0% found this document useful (0 votes)
536 views138 pages

QS4 Fire Alarm Control Panel: Technical Reference Manual

est QS 4 manual

Uploaded by

amjadjaved033148
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
536 views138 pages

QS4 Fire Alarm Control Panel: Technical Reference Manual

est QS 4 manual

Uploaded by

amjadjaved033148
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 138

QS4 Fire Alarm Control Panel

Technical Reference Manual


P/N 3100186 Rev 2.0 12JUL01

Compliance Statement

The QS4, hereinafter referred to as the FACP or control panel, when properly installed, operates as a Local Protected Premises Fire Alarm System in accordance with the following standards: NFPA Standard 72, 1999 Edition Underwriters Laboratories Standard 864, 7th Edition Underwriters Laboratories of Canada Standard ULC S527

In addition, Auxiliary Fire Alarm System operation requires a Reverse Polarity Module (RPM). Central Station Fire Alarm System operation requires a Dialer card (DLD). Installation in accordance with this manual, applicable codes, and the instructions of the authority having jurisdiction is mandatory. Limitation of Liability Edwards Systems Technology (EST) shall not under any circumstances be liable for any incidental or consequential damages arising from loss of property or other damages or losses owing to the failure of EST products beyond the cost of repair or replacement of any defective products. EST reserves the right to make product improvements and changes to product specifications at any time. While every precaution was taken during the preparation of this document to ensure its accuracy, EST assumes no responsibility for errors or omissions. Fire Alarm System Limitations Automatic fire alarm systems can not guarantee against property damage, loss of property, or loss of life. An automatic fire alarm system's ability to provide early warning of a developing fire may be limited for a variety of reasons, but mainly due to improper installation or maintenance. The best way to minimize system failures is to perform regularly scheduled preventive maintenance in accordance with national and local fire codes. All system components and wiring should be tested and maintained by trained fire alarm system professionals. FCC Compliance Statement This equipment can generate and radiate radio frequency energy. If this equipment is not installed in accordance with this manual, it may cause interference to radio communications. This equipment has been tested and found to comply within the limits for Class A computing devices pursuant to Subpart B of Part 15 of the FCC Rules. These rules are designed to provide reasonable protection against such interference when this equipment is operated in a commercial environment. Operation of this equipment is likely to cause interference, in which case the user at his own expense, will be required to take whatever measures may be required to correct the interference.

Copyright 2001. All rights reserved.

Content
About this manual iii Related documentation iv Document history vi Chapter 1 Product description 1.1 System overview 1.2 Component descriptions 1.3 Circuit descriptions 1.5 Controls and indicators 1.9 Controls and indicators behind the flip-down cover 1.10 Controls and indicators on the zone annunciator card 1.11 Interpretation of screen displays 1.12 Installation 2.1 Installation do's and don'ts 2.2 Installation checklist 2.3 Two ways to install the cabinet: Surface or semi-flush mount 2.4 How to assemble the panel 2.6 Wiring mains ac and earth ground 2.7 System jumper settings 2.8 System addressing 2.10 Terminal definitions 2.14 Connecting a PT1S printer 2.22 Installing standby batteries 2.23 Operating instructions 3.1 Instructions for the Level 1 operator (public mode access) 3.2 Instructions for the Level 2 operator (emergency mode access) 3.5 Instructions for the Level 3 operator (maintenance mode access) 3.7 Instructions for the Level 4 operator (service mode access) 3.10 QuickReference list 3.11 Programming instructions 4.1 Overview 4.2 QuickStart setup instructions 4.4 Customizing the system configuration 4.13 Setting up an Output Group 4.21 Setting up a Zone 4.26 Standard applications 5.1 Notification appliance circuits 5.2 Initiating device circuits 5.5 Coded alarm signaling 5.8 Remote station protective signaling system 5.10 Auxiliary protective signaling 5.12 Maintenance instructions 6.1 Pseudo point definitions 6.2 Maintenance tasks 6.6

Chapter 2

Chapter 3

Chapter 4

Chapter 5

Chapter 6

QS4 Technical Reference Manual

Content Appendix A System calculations A.1 Notification appliance circuit maximum wire length calculation A.2 Signature loop maximum wire length calculations A.3 Battery calculation worksheet A.8 Barcode library B.1 SIGA-REL programming C.1 Application block diagram C.2 Programming instructions C.3

Appendix B Appendix C

ii

QS4 Technical Reference Manual

Content

About this manual


Organization This manual provides information on how to properly install, wire, and maintain the FACP and related components, and is organized as follows: Chapter 1 provides a detailed description of the fire alarm control panel and its operation. Chapter 2 provides instructions for installing the fire alarm control panel. Chapter 3 provides instructions for operating the control panel. Chapter 4 provides instructions for programming the fire alarm system from the front panel. Chapter 5 provides simplified wiring schematics for standard applications. Chapter 6 provides instructions for maintaining the system. Appendix A provides worksheets for calculating maximum wire lengths for notification and Signature circuits, and for sizing standby batteries. Appendix B provides a set of bar codes that you can use to enter text for location messages. Appendix C provides information on how to program the SIGAREL using the QSCU (QuickStart Configuration Utility). Safety information Important safety admonishments are used throughout this manual to warn of possible hazards to persons or equipment. WARNING: Warnings are used to indicate the presence of a hazard which will or may cause personal injury or death, or loss of service if safety instructions are not followed or if the hazard is not avoided.

Caution: Cautions are used to indicate the presence of a hazard which will or may cause damage to the equipment if safety instructions are not followed or if the hazard is not avoided.

QS4 Technical Reference Manual

iii

Content

Related documentation
National Fire Protection Association 1 Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9101 NFPA 70 National Electric Code NFPA 72 National Fire Alarm Code NFPA 11 Low-Expansion Foam Systems NFPA 11A Medium- and High-Expansion Foam Systems NFPA 12 Carbon Dioxide Extinguishing Systems NFPA 13 Sprinkler Systems NFPA 15 Water Spray Fixed Systems for Fire Protection NFPA 16 Deluge Foam-Water Sprinkler and Foam-Water Spray Systems NFPA 17Dry Chemical Extinguishing Systems Underwriters Laboratories, Inc. 333 Pfingsten Road Northbrook, IL 60062-2096 UL 38 Manually Actuated Signaling Boxes UL 217 Smoke Detectors, Single & Multiple Station UL 228 Door Closers/Holders for Fire Protective Signaling Systems UL 268 Smoke Detectors for Fire Protective Signaling Systems UL 268A Smoke Detectors for Duct Applications UL 346 Waterflow Indicators for Fire Protective Signaling Systems UL 464 Audible Signaling Appliances UL 521 Heat Detectors for Fire Protective Signaling Systems UL 864 Standard for Control Units for Fire Protective Signaling Systems UL 1481 Power Supplies for Fire Protective Signaling Systems UL 1638 Visual Signaling Appliances UL 1971 Visual Signaling Appliances Underwriters Laboratories of Canada
7 Crouse Road Scarborough, ON Canada M1R 3A9

Canadian Electrical Code Part 1 ULC S527 Standard for Control Units for Fire Alarm Systems ULC S524 Standard for the Installation of Fire Alarm Systems ULC S536 Standard for the Inspection and Testing of Fire Alarm Systems ULC S537 Standard for the Verification of Fire Alarm Systems ULC ORDC6931994 Central Station Fire Protective Signaling System and Services

iv

QS4 Technical Reference Manual

Content

Edwards Systems Technology 6411 Parkland Drive Sarasota, FL 34243

2CTM City Tie Module Installation Sheet (P/N 270496) CDR3 Bell Coder Installation Sheet (P/N 3100023) DLD Dual Inline Dialer Installation Sheet (P/N 3100187) PS6 Power Supply Card Installation Sheet (P/N 3100201) QSA1(X), QSA2(X) Remote Annunciator Cabinet Installation Sheet (P/N 3100295) QSCPU(X) CPU/Display Unit Installation Sheet (P/N 3100276) SL30, SL301 LED/Switch Card Installation Sheet (P/N 3100193) SLIC Signature Intelligent Controller Card Installation Sheet (P/N 3100192) RS485 (NTA) Card and QS232 UART Module Installation Sheet (P/N 3100191) ZA82 Class A Zone Card Installation Sheet (P/N 3100189) ZB164 Class B Zone Card Installation Sheet (P/N 3100188) ZR8 Relay Card Installation Sheet (P/N 3100190) SIGAAPS Auxiliary Power Supply Installation Sheet (P/N 387342) Signature Series Intelligent Smoke and Heat Detectors Applications Bulletin (P/N 270145) Signature Series Component Installation Manual (P/N 270497) EST Strobe Applications Guide (P/N 85000-0049) QuickStart Online Help Utility (P/N 7350047) QuickStart ULI and ULC Compatibility Lists (P/N 3100335) Network Hardware Technical Reference (P/N 250100)

QS4 Technical Reference Manual

Content

Document history
Date 24JUN01 12JUL01 Revision 1.0 2.0 Description of changes Original release. Corrections and additions on pp 2.12, 2.24, 3.9, 4.4, 4.8, 4.10, 4.19, A.3.

vi

QS4 Technical Reference Manual

Chapter 1

Product description

Summary This chapter provides a detailed description of the fire alarm control panel and its operation. Content System overview 1.2 Component descriptions 1.3 Circuit descriptions 1.5 Controls and indicators 1.9 Controls and indicators behind the flip-down cover 1.10 Controls and indicators on the zone annunciator card 1.11 Interpretation of screen displays 1.12

QS4 Technical Reference Manual

1.1

Product description

System overview
System hardware capabilities Hardware capabilities vary depending on cabinet size and option card configuration, but generally: Up to four Class A or Class B Signature signaling line circuits that support up to 250 single-address Signature devices each Up to 40 Class A or 48 Class B initiating device circuits (IDC). Combination systems can not exceed 40 IDC circuits total Up to 16 Class A or 20 Class B notification appliance Up to two 30-zone displays Up to 96 dry-contact relay 4.5 amps of 24 Vdc power for external notification appliances Battery charger capable of charging batteries rated up to 40 Ah. Maximum battery size for ULC applications is 30 Ah Up to eight, fully-supervised, mirrored or customized remote annunciators monitor events. In normal mode, the control panel monitors the system for any events. Off-normal operating mode description The panel operates in off-normal mode any time there is an event introduced into the system. When this happens, the CPU: Changes the contact positions on the appropriate common relays Activates all common alarm outputs (alarm events only) Turns on the panel buzzer Executes the appropriate programmed output response for the input that signaled the event Sends a record of the event to the appropriate display queue and out the serial port If there is no operator in attendance, the panel displays the content of the highest priority display queue containing a record. If there is an operator in attendance, the panel displays the content of the current display queue regardless of any new events introduced into the system. Failsafe operating mode description The panel operates in failsafe mode when the CPU loses the ability to communicate with the PS6 and JP1 on the PS6 is in the ON position. When this happens, the power supply: Closes the common trouble relay contacts Instructs the dialer to send the default trouble message Monitors the system for any alarm events If an alarm event occurs, the power supply: Changes the contact positions on the common alarm relay Turns on all conventional common alarm outputs. Signature common alarm outputs are not affected. Instructs the dialer to send the default alarm message

Minimum system requirements A Local Protected Premises Fire Alarm System requires only the FACP (CPU, PS6, and enclosure) with at least one SLIC, ZB164, or ZA82 card programmed with at least one audible output circuit and one alarm input circuit. In addition to the hardware requirements of a Local system: Add a 2CTM City Tie Module for an Auxiliary Fire Alarm System Add a DLD Dual Line Dialer Card or RPM Reverse Polarity Module for a Remote Supervising Station Fire Alarm System Add a DLD Dual Line Dialer Card or RPM Reverse Polarity Module for a Central Station Fire Alarm System Add a SIGAREL for Releasing Device Service

Normal operating mode description The panel operates in normal mode in the absence of any alarm, supervisory, trouble, and

1.2

QS4 Technical Reference Manual

Product description

Component descriptions
1 2 3
6A

6B

J6

J5

J7 J8

JP1 CONFIG U RATION PIN 1 & 2 = MODEM PWR PIN 2 & 3 = R TS

JP1 3 1 J2

10

15

14

13

12

11

1. Cabinet enclosure: Houses the panel electronics and standby batteries. 2. SL301 LED/Switch Card: Provides thirty circuits for point or zone annunciation. Each circuit has two LEDs for annunciating alarm, supervisory, and trouble signals, and a button numbered from 31 to 60. 3. SL30 LED/Switch Card: Same as SL301 except the buttons are numbered 130.

4. CPU/Display: Provides operator access to system messages, status information, and programming menus, and executes system responses based on the panel programming. 5. PS6 Power Supply Card: Provides primary dc power to the panel electronics and external circuits. The PS6 also provides common alarm, supervisory and trouble relays for remote station supervision.

QS4 Technical Reference Manual

1.3

Product description

6. RS485 (NTA) Class A Card: The NTA comprises the RS485 card and QS232 UART module. Together these provide an additional RS232 channel to allow Class A communication between the control panel and other remote annunciator panels. Control panels require installation of both cards while remote annunciator panels only require installation of a QS232 card and only then if you want to connect a printer or service computer. 7. ZA82 Class A Conventional Zone Card: Provides six dedicated Class A initiating device circuits (IDCs) for connecting two-wire smoke detectors and dry-contact initiating devices. The ZA82 also provides two circuits that you can configure as IDCs or as 24 Vdc notification appliance circuits (NACs). 8. ZB164 Class B Conventional Zone Card: Provides twelve dedicated Class B initiating device circuits (IDCs) for connecting two-wire smoke detectors and dry-contact initiating devices. The ZB164 also provides four circuits that you can configure as IDCs or as Class B 24 Vdc notification appliance circuits (NACs). 9. QSCable12 Expansion Cable: Extends the CPU data and power bus to circuit cards installed on the lower DIN rail in the 12-option cabinet.

10. ZR8 Relay Card: Provides eight dry-contact relays. You can configure each relay for normally-open or normally-closed operation. 11. DLD Dual Line Dialer Card: Provides two telephone line connections for sending system messages to a compatible Digital Alarm Communicator Receiver. 12. SLIC Signature Loop Intelligent Controller Card: Provides one Class A or Class B signaling line circuit (loop) for connecting Signature series detectors and modules. The SLIC also provides two Class A or Class B notification appliance circuits (NACs) for connecting polarized 24 Vdc notification appliances (horns, strobes). 13. Standby batteries: Provides dc power to the panel electronics in the absence of ac power. 14. Transformer: Changes the mains ac supply voltage for the power supply card. 15. AC wiring block and fuse holder: Provides connections for mains ac (primary power) and 5A fuse.

1.4

QS4 Technical Reference Manual

Product description

Circuit descriptions
PS6 Power Supply Card 1. Relay 1 (Common Alarm) Style: Form C Contact rating: 1 A @ 20.4 26.4 Vdc (0.6 PF) Wire size: 18 to 12 AWG (0.75 to 2.5 mm) Nonsupervised and power-limited only when connected to a power-limited source 2. Relay 2 (Common Supervisory) Style: Normally-open Contact rating: 1 A @ 20.4 26.4 Vdc (0.6 PF) Wire size: 18 to 12 AWG (0.75 to 2.5 mm) Nonsupervised and power-limited only when connected to a power-limited source 3. Relay 3 (Common Trouble) Style: Normally-open, held closed Contact rating: 1 A @ 20.4 26.4 Vdc (0.6 PF) Wire size: 18 to 12 AWG (0.75 to 2.5 mm) Nonsupervised and power-limited only when connected to a power-limited source 4. Relay 4 (Programmable) Style: Normally-open Contact rating: 1 A @ 20.4 26.4 Vdc (0.6 PF) Wire size: 18 to 12 AWG (0.75 to 2.5 mm) Nonsupervised and power-limited only when connected to a power-limited source 5. Smoke/Accessory Power Output: Continuous or interruptible via jumper selection Voltage: 24 Vdc, regulated Current: 250 mA Wire size: 18 to 12 AWG (0.75 to 2.5 mm) Supervised and power-limited 6. RS485 Wire size: 18 to 12 AWG (0.75 to 2.5 mm) Wire type: Twisted pair, six twists per foot minimum Circuit capacitance: 0.4 F Circuit resistance: 100 Supervised and power-limited 7. RS232 Wire size: 18 to 12 AWG (0.75 to 2.5 mm) Nonsupervised and power-limited Wire length: 20 ft maximimum 8. AUX Power #1, #2, and #3 Voltage: 17.5 26.4 Vdc FWR (full wave rectified) Current: 1.5 A each Wire size: 18 to 12 AWG (0.75 to 2.5 mm) Power-limited and supervised for short circuit conditions only 9. Battery Circuit Charge current: 2 A Charge capacity: 40 Ah (UL), 30 Ah (ULC) Supervised and nonpower-limited
8

2 1

6 7

QS4 Technical Reference Manual

1.5

Product description

SLIC Signature Loop Intelligent Controller Card circuits


1. NAC #1 Configuration: Class B or Class A Output voltage: 24 Vdc, nominal Output current: 2.0 A @ 24 Vdc 2 Wire size: 18 to 12 AWG (0.75 to 2.5 mm ) End of line resistor: 10 k, 1/2W Supervised and power-limited 2. NAC #2 Configuration: Class B or Class A Output voltage: 24 Vdc, nominal Output current: 1.0 A @ 24 Vdc 2 Wire size: 18 to 12 AWG (0.75 to 2.5 mm ) End of line resistor: 10 k, 1/2W Supervised and power-limited 3. Signature Loop Configuration: Class B (Style 4) or Class A (Style 6) Capacity: 125 Signature detectors, 125 Signature single-address modules 2 Wire size: 18 to 12 AWG (0.75 to 2.5 mm ) Circuit resistance: 65 Circuit capacitance: 0.3 F Supervised and power-limited 4. NAC Riser In/Out Voltage: 24 Vdc, nominal 2 Wire size: 18 to 12 AWG (0.75 to 2.5 mm )

ZR8 Relay Card circuits


1. Dry-contact relays R1 R4 Outputs: Normally-open or normally-closed contacts via jumper selection Contact rating: 24 Vdc @ 1.0 A 2 Wire size: 18 to 12 AWG (0.75 to 2.5 mm ) Nonsupervised, and power-limited only when connected to a power-limited source 2. Dry-contact relays R5 R8 Outputs: Normally-open or normally-closed contacts via jumper selection Contact rating: 24 Vdc @ 1.0 A 2 Wire size: 18 to 12 AWG (0.75 to 2.5 mm ) Nonsupervised, and power-limited only when connected to a power-limited source

1.6

QS4 Technical Reference Manual

Product description

ZB164 Class B Conventional Zone Card circuits


1. IDC Circuits Z1 Z12 Wiring configuration: Class B Detector voltage: 20.33 24.76 Vdc, max ripple 2000 mV Short circuit current: 75.9 mA, max. Resistance: 50 , max. Capacitance: 100 F, max 2 Wire size: 18 to 12 AWG (0.75 to 2.5 mm ) End of line resistor: 4.7 k, 1/2W Supervised and power-limited 2. NAC Circuits Z13 Z16 Wiring configuration: Class B Output voltage: 24 Vdc, nominal Output current: 2.0 A @ 24 Vdc 2 Wire size: 18 to 12 AWG (0.75 to 2.5 mm ) End of line resistor: 10 k, 1/2W Supervised and power-limited IDC specifications apply when programmed as IDC circuit 3. R1 Voltage: 24 Vdc, nominal 2 Wire size: 18 to 12 AWG (0.75 to 2.5 mm ) 4. R2 Voltage: 24 Vdc, nominal 2 Wire size: 18 to 12 AWG (0.75 to 2.5 mm )

2 1 3 4

ZA82 Class A Conventional Zone Card circuits


1. IDC Circuits Zone 1 Zone 3, Zone 5 Zone 7 Wiring configuration: Class A Detector voltage: 19.90 22.46 Vdc, max ripple 2000 mV Short circuit current: 75.9 mA, max. Resistance: 50 , max. Capacitance: 100 F, max 2 Wire size: 18 to 12 AWG (0.75 to 2.5 mm ) End of line resistor: 4.7 k, 1/2W Supervised and power-limited 2. NAC Circuits Zone 4, Zone 8 Wiring configuration: Class A Output voltage: 24 Vdc, nominal Output current: 2.0 A, 24 Vdc 2 Wire size: 18 to 12 AWG (0.75 to 2.5 mm ) End of line resistor: 10 k, 1/2W Supervised and power-limited IDC specifications apply when programmed as IDC circuit 3. NAC PWR IN (Zone 4) Voltage: 24 Vdc, nominal 2 Wire size: 18 to 12 AWG (0.75 to 2.5 mm ) 4. NAC PWR IN (Zone 8) Voltage: 24 Vdc, nominal 2 Wire size: 18 to 12 AWG (0.75 to 2.5 mm )

3 2

2 1 4

QS4 Technical Reference Manual

1.7

Product description

DLD Dual Line Dialer Card circuits


1. Line #1 Supervised and nonpower-limited 2. Line #2 Supervised and nonpower-limited

RS485 (NTA) Class A Card circuits


1. Secondary RS485 channel 2 Wire size: 18 to 12 AWG (0.75 to 2.5 mm ) Supervised and power-limited 2. Primary RS485 channel 2 Wire size: 18 to 12 AWG (0.75 to 2.5 mm ) Supervised and power-limited Note: JP1 installed for ground fault detection on RS485 circuits.

