Manifold Swagelok Ms 01 178

Download as pdf or txt
Download as pdf or txt
You are on page 1of 16

www.swagelok.

com

Instr ume nt Manifolds

V, V B, a nd V L Se r ie s
2-, 3-, and 5-valve instrument manifolds All 316 stainless steel construction with PTFE packing Working pressures up to 6000 psig (413 bar) Temperatures up to 1200F (648C) with Grafoil valve packing

Instrument ManifoldsV, VB, and VL Series

Contents

Manifold Features
Page Swagelok offers a variety of 2-, 3-, and 5-valve instrument manifolds. The 2-valve manifolds are designed for static pressure and liquid level applications; the 3- and 5-valve manifolds are designed for differential pressure applications. The V, VB, and VL series manifolds feature a horizontal body design. Manifold connections include 1/2 in. and 12 mm female Swagelok tube fitting, 1/2 in. female pipe (NPT and ISO 228/1), and flange (MSS SP-99).

Manifold Features . . . . . . . . . . . 2 Valve Features . . . . . . . . . . . . . . 3 Technical Data . . . . . . . . . . . . . . 3 Testing . . . . . . . . . . . . . . . . . . . . 3 Cleaning and Packaging . . . . . . 3 Pressure-Temperature Ratings . . . . . . . . . . . . . . . . . . . 3 2-Valve Manifolds . . . . . . . . . . . . 4
Introduction V Series VL Series

Flange Connections
Flange design meets the

requirements of MSS SP-99.


Standard flange seal is a

fluorocarbon FKM O-ring.


Flange seals and flange bolts

are included with manifold.

Safety Stop Pin


316 stainless steel pin

3-Valve Manifolds . . . . . . . . . . . . 7
Introduction V Series

5-Valve Manifolds . . . . . . . . . . . . 9
Introduction V Series VB Series

prevents detachment of the bonnet from the body due to vibration.


Design is vibration tested

Bonnet-to-Body Seal
Metal-to-metal seal

eliminates the need for O-ring seals.

to MIL-STD 1671, Sections 5.1.2.4.2 through 5.1.2.4.6.

Options . . . . . . . . . . . . . . . . . . . 12
High-Temperature Packing Flange Seal Materials Flange Fasteners Mounting Hole Center Line Hydrostatic Testing

Mounting Kits . . . . . . . . . . . . . . 12
Mounting Bracket Kit Steam-Trace Block Kits

Maintenance Kits . . . . . . . . . . . 12
Flange Seal and Bolt Kits

Body Design
One-piece construction

Mounting Options
2 1/8 in. (54 mm) port

Accessories . . . . . . . . . . . . . . . 13
Eccentric Flanges C  oncentric and Eccentric

provides strength.

center lines for direct instrument mounting with flange connections.


Remote mounting

Pipe Nipples
D  P Transmitter Calibration

Materials of Construction
All 316 stainless steel construction. Designed with 4:1 design factor.

Fittings
Gauge Adapters Positionable Gauge Adapters

with female Swagelok tube fitting and NPT connections.

Internal Finish
Burr-free threads and internal

surfaces reduce leaks, promoting accurate transmitter readings.

A packing adjustment may be required periodically to increase service life and to prevent leakage. Valves that have not been cycled for a period of time may have a higher initial actuation torque. To increase service life, ensure proper valve performance, and prevent leakage, apply only as much torque as is required to achieve positive shutoff.

Instrument ManifoldsV, VB, and VL Series

Valve Features
The flow through a Swagelok manifold is controlled by a series of stainless steel needle valves. Each valve has a specific functionto block pressure, to bleed off pressure, or to equalize pressuredepending on its location on the manifold. The control of all these functions is shared by two needle valve designsa large-bonnet needle valve for manifold orifices of 0.156 in. (4.0 mm) and a small-bonnet needle valve for manifold orifices of 0.125 in. (3.2 mm). On both designs, the stem packing is externally adjustable in the open position. PTFE is the standard packing material; optional Grafoil packing is available for high-temperature applications.

LargeBonnet Valve

SmallBonnet Valve

Packing nut permits stem packing adjustment. PTFEstem packing seals the system fluid to atmosphere. Rolled stem threads enhance cycle life. Safety back seating seals in the fully open position, providing a secondary stem seal.

