1016
1016
1016
Corp. 1016L2
240/300 SHOWN
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs and HCFCs) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.
WARNING
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies.
Table of Contents
Options / Accessories . . . . . . . . . . . . . . . Page 2 Specifications . . . . . . . . . . . . . . . . . . . . . . Page 5 Blower Data . . . . . . . . . . . . . . . . . . . . . . . Page 6 Electrical / Electric Heat Data . . . . . . . . Page 9 Electric Heat Capacities . . . . . . . . . . . . . Page 13 Parts Arrangement . . . . . . . . . . . . . . . . . Page 15 I Unit Components . . . . . . . . . . . . . . . . . . Control Box . . . . . . . . . . . . . . . . . . . . . Cooling . . . . . . . . . . . . . . . . . . . . . . . . Blower Compartment . . . . . . . . . . . . . . Electric Heat . . . . . . . . . . . . . . . . . . . . Page 16 Page 16 Page 21 Page 22 Page 24
CAUTION
Electrostatic discharge can affect electronic components. Take precautions during unit installation and service to protect the units electronic controls. Precautions will help to avoid control exposure to electrostatic discharge by putting the furnace, the control and the technician at the same electrostatic potential. Neutralize electrostatic charge by touching hand and all tools on an unpainted unit surface, such as the gas valve or blower deck, before performing any service procedure.
CAUTION
Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges.
. . . . . . . . Page 29
OPTIONS / ACCESSORIES
Item Description COOLING SYSTEM Condensate Drain Trap Corrosion Protection Drain Pan Overflow Switch Efficiency Low Ambient Kit Refrigerant Type BLOWER - SUPPLY AIR Motors Model Number PVC - LTACDKP09/36 Copper - LTACDKC09/36 K1SNSR71C-1K1SNSR33C-1 Catalog Number 76M18 76M19 Factory 68W89 Standard 55W72 R-410A Factory Factory Factory Factory Factory Factory Factory Factory Factory Factory Factory Factory Factory Factory 54W79 54W80 54W83 54W84 --53W82 53W83 180 X X O X O X O O O O O O O O O O O O 210 X X O X O X O O O O O O O O O O O O 240 X X O X O X O 300 X X O X O X O
Drive Kits See Blower Data Tables for usage and selection
Belt Drive - 3 hp Belt Drive - 5 hp Belt Drive - 7.5 hp Belt Drive - 10 hp Kit #1 535-725 rpm Kit #2 710-965 rpm Kit #3 685-856 rpm Kit #4 850-1045 rpm Kit #5 945-1185 rpm Kit #6 850-1045 rpm Kit #7 945-1185 rpm Kit #8 1045-1285 rpm Kit #10 1045-1285 rpm Kit #11 1135-1365 rpm C1GARD20C11 C1GARD20C31 C1GARD10C11 C1GARD10C31
O O O
O O O
O O O O O O O O
O O O O O O O O
X X
X X X X X X X X X
CONTROLS Commercial Controls L Connection Building Automation System Smoke Detector - Supply or Return (Power board and one sensor) C1SNSR44C-1 Smoke Detector - Supply and Return (Power board and two sensors) C1SNSR43C-1 INDOOR AIR QUALITY Air Filters MERV 8 - C1FLTR15C-1Healthy Climate High Efficiency Air Filters 24 x 24 x 2 (Order 6 per unit) MERV 13 - C1FLTR40C-1Replacement Media Filter With Metal Mesh C1FLTR30C-1Frame (includes non-pleated filter media) Indoor Air Quality (CO2) Sensors Sensor - Wall-mount, off-white plastic cover with LCD display C0SNSR50AE1L Sensor - Wall-mount, off-white plastic cover, no display C0SNSR52AE1L Sensor - Black plastic case with LCD display, rated for plenum mounting C0SNSR51AE1L Sensor - Wall-mount, black plastic case, no display, rated for C0MISC19AE1 plenum mounting C0MISC19AE1CO2 Sensor Duct Mounting Kit - for downflow applications C0MISC16AE1Aspiration Box - for duct mounting non-plenum rated CO2 sensors (87N53 or 77N39) UVC Germicidal Light Kit 1 Healthy Climate UVC Light Kit (110/230v-1ph) C1UVCL10C-1
1
X X X
X X X
X X X
X X X
X X X
X X X
X X X
X X X X X X
X X X X X X
X X X X X X
X X X X X X
54W65
Lamps operate on 110-230V single-phase power supply. Step-down transformer must be field supplied for field installation in 460V and 575V rooftop units (transformer is furnished for factory installed light kits). Alternately, a separate 110V power supply may be used to directly power the UVC ballast(s) NOTE - Catalog and model numbers shown are for ordering field installed accessories. OX - Configure To Order (Factory Installed) or Field Installed O = Configure To Order (Factory Installed) X = Field Installed
Page 2
OPTIONS / ACCESSORIES
Item Description ELECTRICAL Voltage 60 hz 208/230V - 3 phase 460V - 3 phase 575V - 3 phase Disconnect Switch (see Electric Heat Tables for usage, ) 80 amp - C1DISC080C-1 150 amp - C1DISC150C-1 250 amp - C1DISC250C-1 GFI Service Outlets ELECTRIC HEAT 15 kW 208/230V-3ph - C1EH0150C-1Y 460V-3ph - C1EH0150C-1G 575V-3ph - C1EH0150C-1J 30 kW 208/230V-3ph - C1EH0300C21Y 460V-3ph - C1EH0300C21G 575V-3ph - C1EH0300C21J 45 kW 208/230V-3ph - C1EH0450C21Y 460V-3ph - C1EH0450C21G 575V-3ph - C1EH0450C21J 60 kW 208/230V-3ph - C1EH0600C21Y 460V-3ph - C1EH0600C21G 575V-3ph - C1EH0600C21J 90 kW 208/230V-3ph - C1EH0900C-1Y 460V-3ph - C1EH0900C-1G 575V-3ph - C1EH0900C-1J ECONOMIZER Economizer Economizer - Downflow or Horizontal (Outdoor Air Hood furnished) Economizer Controls Differential Enthalpy Single Enthalpy Downflow Barometric Relief Dampers Barometric Relief Dampers with Exhaust Hood Horizontal Barometric Relief Dampers Barometric Relief Dampers with ExhaustHood
NOTE - Catalog and model numbers shown are for ordering field installed accessories. OX - Configure To Order (Factory Installed) or Field Installed O = Configure To Order (Factory Installed) X = Field Installed
Model Number
Catalog Number Factory Factory Factory 54W85 54W86 54W87 74M70 53W84 53W86 53W87 53W92 53W94 53W95 54W00 54W02 54W03 54W08 54W10 54W11 54W12 54W14 54W15
180
210
240
300
O O O OX OX OX OX X X X X X X X X X X X X
O O O OX OX OX OX X X X X X X X X X X X X X X X
O O O OX OX OX OX X X X X X X X X X X X X X X X
O O O OX OX OX OX X X X X X X X X X X X X X X X
K1ECON20C-1
54W77
OX
OX
OX
OX
X OX OX X
X OX OX X
X OX OX X
X OX OX X
Page 3
OPTIONS / ACCESSORIES
Item Description OUTDOOR AIR Outdoor Air Dampers Motorized Dampers with Outdoor Air Hood Manual Dampers With Outdoor Air Hood POWER EXHAUST Standard Static Model Number Catalog Number 180 210 240 300
OX OX X X X
OX OX X X X
OX OX X X X
OX OX X X X
ROOF CURBS - DOWNFLOW Clip Curb 8 in. height C1CURB40CD1 14 in. height LARMF18/30S-14 18 in. height LARMF18/30S-18 24 in. height LARMF18/30S-24 Standard 14 in. height LARMF18/36-14 24 in. height LARMF18/36-24 Adjustable Pitched Curb 14 in. height L1CURB55C ROOF CURBS - HORIZONTAL (REQUIRES HORIZONTAL RETURN AIR PANEL Standard 26 in. height - slab applications LARMFH18/24-26 37 in. height - rooftop applications LARMFH18/24-37 30 in. height - slab applications LARMFH30/36-30 41 in. height - rooftop applications LARMFH30/36-41 Insulation Kit For Standard Horizontal Curbs for LARMFH18/24-26 C1INSU11C-1for LARMFH18/24-37 C1INSU13C-1for LARMFH30/36-30 C1INSU12C-1for LARMFH30/36-41 C1INSU14C-1Horizontal Return Air Panel Kit Required for Horizontal Applications with Roof Curb C1HRAP10C-1CEILING DIFFUSERS Step-Down - Order one RTD11-185 RTD11-275-R RTD11-150/180S (Canada only) RTD11-275S (Canada only) Flush - Order one FD11-185 FD11-275-R FD11-150/180S (Canada only) FD11-275S (Canada only) Transitions (Supply and Return) - Order one LASRT18 LASRT21/24 LASRT18S (Canada only) LASRT21/24S (Canada only)
NOTE - Catalog and model numbers shown are for ordering field installed accessories. OX - Configure To Order (Factory Installed) or Field Installed O = Configure To Order (Factory Installed) X = Field Installed
26W32 33K44 33K45 33K46 16K87 16K88 43W26 KIT) 97J33 38K53 33K79 38K54 73K32 73K34 73K33 73K35 87M00 29G06 29G07 13K63 13K64 29G10 29G11 13K58 13K59 19K01 19K02 33K48 33K49
X X X X X X X
X X X X X X X
X X X X X X X
X X X X X X X
X X
X X
X X X X
X X
X X
X X X X
X X
X X X X X X X X X X X
X X X X X X
X X X X X X
Page 4
SPECIFICATIONS
General Data Nominal Tonnage Model Number Efficiency Type Blower Type 20 Ton 25 Ton KCA240S4B KCA300S4B Standard Standard Constant Air Constant Air Volume CAV Volume CAV 238,000 282,000 228,000 270,000 7700 8750 20.8 26.9 11.0 10.0 11.2 10.1 R-410A R-410A 14 lbs. 0 oz. 14 lbs. 8 oz. 14 lbs. 0 oz. 14 lbs. 8 oz. 14 lbs. 0 oz. 14 lbs. 8 oz. 15-30-45-60-90 kW Scroll (3) Scroll (3) Scroll (3) 41.40 55.20 55.20 3/8 3/8 3/8 2 2 2 20 20 20 (3) 1/3 (4) 1/3 (4) 1/3 1075 1075 1075 1500 1100 1500 (3) 24 (4) 24 (4) 24 3 3 3 12,000 16,000 16,000 21.40 21.40 21.40 3/8 3/8 3/8 3 4 4 14 14 14 (1) 1 in. FPT (1) 1 in. FPT (1) 1 in. FPT Balance port TXV, removable head 3 hp, 5 hp, 7.5 hp 3 hp, 5 hp, 7.5 hp 5 hp, 7.5 hp, 10 hp 5 hp, 7.5 hp, 10 hp 3.45 hp, 5.75 hp, 3.45 hp, 5.75 hp, 5.75 hp, 8.62 hp, 5.75 hp, 8.62 hp, 8.62 hp 8.62 hp 11.5 hp 11.5 hp 5 hp 3 hp Kit 1 535-725 rpm Kit 3 685-856 rpm Kit 2 710-965 rpm Kit 4 850-1045 rpm Kit 5 945-1185 rpm 5 hp Kit 3 685-856 rpm 7.5 hp Kit 4 850-1045 rpm Kit 6 850-1045 rpm Kit 5 945-1185 rpm Kit 7 945-1185 rpm 7.5 hp Kit 8 1045-1285 rpm 10 hp Kit 6 850-1045 rpm Kit 7 945-1185 rpm Kit 7 945-1185 rpm Kit 10 1045-1285 rpm Kit 8 1045-1285 rpm Kit 11 1135-1365 rpm (2) 15 x 15 (2) 15 x 15 (2) 15 x 15 (2) 15 x 15 Fiberglass, disposable (6) 24 x 24 x 2 208/230V, 460V or 575V - 60 hertz - 3 phase 15 Ton KCA180S4B Standard Constant Air Volume CAV 182,000 176,000 6000 16.0 11.0 11.2 R-410A 14 lbs. 0 oz. 14 lbs. 0 oz. N/A 15-30-45-60 kW Scroll (2) 41.40 3/8 2 20 (3) 1/3 1075 1100 (3) 24 3 12,000 18.60 3/8 3 14 (1) 1 in. FPT 17.5 Ton KCA210S4B Standard Constant Air Volume CAV 204,000 198,000 6125 18.0 11.0 11.2 R-410A 10 lbs. 8 oz. 10 lbs. 8 oz. 10 lbs. 8 oz.
