Wind Loading
Wind Loading
Wind Loading
WIND LOAD ESTIMATION ON TALL BUILDING PART I: COMPARISON OF RUSSIAN AND NIGERIAN CODES OF PRACTICE
S.M. Auta St. Petersburg State University of Architecture and Civil Engineering, Department of Structural Mechanics, 2nd Krasnoarmeiskaja Street, 4, 190005 St. Petersburg, Russian Federation
ABSTRACT
This paper presents a comparison study of Russian and Nigerian standards and codes of practice on wind load estimation for tall buildings. Despite the similarity of the philosophy on which the codes were developed some sizable scatter exist among the wind loading estimation by the codes under similar wind flow conditions and location. Hence the paper seeks to present this scatter as regards static behaviour of a 10-storey building. It is to be noted that the scatter in the predicted wind load arises primarily from the variations in wind field factors and their values recommended in both codes.
Keyword: Codes and standards, static behaviour, wind load, comparison, deflection, tall building 1. INTRODUCTION
Every nation has either developed or in the process of developing its own codes of practice because of its environmental factors peculiar to it among others. In this wise Nigeria and Russia have theirs namely NSCP I [1] and SNiP [2] respectively. Codes have generally been written since 1970 [3] and a lot of researches are still on, in order to perfect these codes as deeper understanding grows about the response of structures to wind load. Some of these researches that have been carried out in this area of comparison, have been made limited to most international codes and standards which include works listed in [4 7]. Recommendations from these studies are being adopted by major international codes and standards [6], in the bid to unify their application globally. With this rising trend for the international codes and standards, some of the national codes are becoming unpopular. NSCP I has been written since 1973 and undergoing perfection, but cannot attain this in isolation except compared with other existing national codes and standards. Hence in this study SNiP is chosen for this comparison study.
234
S.M. Auta
where wc is the average wind pressure, wp wind pressure due to pulsation; w0 nominal wind pressure; wph nominal pulsation wind pressure at the top height (h) of the building; k height factor; dynamic coefficient; z height at which pulsation wind pressure is being determined.
235
respectively. Design wind load: Design wind load from NSCP I can be calculated from Eq. (4) below: P=fs.q0.ce, (4)
where q0 is the nominal wind pressure; v0 is the nominal wind velocity; fs is the shape factor obtainable from Table 6 of the code; ce is the pressure coefficient.
3.3x10 = 33.0m
6.0m
6.0m
The analytic frame is figured out in figure 1. Procedure of the computations is according to both codes as outlined previous paragraphs under both codes and summary of input data recommended by both codes for vertical structures such as the 10-storey building for the case study are presented in Table 1. The wind load at the nodes of the frame, are presented in Table 2. For this static analysis, a structural analysis software popularly known as Lira was used. However, it is to be noted that dead weight of the structure was not taken into account since the analysis is assumed for this study to be linear. The result of the analysis is presented in Table 3.
236
S.M. Auta
Table 1. Input data SNiP Wind zone, exposure, Final wind Coefficients nominal wind pressure load and factors and speed NSCP I Zone I (equivalent zone); A open country with no obstruction, near sea bank; *v0=31 m/s (Table 4); q0=1.125 kN/m2 (Table 5). *v0=31m/s2 is the only value recommended within under which v0SNiP=22.18 m/s2 fall with the same exposure A (Table 4). fs=1 (table 6); ce=0.67, -0.33; sign indicates windward and leeward sides of the building
Zone II; A open country with no obstruction, near sea bank; w0=0.30 kN/m2 (table 5); v0=22.18 m/s; c=0.8, -0.6; wph=0.36m/s2; k, vary in value with height z along the height of the building, h.
Final wind load F is obtained from the expression F=A.w, where A is the surface area=14.85m2; w or P final design wind pressure from Eqs. (1) and (4) for either codes applied appropriately.
Table 2. Summary of wind load for the 10-storey frame Wind load at the nodes of the 10-storey analytic frame NSCP I Floor number 1 2 3 4 5 6 7 8 9 Total wind load, F (kN) Windward, Fwi Fw1 = 16.791 Fw2 = 11.194 Fw3 = 11.194 Fw4 = 11.194 Fw5 = 11.194 Fw6 = 11.194 Fw7 = 11.194 Fw8 = 11.194 Fw9 = 11.194 Leeward, Fli Fl1 = 8.271 Fl2 = 5.514 Fl3 = 5.514 Fl4 = 5.514 Fl5 = 5.514 Fl6 = 5.514 Fl7 = 5.514 Fl8 = 5.514 Fl9 = 5.514 SNiP Total wind load, F (kN) Windward, Fwi Fw1 = 3.562 Fw2 = 4.449 Fw3 = 5.338 Fw4 = 6.225 Fw5 = 6.668 Fw6 = 7.556 Fw7 = 8.444 Fw8 = 8.886 Fw9 = 9.329 Leeward, Fli Fl1 = 2.672 Fl2 = 3.337 Fl3 = 4.004 Fl4 = 4.669 Fl5 = 5.001 Fl6 = 5.667 Fl7 = 6.333 Fl8 = 6.665 Fl9 = 6.997
237
10
Fw10 = 5.597
Fl10 = 2.757
Fw10 = 4.886
Fl10 = 3.665
Table 3. Result of the static calculations Static behaviour of the frame SNiP Drift, max, (mm) Drift limit, lim, (mm) Maximum bending moment, Mmax, (kN.m) Minimum shear force, Qmin, (kN) 89.97 50.59 24.0 NSCP I 28.0 66.0 125.52 66.85 28% 24% Discrepancy 16%
Acknowledgement: The author is grateful to Professor A.M. Maslennikov, Dr. E.B. Oyetola and the Department of Civil Engineering, Federal University of Technology Minna, Nigeria for their support. REFERENCES
238
S.M. Auta
1. 2. 3. 4. 5. 6. 7.
8.
Nigerian Standard Code of Practice, NSCP I: 1973, PART 3: Loading. NIGERIAN STANDARDS ORGANISATION, 1973. SNiP 2.01.0785* Loading and excitations, Official publication, Moscow, 2004 (Russian edition). Peter S. Wind forces in engineering. Pergamon press. Oxford, 1978. Kijewski T. and Kareem A. Dynamic wind effects: A comparative study of provisions in codes and standards with tunnel data, Wind Struct., No.1, 1(1998)77-109. Lee B. E. and Ng W. K. Comparisons of estimated dynamic along-wind responses, J. Wind. Eng., Ind. Aeronaut, 30(1988)153-162. Zhou Y. Kijewski T. and Kareem A. Along-Wind load effects on tall buildings: Comparative study of major international codes and standards, J. Struct. Eng., No.6, 128(2002)788-796. Amin N. Martini K. Fatehi H. and Kurata T. Comparing the behaviour of 40 storey structures designed according to US and Japanese Codes, Proceedings of the Second Conference on Tall Buildings in Seismic Regions 55th Regional Conference, Los Angeles, Califonia, pp. 1-9, 1991. Hachiyan, E. Ye., Seismic action on tall buildings and structures, Aistan Publishing House, Iravan, 1973 (Russian edition).