Cable Size Calculations

This document provides information for calculating cable sizes for a 33kV power distribution system, including: 1) Fault level calculations and substation information for 13 substations on the 33kV system ranging from 2-4 transformers each with capacities of 3-6.3MVA. 2) Short circuit current calculations for each substation from 1.29-1.83kA. 3) Cable sizing calculations based on the short circuit current plus 20% for each substation, ranging from 27-270kA. 4) Recommended cable sizes of 95mm2 or 120mm2 based on the cable sizing calculations.

Uploaded by

joydeep_d3232
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
974 views1 page

Cable Size Calculations

This document provides information for calculating cable sizes for a 33kV power distribution system, including: 1) Fault level calculations and substation information for 13 substations on the 33kV system ranging from 2-4 transformers each with capacities of 3-6.3MVA. 2) Short circuit current calculations for each substation from 1.29-1.83kA. 3) Cable sizing calculations based on the short circuit current plus 20% for each substation, ranging from 27-270kA. 4) Recommended cable sizes of 95mm2 or 120mm2 based on the cable sizing calculations.

Uploaded by

joydeep_d3232
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 1

Cable Size Calculation

Max. Fault Level


=
VH
(kV) =
VL
(kV)=
t (sec) =
De - Rating Factor

200
33
11
0.5
0.466088

ISC (kA) =

3.4991

33 kV System

Sl.
No.

1
2
3
4
5
6
7
8
9
10
11
12
13

Substaion

Sonarpur (6.3//6.3)
Barrackpore (6.3//6.3)
Anantpur (6.3//6.3)
Abdalpur (6.3//6.3)
Kalitala (6.3//3.0)
(3//3.15)
Belmuri (6.3//6.3.0)
Tarui (6.3//6.3)
(6.3//3.0)
Chapra (6.3//3.0)
(3.0//3.0)
Joyshree (6.3//6.3)
Raninagar (3.0//3.0)
Nakashipara (5//3)
(3//3.15)
University Gate (6.3//5)
Raghunathpur

No. of
Power
Traf

3
2
3
3
3
2
4
3
2
2
2
2
2
3

Power
Trafo. ZSYS
Capacity ()
(MVA)
6.3
6.3
6.3
6.3
6.3
3.15
6.3
6.3
6.3
6.3
3
6.3
3
5
3.15
6.3
6.3

5.445
5.445
5.445
5.445
5.445
5.445
5.445
5.445
5.445
5.445
5.445
5.445
5.445
5.445
5.445
5.445
5.445

11 kV System

IF
(kA)

ZTRANS
ZBASE ZTRAN
ZTOTAL
SF.
F.(EQVT.)
ZL ()
()
()
()
()

110.2
110.2
110.2
110.2
110.2
55.11
110.2
110.2
110.2
110.2
52.49
110.2
52.49
87.48
55.11
110.2
110.2

172.86
172.86
172.86
172.86
172.86
345.71
172.86
172.86
172.86
172.86
363.00
172.86
363.00
217.80
345.71
172.86
172.86

12.36
12.36
12.36
12.36
12.36
21.61
12.36
12.36
12.36
12.36
21.61
12.36
22.69
15.57
21.61
12.36
12.36

6.18
6.18
6.18
6.18
8.00
11.06
6.18
6.18
8.00
8.00
11.06
6.18
11.06
9.24
11.06
6.90
4.42

ISC
(kA)

I
(kA)

11.62
1.29
4.92 3.48
11.62
1.29
4.92 3.48
11.62
1.29
4.92 3.48
11.62
1.29
4.92 3.48
13.45
1.49
4.25 3.01
16.51
1.83
3.46 2.45
11.62
1.29
4.92 3.48
11.62
1.29
4.92 3.48
13.45
1.49
4.25 3.01
13.45
1.49
4.25 3.01
16.51
1.83
3.46 2.45
11.62
1.29 4.917 3.48
16.51
1.83 3.463 2.45
14.69
1.63 3.892 2.75
16.505 1.8339 3.463 2.45
12.345 1.3717 4.63 3.27
9.869 1.0966 5.792 4.095

Bank
Size
(kVAR)
2000
1000
200
200
750
500
1500
1500
1250
750
500
1000
200
500
500
1750
250

IFL
IFL
IFL (De- (IFL+20
(A) Rated % OF
) (kA) IFL) (kA)
105.0 225
52.5
113
10.5
23
10.5
23
39.4
84
26.2
56
78.7
169
78.7
169
65.6
141
39.4
84
26.2
56
52.5
113
10.5
23
26.2
56
26.2
56
91.9
197
13.12 28.15

270.27
135.13
27.03
27.03
101.35
67.57
202.70
202.70
168.92
101.35
67.57
135.13
27.03
67.57
67.57
236.48
33.78

Cable
Size
(sq.
mm.)
120
95
95
95
95
95
95
95
95
95
95
95
95
95
95
120
95