1.8

QS4 Technical Reference Manual

Product description

Controls and indicators


1 2 3 4 5 6 7 8 9

1 2 3 4 5

6 7 8 9 10

11 12 13 14 15

16 17 18 19 20

21 22 23 24 25

26 27 28 29 30

1 2 3 4 5

6 7 8 9 10

11 12 13 14 15

16 17 18 19 20

21 22 23 24 25

26 27 28 29 30

12

11

10

1. Text display and controls: Displays system messages, status information, programming menus. Moves the cursor up one line at a time or to the previous record in the display queue Moves the cursor down one line at a time or to the next record in the display queue Moves the cursor right one character at a time or to the next display queue Moves the cursor left one character at a time or to the previous display queue Enters operator input and selects menu items 2. Alarm LED: Indicates the panel posted an alarm event record into the corresponding display queue. 3. Supervisory LED: Indicates the panel posted a supervisory event record into the corresponding display queue. 4. Disable/Test LED: Indicates part of the system is disabled or is currently under test. Disabled components also signal a system trouble.

5. Monitor LED: Indicates the panel posted a monitor event record into the corresponding display queue. 6. Trouble LED: Indicates the panel posted a trouble event record into the corresponding display queue. 7. Ground Fault LED: Indicates a ground fault in the system wiring. Ground faults also signal a system trouble. 8. CPU Fail LED: Indicates an unexpected reboot or failure with the microprocessor. CPU failures also signal a system trouble. 9. Power LED: Indicates the panel has ac power. 10. Panel Silence/Acknowledge button/LED: Turns off the panel buzzer and acknowledges all events. The Panel Silenced LED indicates that all off normal events have been acknowledged and the internal buzzer is off. 11. Status button: Displays the Status menu from which you can identify active or disabled points in the system. 12. Help button: Provides additional information for the event record selected on the display.

QS4 Technical Reference Manual

1.9

Product description

Controls and indicators behind the flip-down cover

1 2 3 4 5

6 7 8 9 10

11 12 13 14 15

16 17 18 19 20

21 22 23 24 25

26 27 28 29 30

1 2 3 4 5

6 7 8 9 10

11 12 13 14 15

16 17 18 19 20

21 22 23 24 25

26 27 28 29 30

7 4

8 5

9 6
1 2 3 4 5 6 7 8 9 0

1. Enable Controls key switch: Gives priority access to control functions reserved for operators with Level 2 access. 2. Barcode scanner jack: Input point for optional barcode scanner. 3. Numeric keypad: Numbered buttons for entering data and selecting menu options. 4. Reset button: Restores devices or zones in alarm or trouble to their standby condition. The LED indicates when the panel is resetting. 5. Alarm Silence button: Turns active notification appliances off according to the panel programming. Pressing Alarm Silence a second time turns them back on. The LED indicates when the panel is in alarm and operating with notification appliances turned off.

6. Drill button: Turns notification appliances on according to the panel programming but does not place the panel in alarm. The LED indicates when the panel is in Drill mode. 7. Menu button: Displays the operator menus. 8. Delete button: Returns to the previous menu or back spaces the cursor. 9. Enter button: Press the Enter button to accept information from the operator or continue to the next item.

1.10

QS4 Technical Reference Manual

Product description

Controls and indicators on the zone annunciator card


1 2 3

1 2 3 4 5

6 7 8 9 10

11 12 13 14 15

16 17 18 19 20

21 22 23 24 25

26 27 28 29 30

1. Zone display button: Displays an event record for each device in the corresponding zone that signaled an alarm. 2. Zone active LED: Indicates a device in the corresponding zone signaled an alarm condition. 3. Zone trouble LED: Indicates a device or wiring fault in the corresponding Zone.

Note: ULC requires that every fire panel have the capability to visually display system status by means of specific indicators for each zone. All status changes must clearly indicate that the information is an Alarm (ALM), Supervisory (SUP), Trouble (TBL), or Monitor (MON).

QS4 Technical Reference Manual

1.11

Product description

Interpretation of screen displays


HH:MM:SS MM/DD
This is what the panel display looks like when there are no event records posted in a display queue. HH:MM:SS is the current time in hours, minutes, and seconds MM/DD is the current month and date nnnn is the number times the panel went into alarm since being placed into service

System Normal Project Name Alarm History: nnnn

HH:MM:SS Axxx Dxxx nnn event name Custom message 1 Custom message 2 nnn event name Custom message 1 Custom message 2 ALM SUP TRBL MON aaa sss ttt mmm

This is what the panel display looks like when there are event records posted in a display queue. HH:MM:SS is the current time in hours, minutes, and seconds Axxx is the current number of active points Dxxx is the current number of disabled points These items comprise the event record: nnn is the posting sequence number (001 = first, 002 = second, and so on) event name is the event produced when the device changed states. Refer to Table 1-1. P:pp C:cc D:ddd is the address of the device that signaled the event (P = panel number, C = card number, D = device number) The event record may also include a custom message that typically indicates the location of the device, depending on the panel programming. These items indicate the content of the display queues: aaa is the number of alarm event records (highest priority) sss is the number of supervisory event records ttt is the number of trouble event records mmm is the number of monitor event records (lowest priority)

1.12

QS4 Technical Reference Manual

Product description Table 1-1: Event descriptions


Event name
ALARM ACTIVE ALARM VERIFY AND GROUP BAD PRSONATY BAD TYPE COMM FAULT DEV COMPATIB DIRTY HEAD DISAB SOUND DISABLED GROUND FAULT HEAT ALARM INTERNAL TBL LCL MONITOR LCL TROUBLE MAINT ALERT MATRIX GROUP MONITOR OBJECT RUN PREALARM PULL STATION SERVICE GROUP SUPERVISORY SWITCH TAMPER TEST TIME CONTROL TROUBLE TROUBLE OPEN TROUBLE SHORT UNEXPECT DEV WATERFLOW ZONE ALARM ZONE MONITOR ZONE SUPER

Event type
Alarm Monitor Alarm Trouble Trouble Trouble Trouble Trouble Trouble Trouble Trouble Alarm Trouble Monitor Trouble Monitor Alarm Monitor Monitor Monitor Alarm Trouble Supervisory Monitor Supervisory Trouble Monitor Trouble Trouble Trouble Trouble Alarm Alarm Monitor Supervisory

Description
Smoke detector active Alarm active. Performing auto reset. And group active SIGA personality mismatch SIGA type mismatch Communication failure SIGA compatibility fault Dirty smoke detector. No compensation remaining Sounder is disabled (EN54 only) Device is disabled Ground fault Heat detector active Internal system trouble Common monitor Generic trouble. Dirty smoke detector. Some compensation remaining Matrix group active Active non-latching input circuit. Service group is enabled and governing all defined objects Possible fire condition exists. Manual fire alarm box active Service group active A device used to monitor a component of the fire suppression system is active Operator presses switch on LED/Switch card Sprinkler tamper active A member of a Service group under test is activated Time control active Common trouble Open detected on a supervised output device's field wiring Short detected on a supervised output device's field wiring Signature device not defined in database Water flowing through the sprinkler system Alarm zone active Monitor zone active Supervisory zone active

QS4 Technical Reference Manual

1.13

Product description

1.14

QS4 Technical Reference Manual

Chapter 2

Installation

Summary This chapter provides instructions for installing the fire alarm control panel. Content Installation do's and don'ts 2.2 Installation checklist 2.3 Two ways to install the cabinet: Surface or semi-flush mount 2.4 How to assemble the panel 2.6 Wiring mains ac and earth ground 2.7 System jumper settings 2.8 System addressing 2.10 Terminal definitions 2.14 Connecting a PT1S printer 2.22 Installing standby batteries 2.23 Connecting a service computer 2.24

QS4 Technical Reference Manual

2.1

Installation

Installation do's and don'ts


When installing cabinets... DO use fasteners that can support the full weight of the cabinet and standby batteries. Tighten firmly to avoid vibrations. DO NOT drill inside the cabinet with circuit cards installed. Remove all metal filings before installing the circuit cards. DO NOT recess the cabinet into the wall deeper than 211/16 inches (68.2 mm) from the finished wall surface to allow room for the trim kit. When installing circuit boards... DO ground yourself with an approved static-protective wrist strap when handling circuit boards. DO keep circuit boards in their protective antistatic packaging. Remove only for inspection or installation. DO NOT touch component leads and connector pins when handling circuit boards. DO disconnect ac power and batteries before installing or removing circuit boards. Installing or removing circuit boards while the control panel is energized may damage the equipment. When installing circuit wiring... DO use appropriately sized wire for the application. Incorrectly-sized wires degrade circuit performance. DO make sure there are no wire-to-ground shorts or wire-towire shorts before connecting field wires to the panel. DO NOT over tighten screw terminals. Over tightening may strip screw terminal threads and cause loose connections. When installing Signature loops... DO NOT install more than fifteen SIGAUMs or MABs configured for two-wire smoke detectors on a loop. DO NOT install more than seven SIGAUMs or MABs configured for two-wire smoke detectors on loops with isolator devices. DO NOT install more than ten SIGARELs on a loop. You must use the QuickStart configuration utility to program a SIGAREL. Refer to the technical manual supplied with the SIGAREL and appendix C of this manual for programming information. When installing standby batteries... DO NOT install standby batteries until after you completely install and test the system.

2.2

QS4 Technical Reference Manual

Installation

Installation checklist
Prepare the site Make sure the installation location is free from construction dust and debris, and immune to extreme temperature ranges and humidity. Allow enough floor and wall space so the panel can be installed and serviced without obstructions. Pull and tag all field wiring. See Appendix A for wire length calculations. Unpack the equipment Open the shipping container and carefully unpack the equipment. Check for any visible signs of damage. If there is any damage, return the equipment to the place of purchase. Keep the container and packing material until after completely installing and testing the equipment. Use the shipping container to return the equipment to the manufacturer. Verify the shipping container contains the correct parts. If any parts are missing or damaged, return the equipment to the manufacturer. Install the cabinet Assemble the panel Wire mains ac and earth ground Bring the primary power conductors into the left side (nonpower-limited area) of the cabinet and wire to the ac terminal block. WARNING: Make sure that the circuit breaker providing ac power is switched off before connecting wires to the terminal block. Connect the field wiring Bring the field wiring into the power-limited area of the cabinet. Verify there are no open or shorts then connect the wires to their respective terminals. Refer to chapter 4. See Figure 2-1 for cabinet dimensions.

Use the AutoLearn and AutoLoop utilities to configure the system Customize the system configuration Install the standby batteries

Refer to chapter 4. Do not connect standby batteries to the panel until after completely testing the panel.

QS4 Technical Reference Manual

2.3

Installation

Two ways to install the cabinet: Surface or semi-flush mount


Surface mount instructions 1. Position the cabinet on the finished wall surface. 2. Fasten the cabinet to the wall surface where indicated. Tighten firmly.
4-7/8 in (123.8 mm)

Semi-flush mount instructions 1. Frame the interior wall as required to support the full weight of the cabinet and standby batteries. 2. Fasten the cabinet to the framing studs where indicated. Tighten firmly.

2-11/16 in (68.2 mm) 2-3/16 in (55.6 mm)

2.4

QS4 Technical Reference Manual

Installation

D3

D4

D1

D5

D2

Dimensions D1 5-option cabinet 12-option cabinet 18 in (45.72 cm) 30 in (76.2 cm) D2 18-5/8 in (47.31 cm) 18-5/8 in (47.31 cm) D3 4-7/8 in (12.38 cm) 4-7/8 in (12.38 cm) D4 16-5/8 in (42.23 cm) 16-5/8 in (42.23 cm) D5 13 in (33.00 cm) 25 in (63.50 cm)

Note: Add 1-1/2 in (3.81 cm) to D1 and D2 dimensions for trim kit.

Figure 2-1: Dimensions for 5-option and 12-option cabinets (arrows show mounting hole locations)

QS4 Technical Reference Manual

2.5

Installation

How to assemble the panel


Circuit card instructions 1. Lock the PS6 onto the DIN rail and configure jumpers. 2. Attach the ground wire to the cabinet. Tighten the lock nut firmly to ensure a good mechanical and electrical connection. 3. Plug the transformer into the PS6. 4. Install remaining option cards according to their respective installation sheets. Use a QSCable12 to connect option cards on the top and bottom DIN rails in a 12-option cabinet.

Door mounting instructions 1. Bolt the door to the cabinet back box. 2. Attach one end of the ground strap to the door and the other to the back box. 3. Screw the CPU/Display unit to the cabinet door. 4. Plug one end of the ribbon cable into the CPU/Display and the other end into the PS6. 5. Screw the key switch ground wire and the CPU cover to the cabinet door.

*Actual cabinet door not shown

2.6

QS4 Technical Reference Manual

Installation

Wiring mains ac and earth ground

H (L1)

G (E)

N (L2)

CAUTION: The middle connection on the ac terminal block makes a mechanical connection to chassis (earth) ground. Do not allow the ac hot and neutral conductors to make contact with the middle connector on the ac terminal block.

Wiring instructions 1. Bring the mains ac conductors into the cabinet through the 3/41/2 inch combination knock-outs on the left side or upper left corner of the cabinet. 2. Wire the hot (H, L1), neutral (N, L2), and ground (G, E) conductors to the ac terminal block as shown. 3. Insert tabbed end of terminal block cover (deadfront) into the slot provided on the side of the cabinet.

Notes Keep power-limited wires in the shaded area and nonpower-limited wires in the nonshaded area. Maintain a 1/4-inch separation between the mains ac and battery wires (power-limited) and and all other nonpower-limited wiring at all times.

QS4 Technical Reference Manual

2.7

Installation

System jumper settings


PS6 Power Supply Card jumpers JP2 configures the Smoke/Accessory power output for constant or resettable 24 Vdc. Set JP2 to ACC PWR to provide constant 24 Vdc for external equipment. Set JP2 to SMK PWR to provide resettable 24 Vdc for four-wire smoke detectors

JP2 ACC PWR SMK PWR

JP1 configures the panel for failsafe operation. Failsafe allows the system to generate output responses even when the CPU loses communication with the power supply card. Set JP1 to ON to turn failsafe mode on Set JP1 to OFF to turn failsafe mode off
JP1 ON OFF

SLIC Signature Loop Intelligent Controller Card jumpers JP1 and JP2 selects the signal that the SLIC uses for the notification appliances connected to NAC1.
Note: NAC 2 always uses the external signal
JP1 JP2 EXT INT

connected to TB23 and TB24. Set JP1 and JP2 to INT to use the 24 Vdc that comes from the PS6 over the bus connection. Set JP1 and JP2 to EXT to use the 24 Vdc that comes from an external source connected to TB23 and TB24.

CAUTION: Do not set JP1 and JP2 to EXT if strobes are connected to NAC 1 and a coded signal is connected to TB23 and TB24.

2.8

QS4 Technical Reference Manual

Installation

ZR8 Relay Card jumpers JP1 JP8 configure which relay contacts are present on the terminal connections for R1 R8, respectively. The normal operating state of the relay (on or off when the panel is normal) determines whether the terminal connections are normally-open or normally-closed. The figure to the right shows the relay contact positions when the relay is turned off.
R4+ R4

JP4

RS485 (NTA) Class A Card jumpers JP1 configures ground fault supervision for Class A remote annunciators. Set a shorting plug across JP11 and JP12 when the PS6 powers the remote annunciator and provides ground fault supervision Set a shorting plug across JP12 and JP13 when an external supply powers the remote annunciator and provides ground fault supervision
1 2 3 JP1

QS4 Technical Reference Manual

2.9

Installation

System addressing
Card addresses Each option card installed in the panel is assigned a unique card address. Only the SLIC, ZB168, ZA82, and ZR8 have card addresses that you can set. The CPU, DLD and PS6 card addresses are fixed. 00: Reserved for the CPU 0107: Used for the SLIC, ZB168, ZA82, and ZR8 0813: Used for the ZB168, ZA82, and ZR8 14: Reserved for the DLD 15: Reserved for the PS6
1 2 3 4
ON ON ON

= 01
1 2 3 4
ON

= 08
1 2 3 4
ON

= 02
1 2 3 4
ON

= 09
1 2 3 4
ON

= 03
1 2 3 4
ON

= 10
1 2 3 4
ON

= 04
1 2 3 4
ON

= 11
1 2 3 4
ON

= 05
1 2 3 4
ON

= 12

= 06
1 2 3 4
ON

= 13
1 2 3 4

= 07
1 2 3 4

Tip: When you install the option cards, set the card addresses in consecutive order as you move away from the power supply starting at address 01.

