / T 53 C PTB 00 ATEX 3117 IECEx BKI 04.0003 Ex e II T6, Ex e ib IIC T6, Ec ed IIC T6 or Ex ed ib IIC T6 20 C to +40 C 55 C to +55 C (option) 690 V AC (with control switch GHG 23 to 500 V) 16 A (with control switch GHG 23 max. 10 A) AC 15: 230 V/10 A / 500 V/6 A DC 13: 24 V/ 2 A / 230 V/0.4 A with gold contact points max. 0.4 A Connecting terminals Insulation class Degree of protection accd. EN 60529 Cable glands/Gland plates/Enclosure drilling Enclosure material Type 414 81 Dimensions (L x W x H) Weight (empty) Type 414 82 Dimensions (L x W x H) Weight (empty) 286 x 140 x 76 mm 2.10 kg 166 x 140 x 76 mm 1.40 kg 2 x 4 mm2 I IP66 (standard) IP65 (measuring instrument AM45, double pushbutton) 1 x drilling 21 mm for cable gland M20 Stainless steel AISI 316 L

3 4 5 6 7 8
Moving coil II G EEx ib IIC Class 1.5 10-fold -5 sec.

Type 414 81 with measuring instrument AM 72 Moving iron Marking to 94/9/EC Accuracy Overload range II G EEx e II Class 2.5 10-fold -25 sec. 25-fold - 4 sec. 50-fold - 1 sec. indicated 1:1.5 Measuring range Li Ci Ui Ii Connecting terminals Weight
1)

9 10 11 12

n / 1A 0 - 25 A direct 2 x 1.5 - 4 mm2 1.25 kg

0 - 20 mA 4 - 20 mA max. 0.1 mH max. 0.1 nF max. 30 V max. 150 mA

Base enclosure can be rotated afterwards (entry from top or down)

Other versions available on request

COOPER CROUSE-HINDS GMBH

9.27

Ex-control stations

Type 414 81...01

Type 414 81...02

Type 414 81...03

Type 414 81...04

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering details type 414 81 with 2 built-in components


Version*
13 21

Built-in components 2 x pushbutton DRT 1 NO + 1 NC each label: 0, I, START, STOP

Weight approx.

Order No.

14 22 13 21

1.80 kg

GHG 414 8100 R0001

14 X1

22 X2

1 x signal lamp SIL 20-250 V AC/DC coloured lens cover: white, red, green, yellow 1 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 1 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 1 x mushroom-head pushbutton SGT 1 NO + 1 NC Emergency stop 1 x measuring instrument AM45 CT connection n/1A Scale 0 100%/150% 1 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 1.85 kg GHG 414 8100 R0004 1.85 kg GHG 414 8100 R0003 1.85 kg GHG 414 8100 R0002

13 I 0 14 13 I 0

21

22 21

14 22 13 21

14 1 13 I 0 14

22 2 21

22

*Without external fixing lugs (see accessories page 9.30)

9.28

COOPER CROUSE-HINDS GMBH

Ex-control stations

1 2
Type 414 82...03 Type 414 82...02 Type 414 82...01

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering details type 414 82 with 4 built-in components


Version*
X1 13 X2 21

3
Order No.

Built-in components 1 x signal lamp SIL 20-250 V AC/DC coloured lens cover: white, red, green, yellow 2 x pushbutton DRT 1 NO + 1 NC label: 0, I, START, STOP 1 x mushroom-head pushbutton SGT 1 NO + 1 NC Emergency stop

Weight approx.

4
2.80 kg GHG 414 8200 R0001

14 22 13 21

14 22 13 21

5 6

14 X1 13 I 0 14 X1 13 I 0 14 X1

22 X2 21

2 x signal lamp SIL 20-250 V AC/DC coloured lens cover: white, red, green, yellow 2 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 2.80 kg GHG 414 8200 R0002

22 X2 21

22 X2

1 x signal lamp SIL 20-250 V AC/DC coloured lens cover: white, red, green, yellow

7 8
2.90 kg GHG 414 8200 R0003

13 I 0

21

1 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 1 x mushroom-head pushbutton SGT 1 NO + 1 NC Emergency stop
II 13 23

14 22 13 21

14
I

22
0

1 x key-operated switch 2 NO SW 5 engaging-engaging-engaging label: I 0 II

()
14 24

*Without external fixing lugs (see accessories page 9.30)

9 10 11 12

COOPER CROUSE-HINDS GMBH

9.29

Ex-control stations

Type 414 81..

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering details type 414 81 with measuring AM72


Version 01 0-5 / 1.5 A / 7.5 A Weight approx. 1.25 kg 1.25 kg 1.25 kg 1.25 kg 1.25 kg 1.35 kg 1.35 kg Order No. GHG 414 8181 R0002 GHG 414 8181 R0003 GHG 414 8181 R0004 GHG 414 8181 R0005 GHG 414 8181 R0007 GHG 414 8181 R0033 GHG 414 8181 R0035

Version direct measurement with 1 x threaded entry 21 mm (without external fixing lugs) 0 - 2.5 / 3.75 A 0 - 10 / 15 A 0 - 16 / 24 A 0 - 20 / 4 - 20 / 24 mA 0-100% / 120% (Ri =320 ) 24 mA 0-100% / 120% (Ri =320 )

Version CT connection n/1A with 1 x threaded entry 21 mm (without external fixing lugs) 01 0-5 / 1.5 A / 7.5 A 1.25 kg 1.25 kg 1.25 kg 1.25 kg 1.25 kg 1.25 kg 1.25 kg 1.25 kg 1.25 kg 1.25 kg 1.25 kg 1.25 kg 1.25 kg GHG 414 8182 R0002 GHG 414 8182 R0003 GHG 414 8182 R0004 GHG 414 8182 R0005 GHG 414 8182 R0007 GHG 414 8182 R0008 GHG 414 8182 R0009 GHG 414 8182 R0010 GHG 414 8182 R0011 GHG 414 8182 R0012 GHG 414 8182 R0013 GHG 414 8182 R0014 GHG 414 8182 R0033 0 - 2.5 / 3.75 A 0 - 10 / 15 A 0 - 15 / 22.5 A 0 - 20 / 30 A 0 - 30 / 45 A 0 - 40 / 60 A 0 - 50 / 75 A 0 - 60 / 90 A 0 - 75 / 112.5 A 0 - 100 / 150 A 0 - 100% / 150%

Accessories

Type External fixing lugs (2 pcs)

Order No. GHG 610 1941 R0013

Dimension drawing

X214 166

X334 286

X214 166

59 X87.5 140 148


Type 414 81

59 76 88
Type 414 81

X87.5 140 148

10 76 88
Dimensions in mm

X87.5 140 148


X = fixing dimension Type 414 82

59 76 88

9.30

COOPER CROUSE-HINDS GMBH

Cooper Crouse-Hinds 2008 - all rights reserved

COOPER CROUSE-HINDS GMBH

9.31

12

11

10

T A T

For individual controls Moulded-plastic version for Zone 1

CEAG control stations can be combined according to customers' specifications. Quick fixing allows up to three CEAG built-in components, such as signal lamps, pushbuttons and switches, to be snapped on a rail in the enclosure. The enclosures consist of low-temperature

Cooper Crouse-Hinds 2008 - all rights reserved


9.32

impact-resistant thermoplastic which fulfils the requirements of EN 60079 and provides a high resistance to chemicals. The well thought out design with low side walls allows optimum cable connection. The components can be snapped out of the enclosure to facilitate cable-entry feeding. Notches in the mounting rails prevent the built-in components from being twisted out of place. CEAG's optional mounting plates offer a timesaving fixing technique. Coupling pieces link enclosures to each other and prevent them from being twisted out of place. Alternatively, metal screws and flanges can be used for mounting the metal flanges also enable external earthing. The built-in components differ in size. The diverse enclosure types allow variable combinations of these components. Example diagrams of the enclosure types show the placement options for the built-in components with numbers or predefined positions. Free mounting areas can be provided for retrofitting certified CEAG components. These are then factory sealed with blanking elements. Internationally approved.

Flat side walls Quick fixing for all built-in components High chemical resistance Different enclosures can be combined

I
Customised control stations, covered by type examination certificates, can be individually combined from CEAG's numerous built-in components. complete control station.

Ex-control stations

ordering. The sum of the code numbers designates a

1 2

For the selection of control units and components, please A coding system for these components with unique designations can be used for planning, selection and see page 9.34 pp.

Double pushbutton DDT

Pushbutton DRT

Cooper Crouse-Hinds 2008 - all rights reserved

2-pole and 4-pole

3 4 5
Measuring instrument AM72

Signal lamp SIL

Mushroom-head pushbutton SGT

6 7
Control switch SCT

8 9

Key-operated pushbutton SLT and keyoperated switch SLS Control switch GHG 23

10
Terminal block KLM Potentiometer POT

11 12
COOPER CROUSE-HINDS GMBH

9.33

Order Code for Individual Control Units

Individual control units can be defined by 4 groups of components: 1. Empty Enclosure 2. Components per mounting area 3. Accessories 4. Cable glands

Code 1: Empty Enclosure

Code 2: Components per mounting area (max. 4) A C D(1) (D2) E F Mounting area 1 MA1 Mounting area 2 MA2 Mounting area 3 MA3 Mounting area 4 MA4

Cooper Crouse-Hinds 2008 - all rights reserved

Code for enclosure


1

D(1)

(D2)

A 411 81

D(1)

(D2)

MA
2 1

A 411 82

D(1)

(D2)

MA

MA

3 2 1

411 83

2 1

Pushbutton DRT 2-pole 4-pole 432

Signal lamp SIL

MA

4 3 2 1

MA

434

Double-pushbutton DDT 2-pole 4-pole

Potentiometer POT

2 1

MA

414 81 Key-operated pushbutton SLT 2-pole 4-pole


4 3 2 1

Control switch Ex 23 Ex 29

MA
2 1 4 3 2 1

414 82

Key-operated switch SLS 2-pole 4-pole

Measuring instrument AM 45 AM 72

MA

413 84

MA

413 85

Mushroom-head pushbutton SGTE SGT

Terminal block KLM

9.34

COOPER CROUSE-HINDS GMBH

I
Example: Enclosure Type 434, Pushbutton (MA4), Signal lamp (MA3) Emergency stop Mushroom head pushbutton (MA2) Double pushbutton (MA1) Code Code Code Code Code

Order Code for Individual Control Units

1: 434.. 2 MA4: DRT 14 001 2 MA3: SIL 1 10 2 MA2 SGTE 13 1 1 2 2 MA1: DDT15 001 007

Code Code Code Code Code

3 MA1: 3 MA2: 3 MA3: 3 MA4: 4: GEH

ZUB 19 ZUB 19 ZUB 02 -1 GK M25 2

1 2 3 4 5 6

Code 3: Lables and locking facilities A B .............. A B .............. A B .............. A B .............. C C C C Mounting area 1 MA1 Mounting area 2 MA2 Mounting area 3 MA3 Mounting area 4 MA4

Code 4: Cable entries and flanges A B C D E

Cooper Crouse-Hinds 2008 - all rights reserved

Metal flange plate FLM Label with holder ZUB 20

plastic cable gland GK locking facility ZUB 14

7
plastic trumpet-shaped cable gland TR

8 9

locking facility with hammer ZUB 05

locking facility ZUB 12

position for drilling/gland

10 11

locking facility double pushbutton ZUB 17

12
COOPER CROUSE-HINDS GMBH

9.35

Ex-control stations

Type 411 81

Type 411 82

Type 432

Type 434

Cooper Crouse-Hinds 2008 - all rights reserved

Technical data
Ex-Control stations Type 41. and 43. for individual configuration Marking to 94/9/EC EC-Type Examination Certificate IECEx Certificate of conformity Marking accd. to IECEx Permissible ambient temperature Rated voltage Rated current Connecting terminals Insulation class Degree of protection accd. EN 60529 Cable glands/Gland plates/Enclosure drilling Enclosure material Enclosure colour Type 411 81 Cable glands/Gland plates/Enclosure drilling Dimensions (L x W x H) Weight (empty) Mounting arrangements Type 411 82 Cable glands/Gland plates/Enclosure drilling Dimensions (L x W x H) Weight (empty) Mounting arrangements Type 411 83 Cable glands/Gland plates/Enclosure drilling Dimensions (L x W x H) Weight (empty) Mounting arrangements Type 432 Cable glands/Gland plates/Enclosure drilling Dimensions (L x W x H) Weight (empty) Mounting arrangements Type 434 Cable glands/Gland plates/Enclosure drilling Dimensions (L x W x H) Weight (empty) Mounting arrangements 2 x M25 EEx-e cable gland for cables from 8 - 17 mm incl. 1 blanking plug or 2 x M20 thread 245 x 100 x 90 mm 0.70 kg 4 mounting areas 2 x M25 EEx-e cable gland for cables from 8 - 17 mm incl. 1 blanking plug or 2 x M20 thread 156 x 100 x 90 mm 0.47 kg 2 mounting areas 1 x M25 EEx-e cable gland for cables from 8 - 17 mm or 1 x M20 thread 165 x 85 x 77.5 mm 0.45 kg 3 mounting areas 1 x M25 EEx-e cable gland for cables from 8 - 17 mm or 1 x M20 thread 125 x 85 x 77.5 mm 0.35 kg 2 mounting areas 1 x M25 EEx-e cable gland for cables from 8 - 17 mm or 1 x M20 thread 85 x 85 x 77.5 mm 0.25 kg 1 mounting area II 2 G EEx e II T6 / EEx e ib IIC T6 / EEx ed IIC T6 / EEx ed ib IIC T6 II 2 D IP66 T 48 C PTB 00 ATEX 3117 IECEx BKI 04.0003 Ex e II T6, Ex e ib IIC T6, Ex ed IIC T6 or Ex ed ib IIC T6 20 C to +40 C 55 C to +55 C (option) 690 V AC 16 A 2 x 4 mm2 I IP66 (standard) IP65 (measuring instrument AM45, double pushbutton) 1 x M25 EEx-e cable gland for cables from 8 - 17 mm or 1 x M20 thread Polyamide black

9.36

COOPER CROUSE-HINDS GMBH

Ex-control stations

1 2
Type 434 Type 432 Type 411 82 Type 411 81

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering codes (Code 1)


1. Empty enclosure 2. Components arrangement/Terminals Mounting area 1 411 811) 411 82 411 83 432 434 X X X X X Mounting area 2 X X X X Mounting area 3 X X Mounting area 4 X X X X X X X X X X X 3. Labels/Locking devices 4. Cable glands

3 4 5
Component Measuring instrument Measuring instrument Signal lamp Potentiometer Terminal block (4 mm2) Blanking element Code AM722) AM45 SIL POT KLM BLV

Possible components (Code 1)


Component Pushbutton (2-pole or 4-pole)2) Double pushbutton (2-pole or 4-pole)2) Key-operated pushbutton (2-pole or 4-pole)2) Key switch (2-pole or 4-pole)2) Control switch (2-pole or 4-pole)2) Control switch
1) 2) 3)

Code DRT DDT SLT SLS SCT GHG 233)

6 7 8 9 10 11 12

Mushroom-head pushbutton (2-pole or 4-pole)2) SGT 4-pole component not possible 2 mounting areas are needed only for type 43., 2 mounting areas are needed

COOPER CROUSE-HINDS GMBH

9.37

Ex-control stations

Type 411 81

Type 411 82

Type 432

Type 434

Cooper Crouse-Hinds 2008 - all rights reserved

Mounting areas

Dimension drawing
85 38 77.5 5 X52 X75 85 38

AM45
115 85 5.6

Type 411 81

22 77.5 5

2 1

AM45 AM72
155 125 40 X92 X75 85 38

5.6

Type 411 82

22 77.5 5

3 2 1

AM45 AM72
40 40 X132 X75 100 X88
AM72 EX23 2 Floors

2 1 1
195 165

5.6

Type 411 83

22 6 90

AM45 EX23 1 Floor

Type 432
100 X88
AM72 3 2 1 3 2 EX23 1 Floor EX23 2 Floors 3 2 1 AM72

156 X 97 5.2

AM45

90

245 X 186

EX23 2 Floors

5.2

Type 434

X = fixing dimension

9.38

COOPER CROUSE-HINDS GMBH

Dimensions in mm

Ex-control stations

1 2
Type 414 82 Type 414 81 Type 413 85 Type 413 84

Cooper Crouse-Hinds 2008 - all rights reserved

Technical data
Ex-Control stations Type 413. and 414. for individual configuration Marking to 94/9/EC EC-Type Examination Certificate IECEx Certificate of conformity Marking accd. to IECEx Permissible ambient temperature Rated voltage Rated current Connecting terminals PE-connection terminals Insulation class Degree of protection accd. EN 60529 II 2 G EEx e II T6 / EEx e ib IIC / EEx ed ib IIC T6 II 2 D IP66 T 48 C PTB 00 ATEX 3117 IECEx BKI 04.0003 Ex e II T6, Ex e ib IIC T6, Ex ed IIC T6 or Ex ed ib IIC T6 20 C to +40 C 55 C to +55 C (option) 690 V AC 16 A see technical data for built-in components 2 x 4 mm2 I IP66 (standard) IP65 (measuring instrument or double pushbutton) Type 413 84 Cable glands/Gland plates/Enclosure drilling Dimensions (L x W x H) Weight (empty) Enclosure material Enclosure colour Mounting arrangements Type 413 85 Cable glands/Gland plates/Enclosure drilling Dimensions (L x W x H) Weight (empty) Enclosure material Enclosure colour Mounting arrangements Type 414 81 Cable glands/Gland plates/Enclosure drilling Dimensions (L x W x H) Weight (empty) Enclosure material Enclosure colour Mounting arrangements Type 414 82 Cable glands/Gland plates/Enclosure drilling Dimensions (L x W x H) Weight (empty) Enclosure material Enclosure colour Mounting arrangements 1 x 21 mm for cable gland M20 286 x 140 x 76 mm 2.10 kg Stainless steel AISI 316 L polished 4 mounting areas 1 x 21 mm for cable gland M20 166 x 140 x 76 mm 1.40 kg Stainless steel AISI 316 L polished 2 mounting areas 1 x M20 thread 122 x 120 x 81 mm 1.45 kg cast aluminium-silicon (AISi) grey RAL 7031 4 mounting areas 1 x M20 thread 122 x 120 x 81 mm 0.85 kg cast aluminium-silicon (AISi) grey RAL 7031 2 mounting areas

