M Jy992d95601

Download as pdf or txt
Download as pdf or txt
You are on page 1of 0

MITSUBISHI ELECTRIC

MELSEC FX Series
Programmable Controllers
Suplementary Manual

FX Series

01 03 2001
JY992D95601
Version A

MITSUBISHI ELECTRIC

INDUSTRIAL AUTOMATION

FX2N-32DP-IF Interface Block

Foreword
This manual contains text, diagrams and explanations which will guide the reader in the
correct installation and operation of an FX series PLC. It should be read and understood
before attempting to install or use the unit.
Further information can be found in the Programming Manual II and the relavent PLCs
associated Hardware Manual.
If in doubt at any stage of the installation a PLC or related system always consult a
professional electrical engineer who is qualified and trained to the local and national
standards which apply to the installation site.
If in doubt about the operation or use of the PLC please consult the nearest Mitsubisi
Electric distributor.
This manual is subject to change without notice.

FX Series Programmable Controllers

FX Series Programming Manual II

SUPPLEMENTARY MANUAL
(Diagnostic Devices)

Manual number : JY992D95601


Manual revision : A
Date

: March 2001

FX Series Programmable Controllers

ii

FX Series Programmable Controllers

Guidelines for the Safety of the User and Protection of the Programmable
Controller
This manual provides information for the use of the FX family of PLCs. The manual has been
written to be used by trained and competent personnel. The definition of such a person or
persons is as follows;
a) Any engineer who is responsible for the planning, design and construction of automatic
equipment using the product associated with this manual should be of a competent
nature, trained and qualified to the local and national standards required to fulfill that
role. These engineers should be fully aware of all aspects of safety with regards to
automated equipment.
b) Any commissioning or service engineer must be of a competent nature, trained and
qualified to the local and national standards required to fulfill that job. These engineers
should also be trained in the use and maintenance of the completed product. This
includes being completely familiar with all associated documentation for the said
product. All maintenance should be carried out in accordance with established safety
practices.
c) All operators of the completed equipment should be trained to use that product in a safe
and coordinated manner in compliance to established safety practices. The operators
should also be familiar with documentation which is connected with the actual operation
of the completed equipment.
Note : Note: the term completed equipment refers to a third party constructed device which
contains or uses the product associated with this manual.
Notes on the Symbols Used in this Manual
At various times through out this manual certain symbols will be used to highlight points of
information which are intended to ensure the users personal safety and protect the integrity of
equipment. Whenever any of the following symbols are encountered its associated note must
be read and understood. Each of the symbols used will now be listed with a brief description of
its meaning.
Hardware Warnings
1) Indicates that the identified danger WILL cause physical and property damage.

2) Indicates that the identified danger could POSSIBLY cause physical and property
damage.
3) Indicates a point of further interest or further explanation.
Software Warnings
4) Indicates special care must be taken when using this element of software.

5) Indicates a special point which the user of the associate software element should
be aware of.
6) Indicates a point of interest or further explanation.

iii

FX Series Programmable Controllers

Under no circumstances will Mitsubishi Electric be liable responsible for any consequential
damage that may arise as a result of the installation or use of this equipment.
All examples and diagrams shown in this manual are intended only as an aid to
understanding the text, not to guarantee operation. Mitsubishi Electric will accept no
responsibility for actual use of the product based on these illustrative examples.
Owing to the very great variety in possible application of this equipment, you must satisfy
yourself as to its suitability for your specific application.

iv

FX Series Programmable Controllers

Table of Contents
Guideline of Safty................................................................................ iii
1. Introduction............................................................................................1-1
1.1 Overview.............................................................................................................. 1-1

2. Diagnostic Devices ................................................................................2-1


2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
2.10
2.11
2.12
2.13
2.14
2.15
2.16
2.17
2.18

Device Lists ......................................................................................................... 2-2


PLC Status (M8000 to M8009 and D8000 to D8009) .......................................... 2-7
Clock Devices (M8010 to M8019 and D8010 to D8019) .................................... 2-8
Operation Flags (M8020 to M8029 and D8020 to D8029) .................................. 2-9
PLC Operation Mode (M8030 to M8039 and D8030 to D8039) ....................... 2-10
Step Ladder (STL) Flags (M8040 to M8049 and D8040 to D8049) .................. 2-11
Interrupt Control Flags (M8050 to M8059 and D8050 to D8059) .................... 2-12
Error Detection Devices (M8060 to M8069 and D8060 to D6069) ................... 2-13
Link and Special Operation Devices (M8070 to M8099 and D8070 to D8099) 2-15
Miscellaneous Devices (M8100 to M8119 and D8100 to D8119) ..................... 2-16
Communication Adapter Devices (M8120 to M8129 and D8120 to D8129) ..... 2-16
High Speed Zone Compare Flags (M8130-M8148, D8130-D8148) ................ 2-17
Miscellaneous Devices (M8160 to M8199) ....................................................... 2-19
Miscellaneous devices (D8158-D8164) and Index Registers (D8182-D8199) . 2-20
N:N Network Flags and Data Registers (M8183-M8191, D8173-D8281) ......... 2-21
Up/Down Counter Control (M8200 to M8234 and D8219 to D8234) ............... 2-22
High Speed Counter Control (M8235 to M8255 and D8235 to D8255) ............ 2-22
Error Code Tables ............................................................................................. 2-23

FX Series Programmable Controllers

vi

Introduction 1
FX1S

1.

FX2N

FX2NC

Introduction

1.1

FX1N

Overview
1) Scope of this manual
This manual gives details on all available diagnostic devices for FX1S, FX1N, FX2N and
FX2NC programmable controllers (PLCs). It is intended to be used in place of the published
data of Chapter 6 Diagnostic Devices in the FX Series Programming Manual II, Version A.
(JY992D88101A). For all information relating to the PLC hardware and installation, refer to
the appropriate manual supplied with the unit. For all other information regarding the
programming of the unit, please refer to the FX Series Programming Manual II
2) How to use this manual
This manual covers all the devices of the highest specification Programmable (Logic)
Controller (PLC). For this reason, the following indicator is included in relevant section titles
to show which PLCs that section applies to;
FX1S

FX1N

FX2N

FX2NC

FX1S - All FX1S PLCs

FX1N - All FX1N PLCs

FX2N - All FX2N PLCs

Shaded boxes indicate


the applicable PLC type

FX2NC - All FX2NC PLCs

If an indicator box is half shaded, as shown to the


left, this means that not all the functions described in
the current section apply to that PLC. The text
explains in further detail or makes an independent
reference.
If there are no indicator boxes then assume the section applies to all PLC types unless
otherwise stated.
FX1S

FX1N

FX2N

FX2NC

3) FX family
This is a generic term which is often used to describe all Programmable Controllers without
identifying individual types or model names.
4) CPU version numbers and programming support
As Mitsubishi upgrades each model different versions have different capabilities.
- Please refer to FX Series Programming Manual II section 1.4 for details about peripheral
support for each model.

1-1

Introduction 1

Memo

1-2

FX Series Programmable Controller

2.

Diagnostic Devices

Diagnostic Devices 2

FX1S

FX1N

FX2N

FX2NC

The following special devices are used by the PLC to highlight the current operational status
and identify any faults or errors that may be occurring. There are some variations in the
application of these devices to members of the FX PLC family, these are noted where
appropriate.
The Internal diagnostic devices consist of both auxiliary (M) coils and data (D) registers.
Often there is a correlation between both M and D diagnostic devices for example M8039
identifies that the PLC is in constant scan mode but D8039 contains the value or length of the
set constant scan.

Devices unable to be set by user:


Any device of type M or D that is marked with a ( ) cannot be set by a users program. In the
case of M devices this means the associated coil cannot be driven BUT all contacts can be
read. For data devices (D) new values cannot be written to the register by a user BUT the
register contents can be used in a data comparison.

Default Resetting Devices:


Certain devices reset to their default status when the PLC is turned from OFF to ON.
These are identified by the following symbol ().
Symbol summary:
not able to be set by user
automatically reset to default at power ON.
R Also reset to default when CPU is switched to RUN.
S Also reset to default when CPU is switched to STOP.

