1) 3ua50-52-55 - 42

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

I

Operating Instructions

51+ 2

Bimetal Relay with Single Phasing Protection


Type 3UA50/52/55
B. Short Circuit Protection The Birelays have to be protected from short circuits. It is mandatory to use back up HRC fuses. The maximum permissible ratings of Siemens fuses (Type 3NA1) as per IS 13947 Pt-4 corresponding to type 2 co-ordination are mentioned on the name plate. Maximum backup fuse rating : 6 Amps (Type 3NA1) C. Mounting The Siemens 3UA50/52/55 birelays provide accurate overload and accelerated single phasing protection for three phase motors with currents upto 45A. It incorporates dual slider principle for accelerated tripping under single phasing. Relay Type Suitable for mounting to contactor Type. 3TB40/41 3TF42/43 3TF44/45 For permissible installed position: (see Fig. l) a. Overload relay with contactor (refer Fig. la). b. Overload relay for individual mounting (refer Fig. lb). Do not subject to sudden shocks or long term vibrations. D. Installation For dimensional drawings. a. 3UA50 + 3UX1418/3UA52 + 3UXI 420/3UA 55 + 3UXI 425 (refer Fig. lla). b. 3UA 50 + 3TB 40/41 (refer Fig. llb). c. 3UA 52 + 3TF 42/43 (refer Fig. llc). d. 3UA 55 + 3TF 44/45 (refer Fig. lld).

3UA50 3UA52 3UA55

A. Technical Data Rated Insulation Voltage : 690 V AC Reated Operational Current 3UA50 : 0.1 to 14.5A 3UA52 : 0.1 to 25A 3UA55 : 5 to 45A Permissible ambient Temp. : -25oC to + 55oC Frequency of operation : 15 ops/hr

For individual mounting an adaptor is available which should be ordered out seperately. Ordering number and suitability are as under : Adaptor type Suitable for Mounting to 3UA50 3UA52 3UA55

3UX1418 3UX1420 3UX1425

E. Connection Permissible cable Cross-sections Auxiliary Conductor 3UA 50/52/55 2 x 1 to 2.5 2 x 0.75 to 1.5 M3.5 0.8 - 1.4

G. Commissioning For instructions, see Fig. IV Set the scale (P1) to the rated current of load. Reset button (Blue) (P2) Push this button before commissioning and after tripping to make relay ready for operation. In the as-delivered condition, the auxiliary contact is set to H = Manual resetting. To change from H = Manual to A = Automatic, Press and turn the button counter-clockwise from H to A. Test button (Red) (P3). When this button is actuated, the NC contact opens and the NO contact closes, i.e. a test function for NC and NO contacts (simulation of over load tripping). Trip indicator (Green) (P4). In the H setting, a green pin protrudes from the front plate to indicate the TRIPPED condition. In the A setting this condition is not indicated. Terminal for contactors coil A2 (P5). H.Tripping Characteristics Individual characteristics for each range are available on request. Please get in touch with the nearest Siemens office.

Phase Conductor Solid (mm2) Finely stranded with end sleeve (mm2) Terminal Screw Tightening torque (Nm) 3UA 50/52 2 x 2.5 to 6 2 x 1.5 to 4 M4 1 to 1.5 3UA 55 2 x 1.5 to 25 2 x 1 to 16 M5 2.5 to 3

For equipment circuit diagram refer Fig. III. In case of single phase loads, the three main circuits must be connected in series. F. Auxiliary Circuit - Rated operational currents AC - 15/Ue - V AC - 15 le - A DC - 13/Ue - V DC - 13/le - A 24 2 24 2 60 1.5 60 0.5 125 1.25 110 0.3 230 1.15 220 0.2 415 1 500 1 690 0.8

Fig. I

Fig. III

Relay Type 3UA50 3UA52 3UA55

d 10 14.3 14.3

e M4 M4 M5

f M3.5 M4 M5

Individual Mounting Plate 3UX1418 3UX1420 3UX1425

Fig. IIa

Fig. IV

Type 3UA 50 + 3TB40, 3TB41 3UA 50 + 3TB40, 3TB41

a 125 130

b 85 100

c 108 100

d 60 60

2)

With 1N0 or 1 NC Auxiliary Contact. With 1No + 2N0 + 2NC auxiliary Contacts. Minimum clearance from earthed element 10 mm.

Fig. IIb. Dimension of 3UA50 mounted on to 3TB40/41

* *

Minimum clearance from the earthed components. Dimension for the square OFF-button (stroke 3 mm). Dimensions for the round RESET-button (stroke 2.5 mm ) less 2.5 mm

Fig. IIc. 3TF42 and 3TF43, with 3UA52 overload relay

1) 2)

Minimum clearance from the earthed components. Dimension for the square OFF-button (stroke 3 mm). Dimension for the RESET-button (stroke 2.5 mm) less 2.5 mm Width for the 3TF44 II and 3TF45 II contactors.

Fig. IId. 3TF44 and 3TF45, with 3UA55 overload relay

Siemens Ltd.
SGR-01-101-030

Product upgradation is a continous process. Hence, data in this leaflet is subject to change without prior notice. For the latest information, please get in touch with our Sales Offices.

Order No: 4I-0092-0116628101

109705