01

02

03

04

07

06

05

2.10

QS4 Technical Reference Manual

Installation

SLIC Signature Loop Intelligent Controller Card device addresses The device address format is PPCCDDD, where: PP is the panel number (01) CC is the card number (any number between 1 and 7 depending on the setting of SW1) DDD is the device or circuit number, where: 001125 are Signature automatic detectors and SIGAIM isolator modules 126250 are Signature modules 270 is the NAC 1 output circuit 271 is the NAC 2 output circuit

PPCC270 PPCC271

PPCC001 to PPCC125

PPCC126 to PPCC250

Note: Some Signature modules use two or more device addresses.

ZR8 Relay Card device addresses The device address format is PPCCDDD, where: PP is the panel number (01) CC is the card number (any number between 1 and 13 depending on the setting of SW1) DDD is the device number, where 001 008 are relays 1 8, respectively

PPCC002 PPCC001

PPCC003 PPCC004

PPCC006 PPCC005

PPCC007 PPCC008

QS4 Technical Reference Manual

2.11

Installation

ZB164 Class B Conventional Zone Card device addresses The device address format is PPCCDDD, where: PP is the panel number (01) CC is the card number (any number between 1 and 13 depending on the setting of SW1) DDD is the circuit number, where: 001 012 are IDC circuits Z1 Z12, respectively 013 016 are NAC circuits Z13 Z16, respectively

PPCC005 PPCC004 PPCC003 PPCC002 PPCC001

PPCC006 PPCC007 PPCC008 PPCC009

Note: NAC circuits Z13 Z16 can also be programmed as IDC circuits.

PPCC012 PPCC011 PPCC010

PPCC013 PPCC014 PPCC015 PPCC016

ZA82 Class A Conventional Zone Card device addresses The device address format is PPCCDDD, where: PP is the panel number (01) CC is the card number (any number between 1 and 13 depending on the setting of SW1) DDD is the circuit number, where: 001 003 and 005 007 are IDC circuits Zone 1 Zone 3 and Zone 5 Zone 7, respectively 004 and 008 are NAC circuits Zone 4 and Zone 8, respectively

PPCC002 PPCC001

PPCC003 PPCC004

Note: NAC circuits Zone 4 and Zone 8 can also be programmed as IDC circuits.

PPCC006 PPCC005

PPCC007 PPCC008

2.12

QS4 Technical Reference Manual

Installation

SL30 (1) LED/Switch Card device addresses The device address format is GGSS for switches and GGSSL for LEDs, where: GG is the group number (01 for SL30, 02 for SL301) SS is the switch number L is the LED number, where: 1 is the red Alarm LED 2 is the yellow Active LED 3 is the yellow Trouble LED

GG011, GG012 GG013

GG01

06-10 11-15 16-20 21-25 26-30

11

16

21

26

GG02

12

17

22

27

GG03

13

18

23

28

GG04

14

19

24

29

GG05

10

15

20

25

30

SL30
01-05 06-10 11-15 16-20 21-25 26-30

GG01

31

36

41

46

51

56

GG02

32

37

42

47

52

57

GG03

33

38

43

48

53

58

GG04

34

39

44

49

54

59

GG05

35

40

45

50

55

60

SL301

QS4 Technical Reference Manual

2.13

Installation

Terminal definitions
Table 2-1: PS6 Power Supply card terminal definitions
SMOKE RELAY 1 RELAY 2 RELAY 3 RELAY 4 ACC PWR RS485 RS232 RTS TX RX COM NO C NC C NO C NO C NO N.C. + + TB1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

BATT PWR +

NC TB2

AUX POWER AUX1 AUX2 COM AUX3 COM TB3


1 2 3 4 5

Terminal No. TB11, 2

Name Relay 1 NO, C

Description Normally-open relay contacts that close automatically when the panel processes an alarm event. The contacts remain closed until all active alarm points restore and the panel resets. Normally-closed relay contacts that open automatically when the panel processes an alarm event. The contacts remain open until all active alarm points restore and the panel resets. Normally-open relay contacts that close automatically when the panel processes a supervisory event. The contacts remain closed until the active supervisory point restores. Normally-open relay contacts that close automatically when the panel energizes. The contacts open when the panel processes a trouble event or when the panel loses power and remain open until the trouble condition restores. Normally-open relay contacts that close depending on how the user programs the panel. Not used Provides regulated 24 Vdc for four-wire smoke detectors or accessory devices depending on jumper setting. Connects to the Channel 1 input on a remote annunciator

TB12, 3

Relay 1 C, NC

TB14, 5

Relay 2 C, NO

TB16, 7

Relay 3 C, NO

TB18, 9 TB110 TB111, 12 TB113, 14

Relay 4 C, NO N.C. SMK/ACC PWR +, RS485 +,

2.14

QS4 Technical Reference Manual

Installation

Terminal No. TB115 TB116 TB117 TB118 TB21 TB22 TB23 TB31

Name RS232 RTS RS232 RX RS232 TX RS232 COM BATT PWR + BATT PWR NC AUX1

Description Not used Connects to the data transmit (TX) terminal on a peripheral device. Connects to the receive data (RX) terminal on a peripheral device. Connects to the common ground (COM) terminal on a peripheral device. Connects to the positive terminal on the standby battery. Connects to the negative terminal on the standby battery. Not used. Provides 24 Vdc, FWR power to auxiliary devices. Note: AUX1, AUX2, and AUX3 can not be used to power remote annunciators

TB32 TB33 TB34 TB35

AUX2 COM AUX3 COM

Provides 24 Vdc, FWR power to auxiliary devices. Negative reference for AUX1 and AUX2 outputs. Provides 24 Vdc, FWR power to auxiliary devices. Negative reference for AUX3 output.

QS4 Technical Reference Manual

2.15

Installation Table 2-2: SLIC Signature Loop Intelligent Controller card


NAC 1 NAC 2 B+ B A+ A B+ B A+ A TB1 1 2 3 4 5 6 7 8

OUT +

IN +

LOOP A+ A B+ B TB2

Terminal No. TB1, 2

Name NAC 1 B+, B

Description Connects to the IN +/ terminals of the first device on the NAC circuit. Polarity markings (+/) indicate output signal polarity with the circuit turned off. Polarity reverses with the circuit turned on. Connects to the OUT +/ terminals of the last device on the NAC circuit. Class A configuration only. Connects to the IN +/ terminals of the first device on the NAC circuit. Polarity markings (+/) indicate output signal polarity with the circuit turned off. Polarity reverses with the circuit turned on. Connects to the OUT +/ terminals of the last device on the NAC circuit. Class A configuration only. Connects to the next device on the same 24VDC riser used to provide 24 Vdc to NAC 1 and NAC 2. Connects to the signal source used to provide 24 Vdc to NAC 1 and NAC 2. Connects to the DATA OUT +/ terminals of last device on the Signature signaling line circuit. Class A configuration only. Connects to the DATA IN +/ terminals of the first device on the Signature signaling line circuit.

TB3, 4 TB5, 6

NAC 1 A+, A NAC 2 B+, B

TB7, 8 TB21, 2 TB23, 4 TB25, 6

NAC 2 A+, A OUT+, OUT IN+, IN LOOP A+, A

TB27, 8

LOOP B+, B

2.16

QS4 Technical Reference Manual

Installation Table 2-3: ZA82 terminal definitions


ZONE 1 ZONE 2 ZONE 3 ZONE 4 NAC PWR B+ B A+ A B+ B A+ A B+ B A+ A B+ B A+ A IN+ IN TB1 1 2 3 4 5 6 7 IDC 8 9 10 11 12 13 14 15 16 17 18

IDC/NAC

IDC

IDC/NAC

ZONE 5 ZONE 6 ZONE 7 ZONE 8 NAC PWR B+ B A+ A B+ B A+ A B+ B A+ A B+ B A+ A IN+ IN TB2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

IDC circuit connections Terminal No. TB11, 2 TB13, 4 Name ZONE 1 B+, B ZONE 1 A+, A Description Connects to the IN +/ terminals of the first device on the IDC. Connects to the OUT +/ terminals of the last device on the IDC.

Note: ZONE 2, 3, 5, 6, and 7 connect the same as described for ZONE 1. IDC/NAC circuit connections Terminal No. TB113, 14 Name ZONE 4 B+, B Description Connects to the IN +/ terminals of the first device on the NAC. Polarity markings (+/) indicate output signal polarity with the circuit turned off. Polarity reverses with the circuit turned on. Connects to the OUT +/ terminals of the last device on the NAC. Connects to the signal source used to provide 24VDC to ZONE 4. Connects to the IN +/ terminals of the first device on the NAC. Polarity markings (+/) indicate output signal polarity with the circuit turned off. Polarity reverses with the circuit turned on. Connects to the OUT +/ terminals of the last device on the NAC. Connects to the signal source used to provide 24VDC to ZONE 8.

TB115, 16 TB117, 18 TB213, 14

ZONE 4 A+, A NAC PWR IN+, IN ZONE 8 B+, B

TB215, 16 TB217, 18

ZONE 8 A+, A NAC PWR IN+, IN

Note: ZONE 4 and ZONE 8 may be programmed as IDC circuits.

QS4 Technical Reference Manual

2.17

Installation Table 2-4: ZB164 Class B Zone card terminal definitions

+ Z1

+ Z2

+ Z3

+ Z4

+ Z5

+ Z6

+ Z7

+ Z8

+ Z9 TB1

9 IDC

10

11

12

13

14

15

16

17

18

IDC + Z10 + Z11 + Z12 + Z13

IDC/NAC + Z14 + Z15 + Z16 + R1 + R2 TB2

10

11

12

13

14

15

16

17

18

IDC circuit connections Terminal No. TB11, 2 Name Z1+, Z1 Description Connects to the IN +/ terminals of the first device on the IDC.

Note: Z2Z16 connect the same as described for Z1. IDC/NAC circuit connections Terminal No. TB27, 8 Name Z13+, Z13 Description Connects to the IN +/ terminals of the first device on the NAC. Polarity markings (+/) indicate output signal polarity with the circuit turned off. Polarity reverses with the circuit turned on. same as above same as above same as above Connects to the signal source used to provide 24VDC to Z13 and Z14. Connects to the signal source used to provide 24VDC to Z15 and Z16.

TB29, 10 TB211, 12 TB213, 14 TB115, 16 TB117, 18

Z14+, Z14 Z15+, Z15 Z16+, Z16 R1+, R1 R2+, R2

Note: Z13, Z14, Z15, and Z16 may be programmed as IDC circuits.

2.18

QS4 Technical Reference Manual

Installation Table 2-5: ZR8 Relay card terminal definitions


+ R1 + R2 + R3 + R4 TB1 1 2 3 4 5 6 7 8

+ R5

+ R6

+ R7

+ R8 TB2

Terminal No. TB11, 2 TB13, 4 TB15, 6 TB17, 8 TB21, 2 TB23, 4 TB25, 6 TB27, 8

Name R1+, R1 R2+, R2 R3+, R3 R4+, R4 R5+, R5 R6+, R6 R7+, R7 R8+, R8

Description Terminal connections for relay 1. Terminal connections for relay 2. Terminal connections for relay 3. Terminal connections for relay 4. Terminal connections for relay 5. Terminal connections for relay 6. Terminal connections for relay 7. Terminal connections for relay 8.

QS4 Technical Reference Manual

2.19

Installation Table 2-6: RS485 (NTA) Class A card terminal definitions


RS485 + CH2 + CH1 TB1 1 2 3 4

Terminal No. TB11, 2 TB13, 4

Name CH2+, CH2 CH1+, CH1

Description Connects to CH2+/ on the first remote annunciator on the Class A RS485 riser. Connects to CH1+/ on the first remote annunciator on the Class A RS485 riser.

2.20

QS4 Technical Reference Manual

Installation Table 2-7: DLD Dual Line Dialer card terminal definitions
LINE 1 LINE 2 IN OUT IN OUT TIP RING TIP RING TIP RING TIP RING TB1 1 2 3 4 5 6 7 8

Terminal No. TB11 TB12 TB13 TB14 TB15 TB16 TB17 TB18

Name LINE 1 TIP IN LINE 1 RING IN LINE 1 TIP OUT LINE 1 RING OUT LINE 2 TIP IN LINE 2 RING IN LINE 2 TIP OUT LINE 2 RING OUT

Description Connects to the Tip In connector on the telco side of an RJ31X block via an RJ12 modular cable. Connects to the Ring In connector on the telco side of an RJ31X block via an RJ12 modular cable. Connects to the Tip Out connector on the protected premises side of an RJ31X block via an RJ12 modular cable. Connects to the Ring Out connector on the protected premises of an RJ31X block via an RJ12 modular cable. Connects to the Tip In connector on the telco side of an RJ31X block via an RJ12 modular cable. Connects to the Ring In connector on the telco side of an RJ31X block via an RJ12 modular cable. Connects to the Tip Out connector on the protected premises side of an RJ31X block via an RJ12 modular cable. Connects to the Ring Out connector on the protected premises of an RJ31X block via an RJ12 modular cable.

QS4 Technical Reference Manual

2.21

Installation

Connecting a PT1S printer


For control panels with only a printer 1. Locate the printer in the same room as and within 20 ft of the panel (printer wiring is nonsupervised and power-limited). 2. Wire the printer cable to the RS232 connections on the power supply card then plug the cable into the printer. 3. Set the printer switches for 9600 bps, 8 bits, no parity. Refer to the documentation included with the printer for more details. For control panels with a printer and a CDR 3 Bell Coder module 1. Install the IOP3A in the same enclosure as the CDR3. Refer to appendix B. 2. Wire the IOP3A to the CDR3. 3. Wire the printer cable to the RS232 connections on the IOP3A then plug the cable into the printer. 4. Configure the IOP3A as follows: JP1 = 23
JB4

PS6 TB118 PS6 TB117 PS6 TB116

COMCOM

7 3 2

TXRX RXTX

TO PT1S

DB25P REAR VIEW

TB1

CDR3 TB24 CDR3 TB25 CDR3 TB26 CDR3 TB27


SW1 UP

1 2 3 4 5 6
JB1 3 2 1

PS6 TB117

JP2 = ON JP3 = ON JP4 = ON SW1 = UP 5. Set the printer switches for 9600 bps, 8 bits, no parity. Refer to the documentation included with the printer for more details.
TO PT1S 7 32
TB3 COMCOM RxDTxD TxDRxD TB2
JB3 JB2

IOP3A

DB25P REAR VIEW

1 2 3 4

2.22

QS4 Technical Reference Manual

Installation

Installing standby batteries


For batteries rated at 10 Ah or less 1. Place the batteries in the bottom of the control panel. 2. Wire the batteries to the PS6. Notes Do not run wires through the bottom knock-outs when batteries are installed in the control panel. Battery wiring is supervised and nonpower-limited. Maintain a 1/4-inch separation between powerlimited and nonpower-limited wiring at all times. For batteries rated greater than 10 Ah 1. Place the batteries in a BC-1 Battery Cabinet. The cabinet must be mounted within 3 ft of the control panel, in the same room, and connected with conduit. 2. Wire the batteries to the PS6.
+ + +

Note: Install, maintain, and test standby batteries in accordance with NFPA 72.

BC-1

QS4 Technical Reference Manual

2.23

Installation

Connecting a service computer


Connection of a service computer to the control panel requires programming cable P/N 260097, ordered separately. Connection of a service computer to a remote annunciator requires programming cable P/N 360136 and a RJ11 to DB9 adapter P/N 240507, both ordered separately.
RTS PS6 RX TX COM P/N 260097
NOT USED

DB-9F REAR VIEW 1 9

2.24

QS4 Technical Reference Manual

Chapter 3

Operating instructions

Summary This chapter provides instructions for operating the control panel. Content Instructions for the Level 1 operator (public mode access) 3.2 Instructions for the Level 2 operator (emergency mode access) 3.5 Instructions for the Level 3 operator (maintenance mode access) 3.7 Instructions for the Level 4 operator (service mode access) 3.10 QuickReference list 3.11

QS4 Technical Reference Manual

3.1

Operating instructions

Instructions for the Level 1 operator (public mode access)


Tasks that do not require you to log in What is it you want to do Silence the panel trouble buzzer Get a list of all the active points on a panel This is how you do it Press Panel Silence. 1. Press Status. 2. Choose All Active to get a list of all the active points. Choose Alarm to get a list of only the active alarm points. Choose Supervisory to get a list of only the active supervisory points. Choose Monitor to get a list of only the active monitor points. 3. Press DEL to backspace the cursor then enter the panel number. 4. Choose Display to view the list on the CPU/Display unit. or Choose Printer to print the list. Identify points that are in trouble 1. Press Status. 2. Choose Trouble 3. Press DEL to backspace the cursor then enter the panel number. 4. Choose Display to view the list on the CPU/Display unit. or Choose Printer to print the list. Identify active points in a Service Group that is being tested 1. Press Status. 2. Choose Test. 3. Press DEL to backspace the cursor then enter the panel number. 4. Choose Display to view the list on the CPU/Display unit. or Choose Printer to print the list.

3.2

QS4 Technical Reference Manual

Operating instructions

Tasks that do not require you to log in What is it you want to do Identify points that are disabled This is how you do it 1. Press Status. 2. Choose Disabled Pts. 3. Press DEL to backspace the cursor then enter the panel number. 4. Choose Display to view the list on the CPU/Display unit. or Choose Printer to print the list. Identify output devices that are turned on 1. Press Status. 2. Choose Outputs 3. Press DEL to backspace the cursor then enter the panel number. 4. Choose Display to view the list on the CPU/Display unit. or Choose Printer to print the list. Verify power supply voltage levels 1. Press Status. 2. Choose Internal 3. Press Enter. 4. Choose Display to view the list on the CPU/Display unit. or Choose Printer to print the list. Get a list of smoke detectors that require servicing (DIRTY attribute greater than 80%) 1. Press Menu. 2. Choose Reports > Maintenance > Dirty>80%. 3 Enter the panel number. or Choose Printer to print the list. 4. Choose Display to view the list on the CPU/Display unit.

QS4 Technical Reference Manual

3.3

Operating instructions

Tasks that do not require you to log in What is it you want to do Get a list of smoke detectors that may require servicing (DIRTY attribute greater than 20%) This is how you do it 1. Press Menu. 2. Choose Reports > Maintenance > Dirty>20%. 3 Enter the panel number. or Choose Printer to print the list. Get the attributes for a single smoke detector 1. Press Menu. 2. Choose Reports > Maintenance > Single Device. 3. Enter the panel number. 4. Choose Display to view the list on the CPU/Display unit. or Choose Printer to print the list. Get the attributes for every smoke detector on a single SLIC 1. Press Menu. 2. Choose Reports > Maintenance > Card Devices. 3 Enter the panel number. or Choose Printer to print the list. Perform a lamp test 1. Press Menu. 2. Choose Test > Lamp Test. 4. Choose Display to view the list on the CPU/Display unit. 4. Choose Display to view the list on the CPU/Display unit.