3 4 5 6 7 8 9 10 11 12
COOPER CROUSE-HINDS GMBH

9.39

Ex-control stations

Type 413 84

Type 413 85

Type 414 81

Type 414 82

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering codes (Code 1)


1. Empty enclosure 2. Components arrangement/Terminals Mounting area 1 413 84 413 85 414 81 414 82 X X X X Mounting area 2 X X X X Mounting area 3 X X Mounting area 4 X X X X X X X X X X 3. Labels/Locking devices 4. Cable glands

Possible components (Code 1)


Component Pushbutton (2-pole or 4-pole) Double pushbutton (2-pole or 4-pole) Key switch (2-pole or 4-pole) Control switch (2-pole or 4-pole) Control switch
1)

Code DRT DDT SLS SCT GHG 231)

Component Measuring instrument Measuring instrument Signal lamp Potentiometer Terminal block (4 mm2) Blanking element

Code AM721) AM45 SIL POT KLM BLV

Key-operated pushbutton (2-pole or 4-pole) SLT

Mushroom-head pushbutton (2-pole or 4-pole) SGT 2 mounting areas are needed

9.40

COOPER CROUSE-HINDS GMBH

Ex-control stations

1
Z

2
Type 414 82 Type 414 81 Type 413 85 Type 413 84

Cooper Crouse-Hinds 2008 - all rights reserved

Mounting areas

Dimension drawing
Z Z

3
Z 122 X 106 7 20.8

AM45 AM72

4 5 6

X82 120

81

Type 413 84
Z Z
4 3 2 1 AM45 AM72 3 2 1 2 1

220 X 204

X82 120

81

Type 413 85
Z Z
2 AM45 AM72

7 8

X214 166

X87.5 140 148

59 76 88

Type 414 81

9 10

4 3 2 1

AM45 AM72 3 2 1 2 1

Type 414 82
Dimensions in mm

X334 286

11 12

X = fixing dimension

X87.5 140 148

59 76 88

COOPER CROUSE-HINDS GMBH

9.41

Ex-control stations

Type 444 23

Type 448 23

Type 449 23

Type 447 23

Cooper Crouse-Hinds 2008 - all rights reserved

Technical data
Ex-Control stations Type 444, 448, 449, and 447 for individual configuration Marking to 94/9/EC EC-Type Examination Certificate IECEx Certificate of conformity Marking accd. to IECEx Permissible ambient temperature Rated voltage Rated current Connecting terminals PE-connection terminals Insulation class Degree of protection accd. EN 60529 Cable glands/Gland plates/Enclosure drilling Enclosure material Enclosure colour Type 444 23 Connecting terminals Dimensions (L x W x H) Weight (empty) Mounting arrangements Type 448 23 Connecting terminals Dimensions (L x W x H) Weight (empty) Mounting arrangements max. 30 terminals UT 4 271 x 271 x 136 mm 2.5 kg with mounting framework distance 40 mm distance 50 mm distance 60 mm Type 449 23 Connecting terminals Dimensions (L x W x H) Weight (empty) Mounting arrangements max. 60 terminals UT 4 544 x 271 x 136 mm 4.5 kg with mounting framework distance 40 mm distance 50 mm distance 60 mm Type 447 23 Connecting terminals Dimensions (L x W x H) Weight (empty) Mounting arrangements max. 90 terminals UT 4 817 x 271 x 136 mm 6.5 kg with mounting framework distance 40 mm distance 50 mm distance 60 mm max. 64 mounting areas max. 45 mounting areas max. 36 mounting areas max. 36 mounting areas max. 30 mounting areas max. 24 mounting areas max. 18 mounting areas max. 15 mounting areas max. 12 mounting areas max. 20 terminals UT 4 271 x 134 x 136 mm 1.5 kg with mounting framework 6 mounting areas II 2 G EEx e II T6 / EEx e ib IIC T6 / EEx ed ib IIC T6 II 2 D IP66 T 80 C/95 C PTB 99 ATEX 1044 IECEx BKI 07.0023 Ex de ia/ib m [ia/ib] IIC T4 .. T6 Ex tD A21 IP66 T80 C 20 C to +40 C 55 C to +55 C (option) 690 V AC 40 A see technical data for built-in components 2 x 4 mm2 I IP66 (standard) IP65 (measuring instrument or double pushbutton) as ordered accd. to manufacturers specification glass-fibre reinforced polyester black

9.42

COOPER CROUSE-HINDS GMBH

Ex-control stations

1 2
Type 447 23 Type 449 23 Type 448 23 Type 444 23

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering codes (Code 1)


1. Empty enclosure 2. Components arrangement/Terminals Mounting area 1 ... 6 444 23 448 23 449 23 447 23 X X X X Mounting area 7 ... 18 X X X Mounting area 19 ... 36 X X Mounting area 37 ... 64 X X X X X X X X X 3. Labels/Locking devices 4. Cable glands

3 4 5 6 7 8 9 10 11 12

Possible components (Code 1)


Component Pushbutton (2-pole or 4-pole) Double pushbutton (2-pole or 4-pole) Key switch (2-pole or 4-pole) Control switch (2-pole or 4-pole) Control switch
1)

Code DRT DDT SLS SCT GHG 231)

Component Measuring instrument Measuring instrument Signal lamp Potentiometer Terminal block (4 mm2) Blanking element

Code AM721) AM45 SIL POT KLM BLV

Key-operated pushbutton (2-pole or 4-pole) SLT

Mushroom-head pushbutton (2-pole or 4-pole) SGT 2 mounting areas are needed

COOPER CROUSE-HINDS GMBH

9.43

Ex-control stations

Type 444 23

Type 448 23

Type 449 23

Type 447 23

Cooper Crouse-Hinds 2008 - all rights reserved

Mounting areas

Dimension drawing

13

14

15

16

17

18

4 7 8 9 10 11 12

2 1 2 3 4 5 6

Distance between centres 40 mm

4 11 12 13 14 15

2 6 7 8 9 19

Distance between centres 40, 50 and 60 mm for positioning of built-in components

148 134 X110

Distance between centres 50 mm


136 116
9 10 11 12

271 X 247

Z Z 7

Distance between centres 60 mm


11 285 271 X 247

136 116

Type 444 23

Type 448 23

271 X 247

X = fixing dimension

9.44

COOPER CROUSE-HINDS GMBH

Dimensions in mm

Ex-control stations

1 2
Type 447 23 Type 449 23 Type 448 23 Type 444 23

Cooper Crouse-Hinds 2008 - all rights reserved

Mounting areas

Dimension drawing

3
31 32 33 34 35 36 26 27 28 29 30 25 26 27 28 29 30 21 22 23 24 25 19 20 21 22 23 24 16 17 18 19 20

31

32

33

34

35

36

25

26

27

28

29

30

19

20

21

22

23

24

4 5 6 7 8 9

31

32

33

34

35

36

26

27

28

29

30

13

14

15

16

17

18
25 26 27 28 29 30 21 22 23 24 25

10

11

12

19

20

21

22

23

24

16

17

18

19

20

6
13 14 15 16 17 18 11 12 13 14 15

Distance between centres 40 mm

10

11

12

19

26

27

28

29

30

21

22

23

24

25

Distance between centres 40 mm

Distance between centres 50 mm

16

17

18

19

20

21

22

23

24

11

12

13

14

15

17

18

19

20

19

13

14

15

16

5
21 22 23 24

Distance between centres 50 mm

17

18

19

20

13

14

15

16

21

22

23

24
9 10 11 12

17

18

19

20

13

14

15

16

Distance between centres 60 mm


9 10 11 12

285 271 X 247

136 116

Distance between centres 60 mm


285 271 X 247 136 116

10
X 247 817 X 793
Dimensions in mm

544 X 520

11 12

Type 449 23

Type 447 23

X = fixing dimension

COOPER CROUSE-HINDS GMBH

9.45

Ex-control stations

Type 443 34

Cooper Crouse-Hinds 2008 - all rights reserved

Technical data
Ex-Control stations Type 443 34 for individual configuration Marking to 94/9/EC EC-Type Examination Certificate Permissible ambient temperature Rated voltage Rated current Connecting terminals PE-connection terminals Insulation class Degree of protection accd. EN 60529 Cable glands/Gland plates/Enclosure drilling Dimensions (L x W x H) Weight Enclosure material Enclosure colour Mounting arrangements II 2 G EEx e II T6 / EEx e ib IIC T6 / EEx ed IIC T6 / EEx ed ib IIC T6 II 2 D IP66 T 80 C/95 C PTB 01 ATEX 1115 20 C to +40 C 55 C to +55 C (option) 690 V AC 63 A as ordered accd. to manufacturers specification 2 x 4 mm2 I IP66 (standard) IP65 (measuring instrument or double pushbutton) as ordered accd. to manufacturers specification 280 x 180 x 90 mm 2.3 kg with mounting framework cast aluminium-silicon (AISi) grey RAL 7031 max. 9 mounting areas

Ordering codes (Code 1)


1. Empty enclosure 2. Components arrangement/Terminals Mounting area 1 ... 3 443 34 X Mounting area 4 ... 6 X Mounting area 7 ... 9 X X X 3. Labels/Locking devices 4. Cable glands

Possible components (Code 1)


Component Pushbutton (2-pole or 4-pole) Double pushbutton (2-pole or 4-pole) Key switch (2-pole or 4-pole) Control switch (2-pole or 4-pole) Signal lamp Potentiometer
1)

Code DRT DDT SLS SCT SIL POT

Component Measuring instrument Measuring instrument Blanking element Control switch Control switch Terminal (4 mm ) Terminal block (4 mm )
2 2

Code AM721) AM45 BLV GHG 231) GHG 291) KLM ... A1) KLM ... B1)

Key-operated pushbutton (2-pole or 4-pole) SLT Mushroom-head pushbutton (2-pole or 4-pole) SGT

2 mounting areas are needed

9.46

COOPER CROUSE-HINDS GMBH

Ex-control stations

1 2
Type 443 34

Cooper Crouse-Hinds 2008 - all rights reserved

Mounting areas

Dimension drawing
Z

3 4
260 X 240

5 6 7

Distance between centres 40, 50 and 60 mm for positioning of built-in components

X 110 160

90

Z 20,8

6,5

Type 443 34

X = fixing dimension

8 9 10
Dimensions in mm

11 12

COOPER CROUSE-HINDS GMBH

9.47

Ex-control stations

Type 444 33

Type 448 33

Type 449 33

Type 447 33

Cooper Crouse-Hinds 2008 - all rights reserved

Technical data
Ex-Control stations Type 444, 448, 449, and 447 stainless steel for individual configuration Marking to 94/9/EC EC-Type Examination Certificate IECEx Certificate of conformity Marking accd. to IECEx Permissible ambient temperature Rated voltage Rated current Connecting terminals PE-connection terminals Insulation class Degree of protection accd. EN 60529 Cable glands/Gland plates/Enclosure drilling Enclosure material Enclosure colour Type 444 33 Connecting terminals Dimensions (L x W x H) Weight (empty) Mounting arrangements Type 448 33 Connecting terminals Dimensions (L x W x H) Weight (empty) Mounting arrangements max. 30 terminals UT 4 312.5 x 312.5 x 135 mm 7.5 kg with mounting framework distance 40 mm distance 50 mm distance 60 mm Type 449 33 Connecting terminals Dimensions (L x W x H) Weight (empty) Mounting arrangements max. 60 terminals UT 4 627 x 312.5 x 135 mm 11.5 kg with mounting framework distance 40 mm distance 50 mm distance 60 mm Type 447 33 Connecting terminals Dimensions (L x W x H) Weight (empty) Mounting arrangements max. 90 terminals UT 4 941.5 x 312.5 x 135 mm 16.5 kg with mounting framework distance 40 mm distance 50 mm distance 60 mm max. 54 mounting areas max. 45 mounting areas max. 36 mounting areas max. 36 mounting areas max. 30 mounting areas max. 24 mounting areas max. 18 mounting areas max. 15 mounting areas max. 12 mounting areas max. 20 terminals UT 4 312.5 x 175 x 135 mm 3.5 kg with mounting framework 6 mounting areas II 2 G EEx e II T6 / EEx e ib IIC T6 / EEx ed IIC T6 / EEx ed ib IIC T6 II 2 D IP66 T 80 C/95 C PTB 99 ATEX 1044 IECEx BKI 07.0023 Ex de ia/ib m [ia/ib] IIC T4 .. T6 Ex tD A21 IP66 T80 C 20 C to +40 C 55 C to +55 C (option) 690 V AC 40 A see technical data for built-in components 2 x 4 mm2 I IP66 (standard) IP65 (measuring instrument or double pushbutton) as ordered accd. to manufacturers specification Stainless steel AISI 316 L polished

9.48

COOPER CROUSE-HINDS GMBH

Ex-control stations

1 2
Type 447 33 Type 449 33 Type 448 33 Type 444 33

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering codes (Code 1)


1. Empty enclosure 2. Components arrangement/Terminals Mounting area 1 ... 6 444 33 448 33 449 33 447 33 X X X X Mounting area 7 ... 18 X X X Mounting area 19 ... 36 X X Mounting area 37 ... 64 X X X X X X X X X 3. Labels/Locking devices 4. Cable glands

3 4 5 6 7 8 9 10 11 12

Possible components (Code 1)


Component Pushbutton (2-pole or 4-pole) Double pushbutton (2-pole or 4-pole) Key switch (2-pole or 4-pole) Control switch (2-pole or 4-pole) Signal lamp Potentiometer
1) 2)

Code DRT DDT SLS SCT SIL POT

Component Measuring instrument Measuring instrument Blanking element Control switch Control switch Terminal (4 mm2) Terminal block (4 mm2)

Code AM721) AM45 BLV GHG 231) GHG 291) KLM ... A2) KLM ... B

Key-operated pushbutton (2-pole or 4-pole) SLT Mushroom-head pushbutton (2-pole or 4-pole) SGT

2 mounting areas are needed Terminal blocks and PE-terminals are attached to terminal rail under the fold-out mounting frame

COOPER CROUSE-HINDS GMBH

9.49

Ex-control stations

Type 444 33

Type 448 33

Type 449 33

Type 447 33

Cooper Crouse-Hinds 2008 - all rights reserved

Mounting area

Dimension drawing

13

14

15

16

17

18

4 7 8 9 10 11 12

2 1 2 3 4 5 6

Distance between centres 40 mm


5 6 5 6

4 11 12 13 14 15

2 6 7 8 9 19

Distance between centres 40, 50 and 60 mm


X 225 175 312.5 X 247 151 135

Distance between centres 50 mm

10

11

12

Distance between centres 60 mm


X362.5 312.5 312.5 X 247 151 135

Type 444 33

Type 448 33

X = fixing dimension

9.50

COOPER CROUSE-HINDS GMBH

Dimensions in mm

Ex-control stations

1 2
Type 447 33 Type 449 33 Type 448 33 Type 444 33

Cooper Crouse-Hinds 2008 - all rights reserved

Mounting area

Dimension drawing

3
31 32 33 34 35 36 26 27 28 29 30 25 26 27 28 29 30 21 22 23 24 25 19 20 21 22 23 24 16 17 18 19 20

31

32

33

34

35

36

25

26

27

28

29

30

19

20

21

22

23

24
31 32 33 34 35 36 26 27 28 29 30

4 5 6

13

14

15

16

17

18

25

26

27

28

29

30

21

22

23

24

25

19

20

21

22

23

24

16

17

18

19

20

10

11

12

13

14

15

16

17

18

11

12

13

14

15

10

11

12

19

Distance between centres 40 mm

26

27

28

29

30

Distance between centres 40 mm 50 mm


21 22 23 24

21

22

23

24

25

16

17

18

19

20
17 18 19 20

13

14

15

16

11

12

13

14

15

21

22

23

24

19
17 18 19 20

7 8 9 10
Dimensions in mm

5
13 14 15 16

Distance between centres 50 mm


9 10 11 12 5 6 7 8

21

22

23

24
1 2 3 4

17

18

19

20

Distance between centres 60 mm


13 14 15 16

X362.5 312.5
9 10 11 12

151 135

X 362.5 312.5

151 135

627 X 561.5

941.5 X 876

Distance between centres 60 mm

11 12

Type 449 33

Type 447 33

X = fixing dimension

COOPER CROUSE-HINDS GMBH

9.51

Built-in Components

DRT 1 x 2-pole

DRT 4 x 1-pole

DDT 2 x 1-pole

DDT 2 x 2-pole

Cooper Crouse-Hinds 2008 - all rights reserved

Technical data
Ex-Pushbutton DRT and Double pushbutton DDT Marking to 94/9/EC EC-Type Examination Certificate Application temperature Rated voltage Rated current Rated current gold contacts Switch rating Degree of protection accd. EN 60529 Type of mounting Enclosure colour Gasket material 2-pole Version Connecting terminals Dimensions (L x W x H) Weight 4-pole Version Connecting terminals Dimensions (L x W x H) Weight
1)

II 2 G EEx ed IIC / PTB 97 ATEX 1081 U 20 C to +40 C 55 C to +55 C (option) 500 V AC 16 A 0.4 A

I M2 EEx de I

400 V / 16 A AC-1 / 400 V / 4 A AC-11 IP66 DIN rail mounting grey Neoprene (Standard), Fluoric Silicone or Viton on request

2 x 2.5 mm2 59 x 31 x 45 mm 0.15 kg

4 x 2.5 mm2 59 x 73 x 45 mm 0.35 kg

The 4-pole pushbutton needs two mounting areas of a 2-pole pushbutton. The actuator will be in the middle of the two mounting areas.