Stainless steel handle features a divot point set screw to resist loosening due to vibration. Hardened stainless steel, nonrotating ball stem tip provides consistent shutoff.

Packing bolt permits stem packing adjustment. Rolled stem threads enhance cycle life. PTFE packing is below stem threads to isolate threads from system fluid. Safety back seating seals in the fully open position, providing a secondary stem seal.

Technical Data
Orifice Size (block valve) 0.125 in. (3.2 mm) for all 2-valve V series 0.156 in. (4.0 mm) for all others 2-valve: 2.0 to 3.5 lb (0.9 to 1.6 kg) Weight 3-valve: 3.2 to 6.4 lb (1.5 to 2.9 kg) 5-valve: 6.0 to 8.0 lb (2.7 to 3.6 kg)

Pressure-Temperature Ratings
ASME Class Material Group 2500 2.2

Testing
Every Swagelok instrument manifold is factory tested with nitrogen at 1000 psig (69 bar). Seats have a maximum allowable leak rate of 0.1 std cm3/min. Shell testing is performed with a liquid leak detector to a require ment of no detectable leakage.

Material Name 316 SS Working Pressure Temperature psig (bar) F (C) 65 (53) to 100 (37) 6000 (413) 200 (93) 5160 (355) 250 (121) 4910 (338) 300 (148) 4660 (321) 350 (176) 4470 (307) 400 (204) 4280 (294) 450 (232) 4130 (284) 500 (260) 3980 (274) 550 (287) 3870 (266) 600 (315) 3760 (259) 650 (343) 3700 (254) 700 (371) 3600 (248) 750 (398) 3520 (242) 800 (426) 3460 (238) 850 (454) 3380 (232) 900 (482) 3280 (225) 950 (510) 3220 (221) 1000 (537) 3030 (208) 1050 (565) 3000 (206) 1100 (593) 2685 (184) 1150 (621) 2285 (157) 1200 (648) 1715 (118)
Ratings based on optional Grafoil packing. Ratings limited to:
20 to 450F (28 to 232C) with standard fluorocarbon FKM flange seals. 450F (232C) with standard PTFE packing. 1000F (537C) with Grafoil packing and MSS flange end connection.

Cleaning and Packaging


Every Swagelok instrument manifold is cleaned and packaged in accordance with Swagelok Standard Cleaning and Packaging (SC-10), MS-06-62.

Instrument ManifoldsV, VB, and VL Series

2-Valve Manifolds
V Series
Process side Instrument side

VL Series

Process side

Instrument side

Block valve Bleed valve

Block valve
Allows for block and bleed (or calibration) of static pressure

Block valve
Designed for liquid level applications Consists of two block valves operating in parallel to shut

transmitter or gauge
Consists of one block valve and one bleed valve End connections1/2 in. and 12 mm female Swagelok tube

off either one of the two process lines through the manifold
No equalizer passage through the manifold End connections1/2 in. female pipe (NPT) to flange Horizontal body style Direct instrument mount

fitting; 1/2 in. female pipe (NPT); flange (MSS)


Horizontal body style Direct instrument mount and remote mount

V Series
Materials of Construction
Materials for pressure-containing wetted parts are in compliance with ASME B31.1.
Component 1 Handle 2 Set screw 3 Packing nut 4 Upper gland 5 Packing 6 Lower gland 7 Bonnet 8a Stem 8b Ball tip 9 Body 10 Stop pin Flange seals (not shown) Flange bolts (not shown) Lubricants PTFE/D1710 316 SS/A240 or A167 316 SS/A479 316 SS/A276 316 SS/A479 316 SS/A479 Fluorocarbon FKM B8M CL.2B/A193 Fluorinated base with PTFE and tungsten disulfide Hydrocarbon-based 316 SS/A479 Material Grade/ ASTM Specification

1 2 3 4 5 6 7 10

8a

8b

Wetted components listed in italics.