3.4

QS4 Technical Reference Manual

Operating instructions

Instructions for the Level 2 operator (emergency mode access)


Tasks that require you to log on as a Level 2 operator What is it you want to do Log onto the panel as a Level 2 operator This is how you do it Turn the Enable Controls key 1/4 of a turn clockwise. or 1. Press Menu. 2. Choose Login then enter the password required for Level 2 access. Reset the panel Turn off alarm signaling circuits when the panel is in alarm (Alarm Silence) Turn on alarm signaling circuits when the panel is not in alarm (Drill) Get a list of all events processed on a panel Press System Reset. Press Alarm Silence.

Press Drill then Enter.

1. Press Menu. 2. Choose Reports > History. 3. Enter the panel number. 4. Choose Display to view the list on the CPU/Display unit. or Choose Printer to print the list.

Change the password required for Level 1 access

1. Press Menu. 2. Choose Program > Edit Password > Level 1. 3. Enter the new password.

Switch automatic detectors to their alternate sensitivity settings

1. Press Menu. 2. Choose Activate > Alt Sens. 1. Press Menu. 2. Choose Restore > Prm Sens.

Switch automatic detectors to their primary sensitivity settings

QS4 Technical Reference Manual

3.5

Operating instructions

Tasks that require you to log on as a Level 2 operator What is it you want to do Distribute event records according to their alternate message routing This is how you do it 1. Press Menu. 2. Choose Activate > Alt Msg Route. 1. Press Menu. 2. Choose Restore > Prm Msg Route. 1. Press Menu. 2. Choose Disable > Zone. 3. Select a Zone from the pick list then press Enter. Enable a Zone 1. Press Menu. 2. Choose Enable > Zone. 3. Select a Zone from the pick list then press Enter. Disable a device 1. Press Menu. 2. Choose Disable > Device. 3. Enter the device address, where: PP is the panel number (01) CC is the card number DDD is the circuit or device number Enable a device 1. Press Menu. 2. Choose Enable > Device. 3. Enter the device address, where: PP is the panel number (01) CC is the card number DDD is the circuit or device number

Distribute event records according to their primary message routing

Disable a Zone

3.6

QS4 Technical Reference Manual

Operating instructions

Instructions for the Level 3 operator (maintenance mode access)


Tasks that require you to log on as a Level 3 operator What is it you want to do Log onto the panel as a Level 3 operator This is how you do it 1. Press Menu. 2. Choose Login then enter the password required for Level 3 access. 1. From the Main Menu, select Program. 2. Select Edit Password. 3. Select Level 2 then enter the new password. Get a list of all the hardware and software components installed on a panel and their revision levels 1. Press Menu. 2. Choose Reports > Revision. 3. Enter the panel number. 4. Choose Display to view the list on the CPU/Display unit. or Choose Printer to print the list. Set the system time and date 1. Press Menu. 2. Choose Program > Time/Date. 3. Choose Enter Time, then press DEL until the display shows HHMMSS. Enter the time in 24hour format where HH is the hour, MM is the minutes, and SS is the seconds. Example: To set the time for 1:00 p.m., enter 130000. 4. Select Enter Date. Enter the date where MM is the number of the month, DD is the date, and YYYY is the year. Example: To set the date for January 1, 2001, enter 01012001.

Change the password required for Level 2 access

QS4 Technical Reference Manual

3.7

Operating instructions

Tasks that require you to log on as a Level 3 operator What is it you want to do Turn on an output circuit Note: A typical system may assign manual override functions a high priority level, alert responses a low priority, and alarm responses a medium priority. This is how you do it 1. Press Menu. 2. Choose Activate > Output. 3. Enter the output circuit's address, where PP is the panel number, CC is the card number, and DDD is the circuit number. 4. Choose Steady to change the circuit's output to always on Choose 20 BPM to change the circuit's output to a 20 beat per minute signal rate (On = 21/2 s; Off = 21/2 s). Choose 120 BPM to change the circuit's output to a 120 beat per minute signal rate (On = 1/4 s; Off = 1/4 s). Choose Temporal to change the circuit's output to a 333 pattern. 5. Choose High Priority. Turn off an output circuit 1. Press Menu. 2. Choose Restore > Output. 3. Enter the output circuit's address, where PP is the panel number, CC is the card number, and DDD is the circuit number. 4. Choose Off. Turn an LED on 1. Press Menu. 2. Choose Activate > LED. 3. Choose one of the following: Steady to turn the LED on Fast Blink to have the LED flash at a fast rate Slow Blink to have the LED flash at a slow rate 4. Enter the LED's address where GG is the group number, SS is the switch number, and L is the LED number. Turn an LED off 1. Press Menu. 2. Choose Restore > LED. 3. Choose Off 4. Enter the LED's address where GG is the group number, SS is the switch number, and L is the LED number.

3.8

QS4 Technical Reference Manual

Operating instructions

Tasks that require you to log on as a Level 3 operator What is it you want to do Disable or enable an And Group, Matrix Group, or Time Control This is how you do it 1. Press Menu. 2. Choose Disable or Enable. 3. Choose And if an And group, Matrix if a Matrix group, or Time Control if a time control. 4. Pick a group from the appropriate list and press Enter. Disable or enable a switch on a zone display 1. Press Menu. 2. Choose Disable > Switch. or Enable > Switch. 3. Enter the switch address, where GG is the group number, and SS is the switch number. Disable or enable the mapping function on an SLIC 1. Press Menu. 2. Choose Disable > Loop Mapping. or Enable > Loop Mapping. 3. Enter the card address for the SLIC. Start a Service Group test 1. Press Menu. 2. Choose Test > Start Test. 3. Select a Service group from the pick list and press Enter. Cancel a Service Group test Note: The panel automatically resets after you cancel a test. 1. Press Menu. 2. Choose Test > Cancel Test. 2. Select a Service group from the pick list and press Enter.

QS4 Technical Reference Manual

3.9

Operating instructions

Instructions for the Level 4 operator (service mode access)


What is it you want to do Log onto the panel as a Level 4 operator This is how you do it 1. Press Menu. 2. Choose Login then enter the password required for Level 4 access. 1. Press Menu. 2. Choose Program > Edit Password > Edit Password 3. Choose Level 3 then enter the new password. Change the password required for Level 4 access 1. Press Menu. 2. Choose Program > Edit Password > Edit Password 3. Choose Level 4 then enter the new password. Restart a panel 1. Press Menu. 2. Choose Program > Restart > Panel 3. Enter the panel's address. Reset the alarm history counter 1. From the Main Menu, select Program. 2. Select Reset. 3. Enter the panel's address.

Change the password required for Level 3 access

3.10

QS4 Technical Reference Manual

Operating instructions

QuickReference list
Required access level What is it you want to do Change smoke detector sensitivity settings to their alternate values Change smoke detector sensitivity settings to their primary values Change the current state of an LED (manual override) Change the current state of an output circuit (manual override) Change the password required for Level 1 access Change the password required for Level 2 access Change the password required for Level 3 access Change the password required for Level 4 access Disable or enable a device Disable or enable a switch on a zone display Disable or enable a zone Disable or enable all the devices on a single card Disable or enable an And Group, Matrix Group, or Time Control Disable or enable the mapping function on an SLIC Get a list of all the active points on a panel Get a list of all the hardware and software components installed on a panel and their revision levels Get a list of smoke detectors that may require servicing (DIRTY attribute greater than 20%) Get a list of smoke detectors that require servicing (DIRTY attribute greater than 80%) Get the attributes for a single smoke detector Get the attributes for all the smoke detectors on a single SLIC Identify output devices that are turned on Identify active points in a Service Group that is being tested Identify points that are disabled Identify points that are in their active state Identify points that are in trouble Log onto the panel as a Level 2 operator Log onto the panel as a Level 3 operator Log onto the panel as a Level 4 operator Perform a lamp test L1 L2 L3 L4

QS4 Technical Reference Manual

3.11

Operating instructions

Required access level What is it you want to do Reset the alarm history counter Reset the panel Restart the panel Restore an LED to its previous state Restore an output circuit to its previous state Route off-normal signals to the alternate set of panels used to post messages Route off-normal signals to the primary set of panels used to post messages Set the system time and date Silence the panel trouble buzzer Start a Service Group test Cancel a Service Group test Turn off alarm signaling circuits when the panel is in alarm (Alarm Silence) Turn on alarm signaling circuits when the panel is not in alarm (Drill) Verify power supply voltage levels L1 L2 L3 L4

3.12

QS4 Technical Reference Manual

Chapter 4

Programming instructions

Summary This chapter provides instructions for programming the fire alarm system from the front panel. Worksheets are provided at the end of the chapter to use as programming aids and to document the system programming. Content Overview 4.2 QuickStart setup instructions 4.4 Customizing the system configuration 4.13 Setting up an Output Group 4.21 Setting up a Zone 4.24

QS4 Technical Reference Manual

4.1

Programming instructions

Overview
What is a Zone?
A Zone is a function in the system software that initiates an active response based on a single alarm event. Firewall designations, planned evacuation criteria, architectural design, and other factors all contribute to how the system designer divides the protected premises into zones.
ZONE 1 FACP

ZONE 2 J

ZONE 3

What is an Output Group?

An Output Group is a function in the system software that establishes the correlation between input circuits and responses. When an input changes states, the condition of the input determines which response the panel runs. For example, a smoke detector initiates the Active response when it signals an alarm condition but initiates the Trouble response when removed from its base.
Output 1
ZONE 1

Active Trouble Output 2 Active Trouble

4.2

QS4 Technical Reference Manual

Programming instructions
Table 4-1: Programmable features Feature And Groups Output Groups Matrix Groups Service Groups Time Controls Zones LED Configure Switch Configure SIGA - Prealarm SIGA - Sensitivity levels Alarm Verification Coded Operation Custom Messages Message Routing SIGA - Diagnostics AC Delay Two-stage Operation General Alarm Inhibit Market Place Card Configuration Language Zone Resound Inhibit Drill Programming Alarm Silence Programming Waterflow Silence Supervisory Duct Enable Trouble Reminder Auto Alarm Signal Silence Alarm Signal Silence/Reset Inhibit Panel Silence Resound Time SIGAREL Front Panel Programming (FPP) No Yes No Limited No Yes Limited Limited Yes Yes Yes Yes Yes (requires bar code wand) No No No No No No Yes No No No No No No No No Yes No No Configuration Utility (CU) Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes

QS4 Technical Reference Manual

4.3

Programming instructions

QuickStart setup instructions


Step 1: Read this before proceeding
Note: If at any time you get an Exception Event while programming the system, note the error code, and then contact EST Technical Services at 6411 Parkland Drive, Sarasota, FL 34243 or at 1-800-655-4497. To clear the Exception Event, press Alarm Silence while the event is displayed. You may have to reset the panel to display the event again. This procedure uses the AutoLearn and AutoLoop utilities to automatically configure the system. The AutoLearn utility configures the option cards. The AutoLoop utility configures the circuits on the Signature loop. Caution: Running the AutoLearn utility deletes the existing panel programming. If you have already programmed the system, running AutoLearn requires you to re-enter everything again from the beginning. If you have a dialer installed, the AutoLearn utility requires you to program the DLD before exiting. Be sure to have the following: Subscriber account numbers, telephone numbers, and transmission formats obtained from the CMS (Central Monitoring Station). Appendic C provides a list of Contact ID event codes. A completed copy of the DLD Programming Worksheet (Figure 4-1).

After you have finished using the AutoLearn and AutoLoop utilities to configure the system, you can either: Customize the system programming Go to step 11 and Save and Sync.

Step 2: Apply power to the system

1. Verify that each circuit card installed in the control panel has a unique card address. 2. Apply power to the control panel and to all the remote annunciators. After applying power, the panel CPU performs a diagnostic check in the background. You can not begin programming until this finishes and the AutoLearn option becomes available.

4.4

QS4 Technical Reference Manual

Programming instructions

On each remote annunciator panel: Step 3: Assign Panel ID numbers to 1. Press Menu. the remote annunciator panels 2. Choose Login then enter the password required for Level 4 access (default is 4444). 3. Choose Program > Configure > AutoLearn. 4. Press Del twice then enter an unused Panel ID from 02 to 09 (01 is reserved for the control panel). 5. Enter the number of panels that are connected to the RS485 riser, including the control panel. This is your maximum number of panel addresses. 6. Select the wiring configuration of the RS485 riser (Class A or Class B) then press Enter. Note: The wiring configuration must be the same for all panels.

Step 4: AutoLearn the control panel.


Note: Before running the AutoLearn utility, make sure you have not installed more cards than the system allows.

On the control panel: 1. Press Menu. 2. Choose Login then enter the password required for Level 4 access (default is 4444). 3. Choose Reports > Revision > Enter > Display. Verify all the cards installed in the cabinet appear in the list. 4. Press Menu then choose Program > Configure > AutoLearn. 5. Enter 01 for the Panel ID. 6. Enter the number of panels that are connected to the RS485 riser, including the control panel. This is your maximum number of panel addresses. 7. Select the wiring configuration of the RS485 riser (Class A or Class B) then press Enter. If you do not have a DLD card installed, the system will automatically reboot after the AutoLearn utility configures the system. Go to step 10. If you do have a DLD card installed, go to step 5.

QS4 Technical Reference Manual

4.5

Programming instructions

Step 5: Set up the receiver call-in numbers and retry attempts

1. Choose #'s of CMS then choose the number of CMS receivers that the DLD may dial into over the public switched telephone network. 2. Choose CMS Phone # then enter the telephone numbers of the CMS receivers: Choose Rcvr 1 Prim # then enter the first number to try for the first CMS receiver. Choose Rcvr 1 Sec # then enter the second number to try for the first CMS receiver. Choose Rcvr 2 Prim # then enter the first number to try for the second CMS receiver. Choose Rcvr 2 Sec # then enter the second number to try for the second CMS receiver. Choose Exit. 3. Choose Retry Count then enter the number of times you want the dialer to attempt to contact the CMS receiver.

Step 6: Set up the subscriber accounts

1. Choose Accounts then <New> to set up a new account or Select an account number then press Enter. 2. Choose Account # then enter the number of the subscriber account. 3. Choose Formats then choose the required transmission format. 4. Choose TestNormal then enter the character string to send when the control panel is normal. 5. Choose TestAbnormal then enter the character string to send when the control panel is off-normal. 6. Choose Test Time then enter when you want the dialer to transmit the test string in 24-hour format. 7. Choose CMS then choose which CMS receiver to dial. This is the receiver that holds the account. 8. Choose Exit.

4.6

QS4 Technical Reference Manual

Programming instructions

Step 7: Edit the default alarm messages


Note: The dialer automatically sends the default alarm message for active alarm inputs that are not programmed to initiate a dialer response.

1. Choose Default Msgs > Alarm. 2. Choose Account then select the subscriber account you want to receive the message. 3. Choose Active Msg then enter the message you want sent for alarm activation events. For example, for Contact ID enter 111000000 4. Choose Restore Msg then enter the message you want sent for alarm restoration event. For example, for Contact ID enter 311000000 5. Choose Exit.

Step 8: Edit the default trouble messages


Note: The dialer automatically sends the default trouble message for inputs that signal a trouble but are not programmed to initiate a dialer response.

1. Choose Default Msgs > Trouble. 2. Choose Account then select the subscriber account you want to receive the message. 3. Choose Active Msg then enter the message you want sent for trouble activation events. For example, for Contact ID enter 130000000 4. Choose Restore Msg then enter the message you want sent for trouble restoration event. For example, for Contact ID enter 330000000 5. Choose Exit.

Step 9: Edit the default supervisory messages


Note: The dialer automatically sends the default supervisory message for active supervisory inputs that are not programmed to initiate a dialer response.

1. Choose Default Msgs > Supervisory. 2. Choose Account then select the subscriber account you want to receive the message. 3. Choose Active Msg then enter the message you want sent for supervisory activation events. For example, for Contact ID enter 120000000 4. Choose Restore Msg then enter the message you want sent for a supervisory restoration event. For example, for Contact ID enter 220000000 5. Choose Exit.

QS4 Technical Reference Manual

4.7

Programming instructions

Step 10: AutoLoop the loop controller cards

Run the AutoLoop utility on each loop controller installed in the control panel. Caution: When the system reboots, the loop controller reinitializes the loop. If you attempt to run the AutoLoop utility during this time, you could corrupt the project database. 1. On the control panel, press Menu. 2. Choose Login then enter the password required for Level 4 access. 3. Choose Program > Configure. If the loop is still initializing, do not proceed until loop initialization has finished. 4. Choose Cards > Edit, then enter the card number for the loop controller. 5. On the Edit Cards menu, choose AutoLoop. 6. If the number of detector and module addresses on the display match the number installed on the loop, press Enter to accept, then wait while the database is updated. If not, press Del to cancel. You must correct the problem before continuing with this loop. 7. On the SLIC menu, choose Exit. 8. For each additional loop controller, repeat steps 47. 9. Choose Exit.

Step 11: Saving the project database


Tip: Only Save and Sync after you have finished programming the control panel and you want to update the project databases in the remote annunciators.

At this point, you have configured the project database for a general alarm system. Refer to Table 4-2, Table 4-3 and Table 4-4 for initial system settings. If you want to accept the general alarm system configuration, choose Save and Sync. If you want to make changes to the system configuration, choose Save, and then make your changes. See Customizing the system configuration. After making all of your changes: 1. Press Menu. 2. Choose Login then enter the password required for Level 4 access. 3. Choose Program > Configure > Exit. 4. Choose Save and Sync. Note: If the local AHJ requires a hard copy of your site programming, use the QuickStart Configuration Utility to retrieve the database from the panel and print the required information.