9.52

COOPER CROUSE-HINDS GMBH

Built-in Components

1 2
DDT 2 x 2-pole DDT 2 x 1-pole DRT 4 x 1-pole DRT 1 x 2-pole

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering code for Component (Code 2)


Code A Component Pushbutton, for enclosure mounting Double pushbutton, for enclosure mounting Code C Contact system 2 NC Contacts
12 22 12 22

3
Code DRT DDT Code silver contact points gold contact points 13 16

4 5 6 7 8 9 10 11 12

2 NO

11 21 14 24

11 14

21 24

14

17

1 NO + 1 NC

13 23 14 22

13 14

23 22

15

18

4 NC

13 21 12 22 11 21

13 32 42 31 41 34 44 33 43 34 44 33 43 32 44 31 43 34 44 33 43

21 12 22 11 21 12 24 11 23 12 22 11 21 12 22 11 21 14 24 13 23 32 42 31 41 34 44 33 43 34 44 33 43 32 44 31 43 34 44 33 43

20

25

1 NC + 3 NO

12 24 11 23

21

26

2 NC + 2 NO

12 22 11 21 12 22 11 21

22

27

3 NC + 1 NO

23

28

4 NO

14 24 13 23

24

29

COOPER CROUSE-HINDS GMBH

9.53

Built-in Components

DRT 1 x 2-pole

DRT 4 x 1-pole

DDT 2 x 1-pole

DDT 2 x 2-pole

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering code for Component (Code 2)


Code D1, D2 Label Inscription 0, I, Start, Stop I START LANGSAM EMERG.STOP ARRET AUF Neutral whtie 0, I, Arret, Marche DOWN ON + Neutral red EIN AUTO SENKEN LINKS FAST RESET Code 001 003 005 007 009 011 014 016 018 020 025 027 030 033 036 039 051 053 055 057 Inscription 0 II STOP NOT-AUS SCHNELL _ MARCHE AB Neutral green UP ZU OFF Neutral yellow AUS HAND HEBEN RECHTS SLOW OPEN Code 002 004 006 008 010 012 015 017 019 024 026 028 031 034 037 050 052 054 056 058

9.54

COOPER CROUSE-HINDS GMBH

Built-in Components

1 2
DDT 2 x 2-pole DDT 2 x 1-pole DRT 4 x 1-pole DRT 1 x 2-pole

Cooper Crouse-Hinds 2008 - all rights reserved

Example for ordering code (Code 2)


Version Contact arrangement Pushbutton with silver contact points Version with standard label (0, I, START, STOP) 2 NC 2 NO 1 NO + 1 NC 4 NC 3 NO + 1 NC 2 NO + 2 NC 1 NC + 3 NO 4 NO 2 NC 2 NO 1 NO + 1 NC 4 NC 3 NO + 1 NC 2 NO + 2 NC 1 NC + 3 NO 4 NO 13 14 15 20 21 22 23 24 DRT DRT DRT DRT DRT DRT DRT DRT 0 0 0 0 0 0 0 0 13 14 15 20 21 22 23 24 001 001 001 001 001 001 001 001 ----------------Code Ordering Code A B C D1 D2

3 4 5 6 7 8 9 10 11 12

Double pushbutton with gold contact points Version with standard label (0, I, START, STOP) 2 NC 2 NO 1 NO + 1 NC 4 NC 3 NO + 1 NC 2 NO + 2 NC 1 NC + 3 NO 4 NO 2 NC 2 NO 1 NO + 1 NC 4 NC 3 NO + 1 NC 2 NO + 2 NC 1 NC + 3 NO 4 NO 16 17 18 20 21 22 23 24 DDT DDT DDT DRT DRT DRT DRT DRT 0 0 0 0 0 0 0 0 16 17 18 20 21 22 23 24 001 001 001 001 001 001 001 001 001 001 001 -----------

COOPER CROUSE-HINDS GMBH

9.55

Built-in Components

SLT 1 x 2-pole

SLT 1 x 4-pole

Cooper Crouse-Hinds 2008 - all rights reserved

Technical data
Ex-Key operated pushbutton SLT Marking to 94/9/EC EC-Type Examination Certificate Application temperature Rated voltage Rated current Rated current gold contacts Switch rating Degree of protection accd. EN 60529 Type of mounting Enclosure colour Gasket material Latch point 2-pole Version Connecting terminals Dimensions (L x W x H) Weight 4-pole Version Connecting terminals Dimensions (L x W x H) Weight
1)

II 2 G EEx ed IIC / M 2 EEx de PTB 97 ATEX 1081 U 20 C to +40 C 55 C to +55 C (option) 500 V AC 16 A 0.4 A 400 V / 16 A AC-1 / 400 V / 4 A AC-11 IP66 DIN rail mounting grey Neoprene (Standard), Fluoric Silicone or Viton on request CEAG 1 (others on request)

2 x 2.5 mm2 59 x 31 x 45 mm 0.15 kg

4 x 2.5 mm2 59 x 73 x 45 mm 0.35 kg

The 4-pole pushbutton needs two mounting areas of a 2-pole pushbutton. The actuator will be in the middle of the two mounting areas.

Example for ordering code (Code 2)


Version Contact arrangement Key switch with silver contact points Version with contact function: lockable/removeable/lockable/removable (code 10) 2 NC 2 NO 1 NO + 1 NC 2 NO + 2 NC 4 NC 4 NO 3 NO + 1 NC 1 NO + 3 NC 2 NC 2 NO 1 NO + 1 NC 2 NO + 2 NC 4 NC 4 NO 3 NO + 1 NC 1 NO + 3 NC 13 14 15 22 20 24 21 23 SLT SLT SLT SLT SLT SLT SLT SLT 0 0 0 0 0 0 0 0 13 14 15 22 20 24 21 23 10 10 10 10 10 10 10 10 Code Ordering Code A B C D

Key switch with gold contact points Version with contact function: lockable/removeable/lockable/removable (code 10) 2 NO + 2 NC 4 NC 4 NO 3 NO + 1 NC 1 NO + 3 NC 2 NO + 2 NC 4 NC 4 NO 3 NO + 1 NC 1 NO + 3 NC 27 25 29 26 28 SLT SLT SLT SLT SLT 0 0 0 0 0 22 20 24 21 23 10 10 10 10 10

9.56

COOPER CROUSE-HINDS GMBH

Built-in Components

1 2
SLT 1 x 4-pole SLT 1 x 2-pole

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering code for Component (Code 2)


Code A Code C Component Key operated pushbutton Contact system 2 NC Contacts
11 21

3
Code SLT Code silver contact points gold contact points 13 16

4 5

2 NO

12 22 13 23

14

17

1 NO + 1 NC

14 13

24 21

15

18

4 NO
()

14 22 14 24 13 23

34 44 33 43 34 44 33 43 34 44 33 43 32 44 31 43 32 42 31 41

20

25

6
21 26 22 27

1 NC + 3 NO
()

12 24 11 23 12 22 () 11 21

2 NC + 2 NO

7
23 28 24 29

3 NC + 1 NO
()

12 22 11 21

4 NC
()

12 22 11 21

8
Key removable removable removable not removable not removable removable Pushbutton pressed lockable lockable not lockable lockable lockable auto lockable Key removable not removable not removable removable removable removable Code 10 11 12 13 14 15

Code D

Function

Pushbutton not pressed lockable lockable lockable lockable not lockable not lockable

9 10 11 12

COOPER CROUSE-HINDS GMBH

9.57

Built-in Components

SLT 1 x 2-pole

SLT 1 x 4-pole

Cooper Crouse-Hinds 2008 - all rights reserved

Technical data
Ex-built-in Components for individual control stations Key switch SLS Marking to 94/9/EC EC-Type Examination Certificate Application temperature Rated voltage Rated current Rated current gold contacts Switch rating Switching system Degree of protection accd. EN 60529 Type of mounting Enclosure colour Latch point 2-pole Version Connecting terminals Dimensions (L x W x H) Weight 4-pole Version Connecting terminals Dimensions (L x W x H) Weight
1)

II 2 G EEx ed IIC / M 2 EEx de PTB 97 ATEX 1081 U 20 C to +40 C 55 C to +55 C (option) 500 V AC 16 A 0.4 A 400 V / 16 A AC-1 / 400 V / 4 A AC-11 engaging engaging engaging IP54 DIN rail mounting grey CEAG 1 (others on request)

2 x 2.5 mm2 59 x 31 x 45 mm 0.15 kg

4 x 2.5 mm2 59 x 73 x 45 mm 0.35 kg

The 4-pole pushbutton needs two mounting areas of a 2-pole pushbutton. The actuator will be in the middle of the two mounting areas.

9.58

COOPER CROUSE-HINDS GMBH

Built-in Components

1 2
SLT 1 x 4-pole SLT 1 x 2-pole

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering code for Component (Code 2)


Code A Code C Component Key switch Contact system 2 NO
()
45 90 135 14 24 13 23

3
Code SLS 5 Code silver contact points gold contact points

Contacts
I 0 II 13/23

4 5

04

14

2 NO
()

II

05

15

45 90 135

14

24

2 NO
()

13

23

33

43

24

34

2 NO
()

4590135 14 24 34 43 13 21 33 41

23

33

2 NO
()

4590135 14 22 13/23 4590135

34 42 33/43

6
25 35 Code 01

14 24

34 44

Code D

Contact lable

Inscription I 0 II 0 0 Ort Auto Fern Hand

7 8

02 03

Other labels on request

Example for ordering code (Code 2)


Contact system Key switch with silver contact points and label I 0 II 04 05 SLS 5 SLS 5 04 05 01 01 Ordering Code A C D

9 10 11 12

Switch can be locked in all positions and key can be removed in all positions

COOPER CROUSE-HINDS GMBH

9.59

Built-in Components

SGTE 1 x 2-pole

SGTE 1 x 4-pole

SGT 1 x 2-pole

SGT 1 x 4-pole

Cooper Crouse-Hinds 2008 - all rights reserved

Technical data
Ex-Mushroom Head Pushbutton (Emergency Stop SGTE and Normal Version SGT) Marking to 94/9/EC EC-Type Examination Certificate Application temperature Rated voltage Rated current Rated current gold contacts Switch rating Degree of protection accd. EN 60529 Type of mounting Enclosure colour Gasket material 2-pole Version Connecting terminals Dimensions (L x W x H) Weight 4-pole Version Connecting terminals Dimensions (L x W x H) Weight
1)

II 2 G EEx ed IIC / M 2 EEx de PTB 97 ATEX 1081 U 20 C to +40 C 55 C to +55 C (option) 500 V AC 16 A 0.4 A 400 V / 16 A AC-1 / 400 V / 4 A AC-11 IP66 DIN rail mounting grey Neoprene (Standard), Fluoric Silicone or Viton on request

2 x 2.5 mm2 59 x 31 x 45 mm 0.15 kg

4 x 2.5 mm2 59 x 73 x 45 mm 0.35 kg

The 4-pole pushbutton needs two mounting areas of a 2-pole pushbutton. The actuator will be in the middle of the two mounting areas. The pushbutton Emergency Stop will be equipped with a black plate in the centre of the pushbutton actuator.

9.60

COOPER CROUSE-HINDS GMBH

Built-in Components

1 2
SGT 1 x 4-pole SGT 1 x 2-pole SGTE 1 x 4-pole SGTE 1 x 2-pole

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering code for Component (Code 2)


Code A Component Mushroom head pushbutton Mushroom head pushbutton (Emergency Stop) Code C Contact system 2 NC Contacts
11 21

3
Code SGT SGTE Code silver contact points gold contact points 13 16

4 5 6 7 8 9 10 11 12

2 NO

12 22 13 23

14

17

1 NO + 1 NC

14 13

24 21

15

18

4 NC

14 22 14 24 13 23

34 44 33 43 34 44 33 43 34 44 33 43 32 44 31 43 32 42 31 41

20

25

3 NO + 1 NC

12 24 11 23

21

26

2 NO + 2 NC

12 22 11 21

22

27

1 NO + 3 NC

12 22 11 21

23

28

4 NO

12 22 11 21

24

29

COOPER CROUSE-HINDS GMBH

9.61

Built-in Components

SGTE 1 x 2-pole

SGTE 1 x 4-pole

SGT 1 x 2-pole

SGT 1 x 4-pole

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering code for Component (Code 2)


Code D Mushroom head inscription Inscription Emergency Stop (German - Englisch)1) Emergency Stop (German - French)1) 0, I, START, STOP 0 I II STOP START LANGSAM SCHNELL _ ARRET MARCHE 0, I, Arret, Marche UP DOWN ZU ON OFF + Code E Mushroom head inscription Colour red yellow2) black2) Code F Function released not lockable not lockable not lockable
1) 2)

Code 1 4 001 002 003 004 005 006 007 009 010 012 014 015 020 024 025 026 027 028 030 031 Code 1 2 3 engaged not lockable lockable lockable unlocking n/a (pushbutton function) hand released key released Code 12) 2 3

only SGTE only SGT

9.62

COOPER CROUSE-HINDS GMBH

Built-in Components

1 2
SGT 1 x 4-pole SGT 1 x 2-pole SGTE 1 x 4-pole SGTE 1 x 2-pole

Cooper Crouse-Hinds 2008 - all rights reserved

Example for ordering code (Code 2)


Contact system Ordering Code A C D E F

3 4 5 6 7 8 9 10 11 12

EMERGENCY STOP mushroom-head pushbutton red, with silver contact points Version with inscription D/E, hand released 2 NC 2 NO 1 NO + 1 NC 2 NO + 2 NC 4 NC 4 NO 3 NO + 1 NC 1 NO + 3 NC SGTE 0 SGTE 0 SGTE 0 SGTE 0 SGTE 0 SGTE 0 SGTE 0 SGTE 0 13 14 15 22 20 24 21 23 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2

Mushroom-head pushbutton with silver contact points, without locking, mushroom head, black Version with standard label (0, I, START, STOP) 2 NC 2 NO 1 NO + 1 NC 2 NO + 2 NC 4 NC 4 NO 3 NO + 1 NC 1 NO + 3 NC SGT 0 SGT 0 SGT 0 SGT 0 SGT 0 SGT 0 SGT 0 SGT 0 13 14 15 27 25 29 26 28 01 01 01 01 01 01 01 01 3 3 3 3 3 3 3 3 1 1 1 1 1 1 1 1

COOPER CROUSE-HINDS GMBH

9.63

Built-in Components

SCT 1 x 2-pole

SCT 1 x 4-pole

Cooper Crouse-Hinds 2008 - all rights reserved

Technical data
Ex-Mini-control switch SCT Marking to 94/9/EC EC-Type Examination Certificate Application temperature Rated voltage Rated current Rated current gold contacts Switch rating Degree of protection accd. EN 60529 Type of mounting Enclosure colour 2-pole Version Connecting terminals Dimensions in mm (L x W x H) Weight 4-pole Version Connecting terminals Dimensions (L x W x H) Weight
1)

II 2 G EEx ed IIC / M 2 EEx de PTB 97 ATEX 1081 U 20 C to +40 C 55 C to +55 C (option) 500 V AC 16 A 0.4 A 400 V / 16 A AC-1 / 400 V / 4 A AC-11 IP66 DIN rail mounting grey

2 x 2.5 mm2 59 x 31 x 45 0.15 kg

4 x 2.5 mm2 59 x 73 x 45 mm 0.35 kg

The 4-pole pushbutton needs two mounting areas of a 2-pole pushbutton. The actuator will be in the middle of the two mounting areas.

