05 Heat Pump 06 ExA Engl
05 Heat Pump 06 ExA Engl
05 Heat Pump 06 ExA Engl
Page
Hoval Genius Description Part N Technical Data Dimensions and required space Performance data Installation
Hoval Genius Description Part N Technical Data Dimensions and required space Performance data Installation
Hoval Thermailia 7-58 kW bzw. 5-46 kW Description Part N Technical Data Dimensions and required space Performance data
CalorierHeat Pump
Hoval CombiVal WP-VT Description Part N Technical Data Dimensions Engineering Examples
Storage Tank
Hoval Storage tank mounted below the heat pump TS 70-100 L Description 471 472 Part N Technical Data 473 474 Engineering Installation 476
Regulations and guidelinesGeneral references Planning Instructions Examples of application Energy demand Construction tips
393
394
Compact air/water heat pump for - Inside installation - Outside installation - Split installation in 2-piece housing (evaporator/fan or condenser /compressor) Stable and cold bridge free housing with aluminium profile frames and plastic corner joints. Removable side walls (panels) from powder covered Zincor sheet steel with optimal heat and sound isolation. Colour RAL 7038 (agate grey). The heat pump is largely free of condensation water. With spiral (scroll) compressor. With extensive aluminium/Cu lamellar tube evaporator and steel/Cu condenser. Working medium circuit with thermostatic expansion valve, filter dryer with level indicator, high and low pressure switches. Starting current limiter (serially installed). With efficient automatic defrosting by reversal principle. Electric and terminal box (integrated in the front down right part). With control and disturbance signalling. Filled in with working medium R 407C, internally wired ready-for-connection (exception: split type). Water connection Complete water connection kit (enclosed in WP housing, assembly to be provided by the owner). Heating and condensate connections from flexible pipes with external thread (R). Connection side is selectable, right or left. Condensate connection The drain pipeline is to be made with sufficient incline and without change of the cross-section. Water connections outdoors (outside or split installation) must be protected from the frost by the owner ! Heat source connection (Air intake or air outlet) Air intake from the rear (broadside). Outlet panel with outlet aperture (readjustable for air outlet direction to the top or to the right or left). Electrical connections Connection: from the bottom in the left or in the right No rigid connections (e.g. cable channel) mounted at the heat pump housing. External electronic control panel with On/ Off switch and built-in heating regulator TopTronicT/N Regulation function integrated for: - 1 mixer circuit - 1 heating circuit without mixer - domestic hot water loading circuit Function extension possibility via different key modules. Installation Variable and cost-efficient installation possibilities owing to selectable outlet side covering (panel with outlet aperture see in Subject to alterations, 1.6.2006
Nominal heat capacity of A2W35 kW 6,6 9,7 11,6 13,6 15,7 Authorizations Switzerland/Germany/Austria Genius (08)test No. WPZ-LW-077-02-03 Genius (12)test No. WPZ-LW-085-03-01 Examined by heat pump testing center (WPZ) The Genius (06-35) series is certied by the seal of approval of the authorization commission of Switzerland
Accessories Vario). Construction variants The heat pump can be supplied in the following types: For inside installation Construction as a compact device with water connection kit. External electronic control panel with heating regulator TopTronicT/N (absolutely necessary!). Air ducting options: Wall fastener, air intake box, outlet panel, air hose mounting plate for outlet to the top, to the right or left selectable), air hose, lead through wall with weather protective grills and sound insulation box for intake. Outlet panel, air pipe connecting plate for outlet upwards, to the right or to the left (as required), air pipe, For outside installation Construction as a compact device with selectable outlet panel. With water connection kit (frost protection provided by the owner). External electronic control panel with heating regulator TopTronicT/N for inside installation (absolutely necessary!). Options: Device roof, intake/outlet weather protective grills and sound insulation box for intake and
outlet and exhaust For split installation (2-piece construction) Inner device with adjustable feet. Connections for working medium connecting pipelines (2 Cu pipes). With water connection kit (frost protection provided by the owner). External electronic control panel with heating regulator TopTronicT/N for inside installation (absolutely necessary!). External device with fixed feet (feet height 160 mm). Connections for working medium connecting pipelines (2 Cu pipes). Options: Device roof, intake/outlet weather protective grills, sound insulation box for intake and outlet and working medium connecting pipelines form Cu pipe completely and professionally installed by a Hoval technician (casing tube, sheath tube for connecting pipelines provided by the owner). Supply Inner and outside installation One-piece construction Complete, packed Split installation Two-piece construction Complete, packed Construction per inquiry 395
Contents
Part N
Euro
Outside installation without outside installation kit AS (06) 6,6 (08) 9,7 (10) 11,6 (12) 13,6 (16) 15,7 Split installation without working medium pipelines (R407c) (06) 6,6 (08) 9,7 (10) 11,6 (12) 13,6 (16) 15,7
7002 550 7002 568 7002 569 7002 570 7002 571
7002 239 7002 240 7002 241 7002 242 7002 243
Necessary accessories
Electronic control panel ET-T External electronic control panel with built-in heating regulator TopTronicT/N. Regulation function integrated for: 1 mixer circuit, 1 heating circuit without mixer, Domestic hot water loading circuit. Function extension via different key modules. Engage switch and terminal strip for outer connection incl. el. heating. Internally ready-wired. 300x400x150 mm, 10,7 kg. Electronic control panel WG500G External electronic control panel with heating regulator TopTronicT/N, Regulation function integrated for: 1 mixer circuit, 1 heating circuit without mixer, Domestic hot water loading circuit. Function extension via different key modules. without connection to el. heating
6013 130
1.014,00
6012 699
577,00
Accessories
Screw-in electrical heating inset EP-3 3 kW, for plants with techn. storage tank according to principal schemes M-WPHA-1a, 1b and 1d. For peak load cover of monovalent plants (monoenergetic utilization). Installation depth Heat output mm kW Type EP-3 EP-4,5 EP-6 3,0 4,5 6,0 390 500 620
Electric ow heater 3kW For plants without techn. storage tank according to principal scheme M-WPHA-1c. Installation in the ow. For peak load cover of monovalent plants (monoenergetic utilization). 396
6013 113
252,00
Contents
Part N
Euro
1-7
Standard functions already included in TopTronicT. - 1 mixing circuit - 1 heating circuit without mixing operation - domestic hot water loading circuit
Functions of key modules Key 2. mixing solar module circuit
1 3 5
1
M
Key Module 1 for 2. mixing circuit Function key 1, 1 flow sensor, 2 loose plugs Key Module 3 for solar plants Function key 3, 1 collector sensor, 1 calorifier sensor, 4 loose plugs Key Module 5 for 2. mixing circuit and solar plants Function key 5, 1 flow sensor, 1 collector sensor, 1 calorifier sensor, 6 loose plugs
6012 154
220,00
6012 156
190,00
5
M
6012 158
390,00
Room station RS-T effective on mixing circuit with room sensor, information, program and correction keys. Remote control RFF-T effective on one mixing circuit with room sensor, simple program key and temperature adjustment Outdoor temperature sensor AF200 Flow temperature sensor VF202K for M-WPHA-1d not necessary Cable sensor KVT20/5/6 for M-WPHA-1a 2 pieces necessary Immersion sleeve for cable sensor SB280 " - 280 mm, nickel-plated brass for M-WPHA-1a 2 pieces necessary Collector sensor PT1000 Subject to alterations, 1.6.2006
2022 237
210,00
115,00 31,00
31,00 31,00
Contents
Part N
Euro
Intake
Wall fastener WAE1 Grey synthetic rubber, 50 mm, for seal of the intake side directly on the wall. for type Hoval Genius (06) for type Hoval Genius (08) for type Hoval Genius (10-16) Wall insulation MI-AF1 4-piece, grey synthetic rubber, steam-tight, 25 mm thick, self adhesive. for type Hoval Genius (06) for type Hoval Genius (08) for type Hoval Genius (10-16) Weather protective grills WG-MI1 From aluminium, with mesh grid for intake with Wall insulation MI-AF1 for type Hoval Genius (06) for type Hoval Genius (08) for type Hoval Genius (10-16) Mesh grid MG-MI1 For Wall insulation MI-AF1 (for air shaft, replaces weather protective grills WG-MI1) for type Hoval Genius (06) for type Hoval Genius (08) for type Hoval Genius (10-16)
Outlet
Wall fastener WAE2 Grey synthetic rubber, 50 mm, seal of the outlet side directly on the wall. for type Hoval Genius (06) for type Hoval Genius (08) for type Hoval Genius (10-16) Wall insulation MI-AF2 4-piece, grey synthetic rubber, steam-tight, 25 mm thick, self adhesive. for type Hoval Genius (06) for type Hoval Genius (08) for type Hoval Genius (10-16) Weather protective grills WG-MI2 From aluminium, with mesh grid for outlet with Wall insulation MI-AF2 for type Hoval Genius (06) for type Hoval Genius (08) for type Hoval Genius (10-16) Mesh grid MG-MI2 For Wall insulation MI-AF2 (for air shaft, replaces weather protective grills WG-MI2) for type Hoval Genius (06) for type Hoval Genius (08) for type Hoval Genius (10-16)
398
Contents
Part N
Euro
Intake
Air intake box ASK Resembles the type of housing of the heat pump (galvanized panels). With selectable connective aperture for intake via air hose or air duct, provided by the owner, depth 575 mm for type Hoval Genius (06) for type Hoval Genius (08) for type Hoval Genius (10-16)
Air hose connection plate LAP1 Oval, incl. air hose clamp. For intake box type ASK or for the WP outlet panel AP for type Hoval Genius (06-08) for type Hoval Genius (10-16)
199,00 XXX,00
Wall insulation MI-AF3 4-piece, grey synthetic rubber, steam-tight, 25 mm thick, self adhesive. for type Hoval Genius (06-08) for type Hoval Genius (10-16)
78,00 92,00
Weather protective grills WG-MI3 From aluminium with mesh grid for type Hoval Genius (06-08) for type Hoval Genius (10-16)
252,00 366,00
Mesh grid MG-MI3 For Wall insulation MI-AF3 (for air shaft, replaces weather protective grills WG-MI3) for type Hoval Genius (06-08) for type Hoval Genius (10-16)
111,00 145,00
Air hose connection plate LAP3 Round, incl. air hose clamp to Wall insulation MI-AF3 for type Hoval Genius (06-08) for type Hoval Genius (10-16)
214,00 XXX,00
Contents
399
Part N
Euro
Outlet
Outlet panel AP Side wall with outlet aperture form powder covered sheet steel, thermally insulated for type Hoval Genius (06) for type Hoval Genius (08) for type Hoval Genius (10-16)
Air hose connection plate LAP1 Oval, incl. air hose clamp. For outlet panel AP of the heat pump for type Hoval Genius (06-08) for type Hoval Genius (10-16)
199,00 XXX,00
Wall insulation MI-AF3 4-piece, grey synthetic rubber, steam-tight, 25 mm thick, self adhesive. for type Hoval Genius (06-08) for type Hoval Genius (10-16)
78,00 92,00
Weather protective grills WG-MI3 From aluminium with mesh grid for type Hoval Genius (06-08) for type Hoval Genius (10-16)
252,00 366,00
Mesh grid MG-MI3 For Wall insulation MI-AF3 (for air shaft, replaces weather protective grills WG-MI3) for type Hoval Genius (06-08) for type Hoval Genius (10-16)
111,00 145,00
Air hose connection plate LAP3 Round, incl. air hose clamp to wall insulation MI-AF3 for type Hoval Genius (06-08) for type Hoval Genius (10-16)
214,00 XXX,00
400
Contents
Euro
Outside installation
Outside installation kit AS Consisting of device roof GD, intake grid AWG1 and outlet grid AWG2. Material: aluminium for type Hoval Genius (06) for type Hoval Genius (08) for type Hoval Genius (10-16)
Options
For outside installation kit AS (Part N per unit) Included in the outside installation kit AS: Device roof GD from aluminium for type Hoval Genius (06) for type Hoval Genius (08) for type Hoval Genius (10-16) Included in the outside installation kit AS: Intake weather protective grills AWG 1 from aluminium for type Hoval Genius (06) for type Hoval Genius (08) for type Hoval Genius (10-16) Included in the outside installation kit AS: Outlet weather protective grills AWG2 from aluminium for type Hoval Genius (06) for type Hoval Genius (08) for type Hoval Genius (10-16)
Contents
401
Part N
Euro
Options
For outside installation kit AS (Part N per unit) Included into the outside installation kit AS: Device roof GD from aluminium for type Hoval Genius (06) for type Hoval Genius (08) for type Hoval Genius (10-16) Included in the outside installation kit AS: Intake weather protective grills AWG 1 from aluminium for type Hoval Genius (06) for type Hoval Genius (08) for type Hoval Genius (10-16) Included in the outside installation kit AS: Outlet weather protective grills AWG2 from aluminium for type Hoval Genius (06) for type Hoval Genius (08) for type Hoval Genius (10-16)
Service
Commissioning Commissioning must be made by works service or Hoval trained authorized serviceman/ company is condition for warranty. For commissioning and other services please contact your Hoval sales ofce. auf Anfrage
402
Contents
Compressor type Working medium lling R407c Fan type Nominal air quantity Rotations Available external pressing Evaporator Pipe rows Stream surface Condenser Content incl. ex. hose Piping connection Nominal volume ow Resistance Volume ow min./max. Resistance min./max. Max. operating pressure Heating side Operating limit values Heat source Outdoor air temperature min. Outdoor air temperature max.
1 x spiral (scroll), hermetic 7,0 9,0 radial 4000 570 90 lamellar tube Alum/Cu 6 0,9 Stahl/Cu 3,1 1 1,2 8,3 1,0/2,0 5,8/23,1 10 5000 570 55 6 0,9 3,4 1 1,5 8,9 1,3/2,6 6,7/26,8 10
C C
-15 32 25 55 50 40
Heating Flow min. (condenser discharge) C Flow max. (condenser discharge) to outdoor temperature tA> +/- 0 C C2 tA= -10 C C2 C2 tA= -15 C Electrical data Power consumption max. Compressor Fan Voltage Compressor Fan Frequency Voltage range Power consumption max. Compressor (Imax.) Blocking current (LRA)3 Starting current with jump start Fan
1 2 3
kW kW V V Hz V A A A A
3,7 0,18
5,9 0,28
8,0 0,43
8,3 0,43
10 50 25 0,56
13,5 74 35 1,0
14 74 36 1,0
kW = the whole device with A2W35 incl. defrosting loss in the range of -10 C to -15 C the outdoor temperature (tA) is gliding between 50 C 40 C LRA = not relevant, because equipped with starting current limiter
Contents
403
(06)
(08)
(10)
(12)
(16)
35 43/37 34
38 43/37 34,5
40 47/41 38
41 47/41 38
42 49/43 40
Data for electric power station (EW) and electrician Type Compressor power consumption2 PNT (kW) A2W35 A7W35 1,72 2,42 2,87 3,47 3,57 1,72 2,52 2,87 3,57 3,67 Operating current I max. A 5,6 10 12,4 13,5 14 Blocking current (LRA)3 A 40 50 66 74 74 Starting current with jump start A 17,5 25 32,5 35 36 Protection (integrated) A 16T 16T 16T 16T 16T
A2W35 = for heat pump plants with monovalent or bivalent parallel operating mode A7W35 = for heat pump plants with bivalent alternative operating mode LRA = not relevant, because equipped with jump start
404
Contents
l
e
u
i
f a
5
h
min. 800 mm
m
n
5
t
5 1, 2, 3
u
g
1 2 3
1 2 3
1 2 3
v
o 1, 2, 3 v
u
4
c
u min. 500 mm
1 Heating flow 1, with flexible connecting hose 2 Heating return1, with flexible connecting hose 3 Condensate drain , with flexible connecting hose Water connections (1-3): connection side is selectable, on the left or on the right (connection kit is separately enclosed for assembly by the owner) 4 Air intake (evaporator inlet). Connection directly to the aluminium frame (2 mm thick) Type (06) (08) (10) (12) (16) Type (06) (08) (10) (12) (16)
1
5 Air outlet aperture, panel demountable, outlet directions: selectable to the top, to the left or right (re-positioning by the owner) 6 Outer electronic control panel with heating regulator TopTronicT/N and engage switch 7 Internal electric and terminal box with WP control device 8 Electrical connection 9 Adjustable feet, see dimension w 8 mm (dimension between axes from outside 90 mm) e1 260 335 310 310 310 v 100 100 100 100 100 f 930 980 1080 1080 1080 w 25 25 25 25 25 g 520 520 520 520 520 z 150 150 150 150 150 i 125 125 125 125 125 x 300 300 300 300 300 k1 735 760 735 735 735 y 400 400 400 400 400 m1 75 75 75 75 75 weight (kg) 250 280 290 300 315 n1 380 380 380 380 380
l 650 750 750 750 750 o 595 595 595 595 595
b 1000 1100 1200 1200 1200 p 375 375 375 375 375
h 1475 1525 1625 1625 1625 r 285 285 285 285 285
a 830 880 980 980 980 s 195 195 195 195 195
c 900 1000 1100 1100 1100 t (ca.) 420 420 420 420 420
Outlet panel AP (see accessoires) Required space, accessibility Necessary distances for assembly, operation and maintenance. Device: In front (operating and maintenance side) = 800 mm. On the left (maintenance side) min. 500 mm Outer electronic control panel: Place operating and metering friendly with short electrical wires to the heat pump. The electrical connection should be provided by a professional according to the local electric power station (EW) regulations.
Assembly Floor: select an even installation area, capable of bearing load. After the positioning the heat pump must be levelled (adjustable feet). No socket is necessary for the heat pump. Provide for a condensate drain with a siphon (height approx. 100 mm) in the direct proximity of the heat pump. The drain pipeline is to be made with sufficient incline and without change of crosssection. The drain pipeline is to be made with sufficient incline and without change of crosssection. Evaporator cleaning must be ensured (check accessibility)
Heat pump
Contents
405
l
m
4
h
min. 800 mm
10
5
c
d
1 2 3
9
12 3
1 2 3
10
h1
1 2 3
i
11
e
1, 2, 3
i
r
10
min. 500 mm
123
min. 500 mm
1 Heating flow 1, with flexible connecting hose 2 Heating return 1, with flexible connecting hose 3 Condensate drain , with flexible connecting hose Water connections (1-3): connection side is selectable, on the left, the right or down (connection kit is separately enclosed for assembly by the owner) 4 Air intake (evaporator inlet) with weather protective grills 5 Air outlet (evaporator outlet) with weather protective grills, outlet directions: selectable to the left or right Type (06) (08) (10) (12) (16) Type (06) (08) (10) (12) (16) l 690 790 790 790 790 k 300 300 300 300 300 b 1040 1140 1240 1240 1240 m 400 400 400 400 400 h 1480 1530 1630 1630 1630 n 150 150 150 150 150 h1(min) 300 300 300 300 300 r 180 180 180 180 180 a 935 985 1085 1085 1085 Weight (kg) 265 295 310 320 335 c 520 520 520 520 520
6 Outer electronic control panel with heating regulator TopTronicT/N and engage switch for inside assembly 7 Internal electric and terminal box with WP control device 8 Electrical connection 9 Adjustable feet, see dimesion d 8 mm, (dimension between axes from outside 90 mm) 10 To be done by the owner, socket or garden plate on the gravel underlay (recommended height is to be determined depending on the climate zone, minimum 300 mm), 11 Diecut opening for water connetions down 175 mm d e f g i 25 25 25 25 25 195 195 195 195 195 285 285 285 285 285 375 375 375 375 375 100 100 100 100 100
Assembly Select an even installation area, capable of bearing load (e.g. concrete basis). After positioning the heat pump must be levelled (adjustable feet). The socket height for the heat pump is to be determined depending on the climate zone (snow height). The water pipelines must be connected to the condenser frost proof (by the owner). Condensate must be able to run off freely and not freeze. Required space, accessibility Necessary distances for assembly, operation and maintenance. Device: In front (operating and maintenance side) = 800 mm. On the left (maintenance side) = 500 mm
Outer electronic control panel For inside assembly. Place operating and metering friendly with short electrical wires to the heat pump. The electrical wires should be provided by a professional according to the local electric power station (EW) regulations.
