Operating Instructions
51+ 2
A. Technical Data Rated Insulation Voltage : 690 V AC Reated Operational Current 3UA50 : 0.1 to 14.5A 3UA52 : 0.1 to 25A 3UA55 : 5 to 45A Permissible ambient Temp. : -25oC to + 55oC Frequency of operation : 15 ops/hr
For individual mounting an adaptor is available which should be ordered out seperately. Ordering number and suitability are as under : Adaptor type Suitable for Mounting to 3UA50 3UA52 3UA55
E. Connection Permissible cable Cross-sections Auxiliary Conductor 3UA 50/52/55 2 x 1 to 2.5 2 x 0.75 to 1.5 M3.5 0.8 - 1.4
G. Commissioning For instructions, see Fig. IV Set the scale (P1) to the rated current of load. Reset button (Blue) (P2) Push this button before commissioning and after tripping to make relay ready for operation. In the as-delivered condition, the auxiliary contact is set to H = Manual resetting. To change from H = Manual to A = Automatic, Press and turn the button counter-clockwise from H to A. Test button (Red) (P3). When this button is actuated, the NC contact opens and the NO contact closes, i.e. a test function for NC and NO contacts (simulation of over load tripping). Trip indicator (Green) (P4). In the H setting, a green pin protrudes from the front plate to indicate the TRIPPED condition. In the A setting this condition is not indicated. Terminal for contactors coil A2 (P5). H.Tripping Characteristics Individual characteristics for each range are available on request. Please get in touch with the nearest Siemens office.
Phase Conductor Solid (mm2) Finely stranded with end sleeve (mm2) Terminal Screw Tightening torque (Nm) 3UA 50/52 2 x 2.5 to 6 2 x 1.5 to 4 M4 1 to 1.5 3UA 55 2 x 1.5 to 25 2 x 1 to 16 M5 2.5 to 3
For equipment circuit diagram refer Fig. III. In case of single phase loads, the three main circuits must be connected in series. F. Auxiliary Circuit - Rated operational currents AC - 15/Ue - V AC - 15 le - A DC - 13/Ue - V DC - 13/le - A 24 2 24 2 60 1.5 60 0.5 125 1.25 110 0.3 230 1.15 220 0.2 415 1 500 1 690 0.8
Fig. I
Fig. III
d 10 14.3 14.3
e M4 M4 M5
f M3.5 M4 M5
Fig. IIa
Fig. IV
a 125 130
b 85 100
c 108 100
d 60 60
2)
With 1N0 or 1 NC Auxiliary Contact. With 1No + 2N0 + 2NC auxiliary Contacts. Minimum clearance from earthed element 10 mm.
* *
Minimum clearance from the earthed components. Dimension for the square OFF-button (stroke 3 mm). Dimensions for the round RESET-button (stroke 2.5 mm ) less 2.5 mm
1) 2)
Minimum clearance from the earthed components. Dimension for the square OFF-button (stroke 3 mm). Dimension for the RESET-button (stroke 2.5 mm) less 2.5 mm Width for the 3TF44 II and 3TF45 II contactors.