D Type Manual Eng v20
D Type Manual Eng v20
D Type Manual Eng v20
SEC ELECTRONICS
tel: ++ 386 5 753 2006 fax: ++ 386 5 753 2007
The information held in this manual may be modified without notice and SEC electronics will not be responsible for changes that may occur in the future.
No part of this manual can be reproduced, for any reason, in any form or by any means ( including recording and photocopying) without the written consent of SEC electronics.
Before the control panel installation, wiring, commissioning and inspection, read this instruction manual carefully.
Keep the manual in a safe place and available to engineering and installation personnel during the control panel functioning period.
SEC electronics is not responsible for those mistakes that may be found in this manual and for the damages that they may cause.
D-type manual
CONTENTS
SAFETY SIMBOL LEGEND 0. 1. 1.1. 2. 2.1. 2.2. 2.3. 2.4. 2.5. 3. 3.1. 3.2. 4. 4.1. 4.2. 5. 5.1. 5.2. 5.3. 5.4. 5.5. 6. 6.1. 6.2. 6.3. 6.4. 6.5. 6.6. 7. 7.1. 7.2. SAFETY PRECAUTIONS PRODUCT LIABILITY AND WARRANTY TERMS OF WARRANTY INSPECTION PROCEDURE UPON DELIVERY INSPECTION PROCEDURE CONTROL PANEL TYPE DESIGNATION NAMEPLATE STANDARD SPECIFICATIONS DISPOSAL OF THE DEVICE INSTALLATION GUIDELINES MECHANICAL SPECIFICATION INSTALLATION MOUNTING CLEARANCE WIRING PROCEDURE AC INPUT CONNECTION MAIN MOTOR CONNECTION PROGRAMMING WITH PROGRAMMER PAGE 1 PARAMETERS PAGE 2 INPUT STAGES DEFINITION PAGE 4 LAST EVENTS CONTROL TABLE PAGE 5 ERROR TABLE PRESETING AND FACTORY RESET PROGRAMMING WITH COMPUTER CONNECTION TO PC PAGE 1 OR PARAMETERS DEFINITION PAGE 2 OR INPUTS DEFINITION PAGE 3 OR ONLINE INPUTS AND OUTPUTS MONITORING PAGE 4 OR LAST EVENTS TABLE PAGE 5 OR ERROR TABLE ABBREVIATIONS TERMINALS ON CONTROL PANEL ELEMENTS ON CONTROL PANEL
5 6 9 9 10 10 10 11 12 12 13 13 14 15 15 16 17 24 34 36 37 38 39 39 39 40 41 42 42 43 43 45
D-type manual
8.
COUNTING SENSORS CONNECTION AND POSITION COUNTING SYSTEM NUMBER 1 - 8 COUNTING SYSTEM NUMBER 1 COUNTING SYSTEM NUMBER 2 COUNTING SYSTEM NUMBER 4 WITH SEPARATED MAGNETS COUNTING SYSTEM NUMBER 4 COUNTING SYSTEM NUMBER 5 COUNTING SYSTEM NUMBER 6 COUNTING SYSTEM NUMBER 7 COUNTING SYSTEM NUMBER 8
47 48 49 50 51 52 53 54 55 56 57 57 57 58 59 59 59 60 60 61 65 66 66 72 74 77 79 81 81 82 82 83 83 83 83 84 85 85 86 87
9. 9.1. 9.2. 9.3. 10. 10.1. 10.2. 10.3. 10.4. 10.5. 10.6 11. 11.1. 11.2. 11.3 11.4. 11.5 12. 12.1. 12.2. 12.3. 13. 13.1. 13.2. 13.3. 13.4. 14. 14.1. 14.2.
CONNECTION DURING INSTALLATION PHASE POWER SUPPLY MOTOR CONNECTION MAINTENANCE AND SAFETY CONNECTION START UP PRE POWER CHECK VOLTAGE AND CONTROL ELEMENTS CHECK MAINTENANCE MODE NORMAL MODE TROUBLESHOOTING ERROR CODE READING FROM INDICATOR D-type LIFT CONTROLLER TECHNICAL INFORMATION TECHNICAL CHARACTERISTIC D-type MODULE TERMINALS INPUTS FOR CALLS CONNECTION OUTPUTS CONNECTION OPERATING IN DUPLEX MODE SAFETY CIRCUIT 186 GENERAL FEATURES DETAILS AND CONNECTIONS REQUIREMENTS FOR INSTALLATION MAINTENANCE CARE SERVICE REPAIRS CUSTOMER SERVICE GUIDE TO ELECTROMAGNETIC COMPATIBILITY THE EMC DIRECTIVE AND APPLICABLE STANDARD EMC COMPLIANT ELECTRICAL CABINET WIRING RULES
D-type manual
WARNING:
Commands attention to an operating procedure, practice, condition, or statement, which, if not strictly observed, could result in personal injury or death. Commands attention to an operation procedure, practice, condition, or statement, which, if not strictly observed, could result in damage or destruction of equipment. Commands attention to an operating procedure, practice, condition, or statement that must be highlighted.
CAUTION:
NOTE:
D-type manual
0. SAFETY PRECAUTIONS
WARNING - ATTENTION
Drive systems cause mechanical motion. It is the responsibility of the user to ensure that any such motion does not result in an unsafe condition. Factory provided interlocks and operating limits should not be bypassed or modified.
WARNING / ATTENTION
Replace all covers before applying power to the control panel. Failure to do so may result in death or serious injury.
WARNING / ATTENTION
Control panels are electrical apparatus for use in industrial installations. Parts of the control panels are energized during operation. The electrical installation and the opening of the device should therefore only be carried out by qualified personnel. Improper installation of motors, control panel or other equipment may therefore cause the failure of the device as well as serious injury to persons or material damage. Control panels are not equipped with motor overspeed protection logic. Follow the instructions given in this manual and observe the local and national safety regulations applicable.
D-type manual
CAUTION / PRECAUTION
Do not connect power supply voltage that exceeds the standard specification voltage fluctuation permissible. If excessive voltage is applied to the control panel, damage to the internal components will result.
CAUTION / PRECAUTION
Do not operate the control panel without the ground wire connected. The motor chassis should be grounded to earth through a ground lead separate from all other equipment ground leads to prevent noise coupling. The grounding wires shall be sized in accordance with the NEC or Canadian Electrical Code. The connection shall be made by a UL listed or CSA certified closed-loop terminal connector sized for the wire gauge involved. The connector is to be fixed using the crimp tool specified by the connector manufacturer.
CAUTION / PRECAUTION
Do not perform a megger test between the control panel terminals or on the control circuit terminals.
CAUTION / PRECAUTION
Because the ambient temperature greatly affects control panel life and reliability, do not install the control panel in any location that exceeds the allowable temperature. Leave the ventilation cover attached for temperatures of 40 oC or below.
CAUTION / PRECAUTION
The control panel must be mounted on a wall that is constructed of heat resistant material. While the control panel is operating, the temperature of the control panel parts can rise to a temperature of 90 C. In case when braking resistors are used, the temperature of this resistor can rise up to 200 C.
D-type manual
NOTE
The terms controller, lift controller and control box are sometimes used interchangeably throughout the industry. We will use the term control panel in this document 1. Never remove the covers while the AC Input power supply is switched on. Minimum time to wait before working on the terminals or inside the device is 1 minute after disconnecting for control panels without electronic regulators for motors and 5 minutes for control panels with electronic regulators ( VVVF, ACVV, soft start) Do not touch or damage any components when handling the device. The changing of the isolation gaps or the removing of the isolation and covers is not permissible. If the doors have to be removed (or opened) because the room temperature is higher than 40 degrees, the user has to ensure that no occasional contact with live parts may occur. Protect the control panel from impermissible environmental conditions (temperature, humidity, shock etc.) No voltage should be connected to the output terminals for the motors, magnets, valves, lights and switches ( terminals 5, 6, 7, 8, 9, 10, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 25, 25a, 26, 26a, 27, 31, 40, 45, 46, 47, 48, 56, 57, 58, 59, 77, 78, 79, 80, 100, 101, 102, 103, 104, 105, 106, 107, 108, 121, 122, 123, 130, 131, 132, 222, 351, 352, 358, 360, 371, 372) A capacitative load ( e.g. Var compensation capacitors) should not be connected to the outputs for the motors (terminals 5, 6, 7, 8, 9, 10, 12, 13, 14, 15, 16, 17, 18, 19, 20) Always connect the control panel to the protective ground ( PE ) via the marked connection terminals ( 0 or GND ) and the housing ( 0 or GND ). Control panels have ground discharge currents greater than 3,5 mA. EN 50178 specifies that with discharge currents greater than 3,5 mA the protective conductor ground connection ( 0 or GND ) must be fixed type and doubled for redundancy. The electrical commissioning should only be carried out by qualified personnel, who are also responsible for the provision of a suitable ground connection and a protected power supply feeder in accordance with the local and national regulations. No dielectric tests should be carried out on parts of the control panel. A suitable measuring instrument ( internal resistance of at least 10 kohm/V ) should be used for measuring the signal voltages. If the control panel has been stored for longer than three years, the operation of the capacitors may be impaired. Before commissioning devices that have been stored for long periods, connect them to a power supply for two hours with no load connected in order to regenerate the capacitors, ( the input voltage has to be applied without enabling the functionality). The control panel may start accidentally in the event of a failure, even if it is disabled, unless it has been disconnected from the AC input feeder.