9.64

COOPER CROUSE-HINDS GMBH

Built-in Components

1 2
SCT 1 x 4-pole SCT 1 x 2-pole

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering code for Component (Code 2) Code A - C - D - E


Code A Code C Component Mini-control switch Switching mechanism Version spring engaging spring
45O 45O

3
Code SCT Code 4 5

4 5 6 7 8 9 10 11 12

engaging engaging engaging


45O 45O

engaging engaging
90O

6 7
45O 45O

spring engaging engaging engaging engaging spring


45O 45O

COOPER CROUSE-HINDS GMBH

9.65

Built-in Components

SCT 1 x 2-pole

SCT 1 x 4-pole

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering code for Component (Code 2) Code A - C - D - E


Code D Contact system Contacts
21/13 45 135

Code silver contact points gold contact points 01 11

45 135

13 21 14 22

22 14 13 21

13 21 45 135 1422 13 23 45 135 1424 45 90 135 45 90 135 13 23

02

12

45 135

14 22 13 23

03

13

45 135

14 24 13/23

04

14

14 24 13 23

45 90 135

14 24 13 23

05

15

45 90 135 14 24 14 24 13 21 13 21 45 90 135 45 90 135 14 22 14 22 12 22 12223444 45 135 45 135 11 21 11213343


14243444 45 135 13233343 14243444 45 135 13233343 14243444 45 135 13233343 13233343 90 45 135 14 243444 13 213341 45 90 135 14223442 13 233343 45 90 135 14243444 45 135 11 21 12 24 45 135 13 23 12 22 14 24

07

17

34 44

22

32

33 43 34 44

23

33

33 43 32 42

21

31

31 41 34 44

26

36

45 135

11 23 13 23

33 43 33 43

25

35

4590 135

14 24 34 43 13 21 33 41 27

37

4590 135

14 22 13/23

34 42 33/43

24

34

4590 135

14 24

34 44

9.66

COOPER CROUSE-HINDS GMBH

Built-in Components

1 2
SCT 1 x 4-pole SCT 1 x 2-pole

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering code for Component (Code 2) Code A - C - D - E


Code E Contact lable Inscription 0 I STOP HAND SENKEN REMOTE I AUS AUS AUF Entriegelt OUT LOCAL Other lables on request 0 BETRIEB 0 0 0 OF REMOTE I II START AUTO HEBEN LOCAL II EIN EIN AB Verriegelt HAND AUTO Code 01 02 03 04 05 06 07 08 09 10 11 12 13 Inscription 0 AUS AUS RTLICH START OFF HAND 0 MAN START HEBEN OFF AUS I AUTO HAND AUS NORMAL 0 OFF IN II EIN AUTO FERN STOP ON AUTO START AUTO STOP SENKEN ON EIN Code 18 19 20 21 22 23 24 25 26 27 28 29 30

3 4 5 6

Example for ordering code (Code 2)


Contact system Switch mechanism Control switch with silver contact points Switch can be locked in all positions I II 0I I II I 0 II I 0 II 0I 6 6 6 4 5 7 01 03 02 04 05 07 SCT SCT SCT SCT SCT SCT 6 6 6 4 5 7 01 or 21 03 or 23 02 or 22 04 or 24 05 or 26 07 or 27 02 01 02 07 07 01 Contact Code Ordering Code A C D E

7 8 9 10 11 12

COOPER CROUSE-HINDS GMBH

9.67

Built-in Components

Potentiometer

Cooper Crouse-Hinds 2008 - all rights reserved

Technical data
Ex-Potentiometer POT Marking to 94/9/EC EC-Type Examination Certificate Application temperature Rated voltage Power consumption Resistance range Tolerance Connecting terminals Degree of protection accd. EN 60529 Dimensions (L x W x H) Weight Type of mounting Enclosure colour Angle of rotation Scale II 2 G EEx ed IIC / M 2 EEx de PTB 97 ATEX 1081 U 20 C to +40 C 55 C to +55 C (option) up to 250 V max. 1 W 100 10000 Ohm 20 % 2 x 2.5 mm2 IP66 approx. 59 x 31 x 45 mm 0.15 kg DIN rail mounting grey 270 0 - 100 %

Ordering code for Component (Code 2) Code A - C


Code A Code C Component Potentiometer Resistance 000100 Ohm 220 Ohm 470 Ohm Code POT Code 01 02 03 04 07 05 06

0 - 1000 Ohm 0 - 2200 Ohm 0 - 4700 Ohm 0 - 10000 Ohm

Example for ordering code (Code 2)


Version Potentiometer 1 W 25 % tolerance 0 - 100 Ohm 0 - 470 Ohm 0 - 4700 Ohm POT 01 POT 03 POT 05 Code

9.68

COOPER CROUSE-HINDS GMBH

Built-in Components

1 2
Signal lamp

Cooper Crouse-Hinds 2008 - all rights reserved

Technical data
Ex-Signal lamp SIL Marking to 94/9/EC EC-Type Examination Certificate Application temperature Rated voltage (EEx ed IIC) (EEx d ia IIC) (EEx ed IIC) Rated current (20 V to 250 V) (10 V to 28 V EEx d ia IIC) 12 V to 30 V Connecting terminals Degree of protection accd. EN 60529 Dimensions (L x W x H) Weight Type of mounting Enclosure colour II 2 G EEx ed IIC / PTB 98 ATEX 1040 U 20 C to +40 C 55 C to +55 C (option) 20 V to 250 V AC/DC 10 V to 28 V DC 12 V to 30 V AC/DC approx. 4 - 15 mA max. 25 mA max. 24 mA 2 x 2.5 mm IP66 approx. 59 x 31 x 45 mm 0.15 kg DIN rail mounting grey
2

3
II 2 G EEx d ia IIC

4 5 6
Code SIL Code 1 2 3 4 5 Code 10 34 11

Ordering code for Component (Code 2) Code A - C - D


Code A Code C Component Signal lamp Colour of lens white yellow red blue green Code D Voltage 20 V - 250 V AC/DC 18 V - 30 V DC (Ex-i*) 12 V - 24 V AC/DC *Supply by valve-driver components, e.gl., with data: Uo = 20 V - 18 V DC with Ri = 200 - 500 or Uo = 10 V - 18 V DC with Ri = 100 - 200 No effective Ci and Li values.

7 8 9 10

Example for ordering code (Code 2)


Version Signal lamp SIL (examples) Universal voltage 20 V - 250 V AC/DC white For intrinsically safe circuits 18 V up to 30 V DC1) blue Low voltage 12 V up to 24 V AC/DC red SIL SIL SIL 1 4 3 10 34 11 Ordering Code A C D

11 12

COOPER CROUSE-HINDS GMBH

9.69

Built-in Components

AM 45

AM 75

Cooper Crouse-Hinds 2008 - all rights reserved

Technical data
Ex-Measuring instrument AM 45/AM 75 moving iron Marking to 94/9/EC EC-Type Examination Certificate Application temperature Rated voltage Power consumption Overload range II 2 G EEx e IIC / I M 2 EEx e I PTB 99 ATEX 2032 U 20 C to +40 C 55 C to +58 C (option) up to 420 V (AM 45) up to 750 V (AM 72) max. 0.31 A 10 fold - 25 sec. 25 fold - 4 sec. 50 fold - 1 sec. indicated 1 : 1.5 Measuring range Inductance Li Capacitance Ci Winding specification of moving coil Internal resistance Open circuit voltage max. Ui Short circuit current max. li Accuracy Circuit Connecting terminals Degree of protection accd. EN 60529 Display size Weight Type of mounting Enclosure material Class 2.5 moving iron 2 x 1.5 - 4 mm2 IP 65 50 x 45 mm (AM 45) 72 x 72 mm (AM 72) 0.35 kg DIN rail mounting grey max. 0 - 25 A direct / n / 1A 0/4 - 24 mA < 0.1 mH y 0.1 nF 26.5 windings 2.5 30 % 30 V 150 mA Class 1.5 moving coil 10 fold - 5 sec. moving coil II 2 G EEx ib IIC / I M 2 EEx ib I

9.70

COOPER CROUSE-HINDS GMBH

Built-in Components

1 2
AM 72 AM 45

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering code for Component (Code 2) Code A - C - D


Code A Component Measuring instrument AM 45 Measuring instrument AM 72 Code C Movement Direct connection Ct connection 1 /A Port 0 - 20/24 mA (scale 0-100% / 120%) 1) Port 4 - 20/24 mA (scale 0-100% / 120%) 1) Moving-coil connection 0 - 20/24 mA (scale 0-100% / 120%) 1) 3) Moving-coil connection 4 - 20/24 mA (scale 0-100% / 120%) 1) 3) Code D Measuring range 0-1 0 - 2.5 / 3.75 A 2) 0-5 / 7.5 A 2) 0 - 10 / 15 A 2) 0 - 15 / 22.5 A 0 - 20 / 30 A 2) 0 - 30 / 45 A 0 - 40 / 60 A 0 - 50 / 75 A 0 - 60 / 90 A
1) 2) 3)

3
Code AM 45 AM 72 Code 1 2 5 6 7 8

4 5 6 7 8

Code 02 03 04 05 06 08 09 10 11 12

Measuring range 0 - 75 / 112.5 A 0 - 100 / 150 A 0 - 150 / 225 A 0 - 200 / 300 A 0 - 250 / 375 A 0 - 300 / 450 A 0 - 400 / 600 A 0 - 500 / 750 A 0 - 600 / 900 A 0 100% / 150%

Code 13 14 15 16 17 18 19 20 21 33

Movements 0 - 20 mA / 4 - 20 mA and with moving-coil connection are only available with scale 0 - 100 %/120 % Version for direct connection (standard: CT connection n/1A) possible Moving coil only for Ex-i of Ex-d flameproof applications

Other interchangeable scales available on request

Example for ordering code (Code 2)


Movement Moving iron measuring instrument AM 45 Version with direct connection Direct Direct 0 - 20 / 24 mA 4 - 20 / 24 mA Moving iron measuring instrument AM 72 Version with CT connection n/1A Converter n / 1A 0 - 100% / 150% AM72 2 33 0 - 1 / 1.5 A 0 - 10 / 15 A 0-100% / 120% 0-100% / 120% AM45 AM45 AM45 AM45 1 1 5 6 02 05 33 33 Measuring range Ordering Code A C D

9 10 11 12

Moving-coil measuring instrument AM 45 (Ex-i application only) Version with dircet connection 0 - 20 / 24 mA 4 - 20 / 24 mA 0-100% / 120% 0-100% / 120% AM45 AM45 7 8 33 33

COOPER CROUSE-HINDS GMBH

9.71

Built-in Components

Ex 23

Ex 29

Cooper Crouse-Hinds 2008 - all rights reserved

Technical data
Ex-built-in Components for individual control stations Control switch Ex 23 and Ex 29 Ex 23 Marking to 94/9/EC EC-Type Examination Certificate Application temperature Rated voltage Rated current Rated current gold contacts Switch rating Connecting terminals Weight 1 tier: 2 tiers: 3 tiers: Type of mounting Enclosure colour
1)

Ex 29 PTB 98 ATEX 1118 U 20 C to +40 C 55 C to +55 C (option) up to 500 V 16 A1) 0.4 A 400 V/4 A 230 V/0.5 A 2 x 0.5 - 2.5 mm2 or 1 x 1.0 - 6.0 mm2 approx. 0.25 kg approx. 0.40 kg approx. 0.55 kg

II 2 G EEx ed IIC / I M 2 EEx e I PTB 98 ATEX 1116 U 20 C to +40 C 55 C to +45 C (option) 10 A AC 15: 230 V/6 A 2 x 0.5 - 2.5 mm2 approx. 0.2 kg approx. 0.35 kg DIN rail mounting grey black

DC 13: 24 V/2 A

12 A cable section must be 2.5 mm2

9.72

COOPER CROUSE-HINDS GMBH

Built-in Components

1 2
Ex 29 Ex 23

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering code for Component (Code 2) Code A - C - D - E - F


Code A Component Ex 23 Ex 29 Code C Switch mechanism spring - engaging - spring engaging - engaging - engaging engaging - engaging spring - engaging - engaging engaging - engaging - spring Code D Contact
45 135 1 3 2 4 1 3 2 4 1 3 2 4 1 3
45O 45O

3
Code Ex 23 Ex 29 Code 4 5 6 7 8

4 5 6 7

45O

45O

90O

45O

45O

45O

45O

Silver contact points


I II 2 1 1/3

Code
45 90 135 45 90 135 45 90 135 45 90 135 1 3 5

Silver contact points


0 I 1 3 5

060
3

034 037 049

45 135 I II

2 4 6 1 3 5

45 90 135 0 I

2 1

6 3 5

45 135

062 065 061


3

45 135 0 I

2 1

4 3

2 4 6 1 3 5

45 90 135 0 I

2 1

4 3 5

45 135

45 135 I 0 II

4 1/3 2 4

2 4 6 1 3 5

45 90 135 I II III

2 1

4 3

6 5

45 90 135 45 90 135 45 90 135

023 019

2 4 1 3

45 90 135 I 0 II 1

2 4 6 1 3 5 2 4 6 1 3 5 7 2 4 68 1 3 5 7

45 90 135 0 I 1

2 3

4 5

063 067 011

2 4 1 3

45 90 135 0 I

4 1 3

45 135

45 135 I II

4 1/3

6 5/7

2 4 1 2

45 90 135 0 I 1

45 135

033
5/7

4
45 90 135

45 135 I 0 II

2 4 6 8 1/3

45 135

024

45 135

2 4 68

45 90 135

2 4 6 8

Versions with gold contact points are available on request. Versions with compulsory NO are possible. Code E Contact lable Inscription 0 I STOP HAND SENKEN REMOTE I AUS AUS AUF Entriegelt OUT LOCAL STOP HAND AUF For further labels, please see page XXX Code F Locking facility None Centre Left Right Code 0 1 2 3 0 BETRIEB 0 0 0 OF REMOTE 0 0 AUS I II START AUTO HEBEN LOCAL II EIN EIN AB Verriegelt HAND AUTO START AUTO ZU Code 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 Inscription 0 AUS AUS RTLICH START OFF HAND 0 MAN START HEBEN OFF AUS HAND ON I II I AUTO HAND AUS NORMAL 0 OFF IN II EIN AUTO FERN STOP ON AUTO START AUTO STOP SENKEN ON EIN AUTO OFF III Code 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

8 9 10 11 12
9.73

COOPER CROUSE-HINDS GMBH

Built-in Components

Ex 23

Ex 29

Cooper Crouse-Hinds 2008 - all rights reserved

Example for ordering code (Code 2)


Version A Ex 23 Ex 23 Ex 29 Ex 29 Movement B
90O

Contact C 6 5 6 6
45 135 1 3 2 4 1 3 5

Label D
I II 2 I 1/3

Locking facility E 02 none 0 Centre 1 none 0 Left 2

Ordering code A B C D E Ex 23 6 060 02 0 Ex 23 5 034 07 1 Ex 29 6 060 02 0 Ex 29 6 065 01 2

060 I - II
1 3 5

45 135 0

45O

45O

45 90 135

034 I - 0 - II07 060 I - II 02 01

2 4 6 1 3 2 4 1 3 2 4

45 90 135 I II 2 1 1/3

90O

45 135

45 135 I II

4 3

90O

45 135

065 0 - I

45 135

9.74

COOPER CROUSE-HINDS GMBH

Built-in Components

1 2
UT4 PE UT4 MKX 4

Cooper Crouse-Hinds 2008 - all rights reserved

Technical data
Ex-built-in Components for individual control stations Te r m i n a l s MXK 4-Ex Marking to 94/9/EC EC-Type Examination Certificate Application temperature Rated voltage Rated current Connecting terminals II 2 G EEx e II PTB 99 ATEX 3132U 50 C to +55 C up to 420 V max. 27 A 4 mm2 4 mm Dimensions (L x B x H) Weight Type of mounting Enclosure colour NS 35 DIN rail mounted grey
2

3
UT 4 / UT 4 PE II 2 G EEx e II / 2 D EEx e II KEMA 04 ATEX 2048 U 50 C to +55 C up to 690 V max. 30 A 0.14 mm2 - 4 mm2 multi-wire 0.14 mm2 - 6 mm2 single-wire 0.14 mm2 - 4 mm2 multi-wire 0.14 mm - 6 mm single-wire 6.2 mm width 47.7 mm x 6.2 mm 0.01 kg NS 35 DIN rail mounted grey
2 2

4 5 6 7 8 9 10 11 12

COOPER CROUSE-HINDS GMBH

9.75

Built-in Components

MKX 4

UT4

UT4 PE

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering code for Component (Code 2) Code A - C - D - E - F


Code A Code C Component KLM Version Ex-e Ex-i Code D Terminal type Terminal block MXK4-Ex max. 6 terminals Terminal insert max. 3 terminals Terminal UT 4 / UT 4 PE Code E Number of terminals 1 2 3 ect. Other variants, e.g. modules with resistors or fine-wire fuses, available on request. Code KLM Code 1 1 Code B E A Code 001 002 003 ect.

Example for ordering code (Code 2)


Version Terminal block MXK 4-EX 6 x Ex-e terminals MXK 4 + 1 PE-terminal Ex-e Connection terminals Terminal UK 4 12 x Ex-e terminal UT 4 + 2 PE-terminal Ex-e terminal 12 KLM 1 A 012 02 6 KLM 1 B 006 01 Number Ordering code A C D E F

9.76

COOPER CROUSE-HINDS GMBH

Built-in Components

1 2
ZUB 17 ZUB 14 ZUB 23 ZUB 20

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering code for labels and locking facilities (Code 3) Code A - B - C


Code A Label 52.0 x 13 mm 37.0 x 17 mm with holder Code B Inscription Text to be determinated Code ZUB 19 ZUB 20 Code 1 ... 4

3 4 5 6 7 8 9 10 11 12

Code C

Mounting area

Code 1 ... 4

Code A

Locking facility with flap (blank) with flap (red) with flap without 0 activation with flap with 0 activation with flap (blank) with flap (red) with bolt and chain Fire alarm (red) with hammer Fire alarm (red) with hammer with flap, not activated with flap, activated with flap, not activated with flap, activated

for operating element Pushbutton Pushbutton Double pushbutton Double pushbutton Mushroom-head pushbutton Mushroom-head pushbutton Mushroom-head pushbutton Mushroom-head pushbutton* activates alarm when broken* Pushbutton Pushbutton Mushroom-head pushbutton Mushroom-head pushbutton

Material Stainless steel Stainless steel Stainless steel Stainless steel Stainless steel Stainless steel Stainless steel Stainless steel Stainless steel Plastic Plastic Plastic Plastic

Code ZUB 12 ZUB 13 ZUB 16 ZUB 17 ZUB 02 ZUB 01 ZUB 14 ZUB 15 ZUB 05 ZUB 23 ZUB 24 ZUB 22 ZUB 21

COOPER CROUSE-HINDS GMBH

9.77

Built-in Components

Metal flange FLM

Cable gland GK

Trumpet-shaped gland TR

Thread plug SV

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering code for Cable glands and flanges (Code 4) Code A - B - C - D - E


Code A Version Entry type Component Entry direct in enclosure Entry via plastic flange Entry via metal flange Code B Version Entry side Position Code C Version Entry element Component Entry side on bottom (left or right) Entry side on top (left or right) Component Only entry Threaded entry Threaded plug Cable plastic gland Cabel metal* gland Cable entry with plastic plug Trumpet-shaped plastic gland Code D Version Size Component M12, M16, M20, M25, M32, M40, M50, M63 21, 26 Code E Version Number Component Number of entries Code GEH FLK FLM Code 1, 2 3, 4 Code OE BO SV GK GM* GV TR Code M.. d.. Code ..