Instrument ManifoldsV, VB, and VL Series

2-Valve Manifolds
V Series
Ordering Information and Dimensions
Dimensions, in inches (millimeters), are for reference only and are subject to change. Direct Instrument Mount Manifolds with Flange Connections
Side Top
Bleed valve 1.25 Process side Instrument side

Front
Process side Instrument side

(31.8)

Block valve D B

G open E
(41.4)

1.63

(2) mounting holes, 0.34 (8.6) dia

(55.6)

2.19

A open

Process connection

Bleed connection

Instrument connection

Manifolds with Female Swagelok Tube Fitting and Pipe Connections


Top
F 1.88 Bleed valve C Process connection Block valve

Process side

Instrument side

Side
(31.8)

1.25

Front
Process side Instrument side Instrument connection

(2) mounting holes, 0.34 (8.6) dia

(47.8)

G open D B

(14.7)

0.58

Bleed connection

A open

(15.7)

0.62

End Connections Process Instrument 1/2 in. female Swagelok tube fitting 1/2 in. female Swagelok tube fitting Flange (MSS) 1/4 in. female NPT Bleed

Ordering Number SS-V2BFS8 SS-V2BFS8-FL SS-V2BFS12MM SS-V2BFS12MM-FL SS-V2BF8

Dimensions, in. (mm) A 4.19


(106)

B 1.89
(48.0)

C 0.44
(11.2)

D 2.48
(63.0)

E 1.31
(33.3)

F 2.75
(69.9)

G 3.02
(76.7)

3.33
(84.6)

1.31
(33.3)

0.90
(22.9)

1.63
(41.4)

1.25
(31.8)

3.46
(87.9)

3.46
(87.9)

12 mm female Swagelok tube fitting 12 mm female Swagelok tube fitting Flange (MSS) 1/2 in. female NPT 1/2 in. female NPT Flange (MSS) 1/4 in. female NPT 1/4 in. female NPT

4.19
(106)

1.89
(48.0)

0.44
(11.2)

2.48
(63.0)

1.31
(33.3)

2.75
(69.9)

3.02
(76.7)

3.33
(84.6)

1.31
(33.3)

0.90
(22.9)

1.63
(41.4)

1.25
(31.8)

3.46
(87.9)

3.46
(87.9)

3.82
(97.0)

1.62
(41.1)

0.31
(7.9)

2.12
(53.8)

1.31
(33.3)

2.50
(63.5)

3.02
(76.7)

SS-V2BF8-FL

3.33
(84.6)

1.31
(33.3)

0.90
(22.9)

1.63
(41.4)

1.25
(31.8)

3.48
(88.4)

3.46
(87.9)

Instrument ManifoldsV, VB, and VL Series

2-Valve Manifolds
VL Series
Materials of Construction
Materials for pressure-containing wetted parts are in compliance with ASME B31.1.
Component 1 Handle 2 Set screw 3 Packing bolt 4 Jam nut 5 Packing 6 Bonnet 7a Stem 7b Ball tip 8 Body 9 Stop pin Flange seals (not shown) Flange bolts (not shown) Lubricants 316 SS/A276 PTFE/D1710 316 SS/A479 316 SS/A276 316 SS/A479 316 SS/A479 Fluorocarbon FKM B8M CL.2B/A193 Fluorinated base with PTFE and tungsten disulfide Hydrocarbon-based 316 SS/A479 Material Grade/ ASTM Specification

8 7b 7a 9

6 5 4 3 1

Wetted components listed in italics.

Ordering Information and Dimensions


Dimensions, in inches (millimeters), are for reference only and are subject to change.
Top
(31.8)

Process side

Instrument side

1.25

Block valve
(2) mounting (8.6) dia

holes, 0.34

Side
2.125
(54.0)

Front
(2) process connections Process side 1.25 Instrument side

(42.9)

1.69

(85.9)

3.38

(31.8)

(41.4)

1.63

8.91 (226) open


(22.9)

(16.0)

0.63

(88.4)

3.48

0.90

(2) instrument connections

End Connections
Block valve
(55.6)

2.19

Process 1/2 in. female NPT

Instrument Flange (MSS)

Ordering Number SS-VL2NBF8-FL

Instrument ManifoldsV, VB, and VL Series

3-Valve Manifolds
V Series
Process side Instrument side

Equalizer valve

Block valve

Block valve

Designed for mounting on differential pressure transmitters

with 2 1/8 in. (54 mm) center-to-center connections


Consists of two block valves and one equalizer valve End connections1/2 in. and 12 mm female Swagelok tube

fitting, 1/2 in. female pipe (NPT), and flange (MSS)


