Crouse Hinds Control Stations
Crouse Hinds Control Stations
Crouse Hinds Control Stations
2 3 4 5 6 7 8
9.211
9 10
E X - I N S TA L L AT I O N S W I T C H
9.411
E X - C O N T R O L S TAT I O N S
9.611
I N D I V I D U A L E X - C O N T R O L S TAT I O N S
9.321
E X - C O N T R O L A N D S I G N A L U N I T S F O R PA N E L M O U N T I N G
9.801
EX-CONTROL-SWITCHES
9.112
11 12
F L A M E P R O O F L I G H T A L L O Y C O N T R O L S TAT I O N S
9.126
Material selection
At the heart of every electrical system is the control station. Even under the most adverse conditions, CEAG control stations can be used and operated reliably. The enclosures consist of impact-resistant thermoplastic, glassfibre-reinforced polyester, light alloy or stainless steel. The robust materials, thermoplastic and polyester, fulfil the specification for surface resistance < 10 9 required by EN 60079. The well-tried enclosure materials have proven their high resistance to chemicals in indoor and outdoor installations especially in the chemical and off-shore industries. All metal parts are made of stainless steel.
9.2
1 2
with a slip-on strain relief and protec -
tive cap and is then completely certified. Planning and procurement of panel-mounted apparatus with different cable lengths is a thing of the past.
3 4 5 6 7 8 9 10 11 12
9.3
E X - I N S T A L L A T I O N
16 A, 250 V Plastic version for Zone 21
S W I T C H
The explosion-protected installation switches are for use in the Zones 1, 2, 21 and 22. The materials used have proved to be safe and reliable for both indoor and outdoor installations, in particular in chemical and off-shore plants. The robust
housings are made of a modified polyamide material. The large actuator surface of the installation switch allows perfect operation, even when wearing working gloves. A protective collar prevents inadvertent operation. The toggle has a luminescent label which is in accordance with 7 of the Workshop Regulations and is also free from radioactive additives. Due to the external fixing facility, the switch can be installed easily while the cover is closed. Cable entry from the top is made possible by turning the base. In special cases a through wiring is possible as one can see on the illustration opposite. International approvals.
Large toggle also for working gloves Safety standard IP66 Cable entry from the top or bottom Connecting terminals easily accessible
Ex-Installation switch
1 2
Switch/Pushbutton
Technical data
Ex-installation switches and Ex-pushbuttons Marking to 94/9/EC EC-Type Examination Certificate IECEx Certificate of conformity Marking acc. IECEx Permissible ambient temperature Rated voltage Rated current Connecting terminals Degree of protection accd. to EN 60529 Cable glands1) Weight Enclosure material II 2 G EEx de IIC T6 / PTB 98 ATEX 3121 IECEx BKI 07.0036 Ex ed IIC T6 Ex tD A21 IP66 T67 C 20 C to +40 C 55 C to +55 C (option) 250 V, 50 - 60 Hz 16 A Switch terminals: 2 x 2.5 mm2 / PE-terminals: 4 x 2.5 mm2 IP66 Ex-e cable glands M25 for cables from 8 - 17 mm 0.32 kg Polyamide II 2 D T 67 C
3 4 5 6
Cable glands1) 1 x M25
L L( N )
Ordering details
Type ON-OFF switch 2-pole Contact arrangement Order No. GHG 273 2000 R0017 GHG 273 2000 R0018 GHG 273 2000 R0003 GHG 273 6000 R0011 GHG 273 6000 R0003 GHG 273 6000 R0014 GHG 273 4000 R0004 GHG 273 4000 R0007
7 8 9
Change-over switch
L
Pushbutton
L
1) 2)
L( N )
Base enclosure can be rotated afterwards (entry from top or down) Threaded only
Dimension drawing
85 X75 85 X75 64 55
X52
X52
85
85
115
115
10
20
Dimensions in mm
53
35
Switch/pushbutton
X = fixing dimension
11 12
9.5
T A T
Moulded plastic Ve r s i o n f o r Z o n e 1
Even under the most adverse conditions, CEAG control stations can be used and operated reliably. The enclosures consist of low-temperature impact-resistant thermoplastic which fulfils the requirements of EN 60079 and provides a high resistance to chemicals. The well thought out
design with low side walls allows optimum cable connection. Quick fixing allows up to three CEAG built-in components, such as signal lamps, pushbuttons and switches, to be snapped on a rail in the enclosure. They can be snapped out of the enclosure to facilitate cable-entry feeding. Notches in the mounting rails prevent the built-in components from being twisted out of place. Wall mounting can be carried out via easily accessible fixing apertures when the enclosure cover is sealed. CEAG mounting pla tes offer a time-saving fixing tech nique. CEAG control stations feature standard M25 moulded-plastic cable entries with an 8 to 17 mm clamping diameter. Coupling pieces link enclosures to each other and prevent them from being twisted out of place. Alternatively, metal screws and flanges can be used for mounting the metal flanges also enable external earthing. Free mounting areas can be provided for retrofitting certified CEAG components. These are then factory sealed with blanking elements. Internationally approved.
Flat side walls Quick fixing of all built-in components High chemical resistance Different enclosures can be combined
Ex-control stations
1 2
Type 411 83 Type 411 82 Type 411 81
Technical data
Ex-Control stations Type 411 81 Type 411 82 Type 411 83 Marking to 94/9/EC EC-Type Examination Certificate IECEx Certificate of conformity Marking acc. to IECEx Permissible ambient temperature Rated voltage Rated current Connecting terminals Insulation class Degree of protection accd. EN 60529 Cable glands/Gland plates/Enclosure drilling Enclosure material Enclosure colour Type 411 81 Dimensions (L x W x H) Weight (empty) Type 411 82 Dimensions (L x W x H) Weight (empty) Type 411 83 Dimensions (L x W x H) Weight (empty) 165 x 85 x 77.5 mm 0.45 kg 125 x 85 x 77.5 mm 0.35 kg 85 x 85 x 77.5 mm 0.25 kg II 2 G EEx e II T6 / EEx e ib IIC T6 / EEx ed IIC T6 / EEx ed ib IIC T6 II 2 D IP66 T 48 C PTB 00 ATEX 3117 IECEx BKI 04.0003 Ex e II T6, Ex e ib IIC T6, Ec ed IIC T6 or Ec ed ib IIC T6 20 C to +40 C 55 C to +55 C (option) 690 V AC 16 A 2 x 2.5 mm2 I IP66 (standard) IP65 (measuring instrument AM45, double pushbutton) 1 x M25 EEx-e cable gland for cables from 8 - 17 mm or 1 x M20 thread Polyamide Black
3 4 5 6 7 8
Moving coil II G EEx ib IIC Class 1.5 10-fold -5 sec.
Type 411 82 with measuring instrument AM 72 Moving iron Marking to 94/9/EC Accuracy Overload range II G EEx e II Class 2.5 10-fold -25 sec. 25-fold - 4 sec. 50-fold - 1 sec. Measuring range Li Ci Ui Ii Connecting terminals Weight
1)
9 10 11 12
9.7
Ex-control stations
Built-in components 1 x pushbutton DRT 1 NO + 1 NC label: 0, I, START, STOP 1 x mushroom-head pushbutton SGT 1 NO + 1 NC Emergency stop 1 x mushroom-head pushbutton SGT 1 NO + 1 NC Emergency stop with key unlocking
Weight approx.
Order No.
14 13
22 21
0.40 kg
14 13 () 14 13 I 0 14
22 21
0.45 kg
22 21
0.50 kg
22
13 23
0.45 kg
II
()
SW 5 engaging-engaging-engaging label: I 0 II 0.52 kg GHG 411 8100 R0018 1 x control switch SCT
I II
21 13
1 change-over SW 6 engaging-engaging label: HAND AUTO label: 0 label: I I II 0.45 kg 0.45 kg 0.45 kg GHG 411 8100 R0003 GHG 411 8100 R0004 GHG 411 8100 R0005
22/14
2 NO SW 5 engaging-engaging-engaging label: HAND 0 AUTO label: I 0 II label: Local Remote Auto 0.45 kg 0.45 kg 0.45 kg GHG 411 8100 R0006 GHG 411 8100 R0007 GHG 411 8100 R0008
14/24
9.8
Ex-control stations
1 2
Type 411 82...18 Type 411 82...17 Type 411 82...03 Type 411 82...01
3
Order No. GHG 411 8200 R0001
Weight approx.
14 22 13 21
0.54 kg
4 5
14 X1
22 X2
1 x signal lamp SIL 20-250 V AC/DC coloured lens cover: white, red, green, yellow
13 I 0 14
21
1 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 1 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 1 x mushroom-head pushbutton SGT 1 NO + 1 NC Emergency stop 0.57 kg GHG 411 8200 R0016 0.65 kg GHG 411 8200 R0003
22
13 I 0 14 13
21
6 7 8 9
0.65 kg GHG 411 8200 R0018
22 21
14 0I
22 21 13
1 x control switch SCT 1 change-over SW 6 engaging-engaging label: 0 I 1 x mushroom-head pushbutton SGT 1 NO + 1 NC Emergency stop 1 x signal lamp SIL 20-250 V AC/DC coloured lens cover: white, red, green, yellow 1 x key-operated switch 0.57 kg GHG 411 8200 R0017
22/14 13 21
14
22
X1
X2
II
13
23
2 NO SW 5 engaging-engaging-engaging label: I 0 II
()
14 24
10 11 12
COOPER CROUSE-HINDS GMBH
9.9
Ex-control stations
Built-in components 1 x signal lamp SIL 20-250 V AC/DC coloured lens cover: white, red, green, yellow 2 x pushbutton DRT 1 NO + 1 NC each label: 0, I, START, STOP
Weight approx.
Order No.
14 13
22 21
0.76 kg
14 X1
22 X2
1 x signal lamp SIL 20-250 V AC/DC coloured lens cover: white, red, green, yellow
13 I 0
21
1 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 1 x mushroom-head pushbutton SGT 1 NO + 1 NC Emergency stop 1 x measuring instrument AM72 CT connection n/1A Scale 0 100%/150% 0.80 kg GHG 411 8300 R0003
14 22 13 21
14 1
22 2
13 21
1 x control switch SCT 1 NO + 1 NC SW 8 engaging-engaging-spring label: 0 I 0.92 kg GHG 411 8300 R0023
14
22
X1
X2
1 x signal lamp SIL 20-250 V AC/DC coloured lens cover: white, red, green, yellow
13 I 0
21
1 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 1 x control switch SCT 1 change-over SW 6 engaging-engaging label: HAND - AUTO 0.80 kg GHG 411 8300 R0004
HA
14 22 21 13
22/14
9.10
Ex-control stations
1 2
Measuring AM72
3 4 5 6 7 8
X92 73
Dimension drawing
85 38 85 38
85 38
85
115 85
X52
155 125
40 X92
40 40 X132
195 165
155
125
9
75 77.5 5
X75 X75
X75
Type 411 81
Type 411 82
Type 411 83
5.6 73
10
Dimensions in mm
22
11 12
X = fixing dimension
Measuring instrument AM 72
9.11
Ex-control stations
Size 1
Size 2
Size 4
Accessories
Mounting plate for type 411 81 Type Size 1 Size 1 Size 1 Size 4 Size 4 Size 4 Application Wall mounting Pipe mounting Trellis-work mounting Wall mounting Trellis-work mounting Pipe mounting Mounting technique screw-on screw-on screw-on snap-on1) snap-on1) snap-on1) OU 1 1 1 1 1 1 Order No. GHG 610 1953 R0101 GHG 610 1953 R0102 GHG 610 1953 R0103 GHG 610 1953 R0126 GHG 610 1953 R0126 GHG 610 1953 R0130
Mounting plate for type 411 82 and 411 83 Type Application Mounting technique OU 1 1 1 1 1 1 10 Order No. GHG 610 1953 R0104 GHG 610 1953 R0105 GHG 610 1953 R0106 GHG 610 1953 R0126 GHG 610 1953 R0126 GHG 610 1953 R0130 GHG 610 1953 R0041 Size 2 Wall mounting screw-on Size 2 Pipe mounting screw-on Size 2 Trellis-work mounting screw-on Size 4 Wall mounting snap-on1) Size 4 Trellis-work mounting snap-on1) Size 4 Pipe mounting snap-on1) Snap-on mounting for CEAG apparatus with 5.5 mm and 11 mm mounting size per 4 pieces
1)
Dimension drawing
134.5 9 134.5 82
118.5
X54 X66
Size 1 Wall mounting Size 1 Pipe mounting
X51 X62
23 134.5
118.5
134.5
27
118.5
237
X = fixing dimension
9.12
Dimensions in mm
Ex-control stations
1 2
Type 434... Type 432...
Technical data
Ex-Control stations Type 432 Type 434 Marking to 94/9/EC EC-Type Examination Certificate IECEx Certificate of conformity Marking accd. to IECEx Permissible ambient temperature Rated voltage Rated current Switch rating control switch GHG 23 Connecting terminals Insulation class Degree of protection accd. EN 60529 Cable glands/Gland plates/Enclosure drilling Enclosure material Enclosure colour Type 432 Dimensions (L x W x H) Weight (empty) Type 434 Dimensions (L x W x H) Weight (empty)
1)
3
II 2 G EEx e II T6 / EEx e ib IIC T6 / EEx ed IIC T6 / EEx ed ib IIC T6 II 2 D IP66 T 48 C / T53 C PTB 00 ATEX 3117 IECEx BKI 04.0003 Ex e II T6, Ex e ib IIC T6, Ex ed IIC T6 or Ex ed ib IIC T6 20 C to +40 C 55 C to +55 C (option) 690 V AC (with control switch GHG 23 to 500 V) 16 A (with control switch GHG 23 max. 10 A) AC 15: 230 V/10 A / 500 V/6 A DC 13: 24 V/ 2 A / 230 V/0.4 A 2 x 4 mm2 I IP66 (standard) IP65 (measuring instrument AM45, double pushbutton) 2 x M25 EEx-e cable gland for cables from 8 - 17 mm incl. 1 blanking plug or 2 x M20 thread Polyamide Black
4 5 6 7 8 9 10 11 12
9.13
Ex-control stations
Type 432...01
Type 432...02
Type 432...03
Type 432...05
Weight approx.
Order No.
14 22 13 21
0.85 kg
14 X1
22 X2
1 x signal lamp SIL 20-250 V AC/DC coloured lens cover: white, red, green, yellow 1 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 0.90 kg GHG 432 0011 R0002 1 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 1 x mushroom-head pushbutton SGT 1 NO + 1 NC Emergency stop 1 x measuring instrument AM45 CT connection n/1A Scale 0 100%/150% 0.85 kg GHG 432 0011 R0003
13 I 0 14 13 I 0
21
22 21
14 22 13 21
14
22
13 I 0 14
21
1 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 0.95 kg GHG 432 0011 R0005
22
9.14
Ex-control stations
1 2
Type 432...17 Type 432...05 Type 432...03
3
Order No. GHG 432 0001 R0003 GHG 432 0001 R0004
Weight approx.
45 135
label: HAND - AUTO label: 0 2 NO SW 5 engaging-engaging-engaging label: HAND 0 AUTO label: I 1 NO + 1 NC SW 8 engaging-engaging-spring return label: 0 label: 0 IN I START 0 II 1 x control switch GHG 23 I 1 x control switch GHG 23
0.70 kg 0.70 kg
4 5 6 7 8
II
5/7 6 8
45 90 135
0.70 kg 0.70 kg
I 6
5 7
45 90 135
GHG 432 0001 R0012 GHG 432 0001 R0013 GHG 432 0001 R0014
II
1/3
5/7
2 change-over SW 6 engaging-engaging label: I II I AUTO 0.70 kg 0.70 kg GHG 432 0001 R0015 GHG 432 0001 R0016
45 135
2 4 6 8
label: HAND
I II III 1 3 5
1 x control switch GHG 23 2 NO + 1 NC SW 5 engaging-engaging-engaging label: I 2 NO + 1 NC SW 8 engaging-engaging-spring return label: 0 label: 0 IN I START 0.86 kg 0.86 kg 0.86 kg GHG 432 0001 R0018 GHG 432 0001 R0019 GHG 432 0001 R0020 II III 0.86 kg GHG 432 0001 R0017 1 x control switch GHG 23
45 90 135
3 5
45 90 135
label: AUS-Betrieb-EIN
9 10 11 12
COOPER CROUSE-HINDS GMBH
9.15
Ex-control stations
Type 432...10
Type 432...09
Type 432...08
Type 432...06
Weight approx.