Cooling Gross Cooling Capacity - Btuh Performance 1 Net Cooling Capacity - Btuh AHRI Rated Air Flow - cfm Total Unit Power - kW 1 EER (Btuh/Watt) 2 IEER (Btuh/Watt) Refrigerant Type Refrigerant Circuit 1 Charge Circuit 2 Furnished Circuit 3 Electric Heat Available, see page 3 Compressor Type (number) Outdoor Net face area (total) - sq. ft. Coils Tube diameter - in. Number of rows Fins per inch Outdoor Coil Motor - (No.) horsepower Fans Motor rpm Total Motor watts Diameter - (No.) in. Number of blades Total Air volume - cfm Indoor Coils Net face area (total) - sq. ft. Tube diameter - in. Number of rows Fins per inch Drain connection - No. and size Expansion device type 3 Indoor Nominal motor output Blower Maximum usable motor and output (US Only) Drive Motor - Drive kit number Selection
Blower wheel nominal diameter x width - in. Filters Type of filter Number and size - in. Electrical characteristics
NOTE - Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction. 1 Certified in accordance with the ULE certification program, which is based on AHRI Standard 340/360; 95F outdoor air temperature and 80F db/67F wb entering evaporator air; minimum external duct static pressure. 2 Integrated Energy Efficiency Ratio certified and tested according to AHRI Standard 340/360. 3 Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of motors furnished are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep within the service factor limitations outlined on the motor nameplate.
Page 5
BLOWER DATA
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL & AIR FILTERS IN PLACE FOR ALL UNITS ADD: 1 - Wet indoor coil air resistance of selected unit. 2 - Any factory installed options air resistance (heat section, economizer, etc.) 3 - Any field installed accessories air resistance (duct resistance, diffuser, etc.) Then determine from blower table blower motor output and drive required. See page 7 for wet coil and option/accessory air resistance data. See page 7 for factory installed drive kit specifications. MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT All units require 6000 cfm minimum air with electric heat.
Air Volume cfm 4750 5000 5250 5500 5750 6000 6250 6500 6750 7000 7250 7500 7750 8000 8250 8500 8750 9000 9250 9500 9750 10,000 10,250 10,500 10,750 11,000 TOTAL STATIC PRESSURE - In. w.g. 0.40 0.60 0.80 1.00 1.20 1.40 1.60 1.80 2.00 2.20 2.40 2.60
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 575 1.10 660 1.45 740 1.80 810 2.15 870 2.50 930 2.85 985 3.20 1040 3.55 1085 3.90 1135 4.25 1180 4.65 1225 5.00 585 1.25 670 1.60 750 1.95 815 2.30 880 2.70 940 3.05 995 3.40 1045 3.80 1095 4.15 1140 4.50 1185 4.90 1230 5.30 595 1.35 680 1.70 755 2.10 825 2.50 890 2.90 945 3.25 1000 3.65 1050 4.00 1100 4.40 1150 4.80 1195 5.20 1235 5.60 605 1.45 690 1.85 765 2.25 835 2.65 895 3.05 955 3.45 1010 3.85 1060 4.25 1110 4.70 1155 5.10 1200 5.50 1240 5.90 615 1.60 700 2.00 775 2.45 840 2.85 905 3.25 960 3.65 1015 4.10 1065 4.50 1115 4.95 1160 5.35 1205 5.80 1250 6.25 630 1.75 710 2.15 785 2.60 850 3.05 910 3.45 970 3.90 1025 4.35 1075 4.80 1120 5.20 1170 5.65 1215 6.10 1255 6.55 640 1.90 720 2.35 795 2.80 860 3.25 920 3.70 975 4.15 1030 4.60 1080 5.05 1130 5.50 1175 5.95 1220 6.45 1265 6.90 650 2.05 730 2.50 805 3.00 870 3.45 930 3.95 985 4.40 1040 4.85 1090 5.35 1140 5.85 1185 6.30 1225 6.75 1270 7.25 665 2.20 745 2.70 815 3.20 880 3.70 940 4.20 995 4.65 1045 5.10 1095 5.60 1145 6.10 1190 6.60 1235 7.10 1275 7.60 675 2.35 755 2.90 825 3.40 890 3.95 950 4.45 1005 4.95 1055 5.40 1105 5.95 1155 6.45 1200 6.95 1240 7.45 1285 8.00 690 2.60 765 3.10 835 3.65 900 4.15 955 4.65 1015 5.25 1065 5.75 1115 6.25 1160 6.75 1205 7.30 1250 7.85 1290 8.35 700 2.75 775 3.30 845 3.85 910 4.45 965 4.95 1020 5.50 1075 6.05 1125 6.60 1170 7.15 1215 7.65 1260 8.25 1300 8.75 715 3.00 790 3.55 855 4.10 920 4.70 975 5.25 1030 5.80 1080 6.35 1130 6.90 1180 7.50 1225 8.05 1265 8.60 1305 9.15 725 3.20 800 3.80 865 4.35 930 4.95 985 5.50 1040 6.10 1090 6.70 1140 7.25 1185 7.85 1230 8.40 1275 9.00 1315 9.60 740 3.40 810 4.00 880 4.65 940 5.25 995 5.85 1050 6.45 1100 7.05 1150 7.65 1195 8.25 1240 8.85 1280 9.40 1325 10.05 750 3.65 825 4.30 890 4.90 950 5.55 1005 6.15 1060 6.80 1110 7.40 1160 8.05 1205 8.65 1250 9.25 1290 9.85 1330 10.45 765 3.90 835 4.55 900 5.20 960 5.85 1015 6.45 1070 7.15 1120 7.75 1165 8.35 1215 9.05 1255 9.65 1300 10.30 1340 10.90 780 4.20 850 4.85 910 5.50 970 6.15 1025 6.80 1080 7.50 1130 8.15 1175 8.75 1220 9.40 1265 10.10 1310 10.80 1350 11.40 790 4.45 860 5.15 925 5.85 985 6.55 1040 7.20 1090 7.85 1140 8.55 1185 9.20 1230 9.85 1275 10.55 1315 11.20 - - 805 4.75 875 5.45 935 6.15 995 6.90 1050 7.60 1100 8.25 1150 8.95 1195 9.60 1240 10.30 1285 11.05 - - 820 5.05 885 5.75 950 6.55 1005 7.20 1060 7.95 1110 8.65 1160 9.40 1205 10.05 1250 10.80 1295 11.50 - - 835 5.40 900 6.15 960 6.85 1015 7.60 1070 8.35 1120 9.05 1170 9.80 1215 10.50 1260 11.25 - - 845 5.65 910 6.45 970 7.20 1030 8.00 1080 8.75 1135 9.55 1180 10.25 1225 11.00 - - 860 6.00 925 6.85 985 7.65 1040 8.40 1095 9.20 1145 10.00 1190 10.70 1235 11.45 - - 875 6.40 940 7.25 1000 8.05 1055 8.85 1105 9.65 1155 10.45 1200 11.20 - - 890 6.80 950 7.60 1010 8.45 1065 9.30 1115 10.05 1165 10.90 - - ---------------------------------------------------------------------------------------------
Page 6
BLOWER DATA
FACTORY INSTALLED BELT DRIVE KIT SPECIFICATIONS
Nominal hp 3 3 5 5 5 7.5 7.5 7.5 10 10 10 Maximum hp 3.45 3.45 5.75 5.75 5.75 8.63 8.63 8.63 11.50 11.50 11.50 Drive Kit Number 1 2 3 4 5 6 7 8 7 10 11 RPM Range 535 - 725 710 - 965 685 - 856 850 - 1045 945 - 1185 850 - 1045 945 - 1185 1045 - 1285 945 - 1185 1045 - 1285 1135 - 1365
NOTE - Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of motors furnished are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep within the service factor limitations outlined on the motor nameplate.
Page 7
BLOWER DATA
CEILING DIFFUSER AIR RESISTANCE - in. w.g.
Air Volume cfm 5000 5200 5400 5600 5800 6000 6200 6400 6500 6600 6800 7000 7200 7400 7500 7600 8000 8500 9000 9500 10,000 10,500 11,000
Step-Down Diffuser RTD11-185 RTD11-275 1 Side/2 Ends All Ends & 1 Side/2 Ends All Ends & 2 Ends Open 2 Ends Open Open Sides Open Open Sides Open .51 .44 .39 ------.56 .48 .42 ------.61 .52 .45 ------.66 .56 .48 ------.71 .59 .51 ------.76 .63 .55 .36 .31 .27 .80 .68 .59 ------.86 .72 .63 ------------.42 .36 .31 .92 .77 .67 ------.99 .83 .72 ------1.03 .87 .76 .49 .41 .36 ------1.09 .92 .80 1.15 .97 .84 ------------.51 .46 .41 1.20 1.02 .88 ------------.59 .49 .43 ------.69 .58 .50 ------.79 .67 .58 ------.89 .75 .65 ------1.00 .84 .73 ------1.10 .92 .80 ------1.21 1.01 .88
Flush Diffuser FD11-185 .27 .30 .33 .36 .39 .42 .46 .50 --.54 .58 .62 .66 .70 --.74 --------------FD11-275 ----------.29 ----.34 ----.40 ----.45 --.50 .57 .66 .74 .81 .89 .96
180
Model No.
Air Volume cfm 7200 7400 7600 7800 8000 8200 8400 8600 8800
1 Throw is the horizontal or vertical distance an airstream travels on leaving the outletor diffuser before the maximum velocity is reduced to 50 ft. per minute. Four sides open.