2.
3.
4.
5.
6.
7.
8.
9.
10.
D-type manual
D-type manual
2. INSPECTION PROCEDURE
2.1. UPON DELIVERY INSPECTION PROCEDURES
A high degree of care is taken in packing our control panels and preparing them for delivery. They should only be transported with suitable transport equipment (see weight data). Observe the instructions printed on the packaging. This also applies when the device is unpacked and installed.
In the event of any damage or of an incomplete or incorrect delivery please notify the responsible sales offices immediately. The devices should only be stored in dry rooms within the specified temperature ranges.
NOTE:
A certain degree of moisture condensation is permissible if this arises from changes in temperature ( see Permissible Environmental Conditions ). This does not however, apply when the devices are in operation. Always ensure that there is no moisture condensation in devices that are connected to the power supply
D-type manual
10
2.3 NAMEPLATE
Check that all the data stated in the nameplate enclosed with the control panel corresponds to what has been ordered.
SEC ELECTRONICS
Type ____________ S/N __________________ Input frequency __________ Brake _____________________ Valves ___________________
Dimensions __________________________________________
Type S/N Input voltage Input frequency Rated current Brake Retiring cam Valves Dimensions
- control panel model - serial number ( type code) - power supply voltage - power supply frequency - output rated current - rated voltage of brake ( in electric lift) - rated voltage of retiring cam - rated voltage of valves ( in hydraulic lift) - dimensions of control panel H x W x D
D-type manual
11
2.4.
STANDARD SPECIFICATIONS
Ta Ambient temperature Installation location Degree of protection Installation altitude Temperature operation 0 +50 oC -20 +55 oC -20 +70 oC 5% to 85% 1 g/m3 to 25 g/m3 without moisture condensation or icing Class 3K3 as per EN50178 5% to 95% 1 g/m3 to 29 g/m3 Class 1K3 as per EN50178 95% 60 g/m3 greatest absolute air humidity if the device is brought suddenly from 70 to 15 oC A light condensation of moisture may occur for a short time occasionally if the device is not in operation ( Class 2K3 as per EN50178) 86 to 106 kPa (Class 3K3 as per EN50178) 86 to 106 kPa (Class 1K4 as per EN50178) 70 to 106 kPa (Class 2K3 as per EN50178) IEC 68-2 Part 2 and 3 EN50178 IEC68-2 Part 6 EN12015 and EN12016 (see chapter EMC Guidelines ) CE 0 +40 oC; 40 +50 oC with current derated to 0.8 rated output current Pollution degree 2 or better ( free from direct sunlight, vibration, dust, corrosive or inflammable gases, fog, vapor oil and dripped water, avoid saline environment) IP 44 Up to 1000 m above the sea level; for higher altitudes a current reduction of 1,2% for every 100 m of additional height applies
ENVIRONMENT
Air pressure operation storage transport Climatic conditions STANDARD Clearance and creepage Vibration EMC compatibility Approvals
D-type manual
12
3. INSTALLATION GUIDELINES
3.1. MECHANICAL SPECIFICATION
Control panel dimensions and fixing holes dimensions Doors can be left or right side opening. 700 x 500 x 200 500 700 200 450 650 107,5 285 107,5 40 30 10 CONTROL PANEL DIMENSIONS ( information on nameplate) 700 x 800 x 800 x 800 x 1000 x 1000 x 1000 x 500 x 600 x 600 x 600 x 600 x 600 x 600 x 250 200 250 300 250 300 350 500 600 600 600 600 600 600 700 800 800 800 1000 1000 1000 250 200 250 300 250 300 350 450 550 550 550 550 550 550 650 750 750 750 950 950 950 107,5 157,5 157,5 157,5 157,5 157,5 157,5 285 285 285 285 285 285 285 107,5 157,5 157,5 157,5 157,5 157,5 157,5 40 40 40 40 40 40 40 30 30 30 30 30 30 30 10 10 10 10 10 10 10 900 x 800 x 350 800 900 350 700 870 150 500 150 40 40 8
A B C D1 D2 E1 E2 E3 F1 F2 G fi
mm mm mm mm mm mm mm mm mm mm mm
NOTE:
In case when VVVF control panel is used, the braking resistor is mounted on the control panel. Dimensions of braking resistor depends on model, power and manufacturer. Braking resistor can be fixed at the side or at the top of the box.
D-type manual
13
NOTE:
NOTE: NOTE:
The maximum angle of inclination is 30o The control panels must be mounted in such a way that the free flow of air is ensured. The clearance to the device must be at least 150 mm. A space of at lease 50 mm must be ensured at the front. Devices that generate a large amount of heat must not be mounted in the direct vicinity of the control panel.
D-type manual
14
4. WIRING PROCEDURE
4.1. AC INPUT CONNECTION
The device must be connected to a protective grounding which will be the first to be connected and the last one to be disconnected. Flexible copper cables, class 5, type O5V-K must be used for mains connection of the device. These copper cables must be short circuit protected with external fuses. Thermomagnetic differential switches for protection can be used.
NOTE:
Residualcurrent ( FI-type) circuitbreakers can be tripped inadvertently when power is switched on if a noise filter is being used (VVVF and ACVV control panels). In these cases only use residualcurrent circuitbreakers with a drop-out delay.
Cable diameters and dimensions of protective switches must be consistent with table 4.4.4 for input voltage 400 V AC (415 V AC) or table 4.4.5 for input voltage 230 V AC (240 V AC).
P In Ci Cl S1 S2 S3 S4
rated power rated current diameter of wires for main supply (mm2) diameter of wires for lighting connection (mm2) thermomagnetic main switch curve type C (value is equivalent to short circuit current) differential main switch sensitivity 300 mA thermomagnetic switch lighting curve C differential switch lighting sensitivity 30 mA
D-type manual
15
rated power rated current star / delta current diameter of wires for motor (mm2) diameter of wires for star delta connection (mm2)
D-type manual
16
On the programmer you will find seven keys: READ WRITE PAGE UP PARAMETER UP PARAMETER DOWN VALUE UP VALUE DOWN And three separated displays for: LEFT MIDDLE RIGHT one digit display to display page number two digit display to display parameter number or error number two digit display to display parameter value or error code IT IS STRONGLY RECOMMENDED NOT TO CONNECT THE PROGRAMMER WHILE LIFT IS RUNNING! IT IS RECOMMENDED THAT THE PROGRAMMER BE DISCONNECTED WHEN PROGRAMMING OR MONITORING IS COMPLETE!
NOTE NOTE
D-type manual
17
The programmer will store all data in its internal non-volatile integrated circuit even after it is disconnected from the supply. The programmer can therefore be used to transfer data to another control panel. The data in the programmer is stored on six separate pages. The pages can be selected by pressing key PAGE UP
- page 1
PARAMETERS
For transfer of data from control panel to programmer, press key READ, with page 1 selected in page number display. Only data for page 1 will be transferred from control panel to programmer. On this page all parameters for adjusting the lift are stored. On the two digit display parameters we can see parameter number. On the two-digit display value we will see parameter's value. To move between parameters, press keys PARAMETER UP and PARAMETER DOWN.