Order No.
1 6
1 x control switch GHG 23 1 change-over SW 6 spring return-engaging label: 0 I 1.35 kg GHG 432 0011 R0006 1 x measuring instrument AM45 CT connection n/1A Scale 0 100%/150%
5/7
45 135
II
1 x control switch GHG 23 2 NO SW 5 engaging-engaging-engaging label: I 0 II 1.35 kg GHG 432 0011 R0008 1 x measuring instrument AM45 CT connection n/1A Scale 0 100%/150%
45 90 135
6 8
I 6
5 7
1 x control switch GHG 23 1 NO + 1 NC SW 8 engaging-engaging-spring label: 0 I 1.35 kg GHG 432 0011 R0009 1 x measuring instrument AM45 CT connection n/1A Scale 0 100%/150%
45 90 135
II III
1 x control switch GHG 23 1 NO + 1 NC SW 5 engaging-engaging-engaging label: I II III 1.35 kg GHG 432 0011 R0010
45 90 135
9.16
Ex-control stations
1 2
Type 434...11 Type 434...10 Type 434...02
3
Weight approx. Order No.
13 I 0
21
1 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 1 x mushroom-head pushbutton SGT 1 NO + 1 NC Emergency stop 1 x measuring AM72 CT connection n/1A Scale 0 100%/150% 1.40 kg GHG 434 0111 R0002
4 5 6
1.55 kg GHG 434 0111 R0010
14 22 13 21
14 1
22 2
13
21
14
0 1
22
1 x control switch GHG 23 1 change-over SW 6 engaging-engaging label: 0 I 1 x measuring AM72 CT connection n/1A Scale 0 100%/150%
45 135
7 8
1.55 kg GHG 434 0111 R0011
13
21
14
0
22
I 6
9 10 11 12
COOPER CROUSE-HINDS GMBH
9.17
Ex-control stations
Type 434...04
Type 434...05
Type 434...09
Built-in components 1 x signal lamp SIL 20-250 V AC/DC coloured lens cover: white, red, green, yellow 2 x pushbutton DRT 1 NO + 1 NC label: 0, I, START, STOP 1 x mushroom-head pushbutton SGT 1 NO + 1 NC Emergency stop
Weight approx.
Order No.
14 13
22 21
14 13
22 21
1.45 kg
14 X1 13 I 0 14 X1 13 I 0 14 X1 13 I 0 14 13
22 X2 21
2 x signal lamp SIL 20-250 V AC/DC coloured lens cover: white, red, green, yellow 2 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 1.45 kg GHG 434 1111 R0005
22 X2 21
22
X2 21
1 x signal lamp SIL 20-250 V AC/DC coloured lens cover: white, red, green, yellow 1 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 1 x mushroom-head pushbutton SGT 1 NO + 1 NC Emergency stop
13 23
22 21
14
22
II
()
14 24
9.18
Ex-control stations
1 2
Size 5 Size 3 Size 2
Accessories
Mounting plate for type 432 Type Size 2 Size 2 Size 2 Size 5 Size 5 Size 5 Application Wall mounting Pipe mounting Trellis-work mounting Wall mounting Trellis-work mounting Pipe mounting Mounting technique screw-on screw-on screw-on snap-on * snap-on * snap-on * OU 1 1 1 1 1 1 Order No. GHG 610 1953 R0104 GHG 610 1953 R0105 GHG 610 1953 R0106 GHG 610 1953 R0128 GHG 610 1953 R0128 GHG 610 1953 R0132
3 4 5 6 7 8 9
Mounting plate for type 434 Type Application Mounting technique OU 1 1 1 1 1 1 10 Order No. GHG 610 1953 R0118 GHG 610 1953 R0110 GHG 610 1953 R0118 GHG 610 1953 R0128 GHG 610 1953 R0128 GHG 610 1953 R0132 GHG 610 1953 R0041 Size 3 Wall mounting screw-on Size 3 Pipe mounting screw-on Size 3 Trellis-work mounting screw-on Size 5 Wall mounting snap-on * Size 5 Trellis-work mounting snap-on * Size 5 Pipe mounting snap-on * Snap-on mounting for CEAG apparatus with 5.5 mm and 11 mm mounting size per 4 pieces * snap-on with snap-on mounting 5.5 mm
Dimension drawing
100 X88 90 100 X88 90
156 X 97 5.2
Type 432
134.5 9 134.5
Type 434
82 134.5 23
245 X 186
5.2
10
186 186 X94 X105 186 X30
Dimensions in mm
11 12
X54 X66
9.19
E X - C O N T R O L
Light alloy Ve r s i o n f o r Z o n e 1
S T A T I O N S
Light-alloy control stations in explosionprotected design are equipped with up to four components. These control stations are made of high-quality cast aluminium-silicon (AlSi). A robust plastic powder coating according to RAL 7031 protects the CEAG control stations
against aggres sive atmospheres and chemicals. Cover screws as well as all internal and external metal parts are made of stainless steel. CEAG flameproof built-in components, such as signal lamps, pushbuttons and switches, provide snap-on mounting on rails screwed into the enclosures. To facilitate insertion of cables into the entries, the built-in components can be snapped out of the enclosures. Notches in the mounting rails define the position of the built-in components and prevent them from being twisted out of place. Free mounting areas can be provided for retrofitting certified CEAG components. These are then factory sealed with blanking elements. Internationally approved.
High mechanical, chemical and thermal resistance Individual configuration Impact-resistant plastic powder coating
Ex-control stations
1 2
Measuring AM72 Type 413 85 Type 413 84
Technical data
Ex-Control stations Type 413 84 Type 413 85 Marking to 94/9/EC EC-Type Examination Certificate IECEx Certificate of conformity Marking accd. to IECEx Permissible ambient temperature Rated voltage Rated current Switch rating control switch GHG 23 Connecting terminals Insulation class Degree of protection accd. EN 60529 Cable glands/Gland plates/Enclosure drilling Enclosure material Enclosure colour Type 413 84 Dimensions (L x W x H) Weight (empty) Type 413 85 Dimensions (L x W x H) Weight (empty) 122 x 120 x 81 mm 1.45 kg 122 x 120 x 81 mm 0.85 kg II 2 G EEx e II T6 / EEx e ib IIC T6 / EEx ed IIC T6 / EEx ed ib IIC T6 II 2 D IP66 T 48 C / T 53 C PTB 00 ATEX 3117 IECEx BKI 04.0003 Ex e II T6, Ex e ib IIC T6, Ec ed IIC T6 or Ex ed ib IIC T6 20 C to +40 C 55 C to +55 C (option) 690 V AC (with control switch GHG 23 to 500 V) 35 A (with control switch GHG 23 max. 10 A) AC 15: 230 V/10 A / 500 V/6 A DC 13: 24 V/ 2 A / 230 V/0.4 A 2 x 4 mm2 I IP66 (standard) IP65 (measuring instrument AM45, double pushbutton) 1 x M20 threaded entry High quality cast aluminium-silicone (AISi) Grey RAL 7031
3 4 5 6 7 8
Moving coil II G EEx ib IIC Class 1.5 10-fold -5 sec.
Type 413 84 with measuring instrument AM 72 Moving iron Marking to 94/9/EC Accuracy Overload range II G EEx e II Class 2.5 10-fold -25 sec. 25-fold - 4 sec. 50-fold - 1 sec. indicated 1:1.5 Measuring range Li Ci Ui Ii Connecting terminals Weight
1)
9 10 11 12
9.21
Ex-control stations
Weight approx.
Order No.
14 22 13 21
1.25 kg
14 X1
22 X2
1 x signal lamp SIL 20-250 V AC/DC coloured lens cover: white, red, green, yellow 1 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 1 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 1 x mushroom-head pushbutton SGT 1 NO + 1 NC Emergency stop 1 x measuring instrument AM45 CT connection n/1A Scale 0 100%/150% 1 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 1.35 kg GHG 413 8400 R0004 1.30 kg GHG 413 8400 R0003 1.30 kg GHG 413 8400 R0002
13 I 0 14 13 I 0
21
22 21
14 22 13 21
14 1 13 I 0 14
22 2 21
22
9.22
Ex-control stations
1 2
Type 413 85...03 Type 413 85...02 Type 413 85...01
3
Order No.
Built-in components 1 x signal lamp SIL 20-250 V AC/DC coloured lens cover: white, red, green, yellow 2 x pushbutton DRT 1 NO + 1 NC label: 0, I, START, STOP 1 x mushroom-head pushbutton SGT 1 NO + 1 NC Emergency stop
Weight approx.
4
2.10 kg GHG 413 8500 R0001
14 22 13 21
14 22 13 21
5 6
14 X1 13 I 0 14 X1 13 I 0 14
22 X2 21
2 x signal lamp SIL 20-250 V AC/DC coloured lens cover: white, red, green, yellow 2 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 2.10 kg GHG 413 8500 R0002
22 X2 21
22
X1
X2
1 x signal lamp SIL 20-250 V AC/DC coloured lens cover: white, red, green, yellow label: I 0 II
7 8 9
2.20 kg GHG 413 8500 R0003
13 I 0
21
1 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 1 x mushroom-head pushbutton SGT 1 NO + 1 NC Emergency stop
13 23
14 22 13 21
14
I 0
22
II
()
14 24
10 11 12
COOPER CROUSE-HINDS GMBH
9.23
Ex-control stations
Measuring AM72
Version CT connection n/1A with 1 x threaded entry M20 01 0-5 / 1.5 A / 7.5 A
Z
GHG 413 8482 R0002 GHG 413 8482 R0003 GHG 413 8482 R0004 GHG 413 8482 R0005 GHG 413 8482 R0007 GHG 413 8482 R0008 GHG 413 8482 R0009 GHG 413 8482 R0010 GHG 413 8482 R0011 GHG 413 8482 R0012 GHG 413 8482 R0013 GHG 413 8482 R0014 GHG 413 8482 R0033
Dimension drawing
Z Z Z Z
122 X 106
81
220 X 204
122 X 106
X82 120 Z
90
20.8
Type 413 84
Type 413 84
Dimensions in mm COOPER CROUSE-HINDS GMBH
X = fixing dimension
Type 413 85
9.24
9.25
12
11
10
Stainless steel Ve r s i o n f o r Z o n e 1
CEAG explosion-protected control stations made of high-grade 316L stainless steel are designed to accommodate up to four built-in components. These stainless-steel control stations with electro-polished sur faces offer protection for applications in the off-shore industry and at sites
with especially severe mechanical, chemical and climatic conditions. CEAG flameproof built-in components, such as signal lamps, pushbuttons and switches, provide snap-on mounting on rails screwed into the enclosures. To facilitate insertion of cables into the entries, the built-in components can be snapped out of the enclosures. Notches in the mounting rails define the position of the built-in components and prevent them from being twisted out of place. Free mounting areas can be provided for retrofitting certified CEAG components. These are then factory sealed with blanking elements. Internationally approved.
High mechanical, chemical and thermal resistance Individual configuration Clean-room applications
Ex-control stations
1 2
Type 414 81.. Housing GHG 414 82 Housing GHG 414 81
Technical data
Ex-Control stations Type 414 81 Type 414 82 Marking to 94/9/EC EC-Type Examination Certificate IECEx Certificate of conformity Marking accd. to IECEx Permissible ambient temperature Rated voltage Rated current Switch rating control switch GHG 23 II 2 G EEx e II T6 / EEx e ib IIC T6 / EEx ed IIC T6 / EEx ed ib IIC T6 II 2 D IP66 T 48 C / T 53 C PTB 00 ATEX 3117 IECEx BKI 04.0003 Ex e II T6, Ex e ib IIC T6, Ec ed IIC T6 or Ex ed ib IIC T6 20 C to +40 C 55 C to +55 C (option) 690 V AC (with control switch GHG 23 to 500 V) 16 A (with control switch GHG 23 max. 10 A) AC 15: 230 V/10 A / 500 V/6 A DC 13: 24 V/ 2 A / 230 V/0.4 A with gold contact points max. 0.4 A Connecting terminals Insulation class Degree of protection accd. EN 60529 Cable glands/Gland plates/Enclosure drilling Enclosure material Type 414 81 Dimensions (L x W x H) Weight (empty) Type 414 82 Dimensions (L x W x H) Weight (empty) 286 x 140 x 76 mm 2.10 kg 166 x 140 x 76 mm 1.40 kg 2 x 4 mm2 I IP66 (standard) IP65 (measuring instrument AM45, double pushbutton) 1 x drilling 21 mm for cable gland M20 Stainless steel AISI 316 L
3 4 5 6 7 8
Moving coil II G EEx ib IIC Class 1.5 10-fold -5 sec.
Type 414 81 with measuring instrument AM 72 Moving iron Marking to 94/9/EC Accuracy Overload range II G EEx e II Class 2.5 10-fold -25 sec. 25-fold - 4 sec. 50-fold - 1 sec. indicated 1:1.5 Measuring range Li Ci Ui Ii Connecting terminals Weight
1)
9 10 11 12
9.27
Ex-control stations
Weight approx.
Order No.
14 22 13 21
1.80 kg
14 X1
22 X2
1 x signal lamp SIL 20-250 V AC/DC coloured lens cover: white, red, green, yellow 1 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 1 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 1 x mushroom-head pushbutton SGT 1 NO + 1 NC Emergency stop 1 x measuring instrument AM45 CT connection n/1A Scale 0 100%/150% 1 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 1.85 kg GHG 414 8100 R0004 1.85 kg GHG 414 8100 R0003 1.85 kg GHG 414 8100 R0002
13 I 0 14 13 I 0
21
22 21
14 22 13 21
14 1 13 I 0 14
22 2 21
22
9.28
Ex-control stations
1 2
Type 414 82...03 Type 414 82...02 Type 414 82...01
3
Order No.
Built-in components 1 x signal lamp SIL 20-250 V AC/DC coloured lens cover: white, red, green, yellow 2 x pushbutton DRT 1 NO + 1 NC label: 0, I, START, STOP 1 x mushroom-head pushbutton SGT 1 NO + 1 NC Emergency stop
Weight approx.