Horizontal body style Direct instrument mount and remote mount

V Series
Materials of Construction
Materials for pressure-containing wetted parts are in compliance with ASME B31.1.
Component 1 Handle 2 Set screw 3 Packing bolt 4 Jam nut 5 Packing 6 Bonnet 7a Stem 7b Ball tip 8 Body 9 Stop pin Flange seals (not shown) Flange bolts (not shown) Lubricants 316 SS/A276 PTFE/D1710 316 SS/A479 316 SS/A276 316 SS/A479 316 SS/A479 Fluorocarbon FKM B8M CL.2B/A193 Fluorinated base with PTFE and tungsten disulfide Hydrocarbon-based 316 SS/A479 Material Grade/ ASTM Specification

1 2 3 4 5

7a

7b 8

Wetted components listed in italics.

Instrument ManifoldsV, VB, and VL Series

3-Valve Manifolds
V Series
Ordering Information and Dimensions
Dimensions, in inches (millimeters), are for reference only and are subject to change.
Top Side
1.60 (2) mounting holes, 0.34 (8.6) dia
(50.8)

Process side

Instrument side

2.00

Equalizer valve Process side


(15.0)

Front
Instrument side

(42.9)

G open D

Block valve

Block valve

0.59

(41.4)

1.63

2.125
(54.0)

(2) process connections

A open

F (2) instrument connections

Manifold with female Swagelok tube fitting-to-flange connections shown. K

SS-V3NBF8: 1.75 (44.4).

End Connections Process Instrument 1/2 in. female NPT 1/2 in. female NPT Flange (MSS)

Ordering Number SS-V3NBF8 SS-V3NBF8-FL SS-V3NBFS8 SS-V3NBFS8-FL SS-V3NBFS12MM SS-V3NBFS12MM-FL SS-V3NBFL

Dimensions, in. (mm) A 9.03


(229)

C 0.31 (7.9) 0.90


(22.9)

D 3.50
(88.9)

E 1.31
(33.3)

F 2.50
(63.5)

G 4.08
(104)

H 0.66
(16.8)

K 1.88
(47.8)

1.25
(31.8)

3.48
(88.4)

4.51
(115)

0.63
(16.0)

2.19
(55.6)

1/2 in. female Swagelok tube fitting 1/2 in. female Swagelok tube fitting Flange (MSS)

0.46
(11.7)

1.31
(33.3)

3.04
(77.2)

4.08
(104)

0.66
(16.8)

1.88
(47.8)

0.90 8.91
(226) (22.9)

1.25 3.38
(85.9) (31.8)

3.48
(88.4)

4.51
(115)

0.63
(16.0)

2.19
(55.6)

12 mm female Swagelok tube fitting 12 mm female Swagelok tube fitting Flange (MSS)

0.46
(11.7)

1.31
(33.3)

3.04
(77.2)

4.08
(104)

0.66
(16.8)

1.88
(47.8)

1.25 0.90
(22.9) (31.8)

3.48
(88.4)

4.51
(115)

0.63
(16.0)

2.19
(55.6)

Flange (MSS)

2.40
(61.0)

4.07
(103)

4.55
(116)

1.20
(30.5)

Instrument ManifoldsV, VB, and VL Series

5-Valve Manifolds
V Series
Equalizer valves
Process side Instrument side

VB Series
Equalizer valve Bleed valve Block valve

Process side

Instrument side

Bleed valve

Bleed valve Block valve

Block valve

Block valve

Designed for mounting on differential pressure transmitters

Designed for mounting on differential pressure transmitters

where a double-equalize function is required


Consists of two block valves, two equalizer valves, and one

where a double-bleed function is required.


Consists of two block valves, two bleed valves, and one

bleed valve
End connections1/2 in. and 12 mm female Swagelok tube

equalizer valve
End connections1/2 in. and 12 mm female Swagelok tube

fittings, 1/2 in. female pipe (NPT), and flange (MSS)


Horizontal body style Direct instrument mount and remote mount

fittings, 1/2 in. female pipe (NPT), and flange (MSS)


Horizontal body style Direct instrument mount and remote mount

V Series
Materials of Construction
Materials for pressure-containing wetted parts are in compliance with ASME B31.1.
Component 1 Handle 2 Set screw 3 Packing bolt 4 Packing nut 5 Upper gland 6 Jam nut 7 Lower gland 8 Packing 9 Bonnet 10a Stem 10b Ball tip 11 Body 12 Stop pin Flange seals (not shown) Flange bolts (not shown) Lubricants

Material Grade/ ASTM Specification

316 SS/A479

316 SS/A276 316 SS/A240 or A167 PTFE/D1710 316 SS/A479 316 SS/A276 316 SS/A479 316 SS/A479 Fluorocarbon FKM B8M CL.2B/A193 Fluorinated base with PTFE and tungsten disulfide Hydrocarbon-based

1 4 5 7 9 8

12

10a 10b

Wetted components listed in italics.