D-type manual
18
To change the value of each parameter press keys, VALUE UP or VALUE DOWN. To transfer data for page 1 from programmer to control panel press keys: first WRITE and than PAGE UP at the same time. Transfer will be made only if maintenance drive (input 69) is active. All data for page 1 will be transferred.
- page 2
To transfer data from control panel to programmer, press key READ, with page 2 selected in the page number display. Only data for page 2 will be transferred from the control panel to programmer. On this page the functional inputs stages are set as N/O or N/C. On the two digit display parameters we can see the number of input. On the two digit display value we will see its state. Setting 0 gives a normally open input and setting 1 gives a normally closed input.
D-type manual
19
The stage is changed with keys VALUE UP or VALUE DOWN. The input number is changed with keys PARAMETER UP and PARAMETER DOWN. To transfer data for page 2 from programmer to control panel press keys: first WRITE and than PAGE UP at the same time. Transfer will be made only if maintenance drive (input 69) is active. All data for page 2 will be transferred.
- page 4
To transfer data from control panel to programmer, use the key, READ, with page 4 selected in the page number display. Only data for page 4 will be transferred from control panel to programmer. On transfer the last ten events will be transferred from the control panel to the programmer. The serial number of events will be displayed on the two digit display of parameters. The last event has serial number 10 and previous events count down to serial number 1. To move between events press keys PARAMETER UP or PARAMETER DOWN. On two-digit display of value we have the code of each event. We can convert the code to the corresponding event with the coding table found in chapter 4.
D-type manual
20
By pressing VALUE UP OR VALUE DOWN we see on the two digit display the value corresponding to the floor where the event occurred.
- page 5
ERROR TABLE
To transfer data from the control panel to the programmer, we must press key READ, with page 5 selected in the page number display. Only data for page 5 will be transferred from control panel to programmer. The complete error table will be transferred from the control panel to the programmer. The maximum number of errors in the error table is 80. On the two-digit display of parameters we see the serial number of the error. After transfer the last number of the error in the error table will be displayed. We can view previous errors by pressing keys PARAMETER UP or PARAMETER DOWN. On two digit display of value we can see the code of the error. We can convert the code to the error by using the error-coding table in chapter 5.
D-type manual
21
By pressing VALUE UP OR VALUE DOWN we see on the two digit display the value corresponding to the floor where the error occurred.
To clear the error table press keys: first WRITE and than PAGE UP at the same time. Error table in programmer and in control panel will be cleared.
D-type manual
22
- page 6
Page 6 monitors the position, direction and speed of the lift. The programmer, once connected will automatically start at page 6. On the two digit display of parameters we can see the position of the lift within the shaft. On the two digit display we can see the direction and speed of the lift as shown below: - display is empty = Lift is stood at a floor
If communication between programmer and control panel not work, Err sign will appear
NOTE
CONTROLLER MUST BE IN MAINTENANCE OPERATION TO EXECUTE WRITING DATA FROM PROGRAMMER TO CONTROLLER.
D-type manual
23
5.1. PAGE 1
01 OPEN DOOR TIME
PARAMETERS
1 - 60 sec. 1 - 60 sec. 1 - 90 sec.
Additional time which will add to open door time (01) when input Photocell (input 76) is activated
Timer is active when we use door type 5 or 8 (parameter 48). In this case after the timed period the outputs for doors will cancel as long as the lift stays at the floor. If timer is set on value 1 then antivandal is not in function.
1 - 60 sec.
Time in which the doors must close - input 305 must be active. If input is not active when timer comes to zero, the doors will open again. After three attempts without a result the timer 07 (door error) will activate, then after this time there will be one attempt to close the doors. Also the error will be logged in the error table
1 - 20 sec.
Time in which locks must be made after closing doors. Input 306 must be active. If the input is not active when the timer comes to zero, the doors will open again. After three attempts without a result the timer 07 (door error) will activate, and after this time there will be one attempt to close and lock the doors. Also the error will be logged in the error table.
Time delay between close relay de-energizing and open relay energizing.
Time which will start after 3 errors in doors closing or locking. Also all commands will be cleared when this is active.
08 PARKING TIME 1,
1 - 60 min.
Time after which the lift will go to the parking floor 1 if there is no landing or car calls. Parking floor 1 is defined in parameter 51.
09 PARKING TIME 2,
1 - 60 min.
Time after which the lift will go to parking station 2 if there is no landing or car calls. Parking station 2 is defined in parameter 52. Parking station 2 has priority over parking station 1. This parking station is normally used for lowering hydraulic lifts to the lowest station after 15 minutes without calls.
1 - 20 sec.
Time in which the output for the direction is still present after arrival at the floor. (outputs 131 and 132). Also the lift will continue to travel in this direction if a call is active in the same direction when time comes to zero..
1 - 20 sec.
D-type manual
24
1 - 90 sec.
Timer to define how long the output for the car extraction fan (relay RE9 outputs 419,420) remains on after the end of travel. If this timer is set to 90 the DEMONSTRATION DRIVE option is active. This mean that computer generate random calls to keep lift running. To disable this function this parameter must be programmed to some other value.
0 - 20 sec.
Timer for the pump change-over in star delta connection. On starting, outputs (relay RE4 terminals 407,408) and (relay RE6 terminals 410,411) are activated. After the star delta timer output (relay RE6) goes off and output (relay RE5 terminals 413,414) goes on.
Timer defining the delay of outputs for the pump or valves after the end of travel in up direction on hydraulic lifts. Selection between pump or valves is made with parameter 30 (settings 2 or 4 ).
Timer to eliminate double counting because of bad contacts on the switches for counting and positioning. This timer is active on inputs 61, 62, 63, 64, 65 and 66. After changing the state of these inputs the input is enabled for the period of this timer. The timer runs for each input independently.
16 STABILIZATION TIME
Timer starts after the end of travel. In the period of this timer all activities are disabled. After this time expires the next stage starts (opening doors, drive with fast or slow speed etc. )
0 - 450 sec.
Security timer. Timer runs when the lift is in fast speed. When the lift reaches switch for stop in station the timer runs again. The lift must reach next station or stop before this timer reaches zero. If the timer reaches zero during fast speed all outputs are disabled. Reset is only possible by switching the power off and back on after a few seconds. Unit of setting is 5 seconds per unit. (1 = 5 sec., 2 = 10 sec. etc). Timer is disabled when it is set to 00.
0 - 450 sec.
Security timer. Timer runs when the lift is in slow speed. The lift must stop before this timer reaches zero. If the timer reaches zero during slow speed all outputs are disabled . Reset is only possible by switching the power off and back on after a few seconds Unit of setting is 5 seconds per unit. (1 = 5 secs, 2 = 10 secs etc)) Timer is disabled when it is set to 00.
0 - 450 sec.
Security timer. Timer runs when the lift is driven on maintenance. The lift must stop before this timer reaches zero. If the timer reaches zero during maintenance drive all outputs are disabled. Reset is only possible by switching the power off and back on after a few seconds Unit of setting is 5 second. ( 1 = 5 secs, 2 = 10 secs etc) Timer is disabled when it is set to 00..