Air supply Distances necessary for air intake and outlet. Intake (behind, opposite the front side) Min. distance between protective grills and external wall = 500 mm Outlet (selectable, left or right) Min. distance to the wall 2000 mm
Front side Heat pump Heat pump Electronic control panel Inside
Front side
406
Contents
Outer device
5
10
11
Outer device
min. 500 mm
min. 500 mm
Inner device
min. 800 mm
Inner device
1, 2, 3
i
1, 2, 3
min. 500 mm
1 Heating flow 1, with flexible connecting hose 2 Heating return1, with flexible connecting hose 3 Condensate drain , with flexible connecting hose Water connections (1-3): connection side is selectable, on the left or on the right (connection kit is separately enclosed for assembly by the owner) 4 Air intake (evaporator inlet) with weather protective grills 5 Air outlet (evaporator outlet) with weather protective grills, outlet directions: selectable to the left or right Type l b h h1(min) a c (06) (08) (10) (12) (16) Type 690 790 790 790 790 k 1040 1140 1240 1240 1240 m 1035 1085 1185 1185 1185 n 300 300 300 300 300 o 935 985 1085 1085 1085 p 520 520 520 520 520 r
6 Outer electronic control panel with heating regulator TopTronicT/N and engage switch for inside assembly 7 Internal electric and terminal box with WP control device 8 Electrical connection 9 Adjustable feet, see dimension d 8 mm (dimension between axes from outside 90 mm) 10 To be done by the owner, socket or garden plate on the gravel underlay (recommended height is to be determined depending on the climate zone, minimum 300 mm), 11 Working medium connecting pipeline 175 mm d e f i 25 25 25 25 25 s 285 285 285 285 285 375 375 375 375 375 100 100 100 100 100 Inner device (kg)
(06) 300 400 150 1000 (08) 300 400 150 1100 (10) 300 400 150 1200 (12) 300 400 150 1200 (16) 300 400 150 1200 Assembly Outer device (evaporator unit) Select an even installation area, capable of bearing load (e.g. concrete basis). The socket height for the heat pump is to be determined depending on the climate zone (snow height, etc). Condensate must be able to run off freely and not freeze. Inner device (compressor / condenser unit) No socket is necessary for the heat pump. After positioning the heat pump must be levelled (adjustable feet). Attention The outer device must be always installed higher than the inner device! Required space, accessibility Necessary distances for assembly, operation and maintenance. Subject to alterations, 1.6.2006
650 180 95 165 750 180 95 180 180 95 185 750 750 180 95 185 750 180 95 185 Outer device: fan side (for maintenance) = min. 500 mm. Inner device: in front and on the left = min. 500 mm
120 140 150 160 180 The electrical wires should be provided by a professional according to the local electric power station (EW) regulations.
Outer electronic control panel For inside assembly. Place operating and metering friendly with short electric lead wires to the heat pump.
Outer device
Air supply Distances necessary for air intake and outlet. Intake (behind, opposite the front side) Min. distance between protective grills and external wall = 500 mm Outlet (selectable, left or right) Min. distance to the wall 2000 mm
Outer device
Fan side
Contents
407
(06)
P kW 1,9 1,9 1,9 1,9 1,9 1,9 1,9 1,9 1,9 1,9 1,9 1,9 1,9 2,1 2,1 2,1 2,1 2,1 2,1 2,1 2,1 2,1 2,1 2,1 2,1 2,1 2,3 2,3 2,4 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,6 2,6 2,6 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 COP 5,2 5,1 4,2 4,1 3,8 3,5 3,3 2,9 2,7 2,6 2,5 2,3 1,8 4,7 4,6 3,8 3,7 3,4 3,2 3,0 2,6 2,5 2,4 2,2 2,1 1,7 4,3 4,1 3,4 3,2 3,0 2,8 2,7 2,4 2,2 2,1 2,0 1,9 3,8 3,7 3,0 2,8 2,6 2,5 2,3 2,1 2,0 1,9 1,8 1,7 QWP kW 14,4* 14,0 11,6* 10,9* 10,2 9,7* 9,2 8,1 7,6 7,3* 7,1 6,6 5,2 14,2 13,9 11,5 10,8 10,1 9,6 9,1 8,0 7,5 7,3 7,0 6,5 5,2 14,1 13,7 11,4 10,7 9,9 9,4 9,0 8,0 7,5 7,2 7,0 6,5 13,9* 13,6* 11,3 10,6* 9,8 9,3* 8,8 7,9 7,4 7,1* 6,9 6,4
(08)
P kW 2,8* 2,8 2,8* 2,8* 2,8 2,7* 2,8 2,8 2,8 2,8* 2,8 2,8 2,8 3,1 3,2 3,2 3,1 3,1 3,1 3,1 3,1 3,1 3,1 3,1 3,1 3,2 3,5 3,5 3,5 3,5 3,4 3,4 3,4 3,4 3,5 3,5 3,5 3,5 3,8* 3,9* 3,9 3,8* 3,8 3,8* 3,8 3,8 3,8 3,8* 3,8 3,8 COP 5,2* 5,0 4,1* 3,9* 3,7 3,5* 3,3 2,9 2,7 2,6* 2,5 2,4 1,9 4,7 4,5 3,7 3,6 3,3 3,2 3,0 2,7 2,5 2,4 2,3 2,1 1,7 4,2 4,0 3,3 3,2 3,0 2,8 2,7 2,4 2,2 2,1 2,0 1,9 3,6* 3,5* 2,9 2,8* 2,6 2,5* 2,4 2,1 2,0 1,9* 1,8 1,7 QWP kW 17,7 17,3 14,2 13,7 12,5 11,6 11,0 9,6 8,9 8,5 8,2 7,5 5,8 17,5 17,1 14.1 13,3 12,1 11,3 10,7 9,4 8,7 8,4 8,1 7,4 5,8 17,3 16,9 13,9 12,8 11,7 11,0 10,4 9,2 8,5 8,2 7,9 7,3 17,1 16,7 13,8 12,3 11,4 10,7 10,1 9,0 8,4 8,1 7,9 7,2
(10)
P kW 3,4 3,4 3,4 3,3 3,3 3,3 3,3 3,2 3,2 3,2 3,2 3,2 3,2 3,8 3,8 3,8 3,7 3,6 3,6 3,6 3,6 3,5 3,5 3,5 3,5 3,5 4,1 4,1 4,1 4,0 3,9 3,9 3,9 3,9 3,8 3,8 3,8 3,8 4,5 4,5 4,5 4,3 4,3 4,2 4,2 4,2 4,1 4,1 4,1 4,1 COP 5,2 5,0 4,2 4,1 3,8 3,6 3,4 3,0 2,8 2,6 2,6 2,3 1,8 4,7 4,6 3,8 3,7 3,4 3,2 3,0 2,7 2,5 2,4 2,3 2,1 1,7 4,3 4,2 3,4 3,3 3,0 2,9 2,7 2,4 2,3 2,2 2,1 2,0 3,8 3,7 3,1 2,8 2,7 2,5 2,4 2,1 2,0 2,0 1,9 1,8 QWP kW 20,8* 19,7 18,7* 16,2* 14,7 13,6* 13,3 12,5 12,2 12,0* 11,8 11,4 10,5 20,5 19,4 17,8 15,7 14,4 13,5 13,2 12,5 12,1 11,9 11,8 11,4 10,4 20,2 19,0 17,0 15,2 14,1 13,4 13,1 12,4 12,0 11,8 11,7 11,3 20,0* 18,6* 16,1 14,7* 13,9 13,3* 13,0 12,3 11,9 11,7* 11,6 11,2
(12)
P kW 4,1* 4,1 4,1* 4,0* 3,9 3,9* 3,9 4,0 4,0 4,0* 4,0 4,0 4,0 4,6 4,6 4,5 4,4 4,4 4,4 4,4 4,4 4,4 4,4 4,4 4,5 4,5 5,1 5,1 5,0 4,8 4,8 4,8 4,8 4,9 4,9 4,9 4,9 4,9 5,6* 5,6* 5,4 5,3* 5,3 5,3* 5,3 5,3 5,4 5,4* 5,4 5,4 COP 5,1* 4,8 4,5* 4,1* 3,7 3,5* 3,4 3,2 3,0 3,0* 3,0 2,9 2,6 4,6 4,3 4,0 3,6 3,4 3,2 3,1 2,9 2,8 2,7 2,6 2,6 2,4 4,1 3,8 3,5 3,2 3,0 2,8 2,8 2,6 2,5 2,5 2,4 2,3 3,6* 3,3* 3,0 2,8* 2,6 2,5* 2,5 2,3 2,2 2,2* 2,1 2,1 QWP kW 24,0 22,7 21,6 18,7 17,0 15,7 15,4 14,4 14,0 13,9 13,7 13,2 12,1 23,7 22,4 20,5 18,1 16,6 15,6 15,2 14,4 13,9 13,7 13,5 13,2 12,0 23,3 21,9 19,6 17,5 16,3 15,5 15,1 14,3 13,8 13,6 13,4 13,0 23,1 21,5 18,6 17,0 16,0 15,4 15,0 14,2 13,7 13,5 13,2 12,9
(16)
P kW 4,2 4,2 4,2 4,1 4,0 4,0 4,0 4,1 4,1 4,1 4,1 4,1 4,1 4,7 4,7 4,6 4,5 4,5 4,5 4,5 4,5 4,5 4,5 4,6 4,6 4,6 5,2 5,2 5,1 4,9 4,9 4,9 4,9 5,0 5,0 5,0 5,0 5,0 5,7 5,7 5,5 5,4 5,4 5,4 5,4 5,4 5,5 5,5 5,5 5,5 COP 5,7 5,4 5,1 4,6 4,2 3,9 3,8 3,5 3,4 3,4 3,3 3,2 3,0 5,0 4,7 4,5 4,0 3,7 3,5 3,4 3,2 3,1 3,0 2,9 2,9 2,6 4,5 4,2 3,8 3,6 3,3 3,1 3,1 2,8 2,8 2,7 2,7 2,6 4,0 3,7 3,4 3,1 3,0 2,8 2,8 2,6 2,5 2,4 2,4 2,3
35
40
45
50
* the data checked by the heat pump testing center tVL tA Q P = = = = heating ow temperature (C) outdoor temperature (C) heat output with defrosting loss (kW) power consumption of the whole device (kW) performance of the whole device Subject to alterations, 1.6.2006
COP = 408
Contents
Heat output (Qmom ) = f x QWP Example Type Hoval Genius (08) QA2W35 9,7 Q A-10W45 6,5 f35 = 1,0503 Qmom A2W35 10,19 f45 = 1,0417 (because of interpolation f35 = 1,045 and f50 = 1,04) Qmom A-10W45 6,77
kPa
m3/h
Contents
409
Standard 2
45
45
7
min. 500 mm
min. 800 mm
6 5 4
min. 800 mm
2 1
7
45
min. 500 mm
Operation and maintenance surface
45
Standard 3
Standard 4
45
45
Operation and maintenance surface
min. 500 mm
1 2
3
min. 800 mm
4 5 6
Heat pump type Genius
min. 500 mm
min. 800 mm
45
45
3
Application
1
Type (06) Art.Nr.
6
Type(16) Art.Nr. 7002 563 2008 402 2018 986 2018 995 2009 280 2018 991 2019 000
Accessories Type
Heat pump Hoval Genius Type (08) Type (10) Type (12) Art.Nr. Art.Nr. Art.Nr. 7002 560 2008 401 2018 985 2018 994 2009 279 2018 990 2018 999 7002 561 2008 402 2018 986 2018 995 2009 280 2018 991 2019 000 7002 562 2008 402 2018 986 2018 995 2009 280 2018 991 2019 000
Heat pump Inside installation 7002 549 1 Wall fastener Intake WAE1 2008 400 2 Wall insulation Intake MI-AF1 2018 984 3 Weather protective grills Intake WG-MI1 2018 993 4 Wall fastener Outlet WAE2 2009 278 5 Wall insulation Outlet MI-AF2 2018 989 6 Weather protective grills Outlet WG-MI2 2018 998 7 Condensate drain (provided by the owner, siphon height approx. 100mm) 410
Contents
Standard 6
7
Heat pump, type Genius
45
45
6 5 4
min. 800 mm
min. 500 mm
min. 800 mm
2 1
7
45
45
Standard 7
45
Standard 8
1 2
3
min. 500 mm
45
min. 800 mm
min. 800 mm
min. 500 mm
4 5 6
Heat pump, type Genius
45
45
Application
Accessories Type
Heat pump Hoval Genius Type (08) Type (10) Type (12) Art.Nr. Art.Nr. Art.Nr. 7002 560 2008 401 2018 985 2018 994 2009 279 2018 990 2018 999 7002 561 2008 402 2018 986 2018 995 2009 280 2018 991 2019 000 7002 562 2008 402 2018 986 2018 995 2009 280 2018 991 2019 000
Type (16) Art.Nr. 7002 563 2008 402 2018 986 2018 995 2009 280 2018 991 2019 000
Heat pump Inside installation 7002 549 1 Wall fastener Intake WAE1 2008 400 2 Wall insulation Intake MI-AF1 2018 984 3 Weather protective grills Intake WG-MI1 2018 993 4 Wall fastener Outlet WAE2 2009 278 5 Wall insulation Outlet MI-AF2 2018 989 6 Weather protective grills Outlet WG-MI2 2018 998 7 Condensate drain (provided by the owner, siphon height approx. 100mm) Subject to alterations, 1.6.2006
Contents
411
3 1 2
e
c
a
e
a
c
e
d
e
d
d
45
10
45
45
10
. ca 0 20
g
n. mi 0 50
45
n. mi
80
mi
n.
80 0
Attention: dimensions for Hoval Genius with storage tank placed below the heat pump see Storage tank TS Engineering.
Accessories Type
Heat pump Hoval Genius Type (10) Type (12) Art.Nr. Art.Nr. 7002 561 2008 402 2018 986 2018 995 2009 280 2018 991 2019 000 7002 562 2008 402 2018 986 2018 995 2009 280 2018 991 2019 000
Type (16) Art.Nr. 7002 563 2008 402 2018 986 2018 995 2009 280 2018 991 2019 000
1 Heat pump 7002 549 7002 560 Intake 2 Wall fastener WAE1 2008 400 2008 401 3 Wall insulation (25 mm) MI-AF1 2018 984 2018 985 4 Weather protective grills WG-MI1 2018 993 2018 994 Outlet 5 Wall fastener WAE2 2009 278 2009 279 6 Wall insulation (25 mm) MI-AF2 2018 989 2018 990 7 Weather protective grills WG-MI2 2018 998 2018 999 8 Condensate drain (provided by the owner, siphon height approx. 100mm) 412
Contents
70
c e
70
f
b
70
g
Type Weather protective grills Type Genius WG-MI1 WG-MI1 WG-MI1 WG-MI2 WG-MI2 WG-MI2 WG-MI3 WG-MI3 (06) (08) (10-16) (06) (08) (10-16) (06-08) (10-16)
Part N 2018 993 2018 994 2018 995 2018 998 2018 999 2019 000 2023 709 2023 710
g 80 80 80 80 80 80 80 80
Contents
413
c f
Floor plan
4
min. 800 mm
min. 500 mm
4 4
d
h
7
5 5
6
i
1, 2, 3
c
1, 2, 3
1 2 3
c f
1 Heating ow 1, with exible connecting hose 2 Heating return1, with exible connecting hose 3 Condensate drain , with exible connecting hose Water connections (1-3): connection side is selectable, left or right (connection kit is separately enclosed for assembly by the owner) 4 Air intake aperture, intake directions selectable, from the top, from the left or right. 5 Air outlet aperture, outlet directions: selectable to the top, to the left or right (replacement provided by the owner) 6 Intake box 7 Internal electric and terminal box with WP control device 8 Condensate drain (provided by the owner, siphon height = ca. 100 mm) Vario installation 1 Vario installation 2
g 75 75 75 75 75
Vario installation 3
7
4
c
1, 2, 3
1, 2, 3
1, 2, 3
8
8
5
5 5
5
min. 500 mm
6
4
5
1, 2, 3 8
min. 500 mm
min. 500 mm
7
Operation and Bedienungsund maintenance surface Wartungsflche
min. 800 mm
Vario installation 4
Vario installation 5
Vario installation 6
min. 800 mm
min. 500 mm
min. 800 mm
min. 500 mm
min. 500 mm
1, 2, 3
5
7
5 5
7
5 5
5
1, 2, 3
Operation and Bedienungsund maintenance Wartungsflche surface
1, 2, 3
1, 2, 3
8
8
4
4
c
8
6
min. 800 mm
414
Contents
min. 800 mm
5
7
min. 800 mm
8
4
Intake
6
b
4
Outlet Selectable
c1
6 7 5
3
Intake from the top
680 680 Depending on the plant 880 880 Depending on the plant
Consider the air hose bending radius = 1R! Intake from the left
2 3
Outlet to the top Intake selectable
7 6 5 4
3
Outlet to the left
3
Outlet to the right
1
Heat pump Hoval Genius Type (10) Type (12) Art.Nr. Art.Nr. 7002 561 6006 375 6015 369 6015 367 600 6015 370 2023 708 2023 710 7002 562 6006 375 6015 369 6015 367 600 6015 370 2023 708 2023 710
Accessories Type Heat pump Air intake box Air hose connecting plate, oval Air hose, 2 m long i mm 5 Air hose connecting plate, round 6 Wall insulation 7 Weather protective grills 1 2 3 4 ASK LAP1 LS LAP3 MI-AF3 WG-MI3
Type (06) Art.Nr. 7002 549 6006 373 6010 116 6010 113 500 6013 183 2023 707 2023 709
Type (08) Art.Nr. 7002 560 6006 374 6010 116 6010 113 500 6013 183 2023 707 2023 709
Type (16) Art.Nr. 7002 563 6006 375 6015 369 6015 367 600 6015 370 2023 708 2023 710
Contents
415
Air ducting
Corner installation Vario with intake box This solution has many installation variants. (See Installation Vario 1-6). Air ducting with air hoses can be optionally varied. The minimum bending radius (1R) as well as operation and maintenance surface should be kept. Recess The placement of recesses is to be determined depending on the plant. See dimensions in Installation and recesses dimensions for installation of Vario.
min. 800 mm
6
4
b
5 3
2
c
3
a
Type Genius
4
d
min. 500 mm
7
Hoval
6
1
e
4 3
3 45
min. 800 mm
8
min. 500 mm
d
Accessories Typ 1 2 3 4 5 6 7 8
Heat pump Hoval Genius Type (10) Type (12) Art.Nr. Art.Nr. 7002 561 6006 375 6015 369 6015 367 600 6015 370 2023 708 2023 710 7002 562 6006 375 6015 369 6015 367 600 6015 370 2023 708 2023 710
Type (16) Art.Nr. 7002 563 6006 375 6015 369 6015 367 600 6015 370 2023 708 2023 710
Heat pump 7002 549 7002 560 Air intake box ASK 6006 373 6006 374 Air hose connection plate, oval LAP1 6010 116 6010 116 Air hose, 2 m long LS 6010 113 6010 113 i mm 500 500 Air hose connection plate, round LAP3 6013 183 6013 183 Wall insulation MI-AF3 2023 707 2023 707 Weather protective grills WG-MI3 2023 709 2023 709 Condensate drain (provided by the customer, siphon height approx. 100 mm)
416
Contents
Air ducting
7
6
7
6
5
4
d
3
c
2 3 1
b
8
min. 500 mm
Hoval
1
e
4 3
3 4 5
min. 800 mm
8
min. 500 mm
8
d
Heat pump Hoval Genius Type (10) Type (12) Art.Nr. Art.Nr. 7002 561 6006 375 6015 369 6015 367 600 6015 370 2023 708 2023 710 7002 562 6006 375 6015 369 6015 367 600 6015 370 2023 708 2023 710
Type (16) Art.Nr. 7002 563 6006 375 6015 369 6015 367 600 6015 370 2023 708 2023 710
Heat pump 7002 549 7002 560 Air intake box ASK 6006 373 6006 374 Air hose connection plate, oval LAP1 6010 116 6010 116 Air hose, 2 m long LS 6010 113 6010 113 i mm 500 500 6013 183 6013 183 Air hose connection plate, round LAP3 Wall insulation MI-AF3 2023 707 2023 707 Weather protective grills WG-MI3 2023 709 2023 709 Condensate drain (provided by the customer, siphon height approx. 100 mm)
Contents
417
Air ducting
7
6
Corner installation Vario with intake box This solution has many installation variants. (See Installation Vario 1-6). Air ducting with air hoses can be optionally varied. The minimum bending radius (1R) as well as operation and maintenance surface should be kept. Recess The placement of recesses is to be determined depending on the plant. See dimensions in Installation and recesses dimensions for installation of Vario.
