ENGLISH
Users manual
English
FOREWORD
Thank you for purchasing this GREEN TEST FTV 100. For best results from your instrument: read this operating manual carefully observe the safety precautions
Improper use of the instrument impairs its protection functions and may create a hazardous situation. When removing and installing the battery, make sure that the test leads, sensors, and power supply units are disconnected. The instrument must be disconnected and locked off. Responsibility for the safety of any installation built using this tool lies with the system assembler. For your safety, use only the compatible accessories and cables supplied with the instrument, in conformity with IEC standard 61010-031 (2002). When sensors or accessories having a lower voltage rating and/or category than the device are used, the lower voltage rating and/or category applies to the system so constituted.
Page 2 sur 47
English
Before each use, check that the cables, housings, and accessories are in perfect condition. Any cable, sensor, or accessory of which the insulation is damaged (even partially) must be repaired or scrapped. Comply with the environmental conditions. We recommend using the personal protection equipment appropriate to the environmental conditions of use of the instrument. This tool can be used on class IV installations at voltages (AC or DC) not exceeding 600V referred to earth (IEC 61010-1) or on category III installations, at voltages not exceeding 1000V. Never use the instrument on networks of which the voltage or category exceeds those mentioned. Use the instrument only with the mains power supply unit or the battery pack supplied by the manufacturer. These units include specific safety devices. Observe the limits of physical protection of the equipment and sensors. Keep your hands away from unused terminals.
MEASUREMENT CATEGORIES
Definitions of the measurement categories according to EN-61010-1: CAT I: CAT II: Measurement category I corresponds to measurements taken on circuits not directly connected to the network. Measurement category II corresponds to measurements taken on circuits directly connected to the network. Example: measurements on electrodomestic units, portable tools, and similar devices Measurement category III corresponds to measurements on building installations. Example: measurements on distribution panels and wiring.
CAT III:
CAT IV: Measurement category IV corresponds to measurements taken at the source of low-voltage installations. Example: meters and measurements on overvoltage protection devices.
Page 3 sur 47
English
CONTENTS
FOREWORD................................................................................................................. 2
Meanings of the symbols used on the instrument ......................................................................................... 2
PRECAUTIONS FOR USE.............................................................................................. 2 MEASUREMENT CATEGORIES ...................................................................................... 3 REMARKS CONCERNING THIS MANUAL ...................................................................... 3 CONTENTS .................................................................................................................. 4 1. INTRODUCTION...................................................................................................... 6 2. CONTENT OF THE DELIVERY ................................................................................... 6 3. PRESENTATION ...................................................................................................... 7 4. SWITCHING ON/OFF .............................................................................................. 8 5. PREPARING THE SCREEN ........................................................................................ 9 6. POWER SUPPLY .................................................................................................... 12
6.1 BATTERY LIFE BETWEEN CHARGES........................................................................ 12 6.2 CHARGING THE BATTERY ..................................................................................... 12 6.3 POWER SUPPLY................................................................................................... 12
8.1 USING THE ALPHANUMERIC KEYPAD ..................................................................... 16 8.2 SITE MENU......................................................................................................... 16 8.2.1 NEW SITE DATA ......................................................................................... 16 8.2.2 8.2.3 8.2.4 A LOOK AT THE THEORY .............................................................................. 16 SELECT A SITE ........................................................................................... 17 MODIFY A SITE........................................................................................... 17
8.3 MEASUREMENT MENU.......................................................................................... 17 8.3.1 MEASUREMENT ACQUISITION ...................................................................... 17 8.3.2 MEASUREMENT ACQUIRED........................................................................... 18 8.4 ADJUSTMENTS MENU........................................................................................... 19 8.5 CONFIGURATION ................................................................................................ 20 8.6 REMOTE MEASUREMENT ...................................................................................... 20 8.7 LOCATIONS OF THE MEASUREMENT POINTS ON THE PHOTOVOLTAIC PANELS............ 21 8.8 MEASUREMENT ACQUISITION............................................................................... 22 8.9 LOCATIONS OF THE MEASUREMENT POINTS ON A SINGLE-PHASE INVERTER ............. 23 8.10 MEASUREMENT ACQUISITION............................................................................. 24 8.11 CONNECTIONS OF THE MEASUREMENTS OF THE COMPLETE SITE WITH SINGLE-PHASE OUTPUT................................................................................................................... 25 8.12 MEASUREMENT ACQUISITION............................................................................. 26 8.13 LOCATIONS OF THE MEASUREMENT POINTS ON A THREE-PHASE INVERTER............. 27 8.14 MEASUREMENT ACQUISITION............................................................................. 28 8.15 CONNECTIONS OF THE MEASUREMENTS OF THE COMPLETE SITE WITH THREE-PHASE OUTPUT................................................................................................................... 29 8.16 MEASUREMENT ACQUISITION............................................................................. 30 Page 4 sur 47