30 LIFT TYPE
0 1 2 3 4 -
0-4
electric two speed - or one speed electric VVVF hydraulic type 1 - delay of pump on travel UP time of delay is defined in parameter14 (delay time) hydraulic type 2 - no delays hydraulic type 3 - delay of valves on travel UP time of delay is defined in parameter14 (delay time)
D-type manual
25
31 OPERATION SYSTEM
1 - up and down collective two buttons - max. 6 floors
1-6 2-6 1-5 cabin call; inputs: 81,82,83,84,85,86 call down; inputs: 87,88,89,90,91 call up; inputs: 92,93,94,95,96
1-9
3 down collective all floors + 2 floors up and down, single button 8 stops max
1-8 1 2 3-8 cabin call; inputs: 81,82,83,84,85,86,87,88 call up; input: 89 call up and down; input: 90 call down; inputs: 91,92,93,94,95,96
1 - 15 cabin and floor call; inputs: 81,82,83,84,85,86,87,88,89,90,91,92,93,94,95 supply for cabin calls 141, 142supplies for down calls 143, 144 NOTE additional board D-switch is required
cabine call; inputs: 81,82,83,84,85,86,87,88 call up (upper station call down); inputs: 89,90,91,92,93,94,95,96
32 COUNTING SYSTEM
1 - 4 switches
stop up input 61 stop down input 62 slow speed up input 65 slow speed down input 66
0-8
2 1 switch
stop and slow speed input 61
D-type manual
26
4 - 3 switches
stop up input 61 stop down input 62 slow speed input 65
5 - 2 switches
stop up and down input 61 slow speed input 65
33 NUMBER OF FLOORS
2 - 16
Defines the number of floors for the lift. Change of value will be valid only after restart of CPU (power off and on)
34 DOOR OPEN IN FLOOR 1 no/yes 35 DOOR OPEN IN FLOOR 2 no/yes 36 DOOR OPEN IN FLOOR 3 no/yes 37 DOOR OPEN IN FLOOR 4 no/yes 38 DOOR OPEN IN FLOOR 5 no/yes 39 DOOR OPEN IN FLOOR 6 no/yes 40 DOOR OPEN IN FLOOR 7 no/yes 41 DOOR OPEN IN FLOOR 8 no/yes
01 01 01 01 01 01 01 01
D-type manual
27
1-4
output 122 is activated when the lift changes speed from fast to slow. Length of time is defined in parameter 11
output 122 is activated when lift changes speed from fast to slow but only if the landing call is active at the current floor. Length of time is defined in parameter 11
4 - starts when lift has stopped at floor and has active floor call
output 122 is activated when lift arrives at floor level but only if the landing call is active at that floor. Length of time is defined with parameter 11
1-4
output for direction (131 or 132) is active during all drive time (fast and slow speed)
output for direction (131 or 132) is active when lift is in slow speed and when waiting at a floor. When the lift is waiting at a floor without calls both outputs (131 and 132) are activated
output for direction (131 or 132) is active when lift is waiting at a floor. When lift is waiting at a floor without calls both outputs (131 and 132) are activated
10
Definition for doors when fire alarm input (input 307) is activated. Input for fire alarm is defined as on when the remote alarm contact is closed. Conversion to a normally closed contact is not possible. When lift came into fire station doors are opened and closed. Doors can be opened with cabin call, landing call or door open buttons. If the parameter value is 1 doors in fire station stays open.
0-2
D-type manual
28
0-1
1 - when the lift is on firemans mode, (input 307 is on) and input 73 (priority drive) is activated, firemans use is possible. In this stage only cabin calls are in use. If the input for firemans drive goes off the lift will return to the fire alarm station. Additional controller operation in EN81-72 norm: If maintenance mode is present on fire alarm , output 121 cabin overload is blinking with 0,5Hz frequency. Input for photocell (terminal 74) is not active doors are closing. - If the fireman drive and fire alarm are present doors are closing after two minutes regardless to input obstruction door (terminal 76). At the same time output 121 (buzzer) and 108 (door slow speed) are activated.
WARNING!
Output 108 (door slow speed) it can be used only when is not used for output position. When it can not be used we must assure correct door opening with additional reley logic.
48 DOOR TYPE
1 - photocell / semiautomatic NOTE: NOT FOR USE IN THE EU
1-8
photocell is connected between inputs 304 and 305. Doors locks are connected in series between inputs 305 and 306. The output relay RE7 drives the retiring cam
2 - manual / semi-automatic - input priority drive is on when the car is empty NOT FOR USE IN THE EU
photocell is connected between inputs 304 and 305. doors locks are connected in series between inputs 305 and 306. The output relay RE7 drives retiring cam. Input 73 - priority drive becomes on, with car empty. If the car is empty the lift will respond to a floor call even if the car door is not closed
car door contact is connected between inputs 304 and 305 series connected switches of landing doors are connected between inputs 305 and 306. Outputs RE7 and RE8 drives opening and closing of car door. Car door will remain open when the lift is waiting at floors
4 - automatic / semi-automatic
car door contact is connected between inputs 304 and 305 series connected switches of landing doors are connected between inputs 305 and 306. Outputs RE7 and RE8 drive opening and closing of car door. Car door remains open when lift is waiting at a floor
D-type manual
29
6 - automatic / automatic
car door contact is connected between inputs 304 and 305 series connected switches of landing doors are connected between inputs 305 and 306. Outputs RE7 and RE8 drives opening and closing of car door. Car door parks closed when lift is waiting at floor..
7 - automatic / automatic - waiting with open door NOTE: NOT FOR USE IN THE EU
car door switch is connected between inputs 304 and 305 series connected switches of landing doors are connected between inputs 305 and 306. Outputs RE7 and RE8 drive opening and closing of car door. Car door remains open when lift is waiting at floor.
car door switch is connected between inputs 304 and 305 series connected switches of landing doors are connected between inputs 305 and 306. Outputs RE7 and RE8 drive opening and closing of car door. Car door is parked closed when lift is waiting at floor. Park time defined with parameter 03 output RE8 for open door goes off
49 PRE-OPENING OF DOOR
0-2
0 - disabled 1 - reserved 2 - when relevelling switches + zone A and zone B are on pre-opening is activated when the lift approaches in slow speed to floor and the three inputs below are activated: when traveling up when traveling down 63 relevelling down 64 relevelling up 61 zone A 61 zone A 62 zone B 62 zone B
1-2 0-1
Definition of parking station 1. If input value is 0 parking 1 is disabled. Time without calls needed before parking 1 is defined with parameter 08
52 PARKING STATION 2
0-1
Definition of parking station 2. If input value is 0 parking 2 is disabled. Time without calls needed before parking 2 is defined with parameter 09
1 - 15
Defines fire alarm floor. Setting 0 is not possible. Lift goes to fire alarm floor when input for fire alarm (input 307) becomes active.
D-type manual
30
1-6
D-type manual
31
36
101 = 1-a 102 = 2-b 103 = 3-c 104 = 4-d 105 = 5-e 106 = 6-f 107 = 7-g 108 = parameter value 3 or 4 = 7-g; 108 = parameter value 5 or 6 = 2-b and 3-c
D-type manual
32
5.2. PAGE 2
61 INPUT 61 STOP UP ( ZONE A ) NO / NC ( 0 - 1 ) 62 INPUT 62 STOP DOWN ( ZONE B ) NO / NC ( 0 - 1 ) 63 INPUT 63 SLOW UP - RELEVELLING UP NO / NC ( 0 - 1 ) 64 INPUT 64 SLOW DOWN - RELEVELLING DOWN NO / NC ( 0 - 1 ) 65 INPUT 65 SLOW UP NO / NC ( 0 - 1 ) 66 INPUT 66 SLOW DOWN NO / NC ( 0 - 1 ) 67 INPUT 67 CABIN FULL LOAD NO / NC ( 0 - 1 ) 68 INPUT 68 CABIN OVERLOAD NO / NC ( 0 - 1 ) 69 INPUT 69 MAINTENANCE ON NO / NC ( 0 - 1 ) 70 INPUT 70 MAINTENANCE UP NO / NC ( 0 - 1 ) 71 INPUT 71 MAINTENANCE DOWN NO / NC ( 0 - 1 ) 72 INPUT 72 DOOR CLOSING BUTTON NO / NC ( 0 - 1 ) 73 INPUT 73 PRIORITY DRIVE NO / NC ( 0 - 1 ) 74 INPUT 74 DOOR PHOTOCELL NO / NC ( 0 - 1 ) 75 INPUT 75 DOOR OPENING BUTTON NO / NC ( 0 - 1 ) 76 INPUT 76 DOOR OBSTRUCTION NO / NC ( 0 - 1 ) 81 FIRE AND FIREFIGHTERS DRIVE EU standard / Australian standard ( 0 1 ) 82 DOOR OPENING OUT OF STATION (first drive) no / yes ( 0 - 1 ) 83 RESERVED 84 RESERVED 85 RESERVED 86 RESERVED 87 RESERVED 88 RESERVED 89 RESERVED 90 RESERVED 91 RESERVED 92 RESERVED 93 RESERVED 94 RESERVED 95 RESERVED 96 RESERVED
D-type manual
33
5.3. PAGE 4
List of event codes: 50 Door open 51 Door preliminary open 52 Door close 53 Door lock 54 Error in closing door cycle 55 Fast speed up 56 Slow speed up 57 Stabilization after drive cycle 58 Fast speed down 59 Slow speed down 60 Fireman's drive 61 Maintenance drive 62 Parking drive 63 Waiting for call 65 Safety circuit missing in terminal 36 66 Door is not locked 67 Travel timer fast speed 68 Travel timer slow speed 69 Travel timer maintenance speed 70 Car overload 71 Thermal protection is activated 72 Relevelling up 73 Relevelling down 74 Error in elements check 75 Lift hold 76 Priority drive. 77 Door photocell 79 Maintenance drive down 80 Maintenance drive up 81 Hydraulic pump star 82 Error in door 83 Slip correction up 84 Slip correction down 85 Fireman's drive 86 Car door is not closed 87 Landing door is not closed 88 Error in parameters 89 Slow speed limiter 91 Error in re-levelling cycle 92 Door jammed error 94 Error fast speed limit switches 95 Error first drive 96 Error safety 36
D-type manual
34
5.4. PAGE 5
ERROR TABLE
03 Error in counting
Lift approaches bottom or top floor with wrong position number - error in limit switch for fast speed at bottom (input 301) switch must be off when in zone for slow speed at bottom floor - error in limit switch for fast speed at top (input 302) switch must be off when in zone for slow speed at top floor - error on supply voltage for limit switches for fast speed - magnet to activate bi-stable limit switch for fast speed is too close to switch or wrong polarity (this can cause two pulses) - number of floors defined in parameter 33 is not correct.