4
a
5
c
3
d
8
6
4 5
1
b
min. 500 mm
Type Genius
Bedienungs- und maintenance Wartungsflche
surface Operation and
min. 800 mm
Hoval
6
5
6
4
8
min. 800 mm
min. 500 mm
Type (10) Art.Nr. 7002 561 6006 375 6015 369 6015 367 600 6015 370 2023 708 2023 710
Heat pump Hoval Genius Type (12) Art.Nr. 7002 562 6006 375 6015 369 6015 367 600 6015 370 2023 708 2023 710
Type (16) Art.Nr. 7002 563 6006 375 6015 369 6015 367 600 6015 370 2023 708 2023 710
Heat pump 7002 549 7002 560 Air intake box ASK 6006 373 6006 374 Air hose connection plate, oval LAP1 6010 116 6010 116 Air hose, 2 m long LS 6010 113 6010 113 i mm 500 500 6013 183 6013 183 Air hose connection plate, round LAP3 Wall insulation MI-AF3 2023 707 2023 707 Weather protective grills WG-MI3 2023 709 2023 709 Condensate drain (provided by the customer, siphon height approx. 100 mm)
418
Contents
Air ducting
7
6
Corner installation Vario with intake box This solution has many installation variants. (See Installation Vario 1-6). Air ducting with air hoses can be optionally varied. The minimum bending radius (1R) as well as operation and maintenance surface should be kept. Recess The placement of recesses is to be determined depending on the plant. See dimensions in Installation and recesses dimensions for installation of Vario.
5
6
7
3
c
5
2 1
b
4
d
8
min. 500 mm
3
a
Operation and
min. 800 mm
5
4
5 4 3
a
3
Hoval
f
1
e
1 2
min. 800 mm
c
8
min. 500 mm
d
Heat pump Type Hoval Genius Type (08) Type (10) Type (12) Art.Nr. Art.Nr. Art.Nr. 7002 561 6006 375 6015 369 6015 367 600 6015 370 2023 708 2023 710 7002 562 6006 375 6015 369 6015 367 600 6015 370 2023 708 2023 710
Type (16) Art.Nr. 7002 563 6006 375 6015 369 6015 367 600 6015 370 2023 708 2023 710
Heat pump 7002 549 7002 560 Air intake box ASK 6006 373 6006 374 Air hose connection plate, oval LAP1 6010 116 6010 116 Air hose, 2 m long LS 6010 113 6010 113 i mm 500 500 6013 183 6013 183 Air hose connection plate, round LAP3 Wall insulation MI-AF3 2023 707 2023 707 Weather protective grills WG-MI3 2023 709 2023 709 Condensate drain (provided by the customer, siphon height approx. 100 mm)
Contents
419
Air ducting
7
6
Corner installation Vario with intake box This solution has many installation variants. (See Installation Vario 1-6). Air ducting with air hoses can be optionally varied. The minimum bending radius (1R) as well as operation and maintenance surface should be kept. Recess The placement of recesses is to be determined depending on the plant. See dimensions in Installation and recesses dimensions for installation of Vario.
d
5
c
3 1
8
4
3
b
min. 500 mm
a
Operation and Bedienungsund maintenance Wartungsflche surface
min. 800 mm
5
4 4 3
Hoval
f
5 4 3
b
1
1
e
min. 800 mm
8
min. 500 mm
d
Heat pump Type Hoval Genius Type (08) Type (10) Type (12) Art.Nr. Art.Nr. Art.Nr. 7002 561 6006 375 6015 369 6015 367 600 6015 370 2023 708 2023 710 7002 562 6006 375 6015 369 6015 367 600 6015 370 2023 708 2023 710
Type (16) Art.Nr. 7002 563 6006 375 6015 369 6015 367 600 6015 370 2023 708 2023 710
Heat pump 7002 549 7002 560 Air intake box ASK 6006 373 6006 374 Air hose connection plate, oval LAP1 6010 116 6010 116 Air hose, 2 m long LS 6010 113 6010 113 500 500 i mm Air hose connection plate, round LAP3 6013 183 6013 183 Wall insulation MI-AF3 2023 707 2023 707 Weather protective grills WG-MI3 2023 709 2023 709 Condensate drain (provided by the customer, siphon height approx. 100 mm)
420
Contents
12
a
75
11
30 45
3 4 5
1
Hoval
10
13
min. 500 mm
1
10
min. 800 mm
3 45
500
Intake: Vario with air box as well as with air hose and wall lead through, outlet: Standard with wall lead through Outlet to the left reection.
10
d
6
Hoval
5
4
3 2
e
11
1
min. 500 mm
4 3
11
min. 800 mm
30 45 75
11
min. 500 mm
Air ducting
The minimum bending radius (1R) as well as operation and maintenance surface should be kept.
See dimensions in Installation and recesses dimensions for installation of Standard or Vario. Type (16) Art.Nr. 7002 563 6006 375 6015 369 6015 367 600 6015 370 2018 991 2008 402 2018 986 2009 280 2023 708 2019 000 2018 995 2023 710 421
Heat pump Type Hoval Genius Type (08) Type (10) Type (12) Art.Nr. Art.Nr. Art.Nr. 7002 561 6006 375 6015 369 6015 367 600 6015 370 2018 991 2008 402 2018 986 2009 280 2023 708 2019 000 2018 995 2023 710 7002 562 6006 375 6015 369 6015 367 600 6015 370 2018 991 2008 402 2018 986 2009 280 2023 708 2019 000 2018 995 2023 710
Heat pump 7002 549 7002 560 Air intake box ASK 6006 373 6006 374 Air hose connection plate, oval LAP1 6010 116 6010 116 Air hose, 2 m long LS 6010 113 6010 113 i mm 500 500 6013 183 6013 183 Air hose connection plate, round LAP3 Wall insulation MI-AF2 2018 989 2018 990 Wall fastener intake WAE1 2008 400 2008 401 Wall insulation MI-AF1 2018 984 2018 985 Wall fastener outlet WAE2 2009 278 2009 279 Wall insulation MI-AF3 2023 707 2023 707 Weather protective grills WG-MI2 2018 998 2018 999 Weather protective grills WG-MI1 2018 993 2018 994 Weather protective grills WG-MI3 2023 709 2023 709 Condensate drain (provided by the customer, siphon height approx. 100 mm)
Contents
8
a
7 6
75
30 45
min. 500 mm
5
b
*Attention The min. bending radius (1R) is larger than dimension of b. The air hose must be installed diagonally, or there should be planed an intermediate piece (90 bend, rm) with hose connection, provided by the customer (A).
min. 800 mm
A
Hoval
min. 500 mm
3 4 5
9
Air ducting
Installation room with outer wall, parallel installation As air inlet and air outlet are situated on the same wall in this variant, a short circuit must be avoided. Under unfavourable conditions (wind side etc.) bulkheading should be planed between the intake and blow. Do not place inlet and outlet in the same shaft!
The minimum bending radius (1R) as well as operation and maintenance surface should be kept. Recess The placement of recesses is to be determined depending on the plant. See dimensions in Installation and recesses dimensions for installation of Standard or Vario.
Abschottung
Heat pump Type Hoval Genius Type (08) Type (10) Type (12) Art.Nr. Art.Nr. Art.Nr. 7002 561 2008 402 2018 986 6015 369 6015 367 600 6015 370 2023 708 2023 712 2018 995 7002 562 2008 402 2018 986 6015 369 6015 367 600 6015 370 2023 708 2023 712 2018 995
Type (16) Art.Nr. 7002 563 2008 402 2018 986 6015 369 6015 367 600 6015 370 2023 708 2023 712 2018 995
Heat pump 7002 549 7002 560 Wall fastener intake WAE1 2008 400 2008 401 2018 985 Wall insulation intake MI-AF1 2018 984 Air hose connection plate, oval LAP1 6010 116 6010 116 Air hose, 2 m long LS 6010 113 6010 113 i mm 500 500 6013 183 6013 183 Air hose connection plate, round LAP3 Wall insulation MI-AF3 2023 707 2023 707 Weather protective grills WG-MI3 2023 711 2023 711 Weather protective grills WG-MI1 2018 993 2018 994 Condensate drain (provided by the customer, siphon height approx. 100 mm)
422
Contents
6
min. 2000 mm
min. 2000 mm
min. 500 mm
Maintenance surface
1 2 3
1 2 3 min.
Operation surface
14
7 8 1 2 3
min. 800 mm
10
1 2 3
500 mm
10
1 2 3
12
Connections pipe (1,2) and condensate drain (3) with electric trace heating frost protected.
11
1 Heating flow 1 with flexible connecting hose 2 Heating return1, with flexible connecting hose 3 Condensate drain , with flexible connecting hose. Water connections (1-3): connection side is selectable, left or right (connection kit is separately enclosed for assembly by the customer) frost protected ! The pipelines must be connected thermally insulated and frost protected ! (e.g. self-doped electric trace heating) Air intake (evaporator inlet) with weather protective grills Air blow (evaporator outlet) with weather protective grills (Blow directions is selectable to the left or right). Device roof Internal electric and terminal box with WP control device Electrical connection.
4 5 6 7 8
11 9 Adjustable feet 25 mm ( 8 mm) (dimension between axes from outside 90 mm) 10 To be provided by the customer, socket or garden plate on the gravel underlay (the height is to be determined depending on the climate zone, recommended minimum height 300 mm), 11 Condensate drain (siphon height = approx. 100 mm), provided by the customer Frost protected drain must be provided! 12 Casing tube with incline and packing (by the customer) 13 Outer electronic control panel with heating regulator TopTronicT/N and engage switch for inside assembly 14 Electrical connection cables (by the customer)
13
The Hoval Genius-air/water heat pump is assembled outdoors. The installation place must be carefully selected. The following boundary conditions must be kept: The installation place should be selected in such a way that air intake and blow is not hampered or obstructed by snow, leaves etc. There should be provided sufficient space for intake and blow as well as for operation and maintenance. Air short-circuit must be avoided. The space necessary for intake and blow must be always provided. The minimum distances apply only to the indicated example. Under unfavourable conditions (e.g. air short-circuit because of wind influence) the heat pump should be provided with a bilateral blow. Intake air must be completely free from aggressive substances like ammonia, sulphur, chlorine etc. Accessories Type Heat pump Kit for outside installation Included into AS kit: Device roof Intake weather protective grills Outlet weather protective grills Subject to alterations, 1.6.2006 AS Pos.6 Pos.4 Pos.5
Installation
The installation place should not be situated under the living room or bedroom because of sound emission and be placed at sufficient distance from the neighbouring building. Is not recommended to install the heat pump into wall niches (air short-circuit, sound echo) Heating connections and pipelines The pipelines for outdoors (flow and return) should be selected as short as possible. The pipelines outdoors and the condensor should be professionally installed with thermal insulation and antifreeze agent (e.g. self-doped electric trace heating). Deaeration and emptying of the heat pump must be ensured.
Condensate pipeline Condensate must be able to run off freely and non-freezing (frost protected drain, recommended siphon height approx. 100 mm) Wall lead through Wall lead through for pipelines must be implemented and sealed by technicians. Outer electronic control panel Should be installed only inside (room temperature min. +5 C, max. 40C) Electrical connection cables should be selected short, connected flexibly professionally routed according to local rules.
Heat pump Type Hoval Genius Type (06) Type (08) Type (10) Art.Nr. Art.Nr. Art.Nr. 7002 550 6006 376 2009 293 2009 294 2009 295 7002 568 6006 377 2009 296 2009 297 2009 298 7002 569 6006 378 2009 299 2009 300 2009 301
Type (12) Art.Nr. 7002 570 6006 378 2009 299 2009 300 2009 301
Type (16) Art.Nr. 7005 571 6006 378 2009 299 2009 300 2009 301 423
Contents
5 4 7 6 8
min. 500 mm
Working medium connecting pipelines Working medium connecting pipelines may be installed only by professionally authorized persons and after consultation or authorization by Hoval. The pipeline dimensions should be accurately kept (see Part N; working medium connecting pipelines) Inner and outer devices should be professionally installed with common thermal insulation for intake gas, condensate and fluid pipelines as well as filled in with necessary quantity of working medium R407C. Condensate pipeline Condensate must be able to run off freely (frost protected drain, recommended siphon height approx. 100 mm) Wall lead through, sheath tube for conguration of pipelines Wall lead through and sheath tubing for connecting pipelines must be routed without direction changes, professionally implemented and thermally packed. Electrical connection cables Sensor cable should be routed separately and shielded (no common cable piping with 230 V or 400 V cables). Electrical connection cables on the inner and outer device should be connected flexibly.
6 5 4 3
10 13 12
11
14
min. 500 mm
15 16
Plan view
Outside
Heat room
1 Inner device (engine part / compressor) 2 Outer device (vaporiser/ ventilator) 3 Outer electronic control panel with heating regulator TopTronicT/N and engage switch for inside assembly 4 Protective covering (by the customer) 5 Electrical connection cable (by the customer) 6 Working medium connecting pipelines with thermal insulation 7 Working medium fluid pipeline 8 Working medium intake pipeline 10 Casing tube PE I.D. 150 mm with packing (by the customer). All the casing tubes for AM pipelines must be routed without direction changes (Visual contact to the end of the pipe!). 11 Condensed water drain pipeline , flexible 12 Condensate drain, siphon height = approx. 100 mm, provided by the customer Frost protected drain must be provided 13 To be provided by the customer, socket or garden plate on the gravel underlay (the height is to be determined depending on the climate zone, recommended minimum height 300 mm) 14 Drainage (by the customer) 15 Heating flow 1 with flex. connecting hose 16 Heating return 1with flex. connecting hose Subject to alterations, 1.6.2006
424
Contents
Compact air/water heat pump for - Inside installation - Outside installation Stable and cold bridge free housing with aluminium profile frames and plastic corner joints. Removable side walls (panels) from powder covered Zincor sheet steel with optimal heat and sound insulation. The heat pump is extensively free from condensation water. Colour RAL 7038 (agate grey). The heat pump is largely free of condensation water. With spiral (scroll) compressor. With extensive aluminium/Cu lamellar tube evaporator and steel/Cu condenser. Working medium circuit with thermostatic expansion valve, filter dryer with level indicator, high and low pressure switches. Starting current limiter (serially installed). With efficient automatic defrosting by reversal principle. Electric and terminal box (integrated in the front down right part). With control and disturbance signalling. Filled in with working medium R 407C, internally wired ready-for-connection (exception: split Type) Water connections Complete water connection kit (enclosed in WP (heat pump) housing, assembly to be provided by the owner). Heating and condensate connections from flexible HD pipes with external thread (R). Connection side is selectable, right or left. Kondensatanschluss The drain pipeline is to be made with sufcient incline and without change of the cross-section. Water connections outdoors (outside or split installation) must be protected from the frost by the owner ! Heat source connections (Air intake or air outlet) Air intake from the rear (broadside). Outlet panel with outlet aperture (readjustable for air outlet direction to the top or to the right or left). Electrical connections Connection: from the bottom on the left or on the right No rigid connections (e.g. cable channel) mounted at the heat pump housing. External electronic control panel with On/Off switch and built-in heating regulator TopTronicT/N Regulation function integrated for: - 1 mixer circuit - 1 heating circuit without mixer - Domestic hot water loading circuit Function extension possibility via different key modules.
Authorizations Switzerland/Germany/Fromtria Hoval Genius (08) Prf.Nr. WPZ-LW-077-02-03 Prf.Nr. WPZ-LW-085-03-01 Hoval Genius (12) Examined by heat pump testing center (WPZ) The Genius (06-35) series is certied by the seal of approval of the authorization commission of Switzerland
Installation Variable and cost-efficient installation possibilities owing to selectable outlet side covering (panel with outlet aperture see in Accessories). Construction variants The heat pump can be supplied in the following Typees: For inside installation Construction as a compact device with water connection kit. External electronic control panel with heating regulator TopTronicT/N (absolutely necessary!). Air ducting options: Wall fastener, air intake box, wall lead through with weather protective grills and sound insulation box for intake.
For outside installation Construction as a compact device with selectable outlet panel. With water connection kit (antifreeze agent provided by the owner). External electronic control panel with heating regulator TopTronicT/N for inside installation (absolutely necessary!). Options: Device roof, intake/outlet weather protective grills and sound insulation box for intake and outlet. Supply Inner and outside installation One-piece construction Complete, packed Construction per inquiry Inside installation: two-piece for bringing in Spilt construction (two piece)
Contents
425
Part N
Euro
Necessary Accessories
Electronic control panel ET-T External electronic control panel with built-in heating regulator TopTronicT/N. Regulation function integrated for: - 1 mixer circuit - 1 heating circuit without mixer - Domestic hot water loading circuit Function extension via different key modules. Engage switch and terminal strip for outer connection incl. el. heating. Internally ready-wired. 300x400x150 mm, 10.7 kg.