4
2.80 kg GHG 414 8200 R0001
14 22 13 21
14 22 13 21
5 6
14 X1 13 I 0 14 X1 13 I 0 14 X1
22 X2 21
2 x signal lamp SIL 20-250 V AC/DC coloured lens cover: white, red, green, yellow 2 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 2.80 kg GHG 414 8200 R0002
22 X2 21
22 X2
1 x signal lamp SIL 20-250 V AC/DC coloured lens cover: white, red, green, yellow
7 8
2.90 kg GHG 414 8200 R0003
13 I 0
21
1 x double pushbutton DDT 1 NO + 1 NC label: 0, I, START, STOP 1 x mushroom-head pushbutton SGT 1 NO + 1 NC Emergency stop
II 13 23
14 22 13 21
14
I
22
0
()
14 24
9 10 11 12
9.29
Ex-control stations
Version direct measurement with 1 x threaded entry 21 mm (without external fixing lugs) 0 - 2.5 / 3.75 A 0 - 10 / 15 A 0 - 16 / 24 A 0 - 20 / 4 - 20 / 24 mA 0-100% / 120% (Ri =320 ) 24 mA 0-100% / 120% (Ri =320 )
Version CT connection n/1A with 1 x threaded entry 21 mm (without external fixing lugs) 01 0-5 / 1.5 A / 7.5 A 1.25 kg 1.25 kg 1.25 kg 1.25 kg 1.25 kg 1.25 kg 1.25 kg 1.25 kg 1.25 kg 1.25 kg 1.25 kg 1.25 kg 1.25 kg GHG 414 8182 R0002 GHG 414 8182 R0003 GHG 414 8182 R0004 GHG 414 8182 R0005 GHG 414 8182 R0007 GHG 414 8182 R0008 GHG 414 8182 R0009 GHG 414 8182 R0010 GHG 414 8182 R0011 GHG 414 8182 R0012 GHG 414 8182 R0013 GHG 414 8182 R0014 GHG 414 8182 R0033 0 - 2.5 / 3.75 A 0 - 10 / 15 A 0 - 15 / 22.5 A 0 - 20 / 30 A 0 - 30 / 45 A 0 - 40 / 60 A 0 - 50 / 75 A 0 - 60 / 90 A 0 - 75 / 112.5 A 0 - 100 / 150 A 0 - 100% / 150%
Accessories
Dimension drawing
X214 166
X334 286
X214 166
59 76 88
Type 414 81
10 76 88
Dimensions in mm
59 76 88
9.30
9.31
12
11
10
T A T
CEAG control stations can be combined according to customers' specifications. Quick fixing allows up to three CEAG built-in components, such as signal lamps, pushbuttons and switches, to be snapped on a rail in the enclosure. The enclosures consist of low-temperature
impact-resistant thermoplastic which fulfils the requirements of EN 60079 and provides a high resistance to chemicals. The well thought out design with low side walls allows optimum cable connection. The components can be snapped out of the enclosure to facilitate cable-entry feeding. Notches in the mounting rails prevent the built-in components from being twisted out of place. CEAG's optional mounting plates offer a timesaving fixing technique. Coupling pieces link enclosures to each other and prevent them from being twisted out of place. Alternatively, metal screws and flanges can be used for mounting the metal flanges also enable external earthing. The built-in components differ in size. The diverse enclosure types allow variable combinations of these components. Example diagrams of the enclosure types show the placement options for the built-in components with numbers or predefined positions. Free mounting areas can be provided for retrofitting certified CEAG components. These are then factory sealed with blanking elements. Internationally approved.
Flat side walls Quick fixing for all built-in components High chemical resistance Different enclosures can be combined
I
Customised control stations, covered by type examination certificates, can be individually combined from CEAG's numerous built-in components. complete control station.
Ex-control stations
1 2
For the selection of control units and components, please A coding system for these components with unique designations can be used for planning, selection and see page 9.34 pp.
Pushbutton DRT
3 4 5
Measuring instrument AM72
6 7
Control switch SCT
8 9
Key-operated pushbutton SLT and keyoperated switch SLS Control switch GHG 23
10
Terminal block KLM Potentiometer POT
11 12
COOPER CROUSE-HINDS GMBH
9.33
Individual control units can be defined by 4 groups of components: 1. Empty Enclosure 2. Components per mounting area 3. Accessories 4. Cable glands
Code 2: Components per mounting area (max. 4) A C D(1) (D2) E F Mounting area 1 MA1 Mounting area 2 MA2 Mounting area 3 MA3 Mounting area 4 MA4
D(1)
(D2)
A 411 81
D(1)
(D2)
MA
2 1
A 411 82
D(1)
(D2)
MA
MA
3 2 1
411 83
2 1
MA
4 3 2 1
MA
434
Potentiometer POT
2 1
MA
Control switch Ex 23 Ex 29
MA
2 1 4 3 2 1
414 82
Measuring instrument AM 45 AM 72
MA
413 84
MA
413 85
9.34
I
Example: Enclosure Type 434, Pushbutton (MA4), Signal lamp (MA3) Emergency stop Mushroom head pushbutton (MA2) Double pushbutton (MA1) Code Code Code Code Code
1: 434.. 2 MA4: DRT 14 001 2 MA3: SIL 1 10 2 MA2 SGTE 13 1 1 2 2 MA1: DDT15 001 007
1 2 3 4 5 6
Code 3: Lables and locking facilities A B .............. A B .............. A B .............. A B .............. C C C C Mounting area 1 MA1 Mounting area 2 MA2 Mounting area 3 MA3 Mounting area 4 MA4
7
plastic trumpet-shaped cable gland TR
8 9
10 11
12
COOPER CROUSE-HINDS GMBH
9.35
Ex-control stations
Type 411 81
Type 411 82
Type 432
Type 434
Technical data
Ex-Control stations Type 41. and 43. for individual configuration Marking to 94/9/EC EC-Type Examination Certificate IECEx Certificate of conformity Marking accd. to IECEx Permissible ambient temperature Rated voltage Rated current Connecting terminals Insulation class Degree of protection accd. EN 60529 Cable glands/Gland plates/Enclosure drilling Enclosure material Enclosure colour Type 411 81 Cable glands/Gland plates/Enclosure drilling Dimensions (L x W x H) Weight (empty) Mounting arrangements Type 411 82 Cable glands/Gland plates/Enclosure drilling Dimensions (L x W x H) Weight (empty) Mounting arrangements Type 411 83 Cable glands/Gland plates/Enclosure drilling Dimensions (L x W x H) Weight (empty) Mounting arrangements Type 432 Cable glands/Gland plates/Enclosure drilling Dimensions (L x W x H) Weight (empty) Mounting arrangements Type 434 Cable glands/Gland plates/Enclosure drilling Dimensions (L x W x H) Weight (empty) Mounting arrangements 2 x M25 EEx-e cable gland for cables from 8 - 17 mm incl. 1 blanking plug or 2 x M20 thread 245 x 100 x 90 mm 0.70 kg 4 mounting areas 2 x M25 EEx-e cable gland for cables from 8 - 17 mm incl. 1 blanking plug or 2 x M20 thread 156 x 100 x 90 mm 0.47 kg 2 mounting areas 1 x M25 EEx-e cable gland for cables from 8 - 17 mm or 1 x M20 thread 165 x 85 x 77.5 mm 0.45 kg 3 mounting areas 1 x M25 EEx-e cable gland for cables from 8 - 17 mm or 1 x M20 thread 125 x 85 x 77.5 mm 0.35 kg 2 mounting areas 1 x M25 EEx-e cable gland for cables from 8 - 17 mm or 1 x M20 thread 85 x 85 x 77.5 mm 0.25 kg 1 mounting area II 2 G EEx e II T6 / EEx e ib IIC T6 / EEx ed IIC T6 / EEx ed ib IIC T6 II 2 D IP66 T 48 C PTB 00 ATEX 3117 IECEx BKI 04.0003 Ex e II T6, Ex e ib IIC T6, Ex ed IIC T6 or Ex ed ib IIC T6 20 C to +40 C 55 C to +55 C (option) 690 V AC 16 A 2 x 4 mm2 I IP66 (standard) IP65 (measuring instrument AM45, double pushbutton) 1 x M25 EEx-e cable gland for cables from 8 - 17 mm or 1 x M20 thread Polyamide black
9.36
Ex-control stations
1 2
Type 434 Type 432 Type 411 82 Type 411 81
3 4 5
Component Measuring instrument Measuring instrument Signal lamp Potentiometer Terminal block (4 mm2) Blanking element Code AM722) AM45 SIL POT KLM BLV
6 7 8 9 10 11 12
Mushroom-head pushbutton (2-pole or 4-pole)2) SGT 4-pole component not possible 2 mounting areas are needed only for type 43., 2 mounting areas are needed
9.37
Ex-control stations
Type 411 81
Type 411 82
Type 432
Type 434
Mounting areas
Dimension drawing
85 38 77.5 5 X52 X75 85 38
AM45
115 85 5.6
Type 411 81
22 77.5 5
2 1
AM45 AM72
155 125 40 X92 X75 85 38
5.6
Type 411 82
22 77.5 5
3 2 1
AM45 AM72
40 40 X132 X75 100 X88
AM72 EX23 2 Floors
2 1 1
195 165
5.6
Type 411 83
22 6 90
Type 432
100 X88
AM72 3 2 1 3 2 EX23 1 Floor EX23 2 Floors 3 2 1 AM72
156 X 97 5.2
AM45
90
245 X 186
EX23 2 Floors
5.2
Type 434
X = fixing dimension
9.38
Dimensions in mm
Ex-control stations
1 2
Type 414 82 Type 414 81 Type 413 85 Type 413 84
Technical data
Ex-Control stations Type 413. and 414. for individual configuration Marking to 94/9/EC EC-Type Examination Certificate IECEx Certificate of conformity Marking accd. to IECEx Permissible ambient temperature Rated voltage Rated current Connecting terminals PE-connection terminals Insulation class Degree of protection accd. EN 60529 II 2 G EEx e II T6 / EEx e ib IIC / EEx ed ib IIC T6 II 2 D IP66 T 48 C PTB 00 ATEX 3117 IECEx BKI 04.0003 Ex e II T6, Ex e ib IIC T6, Ex ed IIC T6 or Ex ed ib IIC T6 20 C to +40 C 55 C to +55 C (option) 690 V AC 16 A see technical data for built-in components 2 x 4 mm2 I IP66 (standard) IP65 (measuring instrument or double pushbutton) Type 413 84 Cable glands/Gland plates/Enclosure drilling Dimensions (L x W x H) Weight (empty) Enclosure material Enclosure colour Mounting arrangements Type 413 85 Cable glands/Gland plates/Enclosure drilling Dimensions (L x W x H) Weight (empty) Enclosure material Enclosure colour Mounting arrangements Type 414 81 Cable glands/Gland plates/Enclosure drilling Dimensions (L x W x H) Weight (empty) Enclosure material Enclosure colour Mounting arrangements Type 414 82 Cable glands/Gland plates/Enclosure drilling Dimensions (L x W x H) Weight (empty) Enclosure material Enclosure colour Mounting arrangements 1 x 21 mm for cable gland M20 286 x 140 x 76 mm 2.10 kg Stainless steel AISI 316 L polished 4 mounting areas 1 x 21 mm for cable gland M20 166 x 140 x 76 mm 1.40 kg Stainless steel AISI 316 L polished 2 mounting areas 1 x M20 thread 122 x 120 x 81 mm 1.45 kg cast aluminium-silicon (AISi) grey RAL 7031 4 mounting areas 1 x M20 thread 122 x 120 x 81 mm 0.85 kg cast aluminium-silicon (AISi) grey RAL 7031 2 mounting areas
3 4 5 6 7 8 9 10 11 12
COOPER CROUSE-HINDS GMBH
9.39
Ex-control stations
Type 413 84
Type 413 85
Type 414 81
Type 414 82
Component Measuring instrument Measuring instrument Signal lamp Potentiometer Terminal block (4 mm2) Blanking element
9.40
Ex-control stations
1
Z
2
Type 414 82 Type 414 81 Type 413 85 Type 413 84
Mounting areas
Dimension drawing
Z Z
3
Z 122 X 106 7 20.8
AM45 AM72
4 5 6
X82 120
81
Type 413 84
Z Z
4 3 2 1 AM45 AM72 3 2 1 2 1
220 X 204
X82 120
81
Type 413 85
Z Z
2 AM45 AM72
7 8
X214 166
59 76 88
Type 414 81
9 10
4 3 2 1
AM45 AM72 3 2 1 2 1
Type 414 82
Dimensions in mm
X334 286
11 12
X = fixing dimension
59 76 88
9.41
Ex-control stations
Type 444 23
Type 448 23
Type 449 23
Type 447 23
Technical data
Ex-Control stations Type 444, 448, 449, and 447 for individual configuration Marking to 94/9/EC EC-Type Examination Certificate IECEx Certificate of conformity Marking accd. to IECEx Permissible ambient temperature Rated voltage Rated current Connecting terminals PE-connection terminals Insulation class Degree of protection accd. EN 60529 Cable glands/Gland plates/Enclosure drilling Enclosure material Enclosure colour Type 444 23 Connecting terminals Dimensions (L x W x H) Weight (empty) Mounting arrangements Type 448 23 Connecting terminals Dimensions (L x W x H) Weight (empty) Mounting arrangements max. 30 terminals UT 4 271 x 271 x 136 mm 2.5 kg with mounting framework distance 40 mm distance 50 mm distance 60 mm Type 449 23 Connecting terminals Dimensions (L x W x H) Weight (empty) Mounting arrangements max. 60 terminals UT 4 544 x 271 x 136 mm 4.5 kg with mounting framework distance 40 mm distance 50 mm distance 60 mm Type 447 23 Connecting terminals Dimensions (L x W x H) Weight (empty) Mounting arrangements max. 90 terminals UT 4 817 x 271 x 136 mm 6.5 kg with mounting framework distance 40 mm distance 50 mm distance 60 mm max. 64 mounting areas max. 45 mounting areas max. 36 mounting areas max. 36 mounting areas max. 30 mounting areas max. 24 mounting areas max. 18 mounting areas max. 15 mounting areas max. 12 mounting areas max. 20 terminals UT 4 271 x 134 x 136 mm 1.5 kg with mounting framework 6 mounting areas II 2 G EEx e II T6 / EEx e ib IIC T6 / EEx ed ib IIC T6 II 2 D IP66 T 80 C/95 C PTB 99 ATEX 1044 IECEx BKI 07.0023 Ex de ia/ib m [ia/ib] IIC T4 .. T6 Ex tD A21 IP66 T80 C 20 C to +40 C 55 C to +55 C (option) 690 V AC 40 A see technical data for built-in components 2 x 4 mm2 I IP66 (standard) IP65 (measuring instrument or double pushbutton) as ordered accd. to manufacturers specification glass-fibre reinforced polyester black
9.42
Ex-control stations
1 2
Type 447 23 Type 449 23 Type 448 23 Type 444 23
3 4 5 6 7 8 9 10 11 12
Component Measuring instrument Measuring instrument Signal lamp Potentiometer Terminal block (4 mm2) Blanking element
9.43
Ex-control stations
Type 444 23
Type 448 23
Type 449 23
Type 447 23
Mounting areas
Dimension drawing
13
14
15
16
17
18
4 7 8 9 10 11 12
2 1 2 3 4 5 6
4 11 12 13 14 15
2 6 7 8 9 19
271 X 247
Z Z 7
136 116
Type 444 23
Type 448 23
271 X 247
X = fixing dimension
9.44
Dimensions in mm
Ex-control stations
1 2
Type 447 23 Type 449 23 Type 448 23 Type 444 23
Mounting areas
Dimension drawing
3
31 32 33 34 35 36 26 27 28 29 30 25 26 27 28 29 30 21 22 23 24 25 19 20 21 22 23 24 16 17 18 19 20
31
32
33
34
35
36
25
26
27
28
29
30
19
20
21
22
23
24
4 5 6 7 8 9
31
32
33
34
35
36
26
27
28
29
30
13
14
15
16
17
18
25 26 27 28 29 30 21 22 23 24 25
10
11
12
19
20
21
22
23
24
16
17
18
19
20
6
13 14 15 16 17 18 11 12 13 14 15
10
11
12
19
26
27
28
29
30
21
22
23
24
25
16
17
18
19
20
21
22
23
24
11
12
13
14
15
17
18
19
20
19
13
14
15
16
5
21 22 23 24
17
18
19
20
13
14
15
16
21
22
23
24
9 10 11 12
17
18
19
20
13
14
15
16
136 116
10
X 247 817 X 793
Dimensions in mm
544 X 520
11 12
Type 449 23
Type 447 23
X = fixing dimension
9.45
Ex-control stations
Type 443 34
Technical data