3 1

12

10a

10b

11

10

Instrument ManifoldsV, VB, and VL Series

5-Valve Manifolds
V Series
Ordering Information and Dimensions
Dimensions, in inches (millimeters), are for reference only and are subject to change. Direct Instrument Mount Manifolds with Flange Connections
Top Side
Bleed valve
(28.7)

Process side

Instrument side

Front
Equalizer valve Block valve G open E H F (2) instrument connections Process side
(31.8)

1.13

Equalizer valve Block valve (1) bleed connection

1.25

Instrument side

(85.9)

3.38

(50.8)

2.00

(41.4)

1.63

2.125
(54.0)

(2) mounting holes, 0.34 (8.6) dia

8.91 (226) open

(2) process connections

Manifolds with Female Swagelok Tube Fitting and Pipe Connections


Top Side
(2) mounting holes, 0.34 (8.6) dia Bleed valve Equalizer valve Block valve Bleed connection 3.38
(50.8)

Front
Equalizer valve Block valve G E H F
(15.0)

Process side

(31.8)

1.25

Instrument side

0.59

2.00

(85.9)

C 1.13

2.125
(54.0)

(2) process

connections

8.91 (226) open


(28.7)

(2) instrument connections

End Connections Process Instrument Bleed 1/2 in. female Swagelok tube fitting 1/2 in. female Swagelok tube fitting Flange (MSS)

Ordering Number SS-V5NBFS8 SS-V5NBFS8-FL SS-V5NBFS12MM

Dimensions, in. (mm) C 1.28


(32.5)

E 1.31
(33.3)

F 3.55
(90.2)

G 3.65
(92.7)

H 0.63
(16.0)

2.88
(73.2)

1.49
(37.8)

4.43
(114)

3.64
(92.5)

0.75
(19.1)

12 mm female Swagelok tube fitting 12 mm female Swagelok tube fitting 1/4 in. female NPT Flange (MSS)

1.28
(32.5)

1.31
(33.3)

3.55
(90.2)

3.65
(92.7)

0.63
(16.0)

SS-V5NBFS12MM-FL SS-V5NBF8 SS-V5NBF8-FL 1/8 in. female NPT SS-V5NBFL

2.88
(73.2)

1.49
(37.8)

4.43
(114)

3.64
(92.5)

0.75
(19.1)

1/2 in. female NPT 1/2 in. female NPT Flange (MSS)

1.42 (36.0) 2.88


(73.2)

1.31
(33.3)

3.62
(91.9)

3.07
(78.0)

0.63
(16.0)

1.49
(37.8)

4.47
(114)

0.75 3.66
(93.0) (19.1)

Flange (MSS)

2.98 (75.7)

1.50
(38.1)

5.00
(127)

Instrument ManifoldsV, VB, and VL Series

11

5-Valve Manifolds
VB Series
Materials of Construction
Materials for pressurecontaining wetted parts are in compliance with ASMEB31.1.
Component 1 Handle 2 Set screw 3 Packing bolt 4 Packing nut 5 Upper gland 6 Jam nut 7 Lower gland 8 Packing 9 Bonnet 10a Stem 10b Ball tip 11 Body 12 Stop pin Flange seals (not shown) Flange bolts (not shown) Lubricants

Material Grade/ ASTM Specification

316 SS/A479

316 SS/A276 316 SS/A240 or A167 PTFE/D1710 316 SS/A479 316 SS/A276 316 SS/A479 316 SS/A479 Fluorocarbon FKM B8M CL.2B/A193 Fluorinated base with PTFE and tungsten disulfide Hydrocarbon-based

1 4 5 7 9 8 12

10a

2 1

Wetted components listed in italics.