4.8

QS4 Technical Reference Manual

Programming instructions
Table 4-2: AutoLearn initial project settings Option Alarm Silence Drill Drill Activation Type Alarm Signal Silence/Reset Inhibit Buzzer Reminder Time AC Power Trouble Delay Two-stage Timer Value Audible only Audible only Steady None Description Turns off Audible and Common Alarm Output circuits when someone presses Alarm Silence. Turns off Audible and Common Alarm Output circuits when someone presses Drill. The Drill signal is a constant signal. Alarm Silence or Reset functions are not inhibited. You can turn off (silence) notification circuits or reset the panel any time after notification circuits are activated. The panel trouble buzzer remains silenced until the control panel processes a new off-normal signal. The panel will operate on battery power for 6 hours before signaling a trouble condition. The panel will turn on notification circuits immediately after processing an alarm signal (UL) or after 5 minutes (ULC). Turn silenced NAC circuits back on if an active alarm input circuit remains in the active condition after resetting the panel. Distribute event records to all panels in the system when primary routing is activated. Distribute event records to all panels in the system when alternate routing is activated. U.S. English displayed on CPU/Display. Alarm events cause the contact positions of Relay 1 on the PS6 to change positions. Supervisory events cause the contact positions of Relay 2 on the PS6 to change positions. Trouble events cause the contact positions of Relay 3 on the PS6 to change positions. Monitor events cause the contact positions of Relay 4 on the PS6 to change positions. Edit? CU CU CU FPP/CU

Indefinitely 6h 0 s (UL) 300 s (ULC) No

No FPP/CU CU

Zone Resound Inhibit

No

Primary Routing Alternate Routing Language Relay 1 Type Relay 2 Type Relay 3 Type Relay 4 Type

All Cabinets All Cabinets English (U.S.) Alarm Supervisory Trouble Monitor

CU CU No No No No CU

QS4 Technical Reference Manual

4.9

Programming instructions
Table 4-3: AutoLearn initial card configuration settings Card SLIC Circuit NAC 1 NAC 2 Address 270 271 Device type Visible Common Alarm Output Edit? FPP/CU FPP/CU Diagram

NAC 1

NAC 2

Card ZB164

Circuit Z1 Z2 Z3 Z4 Z5 Z6 Z7 Z8 Z9 Z10 Z11 Z12 Z13 Z14 Z15 Z16

Address 001 002 003 004 005 006 007 008 009 010 011 012 013 014 015 016

Device type Alarm Alarm Alarm Alarm Alarm Alarm Alarm Alarm Alarm Alarm Alarm Alarm Common Alarm Output Common Alarm Output Visible Visible

Edit? FPP/CU FPP/CU FPP/CU FPP/CU FPP/CU FPP/CU FPP/CU FPP/CU FPP/CU FPP/CU FPP/CU FPP/CU FPP/CU FPP/CU FPP/CU FPP/CU
Z12 Z11 Z10 Z4 Z3 Z2 Z1

Diagram
Z5 Z6 Z7 Z8 Z9

Z13 Z14 Z15 Z16

4.10

QS4 Technical Reference Manual

Programming instructions
Table 4-3: AutoLearn initial card configuration settings (cont.) Card Circuit Address Setting Edit? Diagram

ZA82

Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 Zone 7 Zone 8

001 002 003 004 005 006 007 008

Alarm Alarm Alarm Common Alarm Output Alarm Alarm Alarm Visible

FPP/CU FPP/CU FPP/CU FPP/CU FPP/CU FPP/CU FPP/CU FPP/CU

Zone 1 Zone 2 Zone 3 Zone 4

Zone 8 Zone 7 Zone 6 Zone 5

QS4 Technical Reference Manual

4.11

Programming instructions

Table 4-4: AutoLoop initial settings for SIGA devices SIGA Device SIGAIPHS, PHS, PS, IS Personality none Description Smoke detector settings as follows: Sensitivity: Least Verification: None Prealarm: None Heat detector settings not programmable Class B Alarm Latching Class B Alarm Latching Class B Alarm Latching Class B Active Non-Latching Class B Active Non-Latching Riser selector Dual riser selector Dry contact Class B Alarm Latching Class B Alarm Latching Class B Alarm Latching Class B Alarm Latching Monitor Input/Output N.O. Class A Signal Output not used Class A Signal Output not used Class B Active Non-Latching Class B Active Latching - Delayed Class B Active Latching. Riser monitor - 24 Vdc Monitor Alarm Supervisory Monitor FPP/CU FPP/CU FPP/CU FPP/CU Monitor FPP/CU Device Type Alarm Edit? FPP/CU

SIGAHFS, HRS, IM Single-stage pull stations Dual-stage pull stations

none 01 01 01

Alarm Pull Monitor Pull Monitor Monitor Common Alarm Output Common Alarm Output Nonsupervised Output Alarm Alarm Alarm Alarm Monitor Monitor

FPP/CU FPP/CU FPP/CU FPP/CU FPP/CU FPP/CU FPP/CU FPP/CU FPP/CU FPP/CU FPP/CU FPP/CU FPP/CU FPP/CU FPP/CU

SIGAAPS

03 03

SIGA(M)CC1(S) SIGA(M)CC2 SIGA(M)CR(R) SIGA(M)CT1 SIGA(M)CT2

05 07 08 01 01 01

SIGADTS SIGAIO SIGAMAB

01 31 00 00

SIGAUM

00 00

SIGAMM1 SIGAWTM

03 02 04

SIGA(M)RM1

23

Note: If you use Signature devices from another system, the AutoLoop utility uses the attributes programmed from the previous system as the initial settings for a general alarm system.

4.12

QS4 Technical Reference Manual

Programming instructions

Customizing the system configuration


You can customize the system configuration, if your requirements exceed that of the general alarm system created using the AutoLearn and AutoLoop utilities. Before you can make any changes to the system programming, you must log onto the system to start an editing session. The control panel has a watchdog timer that kicks you out of an editing session after a period of inactivity. If this happens, you will have to log in again to continue. After you finish customizing the system configuration, save your changes, and then test the system. After everything checks out then Save and Sync to copy the database to the remote annunciators.
What is it you want to do

WARNING: Entering Edit mode (choosing Configure on the Program menu) disables the control panel and leaves the premises unprotected until you exit Edit mode. To start an editing session: 1. Press Menu. 2. Choose Login then enter the password required for Level 4 access. 3. Choose Program > Configure.

This is how you do it

Make information about the installer available on the CPU/Display AutoLearn default: No text

1. On the Configure menu, choose System > User Labels. 2. Choose Facility Name, scan in the name of the project, and then press Enter. 3. Choose Inst Company, scan in the name of the installing company, and then press Enter. 4. Choose Phone Number, scan in the telephone number to call for service-related issues, and then press Enter. 5. Choose Programmer, scan in the name of the person that programmed the system, and then press Enter. 6. Choose Exit.

Set how long notification circuits must stay on before pressing Alarm Silence can turn them off or pressing Reset can reset the panel AutoLearn default: None (no delay) Set how long the panel must wait before signaling an ac power failure AutoLearn default: 0 (no delay)

1. On the Configure menu, choose System > ALM/RST Inhib. 2. Select a time delay from the pick list then press Enter. 1. On the Configure menu, choose System > AC Power Dly. 2. Select a time delay from the pick list then press Enter.

QS4 Technical Reference Manual

4.13

Programming instructions

What is it you want to do

This is how you do it

Enter location message text for a circuit on a ZB164 or ZA82 card

1. On the Configure menu, choose Card, and then enter the card address number. 2. Choose Text Message, scan in the text, and then press Enter. 3. Choose Exit.

Change the device type of a circuit on a ZB16 4 or ZA82 card

WARNING: Changing the device type of an input circuit to a device type for an output circuit removes the circuit from all input logic groups. Changing the device type of an output circuit to a device type for an input circuit removes the output circuit from all output groups. 1. On the Configure menu, choose Card, and then enter the card address number. 2. Choose Device Type, select the device type from the pick list, and then press Enter. 3. Choose Exit.

Change the device type of the NAC circuits on the SLIC AutoLearn defaults: NAC1 device type is Visible; NAC 2 device type is Common Alarm Output Common Alarm Output circuits turn on automatically when an input signals an alarm event. Visible and Audible output circuits must be placed in an Output Group in order to turn them on. The AutoLearn utility automatically places Visible circuits in an Output Group

WARNING: Changing an output circuit from a Common Alarm Output device type to an Audible device type does not automatically place the Audible circuit in an Output Group. You must add the Audible Circuit to the Output Group manually or the Audible circuit will not turn on. 1. On the Configure menu, choose Cards > Edit then enter the card address number. 2. Choose Config Card. 3. Choose NAC 1 then choose the device type for NAC 1. 4. Choose NAC 2 then choose the device type for NAC 2. 5. Choose Exit > Save Edits, then wait while the database is updated.

4.14

QS4 Technical Reference Manual

Programming instructions

What is it you want to do

This is how you do it

Change the performance class of the Signature loop wiring AutoLearn default: Wiring is Class B.

1. On the Configure menu, choose Cards > Edit then enter the card address number. 2. Choose Config Card. 3. Choose Wiring Class then choose how the loop is wired to the SLIC. 4. Choose Exit > Save Edits, then wait while the database is updated.

Enter location message text for an automatic detector

1. On the Configure menu, choose Cards > Edit and then enter the card address number of the loop controller. 2. Choose Config Detect > Edit > Enter Serial # and then scan or enter the detector's serial number. 3. Choose Message then scan in the text that you want sent when the detector signals an event. 4. Choose Exit > Save Edits.

Change the Alarm Sensitivity setting of a smoke detector

WARNING: Selection of the appropriate detector technology and sensitivity settings should result from a careful analysis of the hazard, environmental conditions, and expected results. 1. On the Configure menu, choose Cards > Edit and then enter the card address number of the loop controller. 2. Choose Config Detect > Edit > Enter Serial # and then scan or enter the detector's serial number. 3. Choose Sensitivity then choose the alarm sensitivity setting you want the detector to use. Refer to Table 4-5 and Table 4-6. 4. Choose Exit > Save Edits.

QS4 Technical Reference Manual

4.15

Programming instructions

What is it you want to do

This is how you do it

Change the Alarm Verification setting of a smoke detector

1. On the Configure menu, choose Cards > Edit and then enter the card address number of the loop controller. 2. Choose Config Detect > Edit > Enter Serial # and then scan or enter the detector's serial number. 3. Choose Verification then choose the length of the alarm verification period. 4. Choose Exit > Save Edits.

Change the Prealarm setting of a smoke detector

WARNING: Prealarm obscuration levels below 80% should not be used without full knowledge of the possible consequences. 1. On the Configure menu, choose Cards > Edit and then enter the card address number of the loop controller. 2. Choose Config Detect > Edit > Enter Serial # and then scan or enter the serial number of the detector. 3. Choose Pre-Alarm then choose the warning threshold setting you want the detector to use. Refer to Table 4-5 and Table 4-6. 4. Choose Exit > Save Edits.

4.16

QS4 Technical Reference Manual

Programming instructions
Table 4-5: %Obscuration levels for SIGAIPHS, SIGAPS, and SIGAPHS
Alarm Obscuration Levels Sensitivity Settings %Obscuration Prealarm Settings 95% 90% 85% 80% 75% 70% 65% 60% 55% 50% 45% 40% 35% 30% 25% 20% 15% 10% 5% 0.95% 0.90% 0.85% 0.80% 0.75% 0.70% 0.65% 0.60% 0.55% 0.50% 0.45% 0.40% 0.35% 0.30% 0.25% 0.20% 0.15% 0.10 0.05 Most 1.00% More 2.00% Normal 2.50% Less 3.00% Least 3.50%

Prealarm Obscuration Levels 1.90% 1.80% 1.70% 1.60% 1.50% 1.40% 1.30% 1.20% 1.10% 1.00% 0.90% 0.80% 0.70% 0.60% 0.50% 0.40% 0.30% 0.20% 0.10% 2.38% 2.25% 2.13% 2.00% 1.88% 1.75% 1.63% 1.50% 1.38% 1.25% 1.13% 1.00% 0.88% 0.75% 0.13% 0.50% 0.38% 0.25% 0.13% 2.85% 2.70% 2.55% 2.40% 2.25% 2.10% 1.95% 1.80% 1.65% 1.50% 1.35% 1.20% 1.05% 0.90% 0.31% 0.60% 0.45% 0.30% 0.15% 3.33% 3.15% 2.98% 2.80% 2.63% 2.45% 2.28% 2.10% 1.93% 1.75% 1.58% 1.40% 1.23% 1.05% 0.88% 0.70% 0.53% 0.35% 0.18%

Note: Shaded prealarm settings not available for SIGAIPHS

Table 4-6: %Obscuration levels for SIGAIS


Alarm Obscuration Levels Sensitivity Settings %Obscuration Prealarm Settings 95% 90% 85% 80% 75% 70% 65% 60% 55% 50% 0.67% 0.63% 0.60% 0.56% 0.53% 0.49% 0.46% 0.42% 0.39% 0.35% Most 0.7% More 1.00% Normal 1.20% Less 1.40% Least 1.6%

Prealarm Obscuration Levels 0.95% 0.90% 0.85% 0.80% 0.75% 0.70% 0.65% 0.60% 0.55% 0.50% 1.14% 1.08% 1.02% 0.96% 0.90% 0.84% 0.78% 0.72% 0.66% 0.60% 1.33% 1.26% 1.19% 1.12% 1.05% 0.98% 0.91% 0.84% 0.77% 0.70% 1.52% 1.44% 1.36% 1.28% 1.20% 1.12% 1.04% 0.96% 0.88% 0.80%

QS4 Technical Reference Manual

4.17

Programming instructions

What is it you want to do

This is how you do it

Enter location message text for a circuit on a SIGA module

1. On the Configure menu, choose Cards > Edit and then enter the card address number of the loop controller. 2. Choose Config Module > Edit > Enter Serial # and then scan or enter the serial number of the module. 3. For a single-address module or the first address of a dual-address module, choose Device 1. or For the second address of a dual-address module, choose Device 2. 4. 5. Choose Message, scan in the text, and then press Enter. Choose Exit.

Change the device type for a circuit on a SIGA module Note: The device types shown in the pick lists vary depending on the SIGA module. The device types shown in the pick lists for the second address of a dual-address module also vary depending on the device type chosen for the first address.

1. On the Configure menu, choose Cards > Edit and then enter the card address number of the loop controller. 2. Choose Config Module > Edit > Enter Serial # and then scan or enter the serial number of the module. 3. For a single-address module or the first address of a dual-address module, choose Device 1. or For the second address of a dual-address module, choose Device 2. 4. Choose Type, select a device type from the pick list, and then press Enter. 5. Choose Exit.

4.18

QS4 Technical Reference Manual

Programming instructions

What is it you want to do

This is how you do it

Change the personality code for a circuit on a SIGA module Note: The personality codes shown in the pick lists vary depending on the SIGA module and the chosen device type.

1. On the Configure menu, choose Cards > Edit and then enter the card address number of the loop controller. 2. Choose Config Module > Edit > Enter Serial # and then scan or enter the serial number of the module. 3. For a single-address module or the first address of a dual-address module, choose Device 1. or For the second address of a dual-address module, choose Device 2. 4. Choose Personality, select a personality code from the pick list, and then press Enter. 5. Choose Exit.

Enable the loop controller mapping function AutoLearn default: Mapping disabled

1. Press Menu. 2. Log onto the panel as a Level 4 operator. 3. Choose Enable > Loop Mapping. 4. Enter the card number of the SLIC that connects to the device you want to replace. Wait until mapping finishes before continuing. 5. Choose Cards > Edit. 6. Enter the card number of the SLIC that connects to the device you want to replace. 7. Choose Accept Map. If actual and expected data for detectors and modules are the same, press Enter. 8. Choose Exit > Exit > Save.

QS4 Technical Reference Manual

4.19

Programming instructions
Table 4-7: Device type descriptions Alarm Alarm Output Device type assigned to IDC circuits that connect to automatic or a combination of automatic and manual alarm-signal initiating devices. Alarm circuits signal Alarm Active events. Device type assigned to IDC/NAC circuits that connect to notification appliances that you want turned on automatically when the panel processes an alarm signal. Alarm Output circuits turn off when you press Alarm Silence and turn on when you press Drill. Device type assigned to IDC/NAC circuits that connect to audible notification appliances (horns). Audible circuits turn off when you press Alarm Silence and turn on when you press Drill. Device type assigned to IDC circuits that connect to automatic alarm-signal initiating devices that detect a rise in the surrounding temperature. Heat circuits signal Heat Alarm events. Device type assigned to IDC circuits that connect to monitor-signal initiating devices that monitor the operation of ancillary system functions. Monitor circuits signal Monitor events. Device type assigned to IDC/NAC circuits that supervise their output wiring for opens and shorts. Output circuits do not turn off when you press Alarm Silence or turn on when you press Drill. Device type assigned to IDC circuits that connect to manually operated alarm-signal initiating devices. Pull circuits signal Pull Station events. Device type assigned to IDC circuits that connect to supervisory-signal initiating devices that detect abnormal conditions that could make the sprinkler system inoperative or ineffective. Supervisory circuits signal Supervisory events. Device type assigned to IDC circuits that connect to supervisory-signal initiating devices that detect when someone tampers with a component of the sprinkler system. Tamper circuits signal Tamper events. Device type assigned to IDC circuits that connect to automatic alarm-signal initiating devices that use alarm verification. Verified Smoke circuits signal Alarm Verify events when the fire condition is first detected then Alarm Active events after verifying the fire condition exists. Device type assigned to IDC/NAC circuits that connect to visual notification appliances (strobes). Visible circuits do not turn off when you press Alarm Silence or turn on when you press Drill unless programmed to do so. Device type assigned to IDC circuits that connect to alarm-signal initiating devices that detect water flowing through the sprinkler system. Water Flow circuits signal Waterflow events.

Audible

Heat Monitor Output

Pull Supervisory

Tamper

Verified Smoke

Visible

Water Flow

4.20

QS4 Technical Reference Manual

Programming instructions

Setting up an Output Group


Before you begin Before you begin, you should complete an Output Group Programming Worksheet (Figure 4-8) for each Output group. Keep a copy for your records. To set up an Output Group: 1. On the control panel, press Menu. 2. Choose Login then enter the password required for Level 4 access. 3. Choose Program > Configure > Output. 4. To program a new Output group, choose Add. or To edit an existing Output group, choose Edit, select the group from the pick list, and then press Enter. 5. Add the responses. 6. After you finish entering the responses, you should review them to make sure they are correct. Adding a response that activates an output circuit 1. Choose Responses. 2. Choose Active or Trouble 3. Choose Add > Relay, then enter the circuit address where CC is the card number and DDD is the circuit number. 4. Choose the activation setting. 5. Choose Exit > Save Edits. Adding a response that activates a delay 1. Choose Responses. 2. Choose Active or Trouble. 3. Choose Add > Delay. 4. Choose Delay Type, then choose when to initiate the delay response. 5. Choose Delay Time, press Del four times, and then enter how many seconds you want the delay to last. 6. Choose Exit > Save Edits.

QS4 Technical Reference Manual

4.21

Programming instructions

Adding a response that sends a dialer string

1. Choose Responses. 2. Choose Active or Trouble. 3. Choose Add > Dialer. 4. Select an account number from the pick list, and then press Enter. 5. Choose Send On, select when to send the dialer string from the pick list, and then press Enter. 6. Choose Priority, select the priority classification from the pick list, and then press Enter. 7. Choose String, then enter the message you want sent. 8. Choose Exit > Save Edits.