*For metal glands, the type of cable/entry must be stated in plain language in the order. Other versions on request.

Example for ordering code


Version 2 cable entries M25 moulded plastic Version without plug direct from below into the enclosure X GEH 3 GK M25 02 Number Ordering Code A B C D E

9.78

COOPER CROUSE-HINDS GMBH

Cooper Crouse-Hinds 2008 - all rights reserved

COOPER CROUSE-HINDS GMBH

9.79

12

11

10

E X - C O N T R O L
For panel mounting

A N D

S I G N A L

U N I T S

CEAG control and indicating elements can be integrated in panels with a wall thick ness of up to 5 mm. The CEAG components for panel mounting, such as signal lamps, pushbuttons and switches, can be instantly plugged into the

Cooper Crouse-Hinds 2008 - all rights reserved


9.80

control and indicating elements on the panel via bayonet-ring fitting. The single-wire instal lation is clear and simple. All panel-mounted apparatus can be retrofitted for cable con nection with a slip-on strain relief and protective cover and is then completely certified. Planning and procurement of panelmounted apparatus with different cable lengths is a thing of the past. The completely certified measuring instruments for direct and indirect measurement are available for different amperage ranges. The instruments are equipped with a transformer for easy adaptation to other ranges on the interchangeable scales.

Bayonet-ring catch for quick one-hand mounting Complete certification of built-in apparatus Connection terminals for variable, low-cost wiring Standard actuator-element size of 30.5 mm

Ex-Control and signal units

1 2
Double-Pushbutton Pushbutton

Cooper Crouse-Hinds 2008 - all rights reserved

Technical data
Ex-Control and signal units for panel mounting Pushbutton Type 418 811 and Double pushbutton Type 418 814 Marking to 94/9/EC EC-Type Examination Certificate Permissible ambient temperature Rated voltage Rated current Rated current gold contacts Switch rating Connecting terminals Degree of protection accd. EN 60529 Dimensions (L x W x H) Weight Type of mounting Enclosure colour Gasket material
1)

3
II 2 G EEx ed IIC T6 / I M 2 EEx e I II 2 G Ex ed IIC T6 / I M 2 Ex e l PTB 97 ATEX 1081 U PTB 99 ATEX 10341) 20 C to +40 C 55 C to +55 C (option) 500 V AC 16 A 0.4 A AC 15 DC 13 250 V/6 A 24 V/6 A 2 x 2.5 mm2 IP661) approx. 59 x 31 x 45 mm 0.20 kg 30.5 mm fixing hole grey Neoprene (Standard), Fluoric silicone or viton on request 500 V/4 A 60 V/0.8 A 110 V/0.5 A

4 5 6 7 8 9 10 11 12

If protective covers are used

COOPER CROUSE-HINDS GMBH

9.81

Ex-Control and signal units

Pushbutton

Double-Pushbutton

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering code for Component (Code 2) Code A - B - C1 - (C2)


A GHG 418 81_ Code A B _ R C2 __ C1 __ Code GHG 418 811 GHG 418 814 Contacts
11 21

Component Pushbutton Double pushbutton

Code B

Contact system 2 NC

Code silver contact points 3

gold contact points 6

2 NO

12 22 13 23

1 NO + 1 NC

14 13

24 21

14

22

Code C1, C2

Label

Inscription 0, I, Start, Stop I START LANGSAM EMERG.STOP MARCHE AB Neutral green UP ZU OFF Neutral yellow AUS AUTO HAND HEBEN RECHTS SLOW OPEN

Code 01 03 05 07 09 11 13 15 17 19 24 26 28 31 34 37 39 50 52 54 56 58

Inscription 0 II STOP NOT-AUS SCHNELL ARRET AUF Neutral whtie 0, I, Arret, Marche DOWN ON + Neutral red EIN Neutral black Neutral blue SENKEN LINKS FAST RESET

Code 02 04 06 08 10 12 14 16 18 20 25 27 30 33 36 38 40 51 53 55 57

9.82

COOPER CROUSE-HINDS GMBH

Ex-Control and signal units

1 2
Double-Pushbutton Pushbutton

Cooper Crouse-Hinds 2008 - all rights reserved

Example for ordering code (Code 2)


Version Label Ordering code A Pushbutton without protective cover, silver contact points 2 NC 2 NO 1 NO + 1 NC (0, I, START, STOP) (0, I, START, STOP) (0, I, START, STOP) GHG 418 811 GHG 418 811 GHG 418 811 3 4 5 R0001 R0001 R0001 B C1 C2

3 4 5 6 7 8 9 10 11 12

Double-pushbutton without protective cover, with gold contact points 2 NC 2 NO 1 NO + 1 NC (0, I, START, STOP) (0, I, START, STOP) (0, I, START, STOP) GHG 418 814 GHG 418 814 GHG 418 814 6 7 8 R01 R01 R01 01 01 01

Accessories

Type Protective cover to meet IP66 Please note that we can only deliver in the ordering units (OU) stated in the tables above

OU 5

Order No. GHG 410 1939 R0002

COOPER CROUSE-HINDS GMBH

9.83

Ex-Control and signal units

Pushbutton

Double-Pushbutton

Cooper Crouse-Hinds 2008 - all rights reserved

Dimension drawing

68

57

5 14 77 38
(Double-)pushbutton without protective cover

126

38

57

10 140
(Double-)pushbutton with protective cover

3.1+0.1 65

31.5 +0.2

40
Minimum distances

30.3 +0.2

9.84

COOPER CROUSE-HINDS GMBH

Dimensions in mm

Ex-Control and signal units

1 2
Key operated pushbutton

Cooper Crouse-Hinds 2008 - all rights reserved

Technical data
Ex-Control and signal units for panel mounting Key operated pushbutton Type 418 812 Marking to 94/9/EC EC-Type Examination Certificate Permissible ambient temperature Rated voltage Rated current Rated current gold contacts Switch rating Connecting terminals Degree of protection accd. EN 60529 Dimensions (L x W x H) Weight Type of mounting Enclosure colour Gasket material Latch point
1)

3
II 2 G Ex ed IIC T6/ I M 2 Ex e I PTB 97 ATEX 1081 U PTB 99 ATEX 10341) 20 C to +40 C 55 C to +55 C (option) 500 V AC 16 A 0.4 A AC 15 DC 13 250 V/6 A 24 V/6 A 2 x 2.5 mm2 IP661) approx. 59 x 31 x 45 mm 0.15 kg 30.5 mm fixing hole grey Neoprene (Standard), Fluoric silicone or viton on request CEAG 1 (others on request) 500 V/4 A 60 V/0.8 A 110 V/0.5 A

4 5 6 7 8 9 10 11 12

If protective covers are used

COOPER CROUSE-HINDS GMBH

9.85

Ex-Control and signal units

Key operated pushbutton

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering code for Component (Code 2) Code A - B - C


A GHG 418 812 Code A Code B B _ R00 C __ Code GHG 41 812 Contacts
11 21

Component Key operated pushbutton Contact system 2 NC Code silver contact points 3

gold contact points 6

2 NO

12 22 13 23

1 NO + 1 NC

14 24 13 21

14

22

Code C

Function

Pushbutton not pressed lockable lockable lockable lockable not lockable not lockable

Key removable removable removable not removable not removable removable

pushbutton pressed lockable lockable not lockable lockable lockable auto lockable

Key removable not removable not removable removable removable removable

Code 10 11 12 13 14 15

Example for ordering code (Code 2)


Version Label pushbutton not pressed 1 NO + 1 NC 2 NC 2 NO lockable Key removable lockable Key removable lockable Key removable pushbutton pressed lockable Key removable lockable Key removable not lockable Key not removable GHG 418 812 4 R00 12 GHG 418 812 3 R00 11 Ordering code A GHG 418 812 B 5 R00 C 10

Key switch with silver contact points, without protective cover

Key switch with gold contact points, without protective cover 1 NO + 1 NC 2 NC 2 NO lockable Key removable lockable Key removable lockable Key removable lockable Key removable lockable Key removable not lockable Key not removable GHG 418 812 7 R00 12 GHG 418 812 6 R00 11 GHG 418 812 8 R00 10

Accessories

Type Protective cover to meet IP66 Please note that we can only deliver in the ordering units (OU) stated in the tables above

OU 5

Order No. GHG 410 1939 R0002

9.86

COOPER CROUSE-HINDS GMBH

Ex-Control and signal units

1 2
Key operated pushbutton

Cooper Crouse-Hinds 2008 - all rights reserved

Dimension drawing

3
57

4
38

56 5 77
Key switch without protective cover

5 6 7
57

126

Key switch with protective cover

3.1+0.1 65

10

31.5 +0.2

8 9 10
Dimensions in mm

40
Minimum distances

30.3 +0.2

11 12

COOPER CROUSE-HINDS GMBH

9.87

Ex-Control and signal units

Key-operated pushbutton

Cooper Crouse-Hinds 2008 - all rights reserved

Technical data
Ex-Control and signal units for panel mounting Key operated switch Type 418 8195 Marking to 94/9/EC EC-Type Examination Certificate Permissible ambient temperature Rated voltage Rated current Rated current gold contacts Switch rating Connecting terminals Switching system Dimensions (L x W x H) Weight Type of mounting Enclosure colour Latch point
1)

II 2 G Ex ed IIC T6/ I M 2 Ex e I PTB 97 ATEX 1081 U PTB 99 ATEX 10341) 20 C to +40 C 55 C to +55 C (option) 500 V AC 16 A 0.4 A AC 15 DC 13 250 V/6 A 24 V/6 A 2 x 2.5 mm2 engaging - engaging - engaging approx. 59 x 31 x 45 mm 0.15 kg 30.5 mm fixing hole grey CEAG 1 (others on request) 500 V/4 A 60 V/0.8 A 110 V/0.5 A

If protective covers are used

9.88

COOPER CROUSE-HINDS GMBH

Ex-Control and signal units

1 2
Key-operated pushbutton

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering code for Component (Code 2) Code A - B - C


A GHG 418 8195 Code A Code B R5 B _ C __ Code GHG 418 8195 Contacts
13/23 14 24 13 23

3 4 5 6 7

Component Key switch Contact system 2 NC


()
45 90 135

Code silver contact points


II

gold contact points 7

2 NO
()

II

45 90 135

14

24

Code C

Inscription I Fern Hand 0 0 0 II Ort Auto

Code 07 08 09

other labels on request

Example for ordering code (Code 2)


Switch mechanism 4 4 4 5 5 5
()
45 90 135 14 24

Contact system
13/23 14 24 13 23

Label

Order No. A C R5 R5 R5 R5 R5 R5 4 4 4 5 5 5 D 07 08 09 07 08 09

Key switch with silver contacts, without protective cover


I 0 II

I 0 II FERN 0 ORT HAND 0 AUTO I 0 II FERN 0 ORT HAND 0 AUTO

GHG 418 8195 GHG 418 8195 GHG 418 8195 GHG 418 8195 GHG 418 8195 GHG 418 8195

()
45 90 135 I 0 II

8 9

Switch can be locked in all positions and key can be removed in all positions Key switch with gold contacts, without protective cover 4 4 4 5 5 5 I 0 II FERN 0 ORT HAND 0 AUTO I 0 II FERN 0 ORT HAND 0 AUTO GHG 418 8195 GHG 418 8195 GHG 418 8195 GHG 418 8195 GHG 418 8195 GHG 418 8195 R5 R5 R5 R5 R5 R5 7 7 7 8 8 8 07 08 09 07 08 09

10 11 12

Accessories

Type Protective cover to meet IP66 Please note that we can only deliver in the ordering units (OU) stated in the tables above

OU 5

Order No. GHG 410 1939 R0002

COOPER CROUSE-HINDS GMBH

9.89

Ex-Control and signal units

Key-operated pushbutton

Cooper Crouse-Hinds 2008 - all rights reserved

Dimension drawing

57 62 5 77
Key switch without protective cover

38

126

Key switch with protective cover

3.1+0.1 65

31.5 +0.2

40
Minimum distances

30.3 +0.2

10

57

9.90

COOPER CROUSE-HINDS GMBH

Dimensions in mm

Ex-Control and signal units

1 2
Mushroom-h.p.-button Mushroom-h.p.-button

Cooper Crouse-Hinds 2008 - all rights reserved

Technical data
Ex-Control and signal units for panel mounting Mushroom head pushbutton (Emergency stop and normal version) Marking to 94/9/EC EC-Type Examination Certificate Permissible ambient temperature Rated voltage Rated current Rated current gold contacts Switch rating Connecting terminals Dimensions (L x W x H) Weight Type of mounting Enclosure colour Gasket material
1)

3
II 2 G EEx ed IIC T6/ I M 2 EEx e I PTB 97 ATEX 1081 U PTB 99 ATEX 10341) 20 C to +40 C 55 C to +55 C (option) 500 V AC 16 A 0.4 A 400 V/16 A AC-1 400 V/ 4 A AC-11 2 x 2.5 mm2 approx. 59 x 31 x 45 mm 0.15 kg 30.5 mm fixing hole grey Neoprene (Standard), fluoric silicone or viton on request

4 5 6 7 8 9 10 11 12

If protective covers are used

COOPER CROUSE-HINDS GMBH

9.91

Ex-Control and signal units

Mushroom-h.p.-button

Mushroom-h.p.-button

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering code for Component (Code 2) Code A - B - C - D - E


A GHG 418 815 Code A Code B B _ R C _ D _ E __ Code GHG 418 815 Contacts hand released
11 21

Component Mushroom head pushbutton Contact system 2 NO Code silver contact points 3

key released
11 21

gold contact points 6

2 NC

12 22 13 23

12 22 13 23

1 NO + 1 NC

14 24 13 21

14 13

24 21

14

22

14

22

Code C

Mushroom head insription and color NOT-AUS EMERGENCY STOP (German - English)1) NOT-AUS ARRET DURGENCE (German - French)1) Red Yellow1) Black2)

Code 1 4 1 2 3

Code D

Function

released not lockable not lockable not lockable

engaged not lockable lockable lockable Code 01 03 05 07

unlocking hand released key released Inscription 0 II STOP NOT-AUS1)

Code 21) 31) Code 02 04 06 08

n/a (pushbutton function) 12)

Code E

Label

Inscription 0, I, Start, Stop I START

1) 2)

only Emergency stop mushroom head pushbutton only Mushroom head pushbutton normal version

9.92

COOPER CROUSE-HINDS GMBH

Ex-Control and signal units

1 2
Mushroom-h.p.-button Mushroom-h.p.-button

Cooper Crouse-Hinds 2008 - all rights reserved

Example for ordering code (Code 2)


Contact system Version with inscription D/E, hand released 2 NC 2 NC 2 NO 2 NO 1 NO + 1 NC 1 NO + 1 NC red red red red red red German/English German/French German/English German/French German/English German/French GHG 418 815 GHG 418 815 GHG 418 815 GHG 418 815 GHG 418 815 GHG 418 815 3 3 4 4 5 5 R1 R4 R1 R4 R1 R4 2 2 2 2 2 2 00 00 00 00 00 00 Mushroom head colour Inscription Order No. A B C D E

3 4 5 6 7 8 9 10 11 12

EMERGENCY STOP mushroom-head pushbutton red, with silver ocntact points, without protective cover

Version with inscription D/E, key released 2 NC 2 NC 2 NO 2 NO 1 NO + 1 NC 1 NO + 1 NC red red red red red red German/English German/French German/English German/French German/English German/French GHG 418 815 GHG 418 815 GHG 418 815 GHG 418 815 GHG 418 815 GHG 418 815 3 3 4 4 5 5 R1 R4 R1 R4 R1 R4 3 3 3 3 3 3 00 00 00 00 00 00

Mushroom-head pushbutton, with silver ocntact points, without protective cover Version with inscription D/E, pushbutton function only 2 NC 2 NC 2 NO 2 NO 1 NO + 1 NC 1 NO + 1 NC black yellow black yellow black yellow 0, I, START, STOP 0, I, START, STOP 0, I, START, STOP 0, I, START, STOP 0, I, START, STOP 0, I, START, STOP GHG 418 815 GHG 418 815 GHG 418 815 GHG 418 815 GHG 418 815 GHG 418 815 3 3 4 4 5 5 R3 R2 R3 R2 R3 R2 1 1 1 1 1 1 01 01 01 01 01 01

Accessories

Type Protective cover to meet IP66 Please note that we can only deliver in the ordering units (OU) stated in the tables above

OU 5

Order No. GHG 410 1939 R0002

COOPER CROUSE-HINDS GMBH

9.93

Ex-Control and signal units

Mushroom-h.p.-button

Mushroom-h.p.-button

Cooper Crouse-Hinds 2008 - all rights reserved

Dimension drawing

57 56 5 77 38

Mushroom-head pushbutton without protective cover with key release

57 30 5 77

38

Mushroom-head pushbutton without protective cover

126

57 30
Mushroom-head pushbutton with protective cover

10

3.1+0.1 65

31.5 +0.2

40
Minimum distances

30.3 +0.2

9.94

COOPER CROUSE-HINDS GMBH

Dimensions in mm

Ex-Control and signal units

1 2
Mini-control switch

Cooper Crouse-Hinds 2008 - all rights reserved

Technical data
Ex-Control and signal units for panel mounting Mini-Control switch Type 418 8190 Marking to 94/9/EC EC-Type Examination Certificate Permissible ambient temperature Rated voltage Rated current Rated current gold contacts Switch rating Connecting terminals Dimensions (L x W x H) Weight Type of mounting Enclosure colour
1)