Ex-Control stations Type 443 34 for individual configuration Marking to 94/9/EC EC-Type Examination Certificate Permissible ambient temperature Rated voltage Rated current Connecting terminals PE-connection terminals Insulation class Degree of protection accd. EN 60529 Cable glands/Gland plates/Enclosure drilling Dimensions (L x W x H) Weight Enclosure material Enclosure colour Mounting arrangements II 2 G EEx e II T6 / EEx e ib IIC T6 / EEx ed IIC T6 / EEx ed ib IIC T6 II 2 D IP66 T 80 C/95 C PTB 01 ATEX 1115 20 C to +40 C 55 C to +55 C (option) 690 V AC 63 A as ordered accd. to manufacturers specification 2 x 4 mm2 I IP66 (standard) IP65 (measuring instrument or double pushbutton) as ordered accd. to manufacturers specification 280 x 180 x 90 mm 2.3 kg with mounting framework cast aluminium-silicon (AISi) grey RAL 7031 max. 9 mounting areas
Component Measuring instrument Measuring instrument Blanking element Control switch Control switch Terminal (4 mm ) Terminal block (4 mm )
2 2
Code AM721) AM45 BLV GHG 231) GHG 291) KLM ... A1) KLM ... B1)
Key-operated pushbutton (2-pole or 4-pole) SLT Mushroom-head pushbutton (2-pole or 4-pole) SGT
9.46
Ex-control stations
1 2
Type 443 34
Mounting areas
Dimension drawing
Z
3 4
260 X 240
5 6 7
X 110 160
90
Z 20,8
6,5
Type 443 34
X = fixing dimension
8 9 10
Dimensions in mm
11 12
9.47
Ex-control stations
Type 444 33
Type 448 33
Type 449 33
Type 447 33
Technical data
Ex-Control stations Type 444, 448, 449, and 447 stainless steel for individual configuration Marking to 94/9/EC EC-Type Examination Certificate IECEx Certificate of conformity Marking accd. to IECEx Permissible ambient temperature Rated voltage Rated current Connecting terminals PE-connection terminals Insulation class Degree of protection accd. EN 60529 Cable glands/Gland plates/Enclosure drilling Enclosure material Enclosure colour Type 444 33 Connecting terminals Dimensions (L x W x H) Weight (empty) Mounting arrangements Type 448 33 Connecting terminals Dimensions (L x W x H) Weight (empty) Mounting arrangements max. 30 terminals UT 4 312.5 x 312.5 x 135 mm 7.5 kg with mounting framework distance 40 mm distance 50 mm distance 60 mm Type 449 33 Connecting terminals Dimensions (L x W x H) Weight (empty) Mounting arrangements max. 60 terminals UT 4 627 x 312.5 x 135 mm 11.5 kg with mounting framework distance 40 mm distance 50 mm distance 60 mm Type 447 33 Connecting terminals Dimensions (L x W x H) Weight (empty) Mounting arrangements max. 90 terminals UT 4 941.5 x 312.5 x 135 mm 16.5 kg with mounting framework distance 40 mm distance 50 mm distance 60 mm max. 54 mounting areas max. 45 mounting areas max. 36 mounting areas max. 36 mounting areas max. 30 mounting areas max. 24 mounting areas max. 18 mounting areas max. 15 mounting areas max. 12 mounting areas max. 20 terminals UT 4 312.5 x 175 x 135 mm 3.5 kg with mounting framework 6 mounting areas II 2 G EEx e II T6 / EEx e ib IIC T6 / EEx ed IIC T6 / EEx ed ib IIC T6 II 2 D IP66 T 80 C/95 C PTB 99 ATEX 1044 IECEx BKI 07.0023 Ex de ia/ib m [ia/ib] IIC T4 .. T6 Ex tD A21 IP66 T80 C 20 C to +40 C 55 C to +55 C (option) 690 V AC 40 A see technical data for built-in components 2 x 4 mm2 I IP66 (standard) IP65 (measuring instrument or double pushbutton) as ordered accd. to manufacturers specification Stainless steel AISI 316 L polished
9.48
Ex-control stations
1 2
Type 447 33 Type 449 33 Type 448 33 Type 444 33
3 4 5 6 7 8 9 10 11 12
Component Measuring instrument Measuring instrument Blanking element Control switch Control switch Terminal (4 mm2) Terminal block (4 mm2)
Code AM721) AM45 BLV GHG 231) GHG 291) KLM ... A2) KLM ... B
Key-operated pushbutton (2-pole or 4-pole) SLT Mushroom-head pushbutton (2-pole or 4-pole) SGT
2 mounting areas are needed Terminal blocks and PE-terminals are attached to terminal rail under the fold-out mounting frame
9.49
Ex-control stations
Type 444 33
Type 448 33
Type 449 33
Type 447 33
Mounting area
Dimension drawing
13
14
15
16
17
18
4 7 8 9 10 11 12
2 1 2 3 4 5 6
4 11 12 13 14 15
2 6 7 8 9 19
10
11
12
Type 444 33
Type 448 33
X = fixing dimension
9.50
Dimensions in mm
Ex-control stations
1 2
Type 447 33 Type 449 33 Type 448 33 Type 444 33
Mounting area
Dimension drawing
3
31 32 33 34 35 36 26 27 28 29 30 25 26 27 28 29 30 21 22 23 24 25 19 20 21 22 23 24 16 17 18 19 20
31
32
33
34
35
36
25
26
27
28
29
30
19
20
21
22
23
24
31 32 33 34 35 36 26 27 28 29 30
4 5 6
13
14
15
16
17
18
25
26
27
28
29
30
21
22
23
24
25
19
20
21
22
23
24
16
17
18
19
20
10
11
12
13
14
15
16
17
18
11
12
13
14
15
10
11
12
19
26
27
28
29
30
21
22
23
24
25
16
17
18
19
20
17 18 19 20
13
14
15
16
11
12
13
14
15
21
22
23
24
19
17 18 19 20
7 8 9 10
Dimensions in mm
5
13 14 15 16
21
22
23
24
1 2 3 4
17
18
19
20
X362.5 312.5
9 10 11 12
151 135
X 362.5 312.5
151 135
627 X 561.5
941.5 X 876
11 12
Type 449 33
Type 447 33
X = fixing dimension
9.51
Built-in Components
DRT 1 x 2-pole
DRT 4 x 1-pole
DDT 2 x 1-pole
DDT 2 x 2-pole
Technical data
Ex-Pushbutton DRT and Double pushbutton DDT Marking to 94/9/EC EC-Type Examination Certificate Application temperature Rated voltage Rated current Rated current gold contacts Switch rating Degree of protection accd. EN 60529 Type of mounting Enclosure colour Gasket material 2-pole Version Connecting terminals Dimensions (L x W x H) Weight 4-pole Version Connecting terminals Dimensions (L x W x H) Weight
1)
II 2 G EEx ed IIC / PTB 97 ATEX 1081 U 20 C to +40 C 55 C to +55 C (option) 500 V AC 16 A 0.4 A
I M2 EEx de I
400 V / 16 A AC-1 / 400 V / 4 A AC-11 IP66 DIN rail mounting grey Neoprene (Standard), Fluoric Silicone or Viton on request
The 4-pole pushbutton needs two mounting areas of a 2-pole pushbutton. The actuator will be in the middle of the two mounting areas.
9.52
Built-in Components
1 2
DDT 2 x 2-pole DDT 2 x 1-pole DRT 4 x 1-pole DRT 1 x 2-pole
3
Code DRT DDT Code silver contact points gold contact points 13 16
4 5 6 7 8 9 10 11 12
2 NO
11 21 14 24
11 14
21 24
14
17
1 NO + 1 NC
13 23 14 22
13 14
23 22
15
18
4 NC
13 21 12 22 11 21
13 32 42 31 41 34 44 33 43 34 44 33 43 32 44 31 43 34 44 33 43
21 12 22 11 21 12 24 11 23 12 22 11 21 12 22 11 21 14 24 13 23 32 42 31 41 34 44 33 43 34 44 33 43 32 44 31 43 34 44 33 43
20
25
1 NC + 3 NO
12 24 11 23
21
26
2 NC + 2 NO
12 22 11 21 12 22 11 21
22
27
3 NC + 1 NO
23
28
4 NO
14 24 13 23
24
29
9.53
Built-in Components
DRT 1 x 2-pole
DRT 4 x 1-pole
DDT 2 x 1-pole
DDT 2 x 2-pole
9.54
Built-in Components
1 2
DDT 2 x 2-pole DDT 2 x 1-pole DRT 4 x 1-pole DRT 1 x 2-pole
3 4 5 6 7 8 9 10 11 12
Double pushbutton with gold contact points Version with standard label (0, I, START, STOP) 2 NC 2 NO 1 NO + 1 NC 4 NC 3 NO + 1 NC 2 NO + 2 NC 1 NC + 3 NO 4 NO 2 NC 2 NO 1 NO + 1 NC 4 NC 3 NO + 1 NC 2 NO + 2 NC 1 NC + 3 NO 4 NO 16 17 18 20 21 22 23 24 DDT DDT DDT DRT DRT DRT DRT DRT 0 0 0 0 0 0 0 0 16 17 18 20 21 22 23 24 001 001 001 001 001 001 001 001 001 001 001 -----------
9.55
Built-in Components
SLT 1 x 2-pole
SLT 1 x 4-pole
Technical data
Ex-Key operated pushbutton SLT Marking to 94/9/EC EC-Type Examination Certificate Application temperature Rated voltage Rated current Rated current gold contacts Switch rating Degree of protection accd. EN 60529 Type of mounting Enclosure colour Gasket material Latch point 2-pole Version Connecting terminals Dimensions (L x W x H) Weight 4-pole Version Connecting terminals Dimensions (L x W x H) Weight
1)
II 2 G EEx ed IIC / M 2 EEx de PTB 97 ATEX 1081 U 20 C to +40 C 55 C to +55 C (option) 500 V AC 16 A 0.4 A 400 V / 16 A AC-1 / 400 V / 4 A AC-11 IP66 DIN rail mounting grey Neoprene (Standard), Fluoric Silicone or Viton on request CEAG 1 (others on request)
The 4-pole pushbutton needs two mounting areas of a 2-pole pushbutton. The actuator will be in the middle of the two mounting areas.
Key switch with gold contact points Version with contact function: lockable/removeable/lockable/removable (code 10) 2 NO + 2 NC 4 NC 4 NO 3 NO + 1 NC 1 NO + 3 NC 2 NO + 2 NC 4 NC 4 NO 3 NO + 1 NC 1 NO + 3 NC 27 25 29 26 28 SLT SLT SLT SLT SLT 0 0 0 0 0 22 20 24 21 23 10 10 10 10 10
9.56
Built-in Components
1 2
SLT 1 x 4-pole SLT 1 x 2-pole
3
Code SLT Code silver contact points gold contact points 13 16
4 5
2 NO
12 22 13 23
14
17
1 NO + 1 NC
14 13
24 21
15
18
4 NO
()
14 22 14 24 13 23
34 44 33 43 34 44 33 43 34 44 33 43 32 44 31 43 32 42 31 41
20
25
6
21 26 22 27
1 NC + 3 NO
()
12 24 11 23 12 22 () 11 21
2 NC + 2 NO
7
23 28 24 29
3 NC + 1 NO
()
12 22 11 21
4 NC
()
12 22 11 21
8
Key removable removable removable not removable not removable removable Pushbutton pressed lockable lockable not lockable lockable lockable auto lockable Key removable not removable not removable removable removable removable Code 10 11 12 13 14 15
Code D
Function
Pushbutton not pressed lockable lockable lockable lockable not lockable not lockable
9 10 11 12
9.57
Built-in Components
SLT 1 x 2-pole
SLT 1 x 4-pole
Technical data
Ex-built-in Components for individual control stations Key switch SLS Marking to 94/9/EC EC-Type Examination Certificate Application temperature Rated voltage Rated current Rated current gold contacts Switch rating Switching system Degree of protection accd. EN 60529 Type of mounting Enclosure colour Latch point 2-pole Version Connecting terminals Dimensions (L x W x H) Weight 4-pole Version Connecting terminals Dimensions (L x W x H) Weight
1)
II 2 G EEx ed IIC / M 2 EEx de PTB 97 ATEX 1081 U 20 C to +40 C 55 C to +55 C (option) 500 V AC 16 A 0.4 A 400 V / 16 A AC-1 / 400 V / 4 A AC-11 engaging engaging engaging IP54 DIN rail mounting grey CEAG 1 (others on request)
The 4-pole pushbutton needs two mounting areas of a 2-pole pushbutton. The actuator will be in the middle of the two mounting areas.
9.58
Built-in Components
1 2
SLT 1 x 4-pole SLT 1 x 2-pole
3
Code SLS 5 Code silver contact points gold contact points
Contacts
I 0 II 13/23
4 5
04
14
2 NO
()
II
05
15
45 90 135
14
24
2 NO
()
13
23
33
43
24
34
2 NO
()
4590135 14 24 34 43 13 21 33 41
23
33
2 NO
()
34 42 33/43
6
25 35 Code 01
14 24
34 44
Code D
Contact lable
7 8
02 03
9 10 11 12
Switch can be locked in all positions and key can be removed in all positions
9.59
Built-in Components
SGTE 1 x 2-pole
SGTE 1 x 4-pole
SGT 1 x 2-pole
SGT 1 x 4-pole
Technical data
Ex-Mushroom Head Pushbutton (Emergency Stop SGTE and Normal Version SGT) Marking to 94/9/EC EC-Type Examination Certificate Application temperature Rated voltage Rated current Rated current gold contacts Switch rating Degree of protection accd. EN 60529 Type of mounting Enclosure colour Gasket material 2-pole Version Connecting terminals Dimensions (L x W x H) Weight 4-pole Version Connecting terminals Dimensions (L x W x H) Weight
1)
II 2 G EEx ed IIC / M 2 EEx de PTB 97 ATEX 1081 U 20 C to +40 C 55 C to +55 C (option) 500 V AC 16 A 0.4 A 400 V / 16 A AC-1 / 400 V / 4 A AC-11 IP66 DIN rail mounting grey Neoprene (Standard), Fluoric Silicone or Viton on request
The 4-pole pushbutton needs two mounting areas of a 2-pole pushbutton. The actuator will be in the middle of the two mounting areas. The pushbutton Emergency Stop will be equipped with a black plate in the centre of the pushbutton actuator.
9.60
Built-in Components
1 2
SGT 1 x 4-pole SGT 1 x 2-pole SGTE 1 x 4-pole SGTE 1 x 2-pole
3
Code SGT SGTE Code silver contact points gold contact points 13 16
4 5 6 7 8 9 10 11 12
2 NO
12 22 13 23
14
17
1 NO + 1 NC
14 13
24 21
15
18
4 NC
14 22 14 24 13 23
34 44 33 43 34 44 33 43 34 44 33 43 32 44 31 43 32 42 31 41
20
25
3 NO + 1 NC
12 24 11 23
21
26
2 NO + 2 NC
12 22 11 21
22
27
1 NO + 3 NC
12 22 11 21
23
28
4 NO
12 22 11 21
24
29
9.61
Built-in Components
SGTE 1 x 2-pole
SGTE 1 x 4-pole
SGT 1 x 2-pole
SGT 1 x 4-pole
Code 1 4 001 002 003 004 005 006 007 009 010 012 014 015 020 024 025 026 027 028 030 031 Code 1 2 3 engaged not lockable lockable lockable unlocking n/a (pushbutton function) hand released key released Code 12) 2 3
9.62
Built-in Components
1 2
SGT 1 x 4-pole SGT 1 x 2-pole SGTE 1 x 4-pole SGTE 1 x 2-pole
3 4 5 6 7 8 9 10 11 12
EMERGENCY STOP mushroom-head pushbutton red, with silver contact points Version with inscription D/E, hand released 2 NC 2 NO 1 NO + 1 NC 2 NO + 2 NC 4 NC 4 NO 3 NO + 1 NC 1 NO + 3 NC SGTE 0 SGTE 0 SGTE 0 SGTE 0 SGTE 0 SGTE 0 SGTE 0 SGTE 0 13 14 15 22 20 24 21 23 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2
Mushroom-head pushbutton with silver contact points, without locking, mushroom head, black Version with standard label (0, I, START, STOP) 2 NC 2 NO 1 NO + 1 NC 2 NO + 2 NC 4 NC 4 NO 3 NO + 1 NC 1 NO + 3 NC SGT 0 SGT 0 SGT 0 SGT 0 SGT 0 SGT 0 SGT 0 SGT 0 13 14 15 27 25 29 26 28 01 01 01 01 01 01 01 01 3 3 3 3 3 3 3 3 1 1 1 1 1 1 1 1
9.63
Built-in Components
SCT 1 x 2-pole
SCT 1 x 4-pole
Technical data
Ex-Mini-control switch SCT Marking to 94/9/EC EC-Type Examination Certificate Application temperature Rated voltage Rated current Rated current gold contacts Switch rating Degree of protection accd. EN 60529 Type of mounting Enclosure colour 2-pole Version Connecting terminals Dimensions in mm (L x W x H) Weight 4-pole Version Connecting terminals Dimensions (L x W x H) Weight
1)
II 2 G EEx ed IIC / M 2 EEx de PTB 97 ATEX 1081 U 20 C to +40 C 55 C to +55 C (option) 500 V AC 16 A 0.4 A 400 V / 16 A AC-1 / 400 V / 4 A AC-11 IP66 DIN rail mounting grey
The 4-pole pushbutton needs two mounting areas of a 2-pole pushbutton. The actuator will be in the middle of the two mounting areas.