04 Error on pre-opening
Error in Lift pre-opening cycle - one of three conditional inputs failed during pre-opening- or opening in drive up inputs: 63 relevelling down, 61 zone A, 62 zone B in drive down inputs: 64 relevelling up, 61 zone A, 62 zone B - wrong position of switches or magnets - error on safety circuit 185 for pre-opening-opening and relevelling with open door - error on elements for slow speed - pre-opening-opening in fast speed
D-type manual
35
D-type manual
36
19 Error in parameters
Error in parameters in memory circuit on PCB - error because parameters in memory circuit changed incorrectly check all parameters - value in one or more parameters is not within the limits - error with memory circuit on PCB.
NOTE
In this case all parameters ( page 1 ) and Input definitions ( page 2 ) must be read to the programmer, check if they are good, and write to the control panel again. After this switch the power of control panel off and on again
29 Error security 36
Continuous errors (more than 5 in one minute) on security 36 (terminal 303) - bad connection or interrupted safety line - continuous disconnections of high pressure safety on hydraulic
D-type manual
37
WARNING
SEC ELECTRONICS is not responsible for all additional parameter changing, which would be made from non authorizated person and could bring to controller or person damage. FACTORY RESET can be made when the power is ON and the controller is in maintenance mode (terminal 69). We must activate for 1 second, fire drive (terminal 307), maintenance up and maintenance down (terminals 70 and 71 ) at the same time. These function is possible only 10 seconds after the controller is powered ON (controller signal LED is ON ).
WARNING
When factory reset is made parameters are diferent as preset values. Is essential to made parameter correction. Look to the list of preset parameters or contact SEC ELECTRONICS!
WARNING
During the factory reset procedure it could came to uncontrollable controller activity so all controller outputs must be disconected.
D-type manual
38
Special program for programming D type control panel runs under Microsoft Excel c program. Normally, three files must be in CD with this program: 1. 2. 3. xxxxxx.xls the Microsoft Excel c file with running program xxxxxx.dll supporting dll file which support connection between program and computer serial port readme.txt with description where to install dll file and how to use program
Through programming with PC all features of programming with programmer are accessible and some more things.
Parameters
Parameter 01 Open door time 03 Hold door time 05 Lock door time 07 Door error time 08 Parking time 1 09 Parking time 2 11 Arrival gong time (* 1 - 60s *) (* 1 - 60s *) (* 1 - 20s *) (* 1 - 10min *) (* 1 - 60min *) (* 1 - 60min *) (* 1 - 20s *)
Factory value
Parameter 30 Lift type 31 System type 32 Copying system 34 Door open in 1. floor 35 Door open in 2. floor 36 Door open in 3. floor 37 Door open in 4. floor 38 Door open in 5. floor 39 Door open in 6. floor 40 Door open in 7. floor 41 Door open in 8. floor (* 0 - 4 *) (* 1 - 9 *) (* 1 - 8 *)
Factory value
3 1 1 10 10 0,5 1 1 2 2 5 20
0 1 4 6 1 1 1 1 1 1 1 1
02 Extend open door time (* 1 - 60s *) 04 Closing door time (* 1 - 60s *) 06 Exchange close/open (* 0,1 - 9,9s *)
D-type manual
39
13 Star delta time 14 Pump delay time 15 Switch time 16 Stabilisation time
1 1 1 1 300 300 0
42 Arrival output type 44 Doors in fire alarm 45 Ouput from fire alarm 46 Fireman drive 48 Door type 49 Preopening doors 50 Speed on maintenance 51 Parking station 1 52 Parking station 2 53 Fire alarm station 54 Output for position
1 1 0 0 0 1 6 0 1 0 0 1 0
17 Flight time - fast speed (* 0 - 450s *) 18 Flight time - slow speed (* 0 - 450s *) 19 Flight time - maint. speed (* 0 - 450s *)
I / O type
Input logic (pos/neg=0/1) 61 Input 61 stop up 62 Input 62 stop down 63 Input 63 slow relevel up 64 Input 64 slow relevel down 65 Input 65 slow speed up 66 Input 66 slow speed down 67 Input 67 full load cabin 68 Input 68 overload cabin 69 Input 69 maintenance on 70 Input 70 maintenance up 71 Input 71 maintenance down 72 Input 72 door closing button 73 Input 73 priority drive 74 Input 74 door photocell 75 Input 75 door opening button 76 Input 76 door stuck
Factory value
Parameter 81 Fire and firefighter drive (0=EU, 1=AUS) 82 Doors open out of station 83 Reserved 84 Reserved 85 Reserved 86 Reserved 87 Reserved 88 Reserved 89 Reserved 90 Reserved 91 Reserved 92 Reserved 93 Reserved 94 Reserved 95 Reserved 96 Reserved
Factory value
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
D-type manual
40
I / O status
Input Input stop up Input stop down Input relevel down Input relevel up Input slow speed up Input slow speed down Cabin full load Cabin overload Maintenance on Maintenance up Maintenance down Doors closing Priority drive Door photocell Door open button Door stuck End fast speed down End fast speed up Protections Land doors close Cabin doors close Doors locks close Fire drive Elements check state Output 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 0 1 Drive down Drive up Fast speed Pump delta Pump on Cabin blower Doors opening Pump star Doors closing Directions up Directions down Error Beep Gong state 0 1 1 1 1 1 0 0 1 1 0 0 0 0
Calls
UP button 16 15 14 13 12 11 10 9 0 0 0 0 0 0 0 0 call indicator 0 0 0 0 0 0 0 0 DOWN button 0 0 0 0 0 0 0 0 call indicator 0 0 0 0 0 0 0 0 CAR button 0 0 0 0 0 0 0 0 call indicator 0 0 0 0 0 0 0 0
D-type manual
41
8 7 6 5 4 3 2 1
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
Last events
Message(FIFO) Waiting for call Doors close Doors open Waiting for call Stabilisation Slow speed down Fast speed down Doors lock Mes. nr. 63 52 50 63 57 59 58 53 Station 1 1 1 1 1 16 16 16 16
Errors table
Error E4 Counting E4 Counting Error nr. 3 3 Station 3 1
NOTE
For programming with computer read also readme file on CD with program
D-type manual
42
7. ABBREVIATIONS
7.1. TERMINALS ON CONTROL PANEL
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 25a 26 26a 27 28 29 31 31a 32 33 34 35 35a 36 37 38 39 40 41 42 43 45 46 47 48 ground L1 input L2 input L3 input N input motor U1 motor V1 motor W1 motor U2 motor W2 motor V2 3F 400V (415V) AC 50 Hz (60 Hz)
L input phase for cabin light power for transformer door motor U1 door motor V1 door motor W1 door motor U1 door motor V1 door motor W1 DOOR A
DOOR B
blower motor U1 ( only on electric elevator ) blower motor V1 blower motor W1 blower in cabin 230V AC oil heater thermal switch for blower motor ( only on electric elevator ) thermal switch for blower motor brake ( only on electric elevator ) brake second terminal ( if brake voltage is not insulated with transformer) retiring cam ( only on semiautomatic door ) retiring cam second terminal ( if retiring cam voltage is not insulated with transformer) +48V fast speed limit switch down fast speed limit switch up safety circuit start safety circuit after stop in cabin safety circuit after stop maintenance safety circuit after rope malfunction switch safety circuit after overspeed brake switch safety circuit after stop in shaft switch safety circuit after end limit switch safety circuit after overspeed governor switch safety circuit after landing doors switches safety circuit after cabin door switch safety circuit after landing doors lock switches +48V open contact for door - common open contact for door - opening open contact for door - closing end switch door opening end switch door closing
D-type manual
43
51 52 56 57 58 59 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 101 102 103 104 105 106 107 108 121 122 123 131 132
zone A switch zone B switch solenoid valve down solenoid valve up solenoid valve fast speed down solenoid valve fast speed up stop up switch stop down switch relevelling down switch relevelling up switch slow speed up switch slow speed down switch cabin full load switch cabin overload maintenance drive on switch maintenance drive up switch maintenance drive down switch button force door closing priority drive switch door photocell switch button force door opening door obstruct ion switch 0V (ground) for cabin call buttons 0V (ground) for landing call buttons +24V for cabin call lamps +24V for landing call buttons cabin call 1 cabin call 2 cabin call 3 cabin call 4 cabin call 5 cabin call 6 cabin call 7 cabin call 8 landing call landing call landing call landing call landing call landing call landing call landing call output output output output output output output output