English
8.17 MEASUREMENT OF THE COMPLETE SITE IN TWO SEPARATE STAGES ....................... 30 8.18 COMMUNICATION INTERFACE............................................................................. 31 8.18.1 RS232 INTERFACE - TECHNICAL CHARACTERISTICS.................................... 31 8.18.2 USB INTERFACE - TECHNICAL CHARACTERISTICS ....................................... 31 8.19 "GREEN REPORT" SOFTWARE.............................................................................. 31 8.19.1 GREEN REPORT SOFTWARE INSTALLATION PROCEDURE .............................. 32 8.19.2
8.19.2.1 8.19.2.2 8.19.2.3 8.19.2.4 8.19.2.5 8.19.2.6
8.19.3
9. REPORT ON STATUSES AND MEASUREMENTS ....................................................... 34 10. TECHNICAL CHARACTERISTICS OF THE INSTRUMENT ........................................ 36 11. CHARACTERISTICS OF THE REMOTED MODULE................................................... 37
12. TECHNICAL CHARACTERISTICS OF THE "BLUETOOTH" COMMUNICATION KIT.... 39 13. TECHNICAL CHARACTERISTICS OF THE "CABLE" KIT ......................................... 40 14. PRODUCING A CABLE USING THE RS232 CONNECTORS PROVIDED WITH THE OPTIONAL REMOTED FTV 100 MODULE .................................................................... 41 15. TECHNICAL CHARACTERISTICS OF THE PYRANOMETER...................................... 41
11.1 PROCEDURE FOR CONNECTION AND CONFIGURATION OF THE REMOTED FTV 100 MODULE .................................................................................................................. 38
13.1 PROCEDURE FOR CONNECTION AND CONFIGURATION OF THE "BLUETOOTH" OR "RS232 CABLE" COMMUNICATION KIT ........................................................................ 40
15.1 INTRODUCTION ................................................................................................ 41 15.2 OPERATING PRINCIPLE ...................................................................................... 41 15.3 INSTALLATION AND ASSEMBLY OF THE PYRANOMETER.......................................... 42 15.4 TECHNICAL CHARACTERISTICS........................................................................... 43
18. TO ORDER........................................................................................................... 45
17.1 CLEANING ........................................................................................................ 44 17.2 METROLOGICAL CHECKS.................................................................................... 44 17.3 REPAIRS .......................................................................................................... 44 17.4 REPAIR OUTSIDE WARRANTY......................................... ERREUR ! SIGNET NON DEFINI.
Page 5 sur 47
English
1. INTRODUCTION
The GREEN TEST FTV 100 is a measuring instrument designed and built to meet the needs of technicians during the installation, testing, certification, and maintenance of photovoltaic systems. Photovoltaic systems comprise two parts: A photovoltaic generator, comprising one or more series of photovoltaic panels that generate a direct current. The inverter that converts the direct current generated by the panels into an alternating current that is supplied to the network for use.
The GREEN TEST FTV 100 has three inputs for measurements of the voltage (VDC) and current (IDC) delivered by the photovoltaic generator, making it possible to measure up to three series of solar panels at a time. Depending on the needs of the installation, you may use one input, two, or all three. The other side of the instrument has three inputs for measurements of AC voltages (VAC) and three for measurements of alternating currents (IAC), making possible measurements on one, two, or three phases. Make sure that the voltage and current connections are in phase, to avoid the acquisition of errored measurements. The measurements available on the GREEN TEST FTV 100: measurement of solar radiation by pyranometer (up to 2000W/m); measurement of outdoor temperature using a Pt100 probe (up to 80 C); measurement of the temperature of the solar panels using a Pt100 probe (up to 120 C); calculations of the theoretical power available; measurement of the voltage (1000VDC), of the current (PAC10-FTV current clamps 200ADC, PAC20-FTV current clamps 1400 ADC) and of the power delivered by the solar panels; measurement of the voltage (600VAC), of the current (MN-FTV current clamps 200AAC, C107FTV current clamps1000AAC, D43-FTV current clamps 3000AAC) and of the output power of the inverter; calculation of the efficiency of the solar panels with display of the values and highlighting of the test result; calculation of the DC/AC energy conversion (inverter) efficiency with display of the values and highlighting of the test result; Memory used to store customer data and system measurements;
Page 6 sur 47
English
MN-FTV ammeter clamps for measurement of the alternating current (200AAC) PAC10-FTV ammeter clamps for measurement of the direct current (200ADC) Set of 3m leads (red/black) Pairs of test probes (red/black) 4.5Ah Li-Ion battery Power supply unit USB cable Transport accessories Certificate of validation of the instrument CD-ROM containing: Operating manual of the Green Test FTV 100 Green Report V2.5 + instructions UpLoader 2.1 + instructions USB serial driver + instructions
3 1 4 4 1 1 1 1 1 1
PAC20-FTV ammeter clamps for measurement of the direct current (1400ADC) FTV 100 remoted module + 2 male/male RS232 connectors Bluetooth communication kit (transmitter/receiver) 15m serial cable with male/male RS232 connector RS232/USB adapter Alligator clips No. 22 carrying bag
3. PRESENTATION
22
10
11
20 21
12
19 18
13
15
14
16
17
Page 7 sur 47
English
input 1: ammeter clamp AAC input 2: ammeter clamp AAC input 3: ammeter clamp AAC input 2: ammeter clamp ADC input 2: ammeter clamp ADC input 3: ammeter clamp ADC input 1: voltage VAC input 2: voltage VAC input 3: voltage VAC input 1: voltage VDC input 2: voltage VDC input 3: voltage VDC ambient temperature probe input pyranometer input solar panel temperature probe input USB serial port (to PC) RS232 serial port to remoted unit) multi-function alphanumeric keypad having the following keys: "up" navigation key ENTER selection validation key "down" navigation key
On/Off button ESC menu exit key DEL entry deletion key input of external power supply (15V DC, 2A maximum consumed) PWR ON/CHARGE FULL (only when an external power supply is connected); lights during recharging of the internal batteries or when they have reached full charge. BAT Ch (only when an external power supply is connected); lights during the charging of the batteries.