2-1

FX Series Programmable Controller

2.1

Diagnostic Devices 2

Device Lists
Device
M8000
M8001
M8002
M8003
M8004
M8005
M8006
M8007
M8008
M8009
M8010
M8011
M8012
M8013
M8014
M8015
M8016
M8017
M8018
M8019
M8020
M8021
M8022
M8023
M8024
M8025
M8026
M8027
M8028
M8029
M8030
M8031
M8032
M8033
M8034
M8035
M8036
M8037
M8038
M8039
M8040
M8041
M8042
M8043
M8044
M8045
M8046
M8047
M8048
M8049

FX1S

() *1

FX1N

FX2N FX2NC

Reserved

Reserved

Device
D8000
D8001
D8002
D8003
D8004
D8005
D8006
D8007
D8008
D8009
D8010
D8011
D8012
D8013
D8014
D8015
D8016
D8017
D8018
D8019
D8020
D8021
D8022
D8023
D8024
D8025
D8026
D8027
D8028
D8029
D8030
D8031
D8032
D8033
D8034
D8035
D8036
D8037
D8038
D8039
D8040
D8041
D8042
D8043
D8044
D8045
D8046
D8047
D8048
D8049

FX1S

FX1N

FX2N FX2NC

Reserved

Reserved

Reserved

Note *1: M8028 offers a different functionality for FX1S than it does for FX2N and
FX2NC. See page 2-9 for details

2-2

FX Series Programmable Controller

Device
M8050
M8051
M8052
M8053
M8054
M8055
M8056
M8057
M8058
M8059
M8060
M8061
M8062
M8063
M8064
M8065
M8066
M8067
M8068
M8069
M8070
M8071
M8072
M8073
M8074
M8075
M8076
M8077
M8078
M8079
M8080
M8081
M8082
M8083
M8084
M8085
M8086
M8087
M8088
M8089
M8090
M8091
M8092
M8093
M8094
M8095
M8096
M8097
M8098
M8099

FX1S

FX1N

Diagnostic Devices 2

FX2N FX2NC

Reserved

Reserved

Reserved

Device
D8050
D8051
D8052
D8053
D8054
D8055
D8056
D8057
D8058
D8059
D8060
D8061
D8062
D8063
D8064
D8065
D8066
D8067
D8068
D8069
D8070
D8071
D8072
D8073
D8074
D8075
D8076
D8077
D8078
D8079
D8080
D8081
D8082
D8083
D8084
D8085
D8086
D8087
D8088
D8089
D8090
D8091
D8092
D8093
D8094
D8095
D8096
D8097
D8098
D8099

FX1S

FX1N

FX2N FX2NC

Reserved

Reserved

2-3

FX Series Programmable Controller

Device
M8100
M8101
M8102
M8103
M8104
M8105
M8106
M8107
M8108
M8109
M8110
M8111
M8112
M8113
M8114
M8115
M8116
M8117
M8118
M8119
M8120
M8121
M8122
M8123
M8124
M8125
M8126
M8127
M8128
M8129
M8130
M8131
M8132
M8133
M8134
M8135
M8136
M8137
M8138
M8139
M8140
M8141
M8142
M8143
M8144
M8145
M8146
M8147
M8148
M8149

FX1S

FX1N

Diagnostic Devices 2

FX2N FX2NC

Reserved

Reserved

Reserved

Reserved

Reserved

Reserved

Reserved

Device
D8100
D8101
D8102
D8103
D8104
D8105
D8106
D8107
D8108
D8109
D8110
D8111
D8112
D8113
D8114
D8115
D8116
D8117
D8118
D8119
D8120
D8121
D8122
D8123
D8124
D8125
D8126
D8127
D8128
D8129
D8130
D8131
D8132
D8133
D8134
D8135
D8136
D8137
D8138
D8139
D8140
D8141
D8142
D8143
D8144
D8145
D8146
D8147
D8148
D8149

FX1S

FX1N

FX2N FX2NC

Reserved

Reserved

Reserved

Reserved

Reserved

Reserved

Reserved

2-4

FX Series Programmable Controller

Device
M8150
M8151
M8152
M8153
M8154
M8155
M8156
M8157
M8158
M8159
M8160
M8161
M8162
M8163
M8164
M8165
M8166
M8167
M8168
M8169
M8170
M8171
M8172
M8173
M8174
M8175
M8176
M8177
M8178
M8179
M8180
M8181
M8182
M8183
M8184
M8185
M8186
M8187
M8188
M8189
M8190
M8191
M8192
M8193
M8194
M8195
M8196
M8197
M8198
M8199

FX1S

FX1N

Diagnostic Devices 2

FX2N FX2NC

Reserved

Reserved

Reserved

Reserved

Reserved

Reserved
M504
M505
M506
M507
M508
M509
M510
M511
M503

Reserved

Device
D8150
D8151
D8152
D8153
D8154
D8155
D8156
D8157
D8158
D8159
D8160
D8161
D8162
D8163
D8164
D8165
D8166
D8167
D8168
D8169
D8170
D8171
D8172
D8173
D8174
D8175
D8176
D8177
D8178
D8179
D8180
D8181
D8182
D8183
D8184
D8185
D8186
D8187
D8188
D8189
D8190
D8191
D8192
D8193
D8194
D8195
D8196
D8197
D8198
D8199

FX1S

FX1N

FX2N FX2NC

Reserved

Reserved
-

Reserved

Reserved

Reserved

Reserved

Note;
When using an N:N network configuration with the FX1S, M503 to M511 are used in
place of the regular M devices as shown above. D208 to D218 are used in place of the
regular D devices shown on the next page.

2-5

FX Series Programmable Controller

Device
M8200
M8201
M8202
M8203
M8204
M8205
M8206
M8207
M8208
M8209
M8210
M8211
M8212
M8213
M8214
M8215
M8216
M8217
M8218
M8219
M8220
M8221
M8222
M8223
M8224
M8225
M8226
M8227
M8228
M8229
M8230
M8231
M8232
M8233
M8234
M8235
M8236
M8237
M8238
M8239
M8240
M8241
M8242
M8243
M8244
M8245
M8246
M8247
M8248
M8249
M8250
M8251
M8252
M8253
M8254
M8255

FX1S

FX1N

Diagnostic Devices 2

FX2N FX2NC

Device
D8200
D8201
D8202
D8203
D8204
D8205
D8206
D8207
D8208
D8209
D8210
D8211
D8212
D8213
D8214
D8215
D8216
D8217
D8218
D8219
D8220
D8221
D8222
D8223
D8224
D8225
D8226
D8227
D8228
D8229
D8230
D8231
D8232
D8233
D8234
D8235
D8236
D8237
D8238
D8239
D8240
D8241
D8242
D8243
D8244
D8245
D8246
D8247
D8248
D8249
D8250
D8251
D8252
D8253
D8254
D8255

FX1S
D201
D202
D203
D204
D205
D206
D207
D208
D209
D210
D211
D212
D213
D214
D215
D216
D217
D218

FX1N

FX2N FX2NC

Reserved

Reserved

Reserved

Reserved

Reserved

Reserved

2-6

FX Series Programmable Controller

2.2

Diagnostic Devices 2

PLC Status (M8000 to M8009 and D8000 to D8009)


Diagnostic
Device
M8000 ( )
RUN monitor
NO contact
M8001 ( )
RUN monitor
NC contact
M8002 ( )
Initial pulse
NO contact

Operation

Diagnostic
Device

FX1N

FX2N

FX2NC

Operation

D8000 ()
Watchdog
timer

M8061 error occurence


M8000
M8001
M8002

FX1S, FX1N, FX2N, FX2NC:


200ms
See note 1

D8001 ( )
PLC type and
version

FX1S: 22
FX1N: 26 E.g. 26100 = FX1N, V1.00
FX2N: 24
FX2NC: 24

D8002 ( )
Memory
capacity

RUN
Input

0002: 2K steps (FX1S only)


0004: 4K steps (FX2N, FX2NC)
0008: 8K or 16k steps (FX1N,
FX2N, FX2NC)

(see also D8102)

M8003

M8003 ( )
Initial pulse
NC contact

FX1S

Program scan time

D8003 ( )
Memory type

00H = Option RAM,


01H = Option EPROM,
02H = Option EEPROM,
0AH = Option EEPROM (protected)
10H = Built-in MPU memory

M8004 ( )
Error
occurrence

ON when one or more error


flags from the range M8060
to M8067 are ON

D8004 ( )
Error number
M

The contents of this register


identifies which error flag is active, i.e.
if = 8060 identifies M8060

M8005 ( )
Battery voltage
Low

On when the battery


voltage is below the value
set in D8006

D8005 ( )
Battery voltage

E.g. 36 = 3.6 volts

(Not FX1S, FX1N)

M8006 ( )
Battery error
latch

Latches the battery Low


error

(Not FX1S, FX1N)

M8007 ( )
Momentary
power failure

(Not FX1S, FX1N)

M8009 ( )
24V DC Down
(Not FX1S, FX1N)

D8006 ( )
Low battery
voltage

The level at which a low


battery voltage is detected

(Not FX1S, FX1N)

See note 2

The number of times a


D8007 ( )
momentary power failure has
Power failure
count (Not FX1S, FX1N) occurred since power ON.