Reviewing your responses

1. Choose Review. 2. Choose Active to review the active responses. or Choose Trouble to review the trouble responses.

4.22

QS4 Technical Reference Manual

Programming instructions
Table 4-8: Response code definitions Response PppCccDddd 1234 Description This is what the panel display looks like when you review a response for an output circuit. P:pp C:cc D:ddd is the address of the of the output circuit (P = panel number, C = card number, D = device number) 1 is the command direction (B = Both activation and restoration, A = Activation only, R = Restoration only) 2 is the command (N = no operation, A = Activate, E = Enable, R = Restore, I = Disable, D = Delay) 3 is the priority attribute (S = Set, A = Latch, L = Low, M = Medium, H = High) 4 is the command attribute (S = Set, R = Reset, W = 20 bpm, F = 120 bpm, T = Temporal)

PppCccDddd 1234

This is what the panel display looks like when you review a response for an LED. P:pp C:cc D:ddd is the address of the of the output circuit (P = panel number, C = card number, D = device number) 1 is the command direction (B = Both activation and restoration, A = Activation only, R = Restoration only) 2 is the command (N = no operation, A = Activate, E = Enable, R = Restore, I = Disable, D = Delay) 3 is the priority attribute (S = Set, A = Latch, L = Low, M = Medium, H = High) 4 is the command attribute (S = Steady, R = Restore, W = Slow Blink, F = Fast Blink)

Delay: ssss 1

This is what the panel display looks like when you review a response for delay. ssss is the amount of delay in seconds 1 is the command direction (B = Both activation and restoration, A = Activation only, R = Restoration only)

ACCT12QEEEGGPPP or ACCT12PP

This is what the panel display looks like when you review a response for dialer string. ACCT is the 4-digit subscriber account number (00009999) 1 is the priority attribute (L = Life Safety, P = Property, S = System Integrity) 2 s the command direction (B = Both activation and restoration, A = Activation only, R = Restoration only) For Contact ID dialer strings: Q is the event qualifier (1 = activation event, 3 = restoration event) EEE is the event code. See Table 4-9. GGPPP is the point being reported For 4/2 dialer strings: PP is the point being reported (0099)

QS4 Technical Reference Manual

4.23

Programming instructions
Table 4-9: Contact ID Event Codes 100 Medical alarm 101 Pendant transmitter 102 Fail to report in 110 Fire Alarm 111 Smoke 112 Combustion 113 Water Flow 114 Heat 115 Pull Station 116 Duct 117 Flame 118 Near alarm 120 Panic Alarm 121 Duress 122 Silent 123 Audible 130 Burglar Alarm 131 Perimeter 132 Interior 133 24 Hour 134 Entry/Exit 135 Day/Night 136 Outdoor 137 Tamper 138 Near alarm 140 General Alarm 141 Polling loop open 142 Polling loop short 143 Expansion module failure 144 Sensor tamper 145 Expansion module failure 150 and 160 24-hour NonBurglary 151 Gas detection 152 Refrigeration 153 Loss of heat 154 Water leakage 155 Foil break 156 Day trouble 157 Low bottled gas level 158 High temperature 159 Low temperature 161 Loss of air flow 200 and 210 Fire Supervisory 201 Low water pressure 202 Low CO2 203 Gate valve sensor 204 Low water level 205 Pump activated 206 Pump failure 300 and 310 System Troubles 301 AC loss 302 Low system battery 303 RAM checksum bad 304 ROM checksum bad 305 System reset 306 Panel program changed 307 Selftest failure 308 System shutdown 309 Battery test failure 310 Ground fault 320 Sounder/Relay Trouble 321 Bell 1 322 Bell 2 323 Alarm relay 324 Trouble relay 325 Reversing 330 and 340 System Peripheral Trouble 331 Polling loop open 332 Polling loop short 333 Expansion module failure 334 Repeater failure 335 Local printer paper out 336 Local printer failure 350 and 360 Communication Trouble 351 Telco 1 fault 352 Telco 2 fault 353 Long range radio 354 Fail to communicate 355 Loss of radio supervision 356 Loss of central polling 370 Protection LoopTrouble 371 Protection loop open 372 Protection loop short 373 Fire trouble 380 Sensor Trouble 381 Loss of supervisory (RF) 382 Loss of supervisory (RPM) 383 Sensor tamper 384 RF transmitter low battery 400 Open/Close 401 Open/Close by user 402 Group open/close 403 Automatic open/close 404 Late to open/close 405 Deferred open/close 406 Cancel 407 Remote arm/disarm 408 Quick arm 409 Keyswitch open/close 410 Remote Access 411 Call request made 412 Success Download access 413 Unsuccessful access 414 System shutdown 415 Dialer shutdown

4.24

QS4 Technical Reference Manual

Programming instructions
Table 4-9: Contact ID Event Codes (cont.) 420 Access Control 421 Access denied 422 Access report by user 441 Stay arming 451 Early opening/closing 452 Late opening/closing 453 Late to open 454 Late to close 455 Autoarm failure 500 and 510 System Disable 520 Sounder/Relay Disable 521 Bell 1 disable 522 Bell 2 disable 523 Alarm relay disable 524 Trouble relay disable 525 Reversing relay disable 530 and 540 System Peripheral Disable 550 and 560 Communication Disable 551 Dialer disable 552 Radio transmitter 570 Disable Bypasses 570 Zone bypass 571 Fire zone bypass 572 24 Hour zone bypass 573 Burglary zone bypass 574 Group bypass 600 Test/Misc. 601 Manual trigger test 602 Periodic test report 603 Periodic RF transmission 604 Fire test 605 Status report to follow 606 Listenin follow 607 Walk Test mode 621 Event Log reset 622 Event Log 50% full 623 Event Log 90% full 624 Event log overflow 625 Time/Date reset 626 Time/Date inaccurate 627 Program mode entry 628 Program mode exit 631 Exception schedule change

QS4 Technical Reference Manual

4.25

Programming instructions

Setting up a Zone
Before you begin Before you begin, you should complete a Zone Programming Worksheet (Figure 4-9) for each Zone. Keep a copy for your records. You will also need to refer to the Output Group programming worksheets. To set up a Zone: 1. On the control panel, press Menu. 2. Choose Login then enter the password required for Level 4 access. 3. Choose Program > Configure > Zone. 4. To program a new Zone, choose Add, and then choose a zone type (Alarm, Supervisory, or Monitor). or Choose Edit, select an existing zone from the pick list, and then press Enter. Configure the Zone 1. Choose Message, scan in the message text, and then press Enter. 2. Choose Members, then for each device that comprises the Zone: Choose Device Address, then enter the member's device number from the worksheet or Choose Enter Serial#, scan in or enter the member's serial number. 3. Choose Review to verify which devices you added to the Zone. If you added any devices in error, delete them. 4. Choose Output Group > Add, then select the Output group from the pick list that contains the responses you want activated, and then press Enter. Repeat for each Output group you want to add. 5. Choose Review to verify which Output groups you added to the Zone. If you added any Output groups in error, remove them. 6 For coded systems, choose Coding, and then enter the Zone Code.

4.26

QS4 Technical Reference Manual

Programming instructions Job Name: Panel:


# of CMS receivers: CMS phone numbers:

Page Card: 14
1 2 Receiver 1: #1) Receiver 2: #1) Receiver 1: #2) Receiver 2: #2)

of

Retry Count:

5 6 7 8 9 10 Format: 4/2 Contact ID Panel normal: CMS receiver to dial: 1 2 Format: 4/2 Contact ID Panel normal: CMS receiver to dial: 1 2 Format: 4/2 Contact ID Panel normal: CMS receiver to dial: 1 2 Format: 4/2 Contact ID Panel normal: CMS receiver to dial: 1 2 Format: 4/2 Contact ID Panel normal: CMS receiver to dial: 1 2 Format: 4/2 Contact ID Panel normal: CMS receiver to dial: 1 2 Format: 4/2 Contact ID Panel normal: CMS receiver to dial: 1 2 Format: 4/2 Contact ID Panel normal: CMS receiver to dial: 1 2 Panel off-normal: Panel off-normal: Panel off-normal: Panel off-normal: Panel off-normal: Panel off-normal: Panel off-normal: Panel off-normal:

Account Number: Test strings: Time: Account Number: Test strings: Time: Account Number: Test strings: Time: Account Number: Test strings: Time: Account Number: Test strings: Time: Account Number: Test strings: Time: Account Number: Test strings: Time: Account Number: Test strings: Time:

Figure 4-1: DLD Programming Worksheet (sheet 1 of 2)

QS4 Technical Reference Manual

4.27

Programming instructions Job Name: Panel: Card: 14 Page of

Default Alarm Message:

Account Number: Active Message: Restore Message:

Default Trouble Message:

Account Number: Active Message: Restore Message:

Default Supervisory Message:

Account Number: Active Message: Restore Message:

Figure 4-1 DLD Programming Worksheet (sheet 1 of 2)

4.28

QS4 Technical Reference Manual

Programming instructions Job Name: Panel: Card: Page of

001

Device Type: Text Message: 1) 2)

002

Device Type: Text Message: 1) 2)

IDC 001 IDC 002 IDC 003 IDC/NAC 004

003

Device Type: Text Message: 1) 2)

004

Device Type: Text Message: 1) 2)

IDC/NAC 008 IDC 007 IDC 006 IDC 005

005

Device Type: Text Message: 1) 2) Defaults: Alarm for IDC 001 003 and IDC 005 007, Common Alarm Output for IDC/NAC 004, Visual for IDC/NAC 008

006

Device Type: Text Message: 1) 2)

007

Device Type: Text Message: 1) 2)

008

Device Type: Text Message: 1) 2)

Figure 4-2: ZA82 Programming Worksheet

QS4 Technical Reference Manual

4.29

Programming instructions Job Name: Panel:


001 Device Type: Text Message: 1) 2) 002 Device Type: Text Message: 1) 2) 003 Device Type: Text Message: 1) 2) 004 Device Type: Text Message: 1) 2) 005 Device Type: Text Message: 1) 2) 006 Device Type: Text Message: 1) 2) 007 Device Type: Text Message: 1) 2) 008 Device Type: Text Message: 1) 2) 009 Device Type: Text Message: 1) 2) 010 Device Type: Text Message: 1) 2) 011 Device Type: Text Message: 1) 2) 016 Device Type: Text Message: 1) 2) 015 Device Type: Text Message: 1) 2) 014 Device Type: Text Message: 1) 2) 013 Device Type: Text Message: 1) 2) 012 Device Type: Text Message: 1) 2)
IDC 012 IDC 011 IDC 010 IDC/NAC 013 IDC/NAC 014 IDC/NAC 015 IDC/NAC 016 IDC 001 IDC 002 IDC 003 IDC 004

Page Card:
IDC 005 IDC 006 IDC 007 IDC 008 IDC 009

of

Defaults: Alarm for IDC 001012, Common Alarm Output for IDC/NAC 013014, Visual for IDC/NAC 015 016

Figure 4-3: ZB164 Programming Worksheet

4.30

QS4 Technical Reference Manual

Programming instructions Job Name: Panel: Card: Page of

001

NC (normally-closed) NO (normally-open) Device type:

004 003 002 001

004+

004

JP4

002

NC (normally-closed) NO (normally-open) Device type:


NC NO

003

NC (normally-closed) NO (normally-open) Device type:


NC

004

NC (normally-closed) NO (normally-open) Device type:


NO

005

NC (normally-closed) NO (normally-open) Device type:

005 006 007 008

JP8

008+

008

006

NC (normally-closed) NO (normally-open) Device type:

007

NC (normally-closed) NO (normally-open) Device type:

008

NC (normally-closed) NO (normally-open) Device type:

Figure 4-4: ZA82 Programming Worksheet

QS4 Technical Reference Manual

4.31

Programming instructions Job Name: Panel: Card: NAC 1 device type: Audible Visible Wiring class: Class A Class B Number of detector addresses used on loop: Number of module addresses used on loop: Card: NAC 1 device type: Audible Visible Wiring class: Class A Class B Number of detector addresses used on loop: Number of module addresses used on loop: Card: NAC 1 device type: Audible Visible Wiring class: Class A Class B Number of detector addresses used on loop: Number of module addresses used on loop: Card: NAC 1 device type: Audible Visible Wiring class: Class A Class B Number of detector addresses used on loop: Number of module addresses used on loop: NAC 2 device type: Audible Visible NAC 2 device type: Audible Visible NAC 2 device type: Audible Visible NAC 2 device type: Audible Visible Page of

Figure 4-5: SLIC Programming Worksheet

4.32

QS4 Technical Reference Manual

Programming instructions Job Name: Panel: Card: Page of

Model: Sensitivity: Verification: Pre-Alarm: Base type: Message: Most None None

S/N More 12 s 20% Relay Normal 24 s 40% Isolator 2)

Device: Less 36 s 60% Least 60 s 80%

Standard 1)

Model: Sensitivity: Verification: Pre-Alarm: Base type: Message: Most None None

S/N More 12 s 20% Relay Normal 24 s 40% Isolator 2)

Device: Less 36 s 60% Least 60 s 80%

Standard 1)

Model: Sensitivity: Verification: Pre-Alarm: Base type: Message: Most None None

S/N More 12 s 20% Relay Normal 24 s 40% Isolator 2)

Device: Less 36 s 60% Least 60 s 80%

Standard 1)

Model: Sensitivity: Verification: Pre-Alarm: Base type: Message: Most None None

S/N More 12 s 20% Relay Normal 24 s 40% Isolator 2)

Device: Less 36 s 60% Least 60 s 80%

Standard 1)

Figure 4-6: Signature Detector Programming Worksheet

QS4 Technical Reference Manual

4.33

Programming instructions Job Name: Panel: Card: Page of

Model: Device #1 Device Type: Personality: Message: 1) 2)

S/N

Device: 1st) Device #2 Device Type: Personality: Message: 1) 2)

2nd)

Model: Device #1 Device Type: Personality: Message: 1) 2)

S/N

Device: 1st) Device #2 Device Type: Personality: Message: 1) 2)

2nd)

Model: Device #1 Device Type: Personality: Message: 1) 2)

S/N

Device: 1st) Device #2 Device Type: Personality: Message: 1) 2)

2nd)

Model: Device #1 Device Type: Personality: Message: 1) 2)

S/N

Device: 1st) Device #2 Device Type: Personality: Message: 1) 2)

2nd)

Figure 4-7: Signature Module Programming Worksheet

4.34

QS4 Technical Reference Manual

Programming instructions Job Name: Panel: Output Group: Page of

Response: __ __ __ Relay Delay Dialer

Type: Active Trouble On 20 bpm 120 bpm Temporal

Device: __ __ __ __ __

Delay Type: Act and Restoration Activation Restoration Time: __ __ __ __s Account No.: __ __ __ __ Send On: Activation Restoration

Priority: Life Safety Property System Integrity String: (CID) __ __ __ __ __ __ __ __ __ (4/2) __ __

Response: __ __ __ Relay Delay Dialer

Type: Active Trouble On 20 bpm 120 bpm Temporal

Device: __ __ __ __ __

Delay Type: Act and Restoration Activation Restoration Time: __ __ __ __s Account No.: __ __ __ __ Send On: Activation Restoration

Priority: Life Safety Property System Integrity String: (CID) __ __ __ __ __ __ __ __ __ (4/2) __ __

Response: __ __ __ Relay Delay Dialer

Type: Active Trouble On 20 bpm 120 bpm Temporal

Device: __ __ __ __ __

Delay Type: Act and Restoration Activation Restoration Time: __ __ __ __s Account No.: __ __ __ __ Send On: Activation Restoration

Priority: Life Safety Property System Integrity String: (CID) __ __ __ __ __ __ __ __ __ (4/2) __ __

Response: __ __ __ Relay Delay Dialer

Type: Active Trouble On 20 bpm 120 bpm Temporal

Device: __ __ __ __ __

Delay Type: Act and Restoration Activation Restoration Time: __ __ __ __s Account No.: __ __ __ __ Send On: Activation Restoration

Priority: Life Safety Property System Integrity String: (CID) __ __ __ __ __ __ __ __ __ (4/2) __ __

Figure 4-8: Output Group Programming Worksheet

QS4 Technical Reference Manual

4.35

Programming instructions Job Name: Panel: Zone: Page of

Zone Type: Alarm Supervisory Monitor Zone Code: Message: 1) 2)

Zone Members (32 max):

Output groups (6 max):

Figure 4-9: Zone Programming Worksheet

4.36

QS4 Technical Reference Manual

Chapter 5

Standard applications

Summary This chapter provides simplified wiring schematics for standard applications. Content Notification appliance circuits 5.2 Initiating device circuits 5.5 Coded alarm signaling 5.8 Remote station protective signaling system 5.10 Auxiliary protective signaling 5.12

QS4 Technical Reference Manual

5.1

Standard applications

Notification appliance circuits


SLIC NAC1 B+ NAC1 B

Note: The plus and minus symbols indicate signal polarity when the NAC circuit is turned on.

NAC1 A+ NAC1 A UL/ULC LISTED 10 K EOLR

NAC2 B+ NAC2 B

NAC2 A+ NAC2 A UL/ULC LISTED 10 K EOLR

Typical Class A NAC circuits

SLIC NAC1 B+ NAC1 B NAC1 A+ NAC1 A NOT USED UL/ULC LISTED 10 K EOLR

Note: The plus and minus symbols indicate signal polarity when the NAC circuit is turned on.