Air Volume Exhausted cfm 8630 8210 7725 7110 6470 5790 5060 4300 3510 2690 1840
Page 8
15 TON
KCA180S4 208/230V - 3 Ph 25 164 25 164 2.4 (7.2) 2.4 (4.8) 460V - 3 Ph 12.2 100 12.2 100 1.3 (3.9) 1.3 (2.6) 7.5 24.2 110 110 88 93 3 4.8 45 50 37 39 15 5 7.6 50 50 39 42 7.5 11 50 50 43 45 3 3.9 35 35 28 30 575V - 3 Ph 9 78 9 78 1 (3) 1 (2) 15 5 6.1 35 40 30 32 7.5 9 40 40 33 35
Rated Load Amps Locked Rotor Amps Rated Load Amps Locked Rotor Amps Full Load Amps (total) Full Load Amps
(total) (2) 0.33 HP Service Outlet 115V GFI (amps) Indoor Blower Horsepower Full Load Amps Motor
2
3 10.6 90 100 75 79
Maximum
Overcurrent
3
Unit Only With (2) 0.33 HP Power Exhaust Unit Only With (2) 0.33 HP Power Exhaust
Unit+
Electric Heat
Minimum
Circuit Ampacity
2
Maximum
Unit+ Electric Heat and (2) 0.33 HP Power Exhaust Unit+ Electric Heat and (2) 0.33 HP Power Exhaust
Overcurrent Protection
3
15 kW 30 kW 45 kW 60 kW 15 kW 30 kW 45 kW 60 kW 15 kW 30 kW 45 kW 60 kW 15 kW 30 kW 45 kW 60 kW
208V 240V 208V 240V 208V 240V 480V 480V 480V 600V 600V 600V 90 90 100 100 110 110 45 50 50 35 35 40 100 110 100 125 110 125 60 60 60 45 45 50 150 150 150 175 150 175 80 80 90 60 70 70 150 175 150 175 175 175 80 90 90 70 70 70 75 75 81 81 88 88 37 39 43 28 30 33 92 104 100 112 109 121 52 55 59 41 44 48 131 149 139 157 148 166 74 78 82 60 62 66 139 158 146 166 156 175 79 82 86 63 66 69 100 100 100 100 110 110 50 50 50 35 40 40 100 110 110 125 125 150 60 60 70 45 50 50 150 175 150 175 175 175 80 90 90 70 70 70 150 175 175 175 175 200 90 90 90 70 70 80 79 98 137 145 79 110 155 164 85 106 145 152 85 118 163 172 93 115 154 162 93 127 172 181 39 55 77 82 42 58 81 85 45 63 85 90 30 44 62 66 32 47 65 68 35 50 68 72
Minimum
Circuit Ampacity
ELECTRICAL ACCESSORIES Disconnect Unit Only Unit + Power Exhaust Unit + Electric Heat 15 kW Unit + Electric Heat 30 kW Unit + Electric Heat 45 kW Unit + Electric Heat 60 kW Unit + Power Exhaust + Elec. Heat 15 kW Unit + Power Exhaust + Elec. Heat 30 kW Unit + Power Exhaust + Elec. Heat 45 kW Unit + Power Exhaust + Elec. Heat 60 kW
1 2
54W85 54W85 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85 54W86 54W86 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85 54W85 54W85 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85 54W86 54W86 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85 54W86 54W86 54W86 54W86 54W87 54W87 54W85 54W85 54W85 54W85 54W85 54W85 54W87 54W87 54W87 54W87 54W87 54W87 54W86 54W86 54W86 54W85 54W85 54W85 54W86 54W86 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85 54W86 54W86 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85 54W86 54W86 54W86 54W86 54W87 54W87 54W85 54W85 54W85 54W85 54W85 54W85 54W87 54W87 54W87 54W87 54W87 54W87 54W86 54W86 54W86 54W85 54W85 54W85
Extremes of operating range are plus and minus 10% of line voltage. HACR type breaker or fuse. 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
Page 9
17.5 TON
208/230V - 3 Ph 19 123 19 123 19 123 2.4 (7.2) 2.4 (4.8) 460V - 3 Ph 9.7 62 9.7 62 9.7 62 1.3 (3.9) 1.3 (2.6) 7.5 24.2 110 110 95 100 3 4.8 45 50 41 43 15 5 7.6 50 50 44 46 7.5 11 50 60 47 50 3 3.9 35 40 31 33 KCA210S4 575V - 3 Ph 7.4 50 7.4 50 7.4 50 1 (3) 1 (2) 15 5 6.1 40 40 34 36 7.5 9 45 45 37 39
3 10.6 90 100 80 85
Maximum
Overcurrent
3
Unit Only With (2) 0.33 HP Power Exhaust Unit Only With (2) 0.33 HP
Power Exhaust Ampacity ELECTRIC HEAT DATA Electric Heat Voltage 2 Unit+ 15 kW Maximum 30 kW Electric Heat Overcurrent 45 kW Protection 60 kW 90 kW 3 Unit+ 15 kW Minimum 30 kW Electric Heat Circuit 45 kW Ampacity 60 kW 90 kW 2 15 kW Unit+ Maximum 30 kW Electric Heat Overcurrent 45 kW and (2) 0.33 HP Protection 60 kW Power Exhaust 90 kW 3 15 kW Unit+ Minimum 30 kW Electric Heat Circuit 45 kW and (2) 0.33 HP Ampacity 60 kW Power Exhaust 90 kW ELECTRICAL ACCESSORIES Disconnect Unit Only Unit + Power Exhaust Unit + Electric Heat 15 kW Unit + Electric Heat 30 kW Unit + Electric Heat 45 kW Unit + Electric Heat 60 kW Unit + Electric Heat 90 kW Unit + Power Exhaust + Elec. Heat 15 kW Unit + Power Exhaust + Elec. Heat 30 kW Unit + Power Exhaust + Elec. Heat 45 kW Unit + Power Exhaust + Elec. Heat 60 kW Unit + Power Exhaust + Elec. Heat 90 kW
1 2 3
208V 240V 208V 240V 208V 240V 480V 480V 480V 600V 600V 600V 90 90 100 100 110 110 45 50 50 35 40 45 100 110 100 125 110 125 60 60 60 45 45 50 150 150 150 175 150 175 80 80 90 60 70 70 150 175 150 175 175 175 80 90 90 70 70 70 225 250 225 250 225 250 125 125 125 100 100 100 80 80 86 86 95 95 41 44 47 31 34 37 92 104 100 112 109 121 52 55 59 41 44 48 131 149 139 157 148 166 74 78 82 60 62 66 175 79 82 86 63 66 69 139 158 146 166 156 201 230 209 238 218 247 115 118 123 92 95 98 100 100 100 100 110 110 50 50 60 40 40 45 100 110 110 125 125 150 60 60 70 45 50 50 150 175 150 175 175 175 80 90 90 70 70 70 150 175 175 175 175 200 90 90 90 70 70 80 225 250 225 250 225 300 125 125 150 100 100 110 85 85 91 91 100 100 43 46 50 33 36 39 98 110 106 118 115 127 55 58 63 44 47 50 137 155 145 163 154 172 77 81 85 62 65 68 145 164 152 172 162 181 82 85 90 66 68 72 207 236 215 244 224 253 118 122 126 94 97 101 54W86 54W86 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85 54W86 54W86 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85 54W86 54W86 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85 54W86 54W86 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85 54W86 54W86 54W86 54W86 54W87 54W87 54W85 54W85 54W85 54W85 54W85 54W85 54W87 54W87 54W87 54W87 54W87 54W87 54W86 54W86 54W86 54W85 54W85 54W85 4 N/A 4 N/A 4 N/A 4 N/A 4 N/A 4 N/A 54W86 54W86 54W86 54W86 54W86 54W86 54W86 54W86 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85 54W86 54W86 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85 54W86 54W86 54W86 54W86 54W87 54W87 54W85 54W85 54W85 54W85 54W85 54W85 54W87 54W87 54W87 54W87 54W87 54W87 54W86 54W86 54W86 54W85 54W85 54W85 4 N/A 4 N/A 4 N/A 4 N/A 4 N/A 4 N/A 54W86 54W86 54W86 54W86 54W86 54W86
Extremes of operating range are plus and minus 10% of line voltage. HACR type breaker or fuse. Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. 4 Disconnect must be field furnished.
Page 10
20 TON
208/230V - 3 Ph 22.4 149 22.4 149 22.4 149 2.4 (9.6) 2.4 (4.8) 460V - 3 Ph 10.6 75 10.6 75 10.6 75 1.3 (5.2) 1.3 (2.6) 10 30.8 125 150 116 121 5 7.6 50 60 48 50 15 7.5 11 60 60 51 54 10 14 60 70 55 58 5 6.1 40 40 36 38 KCA240S4 575V - 3 Ph 7.7 54 7.7 54 7.7 54 1 (4) 1 (2) 15 7.5 9 45 45 39 41 10 11 50 50 41 43
Maximum
Overcurrent
3
Power Exhaust Ampacity ELECTRIC HEAT DATA Electric Heat Voltage 2 Unit+ 15 kW Maximum 30 kW Electric Heat Overcurrent 45 kW Protection 60 kW 90 kW 3 Unit+ 15 kW Minimum 30 kW Electric Heat Circuit 45 kW Ampacity 60 kW 90 kW 2 15 kW Unit+ Maximum 30 kW Electric Heat Overcurrent 45 kW and (2) 0.33 HP Protection 60 kW Power Exhaust 90 kW 3 15 kW Unit+ Minimum 30 kW Electric Heat Circuit 45 kW and (2) 0.33 HP Ampacity 60 kW Power Exhaust 90 kW ELECTRICAL ACCESSORIES Disconnect Unit Only Unit + Power Exhaust Unit + Electric Heat 15 kW Unit + Electric Heat 30 kW Unit + Electric Heat 45 kW Unit + Electric Heat 60 kW Unit + Electric Heat 90 kW Unit + Power Exhaust + Elec. Heat 15 kW Unit + Power Exhaust + Elec. Heat 30 kW Unit + Power Exhaust + Elec. Heat 45 kW Unit + Power Exhaust + Elec. Heat 60 kW Unit + Power Exhaust + Elec. Heat 90 kW
1 2
208V 240V 208V 240V 208V 240V 480V 480V 480V 600V 600V 600V 110 110 125 125 125 125 50 60 60 40 45 50 110 125 125 125 125 150 60 60 70 45 50 50 150 175 150 175 175 175 80 90 90 70 70 70 150 175 175 175 175 200 90 90 90 70 70 80 225 250 225 250 250 300 125 125 150 100 100 110 100 100 108 108 116 116 48 51 55 36 39 41 100 112 109 121 117 129 55 59 63 44 48 50 139 157 148 166 156 174 78 82 86 62 66 68 183 82 86 90 66 69 72 146 166 156 175 164 209 238 218 247 227 256 118 123 126 95 98 101 125 125 125 125 150 150 60 60 70 40 45 50 125 125 125 150 150 150 60 70 70 50 50 60 150 175 175 175 175 200 90 90 90 70 70 80 175 175 175 200 175 200 90 90 100 70 80 80 225 250 225 300 250 300 125 150 150 100 110 110 104 104 112 112 121 121 50 54 58 38 41 43 106 118 115 127 123 135 58 63 66 47 50 53 145 163 154 172 162 180 81 85 89 65 68 71 152 172 162 181 170 189 85 90 93 68 72 74 215 244 224 253 233 262 122 126 130 97 101 103 54W86 54W86 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85 54W86 54W86 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85 54W86 54W86 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85 54W86 54W86 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85 54W86 54W86 54W87 54W87 54W87 54W87 54W85 54W85 54W85 54W85 54W85 54W85 54W87 54W87 54W87 54W87 54W87 54W87 54W86 54W86 54W86 54W85 54W85 54W85 4 N/A 4 N/A 4 N/A 4 N/A 4 N/A 4 N/A 54W86 54W86 54W86 54W86 54W86 54W86 54W86 54W86 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85 54W86 54W86 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85 54W86 54W86 54W87 54W87 54W87 54W87 54W85 54W85 54W86 54W85 54W85 54W85 54W87 54W87 54W87 54W87 54W87 54W87 54W86 54W86 54W86 54W85 54W85 54W86 4 N/A 4 N/A 4 N/A 4 N/A 4 N/A 4 N/A 54W86 54W86 54W86 54W86 54W86 54W86
Extremes of operating range are plus and minus 10% of line voltage. HACR type breaker or fuse. 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. 4 Disconnect must be field furnished.