6013 130
1.014,00
Electronic control panel WG500G External electronic control panel with heating regulator TopTronicT/N, Regulation function integrated for: - 1 mixer circuit - 1 heating circuit without mixer - Domestic hot water loading circuit Function extension via different key modules. without connection to el. heating Accessories Screw-in electric heat capping EP-3 3 kW, for plants with techn. storage tank according to principal schemes M-WPHA-1a, 1b and 1d. For peak load cover of monovalent plants (monoenergetic utilization). Type Heat output kW 3,0 4,5 6,0 Installation depth mm 390 500 620
6012 699
577,00
426
Contents
Part N
Accessories for heating regulation system TopTronicT
Key modules for Hoval TopTronicT for further functions additionally to standard functions. Key module consists of: Function key for plugging into TopTronicT incl. accessories Only one key module is possible!
Part N
Euro
1-7
Standard functions already included in TopTronicT. - 1 mixing circuit - 1 heating circuit without mixing operation - domestic hot water loading circuit
Functions of key modules solar Key 2. mixing module circuit
1 3 5
1
M
Key Module 1 for 2. mixing circuit Function key 1, 1 flow sensor, 2 loose plugs Key Module 3 for solar plants Function key 3, 1 collector sensor, 1 calorifier sensor, 4 loose plugs Key Module 5 for 2. mixing circuit and solar plants Function key 5, 1 flow sensor, 1 collector sensor, 1 calorifier sensor, 6 loose plugs
6012 154
220,00
6012 156
190,00
5
M
6012 158
390,00
Room station RS-T effective on mixing circuit with room sensor, information, program and correction keys. Remote control RFF-T effective on one mixing circuit with room sensor, simple program key and temperature adjustment Outdoor temperature sensor AF200 Flow temperature sensor VF202K for M-WPHA-1d not necessary Cable sensor KVT20/5/6 for M-WPHA-1a 2 pieces necessary Immersion sleeve for cable sensor SB280 " - 280 mm, nickel-plated brass for M-WPHA-1a 2 pieces necessary Collector sensor PT1000 Subject to alterations, 1.6.2006
2022 237
210,00
115,00 31,00
31,00 31,00
Contents
Part N
Euro
75,00 78,00
362,00 444,00
191,00 226,00
1.175,00 1.336,00
Outlet
Wall fastener WAE2 Grey synthetic rubber, 50 mm, seal of the outlet side directly on the wall. for Type Hoval Genius (20-25) for Type Hoval Genius (30-35) Wall insulation MI-AF2 4-piece, grey synthetic rubber, steam-tight, 25 mm thick, self adhesive covering and protected with peel-off film. for Type Hoval Genius (20-25) for Type Hoval Genius (30-35) Weather protective grills WG-MI2 For outlet with wall insulation MI-AF2 for Type Hoval Genius (20-25) for Type Hoval Genius (30-35) Mesh grid MG-MI2 To wall insulation MI-AF2 (for air shaft, replaces weather protective grills WG-MI2) for Type Hoval Genius (20-25) for Type Hoval Genius (30-35) Outlet panel AP Side wall with outlet aperture form powder covered sheet steel, thermally insulated for Type Hoval Genius (20-25) for Type Hoval Genius (30-35)
71,00 75,00
96,00 116,00
287,00 362,00
157,00 191,00
1.175,00 1.336,00
428
Contents
Part N
Euro
632,00 823,00
Optionen
For outside installation kit AS (Part N per unit) Included into the outside installation kit AS: Device roof GD from aluminium for Type Hoval Genius (20-25) for Type Hoval Genius (30-35) Intake weather protective grills AWG 1 from alumimium for Type Hoval Genius (20-25) for Type Hoval Genius (30-35) Outlet weather protective grills AWG2 from aluminium for Type Hoval Genius (20-25) for Type Hoval Genius (30-35)
181,00 226,00
232,00 280,00
218,00 318,00
Service
Commissioning Commissioning must be made by works service or Hoval trained authorized serviceman/ company is condition for warranty. For commissioning and other services please contact your Hoval sales ofce. auf Anfrage
Contents
429
Verdichter Type Working medium lling R407c Fan type Nominal air quantity Rotations Available external pressing Evaporator Pipe rows Stream surface Condenser Content incl. ex. connecting hoses Piping connection Nominal volume ow Resistance Volume ow min./max. Resistance min./max. Max. operating pressure Heating side Operating limit values Heat source Outdoor air temperature min. Outdoor air temperature max.
C C
-15 32 25 553 50 40
Heating Flow min. (condenser discharge) C Flow max. (condenser discharge) to outdoor temperature tA> 0 C C tA= -10 C C2 tA= -15 C C2 Electrical data Power consumption max. Compressor Fan Voltage Compressor Fan Frequency Voltage range Nominal current Compressor (Imax.) Blocking current (LRA)4 Starting current with jump start Fan
1 2 3 4
kW kW V V Hz V A A A A
8,9 0,96
12,1 1,37/2,02
15,3 1,37/2,02
27 1674 66 2,4/42
25 1674 66 2,4/42
kW = the whole device with A2W35 incl. defrosting loss with Y or -switching (-switching as recommended or necessary for air ducts to be made by the owner) 3 in the range of -10 C to -15 C the outdoor temperature (tA) is gliding between 50 C 40 C LRA = not relevant, because equipped with starting current limiter
430
Contents
(20)
(25)
(30)
(35)
46 47 44
47 47 44
48 50 47
49 50 47
Data for electric power station (EW) and electrician Type Hoval Genius (20) (25) (30) (35)
2 2
Compressor power consumption2 PNT (kW) A2W35 A7W35 6,35 6,85 8,53 8,73 6,35 6,95 8,33 8,73
A2W35 = for heat pump plants with monovalent or bivalent parallel operating mode A7W35 = for heat pump plants with bivalent alternative operating mode 3 LRA = not relevant, because equipped with jump start
Contents
431
l
e
d
i u
m
u
5
i
f a
5
h
min. 800 mm
m
n
5
t
5 1, 2, 3
1 2 3
1 2 3
9
1 2 3
v
o
s
r
p
1, 2, 3
v
u
4
c
u min. 500 mm
1 Heating flow with flexible connecting hose 1 2 Heating return with flexible connecting hose 1 3 Condensate drain , with flexible connecting hose Water connections (1-3): connection side is selectable, in the left or in the right (connection kit is separately enclosed for assembly by the owner) 4 Air intake (evaporator inlet). Connection directly to the aluminium frame (2 mm thick)
5 Air outlet aperture, panels demountable, outlet directions: selectable to the top, to the left or right (re-placement by the owner) 6 Outer electronic control panel with heating regulator TopTronicT/N and engage switch 7 Internal electric and terminal box with WP control device 8 Electrical connection 9 Adjustable feet, see dimension w 8 mm (dimension between axes from outside 90 mm) e2 325 325 325 325 v 110 110 110 110 f 1000 1000 1200 1200 w 35 35 35 35 g 670 670 670 670 z 150 150 150 150 i1 x 300 300 300 300 k2 830 830 930 930 y 400 400 400 400 m2 75 75 75 75 weight (kg) 410 420 440 450 n2 450 450 450 450
Type (20) (25) (30) (35) Type (20) (25) (30) (35)
1
Not applicable for Hoval Genius type (20-35) (air hose connection not possible. If no standard installation is possible, air ducting must be supplied via the air duct system to be provided by the owner). Outlet panel AP (see accessories)
Assembly Floor: select an even installation area, capable of bearing load. After the positioning the heat pump must be levelled (adjustable feet 35mm +/- 8mm). No socket is necessary for the heat pump. Provide for a condensate drain with a siphon (height approx. 100 mm) and in the direct proximity of the heat pump. The drain pipeline is to be made with sufficient incline and without change of crosssection. Evaporator cleaning must be ensured (check accessibility)
Required space, accessibility Necessary distances for assembly, operation and maintenance. Device: In front (operating and maintenance side) = 800 mm. On the left (maintenance side) min. 500 mm Outer electronic control panel: Place operating and metering friendly with short electrical wires to the heat pump. The electrical connection should be provided by a professional according to the local electric power station (EW) regulations.
432
Contents
4
h
min. 800 mm
10
5
c
d
1 2 3
9
12 3
1 2 3
10
h1
1 2 3
i
11
e
1, 2, 3
i
r
10
min. 500 mm
123
min. 500 mm
1 Heating flow with flexible connecting hose 1 2 Heating return with flexible connecting hose 1 3 Condensate drain , with flexible connecting hose Water connections (1-3): connection side is selectable, on the left, the right or down (connection kit is separately enclosed for assembly by the owner) 4 Air intake (evaporator inlet) with weather protective grills 5 Air outlet (evaporator outlet) with weather protective grills, outlet directions: selectable to the left or right Type (20) (25) (30) (35) Type (20) (25) (30) (35) l 920 920 1040 1040 k 300 300 300 300 b 1240 1240 1340 1340 m 400 400 400 400 h 1710 1710 1910 1910 n 150 150 150 150 h1(min) 300 300 300 300 r 180 180 180 180 a 1005 1005 1205 1205 Weight (kg) 445 455 480 490 c 670 670 670 670
6 Outer electronic control panel with heating regulator TopTronicT/N and engage switch for inside assembly 7 Internal electric and terminal box with WP control device 8 Electric connection 9 Adjustable feet, see dimesion d 8 mm, (dimension between axes from outside 90 mm) 10 To be done by the owner, socket or garden plate on the gravel underlay (recommended height is to be determined depending on the climate zone, minimum 300 mm) 11 Diecut opening for water connetions down 175 mm d 35 35 35 35 e 213 213 213 213 f 370 370 370 370 g 527 527 527 527 i 110 110 110 110
Assembly Select an even installation area, capable of bearing load (e.g. concrete socket). After the placement the heat pump must be levelled (adjustable feet 35mm +/- 8mm). The socket height for the heat pump is to be determined depending on the climate zone (snow height). The water pipelines must be connected to the condenser frost proof (by the owner). Condensate must be able to run off freely and not freeze. Required space, accessibility Necessary distances for assembly, operation and maintenance. Device: In front (operating and maintenance side) = 800 mm. On the left (maintenance side) = 500 mm Subject to alterations, 1.6.2006
Outer electronic control panel For inside assembly. Place operating and metering friendly with short electrical wires to the heat pump. The electrical wires should be provided by a professional according to the local electric power station (EW) regulations.
Air supply Distances necessary for air intake and outlet. Intake (behind, opposite the front side) Min. distance between protective grills and external wall = 500 mm Outlet (selectable, left or right) Min. distance to the wall 2000 mm
Front side Heat pump Heat pump Electronic control panel Inside
Front side
Contents
433
(20)
P kW 6,9 6,7 6,6 6,3 6,3 6,3 6,2 6,0 5,9 5,8 5,6 7,3 7,2 7,0 6,7 6,7 6,7 6,6 6,4 6,3 6,2 6,0 7,6 7,6 7,4 7,1 7,1 7,1 7,0 6,8 6,7 6,6 6,3 8,0 8,1 7,7 7,5 7,5 7,5 7,4 7,2 7,1 6,9 4,7 4,4 4,2 3,6 3,3 3,2 3,1 2,9 2,8 2,7 2,5 4,3 4,1 3,8 3,4 3,1 3,0 2,9 2,7 2,6 2,5 2,3 4,0 3,9 3,5 3,1 2,9 2,8 2,7 2,5 2,4 2,3 2,2 3,7 3,6 3,2 2,9 2,7 2,6 2,5 2,4 2,3 2,2 COP QWP kW 41,5 38,5 35,5 29,9 27,7 26,2 25,3 23,5 22,2 21,0 19,3 40,5 38,5 34,6 29,8 27,6 26,1 25,3 23,5 22,2 21,0 19,0 39,5 38,5 33,7 29,6 27,5 26,0 25,2 23,5 22,3 21,0 19,4 47,5 44,0 39,1 36,1 33,7 32,1 31,1 29,1 27,6 26,1
(25)
P kW 7,6 7,6 7,7 7,7 7,8 7,8 7,8 7,9 7,9 7,9 8,0 8,4 8,5 8,5 8,5 8,6 8,6 8,6 8,7 8,7 8,7 8,8 9,2 9,3 9,3 9,3 9,4 9,5 9,5 9,5 9,5 9,5 9,5 10,0 10,1 10,1 10,1 10,2 10,3 10,3 10,3 10,3 10,3 5,5 5,0 4,6 3,9 3,6 3,4 3,2 3,0 2,8 2,6 2,4 4,8 4,5 4,1 3,5 3,2 3,0 2,9 2,7 2,6 2,4 2,2 4,3 4,1 3,6 3,2 2,9 2,8 2,7 2,5 2,3 2,2 2,0 3,8 3,8 3,3 2,9 2,7 2,5 2,4 2,3 2,2 2,1 COP QWP kW 51,5 47,8 44,0 36,6 34,2 32,6 31,4 29,1 27,4 25,8 23,7 50,2 46,5 42,4 36,4 34,0 32,4 31,3 29,1 27,5 25,9 23,4 48,8 45,3 40,7 36,3 33,8 32,2 31,2 29,1 27,5 26,0 23,9 41,8 39,2 34,2 31,1 29,5 28,6 27,8 26,4 25,4 24,3
(30)
P kW 9,9 9,8 9,8 9,7 9,8 9,9 9,9 9,9 10,0 10,0 10,0 10,9 10,9 10,8 10,7 10,9 11,0 11,0 11,0 11,0 11,0 11,0 11,9 11,9 11,8 11,7 11,9 12,0 12,0 12,0 12,1 12,1 12,1 12,9 13,0 12,8 12,8 13,0 13,1 13,1 13,1 13,1 13,1 5,2 4,9 4,5 3,8 3,5 3,3 3,2 2,9 2,8 2,6 2,4 4,6 4,3 3,9 3,4 3,1 3,0 2,9 2,6 2,5 2,4 2,1 4,1 3,8 3,4 3,1 2,8 2,7 2,6 2,4 2,3 2,2 2,0 3,7 3,4 3,0 2,8 2,6 2,5 2,4 2,2 2,1 2,0 COP QWP kW 55,0 51,4 47,0 39,0 36,2 34,4 33,1 30,6 28,7 27,0 24,6 53,5 50,7 45,5 38,6 35,9 34,1 32,9 30,4 28,5 26,8 23,9 52,0 50,3 44,0 38,3 35,6 33,8 32,6 30,2 28,4 26,6 24,2 50,5 50,0 42,5 38,0 35,3 33,5 32,3 30,0 28,2 26,4
(35)
P KW 10,9 10,7 10,5 10,2 10,1 10,1 10,0 9,8 9,6 9,4 9,1 11,6 11,5 11,2 10,9 10,9 10,8 10,7 10,5 10,3 10,1 9,8 12,3 12,3 11,9 11,6 11,6 11,5 11,4 11,2 11,0 10,8 10,4 13,1 13,2 12,7 12,4 12,3 12,3 12,1 11,9 11,6 11,4 5,0 4,8 4,5 3,8 3,6 3,4 3,3 3,1 3,0 2,9 2,7 4,6 4,4 4,1 3,5 3,3 3,1 3,1 2,9 2,8 2,7 2,4 4,2 4,1 3,7 3,3 3,1 2,9 2,9 2,7 2,6 2,5 2,3 3,9 3,8 3,4 3,1 2,9 2,7 2,7 2,5 2,4 2,3 COP
heating ow temperature (C) outdoor temperature (C) heat output incl. defrosting loss (kW) power consumption of the whole device (kW) performance of the whole device
434
Contents
Heat output (Qmom ) = f x QWP Example Type Hoval Genius (20) QA2W35 20,4 Q A-10W45 17,5 f35 = 1,0503 Qmom A2W35 21,43 f45 = 1,0417 (because of interpolation f35= 1,045 und f50= 1,04) Qmom A-10W45 18,23
m3 /h
Contents
435
Standard 2
45
45
7
min. 500 mm
min. 800 mm
6 5 4
min. 800 mm
2 1
7
45
min. 500 mm
Operation and maintenance surface
45
Standard 3
45
Operation and maintenance surface
Standard 4
45
min. 500 mm
1 2
3
min. 800 mm
4 5 6
Heat pump type Genius
min. 500 mm
min. 800 mm
45
45
3
Application
1
Accessories Type (20) Art.Nr.
6
(35) Art.Nr. 7002 567 2017 517 2018 988 2018 997 2017 519 2018 987 2019 002
Heat pump Genius Type (25) (30) Art.Nr. Art.Nr 7002 565 2017 519 2018 987 2018 996 2017 518 2018 992 2019 001 7002 566 2017 517 2018 988 2018 997 2017 519 2018 987 2019 002
Heat pump Inside installation 7002 564 1 Wall fastener Intake WAE1 2017 519 2 Wall insulation Intake MI-AF1 2018 987 3 Weather protective grills Intake WG-MI1 2018 996 4 Wall fastener Outlet WAE2 2017 518 5 Wall insulation Outlet MI-AF2 2018 992 6 Weather protective grills Outlet WG-MI2 2019 001 7 Condensate drain (provided by the owner, siphon height approx. 100 mm) 436
Contents
Standard 6
7
Heat pump, type Genius
45
45
6 5 4
min. 800 mm
min. 500 mm
min. 800 mm
2 1
7
45
45
Standard 7
45
Standard 8
1 2
3
min. 500 mm
45
min. 800 mm
min. 800 mm
min. 500 mm
4 5 6
Heat pump, type Genius
45
45
4
Accessories Type
1
(20) Art.Nr.
3
Heat pump Genius Type (25) (30) Art.Nr. Art.Nr 7002 565 2017 519 2018 987 2018 996 2017 518 2018 992 2019 001 7002 566 2017 517 2018 988 2018 997 2017 519 2018 987 2019 002 (35) Art.Nr. 7002 567 2017 517 2018 988 2018 997 2017 519 2018 987 2019 002
Application
Heat pump Inside installation 7002 564 1 Wall fastener Intake WAE1 2017 519 2 Wall insulation Intake MI-AF1 2018 987 3 Weather protective grills Intake WG-MI1 2018 996 4 Wall fastener Outlet WAE2 2017 518 5 Wall insulation Outlet MI-AF2 2018 992 6 Weather protective grills Outlet WG-MI2 2019 001 7 Condensate drain (provided by the owner, siphon height approx. 100 mm) Subject to alterations, 1.6.2006
Contents
437
3 1 2
e
c
a
e
a
c
e
d
e
d
d
45
mi n 50 . 0
ca 20 . 0
0 10
45
45
10
. ca 0 20
g
n. mi 0 50
45
0 80 n. mi
mi
n. 80 0
a 1110 1210
b 910 1110
c 790 910
d 750 750
e 90 90
f 880 1000
g 1200 1300 Heat pump Hoval Genius Type (25) Type (30) Type (35) Art.Nr. Art.Nr. Art.Nr. 7002 565 2017 519 2018 987 2018 996 2017 518 2018 992 2019 001 7002 566 2017 517 2018 988 2001 997 2017519 2018 987 2019 002 7002 567 2017 517 2018 988 2018 997 2017 519 2018 987 2019 002
Accessories Type 1 Heat pump Intake 2 Wall fastener 3 Wall insulation (25 mm) 4 Weather protective grills
Outlet 5 Wall fastener WAE2 2017 518 6 Wall insulation (25 mm) MI-AF2 2018 992 7 Weather protective grills WG-MI2 2019 001 8 Condensate drain (provided by the owner, siphon height approx. 100 mm)
438
Contents
min. 800 mm
a
g f
c f
Plan view
4
min. 800 mm
min. 500 mm
4 4
d
h
7
5 5
6
i
1, 2, 3
c
1, 2, 3
1 2 3
c f
1 Heating flow with flexible connecting hose 1 2 Heating return with flexible connecting hose 1 3 Condensate drain , with flexible connecting hose Water connections: connection side is selectable, in the left or in the right (connection kit is separately enclosed for assembly by the owner) 4 Air intake aperture, intake directions selectable, from the top, from the left or right.
