Photoelectric Smoke Detectors

System Sensor i3 series smoke detectors represent signicant advancement in conventional detection. The i3 family is founded on three principles: installation ease, intelligence, and instant inspection.

Features
Plug-in detector line, mounting base included Large wire entry port In-line terminals with SEMS screws Mounts to octagonal and single-gang back boxes, 4-square back boxes, or direct to ceiling Stop-Drop N Lock attachment to base Removable detector cover and chamber Built-in remote maintenance signaling Drift compensation and smoothing algorithms Simplified sensitivity measurement Wide-angle, dual-color LED indication Loop testing via EZ Walk feature Built-in test switch

Installation ease. The i3 line redenes installation ease with its plug-in design. This allows an installer to pre-wire bases (included with heads). The large wire entry port and in-line terminals provide ample room for neatly routing the wiring inside the base. The base accommodates a variety of back box mounting methods as well as direct mounting with drywall anchors. To complete the installation, i3 heads plug into the base with a simple Stop-Drop N Lock action. Intelligence. i3 detectors oer a number of intelligent features to simplify testing and maintenance. Drift compensation and smoothing algorithms are standard with the i3 line to minimize nuisance alarms. 2-wire i3 detectors can generate a remote LEDindicated maintenance signal when connected to the 2W-MOD2 loop test/maintenance module or a panel equipped with the i3 protocol. The SENS-RDR, a wireless device, displays the sensitivityof i3 detectors in terms of percent-per-foot obscuration. Instant inspection. The i3 series provides wide-angle red and green LED indicators for instant inspection of the detectors condition: normal standby, out-of-sensitivity, alarm, or freeze trouble. When connected to the 2W-MOD2 loop test/maintenance module or a panel with the i3 protocol, the EZ Walk loop test feature is available on 2-wire i3 detectors. This feature veries the initiating loop wiring by providing LED status indication at each detector.

Agency Listings

S911

3011446

7272-1653:152

290-01-E

2093

3180932

Smoke Detector Specifications


Architectural/Engineering Specifications Smoke detector shall be a System Sensor i3 Series model number_______, listed to Underwriters Laboratories UL 268 for Fire Protection Signaling Systems. The detector shall be a photoelectric type (Model 2W-B, 4W-B) or a combination photoelectric/thermal (Model 2WT-B, 4WT-B) with thermal sensor rated at 135F (57.2C). The detector shall include a mounting base for mounting to 3-inch and 4-inch octagonal, single-gang, and 4-inch square back boxes with a plaster ring, or direct mount to the ceiling using drywall anchors. Wiring connections shall be made by means of SEMS screws. The detector shall allow pre-wiring of the base and the head shall be a plug-in type. The detector shall have a nominal sensitivity of 2.5 percent-per-foot nominal as measured in the UL smoke box. The detector shall be capable of automatically adjusting its sensitivity by means of drift compensation and smoothing algorithms. The detector shall provide dualcolor LED indication that blinks to indicate power up, normal standby, out of sensitivity, alarm, and freeze trouble (Model 2WT-B, 4WT-B) conditions. When used in conjunction with the 2W-MOD2 module, 2-wire models shall include a maintenance signal to indicate the need for maintenance at the alarm control panel and shall provide a loop testing capability to verify the circuit without testing each detector individually. Electrical Specifications Operating Voltage Nominal: 12/24 V non-polarized Minimum: 8.5 V Maximum: 35 V Maximum Ripple Voltage 30% peak to peak of applied voltage Standby Current 2-wire: 50 A maximum average; 4-wire: 50 A maximum average Maximum Alarm Current 2-wire: 130 mA limited by control panel; 4-wire: 20 mA @12 V, 23 mA @ 24 V Peak Standby Current 2-wire: 100 A; 4-wire: n/a Alarm Contact Ratings 2-wire: n/a; 4-wire: 0.5 A @ 30 V AC/DC Physical Specifications Dimensions (including base) 5.3 inches (127 mm) diameter; 2.0 inches (51 mm) height Weight 6.3 oz (178 g) Operating Temperature Range 2W-B and 4W-B: 32F to 120F (0C to 49C); 2WT-B and 4WT-B: 32F to 100F (0C to 37.8C) Operating Humidity Range 0 to 95% RH non-condensing Thermal Sensor 135F (57.2C) fixed Freeze Trouble 2WT-B and 4WT-B only: 41F (5C) Sensitivity 2.5%/ft nominal Input Terminals 14 to 22 AWG Mounting 3-inch octagonal back box 4-inch octagonal back box Single-gang back box 4-inch square back box with a plaster ring Direct mount to ceiling LED Modes LED Mode Power up Normal (standby) Out of sensitivity Freeze trouble Alarm Green LED Blink every 10 seconds Blink every 5 seconds o o o Red LED Blink every 10 seconds o Blink every 5 seconds Blink every 10 seconds Solid Power-Up Sequence for LED Indication Condition Initial LED status indication Duration 80 seconds

Ordering Information
Model 2W-B 2WT-B 4W-B 4WT-B Accessories 2W-MOD2 SENS-RDR Thermal No Yes No Yes Wiring 2-wire 2-wire 4-wire 4-wire RT A77-AB2 Alarm Current 130 mA max. limited by control panel 130 mA max. limited by control panel 20 mA @ 12 V, 23 mA @ 24 V 20 mA @ 12 V, 23 mA @ 24 V Removal / replacement tool Retrot adapter bracket, 6.6 inch (16.76 cm) diameter

2-wire loop test / maintenance module Sensitivity reader

3825 Ohio Avenue St. Charles, IL 60174 Phone: 800-SENSOR2 Fax: 630-377-6495