Page 11
25 TON STANDARD EFFICIENCY 1 Voltage - 60hz Compressor 1 Rated Load Amps Locked Rotor Amps Compressor 2 Rated Load Amps Locked Rotor Amps Compressor 3 Rated Load Amps Locked Rotor Amps Outdoor Fan Full Load Amps (total) Motors (3) Power Exhaust (2) 0.33 HP Service Outlet 115V GFI (amps) Indoor Blower Horsepower Full Load Amps Motor
2
25 TON
Maximum
Overcurrent
3
Unit Only With (2) 0.33 HP Power Exhaust Unit Only With (2) 0.33 HP
Power Exhaust Ampacity ELECTRIC HEAT DATA Electric Heat Voltage 208V 240V 208V 240V 208V 240V 480V 480V 480V 600V 600V 600V 2 Unit+ 15 kW 125 125 125 125 150 150 60 60 70 45 50 50 Maximum 30 kW 125 125 125 125 150 150 60 60 70 45 50 50 Electric Heat Overcurrent 45 kW 150 175 150 175 175 175 80 90 90 70 70 70 Protection 60 kW 150 175 175 175 175 200 90 90 90 70 70 80 90 kW 225 250 225 250 250 300 125 125 150 100 100 110 15 kW 30 kW 45 kW Ampacity 60 kW 90 kW 2 15 kW Unit+ Maximum 30 kW Electric Heat Overcurrent 45 kW and (2) 0.33 HP Protection 60 kW Power Exhaust 90 kW 3 15 kW Unit+ Minimum 30 kW Electric Heat Circuit 45 kW and (2) 0.33 HP Ampacity 60 kW Power Exhaust 90 kW ELECTRICAL ACCESSORIES Disconnect Unit Only Unit + Power Exhaust Unit + Electric Heat 15 kW Unit + Electric Heat 30 kW Unit + Electric Heat 45 kW Unit + Electric Heat 60 kW Unit + Electric Heat 90 kW Unit + Power Exhaust + Elec. Heat 15 kW Unit + Power Exhaust + Elec. Heat 30 kW Unit + Power Exhaust + Elec. Heat 45 kW Unit + Power Exhaust + Elec. Heat 60 kW Unit + Power Exhaust + Elec. Heat 90 kW
3
Minimum
Unit+
Circuit
Electric Heat
108 108 139 146 209 125 125 150 175 225 113 113 145 152 215
108 112 157 166 238 125 125 175 175 250 113 118 163 172 244
116 116 148 156 218 125 125 175 175 225 120 120 154 162 224
116 121 166 175 247 125 150 175 200 300 120 127 172 181 253
124 124 156 164 227 150 150 175 175 250 128 128 162 170 233
124 129 174 183 256 150 150 200 200 300 128 135 180 189 262
40 44 62 66 95 50 50 70 70 100 42 47 65 68 97
43 48 66 69 98 50 50 70 80 110 45 50 68 72 101
54W86 54W86 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85 54W86 54W86 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85 54W86 54W86 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85 54W86 54W86 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85 54W86 54W86 54W87 54W87 54W87 54W87 54W85 54W85 54W85 54W85 54W85 54W85 54W87 54W87 54W87 54W87 54W87 54W87 54W86 54W86 54W86 54W85 54W85 54W85 4 N/A 4 N/A 4 N/A 4 N/A 4 N/A 4 N/A 54W86 54W86 54W86 54W86 54W86 54W86 54W86 54W86 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85 54W86 54W86 54W86 54W86 54W86 54W86 54W85 54W85 54W85 54W85 54W85 54W85 54W86 54W86 54W87 54W87 54W87 54W87 54W85 54W85 54W86 54W85 54W85 54W85 54W87 54W87 54W87 54W87 54W87 54W87 54W86 54W86 54W86 54W85 54W85 54W86 4 N/A 4 N/A 4 N/A 4 N/A 4 N/A 4 N/A 54W86 54W86 54W86 54W86 54W86 54W86
Extremes of operating range are plus and minus 10% of line voltage. HACR type breaker or fuse. 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. 4 Disconnect must be field furnished.
1 2
Page 12
30.0 102,400
30.0 102,400
30.0 102,400
Page 13
MANUFACTURERS NUMBERS
RPM
Drive No. H.P.
ADJUSTABLE SHEAVE Supplier No. 1VP40x7/8 1VP40x7/8 1VP50x11/8 1VP65x11/8 1VP60x11/8 1VP65x13/8 1VP60x13/8 1VP65x13/8 1VP65x13/8 1VP65x13/8 OEM Part No. 79J0301 79J0301 P81977 10023903 41C1301 78M7101 78L5501 78M7101 78M7101 78M7101
DRIVE COMPONENTS FIXED SHEAVE Supplier No. BK95X17/16 BK72x1-7/16 BK100x1-7/16 BK110H BK90H BK110H BK90H BK90H 1B5V86 1B5V80 OEM Part No. 80K1601 10024413 39L1301 10078806 10078804 10078806 10078804 10078804 78M8301 10024005
BELTS Supplier No. BX59 BX55 BX61 BX65 BX61 BX66 BX63 BX64 5VX670 5VX660 OEM Part No. 59A5001 63K0501 93J9801 10024508 93J9801 97J5901 97J5501 97J5801 10024521 10024520
SPLIT BUSHING Supplier No. N/A N/A N/A H17/16 H17/16 H17/16 H17/16 H17/16 B17/16 B17/16 OEM Part No. N/A N/A N/A 49M6201 49M6201 49M6201 49M6201 49M6201 10024601 10024601
Min 535 710 685 850 945 850 945 1045 1045 1135
Max 725 965 865 1045 1185 1045 1185 1285 1285 1365
1 2 3 4 5 6 7 8 10 11
3 3
5
Page 14
BLOWERS
FILTER DRIERS
CONDENSATE DRAIN
FIGURE 1
FIGURE 2
Page 15
IUNIT COMPONENTS
KCA unit components are shown in figure 1. All units come standard with removeable unit panels. All L1, L2 and L3 wiring is color coded; L1 is red, L2 is yellow and L3 is blue.
3Fuse F4
Fuse F4 is used only with single point power supply. F4 gives over amperage protection to the compressor and other cooling components. F4, S48 and TB2 are located inside a sheet metal enclosure in the unit left front corner mullion.
9Outdoor Fan Capacitors C1, C2, C18 (all units) & C19 (240 & 300 only)
Fan capacitors C1, C2, C18, C19 are 10 MFD / 370V capacitors used to assist in the start up of condenser fans B4, B5, B21, B22 (240 & 300 only) respectively.
5Control Transformer T1
All use a single line voltage to 24VAC transformer mounted in the control box. Transformer supplies power to control circuits in the unit. The transformer is rated at 70VA and is protected by a 3.5 amp circuit breaker (CB8) which is located on the transformer itself. The 208/230 (Y) voltage transform208/230V TRANSFORMER ers have two primary SECONDARY voltage taps, but only one may be used de208 VOLTS pending on supply voltage. See figure 3. 460 230 VOLTS (G) and 575 (J) voltage PRIMARY transformers use a FIGURE 3 single primary voltage tap.
10Outdoor Fan Relay K10 (all units) & K149 (240 & 300 only)
Outdoor fan relays K10 and K149, are DPDT relays with a 24VAC coil. For 180 and 210 units, K10 energizes condenser fans B4, B5 and B21. For 240 and 300 units, K10 energizes condenser fans B4 and B5 and K149 energizes condenser fans B21 and B22.
12Compressor Contactor K1 & K2 (all units) K14 (210, 240, & 300 units only)
All compressor contactors are three-pole-double-break contactors with 24VAC coils. K1 and K2 energize compressors B1 and B2 respectively, in response to thermostat demand. For 210, 240 and 300 units, K14 energizes compressor B13 in response to thermostat demand.
Page 16
13Blower Contactor K3
Blower contactor K3, used in all units, is a three-pole-doublebreak contactor with a 24VAC coil used to energize the indoor blower motor B3 in response to blower demand. K3 is energized from terminal G on TB1.
BLUE RESET BUTTON IN FACTORY-SET AUTO MODE (Turn clockwise to H for manual reset) GREEN TRIP INDICATOR (Flush with surface not tripped; Above surface tripped)
Adjust relay amp setting according to value given on the blower motor nameplate. Proper relay amp setting equals motor nameplate FLA X service factor of 1.15 X .95. Use small slotted screwdriver to adjust control mode from automatic reset (A) to manual reset (H). Control must be in the manual reset mode (H) to perform a test. Press the red test button. Green trip indicator should pop out. Press the blue reset screw to reset the relay.
FIGURE 4
Page 17
EVAPORATOR COIL
B1
B2
DRIERS (2)
PRESSURE TAP
DISCHARGE LINE
PRESSURE TAP
FIGURE 5
Page 18
EVAPORATOR COIL
FREEZESTATS (3) ONE FOR EACH STAGE OF COIL (LOCATED ON RETURN BEND)
B1
B2
DRIERS (3)
PRESSURE TAP
DISCHARGE LINE
PRESSURE TAP
FIGURE 6
Page 19
EVAPORATOR COIL
FREEZESTATS (3) ONE FOR EACH STAGE OF COIL (LOCATED ON RETURN BEND)
B1
B2
DRIERS (3)
PRESSURE TAP
DISCHARGE LINE
PRESSURE TAP
FIGURE 7
Page 20
BCooling Components
All units use independent cooling circuits consisting of separate compressors, condenser coils and evaporator coils. See figures 5, 6 and 7. Drawthrough type condenser fans are used in all units. All units are equipped with belt-drive blowers which draw air across the evaporator during unit operation. Cooling may be supplemented by an optional factory or field-installed economizer. The evaporators are slab type and are stacked. Each evaporator uses a thermostatic expansion valve as the primary expansion device. Each evaporator is also equipped with enhanced fins and rifled tubing. In all units each compressor is protected by a freezestat (on each evaporator) and a high pressure switch (on each discharge line). Optional field installed low ambient switches are available for additional compressor protection.
3Low Ambient Switches (optional) S11, S84 (all units) & S85 (210, 240, 300 units)
The low ambient switch is an optional field installed auto-reset N.O. pressure switch which allows for mechanical cooling operation at low outdoor temperatures. The switch is located in each liquid line prior to the indoor coil. In 180 units, S11 and S84 are wired in parallel with outdoor fan relay K10 coil. Both S11 and S84 have to be open to de energize condenser fans (all three fans will be deenergized at the same time). Either S11 or S84 closing will return all three condenser fans to operation. In 210 units, S11, S84 and S85 are wired in parallel with outdoor fan relay K10 coil. All three low ambient switches; S11, S84 and S85 have to be open to deenergize condenser fans (all three fans will be deenergized at the same time). Any one low ambient switch, S11, S84, or S85 closing will return all three condenser fans to operation. In 240 and 300 units, S11 is wired in series with outdoor fan relay K10 coil. When S11 opens, condenser fans 1 and 2 are deenergized. When S11 closes, both condenser fans 1 and 2 will return to operation. S84 and S85 are wired in parallel with outdoor fan relay coil K149. Both S84 and S85 have to be open to energize condenser fans 3 and 4. Either S84 or S85 closing will return condenser fans 3 and 4 to operation. When liquid pressure rises to 450 10 psig (3103 69 kPa), pressure switch(es) close, energizing the appropriate condenser fan(s). When liquid pressure drops to 240 10 psig (1655 69 kPa), pressure switch(es) open, deenergizing the appropriate condenser fan(s). Intermittent fan operation results in higher evaporating temperature allowing the system to operate without icing the evaporator coil and losing capacity.
WARNING
Electrical shock hazard. Compressor must be grounded. Do not operate without protective cover over terminals. Disconnect power before removing protective cover. Discharge capacitors before servicing unit. Failure to follow these precautions could cause electrical shock resulting in injury or death.
Each compressor is energized by a corresponding compressor contactor. NOTERefer to the wiring diagram section for specific unit operation.