Power loss has occurred


See note 2

D8008
Power failure
detection.

(Not FX1S, FX1N)

M8008 ( )
Power failure

(Not FX1S, FX1N)

(Not FX1S, FX1N)

Power failure of 24V DC


service supply

The time period before shut


down when a power failure
occurs (default 10ms)
See note 2

D8009 ( )
Lowest device affected by 24V
24V DC failed
DC power failure
device(Not FX1S, FX1N)

For symbol key see page 2-1.

Note 1:

The contents of this register can be changed by the user.


Settings in 1 msec steps are possible. The value should
be set greater than the maximum scan time (D8012) to
ensure constant scan operation.

Note 2:

When the power supply used is 200V AC, the power


down detection period is determined by the value of
D8008. This can be altered by the user within the
allowable range of 10 to 100msec.

AC
Power
M8000
Approx. 5msec
M8007
Momentry power failure
M8008
Power failure
D8008 (Power failure
10msec detection period)
2-7

FX Series Programmable Controller

2.3

Diagnostic Devices 2

Clock Devices (M8010 to M8019 and


D8010 to D8019)
Diagnostic
Device

Operation

FX1S
Diagnostic
Device

FX1N

FX2N

FX2NC

Operation

Reserved

D8010 ( )
Present scan
time

Current operation cycle / scan


time in units of 0.1 msec
(waiting time for constant scan
mode is included)

M8011 ( )
10 msec
clock pulse

Oscillates in 10 msec cycles

D8011 ( )
Minimum
scan time

Minimum cycle/ scan time in


units of 0.1 msec
(waiting time for constant scan
mode is included)

M8012 ( )
100 msec
clock pulse

Oscillates in 100 msec


cycles

D8012 ( )
Maximum
scan time

Maximum cycle/ scan time in


units of 0.1 msec
(waiting time for constant scan
mode is included)

M8013 ( )
1 sec
clock pulse

Oscillates in 1 sec cycles

M8014 ( )
1 min
clock pulse

Oscillates in 1 min cycles

M8010

The following devices apply to FX2N, FX1N and FX1S PLCs as standard and to the FX2NC
PLC when a real time clock option board installed.
D8013
Seconds

Seconds data for use with an


RTC (0 - 59)

D8014
Minute data

Minute data for use with an


RTC (0-59)

M8015
Time setting

When ON - clock stops, ON


OFF restarts clock

D8015
Hour data

Hour data for use with an RTC


(0-23)

M8016
Register data

When ON D8013 to 19 are


frozen for display but clock
continues

D8016
Day data

Day data for use with an RTC


(1-31)

M8017
Min. rounding

When pulsed ON set RTC


to nearest minute

D8017
Month data

Month data for use with an


RTC (1-12)

M8018 ( )
RTC available

When ON Real Time Clock


is installed

D8018
Year data

Year data for use with an RTC


(00-99 or 1980-2079, can be
selected)

M8019
Setting error

Clock data has been set out


of range

D8019
Weekday data

Weekday data for use with an


RTC (0-6)

For symbol key see page 2-1.

2-8

FX Series Programmable Controller

2.4

Diagnostic Devices 2

Operation Flags (M8020 to M8029 and


D8020 to D8029)
Diagnostic
Device

Operation

M8020 ( )
Zero

M8021 ( )
Borrow

M8022 ()
Carry

Set when carry occurs


during an ADD (FNC 20) or
when an overflow occurs as
a result of a data shift
operation

M8024
(Not FX1S, FX1N)

M8025
(Not FX1S, FX1N)

M8026
(Not FX1S, FX1N)

M8027
(Not FX1S, FX1N)

M8028
Note:
Separate FX1S and
FX2N/2NC operation
(Not FX1N)

M8029 ( )
Instruction
execution
complete

FX1N

Diagnostic
Device

Set when the result of an


ADD (FNC 20) or SUB (FNC
21) is 0
Set when the result of a SUB
(FNC 21) is less than the
min. negative number

FX1S

D8020 ()
See note 4

FX2N

FX2NC

Operation
Input filter setting for devices;
X000 to X017 (FX2N,FX2NC)
default value = 10 msec,
zero value = 50 sec
(X000, X001: 20 sec)
X000 to X007 (FX1S,FX1N)
default value = 10msec
zero value = 50 sec
(X000, X001: 10 sec)

See note 4

Input filter setting for devices;


X010 to X017 (FX1S)
default value = 10 msec,
zero value = 50 sec

D8022 -D8027

Reserved

FX1S: Change timers


T32 ~ T62 to 10ms type
FX2N, FX2NC:Permit
FROM/TO to interrupt
program. (V3.00 and above)

D8028 ( )

Current value of the Z0 index


register
See note 5

Set on the completion of


operations such as DSW
(FNC 72), RAMP (FNC 67)
etc.

D8029 ( )

Current value of the V0 index


register
See note 5

D8021 ()
(Not FX1N, FX@N,
FX2NC

BMOV (FNC 15) reverse


mode. See note 3
When ON HSC (FNC 53 - 55)
instructions are processed
even when the external HSC
reset input is activated
RAMP (FNC 67) hold mode
PR (FNC 77) 16 element
data string

For symbol key see page 2-1.

Note 3
If M8024 is used with a BMOV (FNC 15) instruction, it will operate as follows;
M8024 OFF - Normal operation (Forwarding direction is [S] to [D])
M8024 ON - Reverse operation (Forwarding direction becomes [D] to [S])
This device is not supported in FX1S and FX1N

Note 4
The settings for input filters only apply to the main processing units which use 24V DC
inputs. AC input filters are not adjustable.

Note 5
For Z1~Z7 and V1~V7 (D8128~D8195) please see page 2-20.
2-9

FX Series Programmable Controller

2.5

Diagnostic Devices 2

PLC Operation Mode


(M8030 to M8039 and D8030 to D8039)
Diagnostic
Device
M8030 ()
Battery LED
OFF

Operation
Battery voltage is low but
BATT.V LED not lit

FX1S

FX1N

Diagnostic
Device
D8030 ( )
(Not FX2N, FX2NC)

FX2N

FX2NC

Operation
Value read from first setting
pot in msec, (0 to 255)

(Not FX1S, FX1N)

M8031 ()
Non-latch
memory all
clear
M8032 ()
Latch memory
all clear

Current device settings are


reset at next END, i.e.
contacts, coils and current
data values for Y, M, S, T, C
and D devices respectively.
Special devices and file
registers which have default
settings are refreshed with
those defaults

M8033 ()
Memory hold
in stop mode

All of the physical switch


gear for activating outputs is
disabled. However, the
program still operates
normally.

(Not FX2N, FX2NC)

Value read from second


setting pot in msec, (0 to
255)

The device statuses and


settings are retained when
the PLC changes from RUN
to STOP and back into RUN

M8034 ()
All outputs
disable

D8031 ( )

M8035 (S)
Forced
operation
mode
M8036 (S)
Forced RUN
signal
M8037 (S)
Forced STOP
signal

D8032 -D8038

Reserved

D8039 ()
Constant
scan duration

This register can be written to


by the user to define the
duration of the constant scan.
Resolutions of 1msec are
possible.
This register has a default
setting 0 msec which will be
initiated during power ON.