4. SWITCHING ON/OFF
Pressing the Pressing the button for 1 second switches the instrument on. button for 3 seconds when the instrument is on switches it off.
REMARK: Pressing for more than one second when switching on may resulting in faulty lighting of the screen. If this happens, hold the button down for more than 3 seconds, then switch the instrument back on.
The instrument can operate on battery power alone (without the external supply) if it is adequately charged, or when connected to the power supply unit.
Page 8 sur 47
English
SYSTEM
4
ENVIRONMENT MEASUREMENT Radiation W/m2: 0.00 environm temp. C: ---.-panel temp. C: ---.-temp. coeff.: -.-THEORATICAL AVAIL POWER [kW]: 0.00 DC MEASUREMENT ERROR V1: - I1: - 37.9A V2: - I2: - 38.1A V3: - I3: - 38.9A DC POWER [kW]: AC MEASURE V1: - V2: - V3: - AC POWER [kW]: 0.00 ERROR 0.00A 0.00A 0.00A 0.00
11
7 8
OFF
12
14
13
15
1. 2. 3. 4.
IMP: indicates the number of the photovoltaic installation selected POWER [kW]: indicates the nominal power of the photovoltaic installation (value entered by the user). MIN RAD [W/m]: indicates the minimum insolation required for the performance calculations (see ADJUSTMENTS MENU). The default value is 600 W/m. ENVIRONMENT MEASURES: Radiation W/m: indicates the insolation measured by pyranometer (located on the panels and having the same inclination) (see also the directions for use of the pyranometer). temp. environm C: indicates the value of environme nt temperature measured by a Pt100 probe. temp. panels C: indicates the temperature of the solar panels measured by a Pt100 probe. temp. coeff.: indicates the panel performance correction parameter. This value changes when the temperature is above the data entered (NOCT). It is a constant 0.85 when the temperature is between 0 C and the NOCT (normal operating cell temperature).
Page 9 sur 47
English
When it exceeds the NOCT, the coefficient falls below 0.85 and the panel loses efficiency (see page 34, 15.2). The variation of the temperature coefficient also depends on the values entered for Gamma and for NOCT. REMARK: For all of the atmospheric measurements above, when the screen displays ---,-- with the text LOST (in red) at bottom right, communication has been broken off between the GREEN TEST instrument and the remoted module. This interruption may be because the batteries of the remoted module are discharged or because the signal has been lost (no Bluetooth link). 5. THEORETICAL AVAILABLE POWER [kW]: theoretical power for an insolation of 1000 W/m (value entered by the user, see SITE MENU NEW SITE DATA). 6. DC MEASUREMENTS: Display blank V1: DC voltage or - * - I1: direct current or -37.9A (-279.3A in 1.4kA version) V2: DC voltage or - * - I2: direct current or -38.1A (-279.8A in 1.4kA version) V3: DC voltage or - * - I3: direct current or -38.9A (-276.2A in 1.4kA version) - -: alert for each individual input (V1, V2, or V3): No connection to the PV system Voltage < 10VDC DC polarity reversed AC voltage on DC inputs (connection error) The - * - symbol also flashes WARNING is displayed at bottom right of the screen
7. 8.
DC POWER [kW]: indicates the measured direct current power from the solar generator. ALTERNATING CURRENT MEASUREMENTS: Display blank V1: AC voltage or - * - I1: alternating current (2.0A for the 3kA version) V2: AC voltage or - * - I2: alternating current (1.0A for the 3kA version) V3: AC voltage or - * - I3: alternating current (1.1A for the 3kA version)
- -: alert for each individual input (V1, V2, or V3): No connection to the PV system Voltage < 25VAC The - * - symbol also flashes WARNING is displayed at bottom right of the screen
REMARK: when connecting to the PV system, check that the phases correspond (V1-I1, V2-I2, etc.)
9. 10. AC POWER [kW]: indicates the measured AC output power of the inverter. EFFICIENCY OF PANELS: indicates the efficiency of the photovoltaic generator as a percentage (%), along with all of the test results.
REMARK: if Italian is the language selected for this device, under the provisions of standards applicable in Italy (DM19/02/2007, IEC guide 82-25), the results of the "Good/Bad" tests appear alongside the % efficiencies.
Page 10 sur 47
English
In this case:
TEST RESULTS
OK REJECTED -----
REMARK
Value in percentage and "OK" displayed in steady green Value in percentage and "REJECTED" displayed in steady red Flashing red dashes: anomaly, check the measurement parameters (power, current, voltage, insolation) and the connections of the photovoltaic system
11.
INVERTER EFFICIENCY indicates the efficiency of the DC/AC conversion as a percentage and displays all checks.
REMARK: if Italian is the language selected for this device, under the provisions of standards applicable in Italy (DM19/02/2007, IEC guide 82-25), the results of the "Good/Bad" tests appear alongside the % efficiencies. In this case:
REMARK
Value in percentage and "OK" displayed in steady green Value in percentage and "REJECTED" displayed in steady red Flashing red dashes: anomaly, check the measurement parameters (power, current, voltage, insolation) and the connections of the photovoltaic system
OK REJECTED -----
13.
14. 15.