10b 11

12

10a

10b
Process side Instrument side

Ordering Information and Dimensions


Dimensions, in inches (millimeters), are for reference only and are subject to change.
Top Side
Equalizer valve

Front
Bleed valve Block valve (2) process connections Process side 0.59 G open (15.0) E H
(31.8)

K C 1.69

Bleed valve Block valve

1.25

Instrument side Bleed connection

(42.9) (85.9)

3.38

(50.8)

2.00

(41.4)

1.63

2.125 (2) mounting holes, 0.34 (8.6) dia


(54.0)

8.91 (226) open

End Connections Process


Manifold with female Swagelok tube fitting-to-flange connections shown.

Instrument

Bleed

Ordering Number SS-VB5NBF8

Dimensions, in. (mm) C 1.21


(30.7)

1/2 in. female NPT 1/2 in. female NPT Flange (MSS) 1/8 in. female NPT

E 1.31
(33.3)

F 3.62
(91.9)

G 4.08
(104)

H 0.61
(15.5)

K 1.88
(47.8)

SS-VB5NBF8-FL SS-VB5NBFS8 SS-VB5NBFS8-FL

0.94
(23.9)

1.49
(37.8)

4.47
(114)

4.76
(121)

0.71
(18.0)

1.35
(34.3)

1/2 in. female Swagelok tube fitting 1/2 in. female Flange Swagelok tube fitting (MSS)

1.22
(31.0)

1.31
(33.3)

3.55
(90.2)

4.08
(104)

0.61
(15.5)

1.88
(47.8)

0.94
(23.9)

1.49
(37.8)

4.43
(113)

4.71
(120)

0.75
(19.1)

1.35
(34.3)

12

Instrument ManifoldsV, VB, and VL Series

Options
High-Temperature Packing
Grafoil valve packing material for high-temperature service.

MSSFlange Fasteners
Optional long studs or short bolts are available for special

See Pressure-Temperature Ratings, page 3.


Includes Grafoil flange seals on MSS flanges.

flange mounting applications. See table below for flange fastener length comparison.
All fasteners are stainless steel with 7/16-20 threads. Optional fasteners are available for all V, VB, and VL series

To order a manifold with optional Grafoil packing, add -G to the manifold ordering number. Example: SS-V3NBF8-FL-G

manifolds with MSS flanges. To order a manifold with optional flange fasteners, add a fastener designator to the manifold ordering number.
MSS Flange Fasteners Standard hex head bolt Long stud with hex nut Short hex head bolt Length in. (mm) 1.0 (25.4) 2.6 (66.0) 0.875 (22.2) Hex Size in. 5/8 11/16 5/8 Fastener Designator -LGB -SHB

Flange Seal Materials


MSS flange seals are available in Grafoil, virgin PTFE, and

reinforced PTFE for system compatibility.


Temperature ratings are included in the table below.

To order a manifold with an optional MSS flange seal material, add a material designator to the manifold ordering number. Example: SS-V3NBF8-FL-T
MSS Flange Seal Material Material Designator Fluorocarbon FKM Grafoil Virgin PTFE Reinforced PTFE -G -T -TRL Temperature Lubricant/ Rating Sealant F (C) Silicone 20 to 450 base (28 to 232) Fluorinated 65 to 1000 base (53 to 537) Silicone base 65 to 250 (53 to 121) Packing Material PTFE Grafoil PTFE PTFE

Example: SS-V3NBF8-FL-LGB

Mounting Hole Center Line


Elongated mounting holes on the instrument flange allow

for center line installations between 2 1/8 and 2 1/4 in. (54.0 and 57.2 mm).
Available on 3- and 5-valve V and VB series manifolds with

MSS flanges.
Pressure rating is 3600 psig at 100F (248 bar at 37C) and

Mounting Kits
Mounting Bracket Kit
Kit contains stainless steel bracket, U-bolts, cap screws, nuts, lock washers, spacer, and instructions. Kit does not fit 3-valve manifolds with flangeto-flange end connections. Ordering number: SS-MB-VBK

2480 psig at 450F (170 bar at 232C). To order, add -EH to the manifold ordering number. Example: SS-V5NBF8-FL-EH

Hydrostatic Testing
Hydrostatic testing is available as an option. To order, add -W20 to the manifold ordering number. Example: SS-V2BF8-W20

Maintenance Kits
Flange Seal and Bolt Kits
Kit contains flange seals,

Steam-Trace Block Kits


Kit contains plated steel trace block with two 1/4 in. female NPT ports, cap screws, nuts, lock washers, block retainer plate, heat transfer gasket, and instructions.
Kit Ordering Number S-MB-M3SK S-MB-M5SK

flange bolts, lubricant, and instructions.