By using forced operation


mode, i.e.M8035 is turned
ON, it is possible to perform
remote RUN/STOP or
pulsed RUN/ STOP
operation.
Please see Chapter 10
(Programming Manual II) for
example operation

M8038
N to N
networking

For the setting of devices


when using an N to N
network

M8039 ()
Constant
scan mode

When ON the PLC executes


the user program within a
constant scan duration. The
difference between the
actual end of the program
operation and the set
constant scan duration
causes the PLC to pause.

For symbol key see page 2-1.

2-10

FX Series Programmable Controller

2.6

Diagnostic Devices 2

Step Ladder (STL) Flags


(M8040 to M8049 and D8040 to D8049)
Diagnostic
Device

Operation

FX1S

FX1N

Diagnostic
Device

FX2N

FX2NC

Operation

M8040 ()
STL transfer
disable

When ON STL state transfer


is disabled

D8040 ( )
Lowest active
STL step

M8041 (S)
Transfer start

When ON STL transfer from


initial state is enabled during
automatic operation
(ref. IST FNC 60)

D8041 ( )
2nd active
STL state

M8042 ()
Start pulse

A pulse output is given in


response to a start input
(ref. IST FNC 60)

D8042 ( )
3rd active
STL state

M8043 (S)
Zero return
complete

On during the last state of


ZERO RETURN mode
(ref. IST FNC 60)

D8043 ( )
4th active STL
state

M8044 (S)
Zero point
condition

ON when the machine zero


is detected
(ref. IST FNC 60)

D8044 ( )
5th active STL
state

M8045 ()
All output
reset disable

Disables the all output reset


function when the operation
mode is changed
(ref. IST FNC 60)

D8045 ( )
6th active STL
state

M8046 ( )
STL state ON

ON when STL monitoring


has been enabled (M8047)
and there is an active STL
state

D8046 ( )
7th active STL
state

M8047 ()
Enable STL
monitoring

When ON D8040 to D8047


are enabled for active STL
step monitoring

D8047 ( )
8th active STL
state

M8048 ( )
Annunciator
ON

D8048

Reserved

(Not FX1S, FX1N)

ON when Annunciator
monitoring has been
enabled (M8049) and there
is an active Annunciator flag

M8049 ()
Enable
Annunciator
monitoring

When ON D8049 is enabled


for active Annunciator state
monitoring

D8049 ( )
Lowest active
Annunciator

Stores the lowest currently


active Annunciator from the
range S900 to S999
(Updated at END)

(Not FX1S, FX1N)

(Not FX1S, FX1N)

Up to 8 active STL states,


from the range S0 to S899,
are stored in D8040 to D8047
in ascending numerical order.
(Updated at END)

For symbol key see page 2-1.

General note:
M8046 to M8049 STL states are updated when the END instruction is executed.

2-11

FX Series Programmable Controller

2.7

Diagnostic Devices 2

Interrupt Control Flags


(M8050 to M8059 and D8050 to D8059)
Diagnostic
Device

Operation

FX1S

FX1N

Diagnostic
Device

FX2N

Operation

M8050 ()
I00 disable
M8051 ()
I10 disable
M8052 ()
I20 disable
M8053 ()
I30 disable
M8054 ()
I40 disable
M8055 ()
I50 disable
M8056 ()
I6 disable
(Not FX1S, FX1N)

M8057 ()
I7 disable

D8050 -D8059

Reserved

When the EI (FNC 04)


instruction is driven in the
user program, all interrupts
are enabled unless the
special M devices noted
here are driven ON. In that
case for each special M coil
that is ON, the associated
interrupt is disabled, i.e. will
not operate.
Note denotes all types of
that interrupt

(Not FX1S, FX1N)

M8058 ()
I8 disable
(Not FX1S, FX1N)

M8059()
I010 to I060
disabled as a
single group
(Not FX1S, FX1N)

I010 ~ I060 is disabled for


high speed counter interrupt
(FNC53)
When this flag is ON, the
associated interrupt is
disabled and therefore will
not operate.

For symbol key see page 2-1.

2-12

FX2NC

FX Series Programmable Controller

2.8

Diagnostic Devices 2

Error Detection Devices


(M8060 to M8069 and D8060 to D6069)
Diagnostic
Device
M8060 ( )
I/O
configuration
error

Operation
Detection
ON- OFF
OFF -ON

(Not FX1S, FX1N)

M8061 ( )
PLC hardware
error

M8063( )(R)
Parallel link/
RS232-C and
RS485 (422)
comms error on
optional port

OFF

RUN

ON

STOP

While the
PLC is in
RUN

M8067( )(R)
Operation
error
-

(Not FX1S, FX1N)

D8061 ( )

D8063( )(-R)

When the
program is
changed
(PLC in
STOP) and
when a
program is
transferred
(PLC in
STOP)

Flash

STOP

OFF

RUN

(Not FX1S, FX1N)

FX2NC

Operation

The first I/O number of


the unit or block causing
the error - See note 6
Error code for hardware
error - See appropriate
error code table
Error code for PC/HPP
Communications error See appropriate error
code table

Error code for parallel


link error - See FX
communication users
manual

Error code identifying


parameter error - See
D8064 ( )
appropriate error code
table
Error code identifying
syntax error - See
D8065 ( )
appropriate error code
table
Error code identifying
program construction
error
D8066 ( )
See appropriate error
code table
Error code identifying
operation error. See
D8067( )(R)
appropriate error code
table
D8068 ()

See note 7

FX2N

RUN

While in PLC
is in RUN

D8060 ( )

(Not FX1S, FX1N)

OFF

FX1N

Diagnostic
Device

D8062 ( )

When a
signal from
the optional
port is
received

M8066 ( )
Program
error

M8068 ()
Operation
error latch
M8069 ()
I/O bus error

PROG.E
PLC
LED
STATUS

When a
signal from
the
programming
port is
received

M8064 ( )
Parameter
error
M8065 ( )
Syntax error

Other

M8062 ( )
PC/HPP
comms error on
programming
port
(Not FX1S, FX1N)

FX1S

Operation error step


number latched

Step numbers for found


D8069( )(R) errors corresponding to
flags M8065 to M8067

For symbol key see page 2-1.


Please see the following page for the notes referenced in this table.

2-13

FX Series Programmable Controller

Diagnostic Devices 2

Note 6:
If the unit or block corresponding to a programmed I / O
number is not actually loaded, M8060 is set to ON and the
first device number of the erroneous block is written to
D8060.

Note 7:

Contents of
D8060
1

= X 20
Device number:
10 to 177
Device type:
1 - Input X
0 - Output Y

An I/O bus check is executed when M8069 is turned ON.


If an I/O bus error occurs, error code 6103 is written to
D8069 and M8061 is turned ON.
If an Extension unit 24V failure occurs, error code 6104 is written to D8061 and M8061 is
turned ON. M8009 will then be turned ON and the I/O address of the lowest numbered device
affected by the 24V DC power failure is written to D8009

General note:
HPP refers to Handy programming panel.

2-14

FX Series Programmable Controller

2.9

Diagnostic Devices 2

Link and Special Operation


Devices (M8070 to M8099 and D8070 to D8099)
Diagnostic
Device
M8070 (R)

M8071 (R)
M8072 ( )
M8073 ( )

Operation
Driven when the PLC is a
master station in a parallel
link application
Driven when the PLC is a
slave station in a parallel
link application
ON while the PLC is
operating in a parallel link
ON when M8070/ M8071
are incorrectly set during
parallel link operations

M8074

Reserved

M8075

When executing Sampling


trace in GX-Developer or
FX-PCS/WIN-E, these
devices are used by the
PLC internal system

(Not FX1S, FX1N)

M8076
(Not FX1S, FX1N)

M8077
(Not FX1S, FX1N)

M8078
(Not FX1S, FX1N)

M8079
(Not FX1S, FX1N)

ON during sampling trace


ON when sampling trace
complete
When executing Sampling
trace in GX-Developer or
FX-PCS/WIN-E, this device
is used by the PLC internal
system

FX1S

FX1N

Diagnostic
Device
D8070 ( )

FX2N

FX2NC

Operation
Parallel link watchdog time 500 msec

D8071 - D8073 Reserved

D8074
(Not FX1S, FX1N)

D8075
(Not FX1S, FX1N)

D8076
(Not FX1S, FX1N)

D8077
(Not FX1S, FX1N)

D8078
(Not FX1S, FX1N)

D8079

When executing Sampling


trace in GX-Developer or
FX-PCS/WIN-E, these
devices are used by the PLC
internal system

(Not FX1S, FX1N)

D8080 to
D8095
M8080 -M8098 Reserved

(Not FX1S, FX1N)

D8096 to
D8098
(Not FX1S, FX1N)

M8099 ()
(Not FX1S, FX1N)

High speed free timer


operation
When ON, continue
counting free ring timer
(D8099)

D8099
(Not FX1S, FX1N)

Free ring timer, range: 032,767 in units of 0.1 msec


(for use in measuring high
speed pulse input durations)
See section 10.9.2
FX Programming manual II

For symbol key see page 2-1.