ERROR: indicates an alert in the following cases: - Wrong connections between the photovoltaic installation and the FTV 100, in the matching of the AC measurement phases (for example V1-I2, current clamps connected backwards) resulting in a negative AC power reading; - Wrong connections between the photovoltaic installation and the FTV 100, in the DC measurements part (current clamps connected backwards) resulting in a negative DC power reading. DC CURRENT (current clamps not connected): Because of the great sensitivity of the inputs and their high impedances, the display unit indicates non-zero values. When a clamp is connected, this value can briefly reach (for the 200A clamp) I1 = -37.9A, I2 = -38.1A, I3 = -38.9A or (for the 1.4kA clamp) I1 = -279.3A, I2 = -279.8A, I3 = -276.2A) before falling back to zero. If low values remain displayed for a non-zero direct current when clamps are connected to the instrument, adjust the potentiometer to eliminate the residual magnetization of the ammeter causing the "ZERO" reading (see the instructions in the PAC current clamps manual). AC CURRENT (current clamps not connected): When the instrument is switched on, the alternating current displayed is zero. OFFONLOST INDICATIONS (REMOTE MEASUREMENT MENU) set to point 15, these texts may indicate: OFF (red): If the remote module is used, it is possible to choose "with" or "without" the panel temperature probe (see ENVIRONMENT MEASUREMENT sub-menu); ON (red): The instrument is connected to the remoted module in the two cases anticipated (see ENVIRONMENT MEASUREMENT sub-menu); LOST (red): interruption of communication between the GREEN TEST instrument and the remoted module, because the batteries of the remoted module are discharged or the signal has been lost (no Bluetooth transmission). The response time of the instrument for the display of "Lost" is approximately 20 seconds. Communication is restored automatically only if the instrument and the remoted module are off (ON is displayed on the screen instead of LOST).
Page 11 sur 47
English
6. POWER SUPPLY
6.1 BATTERY LIFE BETWEEN CHARGES
The battery icon at bottom right on the screen indicates the charge level (proportional to the number of bars of the icon that are visible).
Battery full. Life: approximately 8 hours Battery half-charged. Life: approximately 30 minutes Battery discharged (symbol flashes). Life: approximately 10 minutes
REMARK: If the fuses blow, do not attempt to replace them, but send the power supply unit to Customer Service for inspection.
Page 12 sur 47
English
7. MENU TREE
When the instrument is powered up, the "FUNCTIONS MENU" is displayed in the bottom right part of the screen.
Page 13 sur 47
English
Page 14 sur 47
English
Page 15 sur 47
English
REMARK: the data entered are recorded only if the power of the site, NOCT, and GAMMA have been entered correctly.
English
Tcel, which is the cell temperature of a PV module, can be measured using a thermoresistive sensor directly connected to the instrument or using the remoted FTV 100 module. Tamb is the ambient temperature, which can be measured using a sensor connected directly to the instrument or using a remoted FTV 100 module (the probe is generally placed in the shade).
C is measured on the backs of the modules, a In the measurement of PDC, if an operating temperature 40 temperature correction of the site itself is allowed. In this case, the relation Pcc > 0.85 x Pnom x I/Istc becomes: PDC > (1 Ptpv 0.08) x Pnom x I/Istc where Ptpv corresponds to the thermal losses of the photovoltaic generator.
Several practices exist. It is possible to select two types of mathematical relation to calculate the correction factor. The temperature of the photovoltaic cells being known, this parameter is calculated using the relation: Ptpv = (Tcel 25) x Or, from the ambient temperature, by: Ptpv = [Tamb - 25 + (NOCT 20) x I/0,8] x
Press ENTER to select the ENVIRONMENT and DC measurements of the photovoltaic generator (a red asterisk * appears on the element selected). To confirm the storage of the selected measurements, place the cursor on CONFIRM MEASUREMENT and press ENTER.
Page 17 sur 47
English
INVERTER
Press ENTER to select the INVERTER measurements (DC and AC side) (a red asterisk * appears on the element selected). To confirm the storage of the selected measurements, place the cursor on CONFIRM MEASUREMENT and press ENTER. ALL MEASUREMENTS
Press ENTER to select the ENVIRONMENT AND DC and INVERTER measurements (DC and AC side) (a red asterisk * appears on the element selected). To confirm the storage of the measurements selected, place the cursor on CONFIRM MEASUREMENT and press ENTER. CANCELLED
Press ENTER to display the data of the site after the one currently displayed. PREVIOUS SITE
Press ENTER to display the data of the site before the one currently displayed. MEASUREMENT OF THE SITE SELECTED
Press ENTER to display all measurements of the selected system, with the test results (OK or REJECTED): This menu includes the following commands: NEXT MEASUREMENT Press ENTER to display the measurements of the site after the one currently displayed. PREVIOUS MEASUREMENT
Press ENTER to display the measurements of the site before the one currently displayed. ERASE THE SELECTED MEASUREMENTS
Press ENTER to erase the measurements of the selected site. ERASE ALL MEASUREMENTS Press ENTER to erase the measurements of all sites stored in memory. (*) for the efficiency calculation, a minimum insolation of 600W/m or more on the plane of the modules (gamma) is recommended. A radiation threshold can be assigned in the Adjustments menu.