5 Air outlet aperture, outlet directions selectable, to the top, to the left or right (replacement by the owner) 6 Intake box 7 Internal electric and terminal box with WP control device 8 Condensate drain (provided by the owner, siphon height approx. 100 mm)
g 75 75 75 75
Contents
439
70
70
c e
70
For recesses with Hoval wall insulation type MIAF1 (intake) or MI-AF2 (outlet). If provided by the owner, pay attention that the thermal insulation should be 25 mm thick! The recesses should be provided by a technician! The recesses dimensions are intermediate space from the ready floor!
f
b
70
g
g 63 63 63 63
440
Contents
6
min. 2000 mm
min. 500 mm
min. 2000 mm
Maintenance surface
1 2 3
1 2 3 min.
Operation surface
14
7 8 1 2 3
min. 800 mm
10
1 2 3
500 mm
10
1 2 3
12 11
Connections pipe (1,2) and condensate drain (3) with electric trace heating frost protected.
11
1 Heating flow 1 with flexible connecting hose 2 Heating return1, with flexible connecting hose 3 Condensate drain , with flexible connecting hose. Water connections (1-3): connection side is selectable, left or right (connection kit is separately enclosed for assembly by the customer) frost protected ! The pipelines must be connected thermally insulated and frost protected ! (e.g. self-doped electric trace heating) Air intake (evaporator inlet) with weather protective grills Air blow (evaporator outlet) with weather protective grills (Blow directions is selectable to the left or right). Device roof Internal electric and terminal box with WP control device Electrical connection.
4 5 6 7 8
9 Adjustable feet 25 mm ( 8 mm) (dimension between axes from outside 90 mm) 10 To be provided by the customer, socket or garden plate on the gravel underlay (the height is to be determined depending on the climate zone, recommended minimum height 300 mm), 11 Condensate drain (siphon height = approx. 100 mm), provided by the customer Frost protected drain must be provided! 12 Casing tube with incline and packing (by the customer) 13 Outer electronic control panel with heating regulator TopTronicT/N and engage switch for inside assembly 14 Electrical connection cables (by the customer)
13
Installation The Hoval Genius air/water heat pump will The installation place should not be situated Condensate pipeline be assembled outdoors. The installation place under the living room or bedroom becauCondensate must be able to run off freely and must be carefully selected. The following se of sound emission and be placed at not freeze (frost protected drain, recommended boundary conditions should be obligatory kept: sufficient distance from the neighbouring siphon height approx. 100 mm) The installation place should be determined building. in such a way that air intake and outlet is not Is not recommended to install the heat pump Wall lead through hampered or obstructed by snow, leaves etc. into wall niches (air short-circuit, sound Wall lead through for pipelines must be imple There should be provided sufficient space echo) mented and sealed by technicians. for intake and outlet as well as for operation and maintenance. Heating connections and pipelines Outer electronic control panel Air short-circuit must be avoided. The space The pipelines for outdoors (flow and return) Should be installed only inside (room tempenecessary for intake and outlet must be should be selected as short as possible. rature min. +5 C, max. 40C) always provided. The minimum distances The pipelines outdoors and the conden Electric connection cables should be selecapply only to the indicated example. Under ser should be professionally installed with ted short, connected flexibly be professionalunfavourable conditions (e.g. air short-circuit thermal insulation and antifreeze agent (e.g. ly routed according to local rules. because of wind influence) the heat pump self-doped electric trace heating). should be provided with a bilateral outlet. Deaeration and emptying of the heat pump Intake air must be completely free from agmust be ensured. gressive substances like ammonia, sulphur, chlorine etc. Heat pump Type Hoval Genius Accessories Type (20) Type (25) Type (30) Type (35) Art.Nr. Art.Nr. Art.Nr. Art.Nr. Heat pump Kit for outside installation Included into AS kit: Device roof Intake weather protective grills Outlet weather protective grills Subject to alterations, 1.6.2006 AS Pos.6 Pos.4 Pos.5 7000 572 6009 144 2017 532 2017 534 2017 536 7002 573 6009 144 2017 532 2017 534 2017 536 7002 574 6009 145 2017 533 2017 535 2017 537 7002 575 6009 145 2017 533 2017 535 2017 537 441
Contents
442
Contents
Thermalia - series Type (5P) (7P) (8P) Working medium R407C R407C R407C Nominal heat output Flow B0W35 / W10W35 max. C kW 55 55 55 55 55 55 55 55 55 55 55 55 55 65 65 65 65 65 65 65 65 65 65 65 5,4 6,8 8,3 9,7 12,0 15,0 16,9 19,4 21,9 24,2 27,9 34,4 41,8 5,2 6,1 7,4 9,3 10,9 12,5 14,0 16,6 19,3 23,0 29,0 6,9 8,7 10,5 12,3 15,3 19,4 21,5 24,7 27,9 32,5 37,4 46,4 56,3 6,8 8,0 9,6 12,1 14,1 16,2 18,2 21,6 25,1 29,9 37,7
(10P) R407C (12P) R407C (15P) R407C (17) (19) (22) (26) (30) (37) (45) (8HP) (10HP) (12HP) (15HP) R407C R407C R407C R407C R407C R407C R407C R134a R134a R134a R134a
(17H) R134a (19H) R134a (22H) R134a (26H) (30H) (37H) (45H) R134a R134a R134a R134a
Authorizations Switzerland / Germany / Austria test No. WPZ Thermalia 8 test No. WPZ Thermalia 8H Thermalia 15 test No. WPZ Thermalia 15H test No. WPZ test No. WPZ Thermalia 8 Thermalia 8H test No. WPZ test No. WPZ Thermalia 15 Thermalia 15H test No. WPZ Examined by heat pump testing center (WPZ)
The Thermalia (5-30) or (8H-45H) series is certified by the seal of approval of the authorization commission of Switzerland Subject to alterations, 1.6.2006
Contents
443
Part N
Euro
Hoval Thermalia
Working medium R407c Flow temperature max. 55C Regulator Type Heat source Heat output and B0W35/W10W35 heating pump kW installed installed installed installed installed installed without without without ohne ohne ohne ohne 5,4 6,8 8,3 9,7 12,0 15,0 16,9 19,4 21,9 24,2 27,9 34,4 41,8 6,9 8,7 10,5 12,3 15,3 19,4 21,5 24,7 27,9 32,5 37,4 46,4 56,3 7002 682 7002 683 7002 684 7002 685 7002 686 7002 687 7002 688 7002 689 7002 690 7002 691 7002 692 7002 693 7002 694 6.055,00 6.125,00 6.401,00 7.265,00 7.501,00 8.013,00 8.349,00 8.525,00 9.374,00 10.246,00 11.538,00 16.147,00 17.677,00
Type
(5P) TopTronic T/N (7P) TopTronic T/N (8P) TopTronic T/N (10P) TopTronic T/N (12P) TopTronic T/N (15P) TopTronic T/N (17) TopTronic T/N (19) TopTronic T/N (22) TopTronic T/N (26) (30) (37) (45) TopTronic T/N TopTronic T/N TopTronic T/N TopTronic T/N
Hoval Thermalia -H
Working medium R134a Flow temperature max. 65C Regulator Type Heat source Heat output and B0W35/W10W35 heating pump kW installed installed installed installed without without without without without without without 5,2 6,1 7,4 9,3 10,9 12,5 14,0 16,6 19,3 23,0 29,0 6,8 8,0 9,6 12,1 14,1 16,2 18,2 21,6 25,1 29,9 37,7 7002 695 7002 696 7002 697 7002 698 7002 699 7002 700 7002 701 7002 702 7002 703 7002 704 7002 705 6.401,00 7.265,00 7.501,00 8.013,00 8.349,00 8.525,00 9.374,00 10.246,00 11.538,00 16.147,00 17.677,00
Type
(8HP) TopTronic T/N (10HP) TopTronic T/N (12HP) TopTronic T/N (15HP) TopTronic T/N (17H) TopTronic T/N (19H) TopTronic T/N (22H) TopTronic T/N (26H) (30H) (37H) (45H) TopTronic T/N TopTronic T/N TopTronic T/N TopTronic T/N
Necessary accessories
for Type (8-22) or (8H-22H) Start-up current limiter Model ASB-E Electronic start-up current limiter for Thermalia Models 8-22 or 8H-22H, incl. installation costs. (Not necessary for model 5-7; built-in as standard in models 26-45 and 26H-45H) 444
2015 236
652,00
Contents
Part N
Euro
2004 481
295,00
2022 216
226,00
6013 113
252,00
Flow switch F61 TB-9100 Protection class IP 67 to heat source Ground water, operating range -30/85C
2004 483
470.
Frost protection temperature switch 270XT-95068 Protection class IP 40 to heat source Ground water, operation range -24/18C
2007 313
310.
Accessories for water heating only for model 8H-15H Changeover valve EMV 110F3L-1 for DHW loading M -WPHA-1c/1d-WW Changeover valve EMV 110F3L-1 for DHW loading M -WPHA-1c/1d-WW Cable sensor KVT20/5/6 for DHW loading M -WPHA-1c-WW Flow temperature sensor VF202K for DHW loading M -WPHA-1d-WW 2015 626 169,00
2006 302
181,00
2022 992
31,00
6012 595
31,00
Contents
445
Part N
Euro
1-7
Standard functions already included in TopTronicT. - 1 mixing circuit - 1 heating circuit without mixing operation - Domestic hot water loading circuit
Functions of key modules Key 2. mixing solar module circuit
1 3 5
1
M
Key Module 1 for 2. mixing circuit Function key 1, 1 flow sensor, 2 loose plugs Key Module 3 for solar plants Function key 3, 1 collector sensor, 1 calorifier sensor, 4 loose plugs Key Module 5 for 2. mixing circuit and solar plants Function key 5, 1 flow sensor, 1 collector sensor, 1 calorifier sensor, 6 loose plugs
6012 154
220,00
6012 156
190,00
5
M
6012 158
390,00
For systems solutions and applications see Hoval CDROM or visit www.hoval.ch Room station RS-T effective on mixing circuit with room sensor, information, program and correction keys. Remote control RFF-T effective on one mixing circuit with room sensor, simple program key and temperature adjustment Outdoor temperature sensor AF200 Flow temperature sensor VF202K for M-WPHA-1d not necessary Cable sensor KVT20/5/6 for M-WPHA-1a 2 pieces necessary Immersion sleeve for cable sensor SB280 " - 280 mm, nickel-plated brass for M-WPHA-1a 2 pieces necessary Collector sensor PT1000 446
2022 237
210,00
115,00 31,00
31,00 31,00
17,00 31,00
Contents
Part N
Euro
auf Anfrage
Contents
447
dm Rp
0,8/1,3 1
Plate heat exchanger Stainless steel V4A, AISI 316, 1,4401 1/1,3 1,3/1,3 1,3/1,6 1,6/1,8 1 1 1 1
1,6/2,4 1
m3/h kPa K m3/h kPa K m3/h kPa K m3/h kPa K bar bar
C C C C C C
Brine or water -5/15 bzw, 8/15 -8/12 bzw, 4/12 5/40 -15/50
Electrical data Compressor Operating current (max.) Blocking current (LRA) Starting current without jump start2 Starting current with jump start2 Voltage Frequency Voltage range
1 2
A A A A V Hz V
4,2 24 17,5 -
5,1 32 23 -
7 46 33 16,5
10 50 36 18
12,4 66 47 23,5
kW = Standard values according to AWP; Values for B0W35 with 25 % ethylene glycol (Antifrogen N) Effective value
448
Contents
dm Rp
2,1/2,4 11/4
Plate heat exchanger Stainless steel V4A, AISI 316, 1,4401 2,4/2,9 2,9/3,2 2,9/4,2 3,4/5 11/4 11/2 11/2 11/2
5/5,6 2
5/6,2 2
m3/h kPa K m3/h kPa K m3/h kPa K m3/h kPa K bar bar
2,97 9,5 7 5,63 16,5 3 4,0 17,0 7 4,6 9,9 5 6 30 Water 15/45 25/55 Brine or water -5/15 bzw, 8/15 -8/12 bzw, 4/12 5/40 -15/50
C C C C C C
Electrical data Compressor Operating current max. Blocking current (LRA) Starting current without jump start2 Starting current with jump start2 Voltage Frequency Voltage range
1 2
A A A A V Hz V
13,5 74 53 27
16 101 71 36
15,1 99 70 35
20,7 127 90 45
25 167 118 59
kW = Standard values according to AWP; Values for B0W35 with 25 % ethylene glycol (Antifrogen N) Effective value
Contents
449
dm Rp
1,3/1,3 1
Plate heat exchanger Chromstahl V4A, AISI 316, 1,4401 1,3/1,6 1,6/1,8 1 1
1,6/2,4 1
m3/h kPa K m3/h kPa K m3/h kPa K m3/h kPa K bar bar
0,95 4,9 7 1,1 2,5 5 6 30 Water2 15/55 25/65 Brine or water -5/15 bzw, 8/15 -8/12 bzw, 4/12 5/40 -15/50
C C C C C C
Electrical data Compressor Operating current max. Blocking current (LRA) Starting current without jump start3 Starting current with jump start3 Voltage Frequency Voltage range
1 2
A A A A V Hz V
4,4 40 25 12,5
5,9 50 36 18
7,4 66 47 23,5
kW = Standard values according to AWP; Values for B0W35 with 25 % ethylene glycol (Antifrogen N) Limit values during operation as indicated in performance data table 3 Effective value
450
Contents
dm Rp
2,1/2,4 11/4
2,4/2,9 11/4
Plate heat exchanger Stainless steel V4A, AISI 316, 1,4401 2,9/3,2 2,9/4,2 3,4/5 11/2 11/2 11/2
5/5,6 2
5/6,2 2
m3/h kPa K m3/h kPa K m3/h kPa K m3/h kPa K bar bar
2,1 4,5 7 4,0 9,1 3 2,6 7,2 7 3,0 4,6 5 6 30 Water2 15/55 25/65 Brine or water -5/15 -8/12 5/40 -15/50
C C C C C C
Electrical data Compressor Operating current max. Blocking current (LRA) Starting current without jump start3 Starting current with jump start3 Voltage Frequency Voltage range
1 2
A A A A V Hz V
8,2 74 53 27
10 101 71 36
11,4 99 70 35
15 127 90 45
kW = Standard values according to AWP; Values for B0W35 with 25 % ethylene glycol (Antifrogen N) Limit values during operation as indicated in performance data table 3 Effective value
Contents
451
(5)
(7)
(8)
(10)
(12)
(15)
(17)
(19)
(22)
(26)
(30)
(37)
(45)
34
34
34
35
35
38
46
47
50
52
52
55
58
Sound pressure level, distance 1m (in standard room with approx. 5-6 dB (A) sound absorption)
Data for electric power station (EW) and electrician Type Thermalia (5P) (7P) (8/8HP) (10/10HP) (12/12HP) (15/15HP) (17/17H) (19/19H) (22/22H) (26/26H) (30/30H) (37/37H) (45/45H)
2 3
Compressor power consumption2 PNT (kW) B0W35 W10W35 1,22 1,54 1,8/1,15 2,1/1,29 2,63/1,53 3,26/1,97 3,6/2,29 4,1/2,64 4,88/3,12 5,88/3,7 6,75/4,27 8,05/5,1 10,2/6,8 1,20 1,50 1,79/1,14 2,12/1,32 2,7/1,58 3,39/2,02 3,74/2,33 4,28/2,7 5,10/3,19 6,12/3,77 7,02/4,35 8,37/5,18 10,6/6,87
Operating current Blocking current I max. (LRA) A A 4,2 5,1 6,2/4,4 7/4,8 10/5,9 12,4/7,4 13,5/8,2 16/10 15,1/11,4 18/13 20,7/15 25/18,2 29,8/20,7 24 32 40 46 50 66 74 101 99 123 127 167 198
Protection A 13 T 13 T 16 T 16 T 16 T 16 T 25 T 25 T 32 T 32 T 32 T 40 T 40 T
Starting current3 without/with jump start A 17,5/n,r 23/n,r 25/12,5 33/16,5 36/18 47/23,5 53/27 71/36 70/35 87/43 90/45 118/59 141/71
Execution with heating and heat source pump Installations comprising a ground heat exchanger for applications according to block diagram M-WPHA-1c or M-WPHA-WW-1c(8HP-15HP) Heat pump Thermalia Heating pump 230V/50Hz Installation place Nominal volume ow (water) T Discharge head Power consumption P Condenser P available external Heat source pump 230V/50Hz Installation place Nominal volume ow (EthGly25%/water75%) T Discharge head Power consumption P Evaporator P available external Typ Typ m3/h K kPa W kPa kPa Typ m3/h K kPa W kPa kPa 5P MX12-1 0,77 6 33,5 70 8,5 25 M14 1,28 3 52,6 156 10,3 42,3 7P 8P/8HP 10P/10HP 12P/12HP MX12-1 1,72/1,34 6/5 26,4/29,4 77/74 9,4/5,7 17/23,7 M15 2,87/1,8 3 55,6/63,7 224/196 14,4/5,7 41,2/58 15P/15HP MX13-1 2,09/1,71 6/5 35,4/38,3 114/111 13,9/9,3 21,5/29 M15 3,5/2,3 3 50,2/60,1 232/206 12,7/5,5 37,5/54,6
MX12-1 MX12-1 MX12-1 Condenser-discharge (Flow) 0,98 1,18/0,98 1,38/1,12 6 6/5 6/5 31,8 31/31,8 29,5/30,9 72 74/72 75/74 8,8 23 7,6/5,2 23,4/26,6 10,4/6,8 19,1/24,1
M14 M14 M15 Evaporator inlet (Heat source inlet) 1,62 1,97/1,3 2,3/1,5 3 3 3 51 49,1/52,6 60,1/65,6 156 167/156 206/185 9,6 41,4 14,2/6,2 34,9/46,4 11,7/5 48,4/60,6
452
Contents