2-15

FX Series Programmable Controller

2.10

Diagnostic Devices 2

Miscellaneous Devices
(M8100 to M8119 and D8100 to D8119)
Diagnostic
Device

Operation

FX1S

FX1N

Diagnostic
Device

FX2N

FX2NC

Operation

D8102 ( )
Memory
Capacity
M8109 ( )
(Not FX1S, FX1N)

2.11

Output refresh error

0002: 2K steps (FX1S only)


0004: 4K steps (FX2N, FX2NC)
0008: 8K steps (FX1N, FX2N, FX2N)
0016: 16K steps (FX2N, FX2NC)

D8109 ( )

Output refresh error, lowest


device number; 0, 10, 20, etc.

(Not FX1S, FX1N)

Communication Adapter
Devices, i.e. 232ADP, 485ADP
(M8120 to M8129 and D8120 to D8129)
Diagnostic
Device

Operation

FX1S

FX1N

Diagnostic
Device

FX2N

FX2NC

Operation

Communications format
(RS instruction, Computer
link)
Station number setting
D8121
(Computer link)
Amount of remaining data to
D8122( )(R) be transmitted
(RS instruction)
Amount of data already
D8123( )(R) received
(RS instruction)
Data header, default STX
D8124 ()
(02H)
(RS instruction)
Data terminator, default ETX
D8125 ()
(03H)
(RS instruction)

M8120

Reserved

D8120

M8121( )(R)

Data transmission delayed


(RS instruction)

M8122 (R)

Data transmission flag


(RS instruction)

M8123 (R)

Finished receiving data


(RS instruction)

M8124( )

Carrier detection flag


(RS instruction)

M8125

Reserved

M8126

Global flag
(Computer link)

D8126

M8127 ()

On Demand handshake flag


(Computer link)

D8127 ()

M8128 ()

On Demand error flag


(Computer link)

D8128 ()

M8129 ()

On Demand Byte/Word
changeover
(Computer link),
Time out evaluation flag
(RS instruction)

D8129

Reserved
On Demand head device
register
(Computer link)
On Demand data length
register
(Computer link)
Data network time-out timer
value
(RS instruction, Computer
link)

For symbol key see page 2-1.

2-16

FX Series Programmable Controller

2.12

Diagnostic Devices 2

High Speed Zone Compare


Table Comparison Flags
(M8130 to M8148 and D8130 to D8148)
Diagnostic
Device
M8130
(Not FX1S, FX1N)

See note 8

M8131 ( )()
(Not FX1S, FX1N)

See note 8
M8132
(Not FX1S, FX1N)

See note 8
M8133 ( )()
(Not FX1S, FX1N)

See note 8

Operation

FX1S

Diagnostic
Device

Selects comparison tables


to be used with the HSZ
instruction

D8130 ( )()

ON when the HSZ


comparison table has been
completed.

D8131 ( )()

Selects the use of the PLSY


instruction with the HSZ
comparison tables
ON when the HSZ
comparison table (when
used with the PLSY
instruction) has been
completed.

(Not FX1S, FX1N)

(Not FX1S, FX1N)

D8132
D8133
( )()
(Not FX1S, FX1N)

D8134
D8135
( ) ()
(Not FX1S, FX1N)

M8134M8139

FX1N

Reserved
D8136
D8137
( ) ()
D8138 D8139

FX2N

FX2NC

Operation
Contains the number of the
current record being
processed in the HSZ
comparison table
Contains the number of the
current record being
processed in the HSZ
comparison table when the
PLSY operation has been
enabled
Contains the source (output
pulse frequency) data for the
PLSY instruction when used
with the HSZ comparison
table
Contains a copy of the value
for the current comparison
when the HSZ comparison
table and combined PLSY
output are used. This data is
only available in 32 bit or
double word format.
Contains the total number of
pulses that have been output
using the PLSY (or PLSR)
instruction on Y000 and Y001.
This data is only available in
32 bit or double word format
Reserved

Note 8
See section 5.6.6 in FX Programming Manual II for full explanation and use.

2-17

FX Series Programmable Controller

Diagnostic
Device

M8140 ( )()
(Not FX2N, FX2NC)

M8141 to
M8144

M8145 ()
(Not FX2N, FX2NC)

M8146 ()
(Not FX2N, FX2NC)

M8147 ( )
(Not FX2N, FX2NC)

M8148 ( )
(Not FX2N, FX2NC)

Diagnostic Devices 2

Operation

Diagnostic
Device

When ON, clears pulse


output in FNC156(ZRN)
instruction

D8140
D8141
( ) ()

Reserved

D8142
D8143
( ) ()

Y000 Pulse output stop


command

D8145 ()

Y001 Pulse output stop


command

D8146 ()

Y000 Pulse output monitor


(Busy/Ready)

D8147 ()

Y001 Pulse output monitor


(Busy/Ready)

D8148 ()

(Not FX2N, FX2NC)

(Not FX2N, FX2NC)

(Not FX2N, FX2NC)

(Not FX2N, FX2NC)

Operation
Contains the total number of
pulses that have been output
to Y0 using the PLSY or PLSR
instructions. This data is only
available in 32 bit or double
word format.
Contains the total number of
pulses that have been output
to Y1 using the PLSY or PLSR
instructions. This data is only
available in 32 bit or double
word format.
FNC156(ZRN),
FNC158(DRVI),
FNC159(DRVA) Bias value
setting (default:0)
FNC156(ZRN),
FNC158(DRVI),
FNC159(DRVA)
Max. speed setting
(default:100,000)
FNC156(ZRN),
FNC158(DRVI),
FNC159(DRVA) Acceleration/
Deceleration time setting
(default:100)

For symbol key see page 2-1

2-18

FX Series Programmable Controller

2.13

Diagnostic Devices 2

Miscellaneous Devices (M8160 to M8199)


Diagnostic
Device
M8160 ()
(Not FX1S, FX1N)

M8161 ()

M8162 ()

M8164 ()
(Not FX1S, FX1N)

M8167 ()
(Not FX1S, FX1N)

M8168 ()
(Not FX1S, FX1N)

M8169
M8170 (R)
X0 pulse catch
M8171 (R)
X1 pulse catch
M8172 (R)
X2 pulse catch
M8173 (R)
X3 pulse catch
M8174 (R)
X4 pulse catch
M8175 (R)
X5 pulse catch

Operation

FX1S

FX1N

Diagnostic
Device

FX2N

Operation

Selection of XCH operation


to swap bytes in a single
data word
Selection of 8 bit operations
for applied instructions
ASC, RS, ASCI, HEX, CCD
High speed mode for
Parallel link, 2 data words
Read/write only
When ON, a value in D8164
is used as the number of
FROM/TO exchange points.
(FX2N/2NC CPU Version 2.00
and above)

Selection of hexadecimal
input mode for the HKY
instruction
Selection of BCD mode for
use with the SMOV
instruction
Reserved
When the leading edge of a
pulse is received at an input
from the range X0 to X5 the
associated M device
detailed here is set ON. By
resetting the same device
within the user program the
next pulse occurrence will
again set the M coil ON.
Hence, fast input pulses are
caught and stored. This
operation requires the EI
(FNC04) instruction to be
active. For details see page
2-12

M8176 -M8199 Reserved

For symbol key see page 2-1.