Page 18 sur 47
English
Press ENTER to select the SENSITIVITY OF THE PYRANOMETER (value expressed in [mV/(kW/m2)] and displayed on the panel of the pyranometer) if it differs from the assigned value (see: standard sensitivity value) or in the event of replacement. Press ENTER to enter the sensitivity value. Press ENTER again to validate the value entered. LOGO (NAME OF THE COMPANY THAT CERTIFIED THE SITE)
Press ENTER to select INSERTION OF THE LOGO. Press ENTER to enter the abbreviated name of the installer company that makes the measurement or to replace the name already entered. Press ENTER again to validate the name entered. DATE/TIME
Press ENTER to select DATE/TIME. Place the cursor on each field; press ENTER to enter a value (numerical only). Press ENTER again to confirm the value entered. Place the cursor on CONFIRMATION and press ENTER to record the data in memory.
Press ENTER to select POWER CALCULATION. This function is used to calculate the power with allowance for the Ptpv losses due to the reduction of performance of the photovoltaic generator as a function of AMBIENT TEMPERATURE (Tamb) or of PANEL TEMPERATURE (Tcel), Place the cursor on the desired option and press ENTER to select it (a red asterisk "*" appears on the option chosen). LANGUAGE
Press ENTER to select LANGUAGE. Place the cursor on the desired option and press ENTER to select it (a red asterisk "*" appears on the option chosen). DC MEASUREMENT
Press ENTER to select DC MEASUREMENT. Place the cursor on the desired option and press ENTER to select a type of site on the DC side (a red asterisk "*" appears on the option chosen). Example: 1 = site with one chain, 1+2 = system with two chains, 1+2+3 = system with three chains. AC MEASUREMENT
Press ENTER to select AC MEASUREMENT. Place the cursor on the desired option and press ENTER to select a type of site on the AC side (a red asterisk "*" appears on the option chosen). Example: 1 = site with one chain, 1+2 = system with two chains, 1+2+3 = system with three chains. MINIMUM INSOLATION
Press ENTER to select MINIMUM INSOLATION (W/m2). Press ENTER to enter the minimum insolation used for the efficiency calculation. Press ENTER again to validate the value entered.
Page 19 sur 47
English
CURRENT CLAMPS
Press ENTER to select the "CURRENT CLAMPS" MENU. Move the cursor to the desired IDC clamp model and press ENTER to validate your choice (a red asterisk "*" appears on the option chosen). Move the cursor to the desired IAC clamp model and press ENTER to validate your choice. (a red asterisk "*" appears on the option chosen).
8.5 CONFIGURATION
Press ENTER to display the data of the instrument for updates and periodic checks: Serial number; Microprogram version installed; Version of video board.
Press ENTER to select use of the local atmospheric input values present in the instrument, without the help of the remoted FTV 100 module (a red asterisk "*" appears on the option chosen). A test of communication with the remoted module is performed. An indication, OK or REJECTED, appears at the end of not more than 30 seconds (...Loading, flashing). On the main screen, the REMOTE MEASUREMENT indication changes to ON. The following functions can be activated only with the remoted FTV 100 module on and connected by the optional communication kit (cable or Bluetooth). REMOTE WITHOUT T pan
Press ENTER to select use of the local atmospheric input values present on the remoted FTV 100 module, without the AMBIENT TEMPERATURE value (a red asterisk "*" appears on the option chosen). The texts OK or REJECTED that appear at the end of 30 seconds (...LOADING, flashing) indicate the result of the link with the data of the remoted FTV 100 module, and are confirmed on the main screen, to the right of REMOTE MEASUREMENT, by ON or REJECTED. REMOTE WITH T pan Press ENTER to select the use of the local atmospheric input values present on the remoted FTV 100 module, with the AMBIENT TEMPERATURE value (a red asterisk "*" appears on the option chosen). The texts OK or REJECTED that appear at the end of 30 seconds (...LOADING, flashing) indicate the result of the link with the data of the remoted FTV 100 module, and are confirmed on the main screen, to the right of REMOTE MEASUREMENT, by ON or REJECTED.
Page 20 sur 47
English
English
Page 22 sur 47
English
Photovoltaic panel DC current clamp Inverter AC current clamp Electric meter Electric line
Page 23 sur 47
English
Page 24 sur 47
English
8.11 CONNECTIONS OF THE MEASUREMENTS OF THE COMPLETE SITE WITH SINGLE-PHASE OUTPUT
2. 3. 4. 5. 6. 7. 8. 9. Pyranometer Panel temperature probe Ambient temperature probe Photovoltaic panel DC current clamp Inverter AC current clamp Electric meter Electric line
Figure 3: Connections of the measurements of the complete site with single-phase output
Page 25 sur 47
English
See Figure 3: Connections of the measurements of the complete site with single-phase output
The measurements described in the previous chapters can be made simultaneously. 1. 2. Connect the VDC MEASURE LINE1 voltage inputs to the DC voltage output of the photovoltaic panel using the cables provided, respecting the polarity; Connect the DC current clamp to the IDC MEASURE PROBE1 input and to the positive or negative cable of the DC output of the photovoltaic panel. Note that the clamp is sensitive to the direction of the current measured; Activate the DC clamp; Connect the pyranometer to the PYRANOMETER input. The pyranometer measures the insolation; Connect the ambient temperature probe to the AMBIENT TEMPERATURE input. Place the probe near the photovoltaic panel; Connect the contact probe to the PANEL TEMPERATURE input. Place the probe in thermal contact with the photovoltaic panel; Connect the VAC MEASURE LINE1 voltage inputs to the AC voltage output of the inverter using the cables provided; Connect the AC current clamp to the IAC MEASURE PROBE1 input and to the alternating current output cable of the inverter.