3
II 2 G Ex ed IIC T6/ I M 2 Ex e I PTB 97 ATEX 1081 U PTB 99 ATEX 10341) 20 C to +40 C 55 C to +55 C (option) 500 V AC 16 A 0.4 A AC 15 DC 13 250 V/6 A 24 V/6 A 2 x 2.5 mm2 approx. 59 x 31 x 45 mm 0.15 kg 30.5 mm fixing hole grey 500 V/4 A 60 V/0.8 A 110 V/0.5 A

4 5 6 7 8 9 10 11 12

If protective covers are used

COOPER CROUSE-HINDS GMBH

9.95

Ex-Control and signal units

Mini-control switch

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering code for Component (Code 2) Code A - B - C - D


A GHG 418 819 Code A Code B B _ R C _ D _ E __ Code GHG 418 819 Code
45O 45O

Component Mini-Control Switch Switch mechanism spring - engaging - engaging engaging - engaging - engaging engaging - engaging spring - engaging - engaging engaging - engaging - spring

4 5 6 7 8 Code 0 1

45O

45O

90O

45O

45O

45O

45O

Code C

Contact material silver gold

Code D

Contact system

Contacts
45 135 13 21 14 22

Code
21/13

0 1 2

45 135

22 14 13 21

13 21 45 135 1422 13 23 45 135 1424 45 90 135 13 23

45 135

14 22 13 23

45 135

14 24 13/23

3
23

14 24 13 23

45 90 135

14 24 13

45 90 135

5 7

14 24

45 90 135

14

24

13 21 45 90 135 14 22

13 21 45 90 135

14

22

Code E

Contact lable

Inscription 0 I STOP HAND SENKEN REMOTE I AUS AUS AUF STOP 0 BETRIEB 0 0 0 I II START AUTO HEBEN LOCAL II EIN EIN AB START

Code 01 02 03 04 05 06 07 08 09 10 14

Inscription HAND AUF HAND 0 AUS AUS RTLICH START OFF HAND 0 0 AUS AUS I AUTO HAND AUS NORMAL 0 OFF IN AUTO ZU AUTO II EIN AUTO FERN STOP ON AUTO START

Code 15 16 17 18 19 20 21 22 23 24 25

9.96

COOPER CROUSE-HINDS GMBH

Ex-Control and signal units

1 2
Mini-control switch

Cooper Crouse-Hinds 2008 - all rights reserved

Example for ordering code (Code 2)


Switching mechanism Code Contact system Code Label Order No. A Control switch with silver contact points, without protective cover Switch can be locked in all positions 6 6 6 5 5 8
45 135 13 21 14 22

3
B C D

21/13 45 135

4
0 2 1 I 0 I I I 0 II I II 0 0 I II II GHG 418 8190 R GHG 418 8190 R GHG 418 8190 R GHG 418 8190 R GHG 418 8190 R GHG 418 8190 R 6 6 6 5 5 8 0 2 1 3 5 7 02 01 02 07 07 01

90O

22 14 13 23

90O

13 23 45 135 1424 13 21 45 135 1422 45 90 135 13 23

45 135

14 24 13 21

90O

45 135

14 22 13/23

5 6 7 8

45O

45O

14 24 13 23

45 90 135

14 24 13 23

3 5 7

45 90 135

45O

45O

14 24

45 90 135

14

24

45O

45O

13 21 45 90 135 14 22

13 21 45 90 135

14

22

Accessories

Type Protective cover to meet IP66 Please note that we can only deliver in the ordering units (OU) stated in the tables above

OU 5

Order No. GHG 410 1939 R0002

Dimension drawing
150

57

57

57

24 5 77
Mini-control switch without protective cover

9
10 24 5

38

Mini-control switch with protective cover

57

3.1+0.1 65

10
31.5 +0.2
Dimensions in mm

40
Minimum distances

30.3 +0.2

11 12

COOPER CROUSE-HINDS GMBH

9.97

Ex-Control and signal units

Control switch GHG 249

Cooper Crouse-Hinds 2008 - all rights reserved

Technical data
Ex-Control and signal units for panel mounting Control switch GHG 249 Marking to 94/9/EC EC-Type Examination Certificate Permissible ambient temperature Rated voltage Rated current Rated current gold contacts Switch rating AC 1 AC 3 AC 11 DC 11 Connecting terminals Weight Type of mounting Enclosure colour
1)

II 2 G Ex ed IIC T6/ I M 2 Ex e I PTB 98 ATEX 1117 U1) 20 C to +40 C 55 C to +45 C (option) up to 690 V AC up to 20 A up to 0.4 A 690 V/20 A 400 V/20 A / 500 V/16 A 230 V/ 8 A / 500 V/ 6 A 24 V/ 6 A / 230 V/0.4 A 2 x 2.5 mm2 multi wire, 6 mm2 single wire 0.55 kg 30.5 mm fixing hole grey

Must be installed in a certified enclosure

9.98

COOPER CROUSE-HINDS GMBH

Ex-Control and signal units

1 2
Control switch GHG 249

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering code for Component (Code 2) Code A - B - C - D


A 249 Code A Code B B _ C ___ D 1) __ Code 249 Code
45O 45O

3 4 5 6 7 8
Code I AUTO HAND AUS NORMAL 0 OFF IN II EIN AUTO FERN STOP ON AUTO START AUTO STOP SENKEN ON EIN AUTO OFF II III 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

Component Control switch GHG 249 Switch mechanism spring - engaging - spring engaging - engaging - engaging engaging - engaging spring - engaging - engaging engaging - engaging - spring

4 5 6 7 8 Code Silver contact points


0 I 1 3 5

45O

45O

90O

45O

45O

45O

45O

Code C

Contact system

Contacts
1 3 5 2 4 6 1 3 5 7 2 4 68 1 3 5 7

45 135

019
5/7

45 135 I II

4 1/3

45 135

033
5/7

45 135 I 0 II

2 4 6 8 1/3

45 90 135

024 021 049 037


9/11

2 4 68 1 3 5

45 90 135 0 I 1

2 4 6 8 3 5

45 90 135

2 4 6 1 3 5

45 90 135 0 I

2 1

6 3 5

45 90 135

2 4 6 1 3 5

45 90 135 0 I

2 1

6 3 5

45 90 135

2 4 6

45 90 135 I II

4 1/3

6 5/7

45 135

1 3 5 7 9 11 2 4 6 8 1012 1 3 5 7 9 11

039 038

45 135 I 0 II

2 4 6 8 10 12 1/3 5/7 9/11

45 90 135

2 4 6 8 1012

45 90 135

2 4 6 8 10 12

Code D

Contact lable

Inscription 0 I STOP HAND SENKEN REMOTE I AUS AUS AUF Entriegelt OUT LOCAL STOP HAND AUF I II START AUTO HEBEN LOCAL 0 BETRIEB 0 0 0 OF REMOTE 0 0 AUS II EIN EIN AB Verriegelt HAND AUTO START AUTO ZU

Code 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16

Inscription 0 AUS AUS RTLICH START OFF HAND 0 MAN START HEBEN OFF AUS HAND ON

9 10 11 12

1)

The code will represent only a selected part of configuration.

COOPER CROUSE-HINDS GMBH

9.99

Ex-Control and signal units

Control switch GHG 249

Cooper Crouse-Hinds 2008 - all rights reserved

Example for ordering code (Code 2)


Version A GHG 249
90O

Switching mechanism B

Code

Contact C

Code

Label D

Code

Order No.

6 6
90O

45 135

1 3 5 2 4 6 1 3 5

019
3 5

0I STOP - 0 - START I - II

01 14 02

GHG 249 0004 R0058 GHG 249 0004 R0039 GHG 249 0004 R0084

45 135 0 I

2 1

GHG 249 GHG 249


90O

45 90 135 45 135

037 033

2 4 6 1 3 5 7 2 4 68

45 90 135 I II

2 1/3

4 5/7

45 135

2 4 6 8

Dimension drawing
20

50

72 85 6 54 30

71

34 26

30
Diagram

9.100

COOPER CROUSE-HINDS GMBH

Dimensions in mm

Ex-Control and signal units

1 2
Potentiometer

Cooper Crouse-Hinds 2008 - all rights reserved

Technical data
Ex-Control and signal units for panel mounting Potentiometer Type 418 8131 Marking to 94/9/EC EC-Type Examination Certificate Permissible ambient temperature Rated voltage Power consumption Resistance range Tolerance Connecting terminals Dimensions (L x W x H) Weight Type of mounting Enclosure colour Angle of rotation Scale
1)

3
II 2 G Ex ed IIC T6/ I M 2 Ex e I PTB 97 ATEX 1081 U PTB 99 ATEX 10341) 20 C to +40 C 55 C to +55 C (option) up to 250 V AC max. 1 W 100 - 10000 20 % 2 x 2.5 mm 0.15 kg 30.5 mm fixing hole grey 270 0 - 100 %
2

4 5 6 7 8 9 10 11 12

approx. 59 x 31 x 45 mm

If protective covers are used

COOPER CROUSE-HINDS GMBH

9.101

Ex-Control and signal units

Potentiometer

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering code for Component (Code 2) Code A - B


A GHG 418 8131 Code A Code B R00 B __ Code GHG 418 8131 Code 11 12 13 14 17 15 16

Component Potentiometer Resistance 000100 Ohm 220 Ohm 470 Ohm

0 - 1000 Ohm 0 - 2200 Ohm 0 - 4700 Ohm 0 - 10000 Ohm

Example for ordering code (Code 2)


Version Potentiometer 1 W 25 % tolerance, without protective cover 0 - 100 Ohm 0 - 220 Ohm 0 - 470 Ohm 0 - 1000 Ohm 0 - 2200 Ohm 0 - 4700 Ohm 0 - 10000 Ohm GHG 418 8131 GHG 418 8131 GHG 418 8131 GHG 418 8131 GHG 418 8131 GHG 418 8131 GHG 418 8131 R 0011 R 0012 R 0013 R 0014 R 0017 R 0015 R 0016 Order No. A B

Accessories

Type Protective cover to meet IP66 Please note that we can only deliver in the ordering units (OU) stated in the tables above

OU 5

Order No. GHG 410 1939 R0002

Dimension drawing
126

57 57 24 5 77
Potentiometer without protective cover
65 3.1+0.1

31.5 +0.2

40

30.3 +0.2

Potentiometer with protective cover

Minimum distances

9.102

COOPER CROUSE-HINDS GMBH

Dimensions in mm

38

10

Ex-Control and signal units

1 2
Signal lamp

Cooper Crouse-Hinds 2008 - all rights reserved

Technical data
Ex-Control and signal units for panel mounting Signal lamp Type 418 8170 Marking to 94/9/EC EC-Type Examination Certificate Permissible ambient temperature Rated voltage (Ex ed IIC) (Ex d ia IIC) (Ex ed IIC) Rated current (20 V to 250 V) (10 V to 28 V Ex d ia IIC) (12 V to 30 V) Connecting terminals Dimensions (L x W x H) Weight Type of mounting Enclosure colour
1)

3
II 2 G Ex ed IIC / II 2 G Ex d ia IIC PTB 98 ATEX 1040 U PTB 99 ATEX 10341) 20 C to +40 C 55 C to +55 C (option) 20 V to 250 V AC/DC 10 V to 28 V DC 12 V to 30 V AC/DC approx. 4 - 15 mA max. 25 mA max. 24 mA 2 x 2.5 mm2 approx. 59 x 31 x 45 mm 0.15 kg 30.5 mm fixing hole grey

4 5 6 7 8 9 10 11 12

If protective covers are used

COOPER CROUSE-HINDS GMBH

9.103

Ex-Control and signal units

Signal lamp

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering code for Component (Code 2) Code A - B


A GHG 418 8170 Code A Code B R00 B __ Code GHG 418 8170 Code 51 52 53

Component Signal lamp Resistance 20 V - 250 V AC/DC 18 V - 30 V DC (Ex-i1)) 12 V - 24 V AC/DC

Example for ordering code (Code 2)


Version Version without protective cover with lens cover yellow, red, green and white Universal voltage 20V - 250 V AC/DC For intrinsically safe circuits (18 V up to 30 V DC1) Low voltage 12 V up to 24 V AC/DC * Supply by valve-driver components, e.g., with data: Uo = 20 V 28 V DC with Ri = 200 500 or Uo = 10 V 18 V DC with Ri = 100 200 No effective Ci and Li values. GHG 418 81 70 GHG 418 81 70 GHG 418 81 70 R0051 R0052 R0053 Order No. A B

Accessories

Type Protective cover to meet IP66 Please note that we can only deliver in the ordering units (OU) stated in the tables above

OU 5

Order No. GHG 410 1939 R0002

Dimension drawing
126

57 57 21 5 77
Signal lamp without protective cover

38
Signal lamp with protective cover

10

3.1+0.1 65

40
Minimum distances

30.3 +0.2

9.104

COOPER CROUSE-HINDS GMBH

Dimensions in mm

31.5 +0.2

Ex-Control and signal units

1 2
Interchangeable scales Measuring instrument

Cooper Crouse-Hinds 2008 - all rights reserved

Technical data
Type 413 84 with measuring instrument AM 72 Moving iron Marking to 94/9/EC EC-Type Examination Certificate Permissible ambient temperature Rated voltage Power consumption Overload range II G Ex e II / I M 2 Ex e I PTB 00 ATEX 3117 20 C to +40 C 55 C to +55 C (option) up to 690 V max. 0.31 VA 10 fold - 25 sec. 25 fold - 4 sec. 50 fold - 1 sec. indicated 1 : 1.5 Measuring range Inductance Li Capacitance Ci Winding specification of moving coil Internal resistance Open circuit voltage max. Ui Short circuit current max. li Accuracy Connecting terminals Degree of protection accd. EN 60529 Cable glands/Gland plates/Enclosure drilling Dimensions (L x W x H) Display size AM 72 Weight Type of mounting Enclosure colour Class 2.5 2 x 1.5 - 4 mm2 IP66 1 x M25 ( 8 - 17 mm) 160 x 95 x 62 mm 72 x 72 mm 0.8 kg DIN rail mounting grey max. 0 - 25 A direct / n / 1A 0/4 - 24 mA < 0.1 mH < 0.1 nF 26.5 windings 2.5 30 % 30 V 150 mA Class 1.5 10-fold - 5 sec. Moving coil II G Ex ib IIC / I M 2 Ex ib I

3 4 5 6 7 8 9 10 11 12
COOPER CROUSE-HINDS GMBH

9.105

Ex-Control and signal units

Measuring instrument

Interchangeable scales

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering code for Component (Code 2) Code A - B - C


A GHG 412 828 Code A Code B B _ R0 C __ Code GHG 412 828 Code 1 2 5 6
3) 3)

Component Measuring instrumtent AM 72 Movement Direct connection Ct connection 1 /A Port 0 - 20/24 mA (scale 0-100% / 120%) 1) Port 4 - 20/24 mA (scale 0-100% / 120%) 1) Moving-coil connection 0 - 20/24 mA (scale 0-100% / 120%) 1) Moving-coil connection 4 - 20/24 mA (scale 0-100% / 120%) 1)

7 8 Measuring range/scale 0 - 75 /112.5 A 0 - 100 / 150 A 0 - 150 / 225 A 0 - 200 / 300 A 0 - 250 / 375 A 0 - 300 / 450 A 0 - 400 / 600 A 0 - 500 / 750 A 0 - 600 / 900 A 0 - 100% / 150% Code C 013 014 015 016 017 018 019 020 021 033

Code

Mesasuring range/scale 0-1 0 - 2.5 / 3.75 A 2) 0 - 5 / 7.5 A 2) 0 - 10 / 15 A 2) 0 - 15 / 22.5 A 0 - 20 / 30 A 2) 0 - 30 / 45 A 0 - 40 / 60 A 0 - 50 / 75 A 0 - 60 / 90 A

Code C 002 003 004 005 006 008 009 010 011 012

1) 2) 3)

Movements 0 - 20 mA/ 4 - 20 mA and with moving-coil connection are only available with scale 0 - 100%/ 120%. Version for direct connection (standard: CT connection n/1A) possible. Moving coil only for Ex-i of Ex-d flameproof applications

Other interchangeable scales available on request.