2-19

FX2NC

FX Series Programmable Controller

2.14

Diagnostic Devices 2

Miscellaneous devices (D8158 to D8164) and


Index Registers (D8182 to D8199)
Diagnostic
Device
D8158 ()
(Not FX2N, FX2NC)

D8159 ()
(Not FX2N, FX2NC)

D8164 ()

Operation

Control device for


FX1N-5DM*1

FX1S

Diagnostic
Device

FX1N FX2N FX2NC


Operation

D8187 ( )

Value of V3 index register

D8188 ( )

Value of Z4 index register

D8189 ( )

Value of V4 index register

Default: k-1

Control device for


FX1N-5DM*1
Default: k-1
Number of FROM/TO
exchange points

(Not FX1S, FX1N)

(FX2N/2NC CPU Version 2.00 and


above)

D8181 ( )

Reserved

D8190 ( )

Value of Z5 index register

D8182 ( )

Value of Z1 index register

D8191 ( )

Value of V5 index register

D8183 ( )

Value of V1 index register

D8192 ( )

Value of Z6 index register

D8184 ( )

Value of Z2 index register

D8193 ( )

Value of V6 index register

D8185 ( )

Value of V2 index register

D8194 ( )

Value of Z7 index register

D8186 ( )

Value of Z3 index register

D8195 ( )

Value of V7 index register

For symbol key see page 2-1.


*1 See Chapter 10.19.2, FX Programming Manual II (JY992D88101)

2-20

FX Series Programmable Controller

2.15

Diagnostic Devices 2

N:N Network Related Flags and Data Registers

FX1S

FX1N

FX2N

FX2NC

Note: Functionalily available for FX2N CPU Version 2.00 and above
Diagnostic
Device
M8183 ( )
(For FX1S use M504)

M8184 ( )
(For FX1S use M505)

M8185 ( )
(For FX1S use M506)

M8186 ( )
(For FX1S use M507)

M8187 ( )
(For FX1S use M508)

M8188 ( )
(For FX1S use M509)

M8189 ( )
(For FX1S use M510)

M8190 ( )
(For FX1S use M511)

M8191 ( )
(For FX1S use M503)

Operation

Diagnostic
Device

Operation

ON when communication error


in master station
ON when communication error
in 1st slave station
ON when communication error
in 2nd slave station
ON when communication error
in 3rd slave station

D8173 ( )

Station number

D8174 ( )

Total number of slave stations

D8175 ( )

Refresh range

D8176
See note 10

Default value k0

ON when communication error


in 4th slave station

D8177
See note 10

ON when communication error


in 5th slave station
ON when communication error
in 6th slave station
ON when communication error
in 7th slave station

D8178
See note 10
D8179
See note 10
D8180
See note 10
D8201 ( )

ON when communicating to
another station

(For FX1S use D201)

D8202 ( )
(For FX1S use D202)

D8203 ( )
(For FX1S use D203)

D8204 to
D8210 ( )
(For FX1S use D204
to D210)

D8211 ( )
(For FX1S use D2113)

D8212 to
D8218 ( )
(For FX1S use D212
to D218)

Station number setting


Total number of slave stations
setting
Default value k7

Refresh range setting


Default value k0

Retry count setting


Default value k3

Comms time-out setting


Default value k5

Current network scan time


Maximum network scan time

Number of communication
error at master station
Number of communication
error at respective slave
station
Code of communication error
at master station
Code of communication error
at respective slave station

Note 9
Devices M503-M511 and D201-D255 in the FX1S cannot be applied to other functions in
the user program. These devices are used exclusively for the N:N Network.

Note 10
When these devices are not being used for an N:N Network their respective default
vaues are all 0. The relavent default values are assumed at each power ON.

2-21

FX Series Programmable Controller

2.16

Diagnostic Devices 2

Up/Down Counter Control


(M8200 to M8234 and D8219 to D8234)
Diagnostic
Device

M8200 M8234 ()

FX1S

Operation

Diagnostic
Device

When M8 is operated,
counter C functions as
a down counter. When
M8 is not operated the
associated counter operates
as an up counter

D8219 -D8234

FX1N

FX2N

FX2NC

Operation

Reserved

For symbol key see page 2-1.

2.17

High Speed Counter Control


(M8235 to M8255 and D8235 to D8255)
Diagnostic
Device

Operation

When M8 is operated,
the 1 phase high speed
counter C functions as
a down counter. When
M8235 -M8245
M8 is not operated the
()
associated counter operates
as an up counter.
The available counters
depends upon the PLC type.
When M8 is operated,
the 2 phase high speed
counter C functions as
a down counter. When
M8246 - M8255
M8 is not operated the
( )()
associated counter operates
as an up counter.
The available counters
depends upon the PLC type.

FX1S

Diagnostic
Device

D8235 -D8255

FX1N

FX2N

Operation

Reserved

For symbol key see page 2-1.

2-22

FX2NC

FX Series Programmable Controller

2.18

Diagnostic Devices 2

FX1S

Error Code Tables


Error Detection
Device

D8061
PLC Hardware
error

Stored Error
Number
0000
6101
6102
6103
6104
6105

Error Detection
Device
D8062
PC/HPP
communication
error
(Not FX1S, FX1N)

Error Detection
Device

D8063
Serial
communication
errors

Stored Error
Number
0000
6201
6202
6203
6204
6205

Stored Error
Number
0000
6301
6302
6303
6304
6305
6306
6312
6313
6314

FX1N

FX2N

FX2NC

Associated Meaning

Action

No error
RAM error
Operation circuit error
I/O bus error (M8069 = ON)
Extension unit 24V failure (M8069=ON)

Check the cable


connection between the
extension unit/block and
the PLC

Watch Dog Timer error

Scan time has exceeded


the WDT time value set
in D8000. Check user
program.

Associated Meaning
No error
Parity/ overrun/ framing error
Communications character error
Communication data sum check error
Data format error
Command error

Associated Meaning
No error
Parity/ overrun/ framing error
Comms character error
Comms data sum check error
Comms data format error
Command error
Computer link - received command
other than GW (global) when station
number was FF
Watchdog timer error
Parallel link character error
Parallel link data sum check error
Parallel link data format error

Action

Check the cable


connection between the
programming device and
the PLC

Note

Check communication
settings, parameters and
applicable devices.
(Computer link, N:N
network, Parallel link
etc.)
Refer to FX
Communication Users
Manual for wiring
techniques

2-23

FX Series Programmable Controller

Error Detection Stored Error


Device
Number
0000
6401
6402
D8064
6403
Parameter
6404
error
6405
6406 - 6408
6409

Diagnostic Devices 2

Associated Meaning
No error
Program sum check error
Memory capacity setting error
Latched device area setting error
Comment area setting error
File register area setting error
Reserved
Other setting error

Error Detection Stored Error


Associated Meaning
Device
Number
0000
No error
Incorrect instruction/ device symbol/
6501
device number combination
No timer or counter coil before setting
6502
value
1)No setting value following either a timer
or a counter coil
6503
2)Insufficient number of operands for an
applied instruction
1)The same label number is used more
than once
6504
2)The same interrupt input or high speed
D8065
counter input is used more than once
Syntax error
Device number is outside the allowable
6505
range
6506
Invalid applied instruction
Invalid Pointer device [P] assignment for
6507
Jump or Call instruction
Invalid Interrupt pointer device [I]
6508
assignment
6509
Other error
6510
MC nesting (N) number error
The same interrupt input or high speed
6511
counter input is used more than once

Action

STOP the PLC, check


parameter, if incorrect
change to a suitable
value

Action

During programming,
each instruction is
checked as it is entered.
If a syntax error is
detected, re-enter the
instruction correctly

2-24

FX Series Programmable Controller

Error Detection Stored Error


Associated Meaning
Device
Number
0000
No error
LD and LDI is used continuously 9 or
6601
more times in succession
1)No LD/ LDI instruction.
The use of LD/LDI or ANB/ORB
instruction is incorrect.
2)The following instructions are not
connected to the active bus line:
6602
STL, RET, MCR, (P)ointer, (I)nterrupt, EI,
DI, SRET, IRET, FOR, NEXT, FEND and
END
3)When MPP is missing
MPS is used continuously more than 12
6603
times
The use of MPS, MRD, MPP instruction is
6604
incorrect.
1)The STL instruction is continuously
used 9 times or more
2)MC, MCR instruction, (I)nterrupt pointer
or SRET instruction is used within an STL
6605
D8066
program area
Circuit error
3)RET has not been used in the program
or is not connected to an STL instruction
1)No (P)ointer, (I)nterrupt pointer
2)No SRET/ IRET
3)An (I)nterrupt pointer, SRET or IRET
has been used within the main program
6606
4)STL, RET, MC or MCR have been used
within either a subroutine or an interrupt
routine
1)The use of FOR and NEXT is incorrect
2)The following instructions have been
6607
used within a FOR -NEXT loop:
STL, RET, MC, MCR, IRET, SRET, FEND
or END
1)The use of MC/ MCR is incorrect
2)Missing MCR N0
6608
3)SRET, IRET instruction or an (I)nterrupt
pointer has been used within an MC/
MCR instruction area
6609
Other error

Diagnostic Devices 2

Action

A circuit error occurs if a


combination of
instructions is incorrect
or badly specified.
Select programming
mode and correct the
identified error.