Select a kit ordering number

from the tables below based on the manifold series, flange style, and seal material.

Manifold Styles 3-valve, flange 3-valve, pipe-to-pipe 3-valve, tube-to-tube 5-valve, all styles

V, VB, and VL Series with MSS Flanges


Flange Seal Material Fluorocarbon FKM Grafoil Virgin PTFE Reinforced PTFE Kit Ordering Number 2-Valve SS-MK-V2V SS-MK-V2G SS-MK-V2T SS-MK-V2R 3- and 5-Valve SS-MK-V3V SS-MK-V3G SS-MK-V3T SS-MK-V3R

Instrument ManifoldsV, VB, and VL Series

13

Accessories
Eccentric Flanges
Used with flange-to-flange manifolds to allow the

connection of process flange taps or process root valves.


Offered with Swagelok tube fitting, female NPT, or pipe

butt weld connections.


Provide an offset connection of 1/16 in. (1.6 mm) from the

bolt hole center line.

Eccentric View

Swagelok Tube Fitting

Female NPT

Pipe Butt Weld

Dimensions
Dimensions, in inches (millimeters), are for reference only and are subject to change.
(31.0)

Ordering Information
Kit includes two (2) flanges, two (2) flange seals, four (4) 7/16-20 hex bolts,

lubricant, and instructions.


Flange seal material is fluorocarbon FKM with a temperature rating of

1.22

20 to 450F (28 to 232C).

(33.3)

1.31

0.063
(62.2)

2.45

eccentricity

(1.6)

Eccentric Flange Seal Kits


A
(26.2)

1.03

Material Grade/ASTM Specification CF8M SS/ ASTM A351 CF3M SS/ ASTM A351

End Connection Size 1/4 in. 1/2 in. Type Female NPT Swagelok tube fitting Female NPT

Kit Ordering Number SS-MKV-V3F4 SS-MKV-V3S8 SS-MKV-V3F8

Bolt Material

End Connection Swagelok tube fitting Female NPT Pipe butt weld

A, in. (mm) 2.25 (57.2) 1.03 (26.2) 1.55 (39.4)

316 SS

1/2 in. Pipe butt weld SS-MKV-V3W8P

Optional Eccentric Flange Seal Materials To order an eccentric flange seal kit with an optional seal material, replace MKV in the kit ordering number with a seal designator.
Flange Seal Material Virgin PTFE Reinforced PTFE Grafoil Seal Designator -MKT -MKR -MKG Temperature Rating F (C) 65 to 250 (53 to 121) 65 to 1000 (53 to 537)

Example: SS-MKT-V3F4

14

Instrument ManifoldsV, VB, and VL Series

Accessories
Concentric and Eccentric Pipe Nipples
Used with eccentric flanges to adapt Concentric Pipe Nipples Eccentric Pipe Nipples

to different flange tap spacings.


Provide an offset of 1/16 in. (1.6 mm)

from center line.


Offered with 1/2 in. male NPT end

connections.
Available in 316 stainless steel and

carbon steel.

Ordering Information
Order pipe nipples as individual

components.
See ordering number in the

(76.2)

3.00

0.38
(9.6)

(11.4)

0.45

dia

dia

(76.2)

3.00

0.33
(8.4)

dia

Pipe Nipple Selection table below.


7/8 hex 0.063
(1.6)

eccentricity

15/16 hex

Dimensions, in inches (millimeters), are for reference only and are subject to change.

