Application The JOVENTA SPRINGBACK electric, spring return damper-actuator series has been specially developed for the motorized operation of safety air dampers (anti-icing) in air conditioning systems, smoke evacuation dampers and sealing dampers. When the control signal is applied the actuator drives the damper to the operational position, while evenly tensioning the integrated spring. After a power failure the stored energy in the spring immediately brings the damper to the safety position. Manual operation is automatically cancelled when the actuator is in electrical operation. The compact design and universal adapter fitted with limitation of rotation angle make this JOVENTA actuator highly versatile. Key features 2-point control Up to 5 actuators in parallel operation possible Plug-in terminal block connection Simple direct mounting with universal adapter on 10 mm to 20 mm shaft or 10 mm to 16 mm square shaft. 77 mm min shaft length Selectable direction of rotation Limitation of rotation angle Manual positioning with crank handle 2 adjustable auxiliary switches See back page for settings Automatic shut-off at end position (overload switch) Energy saving at end positions Actuators available with 1 m halogen-free cable Customized versions available Devices meet CE requirements Accessories ZK damper linkage selection ZKG ball joints (see data sheet 6.10)
Nomenclature/Specification/Technical data DA1.F DA1.FS DA2.F DA2.FS ......K AC/DC24V AC/DC24V AC230V AC230V with 2 auxiliary switches with 1 m halogen-free cable with 2 auxiliary switches
Actuator Torque Damper area* Running time Motor Running time Spring return Supply voltage Frequency Power consumption - Running - At end position Dimensioning Weight Control signal Position signal Angle of rotation / working range Angle of rotation / limitation Service lifetime Auxiliary switches Setting range / adjustable Noise level Protection class Degree of protection Cable aperture connection Mode of action Ambient conditions - Operating temperature - Storage temperature - Humidity Service Standards
DA1.F(S) 16 Nm 3.0 m2 90...120 s 10 s AC/DC24V 50-60 Hz 10.0 W 4.0 W 18.0VA / 4A @ 2 ms 2.7 kg 2-point None 90 (93 mech.) 0...30 and 90...60 60,000 rotations 3(1.5)A, AC230V 5...85 < infinity 50 d B (A) II IP 54 PG11 Type 1 20...+50C / IEC 721-3-3 30...+60C / IEC 721-3-2 5...95% r.F. Maintenance-free Mechanics Elektronics EMC Emissions EMC Immunity
DA2.F(S) 16 Nm 3.0 m2 90...120 s 10 s AC230V 50-60 Hz 8.0 W 4.5 W 13.0VA / 0.3A @ 2 ms 2.9 kg
* Caution: Please note damper manufacturers information concerning the open/close torque.
S P R I N G B A C K
Wiring diagram DA1.F(S)/DA2.F(S)
3.10
1 16 93
1 2 3 4
0
6 70 47
0
25.5
02
54.5
01
01
59 34 73.25
6
S
09
03
06
84
03
35.4
1020
1016
35
250
~
AC24V 20% DC24V 10% AC230V 10%
Parallel connection
The change in rotation direction is archieved by removing the adapter bush from one side and replacing it in the other side.
Max 5
2-point
20
30
30
b
Crank handle
21
22
23
24
25
26
Actuator at 0 position
Angle of rotation The 90 angle of rotation/ working range can, through segments 1 and 2, be reduced by up to 30 from both end positions.
For details of installation and commissioning see Manual 3.10
30
10
Segment 1
90152/E/12-04
Segment 2
0
30
30
3(1.5)A, AC230V
20
20
10
The switching position can be manually changed to any required position by turning the ratchet.
70
90
186
190
190
02
03
10