5Freezestats S49, S50 (all units) S53 (210, 240, 300 units only)
Each unit is equipped with a low temperature switch located on a return bend of each evaporator coil. S49 (first circuit), S50 (second circuit) and S53 (third circuit) are located on the corresponding evaporator coils. Each freezestat is wired in series with the corresponding compressor contactor. Each freezestat is an autoreset switch which opens at 29F + 3F (-1.7C + 1.7C) on a temperature drop and closes at 58 F + 4 F (14.4 C + 2.2 C) on a temperature rise. To prevent coil icing, Freezestats open during compressor operation to temporarily disable the respective compressor until the coil temperature rises.
2High Pressure Switches S4, S7 (all units) S28 (210, 240, 300S only)
The high pressure switch is a manual reset N.C switch which opens on a pressure rise. S4 (first circuit), S7 (second circuit) and S28 (third circuit) are wired in series with the respective compressor contactor coils. When discharge pressure rises to 640 10 psig (4413 69 kPa) (indicating a problem in the system) the switch opens and the respective compressor is deenergized (the economizer can continue to operate).
Page 21
6Condenser Fans B4, B5, B21 (all units) & B22 (240 & 300 only)
See SPECIFICATIONS tables at the front of this manual for specifications of condenser fans used in all units. All condenser fans used have singlephase motors. The fan assembly may be removed for servicing and cleaning.
CBlower Compartment
The blower compartment in KCA180/300 units is located between the evaporator coil and the compressor / control section on the opposite side of the condenser coil. The blower assembly is accessed by removing the screws on either side of the sliding base. The base pulls out as shown in figure 8.
1Blower Wheels
All KCA180/300 units have two 15 in. x 15 in. (381 mm x 381 mm) blower wheels. Both wheels are driven by one motor mounted on a single shaft. Shaft bearings are equipped with grease ports for service.
Blower Access
The blower assembly is secured to a sliding base which allows the entire assembly to be pulled out of the unit. See figure 8. 1 Remove the clamp which secures the blower wiring to the blower motor base. 2 Remove and retain screws on either side of sliding base. Pull base toward outside of unit. When pulling the base out further than 12" (305mm), disconnect wiring to K3 blower contactor T1, T2 and T3. Pull wiring toward blower to allow enough slack to slide the base out further.
BLOWER ASSEMBLY
TO INCREASE CFM
LOOSEN ALLEN SCREW & TURN PULLEY CLOCKWISE
TO INCREASE BELT TENSION 1Loosen four screws securing blower motor to sliding base. 2Turn adjusting screw to the left, or counterclockwise, to move the motor downward and tighten the belt. 3Tighten four screws. BELT TENSION ADJUSTING SCREW
TO DECREASE CFM
TURN PULLEY COUNTERCLOCKWISE
BLOWER WHEEL
LOOSEN (4) SCREWS ON MOTOR BASE TO ALLOW MOTOR TO MOVE. SIDE VIEW PULLEY
MOTOR
FIGURE 8 Page 22
3 Slide base back into original position when finished servicing. Replace the clamp and blower wiring in the previous location on the blower motor base. Reconnect wiring to K3 if it was disconnected. 4 Replace retained screws on either side of the sliding base.
2 To relieve belt tension Turn adjusting bolt to the right, or clockwise, to move the motor upward and loosen the belt. This decreases the distance between the blower motor pulley and the blower housing pulley. To increase belt tension Turn the adjusting bolt to the left, or counterclockwise to increase belt tension. This increases the distance between motor pulley and blower housing pulley (motor moves downward and tightens belt). 3 Tighten four bolts securing motor base to mounting frame. IMPORTANT Align top edges of blower motor base and mounting frame base parallel before tightening bolts on the both sides of base. Motor shaft and blower shaft must be parallel.
BLOWER PULLEY
BELT
MOTOR PULLEY
NOT ALIGNED
FORCE
FIGURE 9 1 Loosen four bolts securing motor base to mounting frame. See figure 8.
DEFLECTION 1/64" PER INCH OF SPAN OR 1.5mm PER 100mm OF SPAN
FIGURE 10
Page 23
FIGURE 11
EHA 15, 30, 45, 60 and 90 KW ELECTRIC HEAT SECTION PARTS ARRANGEMENT
HEATING ELEMENTS HE1 HE14
CONTROL WIRE HARNESS PRIMARY ELECTRIC HEAT LIMIT S15(1ST SECTION) S107(2nd SECTION)
FIGURE 12
Page 24
FUSE F3 F3 - 1
FUSE F3 F3 - 2
FUSE F3 F3 - 3
FUSE F3 F3 - 4
FUSE F3 F3 - 5
FUSE F3 F3 - 6
FUSE F3 F3 - 7
FUSE F3 F3 - 8
Figure 13
Page 25
strip TB3 (or a fuse block on some models) located in the upper left corner of the electric heat vestibule.
Heating elements are composed of helix wound bare nichrome wire exposed directly to the air stream. Three elements are connected in a three-phase arrangement. The 7Fuse F3 elements in 208/230V units are connected in a Delta" arFuse F3 are housed in a fuse block which holds three fuses. rangement. Elements in 460 and 575V units are connected Each F3 fuse is connected in series with each leg of electric in Wye" arrangement. Each stage is energized indepenheat. Figure 13 and table 2 show the fuses used with each dently by the corresponding contactors located on the elecelectric heat section. For simplicity, the service manual latric heat vestibule panel. Once energized, heat transfer is bels the fuses F3 1 through F3 8. instantaneous. High temperature protection is provided by 8Terminal Strip TB3 primary and redundant high temperature limits and overElectric heat line voltage connections are made to terminal current protection is provided by fuses. TABLE 2 KCA180/300 ELECTRIC HEAT SECTION FUSE RATING EHA QUANTITY & SIZE
(1) EHA2407.5 & (1) EHA240S7.5 (15 kW Total) (1) EHA36015 & (1) EHA360S15 (30 kW Total) or (1) EHA15615 & (1) EHA156S15 (2) EHA36022.5 (45 kW Total) or (2) EHA15622.5 (2) EHA15030 (60 kW Total) or (2) EHA15630
VOLTAGES
208/230V 460V 575V 208/230V 460V 575V 208/230V 460V 575V 208/230V 460V 575V 208/230V
FUSE (3 each) F3 1
50 Amp 250V 25 Amp 600V 20 Amp 600V 60 Amp 250V 50 Amp 600V 40 Amp 600V 50 Amp 250V 25 Amp 600V 20 Amp 600V 50 Amp 250V 25 Amp 600V 20 Amp 600V 50 Amp 250V 25 Amp 600V 20 Amp 600V
F3 2
60 Amp 250V
F3 3
60 Amp 250V
F3 4
25 Amp 250V 15 Amp 600V 10 Amp 600V 50 Amp 250V 25 Amp 600V 20 Amp 600V 60 Amp 250V 50 Amp 600V 40 Amp 600V
F3 5
50 Amp 250V 25 Amp 600V 20 Amp 600V 50 Amp 250V 25 Amp 600V 20 Amp 600V 50 Amp 250V 25 Amp 600V 20 Amp 600V
F3 6
F3 7
60 Amp 250V
F3 8
25 Amp 250V 15 Amp 600V 10 Amp 600V 50 Amp 250V 25 Amp 600V 20 Amp 600V 60 Amp 250V 50 Amp 600V 40 Amp 600V
460V 575V
Page 26
4. 180 Units contain two refrigerant circuits or systems. Evaporator and condenser coil refrigerant circuit 1 makes up stage 1 cooling. Evaporator and condenser coil refrigerant circuit 2 makes up stage 2 cooling. See figure 14. 210, 240, 300 Units contain three refrigerant circuits or systems. Evaporator and condenser coil refrigerant circuits 1 and 2 make up stage 1 cooling. Evaporator and condenser refrigerant circuit 3 makes up stage 2 cooling. See figure 15. 5. 180, 210 Firststage thermostat demand will energize condenser fans 1, 2 and 3. Fans will continue to operate with additional thermostat demands. See figure 14. 180 AND 210 UNIT CONDENSER FANS
COND. FAN 1 COND. FAN 2 COND. FAN 3
IIISTARTUP OPERATION
Refer to startup directions and to the unit wiring diagram when servicing. See unit nameplate for minimum circuit ampacity and maximum fuse size.
FIGURE 14 240, 300 Firststage thermostat demand will energize condenser fans 1, 2, 3 and 4. See figure 15. Fans will continue to operate with additional thermostat demands. 240 AND 300 UNIT CONDENSER FANS
COND. FAN 3 COND. FAN 1
BCooling Start Up
AOperation 1. Remove coil covers before starting unit. 2. Initiate first and second stage cooling demands according to instructions provided with thermostat. 3. 180 units Firststage thermostat demand will energize compressor 1; a secondstage thermostat demand will energize compressor 2. 210300 units Firststage thermostat demand will energize compressors 1 & 2; a secondstage thermostat demand will energize compressor 3. On units with an economizer, when outdoor air is acceptable, a firststage demand will energize the economizer; a secondstage demand will energize compressor 1 (and compressor 2 on 210300 units).
COND. FAN 4 1 2 3
COND. FAN 2
FIGURE 15 6. Each refrigerant circuit is separately charged with R410A refrigerant. See unit rating plate for correct amount of charge. 7. Refer to Cooling Operation and Adjustment section for proper method to check refrigerant charge.
Page 27
IVCHARGING
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly. Failure to follow this warning may result in personal injury or death. WARNINGDo not exceed nameplate charge under any condition. This unit is factory charged and should require no further adjustment. If the system requires additional refrigerant, reclaim the charge, evacuate the system and add required nameplate charge. NOTE System charging is not recommended below 60F (15C). In temperatures below 60F (15C) , the charge must be weighed into the system. If weighing facilities are not available, or to check the charge, use the following procedure: 1. Attach gauge manifolds and operate unit in cooling mode with economizer disabled until system stabilizes (approximately five minutes). Make sure outdoor air dampers are closed. 2. Check each system separately with all stages operating. 3. Use a thermometer to accurately measure the outdoor ambient temperature. 4. Apply the outdoor temperature to tables 3 through 6 to determine normal operating pressures. Pressures are
listed for sea level applications at 80F dry bulb and 67F wet bulb return air.
Circuit 1 Dis. +10 psig 268 310 353 400 449 505 Suc. +5 psig 128 130 132 135 137 141
Circuit 2 Dis. +10 psig 282 325 368 417 470 527 Suc. +5 psig 132 134 135 138 140 144
Circuit 1 Dis. Suc. +10 +5 psig psig 290 133 330 136 373 137 421 140 474 143 526 146
Circuit 2 Dis. Suc. +10 +5 psig psig 290 128 330 132 373 135 421 138 474 140 526 142
Circuit 3 Dis. Suc. +10 +5 psig psig 307 133 347 135 390 138 437 140 488 143 540 146
Circuit 1 Dis. Suc. +10 +5 psig psig 270 136 313 138 351 140 397 143 450 146 506 149
Circuit 2 Dis. Suc. +10 +5 psig psig 286 135 329 138 366 140 412 143 467 147 522 150
Circuit 3 Dis. Suc. +10 +5 psig psig 285 137 327 140 368 142 414 144 465 147 524 150
5. Compare the normal operating pressures to the pressures obtained from the gauges. Minor variations in these pressures may be expected due to differences in installations. Significant differences could mean that the system is not properly charged or that a problem exists with some component in the system. Correct any system problems before proceeding. 6. If discharge pressure is high, remove refrigerant from the system. If discharge pressure is low, add refrigerant to the system. S Add or remove charge in increments. S Allow the system to stabilize each time refrigerant is added or removed. 7. Use the following approach method along with the normal operating pressures to confirm readings.