Thermalia
Hoval
operation side
1 2 3 4 Type 5-19 and 8H-19H Heat source - discharge type 5-15 or 8H-15H R1, 17-19 or 17H-19H R1 Heat source - Inlet type 5-15 or 8H-15H R1, 17-19 or 17H-19H R1 Heating supply type 5-15 or 8H-15H R1, 17-19 or 17H-19H R1 Heating return type 5-15 or 8H-15H R1, 17-19 or 17H-19H R1 a 550 b 750 h 1045 h1 975 c 405 d 320 e 175
5 6 7 8 f 90
Operating panel with TopTronic controller Vibration damping, adjustable feet +/- 8mm Openings on both sides for water connections Electrical connection g 125 i 640 k 880 l 25 m 95
Hoval
Thermalia
1 2 3 4 Heat source - discharge type 22-30 or 22H-30H R1, 37-45 or 37H-45H R2 Heat source - Inlet type 22-30 or 22H-30H R1, 37-45 or 37H-45H R2 Heating supply type 22-30 or 22H-30H R1, 37-45 or 37H-45H R2 Heating return type 22-30 or 22H-30H R1, 37-45 or 37H-45H R2 a 700 700 700 b 750 750 1000 h 1195 1195 1275 h1 1125 1125 1205 c 1100 1100 1180 d 170 170 190 e 635 635 705 f 995 995 1075
5 Operating panel with TopTronic controller 6 Vibration damping, adjustable feet +/- 8mm 7 Electrical connection
g 55 55 60
l 25 25 105
Required space (required wall distance in mm for operation and maintenance) Type front rear right or left side 5-19 and 8H-19H 22-45 and 22H-45H min. 800 min. 800 min. 500 min. 500 min. 500
Contents
453
Brine (Sole) 30
4,34 4,84 5,19 5,46 5,84 6,63 6,79 6,94 7,15 3,65 4,07 4,35 4,60 4,96 5,51 5,70 5,88 6,15 3,14 3,49 3,74 3,96 4,29 4,69 4,89 5,09 5,37 2,75 3,06 3,27 3,46 3,77 4,08 4,27 4,47 4,76 2,44 2,71 2,89 3,07 3,35 3,60 3,79 3,97 4,26
4,36 4,87 5,22 5,49 5,87 6,55 6,83 7,10 7,49 3,67 4,09 4,38 4,62 4,98 5,47 5,73 5,98 6,35 3,16 3,51 3,76 3,98 4,31 4,69 4,92 5,15 5,48 2,76 3,07 3,28 3,48 3,79 4,09 4,30 4,51 4,82 2,45 2,72 2,91 3,09 3,36 3,61 3,81 4,00 4,28
4,40 4,94 5,31 5,63 6,11 6,55 6,93 7,33 7,92 3,70 4,14 4,45* 4,72 5,13* 5,50 5,81* 6,13 6,61* 3,18 3,56 3,82 4,05 4,41 4,73 4,99 5,25 5,65 2,79 3,11 3,33 3,54 3,85 4,13 4,36 4,58 4,92 2,48* 2,76 2,95* 3,13 3,41* 3,66 3,86* 4,05 4,34*
Water
Brine (Sole) 35
Water
Brine (Sole) 40
Water
Brine (Sole) 45
Water
Brine (Sole) 50
Water
Performance data
Q P COP t1 tVL = = = = Heat output (kW) Power consumption (kW) Performance Heat source (evaporator) Inlet temperature (C) = Discharge temperature (Heating supply ow) at condenser (C) Heat source Medium T Water/frost protection* 75% 100% 100% 25% -
454
Contents
Brine (Sole) 30
4,55 4,95 5,21 5,53 6,00 6,51 6,81 7,11 7,55 3,91 4,23 4,45 4,70 5,09 5,38 5,65 5,91 6,30 3,42 3,69 3,86 4,08 4,40 4,57 4,81 5,04 5,39 3,03 3,25 3,40 3,58 3,86 3,96 4,17 4,38 4,69 2,71 2,90 3,02 3,18 3,42 3,48 3,67 3,86 4,14
4,58 4,98 5,25 5,57 6,05 6,44 6,74 7,04 7,48 3,93 4,26 4,48 4,74 5,13 5,36 5,63 5,89 6,28 3,44 3,71 3,89 4,11 4,43 4,57 4,81 5,05 5,40 3,05 3,27 3,42 3,61 3,89 3,98 4,19 4,40 4,71 2,73 2,92 3,04 3,21 3,45 3,51 3,70 3,88 4,17
4,67 5,07 5,34 5,63 6,08 6,43 6,73 7,02 7,45 4,01* 4,34 4,55* 4,80 5,17* 5,41 5,67* 5,93 6,31* 3,51 3,77 3,95 4,16 4,48 4,64 4,87 5,11 5,45 3,11 3,33 3,47 3,66 3,94 4,04 4,25 4,47 4,78 2,78* 2,97 3,09* 3,26 3,50* 3,57 3,76* 3,95 4,24*
Water
Brine (Sole) 35
Water
Brine (Sole) 40
Water
Brine (Sole) 45
Water
50
Brine (Sole)
Water
Performance data
Q P COP t1 tVL = = = = Heat output (kW) Power consumption (kW) Performance Heat source (evaporator) Inlet temperature (C) = Discharge temperature (Heating supply ow) at condenser (C) Heat source Medium T Water/frost protection* 75% 100% 100% 25% -
Contents
Brine (Sole) 30
4,75 5,16 5,44 5,75 6,21 6,39 6,71 7,04 7,52 4,08 4,42 4,64 4,90 5,28 5,40 5,69 5,97 6,39 3,57 3,85 4,03 4,25 4,58 4,67 4,91 5,16 5,53 3,16 3,40 3,55 3,74 4,02 4,09 4,31 4,53 4,86 2,83 3,03 3,16 3,33 3,57 3,64 3,83 4,03 4,32
4,77 5,20 5,48 5,78 6,25 6,42 6,75 7,08 7,56 4,10 4,45 4,67 4,93 5,31 5,44 5,72 6,00 6,42 3,59 3,87 4,06 4,28 4,61 4,69 4,94 5,19 5,56 3,18 3,42 3,57 3,76 4,05 4,12 4,34 4,56 4,89 2,85 3,05 3,18 3,34 3,60 3,66 3,85 4,05 4,35
4,52 4,92 5,19 5,48 5,92 6,09 6,40 6,71 7,16 3,89 4,21 4,42 4,67 5,03 5,15 5,42 5,69 6,08 3,40 3,67 3,84 4,05 4,36 4,45 4,68 4,92 5,27 3,01 3,24 3,38 3,56 3,83 3,90 4,11 4,32 4,63 2,70 2,89 3,01 3,17 3,41 3,47 3,65 3,84 4,12
Water
Brine (Sole) 35
Water
Brine (Sole) 40
Water
Brine (Sole) 45
Water
Brine (Sole) 50
Water
Performance data
Q P COP t1 tVL = = = = Heat output (kW) Power consumption (kW) Performance Heat source (evaporator) Inlet temperature (C) = Discharge temperature (Heating supply ow) at condenser (C) Heat source Medium T Water/frost protection* 75% 100% 100% 25% -
456
Contents
Brine (Sole) 30
3,96 4,42 4,62 4,91 5,40 5,92 6,28 6,50 6,99 3,51 3,87 4,07 4,30 4,71 5,14 5,46 5,63 6,02 3,12 3,41 3,56 3,77 4,07 4,48 4,73 4,87 5,25 2,70 2,95 3,08 3,22 3,50 3,81 4,01 4,12 4,44 2,51 2,69 2,80 2,93 3,17 3,43 3,62 3,72 3,98
4,05 4,48 4,71 4,98 5,47 5,98 6,40 6,61 7,06 3,59 3,94 4,10 4,35 4,79 5,23 5,54 5,72 6,10 3,17 3,47 3,62 3,82 4,13 4,54 4,78 4,94 5,31 2,75 2,98 3,10 3,26 3,54 3,85 4,05 4,17 4,48 2,57 2,74 2,83 2,96 3,20 3,47 3,64 3,73 3,81
4,03 4,47 4,68 4,91 5,39 5,91 6,21 6,41 6,80 3,57 3,92 4,10 4,32 4,69 5,15 5,46 5,55 6,00 3,16 3,45 3,59 3,77 4,08 4,48 4,68 4,86 5,23 2,72 2,95 3,08 3,22 3,48 3,78 3,98 4,08 4,38 2,50 2,69 2,79 2,92 3,15 3,42 3,58 3,69 3,93
4,07 4,52 4,74 5,03 5,49 5,98 6,32 6,45 6,88 3,57 3,96 4,14 4,40 4,80 5,26 5,52 5,68 6,08 3,15 3,47 3,62 3,81 4,12 4,51 4,78 4,94 5,34 2,73 2,97 3,08 3,23 3,51 3,82 4,00 4,14 4,45 2,51 2,71 2,81 2,93 3,18 3,43 3,60 3,73 4,00
Water
Brine (Sole) 35
Water
Brine (Sole) 40
Water
Brine (Sole) 45
Water
Brine (Sole) 50
Water
Performance data
Q P COP t1 tVL = = = = Heat output (kW) Power consumption (kW) Performance Heat source (evaporator) Inlet temperature (C) = Discharge temperature (Heating supply ow) at condenser (C) Heat source Medium T Water/frost protection* 75% 100% 100% 25% -
Contents
35
-5 -2 0 2 5 10 15 -5 -2 0 2 5 10 15 -5 -2 0 2 5 10 15 -5 -2 0 2 5 10 15 -5 -2 0 2 5 10 15 -2 0 2 5 10 15
4,37* 4,86 5,20* 5,51 5,98* 6,78* 7,77* 4,31 4,81 5,14 5,46 5,93 6,68 7,69 4,25 4,76 5,09 5,41 5,88 6,58 7,62 4,19* 4,70 5,04* 5,36 5,83* 6,48* 7,54* 4,07 4,61 4,98 5,30 5,77 6,42 7,43 4,53 4,92 5,24 5,71 6,36 7,33
1,18* 1,18 1,18* 1,17 1,16* 1,15* 1,15* 1,34 1,33 1,33 1,32 1,32 1,32 1,32 1,51 1,49 1,48 1,48 1,48 1,48 1,49 1,67* 1,65 1,63* 1,63 1,63* 1,65* 1,66* 1,85 1,83 1,82 1,83 1,84 1,84 1,86 2,02 2,01 2,02 2,04 2,04 2,06
3,71* 4,14 4,42* 4,71 5,14* 5,89* 6,76* 3,21 3,61 3,87 4,12 4,49 5,07 5,83 2,82 3,19 3,44 3,66 3,98 4,44 5,11 2,51* 2,85 3,09* 3,28 3,57* 3,93* 4,54* 2,19 2,52 2,74 2,90 3,14 3,48 3,99 2,24 2,45 2,59 2,80 3,12 3,55
5,23 5,76 6,12 6,50 7,07 7,96 9,03 5,13 5,69 6,06 6,44 7,00 7,85 8,93 5,03 5,61 6,00 6,37 6,93 7,74 8,83 4,93 5,54 5,94 6,31 6,86 7,63 8,74 4,79 5,44 5,87 6,24 6,80 7,55 8,63 5,34 5,81 6,18 6,73 7,46 8,52
1,31 1,32 1,33 1,33 1,33 1,35 1,36 1,49 1,50 1,51 1,51 1,51 1,53 1,54 1,67 1,68 1,69 1,69 1,69 1,71 1,72 1,85 1,86 1,87 1,87 1,87 1,88 1,90 2,09 2,09 2,09 2,09 2,10 2,12 2,14 2,31 2,30 2,31 2,33 2,35 2,37
3,99 4,36 4,60 4,88 5,30 5,88 6,65 3,44 3,79 4,01 4,26 4,63 5,13 5,80 3,01 3,34 3,55 3,77 4,10 4,53 5,14 2,66 2,97 3,18 3,37 3,67 4,05 4,59 2,29 2,61 2,82 2,98 3,23 3,57 4,04 2,31 2,52 2,67 2,88 3,18 3,59
6,30 6,95 7,38 7,84 8,52 9,59 10,89 6,18 6,86 7,31 7,76 8,44 9,46 10,77 6,07 6,77 7,24 7,69 8,36 9,33 10,65 5,95 6,68 7,17 7,61 8,28 9,20 10,53 5,77 6,56 7,08 7,53 8,20 9,10 10,40 6,44 7,00 7,45 8,12 9,00 10,27
1,57 1,59 1,60 1,60 1,60 1,62 1,63 1,79 1,80 1,81 1,81 1,81 1,84 1,84 2,00 2,02 2,03 2,03 2,03 2,05 2,06 2,22 2,23 2,24 2,24 2,24 2,26 2,28 2,51 2,50 2,50 2,51 2,52 2,53 2,56 2,77 2,76 2,77 2,80 2,81 2,84
4,01 4,38 4,63 4,91 5,33 5,91 6,69 3,46 3,81 4,04 4,29 4,66 5,16 5,84 3,03 3,36 3,57 3,79 4,12 4,56 5,17 2,68 2,99 3,20 3,40 3,69 4,08 4,62 2,30 2,62 2,84 3,00 3,25 3,59 4,06 2,32 2,54 2,69 2,90 3,20 3,61
40
45
50
55
60
Performance data
Q P COP t1 tVL = = = = Heat output (kW) Power consumption (kW) Performance Heat source (evaporator) Inlet temperature (C) = Discharge temperature (Heating supply ow) at condenser (C) Heat source Medium T Water/frost protection* 75% 100% 100% 25% -
458
Contents
35
-5 -2 0 2 5 10 15 -5 -2 0 2 5 10 15 -5 -2 0 2 5 10 15 -5 -2 0 2 5 10 15 -5 -2 0 2 5 10 15 -2 0 2 5 10 15
7,96* 8,77 9,32* 9,90 10,77* 12,09* 13,73* 7,70 8,62 9,23 9,80 10,65 11,93 13,58 7,44 8,46 9,14 9,70 10,54 11,78 13,42 7,18* 8,30 9,05* 9,60 10,43* 11,62* 13,27* 7,10 8,21 8,95 9,50 10,33 11,49 13,12 8,11 8,84 9,40 10,23 11,36 12,97
1,97* 1,98 1,99* 1,99 2,00* 2,03* 2,03* 2,20 2,21 2,22 2,23 2,24 2,27 2,29 2,44 2,44 2,45 2,46 2,48 2,52 2,55 2,67* 2,67 2,68* 2,69 2,72* 2,76* 2,81* 3,00 2,99 2,99 3,01 3,03 3,09 3,14 3,31 3,30 3,32 3,35 3,42 3,47
4,05* 4,43 4,67* 4,96 5,40* 5,96* 6,75* 3,50 3,89 4,15 4,40 4,76 5,25 5,92 3,05 3,46 3,73 3,94 4,25 4,68 5,26 2,69* 3,10 3,38* 3,56 3,84* 4,21* 4,72* 2,37 2,74 2,99 3,16 3,41 3,72 4,18 2,45 2,68 2,83 3,06 3,32 3,74
9,29 10,24 10,88 11,55 12,57 14,14 16,05 9,12 10,11 10,77 11,44 12,44 13,95 15,88 8,94 9,98 10,67 11,33 12,32 13,76 15,70 8,77 9,85 10,56 11,22 12,20 13,56 15,53 8,51 9,67 10,44 11,10 12,09 13,41 15,34 9,50 10,32 10,98 11,97 13,26 15,14
2,29 2,31 2,32 2,32 2,32 2,36 2,37 2,55 2,57 2,59 2,59 2,61 2,65 2,67 2,82 2,84 2,85 2,87 2,89 2,93 2,97 3,09 3,11 3,12 3,14 3,17 3,21 3,28 3,49 3,48 3,48 3,50 3,53 3,56 3,62 3,86 3,84 3,86 3,89 3,91 3,97
4,07 4,44 4,69 4,98 5,41 5,99 6,78 3,57 3,93 4,17 4,41 4,77 5,27 5,95 3,17 3,51 3,74 3,95 4,27 4,70 5,28 2,84 3,17 3,39 3,57 3,85 4,22 4,74 2,44 2,78 3,00 3,17 3,42 3,76 4,23 2,46 2,69 2,85 3,08 3,39 3,81
10,66 11,75 12,48 13,25 14,41 16,22 18,41 10,46 11,60 12,36 13,13 14,28 16,00 18,21 10,26 11,45 12,24 13,00 14,14 15,78 18,01 10,06 11,29 12,12 12,87 14,00 15,56 17,81 9,76 11,09 11,98 12,73 13,87 15,39 17,59 10,89 11,84 12,60 13,73 15,21 17,37
2,65 2,67 2,69 2,69 2,70 2,74 2,74 2,97 2,99 3,01 3,02 3,03 3,08 3,10 3,29 3,31 3,32 3,34 3,36 3,41 3,46 3,60 3,63 3,64 3,66 3,70 3,75 3,82 4,07 4,06 4,06 4,08 4,12 4,16 4,23 4,50 4,48 4,50 4,54 4,57 4,63
4,02 4,39 4,64 4,92 5,35 5,92 6,71 3,52 3,88 4,11 4,35 4,71 5,20 5,87 3,12 3,46 3,68 3,89 4,20 4,62 5,20 2,79 3,12 3,33 3,51 3,78 4,15 4,66 2,40 2,73 2,95 3,12 3,37 3,70 4,16 2,42 2,64 2,80 3,02 3,33 3,75
40
45
50
55
60
Performance data
Q P COP t1 tVL = = = = Heat output (kW) Power consumption (kW) Performance Heat source (evaporator) Inlet temperature (C) = Discharge temperature (Heating supply ow) at condenser (C) Heat source Medium T Water/frost protection* 75% 100% 100% 25% -
Contents
35
-5 -2 0 2 5 10 15 -5 -2 0 2 5 10 15 -5 -2 0 2 5 10 15 -5 -2 0 2 5 10 15 -2 0 2 5 10 15 0 2 5 10 15
11,96 13,18 14,00 14,87 16,17 18,20 20,65 11,73 13,01 13,86 14,72 16,01 17,95 20,43 11,51 12,84 13,73 14,58 15,86 17,70 20,21 11,28 12,67 13,59 14,44 15,70 17,45 19,98 12,44 13,44 14,28 15,55 17,26 19,73 13,28 14,13 15,41 17,07 19,48
3,12 3,15 3,17 3,17 3,18 3,23 3,23 3,51 3,53 3,55 3,56 3,58 3,63 3,67 3,89 3,92 3,93 3,95 3,98 4,04 4,10 4,27 4,30 4,32 4,34 4,38 4,44 4,53 4,82 4,81 4,84 4,88 4,93 5,01 5,31 5,34 5,38 5,41 5,49
3,83 4,18 4,42 4,69 5,09 5,64 6,39 3,35 3,68 3,90 4,13 4,47 4,94 5,57 2,96 3,28 3,49 3,69 3,98 4,38 4,93 2,64 2,95 3,15 3,32 3,58 3,93 4,41 2,58 2,79 2,95 3,18 3,50 3,94 2,50 2,65 2,86 3,15 3,55
14,19 15,65 16,62 17,65 19,20 21,61 24,51 13,93 15,45 16,46 17,48 19,01 21,31 24,25 13,66 15,24 16,30 17,31 18,82 21,02 23,99 13,39 15,04 16,14 17,14 18,64 20,72 23,72 14,77 15,95 16,96 18,46 20,49 23,43 15,77 16,78 18,29 20,26 23,13
3,68 3,72 3,74 3,74 3,75 3,81 3,81 4,14 4,17 4,20 4,21 4,23 4,29 4,33 4,60 4,63 4,65 4,68 4,71 4,78 4,85 5,06 5,09 5,11 5,14 5,19 5,26 5,37 5,71 5,70 5,73 5,78 5,84 5,94 6,29 6,32 6,38 6,41 6,50
3,85 4,21 4,44 4,72 5,12 5,67 6,43 3,36 3,70 3,92 4,15 4,50 4,96 5,60 2,97 3,29 3,50 3,70 4,00 4,40 4,95 2,65 2,96 3,16 3,33 3,59 3,94 4,42 2,59 2,80 2,96 3,19 3,51 3,95 2,51 2,65 2,87 3,16 3,56
16,48 18,17 19,30 20,50 22,29 25,09 28,47 16,17 17,94 19,11 20,30 22,08 24,75 28,16 15,86 17,70 18,93 20,10 21,86 24,41 27,85 15,55 17,47 18,74 19,90 21,65 24,06 27,55 17,16 18,52 19,69 21,44 23,79 27,20 18,31 19,48 21,24 23,53 26,86
4,27 4,31 4,34 4,34 4,35 4,42 4,43 4,80 4,83 4,86 4,87 4,90 4,97 5,02 5,32 5,36 5,38 5,41 5,45 5,52 5,61 5,84 5,88 5,90 5,94 5,99 6,08 6,20 6,59 6,58 6,62 6,68 6,74 6,85 7,26 7,30 7,36 7,40 7,51
3,86 4,21 4,45 4,72 5,13 5,68 6,43 3,37 3,71 3,93 4,16 4,51 4,98 5,61 2,98 3,31 3,52 3,72 4,01 4,42 4,97 2,66 2,97 3,18 3,35 3,61 3,96 4,45 2,60 2,82 2,98 3,21 3,53 3,97 2,52 2,67 2,88 3,18 3,58
40
45
50
60
Performance data
Q P COP t1 tVL = = = = Heat output (kW) Power consumption (kW) Performance Heat source (evaporator) Inlet temperature (C) = Discharge temperature (Heating supply ow) at condenser (C) Heat source Medium T Water/frost protection* 75% 100% 100% 25% -
460
Contents
35
-5 -2 0 2 5 10 15 -5 -2 0 2 5 10 15 -5 -2 0 2 5 10 15 -5 -2 0 2 5 10 15 -2 0 2 5 10 15 0 2 5 10 15
19,64 21,66 23,00 24,43 26,57 29,90 33,93 19,27 21,38 22,78 24,19 26,31 29,49 33,56 18,90 21,10 22,56 23,95 26,05 29,08 33,19 18,54 20,81 22,33 23,72 25,79 28,68 32,83 20,44 22,08 23,47 25,55 28,36 32,42 21,82 23,22 25,31 28,04 32,01
5,07 5,12 5,15 5,15 5,16 5,24 5,25 5,70 5,74 5,77 5,79 5,81 5,90 5,96 6,32 6,36 6,39 6,42 6,47 6,56 6,66 6,94 6,98 7,01 7,05 7,12 7,22 7,36 7,83 7,82 7,86 7,93 8,01 8,14 8,62 8,67 8,75 8,79 8,92
3,87 4,23 4,47 4,74 5,15 5,70 6,46 3,38 3,72 3,95 4,18 4,52 5,00 5,64 2,99 3,32 3,53 3,73 4,03 4,43 4,99 2,67 2,98 3,19 3,36 3,62 3,97 4,46 2,61 2,82 2,98 3,22 3,54 3,98 2,53 2,68 2,89 3,19 3,59
24,77 27,31 29,00 30,80 33,50 37,70 42,78 24,30 26,95 28,72 30,50 33,17 37,19 42,31 23,84 26,60 28,44 30,20 32,85 36,67 41,85 23,37 26,24 28,16 29,90 32,52 36,16 41,39 25,78 27,84 29,59 32,22 35,75 40,88 27,51 29,27 31,91 35,35 40,36
6,80 6,86 6,90 6,91 6,91 7,02 7,04 7,66 7,72 7,76 7,79 7,82 7,94 8,01 8,53 8,59 8,63 8,67 8,73 8,86 8,99 9,40 9,45 9,49 9,55 9,64 9,77 9,96 10,60 10,58 10,65 10,74 10,84 11,02 11,67 11,74 11,84 11,91 12,08
3,64 3,98 4,20 4,46 4,84 5,37 6,08 3,17 3,49 3,70 3,92 4,24 4,68 5,28 2,79 3,10 3,30 3,48 3,76 4,14 4,66 2,49 2,78 2,97 3,13 3,37 3,70 4,15 2,43 2,63 2,78 3,00 3,30 3,71 2,36 2,49 2,69 2,97 3,34
40
45
50
60
Performance data
Q P COP t1 tVL Heat output (kW) Power consumption (kW) Performance Heat source (evaporator) Inlet temperature (C) = Discharge temperature (Heating supply ow) at condenser (C) = = = = Heat source Medium T Water/frost protection* 75% 100% 100% 25% -
Contents
461
V=
t1
( m3/h )
Q = t1 = C =
kPa
3 4
7 5 6
2 9 1
m3/h
1 2 3 4 5 6 7 8 9 = = = = = = = = = Type (5) Type (7) Type (8-10) and (8H-10H) Type (12-15) and (12H-15H) Type (17) and (17H) Type (19) and (19H) Type (22-26) and (22H-26H) Type (30) and (30H) Type (37-45) and (37H-45H)
462
Contents
Heat source
Volume ow evaporator
V=
t2 C
Q0 . c ( m3/h ) t2.cp.