9.64
Built-in Components
1 2
SCT 1 x 4-pole SCT 1 x 2-pole
3
Code SCT Code 4 5
4 5 6 7 8 9 10 11 12
engaging engaging
90O
6 7
45O 45O
9.65
Built-in Components
SCT 1 x 2-pole
SCT 1 x 4-pole
45 135
13 21 14 22
22 14 13 21
02
12
45 135
14 22 13 23
03
13
45 135
14 24 13/23
04
14
14 24 13 23
45 90 135
14 24 13 23
05
15
07
17
34 44
22
32
33 43 34 44
23
33
33 43 32 42
21
31
31 41 34 44
26
36
45 135
11 23 13 23
33 43 33 43
25
35
4590 135
14 24 34 43 13 21 33 41 27
37
4590 135
14 22 13/23
34 42 33/43
24
34
4590 135
14 24
34 44
9.66
Built-in Components
1 2
SCT 1 x 4-pole SCT 1 x 2-pole
3 4 5 6
7 8 9 10 11 12
9.67
Built-in Components
Potentiometer
Technical data
Ex-Potentiometer POT Marking to 94/9/EC EC-Type Examination Certificate Application temperature Rated voltage Power consumption Resistance range Tolerance Connecting terminals Degree of protection accd. EN 60529 Dimensions (L x W x H) Weight Type of mounting Enclosure colour Angle of rotation Scale II 2 G EEx ed IIC / M 2 EEx de PTB 97 ATEX 1081 U 20 C to +40 C 55 C to +55 C (option) up to 250 V max. 1 W 100 10000 Ohm 20 % 2 x 2.5 mm2 IP66 approx. 59 x 31 x 45 mm 0.15 kg DIN rail mounting grey 270 0 - 100 %
9.68
Built-in Components
1 2
Signal lamp
Technical data
Ex-Signal lamp SIL Marking to 94/9/EC EC-Type Examination Certificate Application temperature Rated voltage (EEx ed IIC) (EEx d ia IIC) (EEx ed IIC) Rated current (20 V to 250 V) (10 V to 28 V EEx d ia IIC) 12 V to 30 V Connecting terminals Degree of protection accd. EN 60529 Dimensions (L x W x H) Weight Type of mounting Enclosure colour II 2 G EEx ed IIC / PTB 98 ATEX 1040 U 20 C to +40 C 55 C to +55 C (option) 20 V to 250 V AC/DC 10 V to 28 V DC 12 V to 30 V AC/DC approx. 4 - 15 mA max. 25 mA max. 24 mA 2 x 2.5 mm IP66 approx. 59 x 31 x 45 mm 0.15 kg DIN rail mounting grey
2
3
II 2 G EEx d ia IIC
4 5 6
Code SIL Code 1 2 3 4 5 Code 10 34 11
7 8 9 10
11 12
9.69
Built-in Components
AM 45
AM 75
Technical data
Ex-Measuring instrument AM 45/AM 75 moving iron Marking to 94/9/EC EC-Type Examination Certificate Application temperature Rated voltage Power consumption Overload range II 2 G EEx e IIC / I M 2 EEx e I PTB 99 ATEX 2032 U 20 C to +40 C 55 C to +58 C (option) up to 420 V (AM 45) up to 750 V (AM 72) max. 0.31 A 10 fold - 25 sec. 25 fold - 4 sec. 50 fold - 1 sec. indicated 1 : 1.5 Measuring range Inductance Li Capacitance Ci Winding specification of moving coil Internal resistance Open circuit voltage max. Ui Short circuit current max. li Accuracy Circuit Connecting terminals Degree of protection accd. EN 60529 Display size Weight Type of mounting Enclosure material Class 2.5 moving iron 2 x 1.5 - 4 mm2 IP 65 50 x 45 mm (AM 45) 72 x 72 mm (AM 72) 0.35 kg DIN rail mounting grey max. 0 - 25 A direct / n / 1A 0/4 - 24 mA < 0.1 mH y 0.1 nF 26.5 windings 2.5 30 % 30 V 150 mA Class 1.5 moving coil 10 fold - 5 sec. moving coil II 2 G EEx ib IIC / I M 2 EEx ib I
9.70
Built-in Components
1 2
AM 72 AM 45
3
Code AM 45 AM 72 Code 1 2 5 6 7 8
4 5 6 7 8
Code 02 03 04 05 06 08 09 10 11 12
Measuring range 0 - 75 / 112.5 A 0 - 100 / 150 A 0 - 150 / 225 A 0 - 200 / 300 A 0 - 250 / 375 A 0 - 300 / 450 A 0 - 400 / 600 A 0 - 500 / 750 A 0 - 600 / 900 A 0 100% / 150%
Code 13 14 15 16 17 18 19 20 21 33
Movements 0 - 20 mA / 4 - 20 mA and with moving-coil connection are only available with scale 0 - 100 %/120 % Version for direct connection (standard: CT connection n/1A) possible Moving coil only for Ex-i of Ex-d flameproof applications
9 10 11 12
Moving-coil measuring instrument AM 45 (Ex-i application only) Version with dircet connection 0 - 20 / 24 mA 4 - 20 / 24 mA 0-100% / 120% 0-100% / 120% AM45 AM45 7 8 33 33
9.71
Built-in Components
Ex 23
Ex 29
Technical data
Ex-built-in Components for individual control stations Control switch Ex 23 and Ex 29 Ex 23 Marking to 94/9/EC EC-Type Examination Certificate Application temperature Rated voltage Rated current Rated current gold contacts Switch rating Connecting terminals Weight 1 tier: 2 tiers: 3 tiers: Type of mounting Enclosure colour
1)
Ex 29 PTB 98 ATEX 1118 U 20 C to +40 C 55 C to +55 C (option) up to 500 V 16 A1) 0.4 A 400 V/4 A 230 V/0.5 A 2 x 0.5 - 2.5 mm2 or 1 x 1.0 - 6.0 mm2 approx. 0.25 kg approx. 0.40 kg approx. 0.55 kg
II 2 G EEx ed IIC / I M 2 EEx e I PTB 98 ATEX 1116 U 20 C to +40 C 55 C to +45 C (option) 10 A AC 15: 230 V/6 A 2 x 0.5 - 2.5 mm2 approx. 0.2 kg approx. 0.35 kg DIN rail mounting grey black
DC 13: 24 V/2 A
9.72
Built-in Components
1 2
Ex 29 Ex 23
3
Code Ex 23 Ex 29 Code 4 5 6 7 8
4 5 6 7
45O
45O
90O
45O
45O
45O
45O
Code
45 90 135 45 90 135 45 90 135 45 90 135 1 3 5
060
3
45 135 I II
2 4 6 1 3 5
45 90 135 0 I
2 1
6 3 5
45 135
45 135 0 I
2 1
4 3
2 4 6 1 3 5
45 90 135 0 I
2 1
4 3 5
45 135
45 135 I 0 II
4 1/3 2 4
2 4 6 1 3 5
45 90 135 I II III
2 1
4 3
6 5
023 019
2 4 1 3
45 90 135 I 0 II 1
2 4 6 1 3 5 2 4 6 1 3 5 7 2 4 68 1 3 5 7
45 90 135 0 I 1
2 3
4 5
2 4 1 3
45 90 135 0 I
4 1 3
45 135
45 135 I II
4 1/3
6 5/7
2 4 1 2
45 90 135 0 I 1
45 135
033
5/7
4
45 90 135
45 135 I 0 II
2 4 6 8 1/3
45 135
024
45 135
2 4 68
45 90 135
2 4 6 8
Versions with gold contact points are available on request. Versions with compulsory NO are possible. Code E Contact lable Inscription 0 I STOP HAND SENKEN REMOTE I AUS AUS AUF Entriegelt OUT LOCAL STOP HAND AUF For further labels, please see page XXX Code F Locking facility None Centre Left Right Code 0 1 2 3 0 BETRIEB 0 0 0 OF REMOTE 0 0 AUS I II START AUTO HEBEN LOCAL II EIN EIN AB Verriegelt HAND AUTO START AUTO ZU Code 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 Inscription 0 AUS AUS RTLICH START OFF HAND 0 MAN START HEBEN OFF AUS HAND ON I II I AUTO HAND AUS NORMAL 0 OFF IN II EIN AUTO FERN STOP ON AUTO START AUTO STOP SENKEN ON EIN AUTO OFF III Code 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
8 9 10 11 12
9.73
Built-in Components
Ex 23
Ex 29
Contact C 6 5 6 6
45 135 1 3 2 4 1 3 5
Label D
I II 2 I 1/3
060 I - II
1 3 5
45 135 0
45O
45O
45 90 135
2 4 6 1 3 2 4 1 3 2 4
45 90 135 I II 2 1 1/3
90O
45 135
45 135 I II
4 3
90O
45 135
065 0 - I
45 135
9.74
Built-in Components
1 2
UT4 PE UT4 MKX 4
Technical data
Ex-built-in Components for individual control stations Te r m i n a l s MXK 4-Ex Marking to 94/9/EC EC-Type Examination Certificate Application temperature Rated voltage Rated current Connecting terminals II 2 G EEx e II PTB 99 ATEX 3132U 50 C to +55 C up to 420 V max. 27 A 4 mm2 4 mm Dimensions (L x B x H) Weight Type of mounting Enclosure colour NS 35 DIN rail mounted grey
2
3
UT 4 / UT 4 PE II 2 G EEx e II / 2 D EEx e II KEMA 04 ATEX 2048 U 50 C to +55 C up to 690 V max. 30 A 0.14 mm2 - 4 mm2 multi-wire 0.14 mm2 - 6 mm2 single-wire 0.14 mm2 - 4 mm2 multi-wire 0.14 mm - 6 mm single-wire 6.2 mm width 47.7 mm x 6.2 mm 0.01 kg NS 35 DIN rail mounted grey
2 2
4 5 6 7 8 9 10 11 12
9.75
Built-in Components
MKX 4
UT4
UT4 PE
9.76
Built-in Components
1 2
ZUB 17 ZUB 14 ZUB 23 ZUB 20
3 4 5 6 7 8 9 10 11 12
Code C
Mounting area
Code 1 ... 4
Code A
Locking facility with flap (blank) with flap (red) with flap without 0 activation with flap with 0 activation with flap (blank) with flap (red) with bolt and chain Fire alarm (red) with hammer Fire alarm (red) with hammer with flap, not activated with flap, activated with flap, not activated with flap, activated
for operating element Pushbutton Pushbutton Double pushbutton Double pushbutton Mushroom-head pushbutton Mushroom-head pushbutton Mushroom-head pushbutton Mushroom-head pushbutton* activates alarm when broken* Pushbutton Pushbutton Mushroom-head pushbutton Mushroom-head pushbutton
Material Stainless steel Stainless steel Stainless steel Stainless steel Stainless steel Stainless steel Stainless steel Stainless steel Stainless steel Plastic Plastic Plastic Plastic
Code ZUB 12 ZUB 13 ZUB 16 ZUB 17 ZUB 02 ZUB 01 ZUB 14 ZUB 15 ZUB 05 ZUB 23 ZUB 24 ZUB 22 ZUB 21
9.77
Built-in Components
Cable gland GK
Trumpet-shaped gland TR
Thread plug SV
*For metal glands, the type of cable/entry must be stated in plain language in the order. Other versions on request.
9.78
9.79
12
11
10
E X - C O N T R O L
For panel mounting
A N D
S I G N A L
U N I T S
CEAG control and indicating elements can be integrated in panels with a wall thick ness of up to 5 mm. The CEAG components for panel mounting, such as signal lamps, pushbuttons and switches, can be instantly plugged into the
control and indicating elements on the panel via bayonet-ring fitting. The single-wire instal lation is clear and simple. All panel-mounted apparatus can be retrofitted for cable con nection with a slip-on strain relief and protective cover and is then completely certified. Planning and procurement of panelmounted apparatus with different cable lengths is a thing of the past. The completely certified measuring instruments for direct and indirect measurement are available for different amperage ranges. The instruments are equipped with a transformer for easy adaptation to other ranges on the interchangeable scales.