NAC2 B+ NAC2 B NAC2 A+ NAC2 A NOT USED UL/ULC LISTED 10 K EOLR

Typical Class B NAC circuits

5.2

QS4 Technical Reference Manual

Standard applications

UL/ULC LISTED 47 K EOLR

10 9

SIGACC1
8 7 6 5 4 3 2 1

SIGARM1
8 7 6 5 4 3 2 1

PS6 AUX(n) COM

SLIC LOOP B+ LOOP B LOOP A+ LOOP A TO DATA OUT TERMINALS ON LAST DEVICE (CLASS A ONLY)

TO DATA IN TERMINALS ON NEXT DEVICE

Note: The plus and minus symbols indicate signal polarity when the NAC circuit is turned on. Typical NAC riser wiring

QS4 Technical Reference Manual

5.3

Standard applications

ZB164 Z13+ Z13 UL/ULC LISTED 10 K EOLR

Z14+ Z14

UL/ULC LISTED 10 K EOLR

Z15+ Z15

UL/ULC LISTED 10 K EOLR

Z16+ Z16

UL/ULC LISTED 10 K EOLR

Typical Class B NAC circuits

ZA82 ZONE 4 B+ ZONE 4 B ZONE 4 A+ ZONE 4 A UL/ULC LISTED 10 K EOLR

NAC1 B+ NAC1 B NAC1 A+ NAC1 A UL/ULC LISTED 10 K EOLR

Typical Class A NAC circuit

5.4

QS4 Technical Reference Manual

Standard applications

Initiating device circuits


PS6 24VDC+ 24VDC JP2 ACC PWR SMK PWR
8 7

UL/ULC LISTED EOL RELAY

UL/ULC LISTED 47 K EOLR

SIGACT1
4 3 2 1

SLIC LOOP B+ LOOP B LOOP A+ LOOP A TO DATA IN TERMINALS ON NEXT DEVICE TO DATA OUT TERMINALS ON LAST DEVICE (CLASS A ONLY)

Typical four-wire smoke detector circuit

PS6 24VDC+ 24VDC JP2 ACC PWR SMK PWR 2SMK UL/ULC LISTED 22 K EOLR UL/ULC LISTED 15 K EOLR

14 13 3-2-1 12 11 10 9

SIGAUM
8 7 6 5 4 3 2 1

SLIC LOOP B+ LOOP B LOOP A+ LOOP A TO DATA OUT TERMINALS ON LAST DEVICE (CLASS A ONLY)

TO DATA IN TERMINALS ON NEXT DEVICE

Typical Class B two-wire smoke detector circuit

QS4 Technical Reference Manual

5.5

Standard applications

PS6 24VDC+ 24VDC JP2 ACC PWR SMK PWR 2SMK UL/ULC LISTED 22 K EOLR

14 13 3-2-1 12 11 10 9

SIGAUM
8 7 6 5 4 3 2 1

SLIC LOOP B+ LOOP B LOOP A+ LOOP A TO DATA OUT TERMINALS ON LAST DEVICE (CLASS A ONLY)

TO DATA IN TERMINALS ON NEXT DEVICE

Typical Class A two-wire smoke detector circuit

ZB164 Z(n)+ Z(n) UL/ULC LISTED 4.7 K EOLR

Typical Conventional Class B IDC circuit

ZA82 ZONE (n) B+ ZONE (n) B ZONE (n) B+ ZONE (n) B UL/ULC LISTED 4.7 K EOLR

Typical Conventional Class A IDC circuit

5.6

QS4 Technical Reference Manual

Standard applications
UL/ULC LISTED EOL RELAY PS6 24VDC+ 24VDC JP2 ACC PWR SMK PWR

UL/ULC LISTED 4.7 K EOLR

ZB164 Z(n)+ Z(n)

Typical Conventional Class B four-wire smoke detector circuit

PS6 24VDC+ 24VDC JP2 ACC PWR SMK PWR UL/ULC LISTED EOL RELAY

ZA82 ZONE (n) B+ ZONE (n) B ZONE (n) A+ ZONE (n) A UL/ULC LISTED 4.7 K EOLR

Typical Conventional Class A four-wire smoke detector circuit

QS4 Technical Reference Manual

5.7

Standard applications

Coded alarm signaling


1 2 3

1. FACP: Fire alarm control panel with a CPU, PS6, ZB164, and standby batteries. 2. MFCA Accessory Enclosure: Used for mounting the remote fire alarm equipment. 3. CDR3 Bell Coder: Provides coded alarm signals for 24 Vdc notification appliance circuits and one of three evacuation signals (temporal, 60 bpm, and 90 bpm). Note: CDR3 must have firmware version greater than 2.0.

Notes Place the MFCA and the FACP in the same room and connect using a section of conduit no greater than 20 ft in length. Run all wiring between cabinets through the conduit. Set SW6 on CDR3 to ON. Refer to the CDR 3 installation sheet for programming information. Install a 10 k EOLR across TB21 and TB2 2, and TB211 and TB212 on the CDR3. Set JP2 on the PS6 for ACC PWR If the system uses a NAC circuit on an SLIC to output the coded signal, program the NAC circuit signal rate as Steady. If the system uses the NAC 1 circuit on an SLIC to output the coded signal to audible notification appliances, set JP1 and JP2 on the SLIC to EXT.

Figure 5-1: Typical equipment layout, coded alarm signaling application

5.8

QS4 Technical Reference Manual

Standard applications

PS6TB116 PS6TB118 PS6TB112 PS6TB111

PS6TB33 PS6TB31

NAC RISER NAC RISER + SW1 TB1 JP1 JP2 TB2 10K 10K

CDR3

Figure 5-2: Coded alarm signaling wiring (coded alarm signal only)

PS6TB116 PS6TB118 PS6TB112 PS6TB111

PS6TB33 PS6TB31

NAC RISER NAC RISER + SW1 TB1 JP1 JP2 TB2 10K 10K

CDR3

Figure 5-3: Coded alarm signaling wiring (coded signal followed by evacuation signal)

QS4 Technical Reference Manual

5.9

Standard applications

Remote station protective signaling system


1 2 3

1. FACP: Fire alarm control panel with a CPU, PS6, ZB164, and standby batteries. 2. MFCA Accessory Enclosure: Used for mounting the remote fire alarm equipment. 3. RPM Reverse Polarity Module: Provides three independent reverse polarity signals (alarm, supervisory, trouble) for transmitting system status to a remote location.

Notes Place the MFCA and the FACP in the same room and connect using a section of conduit no greater than 20 ft in length. Run all wiring between cabinets through the conduit. Set JP2 on the PS6 for ACC PWR. Install a 3.9 K EOLR across TB11 and TB1 2 on the RPM.

Figure 5-4: Typical equipment layout, Remote station protective signaling application

5.10

QS4 Technical Reference Manual

Standard applications

PS6 RELAY 1 NO RELAY 1 C RELAY 2 C RELAY 2 NO RELAY 3 C RELAY 3 NO 24VDC+ 24VDC TRBL +24V COM SUPV ALRM

RPM CITY BOX+ JP1 CITY BOX ALARM+ ALARM TROUBLE+ TROUBLE SUPV+ SUPV OFF-SITE MONITORING
3.9 K

Note: Plus and minus symbols indicate signal polarity when the circuit is active.

Figure 5-5: Remote station protective signaling wiring

QS4 Technical Reference Manual

5.11

Standard applications

Auxiliary protective signaling


Wire as shown in Figure 5-6. Program the SIGACC1 as a common alarm output device. Plus and minus symbols indicate signal polarity with the circuit turned on.

10 9

1 2

SIGACC1
8 7 6 5 4 3 2 1

2CTM
2 1

LISTED 24VDC SUPPLY 24VDC+ 24VDC TO NEXT DEVICE SLIC LOOP B+ LOOP B LOOP A+ LOOP A TO DATA OUT TERMINALS ON LAST DEVICE (CLASS A ONLY)

Master box

TO DATA IN TERMINALS ON NEXT DEVICE Municipal circuit

Figure 5-6: Auxiliary protective signaling cabling diagram

5.12

QS4 Technical Reference Manual

Chapter 6

Maintenance instructions

Summary
This chapter provides instructions for maintaining the system.

Content Pseudo point definitions 6.2 Table 6-1: Main Panel pseudo points 6.2 Table 6-2: Remote Annunciator pseudo points 6.2 Table 6-3: Power Supply pseudo points 6.3 Table 6-4: SLIC card pseudo points 6.3 Table 6-5: Dialer pseudo points 6.4 Table 6-6: General CPU pseudo points 6.5 Maintenance tasks 6.6

QS4 Technical Reference Manual

6.1

Maintenance instructions

Pseudo point definitions


Table 6-1: Main Panel pseudo points LCD Indication Panel xx Card Communications Panel 01 Reset Extension Panel 01 Service Active Trouble Pnl 0x Database Incompatible Panel 01 Reboot Fault Panel 0x, CH1 Communications Panel 01 Task Failure Card xx Setup Mismatch Dailer Setup Mismatch Power Supply Setup Mismatch Panel 01 LED/Switch display Panel 0x, CH2 Communications Pnl 01 Database Supervision Panel 01 Code Supervision Panel 01, Call For Service Panel 01, ROM Supervision Panel 01 RS232 Port Fault Panel 01 Unexpected Card Panel 01 Switch Latched Panel 01 Loop Database Fault Trouble Trouble Trouble Trouble Trouble Trouble Trouble Trouble Trouble Trouble Trouble Trouble Trouble Trouble Trouble CPU detected an option card not defined in the database. Button either on the main display or on an LED/Switch card has been pressed too long. Internal CPU memory failure with Signature data. Event Type Trouble Monitor/Trouble Trouble Trouble Definition CPU has failed to communicate with the option card at address xx. Signature loop is still resetting. Service group was restored with a device still in the active condition. Changes made to the system programming on the control panel were not updated in this unit. Control panel CPU restarted unexpectedly. Annunciator is not communicating on RS485 channel 1. Internal processing fault. CPU encountered problem configuring the option card at address xx. A problem has occurred with the CPU configuring the dialer card. A problem has occurred with the CPU configuring the POWER supply card. LED/Switch card is not connected. Annunciator is not communicating on RS485 channel 2. Internal CPU memory failure Internal CPU memory failure Internal CPU processing error Internal CPU memory failure

Table 6-2: Remote Annunciator pseudo points LCD Indication Ann 0x Service Active Trouble Ann 0x Database Incompatible Annunciator 0x Reboot Fault Event Type Trouble Trouble Trouble Definition Indicates that a device was left in an active condition after service group has restored. Indicates that the data Indicates CPU has restarted due to internal processing failure.

6.2

QS4 Technical Reference Manual

Maintenance instructions

LCD Indication Ann 0x, CH1 Communications Annunciator 0x Task Failure Ann 0x, LED/ Switch Display Ann 0x, CH2 Communications Ann 0x Database Supervision Ann 0x Code Supervision Ann 0x, Call For Service Ann 0x ROM Supervision Ann 0x RS232 Port Fault Ann 0x Program Mode Ann 0x Switch Latched Annunciator 0x Power Fault

Event Type Trouble Trouble Trouble Trouble Trouble Trouble Trouble Trouble Trouble Trouble Trouble Trouble

Definition Indicates failure to communicate with the main panel on RS485 channel 1. Internal software failure Indicates that a SL30-x has been disconnected or is connected but not defined. Indicates failure to communicate with the main panel on RS485 channel 2. Internal memory failure Internal memory failure Internal software failure Internal memory failure

Panel has entered program mode. Indicates that a button either on the main display or on an SL30-x has been pressed to long. Indicates a loss of power on either of the 24vdc inputs to the RAI card.

Table 6-3: Power Supply pseudo points LCD Indication Battery Charger Fault Battery Wiring or Battery Fault Aux Power 1/2 Shorted Aux Power 3 Shorted Smoke Power Shorted Primary AC Power Failure Excessive Battery Current Check System Wiring Power Supply Card RAM Fault Power Supply Card ROM Fault Power Supply EEPROM Fault Table 6-4: SLIC card pseudo points LCD Indication Card 0x, Loop Wiring Problem Card 0x Map Fault Event Type Trouble Trouble Definition Indicates a break on a Class A signature loop Signature map is different than the one written in memory Event Type Trouble Trouble Trouble Trouble Trouble Trouble Trouble Trouble Trouble Trouble Trouble Definition This fault will occur when the battery charger charging voltage falls below 20.4vdc. Caused by an open in the battery wiring or if the batteries are below 20.4vdc. This point occurs when Aux 1 or Aux 2 power is shorted on the PS6 This point occurs when Aux 3 This point occurs when smoke power is shorted Caused by loss of AC or very low AC. Will go active when PS6 detects over current condition Indicates a ground fault exists on field wiring. Internal memory fault Internal memory fault Internal memory fault

QS4 Technical Reference Manual

6.3

Maintenance instructions

LCD Indication Card 0x, Mapping In Progress Card 0x Unconfig. Device Card 0x, Line Initialization Card 0x, Loop Ground Fault Card 0x, LIM Driver Fault Card 0x, RAM Supervision Card 0x, ROM Supervision Card 0x, EEPROM Supervision Table 6-5: Dialer pseudo points LCD Indication Primary Phone Line:check Telco Secondary Phone Line:check Telco Pri. Receiver Failed to answer Sec. Receiver Failed to answer Dialer Account 1 Fault Dialer Account 2 Fault Dialer Account 3 Fault Dialer Account 4 Fault Dialer Account 5 Fault Dialer Account 6 Fault Dialer Account 7 Fault Dialer Account 8 Fault Dialer ROM Fault Dialer Queue Overflow Dialer Card, RAM Supervision

Event Type Monitor Trouble Monitor Trouble Trouble Trouble Trouble Trouble

Definition Indicates Signature devices are in the process of being mapped. Indicates that a new signature device has been detected on a loop. Occurs after power up or a restart. Indicates signature devices are being initialized. Indicates a ground fault on a signature module. Internal hardware failure. Internal memory fault Internal memory fault Internal memory fault

Event Type Trouble Trouble Trouble Trouble Trouble Trouble Trouble Trouble Trouble Trouble Trouble Trouble Trouble Trouble Trouble

Definition Telephone line has low or no voltage Telephone line has low or no voltage Dialer attempted to dial event to CMS but did not get an answer. Dialer attempted to dial event to CMS but did not get an answer. Indicates dialer did not get proper handshake for event sent to the CMS for Account 1. Indicates dialer did not get proper handshake for event sent to the CMS for Account 2. Indicates dialer did not get proper handshake for event sent to the CMS for Account 3. Indicates dialer did not get proper handshake for event sent to the CMS for Account 4. Indicates dialer did not get proper handshake for event sent to the CMS for Account 5. Indicates dialer did not get proper handshake for event sent to the CMS for Account 6. Indicates dialer did not get proper handshake for event sent to the CMS for Account 7. Indicates dialer did not get proper handshake for event sent to the CMS for Account 8. Internal memory fault Indicates that too many dialer messages are trying to be sent. Internal memory fault

6.4

QS4 Technical Reference Manual

Maintenance instructions
Table 6-6: General CPU pseudo points LCD Indication Startup Response First Alarm First Supervisory First Trouble First Monitor Evacuation Drill Alarm Silence Two Stage Expiration Reset Reset Phase 1 Reset Phase 2 Reset Phase 3 First Disable First Test Two Stage Timer Started User Trouble Trouble Triggered by custom programming. Monitor Monitor Monitor Monitor Trouble Trouble This point goes active anytime reset is pressed. Active during the power down phase of reset. Active during the retard phase of reset. Active during the restoration phase of reset. Activated the first time an item is disabled from the front menu. Activated the first time a service group is started from the front menus. Monitor Monitor This point will go active anytime drill is pressed. This point will go active anytime alarm silence is pressed. Event Type Monitor Alarm Supervisory Trouble Monitor Definition Monitor point that goes active on system startup or after restart. Occurs anytime that the system goes into alarm for the first time. Occurs anytime that the system goes into supervisory for the first time. Occurs anytime that the system goes into a trouble for the first time. Occurs anytime that the system goes into a monitor condition for the first time.

QS4 Technical Reference Manual

6.5

Maintenance instructions

Maintenance tasks
What is it you want to do Change the fuse This is how you do it

1. Switch the circuit breaker that supplies ac power to the control panel to the OFF position. 2. Expose the ac terminal block and pull out the fuse holder. 3. Replace the blown fuse with a new one of the same type and size. 4. Plug the fuse holder back into the ac terminal block. 5. Switch the circuit breaker that supplies ac power to the control panel to the ON position.

Replacing a SIGA device when mapping is disabled)

WARNING: Replacing a device when mapping is disabled leaves the area unprotected. The control panel does not automatically reassign responses to replaced devices when mapping is disabled. To replace devices on a loop that operates with mapping disabled, you must first enable mapping then accept the map. After you replace your devices, you can disable mapping on the loop. Note: Replacement devices must be the same model as the devices being replaced. 1. Press Menu. 2. Log onto the panel as a Level 4 operator. 3. Choose Enable > Loop Mapping. 4. Enter the card number of the SLIC that connects to the device you want to replace. Wait until mapping finishes before continuing. 5. Choose Cards > Edit. 6. Enter the card number of the SLIC that connects to the device you want to replace. 7. Choose Accept Map. If actual and expected data for detectors and modules are the same, press Enter. 8. Choose Exit > Exit > Save and Sync. 9. Replace the device.

6.6

QS4 Technical Reference Manual

Appendix A

System calculations

Summary This appendix provides worksheets for calculating maximum wire lengths for notification and Signature circuits, and for sizing standby batteries. Content Notification appliance circuit maximum wire length calculation A.2 Signature loop maximum wire length calculations A.3 Battery calculation A.8

QS4 Technical Reference Manual

A.1

System calculations

Notification appliance circuit maximum wire length calculation


Use this worksheet to determine the maximum wire length of a notification appliance circuit. Fill in one worksheet for each NAC connected to the panel. Maximum signal loss allowed
1

1.5 1000 1500

Wire resistance per 1000 ft/pair

Total operating current required Maximum wire length Notes

A ft

1. For worst case estimates, assume a 1.5 V line loss and all appliances are clustered at the end of the circuit. 2. Use 3.5 for 12 AWG and 2.5 mm wire, 5.2 for 14 AWG and 1.5 mm wire, 8.0 for 16 AWG 2 2 and 1.0 mm wire, and 13.0 for 18 AWG and 0.75 mm wire. 3. Use the filtered 20 Vdc Average Operating Current ratings found on the installation or catalog sheet of each device.
2 2

A.2

QS4 Technical Reference Manual

System calculations

Signature loop maximum wire length calculations


Use this worksheet to determine the maximum amount of wire you can use to construct a Signature loop. Step 1: Calculate the total amount of wire you can used based on the cable manufacturer's capacitance per foot rating. Total amount of wire shall not exceed the values listed in Table A-1. 500000 Cable capacitance Total wire pF/ft ft

Table A-1: Maximum amount of wire you can use to construct a Signature loop Wire type Twisted pair, nonshielded 25 pF/36 pF/38 pF Twisted pair, shielded 58 pF/82 pF/84 pF Nontwisted pair, nonshielded 20 pF/20 pF/20 pF 14 AWG / 1.5 mm 13157 ft (4010 m) 5952 ft (1814 m) 20000 ft (6096 m) 16 AWG / 1.0 mm 13888 ft (4233 m) 6098 ft (1859 m) 20000 ft (6096 m) 18 AWG / 0.75 mm 20000 ft (6096 m) 8621 ft (2628 m) 20000 ft (6096 m)
2

Step 2: Use Table A-2, Table A-3, Table A-4, and Table A-5 to determine the longest allowable circuit path based on wire size and type, and the number of detector, module, SIGAUMs or MABs installed on the loop. In the illustration below, the longest circuit path (shown in bold lines) is 1240 ft (377.95 m). The total amount of wire comprising the loop is 1740 ft (530.35 m)
10 ft (3.05 m) 200 ft (60.96 m)

FACP

30 ft (9.14 m) 200 ft (60.96 m) J J 200 ft (60.96 m)

100 ft (30.48 m)

1000 ft (304.8 m)

QS4 Technical Reference Manual

A.3

System calculations Table A-2: Longest allowable circuit path with 0 SIGA-UMs or SIGA-MABs configured for 2-wire smokes
Maximum allowable wire distance using nontwisted, nonshielded wire pairs

Signature detector addresses


125 2650 5175 76100 101125 0 125 2650 5175 76100 101125 0 125 2650 5175 76100 101125 0 125 2650 5175 76100 101125 0 125 2650 5175 76100 101125 0 125 2650 5175 76100 101125

Signature module addresses


0 0 0 0 0 125 125 125 125 125 125 2650 2650 2650 2650 2650 2650 5175 5175 5175 5175 5175 5175 76100 76100 76100 76100 76100 76100 101125 101125 101125 101125 101125 101125