Circuit 1 Dis. Suc. +10 +5 psig psig 290 136 330 138 375 141 423 144 475 146 526 149
Circuit 2 Dis. Suc. +10 +5 psig psig 296 132 338 135 382 137 432 140 486 142 546 144
Circuit 3 Dis. Suc. +10 +5 psig psig 306 137 348 138 394 140 440 142 492 145 550 148
CCharge Verification Approach Method AHRI Testing 1. Using the same thermometer, compare liquid temperature to outdoor ambient temperature. Approach Temperature = Liquid temperature (at condenser outlet) minus ambient temperature. 2. Approach temperatures should match values in table 7. An approach temperature greater than this value indicates an undercharge. An approach temperature less than this value indicates an overcharge.
Page 28
3 Do not use the approach method if system pressures do not match pressures in tables 3 through 6. The approach method is not valid for grossly over or undercharged systems.
TABLE 7 APPROACH TEMPERATURES Liquid Temp. Minus Ambient Temp.
1st Stage 8F + 1 (4.4C + 0.5) 8F + 1 (4.4C + 0.5) 8F + 1 (4.4C + 0.5) 7F + 1 (3.9C + 0.5) 2nd Stage 8F + 1 (4.4C + 0.5) 8F + 1 (4.4C + 0.5) 8F + 1 (4.4C + 0.5) 7F + 1 (3.9C + 0.5) 3rd Stage
WARNING
Product contains fiberglass wool. Disturbing the insulation in this product during installation, maintenance, or repair will expose you to fiberglass wool. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of California to cause cancer.) Fiberglass wool may also cause respiratory, skin and eye irritation. To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown on unit nameplate or contact your supervisor.
Unit
NA
10F + 1 (5.6C + 0.5) 8F + 1 (4.4C + 0.5) 9F + 1 (5.0C + 0.5)
AFilters
Units are equipped with six 24 X 24 X 2" filters. Filters should be checked and replaced when necessary with filters of like kind and size. Take note of air flow direction marking on filter frame when reinstalling filters. See figure 16. NOTEFilters must be U.L.C. certified or equivalent for use in Canada.
BLubrication
All motors used in KCA units are factory lubricated, no further lubrication is required. Blower shaft bearings are prelubricated. For extended bearing life, relubricate at least once every two years with a lithium base grease such as Alvania 3 (Shell Oil), Chevron BRB2 (Standard OIl) or Regal AFB2 (Texas Oil). Use a hand grease gun for lubrication. Add only enough grease to purge through the bearings so that a bead of grease appears at the seal lip contacts.
VIMAINTENANCE
! WARNING
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies.
CAUTION
Electrical shock hazard. Turn off power to unit before performing any maintenance, cleaning or service operation on the unit.
PULL TO REMOVE FILTERS
CAUTION
Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges. FIGURE 16
Page 29
CEvaporator Coil
Inspect and clean coil at beginning of each cooling season. Clean using mild detergent or commercial coil cleaner. Flush coil and condensate drain with water taking care not to get insulation, filters and return air ducts wet.
DCondenser Coil
Clean condenser coil annually with detergent or commercial coil cleaner and inspect monthly during the cooling season. Access panels are provided on the front and back of the condenser section.
FElectrical
1 Check all wiring for loose connections. 2 Check for correct voltage at unit (unit operating). 3 Check ampdraw on both condenser fan motor and blower motor. Fan Motor Rating Plate ____ Actual ________ Indoor Blower Motor Rating Plate____ Actual____
FIGURE 17
VIIOPTIONAL ACCESSORIES
The accessories section describes the application of most of the optional accessories which can be installed to the KCA units.
ROOFING MATERIAL
FIGURE 18
BTransitions
Optional supply/return transitions LASRT18/24 are available for use with KCA series units utilizing optional LARMF18/36 roof mounting frame. Transition must be installed in the LARMF18/36 mounting frame before mounting the unit to the frame. Refer to the manufacturers instructions included with the transition for detailed installation procedures.
Page 30
DK1ECON
Unit may contain an optional modulating economizer equipped with an A6 enthalpy control and an S175 outdoor temperature sensor or A7 enthalpy sensor. The economizer modulates to use outdoor air for free cooling when temperature is suitable. The A6 enthalpy control is located in the economizer access area. See figure 19. The S175 temperature sensor or A7 enthalpy sensor is located on the division panel between horizontal supply and return air sections. Optional Sensors An optional differential sensor (A62) may be used with the A7 outdoor sensor to compare outdoor air enthalpy to return air enthalpy. When the outdoor air enthalpy is below the return air enthalpy, outdoor air is used for free cooling. A mixed air sensor (R1) is used in modulating the dampers to 55F (13C) blower compartment air temperature.
When an optional IAQ sensor is installed, a steady green DCV LED indicates that the IAQ reading is higher than setpoint requiring more fresh air. See figure 20. A6 ENTHALPY CONTROLLER
EXH Set 10V
2V EXH
Open
Min Pos
2V DCV
2V Free Cool
IAQ SETPOINT
C D
SIDE PANEL
ECONOMIZER
FIGURE 20
OUTDOOR/ RETURN AIR DIVISION PANEL
Single Temperature or Enthalpy Sensing: The enthalpy control (A6) setpoint may be adjusted when an enthalpy (A7) sensor is used to determine outdoor air suitability, See figure 20. Free cooling will be enabled when outdoor air temperature or enthalpy are lower than the free cooling setpoint. The free cooling setpoints for sensible temperature sensors is 55F. Table 8 shows the free cooling setpoints for enthalpy sensors. Use the recommended setpoint and adjust as necessary. For example: At setting A (table 8), free cooling will be enabled when outdoor air enthalpy is lower than 73F and 50% RH. If indoor air is too warm or humid, lower the setpoint to B. At setting B, free cooling will be enabled at 70F and 50% RH. TABLE 8 ENTHALPY FREE COOLING SETPOINTS
Control Setting A* B C D Enthalpy Setpoint At 50% RH 73 F (23 C) 70 F (21 C) 67 F (19 C) 63 F (17 C)
J3 J105 P4 P3
A6 ENTHALPY CONTROLLER
J10
FIGURE 19 An optional IAQ sensor (A63) may be used to lower operating costs by controlling outdoor air based on CO2 level or room occupancy (also called demand control ventilation or DCV). Damper minimum position can be set lower than traditional minimum air requirements; dampers open to traditional ventilation requirements when CO2 level reaches DCV (IAQ) setpoint. Refer to instructions provided with sensors for installation. A6 Enthalpy Control LEDs A steady green Free Cool LED indicates that outdoor air is suitable for free cooling.
*Setting A is recommended.
Page 31
Differential Sensing: Two sensors can be used to compare outdoor air to return air. When outdoor air is cooler than return air, outdoor air is suitable for free cooling. Adjust the free cooling setpoint to D" in this application. When return air is cooler than outdoor air, the damper will modulate to the minimum position. Damper Minimum Position NOTE A jumper is factoryinstalled between TB1 R and OC terminals to maintain occupied status (allowing minimum fresh air). See figure 21. When using an electronic thermostat or energy management system with an occupied/unoccupied feature, remove jumper. Make wire connections to R and OC as shown in literature provided with thermostat or energy management system literature. Either the jumper wire or optional device must be connected to R and OC for the economizer to function. TB1 TERMINAL R AND OC JUMPER
4 Measure return air temperature. Mark that point on the top line of chart 1 and label the point B" (74_F, 23_C shown). 5 Measure mixed air (outdoor and return air) temperature. Mark that point on the top line of chart 1 and label point C" (70_F, 21_C shown). 6 Draw a straight line between points A and B. 7 Draw a vertical line through point C. 8 Draw a horizontal line where the two lines meet. Read the percent of fresh air intake on the side. 9 If fresh air percentage is less than desired, adjust MIN POS SET potentiometer clockwise (further open). If fresh air percentage is more than desired, adjust MIN POS SET potentiometer counterclockwise (less open). Repeat steps 3 through 8 until calculation reads desired fresh air percentage. DCV Set and Max Settings The DCV SET potentiometer is factoryset at approximately 50% of the potentiometer range. Using a standard 12000ppm CO2 sensor, dampers will start to open when the IAQ sensor reads approximately 1000ppm. Adjust the DCV SET potentiometer to the approximate setting specified by the controls contractor. Refer to figure 20. The DCV MAX potentiometer is factoryset at approximately 50% of the potentiometer range or 6VDC. Dampers will open approximately half way when CO2 rises above setpoint. Adjust the DCV MAX potentiometer to the approximate setting specified by the controls contractor. Refer to figure 20. Note DCV Max must be set higher than economizer minimum position setting for proper demand control ventilation. Economizer Operation
TB1
FIGURE 21 1 Set thermostat to occupied mode if the feature is available. Make sure jumper is in place between TB1 terminals R and OC if using a thermostat which does not have the feature. 2 Rotate MIN POS SET potentiometer to approximate desired fresh air percentage. Note Damper minimum position can be set lower than traditional minimum air requirements when an IAQ sensor is specified. 3 Measure outdoor air temperature. Mark the point on the bottom line of chart 1 and label the point A" (40_F, 4_C shown).
When the outdoor air is suitable, dampers will modulate between minimum position and full open to maintain 55_F (12.8_C) supply air. See table 9 for economizer operation when outdoor air is suitable. See table 10 for economizer operation when outdoor air is NOT suitable. IAQ Sensor During the occupied period, dampers will open to DCV MAX when IAQ reading is above setpoint (regardless of thermostat demand or outdoor air suitability). DCV MAX will NOT override damper fullopen position. The DCV MAX setting may override damper free cooling position when occupancy is high and outdoor air temperatures are low. Note R1 senses mixed air temperature below 45_F (7_C), dampers will move to minimum position until mixed air temperature rises to 48_F (9_C).
Page 32
0 10 20 30 40 50 60 70 80 90
10 20 30 40 50 60 70 80 90 100
_F 20 _C 29 10 23 0 18 10 12 20 7 30 1
A
40 4 50 10 60 16 70 21 80 27 90 32
100
100 _F 38 _C
THERMOSTAT DEMAND Off G Y1 Y2 DAMPER POSITION UNOCCUPIED OCCUPIED Closed Closed Closed Minimum MECHANICAL COOLING No No No Modulating Modulating Modulating Modulating Stage 1
TABLE 9 ECONOMIZER OPERATIONOUTDOOR AIR IS SUITABLE FOR FREE COOLING FREE COOL LED ON"
TABLE 10 ECONOMIZER OPERATIONOUTDOOR AIR IS NOT SUITABLE FOR FREE COOLING FREE COOL LED OFF"
THERMOSTAT DEMAND Off G Y1 Y2 DAMPER POSITION UNOCCUPIED Closed Closed Closed Closed OCCUPIED Closed Minimum* Minimum* Minimum* MECHANICAL COOLING No No
Stage 1 Stage 2
BOutdoor Air Dampers Outdoor air dampers used on KCA units consists of a set of dampers which may be manually or motor (M) operated to allow outside air into the system (see figure 22). Either air damper can be installed in KCA units. The motorized damper assembly opens to minimum position during the occupied time period and remains closed during the unoccupied period. Manual damper assembly is set at installation and remains in that position. See figure 23. Washable filter supplied with the outdoor air dampers can be cleaned with wa-
ter and a mild detergent. It should be sprayed with Filter Handicoater when dry prior to reinstallation. Filter Handicoater is R.P. Products coating no. 418 and is available as Lennox Part No. P85069. Optional manual and motorized outdoor air dampers provide fresh outdoor air. Follow the steps to determine fresh air percentage
Page 33
1 Measure outdoor air temperature. Mark the point on the bottom line of chart 1 and label the point A" (40_F, 4_C shown). 2 Measure return air temperature. Mark that point on the top line of chart 1 and label the point B" (74_F, 23_C shown). 3 Measure mixed air (outdoor and return air) temperature. Mark that point on the top line of chart 1 and label point C" (70_F, 21_C shown). 4 Draw a straight line between points A and B. 5 Draw a vertical line through point C.