Bayonet-ring catch for quick one-hand mounting Complete certification of built-in apparatus Connection terminals for variable, low-cost wiring Standard actuator-element size of 30.5 mm
1 2
Double-Pushbutton Pushbutton
Technical data
Ex-Control and signal units for panel mounting Pushbutton Type 418 811 and Double pushbutton Type 418 814 Marking to 94/9/EC EC-Type Examination Certificate Permissible ambient temperature Rated voltage Rated current Rated current gold contacts Switch rating Connecting terminals Degree of protection accd. EN 60529 Dimensions (L x W x H) Weight Type of mounting Enclosure colour Gasket material
1)
3
II 2 G EEx ed IIC T6 / I M 2 EEx e I II 2 G Ex ed IIC T6 / I M 2 Ex e l PTB 97 ATEX 1081 U PTB 99 ATEX 10341) 20 C to +40 C 55 C to +55 C (option) 500 V AC 16 A 0.4 A AC 15 DC 13 250 V/6 A 24 V/6 A 2 x 2.5 mm2 IP661) approx. 59 x 31 x 45 mm 0.20 kg 30.5 mm fixing hole grey Neoprene (Standard), Fluoric silicone or viton on request 500 V/4 A 60 V/0.8 A 110 V/0.5 A
4 5 6 7 8 9 10 11 12
9.81
Pushbutton
Double-Pushbutton
Code B
Contact system 2 NC
2 NO
12 22 13 23
1 NO + 1 NC
14 13
24 21
14
22
Code C1, C2
Label
Inscription 0, I, Start, Stop I START LANGSAM EMERG.STOP MARCHE AB Neutral green UP ZU OFF Neutral yellow AUS AUTO HAND HEBEN RECHTS SLOW OPEN
Code 01 03 05 07 09 11 13 15 17 19 24 26 28 31 34 37 39 50 52 54 56 58
Inscription 0 II STOP NOT-AUS SCHNELL ARRET AUF Neutral whtie 0, I, Arret, Marche DOWN ON + Neutral red EIN Neutral black Neutral blue SENKEN LINKS FAST RESET
Code 02 04 06 08 10 12 14 16 18 20 25 27 30 33 36 38 40 51 53 55 57
9.82
1 2
Double-Pushbutton Pushbutton
3 4 5 6 7 8 9 10 11 12
Double-pushbutton without protective cover, with gold contact points 2 NC 2 NO 1 NO + 1 NC (0, I, START, STOP) (0, I, START, STOP) (0, I, START, STOP) GHG 418 814 GHG 418 814 GHG 418 814 6 7 8 R01 R01 R01 01 01 01
Accessories
Type Protective cover to meet IP66 Please note that we can only deliver in the ordering units (OU) stated in the tables above
OU 5
9.83
Pushbutton
Double-Pushbutton
Dimension drawing
68
57
5 14 77 38
(Double-)pushbutton without protective cover
126
38
57
10 140
(Double-)pushbutton with protective cover
3.1+0.1 65
31.5 +0.2
40
Minimum distances
30.3 +0.2
9.84
Dimensions in mm
1 2
Key operated pushbutton
Technical data
Ex-Control and signal units for panel mounting Key operated pushbutton Type 418 812 Marking to 94/9/EC EC-Type Examination Certificate Permissible ambient temperature Rated voltage Rated current Rated current gold contacts Switch rating Connecting terminals Degree of protection accd. EN 60529 Dimensions (L x W x H) Weight Type of mounting Enclosure colour Gasket material Latch point
1)
3
II 2 G Ex ed IIC T6/ I M 2 Ex e I PTB 97 ATEX 1081 U PTB 99 ATEX 10341) 20 C to +40 C 55 C to +55 C (option) 500 V AC 16 A 0.4 A AC 15 DC 13 250 V/6 A 24 V/6 A 2 x 2.5 mm2 IP661) approx. 59 x 31 x 45 mm 0.15 kg 30.5 mm fixing hole grey Neoprene (Standard), Fluoric silicone or viton on request CEAG 1 (others on request) 500 V/4 A 60 V/0.8 A 110 V/0.5 A
4 5 6 7 8 9 10 11 12
9.85
Component Key operated pushbutton Contact system 2 NC Code silver contact points 3
2 NO
12 22 13 23
1 NO + 1 NC
14 24 13 21
14
22
Code C
Function
Pushbutton not pressed lockable lockable lockable lockable not lockable not lockable
pushbutton pressed lockable lockable not lockable lockable lockable auto lockable
Code 10 11 12 13 14 15
Key switch with gold contact points, without protective cover 1 NO + 1 NC 2 NC 2 NO lockable Key removable lockable Key removable lockable Key removable lockable Key removable lockable Key removable not lockable Key not removable GHG 418 812 7 R00 12 GHG 418 812 6 R00 11 GHG 418 812 8 R00 10
Accessories
Type Protective cover to meet IP66 Please note that we can only deliver in the ordering units (OU) stated in the tables above
OU 5
9.86
1 2
Key operated pushbutton
Dimension drawing
3
57
4
38
56 5 77
Key switch without protective cover
5 6 7
57
126
3.1+0.1 65
10
31.5 +0.2
8 9 10
Dimensions in mm
40
Minimum distances
30.3 +0.2
11 12
9.87
Key-operated pushbutton
Technical data
Ex-Control and signal units for panel mounting Key operated switch Type 418 8195 Marking to 94/9/EC EC-Type Examination Certificate Permissible ambient temperature Rated voltage Rated current Rated current gold contacts Switch rating Connecting terminals Switching system Dimensions (L x W x H) Weight Type of mounting Enclosure colour Latch point
1)
II 2 G Ex ed IIC T6/ I M 2 Ex e I PTB 97 ATEX 1081 U PTB 99 ATEX 10341) 20 C to +40 C 55 C to +55 C (option) 500 V AC 16 A 0.4 A AC 15 DC 13 250 V/6 A 24 V/6 A 2 x 2.5 mm2 engaging - engaging - engaging approx. 59 x 31 x 45 mm 0.15 kg 30.5 mm fixing hole grey CEAG 1 (others on request) 500 V/4 A 60 V/0.8 A 110 V/0.5 A
9.88
1 2
Key-operated pushbutton
3 4 5 6 7
2 NO
()
II
45 90 135
14
24
Code C
Code 07 08 09
Contact system
13/23 14 24 13 23
Label
Order No. A C R5 R5 R5 R5 R5 R5 4 4 4 5 5 5 D 07 08 09 07 08 09
GHG 418 8195 GHG 418 8195 GHG 418 8195 GHG 418 8195 GHG 418 8195 GHG 418 8195
()
45 90 135 I 0 II
8 9
Switch can be locked in all positions and key can be removed in all positions Key switch with gold contacts, without protective cover 4 4 4 5 5 5 I 0 II FERN 0 ORT HAND 0 AUTO I 0 II FERN 0 ORT HAND 0 AUTO GHG 418 8195 GHG 418 8195 GHG 418 8195 GHG 418 8195 GHG 418 8195 GHG 418 8195 R5 R5 R5 R5 R5 R5 7 7 7 8 8 8 07 08 09 07 08 09
10 11 12
Accessories
Type Protective cover to meet IP66 Please note that we can only deliver in the ordering units (OU) stated in the tables above
OU 5
9.89
Key-operated pushbutton
Dimension drawing
57 62 5 77
Key switch without protective cover
38
126
3.1+0.1 65
31.5 +0.2
40
Minimum distances
30.3 +0.2
10
57
9.90
Dimensions in mm
1 2
Mushroom-h.p.-button Mushroom-h.p.-button
Technical data
Ex-Control and signal units for panel mounting Mushroom head pushbutton (Emergency stop and normal version) Marking to 94/9/EC EC-Type Examination Certificate Permissible ambient temperature Rated voltage Rated current Rated current gold contacts Switch rating Connecting terminals Dimensions (L x W x H) Weight Type of mounting Enclosure colour Gasket material
1)
3
II 2 G EEx ed IIC T6/ I M 2 EEx e I PTB 97 ATEX 1081 U PTB 99 ATEX 10341) 20 C to +40 C 55 C to +55 C (option) 500 V AC 16 A 0.4 A 400 V/16 A AC-1 400 V/ 4 A AC-11 2 x 2.5 mm2 approx. 59 x 31 x 45 mm 0.15 kg 30.5 mm fixing hole grey Neoprene (Standard), fluoric silicone or viton on request
4 5 6 7 8 9 10 11 12
9.91
Mushroom-h.p.-button
Mushroom-h.p.-button
Component Mushroom head pushbutton Contact system 2 NO Code silver contact points 3
key released
11 21
2 NC
12 22 13 23
12 22 13 23
1 NO + 1 NC
14 24 13 21
14 13
24 21
14
22
14
22
Code C
Mushroom head insription and color NOT-AUS EMERGENCY STOP (German - English)1) NOT-AUS ARRET DURGENCE (German - French)1) Red Yellow1) Black2)
Code 1 4 1 2 3
Code D
Function
Code E
Label
1) 2)
only Emergency stop mushroom head pushbutton only Mushroom head pushbutton normal version
9.92
1 2
Mushroom-h.p.-button Mushroom-h.p.-button
3 4 5 6 7 8 9 10 11 12
EMERGENCY STOP mushroom-head pushbutton red, with silver ocntact points, without protective cover
Version with inscription D/E, key released 2 NC 2 NC 2 NO 2 NO 1 NO + 1 NC 1 NO + 1 NC red red red red red red German/English German/French German/English German/French German/English German/French GHG 418 815 GHG 418 815 GHG 418 815 GHG 418 815 GHG 418 815 GHG 418 815 3 3 4 4 5 5 R1 R4 R1 R4 R1 R4 3 3 3 3 3 3 00 00 00 00 00 00
Mushroom-head pushbutton, with silver ocntact points, without protective cover Version with inscription D/E, pushbutton function only 2 NC 2 NC 2 NO 2 NO 1 NO + 1 NC 1 NO + 1 NC black yellow black yellow black yellow 0, I, START, STOP 0, I, START, STOP 0, I, START, STOP 0, I, START, STOP 0, I, START, STOP 0, I, START, STOP GHG 418 815 GHG 418 815 GHG 418 815 GHG 418 815 GHG 418 815 GHG 418 815 3 3 4 4 5 5 R3 R2 R3 R2 R3 R2 1 1 1 1 1 1 01 01 01 01 01 01
Accessories
Type Protective cover to meet IP66 Please note that we can only deliver in the ordering units (OU) stated in the tables above
OU 5
9.93
Mushroom-h.p.-button
Mushroom-h.p.-button
Dimension drawing
57 56 5 77 38
57 30 5 77
38
126
57 30
Mushroom-head pushbutton with protective cover
10
3.1+0.1 65
31.5 +0.2
40
Minimum distances
30.3 +0.2
9.94
Dimensions in mm
1 2
Mini-control switch
Technical data
Ex-Control and signal units for panel mounting Mini-Control switch Type 418 8190 Marking to 94/9/EC EC-Type Examination Certificate Permissible ambient temperature Rated voltage Rated current Rated current gold contacts Switch rating Connecting terminals Dimensions (L x W x H) Weight Type of mounting Enclosure colour
1)
3
II 2 G Ex ed IIC T6/ I M 2 Ex e I PTB 97 ATEX 1081 U PTB 99 ATEX 10341) 20 C to +40 C 55 C to +55 C (option) 500 V AC 16 A 0.4 A AC 15 DC 13 250 V/6 A 24 V/6 A 2 x 2.5 mm2 approx. 59 x 31 x 45 mm 0.15 kg 30.5 mm fixing hole grey 500 V/4 A 60 V/0.8 A 110 V/0.5 A
4 5 6 7 8 9 10 11 12
9.95
Mini-control switch
Component Mini-Control Switch Switch mechanism spring - engaging - engaging engaging - engaging - engaging engaging - engaging spring - engaging - engaging engaging - engaging - spring
4 5 6 7 8 Code 0 1
45O
45O
90O
45O
45O
45O
45O
Code C
Code D
Contact system
Contacts
45 135 13 21 14 22
Code
21/13
0 1 2
45 135
22 14 13 21
45 135
14 22 13 23
45 135
14 24 13/23
3
23
14 24 13 23
45 90 135
14 24 13
45 90 135
5 7
14 24
45 90 135
14
24
13 21 45 90 135 14 22
13 21 45 90 135
14
22
Code E
Contact lable
Inscription 0 I STOP HAND SENKEN REMOTE I AUS AUS AUF STOP 0 BETRIEB 0 0 0 I II START AUTO HEBEN LOCAL II EIN EIN AB START
Code 01 02 03 04 05 06 07 08 09 10 14
Inscription HAND AUF HAND 0 AUS AUS RTLICH START OFF HAND 0 0 AUS AUS I AUTO HAND AUS NORMAL 0 OFF IN AUTO ZU AUTO II EIN AUTO FERN STOP ON AUTO START
Code 15 16 17 18 19 20 21 22 23 24 25
9.96
1 2
Mini-control switch
3
B C D
21/13 45 135
4
0 2 1 I 0 I I I 0 II I II 0 0 I II II GHG 418 8190 R GHG 418 8190 R GHG 418 8190 R GHG 418 8190 R GHG 418 8190 R GHG 418 8190 R 6 6 6 5 5 8 0 2 1 3 5 7 02 01 02 07 07 01
90O
22 14 13 23
90O
45 135
14 24 13 21
90O
45 135
14 22 13/23
5 6 7 8
45O
45O
14 24 13 23
45 90 135
14 24 13 23
3 5 7
45 90 135
45O
45O
14 24
45 90 135
14
24
45O
45O
13 21 45 90 135 14 22
13 21 45 90 135
14
22
Accessories
Type Protective cover to meet IP66 Please note that we can only deliver in the ordering units (OU) stated in the tables above
OU 5
Dimension drawing
150
57
57
57
24 5 77
Mini-control switch without protective cover
9
10 24 5
38
57
3.1+0.1 65
10
31.5 +0.2
Dimensions in mm
40
Minimum distances
30.3 +0.2
11 12
9.97
Technical data
Ex-Control and signal units for panel mounting Control switch GHG 249 Marking to 94/9/EC EC-Type Examination Certificate Permissible ambient temperature Rated voltage Rated current Rated current gold contacts Switch rating AC 1 AC 3 AC 11 DC 11 Connecting terminals Weight Type of mounting Enclosure colour
1)
II 2 G Ex ed IIC T6/ I M 2 Ex e I PTB 98 ATEX 1117 U1) 20 C to +40 C 55 C to +45 C (option) up to 690 V AC up to 20 A up to 0.4 A 690 V/20 A 400 V/20 A / 500 V/16 A 230 V/ 8 A / 500 V/ 6 A 24 V/ 6 A / 230 V/0.4 A 2 x 2.5 mm2 multi wire, 6 mm2 single wire 0.55 kg 30.5 mm fixing hole grey
9.98
1 2
Control switch GHG 249
3 4 5 6 7 8
Code I AUTO HAND AUS NORMAL 0 OFF IN II EIN AUTO FERN STOP ON AUTO START AUTO STOP SENKEN ON EIN AUTO OFF II III 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
Component Control switch GHG 249 Switch mechanism spring - engaging - spring engaging - engaging - engaging engaging - engaging spring - engaging - engaging engaging - engaging - spring
45O
45O
90O
45O
45O
45O
45O
Code C
Contact system
Contacts
1 3 5 2 4 6 1 3 5 7 2 4 68 1 3 5 7
45 135
019
5/7
45 135 I II
4 1/3
45 135
033
5/7
45 135 I 0 II
2 4 6 8 1/3
45 90 135
2 4 68 1 3 5
45 90 135 0 I 1
2 4 6 8 3 5
45 90 135
2 4 6 1 3 5
45 90 135 0 I
2 1
6 3 5
45 90 135
2 4 6 1 3 5
45 90 135 0 I
2 1
6 3 5
45 90 135
2 4 6
45 90 135 I II
4 1/3
6 5/7
45 135
1 3 5 7 9 11 2 4 6 8 1012 1 3 5 7 9 11
039 038
45 135 I 0 II
45 90 135
2 4 6 8 1012
45 90 135
2 4 6 8 10 12
Code D
Contact lable
Inscription 0 I STOP HAND SENKEN REMOTE I AUS AUS AUF Entriegelt OUT LOCAL STOP HAND AUF I II START AUTO HEBEN LOCAL 0 BETRIEB 0 0 0 OF REMOTE 0 0 AUS II EIN EIN AB Verriegelt HAND AUTO START AUTO ZU
Code 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16
Inscription 0 AUS AUS RTLICH START OFF HAND 0 MAN START HEBEN OFF AUS HAND ON
9 10 11 12
1)
9.99
Switching mechanism B
Code
Contact C
Code
Label D
Code
Order No.