Continued on next page...

2-25

FX Series Programmable Controller

Error Detection Stored Error


Device
Number
6610
6611
6612
6613
6614
6515
6616

6617

6618

6619
D8066
Circuit error
6620
6621
6622
6623
6624
6625

6626
6627
6628
6629
6630
6631
6632

Diagnostic Devices 2

Associated Meaning

Action

LD, LDI is used continuously 9 or more


times in succession
Number of LD/LDI instructions is more
than ANB/ORB instructions
Number of LD/LDI instructions is less
than ANB/ORB instructions
MPS is used continuously more than 12
times
MPS instruction missing
MPP instruction missing
Unauthorized use of the MPS/ MRD/
MPP instructions; possible coil missing
One of the following instructions is not
connected to the active bus line:
STL, RET, MCR, (P)ointer, (I)nterrupt
pointer, EI, DI, SRET, IRET, FOR, NEXT,
FEND and END
STL, RET, MC or MCR programmed
within either a subroutine or an interrupt
routine
Invalid instruction programmed within a
FOR - NEXT loop:
STL, RET, MC, MCR,(I)nterrupt pointer,
IRET and SRET
FOR - NEXT instruction nesting levels (5)
exceeded
The number of FOR and NEXT
instructions does not match
NEXT instruction not found
MC instruction not found
MCR instruction not found
The STL instruction is continually used 9
times or more
Invalid instruction programmed within an
STL - RET program area:
MC, MCR, (I)nterrupt pointer, IRET and
SRET
RET instruction not found
(I)nterrupt pointer, SRET and IRET
incorrectly programmed within main
program
(P)ointer or (I)nterrupt pointer label not
found
SRET or IRET not found
SRET programmed in invalid location
IRET programmed in invalid location

A circuit error occurs if a


combination of
instructions is incorrect
or badly specified.
Select programming
mode and correct the
identified error.

2-26

FX Series Programmable Controller

Diagnostic Devices 2

Error Detection Stored Error


Associated Meaning
Device
Number
0000
No error
1)No jump destination (pointer) for CJ or
CALL instructions
2)(P)ointer is designated in a block that
6701
comes after the END instruction
3)An independent label is designated in a
FOR-NEXT loop or a subroutine
6 or more CALL instruction nesting levels
6702
have been used
3 or more interrupt nesting levels have
6703
been used
D8067
6 or more FOR - NEXT instruction nesting
6704
Operation
levels have been used
error
An incompatible device has been
6705
specified as an operand for an applied
instruction
A device has been specified outside of
6706
the allowable range for an applied
instruction operand
A file register has been accessed which is
6707
outside of the users specified range
6708
FROM/ TO instruction error
Other error, i.e. missing IRE/ SRET,
6709
unauthorized FOR - NEXT relationship
6730
Sampling time TS (TS<0 or >32767)
6732
Input filter value (<0 or >=101)
6733
Proportional gain KP (KP<0 or >32767)
6734
Integral time constant TI (TI<0 or >32767)
6735
Derivative gain KD (KD<0 or >=101)
Derivative time constant TD
6736
(TD<0 or >32767)
6740
D8067
PID
Operation
error

Sampling time TS is less than the


program scan time.

6746

Current value exceeds its limits


Calculated error exceeds its limits
Integral result exceeds its limits
Derivative gain over, or differential value
exceeds allowable range
Derivative result exceeds its limits

6747

Total PID result exceeds its limits

6750

SV - PVnf < 150, or system is unstable


(SV - PVnf has wide, fast variations)

6751

Large Overshoot of the Set Value

6752

Large fluctuations during Autotuning Set


Process

6742
6743
6744
6745

Action

These error occur during


the execution of an
operation.
When an operation error
occurs, STOP the PLC
enter programming ode
and correct the fault.
Note: operation errors
can occur even when the
syntax or circuit design
is correct, e.g.
D500Z is a valid
statement within an
FX1N PLC. But if Z had a
value of 10000, the data
register D10500 would
be attempted to be
accessed. This will
cause an operation error
as there is no D10500
device available.

The identified parameter


is specified outside of its
allowable range
Execution ceases PID
instruction must be reset
before execution will
resume
TS is set to program
scan time Execution will continue.
Data affected resets to
the nearest limit value.
For all errors except
6745, this will either be a
minimum of -32768 or a
maximum of +32767.
Execution will continue,
but user should reset
PID instruction.
The error fluctuation is
outside the normal
operation limits for the
PID instruction.
Execution ceases. PID
instruction must be
reset.

2-27

FX Series Programmable Controller

Diagnostic Devices 2

2-28

Under no circumstances will Mitsubishi Electric be liable or responsible for any


consequential damage that may arise as a result of the installation, use and/or
programming of the products associated with this manual.
All examples and diagrams shown in this manual are intended as an aid to
understanding the text, not to guarantee operation. Mitsubishi Electric will
accept no responsibility for actual use of the product based on these illustrative
examples.
Owing to the very great variety of possible applications, users must satisfy
themselves as to the suitability of each specific application.

MITSUBISHI ELECTRIC
HEADQUARTERS

EUROPEAN REPRESENTATIVES

EUROPEAN REPRESENTATIVES

MITSUBISHI ELECTRIC EUROPE B.V.


EUROPE
German Branch
Gothaer Strae 8
D-40880 Ratingen
Phone: +49 (0)2102 / 486-0
Fax: +49 (0)2102 / 486-1120
MITSUBISHIELECTRICEUROPEB.V.-org.sl. CZECH REP.
Czech Branch
Avenir Business Park, Radlick 714/113a
CZ-158 00 Praha 5
Phone: +420 - 251 551 470
Fax: +420 - 251-551-471
MITSUBISHI ELECTRIC EUROPE B.V.
FRANCE
French Branch
25, Boulevard des Bouvets
F-92741 Nanterre Cedex
Phone: +33 (0)1 / 55 68 55 68
Fax: +33 (0)1 / 55 68 57 57
MITSUBISHI ELECTRIC EUROPE B.V.
IRELAND
Irish Branch
Westgate Business Park, Ballymount
IRL-Dublin 24
Phone: +353 (0)1 4198800
Fax: +353 (0)1 4198890
MITSUBISHI ELECTRIC EUROPE B.V.
ITALY
Italian Branch
Viale Colleoni 7
I-20041 Agrate Brianza (MB)
Phone: +39 039 / 60 53 1
Fax: +39 039 / 60 53 312
MITSUBISHI ELECTRIC EUROPE B.V.
POLAND
Poland Branch
Krakowska 50
PL-32-083 Balice
Phone: +48 (0)12 / 630 47 00
Fax: +48 (0)12 / 630 47 01
MITSUBISHI ELECTRIC EUROPE B.V.
RUSSIA
52, bld. 3 Kosmodamianskaya nab 8 floor
RU-115054 oscow
Phone: +7 495 721-2070
Fax: +7 495 721-2071
MITSUBISHI ELECTRIC EUROPE B.V.
SPAIN
Spanish Branch
Carretera de Rub 76-80
E-08190 Sant Cugat del Valls (Barcelona)
Phone: 902 131121 // +34 935653131
Fax: +34 935891579
MITSUBISHI ELECTRIC EUROPE B.V.
UK
UK Branch
Travellers Lane
UK-Hatfield, Herts. AL10 8XB
Phone: +44 (0)1707 / 27 61 00
Fax: +44 (0)1707 / 27 86 95
MITSUBISHI ELECTRIC CORPORATION
JAPAN
Office Tower Z 14 F
8-12,1 chome, Harumi Chuo-Ku
Tokyo 104-6212
Phone: +81 3 622 160 60
Fax: +81 3 622 160 75
MITSUBISHI ELECTRIC AUTOMATION, Inc.
USA
500 Corporate Woods Parkway
Vernon Hills, IL 60061
Phone: +1 847 478 21 00
Fax: +1 847 478 22 53