18 AWG ft 7437 7038 6638 6238 5839 7267 6867 6467 6068 5668 5268 6697 6297 5897 5498 5098 4698 5906 5250 4633 4051 3498 2973 3931 3404 2899 2413 1945 1493 2631 2165 1713 1274 847 431 m 2267 2145 2023 1901 1780 2215 2093 1971 1849 1728 1606 2041 1919 1798 1676 1554 1432 1800 1600 1412 1235 1066 906 1198 1037 883 735 593 455 802 660 522 388 258 131

16 AWG ft 11815 11180 10545 9910 9275 11544 10909 10275 9640 9005 8370 10639 10004 9369 8734 8099 7464 9383 8340 7360 6435 5558 4723 6245 5407 4605 3833 3089 2371 4180 3439 2721 2023 1345 685 m 3601 3408 3214 3021 2827 3519 3325 3132 2938 2745 2551 3243 3049 2856 2662 2469 2275 2860 2542 2243 1961 1694 1440 1903 1648 1404 1168 942 723 1274 1048 829 617 410 209

14 AWG ft 18792 17782 16772 15762 14752 18361 17351 16342 15332 14322 13312 16921 15911 14901 13891 12881 11871 14923 13265 11707 10235 8839 7512 9932 8601 7324 6096 4913 3771 6649 5470 4328 3218 2140 1089 m 5728 5420 5112 4804 4497 5597 5289 4981 4673 4365 4057 5157 4850 4542 4234 3926 3618 4549 4043 3568 3120 2694 2290 3027 2621 2232 1858 1498 1149 2027 1667 1319 981 652 332

A.4

QS4 Technical Reference Manual

System calculations Table A-3: Longest allowable circuit path with 15 SIGA-UMs or SIGA-MABs configured for 2-wire smokes
Maximum wire distance using nontwisted, nonshielded wire pairs Signature detector addresses 125 2650 5175 76100 101125 0 125 2650 5175 76100 101125 0 125 2650 5175 76100 101125 0 125 2650 5175 76100 101125 0 125 2650 5175 76100 101125 0 125 2650 5175 76100 101125 Signature module addresses 0 0 0 0 0 125 125 125 125 125 125 2650 2650 2650 2650 2650 2650 5175 5175 5175 5175 5175 5175 76100 76100 76100 76100 76100 76100 101125 101125 101125 101125 101125 101125 1386 760 143 422 232 44 2201 1208 227 671 368 69 3501 1921 361 1067 586 110 18 AWG ft 6778 6131 5501 4885 4282 5353 4720 4100 3491 2893 2306 3776 3153 2539 1935 1340 754 2491 1868 1254 648 50 m 2066 1869 1677 1489 1305 1632 1439 1250 1064 882 703 1151 961 774 590 409 230 759 569 382 198 15 16 AWG ft 10768 9741 8739 7760 6802 8504 7498 6513 5546 4597 3663 5999 5009 4034 3075 2130 1197 3957 2967 1992 1030 80 m 3282 2969 2664 2365 2073 2592 2286 1985 1691 1401 1116 1829 1527 1230 937 649 365 1206 904 607 314 24 14 AWG ft 17126 15492 13899 12342 10819 13525 11926 10359 8821 7311 5826 9542 7966 6416 4890 3387 1905 6293 4720 3168 1638 126 m 5220 4722 4236 3762 3298 4122 3635 3157 2689 2228 1776 2908 2428 1956 1491 1032 581 1918 1439 966 499 39

QS4 Technical Reference Manual

A.5

System calculations Table A-4: Longest allowable circuit path with 610 SIGA-UMs or SIGA-MABs configured for 2-wire smokes
Maximum wire distance using nontwisted, nonshielded wire pairs Signature detector addresses 125 2650 5175 76100 101125 0 125 2650 5175 76100 101125 0 125 2650 5175 76100 101125 0 125 2650 5175 76100 101125 0 125 2650 5175 76100 101125 0 125 2650 5175 76100 101125 Signature module addresses 0 0 0 0 0 125 125 125 125 125 125 2650 2650 2650 2650 2650 2650 5175 5175 5175 5175 5175 5175 76100 76100 76100 76100 76100 76100 101125 101125 101125 101125 101125 101125 833 242 254 74 1323 385 403 117 2105 613 642 187 18 AWG ft 5045 4494 3950 3414 2884 4106 3542 2985 2435 1891 1353 2869 2296 1730 1170 617 68 1796 1214 638 69 m 1538 1370 1204 1040 879 1252 1080 910 742 576 412 874 700 527 357 188 21 547 370 195 21 16 AWG ft 8015 7139 6275 5423 4581 6523 5627 4742 3868 3004 2150 4557 3648 2749 1859 979 108 2853 1929 1014 109 m 2443 2176 1913 1653 1396 1988 1715 1445 1179 916 655 1389 1112 838 567 299 33 869 588 309 33 14 AWG ft 12748 11355 9981 8625 7286 10375 8950 7542 6152 4778 3419 7248 5802 4372 2957 1558 172 4537 3067 1613 173 m 3886 3461 3042 2629 2221 3162 2728 2299 1875 1456 1042 2209 1768 1332 901 475 53 1383 935 492 53

A.6

QS4 Technical Reference Manual

System calculations Table A-5: Longest allowable circuit path with 1115 SIGA-UMs or SIGA-MABs configured for 2wire smokes
Maximum wire distance using nontwisted, nonshielded wire pairs Signature detector addresses 125 2650 5175 76100 101125 0 125 2650 5175 76100 101125 0 125 2650 5175 76100 101125 0 125 2650 5175 76100 101125 0 125 2650 5175 76100 101125 0 125 2650 5175 76100 101125 Signature module addresses 0 0 0 0 0 125 125 125 125 125 125 2650 2650 2650 2650 2650 2650 5175 5175 5175 5175 5175 5175 76100 76100 76100 76100 76100 76100 101125 101125 101125 101125 101125 101125 1263 710 161 385 216 49 2007 1128 256 612 344 78 3192 1794 407 973 547 124 18 AWG ft 3931 3427 2928 2432 1941 3247 2722 2202 1686 1174 666 2204 1664 1129 598 71 m 1198 1045 892 741 592 990 830 671 514 358 203 672 507 344 182 22 16 AWG ft 6245 5444 4651 3864 3083 5158 4324 3498 2678 1865 1058 3502 2644 1793 950 113 m 1903 1659 1418 1178 940 1572 1318 1066 816 568 323 1067 806 547 289 34 14 AWG ft 9932 8659 7397 6145 4903 8204 6878 5563 4259 2966 1683 5570 4205 2852 1511 179 m 3027 2639 2255 1873 1495 2501 2096 1696 1298 904 513 1698 1282 869 460 55

QS4 Technical Reference Manual

A.7

System calculations

Battery calculation worksheet


Use this worksheet to determine the amperage capacity of the panel's standby battery. You can obtain operating current requirements for field devices from their respective installation sheets. Example: There are 10 strobes rated at 80 mA and 40 minihorns rated at 10 mA connected to NAC circuits powered by AUX 1. Enter 1200 mA in the Alarm box for AUX 1.
Standby Current (mA) Base Panel (Form A) SMK/ACC power (FormB) AUX 1 load AUX 2 load AUX 3 load Loop 1 load Loop 2 load Loop 3 load Loop 4 load
[2] [1]

Alarm Current (mA)

Total Current

hr

min

60 + = 1.2 mAh 1000 Battery size


[3]

mAh

Ah

Notes [1] Maximum 1.5 A per AUX circuit. [2] If the Total Current Required value exceeds 6 A, switch part of the load to an auxiliary power source. The auxiliary power source must be UL/ULC listed for Fire Protective Signaling Systems. [3] If the calculated battery size exceeds 40 Ah, switch part of the load to an auxiliary power source.

A.8

QS4 Technical Reference Manual

System calculations (A) Base panel current load calculation


Card PS6 CPU/Display SL30 (1) SLIC DLD ZB164 ZA82 X485 ZR8
[2] [1]

Qty 1

Standby Current (mA) 82 117 1 33 13 117 73 60 11

Qty Standby Current (mA) 82

Alarm Current (mA) 100 135 1 57 20 152 116 60 18

Qty Alarm Current (mA) 100

Totals Notes

[3]

[1] Add 0.75 mA for each energized LED. [2] Add 18 mA for each energized relay. [3] Base panel current must be less than 1.32 mA.

(B) Smoke/Accessory (SMK/ACC) Power current load calculation (max 250 mA)
Card CPU/Display SL30 (1) CDR3 IOP3A RPM
[2] [1] [3]

Qty

Standby Current (mA) 117 1 60 60 20

Qty Standby Current (mA)

Alarm Current (mA) 123 1 100 60 20 17

Qty Alarm Current (mA)

SIGA-UM, -MAB Totals Notes

[4]

17

[4]

[1] Add 0.75 mA for each energized LED. [2] Add 0.7 mA for each output used. [3] This value includes RAI currents

This represents the smoke power requirements. Only the SIGAUM or SIGAMAB that signaled the alarm draws alarm current. The remaining SIGAUMs or SIGAMABs do not.

QS4 Technical Reference Manual

A.9

System calculations

A.10

QS4 Technical Reference Manual

Appendix B

Barcode library

Summary This appendix contains a set of barcodes that you can use to add location messages. Content Uppercase letters B.2 Numbers and ordinals B.2 Common words B.3

QS4 Technical Reference Manual

B.1

Barcode library

Uppercase letters

Backspace

Delete

Enter

Space

Numbers and ordinals

Backspace

Delete

Enter

1ST

2ND

3RD

4TH

5TH

6TH

7TH

8TH

9TH

0TH

B.2

QS4 Technical Reference Manual

Barcode library Common words ABORT ABOVE ALARM APARTMENT APT AREA ATRIUM AUDITORIUM BASEMENT BELOW CAFETERIA CEILING CLASSROOM CLOSET COMPUTER CONFERENCE CORRIDOR DAMPER DETECTOR

QS4 Technical Reference Manual

B.3

Barcode library

DOOR DUCT EAST ELECTRICAL ENTRANCE EXIT FAN FAULT FIRE FIRE PUMP FLAME FLOOR FOYER GARAGE GENERATOR GYM HALL HEAT HORN JANITOR

B.4

QS4 Technical Reference Manual

Barcode library

KITCHEN LAB LEFT LEVEL LIBRARY LOBBY LOWER MACHINE MECHANICAL MENS MEZZANINE MONITOR NORTH OFFICE PARKING PENTHOUSE PULL RELAY RESTROOM RIGHT

QS4 Technical Reference Manual

B.5

Barcode library

ROOM SECURITY SHAFT SMOKE SOUTH STAGE STAIRWELL STOCKROOM STORAGE STROBE SUITE SUPERVISORY TROUBLE UNDER UPPER UTILITY WAREHOUSE WATERFLOW WEST WOMENS

B.6

QS4 Technical Reference Manual

Barcode library

ZONE

QS4 Technical Reference Manual

B.7

Barcode library

B.8

QS4 Technical Reference Manual

Appendix C

SIGA-REL programming

Summary This appendix provides information on how to program the SIGAREL using the QuickStart Configuration Utility Content Application block diagram C.2 Programming instructions C.3

QS4 Technical Reference Manual

C.1

SIGA-REL programming

Application block diagram

FACP

RACCR

MFCA

SLIC

LOOP DATA

SIGAAPS

24VDC LOOP DATA

SIGAREL

Minimum system requirements A QS1 with SLIC card and appropriately sized standby batteries A SIGAAPS mounted in an RACCR enclosure with appropriately sized standby batteries to supply 24 Vdc to the SIGAREL A SIGAREL mounted in an MFCA enclosure

Caution: You can not have more than 10 SIGA RELs on one loop. Related documentation Refer to the SIGAREL Technical Reference Manual (P/N 387348) and the latest technical bulletins for installation and connection information. Refer to the SIGAAPS installation sheet for installation and connection information. Refer to the RACCR installation sheet for installation information.

C.2

QS4 Technical Reference Manual

SIGA-REL programming

Programming instructions
Read me first WARNING: Attempting to program this application without a complete understanding of the operation of the SIGAREL, the latest technical information, and the consequences of exposing someone to fire suppression agents may cause personal injury, event death. WARNING: Improper application of fire suppression agents can lead to property damage, serious injury, or loss of life. Consult the applicable NFPA documents and the local authority having jurisdiction (AHJ) for more information. WARNING: Disabled and Service Group points will not prevent activation of the release circuits. This application requires the operation of at least two automatic detectors to activate the fire suppression system. In order to meet NFPA 72 requirements, you must program an And group with at least two smoke detectors and a minimum activation count of 2. The smoke detectors must have their Primary and Alternate Verification properties set to None. The SIGAREL has six addressable circuits. To add the SIGA REL to the loop controller database you must add three SIGA RELs. The first SIGAREL is for the Abort switch and Manual Release switch circuits, the second for the two release circuits, and the third for the two prerelease circuits. Perform these instructions in order from beginning to end. Check the check box provided as you complete each step. As a safety precaution, disconnect releasing devices from SIGAREL TB4 before downloading setup data to the loop controller. Add the Abort and Manual Release Switch circuits Note: Enter the information exactly as shown to ensure that you program the application according to manufacturer's specifications. 1. Click Configure, then click Cabinets. 2. Select the SLIC connected to the SIGAREL then click Configure. 3. Click the Modules tab, then set the Quantity box to 1. 4. Enter the following information: Device Type: Monitor Model: REL Personality: (3) Active B Message Specification: SIGAREL1 A001 and ABORT SW 2nd Device Type: Pull 2nd Personality: (1) Alarm B 2nd Message Specification: SIGAREL1 A002 and MAN RELEASE SW 5. Click Add.

QS4 Technical Reference Manual

C.3

SIGA-REL programming

Add the the two releasing circuits

1. Set the Quantity box to 1. 2. Enter the following information: Device Type: Output Model: REL Personality: (16) Output B Message Specification: SIGAREL1 A003 and RELEASE 1&2 2nd Device Type: Monitor 2nd Personality: (0) None 2nd Message Specification: SIGAREL1 A004 and NOT USED 3. Click Add.

Add the two prerelease circuits

1. Set the Quantity box to 1. 2. Enter the following information: Device Type: Output Model: REL Personality: (16) Output B Message Specification: SIGAREL1 A005 and PRERELEASE 1&2 2nd Device Type: Monitor 2nd Personality: (0) None 2nd Message Specification: SIGAREL1 A006 and NOT USED 3. Click Add.

This is how your entries in the Modules table should look. Your addresses may be different.
Address 126 127 128 129 130 132 Serial Number Device Type Monitor Pull Output Monitor Output Monitor Model REL REL REL REL REL REL Text 1 SIGAREL1 A001 SIGAREL1 A002 SIGAREL1 A003 SIGAREL1 A004 SIGAREL1 A005 SIGAREL1 A006 Text 2 ABORT SW MAN RELEASE SW RELEASE 1&2 NOT USED PRERELEASE 1&2 NOT USED Personality (3) Active B (1) Alarm B (16) Output B (0) None (16) Output B (0) None

C.4

QS4 Technical Reference Manual

SIGA-REL programming

Create a response that activates the prerelease circuits when any one detector in the protected area signals an alarm

1. Click Configure > Correlations 2. Click the Zones tab, then click Add Zones. 3. Click the Members tab, then click Add Device. 4. Select only the devices required to activate the SIGAREL prerelease circuits then click OK. 5. Click the Responses tab, click the Response Type arrow, and then select Active. 6. Click Outputs, select the device labeled SIGA REL1 A005 PRERELEASE 1&2, and then click OK.

Create a response that activates the release circuits when two or more detectors in the protected area signal an alarm Note: To comply with NFPA 72, you must program an And Group with at least two smoke detectors and a minimum activation count of 2. The smoke detectors must have their Primary and Alternate Verification properties set to None (verified smoke detectors not allowed).

1. Click the And Groups tab, then click Add AND Group. 2. Set the Activation Count box for 2. 3. Click the Members tab, then click Add Device. 4. Select only the detectors required to activate the SIGA REL release circuits then click OK. 5. Click the Responses tab, click the Response Type arrow, and then select Active. 6. Click Delays 7. In the Delay On list, click Activation and Restoration. 8. Set the Seconds box to 10. 9. Click Outputs, select the device labeled SIGA REL1 A003 RELEASE 1&2, and then click OK.

Create a response that activates the release circuits when someone presses the manual release switch

1. Click the Devices tab, then select the circuit labeled SIGAREL A002 MAN RELEASE SW. 2. Click the Responses tab, click the Response Type arrow, and then select Active. 3. Click Outputs, then: Hold the Ctrl key down Select the device labeled SIGA REL1 A005 Prerelease 1&2 Select the device labeled SIGA REL1 A003 Release 1&2 Release the Ctrl key then click OK. Note: The prerelease circuit must appear before the releasing circuit in the response list.

QS4 Technical Reference Manual

C.5

SIGA-REL programming

Create a response that activates the prerelease circuits when someone presses the Drill switch Note: Create this response only if required. Pressing Drill will activate the prerelease circuits but pressing Drill a second time will not restore the prerelease circuits. You must press Reset to silence the prerelease circuits. Retrieve the loop data from the SLIC

1. Click the Devices tab then select the Show Pseudo Points check box. 2. Select the circuit labeled Drill (address 007). 3. Click the Responses tab, click the Response Type arrow, and then select Active. 4. Click Outputs, select the device labeled SIGA REL1 A005 PRERELEASE 1&2, and then click OK.

1. Click Configure, then click Cabinets. 2. Select the SLIC connected to the SIGAREL then click Configure. 3. Set the Communications Port setting for the COM port used to connect the service computer to the control panel. 4. Click Retrieve Signature Data 5. After the upload has finished, click OK.

Reconcile the actual and expected data Caution: Clicking Accept Actual will enter the selected device into the database with its current programmed parameters. This will corrupt the database if you have already entered the device.

1. Click the Mapping tab, then click Model. 2. Look for a string of at least six RELs marked with red backgrounds and double-click the first REL in the string. 3. If the serial number displayed in the Module Properties dialog is not the same as the serial number shown on the bar code attached to the SIGAREL, click Close, and then double-click the next REL in the string. 4. If the serial numbers are the same: Click Select Expected. In the Module Selection dialog, select the row that has the REL with the Monitor device type and marked SIGAREL1 A001 Abort SW, then click OK. Click Close. 5. Select the next REL then click Select Expected. In the Module Selection dialog, select the row that has the REL with the Output device type and marked SIGAREL1 A003 Release 1&2, then click OK. Click Close. 6. Select the next REL then click Select Expected. In the Module Selection dialog, select the row that has the REL with the Output device type and marked SIGAREL1 A005 Prerelease 1&2, then click OK. Click Close.

C.6

QS4 Technical Reference Manual

SIGA-REL programming

Send the reconciled data to the loop controller

Click the Controller tab, then click Send Signature Data.

QS4 Technical Reference Manual

C.7

SIGA-REL programming

C.8

QS4 Technical Reference Manual

You might also like