= Temperature difference heat source supply/discharge ( K ) = 0,86 = 0,89 (specic heat) = 1,05 (specic weight, density)
cp
Pressure loss of the evaporator with 25% ethylene glycol (Antifrogen N)
kPa
4 8 7
9 10 11
1 2 3 4 5 6 7 8 9 10 11
= = = = = = = = = = =
Type (5) Type (7-8) and (8H) Type (10) and (10H) Type (12) and (12H) Type (15-17) and (15H-17H) Type (19) and (19H) Type (22) and (22H) Type (26) and (26H) Type (30) and (30H) Type (37) and (37H) Type (45) and (45H)
P, kPa = Pressure loss with frost protection (1 kPa = 0.1mWC) P = f x P f % Ethylene glycol (Antifrogen N) 0,97 20 1 25 1,03 30 Pw, kPa = Pressure loss with water (1 kPa = 0.1 mWS) P w = P x 0.89
m3/h
The following must be observed: Before installation refer to the installation, operation and maintenance instructions for the Thermalia heat pump.
Notice Planning notes, Heat source usage, Application examples with functional diagrams and functional description, Energy requirements, Installation notes see project plan
Contents
463
464
Contents
Authorization number: SVGW (Swiss Association for Gas and Water Supply) Test number 0411-4897
Contents
465
Part N
Euro
2.632,00
heater ca. 4
Persons = number of persons who can be supplied with domestic hot water (approximate values).
Accessories
for recharge Cable sensor type KVT 20/5/6S with 5 m cable and with plug
6012 687
65.
Cable sensor type KVT 20/5/6 with 5 m cable Temperature sensor type TF 25/12K with cable for connection to modulating gas boiler (TopGas) with TopTronic RS OT
2022 992
65.
242 617
47.
Thermostat type TW 12 with capillary tube At TopTronicT - temperature sensor is included in the boiler control or in the control set. For air ducting Air connection tting kit LS From plastic for air pipeline connections intake or blow sides. For pipeline connection 160 or 200 mm 160 oder 200 mm
6010 080
126.
6009 865
54,00
Service
Commissioning Commissioning must be made by works service or Hoval trained authorized serviceman/ company is condition for warranty. For commissioning and other services please contact your Hoval sales ofce. 466 auf Anfrage
Contents
Supply air temperature maximal Supply air temperature minimal Nominal air quantity (not under load) Stufe 1 Stufe 2 Ext. pressure Noise pressure level Stufe1 Stufe2 Electrical immersion heater 230 V Electric connection (device) Voltage/Frequency Hot water output / day 2 WP-VT (152-157)
1 2
Stufe 1 Stufe 2
number of persons
Mean performance gure when heating potable water from 15C to 47C Number of persons who can be supplied with hot water at the plants without hot water circulation (approximate values without recharge).
Contents
467
12,13
12 (13)
13
12,13 (13)
(13)
VT157
14
17
10
16 15
11
10
(13)
2 3
h
d
e
f
2
6 9 8 7
m
s
3
4
c
1, 5
g
2 u. 1
3, 4 u. 5
p
r
12
t
u
(13)
13
w
(13)
Cold water R 1 Hot water R 1 Circulation R Heating water flow R 1 Heating water return R 1 Immersion sleeve 15 mm, 160 mm long 7 Immersion sleeve 15 mm, 160 mm long 8 Electric heating set 9 Magnesium sacrificial anode Type WP-VT (152-157) a h b c d
1 2 3 4 5 6
10 11 12 13 14 15 16 17
Condensate drain (plastic, DN15) with collector Electric connecting cable with plug Air inlet 160 or 200 mm Air outlet 160 or 200 mm Control panel Compressor Fan Evaporator
g 285
i 35
k 770
n 10
o 180
p 145
u 320
v 190
w 235
835 1175
468
Contents
Water heater or additional heater coils must be provided with loading pump by the customer. There should be installed an automatic deaerator in the hot flow. Flow and return should be connected in such a way, that with switched off loading pump (heating with heat pump or electrically) no back circulation and no gravity circulation can take place. Expansion of heating water must be always ensured (also during electric charging resp. heat pump operation).
Heating assembly
Plumbing installation
Electric connection
The hot water distribution system must be designed to operate without circulation Select short pipeline configurations. Pay attention to compatibility of water pipelines and water heaters. Using copper and galvanized steel tubes always pay attention to the succession of flow direction: copper after galvanized steel.
Required space
Installation area 600x 720 mm Minimum distance to the walls min. 200 mm Required space operation side min. 600 mm Minimum distance to the ceiling: 250 mm
Warm water pipelines must be thermally insulated according to the local (cantonal) regulations. If water pipeline pressure is higher than 5 bar, a pressure reduction valve is to be fitted into the cold water pipeline. Condensed water connection (at the rear of Installation the heat pump, DN15) must be led away Hoval Water heater - heat pumps of type Comvia siphon into the sewer. Condensed water biVal WP-VT (152-157) can be installed without drain can be dumped together with drainage socket in every unheated room with floor drain of expansion water from the safety valve. Defor the condensed water. The room temperature pending on humidity condensate can achieve must not be below 6C with devices without 0.3 l/h. additional heating system. Minimum room size 20 m3 The intake air should not contain any aggressive substances (ammonia, sulphur, chlorine, halogens, etc.). The installation place should Air in be selected according to valid regulations and Air out guidelines (AWP leaflet T6, January, 1997 amongst others)
Blow
Intake
Ceiling
Air connection
The Hoval water heater - heat pumps type CombiVal WP-VT (152-157) are provided with changeable intake air connections. Standard tape: intake from the top, blow to the top (supply) Air ducting variants: intake from the top, blow to the top or sideways for air pipeline connection ( 160 or 200 mm). The changeover is very simple owing to changeable and removable covers (accessories). The air tube lines are to be supplied by the customer. Subject to alterations, 1.6.2006
Contents
469
VT 15 7
Air ducting Air drawn from and blown into the neighbouring room min. room volume 25 m3 Cooling, dehumidification (wine cellar, storeroom)
Installation in the utility room Air ducting Air drawn from and blown into the room min. room volume 20 m3 Dehumidification, use of heat from condensed water (laundry)
VT 15 7
Installation in the hobby room Air ducting Air drawn from and blown either into the room or externally min. room volume 20 m3 When the air is circulating, the window can be closed.
VT157
Air duct pipelines Intake/Blow pipes made of plain tube, min. 160 or 200 mm. max. total length of pipeline should be 6 or 10 m, with max. 3 elbows (90). (for each further elbow the total length of pipe must be reduced by 1m.) Supply of pipeline incl. accessories by the customer (ventilating pipe made of plastic, aluminium or galvanized sheet steel).
470
Contents
Screw-in electrical heating inset Type EP-3-6 made of Incoloy 825 Heat input 3 kW; 4,5 kW; 6 kW. including temperature control and overheating protection Connection 3 x 400 V No use for exclusive electrical heating. Delivery Delivered separately packed On-site Installation of the electrical heating inset
to heat pump
Contents
471
Part N
Euro
Type Nominal contnent TS dm3 (100-1) (100-2) (100-3) 100 100 100
to heat pump Type Genius (06) (08) (10-12) 2015 675 2015 676 2015 677 1.043,00 1.102,00 1.123,00
Accessories
Flexible connection line Flexible connection line made of EPDM (Ethylen-Propylen-Dien-Kautschuk). Verhindert die Krperschallbertragung auf das Rohrleitungssystem. Operating pressure 4 bar/80C Bilateral with srew connection Rp1 Length: 500 mm, piece Length: 1000 mm, piece
26,00 38,00
Screw-in electrical heating inset for plants with techn. storage tank according to principal schemes M-WPHA-1a, 1b and 1d. For peak load cover of monovalent plants (monoenergetic utilization). Type EP-3 EP-4,5 EP-6 heat output kW 3,0 4,5 6,0 installation length mm 390 500 620 2022 216 2022 217 2022 218 180,00 196,00 204,00
Service
Commissioning Commissioning must be made by works service or Hoval trained authorized serviceman/ company is condition for warranty. For commissioning and other services please contact your Hoval sales ofce. auf Anfrage
472
Contents
Unterstell-Speicher 100 100 4/6 4/6 90 25 0,025 95 1000 650 500 90 25 0,025 102 1100 750 500
c
40
40
50
40
6
1
40 40
7
500
1
d
f
7
h
7
4
420
4
3
e
2
40
25
Type (70)
to heat pump
h 525
a 750
b 550
c 225
d 405
e 310
f 230
g 95
Storage tank mounted below the heat pump TS (100-1, 100-2 und 100-3)
Dimensions in mm
50
40
40
40
40
40
k
1
4
1
420
3
f
g
3 2
500
2
5
40
25
g 95 95 95
k 95 95 95
Flow - discharging, R1 Return - discharging or ow - charging, R1 Flow - charging, R1 Sleeve for electric screw-in boiler Type EP-3, 4,5, 6 Rp 1
5 Adjustable feet, (TS 70: demount from the heat pump, TS100: at the heat pump enclosed) 6 Installation face form the heat pump 30mm, 4mm thick 7 Cable routing (bilateral) 473
Contents
a
z
Connections R1
Genius
b
Storage tank TS
500
TS-Speicher
y 25
z 4
30
Attention! The internal piping of the heat pump must be taken into account. The heat pumps of type Thermalia (5P-15P) and (8HP-15HP) are equipped with circulation pumps for the heating and for the heat source transport as standard, together with flexible connecting pipes. Check pump data!
Connection plan 1
Storage tank TS
Connection plan 2
Storage tank TS
parallel conection
serial conection
Storage tank TS
Storage tank TS
lation) 1 2 3 4 Flow discharge, R1 Rcklauf discharge/charge, R1 Flow-charge, R1 Blind or screw-in electrical radiator Type EP-3, 4,5, 6 nozzle Rp1/
1 2 3 4
Flow discharge, R1 Flow charge, R1 No function, blind, R1 Blind or screw-in electrical radiator Type EP-3, EP-4,5, EP-6, nozzle Rp1
Attention ! The connection sketches do not include the necessary instruments, safety ttings and shut off armatures and should not be used as installation plans!
474
Contents
Genius
b
a
z
Genius
A
z
500
500
y
TS-Speicher
Connections R1 Sleeve Rp1 for electric heating Storage tank Type TS (100-1) (100-2) (100-3) Heat pump Type Genius (06) (08) (10-12)
y 25 25 25
z 4 4 4
30 30 30
Total height heat pump Hoval Genius with storage tank TS Attention! Respect the air intake, air outlet and the required room height! (See also capter air/water heat pump Hoval Genius )
1 3 2
lation) 1 Flow discharge, R1 2 Return discharge/charge, R1 3 Flow-charge, R1 4 Screw-in electrical radiator Type EP-3, 4,5, 6, nozzle Rp1/
3 Storage tank TS TS-Speicher Rcklauf Return 2 (Anlage) (installation) 1 Flow discharge, R1 2 Flow charge, R1 3 No function, blind, R1 4 Screw-in electrical radiator Type EP-3, 4,5, 6, nozzle Rp1/
Attention! The connection sketches do not include the necessary instruments, safety ttings and shut off armatures and should not be used as installation plans!
Contents
475
Installation
Storage tank Type TS (70) to heat pump Type Thermalia (5P-15P) resp. (8HP-15HP) Mark the installation position of the TS storage tank in the boiler room. Remove the four adjustable feet from the heat pump and assemble them on the TS storage tank. Place the TS storage tank directly on the floor and use the adjustable feet to make sure that it is standing level. Now place it on the marked position and check that it is still standing level. Place the now footless heat pump on the TS storage tank. The tank is already equipped with a bearing surface for the heat pump (see figure A). Storage tank Type TS(100-1), (100- 2) and (100-3) to heat pump Type Genius (06-12) Mark the installation position of the TS storage tank in the boiler room. Remove the four adjustable feet (at the heat pump enclosed) and assemble them on the TS storage tank. Place the TS storage tank directly on the floor and use the adjustable feet to make sure that it is standing level. Now place it on the marked position and check that it is still standing level. Place the now footless heat pump on the TS storage tank. The tank is already equipped with a bearing surface for the heat pump (see figure B and C).
Figure A
Figure B
Outlet 45
Installation area storage tank TS
Genius (06-12)
Intake
45
Attention! Combination Hoval Genius heat pump with storage tank TS (100). Bottom line of the intermediate space for intake and outlet from the ready oor = Dimension C + 500 mm!