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
output cabin overload output arrival to station - gong output out of work output direction down output direction up
D-type manual
44
221 222 276 276a 277 277a 351 352 538 360 371 372 383 384
serial indicator - ground serial indicator - data solenoid valve down - hydraulic BERINGER with module ELRV solenoid valve up - hydraulic BERINGER with module ELRV
switch for emergency lowering switch for emergency lowering output for emergency door opening solenoid valve for emergency lowering ( 12V DC ) output emergency alarm ( 12V DC ) output emergency light ( 12V DC ) thermistors in main motor or pump motor
Ver. 2.02
D-type manual
45
F1 F2 F4 F5 F6 F7 F8 F31 V1 V2 V3 V4 V9 RE1 RE2 RE3 RE4 RE5 RE6 RE7 RE8 RE9 RE10 RE12 RE11 RE13 RE14 RE18 RE17 RE22 RE16 RE15 RE21 RE19 RE20
fuse for electronic board Doppler LC 3F fuse for door motor fuse transformer fuse transformer fuse 24V fuse 48V fuse 230V AC for contactors 3F fuse for motor solenoid valve down solenoid valve up solenoid valve slow speed solenoid valve fast speed solenoid valve emergency lowering relay down relay up relay fast speed relay pump on relay pump delta relay pump star relay door close relay door open relay cabin blower relay position 1 relay position 2 relay position 3 relay position 4 relay position 5 relay position 6 relay position 7 relay position 8 relay cabin overload relay arrival to station - gong relay out of work relay direction up relay direction down
D-type manual
46
NOTE NOTE
bistable switches must be mounted correctly cable is on bottom side of switch There must be 10 mm space between magnet and switch for proper operation
NOTE
NOTE
switches and magnets must not be mounted near to other metal parts ( bolts, brackets)
magnets for bistable switches must be correctly oriented ( black white) first time bistable switches must be triggered manually ( by magnet ) prelimit switches described in this manual are bistable magnetic type which is not always acceptable especially for speeds up to 1 m/s where prelimit switches must be mechanical type ( as final limit switch ) final limit switch is not described in this manual but it is obligatory
NOTE
D-type manual
47
D-type manual
48
D-type manual
49
D-type manual
50
D-type manual
51
D-type manual
52
D-type manual
53
D-type manual
54
D-type manual
55
D-type manual
56
WARNING ATTENTION Involved personnel must be made fully aware that when using this
wiring during installation phase, the only safety element for stopping lift is the stop button. No other device is connected to the system during this period.
WARNING ATTENTION All wire bridges for terminals short circuit connection must be removed
after the installation period and replaced with the valid wiring system.
WARNING ATTENTION This method for installation is not valid in all countries. In this case local
and national safety regulation must be considered.
NOTE
After switch ON check phase sequence device. BOTH LED DIODES MUST LIT. If not, switch supply OFF and change wires between terminals 2 and 3 ( correct phase sequence)
D-type manual
57
Terminals for one speed motor with 6 wires ( hydraulic star delta start)
NOTE
At hidraulic lift instalation we must also bridge terminals 30 and 30A (final limit switch). Prelimit and final limit switches are not connected in this case and therefore offer no protection from over travel of the lift car 58 291 801 104
WARNING ATTENTION
D-type manual
10. START UP
10.1. PRE POWER CHECKS
The following should be checked before switching ON the control panel: Grounds / Grounding Verify ground connections control panel to main motor and control panel to car Verify ground connections input to control panel Verify AC Input, AC Output and control wiring arent grounded Connections Verify Verify Verify Verify Verify AC Input connections main motor connections prelimit switches connections safety line connections stop in station switches connections ( ( ( ( ( 0, 1, 2, 3, 4, 11 ) 5, 6, 7, 8, 9, 10 ) 27, 28, 29 ) 31, 32, 33, 34, 34A, 35, 35A, 36, 37, 38, 39 ) 51, 52, 61, 62, 63, 64 )
( 69 )
WARNING On first switching on, the control panel must be in maintenance mode 10.2. VOLTAGE AND CONTROL ELEMENTS CHECK
After first switching on the control voltages in system: Measure 48V DC on terminal 40. Measured voltage must be in range between 40 and 50 V DC
NOTE
Measure 24V DC on terminal 80. Measured voltage must be in range between 16 and 23 V DC
NOTE
Measure 12V DC from accumulator charger on faston connectors by removing accumulator. Red faston connector is +12V DC and black one is ground. Measured voltage must be in range between 13 and 15 V DC
NOTE
Check phase sequence device. BOTH LED DIODES MUST LIT. If not, switch supply OFF and change wires between terminals 2 and 3 ( correct phase sequence) Check PTC module ( thermistor control ). LED PTC OK must lit. If not, check thermistors and switches connected on terminals 281, 282, 283, 284.
D-type manual
59
WARNING Maintenance up button must move lift up. If lift goes down, change wires in main motor
connections. If a two speed motor is applied, the fast speed wires must be changed also.
WARNING In hydraulic lift check correct pump rotation. If pump runs in reverse change wires in
pump motor connections
NOTE
When lift is in station LED ELEMENTS CHECK must light. This LED checks the operation of relays, contactors, thermo switches and thermistors
All inputs can be controlled through LEDs. When LED is lit switch is closed.
WARNING ATTENTION
Prelimit and final limit switches are not connected in this case and therefore offer no protection from over travel of the lift car
D-type manual
60
NOTE NOTE
LED 5V DC indicate presence of internal voltage + 5V DC. Voltage can be incorrect because LED only indicates presence and not level of volts LED 24V DC indicate presence of voltage + 24V DC. Voltage can be incorrect because LED only indicate presence and not level of volts
D-type manual
61
10.5. TROUBLESHOOTING
LIFT WILL NOT OPERATE IN MAINTENANCE MODE check AC input voltage on terminals 1, 2 and 3, check AC input neutral on terminal 4, check AC input voltage on terminal 11 ( if exist) check proper operation of phase sequence and failure device. In normal operation both LEDs lit. check fuses and motor protection devices check low voltage in system: 48V DC on terminal 40 ( 40 50 VDC ) 24V DC on terminal 80 ( 16 23 VDC ) 5V DC LED in PCB 5V DC
check safety line on terminals 31, 36, 37, 38, 39 ( use first LEDs in PCB safety circuit 36, 37, 38 and 39 ). Measure also voltage in terminals 31, 36, 37, 38 and 39. Voltage range must be between 40 and 50 VDC. LEDs are only indicators for voltage presence but voltage can be too low. check prelimit switches on terminals 28 and 29 ( use first LEDs in PCB fast speed limit switch up and down ). Measure also voltage in terminals 28 and 29. Voltage range must be between 40 and 50 VDC. LEDs are only indicators for voltage presence but voltage can be too low. check if computer works by looking at LED error table indicator . LED must blink if computer works normally in maintenance mode check parameters and input definitions. ( see section PROGRAMMING ). Specially check parameters and definitions related to maintenance mode: parameter 50 speed on maintenance definition 69 input maintenance ON definition definition 70 input maintenance UP definition definition 71 input maintenance DOWN definition definition 81 input car call 1 definition ( door opening on maintenance mode) definition 82 input car call 2 definition ( door closing on maintenance mode) check action with programmer on page 6 (see section PROGRAMMING WITH PROGRAMMER ) if there is one or two bars up or down, computer works normally and problem is in power section
LIFT WILL NOT OPERATE IN MAINTENANCE DOWN DRIVE check action with programmer on page 6 (see section PROGRAMMING WITH PROGRAMMER ) if there is one or two bars down, computer works normally and problem is in power section: check motor, valves or brake connection check contactors and relays if there is no action in programmer check prelimit switch down ( terminal 28 ) LED fast speed limit switch down. Measure also voltage in terminal 28. Voltage range must be between 40 and 50 VDC. LEDs are only indicators for voltage presence but voltage can be too low.