GEVA
AUSTRIA
Wiener Strae 89
AT-2500 Baden
Phone: +43 (0)2252 / 85 55 20
Fax: +43 (0)2252 / 488 60
TEHNIKON
BELARUS
Oktyabrskaya 16/5, Off. 703-711
BY-220030 Minsk
Phone: +375 (0)17 / 210 46 26
Fax: +375 (0)17 / 210 46 26
ESCO DRIVES & AUTOMATION
BELGIUM
Culliganlaan 3
BE-1831 Diegem
Phone: +32 (0)2 / 717 64 30
Fax: +32 (0)2 / 717 64 31
Koning & Hartman b.v.
BELGIUM
Woluwelaan 31
BE-1800 Vilvoorde
Phone: +32 (0)2 / 257 02 40
Fax: +32 (0)2 / 257 02 49
INEA BH d.o.o.
BOSNIA AND HERZEGOVINA
Aleja Lipa 56
BA-71000 Sarajevo
Phone: +387 (0)33 / 921 164
Fax: +387 (0)33/ 524 539
AKHNATON
BULGARIA
4 Andrej Ljapchev Blvd. Pb 21
BG-1756 Sofia
Phone: +359 (0)2 / 817 6044
Fax: +359 (0)2 / 97 44 06 1
INEA CR d.o.o.
CROATIA
Losinjska 4 a
HR-10000 Zagreb
Phone: +385 (0)1 / 36 940 - 01/ -02/ -03
Fax: +385 (0)1 / 36 940 - 03
AutoCont C.S. s.r.o.
CZECH REPUBLIC
Technologick 374/6
CZ-708 00 Ostrava-Pustkovec
Phone: +420 595 691 150
Fax: +420 595 691 199
Beijer Electronics A/S
DENMARK
Lykkegrdsvej 17
DK-4000 Roskilde
Phone: +45 (0)46/ 75 76 66
Fax: +45 (0)46 / 75 56 26
Beijer Electronics Eesti O
ESTONIA
Prnu mnt.160i
EE-11317 Tallinn
Phone: +372 (0)6 / 51 81 40
Fax: +372 (0)6 / 51 81 49
Beijer Electronics OY
FINLAND
Peltoie 37
FIN-28400 Ulvila
Phone: +358 (0)207 / 463 540
Fax: +358 (0)207 / 463 541
UTECO
GREECE
5, Mavrogenous Str.
GR-18542 Piraeus
Phone: +30 211 / 1206 900
Fax: +30 211 / 1206 999
MELTRADE Kft.
HUNGARY
Fert utca 14.
HU-1107 Budapest
Phone: +36 (0)1 / 431-9726
Fax: +36 (0)1 / 431-9727
Beijer Electronics SIA
LATVIA
Ritausmas iela 23
LV-1058 Riga
Phone: +371 (0)784 / 2280
Fax: +371 (0)784 / 2281
Beijer Electronics UAB
LITHUANIA
Savanoriu Pr. 187
LT-02300 Vilnius
Phone: +370 (0)5 / 232 3101
Fax: +370 (0)5 / 232 2980

ALFATRADE Ltd.
MALTA
99, Paola Hill
Malta- Paola PLA 1702
Phone: +356 (0)21 / 697 816
Fax: +356 (0)21 / 697 817
INTEHSIS srl
MOLDOVA
bld. Traian 23/1
MD-2060 Kishinev
Phone: +373 (0)22 / 66 4242
Fax: +373 (0)22 / 66 4280
HIFLEX AUTOM.TECHNIEK B.V.
NETHERLANDS
Wolweverstraat 22
NL-2984 CD Ridderkerk
Phone: +31 (0)180 46 60 04
Fax: +31 (0)180 44 23 55
Koning & Hartman b.v.
NETHERLANDS
Haarlerbergweg 21-23
NL-1101 CH Amsterdam
Phone: +31 (0)20 / 587 76 00
Fax: +31 (0)20 / 587 76 05
Beijer Electronics AS
NORWAY
Postboks 487
NO-3002 Drammen
Phone: +47 (0)32 / 24 30 00
Fax: +47 (0)32 / 84 85 77
Fonseca S.A.
PORTUGAL
R. Joo Francisco do Casal 87/89
PT - 3801-997 Aveiro, Esgueira
Phone: +351 (0)234 / 303 900
Fax: +351 (0)234 / 303 910
Sirius Trading & Services srl
ROMANIA
Aleea Lacul Morii Nr. 3
RO-060841 Bucuresti, Sector 6
Phone: +40 (0)21 / 430 40 06
Fax: +40 (0)21 / 430 40 02
Craft Con. & Engineering d.o.o.
SERBIA
Bulevar Svetog Cara Konstantina 80-86
SER-18106 Nis
Phone:+381 (0)18 / 292-24-4/5
Fax: +381 (0)18 / 292-24-4/5
INEA SR d.o.o.
SERBIA
Izletnicka 10
SER-113000 Smederevo
Phone: +381 (0)26 / 617 163
Fax: +381 (0)26 / 617 163
SIMAP s.r.o.
SLOVAKIA
Jna Derku 1671
SK-911 01 Trencn
Phone: +421 (0)32 743 04 72
Fax: +421 (0)32 743 75 20
PROCONT, spol. s r.o. Preov
SLOVAKIA
Kpeln 1/A
SK-080 01 Preov
Phone: +421 (0)51 7580 611
Fax: +421 (0)51 7580 650
INEA d.o.o.
SLOVENIA
Stegne 11
SI-1000 Ljubljana
Phone: +386 (0)1 / 513 8100
Fax: +386 (0)1 / 513 8170
Beijer Electronics AB
SWEDEN
Box 426
SE-20124 Malm
Phone: +46 (0)40 / 35 86 00
Fax: +46 (0)40 / 93 23 01
Omni Ray AG
SWITZERLAND
Im Schrli 5
CH-8600 Dbendorf
Phone: +41 (0)44 / 802 28 80
Fax: +41 (0)44 / 802 28 28
GTS
TURKEY
Bayraktar Bulvari Nutuk Sok. No:5
TR-34775 Yukar Dudullu-mraniye-STANBUL
Phone: +90 (0)216 526 39 90
Fax: +90 (0)216 526 3995
CSC Automation Ltd.
UKRAINE
4-B, M. Raskovoyi St.
UA-02660 Kiev
Phone: +380 (0)44 / 494 33 55
Fax: +380 (0)44 / 494-33-66

EURASIAN REPRESENTATIVES
Kazpromautomatics Ltd.
Mustafina Str. 7/2
KAZ-470046 Karaganda
Phone: +7 7212 / 50 11 50
Fax: +7 7212 / 50 11 50

KAZAKHSTAN

MIDDLE EAST REPRESENTATIVES


TEXEL ELECTRONICS Ltd.
ISRAEL
2 Haumanut, P.O.B. 6272
IL-42160 Netanya
Phone: +972 (0)9 / 863 39 80
Fax: +972 (0)9 / 885 24 30
CEG INTERNATIONAL
LEBANON
Cebaco Center/Block A Autostrade DORA
Lebanon - Beirut
Phone: +961 (0)1 / 240 430
Fax: +961 (0)1 / 240 438

AFRICAN REPRESENTATIVE
CBI Ltd.
Private Bag 2016
ZA-1600 Isando
Phone: + 27 (0)11 / 977 0770
Fax: + 27 (0)11 / 977 0761

SOUTH AFRICA

Mitsubishi Electric Europe B.V. /// FA - European Business Group /// Gothaer Strae 8 /// D-40880 Ratingen /// Germany
Tel.: +49(0)2102-4860 /// Fax: +49(0)2102-4861120 /// [email protected] /// www.mitsubishi-automation.com

You might also like