6 Draw a horizontal line where the two lines meet. Read the percent of fresh air intake on the side. 7 If fresh air percentage is less than desired, adjust thumbwheel higher. If fresh air percentage is more than desired, adjust thumbwheel lower. Repeat steps until calculation reads desired fresh air percentage. See figure 24. Set damper minimum position in the same manner as economizer minimum position. Adjust motorized damper position using the thumbwheel on the damper motor. See figure 24. Manual damper fresh air intake percentage can be determined in the same manner.
FIGURE 24
LOOSEN WING NUT AND ADJUST LEVER TO DESIRED SETTING.
FIGURE 23
Page 34
P18
FIGURE 25
GControl Systems
Three different types of control systems may be used with the KCA series units. All thermostat wiring is connected to terminal block TB1 located in the control box of the unit. Each thermostat has additional control options available. See thermostat installation instructions for more detail. 1 Electro-mechanical thermostat (13F06) The electro-mechanical thermostat is a twostage heat / twostage cool thermostat with dual temperature levers. A non-switching or manual system switch subbase may be used. 2 Electronic thermostat (see price book) Any twostage heat / twostage cool electronic thermostat may be used. 3 Honeywell T7300 thermostat (81G59) The Honeywell T7300 thermostat is a programmable, internal or optional remote temperature sensing thermostat. The T7300 provides occupied and unoccupied changeover control.
JUVC Kit
UVC germicidal lamps are a fieldinstalled option. The lamp emits ultraviolet light that greatly reduces the growth and proliferation of mold and other bioaerosols on illuminated surfaces. The lamp is mounted in the blower compartment with the light directed towards the indoor coil. For more details refer to the installation instructions provided with the UVC lamp.
Page 35
24V POWER
T1 24V
TO N 380420V UNITS
L1
TO L1 T1
KEY
S7
DESCRIPTION COMPONENT
2 3 K220 6 3 A K2 B
NOTE IF ANY WIRE IN THIS APPLIANCE IS REPLACED IT MUSTBE REPLACED WITH WIRE OFLIKE SIZE, RATING, TERMINATION AND INSULATION THICKNESS
DL46 5
1 A 4 5 A K66 B B A A K67 B A B A B
K21
K102
J138 P138
J139
Page 36
SENSOR ONE, SMOKE, RETURN AIR SENSOR TWO, SMOKE, SUPPLY AIR MODULE, CONTROL SMOKE DETECTION COMPRESSOR 1 COMPRESSOR 2 MOTOR, BLOWER MOTOR, OUTDOOR FAN 1 MOTOR, OUTDOOR FAN 2 MOTOR, EXHAUST FAN 1 MOTOR, EXHAUST FAN 2
K66,1 RELAY, STAGE COOL 1 K67,1 RELAY, STAGE COOL 2 K220, 1RELAY, OVERFLOW SWITCH JACK, HEAT P2 JACK, EXHAUST FAN COMPT P18 JACK, EXHAUST FAN P24 PLUG, TEST P35 PLUG, TEST COOL P36 JACK, OUTDOOR FAN 1 P47 JACK, OUTDOOR FAN 2 P52 PLUG, SENSE BLOWER P86 P106 JACK, OUTDOOR FAN 3
GND
TB13
S48 5
PLUG, EXHAUST FAN MOTOR 1 PLUG, EXHAUST FAN MOTOR 2 JACK, SMOKE DETECTOR ONE JACK, SMOKE DETECTOR ONE JACK, SMOKE DETECTOR TWO JACK, SMOKE DETECTOR TWO PLUG, MODULE, CONTROL SMOKE DETECTION SWITCH, LIMIT LOW COMPRESSOR 1 TEMP SWITCH, LIMIT HI PRESS COMP 1 ( MANUAL RESET) SWITCH, LIMIT HI PRESS COMP 2 SWITCH, LOW PRESS, LOW AMBIENT KIT SWITCH, LIMIT LOW COMPRESSOR 2 TEMP SWITCH, OVERLOAD RELAY BLOWER MOTOR SWITCH, DISCONNECT SWITCH, FREEZESTAT COMP 1 SWITCH, FREEZESTAT COMP 2 SWITCH, LOW PRESS, LOW AMBIENT KIT COMP 2 SWITCH, OVERFLOW TRANSFORMER, CONTROL TERMINAL STRIP, POWER DISTRIBUTION
J11
H 120/ 60/ 1 N
COOLING
GROUND
MOTOR, OUTDOOR FAN 3 B21 P132 CAPACITOR, OUTDOOR FAN 1 C1 P133 CAPACITOR, OUTDOOR FAN 2 C2 WARNING ELECTRIC SHOCK HAZARD, CAN CAUSE DEATH INJURY OR P250 CAPACITOR, EXHAUST FAN C6 UNITMUST BEGROUNDED IN ACCORDANCE WITHNATIONAL AND LOCAL CODES P251 CAPACITOR, OUTDOOR FAN 3 C18 P252 CIRCUIT, BREAKER T1 CB8 DISCONNECT ALL POWER BEFORE SERVICING. P253 CB10 CIRCUIT, BREAKER MAIN DISCONNECT P255 DL46 DELAY, OVERFLOW SWITCH S3 HR1 HEATER COMPRESSOR 1 S4 C18 HEATER COMPRESSOR 2 HR2 C2 C1 9 7 1 7 9 S7 JACK, HEAT J2 S11 JACK, GFI, RECEPTICLE J11 6 4 4 6 S30 JACK, EXHAUST FAN COMPT J18 P24 1 J24 2 P36 S42 JACK, EXHAUST FAN J24 2 3 J36 1 S48 JACK, TEST J35 1 J18 2 P18 S49 JACK, TEST COOL J86 1 2 3 2 7 8 9 2 J36 4 5 6 B2 S50 P86 JACK, OUTDOOR FAN 1 1 1 J47 B3 J47 3 2 1 J52 3 2 1 J1063 2 1 HR2 S84 HR1 JACK, OUTDOOR FAN 2 J52 P47 P106 P52 S149 JACK, SENSE BLOWER J86 C8 T1 J106 JACK, OUTDOOR FAN 3 3 2 1 TB13 J132 JACK, BLOWER , EXHAUST FAN MOTOR 1 J133 3 2 1 J133 JACK, BLOWER , EXHAUST FAN MOTOR 2 P133 B21 J250 JACK, SMOKE DETECTOR ONE B5 J251 JACK, SMOKE DETECTOR ONE B11 J252 JACK, SMOKE DETECTOR TWO J253 JACK, SMOKE DETECTOR TWO J255 JACK, MODULE, CONTROL SMOKE DETECTION S42USED ON"M"VOLTAGE UNITS AND UNITS J261 JACK, SMOKE DETECTOR JUMPER WITH HIGH EFFICIENCY MOTORS CONNECT A172 SENSOR TO J261 ON SUPPLY AIR K1,1 CONTACTOR, COMPRESSOR 1 P2 IS USED ON KCA UNITS ONLY K2,1 CONTACTOR, COMPRESSOR 2 SMOKE DETECTOR ONLY K3, 1 CONTACTOR, BLOWER IMPORTANT: TO PREVENT MOTOR BURNOUT, NEVER S48 OR CB10 MAY BE USED CONNECT MORE THAN ONE MOTOR LEAD TOANY ONE K10,1,2RELAY, OUTDOOR FAN CONNECTION. TAPE UNUSED MOTOR LEADS K651,2 RELAY, EXHAUST FAN 1
Page 37
24V POWER
TO L1 T18 T1 T18 T1 BLACK 24V TO N 380420V UNITS A171 A172 A173 24V B1 B2 B3 B4 460V, 575V B5 UNITS B10 B11
JACK, MODULE, CONTROL SMOKE DETECTION
WHITE
KEY
SENSOR ONE, SMOKE, RETURN AIR SENSOR TWO, SMOKE, SUPPLY AIR MODULE, CONTROL SMOKE DETECTION COMPRESSOR 1 COMPRESSOR 2 MOTOR, BLOWER MOTOR, OUTDOOR FAN 1 MOTOR, OUTDOOR FAN 2 MOTOR, EXHAUST FAN 1 MOTOR, EXHAUST FAN 2
DESCRIPTION COMPONENT
J138 J139 J250 J251 J252 J253 J255 J261 K1,1 K2,1 K3, 1 K10,1,2 JACK, SMOKE DETECTOR JUMPER CONTACTOR, COMPRESSOR 1 CONTACTOR, COMPRESSOR 2 CONTACTOR, BLOWER RELAY, OUTDOOR FAN ECONOMIZER
BLOWER(G) HEAT 1(W1) HEAT 2(W2)
EXHAUST FAN 2 EXHAUST FAN 3 SMOKE DETECTOR ONE SMOKE DETECTOR ONE SMOKE DETECTOR TWO SMOKE DETECTOR TWO
K2201
S149
DL46
K21
K141
4 6 2 3 P36 J36 1
K102
J138 P138
2 1 C8 3 2 1 J133 3 2 P133 1
J139
Page 38
1 9 4 7 C1 C2 C18 7 9 6 HR5 J2 J11 J18 J24 J35 J36 J47 J52 J86 J106 J132 J133 2 1 J86 1 2 3 7 8 9 4 5 6 P86 J47 3 2 1 J52 3 2 1 J1063 2 1 P47 P106 P52 B5 B21 B11
S42USED ON"M"VOLTAGE UNITS AND UNITS WITH HIGH EFFICIENCY MOTORS CONNECT A172 SENSOR TO J261 ON SUPPLY AIR SMOKE DETECTOR ONLY S48 OR CB10 MAY BE USED P2 IS USED ON KCA UNITS ONLY IMPORTANT: TO PREVENT MOTOR BURNOUT, NEVER CONNECT MORE THAN ONE MOTOR LEAD TOANY ONE CONNECTION. TAPE UNUSED MOTOR LEADS
K220
COMPRESSOR 3 MOTOR, OUTDOOR FAN 3 CAPACITOR, OUTDOOR FAN 1 CAPACITOR, OUTDOOR FAN 2 CAPACITOR, EXHAUST FAN CAPACITOR, OUTDOOR FAN 3 CIRCUIT, BREAKER T1 CIRCUIT, BREAKER MAIN DISCONNECT CIRCUIT, BREAKER T18 DELAY, OVERFLOW SWITCH HEATER, COMPRESSOR 1 HEATER, COMPRESSOR 2
K14, 1 K651,2 K66,1 K67,1 K220, 1 P2 P18 P24 P35 P36 P47 P52
CONTACTOR, COMPRESSOR 3 RELAY, EXHAUST FAN 1 RELAY, STAGE COOL 1 RELAY, STAGE COOL 2 RELAY, OVERFLOW SWITCH JACK, HEAT JACK, EXHAUST FAN COMPT JACK, EXHAUST FAN PLUG, TEST PLUG, TEST COOL JACK, OUTDOOR FAN 1 JACK, OUTDOOR FAN 2
TB13