3. 4. 5. 6. 7. 8.
Page 26 sur 47
English
English
3. 4. 5.
N.B.: AC side: check that the phases exactly match in the connection between the inputs of the voltmeter and of the ammeter:
VAC MEASURE LINE1 IAC MEASURE PROBE1 phase L1, VAC MEASURE LINE2 IAC MEASURE PROBE2 phase L2, VAC MEASURE LINE3 IAC MEASURE PROBE3 phase L3,
Page 28 sur 47
English
8.15 CONNECTIONS OF THE MEASUREMENTS OF THE COMPLETE SITE WITH THREE-PHASE OUTPUT
1. 2. 3. 4. 5. 6. 7. 8. 9. Pyranometer Panel temperature probe Ambient temperature probe Photovoltaic panel DC current clamp Inverter DC current clamp Electric meter Electric line
Figure 5: Connections of the measurements of the complete system with three-phase output
Page 29 sur 47
English
See Figure 5: Connections of the measurements of the complete system with three-phase output.
1. 2. Connect the VDC MEASURE LINE1 voltage inputs to the DC output voltage of the photovoltaic panel using the cables provided, respecting the polarity; Connect the DC current clamp to the IDC MEASURE PROBE1 input and to the positive or negative cable of the DC output of the photovoltaic panel. Note that the clamp is sensitive to the direction of the current measured; Activate the DC clamp; Connect the pyranometer to the PYRANOMETER input. The pyranometer measures the insolation; Connect the ambient temperature probe to the AMBIENT TEMPERATURE input. Place the probe near the photovoltaic panel; Connect the probe to the PANEL TEMPERATURE. Place the probe in thermal contact with the photovoltaic panel; Connect the VAC MEASURE LINE1-LINE2-LINE3 voltage inputs to the AC voltage output of the inverter using the cables provided; Connect the AC current clamp to the IAC MEASURE PROBE1- PROBE1- PROBE1 input and to the alternating current output cable of the inverter.
3. 4. 5. 6. 7. 8.
N.B.: AC side: check that the phases exactly match in the connections between the inputs of the voltmeter and of the ammeter:
VAC MEASURE LINE1 IAC MEASURE PROBE1 phase L1, VAC MEASURE LINE2 IAC MEASURE PROBE2 phase L2, VAC MEASURE LINE3 IAC MEASURE PROBE3 phase L3,
Leave the GREEN TEST FTV 100 on, disconnect it from the DC part of the installation, and acquire the measurements on the AC side downstream of the inverter.
Page 30 sur 47
English
AC SIDE (INVERTER) Connect the instrument to the downstream side of the inverter and connect the instrument as indicated by the "measurements connection diagram, single-phase inverter side (page 21)" or the "measurements connection diagram, three-phase inverter side (page 25)". In the FUNCTIONS MENU - MEASUREMENT, select MEASUREMENT ACQUISITION and place the cursor on INVERTER. Check the connections to the system and press ENTER to acquire the measurements (an * and the flashing text CURRENT ACQUISITION... indicate that the operation is in progress).
To confirm the recording of the DC side and AC side measurements acquired, place the cursor on CONFIRM MEASUREMENT and press ENTER (the text STORING MEASUREMENT... flashes to indicate that the operation is in progress).
English
printing of measurement reports and of the declaration of conformity issued at the end of the tests of the site; real-time analysis of all measurements (manual or automatic) of the PV system; graphic display of all measurements of the PV system vs. time.
3.
8.19.2.1 CONFIGURATION
By clicking on this icon, you can check the status of communication between the instrument (base unit) and the remoted module. Access to the CONFIGURATION function lets you perform the following operations: selection of the power calculation method (see the ADJUSTMENTS menu); selection of the number of DC inputs (current, voltage); selection of the number of AC inputs (current, voltage); selection of the minimum insolation for the efficiency calculation (very important if you want to perform tests with an insolation of less than 600 W/m.
2.
Page 32 sur 47
English
3.
Remote acquisition of measurements in REAL TIME from the remoted module: Connect the instrument to the PC using the USB cable. Connect a Bluetooth adapter to the PC using the RS232 cable provided. Connect the other Bluetooth adapter to the remoted module using the RS232 cable provided. Click on the "CONFIGURATION" icon. Select the COM port of the device in the pull-down menu (if the COM port number does not appear, look for it in the Windows Peripherals Manager). Click on "CONNECT THE BASE UNIT". Wait for CONNECTION STATUS to be displayed: - Green light (connection established); - Red light (no connection). Click on "CONNECTION OF REMOTE MODULE". Select REMOTE MEASUREMENT on the instrument and choose the type of measurement to be made: REMOTE WITH T pan (when you use a PT100 probe on the solar panels) or REMOTE WITHOUT T pan (if you do not use a PT100 probe for the solar panels). Press the ENTER key and wait for the OK message (if REJECTED is displayed, check the connections and repeat the procedure). Press the ESC key to exit from the menu. Click on the REAL TIME icon (see the description of the menu of that name).
8.19.2.3 "REPORT"
This icon is used to select the SITE in the data base of the instrument or on the PC and the measurements to be used to create the declaration and the system measurement sheet, along with the results of the efficiency calculation. The declaration is generated only if the result of the tests is OK. If not, only the measurement sheet is generated.
8.19.2.6 "INSTALLATIONS"
This icon is used to add a new site or to delete one from your PC's database.