D-type manual
62
LIFT WILL NOT OPERATE IN MAINTENANCE UP DRIVE check action with programmer on page 6 (see section PROGRAMMING WITH PROGRAMMER ) if there is one or two bars up, computer works normally and problem is in power section: check motor, valves or brake connection check contactors and relays if there is no action in programmer check prelimit switch up ( terminal 29 ) LED fast speed limit switch up. Measure also voltage in terminal 29. Voltage range must be between 40 and 50 VDC. LEDs are only indicators for voltage presence but voltage can be too low.
LIFT WILL NOT START IN NORMAL MODE check if lift operates normally in maintenance mode. Lift must operate normally in both directions in maintenance mode check LED error table indicator . LED must NOT blink. If LED is blinking some of the conditions are missing check door operation. Doors must close ( safety line 39 ). Check conditions which will prevent door closing: input 76 door obstruction signal input 74 door photocell signal input 75 button door opening check also related input definitions ( definitions 74, 75 and 76) (see section PROGRAMMING ) check conditions which prevent normal mode: input 68 input 73 input 307 check also related input definitions ( definitions car overload key priority drive fire drive input 68 and 73) (see section PROGRAMMING )
check action with programmer on page 6 (see section PROGRAMMING WITH PROGRAMMER ) if there are two bars , computer works normally and problem is in power section: check motor, valves or brake connection check contactors and relays ( especially for fast speed ) check parameters and definitions ( see section PROGRAMMING), use error table or last event table for help to find out reason for abnormal work. SUGGESTION: clear the error table ( see section PROGRAMMING PAGE 5 ) switch control panel off and after 30 seconds on again if lift does not start in normal operation look to the error table there must be at least one error which caused this situation if error table is still empty use last events table to find out the reason by looking at last event in lift ( see section PROGRAMMING - PAGE 4 )
D-type manual
63
LIFT WILL NOT STOP IN STATION FIRST TIME AFTER POWER ON check stop in station signals ( terminals 51, 52, 61, 62, 63, 64 ) Measure also voltage in these terminals. Voltage range must be between 40 and 50 VDC. LEDs are only indicators for voltage presence but voltage can be too low. check appropriate input definitions for these inputs ( definitions 61, 62, 63, 64 )
LIFT STOPPED IN STATION AFTER FIRST TIME BUT WILL NOT ACCEPT CALLS check ELEMENTS CHECK input ( terminal 308 ). LED for this input must lit when lift is in station check FIRE DRIVE input ( terminal 307 ). LED for this input must NOT be lit when lift is in station check safety circuit 185, LED safety OK must lit, if not the device or zone switches are not working properly, see section SAFETY CIRCUIT 185
LIFT COUNTS TWO FLOORS INSTEAD ONE check operation of magnetic switches ( switches for prelimit signals, slow speed signals, stop signals and zone signals) check bistable magnetic switches, distance between switches and magnets must be 1 cm check if there is some bolts or nuts near to the magnets ( they can work like magnets if they are too close to the magnets if magnets are mounted on the guide rails they must be on the outside of the guide, because on the other hand magnetic switches will not work properly
LIFT SOMETIMES STOPS IMMEDIATELY AFTER STARTING check stop is not station switches ( terminals 61 and 62 or LEDs STOP UP and STOP DOWN) both LEDs must be LIT when lift stops in station.
D-type manual
64
NOTE
The visible digit shown on the display is not important. It is the number of flashes or blinks which must be considered.
D-type manual
65
11.
61 - 76
inputs
301 - 308
48VDC (not stabilized) (35VDC - 51VDC) 48VDC (not stabilized) (35VDC - 51VDC) max. 60 V AC/DC
typ. 5 mA
typ. 5 mA
common 300
RE1 - RE9
max. 500 mA for output NO INDUCTIVE LOAD max. 250 V AC/DC max. 1000 mA for output NO INDUCTIVE LOAD
D-type manual
66
D-type manual
67
D-type manual
68
D-type manual
69
D-type manual
70
D-type manual
71
cabine call 1 cabine call 2 cabine call 3 cabine call 4 cabine call 5 cabine call 6 cabine call 7 cabine call 8 landing call 1 landing call 2 landing call 3 landing call 4 landing call 5 landing call 6 landing call 7 landing call 8 input input input input input input input input input input input input input input input input output output output output output output output output output output output output output output output
stop up stop down relevelling down relevelling up slow speed up slow speed down cabine full load cabine overload maintenance on maintenance up maintenance down door closing priority drive door photocell door opening door obstruction common for position outputs, overload output, gong output, out of work output position 1 position 2 position 3 position 4 position 5 position 6 position 7 position 8 cabine overload arrival to station gong lift is out of work common for directions direction down direction up
D-type manual
72
201 202 203 204 211 213 214 221 222 300 301 302 303 304 305 306 307 308 401 402 403 404 405 406 407 408 409 410 411 412 413 414 415 416 417 418 419 420 F1 F2 B2 U22 U41 U9 U3 PRG
voltage supply 24V AC for signalization output voltage +24V for signalization output voltage 0V for signalization
voltage supply 10V AC for computer protective ground output voltage 0V for serial position display output voltage 24V DATA for serial position display common for inputs 301, 302, 303, 304, 305, 306, 307 and 308 input fast speed limit switch down input fast speed limit switch up input safety line after all cabine safety elements input safety line before cabine door input safety line after cabine door input end safety line after landing doors (or doors locks) input fire drive input elements check output output fast speed output output direction down output common direction output direction up
output pump on output NC output COM output NO output NC output COM output NO
pump star
pump delta
output output door close output common door output door open output output cabine blower fuse for computer ( 1A) fuse for 24V (3.15A) rectifier for 24V 6A / 600V integrated circuit for cabine calls 1 8 ULN2803A DIL integrated circuit for landing calls 1 8 ULN2803A DIL memory circuit 93C56 program circuit EPROM 27c256 or 27c512 RJ45 socket for programing ( RS232C)
D-type manual
73
up to 6 stops UP and DOWN collective selective system up to 8 stops DOWN collective selective system up to 9 stops DOWN collective selective system ( 1. and 9. call is the same in car and in floor) up to 11 stops UP and DOWN collective selective system ( D-type switch board is used) up to 15 stops DOWN collective selective system ( D-type switch board is used) up to 16 stops APB system
When D-type switch board is used LED lights in call buttons or diodes on inputs must be installed. Definition of different inputs in different systems is follows: UP and DOWN collective selective system maximal 6 stops ( parameter 31 is 1 )
DOWN collective selective system maximal 8 stops ( parameter 31 is 2 or 3) UP collective selective system maximal 8 stops ( parameter 31 is 9)
D-type manual
74
UP and DOWN collective selective system with D-type switch board maximal 11 stops (parameter 31 is 4)
DOWN collective selective system with D-type switch board maximal 15 stops ( parameter 31 is 6 )
D-type manual
75
D-type manual
76
D-type manual
77
D-type manual
78
Duplex cable
Only original duplex cable must be used to avoid problems in operation. Cable must be 360 grounded near the PRG socket with omega element. Duplex cable must always be separated from other signal or power cables. Distance between cable and other cables must be minimal 10 cm. If cable is crossing other cables this crossing must be made at 90 angle. Maximal length of duplex cable is 5 m. When cable is disconnected elevators will immediately work in simplex mode. If programmer is connected to the PRG socket, the computer will recognize the difference and it will communicate with programmer. For this operation it is not necessary to disconnect power supply. NOTE If serial cable is disconnected take care that the connector will not touch ground or other terminals.