24V COMMON PLUG, SENSE BLOWER JACK, OUTDOOR FAN 3 PLUG, EXHAUST FAN MOTOR 1 PLUG, EXHAUST FAN MOTOR 2 PLUG, EXHAUST FAN 1 JACK, SMOKE DETECTOR ONE JACK, SMOKE DETECTOR ONE JACK, SMOKE DETECTOR TWO JACK, SMOKE DETECTOR TWO
PLUG, MODULE, CONTROL SMOKE DETECTION
S48 5
HEATER, COMPRESSOR 3 JACK, HEAT JACK, GFI, RECEPTICLE JACK, EXHAUST FAN COMPT JACK, EXHAUST FAN JACK, TEST JACK, TEST COOL JACK, OUTDOOR FAN 1 JACK, OUTDOOR FAN 2 JACK, SENSE BLOWER JACK, OUTDOOR FAN 3 JACK, BLOWER , EXHAUST FAN MOTOR 1 JACK, BLOWER , EXHAUST FAN MOTOR 2
LIMIT HI PRESS COMP 2 LOW PRESS, LOW AMBIENT KIT LIMIT LOW COMPRESSOR 2 TEMP OVERLOAD RELAY BLOWER MOTOR DISCONNECT FREEZESTAT COMP 1 FREEZESTAT COMP 2
SWITCH, LOW PRESS, LOW AMBIENT KIT COMP 2
J11
P86 P106 P132 P133 P138 P250 P251 P252 P253 P255 S3 S4 S7 S11 S30 S42 S48 S49 S50 S84 S149 T1 TB13
H 120/ 60/ 1 N
COOLING
GROUND
REV. 2.0
Lennox Commercial
Page 39
24V POWER
DESCRIPTION
J252 J253 J255 J261 K1,1 K2,1 K3, 1 K10,1,2 K14, 1 K651,2 K66,1 K67,1 RELAY, STAGE COOL 2
ECONOMIZER
JACK, SMOKE DETECTOR TWO JACK, SMOKE DETECTOR TWO JACK, MODULE, CONTROL SMOKE DETECTION JACK, SMOKE DETECTOR JUMPER CONTACTOR, COMPRESSOR 1 CONTACTOR, COMPRESSOR 2 CONTACTOR, BLOWER RELAY, OUTDOOR FAN CONTACTOR, COMPRESSOR 3 RELAY, EXHAUST FAN 1 RELAY, STAGE COOL 1
TO L1 L1 A172 A173 B1 B2 TO N 380420V UNITS B5 B10 B11 MOTOR, EXHAUST FAN 2 MOTOR, EXHAUST FAN 1 MOTOR, OUTDOOR FAN 2 L2 460V, 575V UNITS B4 MOTOR, OUTDOOR FAN 1 B3 MOTOR, BLOWER COMPRESSOR 2 COMPRESSOR 1 MODULE, CONTROL SMOKE DETECTION SENSOR TWO, SMOKE, SUPPLY AIR A171 SENSOR ONE, SMOKE, RETURN AIR
KEY
COMPONENT
95 7 B21 7 K661 4 C2 CAPACITOR, OUTDOOR FAN 2 C1 CAPACITOR, OUTDOOR FAN 1 P18 B22 MOTOR, OUTDOOR FAN 4 P2 K671 4 MOTOR, OUTDOOR FAN 3 K220, 1
B13
COMPRESSOR 3
K149,1
RELAY, OUTDOOR FAN 3 RELAY, OVERFLOW SWITCH JACK, HEAT JACK, EXHAUST FAN
COOL 1(Y1) COOL 2 (Y2)
S42
96
K2201
7 2 S53 S50 C8 C18 T18 S28 CB8 CB10 6 DL46 A A K67 F10 HR1 HR2 HR5 J2 J11 J18 J24 J35 F6 J36 J47 J52 1 7 9 K1491 6 2 2 3 J87 2 1 1 2 3 J107 P107 1 3 2 P52 J52 6 4 5 P87 3 4 4 3 5 2 6 1 C8 3 2 1 3 B21 B22 B11 J107
S42 USED ON M VOLTAGE UNITS AND UNITS WITH HIGH EFFICIENCY MOTORS CONNECT A172 SENSOR TO J261 ON SUPPLY AIR SMOKE DETECTOR ONLY S48 OR CB10 MAY BE USED
S149 C6 CAPACITOR, EXHAUST FAN 2 CAPACITOR, OUTDOOR FAN 3 CAPACITOR, OUTDOOR FAN 4 CIRCUIT, BREAKER T1 CIRCUIT, BREAKER MAIN DISCONNECT CIRCUIT, BREAKER T18 DELAY, OVERFLOW SWITCH FUSE, EXHAUST FAN FUSE, OUTDOOR FAN MOTOR HEATER, COMPRESSOR 1 HEATER, COMPRESSOR 2 HEATER, COMPRESSOR 3 JACK, HEAT JACK, GFI, RECEPTICLE JACK, EXHAUST FAN COMPT JACK, EXHAUST FAN JACK, TEST JACK, TEST COOL JACK, OUTDOOR FAN 1 JACK, OUTDOOR FAN 2 9 7 4 6 P24 1 J24 1 J18 P18 6 2 J138 P138 J139 2 J86 J87 J106 JACK, OUTDOOR FANS 1 JACK, OUTDOOR FANS 2 JACK, OUTDOOR FAN 3 CAPACITOR, EXHAUST FAN 1
P35 J35
P24 P35 P36 P47 P52 P86 P87 P106 P107 P132 P133 P138 P250 P251 P252 P253 P255 S3 S4 S7 S11 S28 S30 S42 S48 S49 S50
JACK, EXHAUST FAN PLUG, TEST PLUG, TEST COOL JACK, OUTDOOR FAN 1 JACK, OUTDOOR FAN 2 PLUG, OUTDOOR FANS 1 PLUG, OUTDOOR FANS 2 JACK, OUTDOOR FAN 3 JACK, OUTDOOR FAN 4 PLUG, EXHAUST FAN MOTOR 1 PLUG, EXHAUST FAN MOTOR 2 PLUG, EXHAUST FAN 1 JACK, SMOKE DETECTOR ONE JACK, SMOKE DETECTOR ONE JACK, SMOKE DETECTOR TWO JACK, SMOKE DETECTOR TWO PLUG, MODULE, CONTROL SMOKE DETECTION SWITCH, LIMIT LOW COMPRESSOR 1 TEMP SWITCH, LIMIT HI PRESS COMP 1 ( MANUAL RESET) SWITCH, LIMIT HI PRESS COMP 2 SWITCH, LOW PRESS, LOW AMBIENT KIT SWITCH, LIMIT HI PRESS COMP 3 SWITCH, LIMIT LOW COMPRESSOR 2 TEMP SWITCH, OVERLOAD RELAY BLOWER MOTOR SWITCH, DISCONNECT SWITCH, FREEZESTAT COMP 1 SWITCH, FREEZESTAT COMP 2
DL46 S7 C19
CB18
3 CB18 F6
K220
A P35 J35 8 7 3 5 4
K21
K141
K102
K1492
Page 40
NOTE IF ANY WIRE IN THIS APPLIANCE IS REPLACED IT MUST BE REPLACED WITH WIRE OF LIKE SIZE, RATING, TERMINATION AND INSULATION THICKNESS WARNING ELECTRIC SHOCK HAZARD, CAN CAUSE INJURY OR DEATH UNIT MUST BE GROUNDED IN ACCORDANCE WITH NATIONAL AND LOCAL CODES DISCONNECT ALL POWER BEFORE SERVICING. F10
GND
TB13
N 7 9
S48 C1 C2 C18
C19
2 1
2 1
B13
P86
SWITCH, FREEZESTAT COMP 3 SWITCH, LOW PRESS, LOW AMBIENT KIT COMP 2 SWITCH, LOW PRESS, LOW AMBIENT KIT COMP 3 SWITCH, OVERFLOW TRANSFORMER, CONTROL TRANSFORMER, CONTACTOR CONTROL TERMINAL STRIP, POWER DISTRIBUTION
DENOTES OPTIONAL COMPONENTS LINE VOLTAGE FIELD INSTALLED
B3
B5
J11 JACK, OUTDOOR FAN 4 J132 J133 J138 J139 J250 F6 AND F10 ARE USED ON Y VOLTAGE UNITS ONLY J251 JACK, BLOWER , EXHAUST FAN MOTOR 1 JACK, BLOWER , EXHAUST FAN MOTOR 2 JACK, EXHAUST FAN 2 JACK, EXHAUST FAN 3 JACK, SMOKE DETECTOR ONE JACK, SMOKE DETECTOR ONE
COOLING
120/ 60/ 1
GROUND
IMPORTANT: TO PREVENT MOTOR BURNOUT, NEVER CONNECT MORE THAN ONE MOTOR LEAD TO ANY ONE CONNECTION. TAPE UNUSED MOTOR LEADS
REV. 3.0
Page 41
K191
ELEMENT, ELECTRIC HEAT 6 ELEMENT, ELECTRIC HEAT 7 ELEMENT, ELECTRIC HEAT 8 ELEMENT, ELECTRIC HEAT 9 ELEMENT, ELECTRIC HEAT 10 ELEMENT, ELECTRIC HEAT 11 ELEMENT, ELECTRIC HEAT 12 JACK, ELECTRIC HEAT SUBBASE KIT JACK, ELECTRIC HEAT LIMIT RELAY, HEAT CONTACTOR, ELECTRIC HEAT 1 CONTACTOR, ELECTRIC HEAT 2 CONTACTOR, ELECTRIC HEAT 3 CONTACTOR, ELECTRIC HEAT 4 RELAY, STAGE TWO HEAT
K161
S20
S20
S158
K181
K92
K161
k181
S157
S159
K161
K181
KW 15 30 45 60 90
HE4 15
HE5 15
HE6
S161
HE7
HE8
HE9
7.5 15 15 15 15 15
15 15
7.5 15
S20
S20
S157
S157
S158
S158
S159
S159
S160
S160
HEATING
REV. 3.0
Lennox Commercial
Page 42
K19
A B
A B K9
K18
K16
K17
KW 15 30 45 60 90
HE1
HE1A 7.5 15
HE2A 7.5 15
HE3
HE4
HE5
HE6
HE7
15 15 15
7.5 15 15 15
15 15 15
7.5 15 15 15
HEATING
K15
REV. 0.0
Lennox Commercial
Page 43
Page 44
24V POWER
ECONOMIZER
A B k65
24V COMMON 24V POWER COOL 1 (Y1)
DESCRIPTION COMPONENT SENSOR, ELECTRONIC THERMOSTAT SENSOR, CO2 CLOCK, TIME JACK, UNIT ECONOMIZER RELAY, EXHAUST FAN PLUG, ECONOMIZER BYPASS SENSOR, MIXED AIR OR SUPPLY AIR SENSOR, REMOTE THERMOSTAT TERMINAL STRIP, CLASS II VOLTAGE
COOL 2 (Y2)
24V COMMON REMOVEP3 WHEN ECONOMIZERIS USED, ONLY ON KCA, KGA AND KHA 180 THROUGH 300 UNITS.
CONNECTION SCHEME FOR KCA, KGA AND KHA 092 THROUGH 150 UNITS WITHOUT ECONOMIZER ONLY
ACCESSORIES
TOUCHSCREEN THERMOSTAT
REV. 2.0
Lennox Commercial
POWER: 1. Terminal strip TB1 found on the control panel energizes thermostat components with 24VAC. OPERATION: 2. TB1 receives data from the electronic thermostat A2 (Y1, Y2, W1, W2, G, OCP) TB1 energizes the appropriate components for heat or cool demand. Page 45
KCA ECONOMIZER
SEQUENCE OF OPERATION
POWER: 1. 2. 3. 4. Economizer control module A6 is energized through P4 when contactor K3 is energized. Temperature sensor S175 or enthalpy sensor A7 and A62 (if differential enthalpy is used) communicates to the economizer control module A6 when to power the damper motor B7. Economizer control module A6 supplies B7 with 0 10 VDC to control the positioning of economizer. The damper actuator provides 2 to 10 VDC position feedback. OPERATION:
Page 46