Trox - Ark2
Trox - Ark2
Trox - Ark2
Type ARK2
ARK2 Casing formed from galvanised sheet steel; casing in stainless steel on request Aluminium blades Blade shafts stainless steel Bearing from composite material with antifriction lining of PTFE/Pb (maintenance-free) Seals made of neoprene, temperature resistant up to 80 C Opening pressure difference 50-1000 Pa for dampers up to a width of 600 mm Opening pressure difference max. 600 Pa for dampers with a width greater than 600-1200 mm The required opening pressure difference must be specified when ordering Construction variant ARK2-G As for type ARK2, but both flanges drilled
Surface finish
Powder coating P1 Standard RAL shades: RAL RAL RAL RAL Other shades on request
* GE = Gloss level
9010-GE50*, RAL 9006-GE30*, 9001, RAL 9002, RAL 9003, 9005, RAL 9016, RAL 7001, 7035 all GE70*
Type ARK2
max. 235
38
180
Damper locked
Damper unlocked
H in mm
345 675 1005 1335 1665 1995
Number of Number of holes Number of blade coupling per Bper Hblades sections * dimension dimension
1 2 3 4 5 6 1 1 2 2 2 2 4 5 7 8 10 4 6 9 12 14 17
* only with type ARK
Any combinations of dimensions B x H listed above can be supplied. Intermediate dimensions on request.
Inlet cross-section A in m2
H in mm 200
345 675 1005 1335 1665 1995 0.069 0.135 0.201 0.227 0.333 0.399
400
0.138 0.270 0.402 0.454 0.666 0.798
B in mm 600 800
0.207 0.405 0.603 0.681 0.999 1.197 0.276 0.540 0.804 0.908 1.332 1.596
1200
0.414 0.810 1.206 1.362 1.998 2.394
H + 20 / B + 20
H/B
Detail X
Special screw
Masonry subframe
Construction with one masonry subframe Code 22
For construction using masonry subframe, the casing flanges are drilled on both sides. By using special screws in the masonry subframe, the non return damper or pressure relief damper can easily be demounted or mounted even when subframe is fitted in the wall. Scope of supply masonry subframe: Galvanised angle steel masonry subframe 35/35/3; builders cleats (screw-on type), special screws, screws, nuts and washers made of galvanised steel (installation on site, by others).
H/B
Masonry subframe
H/B
Technical Data
Nomenclature
B H A v pt in mm: Width in mm: Height in m2: Inlet cross-section (see page 5) in m/s: Air velocity with damper opened based on inlet cross-section A in Pa: Total pressure drop (duct mounting) with damper open in l/s: Leakage volume flow rate in m3/h: (independent of width B) in m3/h: Resulting volume flow
Example 1
Data given: Non return damper type ARK B = 600 mm, H = 1005 mm p D = 2000 Pa, v = 7 m/s Horizontal installation orientation Required: Total pressure drop pt Leakage volume flow V L Result: (from diagram) pt = 100 Pa V = 1.3 l/s (4.7 m3/h) L
Example 2
Data given: Pressure relief damper type ARK2 1000 Pa B = 600 mm, H = 1005 mm, A = 0.6 m2 p = 1000 Pa, v = 2 m/s Required: Total pressure drop pt with damper open Resulting volume flow V Result: pt = 50 Pa (from diagram) V = v A 3600 = 2 0.6 3600 = 4320 m3/h
120
100 Pa 80 60 Pa 60 pt pt 40 2 20 20 0 0 2 4 v m/s 6 8 10 40
m/s v
Installation orientation
1 horizontal duct (graph 1) 2 vertical duct (graph 2) 3 horizontal duct
Pa 3000
pt
pt
4000
pD
2000
1000
Installation orientations
Diagram Type ARK 1+2 3 Type ARK1 1+2 3 Type ARK2 1
0.5 2 1 4 . VL 1.5 l/s 2 2.5 10 3 12 3.5
500
6 m3/h 8
pD