Page 33 sur 47
English
Page 34 sur 47
English
Page 35 sur 47
English
AC AMMETER Use a CAT III 600 V class II clamp AC/DC POWER CALCULATION FUNCTIONS DATA RECORDER COMMUNICATION PORT INTERNAL POWER SUPPLY MAINS POWER SUPPLY
Page 36 sur 47
English
OPERATING TEMPERATURE USE MAXIMUM ALTITUDE OF OPERATION RELATIVE HUMIDITY STORAGE TEMPERATURE PROTECTION DIMENSIONS MASS
From 5 C to +40 C. The device must not be used in the rain with the cover open 2000m. 80% UP TO 40 C (LINEAR DECREASE TO 50% AT 50 C). From -10 C to +60 C. protection index IP54 (with cover closed) 360 x 30 x 194mm 3KG (WITH BATTERY)
CONNECTION OPERATING TEMPERATURE USE MAX. ALTITUDE OF OPERATION RELATIVE HUMIDITY STORAGE TEMPERATURE DIMENSIONS MASS
Page 37 sur 47
English
11.1 PROCEDURE FOR CONNECTION AND CONFIGURATION OF THE REMOTED FTV 100 MODULE
1. Connect the probes of the unit (temperature and insolation) to the corresponding inputs of the remoted module (see photograph A)
Photo A
Connect one of the Bluetooth units (a) or the RS232 connector (b) of the serial cable (if one is provided); see photograph B
(a) (b)
3. 4. 5.
Connect the GREEN TEST instrument to the other Bluetooth unit or to the RS232 connector of the serial cable (if one is provided). Power up the remoted module using the On/Off button (the LED indicators confirm the power up and the presence of a power supply provided by the batteries). Follow the instructions (see the REMOTE MEASUREMENT MENU) for activation of communication with the instrument.
Page 38 sur 47
English
Bluetooth v2.0 + EDR 2.42.4835GHz, ISM licence FHSS Class 1 100m - in free field from 0 C to +60 C. In zones protected from water and rain 2000m 90% up to 40 C from -10 C to +70 C. 76 x 62 x 20mm approximately 50g
Other characteristics according to the manufacturer's manual provided The optional Bluetooth adapters are of the highest quality, with the best characteristics and performance available on the market. Even so, some situations may induce perturbations and interfere with communication. In these situations, we suggest moving the Bluetooth adapter (connected to the instrument by a cable of sufficient length fitted with the two male/male RS232 connectors supplied with the remoted module).
Page 39 sur 47
English
13.1 PROCEDURE FOR CONNECTION AND CONFIGURATION OF THE "BLUETOOTH" OR "RS232 CABLE" COMMUNICATION KIT
1. Connect one of the two Bluetooth units or the RS232 connector (b) of the serial cable (if one is provided) to the remoted module 2. Connect one of the two Bluetooth units or the RS232 connector (b) of the serial cable (if one is provided) to the GREEN TEST unit. 3. Power up the remoted module using the On/Off button (the LED indicators confirm the power up and the presence of a power supply provided by the batteries). 4. Follow the instructions (see the REMOTE MEASUREMENT MENU) for activation of communication with the instrument. 5. Check that the blue indicator of the Bluetooth unit is lit, confirming that communication is active.
Instrument
Transmission
Remoted module
Probes
Bluetooth
RS232 cable
Page 40 sur 47
English
14. PRODUCING A CABLE USING THE RS232 CONNECTORS PROVIDED WITH THE OPTIONAL REMOTED FTV 100 MODULE
15.1 INTRODUCTION
The LP PYRA 03 pyranometer measures the insolation on a plane surface (W/m). The insolation measured is the sum of the direct solar radiation and the diffuse radiation (total radiation).
English
The LP PYRA 03 has a dome having an outside diameter of 32mm, 4mm thick, in order to ensure adequate thermal insulation of the thermopile against the effects of wind and to reduce its sensitivity to thermal radiation. The dome also protects the thermopile from dust, which could otherwise modify the spectral sensitivity by accumulating on the blackened part. To prevent the formation of condensation on the inside of the dome in certain particular climatic conditions, the pyranometer contains sachets of silica gel to absorb moisture.
Trous de fixation M 5
Page 42 sur 47
English
16. WARRANTY
The instruments we manufacture are guaranteed for twelve months against malfunctions due to defective workmanship or materials. To make a claim under the warranty, you must produce a copy of the invoice or of the receipt for the purchase of the instrument. The warranty does not apply in the following cases: - Inappropriate use of the equipment or use with incompatible equipment; - Modifications made to the equipment without the explicit permission of the manufacturers technical staff; - Work done on the device by a person not approved by the manufacturer; - Adaptation to a particular application not anticipated in the definition of the equipment or not indicated in the users manual; - Damage caused by shocks, falls, or floods. The batteries are not covered by the warranty.
Page 43 sur 47
English
17. MAINTENANCE
For maintenance, use only the specified spare parts. The manufacturer cannot be held liable for any accident that occurs following a repair done by a party other than Chauvin-Arnoux customer service or an approved repairer.
17.1 CLEANING
To ensure a highly accurate measurement, the outside of the dome must be kept clean at all times. The more often the dome is cleaned, the more accurate the measurement. The cleaning can be done using ordinary camera lens cleaning tissue and water or, if this is not sufficient, pure ethanol. After cleaning with alcohol, the dome must be rinsed with plain water.