9.106

COOPER CROUSE-HINDS GMBH

Ex-Control and signal units

1 2
Interchangeable scales Measuring instrument

Cooper Crouse-Hinds 2008 - all rights reserved

Example for ordering code (Code 2)


Measuring range Measuring instrument AM 72, direct measurement Version with 1 x cable entry M25 0 1 /1.5 A 0 - 2.5 / 3.75 A 0 - 5 / 7.5 A 0 - 10 / 15 A 0 - 16 / 24 A 0 - 20 / 24 mA 0-100% / 120% (Ri = 320 ) 4 - 20 / 24 mA 0-100% / 120% (Ri = 320 ) Measuring instrument AM 72, Ct connection n/1A Version with 1 x cable entry M25 0 1 / 1.5 A 0 - 2.5 / 3.75 A 0 - 5 / 7.5 A 0 - 10 / 15 A 0 - 15 / 22.5 A 0 - 20 / 30 A 0 - 30 / 45 A 0 - 40 / 60 A 0 - 50 / 75 A 0 - 60 / 90 A 0 - 75 / 112.5 A 0 - 100 / 150 A 0 - 150 / 225 A 0 - 200 / 300 A 0 - 250 / 375 A 0 - 300 / 450 A 0 - 400 / 600 A 0 - 500 / 750 A 0 - 600 / 900 A 0 - 100% / 150% GHG 412 8282 R0002 GHG 412 8282 R0003 GHG 412 8282 R0004 GHG 412 8282 R0005 GHG 412 8282 R0006 GHG 412 8282 R0008 GHG 412 8282 R0009 GHG 412 8282 R0010 GHG 412 8282 R0011 GHG 412 8282 R0012 GHG 412 8282 R0013 GHG 412 8282 R0014 GHG 412 8282 R0015 GHG 412 8282 R0016 GHG 412 8282 R0017 GHG 412 8282 R0018 GHG 412 8282 R0019 GHG 412 8282 R0020 GHG 412 8282 R0021 GHG 412 8282 R0031 GHG 412 8281 R0002 GHG 412 8281 R0003 GHG 412 8281 R0004 GHG 412 8281 R0005 GHG 412 8281 R0007 GHG 412 8285 R0033 GHG 412 8286 R0035 Ordering code

3 4 5 6 7 8 9 10
73
Dimensions in mm

Dimension drawing
95

26

160 173

73

147

11 12

22 62

COOPER CROUSE-HINDS GMBH

9.107

1 2
Cooper Crouse-Hinds 2008 - all rights reserved

Accessories

3 4 5 6 7 8 9 10 11 12

Interchangeable AM72

Ordering details
Interchangeable scales for measuring instrument , CT connection n/1A for AM 45/AM 72 Scale 0 - 1 / 1.5 A 0 - 2.5 / 3.75 A 0 - 5 / 7.5 A 0 - 10 / 15 A 0 - 15 / 22.5 A 0 - 20 / 30 A 0 - 25 / 37.5 A 0 - 30 / 45 A 0 - 40 / 60 A 0 - 50 / 75 A 0 - 60 / 90 A 0 - 75 /112.5 A 0 - 100 / 150 A 0 - 150 / 225 A 0 - 200 / 300 A 0 - 250 / 375 A 0 - 300 / 450 A 0 - 400 / 600 A 0 - 500 / 750 A 0 - 600 / 900 A 0 100% / 150% Special scales available on request. Package unit 10 pieces 10 pieces 10 pieces 10 pieces 10 pieces 10 pieces 10 pieces 10 pieces 10 pieces 10 pieces 10 pieces 10 pieces 10 pieces 10 pieces 10 pieces 10 pieces 10 pieces 10 pieces 10 pieces 10 pieces 10 pieces Order No. AM45 GHG 410 1926 R0001 GHG 410 1926 R0002 GHG 410 1926 R0003 GHG 410 1926 R0004 GHG 410 1926 R0005 GHG 410 1926 R0006 GHG 410 1926 R0021 GHG 410 1926 R0007 GHG 410 1926 R0008 GHG 410 1926 R0009 GHG 410 1926 R0010 GHG 410 1926 R0011 GHG 410 1926 R0012 GHG 410 1926 R0013 GHG 410 1926 R0014 GHG 410 1926 R0015 GHG 410 1926 R0016 GHG 410 1926 R0017 GHG 410 1926 R0018 GHG 410 1926 R0019 GHG 410 1926 R0020 Order No. AM72 GHG 410 1928 R0001 GHG 410 1928 R0002 GHG 410 1928 R0003 GHG 410 1928 R0004 GHG 410 1928 R0005 GHG 410 1928 R0006 GHG 410 1928 R0021 GHG 410 1928 R0007 GHG 410 1928 R0008 GHG 410 1928 R0009 GHG 410 1928 R0010 GHG 410 1928 R0011 GHG 410 1928 R0012 GHG 410 1928 R0013 GHG 410 1928 R0014 GHG 410 1928 R0015 GHG 410 1928 R0016 GHG 410 1928 R0017 GHG 410 1928 R0018 GHG 410 1928 R0019 GHG 410 1928 R0051

9.108

COOPER CROUSE-HINDS GMBH

Accessories

1 2
Labels

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering code
Labels for pushbuttons Inscription 0, I, Start, Stop I D START LANGSAM EMERG.STOP ARRET AUF Neutral whtie 0, I, Arret, Marche DOWN ON + Neutral red EIN AUTO SENKEN LINKS FAST RESET HALT VOR FIRE ALARM REVERSE HIGH LP LQ SPERREN ENTRIEGELN Further labels are available on request. Code 001 003 005 007 009 011 014 016 018 020 025 027 030 033 036 039 051 053 055 057 069 073 094 096 101 151 157 163 165 Inscription 0 II STOP NOT-AUS SCHNELL _ MARCHE AB Neutral green UP ZU OFF Neutral yellow AUS HAND HEBEN RECHTS SLOW OPEN III ZURCK FORWARD RUN LOW HQ STR. QUITT ENTSPERREN VERRIEGELN Code 002 004 006 008 010 012 015 017 019 024 026 028 031 034 037 050 052 054 056 058 070 074 095 100 102 152 162 164 166

3 4 5 6 7 8 9 10 11 12
COOPER CROUSE-HINDS GMBH

9.109

Accessories

Flap (with O-activation)

Plastic flap

Combination piec

Contacts label

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering code
Locking facilities Version with flap (blank) with flap (red) with bolt and chain (blank) Fire alarm (red)* Fire alarm (red) with plastic flap with plastic flap with plastic flap with plastic flap with plastic flap with flap (blank) with flap (red) with flap without 0-activation (blank) with flap with 0-activation (blank) with bracket (1 Set) Pushbutton Pushbutton Double pushbutton Double pushbutton Switch GHG 23/28 Operating element Mushroom-head pushbutton Mushroom-head pushbutton Mushroom-head pushbutton Mushroom-head pushbutton Mushroom-head pushbutton Mushroom-head pusbutton activated Mushroom-head pushbutton non-activated Pushbutton activated Pushbutton non-activated Emergency Stop 1 11 1 11 5 OU 1 1 1 1 11 Order No. GHG 410 1901 R0124 GHG 410 1901 R0125 GHG 410 1901 R0126 GHG 410 1901 R0128 GHG 410 1901 R0141 GHG 410 1994 R0001 GHG 410 1994 R0002 GHG 410 1994 R0003 GHG 410 1994 R0004 GHG 410 1994 R0005 GHG 410 1901 R0132 GHG 410 1901 R0133 GHG 410 1901 R0134 GHG 410 1901 R0135 GHG 440 1917 R0001

* released when window is broken select appropriate activation element. Please note that we can only deliver in the ordering units (OU) stated in the tables above. Labels and fools for control switches Unit Label with label holder Combination piece for Control station Typ 411 Mounting and dismantling tool for lock nuts on operating elements Blanking element for control units Protective cap Spanner incl. seal and lock nut for panel-mounted operating elements 1 piece 10 pieces 5 pieces GHG 410 1914 R0001 GHG 410 1920 R0001 GHG 410 1939 R0002 incl. twist protection and seal 1 piece GHG 410 1921 R0001 Version Blank (can be engraved) OU 10 pieces Order No. GHG 410 1953 R0001

Please note that we can only deliver in the ordering units (OU) stated in the tables above.

9.110

COOPER CROUSE-HINDS GMBH

Cooper Crouse-Hinds 2008 - all rights reserved

COOPER CROUSE-HINDS GMBH

9.111

12

11

10

With and without Measuring instruments

The new GHG 29 control switch series features an easy-to-install and easy-to-connect design. This control switch can be implemented with up to 6 contacts and for 2 to 5 switch positions. Thus, practically all applications in modern control engineering can be covered. Contacts

Cooper Crouse-Hinds 2008 - all rights reserved


9.112

are protected against contact to VBG 4 and have a terminal cross section of up to 6 mm 2 for the connection of single and multi-wire conductors. The rated current of the control switch at 500 V is 16 A. The external contours of the enclosure facilitate access to the connection terminals and thus allow easy installation. Further installation advantages result from the snap-on/snap-off switch contact block and measuring instrument. A labyrinth seal in the cover guarantees the degree of protection IP66. The impact-resistant, glass-fibre-reinforced polyester enclosure material is a prerequisite for withstanding even the most rugged industrial operating conditions. The switch can be padlocked using the inte grated locking facility. The locking position is indicated by a red pin. An interchangeable apparatus label and a neutral switch-position label are supplied with each switch. With CEAG installation system, control switches can be installed with high cost-efficiency. The control switches are also available on request with snap-on metal or moulded-plastic flanges.

Decisive cost saving with the CEAG mounting system Easily accessible connection terminals Degree of protection IP66 Cable connection range up to 6 mm 2 Integrated locking facility Optional forced contact on request

Ex-Control switches

1 2
GHG 293 GHG 292

Cooper Crouse-Hinds 2008 - all rights reserved

Technical data
Ex-Control switch Type 292 without and Type 293 with measuring instrument with GHG 29 Marking to 94/9/EC EC-Type Examination Certificate IECEx Certificate of Conformity Marking accord. to IECEx Permissible ambient temperature Rated voltage Rated current Rated current gold contacts Overload range (Type 293 only) II G EEx ed ia IIC T5/T6 / PTB 99 ATEX 1163 IECEx BKI 07.0011 Ex ed ia IIC T5 or T6 Ex tD A21 IP66 T49 C 20 C to +40 C 55 C to +47 C (T6) ... +55 C (T5) option max. 500 V 16 A 0.4 A 10 fold - 25 sec. 25 fold - 4 sec. 50 fold - 1 sec. indicated 1 : 1.5 Measuring range (Type 293 only) Accuracy (Type 293 only) Circuit (Type 293 only) Switch rating AC 3 Switch rating DC 13 Connecting terminals Degree of protection accd. EN 60529 Cable glands/Gland plates/Enclosure drilling Dimensions (L x W x H) Weight max. 0 - 25 A direct / n / 1A Class 2.5 moving iron 500 V/10 A 690 V/10 A 500 V/16 A 400 V/20 A 24 V/6 A / 60 V/0.8 A / 110 V/0.5 A / 230 V/0.3 A 2 x 0.5 - 2.5 mm2 or 1 x 1.0 - 6.0 mm2 IP66 1 x M25 ( 8 - 17 mm)* 170 x 110 x 129 mm approx. 1.10 kg (1 level) approx. 1.25 kg (2 level) approx. 1.40 kg (3 level) Enclosure material Enclosure colour glass-fibre-reinforced polyester black 225 x 110 x 129 mm approx. 1.90 kg (1 level) approx. 2.05 kg (2 level) approx. 2.20 kg (3 level) max. 690 V 20 A with GHG 28 II D IP66 T 49 C

3 4 5 6 7 8 9 10 11 12
COOPER CROUSE-HINDS GMBH

* Brass flange for metal entries available on request (except for II D at date of publication).

9.113

Ex-Control switches

GHG 292

GHG 293

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering code for Control switch (Code 2) Code A - B1 - B2 - C - D - E1 - E2 - F


A GHG 29_ Code A B1 _ B2 ___ C ___ D _ E __ E2 ___ F 1) ___ Code GHG 292 GHG 293 Code
45O 45O

Component Control switch Control switch with measuring instrument

Code B1

Switch mechanism spring - engaging - spring engaging - engaging - engaging engaging - engaging spring - engaging - engaging engaging - engaging - spring

4 5 6 7 8

45O

45O

90O

45O

45O

45

45

Code B2

Contact
45 135 1 3 2 4 1 3 2 4 1 3 2 4 1 3

Silver contact points


I II 2 1 1/3

Code
45 90 135 45 90 135 45 90 135 45 90 135 1 3 5

Silver contact points


0 I 1 3 5

060
3

034 037 049

45 135 I II

2 4 6 1 3 5

45 90 135 0 I

2 1

6 3 5

45 135

062 065 061


3

45 135 0 I

2 1

4 3

2 4 6 1 3 5

45 90 135 0 I

2 1

4 3 5

45 135

45 135 I 0 II

4 1/3 2 4

2 4 6 1 3 5

45 90 135 I II III

2 1

4 3

6 5

45 90 135 45 90 135 45 90 135

023 019

2 4 1 3

45 90 135 I 0 II 1

2 4 6 1 3 5 2 4 6 1 3 5 7 2 4 68 1 3 5 7

45 90 135 0 I 1

2 3

4 5

063 067 011

2 4 1 3

45 90 135 0 I

4 1 3

45 135

45 135 I II

4 1/3

6 5/7

2 4 1 2

45 90 135 0 I 1

45 135

033
5/7

4
45 90 135

45 135 I 0 II

2 4 6 8 1/3

45 135

024

45 135

2 4 68

45 90 135

2 4 6 8

Other versions as well as gold contact points are available on request. Code C Contact lable Inscription 0 I STOP HAND SENKEN REMOTE I AUS AUS AUF Entriegelt OUT LOCAL STOP HAND AUF HAND 0 BETRIEB 0 0 0 OF REMOTE 0 0 AUS AUS I II START AUTO HEBEN LOCAL II EIN EIN AB Verriegelt HAND AUTO START AUTO ZU AUTO Code 001 002 003 004 005 006 007 008 009 010 011 012 013 014 015 016 017 Inscription 0 AUS AUS RTLICH START OFF HAND 0 MAN START HEBEN OFF AUS HAND ON I II I AUTO HAND AUS NORMAL 0 OFF IN II EIN AUTO FERN STOP ON AUTO START AUTO STOP SENKEN ON EIN AUTO OFF III Code 018 019 020 021 022 023 024 025 026 027 028 029 030 031 032 033

9.114

COOPER CROUSE-HINDS GMBH

Ex-Control switches

1 2
GHG 293 GHG 292

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering code for Control switch (Code 2) Code A - B1 - B2 - C - D - E1 - E2 - F


Code D Locking facility None Centre Left Right Code E1 Movement Direct connection Ct connection 1 /A Connection 0 - 20/24 mA (scale 0-100% / 120%) Connection 4 - 20/24 mA (scale 0-100% / 120%) Moving-coil connection 0 - 20/24 mA (scale 0-100% / 120%) Moving-coil connection 4 - 20/24 mA (scale 0-100% / 120%) Code E2 Mesasuring range/scale 0-1 0 - 2.5 / 3.75 A 2) 0 - 5 / 7.5 A 2) 0 - 10 / 15 A 2) 0 - 15 / 22.5 A 0 - 20 / 30 A 2) 0 - 30 / 45 A 0 - 40 / 60 A 0 - 50 / 75 A 0 - 60 / 90 A Code 002 003 004 005 006 008 009 010 011 012 Measuriing range/scale 0 - 75 /112.5 A 0 - 100 / 150 A 0 - 150 / 225 A 0 - 200 / 300 A 0 - 250 / 375 A 0 - 300 / 450 A 0 - 400 / 600 A 0 - 500 / 750 A 0 - 600 / 900 A 0 - 100% / 150% Code 0 1 2 3 Code 01 02 05 06 07 08 Code 013 014 015 016 017 018 019 020 021 031

3 4 5 6 7 8 9 10 11 12

Code F1

Buil-in components designation Entry type Entry direct in enclosure Entry via plastic flange Entry via metal flange GEH FLK FLM BO SV GK GM* GV M1 .. ..

F2

Entry element

only threaded entry Threaded plug Cable entry moulded plastic Cable entry metal* Cable entry with plug

F3 F4
1)

Size Number

M12, M16, M20, M25, M32, M40 21, 26 No. of entries

The code will represent only a selected part of configuration.

COOPER CROUSE-HINDS GMBH

9.115

Ex-Control switches

GHG 292

GHG 293

Cooper Crouse-Hinds 2008 - all rights reserved

Example for ordering code (Code 2)


Control switch with silver contact points, Switch mechanism 5, Contact arrangement 063, Label HAND-0-AUTO, can be locked at 0, Measuring instrument AM72 for Ct connection n/1A, Scale 0 - 50/75 A, Cable entry 1 x threaded entry M25 on bottom direct entry. Code A B1 B2 063 / C 015 / D 1/ E1 2/ E2 011 / F1 GEH / F2 BO / F3 M25 / F4 1

GHG 295 / 5 /

Ordering details
Switching mechanism Contact system Code Label inscription Order No.

Control switch Type 294 with silver contacts Version with locking facility in 0-, or position right (Code 3), cable entry 1 x M25 on bottom. 6 6 4 8 4 8 5 5
45 135 1 3 2 4 1 3 2 4 1 3

062 065 067 067


3 5

0 0 0 0 0 0 I

I I I I I I 0 II

GHG 292 1000 R0001 GHG 292 1000 R0002 GHG 292 1000 R0003 GHG 292 1000 R0004 GHG 292 2000 R0002 GHG 292 2000 R0003 GHG 292 2000 R0004 GHG 292 2001 R0001

45 135 0 I

2 1

4 3

45 135

45 135 0 I

4 1 3

45 90 135 45 90 135 45 90 135 45 90 135 45 90 135

2 4 1 3

45 90 135 0 I

1 3

2 4 1 3 5

45 90 135 0 I

2 1

037 037 024 023

2 4 6 1 3 5

45 90 135 0 I 1

6 3 5

2 4 6 1 3 5 7

45 90 135 I 0 II

1 3 5 7

2 4 6 8

45 90 135

2/4

6/8

HAND OFF AUTO

Switching mechanism

Contact system

Code

Label inscription

Order No.