6 6
90O
45 135
1 3 5 2 4 6 1 3 5
019
3 5
0I STOP - 0 - START I - II
01 14 02
GHG 249 0004 R0058 GHG 249 0004 R0039 GHG 249 0004 R0084
45 135 0 I
2 1
45 90 135 45 135
037 033
2 4 6 1 3 5 7 2 4 68
45 90 135 I II
2 1/3
4 5/7
45 135
2 4 6 8
Dimension drawing
20
50
72 85 6 54 30
71
34 26
30
Diagram
9.100
Dimensions in mm
1 2
Potentiometer
Technical data
Ex-Control and signal units for panel mounting Potentiometer Type 418 8131 Marking to 94/9/EC EC-Type Examination Certificate Permissible ambient temperature Rated voltage Power consumption Resistance range Tolerance Connecting terminals Dimensions (L x W x H) Weight Type of mounting Enclosure colour Angle of rotation Scale
1)
3
II 2 G Ex ed IIC T6/ I M 2 Ex e I PTB 97 ATEX 1081 U PTB 99 ATEX 10341) 20 C to +40 C 55 C to +55 C (option) up to 250 V AC max. 1 W 100 - 10000 20 % 2 x 2.5 mm 0.15 kg 30.5 mm fixing hole grey 270 0 - 100 %
2
4 5 6 7 8 9 10 11 12
approx. 59 x 31 x 45 mm
9.101
Potentiometer
Accessories
Type Protective cover to meet IP66 Please note that we can only deliver in the ordering units (OU) stated in the tables above
OU 5
Dimension drawing
126
57 57 24 5 77
Potentiometer without protective cover
65 3.1+0.1
31.5 +0.2
40
30.3 +0.2
Minimum distances
9.102
Dimensions in mm
38
10
1 2
Signal lamp
Technical data
Ex-Control and signal units for panel mounting Signal lamp Type 418 8170 Marking to 94/9/EC EC-Type Examination Certificate Permissible ambient temperature Rated voltage (Ex ed IIC) (Ex d ia IIC) (Ex ed IIC) Rated current (20 V to 250 V) (10 V to 28 V Ex d ia IIC) (12 V to 30 V) Connecting terminals Dimensions (L x W x H) Weight Type of mounting Enclosure colour
1)
3
II 2 G Ex ed IIC / II 2 G Ex d ia IIC PTB 98 ATEX 1040 U PTB 99 ATEX 10341) 20 C to +40 C 55 C to +55 C (option) 20 V to 250 V AC/DC 10 V to 28 V DC 12 V to 30 V AC/DC approx. 4 - 15 mA max. 25 mA max. 24 mA 2 x 2.5 mm2 approx. 59 x 31 x 45 mm 0.15 kg 30.5 mm fixing hole grey
4 5 6 7 8 9 10 11 12
9.103
Signal lamp
Accessories
Type Protective cover to meet IP66 Please note that we can only deliver in the ordering units (OU) stated in the tables above
OU 5
Dimension drawing
126
57 57 21 5 77
Signal lamp without protective cover
38
Signal lamp with protective cover
10
3.1+0.1 65
40
Minimum distances
30.3 +0.2
9.104
Dimensions in mm
31.5 +0.2
1 2
Interchangeable scales Measuring instrument
Technical data
Type 413 84 with measuring instrument AM 72 Moving iron Marking to 94/9/EC EC-Type Examination Certificate Permissible ambient temperature Rated voltage Power consumption Overload range II G Ex e II / I M 2 Ex e I PTB 00 ATEX 3117 20 C to +40 C 55 C to +55 C (option) up to 690 V max. 0.31 VA 10 fold - 25 sec. 25 fold - 4 sec. 50 fold - 1 sec. indicated 1 : 1.5 Measuring range Inductance Li Capacitance Ci Winding specification of moving coil Internal resistance Open circuit voltage max. Ui Short circuit current max. li Accuracy Connecting terminals Degree of protection accd. EN 60529 Cable glands/Gland plates/Enclosure drilling Dimensions (L x W x H) Display size AM 72 Weight Type of mounting Enclosure colour Class 2.5 2 x 1.5 - 4 mm2 IP66 1 x M25 ( 8 - 17 mm) 160 x 95 x 62 mm 72 x 72 mm 0.8 kg DIN rail mounting grey max. 0 - 25 A direct / n / 1A 0/4 - 24 mA < 0.1 mH < 0.1 nF 26.5 windings 2.5 30 % 30 V 150 mA Class 1.5 10-fold - 5 sec. Moving coil II G Ex ib IIC / I M 2 Ex ib I
3 4 5 6 7 8 9 10 11 12
COOPER CROUSE-HINDS GMBH
9.105
Measuring instrument
Interchangeable scales
Component Measuring instrumtent AM 72 Movement Direct connection Ct connection 1 /A Port 0 - 20/24 mA (scale 0-100% / 120%) 1) Port 4 - 20/24 mA (scale 0-100% / 120%) 1) Moving-coil connection 0 - 20/24 mA (scale 0-100% / 120%) 1) Moving-coil connection 4 - 20/24 mA (scale 0-100% / 120%) 1)
7 8 Measuring range/scale 0 - 75 /112.5 A 0 - 100 / 150 A 0 - 150 / 225 A 0 - 200 / 300 A 0 - 250 / 375 A 0 - 300 / 450 A 0 - 400 / 600 A 0 - 500 / 750 A 0 - 600 / 900 A 0 - 100% / 150% Code C 013 014 015 016 017 018 019 020 021 033
Code
Code C 002 003 004 005 006 008 009 010 011 012
1) 2) 3)
Movements 0 - 20 mA/ 4 - 20 mA and with moving-coil connection are only available with scale 0 - 100%/ 120%. Version for direct connection (standard: CT connection n/1A) possible. Moving coil only for Ex-i of Ex-d flameproof applications
9.106
1 2
Interchangeable scales Measuring instrument
3 4 5 6 7 8 9 10
73
Dimensions in mm
Dimension drawing
95
26
160 173
73
147
11 12
22 62
9.107
1 2
Cooper Crouse-Hinds 2008 - all rights reserved
Accessories
3 4 5 6 7 8 9 10 11 12
Interchangeable AM72
Ordering details
Interchangeable scales for measuring instrument , CT connection n/1A for AM 45/AM 72 Scale 0 - 1 / 1.5 A 0 - 2.5 / 3.75 A 0 - 5 / 7.5 A 0 - 10 / 15 A 0 - 15 / 22.5 A 0 - 20 / 30 A 0 - 25 / 37.5 A 0 - 30 / 45 A 0 - 40 / 60 A 0 - 50 / 75 A 0 - 60 / 90 A 0 - 75 /112.5 A 0 - 100 / 150 A 0 - 150 / 225 A 0 - 200 / 300 A 0 - 250 / 375 A 0 - 300 / 450 A 0 - 400 / 600 A 0 - 500 / 750 A 0 - 600 / 900 A 0 100% / 150% Special scales available on request. Package unit 10 pieces 10 pieces 10 pieces 10 pieces 10 pieces 10 pieces 10 pieces 10 pieces 10 pieces 10 pieces 10 pieces 10 pieces 10 pieces 10 pieces 10 pieces 10 pieces 10 pieces 10 pieces 10 pieces 10 pieces 10 pieces Order No. AM45 GHG 410 1926 R0001 GHG 410 1926 R0002 GHG 410 1926 R0003 GHG 410 1926 R0004 GHG 410 1926 R0005 GHG 410 1926 R0006 GHG 410 1926 R0021 GHG 410 1926 R0007 GHG 410 1926 R0008 GHG 410 1926 R0009 GHG 410 1926 R0010 GHG 410 1926 R0011 GHG 410 1926 R0012 GHG 410 1926 R0013 GHG 410 1926 R0014 GHG 410 1926 R0015 GHG 410 1926 R0016 GHG 410 1926 R0017 GHG 410 1926 R0018 GHG 410 1926 R0019 GHG 410 1926 R0020 Order No. AM72 GHG 410 1928 R0001 GHG 410 1928 R0002 GHG 410 1928 R0003 GHG 410 1928 R0004 GHG 410 1928 R0005 GHG 410 1928 R0006 GHG 410 1928 R0021 GHG 410 1928 R0007 GHG 410 1928 R0008 GHG 410 1928 R0009 GHG 410 1928 R0010 GHG 410 1928 R0011 GHG 410 1928 R0012 GHG 410 1928 R0013 GHG 410 1928 R0014 GHG 410 1928 R0015 GHG 410 1928 R0016 GHG 410 1928 R0017 GHG 410 1928 R0018 GHG 410 1928 R0019 GHG 410 1928 R0051
9.108
Accessories
1 2
Labels
Ordering code
Labels for pushbuttons Inscription 0, I, Start, Stop I D START LANGSAM EMERG.STOP ARRET AUF Neutral whtie 0, I, Arret, Marche DOWN ON + Neutral red EIN AUTO SENKEN LINKS FAST RESET HALT VOR FIRE ALARM REVERSE HIGH LP LQ SPERREN ENTRIEGELN Further labels are available on request. Code 001 003 005 007 009 011 014 016 018 020 025 027 030 033 036 039 051 053 055 057 069 073 094 096 101 151 157 163 165 Inscription 0 II STOP NOT-AUS SCHNELL _ MARCHE AB Neutral green UP ZU OFF Neutral yellow AUS HAND HEBEN RECHTS SLOW OPEN III ZURCK FORWARD RUN LOW HQ STR. QUITT ENTSPERREN VERRIEGELN Code 002 004 006 008 010 012 015 017 019 024 026 028 031 034 037 050 052 054 056 058 070 074 095 100 102 152 162 164 166
3 4 5 6 7 8 9 10 11 12
COOPER CROUSE-HINDS GMBH
9.109
Accessories
Plastic flap
Combination piec
Contacts label
Ordering code
Locking facilities Version with flap (blank) with flap (red) with bolt and chain (blank) Fire alarm (red)* Fire alarm (red) with plastic flap with plastic flap with plastic flap with plastic flap with plastic flap with flap (blank) with flap (red) with flap without 0-activation (blank) with flap with 0-activation (blank) with bracket (1 Set) Pushbutton Pushbutton Double pushbutton Double pushbutton Switch GHG 23/28 Operating element Mushroom-head pushbutton Mushroom-head pushbutton Mushroom-head pushbutton Mushroom-head pushbutton Mushroom-head pushbutton Mushroom-head pusbutton activated Mushroom-head pushbutton non-activated Pushbutton activated Pushbutton non-activated Emergency Stop 1 11 1 11 5 OU 1 1 1 1 11 Order No. GHG 410 1901 R0124 GHG 410 1901 R0125 GHG 410 1901 R0126 GHG 410 1901 R0128 GHG 410 1901 R0141 GHG 410 1994 R0001 GHG 410 1994 R0002 GHG 410 1994 R0003 GHG 410 1994 R0004 GHG 410 1994 R0005 GHG 410 1901 R0132 GHG 410 1901 R0133 GHG 410 1901 R0134 GHG 410 1901 R0135 GHG 440 1917 R0001
* released when window is broken select appropriate activation element. Please note that we can only deliver in the ordering units (OU) stated in the tables above. Labels and fools for control switches Unit Label with label holder Combination piece for Control station Typ 411 Mounting and dismantling tool for lock nuts on operating elements Blanking element for control units Protective cap Spanner incl. seal and lock nut for panel-mounted operating elements 1 piece 10 pieces 5 pieces GHG 410 1914 R0001 GHG 410 1920 R0001 GHG 410 1939 R0002 incl. twist protection and seal 1 piece GHG 410 1921 R0001 Version Blank (can be engraved) OU 10 pieces Order No. GHG 410 1953 R0001
Please note that we can only deliver in the ordering units (OU) stated in the tables above.
9.110
9.111
12
11
10
The new GHG 29 control switch series features an easy-to-install and easy-to-connect design. This control switch can be implemented with up to 6 contacts and for 2 to 5 switch positions. Thus, practically all applications in modern control engineering can be covered. Contacts
are protected against contact to VBG 4 and have a terminal cross section of up to 6 mm 2 for the connection of single and multi-wire conductors. The rated current of the control switch at 500 V is 16 A. The external contours of the enclosure facilitate access to the connection terminals and thus allow easy installation. Further installation advantages result from the snap-on/snap-off switch contact block and measuring instrument. A labyrinth seal in the cover guarantees the degree of protection IP66. The impact-resistant, glass-fibre-reinforced polyester enclosure material is a prerequisite for withstanding even the most rugged industrial operating conditions. The switch can be padlocked using the inte grated locking facility. The locking position is indicated by a red pin. An interchangeable apparatus label and a neutral switch-position label are supplied with each switch. With CEAG installation system, control switches can be installed with high cost-efficiency. The control switches are also available on request with snap-on metal or moulded-plastic flanges.
Decisive cost saving with the CEAG mounting system Easily accessible connection terminals Degree of protection IP66 Cable connection range up to 6 mm 2 Integrated locking facility Optional forced contact on request
Ex-Control switches
1 2
GHG 293 GHG 292
Technical data
Ex-Control switch Type 292 without and Type 293 with measuring instrument with GHG 29 Marking to 94/9/EC EC-Type Examination Certificate IECEx Certificate of Conformity Marking accord. to IECEx Permissible ambient temperature Rated voltage Rated current Rated current gold contacts Overload range (Type 293 only) II G EEx ed ia IIC T5/T6 / PTB 99 ATEX 1163 IECEx BKI 07.0011 Ex ed ia IIC T5 or T6 Ex tD A21 IP66 T49 C 20 C to +40 C 55 C to +47 C (T6) ... +55 C (T5) option max. 500 V 16 A 0.4 A 10 fold - 25 sec. 25 fold - 4 sec. 50 fold - 1 sec. indicated 1 : 1.5 Measuring range (Type 293 only) Accuracy (Type 293 only) Circuit (Type 293 only) Switch rating AC 3 Switch rating DC 13 Connecting terminals Degree of protection accd. EN 60529 Cable glands/Gland plates/Enclosure drilling Dimensions (L x W x H) Weight max. 0 - 25 A direct / n / 1A Class 2.5 moving iron 500 V/10 A 690 V/10 A 500 V/16 A 400 V/20 A 24 V/6 A / 60 V/0.8 A / 110 V/0.5 A / 230 V/0.3 A 2 x 0.5 - 2.5 mm2 or 1 x 1.0 - 6.0 mm2 IP66 1 x M25 ( 8 - 17 mm)* 170 x 110 x 129 mm approx. 1.10 kg (1 level) approx. 1.25 kg (2 level) approx. 1.40 kg (3 level) Enclosure material Enclosure colour glass-fibre-reinforced polyester black 225 x 110 x 129 mm approx. 1.90 kg (1 level) approx. 2.05 kg (2 level) approx. 2.20 kg (3 level) max. 690 V 20 A with GHG 28 II D IP66 T 49 C
3 4 5 6 7 8 9 10 11 12
COOPER CROUSE-HINDS GMBH
* Brass flange for metal entries available on request (except for II D at date of publication).
9.113
Ex-Control switches
GHG 292
GHG 293
Code B1
Switch mechanism spring - engaging - spring engaging - engaging - engaging engaging - engaging spring - engaging - engaging engaging - engaging - spring
4 5 6 7 8
45O
45O
90O
45O
45O
45
45
Code B2
Contact
45 135 1 3 2 4 1 3 2 4 1 3 2 4 1 3
Code
45 90 135 45 90 135 45 90 135 45 90 135 1 3 5
060
3
45 135 I II
2 4 6 1 3 5
45 90 135 0 I
2 1
6 3 5
45 135
45 135 0 I
2 1
4 3
2 4 6 1 3 5
45 90 135 0 I
2 1
4 3 5
45 135
45 135 I 0 II
4 1/3 2 4
2 4 6 1 3 5
45 90 135 I II III
2 1
4 3
6 5
023 019
2 4 1 3
45 90 135 I 0 II 1
2 4 6 1 3 5 2 4 6 1 3 5 7 2 4 68 1 3 5 7
45 90 135 0 I 1
2 3
4 5
2 4 1 3
45 90 135 0 I
4 1 3
45 135
45 135 I II
4 1/3
6 5/7
2 4 1 2
45 90 135 0 I 1
45 135
033
5/7
4
45 90 135
45 135 I 0 II
2 4 6 8 1/3
45 135
024
45 135
2 4 68
45 90 135
2 4 6 8
Other versions as well as gold contact points are available on request. Code C Contact lable Inscription 0 I STOP HAND SENKEN REMOTE I AUS AUS AUF Entriegelt OUT LOCAL STOP HAND AUF HAND 0 BETRIEB 0 0 0 OF REMOTE 0 0 AUS AUS I II START AUTO HEBEN LOCAL II EIN EIN AB Verriegelt HAND AUTO START AUTO ZU AUTO Code 001 002 003 004 005 006 007 008 009 010 011 012 013 014 015 016 017 Inscription 0 AUS AUS RTLICH START OFF HAND 0 MAN START HEBEN OFF AUS HAND ON I II I AUTO HAND AUS NORMAL 0 OFF IN II EIN AUTO FERN STOP ON AUTO START AUTO STOP SENKEN ON EIN AUTO OFF III Code 018 019 020 021 022 023 024 025 026 027 028 029 030 031 032 033
9.114
Ex-Control switches
1 2
GHG 293 GHG 292
3 4 5 6 7 8 9 10 11 12
Code F1
Buil-in components designation Entry type Entry direct in enclosure Entry via plastic flange Entry via metal flange GEH FLK FLM BO SV GK GM* GV M1 .. ..