Pipe Nipple Selection


Material Grade/ASTM Specification 316 SS/A276 Concentric Carbon steel/A108 S-CLNM8 316 SS/A276 Eccentric Carbon steel/A108 S-ELNM8 6 000 (413) SS-ELNM8 8 000 (551) 7 500 (516) Ordering Number SS-CLNM8 Pressure Rating at 70F (20C) psig (bar) 10 000 (689) Temperature Rating F (C) 65 to 1200
(53 to 648)

Type

Pressure Rating at Maximum Temperature 2850 psig at 1200F


(196 bar at 648C)

20 to 350
(28 to 176)

6970 psig at 350F


(480 bar at 176C)

65 to 1200
(53 to 648)

2140 psig at 1200F


(147 bar at 648C)

20 to 350
(28 to 176)

5230 psig at 350F


(360 bar at 176C)

Optional Center Line Distances


A variety of center line distances

can be obtained by using various combinations of eccentric flanges and pipe nipples.
The illustrations at the right show

Two Female NPT Eccentric Flanges with Two Concentric Pipe Nipples

Two Female NPT Eccentric Flanges with One Concentric Pipe Nipple and One Eccentric Pipe Nipple

Two Female NPT Eccentric Flanges with Two Eccentric Pipe Nipples

these combinations using female NPT eccentric flanges.


2.125
(54.0)

2.125
(54.0)

2.125
(54.0)

typ

typ

typ

2.00 to 2.25 center line distance


(50.8 to 57.2)

1.94 to 2.31 center line distance


(49.3 to 58.7)

1.88 to 2.38 center line distance


(47.7 to 60.4)

Dimensions, in inches (millimeters), are for reference only and are subject to change.

Instrument ManifoldsV, VB, and VL Series

15

Accessories
DP Transmitter Calibration Fittings
Speed transmitter calibration by reducing the number of

Gauge Adapters
Adapt female BSP/ISO parallel thread

steps in the traditional calibration.


Allow rapid access to the cell for calibrationonly the bleed

to male NPT threads.


Are offered in 1/4, 3/8, and 1/2 in.

port tap requires removal to access transmitter ports.


Prevent possible galling of transmitter NPT body threads

male NPT sizes.


Are available in 316 stainless steel

straight threads on the calibration tube fitting screw directly into plug/bleed port fittings.
Choice of fitting with 5/16-24 in. thread and 1/4 in. tubing or

material. For more information, see the Swagelok Pipe Fittings catalog, MS-01-147.

1/4-28 in. thread and 1/4 in. tubing, depending on the bleed port size of the transmitter plug.
Are available in 316 stainless steel material.

Positionable Gauge Adapters


Allow 360 orientation of

pressure gauges. Ordering number for fitting with 5/16-24 thread: SS-400-1-0253
Are offered with 1/2 in. male

NPT inlet connection.


Are available with 1/2 in. NPT

and ISO parallel gauge connections.


Are all 316 stainless steel material.

Ordering number for fitting with 1/4-28 thread: SS-400-1-0257

For more information, see the Swagelok Pressure Gauges, Industrial and ProcessPGI Series catalog, MS-02-170.

Dimensions
Dimensions, in inches (millimeters), are for reference only and are subject to change.
Calibration Fitting with 5/16-24 in. Thread
9/16 nut hex 30 0.06 (1.5) min opening

Additional Manifold Products


For direct-mount manifolds, see the Swagelok DirectMount Manifolds VE Series catalog, MS-02-308. For remote-mount manifolds, see the Swagelok RemoteMount Manifold Two Valve catalog, MS-02-330.
Direct-Mount Manifold

Remote-Mount Manifold

(10.2) (15.2)

0.40

0.60

(10.4) (58.9)

0.41

(25.4)

1.00

0.25 (6.4) dia

2.32

Calibration Fitting with 1/4-28 in. Thread


9/16 nut hex 30 0.06 (1.5) min opening

For bellows-sealed 3-valve manifolds, Bellows-Sealed see the Swagelok 3Valve Manifold Bellows-Sealed 3Valve Manifolds V3Series catalog, MS0207. The manifolds use B or U series bellows-sealed valves for systems with difficult fluid containment requirements.

(10.9) (15.2) (42.9)

0.43

0.60

(19.8)

0.78

0.20 (5.1) dia

1.69

Safe Product Selection When selecting a product, the total system design must be considered to ensure safe, trouble-free performance. Function, material compatibility, adequate ratings, proper installation, operation, and maintenance are the responsibilities of the system designer and user. Caution: Do not mix or interchange parts with those of other manufacturers.

Warranty Information
Swagelok products are backed by The Swagelok Limited Lifetime Warranty. For a copy, visit swagelok.com or contact your authorized Swagelok representative.

SwagelokTM Swagelok Company GrafoilTM GrafTech International Holdings, Inc. 20022013 Swagelok Company Printed in U.S.A., AGS February 2013, R6 MS-01-178