Control switch with measuring instrument Type 295 with silver contacts Version with locking facility in 0-, or left position, Measuring instrument AM 72 for CT connection n/1A, Scale 0 - 100/150 %. 1 x M32 on bottom. 6 6
45 135 1 3 2 4 1 3 2 4

062 065

0 0

I I

GHG 293 1000 R0001 GHG 293 1000 R0002

45 135 0 I

2 1

4 3

45 135

45 135

9.116

COOPER CROUSE-HINDS GMBH

Ex-Control switches

1 2
GHG 293 GHG 292

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering details
Measuring range Measuring instrument AM 72, direct measurement Version with 1 x cable entry M25 0 1 /1.5 A 0 - 2.5 / 3.75 A 0 - 5 / 7.5 A 0 - 10 / 15 A 0 - 16 / 24 A 0 - 20 / 24 mA 0-100% / 120% (Ri = 320 ) 4 - 20 / 24 mA 0-100% / 120% (Ri = 320 ) Measuring instrument AM 72, Ct connection n/1A Version with 1 x cable entry M25 0 1 / 1.5 A 0 - 2.5 / 3.75 A 0 - 5 / 7.5 A 0 - 10 / 15 A 0 - 15 / 22.5 A 0 - 20 / 30 A 0 - 30 / 45 A 0 - 40 / 60 A 0 - 50 / 75 A 0 - 60 / 90 A 0 - 75 / 112.5 A 0 - 100 / 150 A 0 - 150 / 225 A 0 - 200 / 300 A 0 - 250 / 375 A 0 - 300 / 450 A 0 - 400 / 600 A 0 - 500 / 750 A 0 - 600 / 900 A 0 - 100% / 150% GHG 412 8282 R0002 GHG 412 8282 R0003 GHG 412 8282 R0004 GHG 412 8282 R0005 GHG 412 8282 R0006 GHG 412 8282 R0008 GHG 412 8282 R0009 GHG 412 8282 R0010 GHG 412 8282 R0011 GHG 412 8282 R0012 GHG 412 8282 R0013 GHG 412 8282 R0014 GHG 412 8282 R0015 GHG 412 8282 R0016 GHG 412 8282 R0017 GHG 412 8282 R0018 GHG 412 8282 R0019 GHG 412 8282 R0020 GHG 412 8282 R0021 GHG 412 8282 R0031 GHG 412 8281 R0002 GHG 412 8281 R0003 GHG 412 8281 R0004 GHG 412 8281 R0005 GHG 412 8281 R0007 GHG 412 8285 R0033 GHG 412 8286 R0035 Order No.

3 4 5 6 7 8 9 10 11 12
COOPER CROUSE-HINDS GMBH

9.117

Ex-Control switches

GHG 292

GHG 293

Cooper Crouse-Hinds 2008 - all rights reserved

Accessories
Mounting plate for type 292 Type Size 2 Size 2 Size 2 Size 4 Size 4 Size 4 Application Wall mounting Pipe mounting Trellis-work mounting Wall mounting Trellis-work mounting Pipe mounting Mounting technique snap-on snap-on snap-on snap-on * snap-on * snap-on * OU 1 1 1 1 1 1 Order No. GHG 610 1953 R0104 GHG 610 1953 R0105 GHG 610 1953 R0106 GHG 610 1953 R0128 GHG 610 1953 R0128 GHG 610 1953 R0132

Mounting plate for type 293 Type Size 3 Size 3 Size 3 Size 5 Size 5 Size 5 Application Wall mounting Pipe mounting Trellis-work mounting Wall mounting Trellis-work mounting Pipe mounting Mounting technique snap-on snap-on snap-on snap-on * snap-on * snap-on * OU 1 1 1 1 1 1 10 Order No. GHG 610 1953 R0118 GHG 610 1953 R0110 GHG 610 1953 R0118 GHG 610 1953 R0128 GHG 610 1953 R0128 GHG 610 1953 R0132 GHG 610 1953 R0041

Snap-on mounting for CEAG apparatus with 5.5 mm and 11 mm mounting size per 4 pieces *snap-on with snap-on mounting 5.5 mm

9.118

COOPER CROUSE-HINDS GMBH

Cooper Crouse-Hinds 2008 - all rights reserved

COOPER CROUSE-HINDS GMBH

9.119

12

11

10

E X - C O N T R O L
Light alloy Ve r s i o n f o r Z o n e 1

S W I T C H E S

CEAG explosion-protected control switch es are made of high-quality cast aluminium-silicon (AlSi). A robust plastic powder coating according to RAL 7031 protects the CEAG control switches against aggressive atmospheres and chemicals. Cover screws as well as all internal and external

Cooper Crouse-Hinds 2008 - all rights reserved


9.120

metal parts are made of stainless steel. These switches feature an easy-to-install and easy-to-connect design. The cam switch version allows implementation of many variants, covering almost all applications in modern control engineering. An optional locking facility allows to secure the switch against unauthorised or inadvertent actuation with a padlock. Internationally approved.

High mechanical, chemical and thermal resistance Impact-resistant plastic powder coating Snap-on switch holder

Ex-Control switches

1 2
GHG 295 GHG 294

Cooper Crouse-Hinds 2008 - all rights reserved

Technical data
Ex-Control switch Type 294 without and Type 295 with measuring instrument with GHG 29 Marking to 94/9/EC EC-Type Examination Certificate IECEx Certificate of Conformity Marking accord. to IECEx Permissible ambient temperature Rated voltage Rated current Rated current gold contacts Overload range (Type 293 only) II G EEx ed ia IIC T5/T6 / PTB 99 ATEX 1163 IECEx BKI 07.0011 Ex ed ia IIC T5 or T6 Ex tD A21 IP66 T49 C 20 C to +40 C 55 C to +47 C (T6) ... +55 C (T5) option max. 500 V 16 A 0.4 A 10 fold - 25 sec. 25 fold - 4 sec. 50 fold - 1 sec. indicated 1 : 1.5 Measuring range (Type 293 only) Accuracy (Type 293 only) Circuit (Type 293 only) Switch rating AC 3 Switch rating DC 13 Connecting terminals Degree of protection accd. EN 60529 Cable glands/Gland plates/Enclosure drilling Dimensions (L x W x H) Weight Enclosure material Enclosure colour as well as M32 and M25 cable entries. max. 0 - 25 A direct / n / 1A Class 2.5 moving iron 500 V/10 A 690 V/10 A 500 V/16 A 400 V/20 A 24 V/6 A / 60 V/0.8 A / 110 V/0.5 A / 230 V/0.3 A 2 x 0.5 - 2.5 mm2 or 1 x 1.0 - 6.0 mm2 IP66 1 x M25 ( 8 - 17 mm)* 170 x 130 x 129 mm approx. 1.90 kg (1 level) approx. 2.05 kg (2 level) grey RAL 7031 260 x 160 x 90 mm approx. 2.90 kg (1 level) approx. 3.05 kg (2 level) max. 690 V 20 A with GHG 28 II D IP66 T 49 C

3 4 5 6 7 8 9 10 11 12
COOPER CROUSE-HINDS GMBH

high quality cast aluminium-silicone (AlSi)

* Control switches with direct indicating measuring instruments in the standard version are delivered with 2 looping terminals and PE terminal

9.121

Ex-Control switches

GHG 294

GHG 295

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering code for Control switch (Code 2) Code A - B1 - B2 - C - D - E1 - E2 - F


A GHG 29_ Code A B1 _ B2 ___ C ___ D _ E __ E2 ___ F 1) ___ Code GHG 294 GHG 295 Code
45O 45O

Component Control switch Control switch with measuring instrument

Code B1

Switch mechanism spring - engaging - spring engaging - engaging - engaging engaging - engaging spring - engaging - engaging engaging - engaging - spring

4 5 6 7 8

45O

45O

90O

45O

45O

45

45

Code B2

Contact
45 135 1 3 2 4 1 3 2 4 1 3 2 4 1 3

Silver contact points


I II 2 1 1/3

Code
45 90 135 45 90 135 45 90 135 45 90 135 1 3 5

Silver contact points


0 I 1 3 5

060
3

034 037 049

45 135 I II

2 4 6 1 3 5

45 90 135 0 I

2 1

6 3 5

45 135

062 065 061


3

45 135 0 I

2 1

4 3

2 4 6 1 3 5

45 90 135 0 I

2 1

4 3 5

45 135

45 135 I 0 II

4 1/3 2 4

2 4 6 1 3 5

45 90 135 I II III

2 1

4 3

6 5

45 90 135 45 90 135 45 90 135

023 019

2 4 1 3

45 90 135 I 0 II 1

2 4 6 1 3 5 2 4 6 1 3 5 7 2 4 68 1 3 5 7

45 90 135 0 I 1

2 3

4 5

063 067 011

2 4 1 3

45 90 135 0 I

4 1 3

45 135

45 135 I II

4 1/3

6 5/7

2 4 1 2

45 90 135 0 I 1

45 135

033
5/7

4
45 90 135

45 135 I 0 II

2 4 6 8 1/3

45 135

024

45 135

2 4 68

45 90 135

2 4 6 8

Other versions as well as gold contact points are available on request. Code C Contact lable Inscription 0 I STOP HAND SENKEN REMOTE I AUS AUS AUF Entriegelt OUT LOCAL STOP HAND AUF HAND 0 BETRIEB 0 0 0 OF REMOTE 0 0 AUS AUS I II START AUTO HEBEN LOCAL II EIN EIN AB Verriegelt HAND AUTO START AUTO ZU AUTO Code 001 002 003 004 005 006 007 008 009 010 011 012 013 014 015 016 017 Inscription 0 AUS AUS RTLICH START OFF HAND 0 MAN START HEBEN OFF AUS HAND ON I II I AUTO HAND AUS NORMAL 0 OFF IN II EIN AUTO FERN STOP ON AUTO START AUTO STOP SENKEN ON EIN AUTO OFF III Code 018 019 020 021 022 023 024 025 026 027 028 029 030 031 032 033

9.122

COOPER CROUSE-HINDS GMBH

Ex-Control switches

1 2
GHG 295 GHG 294

Cooper Crouse-Hinds 2008 - all rights reserved

Ordering code for Control switch (Code 2) Code A - B1 - B2 - C - D - E1 - E2 - F


Code D Locking facility None Centre Left Right Code E1 Movement Direct connection Ct connection 1 /A Connection 0 - 20/24 mA (scale 0-100% / 120%) Connection 4 - 20/24 mA (scale 0-100% / 120%) Moving-coil connection 0 - 20/24 mA (scale 0-100% / 120%) Moving-coil connection 4 - 20/24 mA (scale 0-100% / 120%) Code E2 Mesasuring range/scale 0-1 0 - 2.5 / 3.75 A 2) 0 - 5 / 7.5 A 2) 0 - 10 / 15 A 2) 0 - 15 / 22.5 A 0 - 20 / 30 A 2) 0 - 30 / 45 A 0 - 40 / 60 A 0 - 50 / 75 A 0 - 60 / 90 A Code 002 003 004 005 006 008 009 010 011 012 Measuriing range/scale 0 - 75 /112.5 A 0 - 100 / 150 A 0 - 150 / 225 A 0 - 200 / 300 A 0 - 250 / 375 A 0 - 300 / 450 A 0 - 400 / 600 A 0 - 500 / 750 A 0 - 600 / 900 A 0 - 100% / 150% Code 0 1 2 3 Code 01 02 05 06 07 08 Code 013 014 015 016 017 018 019 020 021 031

3 4 5 6 7 8 9 10 11 12

Code F1

Buil-in components designation Entry type Entry direct in enclosure Entry via plastic flange Entry via metal flange GEH FLK FLM BO SV GK GM* GV M1 .. ..

F2

Entry element

only threaded entry Threaded plug Cable entry moulded plastic Cable entry metal* Cable entry with plug

F3 F4
1)

Size Number

M12, M16, M20, M25, M32, M40 21, 26 No. of entries

The code will represent only a selected part of configuration.

COOPER CROUSE-HINDS GMBH

9.123

Ex-Control switches

GHG 294

GHG 295

Cooper Crouse-Hinds 2008 - all rights reserved

Example for ordering code (Code 2)


Control switch with silver contact points, Switch mechanism 5, Contact arrangement 063, Label HAND-0-AUTO, can be locked at 0, Measuring instrument AM72 for Ct connection n/1A, Scale 0 - 50/75 A, Cable entry 1 x threaded entry M25 on bottom direct entry. Code A B1 B2 063 / C 015 / D 1/ E1 2/ E2 011 / F1 GEH / F2 BO / F3 M25 / F4 1

GHG 295 / 5 /

Ordering details
Switching mechanism Contact system Code Label inscription Order No.

Control switch Type 294 with silver contacts Version with locking facility in 0-, or position right (Code 3), cable entry 1 x M25 on bottom. 6 6 4 8 4 8 5 5
45 135 1 3 2 4 1 3 2 4 1 3

062 065 067 067


3 5

0 0 0 0 0 0 I

I I I I I I 0 II

GHG 294 1000 R0001 GHG 294 1000 R0002 GHG 294 1000 R0003 GHG 294 1000 R0004 GHG 294 2000 R0002 GHG 294 2000 R0003 GHG 294 2000 R0004 GHG 294 2001 R0001

45 135 0 I

2 1

4 3

45 135

45 135 0 I

4 1 3

45 90 135 45 90 135 45 90 135 45 90 135 45 90 135 45 90 135

2 4 1 3

45 90 135 0 I

1 3

2 4 1 3 5

45 90 135 0 I

2 1

037 037 024


5

2 4 6 1 3 5

45 90 135 0 I 1

6 3 5

2 4 6 1 3 5 7

45 90 135 I 0 II

1 3 5 7

2 4 6 8 1 3 5

45 90 135 I II III 1

2/4 3

6/8

023

HAND OFF AUTO

2 4 6

45 90 135

Switching mechanism

Contact system

Code

Label inscription

Order No.

Control switch with measuring instrument Type 295 with silver contacts Version with locking facility in 0-, or left position, Measuring instrument AM 72 for CT connection n/1A, Scale 0 - 100/150 %. 1 x M32 on bottom. 6 6
45 135 1 3 2 4 1 3 2 4

062 065

0 0

I I

GHG 295 1000 R0001 GHG 295 1000 R0002

45 135 0 I

2 1

4 3

45 135

45 135

9.124

COOPER CROUSE-HINDS GMBH

Cooper Crouse-Hinds 2008 - all rights reserved

COOPER CROUSE-HINDS GMBH

9.125

12

11

10

L I G H T

A L L O Y

C O N T R O L

S T A T I O N S

Ex-d pushbutton and control switches

Cooper Crouse-Hinds 2008 - all rights reserved


9.126

Ex-d explosion-protected control stations made of light alloy metal are equipped with up to three components to switch and control processes in areas of Zone 1, 2, 21 and 22 at no risk of explosion. Built-in components, such as signal lamps, pushbuttons and switches are ready installed inside of the enclosures. To facilitate insertion of cables into the entries, Ex-d threads for 3/4 Ex-d cable glands are available at the enclosures. A high IP degree of protection allows universal use in areas at risk of explosion. The light metal control stations have an outside earthing connection.

High degree of protection IP67 High mechanical, chemical and thermal resistance Individual configuration

Ex-d Control stations

1 2
EFS A/A/V EFS A EFS D

Cooper Crouse-Hinds 2008 - all rights reserved

Technical data
Ex-d control stations Type EFS Marking to 94/9/EC EC-Type Examination Certificate IECEx Certificate of Conformity Marking accd. to IECEx Permissible ambient temperature Rated voltage Rated current PE connecting terminals Insulation class Incandescent lamp Degree of protection accd. EN 60529 Cable glands/Gland plates/Enclosure drilling Enclosure material Enclosure colour Other versions available on request II 2 G EEx d IIC T6 / LOM 03 ATEX 2034 IECEx BKI 07.0027 Ex d IIC T6 Ex tD A21 IP67 T80 C 20 C to +55 C max. 660 V AC max. 20 A 2 x 2.5 mm2 / PE ext.: 2 x 6 mm2 I 230 V 3 W IP67 1 x 3/4 ISO 7/1 or 2 x 3/4 ISO 7/1, one plugged Light alloy natural finish II 2 D IP67 T 85 C

3 4 5 6
Weight 0.75 kg 0.85 kg 0.80 kg 0.85 kg 0.85 kg 1.50 kg 1.50 kg 1.20 kg Qty. 1 1 1 1 1 1 1 1 Order No. NOR 000 114 110 511 NOR 000 114 110 553 NOR 000 114 110 587 NOR 000 114 110 540 NOR 000 114 110 595 NOR 000 114 110 747 NOR 000 114 110 748 NOR 000 114 110 740

Ordering details
Type Control units EFS A EFS A/A EFS D EFS A/D EFS L EFS A/A/A EFS A/A/V EFS 72 1 x pushbutton, 1 NO + 1 NC, label "White" 2 x pushbutton, 1 NO + 1 NC, lable "I - 0" 1 x mushroom head pushbutton, 1 NO + 1 NC, label "0" 1 x pushbutton 1 NO, 1 x mushroom head pushbutton NC, label "I - 0" 1 x alarm pushbutton, 1 NO + 1 NC, with windows 3 x pushbutton, 1 NO + 1 NC, label "0 - I - II" 2 x pushbutton, 1 NO + 1 NC, label "0 - I - II", 1 x green signal lamp With measuring instruments 72 mm x 72 mm Description

7 8 9 10 11 12

Control switches EFS I EFS H EFS J EFS P EFS P40 0-1 1-2 1-0-2 0-1 0-1 0.90 kg 0.90 kg 0.90 kg 0.90 kg 0.90 kg 1 1 1 1 1 NOR 000 003 110 945 NOR 000 003 110 937 NOR 000 003 110 953 NOR 000 003 110 995 NOR 000 114 110 738

COOPER CROUSE-HINDS GMBH

9.127