F2
Entry element
only threaded entry Threaded plug Cable entry moulded plastic Cable entry metal* Cable entry with plug
F3 F4
1)
Size Number
9.115
Ex-Control switches
GHG 292
GHG 293
GHG 295 / 5 /
Ordering details
Switching mechanism Contact system Code Label inscription Order No.
Control switch Type 294 with silver contacts Version with locking facility in 0-, or position right (Code 3), cable entry 1 x M25 on bottom. 6 6 4 8 4 8 5 5
45 135 1 3 2 4 1 3 2 4 1 3
0 0 0 0 0 0 I
I I I I I I 0 II
GHG 292 1000 R0001 GHG 292 1000 R0002 GHG 292 1000 R0003 GHG 292 1000 R0004 GHG 292 2000 R0002 GHG 292 2000 R0003 GHG 292 2000 R0004 GHG 292 2001 R0001
45 135 0 I
2 1
4 3
45 135
45 135 0 I
4 1 3
2 4 1 3
45 90 135 0 I
1 3
2 4 1 3 5
45 90 135 0 I
2 1
2 4 6 1 3 5
45 90 135 0 I 1
6 3 5
2 4 6 1 3 5 7
45 90 135 I 0 II
1 3 5 7
2 4 6 8
45 90 135
2/4
6/8
Switching mechanism
Contact system
Code
Label inscription
Order No.
Control switch with measuring instrument Type 295 with silver contacts Version with locking facility in 0-, or left position, Measuring instrument AM 72 for CT connection n/1A, Scale 0 - 100/150 %. 1 x M32 on bottom. 6 6
45 135 1 3 2 4 1 3 2 4
062 065
0 0
I I
45 135 0 I
2 1
4 3
45 135
45 135
9.116
Ex-Control switches
1 2
GHG 293 GHG 292
Ordering details
Measuring range Measuring instrument AM 72, direct measurement Version with 1 x cable entry M25 0 1 /1.5 A 0 - 2.5 / 3.75 A 0 - 5 / 7.5 A 0 - 10 / 15 A 0 - 16 / 24 A 0 - 20 / 24 mA 0-100% / 120% (Ri = 320 ) 4 - 20 / 24 mA 0-100% / 120% (Ri = 320 ) Measuring instrument AM 72, Ct connection n/1A Version with 1 x cable entry M25 0 1 / 1.5 A 0 - 2.5 / 3.75 A 0 - 5 / 7.5 A 0 - 10 / 15 A 0 - 15 / 22.5 A 0 - 20 / 30 A 0 - 30 / 45 A 0 - 40 / 60 A 0 - 50 / 75 A 0 - 60 / 90 A 0 - 75 / 112.5 A 0 - 100 / 150 A 0 - 150 / 225 A 0 - 200 / 300 A 0 - 250 / 375 A 0 - 300 / 450 A 0 - 400 / 600 A 0 - 500 / 750 A 0 - 600 / 900 A 0 - 100% / 150% GHG 412 8282 R0002 GHG 412 8282 R0003 GHG 412 8282 R0004 GHG 412 8282 R0005 GHG 412 8282 R0006 GHG 412 8282 R0008 GHG 412 8282 R0009 GHG 412 8282 R0010 GHG 412 8282 R0011 GHG 412 8282 R0012 GHG 412 8282 R0013 GHG 412 8282 R0014 GHG 412 8282 R0015 GHG 412 8282 R0016 GHG 412 8282 R0017 GHG 412 8282 R0018 GHG 412 8282 R0019 GHG 412 8282 R0020 GHG 412 8282 R0021 GHG 412 8282 R0031 GHG 412 8281 R0002 GHG 412 8281 R0003 GHG 412 8281 R0004 GHG 412 8281 R0005 GHG 412 8281 R0007 GHG 412 8285 R0033 GHG 412 8286 R0035 Order No.
3 4 5 6 7 8 9 10 11 12
COOPER CROUSE-HINDS GMBH
9.117
Ex-Control switches
GHG 292
GHG 293
Accessories
Mounting plate for type 292 Type Size 2 Size 2 Size 2 Size 4 Size 4 Size 4 Application Wall mounting Pipe mounting Trellis-work mounting Wall mounting Trellis-work mounting Pipe mounting Mounting technique snap-on snap-on snap-on snap-on * snap-on * snap-on * OU 1 1 1 1 1 1 Order No. GHG 610 1953 R0104 GHG 610 1953 R0105 GHG 610 1953 R0106 GHG 610 1953 R0128 GHG 610 1953 R0128 GHG 610 1953 R0132
Mounting plate for type 293 Type Size 3 Size 3 Size 3 Size 5 Size 5 Size 5 Application Wall mounting Pipe mounting Trellis-work mounting Wall mounting Trellis-work mounting Pipe mounting Mounting technique snap-on snap-on snap-on snap-on * snap-on * snap-on * OU 1 1 1 1 1 1 10 Order No. GHG 610 1953 R0118 GHG 610 1953 R0110 GHG 610 1953 R0118 GHG 610 1953 R0128 GHG 610 1953 R0128 GHG 610 1953 R0132 GHG 610 1953 R0041
Snap-on mounting for CEAG apparatus with 5.5 mm and 11 mm mounting size per 4 pieces *snap-on with snap-on mounting 5.5 mm
9.118
9.119
12
11
10
E X - C O N T R O L
Light alloy Ve r s i o n f o r Z o n e 1
S W I T C H E S
CEAG explosion-protected control switch es are made of high-quality cast aluminium-silicon (AlSi). A robust plastic powder coating according to RAL 7031 protects the CEAG control switches against aggressive atmospheres and chemicals. Cover screws as well as all internal and external
metal parts are made of stainless steel. These switches feature an easy-to-install and easy-to-connect design. The cam switch version allows implementation of many variants, covering almost all applications in modern control engineering. An optional locking facility allows to secure the switch against unauthorised or inadvertent actuation with a padlock. Internationally approved.
High mechanical, chemical and thermal resistance Impact-resistant plastic powder coating Snap-on switch holder
Ex-Control switches
1 2
GHG 295 GHG 294
Technical data
Ex-Control switch Type 294 without and Type 295 with measuring instrument with GHG 29 Marking to 94/9/EC EC-Type Examination Certificate IECEx Certificate of Conformity Marking accord. to IECEx Permissible ambient temperature Rated voltage Rated current Rated current gold contacts Overload range (Type 293 only) II G EEx ed ia IIC T5/T6 / PTB 99 ATEX 1163 IECEx BKI 07.0011 Ex ed ia IIC T5 or T6 Ex tD A21 IP66 T49 C 20 C to +40 C 55 C to +47 C (T6) ... +55 C (T5) option max. 500 V 16 A 0.4 A 10 fold - 25 sec. 25 fold - 4 sec. 50 fold - 1 sec. indicated 1 : 1.5 Measuring range (Type 293 only) Accuracy (Type 293 only) Circuit (Type 293 only) Switch rating AC 3 Switch rating DC 13 Connecting terminals Degree of protection accd. EN 60529 Cable glands/Gland plates/Enclosure drilling Dimensions (L x W x H) Weight Enclosure material Enclosure colour as well as M32 and M25 cable entries. max. 0 - 25 A direct / n / 1A Class 2.5 moving iron 500 V/10 A 690 V/10 A 500 V/16 A 400 V/20 A 24 V/6 A / 60 V/0.8 A / 110 V/0.5 A / 230 V/0.3 A 2 x 0.5 - 2.5 mm2 or 1 x 1.0 - 6.0 mm2 IP66 1 x M25 ( 8 - 17 mm)* 170 x 130 x 129 mm approx. 1.90 kg (1 level) approx. 2.05 kg (2 level) grey RAL 7031 260 x 160 x 90 mm approx. 2.90 kg (1 level) approx. 3.05 kg (2 level) max. 690 V 20 A with GHG 28 II D IP66 T 49 C
3 4 5 6 7 8 9 10 11 12
COOPER CROUSE-HINDS GMBH
* Control switches with direct indicating measuring instruments in the standard version are delivered with 2 looping terminals and PE terminal
9.121
Ex-Control switches
GHG 294
GHG 295
Code B1
Switch mechanism spring - engaging - spring engaging - engaging - engaging engaging - engaging spring - engaging - engaging engaging - engaging - spring
4 5 6 7 8
45O
45O
90O
45O
45O
45
45
Code B2
Contact
45 135 1 3 2 4 1 3 2 4 1 3 2 4 1 3
Code
45 90 135 45 90 135 45 90 135 45 90 135 1 3 5
060
3
45 135 I II
2 4 6 1 3 5
45 90 135 0 I
2 1
6 3 5
45 135
45 135 0 I
2 1
4 3
2 4 6 1 3 5
45 90 135 0 I
2 1
4 3 5
45 135
45 135 I 0 II
4 1/3 2 4
2 4 6 1 3 5
45 90 135 I II III
2 1
4 3
6 5
023 019
2 4 1 3
45 90 135 I 0 II 1
2 4 6 1 3 5 2 4 6 1 3 5 7 2 4 68 1 3 5 7
45 90 135 0 I 1
2 3
4 5
2 4 1 3
45 90 135 0 I
4 1 3
45 135
45 135 I II
4 1/3
6 5/7
2 4 1 2
45 90 135 0 I 1
45 135
033
5/7
4
45 90 135
45 135 I 0 II
2 4 6 8 1/3
45 135
024
45 135
2 4 68
45 90 135
2 4 6 8
Other versions as well as gold contact points are available on request. Code C Contact lable Inscription 0 I STOP HAND SENKEN REMOTE I AUS AUS AUF Entriegelt OUT LOCAL STOP HAND AUF HAND 0 BETRIEB 0 0 0 OF REMOTE 0 0 AUS AUS I II START AUTO HEBEN LOCAL II EIN EIN AB Verriegelt HAND AUTO START AUTO ZU AUTO Code 001 002 003 004 005 006 007 008 009 010 011 012 013 014 015 016 017 Inscription 0 AUS AUS RTLICH START OFF HAND 0 MAN START HEBEN OFF AUS HAND ON I II I AUTO HAND AUS NORMAL 0 OFF IN II EIN AUTO FERN STOP ON AUTO START AUTO STOP SENKEN ON EIN AUTO OFF III Code 018 019 020 021 022 023 024 025 026 027 028 029 030 031 032 033
9.122
Ex-Control switches
1 2
GHG 295 GHG 294
3 4 5 6 7 8 9 10 11 12
Code F1
Buil-in components designation Entry type Entry direct in enclosure Entry via plastic flange Entry via metal flange GEH FLK FLM BO SV GK GM* GV M1 .. ..
F2
Entry element
only threaded entry Threaded plug Cable entry moulded plastic Cable entry metal* Cable entry with plug
F3 F4
1)
Size Number
9.123
Ex-Control switches
GHG 294
GHG 295
GHG 295 / 5 /
Ordering details
Switching mechanism Contact system Code Label inscription Order No.
Control switch Type 294 with silver contacts Version with locking facility in 0-, or position right (Code 3), cable entry 1 x M25 on bottom. 6 6 4 8 4 8 5 5
45 135 1 3 2 4 1 3 2 4 1 3
0 0 0 0 0 0 I
I I I I I I 0 II
GHG 294 1000 R0001 GHG 294 1000 R0002 GHG 294 1000 R0003 GHG 294 1000 R0004 GHG 294 2000 R0002 GHG 294 2000 R0003 GHG 294 2000 R0004 GHG 294 2001 R0001
45 135 0 I
2 1
4 3
45 135
45 135 0 I
4 1 3
2 4 1 3
45 90 135 0 I
1 3
2 4 1 3 5
45 90 135 0 I
2 1
2 4 6 1 3 5
45 90 135 0 I 1
6 3 5
2 4 6 1 3 5 7
45 90 135 I 0 II
1 3 5 7
2 4 6 8 1 3 5
45 90 135 I II III 1
2/4 3
6/8
023
2 4 6
45 90 135
Switching mechanism
Contact system
Code
Label inscription
Order No.
Control switch with measuring instrument Type 295 with silver contacts Version with locking facility in 0-, or left position, Measuring instrument AM 72 for CT connection n/1A, Scale 0 - 100/150 %. 1 x M32 on bottom. 6 6
45 135 1 3 2 4 1 3 2 4
062 065
0 0
I I
45 135 0 I
2 1
4 3
45 135
45 135
9.124
9.125
12
11
10
L I G H T
A L L O Y
C O N T R O L
S T A T I O N S
Ex-d explosion-protected control stations made of light alloy metal are equipped with up to three components to switch and control processes in areas of Zone 1, 2, 21 and 22 at no risk of explosion. Built-in components, such as signal lamps, pushbuttons and switches are ready installed inside of the enclosures. To facilitate insertion of cables into the entries, Ex-d threads for 3/4 Ex-d cable glands are available at the enclosures. A high IP degree of protection allows universal use in areas at risk of explosion. The light metal control stations have an outside earthing connection.
High degree of protection IP67 High mechanical, chemical and thermal resistance Individual configuration
1 2
EFS A/A/V EFS A EFS D
Technical data
Ex-d control stations Type EFS Marking to 94/9/EC EC-Type Examination Certificate IECEx Certificate of Conformity Marking accd. to IECEx Permissible ambient temperature Rated voltage Rated current PE connecting terminals Insulation class Incandescent lamp Degree of protection accd. EN 60529 Cable glands/Gland plates/Enclosure drilling Enclosure material Enclosure colour Other versions available on request II 2 G EEx d IIC T6 / LOM 03 ATEX 2034 IECEx BKI 07.0027 Ex d IIC T6 Ex tD A21 IP67 T80 C 20 C to +55 C max. 660 V AC max. 20 A 2 x 2.5 mm2 / PE ext.: 2 x 6 mm2 I 230 V 3 W IP67 1 x 3/4 ISO 7/1 or 2 x 3/4 ISO 7/1, one plugged Light alloy natural finish II 2 D IP67 T 85 C
3 4 5 6
Weight 0.75 kg 0.85 kg 0.80 kg 0.85 kg 0.85 kg 1.50 kg 1.50 kg 1.20 kg Qty. 1 1 1 1 1 1 1 1 Order No. NOR 000 114 110 511 NOR 000 114 110 553 NOR 000 114 110 587 NOR 000 114 110 540 NOR 000 114 110 595 NOR 000 114 110 747 NOR 000 114 110 748 NOR 000 114 110 740
Ordering details
Type Control units EFS A EFS A/A EFS D EFS A/D EFS L EFS A/A/A EFS A/A/V EFS 72 1 x pushbutton, 1 NO + 1 NC, label "White" 2 x pushbutton, 1 NO + 1 NC, lable "I - 0" 1 x mushroom head pushbutton, 1 NO + 1 NC, label "0" 1 x pushbutton 1 NO, 1 x mushroom head pushbutton NC, label "I - 0" 1 x alarm pushbutton, 1 NO + 1 NC, with windows 3 x pushbutton, 1 NO + 1 NC, label "0 - I - II" 2 x pushbutton, 1 NO + 1 NC, label "0 - I - II", 1 x green signal lamp With measuring instruments 72 mm x 72 mm Description
7 8 9 10 11 12
Control switches EFS I EFS H EFS J EFS P EFS P40 0-1 1-2 1-0-2 0-1 0-1 0.90 kg 0.90 kg 0.90 kg 0.90 kg 0.90 kg 1 1 1 1 1 NOR 000 003 110 945 NOR 000 003 110 937 NOR 000 003 110 953 NOR 000 003 110 995 NOR 000 114 110 738
9.127