Figure C
d
a
e
f
c
c
45
45
10 0 g
G . ca 0 0 2
m p pu m eu tp rm s a u i e W H en
pe
mi 80 n. 0
Pos.6 Floor drain for condensat
476
n. mi 0 50
entd in a u
5 445
Contents
Installation
Storage tank for heating water Type TS (70) to heat pump Thermalia After the position on which it is to be placed in the boiler room has been determined and marked, the Hoval hot water storage tank type TS (70) can be installed as follows. Assembly (Figure 1) 1 Remove the four feet (a) of the heat pump. 2 Assemble the four vibration reducing and adjustable (+/- 8mm, M8) feet (a) of the heat pump on the TS storage tank, position the tank and check that it is standing level. 3 Place the heat pump flush on the TS storage tank. The tank is equipped with bearing surfaces (b) for the heat pump. The bearing surfaces are non-slip. If the heat pump is to be fixed to the TS storage tank, their aluminium frames can be bolted together. 4 Mount the hydaulic connectors between the heat pump, storage tank and heating circuit according to the selected connection plan. (See figure A, B and C, as well as the installation, operation and maintenance guidelines of Hoval Thermalia). Storage tank TS (70) to heat pump Type Thermalia (5P-15P) resp. (8HP- 15HP)
Figure 1
Make the connections between heat pump and storage tank TS as necessary.
b
Electro cable lead through
1 3 2
b
Figure A
Figure B
Hydaulic connectors Mount the primary and return heating ow pipes as shown on the scale drawings. The connectors are supplied with exible connecting pipes. The connecting pipes (types 5P-15P and 8HP-15-HP) are preassembled to continue upwards, but can be remounted on the left hand side or on the right hand side as required. Please consider the following: Assembly steps 1. Loosen the strap (a) and remove the fittings (b). (figure A) 2. Pull the connecting tube* (c) carefully back into the casing. Replace the rubber coverings (d) of the lead-throughs. Carefully cut out and replace the lagging (side wall of the selected duct). If necessary, glue in place. (figure B) 3. Carefully draw the flexible connecting duct (c) through the new lead-through. If necessary cut to length*. Remount the disassembled fittings (b) with the strap (a) on the tube. (figure C). * see below:
Figure C Figure D
b a e
Heating connections
b a
The exible connecting ducts should not be shortened if possible. Shortened connecting ducts transmit vibrations more readily. The ducts must not be crushed or buckled (do not overbend).
The flexible connecting ducts of the heat source are lagged for thermal insulation. If the ducts are remounted the lagging must not be damaged! For duct size 1 remove the lagging before the duct is remounted
(strip it off carefully) and replace it after the duct has been installed. (see figure D, position e)
Contents
477
Examples
Storage tank for heating water Type TS(100) to heat pump Genius After the position on which it is to be placed in the boiler room has been determined and marked, the Hoval hot water storage tank type TS (100) can be installed as follows. Please check absolute before the assembly , depending on chosen variant (with or without Hoval wall lead through kit): The positions of the recess opening for intake and outlet. The wall distance of the storage tank TS with the heat pump build-on. The position of the floor drain for the condensate drain pipe of the heat pump. Assembly steps (gure 1) 1 Assemble the four vibration reducing and adjustable (+/- 8mm, M10) feet (a) of the heat pump on the TS storage tank. The feet are enclosed in the package with the accessories for the heat pumpe ! 2 Place the heat pump flush on the TS storage tank. The tank is equipped with bearing surfaces (b) for the heat pump. The bearing surfaces are non-slip. If the heat pump is to be fixed to the TS storage tank, their aluminium frames can be bolted together. 3 Mount the hydaulic connectors between the heat pump, storage tank and heating circuit according to the selected connection plan. (see also installation, operation and maintenance guidelines of Hoval Genius). Storage tank TS (100) to heat pump Type Genius (06-12)
Picture 1
Electro cable
1 2 3
Make the connections between heat pump and storage tank as necessary.
1 3 2
Consider the assembly instructions! (Annex to electric heating EP-3; EP-4,5; EP-6)
Accessibility The side walls of the heat pump are removable. Hydaulic connectors The exible connecting duct of the heat pump Genius can be carried out to the left (preferable) or to the right. (gure 2) 1 Heating ow 2 Heating return 3 Condensate drain pipe
Figrue 2
Condensate drainage
1 2 3
478
Contents
1 Heat pump Thermalia (5P-15P) resp. (8HP-15HP) with heating regulator TopTronicT, with circulation pump built-in and with flexible connecting ducts. 2 Storage tank TS (70) 3 Underoor heating 4 Outdoor sensor 5 Return sensor (on/off) with or without pocket 6 Savety valve 7 Expansion tank
8 9 10 11 12 13 14-16 17
Manometer Over flow valve1 Flexible connecting duct Pressure guard Terrestrial heat probes installations Adjustable feet Non relevant Screw-in electrical heating inset EP-3; EP-4,5; EP-6 (possible as emergency heating, for peak load cover with soil as heat source is not recommended!)
Minimum plant water content should be checked (recommendation of AWP: 0,015m3/kW heat output). If the heating circuit is equipped with thermostatic valves, a bypass to the bypass valve should be installed. Minimum water content of 0,015 m3/kW of heat output between the heat pump and the bypass is necessary.
Advice
Keep the connection pipes as short as possible. The size should be adequate to cope with the possible throughput. Make sure that the appliance can be emptied for maintenance purposes. Install bleed valves at the highest points of the pipes. Allow system pressure to be maintained by using an expansion vessel (e.g. Reflex). Attention Improper throughput rates caused by the wrong selection of piping and ttings or faulty pump operation can lead to damage of the appliance.
Contents
479
7
1 Heat pump Hoval Thermalia (5P-10P) resp. (8HP-15HP) with heating regulator TopTronicT, with circulation pump built-in and with flexible connecting ducts. 2 Storage tank TS (70) 3 Heating group 4 Outdoor sensor 5 Sensor (on/off) with pocket 6 Savety valve 7 Expansion tank 8 Manometer 9 Not relevant 10 Flexible connecting ducts 11 Pressure guard 12 Terrestrial heat probes installations 13 Adjustable feet 14 Heating group pump 15 Motor mixer valve 16 Flow sensor 17 Screw-in electrical heating inset EP-3; EP-4,5; EP-6 (possible as emergency heating, for peak load cover with soil as heat source is not recommended!)
5 6
1 2 3 4
Flexible connecting ducts Sensor Type KT10-40 Pocket Typ 8316.G400 Reduction 1-
5 T-piece 1 with inside thread 6 Plug 1 with external thread 7 Nipple 1 with external thread
Advice
Keep the connection pipes as short as possible. The size should be adequate to cope with the possible throughput. Make sure that the appliance can be emptied for maintenance purposes. Install bleed valves at the highest points of the pipes. Allow system pressure to be maintained by using an expansion vessel (e.g. Reflex). Attention Improper throughput rates caused by the wrong selection of piping and ttings or faulty pump operation can lead to damage of the appliance.
480
Contents
1 Heat pump Hoval Genius (06-12) with flexible connecting ducts 2 Storage tank TS (100) 3 Underfloor heating 4 External electronic control panel with regulator TopTronicT 5 Heating pump 6 Return sensor (on/off) with or without pocket 7 Outdoor sensor 8 Seavty valve 9 10 11 12 13
Over flow valve 1 Expansion tank Manometer Flexible connecting duct Screw-in electrical heating inset EP-3; EP-4,5; EP-6 (possible for peak load cover) 14 Adjustable feet 15 Condensate drain
Minimum plant water content should be checked (recommendation of AWP: 0,015m3/kW heat output). If the heating circuit is equipped with thermostatic valves, a bypass to the bypass valve should be installed. Minimum water content of 0,015 m3/kW of heat output between the heat pump and the bypass is necessary.
Advice
Keep the connection pipes as short as possible. The size should be adequate to cope with the possible throughput. Make sure that the appliance can be emptied for maintenance purposes. Install bleed valves at the highest points of the pipes. Allow system pressure to be maintained by using an expansion vessel (e.g. Reflex). Attention Improper throughput rates caused by the wrong selection of piping and ttings or faulty pump operation can lead to damage of the appliance.
Contents
481
(M-WPHA-1d)
(M-WPHA-1b)
1 Heat pump Hoval Genius (06-12) with flexible connecting ducts 2 Storage tank TS (100) 3 Heating group 4 External electronic control panel with regulator TopTronicT 5 Loading pump 6 Senor (on/off) with pocket 7 Outdoor sensor 8 Safety valve 9 Not relevant 10 Expansion tank 11 Manometer 12 Flexible connecting duct 13 Screw-in electrical heating inset EP-3; EP-4,5; EP-6 (possible for peak load cover) 14 Adjustable feet 15 Condensate drain 16 Heating group pump 17 Motor mixer valve 18 Flow sensor
7 5 6 4
1 2 3 4
Flexible connecting duct Sensor Type KT10-40 Pocket Typ 8316.G400 Reduction 1-1/2
5 T-piece 1 with inside thread 6 Plug 1 with external thread 7 Nipple 1 with external thread
Advice
Keep the connection pipes as short as possible. The size should be adequate to cope with the possible throughput. Make sure that the appliance can be emptied for maintenance purposes. Install bleed valves at the highest points of the pipes. Allow system pressure to be maintained by using an expansion vessel (e.g. Reflex). Attention Improper throughput rates caused by the wrong selection of piping and ttings or faulty pump operation can lead to damage of the appliance.
482
Contents
Contents
Installation
The heat sources, to be used predominantly for living room heating, are natural and renewable heat sources like outside air soil ground water surface waters (lakes, rivers). Waste heat utilization with heat pumps is one application of the heat pumps for heat recovery, whereby alongside with usual criteria like the temperature level, kind (waste water, exhaust air, exhaust gas), chemical and mechanical cleanliness etc., also the simultaneousness of availability and heat utilization should be considered. An exact analysis of the plant is necessarily. Outdoor air Outdoor air is available everywhere and its use as a heat source needs no official authorization. When planning outdoor air utilization as a heat source the following points should be considered: Application area of the heat pump Output fluctuations of the heat pump due to temperature fluctuations of the heat source Defrosting losses of the heat pump Sound emission of air delivery Condensed water As the heat pump working medium has clearly defined limits of application, the following must be paid attention to during dimensioning of the plant. max. approved condenser outlet (flow) temperature of the selected heat pump with the min. outdoor temperature (intake temperature) of the climate zone. Movement of the heat source and heating system temperatures in opposite directions leads to the output drop of the air/water heat pumps. Thus an air/water heat pump is dimensioned rather tight from the point of view of economy and an electric additional heating system is planned for peak load covering (monoenergetic operation). If possible, installe a technical storage. For planning and accomplishment of the heat source plant a qualified specialized company should be engaged.
Heat pump is a heat transporting machine which behaves very dynamically. This requires constant volumes flows from both the heat source and heat utilization (heating) over the heat exchangers of the heat pump. As heat exchangers of the heat pump show very small water contents, constantly changing heat output demand of the plant (predominantly heating period time!) lead too excessive switching frequency. Short intervals mean however on the one hand insufficient time for stabilization of working medium cycle (efficiency loss), on the other hand lead to compressor engine damage. In this regard the requirement of electric power stations, limiting switching frequency to 3 x per hour has to be reckoned with because of networking technical considerations. Thus suitable measures must be taken or the plant must be planned in such a way that the general conditions concerning the heat pump and the requirement of electric power stations can be fulfilled every time. The most important criteria for fulfilment of the general conditions are: more constant flow rate over the heat pump during the entire utilization period sufficient storage capability and minimum plant contents that of heat utilization side (heating) Under-floor heating can fulfil these requirements in most cases. If these general conditions cannot be fulfilled, the heat pump must be hydraulically separated from the heat utilization plant must (heating). A technical storage tank (buffer storage tank) is necessary for this. Technical storage tank ensures fulfilment of the general conditions concerning the heat pump in every loading condition of the plant. The technical storage tank is dimensioned as follows (volumes in dm3): 220 x QWP T x n = Volume of the technical storage tank = max. heat output of the heat pump (kW) = Temperature difference between On and Off commands = Switching frequency per hour
The heat source (apart from temperature level of the heating system) essentially determines the attainable annual running time, operating reliability and economy of the heat pump plant. The most important factors are unlimited availability during utilization period. the temperature level of the heat source during utilization period. the energy necessary for delivery of the heat source. chemical and physical harmlessness of the heat source (operating reliability, maintenance costs). Professional planning and accomplishment of the source use belong to the most important tasks of the planner and installer.
Frequently asked questions: Does the heat pump need a storage tank?, should be rather formulated like this: Is the plant planned correctly regarding the heat pump? Or: Does the heat utilization (heating) plant fit with the general conditions? Hoval principle schemes M-WPHA-1a to 1d provide a practically tested choice of solutions for heat pump system planning. For further details see Application examples.
484
Contents
Heat source A2 = Air inlet temperature 2 C Heat utilization (heating): W35 = Water inlet temperature 35 C Further the electric power plants need the following data for granting the authorization: Imax. (A) Blocking current so = Max. power consumption of compressor. Serves for dimensioning of supply and protection. = Power consumption for called. LRA (A) direct startup. Serves for the evaluation of sytem perturbation (voltage drop) = If power consumption during direct startup in the network causes more than 3% voltage drop. = Capacity factor, only with PNTvalue above 10 kW serves for dimensioning of eventual power factor correction
These heat pump specific data are productrelated in the Hoval catalogue and they are specified on the heat pump product sign. If a direct start in the network does not cause more than 3% of voltage drop, it can be done without starting help. The necessary explanations and authorization application must be submitted at stage of plant planning. The authorization of the responsible electricity power station must be already present during ordering of the heat pump!
Contents
485
Product Description Examples of application Examples of application Heat pump plant for heating
Principal scheme M-WPHA-1a
Application Air water heat pumps all types with TopTronic heating regulator. Low temperature heating system with max. 2 heating groups and technical storage tank to max. 1500 dm3 content. Pay attention to: Heating (in the ow) and heating source (evaporator inlet) pumps are supplied. Operation method Monovalent Operation mode Gliding storage charge with 2 point regulati on circuit. Heating circuit (heating groups) Dependent on atmospheric conditions 3 point regulation Heating side Max. heating ow temperature: see range of application of the selected heat pump (performance data)! Recommended ow temperature 35-40 C. Storage tank volume approx. 20-35 dm3 per kW of heat output at standard point of W10W35, B0W35 or A2W35. Heat source side Min. outdoor air temperature -10C Heat pump function Heat pump operates dependent on the outdoor temperature (2 point regulator) with gliding operating mode. The technical storage tank works under unfavourable output / load proportion adjusting, enables energy-effective and user-defined discharge and positively affects the service life of the heat pump. The heat pump is put into operation only when the temperature level in the technical storage tank no longer meets the requirements of the heating plant (sensor 9) and is put out of operation, when increased efficiency of the technical storage tank cannot be taken in any longer (sensor 10). The differential gap is adjustable and enables long operating time. Additional restarting delay permits maximally 3 starts per hour (VSE (Association of Swiss Engineers) recommendation) and guarantees long service life. Owing to microprocessor-controlled switching functions a long running time and high annual coefficient of performance of the heat pump are achieved. Heating regulation The weather-dependent heating regulation (3 point regulator) as discharge regulation guarantees an optimal heat supply of the heating plant and operates user-dened with optimal comfort.
1 Heat pump Genius or Genius-Split 1a Outer device Genius split 1b Working medium connecting pipeline of split devices 2 Technical storage tank EnerVal 3 Heating plant 4 Storage tank loading pump 5 Heating group pump
6 7 8 9 10 11 12 13 14
Motor mixer Flow sensor Outer sensor Storage tank sensor On Storage tank sensor Off Pressure monitor Safety valve Expansion tank Return ow inhibitor with spring load
14 16 17 18 19 20 21
Flow controller Flexible connection Heating regulator TopTronic Connection to heat source ev. start stage Vibration insulation ev. electric peak load cover or emergency heating 22 Condensate drain
Principal scheme M-WPHA-1b Application and function like of the principal scheme M-WPHA-1a, but without storage tank sensor below (10). The sensor (9) is paced in the middle of the storage tank. The heat pump is switched on and off by the storage tank sensor (9) (differential gap adjustable). 486
Contents
Minimum plant water content should be checked (recommendation of AWP: 0.015m3/kW heat output). If the heating circuit is equipped with thermostatic valves, a bypass to the bypass valve should be installed. Minimum water content of 0.015 m3/kW of heat output between the heat pump and the bypass is necessary.
1 Heat pump Genius and Genius split 1a Outer device Genius-Split 1b Working medium connecting pipeline of split devices 2 Heating circuit pump 3 Under-floor heating 4 Outer sensor 5 Return sensor
5 7 8 9 10 11 12 13 14
Heating regulator TopTronic Flexible connections Expansion tank Safety valve Pressure monitor Flow controller Connection to heat source ev. start stage Vibration insulation
14 ev. electric peak load cover or emergency heating 16 Bypass valve, when the flow rate in the heating circuit is variable. Minimum volume between heat pump and bypass min. 15 litre per kW of nominal output of the heat pump 17 Condensate drain
Contents
487
1 Heat pump Genius and Genius-Split 1a outer device Genius-Split 1b working medium connecting pipeline of split devices 2 Technical storage tank EnerVal 3 Heating plant 4 Storage tank loading pump
5 6 7 8 9 10 11 12
Heating group pump Outer sensor Storage tank sensor Pressure monitor Safety valve Expansion tank Return flow inhibitor with spring load Flow controller
13 14 15 16 17 18
Flexible connection Heating regulator TopTronic Connection to heat source ev. start stage Vibration insulation ev. electric peak load cover or emergency heating 19 Condensate drain Subject to alterations, 1.6.2006
488
Contents
HP WPHA
air/ water
2,6-2,8
following annual coefficients of performance. Example EFH, CH middle land air/ water heat pump with terrestrial heat probes. Annual heat demand according to SIA = 14400 kWh 14400 Energy demand= 2,7 = 5333 kWh
Qa = Annual heat demand, kWh n = Total operating time, normally for dwelling houses 13 h /d Qh = Necessary heat output according to SIA Gtz = Daily temperature gure, depending on climate zone ti = Room temperature ta = Minimum outdoor temperature Energy demand of the heat pump with monovalent operation WWP = Qa (kWh)
More precise calculation is possible only dependant on the plant and with application of PC-programs as, e.g., WP-Calc. Planning tips For further data and details see Planning, construction and operation of electric heat pump plants, Ravel Heft 3, Nr.724.356 Standard switches, Ravel booklet 5 Nr.724.359 (to subscribe to Federal Print and Material Centre (EDMZ), 3000 Bern) PC calculating program WP-Calc (Nova Energie Schachenallee 29, 5000 Aarau) Regulations resp. tech. instructions A1-A8 and T1-T6 of TK/AWP (Working Committee for Heat Pumps Arbeitsgemeinschaft Wrmepumpe Konradstrasse 9, 8023 Zrich) Leaflets and checklists of FWS (Swiss Society for Promotion of Heat Pumps Frdergemeischaft Wrmepumps Schweiz)
n . Q . G f (t - t ) 100
tz i a
WP
(kWh)
fz
z
Depending on the balance point for heat pump switch a different proportional result of the total annual heat demand is obtained. This proportion is calculated on the basis of the temperature frequency diagram. fWP = percentage of the total heat demand of the WP fZ = percentage of the total heat demand of additional heating z = efciency of additional heating Total energy demand of the plant Energy demand of auxiliary plants (all additional devices like heating source, storage tank, loading pump, controller and regulator etc., incl. storage tank losses during heating period) should be taken into consideration while calculating the heat pump energy demand. WWPHA = WWP + WHB (kWh) (kWh)
WHB =
Q n
n
dt
P dt
Qtotal Ptotal
> min
h = Operating time of auxiliary plants P = Auxiliary plants wattage = Auxiliary plants efciency rates Annual coefcient of performance of the heat pumps heating plant (JAZ) resp. WPHA = Qa WWPHA
Contents
489
Attention The installer / planner of the plant is responsible for operating instructions and for instruction of foreign products resp. entire plant!
Operation test run serves for check and adjustment of definite plant operating values as well as for instruction of the operating personnel and takes place after putting into operation (usually after approx. 1-2 months of operation).
490