D-type manual
79
Terminal 77 ------------------------------- Terminal 77 ------------------- 0V Terminal 79 --------------------------------------------------------I>I------- 24V Terminal 79 --------I>I----/ ... Terminal 89-------------------------------- Terminal 89 ------------------- Terminal 90-------------------------------- Terminal 90 ------------------- Terminal 91-------------------------------- Terminal 91 ------------------- ... All used landing calls should be connected together!
landing calls
D-type manual
80
This circuit is specially developed to make it possible to move the car while the doors are open. Circuit board 76 x 86 mm with heigh of 35 mm for installation in control unit 4 x 3mm hole for mounting
The following manouvres are possible: - advanced door opening - relevelling upwards or downwards with the doors open
Circuit content:
- 3 x safety relay with six guided contacts - 2 x LED diode for status display - 7 x terminal for connection
Supply voltage Supply current Ambient temperature Degree of protection EMC compatibility Approvals
D-type manual
81
The circuit does not need any additional power supply. All relays are made for 48 V DC supply. Explanation of work: - elevator control unit give 48 VDC to terminal 3 when elevator start - slow speed in arriving to station. This voltage must stay all the time to the next start - then magnetic switch ZONE A give 48 VDC to terminal 2 - and magnetic switch ZONE B give 48 VDC to terminal 1 - in this case connection is closed between terminals 4 - 5 and 6 - 7 - when elevator stopped in station elevator control unit should check one of link (4 5 or 6 7) - in the case that there is no connection elevator must not proceed to drive - LED I1 - LED I2 parallel to input 1 parallel to input 2
Explanation of LED:
D-type manual
82
13. MAINTENANCE
13.1. CARE
The control panels must be installed according to the relevant installation regulations. They do not require any particular maintenance. They should not be cleaned with a wet or moist cloth. The power supply must be switched off before cleaning.
13.2. SERVICE
The screws of all terminals on the device should be re-tightened two weeks after initial commissioning. This should be repeated each year. If control panels have been stored for more than three years, the capacitors may have been impaired. Before commissioning these devices, it is advisable to regenerate the capacitors by connecting them to the voltage for two hours with the control panel disabled. After these operations the device is ready to be installed without limitations.
13.3. REPAIRS
Repairs of the device should only be carried out by the specialist personnel ( qualified by the manufacturer) If you carry out a repair on your own, observe the following points: when ordering spare parts do not only state the device type but also the device serial number. It is also useful to state the serial number of processor card and version of operation program ( sticker on the program circuit U3 )
SPARE PARTS
U3 integrated circuit with operation program. Type is 27C256 or 27C512. Integrated circuit must be properly oriented. Use correct tool for extracting to avoid damage on socket U9 integrated circuit with parameters. Type is 93C56. Integrated circuit must be properly oriented. Use correct tool for extracting to avoid damage on socket U22 integrated circuit drivers for button lamps 1 8. Type is ULN 2803.Integrated circuit must be properly oriented. Use correct tool for extracting to avoid damage on socket U41 integrated circuit drivers for button lamps 9 16. Type is ULN 2803.Integrated circuit must be properly oriented. Use correct tool for extracting to avoid damage on socket B1 rectifier for 12V CPU supply. Type is KBU6K. Rectifier is soldered. Replacement of these components must be made by specialist personnel B2 rectifier for 24V supply for buttons and lamps. Type is KBU6K Rectifier is in the four screw terminals. Observe proper orientation ( + AC AC - ) F1 fuse 2A for 12V CPU supply. Fuse is glass type 5 x 20 mm in socket USE OF INPROPER FUSE CAN DAMAGE PRINTED CIRCUIT BOARD F2 fuse 3,15A for 24V. Fuse is glass type 5 x 20 mm in socket. USE OF INPROPER FUSE CAN DAMAGE PRINTED CIRCUIT BOARD
D-type manual
83
Legend:
integrated circuit with program integrated circuit with parameters integrated circuit drivers for button lamps 1 8 integrated circuit drivers for button lamps 9 16 rectifier for 12V CPU supply rectifier for 24V supply for buttons and lamps fuse 2A for 12V CPU supply fuse 3,15A for 24V socket for programmer or PC cable
D-type manual
84
This product is intended only for professional assemblers. The responsibility for the maintenance of EMC compliance of an installation shall be with the installer and not the manufacturer. The manufacturer is required to provide recommendations and guidelines for maintaining EMC compliance after installation and this is given in this guide. The CE mark and Manufacturers Declaration of Conformity on SEC control panels relate to compliance with the Low Voltage directive only. The product standard for lift control panel is EN 12015 for emission and EN12016 for immunity and all SEC control panels have been tested for conformity with the various levels applicable under the standard. Next normative references are used: Emission: Immunity: EN 55011 EN 55014 EN EN EN EN 61000 61000 61000 61000 4 4 4 4 2 3 4 11
D-type manual
85
GROUND TERMINALS OF THE CONTROL PANEL SEC control panels are provided with two ground terminals ( green-yellow terminal with mark 0 and ground terminal with multi screws ) one must be connected to the ground bus MINIMAL DISTANCE BETWEEN SIGNAL AND POWER CABLES The minimum distance between parallel signals and power cables is 30 cm. Possible crossings have to be made at 90o. SHIELDING OF THE SUPPLY FOR AN AC MOTOR The AC motors have to be supplied through a four pole shielded cable ( three phases plus a green/yellow ground wire), or though four unshielded cables, which are inserted inside a metal channel. It is important that a direct connection ( four cables ) between the panel grounding and the motor ground has been made and that the fourth cable had been inserted in a shield. GROUND CONNECTION TO BOTH SIDES OF THE CABLE SHIELD ( AC MOTOR ) The shield of the supply cable of the AC motors must be grounded on both sides in order to obtain 360o contact, that means the whole shield. This can be accomplished using suitable metallic EMC cables press grounded at full 360o at the input of the cabinet and of the motors terminal strip. If this connection is not possible, the shielded cables should be brought inside the cabinet and connected with an omega connector to the mounting panel- The same must be done on the motor side. In case a 360o connection on the motors terminal strip is not possible, the shield must be grounded before entering into the terminal strip. This should be done on the metal support of the motor, using an omega connector. In case a metal duct has to be used, it should be grounded at full 360o where possible. PIGTAIL AVOIDANCE While grounding the shields of the cables, one has to use a 360o connection ( E.g. omega bus ) with a pigtail connection to be absolutely avoided. By pigtail is meant the connection to earth ground of the cable shield by means of an additional wire. SUPPLY CABLES TO THE DC MOTORS The supply cables of DC motor do not need to be shielded. DIRECT CONNECTION BETWEEN THE GROUND BUS AND MOTOR CHASSIS Independently from ground-connection of the motors chassis, it must always be connected to the ground wire ( green/yellow ) coming from the panel ground bus. MAXIMAL LENGTH OF THE AC MOTORS CABLES INSIDE THE CABINET From the grounding of the screen side cabinet of the panel terminal strip, the supplys cables have to measure 30 cm maximum. ENCODER CABLES The encoder cable must be shielded and grounded at the panel at a full 360o. The female connector on the inverter has been foreseen for that connection, therefore it is enough to have the cable shield connected at 360o in the conductive case of the male connector. In order to check that the shield is not connected on the motor side remove the encoder connector from the inverter and verify with a tester the presence of a high impedance between the shield and the metal case of the encoder or of the motor.
D-type manual
86
SEC ELECTRONICS
___________________________________________________________________________________
Declaration of Conformity
Manufacturer: SEC ELECTRONICS Neverke 30 6256 KOSANA SLOVENIA Details of electrical equipment Model number:
and complies with the previsions of the following EC Directive(s): 73/23/EEC modified by 93/68/EEC and named Low Voltage Directive 2000
Place of Issue:
Neverke
D-type manual
87