17.3 REPAIRS
For repairs under the warranty, send your device to one of the CHAUVIN-ARNOUX-approved MANUMESURE regional agencies. Information and contact data on request: Tel.: 02 31 64 51 43 Fax: 02 31 64 51 09 For repairs outside metropolitan France, whether or not under warranty, send the device to your distributor.
Page 44 sur 47
English
18. TO ORDER
GREEN TEST FTV 100...................................................................................................................P01160700 THE instrument is provided with: A carrying case containing the instrument; 1 pyranometer for solar radiation + connecting cable; 1 Pt100 probe for the ambient temperature; 1 Pt100 probe for the temperature of the panels; 3 MN13-FTV current clamps for measurement of the alternating current; 1 PAC10-FTV current clamp for measurement of the direct current; 4 sets of 3m leads (red/black); 4 pairs of test probes (red/black); 1 4.5Ah Li-Ion battery + power supply unit; Data transfer software + USB cable; Carrying bag for the accessories; Operating manual in French and English.
MEASUREMENT KIT FOR THREE-PHASE SYSTEM .................................................................P01160710 For the measurement of 3 chains of panels, comprising: 2 PAC10-FTV current clamps for measurement of the direct current; 2 sets of 3m leads (red/black); Pairs of test probes (red/black). P01160720 The instrument is provided with: A carrying case containing the instrument; 1 pyranometer for solar radiation + connecting cable; 1 Pt100 probe for the ambient temperature; 1 Pt100 probe for the temperature of the panels; 3 MN13-FTV current clamps for measurement of the alternating current; 3 PAC10-FTV current clamp for measurement of the direct current; 6 sets of 3m leads (red/black); 6 pairs of test probes (red/black); 1 4.5Ah Li-Ion battery + power supply unit; Data transfer software + USB cable; Carrying bag for the accessories; Operating manual in French and English.
ACCESSORIES (OPTIONS) REMOTED FTV 100 MODULE + 2 male/male RS232 connectors........................... P01160736 Bluetooth communication kit (transmitter/receiver) ................................................... P01160738 Serial cable with male/male RS232 connectors ........................................................ P01160737 RS232/USB adapter.................................................................................................. HX0055
Page 45 sur 47
English
SPARE PARTS 1 pyranometer for solar radiation + connecting cable P01160730 1 Pt100 probe for the ambient temperature ........................................................... P01160731 1 Pt100 probe for the temperature of the panels ................................................... P01160732 PAC10 FTV clamp for GREEN TEST ................................................................. P01160734 MN13 FTV clamp for GREEN TEST .................................................................. P01160733 PAC20 FTV clamp .............................................................................................. P01120092 C 107 FTV clamp ................................................................................................ P01120100 D 43 FTV clamp .................................................................................................. P01120337 Li-Ion battery .......................................................................................................... P01160735 Set of 4mm test probes (R/B) ................................................................................ P01102051Z Set of 3m cords (R/B) (straight connectors)........................................................... P01295097 Set of 4mm alligator clips (R/B).............................................................................. P01102052Z
Page 46 sur 47
DEUTSCHLAND - Chauvin Arnoux GmbH Straburger Str. 34 - 77694 Kehl / Rhein Tel: (07851) 99 26-0 - Fax: (07851) 99 26-60 ESPAA - Chauvin Arnoux Ibrica S.A. C/ Roger de Flor N 293, Planta 1- 08025 Barcelona Tel: 902 20 22 26 - Fax: 934 59 14 43
SCHWEIZ - Chauvin Arnoux AG Moosacherstrasse 15 8804 AU / ZH Tel: 044 727 75 55 - Fax: 044 727 75 56 UNITED KINGDOM - Chauvin Arnoux Ltd Unit 1 Nelson Court Flagship Square-Shaw Cross Business ParkDEWSBURY West Yorkshire WF12 7THTel : 011628 788 888 Fax : 01628 628 099 MIDDLE EAST - Chauvin Arnoux Middle East P.O. BOX 60-154 - 1241 2020 JAL EL DIB (Beirut) - LEBANON Tel: (01) 89 04 25 - Fax: (01) 89 04 24 CHINA - Shanghai Pu-Jiang - Enerdis Instruments Co. Ltd 3 F, 3 rd Building - N 381 Xiang De Road - 200081 SHANGHAI Tel: +86 21 65 21 51 96 - Fax: +86 21 65 21 61 07 USA - Chauvin Arnoux Inc - d.b.a AEMC Instruments 200 Foxborough Blvd. - Foxborough - MA 02035 Tel: (508) 698-2115 - Fax: (508) 698-2118
ITALIA - Amra SpA Via SantAmbrogio, 23/25 - 20050 Bareggia di Macherio (MI) Tel: 039 245 75 45 - Fax: 039 481 561 STERREICH - Chauvin Arnoux Ges.m.b.H Slamastrasse 29/3 - 1230 Wien Tel: 01 61 61 961-0 - Fax: 01 61 61 961-61 SCANDINAVIA - CA Mtsystem AB Box 4501 - SE 18304 TBY Tel: +46 8 50 52 68 00 - Fax: +46 8 50 52 68 10
http://www.chauvin-arnoux.com
190, rue Championnet - 75876 PARIS Cedex 18 - FRANCE Tel.: +33 1 44 85 44 85 - Fax: +33 1 46 27 73 89 - [email protected] Export: Tel.: +33 1 44 85 44 86 - Fax: +33 1 46 27 95 59 - [email protected]